407012 7ah2ae spec guide 2024
AIR HANDLERS

7AH2AE
Upflow/Horizontal | Constant Torque Motor | TXV Furnished | R-410A / R-454B | 60Hz

RESIDENTIAL PRODUCT SPECIFICATIONS (EHB)

1.5 to 5 Tons Optional Electric Heat - 5 to 25 kW

NOTE - Air Handlers are furnished with a factory installed R-410A expansion valve. As an option, a R-454B expansion valve may be substituted. See Page 8.
NOTE - See R-454B Refrigerant Conversion Table on Page 8 for additional components required for conversion.
MODEL NUMBER IDENTIFICATION
7 AH 2 A E 36 P X C 01

Refrigerant 7 = R-454B
Type AH = Air Handler EF = Electric Furnace
Cabinet 1 piece 2 piece
Series A = 1st Generation

Major Revision Code 01= Multi Refrigerant

Expansion Device X = TXV

Revision Level -- = 24V C = Comfort Sync® Enabled

Voltage P = 208-230V/ 60Hz/1PH

Motor C = PSC E = Constant Torque V = Variable Speed

Capacity 18 = 1.5 tons 24 = 2 tons 30 = 2.5 tons 36 = 3 tons 42 = 3.5 tons 48 = 4 tons 60 = 5 tons

FEATURE HIGHLIGHTS 6

1. Allied Omniguard® Coil 2. Refrigerant Line Connections 3. Check and Expansion Valve 4. Constant Torque Blower Motor 5. Heavy Gauge Steel Cabinet 6. Electric Heat (optional) 7. Built-in Filter Rack

4

1

5

3

7

2

CONTENTS
Model Number Identification  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  1 Approvals And Warranty  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3 Features .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3 Electrical Data .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installation Clearances With Electric Heat .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  8 Optional Accessories - Order Separately . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Optional R-454B TXV Substitution .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  8 Blower Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9 Replacement Circuit Breakers  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11 Electric Heat Data .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 12 Dimensions .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .23
- Unit - Upflow Position .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .23 - Unit - Downflow Position  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 24 - Unit - Horizontal Right-Hand Position .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .25 - Accessories .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .26
7AH2AE | 1.5 to 5 ton Air Handlers | Page 2

APPROVALS AND WARRANTY
APPROVALS · Tested with matching air conditioners and heat pump units in accordance with AHRI Standard 210/240-2023 · AHRI Certified system match-ups and expanded ratings, visit www.alliedratings.com · ETL Listed to US and Canadian safety standards and components within are bonded for grounding to meet safety
standards for servicing required by NEC and CEC. · Optional electric heaters are ETL listed and rated in accordance with US Department of Energy (DOE) test procedures
and Federal Trade Commission (FTC) labeling regulations · Blower performance data according to unit tests conducted in air test chamber · Air handler units are approved for installation in manufactured housing and mobile homes. · ISO 9001 Registered Manufacturing Quality System
WARRANTY 10-years limited warranty on all parts, extended warranty available. Warranty provides for a total of 10-years of limited warranty. Coverage (Standard 5-year limited parts warranty plus an additional 5-year limited extended parts warranty). Warranty must be registered online within 60 days of installation to qualify for 10-year coverage. Unregistered equipment defaults to 5-year coverage. See full warranty at www.alliedair.com for terms, conditions, and exclusions.

F E AT U R E S

APPLICATIONS
· 1.5 to 5 ton nominal sizes
· Upflow or horizontal applications NOTE - Downflow applications require optional
conversion kit.
· Applicable to expansion valve systems in cooling applications and check and expansion valve systems in heat pump applications
· Wide-range R-410A check and expansion valve is factory installed
NOTE - Coils can be field converted for use with R-454B refrigerant.
· Optional field installed electric heaters available in several sizes for additive heating capacity
REFRIGERANT SYSTEM
1 Omniguard® Coil
· Enhanced aluminum alloy tube/enhanced fin coil for superior corrosion resistance
· Aluminum tubing, hairpins, distributor and header tubes.
· Ripple-edged aluminum fins
· Twin coil construction assembled in a "A" configuration for large surface area
· Provides excellent heat transfer and low air resistance for maximum efficiency
· Precise circuiting for uniform refrigerant distribution
· Lanced fins provide maximum exposure of fin surface to air stream
· Helical grooved tubing provides superior heat transfer
· Coil thoroughly factory tested under high pressure to ensure leakproof construction

2 Refrigerant Line Connections
· Copper refrigerant sweat connections on both liquid and suction lines for easy brazing
· Lines extend outside of the cabinet for ease of connection
· See dimension drawings for locations
3 R-410A Check and Expansion Valve
· For use with R-410A systems
· Wide range valve with Chatleff style fitting
· Factory installed on all models, internal to cabinet
R-454B REFRIGERANT CONVERSION Additional Components are required for conversion to R-454B Refrigerant:
· Refrigerant Detection System (RDS) Air Handler Sensor Kit
· Refrigerant Detection System (RDS) NonCommunicating Blower Control Board
· R-454B Check and Expansion Valve
Optional Accessories
Refrigerant Detection System (RDS) Air Handler Sensor Kit · Complies with UL 60335-2-40 approved standard
· Required for all systems using R-454B refrigerant
· Consists of Refrigerant Detection System (RDS) sensor, mounting brackets and A2L labeling
· See R-454B Refrigerant Conversion Table on Page 8

7AH2AE | 1.5 to 5 ton Air Handlers | Page 3

F E AT U R E S R-454B REFRIGERANT CONVERSION (Continued)

4 BLOWER

Refrigerant Detection System (RDS) Blower Control Board Communicating Blower Control Board (Universal)

Constant Torque Blower Motor · Programmable high efficiency

· Communicating Blower Control Board and Sensor can be used universally with any communicating air handler or any non-communicating 24 volt air handler
Non-Communicating Blower Control Board
· Non-Communicating Blower Control Board and Sensor can be used with any non-communicating 24 volt air handler

· multi-speed blower motor. By · maintaining constant torque · output, blower motor can · deliver more uniform (but no · t constant) airflow over the static · pressure range

Standard Features

· Programmable multi-speed operation is achieved by

· Complies with UL 60335-2-40 approved standard
· Required for all systems using R-454B refrigerant
· Connects to the RDS sensor furnished with the RDS Air Handler Sensor Kit
· Supports up to two RDS Sensors (factory setting)

the use of an ECM (Electronically Commutated Motor) motor
· Leadless blower motor features simple plug-in connections
· Choice of blower speeds is available. See Blower Data tables

· Used as interface between indoor unit and thermostat to control system in case of a refrigerant leak

· Blower speed change is easily accomplished by a simple wiring change

· If a leak is detected the refrigerant detection system will prevent compressor and heating operation until a leak is no longer detected
· Refrigeration detection system also energizes the blower if a leak is detected to dissipate any

Blower Assembly · Statically and dynamically balanced as an assembly
before installation in the unit
· Blower motor is resiliently mounted to blower assembly

concentrations of refrigerant from the conditioned

· Blower slides out of cabinet for servicing

space
· Multi-color LED for system status and as an aid in troubleshooting

5 CABINET
· Constructed of heavy-gauge galvanized steel

· Flashing LED codes for system status (Green/Blue)

· Completely insulated with thick fiberglass insulation

and diagnosing Sensor errors (Red)

· Pre-painted steel with mildly textured enamel finish with

· Alarm relay can trigger an external alarm if a leak is

primer coat on unpainted side of all panels

detected

· Shipped in one piece but may be disassembled into

· Zone relay opens all zone dampers (if part of a zoning system) if a leak is detected

two separate sections for ease of installation in tight applications

· Power is disabled to non-communicating thermostats to prevent demand if a leak is detected

· Thick rubber gasket between sections of the two-piece cabinet provides an air tight seal

· On system start-up blower will run for five minutes and any thermostat demands are disabled

· No exposed screw heads on sides for tight installations without damage to walls or woodwork

· Dimensions (H x W x D): 7-7/16 x 7-7/16 x 2-1/2 (189

· Removable panels provide complete service access

x 189 x 127 mm)

· Electrical inlets provided in sides and top of cabinet

· See R-454B Refrigerant Conversion Table on page 8?
NOTE - Refer to the Installation Instructions for additional information.

