028-0444-01 APPLICATION GUIDE VTR8300 VT8300
Fan Coil Unit Application Guide
VTR8300/VT8300 Series Room Controllers

2

Application Guide Fan Coil Unit Controller Series

VTR8300 AND VC3000 | LINE-VOLTAGE FAN COIL ROOM CONTROLLERS AND RELAY PACKS

This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Room Controller and the VC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, thereby reducing overall costs and installation time.
The VC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is not required for the VT8300 Series models.

Commercial interface (local override)

Power

Part Number

Description

VTR8300A5000B

BACnet® fan coil Room Controller

Humidity No

Onboard PIR
No

Communication BACnet®

VTR8300A5500B

BACnet® fan coil Room Controller

No

Yes

BACnet®

VTR8350A5000B

BACnet® fan coil Room Controller

Yes

No

BACnet®

VTR8350A5500B

BACnet® fan coil Room Controller

Yes

Yes

BACnet®

VTR8350A5000BLTD BACnet® fan coil Room Controller

Yes

No

BACnet®

Transformer Relay Packs for VTR8300 Series

Power

Part Number

Description

VC3500E5000

Transformer relay pack five relay fan outputs

VC3504E5000

Transformer relay pack five relay fan outputs, and four inputs

VC3514E5000

Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs

VC3400E5000

Transformer relay pack four relay outputs and smart VDC output

VC3404E5000

Transformer relay pack four relay outputs, smart VDC output, and four inputs

VC3300E5000

Transformer relay pack three relay fan outputs

ZigBee Pro Module for VT(R)8300 Series

Part Number

Description

Power

VCM8000V5000P

Optional ZigBee Pro module for VT8300 Series room controllers.

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

3

VT8300 LOW-VOLTAGE 24 VAC FAN COIL ROOM CONTROLLERS
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Room Controller. The VT8300 Room Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control of both line-voltage and low-voltage end devices is required.

Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)

Power

Part Number

Description

Humidity PIR Sensor

VT8300U5000B

BACnet® fan coil Room Controller

No

No

VT8300U5500B

BACnet® fan coil Room Controller

No

Yes

VT8350U5000B

BACnet® fan coil Room Controller

Yes

No

VT8350U5500B

BACnet® fan coil Room Controller

Yes

Yes

Communication
BACnet® BACnet® BACnet® BACnet®

Mixed-voltage Relay Packs for VT8300 Series

Part Number

Description

VC1300E5000

3 on/off outputs, 110/130V 3 speed

VC2300E5000

3 on/off outputs, 220/240V 3 speed

Wireless Accessories for VT(R)8300 Series

Power

Part Number

Description

SED-DOR-P-5000

Wireless door switch

SED-WIN-P-5000

Wireless window switch

SED-CMS-P-5045

Wireless ceiling mounted motion sensor

SED-WDS-P-5045 Wireless window and door switch

SED-WMS-P-5045 Wireless wall mounted motion sensor

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

4

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH

Fan

Airflow Direction

Cooling Coil

Heating Coil

VTR8300

2 POSITION
COOLING VALVE

2 POSITION
HEATING VALVE

VC3500E5000

Onboard PIR Sensor

Door Switch
SED-DOR-P-5000

AND / OR

OR*

Wired Remote Wireless Remote

PIR Sensor

PIR Sensor

Configuration Parameter Name
Fan Menu Fan cont. heat. BI1 BI2 Pulsed heating Pipe no. Seq. operation

Configuration Settings
L-M-H-A On Motion NO or Motion NC (remote PIR sensor only) Door Dry Off 4 Ht - Cl

© 2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series VTR8300

1 Tx/Rx 2 7 Vdc 3 Com

5
VC3500E5000

Tx / Rx 7 VDC
Com

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch Wireless door switch automatically toggles occupancy.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Can be configured for 2-pipe systems (without changeover).
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

6

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES

VTR8300

Fan

Airflow Direction

Cooling Coil

Electric Heating

2 POSITION
COOLING VALVE

SSR
SOLID STATE RELAY (GENERIC)

VC3404E5000

Configuration parameter name
Fan menu Fan cont. heat Pulsed heating Pipe no. Seq. operation

L-M-H-A On On 2 Ht-Cl

Configuration settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Tx / Rx 7 VDC
Com

Application Guide Fan Coil Unit Controller Series
VTR8300
SOLIDSTATE (-) RELAY (4-32Vdc) (+)

1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat 10 Heat +

7
VC3404E5000

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature.
On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.

