Technical Manuals Water - Queensland Urban Utilities
WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual QUEENSLAND URBAN UTILITIES WATER BOOSTER PUMP STATION WB065 SEIB STREET KILCOY ________________________________ WATER BOOSTER PUMP STATION OPERATION AND MAINTENANCE MANUAL JPR REFERENCE NUMBER: C63100 Developed by: J & P RICHARDSON INDUSTRIES CAMPBELL AVENUE WACOL QLD 4076 ABN 23 001 952 325 ACN 001 952 325 Ph. (07) 3271 2911 Fax. (07) 3271 3623 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual WATER BOOSTER PUMP STATION OPERATIONS AND MAINTENANCE MANUAL FOR QUEENSLAND URBAN UTILITIES WATER BOOSTER PUMP STATION WB065 SEIB STREET, KILCOY REVISION CONTROL Version 0 Author Ben Aitcheson Issue Purpose Draft Issue Signature Date 18/02/14 Reviewed by Version Author 0 Darren Wedley Position Project Manager Signature Date 18/02/14 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 2 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CONTENTS 1 Electrical Equipment Technical Information 1.1. CIRCUIT BREAKERS & ISOLATORS 1.2. CONTROL DEVICES 1.3. PUSHBUTTONS & SELECTOR SWITCHES 1.4. POWER SUPPLIES, GPOS, PLUGS & SOCKETS 1.5. SURGE PROTECTION & FUSES 1.6. RTU & RADIO 1.7. TERMINALS, LINKS & OTHER ACCESSORIES 2 Pumps 3 Valves 4 Flowmeter 5 Generator 6 Test Results 7 "AS INSTALLED" Drawings 8 Service and Maintenance Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 3 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1 Electrical Equipment Technical Information 1.1 CIRCUIT BREAKERS & ISOLATORS 1.2 CONTROL DEVICES 1.3 PUSHBUTTONS & SELECTOR SWITCHES 1.4 POWER SUPPLIES, GPOs, PLUGS & SOCKETS 1.5 SURGE PROTECTION & FUSES 1.6 RTU & RADIOS 1.7 TERMINALS, LINKS & OTHER ACCESSORIES C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 4 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.1. CIRCUIT BREAKERS & ISOLATORS TERASAKI E125-NJ 63A 63A 3P Moulded Case Circuit Breaker TERASAKI DSRCBH-16-30A 10kA 1P 6A 30mA RCD TERASAKI DTCB10104C 10kA 1P 4A "C" curve Circuit Breaker TERASAKI DTCB10106C 10kA 1P 6A "C" curve Circuit Breaker TERASAKI DTCB15332C+DTLDC 10kA 3P 32A "D" curve Circuit Breaker + Captive Lock Dog C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 5 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MCCB's Thermal magnetic type E125NJ 25kA Current rating: 12.5 125A Approvals and Tests: Standards AS/NZS 3947-2, and IEC60947-2 Interrupting capacity: Voltage AC use 380/415 DC use 250V Icu Ics 25 19 25 19 Trip unit: Adjustable thermal (0.63 Ir to 100% Ir) and adjustable magnetic (6 Im to 12 Im) Dimensions (mm) Poles H W D (less toggle) Toggle cut-out 3 155 90 68 Standard DIN Ampere Rating NRC Adj. Ir 1) Min - Max. Adj. Im 1) Min - Max. 20 12.5 - 20 120 - 240 32 20 - 32 192 - 384 50 32 - 50 300 - 600 63 40 - 63 378 - 756 100 63 - 100 600 - 1200 125 80 - 125 750 - 1500 1) NRC: Adj. Ir: Adj. Im: Nominal rated current Adjustable thermal setting Adjustable magnetic setting Cat. No. E125 NJ 3 20 E125 NJ 3 32 E125 NJ 3 50 E125 NJ 3 63 E125 NJ 3 100 E125 NJ 3 125 Replaces: XS125CJ, Note: check exact ratings or dimenions to suit your application requirement Price Schedule T2 Q-Pulse Id: TMS1594 Active: 18/04/2016 6 Page 6 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs OPERATING CHARACTERISTICS THERMAL MAGNETIC PROTECTION Adjustment Dials SECTION 3 1. IR is the thermal element adjustment dial and is used to set the rated current to match the conductor rating. IR can be set between 0.63 and 1.0 times In. 2. Ii is the magnetic element adjustment dial and is used to set the short circuit tripping threshold to suit the application. Ii can be set between 6 and 12 times In on 125A and 400A frame models. Ii can be set between 6 and 13 times In on 250A frame models with ratings of 160A, 200A and 250A. Ii can be set between 6 and 12 times In on 250A frame models with ratings of 125A and less. Models, Types and Rated Currents of Thermal Elements Model S125 E125 S125 S125 H125 L125 S160 S160 S160 H160 L160 E250 S250 S250 H250 L250 E400 S400 S400 S400 H400 L400 Type -NF -NJ -NJ -GJ -NJ -NJ -NF -NJ -GJ -NJ -NJ -NJ -NJ -GJ -NJ -NJ -NJ -CJ -NJ -GJ -NJ -NJ Current Rating In (A) 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 20, 32, 50, 63, 100, 125, 160 50, 63, 100, 125, 160 160 160 20, 32, 50, 63, 100, 125, 160, 200, 250 160, 200, 250 160, 200, 250 160, 250 160, 250 250, 400 250, 400 250, 400 250, 400 250, 400 250, 400 Beyond the StandardTM page 23 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 7 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs OPERATING CHARACTERISTICS THERMAL MAGNETIC CHARACTERISTICS 125A Frame MCCBs SECTION 3 Q-Pulse Id: TMS1594 Beyond the StandardTM Active: 18/04/2016 page 25 Page 8 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY (DISCRIMINATION) AND CASCADE Selectivity The principle of Selectivity (Discrimination) is based upon an analysis of several circuit breaker characteristics. These include time-current (tripping) curves, peak-let-through current (Ipeak) and energy let-through (I2t). The figures stated give the maximum selectivity level with the two nominated breakers in series under short-circuit conditions. For an indication on selectivity under overloads refer to the circuit breaker tripping/characteristic curves, or use the NHP TemCurve selectivity analysis software package. Selectivity can be enhanced beyond the breaking capacity of the downstream breaker provided it is backed up by an appropriately selected upstream breaker, which should not trip (unlatch) under the stated short circuit current. Cascade Cascading is achieved by using an upstream device to assist (back-up) a downstream device in clearing a fault current. This principal is necessary should the downstream device be required to clear a prospective short circuit current greater than the devices' breaking capacity. In most cascading applications it is generally necessary for the upstream breaker to trip (unlatch), as well as the downstream breaker to give adequate back-up protection. As such, cascade is commonly used in feeding and protecting non-essential loads, such as basic lighting. For more information on selectivity and cascading please refer to the latest NHP Part C catalogue. SECTION 4 page 44 Beyond the StandardTM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 9 of 1068 Page 10 of 1068 Active: 18/04/2016 Q-Pulse Id: TMS1594 page 45 Beyond the StandardTM S250PE H250NE S400NE S400GE H400NE L400NE E630NE S630CE S630GE TL630NE XS800SE XH800SE TL800NE XS1250SE TL1250NE XS1600SE XS2000NE XS2500NE Selectivity & Cascade Tables @ 400 / 415 V Upstream MCCBs Downstream kA MCCBs (RMS) 70 125 50 E125NJ 25 25/25 25/65 25/36 S125NJ 36 36/36 36/85 36/50 S125GJ 65 65/65 65/125 50/50 H125NJ 125 70/70 125/125 50/50 S160NJ 36 36/50 S160GJ 65 50/50 H160NJ 125 E250NJ 25 S250NJ 36 S250GJ 65 S250PE 70 H250NJ 125 H250PE 125 E400NJ 25 S400CJ 36 S400NE 50 S400NJ 50 S400GJ 70 H400NJ 125 H400NE 125 E630NE 36 E630CE 50 S630GE 70 XS630CJ 45 XS630NJ 65 XS630PJ 85 XS630SE 50 XH630SE 65 XH630PE 65 XS800NJ 65 XS800SE 50 XJ800PJ 85 XH800SE 65 XH800PE 65 XS1250SE 65 XS1600SE 85 70 125 200 36 25/50 25/65 25/85 25/36 36/65 36/85 36/125 36/36 65/70 65/125 65/150 36/36 70/70 125/125 125/200 36/36 36/65 36/85 36/125 36/36 65/70 65/125 65/150 36/36 125/125 125/200 36/36 25/65 25/85 25/36 36/85 36/125 36/36 65/125 65/150 36/36 40/125 70/150 36/36 125/125 125/200 36/36 125/125 125/200 36/36 10/25 10/36 10/36 10/36 10/36 10/36 10/36 50 25/25 36/36 50/50 50/50 36/50 50/50 50/50 25/25 36/36 50/50 50/50 50/50 50/50 10/25 10/36 10/50 10/36 10/50 10/50 10/50 SECTION 4 XX / YY Selectivity/ Cascade 70 25/50 36/65 65/70 70/70 36/50 65/70 70/70 25/50 36/65 65/70 70/70 70/70 70/70 10/50 10/65 10/50 10/70 10/70 10/70 10/70 125 25/25 36/36 65/65 70/70 36/36 65/65 70/70 25/25 36/36 65/65 70/70 70/70 70/70 10/36 10/50 10/50 10/65 10/70 10/70 10/70 50 25/36 36/50 65/50 50/50 36/36 50/50 50/50 25/25 36/36 50/50 50/50 50/50 50/50 25/25 25/36 25/50 25/50 25/50 25/50 25/50 25/36 25/50 65 25/36 36/36 65/65 65/65 36/65 50/65 50/65 25/50 36/36 50/65 50/65 50/65 50/65 25/25 25/36 25/50 25/50 25/50 25/65 25/65 25/36 25/50 125 85 125 100 85 85 25/65 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 65/65 65/65 65/65 65/65 65/65 65/65 65/65 85/50 85/50 100/100 85/85 85/85 36/65 36/36 36/36 36/36 36/36 36/36 50/65 65/65 65/65 65/65 65/65 65/65 50/65 85/65 85/65 100/100 85/85 85/85 25/50 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 50/65 65/65 65/65 65/65 65/65 65/65 50/65 70/70 70/70 70/70 70/70 70/70 50/65 85/85 85/85 100/100 85/85 85/85 50/65 85/85 85/85 100/100 85/85 85/85 25/36 25/25 25/25 25/36 25/25 25/25 25/50 36/36 36/36 36/50 36/36 36/36 25/50 50/50 50/50 50/50 50/50 50/50 25/65 50/50 50/50 50/65 50/50 50/50 25/65 70/36 70/36 70/85 70/70 70/70 25/65 125/85 125/85 125/100 125/85 125/85 25/65 125/85 125/85 125/100 125/85 125/85 25/36 36/36 36/36 36/36 36/36 36/36 25/50 50/50 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 30/45 30/45 30/45 35/45 35/45 30/65 30/65 30/65 35/65 36/65 30/85 30/85 30/85 35/85 35/85 30/65 30/65 30/85 30/85 30/85 30/65 30/65 30/85 30/85 30/85 30/65 30/65 30/85 30/85 30/85 15/65 15/65 20/65 35/65 35/65 15/50 15/50 20/50 35/50 35/50 15/85 15/85 20/85 35/85 35/85 15/65 15/65 20/65 35/65 35/65 15/65 15/65 20/65 35/65 35/65 20/65 35/65 35/65 35/85 35/85 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY TABLES WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA CASCADE TABLES L250NJ H250NE H250NJ S250PE S250GJ S250NJ E250NJ L160NJ H160NJ S160GJ S160NJ L125NJ H125NJ S125GJ S125NJ E125NJ SECTION 4 CASCADE @ 380 415 V AC 1) Downstream kA MCCBs (RMS) 25 36 65 125 200 36 65 125 200 25 36 65 70 125 125 200 E125NJ S125NJ S125GJ H125NJ S160NJ S160GJ H160NJ S250NJ S250GJ S250PE H250NJ E400NJ S400CJ S400NJ S400GJ H400NJ 25 36 36 65 85 36 36 65 85 36 36 65 65 85 36 50 85 125 50 85 125 85 85 125 65 125 150 125 150 65 125 125 150 125 200 - 200 65 200 36 65 65 85 125 65 65 85 85 125 65 125 150 70 125 125 150 125 200 - 200 36 65 65 85 85 125 65 70 125 125 150 70 125 125 150 125 200 25 36 65 65 36 50 70 70 50 50 65 85 85 70 50 125 125 125 Note: 1) Ratings have not been verified where a dash "" is shown. All pick-up and time delay settings are to be set at a maximum for upstream MCCB's Upstream MCCBs XS1600SE XS1250SE TL800NE XH800SE XS800NJ XS800SE TL630NE S630GE S630CE E630NE L400NE L400NJ H400NJ H400NE S400GE S400GJ S400NE S400NJ S400CJ CASCADE @ 380 415 V AC 1) Downstream kA MCCBs (RMS) 36 50 70 125 200 200 36 50 70 125 65 65 65 200 65 85 E125NJ S125NJ S125GJ H125NJ S160NJ S160GJ H160NJ E250NJ S250NJ S250GJ S250PE H250NJ E400NJ S400CJ S400NJ S400GJ H400NJ 25 36 36 50 65 85 85 36 - 50 36 36 36 36 50 65 85 125 125 - 65 50 50 65 70 125 150 150 50 70 65 125 200 200 - 65 50 36 50 65 85 125 125 50 50 65 65 65 70 125 150 150 70 125 200 200 65 65 25 36 36 50 65 85 85 36 50 36 50 36 50 65 85 125 125 65 65 65 70 125 150 150 70 70 125 150 150 125 200 200 - 25 36 36 50 65 85 85 36 50 36 36 36 36 50 65 70 100 100 65 50 50 50 50 70 85 125 125 36 70 65 50 65 65 70 125 150 150 36 50 36 85 125 200 200 Note: 1) Ratings have not been verified where a dash "" is shown. All pick-up and time delay settings are to be set at a maximum for upstream MCCBs page 46 Beyond the StandardTM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 11 of 1068 SECTION 4 H400NJ S400GE S400GJ S400CJ S250GJ S250NJ H125NJ S125GJ S125NJ E125NJ WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY AND CASCADE TEMBREAK 2 MCCBs AND DIN-T / SAFE-T MCBs Upstream MCCB SELECTIVITY / CASCADE @ 415 V AC Downstream MCB DTCB6 DTCB10 DSRCBH / DSRCD Din-T10H DTCH15 Safe-T SRCB Amp rating 2 20 25 63 0.5 32 40 63 0.5 32 40 80 125 0.5 32 40 63 16 20 16 20 kA (RMS) 25 36 65 36 65 36 70 125 6 18/18 25/25 35/35 35/35 35/35 6 18/18 20/25 20/25 30/30 30/30 10 18/18 30/30 30/50 35/35 40/50 35/35 40/50 40/50 10 18/18 20/25 25/25 30/30 30/30 30/30 30/30 30/30 10 18/18 30/30 30/50 35/35 40/50 35/35 40/50 40/50 10 18/18 20/25 25/25 30/30 30/30 30/30 30/30 30/30 10 4/18 4/25 4/25 15/15 15/15 10/10 10/10 15 18/18 30 30/50 35/35 40/50 35/35 40/50 40/50 15 18/18 20 25/25 30/30 30/30 30/30 30/30 30/30 6 3/10 3/10 3/10 6 3/10 3/10 3/10 Guide XX / YY Selectivity Cascade Notes: All figures stated are at 400/415 V AC. Q-Pulse Id: TMS1594 Beyond the StandardTM page 47 Active: 18/04/2016 Page 12 of 1068 SECTION 4 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 1 CO-ORDINATION TABLES Short-Circuit Co-Ordination Motor Starting Table Type `1' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 50/65 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 1 50/65 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 5 0 10 32 60 00 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 S125GJ/20 S125GJ/20 S125GJ/32 S125GJ/50 S125GJ/50 S125GJ/63 S125GJ/100 S125GJ/100 S125GJ/125 S125GJ/125 S250PE/250 S250PE/250 S250PE/250 S400GE/400 S400GE/400 S400GE/400 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-210 CA6-300 CA6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB MCCB's can be replaced with S125GJ/20 if required. · Combinations based on the thermal overload relay tripping before the circuit. breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1.0A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25S-2.5A KTA7-25S-4.0A KTA7-25S-6.3A KTA7-25S-6.3A KTA7-25S-10A KTA7-25H-16A KTA7-25H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A KTA3-160S-100A KTA3-160S-160A KTA3-160S-160A KTA3-250S-200A KTA3-250S-250A KTA3-400S-320A KTA3-400S-400A Contactor CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-250 CA6-300 CA6-420 page 48 Beyond the StandardTM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 13 of 1068 SECTION 4 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION TABLES Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 50/65 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 50/65 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 S125GJ/20 S125GJ/20 S125GJ/32 S125GJ/50 S125GJ/50 S125GJ/63 S125GJ/100 S125GJ/100 S125GJ/125 S250PE/160 S250PE/250 S250PE/250 S250PE/250 S400PE/400 S400PE/400 S400PE/400 CA7-9 CA7-9 CA7-9 CA7-16 CA7-16 CA7-16 CA7-30 CA7-30 CA7-30 CA7-30 CA7-30 CA7-43 CA7-43 CA7-43 CA7-72 CA7-72 CA6-105 CA6-105 CA6-140 CA6-170 CA6-210 CA6-210 CA6-300 CA6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB combinations can be replaced with S125GJ/20 and CA7-30 if required. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25S-2.5A KTA7-25S-4A KTA7-25S-6.3A KTA7-25S-6.3A KTA7-25S-10A KTA7-25H-16A KTA7-25H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A KTA3-160S-100A KTA3-160S-160A KTA3-160S-160A KTA3-250S-200A KTA3-250S-250A KTA3-400S-320A KTA3-400S-400A Contactor CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-250 CA6-300 CA6-420 Q-Pulse Id: TMS1594 Beyond the StandardTM page 49 Active: 18/04/2016 Page 14 of 1068 SECTION 4 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 85 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 85 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 H125NJ/20 H125NJ/20 H125NJ/32 H125NJ/50 H125NJ/50 H125NJ/63 H125NJ/100 H125NJ/100 H125NJ/160 H160NJ/160 H250PE/250 H250PE/250 H250PE/250 H400NE/400 H400NE/400 H400NE/400 CA 7-9 CA 7-9 CA 7-9 CA 7-16 CA 7-16 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-43 CA 7-43 CA 7-43 CA 7-72 CA 7-72 CA 6-105 CA 6-105 CA 6-210 CA 6-210 CA 6-210 CA 6-210 CA 6-300 CA 6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB combinations can be replaced with H125GJ/20 and CA7-30 if required. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25H-2.5A KTA7-25H-4A KTA7-25H-6.3A KTA7-25H-6.3A KTA7-25H-10A KTA7-45H-16A KTA7-45H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A - Contactor CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-12 CA 7-16 CA 7-23 CA 7-30 CA 7-37 CA 7-43 CA7-60 CA7-72 CA7-85 - page 50 Beyond the StandardTM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 15 of 1068 SECTION 4 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 100 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 100 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/32 H125NJ/50 H125NJ/50 H125NJ/63 H125-NJ/100 H125-NJ/100 H125-NJ/125 H250-NE/160 H250-NE/250 H250-NE/250 H250-NE/250 H400-NE/400 H400-NE/400 H400-NE/400 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-43 CA 7-43 CA 7-43 CA 7-60 CA 7-72 CA 7-85 CA 6-95 CA 6-140 CA 6-140 CA 6-180 CA 6-420 CA 6-420 CA 6-420 Notes: · Thermal or electronic overload relays may be used. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25H-2.5A KTA7-25H-4A KTA7-25H-6.3A KTA7-25H-6.3A KTA7-25H-10A KTA7-45H-16A KTA7-45H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A - Contactor CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-12 CA 7-16 CA 7-23 CA 7-30 CA 7-37 CA 7-43 - Q-Pulse Id: TMS1594 Beyond the StandardTM page 51 Active: 18/04/2016 Page 16 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs INSTALLATION INSULATION DISTANCE IN mm (AT 440V AC MAXIMUM) Model E125 S125 S125 S125 H125 L125 S160 S160 S160 H160 L160 E250 S250 S250 S250 H250 H250 L250 E400 S400 S400 S400 S400 H400 H400 L400 L400 E630 S630 S630 Type A B1 B2 C NJ 50 10 10 0 NF 50 10 10 0 NJ 50 10 10 0 GJ 75 45 25 0 NJ 100 80 60 0 NJ 100 80 60 0 NF 50 40 30 0 NJ 50 40 30 0 GJ 100 80 60 0 NJ 100 80 60 0 NJ 100 80 60 0 NJ 50 40 30 0 NJ 50 40 30 0 GJ 100 80 30 0 PE 100 80 60 0 NJ 100 80 60 0 NE 100 80 60 0 NJ 100 80 60 0 NJ 100 80 40 0 CJ 100 80 40 0 NJ 100 80 40 0 GJ 100 80 40 0 GE 100 80 40 0 NJ 120 120 80 0 NE 120 120 80 0 NJ 120 120 80 0 NE 120 120 80 0 NE 120 100 80 0 CE 120 100 80 0 GE 120 100 80 0 D E 25 *(1) 25 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 50 *(1) 25 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 50 *(1) 50 *(1) 30 *(1) 30 *(1) 30 *(1) 30 *(1) 30 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) *Note: (1) Insulate the exposed conductor until it overlaps the moulded case at the terminal, or the terminal cover. SECTION 6 page 78 Beyond the StandardTM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 17 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs INSTALLATION TEMPERATURE RATINGS & DERATINGS Calibration Temperature: 45°C MCCB Type E125-NJ S125-NJ S125-GJ Connection Type Front Rear Plug-in H125-NJ L125-NJ Front Rear Plug-in S160-NJ S160-GJ Front Rear Plug-in H160-NJ L160-NJ E250-NJ Front Rear Plug-in Front Rear Plug-in E250-NJ S250-NJ S250-GJ H250-NJ L250-NJ E400-NJ S400-CJ S400-NJ S400-GJ H400-NJ L400-NJ Front Rear Plug-in Front Rear Plug-in Front Rear Front Rear Plug-in Front Rear Plug-in Rating at calibration temperature (50°C) 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 160A 160A 20A 32A 50A 63A 100A 125A 160A 250A 160A 250A 250A 400A 250A 400A 250A 400A Calibration Temperature: 30°C MCCB Type H250-NJ L250-NJ Connection Type Plug-in Conn. Rating at calibration temperature (30°C) 250A Rated Current (A) 50°C 55°C 60°C 19 18.5 18 31 30.5 30 48 45 43 60 57 55 97 94 90 121 117 113 19 18.5 18 31 30 29 48 47 45 61 59 57 97 95 92 121 118 114 19 18.5 18 31 30 29 48 46 44 61 59 57 97 94 91 121 117 113 156 151 146 156 151 147 19 18.5 18 31 30 29 48 46 44 61 59 57 97 94 91 121 117 113 156 151 146 243 235 227 65°C 17.5 29 41 52 87 109 17.5 28 44 55 89 111 17.5 28 42 55 88 109 141 143 17.5 28 42 55 88 109 141 219 156 151 147 143 244 237 230 223 244 237 230 223 390 380 369 358 243 237 230 223 390 381 371 361 243 237 231 224 392 384 376 368 Rated Current (A) 35°C 40°C 45°C 244 236 225 50°C 55°C 219 209 60°C 65°C 200 190 SECTION 6 MCCB Type S250-PE H250-NE S400-NE S400-GE H400-NE L400-NE Connection Type Front Rear Plug-in Front Rear Plug-in Front Rear Plug-in E630-NE S630-CE S630-GE Front Rear* Rating 250A 250A 250A 400A 250A 400A 250A 400A 630A Q-Pulse Id: TMS1594 30°C 250 35°C 250 40°C 250 Rated Current (A) 45°C 50°C 55°C 250 237.5 225 250 237.5 225 225 200 200 250 250 250 250 250 250 400 400 400 400 400 380 250 250 250 250 400 400 400 400 250 250 250 250 400 400 400 400 630 630 630 630 250 400 250 400 598.5 250 380 250 380 598.5 60°C 200 157.5 225 360 225 360 225 360 567 65°C 200 157.5 200 320 200 320 200 320 504 Beyond the StandardTM page 81 Active: 18/04/2016 Page 18 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs DIMENSIONS E125-NJ, S125-NJ, S125-GJ SECTION 7 8.5(max.) 132 17 8.5 154±1 3P 4P Interpole barrier (removable) Mounting hole 47 HL HL Operating knob CL 154 Front panel t2 24 M8 screw Preparation of conductor ø9 17(max.) max.t5 Drilling plan 3P 4P HL HL 155 134 60 14.5 21.5 90 90 30 30 30 45 75 10 Connector plug 45 8 61 45 106 5.5 164.5 28(max.) M4x0.7 Mounting screw 30 30 M4x0.7 Tapped hole Panel hinge position (hatching area) bottom view HL 100 150 200 100 150 200 90 86 HL 154 Operating knob Front panel t2 Mounting plate (max. t3.2) Drilling plan 3P 4P HL HL 103.5 Panel cutout (Front view) 4P 3P HL 5 132 134 R1 155 8 61 134 155 148 CL 15 Conductor CL overlap max. 16 Pad lock Connector plug 45 ø8.5 15 15 61 52 106 102 30 30 30 Stud can be turned 45°or 90° M4X0.7 Mounting screw 30 60 5.5 164.5 28(max.) CL 30 30 30 30 ø18 M4X0.7 Tapped hole 45 90 Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon. Q-Pulse Id: TMS1594 Beyond the StandardTM page 85 Active: 18/04/2016 Page 19 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 Miniature circuit breakers Din-Safe single pole width residual current circuit breaker (RCBO) Standards AS/NZS 61009 Approval N17482 One module wide (18 mm) Short circuit, overcurrent and earth leakage protection Short circuit protection 10 kA Sensitivity 10 and 30 mA Din rail mount Suits CD chassis Type "A" residual current device (AC/DC) Amp rating (A) 6 10 16 20 25 32 40 6 10 16 20 25 32 40 Modules Voltage (18mm) (AC) 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 1 240 Short circuit (kA) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Trip Sensitivity (mA) 30 30 30 30 30 30 30 10 10 10 10 10 10 10 Cat. No 1) 2) DSRCBH0630A DSRCBH1030A DSRCBH1630A DSRCBH2030A DSRCBH2530A DSRCBH3230A DSRCBH4030A i DSRCBH0610A DSRCBH1010A DSRCBH1610A DSRCBH2010A i DSRCBH2510A i DSRCBH3210A i DSRCBH4010A Application The Din-Safe single pole width residual current circuit breaker will fit the standard Din-T chassis for use in NHP panelboards. The design makes it possible to provide an MCB complete with earth leakage protection in an 18 mm wide module, which allows a greater number of devices to be fitted into a distribution board. Connection diagram Note: 1) Neutral not switched. 2) Will not accept side mounting accessories. i Available on indent only. Operation This unit combines the overload and short circuit protection of an MCB with earth leakage protection of an RCD. The unit occupies one, sub- circuit (one pole) of the distribution board and provides single phase protection against overload, short circuit and earth leakage current. The MCB element provides thermal and magnetic tripping protection which is rated to 10 kA prospective fault current. The RCD element of the device provides core-balance detection of the difference between the active and neutral currents and amplification to provide high sensitivity. The rated residual operating current (In) is 10 mA or 30 mA. The green/yellow earth reference cable, in case of loss of supply neutral, ensures the device will continue to provide earth leakage protection and will operate normally upon detection of an earth leakage current. Dimensions (mm) Note: A 1.2 m long pigtail lead is included as standard. Note: Nuisance tripping may be experienced in VFD and motor starting applications refer NHP. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 20 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs + RCDs Technical data Tripping curves according to EN 60898 The following tables show the average tripping curves of the Terasaki Din-T MCBs based on the thermal and magnetic characteristics. Curve C 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 21 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Innovators in Protection Technology RCDs classification according to EN 61008/61009 RCDs may be classified according to: The behaviour in the presence of DC current (types for general use). Type AC Type A The time-delay (in the presence of residual current) RCDs without time delay: type for general use RCDs with time delay: type S for selectivity Type AC 1) 2) The type AC RCDs are designed to release with sinusoidal residual currents which occur suddenly or slowly rise in magnitude. Residual current 0.5 x In 1 x In 2 x In 5 x In Tripping time t = t = <300 ms t = <150 ms t = 40 ms Type A 3) 4) Certain devices during faults can be the source of non- sinusoidal earth leakage currents (DC components) due to the electronic components e.g. diodes, thyristors etc. Type A RCDs are designed to ensure that under these conditions 3 the residual current devices operate on sinusoidal residual current and also with pulsating direct current(*) which occur suddenly or slowly rise in magnitude. (*) Pulsating direct current: current of pulsating wave form which assumes, in each period of the rated power frequency, the value 0 or a value not exceeding 0.006 A DC during one single interval of time, expressed in angular measure of at least 150º. Residual current Tripping time 1. For sinusoidal residual current 0.5 x In 1 x In 2 x In 5 x In 2. For residual pulsating direct current At point of wave 0° 0.35 x In 1.4 x In 2.8 x In 7 x In At point of wave 90° 0.25 x In 1.4 x In 2.8 x In 7 x In t = t = <300 ms t = <150 ms t = 40 ms t = t = <300 ms t = <150 ms t = 40 ms t = t = <300 ms t = <150 ms t = 40 ms At point of wave 135° 0.11 x In 1.4 x In 2.8 x In 7 x In t = t = <300 ms t = <150 ms t = 40 ms Tripping curve type AC 1) Standard in Australia 2) Type A acceptable in Australia Q-Pulse Id: TMS1594 Tripping curve type A 3) Standard in New Zealand 4) DSRCBH is type A. Active: 18/04/2016 Page 22 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Nuisance tripping All DinSafe RCDs have a high level of immunity to transient currents, against current impulses of 8/20 µs according to EN 61008/61009 and VDE 0664.T1. Type A, AC...................................250 A 8/20 µs Type S.......................................3000 A 8/20 µs Innovators in Protection Technology 3 RCDs have a high level of immunity against alternating currents of high frequency according to EN 61008/61009. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 23 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Use of an RCBO (DSRCBH) Innovators in Protection Technology 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 24 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs + RCDs Technical data Product related information Influence of temperature on RCBOs (DinSafe DSRCB) The thermal calibration of the RCBO was carried out at an ambient temperature of 30 °C. Ambient temperatures different from 30 °C influence the bimetal and this results in earlier or 3 later thermal tripping. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 25 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Innovators in Protection Technology Tripping current as a function of the frequency All RCDs are designed to work at frequencies of 50-60 Hz, therefore to work at different values, we must consider the variation of the tripping sensitivity according to the tables below. It should be taken into consideration that there is a no tripping risk when pushing the test-button, due to the fact that such action is made by means of an internal resistor with a fixed value. RCBO DSRCBH 3) Type AC 1) 30 mA 10 Hz 0.62 30 Hz 0.65 50 Hz 0.80 100 Hz 0.91 200 Hz 1.24 300 Hz 1.55 400 Hz 1.88 3 100 mA 0.74 0.71 0.80 0.95 1.16 1.38 1.59 300 mA 0.80 0.74 0.80 0.97 1.19 1.44 1.64 500 mA 1.10 0.81 0.80 0.89 1.18 1.38 1.68 Type A 2) 30 mA 8.17 3.13 0.75 1.70 3.10 3.52 3.67 100 mA 6.81 2.71 0.75 1.43 2.35 2.58 2.71 300 mA 6.20 2.16 0.75 0.49 0.87 0.74 0.95 500 mA 4.34 1.53 0.75 0.39 0.59 0.62 0.64 Notes: 1) The standard NHP/Terasaki type is the "type AC" in Australia, Type "A" in New Zealand. 2) The standard NHP/Terasaki DSRCBH single pole RCBO is "type A" in Australia and New Zealand. 3) The numbers in the table above are multipliers, e.g. A "DSRCD" at 50 hz has an 0.8 multiplier. Therefore a 30 mA, "type AC" RCD will trip at (0.8 x 30 mA) 24 mA. Power losses The power losses are calculated by means of measuring the voltage drop between the incoming and the outgoing terminal of the device at rated current. Power loss per pole: RCBO-Single pole DSRCBH In (A) 6 10 13 16 20 25 32 40 50 63 Z (mOhm) 45.8 16.4 12.5 10.6 7.3 5.4 3.2 2.6 1.9 1.4 Pw (W) 1.65 1.7 2.1 2.7 2.9 3.3 3.4 4.2 4.8 5.6 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 26 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data RCBO (DSRCB) let-through energy I2t The benefit of an RCBO in short-circuit conditions, is its ability to reduce the value of the let-through energy that the short-circuit would be generating. Din-T single pole width RCD (DSRCBH) Curve C Innovators in Protection Technology 3 RCCB - Din-Safe safety switch (DSRCD) RCBO - Din-Safe (DSRCBH) Dimensions in mm Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 27 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Overview Din-Safe RCDs RCBO Innovators in Protection Technology Device type definition Rating/description Standards Cat. No. Magnetic tripping characteristics Residual tripping characteristic 1) Tripping time at In Instantaneous ms Selective ms Rated current A Rated residual current In mA Calibration temperature °C Number of poles versus modules Rated voltage Un 2 P AC V 3 P AC V 4 P AC V Frequency Hz Maximum service voltage Ubmax V Minimum service voltage Ubmin V Power supply Selectivity class Rated making and breaking capacity (Im) A Residual making and breaking capacity (Im) A Conditional short-circuit capacity (Inc) A Conditional residual short-circuit capacity (Ic) A Short-circuit capacity (Icn) A Grid distance (safety distance between two devices) mm Isolator application Insulation degree Insulation voltage V (DC) Shock voltage (1.2/50 ms) kV Insulation resistance (mOhm) Dielectric strength V Shock resistance (in x, y, z direction)(IEC 60077/16.3) Vibration resistance (in x, y, z direction; IEC 60068-2-6) Endurance electrical at Un, In mechanical at Un, In Protection degree (outside/inside electrical enclosure) Self extinguish degree (according to UL 94) Tropicalisation (according to IEC 60068-2, DIN 40046) °C/RH Pollution degree (acc. IEC 60947-1) Operating temperature °C Storage temperature °C Terminals capacity Rigid cable min/max (Top) mm2 Flexible cable min*/max (Top) mm2 Rigid cable min/max (bottom) mm2 Flexible cable min*/max (bottom) mm2 (*Flexible cable 0.75/1/1.5 mm2 with cable lug) DSRCBH IEC 61009-1 C A <300 6, 10, 16, 20, 25, 32, 40 10, 30 30 1 240 (1 P+N) 50/60 255 100 Bottom 3 10xIn 10000 10000 yes 500 2) 6 2) 1000 2) 2500 2) 40 g, 18 shocks 5 ms 2 g, 30 min, 0...80 Hz 10000 20000 IP 20 / IP 40 V2 +55/95 % 3 -5..+60 -25..+70 1/25 1/16 1/35 1/25 Torque Top/Bottom Nm Add-on devices (side add-on) Auxiliary contacts UVT Shunt trip Motor operator Panelboard switch Busbars systems Pin Fork Accessories 3 Bottom Bottom yes Dimensions, weights, # Poles 1+N packaging (HxDxW) 86x68xW mm 18 Weight/unit g 350 Package/unit 1 Note: 1) Refer catalogue section for types. 2) Making sure that N-L and both flying leads are disconnected. Q-Pulse Id: TMS1594 Active: 18/04/2016 3 Page 28 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 Miniature circuit breakers Din-T15 series 15 kA, 20 kA, 25 kA MCBs Standards AS/NZS 3947-2 Current range 6-63 Amp 1, 2, 3 and 4 pole Sealable and lockable handle Modular design Mounts on CD chassis (250 A and 355 A) Industrial applications 1 pole 1 module 3) In (A) Icu (kA) C - Curve 5 - 10 In 6 25 DTCB15106C 10 25 DTCB15110C 13 25 i DTCB15113C 16 25 DTCB15116C 20 25 DTCB15120C 25 25 DTCB15125C 32 20 DTCB15132C 40 20 DTCB15140C 50 15 DTCB15150C 63 15 DTCB15163C 3 pole 3 modules 3) 6 25 10 25 13 25 16 25 20 25 25 25 32 20 40 20 50 15 63 15 DTCB15306C DTCB15310C i DTCB15313C DTCB15316C DTCB15320C DTCB15325C DTCB15332C DTCB15340C DTCB15350C DTCB15363C 2 pole 2 modules 3) In (A) Icu (kA) C - Curve 5 - 10 In 6 25 i DTCB15206C 10 25 i DTCB15210C 13 25 i DTCB15213C 16 25 i DTCB15216C 20 25 i DTCB15220C 25 25 i DTCB15225C 32 20 i DTCB15232C 40 20 i DTCB15240C 50 15 i DTCB15250C 63 15 i DTCB15263C 4 pole 4 modules 2) 3) 6 25 10 25 13 25 16 25 20 25 25 25 32 20 40 20 50 15 63 15 i DTCB15406C i DTCB15410C i DTCB15413C i DTCB15416C i DTCB15420C i DTCB15425C i DTCB15432C i DTCB15440C i DTCB15450C i DTCB15463C DTCB15 1 pole In (A) 1 P 2 P 3 P 4 P 6 - 63 240 V AC 240/415 V AC 240/415 V AC 240/415 V AC Shock resistance (in x, y, z direction) 20 g with shock duration of 10 ms (minimum 18 shocks) 40 g with shock duration of 5 ms (minimum 18 shocks) Vibration resistance (in x, y, z direction) 3 g in frequency range 10 to 55 Hz (operating time at least 30 mins) according to IEC 60068-2-6 Storage temperature from -55 °C to +55 °C according to VDE 0664 parts 1 and 2 Operating temperature from -25 °C to +55 °C according to VDE 0664 Parts 1 and 2. Use at 400 Hz At 400 Hz the magnetic tripping current is approximately 50 % higher than at AC 50/60 Hz DTCB15 2 pole DTCB15 3 pole Notes: 1) 2 P MCB connected in series. The LINE-side is the OFF or bottom of the MCB and connects to CD chassis tee-offs. 2) All poles include overcurrent and short circuit protection. 3) Refer Section 3 for kA ratings at 240/415 V. The above ratings are at 415 V AC. i Available on indent only. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 29 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Innovators in Protection Technology Characteristics according to EN 60947-2 Miniature Circuit Breakers are intended for the protection of the lines against both overloads and short-circuits in industrial wiring installations where normal operation is done by instructed people Tripping characteristic curves Rated ultimate short-circuit breaking capacity (Icu) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO. After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 1000 V. 3 Moreover the MCB shall be capable of tripping when loaded with 2.5 In within the time corresponding to 2 In but greater than 0.1 s. Rated service short-circuit breaking capacity (Ics) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO-t-CO. After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of twice its rated insulation voltage with a minimum of 1000 V. A verification of the overload releases on In and moreover the MCB shall trip within 1 h when current is 1.45 In (for In<63 A) and 2 h (for In>63 A). Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of short-circuit. The standard leaves the calibration of magnetic release to the manufacturers discretion. NHP offers instantaneous tripping ranges: · release between 5 and 10 In · release between 10 and 20 In Thermal release The release is initiated by a bimetal strip in the event of overload. The standard defines the range of release for two special overload values. Reference ambient temperature is 40 °C. O - Represents an opening operation C - Represents a closing operation followed by an automatic opening. t - Represents the time interval between two successive short-circuit operations: 3 minutes. Category A: Without a short-time withstand current rating. Utilization category Application with respect to selectivity A Circuit breakers not specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. without an intentional short-time delay provided for selectivity under short-circuit conditions, and therefore without a short-time withstand current rating according to 4.3.5.4 Test current 1.05 x In 1.30 x In Tripping time t 1 h (In 63 A) t 2 h (In > 63 A) t < 1 h (In 63 A) t < 2 h (In > 63 A) B Circuit breakers specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. without an intentional short-time delay (which may be adjustable), provided for selectivity under short-circuit conditions. Such circuit-breakers have a short-time withstand current rating according to 4.3.5.4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 30 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Tripping curves according to EN 60898 The following tables show the average tripping curves of the Terasaki Din-T MCBs based on the thermal and magnetic characteristics. Curve C 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 31 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Definitions related to circuit breakers MCB = Miniature Circuit Breaker Innovators in Protection Technology Short-circuit (making and breaking) capacity Alternating component of the prospective current, expressed by its RMS value, which the circuit breaker is designed to make, to carry for its opening time and to break under specified conditions. Ultimate or rated short-circuit breaking capacity (Icn - EN 60898) A breaking capacity for which the prescribed conditions, according to a specified test sequence, do not include the capability of the MCB to carry 0.96 times its rated current for the conventional time. Prospective current The current that would flow in the circuit, if each main current path of the MCB were replaced by a 3 conductor of negligible impedance. Conventional non-tripping current (Int) A specified value of current which the circuit breaker is capable of carrying for a specified time without tripping. Open position The position in which the predetermined clearance between open contacts in the main circuit of the MCB is secured. Ultimate short-circuit breaking capacity (Icu - EN 60947-2) A breaking capacity for which the prescribed conditions, according to a specified test sequence, do not include the capability of the MCB to carry its rated current for the conventional time. Service short-circuit breaking capacity (Ics - EN 60898) A breaking capacity for which the prescribed conditions, according to a specified test sequence, include the capability of the MCB to carry 0.96 times its rated current for the conventional time. Closed position The position in which the predetermined continuity of the main circuit of the MCB is secured. Maximum prospective peak current (Ip) The prospective peak current when the initiation of the current takes place at the instant which leads to the highest possible value. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 32 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Influence of ambient air temperature on the rated current The maximum value of the current which can flow through an MCB depends on the nominal current of the MCB, the conductor cross-section and the ambient air temperature. The values shown in the table below are for devices in free air. 3 For devices installed with other modular devices in the same switchboard, a correction factor (K) shall be applied relative to the mounting situation of the MCB, the ambient temperature and the number of main circuits in the installation. The thermal calibration of the MCBs was carried out at an ambient temperature of 30 °C. Ambient temperatures different from 30 °C influence the bimetal and this results in earlier or later thermal tripping. No of devices K 1) 2 or 3 0.9 4 or 5 0.8 6 or 9 0.7 > 10 0.6 Calculation example Within a distribution board consisting of eight 2 Pole, 16 A, `C' curve type MCBs, with an operating ambient temperature of 45 °C, which is the highest temperature the MCB can operate at without unwanted tripping? Calculation The correction factor K = 0.7, for use in an eight circuit installation: 16 A x 0.7 = 11.2 A As the MCB is working at 45 °C it shall be given another factor (90 % = 0.9): In at 45 °C = In at 30 °C x 0.9 = 11.2 A x 0.9 = 10.1 A. Note: 1) Applicable for MCBs working at maximum rated currents. Q-Pulse Id: TMS1594 : 1P (single pole) : mP (multi-pole) Active: 18/04/2016 Page 33 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Innovators in Protection Technology Effects of frequency on the tripping characteristic All the MCBs are designed to work at frequencies of 50-60 Hz, therefore to work at different values, consideration must be given to the variation of the tripping characteristics. The thermal tripping does not change with variation of the frequency but the magnetic tripping values can be up to 50 % higher than the ones at 50-60 Hz. Limitation curves Let-through energy I2t The limitation capacity of an MCB in short-circuit conditions, is its capacity to reduce the value of the let-through energy that the short-circuit would be generating. Peak current Ip Is the value of the maximum peak of the short-circuit current 3 limited by the MCB. Tripping current variation 60 Hz 1 100 Hz 1.1 200 Hz 1.2 300 Hz 1.4 400 Hz 1.5 Power losses The power losses are calculated by measuring the voltage drop between the incoming and the outgoing terminals of the device at rated current. Power loss per pole In Voltage drop Energy loss (A) (V) (W) 0.5 2.230 1.115 1 1.270 1.272 2 0.620 1.240 3 0.520 1.557 4 0.370 1.488 6 0.260 1.570 8 0.160 1.242 10 0.160 1.560 13 0.155 2.011 16 0.162 2.586 20 0.138 2.760 25 0.128 3.188 32 0.096 3.072 40 0.100 4.000 50 0.090 4.500 63 0.082 5.160 Resistance (mOhm) 4458.00 1272.00 310.00 173.00 93.00 43.60 19.40 15.60 11.90 10.10 6.90 5.10 3.00 2.50 1.80 1.30 See following pages Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 34 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Din-T 15 15 kA C curve Innovators in Protection Technology 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 35 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Use of standard MCB for DC use For MCBs designed to be used in alternating current but used in installations in direct current, the following should be taken into consideration: For protection against overloads it is necessary to connect 3 the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is similar to alternating current. For protection against short-circuits it is necessary to connect the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is 40% higher than the one in alternating current. Use in DC selection table Series Din-T 15 Rated current (A) 6....25 A 48 V 1 pole Icu (kA) 10 Installation of Din-T DC MCBs in direct current 110 V 2 poles in series Icu (kA) 10 250 V 1 pole Icu (kA) - 440 V 2 poles in series Icu (kA) - Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 36 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Series Din-T15 AS/NZS 3947-2 Standards (Aust / NZ / International) Tripping characteristics Nominal current Calibration temperature Number of poles (# mod) Neutral pole protected IEC 60947-2 C A 0.5-63 °C 40 1/2/3/4 - Nominal voltage Un Frequency AC 1 P 3 P/4 P DC 1 P 1) 2 P (in series) 1) V 240/415 V 415 V DC 48 V DC 110 Hz 50/60 Hz DC: magn.trip +40% Maximum service voltage Ubmax between two wires Minimum service voltage Ubmin Selectivity class (IEC 60898) Isolator application IEC 60947-2 Hz 400: magn.trip +50% V 250/440; 53/120 V 12; 12 3 yes Rated insulation voltage Pollution degree 2 V 500 Pollution degree 3 Impulse withstand test voltage Insulation resistance Dielectric rigidity V kV mOhm kV 440 6 10,000 2.5 Vibration resistance (in x, y, z direction) (IEC 77/16.3) 3 g Endurance Electrical at Un, In 4000 mechanical Utilisation category (IEC 60947-2) Protection degree (outside / inside, in enclosure with door) Self-extinguish degree (according to UL94) Tropicalisation (according to IEC 60068-2 / DIN 40046) °C/RH Operating temperature °C Storage temperature °C Terminal capacity Rigid cable min/max (top) mm2 Flexible cable min*/max (top) mm2 Rigid cable min/max (bottom) mm2 Flexible cable min*/max (bottom) mm2 (* Flexible cable 0.75/1/1.5 mm2 with cable lug) 20,000 A IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 1/35 0.75/25 1/35 0.75/25 Torque Nm 4.5 Add-on devices (side add-on) Busbar systems Accessories Auxiliary contacts UVT Shunt trip Motor operator Panelboard switch Pin (top/bottom) Fork (top/bottom) yes yes yes yes yes yes/yes -/yes yes Dimensions, weights, packaging (HxDxW) 86x68xW Weight/mod. Package mm/mod. 18 g 120 mod. 12 IEC 60898 Short-circuit capacity AC Icn Ics (service) 1 P 2 P 3 P/4 P (kA) 230/400 V 230/400 V 230/400 V AS/NZS 3947-2 - Icu (ultimate) 1 P 127 V 50 240 V 415 V 50/25/20/15 2) - IEC 60947-2 2 P 127 V - 240 V 50/50/40/30 2) 415 V 50/25/20/15 2) 3 P, 4 P 240 V 415 V 440 V 50/50/40/30 2) 50/25/20/15 2) 50/20/15/10 2) Ics (service) 75 % Icu NEMA AB1 (120/240V) - Short-circuit capacity DC (kA) Icu (ultimate) 1 P 60 V 25 IEC 60947-2 220 V - 2 P 125 V 30 Ics (service) 440 V 100 % Icu Notes Refer pages 3 - 23, 24 for information on SAFE-T MCBs. 1) Preferred values of rated control supply voltage (IEC 60947 - 2): 24 V, 48 V, 110 V, 125 V, 250 V 2) 0.5-4 A/6-25 A/32-40 A/50-63 A 3) 10 (125 V DC) Innovators in Protection Technology 3 4) 10 (250 V DC) 5) On request. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 37 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 Miniature circuit breakers Din-T10 series 10 kA MCB Standard AS/NZS 4898 1) Approval No. N17481 Short circuit breaking capacity - 10000 Amps Current range 0.5 - 63 Amps 1, 2, 3 and 4 pole Sealable and lockable handle Modular design Available in curve type B, C and D Mounts on CD chassis (250 A and 355 A) 1 pole 1 module DTCB10 1 pole In (A) 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63 C Curve 5-10 In DTCB10105C DTCB10101C DTCB10102C DTCB10103C DTCB10104C DTCB10106C DTCB10110C DTCB10113C DTCB10116C DTCB10120C DTCB10125C DTCB10132C DTCB10140C DTCB10150C DTCB10163C Short circuit capacity 10 kA In (A) 0.5 - 63 1 P 240 V AC 2 P 240/415 V AC 3 P 240/415 V AC 4 P 240/415 V AC Use at DC Short circuit Max voltage 1 P 25 kA 48 V DC 2 P 2) 30 kA 110 V DC 2 pole 2 modules 0.5 1 2 4 6 10 13 16 20 25 32 40 50 63 DTCB10205C DTCB10201C DTCB10202C DTCB10204C DTCB10206C DTCB10210C DTCB10213C DTCB10216C DTCB10220C DTCB10225C DTCB10232C DTCB10240C DTCB10250C DTCB10263C Notes: 1) A range of UL standard MCBs is available on indent. (ref DTCBUL1O_ _ _ C). 2) 2 pole MCB connected in series. The line side is the "OFF" (bottom) side of the MCB, and connects to CD chassis tee-offs. i Available on indent only. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 38 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Characteristics according to BS EN 60898 Miniature Circuit Breakers are intended for the protection of wiring installations against both overloads and short-circuits in domestic or commercial wiring installations where operation is possible by uninstructed people Rated short-circuit breaking capacity (Icn) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO. 3 Tripping characteristic curves After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 900 V. Moreover, the MCB shall be capable of tripping when loaded with 2.8 In within the time corresponding to 2.55 In but greater than 0.1s. Service short-circuit breaking capacity (Ics) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO-t-CO. After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 1500 V. Moreover, the MCB shall not trip at a current of 0.96 In. The MCB shall trip within 1h when current is 1.6 In. Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of short-circuit. The NHP Din-T range has 3 different types, following the current for instantaneous release: types B, C and D curve. Icn Test (A) current Tripping time Applications B 3 x In 5 x In 0.1<t<45 s (In32 A) 0.1<t<90 s (In>32 A) t<0.1 s Only for resistive loads eg: · electrical heating · water heater · stoves. C 5 x In 0.1<t<15 s (In32 A) Usual loads such as: 10 x In 0.1<t<30 s (In>32 A) · lighting · socket outlets t<0.1 s · small motors D 10 x In 0.1<t<4 s(**) (In32 A) Control and protection of 20 x In 0.1<t<8 s (In>32 A) circuits having important transient inrush currents t<0.1 s (large motors) Thermal release The release is initiated by a bimetal strip in the event of overload. The standard defines the range of releases for specific overload values. Reference ambient temperature is 30 °C. O - Represents an opening operation C - Represents a closing operation followed by an automatic opening. t - Represents the time interval between two successive short-circuit operations: 3 minutes. The relation between the rated short-circuit capacity (Icn) and the rated service short-circuit breaking capacity (Ics) shall be as follows: Icn (A) 6000 > 6000 10000 > 10000 Ics (A) 6000 0.75 Icn min. 6000 0.75 Icn min. 7500 In both sequences all MCBs are tested for emission of ionized gases during short-circuit (grid distance), in a safety distance between two MCBs of 35 mm when devices are installed in two different rows in the enclosure. This performance allows the use of any NHP/Terasaki enclosure. Test current 1.13 x In 1.45 x In 2.55 x In Tripping time t 1 h (In 63 A) t 2 h (In > 63 A) t < 1 h (In 63 A) t < 2 h (In > 63 A) 1 s < t < 60 s (In 32 A) 1 s < t < 120 s (In >32 A) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 39 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Tripping curves according to EN 60898 The following tables show the average tripping curves of the Terasaki Din-T MCBs based on the thermal and magnetic characteristics. Curve C 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 40 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Din-T 10 10 kA C curve Innovators in Protection Technology 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 41 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Influence of ambient air temperature on the rated current The maximum value of the current which can flow through an MCB depends on the nominal current of the MCB, the conductor cross-section and the ambient air temperature. The values shown in the table below are for devices in free air. 3 For devices installed with other modular devices in the same switchboard, a correction factor (K) shall be applied relative to the mounting situation of the MCB, the ambient temperature and the number of main circuits in the installation. The thermal calibration of the MCBs was carried out at an ambient temperature of 30 °C. Ambient temperatures different from 30 °C influence the bimetal and this results in earlier or later thermal tripping. No of devices K 1) 2 or 3 0.9 4 or 5 0.8 6 or 9 0.7 > 10 0.6 Calculation example Within a distribution board consisting of eight 2 Pole, 16 A, `C' curve type MCBs, with an operating ambient temperature of 45 °C, which is the highest temperature the MCB can operate at without unwanted tripping? Calculation The correction factor K = 0.7, for use in an eight circuit installation: 16 A x 0.7 = 11.2 A As the MCB is working at 45 °C it shall be given another factor (90 % = 0.9): In at 45 °C = In at 30 °C x 0.9 = 11.2 A x 0.9 = 10.1 A. Note: 1) Applicable for MCBs working at maximum rated currents. Q-Pulse Id: TMS1594 : 1P (single pole) : mP (multi-pole) Active: 18/04/2016 Page 42 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Din-T MCBs Technical data Innovators in Protection Technology Effects of frequency on the tripping characteristic All the MCBs are designed to work at frequencies of 50-60 Hz, therefore to work at different values, consideration must be given to the variation of the tripping characteristics. The thermal tripping does not change with variation of the frequency but the magnetic tripping values can be up to 50 % higher than the ones at 50-60 Hz. Limitation curves Let-through energy I2t The limitation capacity of an MCB in short-circuit conditions, is its capacity to reduce the value of the let-through energy that the short-circuit would be generating. Peak current Ip Is the value of the maximum peak of the short-circuit current 3 limited by the MCB. Tripping current variation 60 Hz 1 100 Hz 1.1 200 Hz 1.2 300 Hz 1.4 400 Hz 1.5 Power losses The power losses are calculated by measuring the voltage drop between the incoming and the outgoing terminals of the device at rated current. Power loss per pole In Voltage drop Energy loss (A) (V) (W) 0.5 2.230 1.115 1 1.270 1.272 2 0.620 1.240 3 0.520 1.557 4 0.370 1.488 6 0.260 1.570 8 0.160 1.242 10 0.160 1.560 13 0.155 2.011 16 0.162 2.586 20 0.138 2.760 25 0.128 3.188 32 0.096 3.072 40 0.100 4.000 50 0.090 4.500 63 0.082 5.160 80 0.075 6.000 100 0.075 7.500 125 0.076 9.500 Resistance (mOhm) 4458.00 1272.00 310.00 173.00 93.00 43.60 19.40 15.60 11.90 10.10 6.90 5.10 3.00 2.50 1.80 1.30 0.90 0.75 0.60 See following pages Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 43 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Use of standard MCB for DC use For MCBs designed to be used in alternating current but used in installations in direct current, the following should be taken into consideration: For protection against overloads it is necessary to connect 3 the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is similar to alternating current. Use in DC selection table For protection against short-circuits it is necessary to connect the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is 40% higher than the one in alternating current. Use of special MCB Din-T DC for DC use. (UC = Universal current) For MCBs designed to work in both alternating and direct current, it is necessary to respect the polarity of the terminals since the device is equipped with a permanent magnet. Series Din-T 10 Rated current (A) 0.5....63 A 48 V 1 pole Icu (kA) 25 110 V 2 poles in series Icu (kA) 30 250 V 1 pole Icu (kA) - 440 V 2 poles in series Icu (kA) - Installation of Din-T DC MCBs in direct current Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 44 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Notes Din-T MCBs Technical data Series Din-T10 AS/NZS 4898 Standards (Aust / NZ / International) IEC 60898 Tripping characteristics B, C, D Nominal current A B(6-63), C/D(0.5-63) Calibration temperature °C 30 Number of poles (# mod) Neutral pole protected 1/2/3/4 yes Nominal voltage Un AC 1 P V 240/415 Frequency 3 P/4 P DC 1 P 1) 2 P (in series) 1) V 415 V DC 48 V DC 110 Hz 50/60 Hz DC: magn.trip +40% Hz 400: magn.trip +50% Maximum service voltage Ubmax between two wires V 250/440; 53/120 Minimum service voltage Ubmin Selectivity class (IEC 60898) Isolator application IEC 60947-2 V 12; 12 3 yes Rated insulation voltage Pollution degree 2 V 500 Pollution degree 3 V 440 Impulse withstand test voltage kV 6 Insulation resistance mOhm 10,000 Dielectric rigidity kV 2.5 Vibration resistance (in x, y, z direction) (IEC 77/16.3) 3 g Endurance Electrical at Un, In 10,000 mechanical 20,000 Utilisation category (IEC 60947-2) A Protection degree (outside / inside, in enclosure with door) Self-extinguish degree (according to UL94) Tropicalisation (according to IEC 60068-2 / DIN 40046) °C/RH Operating temperature °C Storage temperature °C IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 Terminal capacity Rigid cable min/max (top) mm2 1/35 Flexible cable min*/max (top) Rigid cable min/max (bottom) mm2 0.75/25 mm2 1/35 Flexible cable min*/max (bottom) mm2 0.75/25 (* Flexible cable 0.75/1/1.5 mm2 with cable lug) Torque Nm 4.5 Add-on devices Auxiliary contacts yes (side add-on) UVT yes Shunt trip yes Motor operator yes Panelboard switch yes Busbar systems Pin (top/bottom) yes/yes Fork (top/bottom) -/yes Accessories yes Dimensions, weights, packaging (HxDxW) 86x68xW mm/mod. 18 Weight/mod. g 120 Package mod. 12 Short-circuit capacity AC (kA) AS/NZS 4898 IEC 60898 Icn Ics (service) 1 P 2 P 3 P/4 P 230/400 V 230/400 V 230/400 V 10 10 10 75 % Icn Icu (ultimate) 1 P 127 V 30 240 V 15 IEC 60947-2 415 V 4 2 P 127 V 40 240 V 30 415 V 15 3 P, 4 P 240 V 30 415 V 15 440 V 10 Ics (service) 50 % Icu NEMA AB1 (120/240V) 30 Short-circuit capacity DC (kA) Icu (ultimate) 1 P 60 V 25 IEC 60947-2 220 V - 2 P 125 V 30 Ics (service) 440 V 100 % Icu Refer pages 3 - 23, 24 for information on SAFE-T MCBs. 1) Preferred values of rated control supply voltage (IEC 60947 - 2): 24 V, 48 V, 110 V, 125 V, 250 V 2) 0.5-4 A/6-25 A/32-40 A/50-63 A 3) 10 (125 V DC) Innovators in Protection Technology 3 4) 10 (250 V DC) 5) On request. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 45 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs + RCDs Technical data Miniature circuit breakers - Din-T 10 Dimensions in mm. 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 46 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.2. CONTROL DEVICES CARLO GAVAZZI DPB-01-C-M48W Phase Failure Relay MULTITRODE MTR 24VDC Sump Pump Level Relay SPRECHER & SCHUH CS 7C-40E24V Pumps Stop Relay SPRECHER & SCHUH CS 7-PV-22 Pumps Stop Relay Aux Contact SPRECHER & SCHUH CS 7C-22E24V 24VDC Relay IDEC RH2B-ULD-D24VDC + SH2B-05 Run Relay + Base SPRECHER & SCHUH CA7-9C-01 24VDC Contactor COSMOTEC KTS01141 - Thermostat C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 47 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multi-function Types DPB01, PPB01 DPB01 PPB01 · TRMS 3-phase over and under voltage, phase sequence and phase loss monitoring relays · Detect when all 3 phases are present and have the correct phase sequence (except for N versions) · Available versions (W4) supplied between phase and neutral · Detect if all the 3-phase-phase or phase-neutral voltages are within the set limits · Upper and lower limits separately adjustable · Measure on own power supply · Selection of measuring range by DIP-switches · Adjustable voltage on relative scale · Adjustable delay function (0.1 to 30 s) · Output: 8 A SPDT relay N.E. · For mounting on DIN-rail in accordance with DIN/EN 50 022 (DPB01) or plug-in module (PPB01) · 22.5 mm Euronorm housing (DPB01) or 36 mm plug-in module (PPB01) · LED indication for relay, alarm and power supply ON Product Description Ordering Key 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, over and under voltage (separately adjustable set points) with built-in time delay function. Supply ranges from 208 to 480 VAC covered by two multivoltage relays. Housing Function Type Item number Output Power supply Type Selection Mounting Phase sequence Output detection Supply: 208 to 240 VAC Supply: 380 to 415 VAC DIN-rail yes Plug-in yes Plug-in yes DIN-rail no Plug-in no Plug-in no SPDT SPDT SPDT SPDT SPDT SPDT DPB 01 C M23 PPB 01 C M23 DPB 01 C M23 N PPB 01 C M23 N DPB 01 C M48 W4 PPB 01 C M48 W4 PPB 01 C M48 DPB 01 C M48 N W4 PPB 01 C M48 N W4 PPB 01 C M48 N DPB 01 C M23 Supply: 380 to 480 VAC DPB 01 C M48 DPB 01 C M48 N Input Specifications Input L1, L2, L3, N DPB01: Terminals L1, L2, L3, N PPB01: Terminals 5, 6, 7, 11 Measure on own supply Note: Connect the neutral only if it is intrinsically at the star centre Measuring ranges 208 to 240 VAC 380 to 415 VAC 380 to 480 VAC 177 to 275 VL-L AC M23 versions 323 to 475 VL-L AC PPB01CM48 PPB01CM48N D/P PB01CM48W4 D/P PB01CM48NW4 323 to 550 VL-L AC DPB01CM48 DPB01CM48N Ranges Upper level +2 to +22% of the nominal voltage Lower level -22 to -2% of the nominal voltage Note: The input voltage must not exceed the maximum rated voltage or drop below the minumum rated voltage reported above. Hysteresis Set points from 2 to 5% 1% Set points from 5 to 22% 2% Specifications are subject to change without notice (10.04.07) Q-Pulse Id: TMS1594 Active: 18/04/2016 1 Page 48 of 1068 DPB01, PPB01 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Output Specifications Output Rated insulation voltage SPDT relay 250 VAC Contact ratings (AgSnO2) Resistive loads AC 1 DC 12 Small inductive loads AC 15 DC 13 µ 8 A @ 250 VAC 5 A @ 24 VDC 2.5 A @ 250 VAC 2.5 A @ 24 VDC Mechanical life 30 x 106 operations Electrical life 105 operations (at 8 A, 250 V, cos = 1) Operating frequency 7200 operations/h Dielectric strength Dielectric voltage 2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 µs) Supply Specifications Power supply Rated operational voltage through terminals: L1, L2, L3, N (DPB01) 5, 6, 7, 11 (PPB01) Overvoltage cat. III (IEC 60664, IEC 60038) D/P PB01CM23, D/P PB01CM23N 208 to 240 VL-L AC ±15% 45 to 65 Hz D/P PB01CM48W4, 380 to 415 VL-L AC ±15% D/P PB01CM48NW4, (220 to 240 VL-N AC ±15%) PPB01CM48, PPB01CM48N 45 to 65 Hz DPB01CM48, DPB01CM48N Rated operational power DPB01CM23x, PPB01CM23x DPB01CM48x, PPB01CM48x DPB01CM48xW4 DPB01CM48xW4 380 to 480 VL-L AC ±15% (220 to 277 VL-N AC ±15%) 45 to 65 Hz 13 VA @ 230 VAC, 50 Hz 13 VA @ 400 VAC, 50 Hz Supplied by L1 and L2 13 VA @ 400 VAC, 50 Hz Supplied by L1 and N General Specifications Power ON delay Reaction time Incorrect phase sequence or total phase loss Voltage level Alarm ON delay Alarm OFF delay Accuracy Temperature drift Delay ON alarm Repeatability Indication for Power supply ON Alarm ON Output relay ON Environment Degree of protection Pollution degree Operating temperature @ Max. voltage, 50 Hz @ Max. voltage, 60 Hz Storage temperature Housing Dimensions DPB01 PPB01 Weight Screw terminals Tightening torque Approvals CE Marking EMC Immunity Emissions 1 s ± 0.5 s or 6 s ± 0.5 s < 200 ms (input signal variation from -20% to +20% or from +20% to -20% of set value) < 200 ms (delay < 0.1 s) < 200 ms (delay < 0.1 s) (15 min warm-up time) ± 1000 ppm/°C ± 10% on set value ± 50 ms ± 0.5% on full-scale LED, green LED, red (flashing 2 Hz during delay time) LED, yellow IP 20 3 (DPB01), 2 (PPB01) -20 to 60°C, R.H. < 95% -20 to 50°C, R.H. < 95% -30 to 80°C, R.H. < 95% 22.5 x 80 x 99.5 mm 36 x 80 x 94 mm Approx. 