PT-Control-Manual
prestige
Control Application
Supplement - TriMax

LISTED

WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given. Skipping or missing procedural steps could result in severe personal injury, death or substantial property damage.

Revised 2/10/2014

2012-13 Prestige Trimax Control Appl. Supl.

Table of Contents
NOTICE This Control Application Supplement applies to TriMax controls with the following software version numbers:
Display SWv.1.14 Burner Controller SW v.0.14 This software version numbers are displayed on the initial screen after turning on the unit.
Product and Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Operating Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Entering Installer Access Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Trimax Installer Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CH Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13 DHW Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18 Boiler Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-20 Reset All Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Factory Trimax Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Cascade Operating Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Trimax Cascade Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Cascade Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-33 Cascade Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Cascade Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-40 Modbus Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-42 Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
i

Product and Safety Information
IMPORTANT INFORMATION - READ BEFORE PROCEEDING

WARNING
This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given. Skipping or missing procedural steps could result in severe personal injury, death or substantial property damage.

DEFINITIONS The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product.
DANGER
Indicates the presence of a hazardous situation which, if ignored, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in death, serious injury or substantial property damage.

NOTICE
Indicates special instructions on installation, operation or maintenance, which are important to the equipment but not related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by ACVTriangle Tube for the installers which will help to ensure optimum operation and longevity of the equipment.

CAUTION
Indicates a potentially hazardous situation which, if ignored, may result in minor injury or substantial property damage.

NOTICE
ACV-Triangle Tube reserves the right to modify the technical specifications and components of its product without prior notice.
1

Operating Information
OPERATING INFORMATION The TriMax Boiler Management System is designed to be flexible yet easy to use. TriMax monitors and controls the Prestige to operate as efficiently as possible. TriMax monitors the boiler supply, return and flue gas temperatures and operates the igniter, gas valve and blower. TriMax uses this information to modulate the boiler's firing rate to maintain the required setpoint. TriMax offers many advanced control options, which may be adjusted for various applications to achieve optimum boiler efficiency and operation. · Two central / space heating (CH) call inputs with separate outdoor reset curves. · Domestic Hot Water (DHW) call input with optional priority. · System temperature sensing and control with an optional system temperature sensor. · Cascade function allows up to six Prestige boilers to operate together in a single heating system. · Modbus interface for integrating with building management systems. These advanced features are adjustable in the Installer Menu after entering an access code.
2

Entering Installer Access Code
ENTERING INSTALLER ACCESS CODE
The INSTALLER button (the small round button) provides the installing contractor with full access to all available features after entering an access code.

Installer Button

Fig. 1: TriMax Navigation Buttons
Entering installer access code procedure
1. Press the round INSTALLER button.
2. Enter the installer access code "054" by using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit. Press the OK button to enter the access code.
3. The Installer Menu will be displayed after successfully entering the access code. The Home Screen will be displayed if the access code is not entered correctly.
NOTICE
Entering the installer access code allows the installer to make adjustments for 30 minutes. After 30 minutes, the access code will need to be entered again to make any adjustments.
The Installer Menu is divided into four sections:

1. CH & DHW Settings ­ Allows the installer to adjust the boilers central / space heating, domestic hot water and boiler settings for the application. See pages 5 through 20.

2. Manual Operation ­ The burner and circulators can be manually enabled for testing. See page 43.

3. Reset All Settings

­ Resets all CH, DHW, Boiler, and Cascade

Settings back to the factory defaults. See pages 20 through 21.

4. Cascade

­ Allows the installer to setup, adjust, and monitor the

Cascade System. See pages 22 through 40.

3

ENTER INSTALLER ACCESS CODE 05[4]
CH & DHW Settings

Trimax Installer Menu Structure TriMax Installer Menu Structure
Home Screen

Installer Access Code ENTER INSTALLER
ACCESS CODE 05[4]
Installer Menu
CH & DHW Settings

CH & DHW Settings Menu CH Settings

Reset All Settings Reset All Settings

Press OK button to restore factory settings,
any other button to keep current settings

Cascade Menu Cascade Information

Manual Operation Manual Operation

FAN
CH CH1 DHW
SYS CH2

Released
O O O

4

CH Settings

CH Settings
Navigation: Home Screen>Installer Menu>CH & DHW Settings>CH Settings The CH Settings menu contains settings related to central heating operation. Each line contains a CH Setting followed by its current value. Six CH Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional CH Settings.

Heating Settings
Heating Operation Enabled Demand Switch & Outdoor Absolute Max CH Setpoint 188ºF CH1 Maximum Setpoint 180ºF CH1 Minimum Setpoint 120ºF Reset Curve Coldest Day 0ºF

Heating Operation

Default: Enabled

Heating Operation allows the central heating function to be enabled and

disabled. Press the UP or DOWN buttons to select Enabled or Disabled

then press the OK button to store the setting.

· Enabled - The Prestige will respond to a central heating call. · Disabled - The Prestige will not respond to a central heating call.
The heating operation disabled icon is displayed on the home
screen when central heating operation has been disabled.

Heating Operation
Disabled Enabled

Demand Type

Default: Switch & Outdoor Reset

Demand Type allows the installer to select how a CH Demand is generat-

ed. Press the UP or DOWN buttons to select the CH Demand Type then

press the OK button to store the setting. The CH Demand options are:

· Switch & Outdoor Reset ­ A central heating call from a dry contact switch will enable the Prestige and the setpoint will vary with the outdoor temperature for central heating calls
· Switch & Setpoint - A central heating call from a dry contact switch will enable the Prestige and the setpoint will be fixed for central heating calls
· Constant & Outdoor Reset - The Prestige will maintain setpoint and the central heating circulators will be constantly enabled without an external call from a dry contact switch. The central heating circulators will be disabled when the outdoor temperature exceeds the Warm Weather Shutdown Temperature setting. The setpoint will vary with the outdoor temperature for central heating calls.
· Constant & Setpoint - The Prestige will maintain setpoint and the central heating circulators will be constantly enabled without an external call from a dry contact switch. The central heating circulators will be disabled when the outdoor temperature exceeds the Warm Weather Shutdown Temperature setting. The setpoint will be fixed for central heating calls.
· 0-10V Modulation Signal ­ This option allows the Prestige firing rate to be controlled by an external control system with a 0-10 VDC signal.
5

Demand Type
Switch & Outdoor Reset Switch & Set point
Constant & Outdoor Reset Constant & Setpoint
0-10V Modulation Signal

CH Settings

Absolute Max CH Setpoint

Default: 188°F [87°C]

Absolute Max CH Setpoint can be used to prevent a user from adjusting the

central heating setpoint or outdoor reset curve above a safe operating tem-

perature in the EZ Setup Menu. A warning screen will be displayed in EZ

Setup if the user attempts to raise the setpoint above the Absolute Max CH 68ºF Setpoint. The Absolute Max CH Setpoint will be displayed on the outdoor

reset curve in EZ Setup if the user selects an outdoor reset curve which goes

above the Absolute Max CH Setpoint. Press the LEFT or RIGHT buttons

to adjust the Absolute Max CH Setpoint then press the OK button to store

the setting.

Absolute Max CH Setpoint
188ºF
188ºF

CH1 Maximum Setpoint

Default: 180°F [82°C]

CH1 Maximum Setpoint is the maximum setpoint for a CH1 heating call

when an Outdoor Reset option is chosen in CH Demand. CH1 Maximum

Setpoint is the fixed setpoint for a CH1 heating call when a Setpoint option

is chosen in CH Demand. Press the LEFT or RIGHT buttons to adjust

the CH1 Maximum Setpoint then press the OK button to store the setting. 68ºF

CH1 Maximum Setpoint
180ºF
188ºF

CH1 Minimum Setpoint

Default: 120°F [49°C]

CH1 Minimum Setpoint is the minimum setpoint for a CH1 heating call

when an Outdoor Reset option is chosen in CH Demand. This setting is

not applicable when a Setpoint option is chosen in CH Demand. CH1

Minimum Setpoint must be set equal to or below the CH1 Maximum Setpoint. Press the LEFT or RIGHT buttons to adjust the CH1 Minimum 60ºF

Setpoint then press the OK button to store the setting.

CH1 Minimum Setpoint
120ºF
188ºF

Reset Curve Coldest Day

Default: 0°F [-18°C]

Reset Curve Coldest Day is the coldest outdoor design temperature of the

heating system when an Outdoor Reset option is chosen in CH Demand.

This setting is not applicable when a Setpoint option is chosen in CH Demand. Press the LEFT or RIGHT buttons to adjust the Reset Curve

-30ºF

Coldest Day then press the OK button to store the setting.