On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or return duct sensor ready.
· Can be configured for 2-pipe systems with changeover.
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

8

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3504E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND WIRELESSS WINDOW SWITCH

Window Switch
SED-WIN-P-5000

Fan

Airflow Direction

Cooling / Heating Coil

Supply Sensor

VTR8300
Onboard PIR Sensor

2 POSITION
COOLING VALVE / HEATING VALVE

SENSOR

C/O
SENSOR
VC3504E5000

Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2

Configuration Parameter Name
Fan Menu Fan cont BI1 RUI1 Pipe No Seq. operation

L-M-H-A On Window COS 2 Cool

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Tx / Rx 7 VDC
Com

Application Guide Fan Coil Unit Controller Series VTR8300

1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS

9
VC3504E5000

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else valve closes.
On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected.

Wireless Window Switch Wireless window switch automatically locks out heating/cooling when window is opened.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or return duct sensor ready.
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

10

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3400E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES

VTR8300

Fan

Airflow Direction

Cooling Coil

Electric Heating

2 POSITION
COOLING VALVE

SSR
SOLID STATE RELAY (GENERIC)

VC3400E5000

Configuration parameter name
Fan menu Fan cont. heat. Pulsed Heating Pipe No Seq. operation

Configuration settings
L-M-H-A On On 2 Cool-Rht

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Tx / Rx 7 VDC
Com

Application Guide Fan Coil Unit Controller Series
VTR8300
SOLIDSTATE (-) RELAY (4-32Vdc) (+)

11
VC3400E5000
1 2 3
9 10

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature.
On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled.

On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

12

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES

Fresh Air

Fan

Airflow Direction

Cooling / Heating Coil

Supply Sensor

DAMPER

Return Air

2 POSITION
COOLING VALVE / HEATING VALVE

SENSOR

VTR8300

VC3514E5000

C/O
SENSOR

Supply Sensor: 10K Ohm type 2. Changeover Sensor: 10K Ohm type 2.

Configuration Parameter Name
Fan menu Fan cont. heat RUI1 Pulsed Heating Pipe no. Seq. operation

L-M-H-A On COS Occ Out 2 Cool

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Tx / Rx 7 VDC
Com

Application Guide Fan Coil Unit Controller Series
VTR8300
7Vdc RELAY COIL

1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 OCC -

13
VC3514E5000

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or return duct sensor ready.
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

14

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3500E5000 AND VC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK

VTR8300

Fan Airflow Direction

Cooling Coil

Heating Coil

2 POSITION
COOLING VALVE

2 POSITION
HEATING VALVE

VC3300E5000 VC3500E5000

Configuration Parameter Name Fan menu Fan cont. heat Pipe No Seq. operation

Configuration Settings
L-M-H-A On 4 Ht-Cl

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

VTR8300

1

2

3

Tx / Rx 7 VDC
Com

1 2 3

15
VC3500E5000T VC3300E5000

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

© 2015 Viconcis Technologies. All rights reserved.

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Can be configured for 2-pipe systems without changeover.
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

16

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3504E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH

Window Switch
SED-WIN-P-5000

Fan

Airflow Direction

Cooling / Heating Coil

Supply Sensor

2 POSITION
COOLING VALVE / HEATING VALVE

SENSOR

VTR8300
Onboard PIR Sensor

C/O
SENSOR
VC3504E5000

Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2

Configuration Parameter

Name

Fan menu

L-M-H-A

Fan cont. heat

On

BI1

Window

RUI1

COS

Pipe no.

2

Seq. operation

Cool

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Tx / Rx 7 VDC
Com

Application Guide Fan Coil Unit Controller Series
VTR8300

1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS

17
VC3504E5000

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

BI1 (Window)

SCom

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected.

