SERVICE INSTRUCTIONS WITH REPLACEMENT PARTS LIST
LC6000-100 CONTROLLER
Part of the Bard Free Cooling Unit System

NOTE: LC6000 Controller is required for operation when multiple MULTI-TEC ® W***AP wall-mount units are used.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

Manual :

2100-669B

Supersedes: 2100-669A

Date:

1-23-18

Page

1 of 19

CONTENTS

General Information............................................3 Free Cooling Unit System........................................3 Controller..............................................................3 Additional Publications...........................................4
Alarms....................................................................5 Alarm Adjustment..................................................5 Acknowledging/Clearing Alarms.........................5 Low Temperature Alarm....................................5 High Temperature Alarm...................................5 High Temperature 2 Alarm................................6 Smoke Alarm..................................................6 Generator Alarm..............................................7 Hydrogen Alarm...............................................7 Zone Unit Alarm..............................................8 Humidity Alarm...............................................9
Control Operation..............................................10 Temperature Control.............................................10 Control Value Averaging..................................10 Comfort Mode...............................................10 Staging .............................................................10 FIFO (First In First Out)..................................10 LIFO (Last In First Out)..................................10 Demand Staging............................................10 Staging Delay................................................11 Maximum Number of Units Running...............11 Rotation.......................................................11 Demand........................................................12 Humidity Control..................................................12 Dehumidification...........................................12 Humidification..............................................13 Enabling Humidifier................................13 Fan Control.........................................................14
Additional Information.....................................15 LC6000 Menus/Screens.......................................15 Main Menu...................................................15 Status Screen...............................................15 Quick Menu..................................................15 Menu Screens and Password Levels.................15 Additional Programming.......................................16 Changing to Celsius.......................................16 Calibrating Sensors........................................16 Clearing Alarm Logs.......................................16
LC6000 Replacement Parts List.......................19

FIGURES AND TABLES

Figure 1 Adjust Alarm Setpoints............................5

Figure 2 Adjust Alarm Remote Notification

Relay Output Direction...............................................5

Figure 3 Adjust Smoke, Generator or Hydrogen

Alarm Input Direction................................................6

Figure 4 Adjust Alarm Remote Notification

Relay Output Direction...............................................7

Figure 5 Adjust Zone Alarm Configuration...............8

Figure 6 Adjust Humidity Alarm Setpoints..............9

Figure 7 Change Indoor Temperature Averaging

Type

10

Figure 8 Adjust Staging Settings..........................11

Figure 9 Staging Maximum Number of Units

Running 11

Figure 10 Rotation...............................................12

Figure 11 Humidity Control Setpoints.....................13

Figure 12 Dehumidification Types..........................13

Figure 13 Enabling Humidifier...............................13

Figure 14 Continuous Blower.................................14

Figure 15 Clearing Alarm Logs...............................16

Figure 16 LC6000 Wiring Diagram.........................18

Table 1 Table 2 Table 3

LC6000 Passwords (Defaults).................15 LC6000 Status Messages.......................15 Terminal Block Index.............................17

Manual 2100-669B Page 2 of 19

GENERAL INFORMATION

Free Cooling Unit System
The Bard Free Cooling Unit system is composed of MULTI-TEC wall-mounted air conditioners matched with an LC6000 supervisory controller or Bard th-Tune stand-alone controller. If only one wall-mounted air conditioner is being used, it can be matched with either the LC6000 supervisory controller or a th-Tune stand-alone controller. If more than one wall-mount unit is installed, the LC6000 controller must be matched with the air conditioning units. The wall-mount units are specifically engineered for telecom/motor control center rooms.
NOTE: The LC6000 supervisory controller and MULTI-TEC wall-mount units are designed specifically to work together. The controller cannot run other brands of systems, nor can other controllers run the MULTI-TEC wall-mount units. They are a complete system, and must be used together.
Controller
LC6000 controller and accessories included shown below.

LC6000 Series

TEC-EYETM Hand-Held Diagnostic Tool Bard P/N 8301-059

LC6000 Series Programmable Logic Controller

Remote Temperature/ Humidity Sensor*
(with 35' shielded cable) Bard P/N 8403-079

Communication EMI Filters
Bard P/N 8301-055

* One remote temperature/humidity sensor and 35' of 5-wire shielded cable are included with the LC6000 controller. If the site in which the LC6000 controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One additional temperature-only sensor (Bard P/N 8301058) may also be used in Zone 1 but will also need to be purchased separately. Temperature-only sensors require field-supplied 2-wire shielded cable.