Reset Curve Coldest Day
0ºF
50ºF

6

CH Settings

Reset Curve Warmest Day

Default: 64°F [18°C]

Reset Curve Warmest Day is the warmest outdoor design temperature of

the heating system when an Outdoor Reset option is chosen in CH

Demand. This setting is not applicable when a Setpoint option is chosen

in CH Demand. Press the LEFT or RIGHT buttons to adjust the Reset 60ºF

Curve Warmest Day then press the OK button to store the setting.

Reset Curve Warmest Day
64ºF
78ºF

CH2 Circuit

Default: Enabled

CH2 Circuit allows the CH2 Maximum and Minimum Setpoints to be

enabled and disabled. When disabled, the CH2 heating call will operate

using the CH1 Maximum and Minimum Setpoints. Press the UP or

DOWN buttons to select Enabled or Disabled then press the OK button

to store the setting.

· Enabled ­ A CH2 heating call will use CH2 Maximum and Minimum Setpoints.

· Disabled ­ A CH2 heating call will use CH1 Maximum and Minimum Setpoints.

CH2 Circuit
Disabled Enabled

CH2 Maximum Setpoint

Default: 140°F [60°C]

CH2 Maximum Setpoint is the maximum setpoint for a CH2 heating call

when an Outdoor Reset option is chosen in CH Demand. CH2

Maximum Setpoint is the fixed setpoint for a CH2 heating call when a

Setpoint option is chosen in CH Demand. Press the LEFT or RIGHT

buttons to adjust the CH2 Maximum Setpoint then press the OK button

to store the setting.

CH2 Minimum Setpoint

Default: 80°F [27°C]

CH2 Minimum Setpoint is the minimum setpoint for a CH2 heating

call when an Outdoor Reset option is chosen in CH Demand. This set-

ting is not applicable when a Setpoint option is chosen in CH Demand.

CH2 Minimum Setpoint must be set equal to or below the CH2

Maximum Setpoint. Press the LEFT or RIGHT buttons to adjust the

CH2 Minimum Setpoint then press the OK button to store the setting.

Warm Weather Shutdown

Default: OFF

Warm Weather Shutdown allows the installer to enter an optional out-

door temperature at which to disable the central heating function and

any circulators placed into constant circulation with the Pump Constant

Circulation setting. The Prestige will continue to respond to a domes-

tic hot water call or a 0-10V Modulation Signal when the outdoor tem-

perature exceeds the Warm Weather Shutdown Temperature setting.

Press the LEFT or RIGHT buttons to adjust the Warm Weather

Shutdown Temperature then press the OK button to store the setting.

The Warm Weather Shutdown icon

is displayed on the home

screen when the outdoor temperature reaches the Warm Weather

Shutdown Temperature.

7

Warm Weather Shutdown
Off

Off

78ºF

CH Settings

Pump Constant Circulation

Default: Disabled

Pump Constant Circulation allows the central heating circulators to be

constantly enabled even without a central heating call. Pump Constant

Circulation can be disabled by the Warm Weather Shutdown function. A

domestic hot water call will cause the circulators to be disabled during the

domestic call as long as DHW Priority is enabled. Press the UP or

DOWN buttons to select Enabled or Disabled then press the OK button to

store the setting.

· Enabled ­ The central heating circulators will be enabled for constant circulation without a central heating call.

Table 1: Circulator Operation with Constant Circulation = Enabled

Prestige Model
Solo Excellence

CH2 Pump/ System Pump
ON
ON

Auxillary Boiler Pump
ON
ON

DHW Pump OFF
OFF

CH (1) Pump ON
OFF

· Disabled ­ The central heating circulators will only be enabled during a central heating call.

Pump Constant Circulation
Disabled Enabled

CH Post Pump Time

Default: 1 Minute

CH Post Pump Time sets how long the central heating circulators will

continue to operate at the completion of a heating call. Reference

System Pump in CH Settings on page 10 to determine which circulators

will continue to operate. Any call during the CH Post Pump Time will be

ignored until the post pump has completed. The CH Post Pump feature Off

allows the heat remaining in the boiler at the completion of a call to be

sent to the heating system, which will improve the overall efficiency of

the system. Press the LEFT or RIGHT buttons to adjust the CH Post

Pump Time then press the OK button to store the setting.

CH Post Pump Time
1 min.
20 min.

Freeze Protection

Default: Enabled

Freeze Protection allows the freeze protection feature to be enabled and

disabled. Press the UP or DOWN buttons to select Enabled or Disabled

then press the OK button to store the setting.

· Enabled ­ The Freeze Protection feature is enabled to protect the boiler from freezing. This feature monitors the boiler water temperature and responds as follows when no call is present:
- 46°F [8°C] ­ Auxiliary Boiler Pump ON

- 42°F [6°C] ­ CH(1), Auxiliary Boiler & System Pumps ON. Burner operates at low fire.

- 60°F [15°C] ­ Freeze protection ends. Burner & all pumps OFF after completing CH Post Pump Time.
· Disabled ­ The Freeze Protection feature is disabled.

8

Freeze Protection
Enabled Disabled

CH Settings

WARNING
Freeze Protection should only be disabled when the system contains antifreeze to prevent the system from freezing. Serious damage could occur to the Prestige as well as the entire heating system if Freeze Protection is disabled without antifreeze in the system.

WARNING

The Prestige should NEVER be installed in a location where freezing could occur. Subjecting the Prestige to freezing conditions could lead to freezing of the condensate possibly causing serious injury or death.

Frost Protection Setpoint

Default: -22ºF [-30ºC]

Frost Protection will enable the central heating circulators if the outdoor

temperature falls below the Frost Protection Setpoint and no call is present.

Frost Protection Setpoint
-22ºF

This feature requires using the outdoor temperature sensor and is always

active and cannot be disabled. Press the LEFT or RIGHT buttons to adjust -22ºF

50ºF

the Frost Protection Setpoint then press the OK button to store the setting.

Table 2: Frost Protection Circulator Operation

Prestige Model
Solo Excellence

CH2 Pump/ System Pump
ON
ON

Auxillary Boiler Pump
ON
ON

DHW Pump OFF
OFF

CH (1) Pump ON
OFF

Parallel Shift Value

Default: 0°F [0°C]

Parallel Shift Value

Parallel Shift allows the CH setpoint to be externally adjusted when a

Constant option is chosen in CH Demand. When a Constant option is cho-

0ºF

sen in CH Demand, continuous CH1 and CH2 heating calls are generated.

Simultaneous CH1 and CH2 calls will result in the Prestige operating at the 0ºF highest CH1 or CH2 setpoint. The CH1 or CH2 Thermostat terminals with

144ºF

the highest setpoint will be used to adjust the setpoint. If the Thermostat

terminals with the highest setpoint are open, the CH setpoint will decrease

by the Parallel Shift Value. If the Thermostat terminals with the highest

setpoint are closed, the CH setpoint will return to the highest CH1 or CH2

setpoint. Press the LEFT or RIGHT buttons to adjust the Parallel Shift

Value then press the OK button to store the setting.

CH Call Blocking

Default: 1 Minute

CH Call Blocking sets the minimum time between burner firings for

central heating calls. At the completion of a burner firing, the CH Call

Blocking time will begin. The burner will not fire again until after the

CH Call Blocking time has elapsed. The CH Call Blocking time only

prevents the burner from firing, the central heating circulators will

respond to a central heating call. This blocking time has no affect on

domestic hot water calls. The CH Call Blocking feature prevents short

cycling of the burner and extends the life of the burner components.

Press the LEFT or RIGHT buttons to adjust the CH Call Blocking

time then press the OK button to store the setting.

CH Call Blocking
1 min.

0 min.

30 min.

9

CH Settings

System Pump

Default: CH1/CH2

System Pump allows the system pump operation to be adjusted for the

application. Press the UP or DOWN buttons to select the desired System

Pump operation then press the OK button to store the setting. The System

Pump options are:

· CH1/CH2/DHW ­ The system pump will be enabled for any CH1, CH2, or DHW call. Figure 2, page 11 illustrates a typical existing system requiring this setting.

Table 3: Circulator Operation with System Pump = CH1/CH2/DHW

CH 1 Call CH 2 Call DHWCall

CH2 Pump/ Auxillary System Pump Boiler Pump

ON

ON

ON

ON

ON

ON

DHW Pump
OFF
(Note 1)
OFF
(Note 1)
ON

CH (1) Pump
ON
ON OFF
(Note 1)

· CH1/CH2 ­ The system pump will only be enabled for a CH1 or CH2 central heating call. Figure 3, page 12 illustrates a system zoned with zone valves requiring this setting.

