Viconics / Schneider Electric
Fan Coil Unit Application Guide VTR8300/VT8300 Series Room Controllers 2 Application Guide Fan Coil Unit Controller Series VTR8300 AND VC3000 | LINE-VOLTAGE FAN COIL ROOM CONTROLLERS AND RELAY PACKS This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Room Controller and the VC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, thereby reducing overall costs and installation time. The VC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is not required for the VT8300 Series models. Commercial interface (local override) Power Part Number Description VTR8300A5000B BACnet® fan coil Room Controller Humidity No Onboard PIR No Communication BACnet® VTR8300A5500B BACnet® fan coil Room Controller No Yes BACnet® VTR8350A5000B BACnet® fan coil Room Controller Yes No BACnet® VTR8350A5500B BACnet® fan coil Room Controller Yes Yes BACnet® VTR8350A5000BLTD BACnet® fan coil Room Controller Yes No BACnet® Transformer Relay Packs for VTR8300 Series Power Part Number Description VC3500E5000 Transformer relay pack five relay fan outputs VC3504E5000 Transformer relay pack five relay fan outputs, and four inputs VC3514E5000 Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs VC3400E5000 Transformer relay pack four relay outputs and smart VDC output VC3404E5000 Transformer relay pack four relay outputs, smart VDC output, and four inputs VC3300E5000 Transformer relay pack three relay fan outputs ZigBee Pro Module for VT(R)8300 Series Part Number Description Power VCM8000V5000P Optional ZigBee Pro module for VT8300 Series room controllers. © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 3 VT8300 LOW-VOLTAGE 24 VAC FAN COIL ROOM CONTROLLERS This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Room Controller. The VT8300 Room Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control of both line-voltage and low-voltage end devices is required. Commercial and Hospitality Interface (Local Override and Degrees C/F Selection) Power Part Number Description Humidity PIR Sensor VT8300U5000B BACnet® fan coil Room Controller No No VT8300U5500B BACnet® fan coil Room Controller No Yes VT8350U5000B BACnet® fan coil Room Controller Yes No VT8350U5500B BACnet® fan coil Room Controller Yes Yes Communication BACnet® BACnet® BACnet® BACnet® Mixed-voltage Relay Packs for VT8300 Series Part Number Description VC1300E5000 3 on/off outputs, 110/130V 3 speed VC2300E5000 3 on/off outputs, 220/240V 3 speed Wireless Accessories for VT(R)8300 Series Power Part Number Description SED-DOR-P-5000 Wireless door switch SED-WIN-P-5000 Wireless window switch SED-CMS-P-5045 Wireless ceiling mounted motion sensor SED-WDS-P-5045 Wireless window and door switch SED-WMS-P-5045 Wireless wall mounted motion sensor © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 4 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH Fan Airflow Direction Cooling Coil Heating Coil VTR8300 2 POSITION COOLING VALVE 2 POSITION HEATING VALVE VC3500E5000 Onboard PIR Sensor Door Switch SED-DOR-P-5000 AND / OR OR* Wired Remote Wireless Remote PIR Sensor PIR Sensor Configuration Parameter Name Fan Menu Fan cont. heat. BI1 BI2 Pulsed heating Pipe no. Seq. operation Configuration Settings L-M-H-A On Motion NO or Motion NC (remote PIR sensor only) Door Dry Off 4 Ht - Cl © 2015 Viconcis Technologies. All rights reserved. * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VTR8300 1 Tx/Rx 2 7 Vdc 3 Com 5 VC3500E5000 Tx / Rx 7 VDC Com BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closed. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closed. Wireless Door Switch Wireless door switch automatically toggles occupancy. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Can be configured for 2-pipe systems (without changeover). · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 6 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES VTR8300 Fan Airflow Direction Cooling Coil Electric Heating 2 POSITION COOLING VALVE SSR SOLID STATE RELAY (GENERIC) VC3404E5000 Configuration parameter name Fan menu Fan cont. heat Pulsed heating Pipe no. Seq. operation L-M-H-A On On 2 Ht-Cl Configuration settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Tx / Rx 7 VDC Com Application Guide Fan Coil Unit Controller Series VTR8300 SOLIDSTATE (-) RELAY (4-32Vdc) (+) 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat 10 Heat + 7 VC3404E5000 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled. On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or return duct sensor ready. · Can be configured for 2-pipe systems with changeover. · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 8 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3504E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND WIRELESSS WINDOW SWITCH Window Switch SED-WIN-P-5000 Fan Airflow Direction Cooling / Heating Coil Supply Sensor VTR8300 Onboard PIR Sensor 2 POSITION COOLING VALVE / HEATING VALVE SENSOR C/O SENSOR VC3504E5000 Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2 Configuration Parameter Name Fan Menu Fan cont BI1 RUI1 Pipe No Seq. operation L-M-H-A On Window COS 2 Cool Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Tx / Rx 7 VDC Com Application Guide Fan Coil Unit Controller Series VTR8300 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 VC3504E5000 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else valve closes. On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wireless Window Switch Wireless window switch automatically locks out heating/cooling when window is opened. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or return duct sensor ready. · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 10 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3400E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES VTR8300 Fan Airflow Direction Cooling Coil Electric Heating 2 POSITION COOLING VALVE SSR SOLID STATE RELAY (GENERIC) VC3400E5000 Configuration parameter name Fan menu Fan cont. heat. Pulsed Heating Pipe No Seq. operation Configuration settings L-M-H-A On On 2 Cool-Rht © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Tx / Rx 7 VDC Com Application Guide Fan Coil Unit Controller Series VTR8300 SOLIDSTATE (-) RELAY (4-32Vdc) (+) 11 VC3400E5000 1 2 3 9 10 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled. On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 12 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES Fresh Air Fan Airflow Direction Cooling / Heating Coil Supply Sensor DAMPER Return Air 2 POSITION COOLING VALVE / HEATING VALVE SENSOR VTR8300 VC3514E5000 C/O SENSOR Supply Sensor: 10K Ohm type 2. Changeover Sensor: 10K Ohm type 2. Configuration Parameter Name Fan menu Fan cont. heat RUI1 Pulsed Heating Pipe no. Seq. operation L-M-H-A On COS Occ Out 2 Cool Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Tx / Rx 7 VDC Com Application Guide Fan Coil Unit Controller Series VTR8300 7Vdc RELAY COIL 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 OCC - 13 VC3514E5000 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes. On Call for Heat If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or return duct sensor ready. · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 14 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3500E5000 AND VC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK VTR8300 Fan Airflow Direction Cooling Coil Heating Coil 2 POSITION COOLING VALVE 2 POSITION HEATING VALVE VC3300E5000 VC3500E5000 Configuration Parameter Name Fan menu Fan cont. heat Pipe No Seq. operation Configuration Settings L-M-H-A On 4 Ht-Cl © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VTR8300 1 2 3 Tx / Rx 7 VDC Com 1 2 3 15 VC3500E5000T VC3300E5000 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom © 2015 Viconcis Technologies. All rights reserved. Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Can be configured for 2-pipe systems without changeover. · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 16 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3504E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH Window Switch SED-WIN-P-5000 Fan Airflow Direction Cooling / Heating Coil Supply Sensor 2 POSITION COOLING VALVE / HEATING VALVE SENSOR VTR8300 Onboard PIR Sensor C/O SENSOR VC3504E5000 Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2 Configuration Parameter Name Fan menu L-M-H-A Fan cont. heat On BI1 Window RUI1 COS Pipe no. 2 Seq. operation Cool Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Tx / Rx 7 VDC Com Application Guide Fan Coil Unit Controller Series VTR8300 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 17 VC3504E5000 BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom BI1 (Window) SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes. On Call for Heat If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wired Window Switch The window switch automatically locks out heating/cooling when window opens. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Models available with factory installed PIR sensor. · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems with changeover. · Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 18 Application Guide Fan Coil Unit Controller Series VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH Fan Airflow Direction Cooling Coil Heating Coil VTR8300 2 POSITION COOLING VALVE 2 POSITION HEATING VALVE VC3500E5000 Onboard PIR Sensor AND / OR OR* Wired Remote Wireless Remote PIR Sensor PIR Sensor Configuration Parameter Name Fan menu Fan cont. heat BI1 BI2 Pipe No Seq. Operat Configuration Settings L-M-H-A On Motion NO or Motion NC (remote PIR sensor only) Door Dry 4 Ht-Cl Door Switch SED-DOR-P-5000 © 2015 Viconcis Technologies. All rights reserved. * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VTR8300 1 Tx/Rx 2 7 Vdc 3 Com 19 VC3500E5000 Tx / Rx 7 VDC Com BACnet+ BACnetBACnet REF UI 16 - BI1 UI 17 - BI2 SCom BI2 (Door) SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Door Switch Door switch automatically toggles occupancy. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Models available with factory installed PIR sensor. · Can be configured for 2-pipe systems without changeover. · Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 20 Application Guide Fan Coil Unit Controller Series VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH Fan Airflow Direction Cooling Coil Heating Coil TRI-STATE COOLING VALVE TRI-STATE HEATING VALVE VT8300 Onboard PIR Sensor AND / OR OR* Wired Remote Wireless Remote PIR Sensor PIR Sensor Configuration Parameter Name Fan menu Control Type UI16 UI17 Pipe no. Seq. operation Configuration Settings L-M-H-A Floating Motion NO or Motion NC (remote PIR sensor only) Door Dry 4 Cool / Heat Door Switch SED-WDS-P-5045 © 2015 Viconcis Technologies. All rights reserved. * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 21 VT8300 Floating Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V 1 23456 7 8 9 10 11 12 HEATING VALVE Close Open Com. COOLING VALVE Close Open Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems with changeover. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 22 Application Guide Fan Coil Unit Controller Series VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS WINDOW SWITCH Fan Airflow Direction Cooling Coil Heating Coil ANALOG COOLING VALVE ANALOG HEATING VALVE VT8300 Window Switch SED-WDS-P-5045 Onboard PIR Sensor Configuration Parameter Name Fan menu Pipe no. Seq. operation L-M-H-A 4 Cool / Heat Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 23 VT8300 Modulating Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat V UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 HEATING VALVE 0-10 v 24 v Com. COOLING VALVE 0-10 v 24 v Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 24 Application Guide Fan Coil Unit Controller Series VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE Fan Airflow Direction Cooling Coil Heating Coil VT8300 2 POSITION COOLING VALVE 2 POSITION HEATING VALVE Configuration Parameter Name Fan menu Control Type Pipe no. Seq. operation L-M-H-A On/Off 4 Cool/Heat Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 25 VT8300 On / Off Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - NC Cool V UO10 - NC Heat V UO11 - NO Cool V UO12 - NO Heat V 1 23456 7 8 9 10 11 12 HEATING VALVE IF NC IF NO Com. COOLING VALVE IF NC IF NO Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Models available with factory installed PIR sensor. · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 26 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE Fresh Air Fan Airflow Direction Cooling Coil DAMPER Return Air VT8300 2 POSITION COOLING VALVE Configuration Parameter Name Fan menu Control Type BO8 AuxOut Pipe no. Seq. operation On-Auto On/Off Aux NO 2 Cool only Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 27 VT8300 On / Off Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat OU9 - NC Cool V UO10 - NC Heat V UO11 - NO Cool V UO12 - NO Heat V S 1 23456 7 8 9 10 11 12 FRESH AIR DAMPER ON / OFF ACTUATOR L COOLING VALVE IF NC IF NO Com. BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS © 2015 Viconcis Technologies. All rights reserved. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The auxiliary contact closes forcing fresh air damper to its minimum position. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The auxiliary contact opens causing fresh air damper to close completely. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. The auxiliary contact closes forcing fresh air damper to its minimum position. On Call for Cool Cooling valve opens. On Call for Heat Cooling valve closes. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Can be configured for two speed or three speed fan control. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 28 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE Fresh Air Fan Airflow Direction Cooling Coil Heating Coil DAMPER Return Air VT8300 ANALOG COOLING VALVE 2 POSITION HEATING VALVE Configuration Parameter Name Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation L-M-H-A 0 = 15 Minute 0 4 Cool-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 29 VT8300 Mod. & On / Off Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat V UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 HEATING VALVE NC Com. COOLING VALVE 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Analog valve starts modulating based on cooling demand. On Call for Heat Heating valve opens. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · Can be configured to single or two speed fan. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 30 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE Fan Airflow Direction Cooling Coil VT8300 ANALOG COOLING VALVE Configuration Parameter Name Fan menu Pipe no. Seq. operation L-M-H-A 2 Cool only Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VT8300 Modulating Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 31 COOLING VALVE 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 193 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Analog valve modulates allowing cool air to flow to reach setpoint. On Call for Heat Valve closes. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Can be configured to two or three speed fan. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 32 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE Fan Airflow Direction Cooling Coil Heating VT8300 2 POSITION COOLING VALVE ON / OFF DUCT HEATER Configuration Parameter Name Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation L-M-H-A On/Off 0 = 15 Minute 0 2 Cool-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S Application Guide Fan Coil Unit Controller Series VT8300 On / Off Control 1 23456 7 8 9 10 11 12 33 COOLING VALVE L IF NC IF NO Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC FAN HI FAN MED FAN LO BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens. Electric heat stays Off. On Call for Heat Valve closes. Electric heat activates. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 4-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Can be configured to single or two speed fan. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 34 Application Guide Fan Coil Unit Controller Series VT8300 as Zone Controllers VT83X0U5X00B HEATING ONLY ANALOG VALVE ACTUATOR, 2 PIPE This section shows how the VT8300 series Room Controllers are used as Zone Controllers. Airflow Direction Heating Coil ANALOG HEATING VALVE Configuration Parameter Name Fan menu Pipe no. Seq. operation ON-AUTO 2 Heat only Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VT8300 Modulating Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 35 HEATING VALVE 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room: · During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used · During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Auxiliary electric reheat can be added if required by application. Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The heating valve modulates from closed to open according to demand. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 36 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING ONLY ANALOG VALVE ACTUATOR, 2 PIPE Airflow Direction Cooling Coil ANALOG COOLING VALVE © 2015 Viconcis Technologies. All rights reserved. Configuration Parameter Name Fan menu Pipe no. Seq. operation ON-AUTO 2 Cool only Configuration Settings Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series VT8300 Modulating Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 37 COOLING VALVE 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room: · During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used · During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The heating valve modulates from closed to open according to demand. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Auxiliary electric reheat can be added if required by application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 38 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING COIL WITH TRI-STATE FLOATING VALVE ACTUATOR AND PWM ELECTRIC DUCT HEATER Airflow Direction Heating Coil On/Off Duct Heater TRI-STATE FLOATING VALVE SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation ON-AUTO Floating 1 = 10 Second 0-Heat 2 Heat-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 39 VT8300 Floating & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PWM DUCT HEATER SOLID STATE RELAY L HEATING VALVE Close Open Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room: · During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used · During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The proportional device will act as a first step and modulates from 0 to 100% capacity. The perimeter heater will operate as a second step. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 40 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING WITH REHEAT, MODULATING DUCT HEATER, ELECTRIC PERIMETER Airflow Direction Two-stage Duct Heater R820 SCR PERIMETER HEATER SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation ON-AUTO 1 = 10 Second 0-Heat 2 Heat-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 41 VT8300 Mod. & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PERMETER HEAT SOLID STATE RELAY L DUCT HEATER, SRC 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room: · During PIR activated Stand-by periods, Stand-by heating and cooling setpoints are used · During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, the unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The proportional device acts as a first step and modulates from 0 to 100% capacity. The perimeter heater operates as a second step. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 42 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG VALVE ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE Airflow Direction Cooling / Heating Coil On/Off Duct Heater 2 POSITION COOLING VALVE / HEATING VALVE CHANGE OVER SENSOR SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name UI19 Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation COS ON-AUTO 1 = 10 Second 0-Heat 2 Cool-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 43 VT8300 Mod. & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PWM DUCT HEATER SOLID STATE RELAY L HEATING VALVE 0-10 v 24 v Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC CO SENSOR SCOM 10 k-2 BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, the occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Stand-by to Unoccupied when no motion is detected in the room: · During PIR activated stand-by periods, stand-by heating and cooling setpoints are used. · During PIR activated unoccupied periods, unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat If supply water temperature is less than 75°F (23.9°C), the valve modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), valve remains closed. On Call for Cool If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 44 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, TRI-STATE FLOATING ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE Airflow Direction Cooling / Heating Coil On/Off Duct Heater TRI-STATE COOLING VALVE / HEATING VALVE CHANGE OVER SENSOR SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name UI19 Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation COS ON-AUTO Floating 1 = 10 Second 0-Heat 2 Cool-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 45 VT8300 Floating & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PWM DUCT HEATER SOLID STATE RELAY L HEATING VALVE Close Open Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC CO SENSOR SCOM 10 k-2 BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room: · During PIR activated stand-by periods, stand-by heating and cooling setpoints are used. · During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During Unoccupied periods, unoccupied heating and cooling setpoints are used. Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat If supply water temperature is less than 75°F (23.9°C), valve modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), valve remains closed. On Call for Cool If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 46 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, PWM DUCT HEATER AND AIR SENSOR FOR CHANGEOVER, 2 PIPE Airflow Direction Analog Damper On/Off Duct Heater CHANGE OVER DAMPER SENSOR SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name UI19 Fan menu BO8 Out Time BO8 AuxOut Prop. band Pipe no. Seq. operation Configuration Settings COS ON-AUTO 1 = 10 Second 0-Heat Default value 3.0. Range = 3.0 to 10. 2 Cool-rht © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 47 VT8300 Mod. & On / Off Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat OU9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PWM DUCT HEATER SOLID STATE RELAY L ZONE DAMPER ACTUATOR 0-10 v 24 v Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC CO SENSOR SCOM 10 k-2 BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room: · During PIR activated stand-by periods, stand-by heating and cooling setpoints are used. · During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used. Local Override The controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step. On Call for Cool If supply air temperature is less than 75°F (23.9°C), damper modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), damper remains closed. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 48 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, FLOATING AIR DAMPER ACTUATOR, PWM DUCT HEATER AND SUPPLY AIR SENSOR FOR CHANGEOVER, 2 PIPE Airflow Direction Floating Damper On/Off Duct Heater CHANGE OVER DAMPER SENSOR SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name UI19 Fan menu Control Type BO8 Out Time BO8 AuxOut Pipe no. Seq. operation COS ON-AUTO Floating 1 = 10 Second 0-Heat 2 Cool-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 49 VT8300 Floating & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PWM DUCT HEATER SOLID STATE RELAY L ZONE DAMPER ACTUATOR Close Open Com. 13 14 15 16 17 18 19 20 21 22 23 24 24 Vac Transformer COMM ON 24 VAC CO SENSOR SCOM 10 k-2 BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room: · During PIR activated stand-by periods, stand-by heating and cooling setpoints are used. · During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used. Local Override The Controller reverts back to the occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat If supply water temperature is higher than 77°F (25°C), valve modulates from closed to open according to demand. If water supply temperature is less than 75°F (23.9°C), valve remains closed. The duct heater operates as a second step. On Call for Cool If supply air temperature is less than 75°F (23.9°C), damper modulates from closed to open according to demand. If water supply temperature is greater than 77°F (25°C), damper remains closed. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 50 Application Guide Fan Coil Unit Controller Series VT83X0U5X00B COOLING AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, ANALOG DUCT HEATER AND ELECTRIC PERIMETER Airflow Direction Modulating Damper Modulating Duct Heater DAMPER PERIMETER HEATER SSR SOLID STATE RELAY (R1810 WITH HEATSINK) Configuration Parameter Name Fan menu BO8 Out Time BO8 AuxOut Pipe no. Seq. operation ON-AUTO 1 = 10 Second 0-Heat 4 Cl/ht-rht Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 51 VT8300 Modulating & PWM Control BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat OU9 - Close Cool V UO10 - Close Heat V UO11 - Open Cool V UO12 - Open Heat V S 1 23456 7 8 9 10 11 12 PERMETER HEAT SOLID STATE RELAY L DUCT HEATER, SRC 0-10 V 24V Com. ZONE DAMPER COOLING ONLY ACTUATOR 0-10 V 24V Com. 13 14 15 16 17 18 19 20 21 22 23 24 FCU Low-voltage TERMINAL BLOCK COMM ON 24 VAC BACnet + BACnet BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Sequence of Operation and Wiring Occupied Mode During Occupied periods, occupied heating and cooling setpoints are used. Stand-by Mode (only available when PIR motion detector sensor is used) When equipped with a PIR (Passive Infrared) accessory sensor the Controller provides advanced active occupancy logic, which automatically switches occupancy levels from occupied to stand-by to unoccupied when no motion is detected in the room: · During PIR activated stand-by periods, stand-by heating and cooling setpoints are used. · During PIR activated unoccupied periods, the unoccupied-by heating and cooling setpoints are used. Unoccupied Mode During unoccupied periods, unoccupied heating and cooling setpoints are used. Local Override The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The damper remains closed. The proportional heater acts as a first step and modulate from 0 to 100% capacity. The perimeter heater operates as a second step. On Call for Cool The damper modulates from closed to open according to demand. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mounted sensor or return air temperature sensor can be used instead of internal temperature sensor of Controller. · 3 universal inputs can be used and configured for advanced functionality as required by the application. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 52 Application Guide Fan Coil Unit Controller Series VT8300 Mixed-voltage Applications Applications in this section make use of the SC1300 and SC2300 mixed-voltage relays. VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE High Voltage Fan Airflow Direction Cooling Coil Heating Coil VT8300 ANALOG COOLING VALVE ANALOG HEATING VALVE SC1300 Configuration Parameter Name Fan menu Pipe no. Seq. operation L-M-H-A 4 Cool / Heat Power supply 120 vac Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 53 VT8300 Mix Voltage 120 volts BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 SC1300 HEATING VALVE COOLING VALVE 0-10v 24v Com. 0-10v 24v Com. 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Power supply 120 Vac High Voltage Fan FAN HI FAN MED FAN LO COMM ON Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 54 Application Guide Fan Coil Unit Controller Series VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE High Voltage Fan Airflow Direction Cooling Coil Heating Coil VT8300 ANALOG COOLING VALVE ANALOG HEATING VALVE SC2300 Power supply 240 vac Configuration Parameter Name Fan menu Pipe no. Seq. operation L-M-H-A 4 Cool / Heat Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 55 VT8300 Mix Voltage 240 volts BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 SC2300 HEATING VALVE COOLING VALVE 0-10v 24v Com. 0-10v 24v Com. 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Power supply 240 Vac High Voltage Fan FAN HI FAN MED FAN LO COMM ON Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 56 Application Guide Fan Coil Unit Controller Series VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE High Voltage Fan Airflow Direction Cooling Coil Heating Coil VT8300 TRI-STATE FLOATING VALVE TRI-STATE FLOATING VALVE SC1300 Power supply 120 vac Configuration Parameter Name Fan menu Control Type Pipe no. Seq. operation L-M-H-A Floating 4 Cool / Heat Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 57 VT8300 Floating Control Mix Voltage BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 SC1300 HEATING VALVE COOLING VALVE Open Close Com. Open Close Com. 