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
These instructions should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications on page 4 for information on codes and standards.

Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier's agent.

Manual 2100-669B

Page

3 of 19

Additional Publications
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code.......................ANSI/NFPA 70
Standard for the Installation of Air Conditioning and Ventilating Systems ....................ANSI/NFPA 90A
Standard for Warm Air Heating and Air Conditioning Systems.............ANSI/NFPA 90B
Load Calculation for Residential Winter and Summer Air Conditioning.............. ACCA Manual J
Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ....................................................... ACCA Manual D
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. The signal word "DANGER" is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to "NOTICE" the word "CAUTION" without the safety alert symbol may be used to indicate a message not related to personal injury.

Manual 2100-669B Page 4 of 19

ALARMS

NOTE: Screenshots shown in this manual reflect default settings (when applicable).
Alarm Adjustment
Acknowledging/Clearing Alarms
Alarm conditions activate a red LED indicator that backlights the ALARM function key. As an option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is acknowledged by pressing the ALARM key. This calls up alarm display screen(s) that provide a text message detailing the alarm condition(s). After an alarm condition is corrected, the alarm can be cleared by pressing the ALARM key for 3 seconds.
Low Temperature Alarm
If the lowest temperature sensor value in a zone is below the low temperature setpoint, an alarm will be generated for that zone. Additionally, a relay output will be actuated from the LC controller to provide remote notification of the event.
NOTE: This alarm is per zone. If each zone is meant to operate within the same alarm parameters, each zone will need to be set accordingly.
To adjust the low temperature alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-8 (Zone 1), Alarm Setpoints A3-8 (Zone 2) or Alarm Setpoints A4-8 (Zone 3).
6. Press ENTER key to scroll to the variable labeled Low Temp (see Figure 1).
7. Press UP or DOWN keys to adjust setpoint.
FIGURE 1 Adjust Alarm Setpoints

To change the direction of the remote notification relay output: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Digital Out
Config C3. 5. Press ENTER key to scroll to the variable in the
table that intersects LoTemp and Dir (see Figure 2) 6. Press UP or DOWN key to change direction. When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.
FIGURE 2 Adjust Alarm Remote Notification
Relay Output Direction
High Temperature Alarm If the highest temperature sensor value in a zone is above the high temperature setpoint, an alarm will be generated for that zone. When this alarm is present, the standby units in this zone will become active. NOTE: This alarm is per zone. If each zone is meant to
operate within the same alarm parameters, each zone will need to be set accordingly. To adjust the high temperature alarm setpoint: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter USER password 2000. 3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key. 4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

Manual 2100-669B

Page

5 of 19

5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-8 (Zone 1), Alarm Setpoints A3-8 (Zone 2) or Alarm Setpoints A4-8 (Zone 3).
6. Press ENTER key to scroll to the variable labeled High Temp (see Figure 1).
7. Press UP or DOWN keys to adjust setpoint.
High Temperature 2 Alarm
If the highest temperature sensor value in a zone is above the high temperature 2 setpoint, an alarm will be generated for that zone. When this alarm is present, the units will emergency cool in this zone. Additionally, a relay output will be actuated from the LC to provide remote notification of the event.
NOTE: This alarm is per zone. If each zone is meant to operate within the same alarm parameters, each zone will need to be set accordingly.
To adjust the high temperature 2 alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-8 (Zone 1), Alarm Setpoints A3-8 (Zone 2) or Alarm Setpoints A4-8 (Zone 3).
6. Press ENTER key to scroll to the variable labeled High Temp 2 (see Figure 1).
7. Press UP or DOWN keys to adjust setpoint.
To change the direction of the remote notification relay output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Out Config C3.
5. Press ENTER key to scroll to the variable in the table that intersects HiTemp and Dir (see Figure 2).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.

Smoke Alarm If the LC gets an input from a smoke detector, an alarm will be generated and all units will be shut down. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The smoke alarm input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input. When this jumper is removed, the alarm will become active. To change the direction of the smoke input: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Digital In
Config C1. 5. Press ENTER key to scroll to the variable in the
table that intersects Smoke and Dir (see Figure 3). 6. Press UP or DOWN key to change direction. By changing this value, the input will operate in reverse. When the direction is set to NC, the alarm will be present when the jumper is present or when the device closes the contacts to this input.
FIGURE 3 Adjust Smoke, Generator or Hydrogen Alarm
Input Direction
To change the direction of the remote notification relay output: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Digital Out
Config C2. 5. Press ENTER key to scroll to the variable in the
table that intersects Smoke and Dir (see Figure 4).