Table 4: Circulator Operation with System Pump = CH1/CH2

CH 1 Call

CH2 Pump/ Auxillary System Pump Boiler Pump

ON

ON

DHW Pump
OFF
(Note 1)

CH (1) Pump
ON

CH 2 Call

ON

ON

OFF

ON

DHWCall

OFF
(Note 1)

ON

ON

OFF
(Note 1)

· CH2 ­ The system pump will only be enabled for a CH2 central heating call. The CH(1) pump will only be enabled for a CH1 central heating call. Figure 4, page 13 illustrates a system zoned with zone circulators requiring this setting.

Table 5: Circulator Operation with System Pump = CH2

CH 1 Call CH 2 Call DHWCall

CH2 Pump/ Auxillary System Pump Boiler Pump

OFF

ON

ON

ON

OFF
(Note 1)

ON

DHW Pump OFF
(Note 1)
OFF
(Note 1)
ON

CH (1) Pump
ON
OFF OFF
(Note 1)

Note 1: Domestic Hot Water Priority can be disabled which allows the CH and DHW circulators to operate at the same time.

NOTICE The circulator operation shown above only applies when Prestige Model is set to Solo. System Pump only allows the system pump operation to be adjusted when Prestige Model is set to Excellence.

10

System Pump
CH1/CH2/DHW CH1/CH2 CH2

CH(1) Pump

CH Settings
Fig. 2: System Piping with System Pump = CH1/CH2/DHW 11

CH(1) Pump

CH Settings
Fig. 3: System Piping with System Pump = CH1/CH2 12

CH(1) Pump

CH Settings
Fig. 4: System Piping with System Pump = CH2 13

DHW Settings

DHW Settings
Navigation: Home Screen>Installer Menu>CH & DHW Settings>DHW Settings The DHW Settings menu contains settings related to domestic hot water operation. Each line contains a DHW Setting followed by its current value. Six DHW Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional DHW Settings.

DHW Settings

DHW Operation Enabled

Demand

Switch

Boiler DHW Setpoint 186ºF

DHW Storage Setpoint 140ºF

DHW On Di erential

6ºF

DHW Storage Adder

46ºF

DHW Operation

Default: Enabled

DHW Operation allows the domestic hot water function to be enabled

and disabled. Press the UP or DOWN buttons to select Enabled or

Disabled then press the OK button to store the setting.

· Enabled - The Prestige will respond to a domestic hot water call. · Disabled - The Prestige will not respond to a domestic hot water
call. The domestic hot water operation disabled icon is dis-
played on the home screen when domestic hot water operation has been disabled.

Demand Type

PRESTIGE Solo Default: Switch

PRESTIGE Excellence Default: Sensor

Demand Type allows the installer to select the type of device which will

generate a domestic hot water call. Press the UP or DOWN buttons to

select the DHW Demand Type then press the OK button to store the set-

ting. The DHW Demand options are:

· Switch - A domestic hot water call from an aquastat or dry contact switch will enable the Prestige with a fixed setpoint for a domestic hot water call.
· Sensor - This option requires the use of Indirect Water Heater Sensor PSRKIT22 which is included with every PRESTIGE Solo. The PRESTIGE Excellence utilizes an Indirect Water Heater Sensor. The Prestige will monitor the DHW storage temperature and generate a domestic hot water call when the temperature drops below the DHW Storage Setpoint - DHW On Differential.

DHW Operation Disabled Enabled
Demand Type Switch Sensor

14

DHW Settings

Boiler DHW Setpoint

Default: 186ºF [86ºC]

Boiler DHW Setpoint is the fixed boiler setpoint temperature during a

domestic hot water call when the Switch option is chosen in DHW

Demand. Press the LEFT or RIGHT buttons to adjust the Boiler DHW

Setpoint then press the OK button to store the setting.

96ºF

Boiler DHW Setpoint
186ºF
188ºF

DHW Storage Setpoint

Default: 140°F [60°C]

DHW Storage Setpoint is the domestic hot water storage setpoint temper-

ature when the Sensor option is chosen in DHW Demand. Press the LEFT

or RIGHT buttons to adjust the DHW Storage Setpoint then press the OK

button to store the setting.
68ºF

DHW Storage Setpoint
140ºF
150ºF

NOTICE
The boiler setpoint is automatically set to the DHW Storage Setpoint + DHW Storage Adder when the Sensor option is chosen in DHW Demand.

DHW On Differential

Default: 6°F [3°C]

DHW On Differential sets how far the DHW storage temperature must fall

DHW On Di erential

below the DHW Storage Setpoint to create a domestic hot water call when

6ºF

the Sensor option is chosen in DHW Demand. The domestic hot water call

will end when the DHW storage temperature rises above the DHW

Storage Setpoint. Press the LEFT or RIGHT buttons to adjust the DHW 4ºF

18ºF

On Differential then press the OK button to store the setting.

DANGER
The DHW On Differential setting greatly affects the production of domestic hot water. A low setting could result in a rapid response to a domestic hot water call resulting in a potential scald hazard. It is strongly recommended that the installer utilize a thermostatic mixing valve on the hot water outlet of the Indirect Water Heater. Failure to comply could result in severe personal injury, death, or substantial property damage.

15

DHW Settings

DHW Storage Adder

Default: 46°F [25°C]

DHW Storage Adder is used to compute the boiler setpoint when the

Sensor option is chosen in DHW Demand. The boiler setpoint will be

DHW Storage Setpoint + DHW Storage Adder for a domestic hot water

call. Press the LEFT or RIGHT buttons to adjust the DHW Storage

Adder then press the OK button to store the setting.

0ºF

DHW Storage Adder
46ºF
54ºF

DHW Post Pump Time

Default: 1 Minute

DHW Post Pump Time sets how long the domestic hot water circulator

will continue to operate at the completion of a domestic hot water call.

Any call during the DHW Post Pump Time will be ignored until the post

pump has completed. The DHW Post Pump feature allows the heat

remaining in the boiler at the completion of a call to be sent to the Off

Indirect Water Heater, which will improve the overall efficiency of the

system. Press the LEFT or RIGHT buttons to adjust the DHW Post

Pump Time then press the OK button to store the setting.

DHW Post Pump Time
1 min.
30 min.

DHW Priority Timeout

Default: Off

DHW Priority Timeout allows the installer to enter an optional time limit

that a domestic hot water call has priority over a central heating call when

DHW Priority is set to Enabled. Press the LEFT or RIGHT buttons to

adjust the DHW Priority Timeout then press the OK button to store the

setting.

DHW Priority Timeout
Off

Off

120 min.

DHW Priority

Default: Enabled

DHW Priority allows the domestic hot water priority function to be

enabled and disabled. Press the UP or DOWN buttons to select Enabled

or Disabled then press the OK button to store the setting.

· Enabled- Domestic hot water calls will have priority over a central heating call. The boiler setpoint will be set to the domestic hot water setpoint during a domestic hot water call. The DHW circulator will be enabled and the heating circulators will be disabled during a domestic hot water call.

· Disabled - Domestic hot water calls will not have priority over a central heating call. The boiler setpoint will be set to the domestic hot water setpoint when only a domestic hot water call is present.

16

DHW Priority
Enabled Disabled

DHW Settings
The boiler setpoint will be set to the highest setpoint when simultaneous domestic hot water and central heating calls are present. The DHW circulator will be enabled during a domestic hot water call. The heating circulators will be enabled during a central heating call.

WARNING
Simultaneous domestic hot water and central heating calls will result in the PRESTIGE operating at the highest target temperature when DHW Priority is set to Disabled. The use of a mixing device on the lower temperature zones such as the Triangle Tube Optima Series SMV Control may be required to protect the lower temperature zones from damage.

NOTICE
DHW Priority should only be set to Disabled when Prestige Model is set to Solo. Setting DHW Priority to Disabled when Prestige Model is set to Excellence will not disable DHW Priority.

DHW Call Blocking

Default: 0 Minute

DHW Call Blocking sets the minimum time between burner firings for

domestic hot water calls. At the completion of a burner firing, the DHW

Call Blocking time will begin. The burner will not fire again until after the

DHW Call Blocking time has elapsed. The DHW Call Blocking time only

prevents the burner from firing, the domestic hot water circulator will 0 min.

respond to a domestic hot water call. This blocking time has no affect on

central heating calls. The DHW Call Blocking feature prevents short

cycling of the burner and extends the life of the burner components. Press

the LEFT or RIGHT buttons to adjust the DHW Call Blocking time then

press the OK button to store the setting.