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Power supply 120 Vac High Voltage Fan FAN HI FAN MED FAN LO COMM ON Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems with changeover. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 58 Application Guide Fan Coil Unit Controller Series VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE High Voltage Fan Airflow Direction Cooling Coil Heating Coil VT8300 TRI-STATE FLOATING VALVE TRI-STATE FLOATING VALVE SC2300 Power supply 240 vac Configuration Parameter Name Fan menu Control Type Pipe no. Seq. operation L-M-H-A Floating 4 Cool / Heat Configuration Settings © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 59 VT8300 Floating Control Mix Voltage BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO11 - Analog Heat UO12 - Analog Cool 1 23456 7 8 9 10 11 12 SC2300 HEATING VALVE COOLING VALVE Open Close Com. Open Close Com. 13 14 15 16 17 18 19 20 21 22 23 24 BACnet + BACnet - BACnet REF UI 16 UI 17 Common UI 19 UI 20 - RS Common UI22 - SS Power supply 240 Vac High Voltage Fan FAN HI FAN MED FAN LO COMM ON Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by "ToccTime" parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. On Demand for Dehumidification Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode. Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value. Reheat disabled if cooling demand reaches 100%. Options · Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring). · Remote wall mount or duct sensor ready. · Can be configured for 2-pipe systems with changeover. · 3 universal inputs can be used and configured for advanced functionality as required by the application. · Universal input can be configured for changeover sensor. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconcis Technologies. All rights reserved. 60 Application Guide Fan Coil Unit Controller Series APPENDIX A - PASSIVE INFRA-RED SENSOR SPECIFICATIONS Passive Infra-Red Sensor Sequence of Operation Initially, the Controller is in Stand-by mode and Stand-by setpoints are used for the Controller. When the Passive Infra-Red (PIR) sensor detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used for this operation. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room switches to Stand-by mode and Stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion switches the room back to Occupied mode. Typical Detection Pattern for PIR Lens Recommended installation height for PIR sensor: 4 - 5 ft. / 1.2-1.5 m Horizontal Angles (Typical) Transverse motion: 4-5 ft/s / 1.5 m/s Vertical Angle (Typical) Sensor Ranges A = 20 ft. / 6.1 m B = 14 ft. / 4.3 m C = 11 ft. / 3.4 m 40O A Center 30O 20O B 20O C 20O B 20O C Center Energy Savings Saving Percentage PIR can maximize your energy saving from 10-30% by adjusting temperature set points in unoccupied zones during scheduled periods. Typical Savings of 10-30% 85 50% 80 75 70 40% 65 60 55 50 30% 45 40 35 20% 30 25 20 15 10% 10 5 0 0% 0 2 4 6 8 10 12 14 16 18 20 22 24 Time of Day (EST) Typical Consumption PIR Thermostat Consumption Savings Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Energy Usage (KWh) © 2015 Viconcis Technologies. All rights reserved. Application Guide Fan Coil Unit Controller Series APPENDIX B - OPTIONAL NETWORK SET-UP BACnet® Communication Wiring BACnet +- thermostat 1 ref BACnet +- thermostat 2 ref BACnet +- thermostat 3 ref Notes: · Wiring should be daisy chained · Always respect polarity · If using 2 conductors and shielded wires, connect shield of each feed together on back of Controller · Only ground shield at one location. Do not connect shield to reference terminal 61 Wireless Communication No communication wires required APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION Setpoints Unoccupied cool Stand-by cool Occupied cool Occupied heat Stand-by heat Unoccupied heat 22°C 72°F Deadband 70°F 21°C Stand-by time 24.5 ° C 76°F Deadband 26.5°C 80°F Deadband 66°F 19°C Unoccupied time 62°F 16.5°C 22°C 72°F 70°F 21°C Movement detected - Stand-by timer reset Into Stand-by mode - Unoccupied timer reset Into Unoccupied mode Next movement detected Time © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 62 Application Guide Fan Coil Unit Controller Series APPENDIX D - VTR8300 CONTROLLER AND VC3000 RELAY PACK Product Overview The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet® MSTP or wireless ZigBee® Pro networked models. No previous building automation training is required for installation and commissioning process, and installation can be completed in approximately fifteen minutes. The VC3000 Series Line Voltage Switching Transformer Relay Pack Controllers are designed for silent control