Manual 2100-669B Page 6 of 19

6. Press UP or DOWN key to change direction. When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.
FIGURE 4 Adjust Alarm Remote Notification Relay
Output Direction
Generator Alarm If the LC detects a generator running event (through a digital input), an alarm will be generated. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user will be able to configure which units are permitted to run during this event. Default will be to not allow any units to run. The generator alarm input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input. When this jumper is removed, the alarm will become active. To change the direction of the generator input: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Digital In
Config C1. 5. Press ENTER key to scroll to the variable in the
table that intersects Gen and Dir (see Figure 3). 6. Press UP or DOWN key to change direction. By changing this value, the input will operate in reverse. When the direction is set to NC, the alarm will be present when the jumper is present or when the device closes the contacts to this input.

To change the direction of the remote notification relay output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Out Config C2.
5. Press ENTER key to scroll to the variable in the table that intersects Gen and Dir (see Figure 4).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.
Hydrogen Alarm
If the LC detects a hydrogen event (through a digital input), an alarm will be generated and the wall units will all be put into emergency ventilation by the LC. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user will be able to configure which zones ventilate during this event.
The hydrogen alarm input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input. When this jumper is removed, the alarm will become active.
To change the direction of the hydrogen input:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital In Config C1.
5. Press ENTER key to scroll to the variable in the table that intersects Hydro and Dir (see Figure 3).
6. Press UP or DOWN key to change direction.
By changing this value, the input will operate in reverse. When the direction is set to NC, the alarm will be present when the jumper is present or when the device closes the contacts to this input.
To change the direction of the remote notification relay output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

Manual 2100-669B

Page

7 of 19

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Out Config C2.
5. Press ENTER key to scroll to the variable in the table that intersects Hydro and Dir (see Figure 4).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.
Zone Unit Alarm
If any of the units communicate a high pressure or low pressure alarm to the LC, the LC will actuate a relay output to provide remote notification of the event. A relay output will be actuated from the LC to provide remote notification of the event for each zone.
To change the direction of the remote notification relay output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Out Config C3.
5. Press ENTER key to scroll to the variable in the table that intersects Z1Alm and Dir, Z2Alm and Dir, or Z3Alm and Dir (see Figure 2 on page 5).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.
The zone alarms can be configured to actuate based on 15 alarms communicated from each wall unit. These items can be selected for each zone.
To select which wall unit alarms actuate zone alarms:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone Alarm Config B4, Zone Alarm Config B5 and Zone Alarm Config B6. The 15 alarms are divided between these three screens.

5. Press ENTER key to scroll to the variable in the table that intersects with each alarm and zone number (see Figure 5).
6. Press UP or DOWN key to change value (N or Y). If a value of Y is entered, the wall unit alarm will trigger the zone alarm relay output. If a value of N is entered, the wall unit alarm will not trigger the zone alarm relay output.
NOTE: By default, only 'no temperature sensors' and high and low pressure actuate the alarms.
NOTE: Power Loss group is also affected by communication loss.
NOTE: If no temperature sensors are detected by the controller for a given zone, that zone alarm output will be actuated. This is nonconfigurable.
FIGURE 5 Adjust Zone Alarm Configuration

Manual 2100-669B Page 8 of 19

Humidity Alarm
When the LC detects a high indoor humidity or low indoor humidity event in a selected zone (through an analog input from a remote sensor), an alarm will be generated. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user can configure the alarm to be actuated when the measurement is high, low or both high and low.
To adjust the humidity alarm setpoints:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-9 (Zone 1), Alarm Setpoints A3-9 (Zone 2) or Alarm Setpoints A4-9 (Zone 3).
6. Press ENTER key to scroll to Low Humidity, High Humidity or Alarm Delay (delay in seconds from the time the alarm is sensed until the alarm is displayed). See Figure 6.
7. Press UP and DOWN keys to adjust setpoints or delay.
FIGURE 6 Adjust Humidity Alarm Setpoints

To adjust the direction of the remote notification relay output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Out Config C3.
5. Press ENTER key to scroll to the variable in the table that intersects HumAl and Dir (see Figure 2 on page 5).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.