DHW Call Blocking
0 min.

30 min.

DHW To CH Call Blocking

Default: 1 Minute

DHW To CH Call Blocking sets the minimum time between a DHW burn-

er firing and a CH burner firing. At the completion of a DHW burner fir-

ing, the DHW to CH Call Blocking time will begin. The burner will not

fire again for a central heating call until after the DHW To CH Call

Blocking time has elapsed. The DHW To CH Call Blocking time only pre- 0 min.

vents the burner from firing, the central heating circulators will respond to

a central heating call. This blocking time has no affect on domestic hot

water calls. The DHW To CH Call Blocking feature prevents the burner

from firing when switching from a domestic hot water call to a central heat-

ing call. This allows the remaining heat in the heat exchanger to be dissi-

pated and potentially satisfy the central heating call. Press the LEFT or

RIGHT buttons to adjust the DHW To CH Call Blocking time then press

the OK button to store the setting.

DHW to CH Call Blocking
1 min.
30 min.

17

DHW Settings

Antilegionella Function

Default: Disabled

The Antilegionella Function ensures that an Indirect Water Heater is heat-

ed at least once per week to prevent the growth of Legionella bacteria.

Press the UP or DOWN buttons to select Enabled or Disabled then press

the OK button to store the setting.

· Enabled- When the Switch option is chosen in DHW Demand, a domestic hot water call is generated for 15 minutes once per week to heat the Indirect Water Heater. When the Sensor option is chosen in DHW Demand, a domestic hot water call is generated until the DHW storage temperature reaches 140°F [60°C] once per week. When the Sensor option is chosen in DHW Demand, the weekly timer is reset whenever the DHW storage temperature reaches 140°F [60°C] to prevent unnecessary firings. This function will be active even if DHW Operation has been set to Disabled.

· Disabled - The Prestige will only fire in DHW mode when a domestic hot water call is received.

WARNING
The Antilegionella Function should only be enabled when an Indirect Water Heater is installed. Enabling the Antilegionella Function without an Indirect Water Heater will result in the Prestige firing once per week in DHW mode. This could cause a Manual Reset Hard Lockout resulting in substantial property damage.
BEST PRACTICE
The Antilegionella Function is most effective when the Sensor option is chosen in DHW Demand. The use of an Indirect Water Heater Sensor ensures that the domestic hot water is heated to 140°F [60°C] at least once per week.

Antilegionella Function
Enabled Disabled

18

Boiler Settings

Boiler Settings
Navigation: Home Screen>Installer Menu>CH & DHW Settings>Boiler Settings The Boiler Settings menu contains settings related to general boiler operation. Each line contains a Boiler Setting followed by its current value.

Boiler Settings

Prestige Model

Solo

LockoutTemp. 210ºF [99ºC]

Modbus Address

0=BCST

Prestige Model

PRESTIGE Solo Default: Solo

PRESTIGE Excellence Default: Excellence

Prestige Model selects how the circulator / diverter valve line voltage ter-

minals will operate. Press the UP or DOWN buttons to select Solo or

Excellence then press the OK button to store the setting.

· Solo - The circulator / diverter valve terminals can be used to operate CH(1), DHW, Auxiliary Boiler, and System circulators.
· Excellence - The CH(1), DHW, and Auxiliary Boiler circulator / diverter valve terminals will operate the internal boiler circulator and diverter valve. Only the System circulator terminals are available for operating a system circulator.

NOTICE

Excellence units also require setting Demand Type to Sensor for correct DHW operation.

Lockout Temp.

Default: 210°F [99°C]

Lockout Temp. allows the High Boiler Temperature lockout (E3) to be

temporarily adjusted down to 102°F [39°C] for inspector demonstra-

tion. Press the UP or DOWN buttons to select 210°F [99°C] or 102°F

[39°C] then press the OK button to store the setting.

· 102°F [39°C] ­ A High Boiler Temperature lockout (E3) will occur when the boiler temperature reaches 102°F [39°C].

· 210°F [99°C] ­ A High Boiler Temperature lockout (E3) will occur when the boiler temperature reaches 210°F [99°C].

Prestige Model Solo
Excellence
Lockout Temp. 102ºF [39ºC] 210ºF [99ºC]

19

Reset All Settings

Modbus Address

Default:0=BCST

Modbus Address assigns the boiler with a unique address in the Modbus

control system. Press the LEFT or RIGHT buttons to change the

Modbus Address then press the OK button to store the setting. See Pages

41 & 42 for Modbus Interface information.

Modbus Address
0=BCST

0=BCST

247

Reset All Settings

Navigation: Home Screen>Installer Menu>Reset All Settings Reset All Settings allows the installer to reset all CH, DHW, Boiler and Cascade settings back to the original PRESTIGE Solo factory defaults. Follow the onscreen instructions to reset all settings back to the original factory defaults
NOTICE
PRESTIGE Excellence units require setting Prestige Model to Excellence and DHW Demand Type to Sensor after using the Reset All Settings function.

Reset All Settings
Press OK button to restore factory settings,
any other button to keep current settings.

20

Factory Trimax Settings

Factory Trimax Settings

HEATING SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EZ SETUP RESET INSTALLER RESET

Heating Operation

Enabled

Demand

Switch & Outdoor Reset

Absolute Max CH Setpoint 188°F [87°C]

68°F [20°C]

188°F [87°C]

CH1 Maximum Setpoint 180°F [82°C]

68°F [20°C]

188°F [87°C]

CH1 Minimum Setpoint 120°F [49°C]

60°F [15°C]

188°F [87°C]

Reset Curve Coldest Day 0°F [-18°C]

-30°F [-34°C]

50°F [10°C]

Reset Curve Warmest Day

64°F [18°C]

60°F [15°C]

78°F [25°C]

CH2 Circuit

Enabled

CH2 Maximum Setpoint CH2 Minimum Setpoint Warm Weather Shutdown Pump Constant Circulation CH Post Pump Time
Freeze Protection Frost Protection Setpoint Parallel Shift Value CH Call Blocking System Pump

140°F [60°C] 80°F [27°C]
OFF Disabled 1 minute
Enabled -22°F [-30°C]
0°F [0°C] 1 minute CH1/CH2

68°F [20°C] 60°F [15°C]
OFF
OFF
-22°F [-30°C] 0°F [0°C] 0 minute

188°F [87°C] 188°F [87°C] 78°F [25°C]
20 minute
50°F [10°C] 144°F [80°C] 30 minutes

DOMESTIC SETTING DHW Operation Demand

FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EZ SETUP RESET INSTALLER RESET Enabled Switch

Boiler DHW Setpoint

186°F [86°C]

96°F [35°C]

188°F [87°C]

DHW Storage Setpoint DHW On Differential

140°F [60°C] 6°F [3°C]

68°F [20°C] 4°F [2°C]

150°F [65°C] 18°F [10°C]

DHW Storage Adder

46°F [25°C]

0°F [0°C]

54°F [30°C]

DHW Post Pump Time DHW Priority Timeout DHW Priority DHW Call Blocking

1 minute OFF
Enabled 0 minute

OFF OFF
0 minute

30 minutes 120 minutes
30 minutes

DHW to CH Call Blocking

1 minute

0 minute

30 minutes

Antilegionella Function

Disabled

BOILER SETTING Prestige Model Lockout Temperature Modbus Address

FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EZ SETUP RESET INSTALLER RESET

Solo

210°F [99°C]

0=BCST

0

247

CASCADE SETTING
Stage Delay Minimum Firing Rate Maximum Firing Rate CH / DHW Boilers Automatic Rotation CH Proportional Gain CH Integral Gain DHW Proportional Gain DHW Integral Gain

FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EZ SETUP RESET INSTALLER RESET

60 seconds 30%
398 MBH [117kW] 0

0 second 0%
0 MBH [0kW] 0

255 seconds 100%
869 MBH [255kW] 6

Enabled

7

1

255

245

1

255

7

1

255

245

1

255

21

Cascade Operating Information

Cascade Operating Information The TriMax Boiler Management System includes a Cascade function which allows multiple Prestige boilers to operate together without the need for an external controller. One Prestige will be selected as the Master and will be wired to accept all the low voltage control signals. The other Prestige boilers will be designated as Slaves and will only have a communication cable connecting them to the other boilers in the Cascade System.

· The Cascade function allows up to six identical Prestige boilers to operate together in a single heating system.
· Parallel Modulation fires as many boilers as possible to maximize system efficiency.
· Lead Stage Automatic Rotation rotates the lead boiler to ensure even wear on each boiler in the Cascade System. This function can be disabled by the Automatic Rotation Setting.
The Cascade Menu is divided into three sections

1. Cascade Information See page 34.

­ Provides real time operating information of the Cascade System.