Wired Window Switch The window switch automatically locks out heating/cooling when window opens.
Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
· Models available with factory installed PIR sensor.
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems with changeover.
· Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

18

Application Guide Fan Coil Unit Controller Series

VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH

Fan

Airflow Direction

Cooling Coil

Heating Coil

VTR8300

2 POSITION
COOLING VALVE

2 POSITION
HEATING VALVE

VC3500E5000

Onboard PIR Sensor

AND / OR

OR*

Wired Remote Wireless Remote

PIR Sensor

PIR Sensor

Configuration Parameter Name
Fan menu Fan cont. heat BI1 BI2 Pipe No Seq. Operat

Configuration Settings
L-M-H-A On Motion NO or Motion NC (remote PIR sensor only) Door Dry 4 Ht-Cl

Door Switch
SED-DOR-P-5000

© 2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series VTR8300

1 Tx/Rx 2 7 Vdc 3 Com

19
VC3500E5000

Tx / Rx 7 VDC
Com

BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom

BI2 (Door)

SCom

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch Door switch automatically toggles occupancy.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Models available with factory installed PIR sensor.
· Can be configured for 2-pipe systems without changeover.
· Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

20

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH

Fan

Airflow Direction

Cooling Coil

Heating Coil

TRI-STATE
COOLING VALVE

TRI-STATE
HEATING VALVE

VT8300

Onboard PIR Sensor

AND / OR

OR*

Wired Remote Wireless Remote

PIR Sensor

PIR Sensor

Configuration Parameter Name
Fan menu Control Type UI16 UI17 Pipe no. Seq. operation

Configuration Settings
L-M-H-A Floating Motion NO or Motion NC (remote PIR sensor only) Door Dry 4 Cool / Heat

Door Switch
SED-WDS-P-5045

© 2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

21

VT8300

Floating Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V

1 23456

7 8 9 10 11 12

HEATING VALVE
Close Open Com.

COOLING VALVE
Close Open Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems with changeover.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

22

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS WINDOW SWITCH

Fan

Airflow Direction

Cooling Coil

Heating Coil

ANALOG
COOLING VALVE

ANALOG
HEATING VALVE

VT8300

Window Switch
SED-WDS-P-5045

Onboard PIR Sensor

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

L-M-H-A 4 Cool / Heat

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

23

VT8300

Modulating Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H
RC (24 Vac) C (Common)
RH BO8 - Aux Heat
V UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

HEATING VALVE
0-10 v 24 v Com.

COOLING VALVE
0-10 v 24 v Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

24

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE

Fan

Airflow Direction

Cooling Coil

Heating Coil

VT8300

2 POSITION
COOLING VALVE

2 POSITION
HEATING VALVE

Configuration Parameter Name
Fan menu Control Type Pipe no. Seq. operation

L-M-H-A On/Off 4 Cool/Heat

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

25

VT8300

On / Off Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - NC Cool V UO10 - NC Heat V UO11 - NO Cool V UO12 - NO Heat V

1 23456

7 8 9 10 11 12

HEATING VALVE
IF NC IF NO Com.

COOLING VALVE
IF NC IF NO Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
· Models available with factory installed PIR sensor.
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

26

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE

Fresh Air

Fan

Airflow Direction

Cooling Coil

DAMPER

Return Air

VT8300

2 POSITION
COOLING VALVE

Configuration Parameter Name
Fan menu Control Type BO8 AuxOut Pipe no. Seq. operation

On-Auto On/Off Aux NO 2 Cool only

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

27

VT8300

On / Off Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat OU9 - NC Cool V UO10 - NC Heat V UO11 - NO Cool V UO12 - NO Heat V S

1 23456

7 8 9 10 11 12

FRESH AIR DAMPER ON / OFF ACTUATOR
L

COOLING VALVE
IF NC IF NO Com.

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS © 2015 Viconcis Technologies. All rights reserved.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC
FAN

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The auxiliary contact closes forcing fresh air damper to its minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The auxiliary contact opens causing fresh air damper to close completely.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. The auxiliary contact closes forcing fresh air damper to its minimum position.
On Call for Cool Cooling valve opens.
On Call for Heat Cooling valve closes.

Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced
functionality as required by the application. · Can be configured for two speed or three speed fan control.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

28

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE

Fresh Air

Fan

Airflow Direction

Cooling Coil

Heating Coil

DAMPER

Return Air

VT8300

ANALOG
COOLING VALVE

2 POSITION
HEATING VALVE

Configuration Parameter Name
Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

L-M-H-A 0 = 15 Minute 0 4 Cool-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

29

VT8300

Mod. & On / Off Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat
V UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

HEATING VALVE

NC

Com.

COOLING VALVE
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Analog valve starts modulating based on cooling demand.
On Call for Heat Heating valve opens.

Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · Can be configured to single or two speed fan. · 3 universal inputs can be used and configured for advanced
functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

30

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE

Fan

Airflow Direction

Cooling Coil

VT8300

ANALOG
COOLING VALVE

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

L-M-H-A 2 Cool only

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

VT8300

Modulating Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H
RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

31
COOLING VALVE
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 193 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat Valve closes.

Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced
functionality as required by the application. · Can be configured to two or three speed fan.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

32

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE

Fan

Airflow Direction

Cooling Coil

Heating

VT8300

2 POSITION
COOLING VALVE

ON / OFF DUCT HEATER

Configuration Parameter Name
Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

L-M-H-A On/Off 0 = 15 Minute 0 2 Cool-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

BO2 - Fan L BO3 - Fan M BO4 - Fan H
RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

Application Guide Fan Coil Unit Controller Series

VT8300

On / Off Control

1 23456

7 8 9 10 11 12

33

COOLING VALVE

L

IF NC IF NO Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC FAN HI FAN MED FAN LO

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens. Electric heat stays Off.
On Call for Heat Valve closes. Electric heat activates.

Options · Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced
functionality as required by the application. · Can be configured to single or two speed fan.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

34

Application Guide Fan Coil Unit Controller Series

VT8300 as Zone Controllers
VT83X0U5X00B HEATING ONLY ANALOG VALVE ACTUATOR, 2 PIPE
This section shows how the VT8300 series Room Controllers are used as Zone Controllers.

Airflow Direction

Heating Coil

ANALOG
HEATING VALVE

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

ON-AUTO 2 Heat only

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

VT8300

Modulating Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H
RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

35
HEATING VALVE
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room:
· During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used
· During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Auxiliary electric reheat can be added if required by application.

Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used.

Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat The heating valve modulates from closed to open according to demand.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

36

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING ONLY ANALOG VALVE ACTUATOR, 2 PIPE

Airflow Direction

Cooling Coil

ANALOG
COOLING VALVE

© 2015 Viconcis Technologies. All rights reserved.

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

ON-AUTO 2 Cool only

Configuration Settings

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

VT8300

Modulating Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

37
COOLING VALVE
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room:
· During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used
· During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used.
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.
On Call for Heat The heating valve modulates from closed to open according to demand.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Auxiliary electric reheat can be added if required by application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

38

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING COIL WITH TRI-STATE FLOATING VALVE ACTUATOR AND PWM ELECTRIC DUCT HEATER

Airflow Direction

Heating Coil

On/Off Duct Heater

TRI-STATE
FLOATING VALVE

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

ON-AUTO Floating 1 = 10 Second 0-Heat 2 Heat-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

39

VT8300

Floating & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

1 23456

7 8 9 10 11 12

PWM DUCT HEATER SOLID STATE RELAY
L

HEATING VALVE
Close Open Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room:
· During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used
· During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used.
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.
On Call for Heat The proportional device will act as a first step and modulates from 0 to 100% capacity. The perimeter heater will operate as a second step.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

40

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING WITH REHEAT, MODULATING DUCT HEATER, ELECTRIC PERIMETER

Airflow Direction

Two-stage Duct Heater

R820 SCR

PERIMETER HEATER

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

ON-AUTO 1 = 10 Second 0-Heat 2 Heat-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

41

VT8300

Mod. & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

1 23456

7 8 9 10 11 12

PERMETER HEAT SOLID STATE RELAY
L

DUCT HEATER, SRC
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room:
· During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used
· During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used.
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.
On Call for Heat The proportional device acts as a first step and modulates from 0 to 100% capacity. The perimeter heater operates as a second step.

Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

42

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG VALVE ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE

Airflow Direction

Cooling / Heating Coil On/Off Duct Heater

2 POSITION
COOLING VALVE / HEATING VALVE

CHANGE OVER
SENSOR

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
UI19 Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

COS ON-AUTO 1 = 10 Second 0-Heat 2 Cool-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

43

VT8300

Mod. & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S

1 23456

7 8 9 10 11 12

PWM DUCT HEATER SOLID STATE RELAY
L

HEATING VALVE
0-10 v 24 v Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

CO SENSOR SCOM

10 k-2

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room:
· During PIR activated stand-by periods, stand-by heating and cooling setpoints are used.
· During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used.
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat If supply water temperature is less than 75°F (23.9°C), the valve modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), valve remains closed.
On Call for Cool If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

44

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, TRI-STATE FLOATING ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE

Airflow Direction

Cooling / Heating Coil On/Off Duct Heater

TRI-STATE
COOLING VALVE / HEATING VALVE

CHANGE OVER
SENSOR

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
UI19 Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

COS ON-AUTO Floating 1 = 10 Second 0-Heat 2 Cool-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

45

VT8300

Floating & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

1 23456

7 8 9 10 11 12

PWM DUCT HEATER SOLID STATE RELAY
L

HEATING VALVE
Close Open Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

CO SENSOR SCOM

10 k-2

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room:
· During PIR activated stand-by periods, stand-by heating and cooling setpoints are used.
· During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During Unoccupied periods, unoccupied heating and cooling setpoints are used.
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat If supply water temperature is less than 75°F (23.9°C), valve modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), valve remains closed.
On Call for Cool If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

46

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, PWM DUCT HEATER AND AIR SENSOR FOR CHANGEOVER, 2 PIPE

Airflow Direction

Analog Damper

On/Off Duct Heater

CHANGE OVER DAMPER
SENSOR

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
UI19 Fan menu BO8 Out Time BO8 AuxOut Prop. band Pipe no. Seq. operation

Configuration Settings
COS ON-AUTO 1 = 10 Second 0-Heat Default value 3.0. Range = 3.0 to 10. 2 Cool-rht

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

47

VT8300

Mod. & On / Off Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat OU9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

1 23456

7 8 9 10 11 12

PWM DUCT HEATER SOLID STATE RELAY
L

ZONE DAMPER ACTUATOR
0-10 v 24 v Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

CO SENSOR SCOM

10 k-2

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room:
· During PIR activated stand-by periods, stand-by heating and cooling setpoints are used.
· During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used.
Local Override The controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step.
On Call for Cool If supply air temperature is less than 75°F (23.9°C), damper modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), damper remains closed.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

48

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, FLOATING AIR DAMPER ACTUATOR, PWM DUCT HEATER AND SUPPLY AIR SENSOR FOR CHANGEOVER, 2 PIPE

Airflow Direction

Floating Damper

On/Off Duct Heater

CHANGE OVER DAMPER
SENSOR

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
UI19 Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

COS ON-AUTO Floating 1 = 10 Second 0-Heat 2 Cool-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

49

VT8300

Floating & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V
S

1 23456

7 8 9 10 11 12

PWM DUCT HEATER SOLID STATE RELAY
L

ZONE DAMPER ACTUATOR
Close Open Com.

13 14 15 16 17 18

19 20 21 22 23 24

24 Vac Transformer
COMM ON 24 VAC

CO SENSOR SCOM

10 k-2

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room:
· During PIR activated stand-by periods, stand-by heating and cooling setpoints are used.
· During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used.
Local Override The Controller reverts back to the occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step.
On Call for Cool If supply air temperature is less than 75°F (23.9°C), damper modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), damper remains closed.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

50

Application Guide Fan Coil Unit Controller Series

VT83X0U5X00B COOLING AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, ANALOG DUCT HEATER AND ELECTRIC PERIMETER

Airflow Direction

Modulating Damper Modulating Duct Heater

DAMPER

PERIMETER HEATER

SSR
SOLID STATE RELAY (R1810 WITH HEATSINK)

Configuration Parameter Name
Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation

ON-AUTO 1 = 10 Second 0-Heat 4 Cl/ht-rht

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

51

VT8300

Modulating & PWM Control

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat OU9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S

1 23456

7 8 9 10 11 12

PERMETER HEAT SOLID STATE RELAY
L

DUCT HEATER, SRC
0-10 V 24V Com.