Manual 2100-669B

Page

9 of 19

CONTROL OPERATION

NOTE: Screenshots shown in this manual reflect default settings (when applicable).
Temperature Control
Indoor Temperature Averaging The LC has the ability to average all of the zone temperature sensors connected to the LC and the return air temperature sensors connected to the wallmount unit, use only the zone temperature sensors, or use the LC sensors and any unit which has its blower run continuously. This can be set differently for each zone. This value will then be used as a zone indoor temperature for the LC and wall-mount unit control functions. There are three possible sensor averaging selections: · LC Only
This configuration only averages the zone temperature sensors connected to the LC and enabled within the specific zone. · Blower On This configuration averages any temperature sensors connected to the LC and enabled and the return air temperature sensor of any wall-mount unit running in continuous blower within the specific zone. · All Sensors This configuration averages the zone temperature sensors connected to the LC and enabled and all the return air temperature sensors of all wallmount units within the specific zone. To change the indoor temperature averaging type: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter USER password 2000. 3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key. 4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key. 5. Press UP or DOWN keys to scroll to Zone Temp A210 (Zone 1), Zone Temp A3-10 (Zone 2) or Zone Temp A4-10 (Zone 3). 6. Press ENTER key to scroll to Selection (see Figure 7). 7. Press UP and DOWN keys to adjust.
Manual 2100-669B Page 10 of 19

FIGURE 7 Change Indoor Temperature Averaging Type
Comfort Mode If comfort mode is activated, all of the zone setpoints will be set to 72°F for cooling and 70°F (Comfort Setoint -2) for heating. This setpoint will be active for 60 minutes. To enable comfort mode: 1. Press UP or DOWN key while on the Status screen
to select Setpoints ( ) from the Quick Menu options; press ENTER key. 2. Press ENTER key to scroll to Comfort Mode. 3. Press UP or DOWN keys to change the duration of comfort mode. 4. Press ENTER key to scroll to Comfort Setpoint. 5. Press UP and DOWN keys to change the cooling setpoint for comfort mode. 6. Press ENTER key to scroll to Comfort Enable. 7. Press UP or DOWN key to change value from OFF to ON; press ENTER key. The system is now in comfort mode and will cool to the comfort setpoint for the duration previously set.
Staging
Each zone is capable of three different staging methods. FIFO (First in First Out) The unit that is turned on first will be the first one turned off. LIFO (Last in First Out) The unit that is turned on last will be the first on turned off. Demand Staging While in cooling operation, the unit with the highest return temperature will be brought on first. The unit with the lowest return temperature will be turned off first. While in heating mode, the unit with the lowest

return air temperature will be brought on first and the unit with the highest return temperature will be turned off first.
To change the staging method type:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Staging A2-4 (Zone 1), A3-4 (Zone 2) or A4-4 (Zone 3).
6. Press ENTER key to scroll to the variable labeled Type (see Figure 1).
7. Press UP or DOWN keys to adjust.
FIGURE 8 Adjust Staging Settings

Maximum Number of Units Running
The maximum number of units that will be staged on can be configured for each zone. The number is defaulted at the total number of units capable so that they are fully utilized by default. This is configurable for economizer, cooling and heating independently.
To adjust the on and off delay times:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Staging A2-5 (Zone 1), Staging A3-5 (Zone 2) or Staging A4-5 (Zone 3).
6. Press ENTER key to scroll to the variable for Freecooling, Cooling or Heating (see Figure 9).
7. Press UP or DOWN keys to adjust number of units.
FIGURE 9 Staging Maximum Number of Units Running

Staging Delay
A delay on and off can be set for economizer, cooling and heating independently for each zone. This will limit how fast the units can be staged on or off.
To adjust the on and off delay times:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Staging A2-4 (Zone 1), Staging A3-4 (Zone 2) or Staging A4-4 (Zone 3).
6. Press ENTER key to scroll to the variable in the table that intersects FC, CL or HT and Delay On or Delay Off (see Figure 8).
7. Press UP or DOWN keys to adjust.

Rotation
The units in each zone can be rotated based on a configurable number of days. The time is defaulted to 7 days. In addition to time-based, a manual rotation can be triggered for troubleshooting.
To change the rotation variables:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Rotation A2-6 (Zone 1), Rotation A3-6 (Zone 2) or Rotation A4-6 (Zone 3).