of typical high voltage fan coil device loads (90 - 277 VAC multi-voltages). It uses advanced microprocessorbased circuitry with a built-in transformer that eliminates all typical required peripheral components when automating a Fan Coil unit with traditional building automation systems. The VC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR83XX Room Controller. A single VTR8300 or VT8300 Room Controller can control up to 10 x VC3000 Series Relay Packs as they are line-powered units. The unit locally contains all relay outputs for fan switching and valve control, and models are also available for extra monitoring/control inputs of the Fan Coil Units. Typical Fan Coil Unit Set-up Typical Fan Coil Unit 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat 10 Heat + Power Supply SC3404E5000 WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC BLACK FAN LOW 1/2 HP or 13A FAN Max MED RED BLUE FAN HIGH BROWN 5A Max COOL YELLOW Low Voltage Connections to VTR8300 Controller H Electrical Cabinet C 1 Tx/Rx 2 7 Vdc 3 Com 4 RUI 1 5 SCom Power Supply xxx-xxxx-xx 6 RBI 2 7 SS 8 RS 9 Heat 10 Heat + WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC BLACK FAN LOW 1/2 HP or 13A FAN Max MED RED BLUE FAN HIGH BROWN 5A Max COOL YELLOW C C © 2015 Viconcis Technologies. All rights reserved. Daisy Chained Topology Mixed Daisy Chained and Star Topology Star Topology Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 Application Guide Fan Coil Unit Controller Series 63 APPENDIX E - SED SERIES WIRELESS SENSORS Wireless ZigBee® Pro Motion Sensors and Door/Window Switch Wireless door switches used with an onboard or remote PIR sensor provide advanced local occupancy routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort. Wireless window switches are used to monitor exterior windows or patio/balcony doors when opened to prevent unnecessary energy consumption. Fan Coil Room Controllers with SED Series ZigBee® Pro wireless switches can be used in stand-alone mode, or with integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions. Up to twenty SED-WIN or SED-DOR ZigBee wireless switches can be used with a VTR8300 or VT8300 Room Controller Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VTR8300 or VT8300 Room Controller Note that if a ZigBee wireless window switch is used, the VT8300 Room Controller cannot also use a remote PIR motion sensor, whether wired or wireless. Using one or more wireless remote PIR motion sensors means that a wired PIR motion sensor cannot be used, and vice versa. The SED Series sensors are factory delivered with batteries and are ready to be installed, configured, and used right out of the box. Due to the extremely small current consumption of the sensors, the expected battery life is approximately 10 years, which is equivalent to the battery shelf life. No tools are required for commissioning or servicing the ZigBee devices. A simple interface on the devices with an on-board LED and hidden switch provides all required functions for local interaction. The VT8300 user interface has screens used to pair and configure ZigBee devices (SED-WMS, SED-CMS, or SED-WDS only). Local information for battery life and connectivity (heartbeat) are also displayed through the ZigBee® Pro wireless network. For more information about using the SED-WIN and SED-DOR switches, consult the SED-WIN / SED-DOR Wireless Door and Window Switch Installation Guide. For more information about using the SED-WDS, SED-WMS and SED-CMS wireless switches and sensors, consult the Pairing VT8000 Series Room Controllers with ZigBee Sensors Installation Guide and Procedure. Model Selection Window Switch Door switch Window switch Door/window switch Wall mounted motion sensor Ceiling mounted motion sensor Door Switch SED-DOR-P-5045 SED-WIN-P-5045 SED-WDS-P-5045 SED-WMS-P-5045 SED-CMS-P-5045 © 2015 Viconcis Technologies. All rights reserved. Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015 64 Application Guide Fan Coil Unit Controller Series LED SED-CMS LED LED SED-WMS SED-WDS SED-WIN SED-DOR LED Hidden Hidden switch switch Hidden switch © 2015 Viconcis Technologies. All rights reserved. Hidden switch APPENDIX F: TERMINAL CORRESPONDENCE The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000 series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller with a VT8300 Room Controller. VT7000 Terminal name Terminal ID Binary Input 1 BI1 Binary Input 2 BI2 Universal Input 3 UI3 Sensor Common Scom Remote Sensor RS Sensor Common Scom Mix/Supply Sensor MS VT8300 Terminal name Terminal ID Universal Input 16 UI16 Universal Input 17 UI17 Universal Input 19 UI19 Terminal 18 Common COM Universal Input 20 UI20 - RS Terminal 21 Common COM Universal Input 22 UI22 - SS Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0444-01 www.viconics.com | sales@viconics.com April 2015Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)