ZONE DAMPER COOLING ONLY
ACTUATOR
0-10 V 24V Com.

13 14 15 16 17 18

19 20 21 22 23 24

FCU Low-voltage TERMINAL BLOCK
COMM ON 24 VAC

BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Sequence of Operation and Wiring
Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used.
Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room:
· During PIR activated stand-by periods, stand-by heating and cooling setpoints are used.
· During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used.
Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used.
Local Override The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller.

On Call for Heat The damper remains closed. The proportional heater acts as a first step and modulate from 0 to 100% capacity. The perimeter heater operates as a second step.
On Call for Cool The damper modulates from closed to open according to demand.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

52

Application Guide Fan Coil Unit Controller Series

VT8300 Mixed-voltage Applications
Applications in this section make use of the SC1300 and SC2300 mixed-voltage relays.
VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE

High Voltage Fan Airflow Direction

Cooling Coil

Heating Coil

VT8300

ANALOG
COOLING VALVE

ANALOG
HEATING VALVE

SC1300

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

L-M-H-A 4 Cool / Heat

Power supply 120 vac
Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

53

VT8300

Mix Voltage 120 volts

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

SC1300

HEATING VALVE COOLING VALVE
0-10v 24v Com. 0-10v 24v Com.

13 14 15 16 17 18

19 20 21 22 23 24

BACnet + BACnet -
BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Power supply 120 Vac

High Voltage Fan
FAN HI FAN MED FAN LO COMM ON

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

54

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE

High Voltage Fan Airflow Direction

Cooling Coil

Heating Coil

VT8300

ANALOG
COOLING VALVE

ANALOG
HEATING VALVE

SC2300

Power supply 240 vac

Configuration Parameter Name
Fan menu Pipe no. Seq. operation

L-M-H-A 4 Cool / Heat

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

55

VT8300

Mix Voltage 240 volts

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

SC2300

HEATING VALVE COOLING VALVE
0-10v 24v Com. 0-10v 24v Com.

13 14 15 16 17 18

19 20 21 22 23 24

BACnet + BACnet -
BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Power supply 240 Vac

High Voltage Fan
FAN HI FAN MED FAN LO COMM ON

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

56

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE

High Voltage Fan Airflow Direction

Cooling Coil

Heating Coil

VT8300

TRI-STATE
FLOATING VALVE

TRI-STATE
FLOATING VALVE

SC1300

Power supply 120 vac

Configuration Parameter Name
Fan menu Control Type Pipe no. Seq. operation

L-M-H-A Floating 4 Cool / Heat

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

57

VT8300

Floating Control Mix Voltage

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

SC1300

HEATING VALVE COOLING VALVE
Open Close Com. Open Close Com.

13 14 15 16 17 18

19 20 21 22 23 24

BACnet + BACnet -
BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Power supply 120 Vac

High Voltage Fan
FAN HI FAN MED FAN LO COMM ON

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems with changeover.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

58

Application Guide Fan Coil Unit Controller Series

VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE

High Voltage Fan Airflow Direction

Cooling Coil

Heating Coil

VT8300

TRI-STATE
FLOATING VALVE

TRI-STATE
FLOATING VALVE

SC2300

Power supply 240 vac

Configuration Parameter Name
Fan menu Control Type Pipe no. Seq. operation

L-M-H-A Floating 4 Cool / Heat

Configuration Settings

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

59

VT8300

Floating Control Mix Voltage

BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common)
RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool

1 23456

7 8 9 10 11 12

SC2300

HEATING VALVE COOLING VALVE
Open Close Com. Open Close Com.