Manual 2100-669B

Page

11 of 19

6. Press ENTER key to scroll to Time Based (see Figure 10).
7. Press UP or DOWN key to change ON to OFF. 8. Press ENTER key to scroll to Num. of Days. 9. Press UP or DOWN keys to adjust the number of
days. 10. Press ENTER key to scroll to Manual. 11. Press UP or DOWN key to change OFF to ON.
FIGURE 10 Rotation
Demand The system will compare the zone temperature (determined by zone averaging selection) to the zone cooling and heating setpoint. A demand will be calculated to determine how many units are required. For cooling, the zone temperature will be compared to the cooling setpoint. The controller will calculate a demand based on how far above the setpoint and how long it has been above the setpoint. The demand value (0-100%) will then be split and applied to freecooling and cooling separately shown as two demands both ranged 0-100% applied to all of the available cooling methods for that zone. For example, if the demand is at 50% and there are 10 available stages of cooling in that zone, there would be 5 stages active (50% x 10 = 5). The system will prioritize freecooling stages over compressor stages. Adding to the example, if 5 of the 10 stages for cooling are economizer, 5 units would be running economizer and no compressors running. The demand is calculated for the cooling application. However, for display purposes, the demand is split so that the user can see demand separately for freecooling and compressor. For heating, the zone temperature will be compared to the heating setpoint. The controller will calculate a demand based on how far below the setpoint and how long it has been below the setpoint. The demand value 0-100% will the be applied to all of the available stages of heating in that zone. For example, if the demand is at 50% and there are 5 available stages of heating in that zone, there would be 2 stages active (50% x 5 = 2.5 and a half of a stage cannot be turned on).

Humidity Control
The LC can be configured to control up to three humidifiers with relay outputs and up to 14 units equipped with dehumidification. The indoor humidity level for each zone is compared to the dehumidification setpoint and humidification setpoint for each zone.
Dehumidification
The supervisory controller will monitor the indoor relative humidity of each zone and compare the value to three setpoints for each zone. The three setpoints will be described as dehumidification off, passive dehumidification and active dehumidification. The default value for these setpoints will be 60%RH, 70%RH and 80%RH, respectively.
When the humidity level inside the shelter falls to the dehumidification off setpoint, the system will stop attempting to dehumidify the space.
When the humidity level rises to the passive dehumidification setpoint, all units with economizers will disable the use of economizers for cooling calls. This will act as passive dehumidification by forcing the use of compressor for space cooling. Availability for passive dehumidification will be determined by model number. All units with economizers will be considered.
When the humidity level rises to the active dehumidification setpoint, the controller will activate staged dehumidification. The controller will then calculate a dehumidification demand based on how far above the setpoint and how long the RH level has been above the setpoint. The demand will then utilize all of the units with active dehumidification capabilities to reduce the indoor humidity level. The units will be staged on based on the existing cooling rotation for the units in the zone up to an optional maximum number of units running value. Availability for active dehumidification will be determined by model number. Units with concurrent electric reheat or mechanical dehumidification will be considered. NOTE: Only one type of dehumidification unit will be considered depending upon configuration of the supervisory controller. Unit capability is determined by the model number.
To change the dehumidification setpoints:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Setpoints A2-2 (Zone 1), Setpoints A3-2 (Zone 2) or Setpoints A4-2 (Zone 3).

Manual 2100-669B Page 12 of 19

6. Press ENTER key to scroll to Dehumidification Off, Passive On or Active On (see Figure 11).
7. Press UP and DOWN keys to change dehumidification setpoints to desired values.
FIGURE 11 Humidity Control Setpoints
In addition to the setpoint configuration for dehumidification, each zone must be configured for the type of active dehumidification. To change the dehumidification type: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Zone 1, Zone 2
or Zone 3; press ENTER key. 5. Press UP or DOWN keys to scroll to Setpoints
A2-11 (Zone 1), Setpoints A3-11 (Zone 2) or Setpoints A4-11 (Zone 3). 6. Press ENTER key to scroll to Type (see Figure 12). 7. Press UP and DOWN keys to change to desired value. Dehumidification type choices are None, Electric Reheat, Mechanical Reheat or Cycling Reheat. The units in the zone being configured will need to have the capability of the setting being selected.
FIGURE 12 Dehumidification Types