Low Leakage Cabinet
· All models have less than 2% air leakage and meet ANSI/ASHRAE Standard 193-2010 "Method of Test for Determining the Air Tightness of HVAC Equipment"

R-454B Check and Expansion Valve · For use with R-454B systems
· Wide range valve with Chatleff style fitting
· Replaces factory installed TXV, internal to cabinet
· See Optional R-454B TXV Substitution table on Page 8

Upflow/Horizontal Capability (Optional Downflow) · Shipped for upflow and horizontal right-hand discharge
· May be field converted to horizontal left-hand air discharge by repositioning horizontal drain pan
· Optional downflow kit required for field conversion

7AH2AE | 1.5 to 5 ton Air Handlers | Page 4

F E AT U R E S
CABINET (Continued)
Dual Position Anti-Microbial Drain Pans · Drain pans designed for upflow, downflow or horizontal
applications
· Deep, corrosion resistant plastic drain pans have dual pipe drains
· Anti-Microbial additive resists growth of mold and mildew on drain pan which improves indoor air quality and reduces drain line blockage See dimension drawings
Optional Accessories
Downflow Combustible Flooring Floor Base · Base is required for models with electric heat installed
in downflow position on combustible floors
Downflow Conversion Kit · Required for field conversion to downflow position
· Kit consists of drip shields and 2 brackets for repositioning coil and drain pan
Horizontal Support Frame Kit · Provides support of unit in horizontal applications
· Consists of (2) 1 x 1-1/2 x 32-5/8 in. and (2) 1 x 3 x 53-7/8 in. painted heavy gauge cold rolled steel support channels with assembly and suspending holes
· Bolts and nuts furnished for field assembly
· Suspending rods must be field provided
Side Return Unit Stand (Upflow Only) · Raises unit 16 in. above floor for side return air duct
connection
· Eliminates need for wooden platform construction
· All aluminum construction
· Two adjustable frames fit -018/024 thru -060 models
Wall Hanging Bracket Kit (Upflow Only) · Allows unit to be hung on wall at any height
· Consists of heavy-gauge steel support brackets (one for air handler, one for wall mount)
· Screws furnished for fastening one bracket to unit
· Bolts for fastening one bracket to wall are field provided
High Performance Economizer (Commercial Applications Only) · Designed for applications requiring outdoor air to be
utilized in a commercial HVAC system. Allows the entry of fresh outdoor air for free cooling, reducing the requirement for mechanical cooling
· Heavy gauge galvanized steel cabinet lined with thick fiberglass insulation
· Mixed air sensor, outdoor air sensor and 24VAC transformer furnished
· Approved for California Title 24 building standards
· ASHRAE 90.1-2010 compliant
· See separate Product Specifications document for additional information and available control and sensor options

CONTROLS Transformer and Blower Cooling Relay · 24 volt transformer with in-line fuse · Blower cooling relay · Factory installed in the unit control box · Terminal strip furnished
OPTIONAL ELECTRIC HEAT
7AH2AE | 1.5 to 5 ton Air Handlers | Page 5

F E AT U R E S

6 · ETL listed
· Field install internal to unit cabinet
· Available in several voltages and kW sizes. See Electric Heat tables
· Helix wound nichrome heating elements exposed directly in air stream resulting in instant heat transfer, low element temperatures and long service life
· Each element equipped with accurately located limit control with fixed temperature off setting and automatic reset

Single-Point Power Source Control Box · Control Box may be used with optional electric heat
when single power supply is connected to multi-circuit electric heat
· Field installs external to the unit cabinet on either side or top
· Constructed of heavy gauge steel, baked enamel finish, pre-punched mounting holes, electrical inlet knockouts, and terminal strip
· Removable cover provides easy access

· Supplemental thermal cutoff limit control, provides positive protection in case of excessive temperatures
· Thermal sequencer relay brings elements on and off line, in sequence and equal increments, with time delay between each
· Initiates and terminates blower operation

· Dimensions (H x W x D) - 7 x 7 x 4 in.
7 Filter
· Disposable 1 inch filter is furnished · Filter rack furnished in cabinet for easy filter installation · See Specifications tables for sizes

· Heating control relay(s) furnished as standard

· Control box and access cover constructed of heavy gauge galvanized steel

· Factory assembled with controls installed and wired

· Electric heat low voltage controls plug-in to air handler

Circuit Breaker (CB) Models · All "CB" model heaters are equipped with circuit
breakers for overload and short circuit protection
· Factory wired and mounted on electric heat unit
· Current sensitive and temperature actuated
· Manual reset
· Circuit breakers qualify as disconnect means at unit in many areas, eliminate the need for field provided disconnect
· Consult local electrical code in your area.
NOTE - 460V-3 phase air handlers can be used in 575V applications. 575V electric heaters are shipped with a 575V to 460V step-down transformer.

Optional Accessories

Electric Heat Circuit Breaker Cover Kit · Flexible plastic cover protects circuit breaker
· Recommended in areas with high humidity or unconditioned areas to prevent nuisance tripping

7AH2AE | 1.5 to 5 ton Air Handlers | Page 6

S P E C I F I C AT I O N S

Size

Nominal Tonnage

Refrigerant Type

Connections

Liquid line (OD) sweat - in.

Suction line (OD) sweat - in.

Condensate drain (FPT) - in.

Indoor Coil

Net face area - ft.2 Tube diameter - in.

Rows

Fins - in.

Blower

HP

Wheel nominal diameter x width - in.

Air volume range - cfm

1 Filters

Size - in.

Shipping Data - lbs.

ELECTRICAL DATA

Line voltage data (Volts-Phase-Hz)

2 Maximum overcurrent protection (MOCP) amps (unit) Minimum circuit ampacity (MCA) - 208/230V (unit) Blower Motor Full Load Amps - 208/230V Minimum circuit ampacity (MCA) - 460V (unit) Blower Motor Full Load Amps - 460V

018 1.5 R-410A 3/8 3/4 (2) 3/4 4.44 3/8 3 14 1/2 10 x 8 262 - 959 20 x 20 x 1 137
208/230-1-60 - - 15 5 4.1 - - - - -

024 2
R-410A 3/8 3/4
(2) 3/4 4.44 3/8
3 14 1/2 10 x 8 365 - 1095 20 x 20 x 1 137
208/230-1-60 - - 15 5 4.1 - - - - -

030 2.5 R-410A 3/8 3/4 (2) 3/4 5.0 3/8 3 14 1/2 11 x 8 365 - 1278 20 x 20 x 1 150
208/230-1-60 - - 15 5 4.1 - - - - -

036 3
R-410A 3/8 3/4
(2) 3/4 5.0 3/8 3 14 1/2
11 x 8 606 - 1498 20 x 20 x 1
150
208/230-1-60 ³ 460V-1ph 15 5 4.1 2.6 2.1

S P E C I F I C AT I O N S

Size

042

048

060

Nominal Tonnage

3.5

4

5

Refrigerant Type

R-410A

R-410A

R-410A

Connections

Liquid line (OD) sweat - in.

3/8

3/8

3/8

Suction line (OD) sweat - in.

7/8

7/8

7/8

Condensate drain (FPT) - in.

(2) 3/4

(2) 3/4

(2) 3/4

Indoor Coil

Net face area - ft.2

7.22

7.22

8.33

Tube diameter - in.

3/8

3/8

3/8

Rows

3

3

3

Fins - in.

14

14

14

Blower

HP

1

1

1

Wheel nominal diameter x width - in.

12 x 9

12 x 9

12 x 9

Air volume range - cfm

815 - 1723

867 - 1903

946 - 2268

1 Filters

Size - in.

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

Shipping Data - lbs.

186

186

199

ELECTRICAL DATA

Line voltage data (Volts-Phase-Hz)

208/230-1-60

208/230-1-60

208/230-1-60

- - -

³ 460V-1ph

³ 460V-1ph

2 Maximum overcurrent protection (MOCP) amps (unit)

15

15

15

Minimum circuit ampacity (MCA) - 208/230V (unit)

10

10

10

Blower Motor Full Load Amps - 208/230V

7.6

7.6

7.6

Minimum circuit ampacity (MCA) - 460V (unit)

- - -

5

5

Blower Motor Full Load Amps - 460V

- - -

4

4

1 Disposable filter. 2 HACR type circuit breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 3 Blower motor is 460V - 1 phase. Optional electric heat is 460V - 3 phase.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 7

OPTIONAL ACCESSORIES - ORDER SEPARATELY

Description

Order Number

Downflow Combustible Flooring Base

44k15

Electric Heat

See Electric Heat Data Tables on Page 12

Electric Heat Circuit Breaker Cover Kit

82W01

Horizontal Support Frame Kit

56J18

Side Return Unit Stand (Upflow Only)

45K32

Single-Point Power Source Control Box (for Electric Heat)

21H39

Wall Hanging Bracket Kit (Upflow Only)

45K30

High Performance Economizer (Commercial Only)

10U53

R-454B REFRIGERANT CONVERSION - ORDER SEPARATELY

Description

Order No.

Refrigerant Detection System (RDS) Coil Sensor Kit

27J27

Refrigerant Detection System (RDS) Blower Control Board

Any Communicating Air Handler or any Non-Communicating 24V Air Handler (Universal)

27A03

Any Non-Communicating 24V Air Handler 27A02

NOTE - Communicating Blower Control Board and Sensor can be used universally with communicating air handler or any non-communicating 24 volt air handler. Non-Communicating Blower Control Board and Sensor can be used with any non-communicating 24 volt air handler.
NOTE - Order R-454B Expansion Valve separately.