120 g Max. 0.5 Nm according to IEC 60947 UL, CSA (except for W4 versions) Yes Electromagnetic Compatibility According to EN 61000-6-2 According to EN 61000-6-3 Mode of Operation Connected to the 3 phases (and neutral) DPB01 and PPB01 operate when all 3 phases are present at the same time, the phase sequence is correct (not N versions) and the phasephase (or phase-neutral) voltage levels are within set limits. If one or more phase-phase or phase-neutral voltages exceeds the upper set level or drops below the lower set level, the red LED starts flashing 2 Hz and the output relay releases after the set time period. In any case if phase-neutral measurement is selected both phasephase and phase-neutral voltages are monitored. If the phase sequence is wrong or one phase is lost, the output relay releases immediately. Only 200 ms delay occurs. The failure is indicated by the red LED flashing 5 Hz during the alarm condition. Example 1 (mains network monitoring) The relay monitors over and under voltage, phase loss and correct phase sequence. In case of N versions, the relay monitors over and under voltage. Example 2 (load monitoring) The relay releases in case of interruption of one or more phases, when one or more voltages drop below the lower set level or exceed the upper set level. 2 Q-Pulse Id: TMS1594 Specifications are subject to change without notice (10.04.07) Active: 18/04/2016 Page 49 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DPB01, PPB01 Function/Range/Level and Time Delay Setting Adjust the input range setting the DIP switches 3 and 4 as shown below. Select the desired function setting the DIP switches 1 and 2 as shown below. To access the DIP swiches open the grey plastic cover as shown below Selection of level and time delay: Upper knob: Setting of lower level on relative scale. Centre knob: Setting of upper level on relative scale. Lower knob: Setting of delay on alarm time on absolute scale (0.1 to 30 s). Power ON delay ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s Monitored voltage ON: Phase-Neutral OFF: Phase-Phase Measuring range SW3 ON SW4 ON M23 Ph-Ph 208 VAC Voltage M48 Ph-Ph 380 VAC Voltage M48 Ph-N 220 VAC Voltage ON OFF OFF ON 220 VAC 230 VAC 400 VAC 415 VAC 230 VAC 240 VAC OFF OFF 240 VAC 480 VAC DPB01CM48, DPB01CM48N only 277 VAC DPB01CM48, DPB01CM48N only Operation Diagrams Specifications are subject to change without notice (10.04.07) Q-Pulse Id: TMS1594 Active: 18/04/2016 3 Page 50 of 1068 DPB01, PPB01 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Operation Diagrams (cont.) (*) (*) N versions don't detect incorrect phase sequence. Wiring Diagrams DPB01 4 Q-Pulse Id: TMS1594 PPB01 Specifications are subject to change without notice (10.04.07) Active: 18/04/2016 Page 51 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DPB01, PPB01 Note When DPB01 or PPB01 is used with phase indicator lamps (see examples in the following diagrams), the lamp H1 or H2 might be dimly lit when there is a phase loss in L1 or L2. This might happen if the lamps used are the typical low power indicator lamps, and there are no other loads present. This fact can be avoided by using W4 models. Note that the neutral must be always connected to the device. DPB01 PPB01 Dimensions DIN-rail 22.5 99.5 Plug-in 36 28.5 94 90 28.5 80 83.5 63 80 63 Specifications are subject to change without notice (10.04.07) Q-Pulse Id: TMS1594 Active: 18/04/2016 5 Page 52 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules 0.1 - 2 - 3 - 5 - 6 - 8 A Common features · Instant ejection of relay by plastic retaining clip · Integral coil indication and protection circuit · 35 mm rail (EN 60715) mounting 6.2 mm wide · EMR - DC, AC or AC/DC coil versions · SSR - DC or AC/DC input versions · Screw and Screwless terminal options EMR Electromechanical Relays 38.51/38.61 SSR Solid State Relays 38.81/38.91 6.2 mm wide · Special coil / input leakage current suppression types · EMR - AC or AC/DC coil versions · SSR - AC or AC/DC input versions · Screw and Screwless terminal options · 1 CO - 6 A 250VAC · Single solid state output: Options 0.1A 48VDC, 2A 24VDC, 2A 240VAC · Silent, high speed switching · Long electrical life Page 1 38.51.3... - 38.61.3... Page 2 38.81.3... - 38.91.3... · 1 CO - 6 A 250VAC 6.2 mm wide · Timed Interface module · 4 functions & 4 time scales 0.1s ... 6h · EMR - AC/DC (12 or 24V) supply versions · SSR - AC/DC (24V) supply · Screw terminals 38.21 · Single solid state output: Options 0.1A 48VDC, 2A 24VDC, 2A 240VAC · Silent, high speed switching · Long electrical life Page 1 Page 2 38.21...9024-8240 14 mm wide · 2 pole 8 A or 1 pole 16 A · EMR - DC or AC/DC coil versions · SSR - DC input versions · Screw and Screwless terminal options · 1 CO - 6 A 250VAC · Single solid state output: Options 2A 24VDC, 2A 240VAC · Silent, high speed switching · Long electrical life Page 3 38.01/38.52/38.11/38.62 38.31/38.41 Page 3 Q-Pulse Id: TMS1594 · 1 CO - 16 A 250VAC · 2 CO - 8 A 250VAC Active: 18/04/2016 · Single solid state output: Options 5A 24VDC, 3A 240VAC · Silent, high speed switching · Long electrical life Page 4 Page 5 Page 53 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - 1 Pole 6 A EMR Features 1 Pole - 6 A electromechanical relay interface modules, 6.2 mm wide. Ideal interface for PLC and electronic systems · Sensitive DC coil or AC/DC coil versions · Integral coil indication and protection circuit · Instant ejection of relay using plastic retaining clip · UL Listing (certain relay/socket combinations) · 35 mm rail (EN 60715) mounting 38.51/61 38.51 / 38.51.3 Screw terminal 38.61 / 38.61.3 Screwless terminal · 1 pole electromechanical relay · Screw terminal and screwless terminal · 35 mm rail (EN 60715) mounting 38.51.3 / 38.61.3 · Leakage current suppression · 1 pole electromechanical relay · Screw terminal and screwless terminal · 35 mm rail (EN 60715) mounting 34.51 PROTECTION AND INDICATION CIRCUIT * Special version for max ambient temperature +70°C. For outline drawing see page 12 Contact specification 93.01/51 Contact configuration 1 CO (SPDT) Rated current/Maximum peak current A 6/10 Rated voltage/Maximum switching voltage V AC 250/400 Rated load AC1 VA 1,500 Rated load AC15 (230 V AC) VA 300 Single phase motor rating (230 V AC) kW 0.185 Breaking capacity DC1: 30/110/220 V A 6/0.2/0.12 Minimum switching load mW (V/mA) 500 (12/10) Standard contact material AgNi Coil specification Nominal voltage (UN) V AC/DC 12 - 24 - 48 - 60 - (110...125) - (220...240) V AC (230...240)* V DC 6 - 12 - 24 - 48 - 60 (non polarized) Rated power AC/DC VA (50 Hz)/W See page 9 Operating range AC/DC AC (0.8...1.1)UN (184...264)V Holding voltage Must drop-out voltage Technical data DC AC/DC AC/DC (0.8...1.2)UN 0.6 UN / 0.6 UN 0.1 UN / 0.05 UN Mechanical life AC/DC cycles 10 · 106 Electrical life at rated load AC1 cycles 60 · 103 Operate/release time ms 5/6 Insulation between coil and contacts (1.2/50 µs) kV 6 (8 mm) Dielectric strength between open contacts V AC 1,000 Ambient temperature range (UN 60 V/>60V) °C Protection category 40...+70/40...+55 IP 20 Approvals relay (according to type) Q-Pulse Id: TMS1594 Active: 18/04/2016 34.51 LEAKAGE CURRENT SUPPRESSION CIRCUIT 93.01.3/51.3 1 CO (SPDT) 6/10 250/400 1,500 300 0.185 6/0.2/0.12 500 (12/10) AgNi (110...125) -- -- (230...240) -- -- 1/1 0.5/-- (94...138)V -- -- (184...264)V -- 0.6 UN / 0.6 UN 44 V 72 V 10 · 106 60 · 103 5/6 6 (8 mm) 1,000 --/40...+55 IP 20 1 Page 54 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Ordering information Ordering information Electromechanical relay - 1 or 2 Pole Example: 38 series screw terminal relay interface module, 1 CO (SPDT), sensitive 12 V DC coil. A B C D 3 8.5 1.7.0 1 2 .0 0 5 0 Series Type 0 = Electromechanical 16 A relay, with screw terminal 1 = Electromechanical 16 A relay, with screwless terminal 2 = Timer multifunction (AI, DI, GI, SW), with screw terminal 5 = Electromechanical relay, with screw terminal 6 = Electromechanical relay, with screwless terminal No. of poles 1 = 1 pole, 6 or 16 A 2 = 2 pole, 8 A Coil version 0 = AC (50/60 Hz)/ DC 3 = Leakage current suppression for (110...125)V AC/DC - (230...240)V AC 7 = Sensitive DC, (6, 12, 24, 48, 60)V only 8 = AC (50/60 Hz) Coil voltage See coil specifications D: Special versions 0 = Standard C: Options 5 = Standard DC 6 = Standard AC/DC B: Contact circuit 0 = CO (nPDT) A: Contact material 0 = AgNi Standard 4 = AgSnO2 5 = AgNi + Au (5 µm) Selecting features and options: only combinations in the same row are possible. Type Coil version A B C D 38.01/11 7 0 - 4 0 5 0 38.01/11 0 0 - 4 0 6 0 38.51/61 7 0-4-5 0 5 0 38.51/61 0 - 3 - 8 0 - 4 - 5 0 6 0 38.52/62 7 0 - 5 0 5 0 38.52/62 0 0 - 5 0 6 0 38.21 0 0 0 6 0 6 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 55 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Ordering information Ordering information Solid state relay - Single output - 6.2 & 14 mm wide Example: 38 series screw terminal SSR relay interface module, 6.2 mm wide, 2 A output, 24 V DC input. 3 8.8 1.7.0 2 4 .9 0 2 4 Series Type 21 = Timer SSR 6.2mm wide, with screw terminal 31 = SSR 14mm wide, with screw terminal 41 = SSR 14mm wide, with screwless terminal 81 = SSR 6.2mm wide, with screw terminal 91 = SSR 6.2mm wide, with screwless terminal Input version 0 = AC/DC for 24V Timer SSR and (110...125)V and (220...240)V SSR only 3 = Leakage current suppression for (110...125)V AC/DC and (230...240)V AC SSR only 7 = DC, (6, 24, 60)V SSR only Input voltage See input specifications Output version 9024 = 2 A - 24 V DC (38.81 & 38.91) 9024 = 5 A - 24 V DC (38.31 & 38.41) 7048 = 0.1 A - 48 V DC (38.81 & 38.91) 8240 = 2 A - 240 V AC (38.81 & 38.91) 8240 = 3 A - 240 V AC (38.31 & 38.41) Selecting features and options: only combinations in the same row are possible. Type Input version Output version 38.81/91 7 9024 - 7048 - 8240 38.81/91 0 - 3 9024 - 7048 - 8240 38.31/41 7 9024 - 8240 38.21 0 9024 - 8240 Q-Pulse Id: TMS1594 Active: 18/04/2016 7 Page 56 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Technical data Technical data - 1 & 2 Pole Electromechanical Relays Insulation Insulation according to EN 61810-1 insulation rated voltage rated impulse withstand voltage pollution degree overvoltage category Insulation between coil and contacts (1.2/50 µs) Dielectric strength between open contacts Conducted disturbance immunity Burst (5...50)ns, 5 kHz, on A1 - A2 Surge (1.2/50 µs) on A1 - A2 (differential mode) Other data Bounce time: NO/NC Vibration resistance (10...55)Hz: NO/NC Power lost to the environment without contact current with rated current Terminals Wire strip length Screw torque Max. wire size Wire strip length Screw torque Max. wire size V kV kV V AC ms g W W mm Nm mm2 AWG mm Nm mm2 AWG 250 400 4 4 3 2 III III 6 (8 mm) 1,000 EN 61000-4-4 level 4 (4 kV) EN 61000-4-5 level 3 (2 kV) 1 Pole 6 A 1 Pole 16 A - 2 Pole 8 A 1/6 2/5 10/5 15/2 0.2 (12 V) - 0.9 (240 V) 0.5 (24 V) - 0.9 (240 V) 0.5 (12 V) - 1.5 (240 V) 1.3 (24 V) - 1.7 (240 V) 38.21 / 38.51 38.61 10 10 0.5 -- solid cable stranded cable solid cable stranded cable 1x2.5/2x1.5 1x2.5/2x1.5 1x2.5 1x2.5 1x14/2x16 1x14/2x16 1x14 1x14 38.01 / 38.52 38.11 / 38.62 10 10 0.5 -- solid cable stranded cable solid cable stranded cable 1x2.5/2x1.5 1x2.5/2x1.5 1x2.5 1x2.5 1x14/2x16 1x14/2x16 1x14 1x14 Contact specification - 1 & 2 Pole Electromagnetic Relays F 38 - Electrical life (AC) v contact current, 1 Pole 6 A H 38 - Maximum DC1 breaking capacity, 1 Pole 6 A Resistive load - cos = 1 Inductive load - cos = 0.4 DC breaking current (A) Cycles F 38 - Electrical life (AC) v contact current, 1 Pole 16 A and 2 Pole 8 A DC voltage (V) H 38 - Maximum DC1 breaking capacity, 1 Pole 16 A and 2 Pole 8 A Resistive load - cos = 1 Inductive load - cos = 0.4 38.01/11 limit current 38.52/62 limit current 2 contacts in series DC breaking current (A) Cycles 8 Q-Pulse Id: TMS1594 single contact DC voltage (V) · When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of 60·103 (1 Pole) or 80·103 ( 2 Pole) can be expected. · In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load. Note: the release time for the load will be increased. Active: 18/04/2016 Page 57 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Technical data Coil specifications - 1 Pole 6 A Electromechnical Relay Coil data sensitive DC, 1 Pole Nominal Coil Operating range voltage code UN Umin Umax V V V 6 7.006 4.8 7.2 12 7.012 9.6 14.4 24 7.024 19.2 28.8 48 7.048 38.4 57.6 60 7.060 48 72 Rated coil Power consumption consumption I at UN mA P at UN W 35 0.2 15.2 0.2 10.4 0.3 6.3 0.3 7 0.4 Coil data AC/DC, 1 Pole Nominal Coil Operating range Rated coil Power voltage code consumption consumption UN Umin Umax I at UN P at UN V V V mA VA/W 12 0.012 24 0.024 9.6 19.2 13.2 16 26.4 12 0.2/0.2 0.3/0.2 48 0.048 38.4 52.8 6.9 0.3/0.3 60 0.060 48 66 110...125 0.125 88 138 7 0.5/0.5 5(*) 0.6/0.6(*) 220...240 0.240 176 264 4(*) 1/0.9(*) (*) Rated coil consumption and power consumption values relate to UN = 125 and 240 V. Coil data AC, 1 Pole (indicated for max ambient temperature +70°C) Nominal voltage UN V (230...240) AC Coil code 8.240 Operating range Umin V 184 Umax V 264 Rated coil Power consumption consumption I at UN mA P at UN VA/W 3 0.7/0.3 Coil data, leakage current suppression types, 1 Pole Nominal voltage UN V (110...125) AC/DC (230...240) AC Coil code 3.125 3.240 Operating range Umin V 94 184 Umax V 138 264 Rated coil Power consumption consumption I at UN mA P at UN VA/W 8(*) 1/1(*) 7(*) 1.7/0.5(*) (*) Rated coil consumption and power consumption values relate to UN = 125 and 240 V. The 38 Series interface modules (supply version 3) have built-in leakage current suppression to address industry concerns of the contacts not dropping-out when there is residual current in the circuit; at (110...125)V AC and (230...240)V AC. This problem can occur, for example, when connecting the interface modules to PLC,s with triac outputs or when connecting via relatively long cables. Coil specifications - 1 Pole 16 A and 2 Pole 8 A Electromechanical Relay Coil data sensitive DC, 1 Pole 16 A and 2 Pole 8 A Coil data AC/DC, 1 Pole 16 A and 2 Pole 8 A Nominal voltage UN V 12 24 60 Coil code 7.012 7.024 7.060 Operating range Umin V 9.6 19.2 48 Umax V 14.4 28.8 72 Rated coil Power consumption consumption I at UN mA P at UN W 41 0.5 19.5 0.5 8 0.5 Nominal voltage UN V 24 60 110...125 220...240 Coil code 0.024 0.060 0.125 0.240 Operating range Umin V 19.2 48 88 184 Umax V 26.4 66 138 264 Rated coil Power consumption consumption I at UN mA P at UN VA/W 20 0.5/0.5 7.1 0.5/0.5 4.6 0.6/0.6 3.8 0.9/0.9 Coil specification - 1 & 2 Pole Electromagnetic Relays R 38 - DC coil operating range v ambient temperature 1 Pole and 2 Pole 1 2 3 4 1 - Max. permitted coil voltage at nominal load (DC coil). 2 - Max. permitted coil voltage at nominal load (AC/DC coils U 60 V). 3 - Max. permitted coil voltage at nominal load (AC/DC coils U > 60 V). 4 - Min pick-up voltage with coil at ambient temperature. Q-Pulse Id: TMS1594 Active: 18/04/2016 9 Page 58 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Technical data Technical data - Solid State Relays Other data Power lost to the environment Terminals Wire strip length Screw torque Max. wire size without output current with rated current Wire strip length Screw torque Max. wire size W W mm Nm mm2 AWG mm Nm mm2 AWG 38.81/38.91 0.25 (24 V DC) 0.4 38.81 10 0.5 solid cable 1x2.5 / 2x1.5 1x14 / 2x16 38.31 10 0.5 solid cable 1x2.5 / 2x1.5 1x14 / 2x16 stranded cable 1x2.5 / 2x1.5 1x14 / 2x16 stranded cable 1x2.5 / 2x1.5 1x14 / 2x16 38.31/38.41 0.5 2.2 (DC output) / 3 (AC output) 38.91 10 -- solid cable stranded cable 1x2.5 1x2.5 1x14 1x14 38.41 10 -- solid cable stranded cable 1x2.5 1x2.5 1x14 1x14 Input specifications - Solid State Relays type 38.81 and 38.91 - 6.2 mm wide Input data DC Nominal voltage UN V 6 24 60 Supply code 7.006 7.024 7.060 Operating range Umin V 5 16.8 35.6 Umax V 7.2 30 72 Release Rated coil Power voltage consumption consumption U I at UN P V mA W 2.4 7 0.2 10 10.5 0.3 20 6.5 0.4 Input data - Leakage current suppression types Nominal Supply Operating range Release Rated coil Power voltage code voltage consumption consumption UN Umin Umax U I at UN P at UN V V V mA W 110...125 AC/DC 3.125 94 138 44 8(*) 1/1(*) 230...240 AC 3.240 184 264 72 6.5(*) 1.6/0.6(*) (*) Rated coil consumption and power consumption values relate to UN = 125 and 240 V. Input data AC/DC Nominal Supply Operating range Release Rated coil Power voltage code voltage consumption consumption UN V 110...125 0.125 Umin V 88 Umax V 138 U I at UN P V mA VA/W 22 5.5* 0.7/0.7 220...240 0.240 184 264 44 3.5* 1/0.9 (*) Rated coil consumption and power consumption values relate to UN = 125 and 240 V. The 38 Series interface modules (supply version 3) have built-in leakage current suppression to address industry concerns of the contacts not dropping-out when there is residual current in the circuit; at (110...125)V AC and (230...240)V AC. This problem can occur, for example, when connecting the interface modules to PLC,s with triac outputs or when connecting via relatively long cables. Input specification - Solid State Relay types 38.31 and 38.41 - 14 mm wide Input data DC Nominal voltage UN V 24 Supply code 7.024 Operating range Umin V 16.8 Umax V 30 Release Rated coil Power voltage consumption consumption U I at UN P V mA W 5 12 0.3 10 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 59 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Timed interface modules Additional technical data - Timed Interface Module EMC specifications Type of test Reference standard Electrostatic discharge contact discharge EN 61000-4-2 air discharge EN 61000-4-2 Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 differential mode EN 61000-4-5 Radio-frequency common mode (0.15 ÷ 80 MHz) on Supply terminals EN 61000-4-6 Radiated and conducted emission EN 55022 Other data EMR Power lost to the environment without contact current W 0.1 with rated current W 0.6 Terminals 38.21 Wire strip length mm 10 Screw torque Nm 0.5 Max. wire size solid cable mm2 1x2.5 / 2x1.5 AWG 1x14 / 2x16 4 kV 8 kV 10 V/m 4 kV 4 kV 4 kV 10 V class B SSR 0.1 0.5 stranded cable 1x2.5 / 2x1.5 1x14 / 2x16 Times scales 1234 1234 1234 1234 Functions Wiring diagram (0.1...3)s (3...60)s (1...20)min (0.3...6)h LED U = Supply voltage Supply voltage OFF ON ON NO contact/output Open Open (time in progress) Closed = Output contact (AI) ON delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. (DI) ON pulse. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. 1234 1234 Q-Pulse Id: TMS1594 1234 1234 Active: 18/04/2016 (GI) Fixed pulse (0.5s) delayed. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs after a fixed time of 0.5s. (SW) Symmetrical recycling: ON start. Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ratio is 1:1 (time on = time off). 11 Page 60 of 1068 38.21 38.51 / 38.51.3 38.81 / 38.81.3 Screw terminal WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 38 Series - Relay interface modules - Dimensional data Outline drawings 38.01 38.31 38.52 Screw terminal 38.61 / 38.61.3 38.91 / 38.91.3 Screwless terminal 38.11 38.41 38.62 Screwless terminal 12 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 61 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 1 Introduction The MultiTrode level control relay is a solid-state electronic module in a hi-impact plastic case with a DIN rail attachment on the back, making a snap-on-snap-off installation. Any number of relays can be easily added to the DIN metal rail then wired together to form a complex pumping system that other wise may have to be controlled and operated by a programmed PLC. The relay is normally matched with the MultiTrode probe which works in conjunction with the relay and uses the conductivity of the liquid to complete an electrical circuit. 2 Electrical Overview There are 10 screw terminals on the unit. Facing the relay as shown, we look at the bottom terminals (left to right): · Lo (Charge mode). This is the point when the probe is dry the relay will turn on. · Lo (Discharge mode). This is the point when the probe in the tank is dry the relay will turn off. · Hi (Charge mode). This is the point when the probe in the tank is wet a relay will turn off · Hi (Discharge mode). This is the point when the probe in the tank is wet a relay will turn on. · C - is common earth. All earth bonding must be terminated here for correct operation. · " L " is "live" (240V AC) · " N " is "neutral" (240V AC) If the tank is plastic, or if you are conducting tests in a plastic bucket, or the vessel has no earth point inside, you must install an earth rod within the tank, vessel or bucket and make sure that it is bonded back to C on the relay unit. 3 DIP Switches 3.1 DIP Switches (See Wiring Diagram for full program functions.) 3.1.1 DIP 1 & 2 DIP 1 and 2 control the Sensitivity, in other words the cleaner the liquid the higher the sensitivity setting must be. Concentrated acids, minerals are by their own chemical composition highly conductive, so a low level of sensitivity is required, purified water is almost an insulator against electrical current flow so a higher sensitivity inside the relay is required. 3.1.2 DIP 3, 4 & 5 DIP switches 3, 4 and 5, control delay on activation. For example, in discharge mode with DIP switches 3, 4 and 5 set to 10 seconds, when the Hi point becomes wet it will activate the motor and it will take 10 seconds of continual coverage of the probe sensor to make the relay close and start the pump. This is invaluable when the probe is in a turbulent part of a well where fluid is splashing around touching the sensors momentarily, and false activation cannot be tolerated. 3.1.3 DIP 6 DIP switch 6 controls the charge/discharge function. Set "ON" for charge, and "OFF" for discharge MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS1594 13-May-2005 Active: 18/04/2016 Page 1 of 4 Page 62 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 3.2 Relay Contacts & their Applications 3.2.1 Contacts 15, 16 & 18 Contacts 15, 16, and 18 are used for electronic or visual notification of a change in state at the pump itself. Contacts 15, 16, and 18 are used for more advanced applications because they are a changeover relay, their state may be the same as contacts 25, 28 or the opposite. Both sets of contactors are triggered simultaneously. An example is when in discharge mode, (see Figure 1). You have a gravity flow coming in so the fluid reaches the lower sensor PB1, contacts 15 and 18 are open (15 being common to both contact 16 and 18) contacts 25 and 28 are also normally open but contacts 15 16 in this current situation are closed, whether PB1 is wet or dry is of no concern all will stay the same. The level now rises to PB2 and both relays change state, contacts 25 and 28 close to turn on the pump, contacts 15 and 16 are open, with 15 and 18 closed. In advanced applications this state change may be fed into a logic device to indicate the pump is running or the pump has stopped and perhaps light an LED or incandescent light source for visual confirmation that a change has occurred in the relay. 3.2.2 Contacts 25 & 28 Contacts 25 and 28 are used to control pump states. Contacts 25 and 28 are mostly used for turning on motors via a starting relay or solenoid, so, these sets of contacts react to the rising or falling levels of the fluid inside the tank, they will operate to turn on a pump in discharge mode when the top sensor is wet and in charge mode turn on the pump when the bottom sensor is dry. 4 Practical Overview 4.1 Discharge Mode DIP switch 6 set to "OFF" Figure 1 Discharge Mode Figure 1 shows two probes, (PB1 connected to Lo and PB2 connected to Hi). The pit is mostly underground and there is a gravity-fed inlet at the top left-hand side. The pit is empty with PB1 completely dry. Dipswitch 6 is set to "OFF." The relay operation depends on the electrical conductivity of liquid in the pit, i.e. no liquid = no current flow. The level starts to rise and covers PB1. This is a discharge operation so we do not want the relay to close and start a pump until the well is full so as the water rises it reaches PB2, the relay closes and the pump starts. The level now drops below PB2 but the pump still continues to run, the level continues to drop below PB1 the relay opens the pump stops. MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS1594 13-May-2005 Active: 18/04/2016 Page 2 of 4 Page 63 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 4.2 Charge Mode DIP switch 6 set to "On" Figure 2 Charge Mode Note: "C" is connected to common bonded earth. The unit will not operate correctly if not earthed. Let's look at the same relay but in a tank that is charging (DIP 6 is now on). See Figure 3, where liquid is being pumped into a tank, and discharging through a gravity feed, the tank is on steel stands "x" metres above the ground. With the tank full, PB1 and PB2 will be wet, the relay is off, and the pump has stopped. Water is slowly fed out from the bottom, and now as PB2 (HI) becomes dry nothing happens; the water now drops to below PB1 (Lo), and the pumps restarts to fill the tank. The pump will continue to fill the tank until PB2 (HI), becomes wet again. 4.3 MTRA Relay with Alarm (Discharge Applications Only) Figure 3 - MTRA Operation MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS1594 13-May-2005 Active: 18/04/2016 Page 3 of 4 Page 64 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting The MTRA relay works in the same way as the MTR relay except the MTRA has a separate alarm output, and does not have a charge mode. The planned application is to close a contact to illuminate a warning alarm light. . Various other applications have included introducing a third probe to latch another relay. In Figure 2 we see three probes in a pit that is plastic, note the steel rod in the tank. (In a plastic vessel a steel rod must be used to create an earth return in the liquid so probes can function.) PB1, PB2, and PB3 are dry, and the relay power LED is on. When water enters the pit and wets PB1, nothing happens, water now reaches PB2 causing contacts 13 and 14 to close, the pump LED to light, and the water to drop. If, for example, the pump has its inlet partially blocked, the level continues to rise and wets PB3. This closes a separate relay that can activate a red flashing light, an audible fog horn or send a 5 volt pulse into another device with the common cause to warn human beings that a spill is due to occur. If the pumps become unclogged and PB3 becomes dry the alarm opens again and breaks the circuit that stops the light from flashing or the foghorn from sounding. 5 Most Common Installation Problems The relay requires a path between the probes to earth through the liquid. If you are testing in a plastic bucket, have installed the probe in a plastic tank or have no good earthing in the vessel you will need to install a separate earth and make sure all earth bonding comes back to the C terminal. Most problems like these are traced back to a lack of or poor earthing, or open circuits in the probe wiring. Now is the time to check the relay by using "the bridge testing line technique" remember you must simulate a fluid flow to correctly ascertain a good relay or a bad one. (All DIPswitch settings from 1 to 6 should be off.) Cut two pieces of insulated flexible copper wire one black one red 250 mm long, strip both ends back 10 mm on both cables, and join one black end and one red end. Insert the joined ends into C on the relay box, observing all safe electrical practises. You should have one black wire and one red wire free. Set your relay for discharge mode (DIP switch 6 is off) with no sensors connected to the unit, connect the red wire to Lo nothing should happen (if it does return the relay for replacement or repair*). Now connect the black wire to the Hi terminal the relay activated LED should light instantly (if it does not, the relay should be returned for repair*). 6 Troubleshooting I have checked all the DIPswitches and settings but in discharge mode as soon as the bottom sensor gets wet the pump turns on then turns off almost straight away. The installation went fine but now and again the pump will not turn on even though I am sure the probe is wet. All wiring is complete and all DIPswitches have been checked but the pump will not turn on at all. · This is the most common problem encountered with relay set up and commissioning, the probe in the bottom of the tank is wired into the Hi terminal instead of the Lo terminal. · Check the sensitivity level set on the relay, some times the level is set for foul water but due to changes in the flow the water becomes grey or clear, try changing the setting from 20K to 80K and monitor the results carefully. · If you have completed the test schedule for the relay and it passed then check the wiring to the sensors for this is now where the problem lies or in the earthing arrangements. If possible check the resistance between the sensor cable and the steel sensor on the probe to prove a solid connection. * Please contact your distributor or agent before returning any product for repair or warranty claim. MultiTrode Pty Ltd--Australia Ph: +61 7 3340 7000 Fx: +61 7 3340 7077 E-mail: sales@multitrode.com.au Sydney--Australia Ph: +61 2 9533 7735 Fx: +61 2 9533 7790 Visit www.multitrode.com.au for the latest information MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS1594 13-May-2005 Active: 18/04/2016 MultiTrode Inc--USA Ph: +1 561 994 8090 Fx: +1 561 994 6282 E-mail: sales@multitrode.net Page 4 of 4 Page 65 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors Electrical Data CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Rated Insulation Voltage Ui IEC, AS,BS,SEV, VDE 0660 [V] 690V UL; CSA [V] 600V Rated Impulse Voltage Uimp [kV] Rated Voltage Ue-Main Contacts AC 50/60Hz [V] DC [V] Operating Frequency for AC Loads [Hz] 8kV 115, 200, 208, 230, 240, 380, 400, 415, 460, 500, 575, 690V 24, 48, 110, 115, 220, 230, 300, 440V 50...60Hz Switching Motor Loads Standard IEC Ratings AC-2, AC-3, AC-4 230V [A] 12 15 20 DOL Reversing 240V [A] 12 15 20 50Hz/60° C 400V [A] 9 12 16 415V [A] 9 12 16 500V [A] 7 10 14 690V [A] 5 7 9 230V [kW] 3 4 5.5 240V [kW] 3 4 5.5 400V [kW] 4 5.5 7.5 415V [kW] 4 5.5 7.5 500V [kW] 4 5.5 7.5 690V [kW] 4 5.5 7.5 UL/CSA/IEC DOL Reversing 115V [A] 9.8 9.8 16 60Hz/60° C 1Ø 230V [A] 10 12 17 115V [HP] 1/2 1/2 1 230V [HP] 1 1/2 2 3 200V [A] 7.8 11 17.5 3Ø 230V [A] 6.8 9.6 15.2 460V [A] 7.6 11 14 575V [A] 9 11 17 200V [HP] 2 3 5 230V [HP] 2 3 5 460V [HP] 5 7-1/2 10 575V [HP] 7-1/2 10 15 AC2 [ops/hr] 450 450 450 Maximum Operating Rate AC3 [ops/hr] 700 700 700 (at max. amps) AC4 [ops/hr] 200 150 120 26.5 35 38 44 62 26.5 35 38 44 62 23 30 37 43 60 23 30 37 43 60 20 25 30 38 55 12 18 21 25 34 7.5 10 11 13 18.5 7.5 10 11 13 18.5 11 15 18.5 22 32 11 15 20 22 32 13 15 20 25 37 10 15 18.5 22 32 24 17 2 3 17.5 22 21 17 5 7-1/2 15 15 400 600 80 24 34 34 56 28 28 40 50 2 3 3 5 5 5 7-1/2 10 25.3 32.2 32.2 48.3 28 28 42 54 27 34 40 52 27 32 32 52 7-1/2 10 10 15 10 10 15 20 20 25 30 40 25 30 30 50 400 400 400 300 600 600 600 500 80 70 70 70 72 85 72 85 72 85 72 85 67 80 42 49 22 25 22 25 40 45 40 45 45 55 40 45 56 80 68 68 5 7-1/2 15 15 62.1 78.2 68 80 65 77 62 62 20 25 25 30 50 60 60 60 250 200 500 500 60 50 Contactors A CA7 Approved by Lloyd's register of shipping. Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A39 Page 66 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors A Electrical Data Switching Motor Loads (continued) CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Contactors CA7 AC-4 230V 200,000 Op. Cycles 240V 50Hz 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V 60Hz 1Ø 115V 230V 115V 230V 200V 3Ø 230V 460V 575V 200V 230V 460V 575V Maximum Operating Rate [ Wye-Delta (Star Delta) 230V 50 Hz 240V 400V 415V 500V 690V 200V 60 Hz 230V 460V 575V AC Elevator Control Ratings UL / CSA Max FLC 500,000 operations 200V 230V 460V 575V 200V 230V 460V 575V [A] 4.3 [A] 4.3 [A] 4.3 [A] 4.3 [A] 4.3 [A] 4.3 [kW] 0.75 [kW] 0.75 [kW] 1.8 [kW] 1.8 [kW] 2.2 [kW] 3 [A] 4.3 [A] 4.3 [HP] 1/8 [HP] 1/3 [A] 4.3 [A] 4.3 [A] 4.3 [A] 4.3 [HP] 3/4 [HP] 1 [HP] 2 [HP] 3 250 [kW] 5.5 [kW] 5.5 [kW] 7.5 [kW] 7.5 [kW] 7.5 [kW] 7.5 [HP] 5 [HP] 5 [HP] 10 [HP] 10 [A] 8.0 [A] 7.8 [A] 6.8 [A] 7.6 [A] 6.1 [HP] 2 [HP] 2 [HP] 5 [HP] 5 6.6 6.6 6.6 6.6 6.6 6.6 1.5 1.5 3 3 3.7 5.5 6.6 6.6 1/4 1/2 6.6 6.6 6.6 6.6 1 1-1/2 3 5 250 7.5 7.5 10 11 11 10 5 7-1/2 15 15 11.0 11.0 9.6 11.0 9.0 3 3 7-1/2 7-1/2 9 9 9 9 9 9 2.2 2.2 4 4 5.5 7.5 9 9 1/3 1 9 9 9 9 2 2 5 7-1/2 220 10 10 13 15 15 13 7-1/2 10 20 20 16.0 11.0 15.2 14.0 11.0 3 5 10 1 0 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 2.2 3 3.7 4 6.3 7.5 11 2.2 3 4 4 7.5 7.5 11 4 5.5 6.3 7.5 13 15 20 4 5.5 6.3 7.5 13 17 20 5.5 7.5 7.5 10 15 20 25 7.5 10 11 15 22 25 32 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 1/2 1/2 3/4 1 2 2 3 1-1/2 2 2 2 3 5 5 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 10 12 14 16.5 25.5 31 38 2 3 3 3 7-1/2 7-1/2 10 3 3 3 5 7-1/2 10 10 5 7-1/2 10 10 15 20 25 7-1/2 10 10 10 20 25 30 200 200 200 200 120 120 120 13 17 20 22 32 37 45 13 18.5 20 22 32 40 50 20 25 32 40 55 63 80 22 25 37 40 55 63 80 22 25 32 45 63 80 90 18.5 25 32 40 55 63 80 7-1/2 10 15 20 30 40 50 10 15 20 25 40 50 60 25 30 40 50 75 100 125 25 30 40 50 75 100 125 21.0 27.0 31.0 37.0 43.0 54.0 62.0 17.5 25.3 25.3 32.2 32.2 48.3 62.1 15.2 22.0 28.0 28.0 42.0 54.0 68.0 21.0 27.0 27.0 34.0 40.0 52.0 65.0 17.0 22.0 27.0 32.0 41.0 52.0 62.0 5 7-1/2 7-1/2 10 10 15 20 5 7-1/2 10 10 15 20 25 15 20 20 25 30 40 50 15 20 25 30 40 50 60 A40 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 67 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors Electrical Data AC-1 Load, 30 Switching Ith Ambient Temperature 40º C 230V 240V 400V 415V 500V 690V Ambient Temperature 60º C Ith 230V 240V 400V 415V 500V 690V Maximum Operating Rate [ Continuous Current (UL/CSA) General Purpose Rating (40°) Open Enclosed Maximum Operating Rate [ Lighting Loads Elec.Dischrg.Lamps-AC-5a, single compensated Open Enclosed Max. capacitance at prospective 10kA short circuit current available at 20kA the contactor 50kA Incandescent Lamps - AC -5b Electrical endurance ~ 100,000 operations Switching power transformers AC-6a 50Hz Inrush = n Rated transformer current n=30 230 VAC 240 VAC 400 VAC 415 VAC 500 VAC 690 VAC n=20 230 VAC 240 VAC 400 VAC 415 VAC 500 VAC 690 VAC n=15 230 VAC 240 VAC 400 VAC 415 VAC 500 VAC 690 VAC CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 [A] 32 32 32 32 65 65 85 100 100 100 [kW] 13 13 13 13 26 26 34 40 40 40 [kW] 13 13 13 13 27 27 35 42 42 42 [kW] 22 22 22 22 45 45 59 69 69 69 [kW] 23 23 23 23 47 47 61 72 72 72 [kW] 28 28 28 28 56 56 74 87 87 87 [kW] 38 38 38 38 78 78 102 120 120 120 [A] 32 32 32 32 65 65 80 100 100 100 [kW] 13 13 13 13 26 26 32 40 40 40 [kW] 13 13 13 13 27 27 33 42 42 42 [kW] 22 22 22 22 45 45 55 69 69 69 [kW] 23 23 23 23 47 47 57 72 72 72 [kW] 28 28 28 28 56 56 69 87 87 87 [kW] 38 38 38 38 78 78 95 120 120 120 1,000 1,000 1,000 1,000 1,000 1,000 300 600 600 600 [A] 25 25 30 30 45 55 60 90 90 100 [A] 25 25 30 30 55 60 75 90 90 100 1,400 1,400 1,200 1,200 1,200 1,000 1000 700 700 600 [A] 22.5 [A] 22.5 [f] 1,000 [f] 500 [f] 200 25 25 1,000 500 200 28 28 1,000 500 200 29 29 1,000 500 200 40.5 37 2,700 1,350 540 45 41 2,700 1,350 540 77 57 3,200 1,600 640 81 57 4,000 2,000 800 85 81 4,000 2,000 800 90 90 4,700 2,350 940 [A] 12 16 18 22 30 37 43 60 70 76 [A] 10.9 10.9 10.9 10.9 20 20 23 40.8 40.8 40.8 [kVA] 4.3 4.3 4.3 4.3 8 8 9.2 16 16 16 [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 10 17 17 17 [kVA] 7.5 7.5 7.5 7.5 14 14 16 28 28 28 [kVA] 7.8 7.8 7.8 7.8 14 14 17` 29 29 29 [kVA] 9.4 9.4 9.4 9.4 17 17 20 35 35 35 [kVA] 13 13 13 13 24 24 27 49 49 49 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3 61.3 61.3 [kVA] 6.5 6.5 6.5 6.5 12 12 13.7 24.4 24.4 24.4 [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5 25.5 25.5 [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.5 42.5 42.5 [kVA] 11.7 11.7 11.7 11.7 21.6 21.6 24.8 44.1 44.1 44.1 [kVA] 14.1 14.1 14.1 14.1 26 26 29.9 53.1 53.1 53.1 [kVA] 19.5 19.5 19.5 19.5 35.9 35.9 41.2 73.3 73.3 73.3 [A] 22 22 22 22 40 40 46 82 82 82 [kVA] 2.3 2.3 2.3 2.3 4.3 4.3 5.0 8.8 8.8 8.8 [kVA] 2.4 2.4 2.4 2.4 4.5 4.5 5.2 9.2 9.2 9.2 [kVA] 4.1 4.1 4.1 4.1 7.5 7.5 8.6 15.3 15.3 15.3 [kVA] 4.2 4.2 4.2 4.2 7.8 7.8 8.9 15.9 15.9 15.9 [kVA] 5.1 5.1 5.1 5.1 9.4 9.4 10.8 19.1 19.1 19.1 [kVA] 7.0 7.0 7.0 7.0 12.9 12.9 14.9 26.4 26.4 26.4 Contactors A CA7 CA7 ratings for lighting loads are provided for technical reference. For cUL rated and labeled devices, see CAL7 contactors listed in this section. Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A41 Page 68 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors A Electrical Data CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Contactors Switching power transformers AC-6a 60Hz Inrush = n Rated transformer current [A] 10.9 10.9 10.9 10.9 20 20 23 40.8 40.8 40.8 n=30 CA7 200 VAC [kVA] 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1 14.1 14.1 208 VAC [kVA] 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7 14.7 14.7 240 VAC [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17 17 17 480 VAC [kVA] 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9 33.9 33.9 600 VAC [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4 42.4 42.4 660 VAC [kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6 46.6 46.6 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3 61.3 61.3 n=20 200 VAC [kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12 21.2 21.2 21.2 208 VAC [kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1 22.1 22.1 240 VAC [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5 25.5 25.5 480 VAC [kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51 51 51 600 VAC [kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7 63.7 63.7 660 VAC [kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1 70.1 70.1 [A] 22 22 22 22 40 40 46 82 82 82 n=15 200 VAC [kVA] 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4 28.4 28.4 208 VAC [kVA] 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5 29.5 29.5 240 VAC [kVA] 9 9 9 9 16.6 16.6 19.1 34.1 34.1 34.1 480 VAC [kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2 68.2 68.2 600 VAC [kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2 85.2 85.2 660 VAC [kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7 93.7 93.7 DC-1 Switching - 60°C 24VDC [A] 25 25 32 32 45 45 50 70 80 80 48VDC [A] 20 20 20 20 25 25 30 40 40 40 1 Pole 60VDC [A] 20 20 20 20 25 25 30 40 40 40 110VDC [A] 6 6 6 6 8 8 9 11 11 11 220VDC [A] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 440VDC [A] 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5 0.5 0.5 24VDC [A] 25 25 32 32 45 45 50 70 80 80 48VDC [A] 25 25 32 32 45 45 50 70 80 80 2 Poles in Series 60VDC [A] 25 25 32 32 45 45 50 70 80 80 110VDC [A] 25 25 32 32 45 45 50 70 80 80 220VDC [A] 8 8 8 8 10 10 10 15 15 15 440VDC [A] 1 1 1 1 1 1 1 1.5 1.5 1.5 24VDC [A] 25 25 32 32 45 45 63 90 90 100 48VDC [A] 25 25 32 32 45 45 63 90 90 100 3 Poles in Series 60VDC [A] 25 25 32 32 45 45 63 90 90 100 110VDC [A] 25 25 32 32 45 45 63 90 90 100 220VDC [A] 25 25 32 32 45 45 50 70 80 80 440VDC [A] 3 3 3 3 3.5 3.5 4 5 5 5 DC-2, 3, 5 Switching - 60°C Starting, reverse current braking, reversing, DC-5, 60ºC 24VDC [A] 25 25 32 32 45 45 63 90 90 100 48VDC [A] 25 25 32 32 45 45 50 70 70 80 60VDC [A] 25 25 32 32 45 45 50 70 70 80 Shunt Wound 110VDC [A] 20 20 25 25 30 30 35 70 70 80 3 Poles in Series 220VDC [A] 6 6 6 10 15 15 20 25 25 30 Series-wound Motors 440VDC [A] 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 3 Poles in Series 24VDC [A] 25 25 32 32 45 45 63 90 90 100 48VDC [A] 25 25 32 32 45 45 50 70 70 80 60VDC [A] 25 25 32 32 45 45 50 70 70 80 110VDC [A] 20 20 25 25 30 30 35 70 70 80 220VDC [A] 6 6 6 10 15 15 20 25 25 30 440VDC [A] 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 A42 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 69 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors Electrical Data Capacitor Ratings Capacitor Switching AC-6b-50 Hz Single Capacitor - 40°C Single Capacitor - 60°C Capacitor Bank - 40°C Capacitor Bank - 60°C Capacitor Switching - 60Hz Single Capacitor - 40°C Capacitor Bank - 40°C 230 V 240 V 400 V 415 V 500 V 690 V 230 V 240 V 400 V 415 V 500 V 690 V 230 V 240 V 400 V 415 V 500 V 690 V 230 V 240 V 400 V 415 V 500 V 690 V 200 V 230 V 460 V 600 V 200 V 230 V 460 V 600 V A CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Contactors [kVar] 8 8 8.5 9 14 14 24 28 28 28 [kVar] 8 8 8.5 9 14 14 25 29 29 29 [kVar] 8 8 10 12.5 20 24 35 48 48 48 [kVar] 8 8 10 12.5 20 25 35 50 50 50 [kVar] 8 [kVar] 8 8 8 10 10 12.5 12.5 20 20 25 25 35 35 50 50 55 55 60 60 CA7 [kVar] 8 8 8.5 9 12.5 12.5 18 28 28 28 [kVar] 8 8 8.5 9 12.5 12.5 18 29 29 29 [kVar] 8 8 10 12.5 20 21.5 30 42 48 48 [kVar] 8 8 10 12.5 20 22 30 42 50 50 [kVar] 8 8 10 12.5 20 25 30 42 50 55 [kVar] 8 8 10 12.5 20 25 30 42 50 55 [kVar] 5 5 8 9 12.5 14 20 28 28 28 [kVar] 5 5 8 9 12.5 14 20 29 29 29 [kVar] 5 5 8 10 15 20 25 40 48 48 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 9 12.5 12.5 18 28 28 28 [kVar] 5 5 8 9 12.5 12.5 18 29 29 29 [kVar] 5 5 8 10 15 20 25 40 48 48 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 10 15 20 25 40 50 50 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 [kVar] 5 5 8 9 12.5 14 20 28 28 28 9 12.5 14 20 29 29 29 10 15 20 25 40 50 50 10 15 20 25 40 50 60 9 12.5 12.5 18 28 28 28 9 12.5 12.5 18 29 29 29 10 15 20 25 40 50 50 10 15 20 25 40 50 50 CA7 capacitor ratings are provided for technical reference. For cUL rated and labeled devices, see CAQ7 contactors listed in this section. CA7-9...CA7-30 = L min. 30 µH; CA7-37...CA7-85 = L min. 6 µH Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A43 Page 70 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors A Electrical Data Contactors Resistance and Watt Loss Ie AC3 Resistance per power pole Watt Loss - 3 power poles Coil and 3 power poles AC DC Coil only AC DC CA7 Short-Circuit Coordination Max. Fuse or circuit breaker ratings DIN Fuses -gG, gL Available Fault Current Type "1" (690V) Type "2" (690V) BS 88 Fuses Available Fault Current Type "1" (690V) Type "2" (690V) Class K1, RK1 Fuses Available Fault Current Type "2" (600V) cUL Short-Circuit Ratings Class K1, RK1, K5, and RK5 Fuses Available Fault Current cUL Max. Rating (600V) Type 1 Class CC & CSA HRCI Fuses Available Fault Current cUL Max. Rating (600V) Type 2 Class J CSA & HRCI-J Fuses Available Fault Current cUL Max. Rating (600V) Type 2 Inverse-Time Circuit Breaker Available Fault Current cUL Max. Rating 480V Type 1 cUL Max. Rating 600V Type 1 Short Time Current Withstand Ratings Icw 60° C 10 s Off Time Between Operations CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 [m] 2.7 2.7 2.7 [W] 0.66 1.2 2.1 [W] 3.3 3.8 4.7 [W] 6.7 7.2 8.1 [W] 2.6 2.6 2.6 [W] 6.0 6.0 6.0 2.0 2.0 2.0 1.5 0.9 0.9 0.9 3.2 5.4 8.2 8.3 9.7 14.0 19.5 6.2 8.4 11.2 11.5 11 13.8 17.5 12.4 14.6 17.4 18.4 11 13.8 17.5 3.0 3.0 3.0 3.2 4.5 4.5 4.5 9.2 9.2 9.2 10.0 4.9 4.9 4.9 [A] 100 KA [A] 50 [A] 25 100 KA 50 35 100 KA 50 35 [A] 80 KA [A] 25 [A] 25 80 KA 32 32 80 KA 35 35 [A] 100 KA 100 KA 100 KA [A] 15 20 20 100 KA 80 40 100 KA 125 80 100 KA 125 80 100 KA 160 100 100 KA 250 160 100 KA 250 160 100 KA 250 160 80 KA 50 50 80 KA 63 63 80 KA 80 80 80 KA 100 100 80 KA 100 100 80 KA 125 125 80 KA 160 160 100 KA 100 KA 100 KA 100 KA 100 KA 100 KA 100 KA 30 40 50 50 80 100 100 [A] 5 KA 5 KA 5 KA [A] 35 40 70 [A] 100 KA 100 KA 100 KA [A] 15 20 30 [A] 100 KA 100 KA 100 KA [A] 15 20 30 [A] 5 KA 5 KA 5 KA [A] 30 30 50 [A] ~ ~ ~ 5 KA 5 KA 5 KA 5 KA 5 KA 5 KA 5 KA 90 110 125 150 200 250 300 100 KA ~ ~ ~ ~ ~ ~ 30 ~ ~ ~ ~ ~ ~ 100 KA 100 KA 100 KA 100 KA 100 KA 100 KA 100 KA 30 50 50 70 80 100 150 5 KA 5 KA 5 KA 5 KA 5 KA 10 KA 10 KA 50 125 125 125 250 250 250 ~ 125 125 125 250 250 250 [A] 170 170 170 [Min.] 20 20 20 215 300 304 375 700 700 700 20 20 20 20 20 20 20 When used as a Branch Circuit Protection device, NEC 430-152 defines the maximum rating of an Inverse-time circuit breaker to be sized at 250% of the motor nameplate FLA for most applications. UL Listed Combination. (UL File E41850) Per UL508A, NEC409 abd CSA 22.2 No.14 for contactor and fuses or circuit breaker only. Per IEC 60947-1 for contactor and fuses only. A44 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 71 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors & Overload Relay Electrical Data Short Circuit Coordination le AC3 Type 2 Coordination Combinations (contactor, overload and fuses) -- Per UL 508 and IEC 60947-4-1 Contactor CA7-9 CA7-12... CA7-16... CA7-23... CA7-30... CA7-37... CA7-43... CA7-60... CA7-72... CA7-85... Overload Relay CEP7-M/A/B32-0.32... CEP7-M/A/B32-1.0... CEP7-M/A/B32-2.9... CEP7-M/A/B32-5... CEP7-M/A/B32-12... CEP7-M/A/B32-12... CEP7-M/A/B32-32... CEP7-M/A/B32-32... CEP7-M/A/B37-37... CEP7-M/A/B37-37... CEP7-M/A/B45-45... CEP7-M/A/B85-85... CEP7-M/A/B85-85... CEP7-M/A/B85-85... Withstand Rating 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA Maximum Voltage 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V Max. Amp Rating (UL Class CC or J Fuses) 1 2 6 10 15 20 20 30 40 50 50 80 100 100 UL Listed Combinations (contactor, overload and circuit breaker) Per UL 508 Contactor CA7-9...12 CA7-12 CA7-16...23 CA7-23 CA7-30...37 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Overload Relay CEP7-M/A32-2.9...12 CT7-24-0.16...10 CT7-24-16 CEP7-M/A32-2.9...32 CT7-24-0.16...16 CT7-24-24 CEP7-M/A37-12...37 CT7-24-16...CT7-45-30 CT7-45-45 CEP7-M/A45...45 CT7-45-30...45 CEP7-M/A85...85 CT7-75-30...60 CEP7-M/A85...85 CT7-75-30...75 CEP7-M/A85...85 CT7-75-30...CT7-100-90 Withstand Rating 5kA 5kA 5kA 5kA 5kA 10kA 10kA Maximum Voltage 480V 480V 600V 600V 600V 600V 600V Max. Amp Rating (UL Listed Circuit Breaker) 30 50 125 125 250 250 250 CEP7 First Generation Scheduled for Obsolesence 2006 Contactors A CA7 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A45 Page 72 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors & Overload Relay A Short Circuit Ratings Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14 Contactors CEP7 Second Generation Cat. No. Max. avail- Conditional able fault S.C. current, current (kA) Iq (kA) S.C.P.D. ED1AB, EEAB ED1BB, EEBB 1 Suitable for use with fuses only ED1CB, ED1DB, CA7 ED1EB, EECB, CEP7 EEDB, EEEB, EEED, 5 EEFD, EEPB, EERB, EESB, EETD 600 Not restricted to EEEE, EEFE, EEGE, EEUE 10 IEC Short Circuit Ratings per EN60947-4-1 CEP7 Second Generation Cat. No. ED1AB, EEAB ED1BB, EEAB CondiProspective tional S.C. current, S.C. Ir (kA) current, Iq (kA) 1 ED1CB, ED1DB, EECB, EEDB, 1 CEP7 EEPB, EERB ED1EB, EEEB, 100 EEED, EEFD, EEEE, EEFE, 3 EESB, EETD EEGE, EEUE 5 Max. voltage (V) 690 S.C.P.D. Suitable for use with fuses only Not restricted to High Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14 CEP7 Second Generation Cat. No. ED1AB, EEAB ED1BB, EEBB ED1CB, ED1DB, ED1EB, EEEB, EECB, EEDB CEP7 EEED, EEFD EEEE, EEFE EEGE Contactor Cat. No. CA7-09 CA7-09 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 Max. starter FLC (A) Max. available fault current (kA) 0.5 1 09 12 16 23 30 100 37 43 60 72 85 Max. voltage (V) 600 UL Class J and CSA HRCI-J fuse (A) 3 6 20 20 30 30 50 50 70 80 100 150 IEC Type 1 and Type II Fuse Coordination with CA7 Series contactors per EN60947-4-1 CEP7 Second Generation Cat. No. ED1AB, EEAB ED1BB, EEBB ED1CB, ED1DB, EECB, EEDB ED1EB, EEEB CEP7 EEED, EEFD EEEE, EEFE EEGE Contactor Cat. No. CA7-09 CA7-09 CA7-12 CA7-16 CA7-23 CA7-09 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA7-60 CA7-72 CA7-85 Max. starter FLC (A) 0.5 1 09 12 16 23 09 12 16 23 30 37 43 60 72 85 60 72 85 Prospective S.C. current, Ir (kA) 1 1 3 3 3 5 Conditional S.C. current, Iq (kA) 100 Max. voltage (V) 600 Type I with Class J fuse (A) 3 6 20 20 30 30 20 20 30 30 50 50 70 80 100 150 80 100 150 Type II with Class J fuse (A) 3 6 15 20 30 30 15 20 30 30 50 50 70 80 100 150 80 100 150 A46 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 73 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors Electro-Mechanical Data Service Life Mechanical AC DC Electrical AC-3 (400V) AC Shipping Weights AC - CA7 AC -CAU7 DC - CA7 DC - CAU7 Terminations - Power Description CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 [Mil.] 13 13 13 13 13 13 12 10 10 10 [Mil.] 13 13 13 13 13 13 13 10 10 10 [Mil.] 1.3 1.3 1.3 1.3 1.3 1.3 1.0 1.0 1.0 1.0 [kg] 0.39 0.39 0.39 0.39 0.48 0.49 0.51 1.45 1.45 1.45 [Lbs.] 0.86 0.86 0.86 0.86 1.06 1.08 1.12 3.20 3.20 3.20 [kg] 0.85 0.85 0.85 0.85 1.08 1.08 1.15 3.14 3.14 3.14 [Lbs.] 1.89 1.89 1.89 1.89 2.39 2.39 2.54 6.92 6.92 6.92 [kg] 0.60 0.60 0.60 0.73 0.85 0.85 1.00 1.47 1.47 1.47 [Lbs.] 1.32 1.32 1.32 1.61 1.87 1.87 2.20 3.24 3.24 3.24 [kg] 1.27 1.27 1.27 1.53 1.81 1.81 2.13 3.22 3.22 3.22 [Lbs.] 2.81 2.81 2.81 3.39 4.00 4.00 4.70 7.10 7.10 7.10 Contactors A CA7 Torque Requirement Terminations - Control Description 1 Wire 2 Wires 1 Wire 2 Wires 1 Wire 2 Wires One saddleclamp per pole: cross, slotted or Pozidrive No. 2/blade No. 3 screw [mm2] 1...4 1...4 1...4 1...4 [mm2] 1...4 1...4 1...4 1...4 Dual connection; one saddleclamp and one box lug per pole; cross, slotted or Pozidrive No. 2/blade No. 4 screw 2.5...10 2.5...10 2.5...16 2.5...10 2.5...10 2.5...10 Dual connection; two box lugs per pole Allen Head: 4mm, 5/32 2.5...35 2.5...35 2.5...35 2.5...25 2.5...25 2.5...25 [mm2] 1.5...6 1.5...6 [mm2] 1.5...6 1.5...6 1.5...6 1.5...6 1.5...6 1.5...6 2.5...16 2.5...16 2.5...16 2.5...16 2.5...25 2.5...50 2.5...50 2.5...50 2.5...16 2.5...35 2.5...35 2.5...35 [AWG] 16...10 16...10 16...10 16...10 14...4 14..4 14...4 14...1 14...1 14...1 [AWG] 16...10 16...10 16...10 16...10 14...4 14..4 14...4 14...1 14...1 14...1 [Nm] 1.0...2.5 1.0...2.5 1.0...2.5 1.0...2.5 2.5...3.5 2.5...4 [Lb-in] 9...22 9...22 9...22 9...22 22...31 22...35 2.5...4 3.5...6 3.5...6 3.5...6 22...35 31...53 31...53 31...53 Coils Wires Control Modules Wires Torque Requirement 1 or 2 1or 2 Degree of Protection - contactor Protection Against Accidental Contact [mm2] [AWG] [mm2] [AWG] [Nm] [Lb-in] Environmental and General Specifications Ambient Temperature Storage Operation Conditioned 15% current reduction after AC-1 at >60° C Altitude at installed site Resistance to Corrosion/Humidity Shock Resistance Vibration Resistance Pollution Degree Operating Position Standards Approvals Combination Screw Head: Cross, Slotted, Pozidrive 1.5...6 16...12 1.5...6 16...12 1...2.5 9...13 IP 2LX per IEC 529 and DIN 40 050 (with wires installed) Safe from touch by fingers and back-of-hand per VDE 0106; Part 100 -55...+80° C (-67...176° F) - [CRI7E Electronic Interface -50...+80° C (-58...176° F)] -25...+60° C (-13...140° F) -25...+70° C (-13...158° F) 2000 meters above sea level per IEC 947-4 Damp-alternating climate: cyclic to IEC 68-2, 56 cycles Dry heat: IEC 68-2, +100°C (212° F), relative humidity <50%, 7 days. Damp tropical: IEC 68-2, +40°C (104°F), relative humidity <92%, 56 days. IEC 68-2: Half sinusoidal shock 11ms, 30g (in all three directions) IEC 68-2: Static > 2g, in normal position no malfunction <5g 3 Refer to Dimension Pages IEC947-1/4, EN 60947; UL 508; CSA 22.2, No. 14 CE, UL, CSA Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A47 Page 74 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 3-Pole Contactors Contactors A Lug Kit and Paralleling Link Specifications CA7-PKN23 / KL23 CA7-P-K37 CA7-P-K43 CA7-P-K85 CA7-P-B23 CA7-P-B37 Approvals UL Listed; CSA Certified; C Conformity to Standards UL508; CSA 22.2 No. 14; IEC 60947-4 Protection Against Accidental Contact IP2LX Finger Protection Terminations CA7 Description Wire Size Torque Requirement 1 Wire 1 Wire 1 Wire Cross, slotted or Pozidrive screw Allen Head; 5mm, 3/16 Allen Head; 7 mm, 15/32 [mm2] [mm2] [AWG] [Nm] [Lb-in] 4...16 4...25 10...4 2...3 18...27 4..16 4..25 10...4 2...3 18...27 6...35 6...50 8...2 3..6 27...54 10...70 10...95 8..2/0 8...12 72...108 35...70 35...95 0...2/0 6...12 54...108 35...70 35...95 0...2/0 6....12 54...108 Coil Data Voltage Range AC: 50Hz, 60Hz, 50/60 Hz DC Coil Consumption Pickup [xUs] Dropout [xUs] Pickup [xUs] Dropout [xUs] AC: 50Hz, 60Hz, 50/60 Hz Pickup [VA/W] Hold-in [VA/W] True DC Coils (CA7C) Pickup [W] Hold-in [W] Two Winding DC Coils Pickup [W] CA7Y & CA7D Hold-in [W] Operating Times AC: 50Hz, 60Hz, 50/60 Hz Pickup [ms] Dropout [ms] with RC Suppressor Dropout [ms] True DC Coils (CA7C) Pickup [ms] without Suppression Dropout [ms] with Integrated Suppression Dropout [ms] with External Suppression Dropout [ms] Two Winding DC Coils (CA7Y/D) Pickup [ms] with Internal Suppression Dropout [ms] CA7-9 70/50 8/2.6 6.5 6.5 120 1.1 15...30 10...60 10...60 40...70 7...15 14...20 70...95 17...26 9...20 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 0.85...1.1 0.3...0.6 0.8...1.1 (9V coils = 0.65...1.3; 24V coils = 0.7...1.25) 0.1...0.6 70/50 8/2.6 6.5 6.5 120 1.1 70/50 8/2.6 6.5 6.5 120 1.1 70/50 9/3 9.2 9.2 200 1.2 80/60 9/3 9.2 9.2 200 1.2 80/60 9/3 9.2 9.2 200 1.2 130/90 10/3.2 10.1 10.1 200 1.3 200/110 16/4.5 ~ ~ 200 4.5 200/110 16/4.5 ~ ~ 200 4.5 200/110 16/4.5 ~ ~ 200 4.5 15...30 10...60 10...60 40...70 7...15 14...20 70...95 17...26 9...20 15...30 10...60 10...60 40...70 7...15 14...20 70...95 15...27 14...24 15...30 10...60 10...60 40...70 7...15 17...23 80...125 15...27 14...24 15...30 10...60 10...60 50...80 7...15 17...23 80...125 15...27 14...24 15...30 10...60 10...60 50...80 7...15 17...23 80...125 15...27 14...24 15...30 20...40 20...40 20...40 10...60 10...60 10...60 10...60 10...60 10...60 10...60 10...60 50...80 ~ ~ ~ 7...15 ~ ~ ~ 17...23 ~ ~ ~ 80...125 ~ ~ ~ 15...27 20...40 20...40 20...40 14...24 20...35 20...35 20...35 220V. A48 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 75 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 4-Pole Contactors Electrical Data Rated Insulation Voltage Ui IEC, AS, BS, SEV, VDE 0660 UL; CSA Rated Impulse Voltage Uimp Rated Voltage Ue - Main Contacts AC 50/60Hz DC Operating Frequency for AC Loads Contactors CA7-9- CA7-12- CA7-16- CA7-23- CA7-40-M22 CA7-40-M40 CA7-90-M22 CA7-90-M40 A M40(31; 22) M40(31; 22) M40(31; 22) M40(31; 22) 690V 600V 8 kV 115, 200, 208, 230, 240, 380, 400, 415, 460, 500, 575, 690V 24, 48, 110, 115, 220, 230, 300, 440V 50...60Hz CA7 Switching Motor Loads Standard IEC Ratings AC-2, AC-3, AC-4 230V [A] 12 15 20 26.5 38 38 85 85 DOL & Reversing 240v [A] 12 15 20 26.5 38 38 85 85 50Hz/60ºC 400V [A] 9 12 16 23. 37 37 85 85 415V [A] 9 12 16 23 37 37 85 85 500V [A] 7 10 14 20 29 30 80 80 690V [A] 5 7 9 12 9 21 22 49 230V [kW] 3 4 5.5 7.5 11 11 25 25 240V [kW] 3 4 5.5 7.5 11 11 25 25 400V [kW] 4 5.5 7.5 11 18.5 18.5 45 45 415V [kW] 4 5.5 7.5 11 18.5 18.5 45 45 500V [kW] 4 5.5 7.5 13 18.5 20 55 55 690V [kW] 4 5.5 7.5 10 7.5 18.5 18.5 45 UL/CSA/IEC DOL & Reversing 115V [A] 7.2 9.8 16 24 34 34 80 80 60Hz/60ºC 1Ø 230V [A] 18 12 17 17 28 28 68 68 115V [HP] 1/2 1/2 1 2 3 3 7-1/2 7-1/2 230V [HP] 1-1/2 2 3 3 5 5 15 15 200V [A] 7.8 11 17.5 17.5 32.2 32.2 78.2 78.2 230V [A] 6.8 9.6 15.2 22 28 28 80 80 460V [A] 7.6 11 14 21 34 34 65 77 575V [A] 9 11 17 17 17 32 22 52 200V [HP] 2 3 5 5 10 10 25 25 230V [HP] 2 3 5 7-1/2 10 10 30 30 460V [HP] 5 7-1/2 10 15 25 25 50 60 575V [HP] 7-1/2 10 15 15 15 30 20 50 Maximum Operating Rate AC2 [ops/hr] 450 450 450 400 400 400 200 200 (at max. amps) AC3 [ops/hr] 700 700 700 600 600 600 500 500 AC4 [ops/hr] 200 150 120 80 70 70 50 50 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A49 Page 76 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 4-pole Contactors Contactors A CA7 Electrical Data AC-1 Load, 3Ø Switching Ambient Temperature 40ºC Ambient Temperature 60º Ith 230V 240V 400V 415V 500V 690V Ith 230V 240V 400V 415V 500V 690V CA7-9M40(31; 22) [A] [kW] 32 [kW] 13 [kW] 13 [kW] 22 [kW] 23 [kW] 28 [kW] 38 [kW] 32 [kW] 13 [kW] 13 [kW] 22 [kW] 23 [kW] 28 [kW] 38 CA7-12M40(31; 22) 32 13 13 22 23 28 38 32 13 13 22 23 28 38 Max Operating Rate [ops/hour] 1,000 1,000, Continuous Current (UL/CSA) General Purpose Rating (40º) Open [A] 25 25 Enclosed [A] 25 25 Max. Operating Rate [ops/hour] 1,400 1,400 Lighting Loads Elec. Dischrg.Lamps-AC-5a, Open [A] 22.5 25 single compensated Enclosed [A] 22.5 25 Incandescent Lamps AC-5b, Electrical endurance~100,000 operations 12 16 DC-1 Switching - 60ºC 24VDC [A] 25 25 48VDC [A] 20 20 1 Pole 60VDC [A] 20 20 110VDC [A] 6 6 220VDC [A] 1.5 1.5 440VDC [A] 0.4 0.4 24VDC [A] 25 25 48VDC [A] 25 25 2 Pole in Series 60VDC [A] 25 25 110VDC [A] 25 25 220VDC [A] 8 8 440VDC [A] 1 1 24VDC [A] 25 25 48VDC [A] 25 25 3 Poles in Series 60VDC [A] 25 25 110VDC [A] 25 25 220VDC [A] 25 25 440VDC [A] 3 3 24VDC [A] 25 25 48VDC [A] 25 25 4 Poles in Series 60VDC [A] 25 25 110VDC [A] 25 25 220VDC [A] 25 25 440VDC [A] 8 8 CA7-16M40(31; 22) 32 13 13 22 23 28 38 32 13 13 22 23 28 38 1,000, 30 30 1,200 28 28 18 32 20 20 6 1.5 0.4 32 32 32 32 8 1 32 32 32 32 32 3 32 32 32 32 32 8 CA7-23M40(31; 22) 32 13 13 22 23 28 38 32 13 13 22 23 28 38 1,000 30 30 1,200 29 29 22 32 20 20 6 1.5 0.4 32 32 32 32 8 1 32 32 32 32 32 3 32 32 32 32 32 8 CA7-40-M22 CA7-40-M40 CA7-90-M22 CA7-90-M40 75 75 130 130 30 30 52 52 31 31 54 54 52 52 90 90 54 54 93 93 65 65 113 113 90 90 155 155 60 60 110 110 24 24 44 44 25 25 46 46 42 42 76 76 43 43 79 79 52 52 95 95 72 72 131 131 300 300 600 600 60 60 125 130 60 60 125 130 1,000 1,000 600 600 65 65 115 115 54 54 95 95 18 25 60 75 45 45 80 80 25 25 40 40 25 30 40 40 10 10 11 11 1.5 1.5 1.8 1.8 0.4 0.4 0.5 0.5 45 45 80 80 45 45 80 80 45 45 80 80 45 45 80 80 10 10 15 15 1 1 1.5 1.5 ~ 48 ~ 100 ~ 48 ~ 100 ~ 48 ~ 100 ~ 48 ~ 100 ~ 48 ~ 80 ~ 3.5 ~ 5 ~ 60 ~ 110 ~ 60 ~ 110 ~ 60 ~ 110 ~ 60 ~ 110 ~ 60 ~ 100 ~ 10 ~ 15 CA7 ratings for lighting loads are provided for technical reference. For cUL rated and labeled devices, see CAL7 contactors listed in this section. A50 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 77 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 4-pole Contactors Electrical Data Resistance and Watt Loss Ie AC3 Resistance per power pole Watt Loss - 4 power poles Coil and 4 power poles AC DC (true) DC (2 winding) Short Circuit Coordination DIN Fuses -gG, gL Available Fault Current Type "1" (690V) Type "2" (690V) BS 88 Fuses Available Fault Current Type "1" (690V) Type "2" (690V) Class K1, RK1 Fuses Available Fault Current Type "2" (600V) cUL Short-Circuit Ratings Class K1, RK1, K5, and RK5 Fuses Available Fault Current cUL Max. Rating (600V) Type 1 Class CC & CSA HRCI Fuses Available Fault Current cUL Max. Rating (600V) Type 2 Class J CSA & HRCI-J Fuses Available Fault Current cUL Max. Rating (600V) Type 2 Inverse-Time Circuit Breaker Available Fault Current cUL Max. Rating 480V Type 1 cUL Max. Rating 600V Type 1 CA7-9- CA7-12- CA7-16- CA7-23- CA7-40-M22 CA7-40-M40 CA7-90-M22 CA7-90-M40 A M40(31; 22) M40(31; 22) M40(31; 22) M40(31;22) Contactors [m] 2.7 2.7 2.7 2.0 2.0 [W] 2.8 2.8 2.8 2.0 11.3 [W] 13.7 13.7 13.7 10.8 26.1 [W] 17.6 17.6 17.6 17.4 32.6 [W] ~ ~ ~ ~ ~ 1.5 0.8 0.7 8.4 13.5 11.8 37.4 36.0 56.3 43.9 ~ ~ ~ 32.5 52.8 CA7 [A] 100 KA [A] 50 [A] 25 [A] 80 KA [A] 25 [A] 25 [A] 100 KA [A] 15 100 KA 50 35 80 KA 32 32 100 KA 20 100 KA 50 35 80 KA 35 35 100 KA 20 100 KA 80 40 80 KA 50 50 100 KA 30 50 KA 160 100 ~ ~ ~ 100 KA 70 [A] 5 KA [A] 35 [A] 100 KA [A] 15 [A] 100 KA [A] 15 [A] 5 KA [A] 30 [A] ~ 5 KA 40 100 KA 20 100 KA 20 5 KA 30 ~ 5 KA 70 100 KA 30 100 KA 30 5 KA 50 ~ 5 KA 90 100 KA 30 100 KA 30 5 KA 50 ~ 5 KA 125 ~ ~ 100 KA 70 5 KA 125 125 50 KA 160 100 ~ ~ ~ 100 KA 70 5 KA 125 ~ ~ 100 KA 70 5 KA 125 125 50 KA 250 160 ~ ~ ~ 100 KA 100 50 KA 250 160 ~ ~ ~ 100 KA 100 10 KA 300 ~ ~ 100 KA 150 10 KA 250 250 10 KA 300 ~ ~ 100 KA 150 10 KA 250 250 Short Time Current Withstand Ratings Icw 60° C [A] 170 170 170 215 304 304 700 700 Off Time Between Operations [Min.] 20 20 20 20 5 5 5 5 When used as a Branch Circuit Protection device, NEC 430-152 defines the maximum rating of an Inverse-time circuit breaker to be sized at 250% of the motor nameplate FLA for most applications. UL Listed Combination. (UL File E41850) Per UL508A, NEC409 abd CSA 22.2 No.14 for contactor and fuses or circuit breaker only. Per IEC 60947-1 for contactor and fuses only. UL Testing not complete a the time of printing this catalog. Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A51 Page 78 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 4-pole Contactors Contactors A Mechanical Data Service Life Mechanical Shipping Weights AC - CA7 CA7 DC - CA7 Terminations - Power Description CA7-9- M40(31; 22) CA7-12- M40(31; 22) CA7-16- M40(31; 22) CA7-23- M40(31; 22) CA7-40-M22 CA7-40-M40 CA7-90M22 CA7-90M40 AC [Mil.] 13 13 13 13 10 DC [Mil.] 13 13 13 13 10 10 10 10 10 10 10 [kg] 0.39 0.39 0.39 0.39 0.51 [Lbs.] 0.86 0.86 0.86 0.86 1.12 [kg] 0.60 0.60 0.60 0.73 1.00 [Lbs.] 1.32 1.32 1.32 1.61 2.20 0.51 1.45 1.45 1.12 3.20 3.20 1.00 1.47 1.47 2.20 3.24 3.24 Torque Requirement Terminations - Control Description 1 Wire [mm2] 2 Wires [mm2] 1 Wire [mm2] 2 Wires [mm2] 1 Wire [AWG] 2 Wires [AWG] [Nm] [Lb-in] One saddleclamp per pole: cross, slotted or Pozidrive No. 2/blade No. 3 screw 1...4 1...4 1.5...6 1.5...6 16...10 16...10 1.0...2.5 9...22 1...4 1...4 1.5...6 1.5...6 16...10 16...10 1.0...2.5 9...22 1...4 1...4 1.5...6 1.5...6 16...10 16...10 1.0...2.5 9...22 1...4 1...4 1.5...6 1.5...6 16...10 16...10 1.0...2.5 9...22 Dual connection; one saddleclamp and one box lug per pole; cross, slotted or Pozidrive No. 2/blade No. 4 screw 2.5...10 2.5...10 2.5...10 2.5...10 2.5...16 2.5...16 2.5...16 2.5...16 14...6 14..6 14...6 14..6 2.5...4 22...35 2.5...4 22...35 Dual connection; two box lugs per pole Allen Head: 4mm, 5/32 2.5...16 2.5...10 2.5...25 2.5...16 14...4 14...4 2.5...4 22...35 2.5...35 2.5...25 2.5...50 2.5...35 14...1 14...1 3.5...6 31...53 Coils 1 or 2 [mm2] Wires [AWG] Control Modules 1or 2 [mm2] Wires [AWG] Torque Requirement [Nm] [Lb-in] Degree of Protection - contactor Protection Against Accidental Contact Combination Screw Head: Cross, Slotted, Pozidrive 1.5...6 16...12 1.5...6 16...12 1...2.5 9...13 IP 2LX per IEC 529 and DIN 40 050 (with wires installed) Safe from touch by fingers and back-of-hand per VDE 0106; Part 100 Environmental and General Specifications Ambient Temperature Storage Operation Conditioned 15% current reduction after AC-1 at >60° C Altitude at installed site Resistance to Corrosion/Humidity Shock Resistance Vibration Resistance Pollution Degree Operating Position Standards Approvals -55...