13 14 15 16 17 18

19 20 21 22 23 24

BACnet + BACnet -
BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS

Power supply 240 Vac

High Voltage Fan
FAN HI FAN MED FAN LO COMM ON

Sequence of Operation and Wiring
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter.
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes.

On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
· Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
· Remote wall mount or duct sensor ready.
· Can be configured for 2-pipe systems with changeover.
· 3 universal inputs can be used and configured for advanced functionality as required by the application.
· Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

© 2015 Viconcis Technologies. All rights reserved.

60

Application Guide Fan Coil Unit Controller Series

APPENDIX A - PASSIVE INFRA-RED SENSOR SPECIFICATIONS
Passive Infra-Red Sensor Sequence of Operation
Initially, the Controller is in Stand-by mode and Stand-by setpoints are used for the Controller. When the Passive Infra-Red (PIR) sensor detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used for this operation. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room switches to Stand-by mode and Stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion switches the room back to Occupied mode.
Typical Detection Pattern for PIR Lens

Recommended installation height for PIR sensor:
4 - 5 ft. / 1.2-1.5 m

Horizontal Angles (Typical)
Transverse motion: 4-5 ft/s / 1.5 m/s

Vertical Angle (Typical)

Sensor Ranges
A = 20 ft. / 6.1 m B = 14 ft. / 4.3 m C = 11 ft. / 3.4 m

40O

A

Center

30O

20O
B
20O
C

20O
B
20O
C

Center

Energy Savings

Saving Percentage

PIR can maximize your energy saving from 10-30% by adjusting temperature set points in unoccupied zones during scheduled periods.

Typical Savings of 10-30%

85

50%

80

75

70

40%

65

60

55

50

30%

45

40

35

20%

30

25

20

15

10%

10

5

0

0%

0

2

4

6

8 10 12 14 16 18 20 22 24

Time of Day (EST)

Typical Consumption

PIR Thermostat Consumption

Savings

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Energy Usage (KWh) © 2015 Viconcis Technologies. All rights reserved.

Application Guide Fan Coil Unit Controller Series

APPENDIX B - OPTIONAL NETWORK SET-UP

BACnet® Communication Wiring

BACnet
+- thermostat

1

ref

BACnet
+- thermostat

2

ref

BACnet
+- thermostat

3

ref

Notes: · Wiring should be daisy chained · Always respect polarity · If using 2 conductors and shielded wires, connect
shield of each feed together on back of Controller · Only ground shield at one location. Do not connect
shield to reference terminal

61
Wireless Communication
No communication wires required

APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION
Setpoints

Unoccupied cool Stand-by cool Occupied cool Occupied heat Stand-by heat
Unoccupied heat

22°C 72°F Deadband
70°F 21°C
Stand-by time

24.5 ° C 76°F Deadband

26.5°C 80°F Deadband

66°F 19°C
Unoccupied time

62°F 16.5°C

22°C 72°F
70°F 21°C

Movement detected -
Stand-by timer reset

Into Stand-by mode -
Unoccupied timer reset

Into Unoccupied mode

Next movement detected

Time

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

62

Application Guide Fan Coil Unit Controller Series

APPENDIX D - VTR8300 CONTROLLER AND VC3000 RELAY PACK
Product Overview
The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet® MSTP or wireless ZigBee® Pro networked models.
No previous building automation training is required for installation and commissioning process, and installation can be completed in approximately fifteen minutes.
The VC3000 Series Line Voltage Switching Transformer Relay Pack Controllers are designed for silent control of typical high voltage fan coil device loads (90 - 277 VAC multi-voltages). It uses advanced microprocessorbased circuitry with a built-in transformer that eliminates all typical required peripheral components when automating a Fan Coil unit with traditional building automation systems.
The VC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR83XX Room Controller.
A single VTR8300 or VT8300 Room Controller can control up to 10 x VC3000 Series Relay Packs as they are line-powered units.
The unit locally contains all relay outputs for fan switching and valve control, and models are also available for extra monitoring/control inputs of the Fan Coil Units.