OPTIONAL R-454B TXV SUBSTITUTION

Size

Order Number

018

26Z70

024

26Z70

030

26Z70

036

26Z70

042

26Z71

048

26Z71

060

26Z72

INSTALLATION CLEARANCES WITH ELECTRIC HEAT

5 to 20kW Electric Heat

25kW Electric Heat

Cabinet

0 inch (0 mm)

Cabinet

To Plenum

0 inch (0 mm)

To Plenum

To Outlet Duct

0 inch (0 mm)

To Outlet Duct within 3 feet (914 mm)

Floor

0 inch (0 mm)

Floor

Service / Maintenance

See Note #2

Service / Maintenance

1 Units installed on combustible floors in the downflow position with electric heat DO require a downflow combustible flooring base. 2 Front service access - 24 inches (610 mm) minimum. NOTE - If cabinet depth is more than 24 inches (610 mm), allow a minimum of the cabinet depth plus 2 inches (51 mm).

0 inch (0 mm) 1 inch (0 mm) 1 inch (0 mm) See Note #1 See Note #2

7AH2AE | 1.5 to 5 ton Air Handlers | Page 8

BLOWER DATA

7AH2E-018 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

589

55

713

80

805

101

805

101

0.20

520

61

666

88

760

109

760

109

0.30

452

67

601

96

710

118

710

118

0.40

407

73

548

101

647

126

647

126

0.50

344

81

502

107

598

132

598

132

0.60

293

84

456

114

561

138

561

138

0.70

- - -

- - -

418

122

522

143

522

143

0.80

- - -

- - -

362

128

479

150

479

150

0.90

- - -

- - -

315

132

435

162

435

162

1.00

- - -

- - -

- - -

- - -

389

167

389

167

1.10

- - -

- - -

- - -

- - -

341

173

341

173

1.20

- - -

- - -

- - -

- - -

- - -

- - -

- - -

- - -

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

Tap 5

cfm

Watts

963

155

928

163

889

173

851

181

803

190

748

199

714

207

676

213

640

220

602

228

576

234

540

243

7AH2E-024 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

665

68

804

101

933

143

933

143

0.20

613

74

762

106

889

151

889

151

0.30

556

81

718

114

856

158

856

158

0.40

481

87

667

122

822

165

822

165

0.50

425

93

614

129

772

175

772

175

0.60

368

97

527

138

733

182

733

182

0.70

336

101

487

143

683

193

683

193

0.80

293

105

455

148

597

202

597

202

0.90

239

108

414

153

555

208

555

208

1.00

- - -

- - -

367

158

519

212

519

212

1.10

- - -

- - -

312

162

485

215

485

215

1.20

- - -

- - -

291

163

468

219

468

219

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

Tap 5

cfm

Watts

1056

197

1019

206

988

214

953

222

922

229

895

238

846

249

799

258

725

268

656

276

592

267

486

240

7AH2E-030 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

775

77

1074

152

1158

182

1158

182

0.20

727

84

1023

163

1115

193

1115

193

0.30

669

91

990

170

1081

200

1081

200

0.40

590

100

948

180

1040

211

1040

211

0.50

522

106

913

186

1007

219

1007

219

0.60

463

114

870

196

967

227

967

227

0.70

417

121

812

206

930

236

930

236

0.80

375

127

735

219

871

250

871

250

0.90

339

130

676

231

791

264

791

264

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

Tap 5

cfm

Watts

1256

215

1215

226

1169

237

1135

246

1100

255

1065

263

1031

272

993

281

965

290

7AH2AE | 1.5 to 5 ton Air Handlers | Page 9

BLOWER DATA

7AH2E-036 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

973

115

1239

210

1301

243

1301

243

0.20

925

123

1194

221

1264

253

1264

253

0.30

876

131

1156

230

1229

263

1229

263

0.40

841

138

1118

240

1189

275

1189

275

0.50

762

150

1082

248

1158

284

1158

284

0.60

694

161

1049

257

1127

293

1127

293

0.70

644

168

1001

270

1094

303

1094

303

0.80

583

178

978

279

1032

321

1032

321

0.90

552

184

868

299

958

339

958

339

1.00

497

193

828

307

913

350

913

350

1.10

455

201

783

318

877

357

877

357

1.20

418

207

745

327

838

367

838

367

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

7AH2E-042 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

1185

150

1330

202

1534

279

1471

282

0.20

1131

161

1278

214

1487

293

1437

292

0.30

1077

171

1236

224

1447

304

1395

305

0.40

1029

181

1191

235

1406

317

1353

315

0.50

989

188

1152

244

1367

327

1310

331

0.60

922

201

1107

255

1319

342

1277

341

0.70

872

210

1061

265

1286

352

1240

352

0.80

833

217

1013

276

1248

363

1200

365

0.90

774

225

970

285

1199

377

1162

376

1.00

742

233

937

293

1160

388

1085

393

1.10

651

250

893

302

1121

398

1072

400

1.20

606

259

816

315

1077

410

1038

410

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

7AH2E-048 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

1202

172

1569

355

1755

470

1753

472

0.20

1147

192

1526

376

1713

486

1728

495

0.30

1121

191

1498

372

1701

497

1675

497

0.40

1066

201

1452

383

1675

529

1669

511

0.50

1031

220

1430

411

1636

524

1639

536

0.60

936

227

1400

404

1602

547

1594

548

0.70

865

237

1358

421

1582

562

1584

541

0.80

827

251

1328

441

1551

566

1545

569

0.90

777

253

1292

442

1524

572

1513

581

1.00

718

278

1258

453

1487

580

1482

588

1.10

692

272

1152

498

1451

613

1452

599

1.20

666

293

1115

507

1429

624

1412

627

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 10

Tap 5

cfm

Watts

1447

320

1411

331

1379

341

1336

354

1306

364

1274

375

1241

386

1215

394

1169

412

1112

430

1059

445

1011

458

Tap 5

cfm

Watts

1697

405

1659

419

1620

434

1590

445

1552

459

1521

471

1483

487

1453

497

1415

511

1384

525

1302

544

1277

553

Tap 5

cfm

Watts

1967

637

1942

647

1916

657

1879

681

1845

704

1811

713

1777

730

1767

731

1732

758

1703

777

1681

788

1639

783

BLOWER DATA

7AH2E-060 BLOWER PERFORMANCE

External Static
Pressure in. w.g.

Tap 1

cfm

Watts

Tap 2

Air Volume and Motor Watts Tap 3

Tap 4

cfm

Watts

cfm

Watts

cfm

Watts

0.10

1354

222

1768

454

1954

616

1870

550

0.20

1307

240

1742

478

1929

627

1845

556

0.30

1267

246

1706

479

1898

643

1817

581

0.40

1222

263

1677

492

1861

675

1781

609

0.50

1177

273

1644

511

1837

693

1759

616

0.60

1150

289

1608

526

1814

703

1719

635

0.70

1044

308

1577

555

1786

687

1671

661

0.80

994

311

1537

577

1773

710

1645

680

0.90

938

317

1516

561

1712

736

1639

666

1.00

877

330

1475

590

1696

753

1613

687

1.10

846

346

1418

619

1677

755

1567

713

1.20

816

345

1392

626

1648

765

1526

719

NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place. Electric heaters have no appreciable air resistance.

Tap 5

cfm

Watts

2148

808

2124

846

2097

843

2058

859

2034

888

2019

894

1975

912

1938

930

1927

938

1892

943

1836

945

1795

940

REPLACEMENT CIRCUIT BREAKERS

Voltage

Description

Catalog No.

25 amp, 2 pole

41K13

30 amp, 2 pole

17K70

35 amp, 2 pole

72K07

208/240V - 1 Phase 40 amp, 2 pole

49K14

45 amp, 2 pole

17K71

50 amp, 2 pole

41K12

60 amp, 2 pole

17K72

Voltage

Description

30 amp, 3 pole

35 amp, 3 pole

40 amp, 3 pole 208/240V - 3 Phase
45 amp, 3 pole

50 amp, 3 pole

60 amp, 3 pole

Catalog No. 64W47 41K14 41K16 18M86 41K15 41K17

7AH2AE | 1.5 to 5 ton Air Handlers | Page 11

ELECTRIC HEAT DATA

7AH2E-018 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Volts

Input

kW

1 Btuh

2 Blower Motor Full Load Amps

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

5 kW

ECB47-5 (27A31)

1

208

3.8 12,800

4.1

4 lbs.

Terminal Block ECB47-5CB (27A24)

220

4.2 14,300

4.1

35A Circuit breaker

230

4.6 15,700

4.1

28

4 30

31

35

31

35

240

5.0 17,100

4.1

31

35

6 kW

ECB47-6 (27A25)

1

208

4.5 15,400

4.1

4 lbs.

Terminal Block ECB47-6CB (27A26)

220

5.0 17,100

4.1

40A Circuit breaker

230

5.5 18,800

4.1

32

4 35

36

40

36

40

240

6.0 20,500

4.1

36

40

8 kW

ECB47-8 (27A21)

1

208

6.0 20,500

4.1

5 lbs.