2. Cascade Settings

­ Allows the installer to adjust the Cascade System settings for the appli-

cation. See pages 35 through 40.

3. Cascade Autodetection System. See page 26.

­ Automatically finds and configures each boiler of the Cascade

22

Trimax Cascade Menu Structure Trimax Cascade Menu Structure
Installer Menu Cascade
Cascade Menu Cascade

Cascade Information Menu

Cascade Information

Cascade Role System Temp. Active Boilers Total Boilers Cascade Firing Rate

Master 86ºF 0 2 --

Cascade Settings Menu Cascade Settings

Stage Delay

60 sec

Minimum Firing Rate 30%

Maximum Firing Rate 398 MBH

CH / DHW Boilers

0

Automatic Rotation Enabled

CH Proportional Gain

7

Cascade Autodetection Cascade Autodetection
Press OK Button to begin Cascade Autodetection, any other button to cancel

23

Cascade Installation
Cascade Installation ­ System Piping Standard Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the system piping as shown in Figure 7, page 28 or a reverse return piping arrangement as shown in Figure 9, page 30. Split Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the central heating loop. Each boiler configured to respond to a domestic hot water call will also have a direct connection to the indirect water heater as shown in Figure 11, page 32. Reference the Prestige Installation and Maintenance Manual for general boiler installation and piping requirements.

Cascade Installation ­ System Sensor Installation Cascade operation requires a System Temperature Sensor to be installed on the common supply header downstream of all boilers in the system. Place the System Temperature Sensor within 10' of the last boiler in the Cascade System for an accurate temperature reading. Proper placement and installation of the System Temperature Sensor is critical for reliable cascade operation. The type of System Temperature Sensor chosen also greatly affects the accuracy of the system temperature readings. Three types of System Temperature Sensor are available:
· Direct Immersion - A direct immersion temperature sensor (MDRKIT05) is the recommended type since it will provide the most accurate water temperature readings. Install the 1/2" NPT direct immersion temperature sensor in a tee on the common supply header downstream of all boilers in the system. Ensure that the temperature sensor probe is directly in the water flow but not touching the opposite side of the tee. Wire the sensor to terminals15 & 16 of the Master boiler.
· Dry Well Installation ­ A temperature sensor (PSRKIT22) installed in a dry well will measure up to 10°F [5°C] lower than the actual water temperature. All water setpoints must be lowered at the Master boiler by 10°F [5°C] from the desired setpoints for reliable Cascade operation. Install a 3/8"ID drywell in the common supply header downstream of all boilers in the system. The drywell should be long enough to be directly in the water flow for the most accurate temperature reading. Insert the temperature sensor into the well and wire to terminals 15 & 16 of the Master boiler.
· Pipe Mounted Installation ­ A temperature sensor (PTSENS12) mounted to the outside of the pipe will measure up to 20°F [11°C] lower than the actual water temperature. All water setpoints must be lowered at the Master boiler by 20°F [11°C] from the desired setpoints for reliable Cascade operation. The Pipe Mounted temperature sensor can be directly strapped to the outside of a 1" to 3" metallic pipe. Install the temperature sensor as follows:
1. Remove the white plastic cover from the sensor
2. Cut a small slit in the seal gasket on the end of the sensor.

Fig. 5: System Sensor Direct Immersion
Fig. 6: System Sensor Dry Well Installation

24

Cascade Installation
3. Route 18 AWG 2-wire cable or similar cable through the seal gasket into the enclosure.
4. Push down on the orange wire terminal retainers to insert the wires into the sensor terminals. Release the orange wire terminal retainers and confirm that the wires are firmly attached to the sensor terminals.
5. Select a location for the sensor on the common supply header downstream of all boilers in the system. Clean the pipe with fine sandpaper or emery cloth to ensure the pipe is clean and sensor will make good contact with the pipe.
6. Press the white cover onto the sensor and strap the sensor to the pipe using the included wire tie.
7. Wire the sensor to terminals 15 & 16 of the Master boiler.
Cascade Installation ­ Cascade Communication Cable
· A communication cable PTCAB01 must be installed between each boiler in the Cascade System. The cable has a 6 pin molex connector on one end and bare wires on the other end. The molex connector plugs into the Cascade Slave connector of the Slave boiler. The bare wires terminate on the Cascade Master terminals of the Master boiler or prior Slave boiler in cascades of three or more boilers. Reference Figure 8,10,12 on pages 29, 31, 33 for wiring details. The connections are as follows:
Red Wire to Terminal #17
White Wire to Terminal #18
Black Wire & Cable Shielding to Terminal #19
Cascade Installation ­ Low Voltage Wiring Connections
· Thermostat Wiring ­ CH1 and CH2 calls must be wired into the Cascade Master.
· Outdoor Sensor Wiring ­ The outdoor temperature sensor must be wired into the Cascade Master.
· Domestic Hot Water Wiring ­ A DHW call must be wired into the Cascade Master.
· Additional Boiler Limits ­ Boiler Limits must be wired into each boiler in the Cascade System. When a boiler limit opens, that particular boiler will lockout and will be removed from Cascade System operation. The other boilers in the Cascade System will continue to operate if they are not in a lockout.
· External Modulation Control ­ An External Modulation Signal must be wired into the Cascade Master. The modulation signal will control the firing rate of the entire Cascade System, not just the Cascade Master.
· Modbus Wiring ­ A building management system (BMS) connection must be wired into the Cascade Master.
25

Cascade Installation
Cascade Installation ­ Line Voltage Wiring Connections · Circulator Wiring - Reference Figures 8,10,12 on pages 29, 31, 33 for
circulator wiring required for each type of Cascade System. The circulator connections used will depend on the systems piping layout.

NOTICE
Each circulator is individually fused with a 2.5A fuse located in the terminal strip. The total combined amp draw of the CH (1), DHW, and Auxiliary Boiler Circulators must not exceed 4 amps at any time for the PRESTIGE Solo 60, 110, 175, or 250. The total combined amp draw of the CH (1), DHW, and Auxiliary Boiler Circulators must not exceed 3 amps at any time for the PRESTIGE Solo 399. Use an isolation relay to lower the total combined amp draw if exceeding these limits.
· Power Supply ­ A dedicated 120 VAC / 15A minimum service must be used to power the boilers in the Cascade System. Multiple boilers in the Cascade System can be placed on the same electrical circuit. Each boiler can draw a maximum of 8 amps.
· Alarm Wiring ­ The alarm contact closes whenever that particular Prestige is in a soft or hard lockout. The alarm contact will also close on the Master boiler when any of the Slave boilers are locked out.
Cascade Installation ­ Cascade Autodetection
Navigation: Home Screen>Installer Menu>Cascade>Cascade Autodetection The Cascade System must be configured after wiring is completed and any required adjustments are made in Cascade Settings. The Cascade Autodetection function automatically finds and configures all boilers in the Cascade System. This eliminates the need to manually configure each boiler of the Cascade System. Select Cascade Autodetection on the Master boiler then follow the onscreen instructions to perform Cascade Autodetection. Once Cascade Autodetection is finished, a message will be displayed indicating how many boilers have been found. If the number of boilers found is correct, press OK to finish Cascade Autodetection. If the number of boilers found is not correct, check the cascade communication cables between the boilers and repeat Cascade Autodetection.

Cascade Autodetection
Press OK button to begin Cascade Autodetection, any other button to cancel

26

Cascade Installation
Cascade Operation ­ Lockouts If a lockout occurs to a boiler in a Cascade System, it will be removed from Cascade System operation. The remainder of the Cascade System continues to operate and the next available boiler will fire if necessary. The Lockout Screen will be displayed on the locked out boiler as well as the Master boiler. The Master boiler Lockout Screen will also indicate which boiler in the Cascade System is locked out.

Boiler #1 Master Failed Ignition
The burner failed to light after 5 ignition attempts. Check gas supply to boiler. If problem persists after two reset attempts, call service.
Press OK to reset.
[3] E1
The Master boiler indicates that boiler #3 is locked out because of failed ignition.

Boiler #2 Slave
-Slave Operation

Boiler #3 Slave
Failed Ignition
The burner failed to light after 5 ignition attempts. Check gas supply to boiler. If problem persists after two reset attempts, call service.
Press OK to reset.
E1
Boiler #3 locked out due to failed ignition

27

CH SYS

DHW

Cascade Installation
Fig. 7: Standard Primary Secondary Cascade System 28

Note: Reference Fig. 8, page 29 for cascade wiring.