Typical Fan Coil Unit Set-up

Typical Fan Coil Unit

1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat 10 Heat +

Power Supply

SC3404E5000

WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC
BLACK

FAN
LOW 1/2 HP or 13A FAN Max MED

RED BLUE

FAN HIGH

BROWN

5A

Max

COOL

YELLOW

Low Voltage Connections to VTR8300 Controller

H

Electrical Cabinet

C

1 Tx/Rx

2 7 Vdc 3 Com 4 RUI 1 5 SCom

Power Supply

xxx-xxxx-xx

6 RBI 2 7 SS 8 RS 9 Heat 10 Heat +

WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC
BLACK

FAN
LOW 1/2 HP or 13A FAN Max MED

RED BLUE

FAN HIGH

BROWN

5A

Max

COOL

YELLOW

C C

© 2015 Viconcis Technologies. All rights reserved.

Daisy Chained Topology

Mixed Daisy Chained and Star Topology

Star Topology

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

Application Guide Fan Coil Unit Controller Series

63

APPENDIX E - SED SERIES WIRELESS SENSORS
Wireless ZigBee® Pro Motion Sensors and Door/Window Switch
Wireless door switches used with an onboard or remote PIR sensor provide advanced local occupancy routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort. Wireless window switches are used to monitor exterior windows or patio/balcony doors when opened to prevent unnecessary energy consumption. Fan Coil Room Controllers with SED Series ZigBee® Pro wireless switches can be used in stand-alone mode, or with integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions. Up to twenty SED-WIN or SED-DOR ZigBee wireless switches can be used with a VTR8300 or VT8300 Room Controller Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VTR8300 or VT8300 Room Controller Note that if a ZigBee wireless window switch is used, the VT8300 Room Controller cannot also use a remote PIR motion sensor, whether wired or wireless. Using one or more wireless remote PIR motion sensors means that a wired PIR motion sensor cannot be used, and vice versa. The SED Series sensors are factory delivered with batteries and are ready to be installed, configured, and used right out of the box. Due to the extremely small current consumption of the sensors, the expected battery life is approximately 10 years, which is equivalent to the battery shelf life. No tools are required for commissioning or servicing the ZigBee devices. A simple interface on the devices with an on-board LED and hidden switch provides all required functions for local interaction. The VT8300 user interface has screens used to pair and configure ZigBee devices (SED-WMS, SED-CMS, or SED-WDS only). Local information for battery life and connectivity (heartbeat) are also displayed through the ZigBee® Pro wireless network. For more information about using the SED-WIN and SED-DOR switches, consult the SED-WIN / SED-DOR Wireless Door and Window Switch Installation Guide. For more information about using the SED-WDS, SED-WMS and SED-CMS wireless switches and sensors, consult the Pairing VT8000 Series Room Controllers with ZigBee Sensors Installation Guide and Procedure.

Model Selection
Window Switch
Door switch
Window switch
Door/window switch Wall mounted motion sensor Ceiling mounted motion sensor

Door Switch SED-DOR-P-5045 SED-WIN-P-5045 SED-WDS-P-5045 SED-WMS-P-5045 SED-CMS-P-5045

© 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01

www.viconics.com | sales@viconics.com

April 2015

64

Application Guide Fan Coil Unit Controller Series

LED SED-CMS

LED

LED

SED-WMS

SED-WDS

SED-WIN SED-DOR

LED
Hidden Hidden switch switch

Hidden switch

© 2015 Viconcis Technologies. All rights reserved.

Hidden switch
APPENDIX F: TERMINAL CORRESPONDENCE
The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000 series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller with a VT8300 Room Controller.

VT7000

Terminal name

Terminal ID

Binary Input 1

BI1

Binary Input 2

BI2

Universal Input 3

UI3

Sensor Common

Scom

Remote Sensor

RS

Sensor Common

Scom

Mix/Supply Sensor

MS

VT8300

Terminal name

Terminal ID

Universal Input 16

UI16

Universal Input 17

UI17

Universal Input 19

UI19

Terminal 18 Common COM

Universal Input 20

UI20 - RS

Terminal 21 Common COM

Universal Input 22

UI22 - SS

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0444-01