Terminal Block ECB47-8CB (27A32)

220

6.7 22,900

4.1

50A Circuit breaker

230

7.3 25,100

4.1

41

4 45

47

50

47

50

240

8.0 27,300

4.1

47

50

9 kW

ECB47-9 (27A22)

2

208

6.8 23,100

4.1

5 lbs.

Terminal Block ECB47-9CB (27A27)

220

7.6 25,800

4.1

60A Circuit breaker

230

8.3 28,200

4.1

46

4 50

52

60

52

60

240

9.0 30,700

4.1

52

60

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 12

ELECTRIC HEAT DATA

7AH2E-024 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Volts

Input

kW

1 Btuh

2 Blower Motor Full Load Amps

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

5 kW

ECB47-5 (27A31)

1

208

3.8 12,800

4.1

4 lbs.

Terminal Block ECB47-5CB (27A24)

220

4.2 14,300

4.1

35A Circuit breaker

230

4.6 15,700

4.1

28

4 30

31

35

31

35

240

5.0 17,100

4.1

31

35

6 kW

ECB47-6 (27A25)

1

208

4.5 15,400

4.1

4 lbs.

Terminal Block ECB47-6CB (27A26)

220

5.0 17,100

4.1

40A Circuit breaker

230

5.5 18,800

4.1

32

4 35

36

40

36

40

240

6.0 20,500

4.1

36

40

8 kW

ECB47-8 (27A21)

1

208

6.0 20,500

4.1

5 lbs.

Terminal Block ECB47-8CB (27A32)

220

6.7 22,900

4.1

50A Circuit breaker

230

7.3 25,100

4.1

41

4 45

47

50

47

50

240

8.0 27,300

4.1

47

50

9 kW

ECB47-9CB (27A27)

2

208

6.8 23,100

4.1

5 lbs.

60A Circuit breaker

220

7.6 25,800

4.1

46

4 50

52

60

230

8.3 28,200

4.1

52

60

240

9.0 30,700

4.1

52

60

10 kW

ECB47-10 (27A22)

2

208

7.5 25,600

4.1

6 lbs.

Terminal Block

220

8.4 28,700

4.1

50

4 50

57

60

230

9.2 31,400

4.1

57

60

240

10.0 34,100

4.1

57

60

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 13

ELECTRIC HEAT DATA

7AH2E-030 | SINGLE PHASE

Electic Heat Model Number

No. of Stages Volts

Input

2 Blower Motor Full

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

kW

1 Btuh

Load Amps

Ckt 1 Ckt 2 Ckt 1 Ckt 2

Single Point Power Source 3 Minimum 5 Maximum Circuit Overcurrent Ampacity Protection

5 kW

ECB47-5 (27A31) 1 208 3.8 12,800 4.1

28 - - - 4 30 - - -

- - -

- - -

4 lbs.

Terminal Block

220 4.2 14,300 4.1

31 - - - 35 - - -

- - -

- - -

ECB47-5CB (27A24) 35A Circuit breaker

230 4.6 15,700 4.1

31 - - - 35 - - -

- - -

- - -

240 5.0 17,100 4.1

31 - - - 35 - - -

- - -

- - -

6 kW

ECB47-6 (27A25) 1 208 4.5 15,400 4.1

32 - - - 4 35 - - -

- - -

- - -

4 lbs.

Terminal Block

220 5.0 17,100 4.1

36 - - - 40 - - -

- - -

- - -

ECB47-6CB (27A26) 40A Circuit breaker

230 5.5 18,800 4.1

36 - - - 40 - - -

- - -

- - -

240 6.0 20,500 4.1

36 - - - 40 - - -

- - -

- - -

8 kW

ECB47-8 (27A21) 1 208 6.0 20,500 4.1

41 - - - 4 45 - - -

- - -

- - -

5 lbs.

Terminal Block

220 6.7 22,900 4.1

47 - - - 50 - - -

- - -

- - -

ECB47-8CB (27A32) 50A Circuit breaker

230 7.3 25,100 4.1

47 - - - 50 - - -

- - -

- - -

240 8.0 27,300 4.1

47 - - - 50 - - -

- - -

- - -

9 kW

ECB47-9 (27A22) 2 208 6.8 23,100 4.1

46 - - - 4 50 - - -

- - -

- - -

5 lbs.

Terminal Block

220 7.6 25,800 4.1

52 - - - 60 - - -

- - -

- - -

ECB47-9CB (27A27) 60A Circuit breaker

230 8.3 28,200 4.1

52 - - - 60 - - -

- - -

- - -

240 9.0 30,700 4.1

52 - - - 60 - - -

- - -

- - -

12.5 kW ECB47-12.5CB (27A28) 2 208 9.4 32,000 4.1

24 38 4 25 4 40

62

70

10 lbs.

(1) 30A Circuit breaker

220 10.5 35,800 4.1

27 43 30 45

70

70

& (1) 45A Circuit breaker

230 11.5 39,200 4.1

27 43 30 45

70

70

240 12.5 42,600 4.1

27 43 30 45

70

70

15 kW

ECB47-15CB (27A23) 2 208 11.3 38,400 4.1

28 45 4 30 4 45

73

80

12 lbs.

(1) 35A Circuit breaker

220 12.6 43,000 4.1

31 52 35 60

83

90

& (1) 60A Circuit Breaker

230 13.8 47,000 4.1

31 52 35 60

83

90

240 15.0 51,200 4.1

31 52 35 60

83

90

THREE PHASE

8 kW 5 lbs.

ECB47-8 (27A44) 1 208 6.0 20,500 4.1

26 - - - 30 - - -

- - -

- - -

Terminal Block

220 6.7 22,900 4.1

29 - - - 30 - - -

- - -

- - -

230 7.3 25,100 4.1

29 - - - 30 - - -

- - -

- - -

240 8.0 27,300 4.1

29 - - - 30 - - -

- - -

- - -

10 kW

ECB47-10 (27A35) 1 208 7.5 25,600 4.1

31 - - - 35 - - -

- - -

- - -

6 lbs.

Terminal Block

220 8.4 28,700 4.1

35 - - - 35 - - -

- - -

- - -

230 9.2 31,400 4.1

35 - - - 35 - - -

- - -

- - -

240 10.0 34,100 4.1

35 - - - 35 - - -

- - -

- - -

15 kW

ECB47-15CB (27A36) 1 208 11.3 38,400 4.1

44 - - - 45 - - -

- - -

- - -

12 lbs.

(1) 50A Circuit breaker

220 12.6 43,000 4.1

50 - - - 50 - - -

- - -

- - -

230 13.5 47,000 4.1

50 - - - 50 - - -

- - -

- - -

240 15.0 51,200 4.1

50 - - - 50 - - -

- - -

- - -

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 14

ELECTRIC HEAT DATA

7AH2E-036 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Volts

Input kW 1 Btuh

3 Minimum 2 Blower Circuit
Motor Ampacity Full Load Amps Ckt 1 Ckt 2

5 Maximum Overcurrent Protection Ckt 1 Ckt 2

Single Point Power Source 3 Minimum 5 Maximum Circuit Overcurrent Ampacity Protection

5 kW

ECB47-5 (27A31) 1 208 3.8 12,800 4.1

28 - - - 4 30 - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-5CB (27A24)

220 4.2 14,300 4.1

31 - - - 35 - - -

- - -

- - -

35A Circuit breaker

230 4.6 15,700 4.1

31 - - - 35 - - -

- - -

- - -

240 5.0 17,100 4.1

31 - - - 35 - - -

- - -

- - -

6 kW

ECB47-6 (27A25) 1 208 4.5 15,400 4.1

32 - - - 4 35 - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-6CB (27A26)

220 5.0 17,100 4.1

36 - - - 40 - - -

- - -

- - -

40A Circuit breaker

230 5.5 18,800 4.1

36 - - - 40 - - -

- - -

- - -

240 6.0 20,500 4.1

36 - - - 40 - - -

- - -

- - -

8 kW

ECB47-8 (27A21) 1 208 6.0 20,500 4.1

41 - - - 4 45 - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-8CB (27A32)

220 6.7 22,900 4.1

47 - - - 50 - - -

- - -

- - -

50A Circuit breaker

230 7.3 25,100 4.1

47 - - - 50 - - -

- - -

- - -

240 8.0 27,300 4.1

47 - - - 50 - - -

- - -

- - -

9 kW

ECB47-9 (27A22) 2 208 6.8 23,100 4.1

46 - - - 4 50 - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-9CB (27A27)

220 7.6 25,800 4.1

52 - - - 60 - - -

- - -

- - -

60A Circuit breaker

230 8.3 28,200 4.1

52 - - - 60 - - -

- - -

- - -

240 9.0 30,700 4.1

52 - - - 60 - - -

- - -

- - -

12.5

ECB47-12.5CB (27A28) 2 208 9.4 32,000 4.1

24 38 4 25 4 40

62

70

kW (1) 30A Circuit breaker and

10 lbs.