+80° C (-67...176° F) - [CRI7E Electronic Interface -50...+80° C (-58...176° F)] -25...+60° C (-13...140° F) -25...+70° C (-13...158° F) 2000 meters above sea level per IEC 947-4 Damp-alternating climate: cyclic to IEC 68-2, 56 cycles Dry heat: IEC 68-2, +100°C (212° F), relative humidity <50%, 7 days. Damp tropical: IEC 68-2, +40°C (104°F), relative humidity <92%, 56 days. IEC 68-2: Half sinusoidal shock 11ms, 30g (in all three directions) IEC 68-2: Static > 2g, in normal position no malfunction <5g 3 Refer to Dimension Pages IEC947-1/4, EN 60947; UL 508; CSA 22.2, No. 14 CE, UL, CSA A52 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 79 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Coil Data (CA7 4-Pole) CA7-9- CA7-12- CA7-16- CA7-23- CA7-40- CA7-40- CA7-90- CA7-90- M40(31; 22) M40(31; 22) M40(31; 22) M40(31; 22) M22 M40 M22 M40 Voltage Range AC: 50Hz, 60Hz, 50/60 Hz DC Coil Consumption Pickup [xUs] Dropout [xUs] Pickup [xUs] Dropout [xUs] 0.85...1.1 0.3...0.6 0.8...1.1 (9V coils = 0.65...1.3; 24V coils = 0.7...1.25) 0.1...0.6 AC: 50Hz, 60Hz, 50/60 Hz Pickup [VA/W] 70/50 70/50 70/50 70/50 130/90 130/90 400/240 400/240 Hold-in [VA/W] 8/2.6 8/2.6 8/2.6 9/3 12/3.6 12/3.6 24/9 24/9 True DC Coils (CA7C) Pickup [W] 6.5 6.5 6.5 9.2 10.1 10.1 ~ ~ Hold-in [W] 6.5 6.5 6.5 9.2 10.1 10.1 ~ ~ Two Winding DC Coils Pickup [W] ~ ~ ~ ~ ~ ~ 325 325 CA7Y & CA7D Hold-in [W] ~ ~ ~ ~ ~ ~ 5.5 5.5 Operating Times AC: 50Hz, 60Hz, 50/60 Hz Pickup [ms] 15...30 15...30 15...30 15...30 15...30 15...30 20...30 20...30 Dropout [ms] 10...60 10...60 10...60 10...60 10...60 10...60 20...40 20...40 with RC Suppressor Dropout [ms] 10...60 10...60 10...60 10...60 10...60 10...60 20...40 20...40 True DC Coils (CA7C) Pickup [ms] 40...70 40...70 40...70 40...70 50...80 50...80 ~ ~ without Suppression Dropout [ms] 7...15 7...15 7...15 7...15 7...15 7...15 ~ ~ with Integrated Suppression Dropout [ms] 14...20 14...20 14...20 17...23 ~ ~ ~ ~ with External Suppression Dropout [ms] 70...95 70...95 70...95 80...125 ~ ~ ~ ~ Two Winding DC Coils Pickup [ms] ~ ~ ~ ~ ~ ~ 15...20 20...25 with Internal Suppression Dropout [ms] ~ ~ ~ ~ ~ ~ 20...25 20...25 Contactors A CA7 Technical Information Auxiliary Contact Data Electrical Contact Ratings - NEMA Min. Contact Rating Contact Ratings - IEC AC-15 (solenoids, contactors) rated voltage IEC 60947-5-1 40 ºC AC-12 (Control of resistive loads) IEC 60947-5-1 60 ºC DC-12 Switching DC Loads L/R < 1 ms, Resistive Loads IEC 60947-5-1 DC-13 IEC 60947-5-1, Solenoids and contactors Mounted Standard Auxiliary 24V 48V 120V 240V 400V 480V/500V 600V 690V Ith 230V 400V 690V Ith 230V 400V 690V 24V 48V 110V 220V 440V 24V 48V 110V 220V 440V Built-in Auxiliary Contacts in Contactor CA7-9...CA7-23 A600, P600 17V, 10 mA 10 A 10 A 10 A 10 A 6 A 2.5 A 1 A 1 A 20 A 8 kW 14 kW 24 kW 20 A 8 kW 14 kW 24 kW 12 A 9 A 3.5 A 0.55 A 0.2 A 5 A 3 A 1.2 A 0.6 A 0.3 A Front Mounted Auxiliary Contacts CA7-PV, CS7-PV, CZE/A7, CV7 Front Mounted Bifurcated Auxiliary Contacts 17V, 5 mA 6 A 6 A 6 A 5 A 3 A 1.6 A 1 A 1 A 10 A A600, Q600 5V, 3 mA 3 A 3 A 3 A 3 A 2 A 1.2 A 0.7 A 0.7 A 10 A 6 A 6 A 12 A 9 A 3.5 A 0.55 A 0.2 A 5 A 3 A 1.2 A 0.6 A 0.15 A 6 A 3.2 A 0.45 A 0.18 A 0.1 A 2.5 A 1.5 A 0.6 A 0.3 A 0.15 A Side Mounted Auxiliary Contacts CA-PA, CM7 A600, Q600 17V, 10 mA 6 A 6 A 6 A 5 A 3 A 1.6 A 1 A 1 A 10 A 6 A 6 A 3.2 A 0.45 A 0.18 A 0.1 A 5 A 3 A 1.2 A 0.6 A 0.15 A Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A53 Page 80 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors A Auxiliary Contacts Contactors CA7 Continuous Current Rating per UL/CSA Rated Voltage AC [V] Continuous Rating 40°C [A] Continuous Rating DC [A] Short-Circuit Protection -gGFuse Type 2 Coordination [A] Rated Impulse Voltage Uimp [kV] Insulation Voltage (between control and load circuit) per DIN< VDE 0103, Part 101 [V] (NAMUR recommendation) Mechanically Linked Contacts (per IEC60947-5-1 Annex L (SUVA Third-party certified) Built-in Auxiliary Contacts in Contactor CA7-9...CA7-23 600 max. 10 A general purpose Heavy pilot duty (A600) 5A, 600 max. Standard pilot duty (P600) 20 8 380 Mutually unrestricted between all NO and NC contacts Terminals Terminal Type Maximum Wire Size per IEC 947-1 Flexible with Wire-End Fernule 1 conductor 2 conductor Solid/Stranded- 1 conductor Conductor 2 conductor Recommended Tightening Torque Max. Wire Size per UL/CSA Recommended Tightening Torque [mm2] [mm2] [mm2] [mm2] [Nm] [AWG] [lb-in] 2xA4 1...4 1...4 1.5...6 1.5...6 1...2.5 16...10 9...22 Front Mounted Auxiliary Contacts CA7-PV, CS7-PV, CZE/A7, CV7 Side Mounted Auxiliary Contacts CA-PA, CM7 600 max. 10 A general purpose Heavy pilot duty (A600) 2.5A, 600 max. Standard pilot duty (Q600) 10 8 600 max. 10 A general purpose Heavy pilot duty (A600) 2.5A, 600 max. Standard pilot duty (Q600) 10 6 440 440 Mutually unrestricted between all NO & Mutually unrestricted between all NC contacts. CZE & CV7 not mechanically NO and NC contacts linked with contactor main contacts 2xA4 0.5...2.5 0.75...2.6 0.5...2.5 0.75...2.6 1...15 18...14 9...13 2xA4 0.5...2.5 0.75...2.6 0.5...2.5 0.75...2.6 1...15 18...14 9...13 Accessories Latch Attachment Release, CV7-11 Coil Consumption Contact Signal Duration Time Attachment Reset Time at min. time setting at max. time setting Repeat Accuracy [VA/W] [W] [min/max] [ms] [ms] AC 45/40 DC 25W 0.03...15s 10 70 ±10% Positively-Guided Contacts ( Mechanically-linked) SUVA Certified · Restricted guidance guarantees without restrictions from contactor to auxiliary contact and auxiliary contact to contactor. Contact Ratings (Per NEMA/UL A600 & Q600) Standard A600 Q600 Circuit Voltage 120AC 240AC 480AC 600AC 125DC 250DC 301-600DC Make (Amps/VA) 60A/7200VA 30A/7200VA 15A/7200VA 12A/7200VA 0.55A/69VA 0.27A/69VA 0.1A/69VA Break (Amps/VA 6A/720VA 3A/720VA 1.5A/720VA 1.2A/720VA 0.55A/69VA 0.27A/69VA 0.1A/69VA Continuous Amps 10 25 See Section G for additional details. A54 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 81 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors - Contact Life Contactors Determining Contact Life To determine the contactor's estimated electrical life, follow these guidelines: 1. Identify the appropriate Utilization Category from Table A. 2. On the following pages, choose the graph for the Utilization Category selected. 3. Locate the Rated Operational Current (le) along the bottom of A the chart and follow the graph lines up to the intersection of the appropriate contactor's life-load curve. 4. Read the estimated contact life along the vertical axis. Table A IEC Special Utilization Categories, AC Ratings Category Typical Applications Rated Current Conditions for testing electrical life Make Break Conditions for testing making and breaking capacity Ops. Make Break Ops. I/Ie U/ue cos Ic/Ie Ur/Ue cos I/Ie U/ue cos I/Ie U/ue cos Non-inductive or slightly AC-1 inductive loads; resistance furnaces All values 1 1 0.95 1 1 0.95 6000 1.5 1.05 0.8 1.5 1.05 0.8 50 AC-2 Slip-ring motors: Starting, plugging All values 2 1.05 0.65 2 1.05 0.65 6000 4 1.05 0.65 4 1.05 0.65 50 Slip-ring motors: AC-3 Starting, switching off motors during running Ie 17Amp 6 17Amp <Ie 100Amp 6 Ie> 100Amp 6 1 0.65 1 0.17 0.65 10 1.1 0.65 8 1.1 0.65 1 0.35 1 0.17 0.35 6000 10 1.1 0.35 8 1.1 0.35 50 1 0.35 1 0.17 0.35 8 1.1 0.35 6 1.1 0.35 AC-4 Squirrel-cage motors: Starting, plugging, inching Ie 17Amp 6 17Amp <Ie 100Amp 6 Ie> 100Amp 6 1 0.65 6 1 0.35 6 1 0.35 6 1 0.65 12 1.1 0.65 10 1.1 0.65 1 0.35 6000 12 1.1 0.35 10 1.1 0.35 50 1 0.35 10 1.1 0.35 8 1.1 0.35 AC-5a Switching of electric discharge lamp control 2 1.05 0.45 2 1.05 0.45 6000 3 1.05 0.45 3 1.05 0.45 50 CONTACTORS AC-5b Switching of incandescent lamps 1 1.05 1 1.05 6000 1.5 1.05 1.5 1.05 50 AC-6a Switching of transformers Rating derived from AC-3 rating (x 0.45) CONTROL DEVICES AC-6b Switching of capacity banks AC-12 AC-13 AC-14 AC-15 AC-20 AC-21 AC-22 AC-23 Control of resistive loads and solid state loads with isolation by All values opto couplers Control of solid state loads with transformer isolation Control of small electromagnetic loads 72 VA Control of electromagnetic loads 72 VA Connecting and disconnecting under no load conditions Switching or resistive loads, including moderate overloads All values Switching of mixed resistive & inductive loads, including moder- All values ate overloads Switching of motor loads or other highly inductive loads All values Depends on circuit conditions of application 1 1 0.9 1 1 0.9 6050 2 1 0.65 1 1 0.65 6050 10 1.1 0.65 1.1 1.1 0.65 10 6 1 0.3 1 1 0.3 6050 6 1.1 0.7 6 1.1 0.7 10 10 1 0.3 1 1 0.3 6050 10 1.1 0.3 10 1.1 0.3 10 No testing required 1 1 0.95 1 1 0.95 10000 1.5 1.05 0.95 1.5 1.05 0.95 5 1 1 0.8 1 1 0.8 10000 3 1.05 0.65 3 1.05 0.65 5 1 1 0.65 1 1 0.65 10000 10 1.05 0.45 8 1.05 0.45 5 SWITCHES CA7 Legend Ue Rated operational voltage U Voltage before make Ur Recovery voltage Ie Rated operational current I Making current Ic Breaking current L Inductance of test circuit R Resistance of test circuit Q-Pulse Id: TMS1594 Utilization categories and test conditions for AC & DC. For contactors according to IEC 158-1, starters according to IEC 292-1 ... 4 and control switches according to IEC 337-1 and IEC 337-1A. With a minimum value of 1000A for I or Ic. With a minimum value of 800A for Ic. With a minimum value of 1200A for I. Plugging is understood as stopping or reversing the motor rapidly by reversing the motor primary connections while the motor is running. Inching [or jogging] is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism. Discount Schedule A-1 Active: 18/04/2016 A55 Page 82 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors - Contact Life Contactors A Determining Contact Life To determine the contactor's estimated electrical life, follow these guidelines: 1. Identify the appropriate Utilization Category from Table A. 2. On the following pages, choose the graph for the Utilization Category selected. 3. Locate the Rated Operational Current (le) along the bottom of the chart and follow the graph lines up to the intersection of the ap- propriate contactor's life-load curve. 4. Read the estimated contact life along the vertical axis. CA7 Table A IEC Special Utilization Categories, DC Ratings Category Typical Applications Rated Current Conditions for testing electrical life Make Break Conditions for testing making and breaking capacity Ops. Make Break Ops. DC-1 DC-2 DC-3 DC-4 DC-5 DC-15 Non-inductive or slightly inductive loads, resistance furnaces Shunt-motors: Starting, switching off motors during running Shunt motors: Starting, plugging, inching Series-motors: Starting , switching off motors during running Series-motors: Starting, plugging, inching Electromagnets for contactors, valves, solenoid actuators All Values All Values All Values All Values All Values All Values I/Ie U/ue cos Ic/Ie Ur/Ue cos 11 1 11 1 2.5 1 2 1 0.1 7.5 2.5 1 2 2.5 1 2 2.5 1 7.5 1 0.3 10 2.5 1 7.5 2.5 1 7.5 1 1 6xP 1 1 6xP I/Ie U/ue cos I/Ie U/ue cos 1.5 1.1 1 1.5 1.1 1 4 1.1 2.5 4 1.1 2.5 4 1.1 2.5 4 1.1 2.5 4 1.1 15 4 1.1 15 4 1.1 15 4 1.1 15 1.1 1.1 6 x P 1.1 1.1 6 x P Legend Ue Rated operational voltage U Voltage before make Ur Recovery voltage Ie Rated operational current I Making current Ic Breaking current L Inductance of test circuit R Resistance of test circuit Utilization categories and test conditions for AC & DC. For contactors according to IEC 158-1, starters according to IEC 292-1 ... 4 and control switches according to IEC 337-1 and IEC 337-1A. Only according to VDE. P = Ue x Ie rated power [W]. The value "6 x P" has been derived from an empiric relationship which covers most magnetic loads for DC up to an upper limit of P = 50W. A56 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 83 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors - Contact Life Predicting Electrical Life Sprecher + Schuh contactors are designed for superior and size of contactor required. This assures reliable opera- A performance in a wide variety of applications, by giving tion and high value the ability to very closely match the consideration to the specific load, utilization category and contactor to the application. required electrical life, you can purchase exactly the type Contactors Identify they appropriate utilization category. For this example, we will determine CA7 contact life for inching and plugging squirrel-cage motors. Utilization Category AC-1 AC-2 AC-3 AC-4 Resistance Furnaces Slip-ring motors Squirrel-cage motors Squirrel-cage motors AC-15 Electromagnets CA7 Definition Non inductive or slightly inductive loads, Resistive Furnaces Starting and stopping of running motors Starting and stopping of running motors Starting, plugging, and inching (Plugging is understood as stopping or reversing the motor rapidly by reversing the motor primary connections while the motor is running. Inching [or jogging] is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.) Electromagnets for contactors, valves, solenoid actuators Choose the graph for the utilization category selected. (a graph pertaining to most Utilization Categories can be found in each contactor section.) Locate the Rated Operational Current (Ie) along the bottom of the chart and follow the graph lines up to the intersection of the appropriate contactor's life-load curve. Contact Life (Millions of Operations) CA7-30 CA7-37 CA7-43 10 CA7-23 CA7-16 CA7-12 1 CA7-9 Starting with inching and plugging; Ue = 230...460 VAC CA7-60 CA7-72 CA7-85 0.1 Read the estimated contact life along 0.01 1 the vertical axis. 10 Rated operational current Ie AC-4 [A] AC-4 100 A comprehensive list of Utilization Categories can be found in each contactor section, however, these are the primary categories used in most industrial motor applications. The life-load curves shown here are based on Sprecher+Schuh tests according to the requirements defined in IEC 60947-4-1. Since contact life in a given application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A57 Page 84 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Life Load Curves Contactors A Life-Load Curves · Locate the Rated Operational Current (le) along the bottom of the chart and follow the graph lines up to the intersection of the appropriate contactor's life-load curve. · Read the estimated contact life CA7 along the vertical axis. AC-1 (to 690V) AC-2 (to 460V) AC-3 (to 460V) NOTE: The life-load curves shown here are based on Sprecher+Schuh tests according to the requirements defined in IEC 60947-4-1. Since contact life in any given application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. 575V applications use 90% of curve value. A58 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 85 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Life Load Curves Life-Load Curves · Locate the Rated Operational Current (le) along the bottom of the chart and follow the graph lines up to the intersection of the appropriate contactor's life-load curve. · Read the estimated contact life along the vertical axis. AC-3 (to 575) CA7-9 10 Starting and stopping of running squirrel-cage induction motors; Ue = 500...575V AC CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 AC-3 Contactors A CA7 1 Contact Life (Millions of Operations) 0.1 1 10 100 Rated operational current Ie AC-3 [A] AC-4 (to 690V) CA7-30 CA7-37 CA7-43 10 CA7-23 CA7-16 CA7-12 Starting with inching and plugging; Ue = 230...690 VAC CA7-60 CA7-72 CA7-85 CA7-9 1 AC-4 Contact Life (Millions of Operations) NOTE: The life-load curves shown here are based on Sprecher+Schuh tests according to the requirements defined in IEC 60947-4-1. Since contact life in any given application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. Q-Pulse Id: TMS1594 0.1 1 10 100 Rated operational current Ie AC-4 [A] Discount Schedule A-1 Active: 18/04/2016 A59 Page 86 of 1068 Contactors Contact Life (Millions of Operations) Max. Starting / Loading time [s] A Life-Load Curves AC-3 (90%), AC-4 (10%) CA7 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Life Load Curves CA7-12 CA7-16 10 Mixed operation of squirrel-cage motors; Ue = 230...460 VAC AC-3 90% Starting and stopping of running motors AC-4 10% Starting with inching or plugging CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 AC-3 (90%), AC-4 (10%) CA7-9 1 0.1 1 10 100 Rated operational current Ie AC-3 / AC-4 [A] Contact Life for Mixed Utilization Categories Heavy Duty Starting and Regular Short-time Operation AC-3 and AC-4 CA7-9/12/16 CA7-23 CA7-30/37 CA7-43 CA7-60/72/85 In many applications, the utilization category cannot be defined as 100 either purely AC-3 or AC-4. In those applications, the electrical life of the contactor can be estimated with the following equation: Lmixed = Lac3/ [1+Pac4 x (Lac3/Lac4-1)], where: Lmixed Approximate contact life in operations for a mixed 10 AC-3/AC-4 utilization category application. Lac3 Approximate contact life in operations for a pure AC-3 utilization category (from the AC-3 life-load curve). Lac4 Approximate contact life in operations for a pure AC-4 utilization category (from the AC-4 life-load curve). 1 10 Pac4 Percentage of AC-4 operations 100 1000 Starting Current / Short-time current [A] 10000 575V applications use 85% of curve value. A60 Q-Pulse Id: TMS1594 NOTE: The life-load curves shown here are based on Sprecher+Schuh tests according to the requirements defined in IEC 60947-4-1. Since contact life in any given application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. Discount Schedule A-1 Active: 18/04/2016 Page 87 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Operating Rates Operating Rates The estimated contact life shown in the life-load curves is based on the standard operating rates shown in Table B below. For applications requiring a higher operating frequency, the maximum operating power (Pn in kW or HP) for a given contactor must be reduced to maintain the same contact life. To find a contactor's maximum operating power, for an operating rate greater than shown in Table B, follow these guidelines: 1. Identify the appropriate curve for the contactor and utilization category from Table B. 2. Locate the appropriate Maximum Operating Rate curve on the following pages. 3. Locate the intersection of the curve with the application's operating rate (ops/hr.) found on the vertical axis. 4. Read the percent of maximum operating power (Pn) of the con- A tactor from the horizontal axis. Contactors 5. Multiply the % maximum power by the standard power rating. Example: The contactor selected for an AC-4 utilization category application is a CA7-16 (10HP at 460V), however, the application requires an operating rate of 200 ops/hr., compared to the standard operating rate of 120 ops/hr. as shown in Table B. CA7 1. Locate the AC-4 Maximum Operating Rate curve on the following pages. 2. Locate the intersection of 200 ops/hr on the CA7-16 curve. The data shows that the maximum operating power of the CA7-16 contactor in this application is 60%. 3. Therefore, the maximum horsepower that can be switched by the CA7-16 contactor in this application is 6 HP (0.60 x 10HP). Table B Standard Operating Rates by Contactor and Utilization Category Contactor CA-9 CA-12 CA-16 CA-23 CA-30 CA-37 CA-43 CA-60 CA-72 CA-85 AC-1 Max. ops/hr. 1000 1000 1000 1000 1000 1000 1000 800 800 600 AC-2 Max. ops/hr. AC-3 Max. ops/hr. AC-4 Max. ops/hr. Operating Parameters and Start Time 40% Duty Cycle 250ms 250ms 500 700 200 500 700 150 500 700 120 400 600 80 400 600 80 400 600 70 400 600 70 300 500 70 250 500 60 200 500 50 AC-4 @ Ie for 200K ops. Max. ops/hr. 250ms 400 300 240 160 160 140 140 140 120 140 Duty Cycle or Load Factor Defined as the "on" time for a given operating cycle per hour including the "start time." A 40% Duty Cycle is calculated in the following manner: Contactor switches six (6) times per minute (tpm), 250ms start time; 40% duty cycle. To determine the "on" time and "off" time: · Operations per hour = 360; [60 min x 6 tpm = 360] · One operating cycle = 10 sec; [60 min ÷ 6 tpm = 10 sec] · "On" time at 40% duty cycle = 4 sec; [10 sec x 0.4 (40%) = 4 sec] · 4 sec "on" time includes the start time of 250ms · "Off" time at 40% duty cycle = 6 sec; [10 sec 4 sec = 6 sec] Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A61 Page 88 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Operating Rates A Operating Rate Curves Contactors Max. Operating Rate [Ops/hr] AC-1 CA7 3000 CA7-9/12/16/23 2500 CA7-30/37 2000 CA7-43 1500 CA7-60/72/85 1000 Non or slightly inductive loads, resistance furnaces; Ue = 230...690 VAC AC-1 500 0 0 10 20 30 40 50 60 70 80 90 100 P/Pn [%] AC-2 10000 Slip-ring motors: starting, switching off; Ue = 230...460 VAC AC-2 Max. Operating Rate [Ops/hr] 1000 CA7-9/CA7-12/CA7-16 CA7-23/CA7-30/CA7-37/CA7-43 CA7-60 CA7-72 CA7-85 100 0 10 20 30 40 50 60 70 80 90 100 P/Pn [%] A62 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 89 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Technical Information CA7 Contactors Operating Rates Operating Rate Curves A Contactors AC-3 10000 Squirrel-cage motors: starting, switching off motors during running; Ue = 230...460 VAC Relative operating time 40%, Starting time tA= 0.25s AC-3 CA7 Max. Operating Rate [Ops/hr] 1000 CA7-9/CA7-12/CA7-16 CA7-23/CA7-30/CA7-37/CA7-43 CA7-60/CA7-72/CA7-85 100 0 10 20 30 40 50 60 70 80 90 100 P/Pn [%] AC-4 1000 100 Squirrel-cage motors: starting, plugging, inching; Ue = 230 ...460 VAC Starting Time tA = 0.25s AC-4 CA7-9 CA7-12 CA7-16 CA7-23/30 CA7-37/43/60 CA7-72 CA7-85 Max. Operating Rate [Ops/hr] 10 0 10 20 30 40 50 60 70 P/Pn [%] 80 90 100 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A63 Page 90 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Dimensions CA7 Contactors Contactors A Series CA7, CAU7, CAQ7, CNX, CAN7 and CAL7 (Contactors, Reversing Contactors & Special Use Contactors) · Dimensions are in millimeters (inches) · Dimensions not intended for manufacturing purposes CA7 AC Contactors Catalog Number CA7-9...CA7-23; CAQ7-16; CAN7-12, CNX-205...208; CAN7-12, CA(V)L7-20 CA7-30...CA7-37; CNX-209; CAN7-30... CAN7-37 CA7-40 CA7-43, CNX-212 CA7-60...CA7-85 CNX-218 CA7-90 CA7-9C...CA7-16C, CAQ7-16C CNX-205C...206C; CAN7-12C True DC Contactors CA7-23C CNX-207C...208C CA7-30C...CA7-37C; CAQ7-37C; CNX-209C; CAN7-30C...CAN7-37C CA7-40C CA7-43C, CNX-212C a 45 (1-25/32) 45 (1-25/32) 59 (2-21/64) 54 (2-1/8) 72 (2-53/64) 95 (3-3/4) 45 (1-25/32) 45 (1-25/32) 45 (1-25/32) 59 (2-21/64) 54 (2-1/8) b 80 (3-3/16) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 122 (4-51/64) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) c 80.5 (3-11/64) 97.5 (4) 100.5 (4-7/64) 100.5 (4-7/64) 117 (4-49/64) 117 (4-49/64) 106.5 (4-3/16) 123.5 (4-55/64) 141.5 (5-37/64) 144.5 (5-11/16) 144.5 (5-11/16) c1 75.5 (3-3/32) 92.6 (3-49/64) 95.5 (3-49/64) 95.5 (3-49/64) 111.5 (4-35/64) 111.5 (4-35/64) 101.5 (4) 119 (4-43/64) 136.5 (5-3/8) 139.5 (5-1/2) 140 (5-33/64) Reversing Contactors, Capacitor Contactors & Accessories (+...) Contactors with... auxiliary contact block-front mounting 2-, or 4-pole (CAQ7) capacitor switching deck -front mounting auxiliary contact block-side mounting 1-, or 2 pole pneumatic timing module electronic timing module on coil terminal side reversing contactor w-mech.interlock on side of contactor mechanical latch interface module on coil terminal side surge suppressor on coil terminal side Dim. [mm] c/c1 + 39 c/c1 + 39 a + 9 c/c1 + 58 b + 24 a+9+a c/c1 + 61 b + 9 b + 3 Labeling with... label sheet +0 marking tag sheet with clear cover +0 marking tag adapter for V7 Terminals +5.5 Dim. [inches] c/c1 +1-37/64 c/c1 +1-37/64 a + 23/64 c/c1 + 2-23/64 b + 15/16 a+ 23/64+a c/c1 +2-31/64 b + 23/64 b + 1/8 +0 +0 +7/32 c2 6 (1/4) 6.5 (17/64) 6.5 (17/64) 6.5 (17/64) 8.5 (21/64) 8.5 (21/64) 6 (1/4) 6 (1/4) 6.5 (17/64) 6.5 (17/64) 6.5 (17/64) ød 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 4-5.4 (4-7/32) 4-5.4 (4-7/32) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) d1 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 100 (3-15/16) 100 (3-15/16) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) d2 35 (1-25/64) 35 (1-25/64) 45 (1-25/32) 45 (1-25/32) 55 (2-11/64) 55 (2-11/64) 35 (1-25/64) 35 (1-25/64) 35 (1-25/64) 45 (1-25/32) 45 (1-25/32) Mounting Position AC contactors True DC contactors A64 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 91 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Dimensions CA7 Contactors Contactors Series CA7 with Two Winding DC Coil A · Dimensions are in millimeters (inches) · Dimensions not intended for manufacturing purposes CA7 Catalog Number CA7-9Y...CA7-23Y CA7-30Y, CA7-37Y AC Contactors CA7-43Y CA7-60D...CA7-85D CAN7-72D, CNX-218D CA7-90D a 54 (2-9/64) 54 (2-9/64) 63 (2-31/64) 81 (3-3/16) 95 (3-3/4) b 90 (3-35/64) 90 (3-35/64) 90 (3-35/64) 131 (5-5/32) 122 (4-51/64) c 80.5 (3-11/64) 97.5 (4) 100.5 (4-7/64) 117 (4-49/64) 117 (4-49/64) c1 75.5 (3-3/32) 92.6 (3-49/64) 95.6 (3-7/8) 111.5 (4-35/64) 111.5 (4-35/64) c2 6 (1/4) 6.5 (17/64) 6.5 (17/64) 8.5 (21/64) 8.5 (21/64) ød 2-4.5 (2-3/16) 2-4.5 (2-3/16) 2-4.5 (2-3/16) 4-5.4 (4-7/32) 4-5.4 (4-7/32) d1 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 100 (3-15/16) 100 (3-15/16) d2 35 (1-25/64) 35 (1-25/64) 45 (1-25/32) 55 (2-11/64) 55 (2-11/64) Reversing Contactors, Capacitor Contactors & Accessories (+...) auxiliary contact block-front mounting auxiliary contact block- left side mounting pneumatic timing module electronic timing module mechanical latch interface module Labeling with... Contactors with... 2-, or 4-pole 1-, or 2 pole on coil terminal side on coil terminal side label sheet marking tag sheet with clear cover marking tag adapter for V7 Terminals Dim. [mm] c/c1 + 39 a + 9 c/c1 + 58 b + 24 c/c1 + 61 b + 9 +0 +0 +5.5 Dim. [inches] c/c1 +1-37/64 a + 23/64 c/c1 + 2-23/64 b + 15/16 c/c1 +61 c/c1 + 2-31/64 +0 +0 +7/32 Mounting Position Two Winding DC contactors Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A65 Page 92 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual A CA7 Contactors with Terminal Lugs · Dimensions are in millimeters (inches) · Dimensions not intended for manufacturing purposes Dimensions CA7 Contactors Contactors CA7 CA7-P-KN23 / KL23 CA7-P-K37 Catalog Number CA7-P-KN23 / KL23 CA7-P-K37 CA7-P-K43 CA7-P-K85 CA7-P-K43 With Contactor CA7-9...16 CA7-23 CA7-30 & 37 CA7-43 CA7-60...85 h1 61.6 (2-27/64) 61.6 (2-27/64) 67.6 (2-21/32) 69.0 (2-23/32) 79.7 (3-1/8) AC Operated Contactor h2 h3 78.6 (3-3/32) ~ 78.6 (3-3/32) ~ 84.6 (3-21/64) 71.5 (2-13/16) 85.0 (3-11/32) 74.5 (2-15/16) 104.7 (4-1/8) 86.7 (3-13/64) h4 ~ ~ 88.5 (3-31/64) 90.5 (3-9/16) 111.7 (4-3/8) CA7-P-K85 h1 87.2 (3-7/16) 105.2 (4-9/64) 111.2 (4-3/8) 112.6 (4-7/16) 79.7 (3-1/8) DC Operated Contactor h2 h3 104.2 (4-3/32) ~ 122.2 (4-13/16) ~ 128.2 (5-3/64) 115.1 (4-17/32) 128.6 (5-1/16) 118.1 (4-21/32) 104.7 (4-1/8) 86.7 (3-13/64) h4 ~ ~ 132.1 (5-13/64) 134.1 (5-9/32) 111.7 (4-3/8) A66 Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 Page 93 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CA7 Contactors with Paralleling Links · Dimensions are in millimeters (inches) · Dimensions not intended for manufacturing purposes Dimensions CA7 Contactors A CA7 Contactors Catalog Number CA7-P-B23 CA7-P-K37 CA7-P-B23 With Contactor CA7-9...16 CA7-23 CA7-30 & 37 h1 65.1 (2-9/16) 65.1 (2-9/16) 69.0 (2-23/32) AC Operated Contactor h2 h3 90.1 (3-9/16) ~ 90.1 (3-9/16) ~ 94.0 (3-45/64) 74.5 (2-15/16) h4 ~ ~ 99.5 (3-29/32) CA7-P-B37 h1 90.7 (1/4) 108.7 (4-9/32) 112.6 (4-7/16) DC Operated Contactor h2 h3 104.2 (2-3/16) ~ 133.7 (5-17/64) 137.6 (5-13/32) ~ 118.1 (4-21/32) h4 ~ ~ 143.1 (5-5/8) Q-Pulse Id: TMS1594 Discount Schedule A-1 Active: 18/04/2016 A67 Page 94 of 1068 Switches & Pilot Lights WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Relays & Sockets RH Series Compact Power Relays SPDT through 4PDT, 10A contacts Compact power type relays The RH series are miniature power relays with a large capacity. The RH relays feature 10A contact capacity as large as the RR series but in a miniature package. The compact size saves space. Display Lights Relays & Sockets Timers Contact SPDT DPDT 3PDT 4PDT Part Number Selection Part Number Model Blade Terminal PCB Terminal Basic RH1B-U RH1V2-U With Indicator RH1B-UL -- With Check Button RH1B-UC -- With Indicator and Check Button RH1B-ULC -- Top Bracket Mounting RH1B-UT -- With Diode (DC coil only) RH1B-UD RH1V2-UD With Indicator and Diode (DC coil only) RH1B-ULD -- Basic RH2B-U RH2V2-U With Indicator RH2B-UL RH2V2-UL With Check Button RH2B-UC -- With Indicator and Check Button RH2B-ULC -- Top Bracket Mounting RH2B-UT -- With Diode (DC coil only) RH2B-UD RH2V2-UD With Indicator and Diode (DC coil only) RH2B-ULD -- Basic RH3B-U RH3V2-U With Indicator RH3B-UL RH3V2-UL With Check Button RH3B-UC -- With Indicator and Check Button RH3B-ULC -- Top Bracket Mounting RH3B-UT -- With Diode (DC coil only) RH3B-D* RH3V2-D* With Indicator and Diode (DC coil only) RH3B-LD* -- Basic RH4B-U RH4V2-U With Indicator RH4B-UL RH4V2-UL With Check Button RH4B-UC -- With Indicator and Check Button RH4B-ULC -- Top Bracket Mounting RH4B-UT -- With Diode (DC coil only) RH4B-UD RH4V2-UD With Indicator and Diode (DC coil only) RH4B-LD* -- Coil Voltage Code (Standard Stock in bold) AC6V, AC12V, AC24V, AC110V, AC120V, AC220V, AC240V DC6V, DC12V, DC24V, DC48V, DC110V DC6V, DC12V, DC24V, DC48V, DC110V DC12V, DC24V, DC48V, DC110V AC6V, AC12V, AC24V, AC110-120V, AC220-240V DC6V, DC12V, DC24V, DC48V, DC100-110V DC6V, DC12V, DC24V, DC48V, DC100-110V AC6V, AC12V, AC24V, AC110V, AC120V, AC220V, AC240V DC6V, DC12V, DC24V, DC48V, DC110V DC6V, DC12V, DC24V, DC48V, DC110V AC6V, AC12V, AC24V, AC110V, AC120V, AC220V, AC240V DC6V, DC12V, DC24V, DC48V, DC110V DC6V, DC12V, DC24V, DC48V, DC110V 1. *Carries no UL recognition mark. 2. PCB terminal relays are designed to mount directly to a circuit board without any socket. Ordering Information When ordering, specify the Part No. and coil voltage code: (example) RH3B-U AC120V Part No. Coil Voltage Code Terminal Blocks Circuit Breakers 726 Q-Pulse Id: TMS1594 www.idec.com Active: 18/04/2016 Page 95 of 1068 Switches & Pilot Lights Display Lights Relays & Sockets Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Sockets (for Blade Terminal Models) Relays Standard DIN Rail Mount 1 Finger-safe DIN Rail Mount 1 RH1B SH1B-05 SH1B-O5C RH2B SH2B-05 SH2B-05C RH3B SH3B-05 SH3B-05C RH4B SH4B-05 SH4B-05C Through Panel Mount SH1B-51 SH2B-51 SH3B-51 SH4B-51 PCB Mount SH1B-62 SH2B-62 SH3B-62 SH4B-62 Hold Down Springs & Clips Appearance Description Relay Pullover Wire Spring RH1B RH2B RH3B RH4B For DIN Mount Socket SY2S-02F1 2 SY4S-02F1 2 SH3B-05F1 2 SH4B-02F1 2 For Through Panel & PCB Mount Socket Min Order Qty SY4S-51F1 10 Leaf Spring (side latch) RH1B, RH2B, RH3B, RH4B SFA-202 3 SFA-302 3 20 Leaf Spring (top latch) RH1B, RH2B, RH3B, RH4B SFA-101 3 SFA-301 3 1. DIN Rail mount socket comes with two horseshoe clips. Do not use unless you plan to insert pullover wire spring. Replacement horseshoe clip part number is Y778-011. 2. Must use horseshoe clip when mounting in DIN mount socket. Replacement horseshoe clip part number is Y778-011. 3. Two required per relay. AC Coil Ratings Rated Current (mA) ±15% at 20°C Voltage (V) SPDT AC 50Hz DPDT 3PDT 4PDT SPDT AC 60Hz DPDT 3PDT 6 170 240 330 387 150 200 280 12 86 121 165 196 75 100 140 24 42 60.5 81 98 37 50 70 110 9.6 -- 18.1 21.6 8.4 -- 15.5 110-120 -- 9.410.8 -- -- -- 8.0-9.2 -- 120 8.6 -- 16.4 19.5 7.5 -- 14.2 220 4.7 -- 8.8 10.7 4.1 -- 7.7 220-240 -- 4.7-5.4 -- -- -- 4.0-4.6 -- 240 4.9 -- 8.2 9.8 4.3 -- 7.1 4PDT 330 165 83 18.2 -- 16.5 9.1 8.3 Coil Resistance () ±10% at 20°C SPDT DPDT 3PDT 4PDT 330 9.4 6.4 5.4 165 39.3 25.3 21.2 83 153 103 84.5 18.2 -- 2,200 1,800 -- -- -- -- 16.5 -- 10,800 7,360 9.1 -- 10,800 7,360 -- 18,820 -- -- 8.3 -- 12,100 9,120 Operation Characteristics (against rated values at 20ºC) Max. Continuous Applied Voltage Pickup Voltage Dropout Voltage 110% 80% maximum 30% minimum DC Coil Ratings Voltage (V) Rated Current (mA) ±15% at 20°C SPDT DPDT 3PDT 4PDT Coil Resistance () ±10% at 20°C SPDT DPDT 3PDT 4PDT 6 128 150 240 12 64 75 120 24 32 36.9 60 48 18 18.5 30 100-110 -- 8.2-9.0 -- 110 8 -- 12.8 250 47 40 25 24 125 188 160 100 96 62 750 650 400 388 31 2,660 2,600 1,600 1,550 -- -- 12,250 -- -- 15 13,800 -- 8,600 7,340 Operation Characteristics (against rated values at 20ºC) Max. Continuous Applied Voltage Pickup Voltage Dropout Voltage 110% 80% maximum 10% minimum Standard coil voltages are in BOLD. Timers Terminal Blocks Circuit Breakers Q-Pulse Id: TMS1594 USA: 800-262-IDEC Canada: 888-317-IDEC Active: 18/04/2016 727 Page 96 of 1068 Switches & Pilot Lights Display Lights Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Relays & Sockets Contact Ratings Maximum Contact Capacity Model Continuous Current Allowable Contact Power Resistive Load Inductive Load Rated Load Voltage Res. Ind. (V) Load Load SPDT 10A 1540VA 300W 990VA 210W 110 AC 10A 7A 220 AC 7A 4.5A 30 DC 10A 7A DPDT 3PDT 10A 4PDT 1650VA 300W 1100VA 225W 110 AC 10A 7.5A 220 AC 7.5A 5A 30 DC 10A 7.5A Note: Inductive load for the rated load -- cos ø = 0.3, L/R = 7 ms TÜV Ratings Voltage RH1 RH2 RH3 RH4 240V AC 10A 10A 7.5A 7.5A 30V DC 10A 10A 10A 10A AC: cos ø = 1.0, DC: L/R = 0 ms UL Ratings Voltage Resistive RH1 RH2 RH3 RH4 240V AC 10A 7.5A 7.5A 120V AC -- 10A 10A 30V DC 10A 10A -- 28V DC -- -- 10A General Use RH1 RH2 RH3 RH4 7A 6.5A 5A -- 7.5A 7.5A 7A -- -- -- ---- Horse Power Rating RH1 RH2 RH3 RH4 1/3 HP 1/3 HP -- 1/6 HP 1/6 HP -- -- ---- -- ---- CSA Ratings Voltage Resistive General Use Horse Power Rating RH1 RH2 RH3 RH4 RH1 RH2 RH3 RH4 RH1, 2, 3 240V AC 10A 10A -- 7.5A 7A 7A 7A 5A 1/3 HP 120V AC 10A 10A 10A 10A 7.5A 7.5A -- 7.5A 1/6 HP 30V DC 10A 10A 10A 10A 7A 7.5A -- -- -- Socket Specifications Sockets DIN Rail Mount Sockets SH1B-05 SH2B-05 SH3B-05 SH4B-05 Finger-safe DIN Rail Mount Through Panel Mount Socket PCB Mount Socket SH1B-05C SH2B-05C SH3B-05C SH4B-05C SH1B-51 SH2B-51 SH3B-51 SH4B-51 SH1B-62 SH2B-62 SH3B-62 SH4B-62 Terminal (Coil) M3 screws (contact) M3.5 screws with captive wire clamp Electrical Rating 250V, 10A M3.5 screws with captive wire clamp 300V, 10A (coil) M3 screws (contact) M3.5 screws with captive wire clamp, fingersafe 250V, 10A M3.5 screws with captive wire clamp, fingersafe 300V, 10A Solder PCB mount PCB mount 300V, 10A 250V, 10A 300V, 10A Wire Size Maximum up to 2#12AWG Torque 5.5 - 9 in·lbs 9 - 11.5 in·lbs Maximum up to 2#12AWG 9 - 11.5 in·lbs Maximum up to 2#12AWG 5.5 - 9 in·lbs 9 - 11.5 in·lbs Maximum up to 2#12AWG 9 - 11.5 in·lbs -- -- -- -- -- -- Accessories Description Appearance Aluminum DIN Rail (1 meter length) DIN Rail End Stop Replacement Hold-Down Spring Anchor Use with All DIN rail sockets DIN rail Part No. BNDN1000 BNL5 Remarks IDEC offers a low-profile DIN rail (BNDN1000). The BNDN1000 is designed to accommodate DIN mount sockets. Made of durable extruded aluminum, the BNDN1000 measures 0.413 (10.5mm) in height and 1.37 (35mm) in width (DIN standard). Standard length is 39" (1,000mm). 9.1 mm wide. DIN mount sockets and hold down springs. Y778-011 For use on DIN rail mount socket when using pullover wire hold down spring. 2 pieces included with each socket. Timers Terminal Blocks Circuit Breakers 728 Q-Pulse Id: TMS1594 www.idec.com Active: 18/04/2016 Page 97 of 1068 Switches & Pilot Lights Display Lights Relays & Sockets Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Specifications Contact Material Contact Resistance 1 Minimum Applicable Load Operate Time 2 SPDT DPDT 3PDT 4PDT Release Time 2 SPDT DPDT 3PDT 4PDT SPDT Power Consumption (approx.) DPDT 3PDT 4PDT Insulation Resistance Dielectric Strength 3 Operating Frequency SPDT DPDT 3PDT 4PDT Vibration Resistance Shock Resistance Mechanical Life Electrical Life Operating Temperature 4 Operating Humidity Weight (approx.) DPDT SPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT Silver cadmium oxide 50m maximum 24V DC, 30 mA; 5V DC, 100 mA (reference value) 20ms maximum 25ms maximum 20ms maximum 25ms maximum AC: 1.1VA (50Hz), 1VA (60Hz) DC: 0.8W AC: 1.4VA (50Hz), 1.2VA (60Hz) DC: 0.9W AC: 2VA (50Hz), 1.7VA (60Hz) DC: 1.5W AC: 2.5VA (50Hz), 2VA (60Hz) DC: 1.5W 100M minimum (500V DC megger) Between live and dead parts: 2,000V AC, 1 minute Between contact and coil: 2,000V AC, 1 minute Between contacts of the same pole: 1,000V AC, 1 minute Between live and dead parts: 2,000V AC, 1 minute Between contact and coil: 2,000V AC, 1 minute Between contacts of different poles: 2,000V AC, 1 minute Between contacts of the same pole: 1,000V AC, 1 minute Electrical: Mechanical: 1,800 operations/hour maximum 18,000 operations/hour maximum Damage limits: 10 to 55Hz, amplitude 0.5 mm Operating extremes: 10 to 55Hz, amplitude 0.5 mm Damage limits: Operating extremes: 1,000m/s2 (100G) 200m/s2 (20G - SPDT, DPDT) 100m/s2 (10G - 3PDT, 4PDT) 50,000,000 operations minimum 500,000 operations minimum (120V AC, 10A) 200,000 operations minimum (120V AC, 10A) 25 to +50°C (no freezing) 25 to +40°C (no freezing) 45 to 85% RH (no condensation) SPDT: 24g, DPDT: 37g, 3PDT: 50g, 4PDT: 74g Note: Above values are initial values. 1. Measured using 5V DC, 1A voltage drop method 2. Measured at the rated voltage (at 20°C), excluding contact bouncing Release time of relays with diode: 40 ms maximum 3. Relays with indicator or diode: 1000V AC, 1 minute 4. For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating temperature range of relays with indicator or diode is 25 to +40°C. Timers Terminal Blocks Circuit Breakers Q-Pulse Id: TMS1594 USA: 800-262-IDEC Canada: 888-317-IDEC Active: 18/04/2016 729 Page 98 of 1068 Switches & Pilot Lights WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Relays & Sockets Electrical Life Curves AC Load 1000 (RH1) 500 120V AC resistive Characteristics (Reference Data) DC Load 1000 (RH1) 500 Life (× 10,000 operations) Life (× 10,000 operations) 100 50 20 10 (RH2) 1000 240V AC inductive 120V AC inductive 240V AC resistive 1 2 3 4 5 6 7 8 9 10 Load Current (A) 120V AC resistive 500 30V DC resistive 100 50 100V DC resistive 30V DC inductive 20 100V DC inductive 10 1 2 3 4 5 6 7 8 9 10 Load Current (A) (RH2) 1000 500 30V DC resistive Display Lights Life (× 10,000 operations) Life (× 10,000 operations) Relays & Sockets Timers Terminal Blocks 100 50 240V AC inductive 20 240V AC resistive 120V AC inductive 10 (RH3/RH4) 1000 500 1 2 3 4 5 6 7 8 9 10 Load Current (A) 120V AC resistive Life (× 10,000 operations) 100 50 20 240V AC inductive 240V AC resistive 120V AC inductive 10 1 2 3 4 5 6 7 8 9 10 Load Current (A) Maximum Switching Capacity (RH1) 10.0 5.0 AC resistive AC inductive Load Current (A) DC resistive 1.0 0.5 DC inductive 100 50 100V DC resistive 100V DC inductive 20 30V DC inductive 10 (RH3/RH4) 1000 500 1 2 3 4 5 6 7 8 9 10 Load Current (A) 30V DC resistive 30V DC inductive Life (× 10,000 operations) 100 50 20 100V DC resistive 100V DC inductive 10 1 2 3 4 5 6 7 8 9 10 Load Current (A) (RH2/RH3/RH4) 10.0 5.0 1.0 0.5 AC resistive AC inductive DC inductive DC resistive Load Current (A) 730 0.1 1 5 10 50 100 200 300 0.1 1 Load Voltage (V) Q-Pulse Id: TMS1594 www.idec.com Active: 18/04/2016 5 10 50 100 200 300 Load Voltage (V) Page 99 of 1068 Circuit Breakers Switches & Pilot Lights Display Lights Relays & Sockets Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Top Bracket Mounting Type) Operating Temperature (oC) Operating Temperature (oC) Operating Temperature (oC) (RH1) Note: The rated voltage is 100 applied to the coil. 90 80 DC Coil 70 60 50 AC Coil 40 30 20 10 0 1 2 3 4 5 6 7 8 9 10 Load Current (A) (RH2) Note: The rated voltage is 100 applied to the coil. 90 80 70 DC Coil 60 50 40 AC Coil 30 20 10 0 1 2 3 4 5 6 7 8 9 10 Load Current (A) (RH3/RH4) Note: The rated voltage is 100 applied to the coil. 90 80 70 60 50 AC/DC Coil 40 30 20 10 0 1 2 3 4 5 6 7 8 9 10 Load Current (A) Internal Connection (View from Bottom) Basic Type SPDT DPDT 1 5 9 13 14 ( ) ( + ) 1 5 9 13( ) 4 8 12 ( + )14 3PDT 1 5 9 13 () 2 4 6 8 10 12 ( + )14 4PDT 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 With Check Button Front Pushbutton Contacts can be operated by pressing the check button. With Indicator (-L type) SPDT Below 100V AC/DC 1 5 9 13 14 ( ) ( + ) 3PDT 1 5 9 13() 2 4 6 8 10 12 ( + )14 100V AC/DC and over 1 5 9 13 14 ( ) ( + ) 1 5 9 13( ) 2 4 6 8 10 12 ( + )14 4PDT 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 DPDT Below 24V AC/DC 24V AC/DC and over 1 5 9 13( ) 4 8 12 ( + )14 1 5 9 13( ) 4 8 12 ( + )14 When the relay is energized, the indicator goes on. · Relay coils less than 100V DC do not contain a protection diode (except DPDT). · Relay coils below 100V use LED indicator, coils above 100V use neon lamp indicator. With Diode (-D type) SPDT DPDT 1 5 9 13 14 ( ) ( + ) 1 5 9 13( ) 4 8 12 ( + )14 3PDT 1 5 9 13() 2 4 6 8 10 12 ( + )14 4PDT 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 Contains a diode to absorb the back emf generated when the coil is de-energized. The release time is slightly longer. Available for DC coil only. · Diode Characteristics Reverse withstand voltage: 1,000V Forward current: 1A Timers Terminal Blocks Circuit Breakers Q-Pulse Id: TMS1594 USA: 800-262-IDEC Canada: 888-317-IDEC Active: 18/04/2016 731 Page 100 of 1068 Switches & Pilot Lights Display Lights Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Relays & Sockets With Indicator LED & Diode (-LD type) SPDT 3PDT Below 100V DC 1 5 9 13 14 ( ) ( + ) 1 5 9 13( ) 2 4 6 8 10 12 ( + )14 100V DC and over 1 5 9 13() 14(+) 1 5 9 13( ) 2 4 6 8 10 12 ( + )14 4PDT 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 1 2 5 6 9 10 13( ) 3 4 7 8 11 12 ( + )14 DPDT 1 Below 5 24V 9 AC/DC 13( ) 1 24V 5 AC/DC 9 and over 13 ( ) 4 8 12 ( + )14 Contains an LED indicator and a surge absorber, and has the same height as the basic type. 4 8 12 14 ( + ) RH1B-U/RH1B-UL/RH1B-UD/RH1B-ULD Total length from panel surface including relay socket SH1B-05: 61.5 (63.5) max., SH1B-51: 39.6 (41.6) max. Dimensions in the ( ) include a hold-down spring. 4.7 27.5 ø2.6 hole 1 5 9 13 14 0.5 5.4 14 35.6 max. 6.4 Dimensions (mm) RH2B-U/RH2B-UL/RH2B-UD/RH2B-ULD Total length from panel surface including relay socket SH2B-05: 61.5 (63.5) max., SH2B-51: 39.6 (41.6) max. Dimensions in the ( ) include a hold-down spring. 4.7 27.5 ø2.6 hole 0.5 35.6 max. 6.4 1 4 5 8 9 12 13 14 21 RH3B-U/RH3B-UL/RH3B-D/RH3B-LD Total length from panel surface including relay socket SH3B-05: 61.5 (63.5) max., SH3B-51: 39.6 (41.6) max. Dimensions in the ( ) include a hold-down spring. 27.5 4.7 ø2.6 hole 0.5 1 2 4 5 6 8 9 10 11 13 14 35.6 max. 6.4 31 RH4B-U/RH4B-UL/RH4B-UD/RH4B-LD Total length from panel surface including relay socket SH4B-05: 61.5 (63.5) max., SH4B-51: 39.6 (41.6) max. Dimensions in the ( ) include a hold-down spring. RH1B-UT 4.7 27.5 43.2 38 ø2.6 hole 0.5 35.6 max. 6.4 1 2 5 6 9 10 13 3 4 7 8 11 12 14 41 3.5 14.5 ø2.6 hole 0.5 2 5.4 35.6 max. 6.4 6.6 4.7 5.9 1 5 9 13 14 4.7 27.5 RH2B-UT 10 43.2 38 3.5 21.5 ø2.6 hole 0.5 4.7 2 35.6 max. 6.4 7.25 4.7 5.9 1 4 5 8 9 12 13 14 RH3B-UT RH4B-UT 27.5 Timers Terminal Blocks 10 10 10 4.7 10 10 Circuit Breakers 43.2 38 732 3.5 ø2.6 hole 0.5 21.5 2 31.5 35.6 max. 6.4 7.25 4.7 5.9 1 2 4 5 6 8 9 10 12 13 14 Q-Pulse Id: TMS1594 28 44 38 4.7 2 ø2.6 hole 0.5 35.6 max. 6.4 42 max. 7.25 4.7 5.9 3.5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 28 41.5 www.idec.com Active: 18/04/2016 28 Page 101 of 1068 Switches & Pilot Lights Display Lights 7.25 4.7 Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series RH1V2-U/RH1V2-UD Dimensions con't (mm) RH2V2-U/RH2V2-UL/RH2V2-UD 27.5 27.5 0.5 35.6 max. 0.5 1 5 9 13 14 4.6 14 RH3V2-U/RH3V2-UL/RH3V2-D 1.5 2 2-ø2 holes 3-ø2.4 holes 7.15 6.6 4.4 12.5 4.7 0.5 0.5 2 0.5 35.6 max. 4.6 2 5 1 4 5 8 9 12 13 14 21 RH4V2-U/RH4V2-UL/RH4V2-UD 11-ø2.4 holes 10 10 4.7 14-ø2.4 holes 7.8 8-ø2.4 holes 10 14.2 30 10 13.15 4.7 2 2 13.15 13.15 27.5 7.8 7.25 35.6 max. 0.5 0.5 4.6 1 2 4 5 6 8 9 10 11 13 14 31 27.5 7.8 7.25 0.5 35.6 max. 0.5 4.6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 41 Standard DIN Rail Mount Sockets SH1B-05 17 8 M3.5 Terminal Screw 31.5 18 DIN Rail (BNDN) SH2B-05 Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 5 1 22 8 M3.5 Terminal Screw 4.2 47 4.2 47 67 67 16 M3 Terminal 5.5 min. 4.8 min. 14 13 Screw 4.4 max. 4 max. 9 (Top View) 16 14.5 ø3.6 min. ø3.2 min. 26 2.5 20 25 30 7.9 max. 5.9 max. 2.5 (For terminals 1, 5, and 9) (For terminals 13 and 14) 31.5 18 DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 85 41 14.5 25 26 4.4 max. 7.9 max. 5.5 min. ø3.6 min. 14 13 12 9 (Top View) 2.5 67 SH3B-05 32 8 36 40 4.2 47 M3.5 Terminal Screw SH4B-05 31.5 18 DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 865 421 42 8 67 36 4.4 max. 5.5 min. 14 13 12 10 9 14.5 7.9 max. (Top View) 46 25 ø3.6 min. 50 4.2 47 31.5 M3.5 Terminal 18 Screw DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 8 765 4 321 14.5 25 46 4.4 max. 5.5 min. 7.9 max. ø3.6 min. 14 13 12 11 10 9 (Top View) Relays & Sockets Timers Terminal Blocks 2.5 Circuit Breakers Q-Pulse Id: TMS1594 USA: 800-262-IDEC Canada: 888-317-IDEC Active: 18/04/2016 733 Page 102 of 1068 Switches & Pilot Lights 69 4.2 48 Display Lights 1.7 Relays & Sockets WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RH Series Relays & Sockets Dimensions con't (mm) Finger-safe DIN Rail Mount Sockets SH1B-05C SH2B-05C 17 7 M3.5 Terminal Screw ø5 36 25 DIN Rail (BNDN) Terminal Arrangement 5 2-ø4.2 Mounting Holes 1 (or M4 Tapped Holes) 22 7 M3.5 Terminal Screw ø5 69 16 M3 Terminal Screw 14 13 9 16 Ring terminals 18.7 cannot be used. (Top View) 1.7 26 30 20 29.5 SH3B-05C 32 7 M3.5 Terminal Screw ø5 SH4B-05C 36 25 DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 865 421 42 7 ø5 4.2 49 69 69 36 14 13 12 10 9 Ring terminals (Top View) 36 18.7 cannot be used. 40 29.5 46 1.7 50 1.7 4.2 49 4.2 49 36 25 18.7 29.5 DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 85 41 26 Ring terminals cannot be used. 14 13 12 9 (Top View) 36 25 18.7 29.5 DIN Rail (BNDN) Terminal Arrangement 2-ø4.2 Mounting Holes (or M4 Tapped Holes) 8 765 4 321 46 Ring terminals cannot be used. 14 13 12 11 10 9 (Top View) Through Panel Mount Socket SH1B-51 SH2B-51 18 3.5 2.4 12.2 Panel Thickness: 1 to 2 Terminal Arrangement 3 11 18.7 1 5 9 13 14 (Bottom View) 5.4 min. 25.6 +0.2 0 [18 (N1) + 12.4] + 0.5 0 N: No. of sockets mounted 10.4 min. when using hold-down springs 27 3.5 21.2 31 0.3 25.4 Panel Thickness: 1 to 2 Terminal Arrangement [27 (N1) + 21.4] +0.5 0 +0.2 0 14 58 9 12 25.6 13 14 3 (Bottom View) N: No. of sockets mounted 11 5.4 min. 18.7 10.4 min. when using hold-down springs SH3B-51 36 30.2 SH4B-51 Panel Thickness: 1 to 2 Terminal Arrangement 0.3 25.4 1 24 568 9 10 12 13 14 3 (Bottom View) 11 18.7 5.4 min. 25.6 +0.2 0 [36 (N1) + 30.4] +0.5 0 N: No. of sockets mounted 3.5 10.4 min. when using hold-down springs 45 3.5 39.2 31 0.3 25.4 Panel Thickness: 1 to 2 Terminal Arrangement [45 (N1) + 39.4] +0.5 0 +0.2 0 25.6 1234 5678 9 10 11 12 13 14 3 (Bottom View) N: No. of sockets mounted 11 5.4 min. 18.7 10.4 min. when using hold-down springs Timers 31 0.3 25.4 Terminal Blocks 31 Circuit Breakers 734 Q-Pulse Id: TMS1594 www.idec.com Active: 18/04/2016 Page 103 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Small, compact Thermostat KTO 011 / KTS 011 Large setting range Small size Simple to mount High switching performance Regulating and Monitoring Thermostat KTO 011 (NC) Thermostat KTS 011 (NO) KTO 011: Thermostat (normally closed); contact breaker for regulating heaters. KTS 011: Thermostat (normally open); contact maker for regulating of filter fans and heat exchangers or for switching signal devised when temperature limit has been exceeded. | Technical Data Switch temperature difference Sensor element Contact type Contact resistance Service life Max. Switching capacity EMC Connection Mounting Casing Dimensions Weight Fitting position Operating/Storage temperature Protection type 7K (± 4K tolerance) thermostatic bimetal snap-action contact < 10mOhm > 100,000 cycles 250VAC, 10 (2) A 120VAC, 15 (2) A DC 30W acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 2-pole terminal for 2.5mm², clamping torque 0.8Nm clip for 35mm DIN rail, EN50022 (or for exit filter EF 118 Series) plastic according to UL94 V-0, light grey 60 x 33 x 43mm approx. 40g variable -20 to +80 °C (-4 to +176 °F) / -45 to +80 °C (-49 to +176 °F) IP20 Thermostat Heater KTO 011 (NC) Thermostat e.g. Fan KTS 011 (NO) Thermostat KTS 011 (NO) e.g. Signal device Example of connection Setting range 0 to +60°C -10 to +50°C +20 to +80°C +32 to +140°F +14 to +122°F 0 to +60°C 26 Q-Pulse Id: TMS1594 Art. No. Contact Breaker (NC) 01140.0-00 01142.0-00 01159.0-00 01140.9-00 01142.9-00 01146.9-00 Example of connection Art. No. Contact Maker (NO) 01141.0-00 01143.0-00 01158.0-00 01141.9-00 01143.9-00 01147.9-00 Approvals VDE VDE VDE UL File No. E164102 UL File No. E164102 UL File No. E164102 Active: 18/04/2016 Page 104 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.3. PUSHBUTTONS & SELECTOR SWITCHES KRAUS & NAIMER CA10-A221-FT2 'LOCAL REMOTE' Selector Switch SPRECHER & SCHUH D7P-MT44-PX01 Emergency Stop Pushbutton C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 105 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual D^R[LQ!7\VL[RWV!JVM!4WVORP\YJ[RWV 4#!42#!425#!4= D^R[LQNZ 7\VL[RWV E`XN&9JVMTN =cSedSX* ;80 ;8<** G\QdU ;80)- ;8-,) ;8-,9) ;.2) ;C0 ;8.1 ;8.19 ;/-1 ;C-, 4WMN JdQWUc 4WVVNL[RWV!5RJPYJU @?&@77!D^R[LQNZ!^R[Q!-'h D^R[LQRVP -!`_\U .!`_\U )& $ $ $ $ 8.,,)2,, - ' $ $ $ $ 8.,-)2,, - /!`_\U $ $ $ $ 8.,.)2,, . /!`_\U gYdX!bUT!XQ^T\U $ $ $ $ 8.,.)2.2 . /!`_\U gYdX!M41, $ $ 8.,.)2.3! . `QT\_S[!QddQSX]U^d 0!`_\U 0!`_\U -!`_\U!`bUS\_cU!2o1!`_\U 2!`_\U 3!`_\U 4!`_\U 4!`_\U .!`_\U!`bUS\_cU!2o5!`_\U -,!`_\U --!`_\U -.!`_\U $ $ $ $ 8.,/)2,, . $ $ $ $ 821/)2,, . $ $ $ $ 8/0-)2,, / $ $ $ $ 8/0.)2,, / $ $ $ $ 8/0/)2,, 0 $ $ $ $ 8/00)2,, 0 $ $ $ $ 8210)2,, 0 $ $ $ $ 8/01)2,,! 1 $ $ $ $ 8/02)2,, 1 $ $ % % 8/03)2,, 2 $ $ % % 8/04)2,, 2 -!`_\U ) ?55 $ $ $ $ 8.,,)2., - .!`_\U ?> $ $ $ $ 8.,-)2., - /!`_\U $ $ $ $ 8.,.)2., . 0!`_\U $ $ $ $ 8.,/)2., . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2., . 1!`_\U $ $ $ $ 8/0-)2., / 2!`_\U $ $ $ $ 8/0.)2., / 3!`_\U $ $ $ $ 8/0/)2., 0 4!`_\U $ $ $ $ 8/00)2., 0 4!`_\U .!`_\U!`bUS\_cU!2o- $ $ $ $ 8210)2., 0 5!`_\U! $ $ $ $ 8/01)2.,! 1 -,!`_\U $ $ $ $ 8/02)2., 1 --!`_\U $ $ & & 8/03)2., 2 -.!`_\U $ $ & & 8/04)2., 2 -!`_\U $ $ $ $ 8.,,)2.- - .!`_\U /!`_\U ) ?55 $ $ $ $ 8.,-)2.- - ?> $ $ $ $ 8.,.)2.- . 0!`_\U $ $ $ $ 8.,/)2.- . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2.- . 1!`_\U $ $ $ $ 8/0-)2.- / 2!`_\U $ $ $ $ 8/0.)2.- / -!`_\U ) 5AL> $ $ $ $ 8.,,)2.. - .!`_\U C8<< $ $ $ $ 8.,-)2.. - /!`_\U $ $ $ $ 8.,.)2.. . 0!`_\U $ $ $ $ 8.,/)2.. . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2.. . 1!`_\U $ $ $ $ 8/0-)2.. / 2!`_\U $ $ $ $ 8/0.)2.. / -!`_\U $ $ $ $ 8.,,)2./ - .!`_\U /!`_\U ) 5AL> $ $ $ $ 8.,-)2./ - C8<< $ $ $ $ 8.,.)2./ . 0!`_\U $ $ $ $ 8.,/)2./ . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2./ . 1!`_\U $ $ $ $ 8/0-)2./ / 2!`_\U $ $ $ $ 8/0.)2./ / -!`_\U 7DED31AHC0A4 $ $ $ $ 8.,,)2.0 - .!`_\U /!`_\U ) 5AL> $ $ $ $ 8.,-)2.0 - C8<< $ $ $ $ 8.,.)2.0 . 0!`_\U $ $ $ $ 8.,/)2.0 . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2.0 . 1!`_\U $ $ $ $ 8/0-)2.0 / 2!`_\U $ $ $ $ 8/0.)2.0 / -!`_\U 7DED31AHC0A4 $ $ $ $ 8.,,)2.1 - .!`_\U /!`_\U )& $ $ $ $ 8.,-)2.1 - ' $ $ $ $ 8.,.)2.1 . 0!`_\U $ $ $ $ 8.,/)2.1 . 0!`_\U -!`_\U!`bUS\_cU!2o- $ $ $ $ 821/)2.1 . 1!`_\U $ $ $ $ 8/0-)2.1 / 2!`_\U $ $ $ $ 8/0.)2.1 / -V_b!ecU!Y^!Q!dXbUU!`XQcU!V_eb)gYbU!cicdU]!gYdX!cgYdSXUT!^UedbQ\ 2 ' ) + - / '' ') '+ '- '/ (' () ( * , . '& '( '* ', '. (& (( (* -)-.!`_\U ')+- (*,. 0!`_\U!-!`_\U!`bUS\_cU!2o ' ) + - / '' ') '+ ( * , . '& '( '* ', 4!`_\U!.!`_\U!`bUS\_cU!2o Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 106 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual >W\V[RVP DRVPTN!9WTN!>W\V[RVP 4#!42#!425#!4= D^R[LQNZ KUb]Y^Q\c b_dQdUT!5,o 4WMN ;80 ;80);C0 ;8<** ;8-,) ;8.1 ;C-, NYdX!\_S[Y^W!^ed!Q^T!cXQVd!cUQ\(!`b_dUSdY_^!AG 22 NYdX_ed!UcSedSXU_^!`\QdU NYdX!caeQbU!UcSedSXU_^!`\QdU ]] ]] >J- -2+.. >J-)M -2+.. >K>K-)M >K/ >K/)M .. .. ..+/, ..+/, >J. -2+.. >J.)M -2+.. >K. >K.)M >K0 >K0)M .. .. ..+/, ..+/, NYdX!bUSdQ^We\Qb!UcSedSXU_^!`\QdU >J0 -2+.. >J0)M -2+.. NYdX!cYjU!J-!UcSedSXU_^!`\QdU!Q^T!XUQfi!Tedi!\QdSXY^W >@/ .. >@/)M .. D_e^dY^W![Ui!V_b!\_S[Y^W!^ed /. Q-Pulse Id: TMS1594 Active: 18/04/2016 J,,!K-3,!,5 Page 107 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ENLQVRLJT!5J[J 4#!42#!4= D^R[LQNZ DNTNL[RWV!5J[J ;80 ;8-, ;8-- ;8., ;8.1 ;0. ;80)- ;C0 ;8-,9 ;C-, ;8--9 ;8.,9 ;8.19 ;.2 ;/. ;0/ ;4, ;-.1 ;/-1+;/-2 CJ[NM!;VZ\TJ[RWV!GWT[JPN!FR A=;!2,503)/(!=E!2,503)/- M<=!,22,!`Qbd!-,3- M J=M0 M LC+;Q^QTQ M ;==+E=DBF M ]Y^*!f_\dQWU M 00, 00, /4, /4, /,, /,, 0,,+/4, u 25, 25, 25, 25, 25, 25, 25, 25, 25, 25, 25,+-,,, 22, 25, 22, 22, 25, 22, 22, 22, 22, 22, 22, /,, 2,, 2,, 2,, /,, 2,, 2,, 2,, 2,, 2,, 2,, /4, u 0,, 0,, u! 0,, 0,, 0,, 0,, u u _^!bUaeUcd CJ[NM!;UX\TZN!HR[QZ[JVM!GWT[JPN!FRUX [M 0 0 CJ[NM!EQNYUJT!4\YYNV[!; &; \ [Q A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 8 -, -, J=M0 LC+;Q^QTQ /4,!M 8 -, -, 22,!M 8 u u 8 -, -, CJ[NM!@XNYJ[RWVJT!4\YYNV[!; N 8;).-8 JgYdSXY^W!_V!bUcYcdYfU \_QTc(!Y^S\eTY^W!]_) TUbQdU!_fUb\_QTc 8;)- IUcYcdYfU!_b!\_g Y^TeSdYfU!\_QTc A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 8 -, -, J=M0 /4,!M 8 -, -, 22,!M 8 u u 2 2 2 2 2 2 2 2 2 2 2+4 ., ., ., .1 -2 -2 -2 .1 -. -. -. .1 ., ., ., /, /. /. 1, 2/ --1 -1, /-1 /. /. 0, 2/ -,, -2, /-1 /. /. 0, 2/ u u /-1 /, 0, 1, 21 -,, -1, .0, ., ., ., .1 /. /. 0, 2/ -,, -1, /-1 -2 -2 -2 .1 /. /. 0, 2/ -,, -2, /-1 -. -. -. ., /. /. 0, 2/ u u /-1 8;)..8 JgYdSXY^W!_V!S_]RY^UT!bU) A=;!2,503)/(!=E!2,503)/ cYcdYfU!_b!\_g!Y^TeSdYfU!\_QTc M<=!,22, ..,!M)1,,!M 8 -, -, ., ., ., .1 /. /. 0, 2/ -,, -1, /-1 Y^S\eTY^W!]_TUbQdU!_fUb\_QTc `Qbd!-,3 22,!M)25,!M 8 u u ., ., ., .1 /. /. 0, 2/ -,, -.1 -.1 8;)-1 JgYdSXY^W!_V!S_^db_\ TUfYSUc(!S_^dQSd_bc( fQ\fUc!UdS* GY\_d!<edi 8]`UbU!IQdY^W IUcYcdYfU!_b!\_g Y^TeSdYfU!\_QTc A=;!2,503)/(!=E!2,503)/ M<=!,22, ..,!M).0,!M 8 `Qbd!-,3 /4,!M)00,!M 8 LC+;Q^QTQ0 @UQfi LC+;Q^QTQ0 8 .(1 .(1 1 1 1 4 -(1 -(1 0 0 0 1 -. -0 -2 u u u u 2 23 uuuu 8/,, ;/,, 8/,, 82,, 82,, 82,, 8/,, 82,, 82,, 82,, u u 82,, -, -, ., ., ., /, /, 0, 1, 21 -,, -1, .0, IUcYcdYfU!\_QT+]_d_b!\_QT ;== E=DBF 8 0+. u 8 2+0. u -,+2 u -,+2 -2+-, u .1+-, /.+-, 0,+-, 2/+-, u u -,+2 u u .,+-, u u u u u u u 3YNJSRVP!LJXJLR[` ..,!M).0,!M 8 1, 1, -1, -1, -1, .,, .4, .4, /4, 11, 42, --,, .,,, /4,!M)00,!M 8 1, 1, -1, -1, -1, .,, .1, .1, /2, 11, 42, --,, .,,, 22,!M)25,!M 8 u u 4, 4, 4, -.1 -1, -1, .3, /21 0,, 05, /0, G_gUb!\_cc!`Ub!S_^dQSd!Qd!Ae N IUcYcdQ^SU!d_!fYRbQdY_^ IUcYcdQ^SU!d_!cX_S[ DQWY[!4RYL\R[!AYW[NL[RWV DQh*!VecU!cYjU $WC)SXQbQSdUbYcdYS% 8 IQdUT!cX_bd)dY]U!gYdXcdQ^T!SebbU^d! $-c)SebbU^d% 8 54!D^R[LQRVP!4JXJLR[`2 E_*!_V!cUbYUc!S_^dQSdc IUcYcdYfU!\_QTc K ! -!]c -./0124 M_\dQWU!M .0 04 3, 51 -., -01 -5, 8 04 51 -0, -5, .0, .5, /1, 2, -., -4, .0, /,, /2, 01, --, .., //, 00, 11, 22, u .., 00, 22, u u u u 00, 22, u u u u u ,(0+,(5 ,(0 ,(5 - ,(5 ,(5 ,(3 -(/ -(/ -(3 1(4 /(4 -3 ]Y^*!0!W(!.)-,,!@j(!-(2!]] _^!bUaeUcd ]Y^*!2!W(!2!]c _^!bUaeUcd -, -, 2, 5, .1 .1 .1 /1 /1 1, 2/ 4, -.1 .,, /-1 -0, -0, -0, .4, 04, /1, 4,, -,,, -/,, .,,, 0.,, CJ[NM!@XNYJ[RWVJT!4\YYNV[!; N ;80 ;8-, ;8-- ;8., ;8.1 ;/-1/ ;80)- ;C0 ;8-,9 ;C-, ;8--9 ;8.,9 ;8.19 ;.2J ;/.J ;0.J ;4, ;-.1 ;/-2/ -, -, ., ., ., .1 /. u 1, u --1 u /-1 2 2 -. -. -. ., .1 /. 0, 2/ -,, -1, .1, .(1 .(1 0(1 0(1 0(1 3(1 -, ./ .3 /, u u u ,(3 ,(3 - -- -(1 . 2(1 u u u u u ,(/ ,(/ ,(0 ,(0 ,(0 ,(1 ,(2 -(. u u u u u ,(. ,(. ,(.3 ,(.3 ,(.3 ,(/ ,(/ ,(0 u u u u u A^TeSdYfU!\_QTc K 7!1,!]c .0 04 3, 51 -., -01 -5, 8 /, 2, 5, -., -1, -4, .0, 04 51 -0, -5, .0, .5, /1, 2, -., -4, .0, /,, /2, 01, --, .., //, 00, 11, 22, u 2 2 -. / /1 - -. ,(3 ,(3 ,(/ ,(/ ,(0 -. -. ., .1 /. 0, 2/ -,, -1, .1, 11 5 -. .1 /, 11 // 1, 3, .. / / -2 ., u u u u -- -(1 -(1 -- -1 u u u u ,(0 ,(0 ,(1 ,(1 /(. /(1 u u u u 2UKRNV[!ENUXNYJ$ [\YN!WO!D[JPNZ1(!3 _`U^!Qd!-,,!#!Ae+AdX U^S\_cUT!Qd!-,,!#!AdXU 11!o;!TebY^W!.0!X_ebc!gYdX!`UQ[c!e`!d_!2,!o; /1!o;!TebY^W!.0!X_ebc!gYdX!`UQ[c!e`!d_!0,!o; -MQ\YT!V_b!\Y^Uc!gYdX!Wb_e^TUT!S_]]_^!^UedbQ\!dUb]Y^QdY_^(!_fUbf_\dQWU!SQdUW_bi!AAA(!`_\\edY_^!TUWbUU!/*!MQ\eUc!V_b!_dXUb!ce``\i!cicdU]c!_^!bUaeUcd*! .MQ\YT!V_b!;80!_^\i*!/<;!cgYdSXY^W!SQ`Q) 0, SYdi!Q``\YUc!d_!FE+F>>!cgYdSXUc*!JgYdSXY^W!SQ`QSYdi!V_b!_dXUb!S_^VYWebQdY_^c!_^!bUaeUcd*! 0A^dUb^QdY_^Q\!JdQ^TQbTc!Q^T!8``b_fQ\c(!bUVUb!d_!`QWU!/5*!1>_b!U\USdb_]QW^UdYS!_`dY_^Q\!UhdbQc!cUU QTTYdY_^Q\!TQdQ!Y^!;QdQ\_W!-,-*!2MQ\eUc!V_b!cgYdSXUc!gYdX!c`bY^W!bUdeb^!_^!bUaeUcd*!!3Jd_bQWU!dU]`UbQdebU6!)0,!o;!d_!41!o;!$Y^!SQcU!_V!dU]`UbQdebU!RU\_g!)1!o;!^_!cX_S[!\_QT!`Ub]YccYR\U%* Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 108 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ENLQVRLJT!5J[J 4#!42#!4= D^R[LQNZ DNTNL[RWV!5J[J ;80 ;8-, ;8-- ;8., ;8.1 ;0. ;/-1 ;80)- ;C0 ;8-,9 ;C-, ;8--9 ;8.,9 ;8.19 ;.2 ;/. ;0/ ;4, ;-.1 ;/-2 CJ[NM!F[RTRaJ[RWV!4J[NPWY` 8;). J\Y`!bY^W!]_d_b!cdQbdY^W( bUfUbcY^W!Q^T!`\eWWY^W( cdQb)TU\dQ!cdQbdY^W ;80);/. A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 /!`XQcU ..,!M).0,!M .(1 .(1 0 0 0 1(1 3(1 4 -, -4(1 /, /3 11 /!`_\U /4,!M)00,!M [N 0(1 0(1 3(1 3(1 3(1 -- -1 -1 -4(1 /, 01 11 5, 1,,!M u u -, -, -, -1 -4(1 -4(1 .. 0, 11 31 --, 22,!M)25,!M u u -, -, -, -/ -1 -1 .. /3 11 11 11 8;)/ <YbUSd)_^)\Y^U!cdQbdY^W( cdQb)TU\dQ!cdQbdY^W ;0.);/-1 /!`XQcU ..,!M).0,!M -(1 -(1 / / / 0 1(1 1(1 3(1 -- -1 .. /3 /!`_\U /4,!M)00,!M [N .(. .(. 1(1 1(1 1(1 3(1 -- -- -1 -4(1 /, /3 11 1,,!M u u 1(1 1(1 1(1 3(1 -- -- -1 -4(1 /, /3 11 22,!M)25,!M u u 1(1 1(1 1(1 3(1 -- -- -1 -4(1 /, /, /3 -!`XQcU .!`_\U --,!M)-.,!M ,(/ ,(/ ,(2 ,(2 ..,!M).0,!M [N ,(11 ,(11 .(. .(. /4,!M)00,!M ,(31 ,(31 / / ,(2 -(1 .(. .(. .(1 / .(. / 0 0 1(1 2 / /(3 1(1 1(1 3(1 -- /(3 1(1 -3(1 -- .. -/ -4(1 /, 8;)0 <YbUSd)_^)\Y^U!cdQbdY^W( bUfUbcY^W(!`\eWWY^W!Q^T Y^SXY^W /!`XQcU ..,!M).0,!M ,(/3 ,(/3 ,(11 ,(11 ,(11 -(1 .(1 .(3 /(3 1(1 2 -, -1 /!`_\U /4,!M)00,!M [N ,(11 ,(11 -(1 -(1 -(1 / 1(1 1(1 2 3(1 -- -1 .1 1,,!M u u -(1 -(1 -(1 / 1(1 1(1 2 3(1 -- -1 .1 22,!M)25,!M u u -(1 -(1 -(1 / 1(1 1(1 2 3(1 -- -1 .. -!`XQcU --,!M)-.,!M ,(-1 ,(-1 ,(/ ,(/ ,(/ ,(01 ,(31 ,(31 -(- -(. -(1 .(. 0 .!`_\U ..,!M).0,!M [N ,(.1 ,(.1 ,(31 ,(31 ,(31 -(- -(1 -(1 .(. .(0 / 0 3(1 /4,!M)00,!M ,(1 ,(1 -(1 -(1 -(1 .(. / / /(3 0 1(1 3(1 -- 8;)./8 >bUaeU^d!cgYdSXY^W!_V ]_d_bc!_b!_dXUb!XYWX Y^TeSdYfU!\_QTc /!`XQcU ..,!M).0,!M -(4 -(4 /(3 /(3 /(3 1(1 3(1 3(1 -- -1 /, /3 31 /!`_\U /4,!M)00,!M [N / / 3(1 3(1 3(1 -- -1 -1 .. /, 01 31 -/. 1,,!M u u 3(1 3(1 3(1 -- -1 -1 /, 01 11 5, -/. 22,!M)25,!M u u 3(1 3(1 3(1 -- -1 -1 .. 0, 01 11 /3 -!`XQcU --,!M)-.,!M ,(/3 ,(/3 ,(31 ,(31 ,(31 -(1 .(. .(. .(1 0 1(1 -- -4(1 .!`_\U ..,!M).0,!M [N ,(31 ,(31 .(1 .(1 .(1 / 0 0 1(1 -, -1 .. /3 /4,!M)00,!M -(- -(- /(3 /(3 /(3 1(1 3(1 3(1 -- -4(1 .. /3 11 CJ[RVPZ LC+;Q^QTQ JdQ^TQbT!]_d_b!\_QT <FC)IQdY^W $cY]Y\Qb!8;)/% --,!M)-.,!M ,(31 ,(31 -(1 -(1 -(1 / 1 1 3(1 3(1 -, -1 /, /!`XQcU ..,!M).0,!M @G - - // / 3(1 -, -, -1 -1 ., .1 31 /!`_\U 00,!M)04,!M u u u1 1 -, u ., .1 .1 /, 0, 31 11,!M)2,,!M u u u1 1 -, u .1 /, /, 0, 1, 2, --,!M)-.,!M ,(// ,(// ,(1 ,(1 ,(1 -(1 . -!`XQcU ..,!M).0,!M ,(31 ,(31 - - -/1 .!`_\U .33!M @G ,(31 ,(31 . . ./1 00,!M)04,!M u u u. .1 u 11,!M)2,,!M u u u. .1 u . / / 1 3(1 -1 1 3(1 3(1 -, -1 0, 1 3(1 3(1 -, -1 0, -, -1 -1 ., .1 1, -1 ., ., .1 /, 1, @UQfi!]_d_b!\_QT IUfUbcY^W)IQdY^W $cY]Y\Qb!8;)0% --,!M)-.,!M u u ,(1 u ,(1 - . . / 1 3(1 -, -1 /!`XQcU ..,!M).0,!M @G u u- u - . / / 1 3(1 -1 ., /, /!`_\U 00,!M)2,,!M u u uu/1 u -, -1 ., .1 /, 0, --,!M)-.,!M u u ,(-3 u ,(-3 ,(// -(1 -(1 -(1 . / 1 3(1 -!`XQcU ..,!M).0,!M @G u u ,(1 u ,(1 ,(31 / / / 1 3(1 -, -1 .!`_\U .33!M u u ,(2 u ,(2 - / / / 1 3(1 -, -1 >J_%!ANYURZZRKTN!HRYN!8JPN!)!LcU!S_``Ub!gYbU!_^\i JY^W\U)S_bU!_b!cdbQ^TUT!gYbU >\UhYR\U!gYbU $c\UUfY^W!Y^!QSS_bTQ^SU!gYdX!<AE!02..4% >\UhYR\U!8N?!gYbUc!$gYdX_ed!c\UUfU% .h -h. .h -h. .h .h .h .h .h .h ]]. -(1 ,(1)-(1 .(1 ,(1).(1 .(1 0 2 2 -, -2 /1 3, -41- 8N? -0 .,)-2 -. .,)-0 -. -, 4 4 4 2 . .+, D;D /1, .h -h. .h -h. .h .h .h .h .h .h ]]. -(1 ,(1)-(1 .(1 ,(1).(1 .(1 0 0 2 2 -, .1 1, -1,- $u% $u% $.(1% $u% $.(1% $.(1% $0% $0% $2% $-,% $.1% $1,% 8N? -2 .,)-2 -0 .,)-0 -0 -. -, -, 4 2 / -+, D;D /,, ;_^^USdY^W!gYbU!)!_edcYTU!TYQ]UdUb ;_^^USdY^W!gYbU!)!`\eW)Y^!TU`dX GUb]YccYR\U!S_^^USdY^W!Q]RYU^dU!dU]`UbQdebU!bQ^WU ]] u -(1).(4 u -(1)/(2 u u u u u u u u u ]] u 4(1 u --(1 u u u u u u u u u o; u 1)0, u 1)0, u u u u u u u u u -;QR\U!\eW!]ecd!QSSU`d!D-.!cSbUg*!.KXU!Y^ce\QdY_^!]QdUbYQ\!_V!dXU!S_^TeSd_b!XQc!d_!RU!GM;!$di`YSQ\!gYbU!S_TUc!QbU!@,1M)B,(1!***!@,3M)B-(1!_b!@,1M)L,(1!***!@,3M) L-(1!UdS*%*!FdXUb!]QdUbYQ\c!_^!bUaeUcd*!;_^^USdUT!S_^TeSd_bc(!gXYSX!XQfU!d_!RU!TYcS_^^USdUT!Q^T!bU)S_^^USdUT!QWQY^!]ecd!RU!Sed!Y^!_bTUb!d_!U^cebU!Q!`b_`Ub!U\USdbY) 0- SQ\!S_^^USdY_^!Q^T!d_!`bUfU^d!Q!S_]`\UdU!Sed)_VV!_V!dXU!gYbU!Y^ce\QdY_^*!KXU!`Ub]YccYR\U!Q]RYU^d!dU]`UbQdebU!bQ^WU!gXU^!S_^^USdY^W!dXU!gYbUc!Yc!1)0,!o;* Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 109 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ENLQVRLJT!5J[J 425!D^R[LQNZ DNTNL[RWV!5J[J ;8<-- ;8<-. CJ[NM!;VZ\TJ[RWV!GWT[JPN!FR A=;!2,503)/(!=E!2,503)/- M<=!,22,!`Qbd!-,3 M 2,, 2,, J=M. M 2,, 2,, LC+;Q^QTQ M /,, /,, ]Y^*!f_\dQWU M - 2 CJ[NM!;UX\TZN!HR[QZ[JVM!GWT[JPN!FRUX CJ[NM!EQNYUJT!4\YYNV[!;\&;[Q A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 8 J=M. 8 LC+;Q^QTQ 8 _^!bUaeUcd 2 2 1 1 2 2 CJ[NM!@XNYJ[RWVJT!4\YYNV[!;N 8;).