Humidification
If the humidity level is below 45% RH (Humidification Setpoint), the LC will enable humidification for that zone. Once the humidity level rises to 55% RH (Humidification Setpoint plus 10% RH), the humidification for that zone will be disabled.
NOTE: Humidifiers supplied by others.
To change the humidification setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5. Press UP or DOWN keys to scroll to Setpoints A2-2 (Zone 1), Setpoints A3-2 (Zone 2) or Setpoints A4-2 (Zone 3).
6. Press ENTER key to scroll to Humidification (see Figure 11).
7. Press UP and DOWN keys to change humidification setpoint to desired value.
Enabling Humidifier
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to General; press ENTER key.
5. Press ENTER key to scroll to Humidifiers (see Figure 13).
6. Press UP or DOWN keys to change value to NONE, Zone 1, Z1 & Z2 or Z1, Z2, & Z3.
7. Press ENTER to scroll to Humidifier Type.
8. Press UP or DOWN keys to change value to Relay from Comm.
FIGURE 13 Enabling Humidifier

Manual 2100-669B

Page

13 of 19

Fan Control
The LC has the capability to change the continuous fan status of all the units in a zone. The user is able to select between none, lead and all. When "none" is selected, all unit blowers will only be enabled on a call for heating or cooling. When "lead" is selected, only the lead unit will be have its blower active. When "all" is selected, the blower on all units (active and standby) will be enabled all the time. To change the continuous fan status of each zone: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Zone 1, Zone 2
or Zone 3; press ENTER key. 5. Press UP or DOWN keys to scroll to Cont. Blower
A2-7 (Zone 1), Cont. Blower A3-7 (Zone 2) or Cont. Blower A4-7 (Zone 3). 6. Press ENTER key to scroll to Selection (see Figure 14). 7. Press UP and DOWN keys to change to desired choice.
FIGURE 14 Continuous Blower
Manual 2100-669B Page 14 of 19

ADDITIONAL INFORMATION

LC6000 Menus/Screens
Main Menu
Press the MENU key from any screen to return to the Main Menu. Press the UP or DOWN keys to scroll through the available menus. When the desired menu is highlighted, press the ENTER key to access that menu. Press the ESCAPE key or MENU key to return to the Status screen from the Main Menu.
Status Screen
The Status screen is the default start-up screen and also the return screen after 5 minutes of no activity. The screen can be accessed any time by pressing the ESCAPE button repeatedly. The LC6000 Status screen displays the current date, time, unit displayed, zone and unit status.
Quick Menu
The Quick Menu is available on the Status screen. Use UP or DOWN keys while on the Status screen to scroll between the three Quick Menu options; press ENTER key.
Data Log
The data log displays the record number, time of alarm event, date of alarm event, description of alarm event and whether the entry is the beginning or end of event. The data log will have as many screens as events occurred.
Info
Info displays wall unit status for each wall-mount unit connected to controller, last hour tracking (shelter), last hour tracking (for each wall-mount unit connected, last hour averages (zone temperatures, OA temperature and OA humidity) and additional LC6000 information.
Setpoints
Setpoints allows setting and enabling of comfort mode.
Menu Screens and Password Levels
A System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
B Adv Sys Config: Technician (1313)
C I-O Config: Technician (1313)
D On/Off: User (2000)
E Alarm Logs: User (2000)

F Settings Date/Time: Technician (1313) Language: User (2000) Network Config: Technician (1313) Serial Ports: Technician (1313) Initialization Clear Logs: User (2000) System Default: Engineer (9254) Restart: User (2000) Parameter Config: Engineer (9254) Alarm Export: User (2000)
G Logout: Used to log out of the current password level. Entering back into the menu requires password.

TABLE 1 LC6000 Passwords (Defaults)

User

2000

Technician

1313

Engineer

9254

Use UP or DOWN keys and ENTER key to enter password

TABLE 2 LC6000 Status Messages

Message

Description

On Off by Alarm Off by BMS Off by Keypad

The system is on
The system has a major fault and is disabled
The system has been disabled by network supervisor
The system has been turned off by local user

Emergency Cooling

The system has detected a high temperature alarm and one or more
zones are emergency cooling

Emergency Vent

The system has detected hydrogen and one or more zones are in emergency ventilation