(1) 45A Circuit breaker

220 10.5 35,800 4.1

27 43 30 45

70

70

230 11.5 39,200 4.1

27 43 30 45

70

70

240 12.5 42,600 4.1

27 43 30 45

70

70

15 kW

ECB47-15CB (27A23) 2 208 11.3 38,400 4.1

28 45 4 30 4 45

73

80

12 lbs. (1) 35A Circuit breaker and (1) 60A Circuit Breaker

220 12.6 43,000 4.1

31 52 35 60

83

90

230 13.8 47,000 4.1

31 52 35 60

83

90

240 15.0 51,200 4.1

31 52 35 60

83

90

20 kW

ECB47-20CB (27A33) 2 208 15.0 51,200 4.1

46 50 4 50 4 50

96

100

19 lbs. (1) 60A Circuit breaker and (1) 60A Circuit Breaker

220 16.8 57,300 4.1

52 57 60 60

109

125

230 18.4 62,700 4.1

52 57 60 60

109

125

240 20.0 68,200 4.1

52 57 60 60

109

125

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 15

ELECTRIC HEAT DATA

7AH2E-036 | THREE PHASE

Electic Heat Model Number

No. of Stages

Volts

Input kW 1 Btuh

3 Minimum 5 Maximum 2 Blower Circuit Overcurrent
Motor Ampacity Protection Full Load Amps Ckt 1 Ckt 2 Ckt 1 Ckt 2

Single Point Power Source 3 Minimum 5 Maximum Circuit Overcurrent Ampacity Protection

8 kW

ECB47-8 (27A44) 1 208 6.0 20,500

4.1

26 - - - 30 - - -

- - -

- - -

5 lbs.

Terminal Block

220 6.7 22,900

4.1

29 - - - 30 - - -

- - -

- - -

230 7.3 25,100

4.1

29 - - - 30 - - -

- - -

- - -

240 8.0 27,300

4.1

29 - - - 30 - - -

- - -

- - -

10 kW ECB47-10 (27A35) 1 208 7.5 25,600

4.1

31 - - - 35 - - -

- - -

- - -

6 lbs.

Terminal Block

220 8.4 28,700

4.1

35 - - - 35 - - -

- - -

- - -

230 9.2 31,400

4.1

35 - - - 35 - - -

- - -

- - -

240 10.0 34,100

4.1

35 - - - 35 - - -

- - -

- - -

ECB47-10 (27A38) 1 440 8.4 28,700

2.1

16 - - - 20 - - -

- - -

- - -

(3) 20A Fuses

460 9.2 31,400

2.1

17 - - - 20 - - -

- - -

- - -

480 10.0 34,100

2.1

17 - - - 20 - - -

- - -

- - -

15 kW ECB47-15CB (27A36) 1 208 11.3 38,400

4.1

44 - - - 4 45 - - -

- - -

- - -

12 lbs. (1) 50A Circuit breaker

220 12.6 43,000

4.1

50 - - - 50 - - -

- - -

- - -

230 13.5 47,000

4.1

50 - - - 50 - - -

- - -

- - -

240 15.0 51,200

4.1

50 - - - 50 - - -

- - -

- - -

ECB47-15 (27A39) 1 440 12.6 43,000

2.1

23 - - - 25 - - -

- - -

- - -

(3) 25A Fuses

460 13.5 47,000

2.1

24 - - - 25 - - -

- - -

- - -

480 15.0 51,200

2.1

25 - - - 30 - - -

- - -

- - -

20 kW ECB47-20CB (27A37) 2 208 15.0 51,200

4.1

31 26 35 4 30

57

60

19 lbs. (2) 35A Circuit breaker

220 16.8 57,300

4.1

35 30 35 4 30

65

70

230 18.4 62,700

4.1

35 30 35 4 30

65

70

240 20.0 68,200

4.1

35 30 35 4 30

65

70

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 16

ELECTRIC HEAT DATA

7AH2E-042 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Input

2 Blower Motor Full Load

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

Single Point Power Source
3 Minimum 5 Maximum

Volts kW 1 Btuh Amps Ckt 1 Ckt 2 Ckt 3 Ckt 1 Ckt 2 Ckt 3 Circuit Overcurrent

Ampacity Protection

5 kW

ECB47-5 (27A31) 1 208 3.8 12,800 7.6 32 - - - - - - 35 - - - - - - - - -

- - -

4 lbs.

Terminal Block ECB47-5CB (27A24)

220 4.2 14,300 7.6 36 - - - - - - 4 40 - - - - - - - - -

- - -

35A Circuit breaker

230 4.6 15,700 7.6 36 - - - - - - 4 40 - - - - - - - - -

- - -

240 5.0 17,100 7.6 36 - - - - - - 4 40 - - - - - - - - -

- - -

6 kW

ECB47-6 (27A25) 1 208 4.5 15,400 7.6 37 - - - - - - 40 - - - - - - - - -

- - -

4 lbs.

Terminal Block ECB47-6CB (27A26)

220 5.0 17,100 7.6 41 - - - - - - 4 45 - - - - - - - - -

- - -

40A Circuit breaker

230 5.5 18,800 7.6 41 - - - - - - 4 45 - - - - - - - - -

- - -

240 6.0 20,500 7.6 41 - - - - - - 4 45 - - - - - - - - -

- - -

8 kW

ECB47-8 (27A21) 1 208 6.0 20,500 7.6 46 - - - - - - 50 - - - - - - - - -

- - -

5 lbs.

Terminal Block ECB47-8CB (27A32)

220 6.7 22,900 7.6 51 - - - - - - 4 60 - - - - - - - - -

- - -

50A Circuit breaker

230 7.3 25,100 7.6 51 - - - - - - 4 60 - - - - - - - - -

- - -

240 8.0 27,300 7.6 51 - - - - - - 4 60 - - - - - - - - -

- - -

9 kW

ECB47-9 (27A22) 2 208 6.8 23,100 7.6 50 - - - - - - 4 50 - - - - - - - - -

- - -

5 lbs.

Terminal Block ECB47-9CB (27A27)

220 7.6 25,800 7.6 56 - - - - - - 60 - - - - - - - - -

- - -

60A Circuit breaker

230 8.3 28,200 7.6 56 - - - - - - 60 - - - - - - - - -

- - -

240 9.0 30,700 7.6 56 - - - - - - 60 - - - - - - - - -

- - -

12.5 kW ECB47-12.5CB (27A28) 2 208 9.4 32,000 7.6 28 38 - - - 30 4 40 - - -

66

80

10 lbs.

(1) 30A Circuit breaker and

220 10.5 35,800 7.6 31 43 - - - 4 35 45 - - -

75

80

(1) 45A Circuit breaker

230 11.5 39,200 7.6 31 43 - - - 4 35 45 - - -

75

80

240 12.5 42,600 7.6 31 43 - - - 4 35 45 - - -

75

80

15 kW

ECB47-15CB (27A23) 2 208 11.3 38,400 7.6 32 45 - - - 35 4 45 - - -

77

80

12 lbs.

(1) 35A Circuit breaker and

220 12.6 43,000 7.6 36 52 - - - 4 40 60 - - -

88

90

(1) 60A Circuit breaker

230 13.5 47,000 7.6 36 52 - - - 4 40 60 - - -

88

90

240 15.0 51,200 7.6 36 52 - - - 4 40 60 - - -

88

90

20 kW

ECB47-20CB (27A33) 2 208 15.0 51,200 7.6 50 50 - - - 4 50 4 50 - - - 100

125

19 lbs.

(1) 60A Circuit breaker and

220 16.8 57,300 7.6 56 57 - - - 60 60 - - - 114

125

(1) 60A Circuit breaker

230 18.4 62,700 7.6 56 57 - - - 60 60 - - - 114

125

240 20.0 68,200 7.6 56 57 - - - 60 60 - - - 114

125

25 kW

ECB47-25CB (27A34) 3 208 18.8 64,100 7.6 47 38 38 4 50 4 40 4 40 123

125

19 lbs.

(1) 60A Circuit breaker and

220 21.0 71,700 7.6 53 43 43 60 45 45 140

150

(2) 45A Circuit breakers

230 23.0 78,300 7.6 53 43 43 60 45 45 140

150

240 25.0 85,300 7.6 53 43 43 60 45 45 140

150

1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 17

ELECTRIC HEAT DATA

7AH2E-042 | THREE PHASE

Electic Heat No. of Model Number Stages
Volts

Input kW 1 Btuh

2 Blower Motor Full

3 Minimum Circuit
Ampacity

Load Amps Ckt 1 Ckt 2

5 Maximum Overcurrent Protection
Ckt 1 Ckt 2

Single Point Power Source
3 Minimum 5 Maximum Circuit Overcurrent
Ampacity Protection

8 kW 5 lbs.

ECB47-8 (27A44) 1 208 6.0 20,500 7.6

30 - - - 30 - - -

- - -

- - -

Terminal block

220 6.7 22,900 7.6

33 - - - 35 - - -

- - -

- - -

230 7.3 25,100 7.6

33 - - - 35 - - -

- - -

- - -

240 8.0 27,300 7.6

33 - - - 35 - - -

- - -

- - -

10 kW

ECB47-10 (27A35) 1 208 7.5 25,600 7.6

36 - - - 40 - - -

- - -

- - -

6 lbs.