AUX

AUX

AUX

Cascade Installation

Master Prestige Boiler

TriMax Control
ACV Line voltage terminal strip

Low voltage terminal strip
CH1 CH2 Outdoor DHW Manual Auto MoSidgunlaaltionSystem Cascade Modbus Cascade T-stat T-stat Sensor Stat/SensReset/lmRt eset/lmt + - Sensor Master A B G
Slave 1 2 3 4 5 6 7 8 9 10111213141516171819202122

CH2 / Sys Aux Boiler DHW Pump /CH(1) Pump / Power Alarm Pump Pump Diverter ValveDiverter Valve Supply Contact
LGN LGN LGN LGN LGN
232425262728293031323334353637383940

White

Red

Black &

Shielding

SYS AUX DHW CH

System Sensor

Zone #1 Zone Valve End Switch
Zone #2 Zone Valve End Switch
Outdoor Sensor DHW Sensor

Cascade Cable (PTCAB01)

Slave Prestige Boiler

TriMax Control
ACV Line voltage terminal strip

Low voltage terminal strip
CH1 CH2 Outdoor DHW Manual Auto MoSidgunlaaltionSystem Cascade Modbus Cascade T-stat T-stat Sensor Stat/SensReset/lmRt eset/lmt + - Sensor Master A B G
Slave 1 2 3 4 5 6 7 8 9 10111213141516171819202122

CH2 / Sys Aux Boiler DHW Pump /CH(1) Pump / Power Alarm Pump Pump Diverter ValveDiverter Valve Supply Contact
LGN LGN LGN LGN LGN
232425262728293031323334353637383940

White

Red

Black &

Shielding

AUX

Cascade Cable (PTCAB01)

Slave Prestige Boiler

TriMax Control
ACV Line voltage terminal strip

Low voltage terminal strip
CH1 CH2 Outdoor DHW Manual Auto MoSidgunlaaltionSystem Cascade Modbus Cascade T-stat T-stat Sensor Stat/SensReset/lmRt eset/lmt + - Sensor Master A B G
Slave 1 2 3 4 5 6 7 8 9 10111213141516171819202122

CH2 / Sys Aux Boiler DHW Pump /CH(1) Pump / Power Alarm Pump Pump Diverter ValveDiverter Valve Supply Contact
LGN LGN LGN LGN LGN
232425262728293031323334353637383940

N G L

Note: Reference Fig. 7, page 28 for cascade piping.

AUX

Fig. 8: Standard Primary Secondary Cascade Wiring

29

CH SYS

DHW

Cascade Installation
Fig. 9: Standard Reverse Return Cascade System 30

Note: Reference Fig. 10, page 31 for cascade wiring.

Cascade Installation

Master Prestige Boiler

Cascade Slave

ACV
CH1 T-stat 12

CH2 T-stat
34

TriMax Control

Low voltage terminal strip

Outdoor Sensor

DHW Manual Stat/Sens Reset/lmt

Auto Reset/lmt

Modulation Signal + -

System Sensor

Cascade Modbus Master A B G

Line voltage terminal strip

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Pump

Pump Diverter Valve Diverter Valve Supply

LGN LGNLGNLGN LGN

Alarm Contact

5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40

White

Red

Black &

Shielding

System Sensor

Heating Call From SZC5 Zone Panel Outdoor Sensor
DHW Sensor

SYS

DHW CH

Cascade Cable (PTCAB01)

Slave Prestige Boiler

TriMax Control
ACV Line voltage terminal strip

Cascade Slave

CH1 T-stat
12

CH2 T-stat
34

Low voltage terminal strip

Outdoor Sensor

DHW Manual Stat/Sens Reset/lmt

Auto Reset/lmt

Modulation Signal + -

System Sensor

Cascade Modbus Master A B G

5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Pump

Pump Diverter Valve Diverter Valve Supply

Alarm Contact

LGN LGNLGNLGN LGN 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40

White

Red

Black &

Shielding

N G L

Cascade Cable (PTCAB01)

Slave Prestige Boiler

TriMTraiMx aCxonCtoronltrol
ACV Line voltage terminal strip

LLoowwvovltoalgteatgeermtienarml stirnipal strip

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Alarm

Cascade

CH1 T-stat

CH2 T-stat

Outdoor Sensor

DHW Manual Stat/Sens Reset/lmt

Auto Reset/lmt

Modulation Signal + -

System Sensor

Cascade Modbus Master A B G

Pump

Pump Diverter Valve Diverter Valve Supply Contact

LGN LGNLGNLGN LGN

Slave 11 22 33 44 55 66 7 78 89 19011011121113214113511461157118611972012811292 202231224225262237224822953206312372238332493350363317332833394304 35 36 37 38 39 40

Note: Reference Fig. 9, page 30 for cascade piping. Fig. 10: Standard Reverse Return Cascade Wiring
31

Cascade Installation
Fig. 11: Split Cascade System 32

DHW

DHW

CH

CH

CH

ZC SYS

Note 1: Reference Fig. 12, page 33 for cascade wiring. Note 2: DHW Priority must be set to Enabled in DHW Settings of the Cascade Master for proper operation.

Cascade Installation

Master Prestige Boiler

ACV

TriMax Control

Line voltage terminal strip

CH1 Cascade T-stat Slave 1 2

CH2 T-stat
34

Low voltage terminal strip

Outdoor DHW Manual Auto Modulation System Cascade Modbus

Sensor

Stat/Sens Reset/lmt Reset/lmt

Signal + -

Sensor

Master A B G

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Pump

Pump Diverter Valve Diverter Valve Supply

Alarm Contact

LGN LGNLGNLGN LGN 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40

White

Red

Black &

Shielding

System Sensor

Heating Call From SZC5 Zone Panel Outdoor Sensor
DHW Sensor

Cascade Cable (PTCAB01)

SYS

DHW CH

Note: ZC Circulator controlled by SZC5 Zone Panel.

Slave Prestige Boiler

Cascade Slave

ACV
CH1 T-stat 12

CH2 T-stat
34

TriMax Control

Low voltage terminal strip

Outdoor Sensor

DHW Manual Stat/Sens Reset/lmt

Auto Reset/lmt

Modulation Signal + -

System Sensor

Cascade Modbus Master A B G

5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22

Line voltage terminal strip

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Pump

Pump Diverter Valve Diverter Valve Supply

Alarm Contact

LGN LGNLGNLGN LGN 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40

White

Red

Black &

Shielding

DHW CH

Cascade Cable (PTCAB01)

Slave Prestige Boiler

Cascade Slave

ACV
CH1 T-stat 12

TriMax Control

Low voltage terminal strip

CH2 T-stat

Outdoor Sensor

DHW Stat/Sens

Manual Reset/lmt

Auto Reset/lmt

Modulation Signal + -

System Sensor

Cascade Modbus Master A B G

3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22

Line voltage terminal strip

CH2 / Sys Aux Boiler DHW Pump / CH(1) Pump / Power

Pump

Pump Diverter Valve Diverter Valve Supply

Alarm Contact

LGN LGNLGNLGN LGN 23 24 25 26 2728 29 30 31 32 33 34 35 36 37 38 39 40

N G L

Note: Reference Fig. 11, page 32 for cascade piping.

CH

Fig. 12: Split Cascade Wiring

33

Cascade Information

Cascade Information

Navigation: Home Screen>Installer Menu>Cascade>Cascade Information Cascade Information provides real time operating information of the Cascade System. Each line contains an information item followed by its current value. See below for a list of all Cascade Information items.

Cascade Information

Cascade Role System Temp. Active Boilers Total Boilers Cascade Firing Rate

Master 86ºF 0 2 --

System Temperature Logging System Temperature has a logging function which records one sample every 12 minutes to produce a graph of the last 24 hours. Select System Temperature in Cascade Information then press the OK button to view the graph.

System Temp.
194

68 -24.00 -16.00 -8.00 0.00

Cascade Information Items

Information Item
Cascade Role
System Temperature Active Boilers Total Boilers
Cascade Firing Rate

Description
Displays the current role of the Prestige in the Cascade System. Cascade Role will be one of the following: · Master ­ Indicates this Prestige is the Master boiler in the Cascade
System. · Slave ­ Indicates this Prestige is a Slave boiler in the Cascade System. · Standalone ­ Indicates this Prestige is not part of a Cascade System.
Displays the current system temperature reading wired to the Master boiler. If the system sensor is not wired in to the Master boiler,"--" is displayed.
Displays the current number of boilers fired in the Cascade System.
Displays the total number of boilers in the Cascade System.
Displays the current firing rate of the entire Cascade System.