Manual 2100-669B

Page

15 of 19

Additional Programming
Changing to Celsius 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to Unit Setup
(A1-1). 5. Press ENTER key to scroll to UOM. 6. Press UP and DOWN keys to change value to SI. Calibrating Sensors 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key. 4. Press UP or DOWN keys to scroll to sensor to be
adjusted. 5. Press ENTER key to scroll to Offset. 6. Press UP or DOWN keys to add or subtract to the
sensor offset value. 7. Press ENTER key to save. Clearing Alarm Logs 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter
USER password 2000. 3. Press UP or DOWN keys to scroll to Settings; press
ENTER key. 4. Press UP or DOWN keys to scroll to Initialization;
press ENTER key. 5. Press ENTER key to scroll to Delete Alarm Logs?
(see Figure 15). 6. Press UP Or DOWN key to change value to YES;
press ENTER key.
FIGURE 15 Clearing LC6000 Alarm Logs
Manual 2100-669B Page 16 of 19

TABLE 3 Terminal Block Index

TB#

Wire Mark

Description

1

- 115 VAC Input

2

- 208 VAC Input

3

- 240 VAC Input

4

- Power Input Common

5

- Power Input Ground

6

DI1 Smoke Detector Input

7 GND Smoke Detector Common

8

DI2 Hydrogen Detector Input

9 GND Hydrogen Detector Common

10 DI3 Generator Run Input

11 GND Generator Run Common

12 B2 Indoor Remote Humidity Sensor (Zone 1)

13 GND Ground

14 B3 Indoor Remote Humidity Sensor (Zone 2)

15 GND Ground

16 B4 Indoor Remote Humidity Sensor (Zone 3)

17 GND Ground

18 B6 Indoor Temperature Sensor (Zone 1)

19 GND Ground

20

B7

Indoor Remote Temperature Sensor (Zone 1)

21 GND Ground

22 VDC+ Power for B2 (Z1 Humidity)

23 VDC+ Power for B3 (Z2 Humidity)

24 VDC+ Power for B4 (Z3 Humidity)

25 VDC+ Power for B10 (Pressure)

26

B8

Indoor Remote Temperature Sensor (Zone 2)

27 GND Ground

28

B9

Indoor Remote Temperature Sensor (Zone 3)

29 GND Ground

TB#

Wire Mark

Description

30 B10 Indoor Space Pressure

31 GND Ground

32 NO1 Humidifier 1

33 C1 Common

34 NO2 Humidifier 2

35 C1 Common

36 NO3 Humidifier 3

37 C1 Common

38 NO4 Smoke Alarm

39 C2 Common

40 NO5 Hydrogen Alarm

41 C2 Common

42 NO6 Generator Alarm

43 C2 Common

44 NO7 Indoor Humidity Alarm

45 C7 Common

46 NO8 High Indoor Temperature Alarm

47 C8 Common

48 NO9 Low Indoor Temperature Alarm

49 C8 Common

50 NO10 Zone 1 Unit Alarm

51 C8 Common

52 NO11 Zone 2 Unit Alarm

53 C8 Common

54 NO12 Zone 3 Unit Alarm

55 C8 Common

56 FB1R- RS485 RX- / TX- (Fieldbus 1)

57 FB1R+ RS485 RX+ / TX- (Fieldbus 1)

58 FB2R- RS485 RX- / TX- (Fieldbus 2)

59 FB2R+ RS485 RX+ / TX- (Fieldbus 2)

60

- Ground

Manual 2100-669B

Page

17 of 19

FIGURE 16 LC6000 Wiring Diagram
Manual 2100-669B Page 18 of 19

LC6000 REPLACEMENT PARTS LIST

3

1

2

7

8

6

5

4

Dwg. No.
1 2 3 4 5 6 7 8 NS NS NS NS NS

Part Number 8407-069 8301-076-001 8301-053 8607-052 8614-059 8607-039 8607-057 8611-144 8301-055 8301-058 8403-079 8301-059 3000-1587

NS ­ Not Shown

Description Transformer Micro PC ­ Medium, Programmed for LC6000 pGDEvolution Panel Display Grounded Terminal Block 1.0 Amp Fuse Fused Terminal Block Terminal Block Double Level End Clamp (for Din Rail) EMI Ferrite Filter Remote Temperature Sensor  Remote Temperature/Humidity Sensor TEC-EYE (Service Tool), 5' Telephone Cable 5' Telephone Cable
 ­ Optional

LC6000

X X X 2 4 4 54 6 2 X X X X

Manual 2100-669B