Terminal Block

220 8.4 28,700 7.6

40 - - - 40 - - -

- - -

- - -

230 9.2 31,400 7.6

40 - - - 40 - - -

- - -

- - -

240 10.0 34,100 7.6

40 - - - 40 - - -

- - -

- - -

15 kW

ECB47-15CB (27A36) 1 208 11.3 38,400 7.6

49 - - - 50 - - -

- - -

- - -

12 lbs.

50A Circuit breaker

220 12.6 43,000 7.6

55 - - - 4 60 - - -

- - -

- - -

230 13.5 47,000 7.6

55 - - - 4 60 - - -

- - -

- - -

240 15.0 51,200 7.6

55 - - - 4 60 - - -

- - -

- - -

20 kW

ECB47-20CB (27A37) 2 208 15.0 51,200 7.6

36 26 4 40 4 30

62

70

19 lbs.

(2) 35A Circuit breaker

220 16.8 57,300 7.6

40 30 4 40 4 30

70

70

230 18.4 62,700 7.6

40 30 4 40 4 30

70

70

240 20.0 68,200 7.6

40 30 4 40 4 30

70

70

25 kW

ECB47-25CB (27A45) 2 208 18.8 64,100 7.6

42 33 4 50 4 35

62

70

19 lbs.

(2) 45A Circuit breaker

220 21.0 71,700 7.6

47 38 4 50 4 40

85

90

230 23.0 78,300 7.6

47 38 4 50 4 40

85

90

240 25.0 85,300 7.6

47 38 4 50 4 40

85

90

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse. 6 Blower motor is rated at 460V.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 18

ELECTRIC HEAT DATA

7AH2E-048 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Input

2 Blower Motor Full Load

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

Single Point Power Source
³ Minimum  Maximum

Volts kW 1 Btuh Amps Ckt 1 Ckt 2 Ckt 3 Ckt 1 Ckt 2 Ckt 3 Circuit Overcurrent

Ampacity Protection

5 kW

ECB47-5 (27A31) 1 208 3.8 12,800 7.6 32 - - - - - - 35 - - - - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-5CB (27A24)
35A Circuit breaker

220 4.2 14,300 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

230 4.6 15,700 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

240 5.0 17,100 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

6 kW

ECB47-6 (27A25) 1 208 4.5 15,400 7.6 37 - - - - - - 40 - - - - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-6CB (27A26)
40A Circuit breaker

220 5.0 17,100 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

230 5.5 18,800 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

240 6.0 20,500 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

8 kW

ECB47-8 (27A21) 1 208 6.0 20,500 7.6 46 - - - - - - 50 - - - - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-8CB (27A32)
50A Circuit breaker

220 6.7 22,900 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

230 7.3 25,100 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

240 8.0 27,300 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

9 kW

ECB47-9 (27A22) 2 208 6.8 23,100 7.6 50 - - - - - - 4 50 - - - - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-9CB (27A27)
60A Circuit breaker

220 7.6 25,800 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

230 8.3 28,200 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

240 9.0 30,700 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

12.5 ECB47-12.5CB (27A28) 2 208 9.4 32,000 7.6 28 38 - - - 30 4 40 - - -

66

70

kW

(1) 30A Circuit breaker

10 lbs. & (1) 45A Circuit breaker

220 10.5 35,800 7.6 31 43 - - - 4 35 45 - - -

75

80

230 11.5 39,200 7.6 31 43 - - - 4 35 45 - - -

75

80

240 12.5 42,600 7.6 31 43 - - - 4 35 45 - - -

75

80

15 kW ECB47-15CB (27A23) 2 208 11.3 38,400 7.6 32 45 - - - 35 4 45 - - -

77

80

12 lbs. (1) 35A Circuit breaker

& (1) 60A Circuit breaker

220 12.6 43,000 7.6 36 52 - - - 4 40 60 - - -

88

90

230 13.5 47,000 7.6 36 52 - - - 4 40 60 - - -

88

90

240 15.0 51,200 7.6 36 52 - - - 4 40 60 - - -

88

90

20 kW ECB47-20CB (27A33) 2 208 15.0 51,200 7.6 50 50 - - - 4 50 4 50 - - -

100

125

19 lbs. (1) 60A Circuit breaker & (1) 60A Circuit breaker

220 16.8 57,300 7.6 56 57 - - - 60 60 - - -

114

125

230 18.4 62,700 7.6 56 57 - - - 60 60 - - -

114

125

240 20.0 68,200 7.6 56 57 - - - 60 60 - - -

114

125

25 kW ECB47-25CB (27A34) 3 208 18.8 64,100 7.6 47 38 38 4 50 4 40 4 40

123

125

19 lbs.

(1) 60A Circuit breaker & (2) 45A Circuit breakers

220 21.0 71,700 7.6 53 43 43 60 45 45

140

150

230 23.0 78,300 7.6 53 43 43 60 45 45

140

150

240 25.0 85,300 7.6 53 43 43 60 45 45

140

150

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 19

ELECTRIC HEAT DATA

7AH2E-048 | THREE PHASE

Electic Heat No. of Model Number Stages
Volts

Input kW 1 Btuh

2 Blower Motor Full

3 Minimum Circuit
Ampacity

Load Amps Ckt 1 Ckt 2

5 Maximum Overcurrent Protection
Ckt 1 Ckt 2

Single Point Power Source
3 Minimum 5 Maximum Circuit Overcurrent
Ampacity Protection

8 kW 5 lbs.

ECB47-8 (27A44) 1 208 6.0 20,500 7.6

30 - - - 30 - - -

- - -

- - -

Terminal block

220 6.7 22,900 7.6

33 - - - 35 - - -

- - -

- - -

230 7.3 25,100 7.6

33 - - - 35 - - -

- - -

- - -

240 8.0 27,300 7.6

33 - - - 35 - - -

- - -

- - -

10 kW

ECB47-10 (27A35) 1 208 7.5 25,600 7.6

36 - - - 40 - - -

- - -

- - -

6 lbs.

Terminal Block

220 8.4 28,700 7.6

40 - - - 40 - - -

- - -

- - -

230 9.2 31,400 7.6

40 - - - 40 - - -

- - -

- - -

240 10.0 34,100 7.6

40 - - - 40 - - -

- - -

- - -

ECB47-10 (27A38) 1 440 8.4 28,700 4.0

18 - - - 20 - - -

- - -

- - -

(3) 20A Fuses

460 9.2 31,400 4.0

19 - - - 20 - - -

- - -

- - -

480 10.0 34,100 4.0

20 - - - 25 - - -

- - -

- - -

15 kW

ECB47-15CB (27A36) 1 208 11.3 38,400 7.6

49 - - - 50 - - -

- - -

- - -

12 lbs.

50A Circuit breaker

220 12.6 43,000 7.6

55 - - - 4 60 - - -

- - -

- - -

230 13.5 47,000 7.6

55 - - - 4 60 - - -

- - -

- - -

240 15.0 51,200 7.6

55 - - - 4 60 - - -

- - -

- - -

ECB47-15 (27A39) 1 440 12.6 43,000 4.0

25 - - - 30 - - -

- - -

- - -

(3) 25A Fuses

460 13.5 47,000 4.0

26 - - - 30 - - -

- - -

- - -

480 15.0 51,200 4.0

27 - - - 30 - - -

- - -

- - -

20 kW

ECB47-20CB (27A37) 2 208 15.0 51,200 7.6

36 26 4 40 4 30

62

70

19 lbs.

(2) 35A Circuit breaker

220 16.8 57,300 7.6

40 30 4 40 4 30

70

70

230 18.4 62,700 7.6

40 30 4 40 4 30

70

70

240 20.0 68,200 7.6

40 30 4 40 4 30

70

70

ECB47-20 (27A40) 1 440 16.8 57,300 4.0

33 - - - 35 - - -

- - -

- - -

(3) 35A Fuses

460 18.4 62,700 4.0

34 - - - 35 - - -

- - -

- - -

480 20.0 68,200 4.0

35 - - - 40 - - -

- - -

- - -

6 ECB47-20 (27A43) 1 550 16.8 57,300 4.0

27 - - - 30 - - -

- - -

- - -

(3) 25A Fuses

575 18.4 62,700 4.0

28 - - - 30 - - -

- - -

- - -

600 20.0 68,200 4.0

29 - - - 30 - - -

- - -

- - -

25 kW

ECB47-25CB (27A45) 2 208 18.8 64,100 7.6

42 33 4 50 4 35

75

80

19 lbs.