34

Cascade Settings

Cascade Settings
Navigation: Home Screen>Installer Menu>Cascade>Cascade Settings The Cascade Settings menu contains settings related to cascade operation. Each line contains a Cascade Setting followed by its current value. Six Cascade Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional Cascade Settings.
NOTICE

Cascade Setting

Stage Delay

60 sec

Minimum Firing Rate 30%

Maximum Firing Rate 398 MBH

CH/DHW Boilers

0

Automatic Rotation Enabled

CH Proportional Gain

7

Cascade Setting changes must be made on the Cascade Master. Cascade Autodetection must be performed after making any changes to a Cascade Setting before the change will take effect.

Stage Delay

Default: 60 Seconds

Stage Delay sets the time delay before enabling or disabling a boiler in the

Cascade System. The Stage Delay begins once the Master boiler determines that

a boiler must be enabled to reach the setpoint or when the Master boiler deter-

mines a boiler should be disabled because of a decreasing load. Press the LEFT

or RIGHT buttons to adjust the Stage Delay then press the OK button to store 0sec.

the setting. Adjusting the Stage Delay will have the following effects:

· Increase Stage Delay

- Reaching the setpoint could take longer due to a longer delay between enabling boilers.

- Overshooting the setpoint could occur due to boilers staying on longer before being disabled.

· Decrease Stage Delay

- Overshooting the setpoint could occur due to boilers being enabled quicker.

- Boilers will be disabled quicker, possibly increasing boiler cycling and decreasing runtimes.

Stage Delay
60Sec. 255sec.

Minimum Firing Rate

Default: 30%

Minimum Firing Rate is the minimum firing rate of a single boiler in the Cascade

System. The Master boiler uses this setting to determine when boilers can be

enabled and disabled. Setting the Minimum Firing Rate below the recommend-

ed minimum will result in boilers being enabled too quickly which may cause

sharp increases in temperature from the Cascade System. Setting the Minimum

Firing Rate above the recommended minimum will delay the enabling of boilers

which may lower the system efficiency. Press the LEFT or RIGHT buttons to

adjust the Minimum Firing Rate then press the OK button to store the setting.

The minimum recommended settings are:

Prestige Model Solo 60
Solo 110 Natural Gas Solo 110 Propane Gas
Solo 175 Solo 250 Solo 399

Minimum Firing Rate 28% 29% 27% 31% 28% 30%

35

Minimum Firing Rate
30%

0%

100%

Cascade Settings

Boiler Enabling Algorithm The Master boiler uses the following algorithm to determine when the next boiler can be enabled:

Number of Boilers Firing +1 Number of Boilers Firing

x

Minimum

Firing

Rate

=

Individual

Boiler

Firing

Rate

Once the currently fired boilers reach the calculated firing rate, the next boiler can be enabled without affecting the overall cascade firing rate. For example, the calculation for a Cascade System consisting of two PRESTIGE Solo 399s would be:
1 + 1 x 30% = 60% 1
Once the first PRESTIGE Solo 399 firing rate reaches 60%, the second PRESTIGE Solo 399 can be enabled. Both will then fire at the minimum 30% firing rate so that the overall output from the Cascade System remains the same.

Boiler Disabling Algorithm Once the firing rate of all currently fired boilers decreases to the Minimum Firing Rate, a boiler can be disabled. The boilers which continue to fire will increase their firing rate if required to replace the output of the disabled boiler.

NOTICE
Stable cascade operation requires that all boilers in a Cascade System be the same size. Mixing boiler sizes in a Cascade System could lead to temperature fluctuations and erratic cascade operation.

Maximum Firing Rate

Default: 398 MBH

Maximum Firing Rate is the maximum firing rate of a single boiler in the

Cascade System. Press the LEFT or RIGHT buttons to adjust the

Maximum Firing Rate then press the OK button to store the setting. The

recommended settings are:

Maximum Firing Rate
398 MBH

Prestige Model Solo 60
Solo 110 Natural Gas Solo 110 Propane Gas
Solo 175 Solo 250 Solo 399

Maximum Firing Rate 57 MBH 109 MBH 95 MBH 170 MBH 245 MBH 398 MBH

0MBH

869MBH

NOTICE
Stable cascade operation requires that all boilers in a Cascade System be the same size. Mixing boiler sizes in a Cascade System could lead to temperature fluctuations and erratic cascade operation.

36

Cascade Settings

CH/DHW Boilers

Default: 0

The CH/DHW Boilers setting specifies how many boilers in a Split

Cascade System will respond to a domestic hot water call. The CH/DHW

Boilers always include the Master boiler. The remaining boilers will only

respond to central heating calls. This allows the Cascade System to sat-

isfy both central heating and domestic hot water calls at the same time. At the completion of a domestic hot water call, the CH/DHW Boilers will

0

again be available to respond to central heating calls. Press the LEFT or

RIGHT buttons to adjust the CH/DHW Boilers setting then press the

OK button to store the setting.

CH/DHW Boilers
0 6

NOTICE
Splitting the Cascade System into CH only and CH/DHW boilers requires the boilers to be piped as shown in Figure 11, page 32. The CH/DHW boilers must be piped to both CH and DHW loads directly for proper operation.
NOTICE
DHW Priority must be set to Enabled in DHW Settings of the Cascade Master for proper operation.

NOTICE
All CH/DHW Boilers will respond to a domestic hot water call. It is important that the domestic load is capable of transferring all of the heat generated to prevent excessive boiler cycling.

Automatic Rotation

Default: Enabled

Automatic Rotation allows the lead stage automatic rotation function to

be disabled. Press the UP or DOWN buttons to select Enabled or

Disabled then press the OK button to store the setting.

Automatic Rotation
Enabled Disabled

· Enabled ­ The lead boiler automatically rotates every time a call for heat is received when a Switch option is chosen in CH Demand or every 24 hours when a Constant option is chosen in CH Demand.
· Disabled ­ The lead boiler is always the Master boiler followed by each Slave boiler.

37

Cascade Settings

CH Proportional Gain

Default: 7

CH Proportional Gain allows the cascade response to be adjusted for a cen-

tral heating call. CH Proportional Gain has the greatest influence when the

system temperature is far away from the setpoint. Press the LEFT or

RIGHT buttons to adjust the CH Proportional Gain then press the OK

button to store the setting.

1

· Increase CH Proportional Gain

- The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.

- To reach the setpoint faster, increase the CH Proportional Gain value by 2. Perform Cascade Autodetection and initiate a central heating call. Observe the cascade response and make further adjustments if necessary.

· Decrease CH Proportional Gain

- The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized.

- If the setpoint is reached too quickly, decrease the CH Proportional Gain value by 2. Perform Cascade Autodetection and initiate a central heating call. Observe the cascade response and make further adjustments if necessary.

CH Proportional Gain
7 255

NOTICE
Only make adjustments to this setting after consulting ACV-Triangle Tube Technical Support. Improper adjustment of CH Proportional Gain could lead to temperature fluctuations and erratic cascade operation.

CH Integral Gain

Default: 245

CH Integral Gain allows the cascade response to be adjusted for a central

heating call. CH Integral Gain has the greatest influence when the system

temperature is close to the setpoint. Press the LEFT or RIGHT buttons to

adjust the CH Integral Gain then press the OK button to store the setting.

1

· Increase CH Integral Gain

- The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized.

- If the setpoint is reached too quickly, increase the CH Integral Gain value by 2. Perform Cascade Autodetection and initiate a central heating call. Observe the cascade response and make further adjustments if necessary.

· Decrease CH Integral Gain

- The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.

CH Integral Gain
245 255

38

Cascade Settings
- To reach the setpoint faster, decrease the CH Integral Gain value by 2. Perform Cascade Autodetection and initiate a central heating call. Observe the cascade response and make further adjustments if necessary.

NOTICE
Only make adjustments to this setting after consulting ACVTriangle Tube Technical Support. Improper adjustment of CH Integral Gain could lead to temperature fluctuations and erratic cascade operation.

DHW Proportional Gain

Default: 7

DHW Proportional Gain allows the cascade response to be adjusted for a

domestic hot water call. DHW Proportional Gain has the greatest influ-

ence when the system temperature is far away from the setpoint. Press

the LEFT or RIGHT buttons to adjust the DHW Proportional Gain then

press the OK button to store the setting.