(2) 45A Circuit breaker

220 21.0 71,700 7.6

47 38 4 50 4 40

85

90

230 23.0 78,300 7.6

47 38 4 50 4 40

85

90

240 25.0 85,300 7.6

47 38 4 50 4 40

85

90

ECB47-25 (27A42) 1 440 21.0 71,700 4.0

39 - - - 40 - - -

- - -

- - -

(3) 40A Fuses

460 23.0 78,300 4.0

41 - - - 45 - - -

- - -

- - -

480 25.0 85,300 4.0

42 - - - 45 - - -

- - -

- - -

6 ECB47-25 (27A41) 1 550 21.0 71,700 4.0

32 - - - 35 - - -

- - -

- - -

(3) 35A Fuses

575 23.0 78,300 4.0

34 - - - 35 - - -

- - -

- - -

600 25.0 85,300 4.0

35 - - - 40 - - -

- - -

- - -

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse. 6 Blower motor is rated at 460V.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 20

ELECTRIC HEAT DATA

7AH2E-060 | SINGLE PHASE

Electic Heat Model Number

No. of Stages

Input

2 Blower Motor Full Load

3 Minimum Circuit
Ampacity

5 Maximum Overcurrent Protection

Single Point Power Source
3 Minimum 5 Maximum

Volts kW 1 Btuh

Amps

Ckt 1 Ckt 2 Ckt 3 Ckt 1 Ckt 2 Ckt 3 Circuit Overcurrent Ampacity Protection

5 kW

ECB47-5 (27A31) 1 208 3.8 12,800 7.6 32 - - - - - - 35 - - - - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-5CB (27A24)
35A Circuit breaker

220 4.2 14,300 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

230 4.6 15,700 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

240 5.0 17,100 7.6 36 - - - - - - 4 40 - - - - - -

- - -

- - -

6 kW

ECB47-6 (27A25) 1 208 4.5 15,400 7.6 37 - - - - - - 40 - - - - - -

- - -

- - -

4 lbs.

Terminal Block ECB47-6CB (27A26)
40A Circuit breaker

220 5.0 17,100 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

230 5.5 18,800 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

240 6.0 20,500 7.6 41 - - - - - - 4 45 - - - - - -

- - -

- - -

8 kW

ECB47-8 (27A21) 1 208 6.0 20,500 7.6 46 - - - - - - 50 - - - - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-8CB (27A32)
50A Circuit breaker

220 6.7 22,900 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

230 7.3 25,100 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

240 8.0 27,300 7.6 51 - - - - - - 4 60 - - - - - -

- - -

- - -

9 kW

ECB47-9 (27A22) 2 208 6.8 23,100 7.6 50 - - - - - - 4 50 - - - - - -

- - -

- - -

5 lbs.

Terminal Block ECB47-9CB (27A27)
60A Circuit breaker

220 7.6 25,800 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

230 8.3 28,200 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

240 9.0 30,700 7.6 56 - - - - - - 60 - - - - - -

- - -

- - -

12.5 ECB47-12.5CB (27A28) 2 208 9.4 32,000 7.6 28 38 - - - 30 4 40 - - -

66

70

kW (1) 30A Circuit breaker

220 10.5 35,800 7.6 31 43 - - - 4 35 45 - - -

75

80

10 lbs. & (1) 45A Circuit breaker

230 11.5 39,200 7.6 31 43 - - - 4 35 45 - - -

75

80

240 12.5 42,600 7.6 31 43 - - - 4 35 45 - - -

75

80

15 kW ECB47-15CB (27A23) 2 208 11.3 38,400 7.6 32 45 - - - 35 4 45 - - -

77

80

12 lbs. (1) 35A Circuit breaker

220 12.6 43,000 7.6 36 52 - - - 4 40 60 - - -

88

90

& (1) 60A Circuit breaker

230 13.5 47,000 7.6 36 52 - - - 4 40 60 - - -

88

90

240 15.0 51,200 7.6 36 52 - - - 4 40 60 - - -

88

90

20 kW ECB47-20CB (27A33) 2 208 15.0 51,200 7.6 50 50 - - - 4 50 4 50 - - -

100

125

19 lbs. (1) 60A Circuit breaker & (1) 60A Circuit breaker

220 16.8 57,300 7.6 56 57 - - - 60 60 - - -

114

125

230 18.4 62,700 7.6 56 57 - - - 60 60 - - -

114

125

240 20.0 68,200 7.6 56 57 - - - 60 60 - - -

114

125

25 kW ECB47-25CB (27A34) 3 208 18.8 64,100 7.6 47 38 38 4 50 4 40 4 40

123

125

19 lbs.

(1) 60A Circuit breaker & (2) 45A Circuit breakers

220 21.0 71,700 7.6 53 43 43 60 45 45

140

150

230 23.0 78,300 7.6 53 43 43 60 45 45

140

150

240 25.0 85,300 7.6 53 43 43 60 45 45

140

150

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 21

ELECTRIC HEAT DATA

7AH2E-060 | THREE PHASE

Electic Heat No. of Model Number Stages
Volts

Input kW 1 Btuh

2 Blower Motor Full

3 Minimum Circuit
Ampacity

Load Amps Ckt 1 Ckt 2

5 Maximum Overcurrent Protection
Ckt 1 Ckt 2

Single Point Power Source
3 Minimum 5 Maximum Circuit Overcurrent
Ampacity Protection

8 kW 5 lbs.

ECB47-8 (27A44) 1 208 6.0 20,500 7.6

30 - - - 30 - - -

- - -

- - -

Terminal block

220 6.7 22,900 7.6

33 - - - 35 - - -

- - -

- - -

230 7.3 25,100 7.6

33 - - - 35 - - -

- - -

- - -

240 8.0 27,300 7.6

33 - - - 35 - - -

- - -

- - -

10 kW

ECB47-10 (27A35) 1 208 7.5 25,600 7.6

36 - - - 40 - - -

- - -

- - -

6 lbs.

Terminal Block

220 8.4 28,700 7.6

40 - - - 40 - - -

- - -

- - -

230 9.2 31,400 7.6

40 - - - 40 - - -

- - -

- - -

240 10.0 34,100 7.6

40 - - - 40 - - -

- - -

- - -

ECB47-10 (27A38) 1 440 8.4 28,700 4.0

18 - - - 20 - - -

- - -

- - -

(3) 20A Fuses

460 9.2 31,400 4.0

19 - - - 20 - - -

- - -

- - -

480 10.0 34,100 4.0

20 - - - 25 - - -

- - -

- - -

15 kW

ECB47-15CB (27A36) 1 208 11.3 38,400 7.6

49 - - - 50 - - -

- - -

- - -

12 lbs.

50A Circuit breaker

220 12.6 43,000 7.6

55 - - - 4 60 - - -

- - -

- - -

230 13.5 47,000 7.6

55 - - - 4 60 - - -

- - -

- - -

240 15.0 51,200 7.6

55 - - - 4 60 - - -

- - -

- - -

ECB47-15 (27A39) 1 440 12.6 43,000 4.0

25 - - - 30 - - -

- - -

- - -

(3) 25A Fuses

460 13.5 47,000 4.0

26 - - - 30 - - -

- - -

- - -

480 15.0 51,200 4.0

27 - - - 30 - - -

- - -

- - -

20 kW

ECB47-20CB (27A37) 2 208 15.0 51,200 7.6

36 26 4 40 4 30

62

70

19 lbs.

(2) 35A Circuit breaker

220 16.8 57,300 7.6

40 30 4 40 4 30

70

70

230 18.4 62,700 7.6

40 30 4 40 4 30

70

70

240 20.0 68,200 7.6

40 30 4 40 4 30

70

70

ECB47-20 (27A40) 1 440 16.8 57,300 4.0

33 - - - 35 - - -

- - -

- - -

(3) 35A Fuses

460 18.4 62,700 4.0

34 - - - 35 - - -

- - -

- - -

480 20.0 68,200 4.0

35 - - - 40 - - -

- - -

- - -

6 ECB47-20 (27A43) 1 550 16.8 57,300 4.0

27 - - - 30 - - -

- - -

- - -

(3) 25A Fuses

575 18.4 62,700 4.0

28 - - - 30 - - -

- - -

- - -

600 20.0 68,200 4.0

29 - - - 30 - - -

- - -

- - -

25 kW

ECB47-25CB (27A45) 2 208 18.8 64,100 7.6

42 33 45 4 35

75

80

19 lbs.

(2) 45A Circuit breaker

220 21.0 71,700 7.6

47 38 4 50 4 40

85

90

230 23.0 78,300 7.6

47 38 4 50 4 40

85

90

240 25.0 85,300 7.6

47 38 4 50 4 40

85

90

ECB47-25 (27A42) 1 440 21.0 71,700 4.0

39 - - - 40 - - -

- - -

- - -

(3) 40A Fuses

460 23.0 78,300 4.0

41 - - - 45 - - -

- - -

- - -

480 25.0 85,300 4.0

42 - - - 45 - - -

- - -

- - -

6 ECB47-25 (27A41) 1 550 21.0 71,700 4.0

32 - - - 35 - - -

- - -

- - -

(3) 35A Fuses

575 23.0 78,300 4.0

34 - - - 35 - - -

- - -

- - -

600 25.0 85,300 4.0

35 - - - 40 - - -

- - -

- - -

NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. 1 Electric heater capacity only - does not include additional blower motor heat capacity. 2 Amps shown are for blower motor only. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F. 4 Bold text indicates that the circuit breaker on "CB" circuit breaker models must be replaced with size noted. See Table on Page 11. 5 HACR type circuit breaker or fuse. 6 Blower motor is rated at 460V.

7AH2AE | 1.5 to 5 ton Air Handlers | Page 22

DIMENSIONS

UNIT - UPFLOW POSITION

SUPPLY

AIR

3/4

OPENING

(19)

3/4

3/4

(19) 11-1/16 (281)

(19)

D

LINE VOLTAGE LOW VOLTAGE

INLETS

INLETS

(Top and Left Side) (Top and

Right Side)

TOP VIEW

B
5/8 (16)

DETAIL OF PIPING PLATE

1-1/8 (29) SUCTION LINE
LIQUID LINE

4-3/8 (111)

CONDENSATE DRAINS (2) (Horizontal)

2 (51)
5-3/8 (137)
2-3/4 (70)

CONDENSATE DRAINS (2) (Upflow and Downflow)

1-3/4 (44) 3-1/2 (89)

C

AIR FLOW

G

OPTIONAL

ELECTRIC

BLOWER

HEAT

(Field

Installed)

A

PIPING PLATE

SUCTION

H

LINE

LIQUID LINE

Return Air

F

5/8 (16)

FRONT VIEW

5/8 (16)

FILTER ACCESS

FILTER 1
(25)

COIL
Return Air
E SIDE VIEW

Note - Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.
5/8 (16)

Dimensions
A B C D E F G H

018, 024

in.

mm

49-1/4 1251

21-1/4 540

20-5/8 524

19-3/4 502

19

483

20

508

24-5/8 625

24-5/8 625

030, 036

in.

mm

51

1295

21-1/4 540

22-5/8 575

19-3/4 502

21

533

20

508

26-3/8 670

24-5/8 625

042, 048

in.

mm

58-1/2 1486

21-1/4 540

24-5/8 625

19-3/4 502

23

584

20

508

27-7/8 708

30-5/8 778

060

in.

mm

62-1/2 1588

21-1/4 540

24-5/8 625

19-3/4 502

23

584

20

508

27-7/8 708

34-5/8 879

7AH2AE | 1.5 to 5 ton Air Handlers | Page 23

DIMENSIONS

UNIT - DOWNFLOW POSITION

NOTE - Optional Downflow Conversion Kit Required

5/8 (16)

5/8

5/8

(16)

(16)

F

RETURN
E AIR
OPENING

1 (25)
TOP VIEW

DETAIL OF PIPING PLATE

1-1/8 (29) SUCTION LINE
LIQUID LINE

4-3/8 (111)

CONDENSATE DRAINS (2) (Horizontal)

2 (51) 3-5/8 (92)

CONDENSATE DRAINS (2) (Upflow and Downflow)

1 (25)

1-3/4 (44) 3-1/2 (89)

FILTER

B

ACCESS

C

PIPING PLATE

FILTER
H
SUCTION LINE

COIL

LIQUID LINE

AIR FLOW

A G

OPTIONAL ELECTRIC
HEAT (Field Installed) LOW VOLTAGE (Right Side) LINE VOLTAGE (Left Side)

5/8 (16)

Supply Air

3/4

D

3/4

(19)

(19)

FRONT VIEW

BLOWER

Supply Air

11-1/16 (281)

5/8 (16)

SIDE VIEW

Note - Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.

Dimensions
A B C D E F G H

018, 024

in.

mm

49-1/4 1251

21-1/4 540

20-5/8 524

19-3/4 502

19

483

20

508

24-5/8 625

24-5/8 625

030, 036

in.

mm

51

1295

21-1/4 540

22-5/8 575

19-3/4 502

21

533

20

508

26-3/8 670

24-5/8 625

042, 048

in.

mm

58-1/2 1486

21-1/4 540

24-5/8 625

19-3/4 502

23

584

20

508

27-7/8 708

30-5/8 778

060

in.

mm

62-1/2 1588

21-1/4 540

24-5/8 625

19-3/4 502

23

584

20

508

27-7/8 708

34-5/8 879

7AH2AE | 1.5 to 5 ton Air Handlers | Page 24

DIMENSIONS

UNIT - HORIZONTAL RIGHT-HAND POSITION

DETAIL OF PIPING PLATE

5-3/8 (137)

2 (51)

LIQUID LINE
SUCTION LINE

FILTER

1-1/8 (29)

1-1/2 (38)

4-3/8 (111)

5-3/4 (146) CONDENSATE DRAINS (2) (Upflow and Downflow)

1-3/4 (44)

CONDENSATE DRAINS (2) (Horizontal)

5/8 (16)

LIQUID LINE

COIL

BLOWER

C

SUCTION LINE

OPTIONAL ELECTRIC HEAT (Field Installed)

TOP VIEW

Note - Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.

A

H

G

5/8 (16) LINE VOLTAGE
INLETS (Top and Right Side)

11-1/16 (281)

3/4 (19)
3/4 (19)

E

5/8

1

(16)

F RETURN

(25)

AIR

OPENING

PIPING PLATE

AIR FLOW

B

SUPPLY AIR

D

OPENING

5/8 (16)
END VIEW

FILTER ACCESS

FRONT VIEW

LOW VOLTAGE INLETS (Bottom and Right Side)

3/4 (19)

END VIEW

FILTER

DETAIL OF PIPING PLATE

C

BLOWER

COIL

Note - Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.

OPTIONAL ELECTRIC HEAT (Field Installed)

SUCTION LINE

3/4 (19) 3/4 (19)

11-1/16 (281)

LOW VOLTAGE 5/8

INLETS

(16)

(Top and

Left Side)

TOP VIEW

A

G

H

LIQUID LINE

4-3/8 (111) 1-1/8 (29)
SUCTION LINE LIQUID LINE

2 (51)

5-3/8 (137)

5/8 (16)

D
3/4 (19)

SUPPLY

AIR

B

OPENING

LINE VOLTAGE INLETS (Bottom and Left Side)
END VIEW

Dimensions
A B C D E F G H

018, 024

in.

mm

49-1/4 1251

21-1/4 540

20-5/8 524

19-3/4 502

19

483

20

508

24-5/8 625

24-5/8 625

AIR FLOW

PIPING PLATE

FILTER ACCESS

CONDENSATE DRAINS (2) (Horizontal)

1 (25)

1-3/4 (44)
FRONT VIEW

5-3/4 (146)

1-1/2 (38)

E

RETURN F
AIR

5/8 (16)

OPENING

5/8 (16)
END VIEW

030, 036

in.

mm

51

1295

21-1/4 540

22-5/8 575

19-3/4 502

21

533

20

508

26-3/8 670

24-5/8 625

042, 048

060

in.

mm

in.

mm

58-1/2 1486 62-1/2 1588

21-1/4 540 21-1/4 540

24-5/8 625 24-5/8 625

19-3/4 502 19-3/4 502

23

584

23

584

20

508

20

508

27-7/8 708 27-7/8 708

30-5/8 778 34-5/8 879

7AH2AE | 1.5 to 5 ton Air Handlers | Page 25

DIMENSIONS

DOWNFLOW COMBUSTIBLE FLOORING BASE
AIR HANDLER

ACCESSORIES

DOWNFLOW COMBUSTIBLE FLOORING BASE

1-5/8 (41)

1-5/8 (41) TOP VIEW
11-3/8 (289)
20 (508)

DOWNFLOW COMBUSTIBLE FLOORING BASE DETAIL

23-1/4 (591)

Break off extended width at pre-perforated line to fit specific air handler application. NOTE - Width of base includes an additional 2 in. (51 mm) for air handler positioning adjustment.

1-5/8 (41)

SUPPLY AIR OPENING

5/8

13-1/2 (343)

(16)

Opening

SIDE VIEW

3 (76)

Model No.
A B C

018, 024

in.

mm

22-5/8

575

- - -

- - -

- - -

- - -

A B C

030, 036

in.

mm

- - -

- - -

24-5/8

625

- - -

- - -

042, 048, 060

in.

mm

- - -

- - -

- - -

- - -

26-5/8

676

7AH2AE | 1.5 to 5 ton Air Handlers | Page 26

DIMENSIONS

HORIZONTAL SUPPORT FRAME KIT
Suspension Rods (Not furnished)

ACCESSORIES

End Channels (2)
DRAIN PAN (not furnished) Includes (2) 1 x 1-1/2 x 32-5/8 in. side channels and (2) 1 x 3 x 53-7/8 in. end channels.
SIDE RETURN UNIT STAND
(Upflow Only)

Side Channels (2)

16 (406)
6 (152)

FRONT
21-1/4 (540)

SIDE
ADJUSTABLE 20 (508) to 25 (635) ALL UNITS

7AH2AE | 1.5 to 5 ton Air Handlers | Page 27

Contact us at 1-800-448-5872

NOTE - Due to Allied Air's ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.

Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.

Installation and service must be performed by a qualified installer and servicing agency.

©2024 Allied Air Enterprises


Adobe PDF Library 17.0