DHW Proportional Gain

7

1

255

· Increase DHW Proportional Gain
- The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.
- To reach the setpoint faster, increase the DHW Proportional Gain value by 2. Perform Cascade Autodetection and initiate a domestic hot water call. Observe the cascade response and make further adjustments if necessary.
· Decrease DHW Proportional Gain
- The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized.
- If the setpoint is reached too quickly, decrease the DHW Proportional Gain value by 2. Perform Cascade Autodetection and initiate a domestic hot water call. Observe the cascade response and make further adjustments if necessary.

NOTICE
Only make adjustments to this setting after consulting ACVTriangle Tube Technical Support. Improper adjustment of DHW Proportional Gain could lead to temperature fluctuations and erratic cascade operation.

39

Cascade Settings

DHW Integral Gain

Default: 245

DHW Integral Gain allows the cascade response to be adjusted for a

domestic hot water call. DHW Integral Gain has the greatest influence

when the system temperature is close to the setpoint. Press the LEFT or

RIGHT buttons to adjust the DHW Integral Gain then press the OK but-

ton to store the setting.

1

DHW Integral Gain
245 255

· Increase DHW Integral Gain
- The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized.
- If the setpoint is reached too quickly, increase the DHW Integral Gain value by 2. Perform Cascade Autodetection and initiate a domestic hot water call. Observe the cascade response and make further adjustments if necessary.
· Decrease DHW Integral Gain
- The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.
- To reach the setpoint faster, decrease the DHW Integral Gain value by 2. Perform Cascade Autodetection and initiate a domestic hot water call. Observe the cascade response and make further adjustments if necessary.

NOTICE
Only make adjustments to this setting after consulting ACVTriangle Tube Technical Support. Improper adjustment of DHW Integral Gain could lead to temperature fluctuations and erratic cascade operation.

40

Modbus Interface

Modbus Interface The Modbus Interface allows a Building Management System (BMS) to directly connect to the Prestige. A BMS can read information from the boiler to determine its operating state, lockout status, sensor readings, etc. A BMS can also operate the boiler by providing a setpoint.

Table 6: Modbus Configuration

Protocol

MODBUS RTU

Baud Rate

38400bps

Data Length

8

Parity

None

Stop Bits

1

Physical Layer

RS485 (2 wire)

DEC 03 04 06 16 17

Table 7: Supported Commands

HEX

Description

0x03

Read Holding Registers

0x04

Read Input Registers

0x06

Write Single Register

0x10

Write Multiple Registers

0x11

Report Slave ID

Address DEC (HEX)
512 (0x0200)

Table 8: Holding Registers (Read/Write)

Supported Commands
0x03 0x06 0x10

Description CH Demand

Byte:Format

Notes

MB:U8

Writing 0= Modbus CH1 Demand has priority over a DHW call 255 = DHW call has priority over a Modbus CH1 Demand

LB:U8

Reading 0 = No CH Calls Present 255 = CH1 or CH2 Call Present

513 (0x201) 514 (0x202) 1280 (0x0500) 1281 (0x0501)

0x03 0x06 0x10
0x03 0x06 0x10 0x03
0x03

Maximum Firing Rate
CHSetpoint
CH1 Maximum Setpoint
DHW Storage Setpoint

LB:U8 LB:U8 LB:U8 LB:U8

Writing 0 = End CH1 Demand 255= Begin CH1 Demand A CH1 Demand lasts for 30 seconds from the last successful write.
Value = Maximum Firing Rate % This register becomes active when 255 is written to register 512 (0x0200)
Value = CH Setpoint °C This register becomes active when 255 is written to register 512 (0x0200)
Value = °C
Value = °C

41

Modbus Interface

Address DEC (HEX) 0 (0x0000)
1 (0x0001)
2 (0x0002)
768 (0x0300)
769 (0x0301) 770 (0x0302) 771 (0x0303) 772 (0x0304) 773 (0x0305) 774 (0x0306) 775 (0x0307) 776 (0x0308)

Table 9: Input Registers (Read Only)

Supported Commands
0x04
0x04

Description Boiler Status
Lockout Status

Byte:Format

Notes

LB: Flag8 MB: Flag8

Bit: Description 0: PC Manual Mode 1: DHW Mode 2: CH Mode 3: Freeze Protection Mode 4: Flame Present 5: CH(1) Pump 6: DHW Pump 7: System / CH2 Pump 0 = Off, 1 = On
Bit: Description 1: Lockout Code Type 0 = Automatic Reset Lockout 1 = Manual Reset Lockout

0x04

Lockout Status

LB:U8 LB:U8

Value = Lockout Code
0 = Single / Master Boiler 1 = Slave 1 2 = Slave 2 3 = Slave 3 4 = Slave 4 5 = Slave 5 F = Single / Master Display

0x04
0x04 0x04 0x04 0x04 0x04

Boiler Supply Temperature / System Temperature
Boiler Return Temperature DHW Storage Temperature Boiler Flue Temperature Outdoor Temperature
Future Use

S16
LB:S8 LB:S8 LB:S8 LB:S8 LB:U8

Value = 0.1°C Invalid Value = 32768 (0x8000) Value is the Boiler Supply Temperature unless the System Temperature Sensor is installed
Value = °C Invalid Value = 65472 (0xFFC0)
Value = °C Invalid Value = 32768 (0x8000)
Value = °C Invalid Value = 65472 (0xFFC0)
Value = °C Invalid Value = 32768 (0x8000)

0x04 0x04 0x04

Flame Ionization Current
Boiler / Cascade Firing Rate
Boiler Setpoint

LB:U8 Value = Flame Current µA

LB:U8 Value = Firing Rate %

LB:U8

Value = °C Invalid Value = 32768 (0x8000)

42

Manual Operation

Manual Operation
Navigation: Home Screen>Installer Menu>Manual Operation The Manual Operation Screen allows the burner and circulators to be manually enabled for testing.
Fan Press the OK button while the FAN icon is highlighted to manually fire the burner and power the CH (1) circulator. Press the LEFT and RIGHT buttons to adjust the firing rate from 1 % (Low Fire) to 100% (High Fire). Hold down the LEFT or RIGHT buttons to rapidly increase or decrease the firing rate. Press the OK button again while the FAN icon is highlighted to shutdown the burner when finished.
NOTICE
An adequate CH load must be present to dissipate the heat generated while the burner is manually fired. If an adequate CH load is not available, an indirect water heater can be used to dissipate the heat by creating a domestic hot water call which will enable the DHW circulator.
CH CH1 Press the OK button while the CH CH1 icon is highlighted to manually power the CH (1) circulator. Press the OK button again while the CH CH1 icon is highlighted to shutdown the CH (1) circulator.
NOTICE
The Auxiliary Boiler circulator is also powered when the CH (1) circulator is manually enabled.
DHW Press the OK button while the DHW icon is highlighted to manually power the DHW circulator. Press the OK button again while the DHW icon is highlighted to shutdown the DHW circulator.
NOTICE
The Auxiliary Boiler circulator is also powered when the DHW circulator is manually enabled.
SYS CH2 Press the OK button while the SYS CH2 icon is highlighted to manually power the System circulator. Press the OK button again while the SYS CH2 icon is highlighted to shutdown the System circulator.

Manual Operation

FAN
CH CH1 DHW
SYS CH2

Released
O O O

Manual Operation

FAN
CH CH1 DHW SYS CH2

Released
O O O

Manual Operation

Released
FAN

CH

O

CH1

O

DHW

SYS

O

CH2

Manual Operation

FAN
CH CH1
DHW SYS CH2

Released
O O O

43

Additional quality water heating equipment available from ACV- Triangle Tube
MAXI-FLO AND SPA HEAT EXCHANGERS
- Construction of high quality corrosion resistant stainless steel (AISI 316) or titanium
- Specially designed built-in flow restrictor to assure maximum heat exchange
- Compact and light weight - Available in 8 sizes that can accommodate any size pool
or spa
SMART INDIRECT FIRED WATER HEATERS
- Exclusive tank-in-tank design - Stainless steel construction - Available in 7 sizes - Limited LIFETIME residential warranty - 6 year Limited commercial warranty - Self cleaning/self descaling design
TTP BRAZED PLATE HEAT EXCHANGERS
- For domestic water, snow melting, radiant floor, refrigeration - Plates made of stainless steel, with a 99.9 % copper and
brazed, ensuring a high resistance to corrosion - Self cleaning and self descaling - Computerized sizing available from ACV- Triangle Tube - Available in capacities from 25,000 BTU/hr to 5,000,000
BTU/hr
Triangle Tube - 1 Triangle Lane - Blackwood, NJ 08012 - Tel: (856) 228 8881 - Fax: (856) 228 3584 E-mail: sales@triangletube.com


QuarkXPress(R) 9.5 QuarkXPress(R) 9.5