-8 JgYdSXY^W!_V!bUcYcdYfU \_QTc(!Y^S\eTY^W!]_) TUbQdU!_fUb\_QTc 8;)- IUcYcdYfU!_b!\_g Y^TeSdYfU!\_QTc A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 LC+;Q^QTQ/ -!M+2!M 8 -.!M+.0!M 8 04!M+--,!M 8 ..,!M+0,,!M 8 00,!M+1,,!M 8 2,,!M 8 J=M. -!M+2!M 8 -.!M+.0!M 8 04!M+--,!M 8 ..,!M+/4,!M 8 00,!M+1,,!M 8 2,,!M 8 2+/ .+,(4+,(0 ,(.+,(-/ ,(-+,(,4 ,(,1 1+/ .+,(4+,(0 ,(.+,(-/ ,(-+,(,4 ,(,1 u+2 1+1 0+/ .+-(/ -+,(4 ,(1 u+1 1+1 0+/ .+-(/ -+,(4 ,(1 G_gUb!\_cc!`Ub!S_^dQSd!Qd!A e DQWY[!4RYL\R[!AYW[NL[RWV DQh*!VecU!cYjU IQdUT!cX_bd)dY]U!gYdXcdQ^T!SebbU^d! N $WC)SXQbQSdUbYcdYS% 8 $-c)SebbU^d% 8 54!D^R[LQRVP!4JXJLR[`1 <;)- IUcYcdYfU!\_QT K 7!-!]c A=;!2,503)/(!=E!2,503)/ M<=!,22,!`Qbd!-,3 J=M. LC+;Q^QTQ/ -!M+2!M 8 -.!M+.0!M 8 04!M+2,!M 8 --,!M+..,!M 8 .0,!M+1,,!M 8 2,,!M 8 ,(1 2 /1 0+.(1 -(1+,(4 ,(/+,(.3 ,(.+,(,(,4+,(,/ ,(,. ,(. 2 1, u+0 /+.(. -(.+,(2+,(/ ,(.1+,(,(- >J_%!ANYURZZRKTN!HRYN!8JPN!)!LcU!S_``Ub!gYbU!_^\i JY^W\U)S_bU!_b!cdbQ^TUT!gYbU .h .h ]]. .(1 .(1 8N? -. -. >\UhYR\U!gYbU $c\UUfY^W!Y^!QSS_bTQ^SU!gYdX!<AE!02..4% ]]. 8N? .h .(1 $.(1% -0 .h .(1 $.(1% -0 2UKRNV[!ENUXNYJ$ [\YN!WO!D[JPNZ0(!2 _`U^!Qd!-,,!#!Ae+AdX U^S\_cUT!Qd!-,,!#!AdXU 11!o;!TebY^W!.0!X_ebc!gYdX!`UQ[c!e`!d_!2,!o; /1!o;!TebY^W!.0!X_ebc!gYdX!`UQ[c!e`!d_!0,!o; -MQ\YT!V_b!\Y^Uc!gYdX!Wb_e^TUT!S_]]_^!^UedbQ\!dUb]Y^QdY_^(!_fUbf_\dQWU!SQdUW_bi!AAA(!`_\\edY_^!TUWbUU!/*!MQ\eUc!V_b!_dXUb!ce``\i!cicdU]c!_^!bUaeUcd* .A^dUb^QdY_^Q\!JdQ^TQbTc!Q^T!8``b_fQ\c(!bUVUb!d_!`QWU!/5*!/DQh*!/,,!M*!0>_b!U\USdb_]QW^UdYS!_`dY_^Q\!UhdbQc!cUU!QTTYdY_^Q\!TQdQ!Y^!;QdQ\_W!-,-* 0/ 1MQ\eUc!V_b!cgYdSXUc!gYdX!c`bY^W!bUdeb^!_^!bUaeUcd*!!2Jd_bQWU!dU]`UbQdebU6!)0,!o;!d_!41!o;!$Y^!SQcU!_V!dU]`UbQdebU!RU\_g!)1!o;!^_!cX_S[!\_QT!`Ub]YccYR\U%* Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 110 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual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h02 -*1,h-*4- 1 *., .5(1 -*-2 /5 -*10 -.(1 *05 ) ) ;8-, ;8-;8<-;8<-. 04 -*45 20 .*1. 0/ -*25 2 *.0 /5 -*10 ) ) -4(. *3. .1(. *55 ;C-, 04 -*45 20 .*1. 1,h12 -*53h.*., 2 *.0 /5 -*10 ) ) -4(. *3. .1(. *55 ;8., 04 -*45 20 .*1. 01 -*33 2 *.0 /5 -*10 ) ) -4(. *3. .1(. *55 ;8.1 04 -*45 20 .*1. 02 -*4- 2 *.0 /5 -*10 ) ) -4(. *3. .1(. *55 G6)) G6))G G7 G7$G G7)) G7))G 2 3 4 5( 5) 5* 6 > 04 ;8-, ;8-;8<-;8<-. ;C-, ;8., ;8-,9 ;8--9 ;8.1. ;8.,9 04 04 04 04 $20% 20 -*45 -*45 -*45 -*45 $.*1.% .*1. 0/ 1,h12 01 02 12 -*25 -*53h.*., -*33 -*4- .*., -,(1 -,(1 -,(1 -,(1 -/(1 *0- *0- *0- *0- *1/ 0(- ) *-2 ) 0(- 0(- 0(- *-2 *-2 *-2 1 ) *., ) 1 1 1 *., *., *., 4)-1 ) */-)*15 ) 4)-1 */-)*15 4)-1 */-)*15 -,)-1 */5)*15 /2 ) -*0. ) /2 /2 $04% 04 -*0. -*0. $-*45% -*45 .(. ) *,5 ) .(. /(. .(1 *,5 *-/ *-, .<Y]U^cY_^c!Y^!$!%!V_b!bUfUbdYfU!]_e^dY^W!`\QdU ;8.19 20 .*1. 12 .*., -/(1 *1/ 0(*-2 1 *., -,)-1 */5)*15 04 -*45 .(1 *-, ;.2 20 .*1. 14 .*.4 -/(1 *1/ 0(*-2 1 *., -,)-1 */5)*15 04 -*45 1 *., -cUU!`QWU!1- ;/. 20 .*1. 2, .*/2 -/(1 *1/ 0(*-2 1 *., -,)-1 */5)*15 04 -*45 1 *., ;0.. ;0/ 20 $44% 44 .*1. $/*02% /*02 22 40 .*2, /*/, -/(1 -2 *1/ *2/ 1(0 1(0 *.- *.- 1 2 *., *.0 -,)-1 */5)*15 -/)-3 *1-)*23 04 $24% 24 -*45 $.*24% .*24 1 3 *., *.4 ;4, 44 /*02 40 /*/, -2 *2/ 1(0 *.- 2 *.0 -/)-3 *1-)*23 24 .*24 4(5 */1 ;-.1 44 /*02 44 /*02 -2 *2/ 1(0 *.- 2 *.0 -/)-3 *1-)*23 24 .*24 4(5 */1 ;/-1 C cgYdSXUc C cgYdSXUc JYjU!J. JYjU!J/ 44 -.4 /*02 1*,0 44 -.2 /*02 0*52 -2 -5(/ *2/ *32 1(0 3 *.- *.4 2 3 *.0 *.4 -/)-3 *1-)*23 -1(1)., *2-)*35 24 -,0 .*24 0*,5 .3 --(0 -*,2 *01 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 111 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Emergency stop operators Components 1 2 3 Protection class IP 66 Individually packaged 3 part ordering 22.5 mm mounting D7P-MT44 1 Mushroom operators Description 30 mm Red operator 40 mm Red operator 60 mm Red operator 40 mm Red operator Operator head Coupling plate Contact Blocks Nonilluminated Plastic Cat. No. Nonilluminated Metal Price $ Cat. No. Illuminated Plastic Price $ Cat. No. 1) Price $ Illuminated Metal Cat. No. 1) Price $ D7P-MT34 67.00 D7M-MT34 74.50 - - D7P-MT44 70.50 D7M-MT44 75.00 D7P-LMT44 90.00 D7M-LMT44 95.50 D7P-MT64 79.00 D7M-MT64 82.50 D7P-LMT64 110.00 D7M-LMT64 118.00 2 D7P-MK44 113.00 D7M-MK44 124.00 - - D7ALP D7-X01 D7PX10 2 Coupling plates Description Plastic coupling plate Metal coupling plate Cat. No. D7-ALP D7-ALM Price $ 4.50 6.50 3 Contact blocks Description Operator Colour Contacts Normally closed contact block Red 1 N/C Normally closed contact block with Red 1 N/C spring clamp terminals Normally closed late break Brown N/C L.B. Normally closed early break Brown N/C E.B. Normally closed low voltage Blue 1 N/C (Quadfurcated gold contacts) Dual circuit 2 normally closed 2) Red 2 N/C "Auto break" safety contact block for Yellow 1 N/C emergency stop operators 2) safety Panel Mount Cat. No. D7-X01 D7-Q01 DIN/Base Mount Price $ Cat. No. 11.80 D7-BX01 16.80 D7-BQ01 D7-X01L D7-X01B D7-X01V 15.40 D7-BX01L 15.40 26.20 D7-BX01V D7-X02D 27.40 D7-X01S 32.00 - Price $ 13.20 18.00 16.80 27.40 2 + 3 Combined contact block and coupling plate Description 1 N/O contact block + coupling plate 1 N/C contact block + coupling plate 1 N/O and 1 N/C contact block + coupling plate Screw Cap Cat. No. D7PX10 D7PX01 D7PX11 Metal Screw Cap Price $ Cat. No. 16.80 D7MX10 16.80 D7MX01 28.60 D7MX11 Price $ 19.60 19.60 32.00 Price Schedule `A2' Notes: 1) For LED 2 lamps refer 2 - 32. 2) Dual circuit and `Auto Break' cannot be mounted in D7 low profile enclosures. For Accessories refer 2 - 33. Q-Pulse Id: TMS1594For further information please coAnctatcivteS:a1le8s/0143/0201N6HP NHP or visit nhp.com.au Page 112GSoT fno1t0i6nc8luded 2 - 5 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.4. POWER SUPPLIES, GPOs, PLUGS & SOCKETS CLIPSAL 2015 + 90B 15A Outlet + Shroud PROCONNECT 3PS6A3NE01 + 3PS6PC 63A 3Phase N&E Inlet + Cover WILCO WIBN27 27Pin Inlet Socket POWERBOX PB251-24CM-CC-T 24VDC 10A RTU Power Supply POWERBOX PBIH-2412J-CC Radio Power Supply Yuasa NP7.2-12 12V 7Ah Battery C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 113 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 114 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 115 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 116 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 117 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ISO Connect 3PS63 Series Maximum cable sizes: Cable outside diameter: Stripping length: IP rating: 50 mm2 strandard 35 mm2 flexible minimum 11 mm maximum 29 mm sheathing 60 mm insulation 30 mm socket outlet IP 66 outlet and inlet IP 66 Rated current:AC23 63 A/440 V AC (AS/NZ 3947-3 / IEC60947-3) 90 A maximum rated current (IEC60309-1) Housing material: polyamide 6 Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2p 3P+E+2p 3P+N+E+2p Voltage rating 220-240 V AC 380-440 V AC 380-440 V AC 220-240 V AC 380-440 V AC 380-440 V AC Socket outlet Cat. No. 3PS6D1NE01 3PS6D30E01 3PS6D3NE01 3PS63D1NE01P 1) 3PS63D30E01P 1) 3PS63D3NE01P 1) 3PS63 Series accessories Description Angled wall box 30° M40X1.5 (without cable gland) Handle maximum outside cable diameter 29 mm Handle with 50 mm thread with cable gland 30° incline sleeve Appliance inlet plug cap Note: 1) Includes 2 x 16 A pilot pins. Price Schedule `B4' Q-Pulse Id: TMS1594 GST not included Active: 18/04/2016 Appliance inlet Cat. No. 3PS6A1NE01 3PS6A30E01 3PS6A3NE01 3PS63A1NE01P 1) 3PS63A30E01P 1) 3PS63A3NE01P 1) Cat. No. 3PS6WAS 3PS6G 3PS6GFP 3PS6LB 3PS6PC 7 Page 118 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ISO Connect Dimensions (mm) Angled wall box with appliance inlet Series A B C d 3PS16 114 108 82 6 3PS32 134 128 91 7 3PS63 169 156 106 8 3PS125 223 204 155 9 3PS200 266 216 155 9 E E' F Kg Draw. No ISO 69 69 82 0.22 1 M20x1.5 78 88 101 0.36 1 M25x1.5 88 111 129 0.64 1 M40x1.5 139 154 170 - 2 M50x1.5 139 154 170 - 2 M63x1.5 1 2 Angled wall box with socket outlet Series A B C d 3PS16 141 126 82 6 3PS32 162 148 91 7 3PS63 202 180 106 8 3PS125 285 242 155 9 3PS200 308 248 155 9 3 E E' F Y Kg Draw. No ISO 69 69 82 196 0.31 3 M20x1.5 78 88 101 226 0.50 3 M25x1.5 88 111 129 273 0.88 3 M40x1.5 139 154 170 354 - 4 M50x1.5 139 154 170 375 - 4 M63x1.5 4 10 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 119 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ISO Connect Dimensions (mm) Socket outlet Series A B C D d E G H Y Z Kg 3PS16 71 92 72 57 4.5 48 47 13 107 120 0.24 3PS32 77 106 82 67 4.5 55 51 17 116 135 0.38 3PS63 89 122 99 80 5.5 66 59 25 132 163 0.64 3PS125 120 140 129 100 6 81 68 24 152 218 1.50 3PS200 122 179 144 120 7 98 94 35 190 230 2.40 Socket outlet with handle Series A B 3PS16 151 97 3PS32 172 107 3PS63 201 123 3PS125 261 145 3PS200 353 177 C Diam. Kg 72 18 0.30 82 22 0.47 99 29 0.79 129 45 1.90 144 58 3.15 Appliance inlet with handle Series A B 3PS16 100 71 3PS32 115 82 3PS63 133 96 3PS125 167 125 3PS200 260 143 C Diam. Kg 30.5 18 0.22 34 22 0.33 40 29 0.56 48 45 1.20 54 58 2.60 Q-Pulse Id: TMS1594 Active: 18/04/2016 11 Page 120 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ISO Connect - Cross reference chart 3PS Series NHP - 3PS16 3PS1D1NE01 3PS1D30E01 3PS1D3NE01 3PS16D1NE01P 3PS16D30E01P 3PS16D3NE01P NHP - 3PS32 3PS3D1NE01 3PS3D30E01 3PS3D3NE01 3PS32D1NE01P 3PS32D30E01P 3PS32D3NE01P NHP - 3PS63 3PS6D1NE01 3PS6D30E01 3PS6D3NE01 3PS63D1NE01P 3PS63D30E01P 3PS63D3NE01P NHP - 3PS125 3PS9D1NE01 3PS9D30E01 3PS9D3NE01 3PS9D1NE01P 3PS9D30E01P 3PS9D3NE01P NHP - 3PS200 3PS2D1NE01 3PS2D30E01 3PS2D3NE01 3PS2D1NE01P 3PS2D30E01P 3PS2D3NE01P Socket outlet Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Note: Not all units are interchangeable Marechal - DS 1 3114015 3114013 3114017 3114015972 3114013972 3114017972 Marechal - DS 3 3134015 3134013 3134017 3134015972 3134013972 3134017972 Marechal - DS 6 3164015 3164013 3164017 3164015972 3164013972 3164017972 Marechal - DS 9 3194015 3194013 3194017 3194015972 3194013172 3194017972 Marechal - DS 2 3924015 3924013 3924017 3924015972 3924013972 3924017972 Eaton - CH 1 CH1D1NE01 CH1D30E01 CH1D3NE01 CH1D1NE01P CH1D30E01P CH1D3NE01P Eaton - CH 3 CH3D1NE01 CH3D30E01 CH3D3NE01 CH3D1NE01P CH3D30E01P CH3D3NE01P Eaton - CH 6 CH6D1NE01 CH6D30E01 CH6D3NE01 CH6D1NE01P CH6D30E01P CH6D3NE01P Eaton - CH 9 CH9D1NE01 CH9D30E01 CH9D3NE01 CH9D1NE01P CH9D30E01P CH9D3NE01P Eaton - CH 2 CH2D1NE01 CH2D30E01 CH2D3NE01 CH2D1NE01P CH2D30E01P CH2D3NE01P 12 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 121 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ISO Connect - Cross reference chart 3PS Series NHP - 3PS16 3PS1A1NE01 3PS1A30E01 3PS1A3NE01 3PS16A1NE01P 3PS16A30E01P 3PS16A3NE01P NHP - 3PS32 3PS3A1NE01 3PS3A30E01 3PS3A3NE01 3PS32A1NE01P 3PS32A30E01P 3PS32A3NE01P NHP - 3PS63 3PS6A1NE01 3PS6A30E01 3PS6A3NE01 3PS63A1NE01P 3PS63A30E01P 3PS63A3NE01P NHP - 3PS125 3PS9A1NE01 3PS9A30E01 3PS9A3NE01 3PS9A1NE01P 3PS9A30E01P 3PS9A3NE01P NHP - 3PS200 3PS2A1NE01 3PS2A30E01 3PS2A3NE01 3PS2A1NE01P 3PS2A30E01P 3PS2A3NE01P Appliance inlet Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Contacts 1P+N+E 3P+E 3P+N+E 1P+N+E+2P 3P+E+2P 3P+N+E+2P Note: Not all units are interchangeable Marechal - DS 1 3118015 3118013 3118017 3118015972 3118013972 3118017972 Marechal - DS 3 3138015 3138013 3138017 3138015972 3138013972 3138017972 Marechal - DS 6 3168015 3168013 3168017 3168015972 3168013972 3168017972 Marechal - DS 9 3198015 3198013 3198017 3198015972 3198013172 3198017972 Marechal - DS 2 3928015 3928013 3928017 3928015972 3928013972 3928017972 Eaton - CH 1 CH1A1NE01 CH1A30E01 CH1A3NE01 CH1A1NE01P CH1A30E01P CH1A3NE01P Eaton - CH 3 CH3A1NE01 CH3A30E01 CH3A3NE01 CH3A1NE01P CH3A30E01P CH3A3NE01P Eaton - CH 6 CH6A1NE01 CH6A30E01 CH6A3NE01 CH6A1NE01P CH6A30E01P CH6A3NE01P Eaton - CH 9 CH9A1NE01 CH9A30E01 CH9A3NE01 CH9A1NE01P CH9A30E01P CH9A3NE01P Eaton - CH 2 CH2A1NE01 CH2A30E01 CH2A3NE01 CH2A1NE01P CH2A30E01P CH2A3NE01P Q-Pulse Id: TMS1594 Active: 18/04/2016 13 Page 122 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PB251A Series 2 2 0 - 3 3 0 WAT T S D C U P S Features · Ultra-low noise output · Independent battery charging · DC OK & battery charger OK alarms & LEDs · Battery disconnected alarm · Battery Low Voltage Disconnect - LVD · Battery fuse fail LED · Over-temperature protection · Analogue meters on standard model · Optional : Liquid Crystal Display · Optional : Network Enabled · Models available Q1 2010 Specifications INPUT Voltage: Line regulation: Current: Inrush current: Frequency: OUTPUT Voltage Current Load regulation Current limit type Current limit type Short circuit protection 190 to 264 vac, or 190 to 400VDC 0.2%typical 1.4A maximum 10A maximum 45 to 65 Hz See table See table 0.5%typical load cct Constant current batt. cct Constant current Indefinite, auto-resetting Over-voltage protection Ripple & noise ENVIRONMENTAL 17.5 to 20V latching (13.8Vdc output) 31.5 to 39V latching (27.6Vdc output) 100 MHz bandwidth 28mVp-p (13.8Vdc output) 55mVp-p (27.6Vdc output) Operating temperature 0 to 70oC ambient with derating, 5...90% relative humidity (non-condensing) Over-temperature protection Automatic & auto-resetting Cooling requirement Natural convection Efficiency 80% minimum STANDARDS & APPROVALS Safety Complies with AS/NZS 60950, class 1, NSW Office of Fair Trading Approval N20602 Selection Table EMC Isolation input - output input - ground output - ground Emissions comply with AS/NZS CISPR11, Group 1, Class B. Complies with ACA EMC Scheme, Safety & EMC Regulatory Compliance Marked 4242VDC for 1 minute 2121VDC for 1 minute 707VDC for 1 minute ALARMS & BATTERY FUNCTIONS DC OK Battery OK Green LED : ON=OK voltage free change over contacts (32V,1A) Alarms on loss of AC mains power or failure of off-line AC/DC converter / battery charger Green LED : ON=OK voltage free change over contacts (32V,1A) Alarms on battery low voltage, failure of battery fuse or battery disconnected. Alarm cancelled when fuse or battery replaced, or AC input restored Battery Low Voltage Disconnect Low voltage disconnect 10.5V for 12V (LVD) battery, 21V for 24V battery, adjustable 1.6 to 2.0V / cell all models Charger over-load protection Auto-resetting electronic circuit breaker Reverse polarity protection Internal battery fuse Battery to load voltage drop 0.2 to 0.35V typical model dependant OPTIONS Liquid Crystal Display Network Enabled 16 character 2 line display, add -LCD to rack mount model Internal network card in conjunction with PB251A becomes a network enabled device combining the benefits of SNMP V1, XML and an embedded webpage. Add -N to all model MECHANICAL Chassis mount case size 264 L x 172 W x 67 H mm CM case size with heatsink 264 L x 186 W x 67 H mm Rack mount size 232 D x 19" W x 2RU H Weight 1.9 kg Weight with heatsink 2.1 kg Weight (rack mounted version) 5.5 kg MODEL NUMBER PB251A-12CM PB251A-24CM PB251A-12CM-H PB251A-24CM-H PB251A-12RML PB251A-24RML PB251A-12B PB251A-24B VDC 13.8V 27.6V 3.8V 27.6V 13.8V 27.6V 13.8V 27.6V OUTPUT ILOAD 16A 11 20A 12A 20A 12A 20A 12A OUTPUT IBATT 2A 2A 2A 2A 4A 2A 20A 12A OUTPUT POWER 220W 300W 275W 330W 275W 330W 275W 330W MECHANICAL chassis mount chassis mount chassis mount / heatsink chassis mount / heatsink rack mount / screw terminals rack mount / screw terminals rack mount / Hirose connector rack mount / Hirose connector NOTE: Non standard battery charging current available on request. ie PB251-12CM-H-10 for Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 123 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PB251A Series 2 2 0 - 3 3 0 WAT T S D C U P S Features 254.0 · Ultra-low noise output P B 251A- **C M (-H) ME C HANIC AL OUT LINE · Independent battery charging HE AT S INK :P B 251A-**C M-H ONLY 130.0 80.0 · DC OK & battery charger OK alarms & LEDs · Battery disconnected alarm · Battery Low Voltage Disconnect - LVD · Battery fuse fail LED · Over-temperature protection · Analogue meters on standard model · Optional : Liquid Crystal Display NOTE S : 1. Mounting C entres: S uitable for M4 Hardware S tandard: 165 x 80 mm Alternate: 254 x 80 mm 2. M3 threaded holes on bottom of base. S tandard: 130 x 80 mm centres Alternate: 221 x 80 mm centres 3. AC Mains: 10A C lass 1 IE C 60320 power inlet 4. Output and B attery: 4W P luggable S crew T erminal B lock S uitable for up to 4 sq. mm wire. 5. Alarms: 6W P luggable S crew T erminal B lock S uitable for up to 1.5 sq. mm wire. 165.0 · Optional : Network Enabled · Models available Q1 2010 OUTPUT / BATTE R Y TE R MINATIONS OUTPUT BATTE R Y +- +- ALAR M TE R MINATIONS BAT OK DC OK 37.0 NC C NO NC C NO Alternate Mounting Specifications EMC Emissions comply with AS/NZS CISPR11, Group 1, Class B. Complies with ACA EMC 12.0 INPUT Scheme, Safety & EMC Regulatory Voltage: 80.0 80.0 S tandard Mounting 190 to 264 vac, or 190 to 400VDC Compliance Marked 67.0 232.00 190.00 62.0 P R E L I M I N A R Y 10.0 Line regulation: Current: Inrush current: Frequency: OUTPUT Voltage Current Load regulation Current limit type Current limit type Short circuit protection 221.0 0.2%typical 1.4A maximum 10A maximum 45 to 65 Hz See table See table 241.0 264.0 0.5%typical load cct Constant current batt. cct Constant current Indefinite, auto-resetting 76.20 88.10 Over-voltage protection Ripple & noise ENVIRONMENTAL Operating temperature POWER SUPPLY 17.5 to 20V latching (13.8Vdc output) 31.5 to 39V latching (27.6Vdc output) 100 MHz bandwidth 28mVp-p (13.8Vdc output) 55mVp-p (27.6Vdc output) 428.00 TOP VIE W 0 to 70oC ambient with derating, 5...90% relative humidity (non-condensing) Isolation input - output input - ground output - ground 4242V1D5C4.f0or 1 minute 2121VDC for 1 minute 707VDC for 1 minute OUTPUT +- BATTE R Y +- ALARMS & BATTERY FUNCTIONS BAT OK DC OK NC C NO NC C NO DC OK Green LED : ON=OK voltage free change over BATTE R Y OK contacts (32V,1A) Alarms on loss of AC mains DC OK power or failure of off-line AC/DC converter / battery1c7h2a.0rger Battery OK 186.0G(PreBe2n51LEAD- **:COMN-=HOOKnlvyo) ltage free change over contacts (32V,1A) Alarms on battery low voltage, failure of battery fuse or battery P B 251A-**RML & -12BdMiscEonCnHecAteNd.ICAAlaLrmOcUanTcLelIlNedEwhen fuse or battery replaced, or AC input restored Battery Low Voltage Disconnect Low voltage disconnect 10.5V for 12V (LVD) battery, 21V for 24V battery, adjustable NOTE S : 1.6 to 2.0V / cell all models 1. 2R U x 19" rack enclosure per IE C 297 Charger over-load p2r. oMteoucnttiiongnslots arAe usutiota-brleesfoertMti6nghaerdlweacrter.onic circuit breaker 3. Input connector is a 10A C lass 1 IE C 60320 inlet. Reverse polarity pro4t. e2cmtieotner IE C mainIns tceorrdnwailthbAautstterarliyanfuplsueg is supplied with unit. 5. P B 251A-12B alarm terminal is DB 25 female. Battery to load volt6a. gPeB2d5r1oAp-12B out0pu.2t atnod b0a.t3te5ryVcotnynpeicctoarlismHoirodseelpdn.eHpSe2n8dRa-4nAt. Mating connector is Hirose pn. HS 28P -4A (not supplied). OPTIONS 7. P B 251A-**R ML alarm and output terminals are M3.5 screws suitable for ring or fork lugs up to 8 mm wide. Liquid Crystal Display 16 character 2 line display, add -LCD to rack mount model Network Enabled Internal network card in conjunction with PB251A-**R MPL BAL2A5R M1AANbD eOcUoTPmUTesTEaR MnINeAtLwS ork enabled device Over-temperature proteDCctOiKon BATT V A Automatic & auto-resetting - A + combining the benefits of SNMP V1, XML and BATTE R Y OK LOAD an embedded webpage. Add -N to all model Cooling requirement NaturaVlOcLoTAnGvE ection LOAD CUR R E NT BATTE R Y CUR R E NT NO C NC NO C NC Efficiency 80% minimum448635..0500 MECHANICAL DC OK BATT OK FR ONT VIE W STANDARDS & APPROVALS Safety POWERSUPPLY Complies with AS/NZS 60950, class 1, Chassis mount case size CM case size with heatsink 264 L x 172 W x 67 H mm + 26+L4O - ALD x 1- 8B6A-TWTE +R Yx 67 H mm 76.20 88.10 MAINS ON FAULT NSW Office of Fair Trading Approval N20602 Rack mount size 232 D x 19" W x 2RU H Selection Table 82.00 MODEL NUMBER PB251A-12CM VDC 13.8V 465.50 483.00 FR ONT VIE W OUTPUT ILOAD 16A OUTPUT IBATT 2A Weight Weight with heatsink 1.9 kg P B 251A-12B OUT P UT & B AT T E R Y C ONNE C T OR 2.1 kg Weight (rack mounted version) 5.5 kg 21 34 OUTPUT POWER MECHANICAL 220W chassis mount PIN1: + OUTPUT PIN2: - OUTPUT PIN3: + BATTE R Y PINN4: O- BTAETT:ENR Yon standard battery charging current available on request. ie PB251-12CM-H-10 for 82.00 PB251A-24CM PB251A-12CM-H PB251A-24CM-H PB251A-12RML 27.6V 3.8V 27.6V 21 13.8V3 4 R E AR 1VI1E W (P B 251A-**R ML) 2A 20A 2A 12A 2A 20A 4A 300W 275W 330W 275W chassis mount P B 251A-12B ALAR M C ONNE C T OR chassis mount / heatsink chassis mount / heatsink PIN 1: C OMMON PIN 6: DC OK (NC) rack mount / screw terminalsPIN 15: BATTE R Y OK (NO) PB251A-24RML 27.6V 12A 2A 330W rack mount / screw terminals PB251A-12B PB251A-24B 13.8V 27.6V 20A 20A R E AR VIE W (P B 251A-12B ) 12A 12A 275W 330W rack mount / Hirose connector rack mount / Hirose connector Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 124 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.5. SURGE PROTECTION & FUSES CRITEC TDS-1100-2SR-277 Surge Diverter CRITEC DAR-275V Surge Diverter Alarm Relay CRITEC TDF-10A-240V Surge Reduction Filter RTU NHP NC63FW + NTIS63 63A Fuse Cartridge & 63A Fuse Holder NHP NC32FW + NNIT6 6A Fuse Cartridge & 32A Fuse Holder RF Industries IS-50NX-C2 Radio Coax Surge Protection Unit C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 125 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Refer Catalogue NF BS fuse holders CIRSCUFUPUIETSREPISROORPTRSEOHCVOTIDRIOETN Compact fuse holders (Bolt-in) New compact size Front (FW) or stud/front (SFW) versions Smaller dimensions Saves panel space S$A$V$EWPFIAUTNHSEENLHESOWPLACDCOEERMSSPAAVCET UP TO 30% SMALLER Rating (A) Fuse link to suit Front wired bolt in 32 NNIT 63 NTIA NTIS 100 NOS NTIA NTIS 200 NTIA 1) NTIS 1) NTFP NOS 1) NTCP Cat. No. NC32FW NC63FW NC100FW NC200FW Dimensions (mm) HW NC32_ 87 27 NC63_ 109 31 NC100_ 118 35 NC200_ 154 54 Suggested Max. D cable size 50 10 mm2 62 25 mm2 72 50 mm2 108 95 mm2 Back stud/front wired bolt in 32 NNIT NC32SFW 63 NTIA NTIS NC63SFW 100 NOS NTIA NTIS NC100SFW 200 NTIA 1) NTIS 1) NC200SFW NTFP NOS 1) NTCP Note: 1) Fuses can be fitted using adaptor 100M FLK. Standard fuse holders (Bolt-in) Ratings from 20 to 200 A Front (FW) or stud/front (SFW) versions Complies with BS88 OLD STYLE N20FW Dimensions (mm) HW N20_ 87 27 N32_ 109 31 N63_ 118 35 N100_ 154 54 N200_ 193 70 Suggested Max. D cable size 50 10 mm2 62 10 mm2 72 50 mm2 108 70 mm2 149 150 mm2 Rating (A) Fuse link to suit Front wired bolt in 20 NNIT 32 NTIA 63 NTIA NTIS 100 NTIA 1) NTIS 1) NOS 1) NTCP 200 NTBC NTC NTF Back stud/front wired bolt in 20 NNIT 32 NTIA 63 NTIA NTIS 100 NTIA 1) NTIS 1) NOS 1) NTCP 200 NTBC NTC NTF Cat. No. N20FW N32FW N63FW N100FW N200FW N20SFW N32SFW N63SFW N100SFW N200SFW Clip-in fuse holders - DIN rail mount Fast, reliable fitting and removal of fuse links Rating (A) Fuse link to suit Front wired clip-in Black 20 NSS 32 NSS 63 NES Front wired Clip-in White NV20FW NV32FW NV63FW 32 NNS 63 NES Q-Pulse Id: TMS1594 Active: 18/04/2016 Cat. No. NV20FW NV32FW NV63FW NV32FWW NV63FWW Page 126 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fuse equivalent chart This chart is designed to help choose the correct fuse to fit a particular switch-fuse (or vice versa) and to help choose the correct replacement fuse. Some data is from other manufacturers publications and as such cannot be guaranteed by NHP. Beware that some motor start fuses are in a larger body size than a normal fuse. It is wise to consult the fuse manufacturer's data to determine their particular fuse sizes (i.e. A2-C3). Fuse manufacturer's part numbers - Australian/British standard BS Ref. Amps EATON/ MEM Holec Alstom GEC Bussmann PDL Siemens F1 2...32 F2 20...63 A1 2...32 A2 2...32 A3 35...63 Hybrid (A3) 80...100 Hybrid (A3) 125...160 A4 80...100 Hybrid (A4) 125...200 - 2...32/40...63 B1 2...32/40...63 B1 80...100 B2 125...200 B3 250...315 - 250...315 B4 355...400 Hybrid (B4) 450...630 C1 355...400 C2 450...630 - 450...630 C3 710...800 - 710...800 D1 1000...1250 DIN pattern NNS NES NNIT NTIA NTIS NOS NTSL00 NTCP NTFP 1) NTB NTBC NTC NTF NTKF NTKM NTMF NTSL3 NTM NTTM NTT NTLM NTLT NTXU SN2 NS SP MES SA2 NIT SB3 TIA SB4 TIS SO - SD5 TCP SD6 TFP SE3/SE4 TB SF3/SF4 TBC SF5 TC SF6 TF SF7 TKF SG7 TKM SF8 TMF SH8 TM SH9 TTM SY9 TT SH10 TLM SY10 TLT SJ11 TXU NS NSD N20C 3NW NS ES ESD N63E 3NW ES NIT NITD N20B 3NW NIT TIA AAO N32B 3NW TIA TIS BAO N63B 3NW TIS OS OSD NOSD 3NW OS TCP CEO N100B 3NW TCP TFP DEO N200B 3NW TFP TB AC/BC N_TB 3NW TB TBC AD/BD N63B_ 3NW TBC TC CD N100B_C 3NW TC TF DD N200B_C 3NW TF TKF ED N315B_C 3NW TKF TKM EFS N315B_C 3NW TKM TMF ED N400B_C 3NW TMF TM EF N404B_C 3NW TM TTM FF N504B_C 3NW TTM TT FG N630B_C 3NW TT TLM GF N804B_C 3NW TLM TLT GG B804B_C 3NW TLT TXU GH N_U44 3NW TXU 00 6...160 1 25...250 2 80...400 3 315...800 Fuse holders N00 NH00 - N1 NH01 - N2 NH02 - N3 NH03 - NHG-00 NH00G - NHG-1 NH1G - NHG-2 NH2G - NHG-3 NH3G - 3NA5 3NA4 144 3NA4 260 3NA1 Clip-in 20A 32A Front wired 20A 32A 63A 100A 200A Stud/ 20A front wired 32A 11 63A 100A 200A NV20FW NV32FW N20FW NC32FW NC63FW NC100FW NC200FW N20SFW NC32SFW NC63SFW NC100SFW NC200SFW V20FF V32FF 20MFB 32MFB 63MFB 100MFB 200MFB 20MFD 32MFD 63MFD 100MFD 200MFD 200846 LCF63FCFC LCF32FCBC LCF63FCBC - SC20H SC32H RSM20H RSM32H RSM63H RSM100H RSM200H RSM20PH RSM32PH RSM63PH RSM100PH RSM200PH 32NNSF - FC20FW NC32FW FB20FW FB32FW FB63FW FB100FW FB200FW FB20SF FB32SF FB63SF FB100SF FB200SF 3NW 32NNSF 3NWCM20FC 3NW CM32F 3NW CM63F 3NW CM100F 3NW 200DF - Note: 1) This hybrid type fuse is actually an A4 size fuse, but as it is over 100 amps it cannot be called an A4 fuse to AS 2005. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 127 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fuse-link terminology NHP Compact fuses HRC High rupturing capacity (HRC) or High breaking capacity denotes the ability of a fuse-link to interrupt extremely high fault currents, usually up to 80kA. Current limiting fuse-link A fuse-link that limits the circuit current during it's operation to a value much lower than the peak value of the prospective current. In practice, the terms HRC and current limiting are synonymous. Rated breaking capacity The highest value of fault current that a fuse-link has been tested to interrupt eg. 80kA. Rated voltage The maximum system voltage that the fuse-link is designed to interrupt. Rated voltages may be in AC, DC, or both. Current rating The value of current that a fuse-link will carry continuously without deterioration under specified conditions. Minimum fusing current The minimum value of current that will cause melting of the fuse element. Power dissipation The power released in a fuse-link carrying rated current under a specified condition, usually expressed in watts. Time current characteristics (refer table 1) A curve detailing the pre-arcing or operating time as a function of prospective current. Let through characteristics (I2t) (refer table 2) A curve or chart showing values `pre-arcing' and `operating' let through energies as a function of prospective current, I2t is proportional to energy in Amp2 seconds. Cut off characteristics (refer table 3) A curve detailing the cut off current as a function of prospective current. Cut off current being the maximum instantaneous value of current let through by the fuse-link during operation. Discrimination (refer tables 4 and 5) Discrimination is the ability of fuse-links to operate selectively and to disconnect only the parts of the circuit that are subject to faults. Discrimination can be checked by ensuring that the time current characteristics, including their tolerances, do not overlap at any point and that the total let through energy (I2t) of the downstream (or minor) fuse-link does not exceed the pre-arcing energy (I2t) of the upstream (or major) fuse-link at the applied system voltage. Discrimination is normally achieved with the ratio of 1.6 between upstream and downstream fuses. Table 1 Typical time current curves Table 2 I2t Fuse rating Operating and pre-arcing I2t values Table 3 Table 4 Cut off characteristics Table 5 Discrimination achieved Q-Pulse Id: TMS1594 Discrimination NOT achieved Active: 18/04/2016 Page 128 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual I2t characteristics BS fuses I2t data I2t characteristics Rating (amperes) 2 4 6 10 16 20 20M25 20M32 25 32 35 32M40 32M50 32M63 40 50 63 80 & 63M80 100 & 63M100 125 & 100M125 160 & 100M160 200 & 100M200 250 & 200M250 315 & 200M315 355 400 & 315M400 450 500 560 630 710 800 1000 1250 I2t pre-arcing 2 10 34 188 92 155 574 574 826 826 1200 2482 3305 5875 2482 3305 5875 7800 14000 30000 58500 120000 210000 270000 365000 480000 755000 1100000 1200000 1550000 1903565 3820349 7000000 12000000 I2t total @ 240 volts 2 15 52 289 211 355 1084 1561 1084 1561 2400 4416 5879 10452 4416 5879 10452 15500 28000 51000 99000 205000 360000 460000 620000 820000 1300000 1850000 2400000 3100000 2992861 6006505 1500000 20500000 I2t total @ 415 volts 4 21 74 408 412 690 1809 2605 1809 2605 4100 7019 9345 16612 7019 9345 16612 26000 46000 75500 145000 300000 530000 680000 915000 1200000 1900000 2700000 4000000 5150000 4306813 8643534 16000000 30000000 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 129 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fuse curves BS fuse curves NHP Compact BS fuses from 20 to 250 amps CUT-OFF CURRENT PEAK kA 8 6 630 560 500 4 450 400 355 315 250 200 2 160 125 100 10 80 8 63 6 50 40 4 32 2 20 1 8 6 4 2 0.1 0.1 2 4 6 81 2 4 6 8 10 2 4 68 PROSPECTIVE CURRENT kA (R.M.S. SYMMETRICAL) Q-Pulse Id: TMS1594 Active: 18/04/2016 NHP Compact BS fuses cut-off current data from 20 to 630 amps Page 130 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fuse curves BS fuse curves NHP Compact BS fuses from 80A to 630 amps (including motor rated fuses) TIME (SECONDS) 10000 6 4 2 1000 6 4 2 100 6 4 2 10 6 4 2 1 6 4 2 0.1 6 4 2 0.01 100 2 FUSE RATING (A) 80 & 63M80 100 & 63M100 100SOM125 125 & 100M125 160 & 100M160 200 & 100M200 250 & 200M250 315 & 200M315 355 400 & 315M400 450 500 560 630 4 6 8 1000 2 4 6 8 10000 2 CURRENT (AMPERES) 4 68 NHP Compact BS fuses cut-off current data from 80 to 630 amps Q-Pulse Id: TMS1594 CUT-OFF CURRENT PEAK kA 8 6 630 560 500 450 4 400 355 315 250 200 2 160 125 100 10 80 8 6 4 2 1 8 6 4 2 0.1 0.1 2 4 6 81 2 4 6 8 10 2 4 68 PROSPECTIVE CURRENT kA (R.M.S. SYMMETRICAL) Active: 18/04/2016 Page 131 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DIN fuses curves and data DIN fuses curves and data NHP Compact DIN fuses Pre-arcing and Total I2t energies, from 6 to 630 amps NHP Compact DIN fuses cut-off current data from 6 to 500 amps NHP Compact DIN fuses Fuse curves from 6 to 630 amps Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 132 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Detailed Specifications for ERICO's TDS-DINLINE SURGE DIVERTER TDS180-4S Applications Features Lightning transients and surges are a major cause of expensive electronic equip- · Robust against abnormal over-voltage ment failure and business disruption. Damage may result in loss of computers, data and communications, loss of revenue, and loss of profits. The new TDSDINLINE family of surge diverters and filters offer economical and reliable · UL1449 Edition 2 compliant protection from power transients in even the most strenuous applications. · Single phase primary protection for Transient Discriminating Technology (TDS) introduces the first quantum leap in transient suppression technology for mains powered equipment. It offers a new medium exposure sites or secondary protection applications level of safety and reliability, yet retains optimum protection levels critical for electronic equipment. TDS is an active frequency based device that discriminates between the slower mains voltages and the higher speed transients. When · Single mode protection, configurable to Ph-N, Ph-E or N-E protection transient frequencies are detected the patented TDS "Quick-Switch" technology "switches in" robust protection devices to limit the transient to safe levels. The frequency discrimination circuit controlling the TDS "Quick-Switch" ensures that · 35mm DIN rail mount, DIN 43 880 profile matches common MCBs the device is virtually immune to the effects of the 50/60Hz sustained overvoltages, allowing fault voltages of up to 480Vrms without degradation, and · 72mm width compact design fits into providing over-voltage robustness in excess of the demanding new and emerging most switch and distribution boards standards. TDS technology is essential for any site where abnormal over-voltages can occur or where the possible catastrophic failure of traditional technologies due to over- · Electronic status indicator ideal for poorly illuminated locations voltage events can not be tolerated. · Long Service life The TDS180-4S unit provides this technology in a single mode shunt-only, 72mm width module. Its unique design allows it to be configured for Ph-N or Ph-E or · Optional retrofittable TDS Alarm N-E applications. Relay for remote alarms Rated to a surge capacity of 80kA (8/20µs), internally 160kA of surge material is provided for additional robustness and to provide long service life. The unit is designed for sites with a medium risk of transients or for secondary protection applications. For the protection of high exposure sites or critical equipment higher surge rated TDS DINLINE units, or TDS MOVTECTM should be installed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 133 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TDS-DINLINE SURGE DIVERTER TDS180-4S SPECIFICATIONS 100 Operation: Nominal input voltage Input frequency Max. permissible abnormal over-voltage Power systems Earth leakage current Protection: Modes Let through voltage @ 3kA 8/20µs Let through voltage @ 20kA 8/20µs Surge rating 8/20µs Surge rating 10/350µs Energy rating MultipulseTM capability Aggregate surge material Alarms and Indicators: Protection status indication Alarm contacts Physicals: Environmental rating Operating conditions Enclosure style Dimensions (W x D x H) Weight Encapsulation Enclosure material Surface finish Wiring terminals Warranty Test standards: Approvals 10 Surge rated to meet 1 0.1 1 20 1000 Number of Impulses 10000 220 -277 Vrms 50/60 Hz 480 Vrms TN-C, TN-S, TN-C-S (MEN), TT <2mA Ph-N, Ph-E or N-E <720V <910V 80kA 16kA 3840J Yes 160kA 8/20µs Two, electronic. On = OK User configurable, with optional TDS-AR IP20 -35 to +55°C, 0-90% humidity DIN 43880 72 x 88 x 70mm 350g (approx.) Shockguard Flame Retardent UL94V-0 Spark eroded finish Accepts up to 6mm² 5 years UL1449 Edition 2 AS 3260, IEC 950 Certificate of suitability, Electricity Regulator ANSI/IEEE C62.41-1991 Cat A, Cat B, Cat C. ANSI/IEEE C62.45-1987 Life cycle testing. AS/NZS 1768-1991 Cat A, Cat.B, Cat C. BS 6651:1992 Cat A, Cat B. IEC801-5 Installation Class 5. IEC 61643-1 Note: Other operating voltages and frequencies are available on application. For specifications on other DINLINE products, refer to relevant Specifications Sheet. Exceeding nominal operating voltage while transient events occur may affect product life. TDS, MULTIPULSE, PROLINE, CRITEC, MOVTEC, DINLINE and SURGE REDUCTION FILTER are trademarks of ERICO. Due to a policy of continual product development, specifications are subject to change without notice. © Copyright 1998 Model Number TDS180-4S-277 Description TDS 277V 80KA SURGE SUPPRESSOR Impulse Magnitude (kA 8/20µs) TDS180.PM5 ISSUE 2.0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 134 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DINLINE ALARM RELAY (DAR) INSTALLATION INSTRUCTIONS MODEL NUMBER DAR 275V 1. PREPARATION DANGER: Electrical shock or burn hazard. Installation of this device should only be made by qualified personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or severe burns. Before making any connections be sure that power has been removed from all associated wiring, electrical panels, and other electrical equipment. CAUTION NOTES: 1. The installation of this device should follow all applicable electrical codes, such as the National Electrical Code. 2. Check to make sure line voltage does not exceed DAR275V voltage ratings. 3. Follow all instructions to ensure correct and safe operation. 4. Do not attempt to open or tamper with the DAR in any way as this may compromise performance and will void warranty. No user serviceable parts are contained. 2. INTRODUCTION Selected DSD, TDS & TDF DINLINE Surge Protection Devices include status monitoring circuits which provide visual status display of device capacity. They may also provide a low voltage opto-coupler alarm output circuit that can be connect to the DAR to provide potential free (Form C) change-over contacts. The DAR alarm contacts may be used to provide output to external alarm systems or remote monitoring circuits. One DAR can be used per DSD/TDS/TDF opto-coupler alarm or up to 16 DSD opto-coupler alarms can be connected in series to the one DAR to provide a common output. It is recommended that the DAR be powered from the same power circuit that feeds the device(s) being monitored, however the DAR can be powered from other circuits. This allows for example, one DAR unit to be connected to separate SPDs that are protecting a three phase circuit. Note. Depending upon the usage of the DAR output contacts, failure of power to the DAR may be interpreted as a failure of one or more of the SPDs being monitored. Visual inspection of the DAR and SPDs status displays would determine this. 3. MOUNTING The DAR is designed to clip to 35mm (top hat) DIN rails (standard EN50022). Unless otherwise mechanically restrained, use horizontal DIN rails with the DAR module spring clips to the bottom and the label text the correct way up. NOTE: The DAR must be installed in an enclosure or panel that: · prevents the DAR temperature from exceeding 131°F (55°C) · provides adequate electrical and safety protection · prevents the ingress of moisture and water · allows DAR status indicators to be inspected 4. ELECTRICAL CONNECTION The interconnecting wiring should: · be of size #10 to #14 AWG (2.5mm² to 6mm²) solid or stranded conductor. · The wire insulation should be stripped back 5/16" (8mm). · NOTE: Do not use greater than 9inlbs (1Nm) of torque when tightening the terminals. CONNECTION TO TELECOMMUNICATIONS NETWORKS The DAR is approved for use in Australia where the alarm contacts may be connected to private lines or building cabling associated with the telecommunications network. NO direct connection to the public switched network should be made. www.erico.com Q-Pulse Id: TMS1594 Page 1 of 2 Active: 18/04/2016 Page 135 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DINLINE ALARM RELAY INSTALLATION INSTRUCTIONS 5. INTERCONNECTION When connecting the DAR to a single opto-coupler output the + terminal of the SPD should connect to the + terminal on the DAR. The terminal should connect to the -- terminal. To transient protected equipment PhN E DSD 2S/2T Ph N DAR Voltage free contacts Opto-coupler output To remote alarm circuit +/- terminal connections are polarity sensitive. Do not reverse. When connecting the DAR to multiple opto-couplers the optocouplers should be connected in series with + terminal of one connected to the terminal of the next. The DAR + terminal should connect to + SPD terminal at one end of the series connection and the DAR terminal connect to the SPD terminal at the other end of the series connection. Ph N E PhN E Ph N DAR Voltage free contacts Up to 16 connections per DAR module DSD 2S/2T +/- terminal connections are polarity sensitive. Do not reverse. 5. STATUS INDICATION STATUS DISPLAY Protection Operational Protection Alarm Fault Mode Normal Normal Normal 8 8 8 Fault 4 Fault 4 Fault 4 6 6 6 Normal operation DSD in alarm mode or power Power to DAR removed to DSD has been removed Protection status unknown EXPLANATION Normal (green) indicator ON Normal (green) indicator OFF Normal (green) indicatorOFF Red indicator OFF Red indicator ON Red indicator OFF Relay is energised Relay is de-energised Relay is de-energised Power is supplied Power is supplied Power is OFF 6. FUSING AND ISOLATION Overcurrent protection must be installed in the upstream circuit of the power supply to the DAR to provide protection to the unit itself and the wiring in case of fault conditions. The fuse rating should be based on the wiring size used to connect to the DAR Ph & N terminals. Australian regulations AS3000-1991, Table B2 specifies the following upstream protection for single phase circuits, unenclosed in air. Cable Size 1.5mm2 2.5mm2 4mm2 6mm2 HRC Fuse or 16A 20A 25A 32A CB Rewirable Fuse 12A 16A 20A 25A Where overcurrent protection of the appropriate rating or smaller is already fitted in the upstream circuit, overcurrent protection at the DAR will not be required 6. MAINTENANCE & TESTING Before removing a DAR unit from service, ensure that the power has been removed. Maintenance, testing and replacement should only be undertaken by qualified personnel. Testing of a DAR unit which is connected to a fully functional DSD unit can be accomplished by removing power to the DSD only. The DAR Status indication and output contacts should alter from the Normal to Fault condition. Testing of the DAR unit alone may be accomplished by disconnecting the + / -connections to the unit. When power is applied the DAR "Fault" Status Indicator should be illuminated. By connecting the + / - terminals together, the "Normal" Status Indicator should be illuminated. The output contacts should alter to the appropriate state. 7. USE OF OTHER INTERFACES Only DAR units are recommended for the interfacing of equipment to the DSD, TDS & TDF opto-coupler alarm output circuit(s). The direct connection of other equipment to these opto-coupler alarm outputs may not provide sufficient isolation or exceed the opto-coupler specifications. This may damage the SPD and/or the connected equipment. Warranty may be voided under such circumstances. NOTE: In connecting to the SPD opto-coupler alarm output(s), do not reverse the +/- connections as damage may o c c u r Btuongdelet/thweisrt(KaNLeps4p-asra6cmtimcthsora)l Sfyuploer feu s i n g d e t asi lescLNE t i o n 8 www.erico.com Q-Pulse Id: TMS1594 Page 2 of 2 Active: 18/04/2016 Doc: HBCR1681, Rev: 1 Page 136 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Detailed specifications for ERICO's TRANSIENT DISCRIMINATING FILTER, TDF-10A SERIES Applications Features Lightning transients and surges are a major cause of expensive electronic · Compact design fits into most distribution equipment failure and business disruption. Damage may result in loss of boards and motor control centres computers, data commmunications, loss of revenue, and loss of profits. The new Transient Discriminating FilterTM family of TVSS devices offer · High efficiency filtering - ideal for the economical and reliable protection from power transients with the conven- protection of switched mode power ience of easy installation on 35mm DIN rail mountings. supplies from large dv/dt and di/dt transients · Three modes of protection L-N, L-G, N-G The TDF series has been specifically designed for process control applica- tions to protect the switched mode power supply units on devices such as · 35mm DIN rail mount - DIN 43 880 PLC controllers, SCADA systems and motor controllers. Units are avail- profile matches common MCB's able for 3A, 10A and 20A loads and in a range of clamping voltages including 30V, 150V, 275V. The range is intended for use in conjunction · LED indication and opto-isolated output with ERICO's Universal Transient Barrier UTB's to provide a coordinated for remote status monitoring approach to protection of both the power and data control circuits. · Transient Discriminating Technology ensures safe operation during abnormal The TDF is a series connected single phase surge filter providing an aggregate surge capacity of 50kA (8/20µs) - 20kA L-N & L-G and 10kA N-G. The space efficient low pass filter, provides some 65dB of attenua- over-voltage events · UL1449 Edition 2 recognized tion to voltage transients. Not only does this reduce the residual let through voltage, but it helps further reduce the steep rates of rise of voltage and current providing superior protection for sensitive electronic equipment. · Large 50kA surge capacity provides a high level of protection and long operational life · 5 year limited warranty Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 137 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PROCESS CONTROL TVSS PROTECTION SPECIFICATIONS Operation: Models available Nominal line voltage Max Continuous Operating Voltage MCOV Max Load Current Input frequency Earth leakage current Protection: Max aggregate surge rating Protection modes Max surge current/mode L-N L-G N-G SPD circuit description Filter: Inductor Capacitor type Attenuation @100kHz L-N Performance: UL1449 SVR L-N ANSI/IEEE C62.41 Cat B3 - 500A ringwave Cat C1 - 3kA, 8/20µs Alarms and Indicators: Protection status indication Physical Data: Dimensions(W x D x H) Weight Enclosure material Connection means Wire size Mounting method Enclosure style Environmental rating Opearting temperature Humidity Surface finish Warranty Test standards: Approvals Surge rated to meet TDF-10A-120V 120VAC/125VDC 170Vrms 10A 50/60Hz <0.2mA TDF-10A-240V 240VAC 340Vrms 50kA 8/20µs L-N, L-G and N-G 20kA 8/20µs 20kA 8/20µs 10kA 8/20µs Series low pass LC filter Transient Discriminating Technology Thermal fusing Ferrite cored X & Y grade interference suppression polypropylene film 65dB 500V 22V 262V 700V 28V 481V Red LED, On = OK. Opto-isolated output 144mm x 88mm x x70mm 750g (approx) Flame Retardant UL94V-O Screw terminals 1.0mm2 - 6.0mm2 DIN T35 Rail DIN 43880 IP20 -30oC to +55oC 0-90% Spark eroded finish 5 years UL1449 Ed 2, UL1283 recognised, CSA22.2 C-Tick AS3260 ANSI/IEEE C62.41 Cat A, Cat B, Cat C AS/NZS 1768-1991 Cat A, B, C Part Number Description TDF-10A-120V 120V 1 phase, 50kA 8/20µs, 10A series TVSS protector TDF-10A-240V 240V 1 phase, 50kA 8/20µs, 10A series TVSS protector tdf10a.pm5 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 138 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.6. RTU & RADIO KINGFISHER BA-6 RTU Backplane (6 Slot) KINGFISHER PS-22 Power Supply KINGFISHER CP-12 Processor Module KINGFISHER DI-5 16 Channel Digital Input Module KINGFISHER DO-1 8 Channel Digital Output Module KINGFISHER IO-3 Mixed I/O Module RADTEL MIRI AD2006 - Radio C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 139 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Kingfisher PLUS+ Modular RTU Hardware Reference Manual 7.12 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 140 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Document Information Document Control Copyright Intellectual Property Licence Copyright CSE-Semaphore (Australia) Pty Ltd. ABN 35 006 805 910 www.cse-semaphore.com/mykingfisher, info.kingfisher@cse-semaphore.com CSE-Semaphore asserts ownership of the intellectual property contained herein and claims copyright and authorship. CSE-Semaphore has and retains all rights of ownership and use of the material herein in its on-going business. This document is provided to the intended recipient(s) under a non-exclusive licence. This licence permits Fair Use of the document for operational requirements, without payment of further royalty or licence fee. Fair Use includes making copies of the document for operational, backup and archive purposes. Fair Use includes distributing copies of the document to other entities for the purposes of their performing related works for the intended recipient(s). Fair Use does not include creating, selling or distributing copies of the document for other purposes. All copies must retain this statement of Intellectual Property and Copyright. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 141 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Revision History Version Number 6.11 7.0 7.1 7.12 Date Summary 2/10/2010 28/10/2011 Added PSU-4 power supply (higher power version of the PSU-3). PS-xx temperature sensor wires are now red with a black stripe. Added PS-22, IO-5 and MC-31 modules Update: adaptor ADP-22B (include Wavecom extend) Update: temp sensor is white / white with a black strip Update: power requirements of T option board Update: power calculation tables Update: Comms option boards selection table Update: safety warnings Update: Lenses for PS-12 and PS-22 Update: Lens for MC-31 Proposed `Linked Backplane Example' chapter removed Update: Various errors found in first release Added CP-12 power consumption Added CP-30/MC-30/MC-31 to compatibility chapter Corrected compatibility chapter and added CP-12 Corrected various spelling and grammatical mistakes. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 142 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Contents 1. INTRODUCTION ................................................................................. 7 2. BACKPLANES ................................................................................... 8 2.1. MODULE DIMENSIONS...........................................................................................................................9 2.2. BA-4-PLUS: 4 SLOT BACKPLANE ...........................................................................................................10 2.3. BA-4-PLUS EXTERNAL CONNECTIONS ....................................................................................................11 2.4. BA-40-PLUS: 4 SLOT BACKPLANE .........................................................................................................12 2.5. BA-40-PLUS EXTERNAL CONNECTIONS...................................................................................................13 2.6. BA-6-PLUS: 6 SLOT BACKPLANE ...........................................................................................................14 2.7. BA-6-PLUS EXTERNAL CONNECTIONS ....................................................................................................15 2.8. BA-12-PLUS: 12 SLOT BACKPLANE .......................................................................................................16 2.9. BA-12-PLUS EXTERNAL CONNECTIONS...................................................................................................17 2.10. LINKING BACKPLANES ..........................................................................................................................18 2.11. RACK SLOT NUMBERING ......................................................................................................................19 2.12. BACKPLANE DIP SWITCH SETTINGS .........................................................................................................20 3. POWER SUPPLY MODULES ............................................................... 21 3.1. PS-12 POWER SUPPLY MODULE ............................................................................................................22 3.2. PS-22 POWER SUPPLY MODULE............................................................................................................31 3.3. PSU-3: 40 WATT AC POWER SUPPLY UNIT .............................................................................................39 3.4. PSU-4: 40 WATT AC POWER SUPPLY UNIT .............................................................................................42 3.5. CALCULATING POWER REQUIREMENTS ....................................................................................................45 3.6. 5 V RAIL OVERLOAD CHECK ..................................................................................................................47 3.7. TOTAL POWER LOAD ...........................................................................................................................49 3.8. BATTERY BACKUP ...............................................................................................................................50 4. PROCESSOR MODULES.................................................................... 51 4.1. PC-1: POWER & PROCESSOR MODULE....................................................................................................53 4.2. CP-12 PROCESSOR MODULE ................................................................................................................59 4.3. CP-30: HIGH PERFORMANCE PROCESSOR MODULE....................................................................................64 5. COMMUNICATIONS MODULES ........................................................... 69 5.1. MC-12 COMMUNICATIONS MODULE .....................................................................................................70 5.2. MC-31 COMMUNICATIONS MODULE .....................................................................................................74 6. COMMUNICATIONS OPTION BOARDS ................................................. 78 6.1. OPTION BOARD I: ISOLATED SERIAL .........................................................................................................79 6.2. OPTION BOARD F: FIBRE OPTIC SERIAL BOARD ..........................................................................................82 6.3. OPTION BOARD D: 33.6 KBPS DIAL OPTION BOARD...................................................................................83 6.4. OPTION BOARD L: LINE/ANALOGUE RADIO INTERFACE ................................................................................85 6.5. OPTION BOARD H: HART INTERFACE......................................................................................................90 6.6. OPTION BOARD T3: 10/100 ETHERNET CONTROLLER.................................................................................93 6.7. OPTION BOARD A3:FIBRE OPTIC ETHERNET..............................................................................................93 6.8. OPTION BOARD R2: AUSTRALIAN SPREAD SPECTRUM RADIO ........................................................................94 6.9. OPTION BOARD R3: INTERNATIONAL SPREAD SPECTRUM RADIO ....................................................................96 6.10. OPTION BOARD R4: US/CANADA SPREAD SPECTRUM RADIO........................................................................98 7. PC-1 OPTION BOARDS ....................................................................100 7.1. PC-1 SERIAL OPTION BOARD ..............................................................................................................100 7.2. PC-1 MODEM BOARD PL: TWO WIRE LINE............................................................................................101 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 143 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.3. PC-1 MODEM BOARD: ANALOGUE RADIO INTERFACE ...............................................................................102 8. COMPATIBILITY ..............................................................................103 Communications Option Boards ...........................................................................................................103 9. ANALOGUE INPUT MODULES ...........................................................104 9.1. AI-1: 8 CHANNEL ANALOGUE CURRENT INPUT MODULE............................................................................105 9.2. AI-10: 8 CHANNEL HIGH IMPEDANCE ANALOGUE INPUT MODULE ...............................................................110 10. ANALOGUE OUTPUT MODULE........................................................115 10.1. AO-3: ANALOGUE OUTPUT MODULE....................................................................................................115 11. DIGITAL INPUT MODULES .............................................................120 11.1. DI-5: DC INPUT 16 CHANNEL DIGITAL INPUT MODULE .............................................................................121 12. DIGITAL OUTPUT MODULES ..........................................................130 12.1. DO-1: 8 CHANNEL ISOLATED RELAY OUTPUT MODULE .............................................................................132 12.2. DO-2: 16 CHANNEL RELAY OUTPUT MODULE ........................................................................................136 12.3. DO-6: 16 CHANNEL OPEN DRAIN OUTPUT MODULE................................................................................140 13. RELAY EXPANSION BOARDS..........................................................144 13.1. TEL REL 002: SPST RELAY BOARD ......................................................................................................145 13.2. TEL REL 003: SPST RELAY BOARD ......................................................................................................149 13.3. TEL REL 004: DPDT RELAY BOARD ....................................................................................................153 14. COMBINATION IO MODULES..........................................................157 14.1. IO-2: COMBINATIONAL DIGITAL IO MODULE..........................................................................................158 14.2. IO-3: COMBINATIONAL ANALOG/DIGITAL IO MODULE .............................................................................162 14.3. IO-4: COMBINATIONAL ANALOGUE / DIGITAL IO MODULE ........................................................................170 14.4. IO-5: COMBINATIONAL ANALOGUE / DIGITAL IO MODULE ........................................................................177 15. ADAPTORS AND CABLES ..............................................................184 15.1. RTU TEST CABLES ............................................................................................................................186 RJC-X-Over: Kingfisher PLUS RJ45 to RH45 RS232 Null Modem Cable (serial crossover) .........................186 RJC-X-Over-E: Kingfisher PLUS+ RJ45 to RJ45 Ethernet Crossover Cable .................................................186 15.2. DEVICE CABLES AND ADAPTORS ...........................................................................................................187 ADP-04: PC-1/MC-1 Radio Port to Tait T2010 or Maxon RDM-01 Radio (SD125)....................................187 ADP-05: RTU Serial Port to PC Serial Port (Creates a null modem cable) ................................................187 ADP-07: RTU Serial Port to External PSTN Modem ................................................................................188 ADP-08: RJ45 to DB9 Female Converter (Straight Connect)....................................................................188 ADP-08-M: Serial Port to Digi External Spread Spectrum Radio .............................................................189 ADP-09: Serial Port to HITECH or Nematron Display Panel ....................................................................189 ADP-16: Serial Port to Trio D-Series Radio or Trio E Series Radio............................................................190 RJC-ADP-17: PC-1/MC-1 Radio Port to Trio S- Series Radio ....................................................................190 RJC-ADP-18: CP-xx Line Option Board to Maxon Analogue Radio (Maxon SD-125).................................191 RJC-ADP-20: CP-xx Line Option Board to Trio S Series Analogue Radio ...................................................192 RJC-ADP-21: CP-xx Line Option Board to Tait T2010 Analogue Radio .....................................................193 RJC-ADP-22B: Serial Port to Wavecom GSM..........................................................................................194 RJC-ADP-23: PC-1/MC-1 Radio Port/Serial Port to Trio S- Series (SB) Repeater.......................................195 RJC-ADP-26: Serial Port to Maxon MM-6280IND 3G Data Modem.........................................................195 RJC-ADP-27: RTU Serial Port to Motorola 9522 Satellite Transceiver......................................................196 ADP-28: RTU Serial Port to Trio HSeries Spread Spectrum Radio ..........................................................196 ADP-29: Serial Port to Trio M Series Radio (with modem fitted) E.g. MR540 ..........................................197 RJC-ADP-30: CP-xx Line Option Board to Trio M Series Analogue Radio .................................................197 ADP-31: PC-1/MC-1 Radio Port to Trio M Series Analogue Radio (no modem fitted) E.g. MR540............198 CAB-FO-PATCH-1: A3 Ethernet MTRJ Fibre Optic to 2 × ST adaptor cable...............................................199 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 144 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CAB-FO-PATCH-2: A3 Ethernet MTRJ Fibre Optic to 2 × SC adaptor cable...............................................199 16. ACCESSORIES.............................................................................200 17. GLOSSARY .................................................................................203 18. APPENDIX...................................................................................204 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 145 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1. Introduction A Kingfisher PLUS+ Remote Terminal Unit (RTU) is a highly configurable device that can monitor and control a wide range of equipment. This manual details the specifications for each type of module, option board, cable and accessory available for use with a Kingfisher PLUS+ Modular RTU. There are three types of Kingfisher PLUS+ modular RTUs identified by the processor module they contain: PC-1, CP-12 or CP-30 PC-1 CP-12 CP-30 Modular RTUs support up to 64 modules, 16 communications ports and 1008 IO (input/output) points. Each modular RTU has at least one backplane, a power supply and a processor module. A PC-1 RTU is powered using an external AC/DC power supply. A PC-1 processor module is only used on a BA-4 PLUS backplane (4 slot). A CP-12 or CP-30 RTU is powered using a power supply module (or modules) and utilizes one of three backplanes: a BA-40 PLUS (4 slot), a BA-6 PLUS (6 slot) or a BA-12 PLUS (12 slot). IO (input/output) modules can be added to the RTU in any combination as required. To obtain more communications ports, one or more communications modules can be added to the RTU. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 146 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2. Backplanes Backplanes allow the processor module to communicate with the other modules in the RTU. The backplane also allows power to be supplied to each module. Multiple backplanes can be linked together to create an RTU with up to 64 modules. All backplanes can be surface mounted. BA-12 backplanes can also be mounted in a 19" rack. Backplanes are available in four versions: BA-4 : 4 slot backplane for use with PC-1 BA-40 : 4 slot backplane BA-6 : 6 slot backplane BA-12 : 12 slot backplane Note: the above part number is followed by -PLUS when the backplane uses the green Phoenix terminals for the inter-rack data connectors. A pair of Phoenix plugs can be obtained to create an inter-rack data cable. Use Phoenix Contact type Plug MC 1.5/7-ST-3.5 (1840418) or equivalent. Alternatively, data cables can be ordered from your Kingfisher supplier. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 147 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.1. Module Dimensions Module is shown in backplane. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 148 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.2. BA-4-PLUS: 4 Slot Backplane A BA-4 PLUS backplane is designed to be used with a PC-1 power and processor module. The PC-1 is installed in the left slot and any IO or communications modules can be installed in the other 3 slots. Please use a BA-40 PLUS backplane if requiring a 4 slot backplane for use with a processor and PS-xx power supply. There are three (3) connectors at the far right of the backplane. There are two green 7-way connectors for linking backplanes together and there is one 6-way connector to supply power to a second linked backplane. The 4-slot backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user fitting. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 149 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.3. BA-4-PLUS External Connections J14 Power Socket: J13 (in) and J15 (out) interrack Phoenix Data Sockets: Orange SL9 Power Socket: The SL9 connector is only present on the BA-4 PLUS backplane for use with the PC-1 Power Supply & Processor Module. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 150 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.4. BA-40-PLUS: 4 Slot Backplane A BA-40 PLUS backplane is identical to a BA-4 PLUS backplane excepting the J5 (PC-1 lower connector) and SL-9 (PC-1 power) connectors have been removed. A BA-40 PLUS is designed to be used with a PS-xx power supply and a CP-xx processor module or linked to any other backplane to provide additional slots. There are three (3) connectors at the far right of the backplane. There are two green 7-way data connectors for linking backplanes together and there is one 6-way connector for external power (+5 V and +12 V DC) if a power supply module is not installed on the backplane. The 4-slot backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user fitting. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 151 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.5. BA-40-PLUS External Connections J14 Power Socket: J13 (in) and J15 (out) interrack Phoenix Data Sockets: Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 152 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.6. BA-6-PLUS: 6 Slot Backplane The BA-6-PLUS six slot backplane is designed to support any power supply, IO or communications module in any slot position. A BA-6-PLUS is designed to be used with a PS-xx power supply and a CP-xx processor module or linked to any other backplane to provide additional slots. There are three (3) connectors at the far right of the backplane. There are two green 7-way data connectors for linking backplanes together and there is one 6-way connector for external power (+5 V and +12 V DC) if a power supply module is not installed on the backplane. This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user fitting. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 153 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.7. BA-6-PLUS External Connections J14 Power Socket: J13 (in) and J15 (out) interrack Phoenix Data Sockets: Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 154 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.8. BA-12-PLUS: 12 Slot Backplane TheBA-12-PLUS twelve slot backplane is designed to support any power supply, IO or communications module in any slot position. A BA-12-PLUS is designed to be used with a PS-xx power supply and a CP-xx processor module or linked to any other backplane to provide additional slots. There are three (3) connectors at the far right of the backplane. There are two green 7-way data connectors for linking backplanes together and there is one 6-way connector for external power (+5 V and +12 V DC) if a power supply module is not installed on the backplane. This backplane is designed for surface mounting. Mounting brackets (2 pieces) are supplied for user fitting. Mounting in a 19" rack may be achieved using the alternative MBR-3 rack mounting brackets. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 155 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.9. BA-12-PLUS External Connections J14 Power Socket: J13 (in) and J15 (out) interrack Phoenix Data Sockets: Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 156 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.10. Linking Backplanes Backplanes can be linked together into `racks'. Each rack can have a maximum of 16 slots. Below is a full rack consisting of a BA-40 PLUS linked to a BA-12-PLUS. Each backplane has an IN and an OUT connector linking it to the RTU data bus. The connector used (J13 or J15) varies according to the revision number of the backplane. A single RTU can support up to 4 racks providing a total of 64 modules slots. Each backplane has data bus terminators (resistors) that can be switched ON or OFF. A chain of backplanes requires the terminators to be switched ON for the first and last backplane in the chain as detailed below. Intermediate backplanes must have terminators switched OFF. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 157 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.11. Rack Slot Numbering Backplanes have hard-coded Slot Numbers that can be set to four different ranges that determine the Rack Number. The BA-4 PLUS and BA-6-PLUS backplanes occupy the start of each rack, while the BA-4 PLUS (and BA-40 PLUS) occupies the later address space of each rack. Each backplane has an IN and OUT connector linking it to the data bus, and termination resistors that can be toggled ON and OFF via DIP switches. Linked backplanes that use the same address space (by default) must be set to different rack numbers to avoid clashes. Users should be mindful of these settings. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 158 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.12. Backplane DIP Switch Settings The following table outlines the DIP switch configuration required for the most recent hardware revisions (2.1, 2.2 and 3.2). For previous hardware versions please refer to the superseded hardware manual available on MyKingfisher. Switch Settings 1 Rack Total Number of Racks in RTU 2 Racks 3 Racks 4 Racks 1st Rack 2nd Rack 3rd Rack 4th Rack Note that supplementary to the data bus connection, each backplane requires a Power Supply Module or a power cable connected to J14. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 159 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3. Power Supply Modules The Kingfisher Power Supply Modules allow real time monitoring of currents, voltages and temperatures supplied to the RTU and the backup battery. The monitoring capability also allows the RTU to determine when a supply has failed if in a redundant configuration. If fitted, auxiliary supplies can be overridden manually or by logic to allow for external equipment or sensor loops to be shut down or reset. The two following modules are the current hardware revision. For previous generations of Power Supply Modules, please refer to the superseded Hardware Manual available on MyKingfisher. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 160 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.1. PS-12 Power Supply module · Monitoring of rail voltages, supply & battery currents and temperature · AC or DC input · Support for redundancy (several supplies per backplane) · Isolated DC output · Sealed Lead Acid battery connection with charging/monitoring and low voltage protection · Software controlled power to the Backplane and Aux Outputs The PS-12 provides AC/DC conversion into 12 VDC and 5 VDC for the backplane, as well as 12 VDC and optional 24 VDC auxiliary outputs. Both auxiliary outputs can be controlled by the RTU logic configuration. The PS-12 is supplied with internal temperature sensor to monitor its PCB temperature and an optional external temperature sensor to monitor an attached battery. When a backup battery is connected, the supplied external sensor should be mounted as close as possible to the negative terminal of the battery to ensure correct temperature compensation. If readings from the external sensor are out of range, internal sensor data is used. Please note the charge circuitry is designed for float operation and short term boost of batteries already charged and in good condition. Use of this supply on flat or fully discharged batteries may cause damage to the module. The Rail Voltage, Supply Current, Battery Current, internal and, optionally, external temperature monitoring circuits enable the RTU to monitor and to control all functions of the PS-12 module. The Processor Module has access to many of these values as analog and digital points in the system. If the Mains supply fails and the system is powered from the backup battery, the PS-12 enters Low Battery Shutdown when battery voltage drops below 10.6 V. All outputs are switched OFF for battery preservation, including Backplane power as well effectively meaning that the whole RTU will be shut down. PS-12 switches itself to the lowest power consumption mode possible, further preserving the battery from deep discharge. PS-12 checks rail voltage regularly, and the Backplane power will be restored when +12V_RAIL voltage rises above 12.4 V (if no Mains present) or 11.5 V (if Mains present). Besides various hardware protection features, PS-12 firmware provides additional protection from overload. If output power exceeds its maximum specified power, the SMPS will enter an Overload Mode. Its output voltage will be ramped down and, if overload still exists when it reaches 10.0 V (minimal output voltage), it will switch all outputs off, similar to Low Battery Shutdown. PS-12 will attempt to switch the Backplane ON again regularly. RTU power will be restored permanently when overload condition is removed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 161 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual A power supply module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Several Power Supply modules of any type can be installed on a backplane thus providing redundant and alternative power source configurations. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 162 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fire Risks A supply voltage outside the specified limits may cause fire. Electrical Hazards Only appropriately qualified and trained personnel can install and service this equipment. Mains Power must be connected in accordance with local national wiring rules and regulations. Building installation shall provide appropriate short-circuit backup protection. Always remove input mains voltage (by disconnecting power cord from the mains power outlet or by switching off an external circuit breaker, depending on installation) before performing any operation on this product. Failure to do so may cause fire and may result in a serious personnel injury or even death. Disconnect power cord from the Power Supply Module before wiring, removing or servicing. Warning The earth Terminals in the mains power inlet provide only FUNCTIONAL EARTH / Ground connection and cannot be relied upon for safety purposes. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 163 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Battery Charging Whenever the battery begins to draw more than 100 mA out of the power supply (e.g. when the power supply is first turned on or a battery is connected), the power supply assumes that a fully discharged backup battery just has been connected and starts its Boost charge. After Boost charging the battery for the estimated time (3-10 hours, see below for details, BATT DET and BATT BST LEDs ON), the power supply will switch to Float charging (BATT DET and BATT FLT LEDs ON). PS-12 also maintains estimated capacity of the connected Sealed Lead Acid battery and this value is provided to the system Processor Module. For the algorithm to work properly, a correct battery capacity should be provided to the PS-12 via the Toolbox / RTU configuration setup. When battery is initially detected, it is assumed to be fully discharged. Boost charging time mentioned earlier is calculated based on the provided battery capacity value. Estimated battery capacity is increased by integrating measured current flowing into the battery over the time till it reaches the stated battery capacity. When battery current becomes negative (for instance, if Mains power is out and the RTU runs from the battery), this current is integrated over the time and subtracted from the estimated battery capacity till it reaches zero. Please note that PS-12 cannot distinguish between the real battery connection and the connection of any other (generic) load or power source to the battery terminals, as it detects such connections only by measuring the Battery Current. As a result, all BATT LEDs may exhibit several various combinations depending on kind of load / source connected to the B terminals. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 164 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Module LEDs LED OK VIN TX RX BATT DET BATT FLT BATT BST BATT SUPP BATT LOW OUT 12BP OUT 5BP OUT 12AUX OUT 24iAUX OVLD FAULT 12BP FAULT 5BP FAULT 12AUX FAULT 24iAUX State Description OFF Module fault (no power) Blinking No communications with RTU Processor Module ON Normal OFF Mains not present / SMPS not running ON SMPS running 1 OFF No data being sent to Processor Module ON The PS-12 is sending data to Processor Module via Backplane OFF No data being sent by other modules ON Any RTU module sends data via Backplane OFF No battery nor load nor DC source connected to B terminals2 ON Battery or load or DC source connected to B terminals OFF Battery is not in Float Charge mode ON Battery is slow (float) charging OFF Battery is not in Boost Charge mode ON Battery is fast (boost) charging OFF Battery does not supply current to the PS-12 ON Battery sources more than 0.1 A3 current to the PS-124 OFF +12V_RAIL voltage has risen above 12.4 V4 ON +12V_RAIL voltage has fallen below 11.5 V4 OFF Backplane power is switched OFF: either start-up or shutdown ON Backplane power is switched ON OFF Backplane power is switched OFF: either start-up or shutdown ON Backplane power is switched ON OFF 12VAUX is switched OFF ON 12VAUX is switched ON OFF 24ViAUX is switched OFF ON 24ViAUX is switched ON OFF PS-12 is not in Overload Mode BLINKING In Overload Mode. Output voltage will be ramped down OFF Backplane power is switched OFF or it is ON and 12VBP is above 9 V4 ON Backplane power is switched ON and 12VBP is below 9 V4 OFF Backplane power is switched OFF or it is ON and 5VBP above 2 V4 ON Backplane power is switched ON and 5VBP is below 2 V4 OFF 12VAUX is switched OFF or it is ON and above 9 V4 ON 12VAUX is switched ON and it is below 9 V4 OFF 24ViAUX is switched OFF or it is ON and above 18 V4 ON 24ViAUX is switched ON and it is below 18 V4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 165 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PS-12 Specifications AC Mains Input Rated Voltage Range DC Mains Input Rated Voltage Range Safety Isolation: Primary (Mains) to Secondary (Backplane, Field) Mains Inlet Connector Input Supply from B terminals Backup Battery Power Outputs Output Power Filed Connector Monitoring Operating Temperature 100 - 240 V, 50 - 60 Hz, 1.5 0.7 A 96 - 340 VDC, 2.0 0.5 A 3kVpeak In accordance with IEC 60950 7.62 mm pitch TB Plug (Phoenix PC4/3-ST-7.62) with optional Cable Housing Phoenix KGG-PC 4/3 Note. Phoenix PC4/3-G-7.62 Header mounted on the module's PCB 12.0-16.0 VDC 12 V Sealed Lead-Acid, 26 AH max. Note: Batteries exceeding 26 AH can be used. However, full charging and estimated battery capacity value cannot be guaranteed. Item Range Max. Protection Switchable from Current Logic? 12 V 10.5 - 15.6 V 4.5 A Firmware No Backplane # 5 V Backplane 5 V + 5% 3.0 A Electronic No Battery # 10.5 - 15.6 V 4.5 A Crowbar over- No voltage and reverse polarity protection; Polyfuse 12 V Aux.# 10.5 - 15.6 V 2.0 A Polyfuse Yes 24 V Isolated 24 V + 5% 0.25 A Polyfuse Yes Aux. # Nominal value is 13.8 V @ 25°C. These voltages are electrically linked and are controlled by the module when charging a battery. They will depend only on backup battery voltage when RTU runs from the battery (e.g. when there is a Mains outage). 60 W max (Note: This is total power from all outputs) 5 mm pitch TB plug (Phoenix MSTB2.5/7-ST or similar) Item Range Accuracy Rail Voltage (12 VBP, Battery, 12 VAUX) 9.0 - 15.6 V ± 2% Supply Current Battery: Supply Current from Battery Charge Current to Battery 0.0 - 4.0 A -4.0 - 0.0 A 0.0 - +4.0 A ± 10% ± 10% ± 10% External Temperature -40 - +100 °C ± 2 °C typ @25 °C Internal Temperature -30 - +100 °C ± 2 °C typ @25 °C -20 - +70 °C Storage Temperature -40 - +85 °C Humidity 5 - 98% RH non-condensing Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 166 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Maximum Working Voltage on any contact of the field connector (7pin TB) 42.4 Vpeak / 60 VDC relative to system (backplane) ground Hot Swap Yes. Module can be swapped while RTU is running, assuming that there is an alternative source for the RTU to be powered during such swap for instance, another (redundant) PS-xx. 1) May keep switching ON and OFF intermittently at very light or no load. 2) Short periodic flashes indicate that PS-12 is trying to detect connection. 3) Current value given to the Processor Module is negative 4) approximate values Part Numbers: PS-12-C AC input, Auxiliary 24 V converter fitted PS-12-0 AC input, Auxiliary 24 V converter not fitted Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 167 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Wiring Diagrams Safety Warning Ensure power cord is un-powered before disconnecting power cord from module. Disconnect power cord from module before wiring, removing or servicing the module. Connect module to Mains supply in accordance with national wiring regulations. Mains connections of PS-12 must comply with all requirements listed in Kingfisher Plus+ Installation Manual AC/DC Supply with battery backup: For best results tape or cable-tie the temperature sensor directly to the battery. Connect the black stripped wire to B- or R-. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 168 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12 16 VDC Supply: A battery or other low voltage DC supply can be connected to the B terminals to power the PS-12. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 169 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.2. PS-22 Power Supply Module · Monitoring of rail voltage, supply & battery currents, and temperature · DC input · Support for redundancy (several supplies per backplane) · Isolated DC Output · Sealed Lead Acid Battery connection with charging/monitoring and low voltage protection · Software controlled power to the Backplane and Aux outputs The PS-22 power supply module provides Medium Voltage DC to DC conversion for the backplane, 12V auxiliary output and for an optional 24V isolated auxiliary output. Both auxiliary outputs can be controlled (switched ON or OFF) by the RTU configuration. The PS-22 is supplied with internal and optional external temperature sensors. When a backup battery is connected, the supplied external sensor should be mounted close to the negative terminal of the battery to ensure correct charging temperature compensated battery charging. If readings from the external sensor are out of range, internal sensor data is used. Please note the charge circuitry is designed for float operation and short term boost of batteries already charged and in good condition. Use of this supply on flat or fully discharged batteries may cause damage to the module. The Rail Voltage, Supply Current, Battery Current, internal and, optionally, external temperature monitoring circuits enable the RTU to monitor and to control all functions of the PS-22 module. The Processor Module has access to many of these values as analog and digital points in the system. If the Mains supply fails and the system is powered from the backup battery, the PS-22 enters Low Battery Shutdown when battery voltage drops below 10.6V. All outputs are switched OFF for battery preservation, including Backplane power as well effectively meaning that the whole RTU will be shut down. PS-22 switches itself to the lowest power consumption mode possible, further preserving the battery from deep discharge. PS-22 checks rail voltage regularly, and the Backplane power will be restored when +12V_RAIL voltage rises above 12.4 V (if no Mains present) or 11.5 V (if Mains present). Besides various hardware protection features, PS-22 firmware provides additional protection from overload. If output power exceeds its maximum specified power, the SMPS will enter an Overload Mode. Its output voltage will be ramped down and, if overload still exists when it reaches 10.0 V (minimal output voltage), it will switch all outputs off, similar to Low Battery Shutdown. PS-22 will attempt to switch the Backplane ON again regularly. RTU power will be restored permanently when overload condition is removed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 170 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual A power supply module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Several Power Supply modules of any type can be installed on a backplane thus providing redundant and alternative power source configurations Fire Risks A supply voltage outside the specified limits may cause fire. Electrical Hazards Only appropriately qualified and trained personnel can install and service this equipment. Mains Power must be connected in accordance with local national wiring rules and regulations. Building installation shall provide appropriate short-circuit backup protection. Always remove input mains voltage (by disconnecting power cord from the mains power outlet or by switching off an external circuit breaker, depending on installation) before performing any operation on this product. Failure to do so may cause fire and may result in a serious personnel injury or even death. Disconnect power cord from the Power Supply Module before wiring, removing or servicing. Warning The earth Terminals in the mains power inlet provide only FUNCTIONAL EARTH / Ground connection and cannot be relied upon for safety purposes. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 171 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Battery Charging Whenever the battery begins to draw more than 100 mA out of the power supply (e.g. when the power supply is first turned on or a battery is connected), the power supply assumes that a fully discharged backup battery just has been connected and starts its Boost charge. After Boost charging the battery for the estimated time (3-10 hours, see below for details, BATT DET and BATT BST LEDs ON), the power supply will switch to Float charging (BATT DET and BATT FLT LEDs ON). Note: if the battery charging current falls below 100 mA at any stage during Boost or Float charging, the Power Supply will stop charging the battery (BATT FLT and BATT BST LEDs OFF, BATT DET shortly flashes every second indicating that PS-22 is trying to detect battery). PS-22 also maintains estimated capacity of the connected Sealed Lead Acid battery and this value is provided to the system Processor Module. For the algorithm to work properly, a correct battery capacity should be provided to the PS-22 via the Toolbox / RTU configuration setup. When battery is initially detected, it is assumed to be fully discharged. Boost charging time mentioned earlier is calculated based on the provided battery capacity value. Estimated battery capacity is increased by integrating measured current flowing into the battery over the time till it reaches the stated battery capacity. When battery current becomes negative (for instance, if Mains power is out and the RTU runs from the battery), this current is integrated over the time and subtracted from the estimated battery capacity till it reaches zero. Please note that PS-22 cannot distinguish between the real battery connection and the connection of any other (generic) load or power source to the battery terminals, as it detects such connections only by measuring the Battery Current. As a result, all BATT LEDs may exhibit several various combinations depending on kind of load / source connected to the B terminals. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 172 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PS-22 Module LEDs LED OK VIN TX RX BATT DET BATT FLT BATT BST BATT SUPP BATT LOW OUT 12BP OUT 5BP OUT 12AUX OUT 24iAUX OVLD FAULT 12BP FAULT 5BP FAULT 12AUX FAULT 24iAUX State Description OFF Module fault (no power) Blinking No communications with RTU Processor Module ON Normal OFF Mains not present / SMPS not running ON SMPS running 1 OFF No data being sent to Processor Module ON The PS-22 is sending data to Processor Module via Backplane OFF No data being sent by other modules ON Any RTU module sends data via Backplane OFF No battery nor load nor DC source connected to B terminals2 ON Battery or load or DC source connected to B terminals OFF Battery is not in Float Charge mode ON Battery is slow (float) charging OFF Battery is not in Boost Charge mode ON Battery is fast (boost) charging OFF Battery does not supply current to the PS-22 ON Battery sources more than 0.1 A3 current to the PS-224 OFF +12V_RAIL voltage has risen above 12.4 V4 ON +12V_RAIL voltage has fallen below 11.5 V4 OFF Backplane power is switched OFF: either start-up or shutdown ON Backplane power is switched ON OFF Backplane power is switched OFF: either start-up or shutdown ON Backplane power is switched ON OFF 12VAUX is switched OFF ON 12VAUX is switched ON OFF 24ViAUX is switched OFF ON 24ViAUX is switched ON OFF PS-22 is not in Overload Mode BLINKING In Overload Mode. Output voltage will be ramped down OFF Backplane power is switched OFF or it is ON and 12VBP is above 9 V4 ON Backplane power is switched ON and 12VBP is below 9 V4 OFF Backplane power is switched OFF or it is ON and 5VBP above 2 V4 ON Backplane power is switched ON and 5VBP is below 2 V4 OFF 12VAUX is switched OFF or it is ON and above 9 V4 ON 12VAUX is switched ON and it is below 9 V4 OFF 24ViAUX is switched OFF or it is ON and above 18 V4 ON 24ViAUX is switched ON and it is below 18 V4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 173 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PS-22 Specifications DC Mains Input Rated Voltage Range Isolation: Primary to Secondary DC Inlet Connector 20 - 60 VDC, 4.0 A 3 kVpeak In accordance with IEC 60950 7.62 mm pitch TB Plug (Weidmuller BLZ 7.62/90-3 or Phoenix GMSTBA 2.5/3-G-7.62 or similar) Note. Weidmuller SL 7.62/90B-3 or Phoenix GMVSTBR 2.5/3-ST-7.62 or similar Header mounted on the module's PCB Input Supply from B terminals Backup Battery Power Outputs 12.0-16.0 VDC 12 V Sealed Lead-Acid, 26 AH max. Note: Batteries exceeding 26 AH can be used. However, full charging and estimated battery capacity value cannot be guaranteed. Item Range Max. Protection Switchable from Current Logic? 12 V Backplane # 10.5 - 15.6 V 4.5 A Firmware No 5 V Backplane # 5 V + 5% 3.0 A Electronic No Battery # 10.5 - 15.6 V 4.5 A Crowbar over- No voltage and reverse polarity protection; Polyfuse Output Power Filed Connector Monitoring Operating Temperature 12 V Aux.# 10.5 - 15.6 V 2.0 A Polyfuse Yes 24 V Isolated Aux. 24 V + 5% 0.25 A Polyfuse Yes # Nominal value is 13.8 V @ 25°C. These voltages are electrically linked and are controlled by the module when charging a battery. They will depend only on backup battery voltage when RTU runs from the battery (e.g. when there is a Mains outage). 60 W max (Note this is total power from all outputs) 5 mm pitch TB plug (Phoenix MSTB2.5/7-ST or similar) Item Rail Voltage (12 VBP, Battery, 12 VAUX) Range 9.0 - 15.6 V Supply Current Battery: Supply Current from Battery Charge Current to Battery 0.0 - 4.0 A -4.0 - 0.0 A 0.0 - +4.0 A External Temperature Internal Temperature -40 - +100 °C -30 - +100 °C -20 - +70 °C Accuracy + 2% + 10% + 10% + 10% + 2 °C typ @25 °C + 2 °C typ @25 °C Storage Temperature -40 - +85 °C Humidity 5 - 98% RH non-condensing Maximum Working 42.4 Vpeak / 60 VDC relative to system (backplane) ground Voltage on any contact Hot Swap Yes. Module can be swapped while RTU is running, assuming that there is an alternative source for the RTU to be powered during such swap for instance, another (redundant) PS-xx. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 174 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1) May keep switching ON and OFF intermittently at very light or no load. 2) Short periodic flashes indicate that PS-22 is trying to detect connection. 3) Current value given to the Processor Module is negative 4) approximate values Part Numbers: PS-22-C DC input, Auxiliary 24 V converter fitted PS-22-0 DC input, Auxiliary 24 V converter not fitted Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 175 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Wiring Diagrams Safety Warning Ensure power cord is un-powered before disconnecting power cord from module. Disconnect power cord from module before wiring, removing or servicing the module. Connect module to Mains supply in accordance with national wiring regulations. Mains connections of PS-22 must comply with all requirements listed in Kingfisher Plus+ Installation Manual AC/DC Supply with battery backup: For best results tape or cable-tie the temperature sensor to the negative battery terminal (or as close as possible). Connect the black stripped wire to B- or R-. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 176 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12 16 VDC Supply: A battery or other low voltage DC supply can be connected to the B terminals to power the PS-22. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 177 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.3. PSU-3: 40 Watt AC Power Supply Unit · AC input supply · 40 Watt DC output The PSU-3 AC to DC power supply is intended as a standalone unit to provide 13.8 VDC (adjustable) typically for PC-1 based RTUs. The PSU-3 does not have any power monitoring functions. Power monitoring is performed by the PC-1 processor module. Specifications: Input Supply 90 to 260 VAC 50/60 Hz Load Capacity 40 W Outputs +13.8 VDC @ 2.8 A Isolation 2.5 kV AC input/DC output Supply Fuse 3 A, M205 internal Monitoring Circuits Nil Status Indicators Nil Connector Screw Terminals Weight 430 gm Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 178 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fire Risks A supply voltage outside the specified limits may cause fire. Electrical Hazards Only appropriately qualified and trained personnel can install and service this equipment. Disconnect power cord from the Power Supply Module before wiring, removing or servicing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 179 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PSU-3 Block Diagram Mounting and Connections PSU-3 Output Characteristics Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 180 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.4. PSU-4: 60 Watt AC Power Supply Unit · AC Input Supply · 60 Watt DC Output The PSU-4 AC to DC power supply is intended as a standalone unit to provide 13.8 VDC (adjustable) typically for PC-1 based RTUs. The PSU-3 does not have any power monitoring functions. Power monitoring is performed by the PC-1 processor module. Specifications: Input Supply 90 to 260 VAC 50/60 Hz Load Capacity 60 W Outputs +13.8 VDC @ 2.8 A Isolation 2.5 kV AC input/DC output Supply Fuse 3.15 A, M205 internal Monitoring Circuits Nil Status Indicators Nil Connector Screw Terminals Weight 480 gm Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 181 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fire Risks A supply voltage outside the specified limits may cause fire. Electrical Hazards Only appropriately qualified and trained personnel can install and service this equipment. Mains Power must be connected in accordance with local national wiring rules and regulations. Building installation shall provide appropriate short-circuit backup protection. Always remove input mains voltage (by disconnecting power cord from the mains power outlet or by switching off an external circuit breaker, depending on installation) before performing any operation on this product. Failure to do so may cause fire and may result in a serious personnel injury or even death. Disconnect power cord from the Power Supply Module before wiring, removing or servicing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 182 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PSU-4 Block Diagram Mounting and Connections Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 183 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.5. Calculating Power Requirements This chapter aims to assist you in selecting an appropriate power supply module/s and backup battery for your RTU. It also allows the power requirements of the RTU to be checked to ensure the power supplies are not overloaded. Note that there is a spreadsheet available from MyKingfisher (called "Kingfisher RTU Backup Battery and Solar Panel Calculator") that can perform the following calculations automatically. PS-22 Typical current consumption at various DC voltages (mA) Input Voltage 20 V 40 V 60 V Basic Module, no options 34 20 19 24 VDC Aux Converter Installed 49 27 25 PS-12 Typical efficiency at various AC supply voltages Input Voltage 100 V Efficiency 85% Note: No DC-DC converter installed 170 V 87% 240 V 88% Processor Modules current consumption (mA at 13.8 VDC) Item CP-12 CP-30 Basic Module, no options 140 135 PC-1 Typical current consumption (mA at 13.8 VDC) Bare Module 54 24 V Aux Converter Installed +53 Option S Board Installed 59 Option R Board Installed 62 Option P Board Installed 59 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 184 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO Module typical current consumption (mA at 13.8 VDC) Part number AI-1 AI-10 AO-3 DI-5 DI-10 DO-1 DO-2 DO-5/6 IO-2 IO-3 IO-4 IO-5 24 V Converter OFF 11 25 5 23 40 7 7 3 5 10 8 TBA 24 V Converter ON 80 185 180 -53 44 TBA Extra current per Analogue Input ON +50 [+0] +62 [+3] +46 [-1] +44 [-2] TBA Extra current per Analogue Input OFF - +50 - +42 - TBA Extra current per Digital Input ON +7 [+2] +11 [+5] +7 [+3] +10 [+1] +9 [+1] TBA Extra current per Digital Input OFF +31 +13 +1 +12 +12 +12 TBA Absolute Max current draw 480 681 380 135 216 255 215 19 157 367 228 TBA Note: Values shown are for inputs powered by the IO module itself when power is available from the 13.8 VDC supply. Values in square brackets `[ ]' denote current consumption when inputs re powered by an external supply. Communications Modules current consumption (mA at 13.8 VDC) Item MC-12 Basic Module, no options 140 MC-31 135 For Communications Option Boards please refer to the 5 V Rail Overload Check chapter. Superseded Communications Modules current consumption (mA at 13.8 VDC) Item Basic Module, no options MC-11 165 MC-30 165 Superseded IO Module typical current consumption (mA at 13.8 VDC) AO-2 11 115 - +55 - - 335 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 185 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.6. 5 V Rail Overload Check The PS-12 and PS-22 modules supply 5 VDC to the backplane for powering modules. A maximum of 3 Amps can be drawn on the 5 VDC rail from each power supply module. Please ensure that this limit us not exceeded by totaling the 5 V current requirements for your RTU. CP-xx and MC-xx typical 5 V Rail current consumption (mA at 5 VDC) CP-11 310 CP-12 150 CP-21 360 CP-30 290 MC-11 / MC-30 370 MC-xx CP-xx Option Board typical 5 V Rail consumption (mA at 5 VDC) Option Board Type A3 Fibre Optic Ethernet Board Dial (PSTN) Fibre Optic Serial HART Isolated Serial (RS232) Private Line or Analogue Radio Interface 2.4 GHz (50 mW) Spread Spectrum Radio: Transmitting Receiving 900 MHz (1 W) Spread Spectrum Radio: Transmitting Receiving T3 Ethernet Option Board Port label A3 D F H I L R3 R2 / R4 T3 Consumption 600 165 40 90 70 90 100 85 100 670 300 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 186 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO Module 5 V Rail current consumption (mA at 5 VDC) Module AI-1 AI-10 AO-2 AO-3 DI-5 DI-10 DO-1 DO-2 DO-5/6 IO-2 IO-3 IO-4 IO-5 All IO inactive 22 15 22 9 6 54 15 9 48 10 26 23 TBA All IO active and powered by module 27 66 28 30 40 85 27 39 39 37 36 37 TBA Superseded Option Boards typical 5 V Rail consumption (mA at 5 VDC) Option Board Type CP-12 Ethernet CP-21 Port 2 Only Ethernet CP-30 Ethernet CP-21 Ethernet Serial (RS232) Line (original version) Image Capture Port label ENET-T ENET-A ENT-T2 ENET-E SER-S L(1) J Consumption 130 65 20 0 idle / 850 max 5 120 1000 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 187 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.7. Total Power Load The total Current load required to power the RTU is as follows: Total Power load is therefore: Note: If Amps is used in the `Total Current Load' calculation in place of milliamps, dividing by 1000 can be omitted (1 Amp = 1000 mA). · The Total Current Load for a PS-12/22 should not exceed 4.5 Amps. Loads greater than 4.5 Amps will require a second PS-12/22 module. · The Total Current Load for a PC-1 should not exceed 4 Amps. Loads greater than 4 Amps will require a PS-12/22 supply to be installed. · Users should be mindful of the current draw on the 5 VDC rail. See the Rail Overload Check chapter for more details Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 188 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.8. Battery Backup For maximum battery life, a maximum discharge depth of 50% is normally used. E.g. for a 7 AH battery, there is 3.5 AH of backup power. Therefore the battery can supply 3.5 Amps for 1 hour or 1 Amp for 3.5 hours etc. The size of the backup battery required depends on how long the RTU needs to be able to run without mains power. In addition to the Total Current Load above, a backup battery will also need to power the PS-11/21 if present (not applicable if using a PC-1 processor). Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 189 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4. Processor Modules The amount of memory, speed, and flexibility of an RTU is determined by the processor module selected. There are three processor modules available in the Kingfisher modular RTU range. These modules are not equipped with any I/O or communications natively and require additional modules to be attached to the backplane. Processor modules summary Model Number CPU Speed PC-1 16 MHz CP-12 40 MHz CP-30 166 MHz Memory 128 KB Flash 256 KB SRAM 512 KB Flash 512 KB NVRAM 128 KB SRAM 16 MB Flash 32 MB NVRAM optional expansions Part number Bare module 24 VDC Aux Supply fitted V.23 FSK Radio 2-wire line V.23 FSK 4-wire line V.23 FSK (obsolete) See Chapters Communications Options Boards and Compatibility Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 190 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Lithium Battery This product contains a lithium battery. Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries in accordance with local regulations or return to the supplier. Fire Risks A supply voltage outside the specified limits may cause fire. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 191 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.1. PC-1: Power & Processor Module · Monitoring of battery and input supplies · Isolated DC Outputs · 16 MHz Processor · DC Input Supply · Up to two Communications Ports · Low Voltage Battery Protection · 256 KB SRAM The PC-1 is one of the best supported processors available to a kingfisher RTU. It is well suited to small and mid-size installations as it features an integrated power supply, reduces the system complexity by negating the need for additional power supply modules. With remote installations in mind the PC-1 was designed to be capable of running from a backup battery, and has a fully isolated low power DC output for external equipment. To configure the PC1, a PC running the Toolbox32 software is required. The Toolbox32 software allows the user to implement ladder logic. The PC-1 can only be installed in the first slot of a 4-slot backplane (BA-4) and operates from a nominal +12 VDC supply (typically 13.8 VDC). The module has one fixed RS-232 port and one option port. A PC-1 has two links that can be accessed from the rear of the module as shown below. The SRAM battery is enabled at shipping time by the factory. The user can clear the SRAM by removing the SRAM link for five minutes. This will clear the RTU configuration and ladder logic. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 192 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Part Numbers The PC-1 is available with 3 options (A, P, M) as detailed below. PC - A P Device: 24 V 10 W Auxiliary Supply Converter Port 2 Option Board Type Part Number: 0 = Not Fitted C = Fitted 0 = Not Fitted R = Radio, V.23 FSK* P = 2-Wire Line, V.23 FSK S = Serial RS232/RS485 M Memory 0=128 KB RAM (obsolete) 1=256 KB RAM (standard) * Radio option boards must be factory modified to suit Trio radios (resistor R15 [150 K] is replaced with a 2K2 resistor). Please add the comment "for Trio radio" when ordering a radio option board for use with a Trio radio. Example: PC-1-CR1 is a PC-1 with 24 VDC auxiliary converter, radio option port and extra RAM. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 193 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PC-1 Module LEDs Both of the communications ports have Tx, Rx, RTS and CD LEDs in a vertical group as shown above. PC-1 LED Description OK ON when module is functioning OK ON when the internal 5 V supply is OK. This LED should DC +5 V always be on +12 V ON when the internal 12 V supply is OK. This LED should always be on (software controlled) T1 Test LED 1. Flashes during Power Down mode. +Vs ON when the Auxiliary 24 V supply is OK (will only display if the 24 V converter is installed). BATT CHG* ON when the battery is being charged DIS* ON when the battery is being discharged LO ON when the battery voltage is low (For a PC-1 this occurs when the supply voltage is less than about 11.2 V) T2 Test LED 2. Not currently used. Tx ON when port is transmitting Rx ON when port is receiving RTS Request to send. Set ON to begin transmitting CD Carrier detect: ON while a communications signal is detected. WD Processor Watchdog Timer. Set ON when the processor is reset. * The battery charging (BATT CHG) and battery discharging (DIS) LEDs will sometimes flicker on and off when the battery is charged to the optimum level or if no battery is connected. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 194 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PROCESSOR SPECIFICATIONS Processor Type Intel 80C188 Word Size 16 Bit internal data bus 8 Bit external data bus Clock Speed 16 MHz BIOS Yes Flash Memory 128 KB Total. 28 KB for firmware drivers. SRAM 256 KB Real-time Clock (RTC) 1 minute per month (+/- 20 ppm) Watchdog Timer Yes Status Indication Yes Battery Type Lithium. Not rechargeable. Battery Life - module unpowered 7 years @ 25°C Communications Ports 2 Port 1 (RS232) Serial, 300 to 115200 Baud Port 2 (Optional) Serial, Analogue Radio Interface, 2-Wire Line or 4-Wire Line 300 to 115200 Baud (depending on port type) Modem Port 2 CCITT V23 (Optional) 1200 Baud Configuration Software Toolbox 32 Diagnostics Software Yes Basic Configuration Auto on power-up RTU Address Range 1 249 Communications P rotocol Kingfisher, DNP3, Modbus, plus many more... Analogue Block Processing Yes PID Block Processing Yes Redundant Power Supplies Not supported Redundant Processors Not supported Redundant Communications Yes Internal Power Consumption 120 mA from +5 VDC I/O Bus Data Rate 250 Kbps CM Bus Data Rate 83 Kbps Cyclic Redundancy Port 1 and 2 Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Hot Swap Not supported. Removing the PC-1 will power down the RTU. PC-1 POWER SUPPLY Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 195 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Input Supply to PC-1 11.5-15 VDC @ 4 A Max (60 W) Typically 13.8 VDC if backup battery connected Outputs From PC-1 +5 VDC @ 1 A Max (5 W) to Backplane +12 VDC @ 4 A Max to Backplane* +12 VDC @ 2 A Max to Vr* +24 VDC @ 400 mA (10 W) Optional Auxiliary Output (3 kV Isolation) # Backup Battery 12 V, 7 AH typical. 26 AH max Deep Discharge Protection RTU Shutdown at 10.6 V RTU Start-up at 11.8 V Supply Fuse 7 A (Maximum Current into the PC-1) Battery Fuse 7 A (Maximum Current into or out of battery) Combined Vr and 24 VDC Fuse 3 A Polyfuse Monitoring Item Accuracy Battery Current PC-1 Supply Voltage PC-1 Supply Current PC-1 Temperature ± 10% ± 5% ± 10% ± 5% * Note: backplane rail voltages are dependent on power supply to the PC-1. Most PC-1s are powered using the 40 W PSU-3 Power Supply set to 13.8 VDC when using a 12 VDC backup battery. # the +24 V converter is optional and must be ordered with the PC-1. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 196 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PC-1 Pinout Port 1 Pins 1 2 3 4 5 6 7 8 Direction OUT OUT OUT IN COM IN IN OUT RS-232 Definition DTR +12 V low power RTS DCD GND (0 V) CTS RXD TXD Please refer to the PC-1 Option boards for more information regarding port 2 option boards. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 197 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.2. CP-12 Processor Module · Support for Processor and Communications Redundancy · Up to 3 communications ports · 40 MHz x86 CPU The CP-12 processor module has up to three independent communications ports. Ports 2 and 3 can house option boards while port 1 is a fixed serial port (RS-232). This processor is targeted at the application space that is too complex for the PC-1 but does not required the additional features made available with a CP-30 based system. The CP-12 has extended functionality over the PC-1 such as redundant processor and communications modules support, and is compatible with Ethernet based boards. The CP-12 uses the same configuration software as the PC-1 processor, and as such is programmable with ladder logic. The CP-12 has 512 KB of flash memory for operating code and system parameter storage, and 512 KB of battery backed SRAM for all configuration and event storage data. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 198 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CP-12 Reset Procedures The SRAM battery is enabled from the factory by default. The user can clear the SRAM by removing the SRAM link for five minutes. This will clear the RTU configuration and Ladder Logic. Clearing Configuration with Monitor Mode (Kingfisher Bootloader Self-Test) Behind the LED lens of the CP-12 there is a diagonally mounted jumper. This is a hardware feature unique to the CP-12 processor. When the jumper pins are shorted while the module is being reset (or power cycled), the processor will enter Monitor Mode (the Kingfisher bootloader) and perform a read/write test of the SRAM. This will forcefully remote any configuration and logic in the RTU. Monitor Mode is a deterministic and efficient way of clearing a Processor as the module does not need to be removed from the Backplane, and as the SRAM is forcibly overwritten. Note: The RAM test is extremely fast. The CP-12 will clear the RAM nearly instantly. To exit monitor mode, remove the short and power cycle the unit again. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 199 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CP-12 Module LEDs CP-12 LED Description OK ON when Processor is functioning correctly MON ON when Processor is in Monitor mode WDT ON when Processor watchdog timer is overflows, such as in the event of a software crash. RST ON when in reset. Will be lit for 200 ms when cold starting. TxD ON when transmitting data on corresponding Port RxD ON when receiving data on corresponding Port RTS ON when asserting Request To Send on corresponding Port DCD ON when Data Carrier Detect affirmed on corresponding Port 10ACT ON when Ethernet is operating at 10 Mbps on corresponding Port 100ACT ON when Ethernet is operating at 100 Mbps on corresponding Port LINK ON when Ethernet Link is established COL ON when Ethernet Collision is detected IOTX IORX Intensity is proportional to load on backplane IO Bus (this bus is used to poll all IO modules) CMTX CMRX Intensity is proportional to load on load on backplane Communications Bus (this bus is used for communications modules data transmission) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 200 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PROCESSOR SPECIFICATIONS Processor 40 MHz x86 Word Size 16 bit data bus BIOS Yes Flash Memory 512 KB SRAM 512 KB Battery Type Lithium Primary (not rechargeable) Battery Life - module unpowered 7 years @ 25°C Real-time Clock (RTC) 1 minute per month (+/- 20 ppm) Watchdog timer Yes Status Indication Yes Communications P orts 1-3 (1 fixed, 2 option ports) Port 1 (RS232) 300 to 115200 Baud (factory default 9600 8-N-1) Ports 2 and 3 (Optional) For supported port types, please see the Option Boards chapter Configuration Software Toolbox 32 RTU Address Range 1 249 (expandable to 2000 by using multiple masters) Communications P rotocol Kingfisher, Modbus + many more Default Data Format 8 data bits, no parity, 1 stop (8, N, 1) Analogue Block Processing Yes PID Block Processing Yes Redundancy Yes. Two CP-12 modules can be installed in the one RTU. One processor module must be installed in an odd numbered slot and one in an even numbered slot. Internal Power Consumption 275 mA from +5 VDC bus on backplane I/O Bus Data Rate 250 Kbps CM Bus Data Rate 83 Kbps Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Hot Swap Yes. When 2 processors are present on the backplane, one processor can be swapped while the RTU is still running. However, a hot swap will cause a Warm Start of the remaining processor. All ports will be reinitialized and ready for communications within 6 seconds. New data received during the changeover may be lost. To preserve data and for more information please see the Redundancy appendix in the Toolbox 32 manual. CP-12 Ports Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 201 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The CP-12 has a fixed serial port (RS-232) on port 1. Ports 2 and 3 can house option boards. For more information regarding communications capabilities please refer to the Option Board Chapter. Port 1 Pins 1 2 3 4 5 6 7 8 Direction OUT - OUT IN COM IN IN OUT RS-232 Definition DTR N/C RTS DCD GND (0 V) CTS RXD TXD Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 202 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.3. CP-30: High Performance Processor Module · Compliant with IEC-61131 programming languages · Up to 3 communications ports · 166 MHz ARM 9 CPU · Supports Communications and Processing Redundancy · 16 MB Flash · 32 MB DRAM The CP-30 is a high performance processor module that can provide exceptional speed, memory and functionality to your RTU. Targeting large RTU Systems, the CP-30 is equipped with a 166 MHz ARM9 CPU, capable of running all IEC-61131-3 certified languages, and utilizes an Ethernet port as the default connection and configuration medium. To configure the CP-30, a PC with an Ethernet port and the Toolbox PLUS software is required. Toolbox PLUS features ISaGRAFTM software, which provides logic programming in the IEC-61131 standard languages: Structured Text, Ladder Logic, Function Blocks, Instruction Lists and Sequential Function Charts. The processor module has up to three independent communications ports. Ports 2 and 3 can use plug-in option boards while port 1 is fixed as Ethernet. RTUs can use a second CP-30 module to provide processor redundancy. One processor is installed in an odd-numbered backplane slot (the passive processor) and the other in an even-numbered slot (the active processor). The passive standby processor will switch to active mode if communications stop on the backplane for 1500 ms (by default). This could be caused by: · Failure, removal or reset of the active processor · Download of the configuration, logic or firmware to the active processor The CP-30 has 16 MB of flash memory for the storage of all operating code, RTU configuration and event logs. It also has 32 MB of SDRAM for program operation and general data storage and 128 KB of battery backed SRAM for non-volatile data such as retained variables. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 203 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The SRAM battery is enabled at shipping time by the factory. The user can clear the SRAM by removing the SRAM link for five minutes. Note: this will not clear the RTU configuration. CAUTION: After removing and re-installing the SRAM link, please ensure that the CP-30 is powered up for at least one second. The SRAM battery will then function for the specified life span. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 204 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CP-30 Module LEDs CP-30 LED Description OK * Steady: Operating system Ok. Set ON after start-up checks pass (see F1, F2 and F3 LEDs below). Slow flash: starting operating system after downloading firmware Fast flash: firmware download error 10 Port 1 10 Mbps Ethernet connection. Flashes when communicating otherwise ON continuously 100 Port 1 100 Mbps Ethernet connection. Flashes when communicating otherwise ON continuously LNK Port 1 Ethernet link established (port is connected to an Ethernet network) COL Port 1 Ethernet collisions detected Tx ON when port is transmitting Rx ON when port is receiving RTS Request to send. RTU Sets RTS ON to begin transmitting CD Ports 2, 3: Carrier detect. ON while a communications signal is detected. F1 * During start-up: set ON if Firmware running OK. When RTU running: flashes if port 2 configuration error. During firmware download: flashes fast if an error occurs. Reset power to clear. F2 * During start-up: set ON if Linux operating system running OK. When RTU running: flashes if port 3 configuration error. During firmware download: flashes fast if an error occurs. Reset power to clear. F3 * During start-up: set ON if ISaGRAFTM and RTU configuration running OK. After start-up: remains steady ON if active (or only) processor or flashes at 1 Hz if passive (redundant standby) processor. Note: the F3 LED may be turned off briefly (less than 1 second) during initial synchronization between redundant processors. Flashes quickly if watchdog timer error return to supplier for repair. During firmware download: flashes fast if an error occurs. Reset power to clear. * As the CP30 starts up, the F1, F2 and F3 LEDs are progressively set ON when successful. After a successful start up, F1 and F2 are set OFF, F3 is left ON and the OK LED is set ON Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 205 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PROCESSOR SPECIFICATIONS Processor Cirrus EP9301 (ARM9) / 166 MHz / 32 bit data bus BIOS Yes SRAM 128 KB (Battery backed) Flash Memory 16 MB. Permanent memory. Used to store the RTU configuration, logic, retained variables and event logs. If power to the processor is lost, nonretained variables and the current state of execution will be reset. SDRAM 32 MB Real-time Clock (RTC) 1 minute per month (+/- 20 ppm) Watchdog timer Yes Status Indication Yes Battery Life module unpowered 7 years @ 25°C Communications P orts 1-3 (1 fixed, 2 option ports) Comms Port 1 (Ethernet) 10 or 100 Mbps auto negotiation Default IP address: 192.168.0.1 Isolation: Transient voltage: 1 kV Comms Ports 2 and 3 (Optional) For supported port types, please see the Option Boards chapter Configuration Software Toolbox PLUS+ Diagnostics Software Yes RTU Address Range 1 65520 Communications Protocol Kingfisher, Modbus (RTU, ASCII and TCP), DNP3 and more (see the protocols document for further details) Default Data Format 8 data bits, no parity, 1 stop (8, N, 1) Analog Block Processing Yes PID Block Processing Yes Redundancy Yes. Two CP-30 modules can be used in the one RTU. Logic Processing IEC 61131 Languages: Ladder Logic, Structured Text, Function Block Diagram, Sequential Function Chart, Instruction List and Flowchart Internal Power Consumption 500 mA from +5 VDC bus on backplane I/O Bus Data Rate 250 Kbps CM Bus Data Rate 250 Kbps Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 206 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CP-30 Pinout Port 1 Pins 1 2 3 4 5 6 7 8 Ethernet Function DTR N/C RTS DCD GND (0 V) CTS RXD TXD Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 207 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5. Communications Modules Communications modules can be utilized to add additional ports and multiple protocol capability to your RTU. Each module is equipped with two expansion ports that can house a wide range of specialized option boards as follows: Part Number Option Board Description I Isolated Serial Interface, RS232/RS485/RS422 F Fiber Optic Interface D Dialup Modem (PSTN) V34 33.6 Kbps L Private Line or Analogue Radio Interface H HART / Bell 202 interface A3 Ethernet MTRJ Fiber Optic Interface T3 Ethernet RJ54 Copper 10/100 Mbps R2 900 MHz Spread Spectrum Radio for Australia R3 2.4 GHz Spread Spectrum Radio for International R4 900 MHz Spread Spectrum Radio for USA For more information regarding option boards and compatibility with superseded hardware, please refer to the chapter Option Boards. Lithium Battery These products contain a lithium battery. There is a risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries in accordance with local regulations or return to the supplier. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 208 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5.1. MC-12 Communications Module · Up to three communications ports per module · Supports Communications Redundancy · Wide range of available option boards · Fixed Serial (RS232) port on port 1 The MC-12 multi-communications module provides up to three additional communications ports. Ports two and three can house option boards while port 1 is fixed as a serial (RS-232) port. An MC-12 supports a maximum baud rate of 83 Kbps between itself and the RTU processor module. This bandwidth can be split across a maximum of 16 ports. Users should be mindful of this limitation when determining the number of ports used simultaneously in one installation. The MC-12 is identical to the CP-12 with the exception of labelling, the lens cover, and firmware. This module consumes power from the +5 VDC bus on the backplane. It also requires +12 VDC. One or more MC-xx modules can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 209 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-12 Module LEDs MC-12 LED Description OK ON when Module is functioning correctly MON ON when Module is in Monitor mode WDT ON when Module watchdog timer is overflows, such as in the event of a software crash. RST ON when in reset. Will be lit for 200 ms when cold starting. TxD ON when transmitting data on corresponding Port RxD ON when receiving data on corresponding Port RTS ON when Request To Send on corresponding Port is asserted DCD ON when Data Carrier Detect affirmed on corresponding Port 10ACT ON when Ethernet is operating at 10 Mbps on corresponding Port 100ACT ON when Ethernet is operating at 100 Mbps on corresponding Port LINK ON when Ethernet Link is established COL ON when Ethernet Collision is detected IOTX IORX Brightness of each indicates load on backplane IO Bus (this bus is used to poll all IO modules) CMTX Brightness of each indicates load on backplane Communications Bus CMRX (this bus is used for communications modules data transmission) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 210 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-12 COMMUNICATIONS MODULE SPECIFICATIONS Processor 40 MHz x86 Word Size 16 bit data bus BIOS Yes Flash Memory 512 KB SRAM 512 KB (Non-Volatile, Battery Backed) Battery Type Lithium Primary (not rechargeable) Battery Life -- module 7 years @ 25°C unpowered Real-time clock Yes. Accuracy ± 1 min/month Watchdog timer Yes Status Indication Yes Communications P orts 1-3 (1 fixed, 2 option ports) Port 1 (RS-232) 300 to 115200 Baud (factory default = 9600 bps) Default Data Format 8 data bits, no parity, 1 stop (8, N, 1) Ports 2 and 3 (Optional) For supported port types, please see the Option Boards chapter Configuration Software Toolbox 32 RTU Address Range 1 249 (expandable to 2000 by using multiple masters) Communications P rotocol Kingfisher, Modbus + many more Analogue Block Processing Yes Redundancy Yes. Two CP-12 modules can be installed in the one RTU. One processor module must be installed in an odd numbered slot and one in an even numbered slot. Internal Power Consumption 275 mA from +5 VDC bus on backplane I/O Bus Data Rate 250 Kbps CM Bus Data Rate 83 Kbps Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Hot Swap Yes. When 2 processors are present on the backplane, one processor can be swapped while the RTU is still running. However, a hot swap will cause a Warm Start of the remaining processor. All ports will be reinitialized and ready for communications within 6 seconds. New data received during the changeover may be lost. To preserve data and for more information please see the Redundancy appendix in the Toolbox 32 manual. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 211 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-12 Pinout The MC-12 has a fixed serial port (RS-232) on port 1. Ports 2 and 3 can house option boards. For more information regarding communications capabilities please refer to the Option Board chapter. Port 1 Pins 1 2 3 4 5 6 7 8 Direction OUT N/C OUT IN COM IN IN OUT RS-232 Definition DTR N/C RTS DCD GND (0 V) CTS RXD TXD Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 212 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5.2. MC-31 Communications Module · Up to three communications ports per module · Supports Communications Redundancy · Wide range of available option boards · Fixed Ethernet port on port 1 · 128 KB SRAM · 16 MB Flash · 32 MB DRAM The MC-31 Communications Module provides three additional communications ports. Ports 2 and 3 are optional and house option boards while port 1 is a fixed Ethernet port. The MC-31 is identical to the CP-30 with the exception of labelling, the lens cover, and firmware. The MC-31 module is only for use with CP-30 based RTUs. This module consumes power from the +5 VDC bus on the backplane. It also requires +12 VDC. One or more MC-31 modules can be installed in any I/O slot of a 4, 6 or 12 slot backplane. An RTU can have up to 16 ports. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 213 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-31 Module LEDs MC-31 LED Description OK * Steady: Operating system Ok. Set ON after start-up checks pass (see F1, F2 and F3 LEDs below). Slow flash: starting operating system after downloading firmware Fast flash: firmware download error 10 Port 1 10 Mbps Ethernet connection. Flashes when communicating otherwise ON continuously 100 Port 1 100 Mbps Ethernet connection. Flashes when communicating otherwise ON continuously LNK Port 1 Ethernet link established (port is connected to an Ethernet network) COL Port 1 Ethernet collisions detected Tx ON when port is transmitting Rx ON when port is receiving RTS Request to Send. RTU sets RTS ON to begin transmitting CD Ports 2, 3: Carrier Detect. ON while a communications signal is detected. L1 * During start-up: set ON if Firmware running OK. When RTU running: flashes if port 2 configuration error. During firmware download: flashes fast if an error occurs. Reset power to clear. L2 * During start-up: set ON if Linux operating system running OK. When RTU running: flashes if port 3 configuration error. During firmware download: flashes fast if an error occurs. Reset power to clear. * As the MC-31 starts up, the top row LEDs are progressively set ON when successful. After a successful start up, L1 and L2 are set OFF. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 214 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-31 COMMUNICATIONS MODULE SPECIFICATIONS Processor Cirrus EP9301 (ARM9) / 166 MHz / 32 bit data bus SRAM 128 KB (Battery backed) Flash Memory 16 MB SRAM 32 MB SDRAM (Non-Volatile, Battery Backed) Battery Type Lithium Primary (not rechargeable) Battery Life -- module 7 years @ 25°C unpowered Status Indication Front Panel LEDs Communications P orts 1-3 (1 fixed, 2 option ports) Port 1 (RS-232) Fixed Ethernet Default Data Format 8 data bits, no parity, 1 stop (8, N, 1) Ports 2 and 3 (Optional) For supported port types, please see the Option Boards chapter Communications P rotocol Kingfisher, Modbus (RTU, ASCII and TCP) and DNP3 Default Data Format 8 data bits, no parity, 1 stop (8, N, 1) MC-30/31 modules per RTU Maximum of 16 ports per RTU E.g. Can use 5 MCs if each has 3 ports Internal Power Consumption 500 mA from +5 VDC bus on backplane Hot Swap Yes. Module can be swapped while RTU is running. Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 215 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MC-31 Pinout Port 1 Pins 1 2 3 4 5 6 7 8 Ethernet Function DTR N/C RTS DCD GND (0 V) CTS RXD TXD Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 216 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6. Communications Option Boards The following option boards are compatible with the CP-12/30 processor modules and the MC-12/31 communications modules (and the LP-3 stand-alone RTU). For PC-1 option boards please see the following chapter. These are the currently supported option boards: Part Number I F D L H A3 T3 R2 R3 R4 Option Board Description Isolated Serial Fiber Optic Interface Dialup Modem (PSTN) V34 33.6 Kbps Private Line or Analogue Radio Interface HART / Bell 202 interface Ethernet MTRJ Fiber Optic Interface Ethernet RJ54 Copper 10/100 Mbps 900 MHz Spread Spectrum Radio for Australia 2.4 GHz Spread Spectrum Radio for International 900 MHz Spread Spectrum Radio for USA For previous generation hardware, please refer to the section Compatibility. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 217 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.1. Option Board I: Isolated serial The isolated serial option board provides an RS-232, RS485 or an RS422 interface. The port is software configurable for any of these modes. When RS485 is configured for an isolated serial option board, the RTS and CD LEDs are set on and when RS422 is configured the RTS LED is set on (there are no LEDs set on for RS232). RS485 requires a 120 terminating resistor at each end of the transmission line and RS422 requires a 100 terminating resistor at the receiver end of the transmission line only (Please see the wiring diagrams at the end of this section). Option Board I Specifications Baud rate 300 115200 bps Internal Power Consumption 15 mA from +5 VDC Bus on backplane Output Power +4.3 V @ 100 mA max. RS422 Line drive 10 Receivers RS485 Line drive 32 Receivers Communications 8 data bits, no parity, 1 stop (8, N, 1) Isolation Transient voltage: 2.5 kV Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing RTU Hardware Required Can be installed in any of the following ports: CP-10/11/21/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 218 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Serial Option Board Connections RJ45 Pin 1 2 3 4 5 6 7 8 Direction OUT OUT OUT IN Common IN IN OUT RS-232 DTR 4.3 V RTS DCD GND TCS RxD TxD RS422 / RS485 N/A N/A TX+ N/A GND RX+ RXTX- RS232 Wiring Diagram (Null Modem Cable) Note maximum recommended RS232 length is 15 meters. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 219 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RS485 Wiring Diagram If the ground resistor is not available, each GND terminal can be tied to EARTH locally via 100 0.5 W resistor. For short cable runs (less than 5 m) a single 60 terminating resistor can be used at one end of the RS485 cable. RS422 Wiring Diagram The master RTU can transmit/receive to any one outstation RTU at any time or each outstation can transmit/receive to the master RTU, one at a time. Note: outstation RTUs cannot communicate with each other. Up to 10 RTUs (or other RS422 devices) can be connected to the RS422 bus. Maximum RS422 Wire Length: 1200 m If GND wire is not available, each GND terminal can be earthed locally via 100 0.5 W resistors. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 220 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.2. Option Board F: Fibre Optic Serial Board The fibre optic serial option board provides a serial interface via a fibre optic cable. A fibre optic port is treated the same way as a standard serial port except a fibre optic cable is used for the communications medium. A fibre optic link offers excellent electrical isolation and a high data rate. Two fibre optic cables are required for each fibre optic port. Option Board F Specifications Maximum Baud rate 115.2 Kbps (equivalent to RS232 port) Communications 8 data bits, no parity, 1 stop (8, N, 1) Maximum Fiber Optic Cable Approx. 4 km (depends on cable and other factors) Length Supported Fiber Optic Cables Multimode 50/125 um, 62.5/125 um, 100/140 um, and 200 um HCS Option Board Connectors Tx: ST female (light grey port) (use male connectors on cable) Rx: ST female (dark grey port) Power Consumption (Tx) 200 mA max. from +5 VDC Bus on backplane Line drive 1 Receiver (point to point) Electrical Isolation 15 kV Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing RTU Hardware Required Can be installed in any of the following ports: CP-10/11/21/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 Cabling Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 221 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.3. Option Board D: 33.6 Kbps Dial Option Board The dial option board provides a V34 PSTN interface to the Kingfisher RTU. The port speed is software configurable, and the dial board is designed to be compliant with telecommunications standards worldwide. Dial Option Board Connections RJ45 Pin 1 2 3 4 5 6 7 8 PSTN Function - Reserved Line Line + Reserved - Telecommunication Line Cord To reduce risk of fire, use only 26 AWG or larger telecommunications line cord. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 222 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Dial Option Board Specifications PSTN Modem / Data Rate V.34, 300 to 33600 bps, auto-negotiating RTU DTE Port Speed 300 115200 bps Line Impedance 600 Approval International Transmit level -10 dBm Receive level -43 dBm to -- 9 dBm Dialling Pulse or Tone Internal Power Consumption 175 mA from +5 VDC Bus on backplane Isolation Maximum working voltage in respect to system earth/ground must not exceed TNV-2 limits (80 V) Transient voltage: 5 kV Recommended Initialization D Option: AT&FE0V0S0=2&W String Original D Option: AT&FE0V0S0=2X0&W (ignores dial tone) Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/21/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 223 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.4. Option Board L: Line/Analogue Radio Interface The line option board provides a Private Line or analogue radio interface and is software configurable for either of these modes. The board is optically isolated, operates at 1200 bps and provides FSK CCITT V.23 modulation. Line Board Connections RJ45 Pin 1 2 3 4 5 6 7 8 Direction OUT IN OUT IN IN IN IN OUT Line / Radio Function Tx Rx - RTS/PTT CD GND (0 V) 12 V Rx + Tx + Telecommunications Line Cord To reduce risk of fire, use only 26 AWG or larger telecommunications line cord. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 224 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Connecting a Radio As the port is isolated it is necessary to use an external voltage source (normally from the RTU `radio' connection +12 V) to power not only the radio but also the carrier detect circuit. Some radios have a very low audio interface level (TX Audio), e.g. Maxon DM 0530, DM-2850, SD-125 and Tait T2010 / 2015. These radios will most likely require a resistor network external to the port to drop the TX Audio level. Some radios (e.g. Maxon) have an internal pull up resistor to +5 V on the carrier detect line, if +12 V is used on the carrier detect optocoupler and then run to the carrier detect output on the radio, the optocoupler will always be driven. There are several ways to get around this: Use a radio without an internal pull up to +5 V (Trio SR, possibly Tait) Modify the radio by removing the internal pull up, as per manufacturer's instructions. Use +5 V to supply the carrier detect optoisolation circuit. (DO NOT USE +5 V FROM THE BACKPLANE UTILUX CONNECTOR AS IT IS NOT ISOLATED) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 225 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2-Wire Line, point-to-point Either RTU can transmit/receive one at a time. Note line termination is required. 2-Wire Line, multi-drop Any RTU can transmit/receive one at a time. Note line termination is required. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 226 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4-Wire Line, point-to-point Either RTU can transmit/receive at any time. 4-Wire Line, multi-drop Master RTU can transmit/receive to any one outstation RTU at any time or each outstation can transmit/receive to master RTU, one at a time. Note that outstations cannot communicate to each other. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 227 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Line/Radio Option Board Specifications Baud rate 1200 Baud Modulation FSK, CCITT V.23 Carrier detect input Optical isolation Active low or high Min. input 2 mA (70 VDC max.) RTS/PTT output Optical isolation Open collector output Active low 30 VDC max @ 20 mA max. Microwave networks typically use a negative supply rail for the carrier detect circuit. The more positive rail should be connected to pin #6 (RTS/PTT) and the difference between the rails must not exceed 30 VDC. Output impedance 30 k Input impedance 30 k Line termination 600 Line configuration 2 or 4 wire The port is not full duplex and cannot use the full duplex functionality of a 4-wire configuration. 4-wire configurations eliminate the ability to communicate peer to peer but allow an increased number of drops on one link. Line driv e in multi-drop 10 drops for 2 wire configuration 20 drops for 4 wire Transmit output lev el -6 dBm (LINE-2) -6 to 21 dBm software configurable (LINE-L) Receive level -43 dBm to -9 dBm Internal Power Consumption 85 mA from +5 VDC Bus on backplane Transmission Distance Allowing 3dB for background noise and a 10dB fade margin, up to 24dB of cable loss can be tolerated. Therefore, transmission distance = 24 / cable loss per Km (dB). Note: if there are more than 2 RTUs (or other devices) on the line, reduce the allowable cable loss (24) by 1dB per additional RTU or device. Isolation Operating Temperature Maximum working voltage in respect to system earth/ground must not exceed TNV-2 limits (80 V) Transient voltage: 3.88 kV -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/21/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 228 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.5. Option Board H: HART Interface The HART option board provides a Bell 202 interface to devices supporting the HART protocol. Each HART option board can communicate with up to 15 Hart devices. Two HART option boards can be installed on the one RTU allowing up to 2 point-to-point circuits or 2 multi-drop circuits. In a point-to-point installation, the loop current can be measured using an RTU analogue input channel. If using two separate point to point circuits and reading the loop current in each, the RTU analogue input channels must be isolated from each other. In a multi-drop installation, the loop current is not used or measured. For more information regarding HART configurations please refer to the HART Implementation Guide available on MyKingfisher. HART Board Connections RJ45 Pin 1 2 to 8 8 HART Function Line + Not Connected Line - Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 229 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Point-to-point Wiring Configuration (Utilizing Analogue Input) Note resistor should be approximately 500 . Multi-drop Wiring Configuration Note the more HART devices connected, the closer the resistor value needs to be to 50 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 230 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Hybrid Wiring Configuration When using multiple HART networks on a single RTU, be sure to isolate the 24 V supplies. HART Option Board Specifications Baud-rate 1200 Baud, Half Duplex Modulation Bell 202 Logical Frequencies 1 = 1200 Hz 0 = 2200 Hz Internal Power Consumption 1 mA from +5 VDC Bus on backplane Maximum No. HART Devices 15 (multi-drop) Data Available HART and loop current for point-to-point HART only for multi-drop Isolation Operating Temperature Maximum working voltage in respect to system earth/ground must not exceed TNV-2 limits (80 V) Transient voltage: 3.88 kV -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 2 or Port 3 MC-30/31 Port 2 or Port 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 231 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.6. Option Board T3: 10/100 Ethernet Controller The T3 Ethernet Option Board provides Ethernet connectivity via the W5300 chipset allowing full MAC & TCP/IP integration, and simultaneous connection to 8 separate sockets with automatic negotiation. T3 Ethernet Option Board Specifications Connection Speed 10/100 auto negotiated (up to 50 Mbps actual) Max Simultaneous S ockets 8 (with 0 ~ 64 KByte memory for data allocation) Connection Durability Approximately 750 cycles Operating Temperature 0 to 70 °C Storage Temperature -40 to85 °C Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 2 or Port 3 MC-30/31 Port 2 or Port 3 6.7. Option Board A3:Fibre Optic Ethernet The A3 option board provides Ethernet connectivity via fibre optic cable. The A3 is functionally equivalent to a T3 Ethernet board, but fibre optical cabling is used in place of copper cabling allowing for excellent electrical isolation. A3 Ethernet Option Board Specifications Connection Speed 10/100 Mbps Optical Compliance Full ATM 100 Mbps physical layer Full 100 Mbps-FX (IEEE802.3u) Fiber Optic Transceiver AFBR-5903Z Supported Fiber Opt ic Cables Multimode 50/125 um, 62.5/125 um, 100/140 um, and 200 um HCS Option Board Connectors (use male connectors on cable) Tx: ST female (light grey port) Rx: ST female (dark grey port) Supported Fiber Opt ic Cables Multimode 50/125 um, 62.5/125 um, 100/140 um, and 200 um HCS Option Board Connectors (use male connectors on cable) MTRJ connector. Available from Semaphore are the MTRJ-SC and MTRJ-ST adaptors. Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 2 or Port 3 MC-30/31 Port 2 or Port 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 232 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.8. Option Board R2: Australian Spread Spectrum Radio The R2 Spread Spectrum radio option board uses the MaxStream 900 MHz RF module to provide a high speed data link in Australia. This radio uses the public frequency band and does not need to be licensed. When installed in a Communications or processor, the corresponding port CD (Carrier Detect) LED will be lit when the board is functioning correctly (weather antenna is connected or not). RF Exposure 900 MHz Spread Spectrum Radio This equipment is approved only for mobile and base station transmitting devices. Antenna(s) used for this transmitter must be installed to provide a separation distance of at least 30 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter. Modifications Use of unauthorised antenna or other changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this product. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 233 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual R2 Spread Spectrum Radio Board Specifications Countries Supported Australia Frequency 902-928 MHz Transmit P ower 1-1000 mW configurable Range Indoors 900 m Range Outdoors 22 km Range with Yagi Up to 32 km Data rate -- RTU to Radio 9600 bps Data rate -- Radio to Radio 115200 or 9600 bps Power Consumption 3.7W maximum Spread Spectrum Type FHSS (Frequency Hopping Spread Spectrum) Encryption None # Antenna Connector RPSMA (reverse polarity SMA) Male (on radio) Receiver Sens itivity -110 dBm @ 9600 bps Operating Temperature -20 to 70 °C Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 234 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.9. Option Board R3: International Spread Spectrum Radio The R3 Spread Spectrum radio option board uses the 2.4 GHz RF module to provide a high speed data link anywhere in the world (international). This radio uses the public frequency band and does not need to be licensed. When installed in a Communications or processor, the corresponding port CD (Carrier Detect) LED will be lit when the board is functioning correctly (weather antenna is connected or not). RF Exposure 2.4 GHz Spread Spectrum Radio This equipment is approved only for mobile and base station transmitting devices. Separation distances of (i) 20 centimetres or more for antennas with gains < 6 dBi or (ii) 2 meters or more for antennas with gains > 6 dBi should be maintained between the antenna of this device and nearby persons during operation. To ensure compliance, operation at distances closer than this is not recommended. Modifications Use of unauthorised antenna or other changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this product. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 235 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual R3 Spread Spectrum Radio Board Specifications Countries Supported International Frequency 2.4000-2.4835 GHz Transmit Power 50 mW Range Indoors 180 m Range Outdoors 5 km Range with Yagi Up to 8 km Data rate -- RTU to Radio 19200 bps Data rate -- Radio to Radio 9600 bps Power Consumption 0.75W maximum Spread Spectrum Type FHSS (Frequency Hopping Spread Spectrum) Encryption None # Antenna Connector RPSMA (reverse polarity SMA) Male (on radio) Receiver Sens itivity -105 dBm Operating Temperature -20 to 70 °C Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 3 only MC-10/11/30/31 Port 3 only LP-2 Port4 LP-3 Port 3 or Port 4 # Encryption by special request in the USA only. Please see www.digi.com/products/wireless for more information. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 236 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.10. Option Board R4: US/Canada Spread Spectrum Radio The R4 Spread Spectrum radio option board uses the MaxStream 900 MHz RF module to provide a high speed data link in the US and Canada. This radio uses the public frequency band and does not need to be licensed. When installed in a Communications or processor, the corresponding port CD (Carrier Detect) LED will be lit when the board is functioning correctly (weather antenna is connected or not). RF Exposure 900 MHz Spread Spectrum Radio This equipment is approved only for mobile and base station transmitting devices. Antenna(s) used for this transmitter must be installed to provide a separation distance of at least 30 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter. Modifications Use of unauthorised antenna or other changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this product. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 237 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual R4 Spread Spectrum Radio Board Specifications Countries Supported US & Canada Frequency 902-928 MHz Transmit P ower 1-1000 mW configurable Range Indoors 900 m Range Outdoors 22 km Range with Yagi Up to 32 km Data rate -- RTU to Radio 9600 bps Data rate -- Radio to Radio 115200 or 9600 bps Power Consumption 3.7W maximum Spread Spectrum Type FHSS (Frequency Hopping Spread Spectrum) Encryption None # Antenna Connector RPSMA (reverse polarity SMA) Male (on radio) Receiver Sens itivity -110 dBm @ 9600 bps Operating Temperature -20 to 70 °C Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Compatibility Can be installed in any of the following ports: CP-10/11/30 Port 2 or Port 3 MC-10/11/30/31 Port 2 or Port 3 LP-1/2 Port4 LP-3 Port 3 or Port 4 # Encryption by special request in the USA only. Please see www.digi.com/products/wireless for more information. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 238 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7. PC-1 Option Boards The PC-1 hybrid power supply and processor module has an accompanying range of communications option boards. These are not compatible with the CP series boards. 7.1. PC-1 Serial Option Board The serial option board provides a RS-232 or RS485 interface. The port is software configurable for either of these modes. When RS485 is used, a 120 terminating resistor is required at each end of the transmission line. PC-1 Serial Board Connections RJ45 Pin 1 2 3 4 5 6 7 8 Direction OUT OUT OUT IN COM IN IN OUT RS-232 DTR +12 V low power RTS DCD GND (0 V) CTS RXD TXD RS485 N/A N/A LINE - * N/A GND (0 V) N/A N/A LINE + * * Polarity is opposite to CP-xx For RS485 wiring diagram please refer to CP-xx/MC-xx serial board RS486 Diagrams Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 239 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.2. PC-1 Modem Board PL: Two Wire Line The 2-wire (Private) line option board provides a 2-wire point-to-point connection to another RTU with a line option board. The board is optically isolated, operates at 1200 bps and utilizes FSK CCITT V.23 modulation. PC-1 Modem Board Connections RJ45 Pin 1 2 3 4 5 6 7 8 Direction OUT OUT OUT IN COM IN IN OUT Radio Function DTR +12 V low power RTS DCD GND (0 V) CTS RXA TXA * Polarity is opposite to CP-xx PC-1 2 Wire Line Wiring Diagram (point-to-point) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 240 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.3. PC-1 Modem Board: Analogue Radio Interface The analogue radio option board provides an FSK interface to external analogue radios (typically Maxon or Trio). When used with a Trio radio, one of the resistors must be factory modified. PC-1 Analog Radio Board Connections RJ12 Pin 1 2 3 4 5 6 7 8 Direction OUT OUT OUT IN COM IN IN OUT Radio Function DTR +12 V low power RTS DCD GND (0 V) CTS RXA TXA Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 241 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 8. Compatibility Not all option boards are universally compatible with all processors and communications modules. The following tables are a selection guide for assuring the hardware you have selected will function as expected. Communications Option Boards CPU/Comms Module A A3 D E F H I J L R2 R3 R4 T T2 T3 CP-30 2676 firmware MC-31 2676 firmware MC-30 276 firmware CP-10/11 1.45b firmware CP-10 previous firmware CP-12 CP-21 MC-10/11 MC-11 V160 Firmware MC-12 PC-1 with MC-10/11 PC-1 with MC-12 Note: The above table was correct at the time of writing. Please refer to MyKingfisher for any recent changes. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 242 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9. Analogue Input Modules Analogue input modules provide analogue inputs to the Kingfisher RTU. Each module is equipped with a fully isolated 24 VDC power supply for energizing field equipment such as sensor loops. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 243 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.1. AI-1: 8 Channel Analogue Current Input Module · 12 Bit resolution · 1.5 kV Field to Logic Isolation · 2 ms scan rate · 24 VDC isolated DC output · 0 -- 20 mA or 4 20 mA current inputs · 0 5 VDC or 1 5 VDC Voltage Inputs (requires factory modification) The analogue input module provides eight input channels, each capable of converting an analogue input signal to a digital variable for use as required by your application. A link on the rear of the module selects 4-20 mA or 0-20 mA for all 8 channels. The default range is 4 to 20 mA. The module can also be factory modified to handle voltage inputs of 0-5 VDC or 1-5 VDC. Conversion speed for each of the eight channels is 20 µs and this provides a total update rate of two milliseconds for the module. Resolution of the converted signal is 12 bits binary (1 part in 4096) over the range. The placement of the 12 bits from the A/D converter in the #AI data word is as follows: LSB MSB 0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0 If the current source is reversed into the input, or is less than the low end of the current range, then the module will output a data word corresponding to the low end of the current range (0000H in #AI). If an input that is out of range is entered (i.e. greater than 20 mA), the A/D converter will output up to full scale (corresponding to 7FF8H in #AI). Scaling of the input is shown below: Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 244 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Input protection for the module is sufficient to guarantee operation with reduced performance with up to 1500 V common-mode. The module provides electrical isolation of externally generated noise between field wiring and the backplane through the use of optical isolation. To minimise the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields can be connected to GND. The GND connection provides access to the backplane (frame ground). This module can be installed in any I/O slot of a 4, 6 or 12-slot backplane. Up to 10 Analogue Current Input modules can be installed on a single 12-slot backplane. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 245 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AI-1 Module LEDs LED OK FU A1-A8 State OFF ON OFF ON OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Channel Input level < 1% Channel Input level > 1% Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 246 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AI-1 Analogue Input Module Specifications Input Current Ranges 4-20 mA and 0-20 mA Input Voltage Ranges 1-5 V and 0-5 V * Inputs per Module Calibration 8 Factory calibrated to 5µA Update Rate 2 ms (all eight channels) Accuracy + 0.25% @ 25°C Resolution 12 bit (no sign bit) Common Mode Voltage 1500 V Linearity < 1 Least Significant Bit Isolation 1.5 kV between field and logic Common Mode Rejection > 70 dB at DC; >70 dB at 60 Hz Cross-Channel Rejection > 80 dB from DC to 1 kHz Input Impedance 250 standard 11 k optional *. The internal load resistors can be factory removed if high impedance voltage inputs are required. Input Filter Response 2 kHz Output Power 24 VDC @ 400 mA Isolated (10 W) Operating Temperature -20 to 70°C Storage Temperature -40 to +85°C Operating Humidity 5 to 98% RH non-condensing Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Inputs are cleared in RTU memory while module is removed. * Analogue inputs can be modified from current inputs to voltage inputs by lifting one leg of the 250 channel resistor. Each channel has its own resistor, so any combination of channels can be converted. It is recommended that modules be returned to Semaphore for factory conversion if required. No responsibility will be taken by Semaphore for damage caused to boards during modification performed by clients. The circuit board resistors to change are: channels 1 -- 8 = R9 -- R16. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 247 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AI-1 Wiring Diagram 2 wire transmitter (powered by module) 3 wire transmitter (powered by module) 4 wire transmitter (powered by module) 2 wire transmitter (powered externally) 3 wire transmitter (powered externally) 4 wire transmitter (powered externally) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 248 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.2. AI-10: 8 Channel High Impedance Analogue Input Module · 16 Bit resolution · 5 kV field to logic isolation · Channel to channel isolation · 24 VDC isolated DC output · AI-10: Current / Low Impedance Inputs · AI-10-V: High Impedance Voltage Inputs · 10 ms scan rate The AI-10 and AI-10-V modules are identical except the AI-10-V has the 250 sensing resistors removed. This increases the input impedance for each channel to more than 1 M which is suitably high for voltage transducers. Both modules provide: · 8 analogue inputs with high electrical isolation between the field terminals and the RTU logic. · A 24 V isolated output that can be used to power field sensors / transducers · 16 bit input resolution · Full compatibility with the AI-1 and AI-4 analogue input modules. However, the resolution has been enhanced to provide a positive raw scale range of 0-32767 (AI-1 and AI-4 use 0-32760) The AI-10 supports various current and voltage input ranges as follows: · 4-20 mA / 1-5 V · 0-20 mA / 0-5 V · ±10 V · ±20 mA / ±5 V · ±10 mA / ±2.5 V The AI-10-V supports various voltage input ranges as follows: · 1-5 V · 0-5 V · ±10 V · ±5 V · ±2.5 V Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 249 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual To minimize the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields can be connected to ground. This module consumes power from the +5 VDC and +12 VDC RTU rails. A 24 V DC-DC converter mounted within the module is used to provide isolated power to the analogue front-end and to provide power to the field devices as required. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Up to 11 Analogue Input modules can be installed on each backplane. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 250 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AI-10 Module LEDs AI-1 LEDs OK * DC OK 1-8 (left side) 1-8 (right side) State OFF ON One second flash* OFF ON OFF ON OFF ON Description Module Fault (no power) Module OK Module Fault AI-10 loop power OFF AI-10 loop power ON Channel Input level < 1% Channel Input level > 1% Channel Normal Channel Fault (under/over range, data invalid) * Early revision modules used ON (a very fast flash) for module OK and steady ON for module fault. Note: On power up some LED's may come on for a short time. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 251 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IA-10 / AI-10-V Analogue Input Module Specifications Input Current ranges 4-20, 0-20, +10, +20 mA (software selectable) (AI-10 only) Input Voltage ranges * 1-5, 0-5, +2.5, +5, +10# VDC (software selectable) Inputs per Module 8 Sub System Isolation The analogue subsystem of the AI-10 is fully isolated from the RTU's digital system. Isolation 3 kV Transient Input impedance AI-10: 250 standard, > 1 M optional* AI-10-V: > 1 M Maximum Input Voltage +12 V on 10 V range, +7 V on other ranges Accuracy ± 0.1% @ 25 °C. ± 0.25% @ -20 to 70 °C Resolution 16 bit (15 data bits and 1 sign bit) Scanning Rate 10 ms per channel max. Input Protection The input multiplexer integrated circuits are designed to withstand pulses of up to 100 V Output Power Isolated 24 VDC @ 160 mA Operating Temperature -20 to 70°C Storage Temperature -40 to +85°C Operating Humidity 5 to 98% RH non-condensing Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Inputs are cleared in RTU memory while module is removed. Compatibility One range setting for all channels when used with a PC-1 or CP-11/12/21 processor. Individual range setting for each channel when used with a CP-30 processor. * Analogue Input channels can be modified from low impedance to high impedance by lifting one leg of the 250 channel resistor. Each channel has its own current sensing resistor, so any combination of channels can be converted. It is recommended that modules be returned to Semaphore for factory conversion if required. No responsibility will be taken by Semaphore for damage caused to boards during modification performed by clients. The circuit board resistors to change are: channels 1 to 8 = R64 to R71. # the +10 V input range can only be used on an AI-10 input channel if the current sensing resistor has been removed. Resistors have already been removed in an AI-10-V. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 252 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AI-10 / AI-10-V wiring diagram 2 wire transmitter (powered by module) 3 wire transmitter (powered by module) 4 wire transmitter (powered by module) 2 wire transmitter (powered externally) 3 wire transmitter (powered externally) 4 wire transmitter (powered externally) Loop * When using the +24 V output to power a transducer, the negative input terminal of the analogue input channel (2, 4, 6, 8, 12, 14, 16 or 18) must be wired to the OV terminal (10 or 20). This will complete the current loop due to electrical isolation between the input channel and the module +24 V Output. Note: Any channels sharing the same power source (e.g. +24 V from module or a field power supply) are no longer isolated from one other. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 253 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10. Analogue Output Module The AO-3 analogue output module provides four 12 bit differential outputs allowing a Kingfisher RTU to drive analogue loads. 10.1. AO-3: Analogue Output Module · 12 bit resolution · 3 kV field to logic isolation · Open loop detection · 0 20 or 4 20 mA outputs · 3 kV channel group to channel group isolation The AO-3 provides four current output channels that use 12-bit digital to analog converters (DAC). The AO-3 also provides open loop detection. The sign bit is not used in the digital to analog conversion process. The placement of the 12 bits within the data word is as follows: LSB MSB 0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0 This module provides two output ranges. The default range is 4 to 20 mA with user data scaled so that a count of 0 corresponds to 4 mA and a count of 32760 corresponds to 20 mA. A range link (on the rear of the module) selects either 4-20 mA or 0-20 mA for all four channels. The default condition is 4-20 mA with the link on. The module provides 12 bits of resolution in either range. Scaling of the output is as shown below. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 254 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Analogue outputs 1 & 2 and analogue outputs 3 & 4 form two groups that are isolated from each other and from the backplane logic. Each group is powered by a separate DC-DC converter module that produces an isolated voltage of +24 V to drive the current loop outputs and analog front-end. The current loop drivers on the module are source type drivers. To minimize the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields should be connected to E (Shield) on the user terminal connector block. The E connection provides path to the backplane (frame Earth / Ground) resulting in attenuation of noise caused by the shield drain currents. To further improve noise immunity, direct connection of the analog cable shields to the Earth / Ground rails with metal clamps or similar method is recommended, especially in environments with high electromagnetic noise levels. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane in a system. This module can be installed in any I/O slot of a 4, 6 or 12-slot backplane. Up to 10 Analogue output modules can be installed on a single 12-slot backplane. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 255 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AO-3 Module LEDs AO-3 LEDs OK RST ANALOG OUT 1-4 OPEN LOOP 1-4 State OFF ON OFF ON OFF ON OFF ON Description Module fault / no power Normal Module running Module in Reset (power-on or watchdog) Channel output set to 0% Channel output greater than 0% Closed Loop (load detected) Open Loop (no load) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 256 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AO-3 Analog Output Module Specifications Output Current Range 4 to 20 mA [default] or 0 to 20 mA (loop current is supplied by module) Outputs per Module 4 Output Power Isolated 24 VDC @ 40 mA for outputs 1 & 2 Isolated 24 VDC @ 40 mA for outputs 3 & 4 Supply Voltage (nominal) +5 VDC and +12 VDC from backplane Update Rate 250 ms (all channels) Determined by I/O scan time and is application dependent Resolution 12 bit (no sign bit) Accuracy ± 0.2% @ 25 °C ± 0.5% @ -20 to 70 °C Load Resistance 0 to 850 Load Capacitance, max 2000 pF Load Inductance, max 1 H Isolation Analog outputs 1 & 2 and analog outputs 3 & 4 form two groups. Each group is isolated from the other group and from the backplane logic. There is no isolation between outputs 1 & 2 and no isolation between outputs 3 & 4. Transient voltage (Group to Group and Group to Logic): 5 kV Maximum working voltage in respect to system earth/ground must not exceed SELV limits (42.4 Vpeak / 60 VDC) Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 90% RH non-condensing Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. Open Loop Detection Yes. Monitors output circuit for failure (e.g. cable breakage) or if the load is disconnected. Note: when using the 0-20 mA range, Open Loop Detection cannot be guaranteed on an output when set below 160 / 0.1 mA / 0.5%. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 257 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AO-3 wiring diagram 0 20 / 4 20 mA Current Loop Receiver Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 258 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11. Digital Input Modules The Digital Input Modules allow various level digital signals to be interpreted by your RTU. All modules provide a minimum of 1 kV field isolation, 16 input channels and can be configured to use counters and input buffers to count incoming pulses. Summary: Module Max input Voltage 10 to 28 VDC D I-5-1 (supports reverse polarity) 30 to 60 VDC D I-5-1-48 (supports reverse polarity) DI-10-1 +10 to +110 VDC 20 126 VAC 35 to 130 VDC DI-10-1-48 27 260 VAC Channel group 1 capture speed Channels 1 and 2 10 kHz max Channels 1 and 2 10 kHz max Channels 1 to 4 10 kHz max Channels 1 to 4 10 kHz max Channel group 2 capture speed Channels 3 and 4 255 Hz max Channels 3 and 4 255 Hz max Channels 5 to 16 1 kHz max Channels 5 to 16 1 kHz max Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 259 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11.1. DI-5: DC Input 16 Channel Digital Input Module · Pulse counting on channels 1 to 4 (up to 10 kHz) · Positive or Negative Polarity Inputs · Isolated DC Outputs for powering inputs The DI-5 provides 16 input channels with one common. As a wide input voltage is accepted a wide range of input devices can be used such as buttons, red switches, line switches, PIR sensors, and proximity sensors. Any combination of inputs powered externally or by the modules own isolated DC supply (+12 V) can be used. Applying a high input voltage results in logic 1 in the modules status register. Low (or not present) input voltages result in logic 0. The DI-5 counter can also count pulses in the first 4 digital inputs. It is able to count up to 10 kHz on inputs 1 and 2 and can count up to 255 Hz on inputs 3 and 4. The pulse total and the frequency for each of the first 4 digital inputs are stored. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane system. The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is colour-coded red to indicate a highvoltage module. (Note the DO-5 module differs from the image shown to the left) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 260 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DI-5 Module LEDs LED OK 1 - 16 State OFF ON OFF ON Description Module fault (no power) Normal Digital Input OFF Digital Input ON Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 261 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-5 Isolated Relay Output Module Specifications Rated Voltage + 12 to 24 VDC nominal (supports reverse polarity) Note: The DI-5-1-48 High Input Voltage module in the Custom Products chapter supports higher DC input voltages (48 VDC nominal) Inputs per Module 16 Input Characteristics Impedance 2.7 k On-state Voltage Chs 1&2: 10 to 28 VDC maximum Chs 3-16: 7.5 to 28 VDC maximum Off-state Voltage Chs 1&2: 0 to 3.5 VDC Chs 3-16: 0 to 3.0 VDC On-state Current 4.3 mA minimum Off-state Current 1 mA maximum On response Time Channels 1 and 2: 50 µs maximum Channels 3 and 4: 500 µs maximum Channels 5 to 16: 10 ms maximum Off response Time Channels 1 and 2: 50 µs maximum Channels 3 and 4: 500 µs maximum Channels 5 to 16: 17 ms maximum Isolation 5 kV Transient Output Power 12 VDC @ 250 mA (3 W) isolated, supplied by module Operating -20 to 70 °C Temperature Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Pulse Tantalization Channels 1 to 4: 0-65535 Pulses Pulse Rates / Channels 1 and 2: 10 kHz maximum Frequency Channels 3 and 4: 255 Hz maximum Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Inputs are cleared in RTU memory while module is removed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 262 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DI-5 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 263 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11.2. DI-10: AC or DC Input, 16 Channel · Frequency/Pulse/Quadrature counters (on up to 7 input pairs) · Isolated DC Field Output · Software Debounce · AC or DC Inputs · Sequence of event recording The DI-10 provides 16 AC or DC input channels allowing it to interface a wide range of input devices to your RTU. Inputs can be powered by the modules own +12 VDC Output Power or from AC or DC field voltages. Applying a high input voltage results in a logical 1 in the status register, no or low input voltage results in a logical 0. The DI-10 features software configurable pre-conditioning of inputs such as debounce filters, channel inversion and sequence-of-event recording selectable on any channel(s). The DI-10 can also perform frequency or pulse counting for up to 7 pairs of input channels. The DI-10 module provides all the functionality of the DI-1 and DI-5 modules except the input voltage cannot be reversed. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane system. The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is colourcoded red to indicate a high-voltage module. (Note the DO-10 module differs from the image shown to the left) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 264 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Configurable Functions The fist 4 channels of the DI-10 are high speed and capable of counting up to 10kHz, while channels 5 to 16 can count up to 1 kHz. Seven user configurable counter inputs are available which appear as 16-bit unsigned integer values in the analogue input register. Each of these counters can be configured to determine frequency, count pulses, or quadrature counters which work with quadrature inputs or pairs of channels. Channel inversion can be configured on any input channel. Normally a high voltage level results in a logical HIGH state (1) to be set in the digital input register with the corresponding LED illuminating on the front panel. By enabling channel inversion, a low voltage level applied to an input will result in a logical HIGH (1). Software debounce can be activated on any input channel. The time constant can be configured from 1 ms to 250 ms. When using software debounce with AC inputs, the input channel must be configured with the debounce filter set to `AC Filter' as shown below. Sequence of Events Recording Sequence-of-Event (SoE) recording can be configured for any input channel. When enabled, any change of state (event) on the input is logged to 1 millisecond accuracy. These events are automatically included in the Event Log of the RTU. The DI-10 module has an internal timer that is synchronized with the Real Time Clock of the processor. The DI-10 module has a buffer capable of storing 1000 events. This means bursts of up to 1000 events can be recorded at a time. Events are uploaded to the processor module at a maximum rate of 100 events per second. Please note that SoE recording is not supported when using a PC-1 processor. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 265 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DI-5 Module LEDs LED OK PCON 1 - 16 State OFF ON OFF ON OFF ON Description Module fault (no power) Normal DI-10 Output Power OFF DI-10 Output Power ON Digital Input OFF Digital Input ON Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 266 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DI-10: AC or DC Input, 16 Channel Rated Voltage +10 to +110 VDC nominal 20 to 125 VAC Inputs per Module 16 Input Characteristics Impedance 1.2 k approx. On-state Voltage 7.5 to 130 VDC maximum 20 to 125 VAC Off-state Voltage 0 to 3.0 VDC On-state Current 3.5 mA minimum Off-state Current 1 mA maximum On response Time Channels 1 to 4: 50 µs maximum Channels 5 to 16: 500 µs maximum Off response Time Channels 1 to 4: 50 µs maximum (DC) Channels 5 to 16: 500 µs maximum (DC) Channels 1-16: 30 ms (AC) Isolation Maximum working voltage in respect to system earth/ground must not exceed 125 VAC or 130 VDC Transient voltage: 3 kV Output Power 12 VDC @ 80 mA (1 W) isolated, supplied by module Operating -20 to 70 °C Temperature Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Pulse Rates / Channels 1 to 4: 10 kHz maximum * Frequency Channels 5 to 16: 1 kHz maximum Frequency Counting 1 Hz resolution on any input(s) (7 counters max.) Pulse Totalisation 0-65535 Pulses on any input(s) (7 counters max.) Quadrature Counting 0-65535 Pulses on any of the following pairs of inputs: 1&2, 3&4, 5&6, 7&8, 9&10, 11&12, 13&14 and 15&16 (7 counters max.) Channel Inversion Selectable on any input(s) Debounce Filtering Time constant 1-250 ms on any input(s) or AC Filter (for AC inputs). 1 ms resolution Sequence of Events Buffering for 1000 events, uploaded to CPU at 100 events/second Selectable on any input(s) Yes. Module can be swapped while RTU is running. Hot swap will Hot Swap not cause a Warm Start. Inputs are cleared in RTU memory while module is removed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 267 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DI-10 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 268 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12. Digital Output Modules The digital output modules provide relay and transistor outputs to the Kingfisher series of RTUs. The DO-1 and DO-2 offer relay outputs, eight and sixteen respectively, while the DO-6 is transistor based. The DO-6 is compatible with the TEL-REL-00x series of relay output boards to allow for higher current and voltage switching. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 269 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MVTech_LT2003G_Origional.rar Switching Inductive Loads When switching inductive loads, users should be mindful of possible reduced relay life due to back-EMF. To mitigate this negative effect, suppression circuits should be used when switching inductive loads. Switching DC Supplied inductive loads (high switching relay output) Switching DC Supplied inductive loads (ground switching relay output) Switching AC supplied inductive loads (*MOV = Metal Oxide Varistor) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 270 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12.1. DO-1: 8 Channel Isolated Relay Output Module · 8 SPDT isolated relay outputs · 500 V channel pair isolation · One common per channel pair · Can switch AC or DC voltages · 3 kV coil to contact isolation The DO-1 provides 8 normally open or normally closed relay circuits for controlling output loads. All output channels are isolated from each other and arranged into pairs. Each channel pair shares a separate common terminal (see the wiring in this chapter for clarification). The relay outputs can control a wide range of user supplied load devices such as motors, starters, solenoids, and indicators. The user is required to supply the AC or DC power to operate the field devices connected to this module. Internal fuses offer protection to the relay contacts should their maximum load be exceeded. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is colour-coded red to indicate a highvoltage module. (Note the DO-1 module differs from the image shown to the left) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 271 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual D0-1 Module LEDs LED OK FU A1, A2 B3, B4 C5, C6 D7, D8 State OFF ON OFF ON OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 272 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-1 Isolated Relay Output Module Specifications Outputs per Module 8 Commons 4 (each common supplies 2 outputs) Relay Type SPDT (Single Pole, Double Throw) Rated Load (per contact) 5 A at 250 VAC Resistive 5 A at 30 VDC Resistive (20 A maximum per DO-1 module) Maximum Operating Voltage 380 VAC, 125 VDC Maximum Switching Power - 1250 VA, 150 W Resistive Maximum Switching Power - 375 VA, 80 W Inductive Minimum Load 10 mA at 5 VDC Relay Operations 100,000 minimum at 1800 operations per hour at rated load Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Isolation 3 kV coil to contacts 500 V between channel groups Coil Rated Voltage 12 VDC @ 16.7 mA Coil Resistance 480 @ 12 VDC Relay Part Number Omron G6B-2114P-US (G6B datasheet is available from www.europe.omron.com) Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 273 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-1 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 274 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12.2. DO-2: 16 Channel Relay Output Module · 16 SPST relay outputs · One common per 8 channels · 3 kV coil to contact isolation · Can switch AC or DC voltages The DO-2 provides 16 normally-open relay circuits for controlling output loads provided by the user. The output points are arranged in two groups of eight. Each group shares a common terminal. The relay outputs can be used to control a wide range of devices such as motor starters, solenoids, and indicators. Internal fuses protect the DO-2 relay contacts should ratings be exceeded. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is colour-coded red to indicate a highvoltage module. (Note the DO-2 module differs from the image shown to the left) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 275 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual D0-2 Module LEDs LED State OK OFF ON FU OFF ON 1-16 OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 276 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-2 16 Channel Digital Output Module Specifications Outputs per Module 16 Commons 2 (each common supplies 8 outputs) Relay Type SPST (Single Pole Single Throw, Normally Open) Maximum Switched Voltage 30 VDC, 250 VAC Maximum Switched Current 5 A per channel 7 A per common Minimum Load 10 mA @ 5 VDC (wetting current) Contact Resistance 100 m maximum Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Operating Humidity 5 to 98% RH non-condensing Isolation Maximum working voltage in respect to system earth/ground must not exceed 250 VAC / 130 VDC Transient voltage: 3 kV Relay Operations 70,000 minimum at 1800 operations per hour at rated load Fuse Monitor LED Enabled when the common is wired to pins 10 and 20. CAUTION! When wired, a maximum voltage of 30 V AC or DC can be used to power the common. Relay Part Number Omron G6D-1A-12VDC (G6D datasheet is available from http://www.europe.omron.com) Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see the beginning of the chapter Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 277 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-2 Wiring Diagram Note * Optional Link for DC Supply Only. Enables the use of fail LED FU. Caution: A maximum of 30 V (AC or DC) can be used to power the common if the link is installed. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 278 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12.3. DO-6: 16 Channel Open Drain Output Module · 16 Open-drain outputs · Designed to operate TELREL 00x relay board · DC Field Output (non-isolated) The DO-6 provides 16 open drain NFET outputs for controlling various loads including the TELREL series of relay boards. Power for external loads can be provided from the modules +12 VDC which is sourced from the backplane rail. The DO-6 output channels are current limited and are protected from high levels of EMI (electro-magnetic interference) that may trigger false outputs. This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. The insert in the hinged cover of the terminal strip has circuit wiring information. Circuit identification information can be recorded on the outside surface of the insert. The outside left edge of the insert is colour-coded red to indicate a highvoltage module. (Note the DO-6 module differs from the image shown to the left) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 279 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual D0-6 Module LEDs LED OK A1-A16 State OFF ON OFF ON Description Module fault (no power) Normal Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 280 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-6 Channel Open Drain Output Module Specifications Outputs per Module 16 Commons 1 Rated Voltage 30 VDC maximum. Output Type N-FET, Open Drain Rated Load 70 mA per channel Current Limit 90 mA per channel Output Power 12 VDC @ 1.6 A, non-isolated, supplied by module On Response Time 15 ms maximum Off Response Time 15 ms maximum Operating Temperature -20 to 70 °C Storage Temperature -40 to +85 °C Operating Humidity 5 to 98% RH non-condensing Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. Compatibility The DO-6 is functionally equivalent and pin compatible with the superseded DO-5. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 281 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-6 Wiring Diagram Note: The +12 V Output is sourced from the backplane power rail and is not isolated. Users should exercise caution to avoid shorting or overloading this output. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 282 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 13. Relay Expansion Boards The Kingfisher Relay Expansion Boards are designed to be used in conjunction to the DO-6 module. The relay boards allow much more flexible use of the DO-6 module due to the wide range of relay types available. Each relay board has unique internal wiring. Users should be mindful that they are not completely pin-compatible. Please refer to individual wiring diagrams for details. TEL REL 002 TEL REL 003 TEL REL 004 · 16 Channel Isolated Relay SPDT for DO-6-x complete with 1.5m cable · Max Voltage 380VAC, 125VDC, 16 commons, (1 common per channel) · Max Current 16A @ 250VAC resistive, 16A @ 30 VDC resistive, 0.45A @ 125 VDC Inductive. · 5kV isolation (Coil to Contact) · Omron G2R-1-E Relay · Relay Board - 16 Channel Isolated Relay SPST for DO-6-x complete with 1.5m cable · Max Voltage 380VAC, 125VDC, 16 commons, (1 common per channel) · Max Current 8A @ 250VAC resistive, 8A @ 30 VDC resistive 1A @ 125 VDC Inductive · 5kV isolation (Coil to Contact) · Omron G2RG-2A4-DC12 Relay · Relay Board - 16 Channel Isolated Relay DPDT for DO-6-x complete with 1.5m cable · Max Voltage 380VAC, 125VDC, 32 commons, (2 common per channel) · Max Current 5A @ 250VAC resistive, 5A @ 30 VDC resistive · 5kV isolation (Coil to Contact) · Omron G2R-2-12V Relay Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 283 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 13.1. TEL REL 002: SPDT Relay Board · 16 SPDT Relay Outputs · Common for each channel · 5 kV coil to contact isolation · Can switch AC or DC voltages The TEL REL 002 is designed to accompany the DO-6 to provide 16 SPDT voltage free output contacts. Each relay consumes 43 mA @ +12 VDC from the backplane power supply. An external supply can be connected to a screw terminal on the PCV is available (this is not the case if the standard cable supplied with the DO-6 modules is utilized). LED indicators are provided for each relay on the relay board. LED ON = relay active. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 284 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 002 SPDT Relay Boards Specifications Outputs per Terminal Board 16 Commons 16 (1 common per channel) Relay Type (per channel) SPDT (Single Pole, Double Throw) Rated Load (per contact) 16 A @ 250 VAC Resistive 16 A @ 30 VDC Resistive Maximum Operating Voltage 380 VAC, 125 VDC Maximum Switching Power - 16 A @ 30 VDC Resistive 5 A @ 48 VDC 0.6 A @ 125 VDC Maximum Switching Power Inductive 16 A @ 12 VDC 8 A @ 30 VDC 0.7 A @ 48 VDC 0.45 A @ 125 VDC Minimum Load 100 mA at 5 VDC Contact Resistance 100 m maximum Relay Operations 100,000 minimum at 1800 operations per hour at rated load Operating Temperature -20 to 70 °C (no icing) Storage Temperature -40 to +85 °C Humidity 5 to 98% RH non-condensing Isolation 5 kV coil to contacts Coil Rated Voltage 12 VDC @ 43 mA Coil Resistance 275 @ 12 VDC Dimensions 253 mm(L) x 90 mm(W) x 70 mm(H) (280 mm long with 2 end clamps) Mounting 35 mm DIN rail Interface cable length 1500 mm (for connection to the DO-6 module) Phoenix double height PCB terminal unit arranged in a Connection Terminals dual three way terminal (please see wiring diagram). These terminals can take wire sizes up to 4 mm2. Omron G2R-1-E Relay Part Number (datasheet is available from www.omroncomponents.eu) CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 285 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 002 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 286 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-6 to TEL REL 00x Interface Cable Fujicon DO-6 Pin DO-6 Outputs Belden 9431 Cable Color Panduit 20 way header pins 1 Channel 1 Black 1 2 Channel 2 White 2 4 Channel 3 Red 4 4 Channel 4 Green 4 5 Channel 5 Orange 5 6 Channel 6 Blue 6 7 Channel 7 White/Black 7 8 Channel 8 Red/Black 8 9 0 V Green/Black 9 10 0 V Orange/Black 10 11 Channel 9 Blue/Black 11 12 Channel 10 Black/White 12 13 Channel 11 Red/White 13 14 Channel 12 Green/White 14 15 Channel 13 Blue/White 15 16 Channel 14 Black/Red 16 17 Channel 15 White/Red 17 18 Channel 16 Orange/Red 18 19 + 12 VDC Blue/Red 19 20 + 12 VDC Green/Red 20 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 287 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 13.2. TEL REL 003: SPST Relay Board · 16 SPST Relay Outputs · Common for each channel · 5 kV coil to contact isolation · Can switch AC or DC voltages · Higher inductive rating than other TEL REL 002 (1 A @ 125 V as opposed to 0.4 A @ 125 V) The TEL REL 003 board is designed to be used in conjunction with the DO-6 (or superseded DO-5) and provides superior inductive load rating than the TEL REL 002. LED indicators are provided for each relay on the relay board. LED ON = relay active. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 288 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 003 SPST Relay Board Specifications Outputs per Terminal 16 Board Commons 16 (1 common per channel) Relay Type (per channel) SPST (Single Pole, Single Throw) Rated Load (per contact) 8 A at 250 VAC Resistive 8 A at 30 VDC Resistive 1 A at 125 VDC Inductive Maximum Operating 380 VAC, 125 VDC Voltage Maximum Switching 2000 VA, 240 W Power - Resistive Contact Resistance 100 m maximum Relay Operations 100,000 minimum at 1800 operations per hour at rated resistive load 50,000 minimum at 360 operations per hour at rated inductive load Operating Temperature -20 to 70 °C (no icing) Humidity 5 to 98% RH non-condensing Isolation 5 kV coil to contacts Coil Rated Voltage 12 VDC @ 66 mA Coil Resistance 180 @ 12 VDC Dimensions 253 mm(L) x 90 mm(W) x 70 mm(H) (280 mm long with 2 end clamps) Mounting 35 mm DIN rail Interface cable length 1.5 m (for connection to the DO-6 module) Connection Terminals Weidmuller single height PCB 3-way terminal unit (please see wiring diagram). These terminals can take wire sizes up to 4 mm2. Relay Part Number Omron G2RG-2A4-DC12 (datasheet is available from www.omroncomponents.eu) CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 289 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 003 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 290 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-6 to TEL REL 00x Interface Cable Fujicon DO-6 Pin DO-6 Outputs Belden 9431 Cable Color Panduit 20 way header pins 1 Channel 1 Black 1 2 Channel 2 White 2 4 Channel 3 Red 4 4 Channel 4 Green 4 5 Channel 5 Orange 5 6 Channel 6 Blue 6 7 Channel 7 White/Black 7 8 Channel 8 Red/Black 8 9 0 V Green/Black 9 10 0 V Orange/Black 10 11 Channel 9 Blue/Black 11 12 Channel 10 Black/White 12 13 Channel 11 Red/White 13 14 Channel 12 Green/White 14 15 Channel 13 Blue/White 15 16 Channel 14 Black/Red 16 17 Channel 15 White/Red 17 18 Channel 16 Orange/Red 18 19 + 12 VDC Blue/Red 19 20 + 12 VDC Green/Red 20 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 291 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 13.3. TEL REL 004: DPDT Relay Board · 16 DPDT relay outputs · 2 commons per channel · 5 kV coil to contact isolation · Can switch AC or DC voltages The TEL REL 004 is designed to be used in conjunction with the DO-6 (or superseded DO-5) and provides Double Pole Double Throw (DPDT) relays. This allows the user to utilize both normally open and normally closed relay operation. LED indicators are provided for each relay on the relay board. LED ON = relay active. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 292 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 004 DPDT Relay Board Specifications Outputs per Terminal Board 16 Commons 32 (2 commons per channel) Relay Type (per channel) DPDT (Double Pole, Double Throw) Rated Load (per contact) 5 A at 250 VAC Resistive 5 A at 30 VDC Resistive Maximum Current 5 A Maximum Operating Voltage 380 VAC, 125 VDC (2 A max.) Maximum Switching Power 750 VA, 90 W Resistive Minimum Load 10 mA at 5 VDC Contact Resistance 50 m maximum Relay Operations >10,000,000 Operating Temperature -20 to 70 °C (no icing) Humidity 5 to 98% RH non-condensing Isolation 5 kV coil to contacts Coil Rated Voltage 12 VDC @ 44 mA per coil Coil Resistance 275 @ 12 VDC Dimensions 253 mm(L) x 90 mm(W) x 70 mm(H) (280 mm long with 2 end clamps) Mounting 35 mm DIN rail Interface cable length 1.5 m (for connection to the DO-5/6 module) Relay Part Number Omron G2R-2-12 V (datasheet is available from www.omroncomponents.eu ) CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 293 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL REL 004 Wiring Diagram Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 294 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DO-6 to TEL REL 00x Interface Cable Fujicon DO-6 Pin DO-6 Outputs Belden 9431 Cable Color Panduit 20 way header pins 1 Channel 1 Black 1 2 Channel 2 White 2 4 Channel 3 Red 4 4 Channel 4 Green 4 5 Channel 5 Orange 5 6 Channel 6 Blue 6 7 Channel 7 White/Black 7 8 Channel 8 Red/Black 8 9 0 V Green/Black 9 10 0 V Orange/Black 10 11 Channel 9 Blue/Black 11 12 Channel 10 Black/White 12 13 Channel 11 Red/White 13 14 Channel 12 Green/White 14 15 Channel 13 Blue/White 15 16 Channel 14 Black/Red 16 17 Channel 15 White/Red 17 18 Channel 16 Orange/Red 18 19 + 12 VDC Blue/Red 19 20 + 12 VDC Green/Red 20 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 295 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14. Combination IO Modules Combinational IO modules provide digital and analogue IO in a single module. They can be installed in any 4, 6, or 12 slot backplane. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 296 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14.1. IO-2: Combinational Digital IO Module · 8 SPST relay outputs · Digital inputs This module can be installed in any slot of a 4, 6 or 12 slot backplane. Digital Inputs The digital inputs are designed to be powered using an external power supply. A wide range of digital input devices can be used such as push buttons, limit switches and electronic proximity switches. Current through an input (in either direction) results in a logic 1 in the status register. Power to operate the field devices must also be supplied by the user. Digital Outputs The output points are arranged in one group of eight points with one common. The output switching capacity of each output is 2 amps. The relay outputs can control a wide range of load devices such as motor starters, solenoids and indicators. Power for the internal relay circuits is provided by the +12 VDC bus on the backplane. The user must supply the AC or DC power to operate the field devices. An internal fuse protects the relay contacts should ratings be exceeded. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 297 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-2 Module LEDs LED OK FU A1-A8 B1-B8 State OFF ON OFF ON OFF ON OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Digital input OFF Digital input ON Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 298 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-2 Combinational IO Module Specifications Operating Temperature -20 to 70 °C Storage Temperature -40 to 85 °C Humidity 5 to 95% RH non-condensing Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. Inputs will be cleared while module is removed. DIGITAL INPUTS Rated Voltage 12 to 24 VAC/DC (can use reverse polarity) Inputs per Module 8 Input Characteristics On-state Voltage 11.5 to 30 VAC/DC maximum Off-state Voltage 0 to +4 VAC/DC On-state Current 3.2 mA minimum Off-state Current 1 mA maximum On response Time 10 ms typical Off response Time 17 ms typical Input Current 4 mA (typical) at rated voltage Isolation 3 kV between field and logic DIGITAL OUTPUTS Outputs per Module 8 Commons 1 (common supplies all 8 outputs) Relay Type SPST (Single Pole Single Throw) Rated Switched Voltage 24 VDC, 120/240 VAC Maximum Switched Voltage 30 VDC, 250 VAC Maximum Switched Current 5 A per channel 8 A per common Isolation 3 kV coil to contacts Minimum Load 10 mA @ 5 VDC Contact Resistance 100 m maximum Relay Operations 70,000 minimum at 1800 operations per hour at rated load Relay Part Number Omron G6D-1A-12 VDC (G6D datasheet is available from www.europe.omron.com) CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 299 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-2 Wiring Diagram Digital Input Example: (Note polarity can be reversed on power supply) Digital Output Example: * Optional link for DC SUPPLY ONLY. Enables fuse fail LED `FU' on module. CAUTION: when the link is installed a maximum of 30 V AC or DC can be used to power the common. Note: DC powered inputs and low voltage AC inputs can both be used on the same module. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 300 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14.2. IO-3: Combinational Analog/Digital IO Module · 4 SPST relay outputs · 4 analog inputs · 4 digital inputs · 1 analog output This module can be installed in any slot of a 4, 6 or 12 slot backplane. Analogue IO The IO-3 provides two signal ranges, 0 to 20 mA and 4 to 20 mA. The default range is 4 - 20 mA. A link on the rear of the module selects 4 - 20 mA (link installed) or 0 - 20 mA I/O for all channels. Resolution of the converted signals is 12 bits binary (1 part in 4096). The sign bit is not used in the conversion process. All channels are updated four times per second (250 ms refresh time). The placement of the bits within the data word is shown below. LSB MSB 0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0 Scaling of the input is shown below: All inputs share a single common and all outputs share a separate common at the zero volt rail. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 301 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Input protection for the module is sufficient to guarantee operation with reduced performance with up to 1500 V common-mode. The module provides electrical isolation of externally generated noise between field wiring and the backplane through the use of optical isolation. To minimise the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields can be connected to E. The E connection provides access to the backplane (frame ground). Digital IO Input characteristics are compatible with a wide range of user supplied input devices, such as push buttons, limit switches and electronic proximity switches, whilst outputs can control a wide range of user supplied load devices such as: motor starters, solenoids and indicators. Power for the internal relay circuits is provided by the +12 VDC bus on the backplane. The user must supply the AC or DC power to operate field devices. An internal fuse protects the relay contacts should ratings be exceeded. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 302 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-3 Module LEDs LED OK FU A1-A4 B1 C1-C4 D1-D4 State OFF ON OFF ON OFF ON OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Not used Not used Digital input OFF Digital input ON Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 303 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-3 Analogue/Digital Combinational IO Module Specifications Operating Temperature -20 to 70 °C Storage Temperature -40 to +85 °C Humidity 5 to 95% RH non-condensing Output Power 24 VDC @ 125 mA (3 W) Isolated Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. Inputs will be cleared while module is removed. ANALOG INPUTS Input Current Ranges 4 to 20 mA or 0 to 20 mA Input Voltage Ranges * 1 to 5 V and 0 to 5 V * Inputs per Module 4 Calibration Factory calibrated to 5 µA Update Rate 2 ms (all four channels) Accuracy + 0.25% @ 25 °C Resolution 12 bit (no sign bit) Linearity <1 Least Significant Bit Isolation Transient voltage: 1 kV Common Mode Rejection > 70 dB at DC; >70 dB at 60 Hz Cross-Channel Rejection > 80 dB from DC to 1 kHz Input Impedance 250 standard 15 k optional *. The internal load resistors can be factory removed if high impedance voltage inputs are required. Input Filter Response 325 Hz Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 304 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ANALOG OUTPUT Output Current Range Outputs per Module Calibration Supply Voltage (nominal) Update Rate Accuracy Resolution User Load Output Load Capacitance Output Load Inductance Isolation DIGITAL INPUTS Rated Voltage Inputs per Module Input Characteristics Input Current Isolation DIGITAL OUTPUTS Outputs per Module Commons Relay Type Maximum Switched Voltage Maximum Switched Current Isolation Minimum Load Contact Resistance Relay Operations Relay Part Number 4 to 20 mA or 0 to 20 mA 1 Factory calibrated to 68 µA pe r c ount +5 VDC and +12 VDC from backplane 250 ms (all channels) Determined by I/O scan time and is application dependent + 0.25% @ 25 °C 12 bit (no sign bit) 0 to 850 2000 pF 1 H 5 kV Transient 12 to 24 VAC/DC (can use reverse polarity) 4 On-state Voltage 11.5 to 30 VAC/DC maximum Off-state Voltage 0 to +4 VAC/DC On-state Current 3.2 mA minimum Off-state Current 1 mA maximum On response Time 10 ms typical Off response Time 17 ms typical 4 mA (typical) at rated voltage 5 kV Transient 4 1 (common supplies all 4 outputs) SPNO (Single Pole, Normally Open) 30 VDC, 250 VAC 4 A per channel 5 A per common 5 kV Transient 10 mA @ 5 VDC (wetting current) 100 m maximum 70,000 minimum at 1800 operations per hour at rated load Omron G6D-1A-12VDC (G6D datasheet is available from www.europe.omron.com) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 305 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. * Analogue inputs can be modified from current inputs to voltage inputs by lifting one leg of the 250 channel resistor. Each channel has its own resistor, so any combination of channels can be converted. It is recommended that modules be returned to Semaphore for factory conversion if required. No responsibility will be taken by Semaphore for damage caused to boards during modification performed by clients. The circuit board resistors to change are: channels 1 - 4 = R 39, R41, R43 and R45 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 306 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-3 Wiring Diagram * Optional link for DC SUPPLY ONLY. Enables fuse fail LED `FU' on module. CAUTION: when the link is installed a maximum of 30 V AC or DC can be used to power the common. Note: DC powered inputs are low voltage AC inputs can both be used on the same module. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 307 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Analogue Input Examples: 2 wire transmitter (powered by module) 3 wire transmitter (powered by module) 4 wire transmitter (powered by module) 2 wire transmitter (powered externally) 3 wire transmitter (powered externally) 4 wire transmitter (powered externally) Analogue Output Example: Analogue load Digital Input Examples: Sensing the output form a field contact Digital Output Examples: Driving external load from digital output Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 308 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14.3. IO-4: Combinational Analogue / Digital IO Module · 2 SPST relay outputs · 2 analogue inputs · 8 digital inputs This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Analogue IO The IO-3 provides two signal ranges, 0 to 20 mA and 4 to 20 mA. The default range is 4 - 20 mA. A link on the rear of the module selects 4 - 20 mA (link installed) or 0 - 20 mA I/O for all channels. Channel 1 can be utilized for a strain gauge input of range approximately 50 mV. 5 V excitation voltage is supplied from this module (please refer to the wiring diagram for further information). Resolution of the converted signals is 12 bits binary (1 part in 4096). The sign bit is not used in the conversion process. The placement of the bits within the data word is shown below. LSB MSB 0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0 Scaling of the input is shown below: All inputs share a single common and all outputs share a separate common at the zero volt rail. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 309 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Input protection for the module is sufficient to guarantee operation with reduced performance with up to 1500 V common-mode. The module provides electrical isolation of externally generated noise between field wiring and the backplane through the use of optical isolation. To minimise the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields can be connected to E. The E connection provides access to the backplane (frame ground). Digital IO Input characteristics are compatible with a wide range of user supplied input devices, such as push buttons, limit switches and electronic proximity switches, whilst outputs can control a wide range of user supplied load devices such as: motor starters, solenoids and indicators. Power for the internal relay circuits is provided by the +12 VDC bus on the backplane. The user must supply the AC or DC power to operate field devices. An internal fuse protects the relay contacts should ratings be exceeded. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 310 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-4 Module LEDs LED OK FU A1-A8 B1-B2 State OFF ON OFF ON OFF ON OFF ON Description Module fault (no power) Normal Fuse OK Fuse fail Digital input OFF Digital input ON Digital output OFF (open) Digital output ON (closed) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 311 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-4 Analogue / Digital Combinational Module Specifications Operating Temperature -20 to 70 °C Storage Temperature -40 to +85 °C Humidity 5 to 95% RH non-condensing Output Power 24 VDC @ 125 mA (3 W) Isolated Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. Outputs will be restored within 2 seconds once module is replaced. Inputs will be cleared while module is removed. ANALOG INPUTS Input Current Ranges 4-20 mA and 0-20 mA Input Voltage Ranges * 1-5 V and 0-5 V * Inputs per Module 2 Calibration Factory calibrated to 5 µA Update Rate 2 ms (all four channels) Accuracy + 0.25% @ 25 °C Resolution 12 bit (no sign bit) Common Mode Voltage 1500 V Linearity <1 Least Significant Bit Isolation 1000 VRMS between field and logic Common Mode Rejection >70 dB at DC; >70 dB at 60 Hz Cross-Channel Rejection >80 dB from DC to 1 kHz Input Impedance 250 standard 15 k optional *. The internal load resistors can be factory removed if high impedance voltage inputs are required. Input Filter Response 325 Hz Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 312 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DIGITAL INPUTS Rated Voltage 12 to 24 VAC/DC (can use reverse polarity) Inputs per Module 8 Input Characteristics On-state Voltage 11.5 to 30 VAC/DC maximum Off-state Voltage 0 to +4 VAC/DC On-state Current 3.2 mA minimum Off-state Current 1 mA maximum On response Time 10 ms typical Off response Time 17 ms typical Input Current 4 mA (typical) at rated voltage Isolation 1000 Vrms between field and logic DIGITAL OUTPUTS Outputs per Module 2 Commons 1 (common supplies both outputs) Relay Type SPST (Single Pole Single Throw) Maximum Switched Voltage 30 VDC, 250 VAC Maximum Switched Current 5 A per channel 8 A per common Isolation 3 kV coil to contacts Minimum Load 10 mA @ 5 VDC Contact Resistance 100 m maximum Relay Operations 70,000 minimum at 1800 operations per hour at rated load Relay Part Number Omron G6D-1A-12 VDC (G6D datasheet is available from www.europe.omron.com) CAUTION! Contacts should be protected with appropriate suppression devices when wired with inductive loads to increase life of relays (please see DO-1 Switching Inductive Loads). Contacts should also be protected with external fusing. * Analogue inputs can be modified from current inputs to voltage inputs by lifting one leg of the 250 channel resistor. Each channel has its own resistor, so any combination of channels can be converted. It is recommended that modules be returned to Semaphore for factory conversion if required. No responsibility will be taken by Semaphore for damage caused to boards during modification performed by clients. The circuit board resistors to change are: channels 1 - 2 = R85 & R41 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 313 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-4 Wiring Diagram * Optional link for DC SUPPLY ONLY. Enables fuse fail LED `FU' on module. CAUTION! When link is installed, a maximum voltage of 30 V AC or DC can be used to power the common Strain gauge input (4 wire Wheatstone bridge) 2 wire transmitter (powered by module) 3 wire transmitter (powered by module) 4 wire transmitter (powered by module) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 314 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2 wire transmitter (externally powered) 3 wire transmitter (externally powered) 4 wire transmitter (externally powered) Field contact input (externally powered) Driving digital load (externally powered) Passive field contact (powered by module) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 315 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14.4. IO-5: Combinational Analogue / Digital IO Module · 4 sinking solid state outputs · 4 analog inputs · 4 digital inputs · 1 analog output with open line detection This module can be installed in any I/O slot of a 4, 6 or 12 slot backplane. Analogue IO Input protection for the module is sufficient to guarantee operation with reduced performance with up to 1500 V common-mode. The module provides electrical isolation of externally generated noise between field wiring and the backplane through the use of optical isolation. To minimise the capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields can be connected to E. The E connection provides access to the backplane (frame ground). Resolution of the converted signals is 12 bits binary (1 part in 4096). The sign bit is not used in the conversion process. The placement of the bits within the data word is shown below. LSB MSB 0 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 0 0 0 Scaling of the input is shown below: All inputs share a single common and all outputs share a separate common at the zero volt rail. For analogue outputs, an Open Line Detection circuit will indicate whether current loop is open or closed. Please note that open line detection circuit performance cannot be guaranteed when AO value is set to less than 1% (328 decimal) of full scale in the 0-20 mA range. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 316 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The IO-3 provides two signal ranges, 0 to 20 mA and 4 to 20 mA. The default range is 4 - 20 mA. A link on the rear of the module selects 4 - 20 mA (link installed) or 0 - 20 mA I/O for all channels. Digital Inputs For high speed isolated digital inputs are provided on the module. All four digital inputs share on one common rail. All channels can be configured as pulse counters that appear 16 bit unsigned integer values in the analogue input registers of the RTU processor module. Because of processor module limitations, only channels 1 and 2 can be configured as pulse counters when used with the CP-11/12/21 and PC-1 processors (Toolbox32). All four channels can be used as pulse counters when used with CP-30 processor module (Toolbox PLUS+). Input characteristics are compatible with a wide range of user supplied input devices, such as push buttons, limit switches, Hall sensors, proximity switches, etc. Digital Outputs Input characteristics are compatible with a wide range of user supplied input devices, such as push buttons, limit switches and electronic proximity switches, whilst outputs can control a wide range of user supplied load devices such as: motor starters, solenoids and indicators. Power for the internal relay circuits is provided by the +12 VDC bus on the backplane. The user must supply the AC or DC power to operate field devices. An internal fuse protects the relay contacts should ratings be exceeded. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is colour-coded blue to indicate a low-voltage module. (Image for demonstration purposes only) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 317 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-5 Module LEDs LED OK RST 24Va AI 1-4 AO1 OL DI 1-4 DO 1-4 State OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Description Module fault (no power) Normal Module Reset in progress Field Power disabled Field Power enabled Analogue input is less or equal to 1% of range Analogue input is greater than 1% of range Analogue output is set to less or equal to 1% of range Analogue output is set to greater than 1% of range Analogue output line is closed (loaded) Analogue output line is open / loop current equal to zero Digital input OFF Digital input ON Digital output OFF (Output switch does not conduct) Digital output ON (Output switch conducts) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 318 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-5 Analogue / Digital Combinational Module Specifications Operating Temperature -20 to 70 °C Storage Temperature -40 to +85 °C Humidity 5 to 95% RH non-condensing Maximum Working 42.4 Vpeak / 60 VDC relative to system (backplane) ground Voltage on any contact of the field connector Hot Swap Yes. Module can be swapped while RTU is running. Hot swap will not cause a Warm Start. ANALOG INPUTS Input Current Ranges 4 - 20 mA or 0 - 20 mA Input Voltage Ranges * 1 - 5 V or 0 - 5 V * Inputs per Module 4 Resolution Unsigned 12 bit Accuracy (includes Gain, ± 0.25% @ 25 °C Linearity and Offset ± 0.50% @ -20 to 70 °C errors) Update Rate 120 ms Cross-Channel Rejection > 115 dB from DC to 1 kHz Input Impedance 250 standard 1 M optional *. The internal load resistors can be factory removed if high impedance voltage inputs are required. Input Filter Bandwidth (- 7 Hz 3 dB cut-off) AC noise attenuation 16 dB @ 50 Hz 18 dB @ 60 Hz Output Field Power 24 VDC @ 80 mA Isolated Isolation 5 kV Transient Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 319 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ANALOG OUTPUT Output Current Range 4 - 20 mA or 0 - 20 mA Outputs per Module 1 Output Type Isolated, Sourcing Resolution Unsigned 12 bit Update Rate 250 ms Determined by I/O scan time and is application dependent Accuracy (includes Gain, ± 0.25% @ 25°C Linearity and Offset errors) ± 0.50% @ -20 to 70 °C User Load 0 to 850 Isolat ion 5 kV Transient DIGITAL INPUTS Inputs per Module 4 with one common Input Type Optically isolated, Sinking Max Input Voltage 30 VDC Guaranteed On-state 10 VDC min Voltage Guaranteed Off-state 4.0 VDC max Voltage Counters Type Pulse, Unsigned 16-bit (all channels) Maximum Counters Speed 10 kHz Input Current Approx. (Vin / 4.7) mA: 2 mA @ 9.4 V in; 6.4 mA @ 30 V in Isolat ion 5 kV Transient DIGITAL OUTPUTS Outputs per Module 4 with one common Output Type Optically isolated, Solid State, Sinking Maximum Switched 30 VDC Voltage Maximum Switched 2 A per channel Current Isolat ion 5 kV Transient * Analogue inputs can be modified from current inputs to voltage inputs by lifting one leg or by the complete removal of the 250 channel resistor from the board. Each channel has its own resistor, so any combination of channels can be converted. It is recommended that modules be returned to Semaphore for factory conversion if required. No responsibility will be taken by Semaphore for damage caused to boards during modification performed by clients. The circuit board resistors to change are: Ch.1: R81 (or R85+R86); Ch.2: R82 (or R87+R88); Ch.3: R83 (or R89+R90); Ch.1: R84 (or R91+R92). Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 320 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual IO-5 Wiring Diagram Analogue Input Examples: 2 wire transmitter (powered by module) 3 wire transmitter (powered by module) 4 wire transmitter (powered by module) 2 wire transmitter (powered externally) 3 wire transmitter (powered externally) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 321 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4 wire transmitter (powered externally) Analogue Output Example: Analogue load Digital Input Examples: Sensing the output form a field contact Digital Output Examples: Driving external load from digital output Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 322 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 15. Adaptors and Cables A range of adaptor and cable accessories are available for the Kingfisher range to allow for communications interfacing. The adaptor plugs universally adapt to RJ45 to allow standard CAT5/6 cabling to be used between RTUs, PLCs and communications devices. Connectivity Example Reference Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 323 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Summary of available adaptors Part Number ADP-04 ADP-05 ADP-N ADP-05-N ADP-07 ADP-08 ADP-08 M ADP-16 ADP-25 ADP-28 ADP-29 ADP-31 RJC-05 RJC-10 RJC-20 RJC-30 RJC-50 RJC-100 RJC-ADP-22B RJC-ADP-26 RJC-ADP-27 RJC-ADP-30 RJC-45/12 RJC-X-OVER RJC-ETHER-X- OVER CAB-OPTION-J CAB-IO-1 CAB-IO-2 CAB-IO-5 CAB-ACR-00 CAB-ACR-AU CAB-ACR-EU CAB-ACR-IN CAB-ACR-UK CAB-ACR-US CAB-FO-PATCH-1 CAB-FO-PATCH-2 Description Maxon and Tait radios (DB9F to RJ45 Adaptor) for 'R' option PC Serial Port (DB9F to RJ45 Adaptor) for 'I' & 'S' options DB9 port saver. Used with ADP-05 for concealed PC serial ports (E.g. Current HP Notebooks) PC Serial Port (DB9F to RJ45 Adaptor) for 'I' & 'S' options DB9 port saver. PSTN modem external 25 pin (DB25M to RJ45 Adaptor) for 'S' options, confirm PSTN pin-outs RJ45 to DB9 Female Converter (Straight Connect) RJ45 to DB9 Male Converter (Straight Connect) for Serial Port to MaxStream External Spread Spectrum Radio Trio "D" and "E" Series Radio (DB9M to RJ45 Adapter) for 'S' options Uni-Op Display Model - MD02R-04-00A5 (DB15M to RJ45 Adapter) for 'S' options Trio "H" series Spread Spectrum Radio (DB9M to RJ45 Adapter) for 'S' options Trio "M" series Radio (Modem fitted) (DB9M to RJ45 Adapter) for 'S' options Trio "M" series Radio (DB9M to RJ45 Adapter) for PC-1 'R' option Cable RJ45 Plug both ends "1:1" - 0.5 meters Cable RJ45 Plug both ends "1:1" - 1.0 meter Cable RJ45 Plug both ends "1:1" - 2.0 meters Cable RJ45 Plug both ends "1:1" - 3.0 meters Cable RJ45 Plug both ends "1:1" - 5.0 meters Cable RJ45 Plug both ends "1:1" - 10.0 meters Wavecom GSM Cable (RJ45 to HD15) for 'S' options, to suit Fastrack Xtend FXT009, and superseded 1205-1306, Supreme 10 Maxon MM-6280IND 3G Cable (RJ45 to DB15) for 'S' options Motorola Satellite Series 9522 L-Band Cable (RJ45 to DB25) for 'S' options Trio "M" series radio Cable (RJ45 to DB15) for 'L' option RJ45 to RJ12 Phone Lead - 2.0m Serial RJ45 to RJ45 cross over cable - 1.5 meters (useful for testing/commissioning) Ethernet RJ45 to RJ45 cross over cable - 2.0 meters Image Capture Option cable - SMB to BNC female - 2.5m External I/O cable - 1m External I/O cable - 2m External I/O cable - 5m Cable PSO-ACR Power Supply 2.5M (Flying leads) Cable PSO-ACR Power Supply 2.5M (3 Pin 240V AU-NZ Plug) Cable PSO-ACR Power Supply 2.5M (3 Pin 240V EU Plug) Cable PSO-ACR Power Supply 2.5M (3 Pin BA546A 240V Plug) Cable PSO-ACR Power Supply 2.5M (3 Pin 240V UK Plug) Cable PSO-ACR Power Supply 2.5M (3 Pin 240V UK Plug) Patch Cable for A3 Ethernet Option Board (MTRJ to ST) Patch Cable for A3 Ethernet Option Board (MTRJ to SC) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 324 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 15.1. RTU Test Cables RJC-X-Over: Kingfisher PLUS RJ45 to RH45 RS232 Null Modem Cable (serial crossover) RJ45 to Kingfisher RTU Serial Port RJ45 to Kingfisher RTU Serial Port RJC-X-Over-E: Kingfisher PLUS+ RJ45 to RJ45 Ethernet Crossover Cable RJ45 to Kingfisher RTU Ethernet Port RJ45 to Kingfisher RTU Ethernet Port Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 325 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 15.2. Device Cables and Adaptors ADP-04: PC-1/MC-1 Radio Port to Tait T2010 or Maxon RDM-01 Radio (SD125) RJ45 to Kingfisher RTU Radio Port To Tait 2010 or Maxon RDM-01 radio ADP-05: RTU Serial Port to PC Serial Port (Creates a null modem cable) To Kingfisher Serial Port To PC Serial Port Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 326 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ADP-07: RTU Serial Port to External PSTN Modem To Kingfisher Serial Port To PSTN Modem ADP-08: RJ45 to DB9 Female Converter (Straight Connect) (Note: when coupled with an ADP-05 forms a null modem cable DB9 female to DB9 female) To Kingfisher Serial Port Q-Pulse Id: TMS1594 Active: 18/04/2016 To External Device Page 327 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ADP-08-M: Serial Port to Digi External Spread Spectrum Radio For Digi XTend-PKG or XStream-PKG, and other 3rd party radios. To Kingfisher Serial Port ADP-09: Serial Port to HITECH or Nematron Display Panel To External Radio To Kingfisher Serial Port To Operators Panel Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 328 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ADP-16: Serial Port to Trio D-Series Radio or Trio E Series Radio For example TC-450ER or TC-900DR. To Kingfisher Serial Port To Trio Radio RJC-ADP-17: PC-1/MC-1 Radio Port to Trio S- Series Radio For TC-450SR, TC-900SR or RTU Serial Port to Trio S-Series Radio with 24/48SR modem. To Kingfisher Serial Port Q-Pulse Id: TMS1594 Active: 18/04/2016 To Trio Radio Page 329 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-18: CP-xx Line Option Board to Maxon Analogue Radio (Maxon SD-125) To Kingfisher Serial Port To Maxon Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 330 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-20: CP-xx Line Option Board to Trio S Series Analogue Radio For use with TC-450SR or TC-900SR. To Kingfisher Serial Port To Maxon Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 331 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-21: CP-xx Line Option Board to Tait T2010 Analogue Radio To Kingfisher Serial Port To Tait Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 332 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-22B: Serial Port to Wavecom GSM For use with the WM02-G900, Fastrack, Fastrack Supreme, or Fastrack Xtend. Note: Adds a RTS/DTR link to the previous RJC-ADP-22 cable. Link required for Fastrack Supreme. Link will also work with the older WM02-G900 and Fastrack modems. To Kingfisher Serial Port To GSM or GPRS Modem Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 333 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-23: PC-1/MC-1 Radio Port/Serial Port to Trio S- Series (SB) Repeater To Kingfisher Serial Port To GSM or GPRS Modem RJC-ADP-26: Serial Port to Maxon MM-6280IND 3G Data Modem (previously used for the Maxon MM-5100 CDMA Modem) To Kingfisher Serial Port Q-Pulse Id: TMS1594 Active: 18/04/2016 To 3G Data Modem Page 334 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RJC-ADP-27: RTU Serial Port to Motorola 9522 Satellite Transceiver To Kingfisher Serial Port To Satellite Transceiver ADP-28: RTU Serial Port to Trio HSeries Spread Spectrum Radio To Kingfisher Serial Port To Trio Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 335 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ADP-29: Serial Port to Trio M Series Radio (with modem fitted) E.g. MR540 To Kingfisher Serial Port To Trio Radio RJC-ADP-30: CP-xx Line Option Board to Trio M Series Analogue Radio (no modem fitted) E.g. MR540 To Kingfisher Serial Port To Trio Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 336 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ADP-31: PC-1/MC-1 Radio Port to Trio M Series Analogue Radio (no modem fitted) E.g. MR540 To Kingfisher Serial Port To Trio Radio Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 337 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CAB-FO-PATCH-1: A3 Ethernet MTRJ Fibre Optic to 2 × ST adaptor cable To Kingfisher A3 Option Board To external Device CAB-FO-PATCH-2: A3 Ethernet MTRJ Fibre Optic to 2 × SC adaptor cable To Kingfisher A3 Option Board Maxon Intermax Serial Modem to Kingfisher Serial Port To external Device Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 338 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 16. Accessories Accessories are available that can ease the installation of your RTU. These include rack mounting hardware and battery carrier mounts. MBR-3: 19" Rack Mounting for BA-12 A 12 slot backplane (BA-12) is mounted in a 19 inch rack using two MBR-3 mounting brackets. The MBR-3 brackets replace the surface mount brackets supplied with BA-12 backplanes. Each pair of MBR-3 brackets is supplied with four M4 x 6 mm pan head screws. Installation Note: The holes in the MBR-3 brackets that are used to attach the brackets to the back of the backplane are drilled oversize to accommodate slight variances in racking equipment. By loosening these screws, pushing the brackets toward the centre of the backplane and then re-tightening the screws, the unit will fit freely into any correctly sized 19-inch rack. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 339 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TEL-RAK-002: 19" Rack Mounting for BA-3/6/40 A four slot backplane (BA-4 or BA-40) or a six slot backplane (BA-6) is mounted in a 19 inch rack using a TEL-RAK-002 mounting bracket. One BA-6 or two BA-4/BA-40 backplanes can be attached to the TEL-RAK-002 using the surface mount brackets supplied with each backplane. The TEL-RAK-002 is supplied with eight M3 x 5 mm screws for attaching the backplane(s). Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 340 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Battery Bracket: 7 AH: 7 AH Battery Mounting Bracket When using a 7 AH backup battery, a standard battery holder is available for mounting on an enclosure gear plate. The bracket supports the battery and allows a General Power Outlet (GPO) to be mounted on the front using M3 x 10 mm pan head screws. The battery holder also allows an ISB50LN lightning arrestor to be mounted underneath. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 341 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 17. Glossary AI, AO, DI, DO Byte Comms Current Sinking IO IP Port Processor Module Protocol RTU TCP/IP UDP Analogue Input, Analogue Output, Digital Input and Digital Output respectively A group of 8 bits. Each bit can be a 0 (off) or a 1 (on) allowing up to 256 combinations. Communications Current is supplied into the RTU's IO terminal. Input, Output Internet Protocol. Used for Ethernet communications. A physical connection or socket on an RTU used for communications Processor module containing a CPU (central processing unit) Refers to the format of messages that may be passed to, from and through an RTU in communication with local and remote devices. Communications may use one or more RTU ports. Examples of protocols used within telemetry include Kingfisher, Modbus and DNP3. Acronym for Remote Terminal Unit. Describes a group of processor, communications and IO modules that comprise a device for monitoring and control of equipment in remote locations. Transfer Control Protocol / Internet Protocol. Commonly used for Ethernet communications. User Datagram Protocol. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 342 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 18. Appendix Superseded items are not present in this hardware manual. For information regarding any modules not present in this document please refer to the Superseded Hardware Manual available on MyKingfisher. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 343 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 344 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 345 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Telemetry Module AD2006 TELEMETRY MODULE QUICKSTART MANUAL This manual is intended to provide sufficient information for the correct installation of your AD2006 telemetry module. In most cases, your AD2006 module will be delivered pre-configured to your project requirements. For programming information please refer to the MiriMap 2000+ Software on-line help. PLEASE ENSURE THAT YOU HAVE THE CORRECT POWER SUPPLY VOLTAGE BEFORE POWERING UP THE MODULE. Q-Pulse Id: TMS1594 Active: 18/04/2016 Rev. August 2009 Page 346 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Ordering Information There are many variations of the AD2006 telemetry modules available. The following shows the ordering code and details for modules with and without internal data radios. For other radio or modem options please contact Miri Technologies directly. The following options are not fitted as factory standard and need to be requested when ordering : - 4 Channel Analog Ouput option Ethernet Port option If you are ordering a module to add to an existing system, please be sure to specify the project when ordering the new module. ORDERING Part No. AD2006Tx-aaabb-xx-xx Add `T' for Ethernet Option Otherwise leave blank 12 - for 12VDC supply. 24 - for 24VDC supply. N - for no analog output option. A - for analog output option fitted. L - for low voltage digital inputs 10 - 35V H - for hi voltage digital inputs 70 - 130V 12 - 12.5kHz Channel 25 - 25kHz Channel SS - Spread Spectrum Radio Type : J02 VHF 138 - 174MHz (12.5KHz only) J51 UHF 450 - 470MHz (12.5KHz only) M50 UHF 395 - 465MHz M51 UHF 450 - 520MHz 90 900MHz Spread Spectrum 24 2.4GHz Spread Spectrum R - with inbuilt radio E - for external radio The AD2006 part number is displayed on the rear of each unit together with other relevant information. AD2006R-M5125-LN-12 Hardware version - Rev. 4 serial no Tx frequency - 450.650 MHz Rx frequency - 450.650 MHz special Brockman Return Water Pumps 10462 Miri Technologies - Perth, West Australia. tel. +61 8 9409 8998 fax. +61 8 9409 9229 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 347 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Overview PORT5 RS232 or ETHERNET PORT4 USB PORT3 RS485 12V + _ + _ DOT 1 2 1A 3 2A 4 3A 3B 4A 4B DIN 1 9 2 3 10 4 11 5 12 6 13 7 14 8 15 C1 16 C2 ALG 1 5 234 678 G G PTT TEST BUTTON PROG /RUN SWITCH POWER SUPPLY 4 DIGITAL OUTPUTS 16 DIGITAL INPUTS 8 ANALOG CHANNELS PORT1 EXTERNAL FFSK or RS232 PORT2 RS232 DISPLAY PANEL pwr The pwr LED should be on at all times when the unit is powered up. run The run LED should flash at 2Hz when the unit is in RUN mode and 4Hz in PROG mode. fault radio tx rx A fault means that the module has received a bad reply to a message. The tx and rx LEDs reflect the PTT and CD status of the internal radio. tx rx lnk port 1 port 2 port 3 port 4 The tx and rx LEDs for each port indicate that a valid system message has been sent or received on that port. A link indication means that the slave time-out period for that port has lapsed or the programmed number of retries have failed and communications have been lost. port 5 DOT config 12341234 12345678 The first four LEDs indicate that the physical outputs are active. The second four LEDs are programmable status indications. DIN These LEDs indicate that a particular input is active. 9 10 11 12 13 14 15 16 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 348 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Digital I/O DIGITAL INPUTS There are two different versions of the AD2006 module with respect to Digital Inputs. There is a low voltage version for nominally 12 or 24 volt inputs, and a high voltage version specifically for 110 volt inputs. AD2006L - Lo Voltage AD2006H - Hi Voltage 10-35VDC/AC 4k7 Impedance 70-130VAC/DC 27k Impedance This is not an on-board selectable option so please ensure that you have the correct version of hardware for your application. The digital input voltage is marked on the terminal strip label with the Lo voltage inputs being highlighted in blue and the Hi voltage inputs being highlighted in orange. The digital inputs are supplied in two blocks of 8 inputs each with a separate common terminal. The inputs will accept an AC input voltage or a DC voltage of either polarity . PULSE COUNTERS Each Digital Input may be used as a pulse counter up to 5Hz. The first two inputs can be configured as high speed pulse counters up to 5KHz equal (mark space ratio). Where the inputs are used as slow counters (to 5Hz.) the inputs are usually referred to the digital input common. Where the fast pulse counters are used, the inputs are referred to the module 0V supply (ground). They will then accept inputs from common emitter transistors, FETs or reed switches etc. as shown below. The factory default setting is for all inputs to be configured as digital inputs/slow counters. The following jumper settings apply where inputs 1 and 2 are required to be fast counters. All inputs DINs (factory default) DIN1 - Fast Pulse DIN2 - Fast Pulse J27 J30 A B J28 J29 J27 J30 A B J28 J29 J27 J30 A B J28 J29 12V + + _ _ +_ 12 VDC supply DIN 1 9 2 3 10 4 5 6 7 8 C1 11 12 13 14 15 16 C2 S1 S2 Fast pulse input DIGITAL OUTPUTS Each Digital Output may be individually configured as an isolated relay or common emitter transistor. LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD RLY4 RLY3 RLY2 RLY1 With all jumpers J12 - J15 in position A the module is configured for 2 form A and 2 form C relay outputs. (factory default) RL2 RL4 RL1 RL3 J12 J13 J14 J15 A B DOT 1 2 3 4 3B 1A 2A 3A 4A 4B S1 S2 S3 S4 LOAD - 3 AMPS MAX. @ 30VDC MAX. or 240VAC With all jumpers J12 J15 in position B, all outputs are common emitter transistors. J12 J13 J14 J15 A B 12V + + _ _ DOT 1 2 3 4 3B 1A 2A 3A 4A 4B LOAD 100mA MAX. + _ @ 30VDC MAX. S1 S2 S3 S4 12 VDC supply ++++ Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 349 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Analog Options The AD2006 module has 8 analog input channels as standard. These are configured from the factory as 4-20mA/1-5V. The following options are available by jumper selection :- A. 0-20mA/0-5V B. 4-20mA/1-5V C. 0-1V Whichever option is selected determines the configuration of ALL analog input channels. Channels 1 to 8 are configured for current or voltage inputs via jumpers J35 to J42 respectively. If a jumper is installed in the appropriate location then that channel will operate as a current input. If no jumper is installed, it will operate as a voltage input. FACTORY DEFAULTS - All channels set to 4-20mA J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 J16 J20 J4 J10 A B J24 J22 J5 J9 J11 OTHER OPTIONS All input channels 0-20mA All input channels 1-5V All input channels 0-5V All input channels 0-1V J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 POWER SUPPLY MONITOR - Analog Input channel 8 is set by factory default to monitor the supply voltage to the telemetry module. This is particularly useful in solar powered installations. If channel 8 is required as a normal analog input channel then J24 is moved from position A to position B. VOLTAGE SOURCE FOR FIELD SENSORS - Analog input channel 8 can be configured as a 5V source to power field sensors to a maximum current supply of 20mA. To select this option, install jumpers in J16 position B and J22 position A. ANALOG OUTPUT OPTION - An analog output board must be installed to utilise this option. This is a factory fitted option. When the analog output option is installed, any of the last four channels can be configured as 4-20mA outputs. ANALOG OUTPUTS - Channels 5-8 configured as outputs J26 J25 J35 J36 J37 J38 A B J39 J40 J41 J42 J16 J20 J4 J10 A B J42 J22 J5 J9 J11 Channels 5 to 8 are selected as 4-20mA outputs by way of locating jumpers in position A as follows :- Ch.5 J4 Ch.6 J5 Ch.7 J20 Ch.8 J22 and J16 Note - If channel 8 is configured as an analog output, analog input 8 will still operate as a supply voltage monitor, provided that J24 is selected in position A. Note - J9, J10 and J11 are not relevant to the analog channel options. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 350 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Serial Ports PORT 1 - EXTERNAL RADIO - FFSK or RS232 Port 1 is intended for connection to an external data radio and provides either FFSK or RS232 options. The FFSK is configurable to 4800 baud. The RS232 option can operate up to 115,200 baud. The on-board selectable options are detailed on the following page of this manual. PORT 2 & PORT 5 - RS232 Port 2 and Port 5 can both be used for connection to third party devices via RS232. Each port can operate up to 115,200 baud. The on-board selectable options are detailed in the following page of this manual. NOTE : Port 5 cannot be used as an RS232 port if the Ethernet connection is being used. PORT 3 - RS485 Port 3 is an RS485 port intended for use as a multidrop serial connection for I/O expansion modules or third party devices. It can run either Miri protocol or Modbus. PORT 4 - USB-B This port is intended for use as a programming port. PORT 5 - Ethernet Option The Ethernet port is a factory fitted 10/100T option which can run either Modbus TCP or Miri protocols. Note that where the Ethernet port is used, Port 5 cannot be used as an RS232 port. External Radio Port Pin assignment 1. n/c 2. RTS 3. TX data 4. PTT 5. GND 6. RX data 7. CTS 8. CD External RS232 ports Pin assignment 1. DTR 2. RTS 3. TX data 4. PTT 5. GND 6. RX data 7. CTS 8. DSR External RS485 port Pin assignment 1. DATA B 2. DATA A 3. GND View looking into ext. radio port. 8 PIN 1 View looking into RS232 ports. 8 PIN 1 View looking into RS485 port. 123 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 351 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Radio Communications Options FACTORY DEFAULTS - Internal radio - 2400 baud. J8 J49 J1 J18 A B A B A B INTERNAL RS232 INTERNAL FFSK J34 J33 J2 J6 A TX LEVEL VR5 J17 J7 B AB A BA RX LEVEL VR6 J3 J50 B AB FFSK BAUD RATE OPTIONS - The jumper arrangement shown is the factory default configuration for an internal radio operating at 2400 baud. Other options are achieved by implementing the following changes to J18, J33, J34. 1200 J18 2400 J18 4800 J18 J34 J33 J34 J33 J34 J33 FFSK EXTERNAL RADIO - To configure the module for an external audio radio, make the following changes to J1, J3, J7, J8, and J9, J10, J11. J8 J49 J1 J18 A B A B A B J7 J3 J50 A BA B AB J16 J20 J4 J10 A J19 B J42 J22 J5 J9 J11 PTT PUSH BUTTON J16 J20 J4 J10 A B J42 J22 J5 J9 J11 RS232 EXTERNAL RADIO CONNECTION - To configure the module for an external RS232 radio port, jumpers J1, J9, J10, J11 should be set up as follows :- EXTERNAL RADIO There are a number of radio options available for the AD2006 modules. Some of these use audio (FFSK) modulation, whereas others have an RS232 interface. The above jumper configuration is applicable to both VHF and UHF internal radios. If an audio (FFSK) external radio is to be used with the module, this is implemented using Port1. Ports 2 and 5 are available for RS232 connections. There is a PTT push button located under the bottom right hand corner of the module. This is intended to be used to check the SWR of antenna installations during commissioning. J8 J49 J1 J18 A B A B A B J16 J20 J4 J10 A B J42 J22 J5 J9 J11 NOTE - The above configuration is the factory default configuration and so it may not be necessary to move any jumpers to implement this mode. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 352 of 1068 miri technologies WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AD2006 Mounting Detail 272 The AD2006 module is installed by means of the clip in stainless steel mounting bracket supplied with the unit. Please ensure when mounting the telemetry module that sufficient clearance is left for wiring to and from the unit. Recommended minimum clearances are shown here. The module is removed by depressing the small tongue at the bottom of the mounting bracket and sliding the unit upwards. 278 90 The terminal blocks are removable such that the I/O 25 wiring need not be disturbed when replacing a module in the field. 202 AD2006 Mounting holes 4.5mm MOUNTING PLATE 60 60 CL 50 178 50 50 miri AD2006 technologies Wiring Diagram Internal DC-DC converter The digital outputs are configurable for relay or solid state format as described in this manual. The relay format is shown here. The relays are isolated - 2 form A , 2 form C. RL2 RL4 There are 8 Analog input channels which share a common ground. Channels 5 - 8 may be configured as 4-20mA analog outputs by way of a factory installed analog output option. Fuse 2A 20 x 5mm RL1 RL3 The digital inputs are optically isolated to 2.5KV. There are two separate groups of 8 inputs each with a separate common. These will both have the same voltage range and can accept either AC or DC source voltages. 12V +_ + _ DOT 1 1A 2 2A 3 3A 4 3B 4A 4B DIN1 2 3 4 5 6 7 8 C1 9 10 11 12 13 14 15 16 C2 ALG 1 2 5 6 3 4 7 G 8 G + POWER SUPPLY 10.5 - 16VDC LOAD LOAD LOAD LOAD S1 S2 S3 S4 LOAD - 3 AMPS MAX. @ 30VDC MAX. or 250VAC MAX. NEGATIVE SUPPLY & COAXIAL CONNECTION MUST BE GROUNDED S1 S2 A1 A2 A3 A4 A5 A6 A7 A8 DIGITAL INPUTS : AD2006 `L' 10 - 35VAC/DC AD2006 `H' 70 - 130VAC/DC PLEASE ENSURE THAT YOU HAVE THE CORRECT INPUT VOLTAGE BEFORE CONNECTION ! The analog input channels are configurable as 4-20ma /1-5V, 0-20mA / 0-5V or 0-1V. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 353 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Cellular Transit Antenna The TLA2000 is an ideal antenna solution for GSM data applications in both fixed and mobile situations. Designed to offer true dual band performance the TLA2000 is ready for use with the latest GSM (GPRS) modems. With a high impact resistant vacuum formed ABS radome and neoprene mounting gasket, the TLA2000 can be used for indoor or outdoor applications. · Applications include public vending machines, ATM kiosks and industrial automotive use · Designed for use on conductive or nonconductive surfaces · TLA3000 model incorporates integrated GPS antenna Typical VSWR response GSM900 2.5 2.4 2.3 2.2 2.1 2.0 1.9 1.8 1.7 1.6 1.5 -35 +35 Typical VSWR response GSM1800 -85 +85 890-960 MHz 1710-1880 MHz TLA2000 TLA3000 TLA2000/3000 Typical E-Plane response @ 890MHz Electrical Model No. Gain dBi Frequency MHz Power W Tuned Bandwidth Tuning Mechanical Model No. Construction Diameter mm Height mm Mounting Cable and Connector TLA2000/3000 2 890 - 960 / 1710 - 1880 10 Entire specified band @<2.5:1 VSWR Pre-tuned TLA2000 TLA3000 White Geloy ASA radome 135 61 (including gasket) M4 hardware (not included) 500mm low loss 9014 RG58 type Cellular: 5m 9014 RG58 type - FME connector GPS: 5m low loss RG174 type - MCX connector GPS Specifications Fo Operation Temperature Storage Temperature System Gain at Fo Impedance Polarization VSWR at Fo Noise Figure at Fo Power Input Power Consumption Power Input Over-Current 1575.42 MHz -40 to +85°C -40 to +100°C 28dBi including cable and filter losses 50 Ohm RHCP 1.5:1 <1.8 dB max. +2.5Vdc to +12Vdc input, Auto Switching 11mA to 13mA (max) Reverse Polarity Short Circuit Shutdown Thermal over-current shutdown >+150°C www.rfi.com.au Q-Pulse Id: TMS1594 Active: 18/04/2016 109 Page 354 of 1068 Data Sheet WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual NP SERIES - NP7-12 Reliability is your Security Utilizing the latest advance design Oxygen Recombination Technology, Yuasa have applied their 80 years of experience in the lead acid battery field to produce the optimum design of Sealed Lead Acid batteries. FEATURES Superb recovery from deep discharge. Electrolyte suspension system. Gas Recombination. Multipurpose: Float or Cyclic use. Usable in any orientation Superior energy density. Lead calcium grids for extended life. Manufactured World wide. Application specific designs. Technical Features Sealed Construction Yuasa's unique construction and sealing technique ensures no electrolyte leakage from case or terminals. Electrolyte Suspension System All NP batteries utilize Yuasa's unique electrolyte suspension system incorporating a microfine glass mat to retain the maximum amount of electrolyte in the cells. The electrolyte is retained in the separator material and there is no free electrolyte to escape from the cells. No gels or other contaminants are added. Control of Gas Generation The design of Yuasa's NP batteries incorporates the very latest oxygen recombination technology to effectively control the generation of gas during normal use. Low Maintenance Operation Due to the perfectly sealed construction and the recombination of gasses within the cell, the battery is almost maintenance free. Terminals Terminals NP batteries are manufactured using a range of terminals which vary in size and type. Please refer to details as shown. Operation in any Orientation The combination of sealed construction and Yuasa's unique electrolyte suspension system allows operation in any orientation, with no loss of performance or fear of electrolyte leakage. Valve Regulated Design The batteries are equipped with a simple, safe low pressure venting system which releases excess gas and automatically reseals should there be a build up of gas within the battery due to severe overcharge. Note. On no account should the battery be charged in a sealed container. General Specifications Layout Nominal Capacity (Ah) 20hr to 1 .75vpc 30ºC 1 0hr to 1 .75vpc 20ºC 5hr to 1.70vpc 20ºC 1 hr to 1 .60vpc 20ºC Voltage Energy Density (Wh.L.20hr) Specific Energy (Wh.kg.20hr) Int. Resistance (m.Ohms) Maximum discharge (A) Short Circuit current (A) Dimensions (mm) Length Width Height overall Weight (Kg) Terminal Layout Terminal Torque Nm NP7-12 7 6.4 5.9 4.2 12 91 32 25 40/75 210 151 65 97.5 2.65 A/D 4 - Q-Pulswe Idw: TMwS1.5y94uasabatteries.coAmctive: 18/04/2016 NP Page 355 of 1068 Data Sheet WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual NP SERIES - NP7-12 Lead Calcium Grids The heavy duty lead calcium alloy grids provide an extra margin of performance and life in both cyclic and float applications and give unparalleled recovery from deep discharge. Long Cycle Service Life Depending upon the average depth of discharge, over a thousand discharge/charge cycles can be expected. Float Service Life The expected service life is five years in float standby applications. Separators The use of the special separator material provides a very efficient insulation between plates preventing inter-plate short circuits and prohibiting the shedding of active materials. Long shelf Life The extremely low self discharge rate allows the battery to be stored for extended periods up to one year at normal ambient temperatures with no permanent loss of capacity. Operating Temperature Range The batteries can be used over a broad temperature range permitting considerable flexibility in system design and location. Charge 15°C to 50°C Discharge 20°C to 60°C Storage 20°C to 50°C (fully charged battery) Q-Pulse Id: TMS1594 Yuasa Battery Inc. 2901 Montrose Ave Laureldale, PA 19605 www.yuasabatteries.com Registered number 1548820 Cat. No. NP7-12 JanuAarcyt0iv8e: 18/04/2016 Distributed by Page 356 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Plug and Play Wireless CPU® FASTRACK Supreme User Guide Reference: WA_DEV_Fastrk_UGD_001 Revision: 001e Date: 5 june, 2007 Supports Open AT® embedded ANSI C applications confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 1 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 357 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Document History Revision 001 001a 001b 001c 001d 001e Date 9 February, 07 23 February, 2007 21 May, 07 1 Jun, 07 4 Jun, 07 5 Jun, 07 List of revisions First Issue Update DC cable GPIO mapping, add AutoShutDown Add detail of IES, RTC and serial port autoshutdown Change to Quad Band Update label/packaging photo Comment confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 2 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 358 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Overview Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 The FASTRACK Supreme 10 and FASTRACK Supreme 20 are discrete, rugged cellular Plug & Play Wireless CPU® offering state-of-the-art GSM/GPRS (and EGPRS for FASTRACK Supreme 20) connectivity for machine to machine applications. Proven for reliable, stable performance on wireless networks worldwide, Wavecom's latest generation of FASTRACK Supreme continues to deliver rapid time to market and painless integration. Having comparable size with the previous M1306B generation, and updated with new features, the FASTRACK Supreme offers an Internal Expansion Socket (IES) interface accessible for customer use. Expanding application features is easy without voiding the warrantee of the FASTRACK Supreme by simply plugging in of an Internal Expansion Socket Module (IESM) board. Fully certified, the quad band 850/900/1800/1900 MHz FASTRACK Supreme 10 offers GPRS Class 10 capability and FASTRACK Supreme 20 offers GPRS/EGPRS Class 10 capability. Both support a powerful open software platform (Open AT®). Open AT® is the world's most comprehensive cellular development environment, which allows embedded standard ANSI C applications to be natively executed directly on the Wireless CPU®. FASTRACK Supreme is controlled by firmware through a set of AT commands. This document describes the FASTRACK Supreme and gives information on the following topics: · general presentation, · functional description, · basic services available, · technical characteristics, · installing and using the FASTRACK Supreme, · user-level troubleshooting. · recommended accessories to be used with the product. Note: This document covers the FASTRACK Supreme Plug & Play alone and does not include The programmable capabilities provided via the use of Open AT® Software Suites. The development guide for IESM for expanding the application feature through the IES interface. For detailed, please refer to the documents shown in the "Reference documents" section. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 3 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 359 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual RoHS Directive Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 The FASTRACK Supreme is now compliant with RoHS Directive 2002/95/EC, which sets limits for the use of certain restricted hazardous substances. This directive states that "from 1st July 2006, new electrical and electronic equipment put on the market does not contain lead, mercury, cadmium, hexavalent chromium, polybrominated biphenyls (PBB), and polybrominated diphenyl ethers (PBDE)". Plug & Plays which are compliant with this directive are identified by the RoHS logo on their label. Disposing of the product This electronic product is subject to the EU Directive 2002/96/EC for Waste Electrical and Electronic Equipment (WEEE). As such, this product must not be disposed off at a municipal waste collection point. Please refer to local regulations for directions on how to dispose off this product in an environmental friendly manner. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 4 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 360 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Cautions Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Information furnished herein by WAVECOM is accurate and reliable. However, no responsibility is assumed for its use. Please read carefully the safety recommendations given in Section 9 for an application based on FASTRACK Supreme Plug & Play. Trademarks ®, WAVECOM®, Wireless CPU®, Open AT® and certain other trademarks and logos appearing on this document, are filed or registered trademarks of Wavecom S.A. in France or in other countries. All other company and/or product names mentioned may be filed or registered trademarks of their respective owners. Copyright This manual is copyrighted by WAVECOM with all rights reserved. No part of this manual may be reproduced in any form without the prior written permission of WAVECOM. No patent liability is assumed with respect to the use of their respective owners. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 5 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 361 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Web Site Support General information about Wavecom and its range of products: Specific support is available for the FASTRACK Supreme Plug & Play Wireless CPU®: Open AT® Introduction: Developer community for software and hardware: www.wavecom.com TBD www.wavecom.com/OpenAT www.wavecom.com/forum confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 6 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 362 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Contents Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 DOCUMENT HISTORY ......................................................................................................................................2 OVERVIEW ........................................................................................................................................................3 CAUTIONS .........................................................................................................................................................5 TRADEMARKS ..................................................................................................................................................5 COPYRIGHT ......................................................................................................................................................5 WEB SITE SUPPORT ........................................................................................................................................6 CONTENTS ........................................................................................................................................................7 LIST OF FIGURES ...........................................................................................................................................11 LIST OF TABLES.............................................................................................................................................12 1 REFERENCES .........................................................................................................................................13 1.1 Reference Documents.........................................................................................................................13 1.1.1 Open AT® Software Documentation ..........................................................................................13 1.1.2 AT Software Documentation......................................................................................................13 1.1.3 Firmware Upgrade Documents..................................................................................................13 1.1.4 Delta between M1306B Documents..........................................................................................13 1.1.5 IESM Related Documents .........................................................................................................13 1.2 Abbreviations .......................................................................................................................................14 2 PACKAGING ............................................................................................................................................17 2.1 Contents ..............................................................................................................................................17 2.2 Packaging Box.....................................................................................................................................18 2.3 Production Labelling ............................................................................................................................19 3 GENERAL PRESENTATION ...................................................................................................................20 3.1 Description...........................................................................................................................................20 3.2 External Connections ..........................................................................................................................22 3.2.1 Connectors ................................................................................................................................22 3.2.1.1 Antenna Connector ............................................................................................................22 3.2.1.2 Power Supply Connector ...................................................................................................22 3.2.1.3 Sub HD 15-pin Connector..................................................................................................23 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 7 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 363 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 3.2.1.4 IES Connector....................................................................................................................25 3.2.2 Power supply cable ...................................................................................................................29 4 FEATURES AND SERVICES...................................................................................................................31 4.1 Basic Features and Services...............................................................................................................31 4.2 Additional NEW Features ....................................................................................................................34 4.2.1 Support Additional GSM850/PCS1900 Bands ..........................................................................34 4.2.2 IES Interface for Easy Expansion of Application Features........................................................34 4.2.3 Serial Port Auto Shut Down or Improving Power Consumption ................................................34 4.2.4 Real Time Clock (RTC) for Saving Date and Time ...................................................................34 4.2.5 SIM Card Lock Feature .............................................................................................................35 5 USING THE FASTRACK SUPREME PLUG & PLAY .............................................................................36 5.1 Getting Started.....................................................................................................................................36 5.1.1 Mount the FASTRACK Supreme...............................................................................................36 5.1.2 Set up the FASTRACK Supreme ..............................................................................................36 5.1.3 Check the communication with the FASTRACK Supreme........................................................37 5.1.4 Reset the FASTRACK Supreme ...............................................................................................37 5.2 Specific Recommendations when Using the FASTRACK Supreme on Trucks ..................................38 5.2.1 Recommended Power Supply Connection on Trucks...............................................................38 5.2.2 Technical Constraints on Trucks ...............................................................................................38 5.3 FASTRACK Supreme Operational Status...........................................................................................39 5.4 Echo Function Disabled.......................................................................................................................40 5.5 Verify the Received Signal Strength....................................................................................................41 5.6 Check the Pin Code Status .................................................................................................................41 5.7 Switch between EU/US Band(s)..........................................................................................................41 5.8 Check the Band(s) Selection ...............................................................................................................42 5.9 Verify the FASTRACK Supreme Network Registration .......................................................................43 5.10 Main AT Commands for the Plug & Play .............................................................................................44 5.11 Firmware Upgrade Procedure .............................................................................................................45 6 TROUBLESHOOTING .............................................................................................................................46 6.1 No Communication with the FASTRACK Supreme through the Serial Link .......................................46 6.2 Receiving "ERROR" Message.............................................................................................................46 6.3 Receiving "NO CARRIER" Message ...................................................................................................47 7 FUNCTIONAL DESCRIPTION .................................................................................................................50 7.1 Architecture..........................................................................................................................................50 7.2 EU and US Bands................................................................................................................................51 7.2.1 General Presentation.................................................................................................................51 7.2.2 AT COMMAND for Bands Switch ..............................................................................................51 7.3 Power Supply.......................................................................................................................................51 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 8 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 364 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.3.1 7.3.2 Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 General Presentation.................................................................................................................51 Protections.................................................................................................................................51 7.4 RS232 Serial Link ................................................................................................................................51 7.4.1 General Presentation.................................................................................................................51 7.4.2 Autobauding Mode ....................................................................................................................52 7.4.3 Pin Description...........................................................................................................................53 7.4.4 Serial Port Auto shut down Feature ..........................................................................................53 7.5 General Purpose Input/Output (GPIO) ................................................................................................54 7.6 BOOT...................................................................................................................................................54 7.7 RESET.................................................................................................................................................54 7.7.1 General presentation .................................................................................................................54 7.7.2 Reset Sequence ........................................................................................................................55 7.8 Audio....................................................................................................................................................56 7.8.1 Microphone Inputs .....................................................................................................................56 7.8.2 Speaker Outputs........................................................................................................................57 7.9 Real Time Clock (RTC) .......................................................................................................................58 7.10 FLASH LED 58 8 TECHNICAL CHARACTERISTICS..........................................................................................................59 8.1 Mechanical Characteristics..................................................................................................................59 8.2 Electrical Characteristics .....................................................................................................................61 8.2.1 Power Supply.............................................................................................................................61 8.2.2 Power Consumption ..................................................................................................................62 8.2.3 Audio Interface ..........................................................................................................................65 8.2.4 General Purpose Input/Output...................................................................................................66 8.2.5 SIM Interface .............................................................................................................................66 8.2.6 RESET Signal............................................................................................................................66 8.2.7 RF Characteristics .....................................................................................................................67 8.2.7.1 Frequency Ranges.............................................................................................................67 8.2.7.2 RF Performances...............................................................................................................68 8.2.7.3 External Antenna ...............................................................................................................69 8.3 Environmental Characteristics.............................................................................................................69 8.4 Conformity ...........................................................................................................................................72 8.5 Protections...........................................................................................................................................72 8.5.1 Power Supply.............................................................................................................................72 8.5.2 Overvoltage ...............................................................................................................................73 8.5.3 Electrostatic Discharge..............................................................................................................73 8.5.4 Miscellaneous ............................................................................................................................73 9 SAFETY RECOMMENDATIONS .............................................................................................................74 9.1 General Safety.....................................................................................................................................74 9.2 Vehicle Safety......................................................................................................................................74 9.3 Care and Maintenance ........................................................................................................................75 9.4 Your Responsibility ..............................................................................................................................75 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 9 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 365 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 10 RECOMMENDED ACCESSORIES..........................................................................................................76 11 ONLINE SUPPORT ..................................................................................................................................77 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 10 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 366 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual List of Figures Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Figure 1: Complete package contents..............................................................................................................17 Figure 2: Packaging box...................................................................................................................................18 Figure 3: Production Label ...............................................................................................................................19 Figure 4: FASTRACK Supreme general description ........................................................................................20 Figure 5: FASTRACK Supreme holding bridles ...............................................................................................21 Figure 6: SMA connector for antenna connection ............................................................................................22 Figure 7: Power supply connector ....................................................................................................................23 Figure 8: Sub HD 15-pin connector ..................................................................................................................24 Figure 9: IES connector for feature expansion.................................................................................................26 Figure 10: Power supply cable .........................................................................................................................29 Figure 11: SIM card lock feature ......................................................................................................................35 Figure 12: FASTRACK Supreme mounting......................................................................................................36 Figure 13: Recommended power supply connection on trucks........................................................................38 Figure 14: Example of electrical connection which may dramatically damage the FASTRACK Supreme ......39 Figure 15: Functional architecture ....................................................................................................................50 Figure 16: RS232 Serial Link signals ...............................................................................................................52 Figure 17: Reset sequence diagram ................................................................................................................56 Figure 18: Dimensioning diagram.....................................................................................................................60 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 11 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 367 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual List of Tables Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 . Table 1: Power supply connector pin description.............................................................................................23 Table 2: Sub HD 15-pin connector description.................................................................................................24 Table 3: IES Connector Description .................................................................................................................27 Table 4: Basic features of the FASTRACK Supreme.......................................................................................31 Table 5: FASTRACK Supreme operational status ...........................................................................................40 Table 6: Values of received signal strength .....................................................................................................41 Table 7: AT+CPIN Responses .........................................................................................................................41 Table 8: AT+WMBS Band Selection ................................................................................................................42 Table 9: AT+WMBS Responses.......................................................................................................................42 Table 10: Values of network registration ..........................................................................................................43 Table 11: Main usual AT commands for the Plug & Play .................................................................................44 Table 12: Solutions for no connection with FASTRACK Supreme through serial link .....................................46 Table 13: Solutions for "NO CARRIER" message............................................................................................48 Table 14: Interpretation of extended error code ...............................................................................................49 Table 15: Mechanical characteristics ...............................................................................................................59 Table 16: Electrical characteristics ...................................................................................................................61 Table 17: Effects of power supply defect..........................................................................................................61 Table 18: Power consumption (1*) ...................................................................................................................62 Table 19: Audio parameters caracteristics .......................................................................................................65 Table 20: Microphone inputs internal audio filter characteristics .....................................................................65 Table 21: Recommended characteristics for the microphone: .........................................................................65 Table 22: Recommended characteristics for the speaker: ...............................................................................66 Table 23: Operating conditions.........................................................................................................................66 Table 24: SIM card characteristics ...................................................................................................................66 Table 25: Electrical characteristics ...................................................................................................................66 Table 26: Operating conditions.........................................................................................................................67 Table 27: Frequency ranges.............................................................................................................................67 Table 28: Receiver and transmitter RF performances .....................................................................................68 Table 29: External antenna characteristics ......................................................................................................69 Table 30: Ranges of temperature.....................................................................................................................69 Table 31: Environmental standard constraints .................................................................................................70 Table 32: List of recommended accessories....................................................................................................76 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 12 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 368 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 References Fastrack Supreme User Guide References 1.1 Reference Documents For more details, several reference documents may be consulted. The Wavecom reference documents are provided in the Wavecom documents package contrary to the general reference documents, which are not Wavecom owned. 1.1.1 Open AT® Software Documentation [1] Getting started with Open AT® (Ref.WM_ASW_OAT_CTI_001) [2] Open AT® Tutorial (Ref.WM_ASW_OAT_UGD_001) [3] Tools Manual (Ref. WM_ASW_OAT_UGD_003) [4] Open AT® Programming Guide (Ref. TBD) [5] Open AT® Customer Release Note (Ref. WM_ASW_OAT_DVD_00062) Remark: The document above is for Open AT3.12 and FASTRACK Supreme will use new release of Open AT4.21. Reference document not yet available and TBC. 1.1.2 AT Software Documentation [6] AT commands interface Guide for X51 (Ref. WM_ASW_OAT_UGD_00016) [7] Customer Release Note X51 (Ref. WM_ASW_OAT_DVD_00120) Remark: The document above is for X51 and FASTRACK Supreme will use new release of FW6.63. Reference document not yet available and TBC. 1.1.3 Firmware Upgrade Documents [8] Firmware upgrade procedure (Ref. WM_SW_GEN_UGD_001) 1.1.4 Delta between M1306B Documents [9] Delta between M1306B and FASTRACK Supreme (Ref. WA_DEV_Fastrk_UGD_004) 1.1.5 IESM Related Documents [10] IESM Product Technical Specification (Ref. WA_DEV_Fastrk_PTS_001) [11] IESM-GPS+USB User Guide (Ref. WA_DEV_Fastrk_UGD_002) [12] IESM-GPS+USB Installation Guide (Ref. WA_DEV_Fastrk_UGD_003) [13] IESM-IO+USB Installation Guide (Ref. WA_DEV_Fastrk_UGD_005) [14] IESM-IO+USB User Guide (Ref. WA_DEV_Fastrk_UGD_006) confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 13 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 369 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide References Note: New versions of software may be available. Wavecom recommends customers to check the web site for the latest documentation. 1.2 Abbreviations Abbreviation AC ACM AMR AT CLK CMOS CS CTS dB dBc dBi dBm DC DCD DCE DCS DSR DTE DTMF DTR EEPROM EFR E-GSM EMC EMI ESD ETSI FIT FR Definition Alternating Current Accumulated Call Meter Adaptive Multi-Rate ATtention (prefix for Wireless CPU® commands) CLocK Complementary Metal Oxide Semiconductor Coding Scheme Clear To Send Decibel Decibel relative to the Carrier power Decibel relative to an Isotropic radiator Decibel relative to one milliwatt Direct Current Data Carrier Detect Data Communication Equipment Digital Cellular System Data Set Ready Data Terminal Equipment Dual Tone Multi-Frequency Data Terminal Ready Electrically Erasable Programmable Read-Only Memory Enhanced Full Rate Extended GSM ElectroMagnetic Compatibility ElectroMagnetic Interference ElectroStatic Discharges European Telecommunications Standards Institute Series of connectors (micro-FIT) Full Rate confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 14 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 370 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Abbreviation FTA GCF GND GPIO GPRS GSM HR I IEC IES IESM IMEI I/O LED MAX ME MIC Micro-Fit MIN MNP MO MS MT NOM O Pa PBCCH PC PCL PDP PIN PLMN PUK RF Fastrack Supreme User Guide References Definition Full Type Approval Global Certification Forum GrouND General Purpose Input Output General Packet Radio Service Global System for Mobile communications Half Rate Input International Electrotechnical Commission Internal Expansion Socket Internal Expansion Socket Module International Mobile Equipment Identification Input / Output Light Emitting Diode MAXimum Mobile Equipment MICrophone Family of connectors from Molex MINimum Microcom Networking Protocol Mobile Originated Mobile Station Mobile Terminated NOMinal Output Pascal (for speaker sound pressure measurements) Packet Broadcast Control CHannel Personal Computer Power Control Level Packet Data Protocol Personal Identity Number Public Land Mobile Network Personal Unblocking Key Radio Frequency confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 15 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 371 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Abbreviation RFI RI RMS RTS RX SIM SMA SMS SNR SPL SPK SRAM TCP/IP TDMA TU TUHigh TX TYP VSWR Fastrack Supreme User Guide References Definition Radio Frequency Interference Ring Indicator Root Mean Square Request To Send Receive Subscriber Identification Module SubMiniature version A RF connector Short Message Service Signal-to-Noise Ratio Sound Pressure Level SpeaKer Static RAM Transmission Control Protocol / Internet Protocol Time Division Multiple Access Typical Urban fading profile Typical Urban, High speed fading profile Transmit TYPical Voltage Stationary Wave Ratio confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 16 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 372 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2 Packaging Fastrack Supreme User Guide Packaging 2.1 Contents The complete package content of the FASTRACK Supreme consists of (see): · one packaging box (A), · one FASTRACK Supreme (B), · two holding bridles (C), · one power supply cable with fuse integrated (D) · a mini notice (E) with: a summary of the main technical features, safety recommendations, EC declaration of conformity. Figure 1: Complete package contents confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 17 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 373 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.2 Packaging Box Fastrack Supreme User Guide Packaging The packaging box is a carton box (see) with the following external dimensions: · width: 54.5 mm, · height: 68 mm, · length: 108 mm. A packaging label is slicked on the packaging box cover and supports the: · WAVECOM logo, · Product reference (Supreme), · CE marking · 15-digit IMEI code · Open AT® Logo · RoHS logo · WEEE logo The packaging label dimensions are: · height: 40 mm, · length: 65 mm. Figure 2: Packaging box confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 18 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 374 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Packaging 2.3 Production Labelling A production label (see Figure 3) located at the FASTRACK Supreme back side gives the following information: · product reference (FASTRACK Supreme 10 or FASTRACK Supreme 20), · part number (WM19183), · CE marking, · 15-digit IMEI code, · OpenAT® logo Figure 3: Production Label confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 19 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 375 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3 General Presentation Fastrack Supreme User Guide General Presentation 3.1 Description The FASTRACK Supreme description is given in the Figure 4 below. Micro-Fit connector Screw for Back Plate Back Plate SIM card inside SIM connector Lock switch of SIM connector IES connector for expanding feature, like GPS, USB, I/O expander... Refer to Section 3.2.1.4 Removed Screw for Back Plate Sub HD connector SMA connector Back Cap GSM LED Indicator Back Cap with 5 screws Removed Back Plate Figure 4: FASTRACK Supreme general description confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 20 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 376 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation CAUTION: Users are free to remove the back plate for IESM board plug in/unplug without voiding the warrantee of the FASTRACK Supreme. However, the warrantee will be voided if unscrewing any screw of the back cap. In addition, two holding bridles are provided to tighten the FASTRACK Supreme on a support. Holding bridles Figure 5: FASTRACK Supreme holding bridles confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 21 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 377 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.2 External Connections 3.2.1 Connectors Fastrack Supreme User Guide General Presentation 3.2.1.1 Antenna Connector The antenna connector is a SMA type connector for a 50 RF connection. SMA connector for antenna connection Figure 6: SMA connector for antenna connection 3.2.1.2 Power Supply Connector The power supply connector is a 4-pin Micro FIT connector for: · external DC Power Supply connection, · GPIOs connection (two General Purpose Input/Output signals available). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 22 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 378 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 Fastrack Supreme User Guide General Presentation 3 4 Figure 7: Power supply connector Table 1: Power supply connector pin description Pin # Signal I/O 1 V+BATTERY I I/O type Power supply Description Battery voltage input: 5.5 V Min. 13.2 V Typ. 32 V Max. Reset State Comment High current 2 GND Power supply Ground 3 GPIO21 I/O 2V8 General Purpose Input/output Undefined Not mux 4 GPIO25 I/O 2V8 General Purpose Input/output Z Multiplex with INT1 Warning: Both pin 3 and pin 4 are used by GPIO interface. It is strictly prohibited to connect them to any power supply at the risk of damage to the FASTRACK Supreme. 3.2.1.3 Sub HD 15-pin Connector The Sub D high density 15-pin connector is used for: · RS232 serial link connection, · Audio lines (microphone and speaker) connection, · BOOT and RESET signal connection. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 23 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 379 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation 54321 10 9 8 7 6 15 14 13 12 11 Figure 8: Sub HD 15-pin connector Pin # 1 2 3 4 5 6 7 8 9 Table 2: Sub HD 15-pin connector description Signal (CCITT / EIA) CDCD/CT109 CTXD/CT103 BOOT I/O I/O type O STANDARD RS232 I STANDARD RS232 I CMOS Description RS232 Data Carrier Detect RS232 Transmit serial data Boot CMIC2P CMIC2N CRXD/CT104 CDSR/CT107 CDTR/CT108-2 GND I Analog I Analog O STANDARD RS232 O STANDARD RS232 I STANDARD RS232 - GND Microphone positive line Microphone negative line RS232 Receive serial data RS232 Data Set Ready RS232 Data Terminal Ready Ground Comment This signal must not be connected. Its use is strictly reserved to Wavecom or competent retailers. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 24 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 380 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Pin # 10 11 12 13 14 15 Signal (CCITT / EIA) CSPK2P CCTS/CT106 CRTS/CT105 CRI/CT125 RESET CSPK2N I/O I/O type Fastrack Supreme User Guide General Presentation Description Comment O Analog Speaker positive line O STANDARD RS232 RS232 Clear To Send I STANDARD RS232 RS232 Request To Send O STANDARD RS232 RS232 Ring Indicator I/O Schmitt Supreme Plug & Play reset Active low O Analog Speaker negative line 3.2.1.4 IES Connector The IES connector is a 50 pins board-to-board connector for expanding application features like GPS, USB, I/O expander... Currently there are already 3 IESM boards available for customer to expand the FASTRACK Supreme features immediately. They are: IESM-GPS+USB+I/O IESM-GPS+USB IESM-USB+I/O For detail, please refer to Document in Section 1.1.5. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 25 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 381 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation For sales and support, please contact Wavecom sales/FAE or your distributor. Pin 2 Pin 1 Pin 50 Pin 49 Figure 9: IES connector for feature expansion confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 26 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 382 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation Pin Number 1 2 3 4 5 6 7 8 9 Signal Name Nominal Mux GND GND GPIO4 COL0 GPIO5 COL1 GPIO6 COL2 GPIO7 COL3 VPAD-USB USB-DP USB-DM 10 GSM-1V8* 11 GSM-2V8* 12 BOOT 13 ~RESET 14 AUX-ADC 15 ~SPI1-CS GPIO31 16 SPI1-CLK GPIO32 17 SPI1-I GPIO30 18 SPI1-IO GPIO29 19 SPI2-CLK GPIO32 20 SPI2-IO GPIO33 21 ~SPI2-CS GPIO35 22 SPI2-I GPIO34 23 CT104RXD2 GPIO15 24 CT103-TXD2 GPIO14 25 ~CT106CTS2 GPIO16 26 ~CT105RTS2 GPIO17 Table 3: IES Connector Description I/O type Voltage I/O* Reset State Description Dealing with unused pins Ground Ground C8 GSM-1V8 I/O Pull-up Keypad column 0 NC C8 GSM-1V8 I/O Pull-up Keypad column 1 NC C8 GSM-1V8 I/O Pull-up Keypad column 2 NC C8 GSM-1V8 I/O Pull-up Keypad column 3 NC VPAD-USB I USB Power supply input NC VPAD-USB I/O USB Data NC VPAD-USB I/O GSM-1V8 O GSM-1V8 O GSM-1V8 I C4 GSM-1V8 I/O A2 Analog I C1 GSM-2V8 O C1 GSM-2V8 O C1 GSM-2V8 I C1 GSM-2V8 I/O C1 GSM-2V8 O C1 GSM-2V8 I/O C1 GSM-2V8 O C1 GSM-2V8 I C1 GSM-1V8 O C1 GSM-1V8 I C1 GSM-1V8 O C1 GSM-1V8 I USB Data NC 1.8V Supply Output (for GPIO pull-up only) 2.8V Supply Output (for GPIO pull-up only) Not Used NC NC Add a test point / a jumper/ a switch to VCC_1V8 (Pin 10) in case Download Specific mode is used (See product specification for details) RESET Input NC or add a test point Analog to Digital Input Pull to GND Z SPI1 Chip Select NC Z SPI1 Clock NC Z SPI1 Data Input NC Z SPI1 Data Input / Output NC Z SPI2 Clock NC Z SPI2 Data Input / Output NC Z SPI2 Chip Select NC Z SPI2 Data Input NC Z Auxiliary RS232 Receive Add a test point for firmware upgrade (TXD2) Pull-up to Z Auxiliary RS232 Transmit VCC_1V8 with 100k and add a test point for firmware update Z Auxiliary RS232 Clear To (CTS2) Add a test point Send for firmware update Z Auxiliary RS232 Request (RTS2) Pull-up to To Send VCC_1V8 with 100k and add a test point for confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 27 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 383 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Pin Number Signal Name Nominal Mux 27 GPIO8 COL4 28 GPIO26 SCL 29 GPIO19 30 GPIO27 SDA 31 GPIO20 32 INT0 GPIO3 33 GPIO23 ** 34 GPIO22 ** 35 ~CT108-2DTR1 GPIO41 36 PCM-SYNC 37 PCM-IN 38 PCM-CLK 39 PCM-OUT 40 AUX-DAC 41 VCC-2V8 42 GND 43 DC-IN 44 DC-IN 45 GND 46 4V 47 4V 48 GND 49 GND 50 GND I/O type C8 A1 C1 A1 C1 C1 C1 C1 C1 C5 Fastrack Supreme User Guide General Presentation Voltage I/O* Reset State Description Dealing with unused pins GSM-1V8 I/O Pull-up Keypad column 4 firmware update NC Open Drain O Z I²C Clock NC GSM-2V8 I/O Z NC Open Drain I/O Z I²C Data NC GSM-2V8 I/O Undefined GSM-1V8 I Z Interruption 0 Input GSM-2V8 I/O Z NC If INT0 is not used, it should be configured as GPIO NC GSM-2V8 GSM-2V8 GSM-1V8 I/O Z I Z O Pull-down Main RS232 Data Terminal Ready PCM Frame Synchro NC (DTR1) Pull-up to VCC_2V8 with 100k NC GSM-1V8 I Pull-up PCM Data Input NC GSM-1V8 O Pull-down PCM Clock NC GSM-1V8 O Pull-up PCM Data Output NC Analog O Digital to Analog Output NC VCC_2V8 O LDO 2.8V Supply Output NC DC-IN from 5.5V~32VDC O DC-IN from 5.5V~32VDC O Ground DC voltage input through Micro-Fit connector NC DC voltage input through Micro-Fit connector NC Ground 4V O 4V O 4V DC/DC converter Output NC 4V DC/DC converter Output NC Ground Ground Ground confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 28 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 384 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.2.2 Power supply cable Fastrack Supreme User Guide General Presentation Figure 10: Power supply cable confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 29 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 385 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Component Micro-Fit connector 4-pin Cable Wire Fastrack Supreme User Guide General Presentation Characteristics Part number: MOLEX 43025-0400 Cable length: 1.5 m Core: tinned copper 24 x 0.2 mm Section: 0.75 mm2 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 30 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 386 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4 Features and Services Fastrack Supreme User Guide Features and Services 4.1 Basic Features and Services Basic features of the FASTRACK Supreme and available services are summarized in the table below. Table 4: Basic features of the FASTRACK Supreme Features Open AT® GSM850 / GSM900 DCS1800 / PCS1900 Open AT® programmable: Native execution of embedded standard ANSI C applications, Custom AT command creation, Custom application library creation, Standalone operation. Standard 850MHz / 900 MHz. 1800 MHz / 1900MHz E-GSM compliant. Output power: class 4 (2W). Output power: class 1 (1W). Fully compliant with ETSI GSM phase 2 + Fully compliant with ETSI GSM phase 2 + small MS. small MS. GPRS Class 10. PBCCH support. Coding schemes: CS1 to CS4. Compliant with SMG31bis. Embedded TCP/IP stack. EGPRS Output power: 0.5W Output power: 0.4W (for Class 10. FASTRACK Supreme 20 PBCCH support. only) Coding schemes: MCS1 to MCS9. Compliant with SMG31bis. Embedded TCP/IP stack. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 31 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 387 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Features Interfaces SMS Data Fax Audio Fastrack Supreme User Guide Features and Services GSM850 / GSM900 DCS1800 / PCS1900 RS232 (V.24/V.28) Serial interface supporting: Baud rate (bits/s): 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400, 460800 and 921600. Autobauding (bits/s): from 1200 to 921600. 2 General Purpose Input/Output gates (GPIOs) available. 1.8 V / 3 V SIM interface. AT command set based on V.25ter and GSM 07.05 & 07.07. Open AT® interface for embedded application. Open AT® Plug-In Compatible. Text & PDU. Point to point (MT/MO). Cell broadcast. Data circuit asynchronous. Transparent and Non Transparent modes. Up to 14.400 bits/s. MNP Class 2 error correction. V42.bis data compression. Automatic fax group 3 (class 1 and Class 2). Echo cancellation Noise reduction Telephony. Emergency calls. Full Rate, Enhanced Full Rate, Half Rate operation and Adaptive Multi-Rate (FR/EFR/HR/AMR). Dual Tone Multi Frequency function (DTMF). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 32 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 388 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Features GSM850 / GSM900 GSM supplement services Call forwarding. Call barring. Multiparty. Call waiting and call hold. Calling line identity. Advice of charge. USSD Other DC power supply Real Time Clock with calendar Complete shielding For other detailed technical characteristics, refer to Section 8. Fastrack Supreme User Guide Features and Services DCS1800 / PCS1900 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 33 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 389 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.2 Additional NEW Features Fastrack Supreme User Guide Features and Services 4.2.1 Support Additional GSM850/PCS1900 Bands Apart from GSM900/DCS1800, the FASTRACK Supreme Plug & Play now supports also the GSM850/PCS1900 bands. FASTRACK Supreme is fully compliant to PTCRB and FCC also. 4.2.2 IES Interface for Easy Expansion of Application Features The FASTRACK Supreme Plug & Play offers a 50 pin Internal Expansion Socket (IES) Interface accessible for customer use. It is the additional interface which is easy for customers to expand their application features without voiding the warrantee of the FASTRACK Supreme, by simply plugging in an Internal Expansion Socket Module (IESM) board through the matting connector of the IES interface. Thanks to the flexible IES interface, customers are ready to expand the application features by plugging in the corresponding Internal Expansion Socket Module (IESM) of GPS, I/O expander..., etc. For brief description of the interface, please refer to Section 3.2.1.4. For technical detail, please refer to Document [11] or contact your Wavecom distributor or Wavecom FAE. 4.2.3 Serial Port Auto Shut Down or Improving Power Consumption In order to save power consumption when there is no data communication between the Plug & Play and the DTE, FASTRACK Supreme has now implement the Serial Port Auto Shut Down feature. User can activate or deactivate the Serial Port Auto Shut Down mode by simple AT-command. For detail, please refer to Section 7.3.4. 4.2.4 Real Time Clock (RTC) for Saving Date and Time The FASTRACK Supreme has now implemented the Real Time Clock for saving date and time when the Plug & Play is unplugged from the DC power supply through the DC power cable. For detail, please refer to Section 7.8. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 34 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 390 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Features and Services 4.2.5 SIM Card Lock Feature The FASTRACK Supreme has now implemented a SIM connector having a carrier with lock. This helps ensuring the user to have proper SIM card insertion and locked before proper use of GSM network. SIM card is inserted but not locked. GSM network is SIM card is inserted and being locked properly. not ready for use. Only emergency call 112 is GSM network is ready for use. possible. Figure 11: SIM card lock feature confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 35 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 391 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5 Using the FASTRACK Supreme Plug & Play 5.1 Getting Started 5.1.1 Mount the FASTRACK Supreme To mount the FASTRACK Supreme on its support, bind it using the holding bridles as shown in the Figure 12 below. Figure 12: FASTRACK Supreme mounting For the drill template, refer to Figure 18. 5.1.2 Set up the FASTRACK Supreme To set up the FASTRACK Supreme, perform the following operations: · Insert the SIM card into the SIM card holder of the FASTRACK Supreme. · Lock the SIM card by sliding the lever towards the SIM card. · Connect the antenna to the SMA connector. · Connect both sides of the serial and control cable (15-pin Sub HD connector on the FASTRACK Supreme side). · Connect the power supply cable to the external power supply source. Note: For automotive application, it is recommended to connect the V+BATTERY line of the FASTRACK Supreme directly to the battery positive terminal. · Plug the power supply cable into the FASTRACK Supreme and switch on the external power supply source. · The FASTRACK Supreme is ready to work. Refer to Section 5.10 for the description of AT commands used to configure the FASTRACK Supreme. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 36 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 392 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.1.3 Check the communication with the FASTRACK Supreme To check the communication with the FASTRACK Supreme, do the following operations: · Connect the RS232 link between the DTE (port COM) and the FASTRACK Supreme (DCE). · Configure the RS232 port of the DTE as follows: Bits per second: 115.200 bps, Data bits: 8, Parity: None, Stop bits: 1, Flow control: hardware. · Using a communication software such as a HyperTerminal, enter the AT command. The response of the FASTRACK Supreme must be OK displayed in the HyperTerminal window. · If the communication cannot be established with the FASTRACK Supreme, do the following: Check the RS232 connection between the DTE and the FASTRACK Supreme (DCE), Check the configuration of the port COM used on the DTE. · Example of AT commands which can be used after getting started the FASTRACK Supreme: AT+CGMI: FASTRACK Supreme answer is "WAVECOM MODEM" when serial link is OK. AT+CPIN=xxxx: to enter a PIN code xxxx (if activated). AT+CSQ: to verify the received signal strength. AT+CREG?: to verify the registration of the FASTRACK Supreme Plug & Play on the network. ATD<phone number>;: to initiate a voice call. ATH: to hang up (end of call). For further information on these AT commands and their associated parameters, refer to "AT Commands Interface Guide" [6]. 5.1.4 Reset the FASTRACK Supreme To reset the FASTRACK Supreme, a hardware reset signal is available on pin 14 of the Sub HD 15-pin connector (RESET). The FASTRACK Supreme reset is carried out when this pin is low for at least 200 s. Warning This signal has to be considered as an emergency reset only. For further details on the FASTRACK Supreme reset, refer to Section 7.7. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 37 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 393 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.2 Specific Recommendations when Using the FASTRACK Supreme on Trucks Warning: The power supply connection of the FASTRACK Supreme must NEVER be directly connected to the truck battery. 5.2.1 Recommended Power Supply Connection on Trucks All trucks have a circuit breaker on the exterior of the cabin. The circuit breaker is used for safety reasons: if a fire blazes in the trucks, (for example, on the wiring trunk) the driver may cut the current source to avoid any damage (explosion). The circuit breaker is connected to the truck ground, most often associated with the fuse box. Most of truck circuit breakers do not cut the Positive Supply line of the battery, but cut the ground line of the later. FASTRACK Suprem e Figure 13: Recommended power supply connection on trucks Figure 13 gives the recommended power supply connection where the ground connection of the FASTRACK Supreme is not directly connected to the battery but is connected after the Circuit Breaker (on the truck ground or the fuse box). 5.2.2 Technical Constraints on Trucks It is highly not recommended to connect directly the power supply on the battery rather than on the circuit breaker. The FASTRACK Supreme may be damaged when starting the truck if the circuit breaker is switched OFF (in this case, the truck ground and the battery ground will be connected through the FASTRACK Supreme as shown in the figure below). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 38 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 394 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play FASTRACK Supreme Figure 14: Example of electrical connection which may dramatically damage the FASTRACK Supreme Figure 14 gives an example of electrical connection which may dramatically damage the FASTRACK Supreme when its ground connection is directly connected to the battery ground. In this example, when the circuit breaker is switched OFF, the current flows through the FASTRACK Supreme and powers the electrical circuit of the truck (for example, dashboard). Furthermore, when the Starter Engine command will be used, it will destroy the cables or the FASTRACK Supreme. Since the internal tracks are not designed to support high current (up to 60 A when starting the truck), they will be destroyed. 5.3 FASTRACK Supreme Operational Status The FASTRACK Supreme operational status is given by the red LED status located next to the SIM connector on the FASTRACK Supreme panel. The Table 5 below gives the meaning of the various statuses available. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 39 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 395 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play Table 5: FASTRACK Supreme operational status LED Status LED light activity FASTRACK Supreme Plug & Play status ON LED ON permanent FASTRACK Supreme is switched ON but not registered on the network LED Flashing slowly FASTRACK Supreme is switched ON and registered on the network, but no communication is in progress (Idle mode) LED Flashing rapidly FASTRACK Supreme is switched ON and registered on the network, and a communication is in progress OFF LED OFF FASTRACK Supreme is switched OFF, or Flash LED is disabled* by the user. * : Flash LED can be disabled by user when in Slow Standby mode in order to save power consumption. For detail, please refer to Section 7.9. 5.4 Echo Function Disabled If no echo is displayed when entering an AT command, that means: · The "local echo" parameter of your communication software (such as HyperTerminal) is disabled. · The FASTRACK Supreme echo function is disabled. To enable the FASTRACK Supreme echo function, enter the ATE1. When sending AT commands to the FASTRACK Supreme by using a communication software, it is recommended: · to disable the "local echo" parameter of your communication software (such as HyperTerminal), · to enable the FASTRACK Supreme echo function (ATE1 command). In a Machine To Machine communication with the FASTRACK Supreme, it is recommended to disable the FASTRACK Supreme echo function (ATE0 command) in order to avoid useless CPU processing. For further information on ATE0 and ATE1 commands, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 40 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 396 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5.5 Verify the Received Signal Strength Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play The FASTRACK Supreme establishes a call only if the received signal is sufficiently strong. To verify the received signal strength, do the following operations: · Using a communication software such as HyperTerminal, enter the AT command AT+CSQ. The response returned has the following format: +CSQ: <rssi>,<ber> with: · <rssi> = received signal strength indication, · <ber> = channel bit error rate. · Verify the <rssi> value returned using the Table 6 below. Table 6: Values of received signal strength Value of received signal strength indication (<rssi>) 0 - 10 Interpretation of the received signal strength Insufficient(*) 11 - 31 Sufficient(*) 32 - 98 99 (*) Based on general observations. Not defined No measure available For further information on AT commands, refer to "AT Commands Interface Guide" [6]. 5.6 Check the Pin Code Status To check that the pin code has been entered, use a communication software such as a HyperTerminal, then enter AT+CPIN? command. The table below gives the main responses returned: Table 7: AT+CPIN Responses AT+CPIN response (*) +CPIN: READY Interpretation Code PIN has been entered +CPIN: SIM PIN Code PIN has not been entered (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. 5.7 Switch between EU/US Band(s) To switch between EU/US band(s) for the FASTRACK Supreme, use a communication software such as a HyperTerminal, then enter AT+WMBS=<band>[,<param>] command. The table below gives the commands for various band(s) selection: confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 41 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 397 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play Table 8: AT+WMBS Band Selection AT+WMBS response (*) AT+WMBS=0,x Interpretation Select mono band mode 850MHz. AT+WMBS=1,x AT+WMBS=2,x AT+WMBS=3,x AT+WMBS=4,x AT+WMBS=5,x Select mono band mode extended 900MHz Select mono band mode 1800MHz Select mono band mode 1900MHz Select dual band mode 850/1900MHz Select dual band mode extended 900MHz/1800MHz AT+WMBS=6,x Select dual band mode extended 900MHz/1900MHz (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. Remark: x=0 : The Plug & Play will have to be reset to start on specified band(s). x=1 : The change is effective immediately. This mode is forbidden while in communication and during Plug & Play initialization. Refer to "AT Commands Interface Guide" [6] for further information on AT commands. 5.8 Check the Band(s) Selection To check the band selection for the FASTRACK Supreme, use a communication software such as a HyperTerminal, then enter AT+WMBS? command. The table below gives the main responses returned: Table 9: AT+WMBS Responses AT+WMBS response (*) +WMBS: 0,x Interpretation Mono band mode 850MHz is selected +WMBS: 1,x Mono band mode extended 900MHz is selected +WMBS: 2,x Mono band mode 1800MHz is selected +WMBS: 3,x Mono band mode 1900MHz is selected +WMBS: 4,x Dual band mode 850/1900MHz are selected +WMBS: 5,x Dual band mode extended 900MHz/1800MHz are selected +WMBS: 6,x Dual band mode extended 900MHz/1900MHz are selected (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 42 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 398 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.9 Verify the FASTRACK Supreme Network Registration 1. Make sure a valid SIM card has been previously inserted and locked in the FASTRACK Supreme SIM card holder. 2. Using a communication software such as a HyperTerminal, enter the following AT commands: a. AT+CPIN=xxxx to enter PIN code xxxx. b. AT+WMBS? To check the current band setting in the Plug & Play c. AT+WMBS=<Band>[,<param>] To switch band/mode when needed d. AT+CREG?. To ascertain the registration status. The format of the returned response is as follows: +CREG: <mode>,<stat> with: · <mode> = unsolicited registration message configuration, · <stat> = registration state. 3. Verify the state of registration according the returned value given in the table below. Table 10: Values of network registration Returned Value (*) Network registration <mode>,<stat> +CREG: 0,0 No (not registered) +CREG: 0,1 Yes (registered, home network) +CREG: 0,5 Yes (registered, roaming) (*)For further information on the other returned values and their meaning, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 43 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 399 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play If the FASTRACK Supreme is not registered, perform the following procedure: · Check the connection between the FASTRACK Supreme and the antenna. · Verify the signal strength to determine the received signal strength (refer to Section 5.5). Note: For information on AT command relating to the network registration in GPRS mode, and in particular: CGREG, CGCLASS, CGATT, refer to "AT Commands Interface Guide" [6]. 5.10 Main AT Commands for the Plug & Play The table below lists the main AT commands required for starting the Plug & Play. For other AT commands available or further information on the AT commands, refer to "AT Commands Interface Guide" [6]. Table 11: Main usual AT commands for the Plug & Play Description AT commands Check for selected AT+WMBS? band(s) Band(s) switch AT+WMBS=<Band> AT+WMBS=<Band>,0 AT+WMBS=<Band>,1 Enter PIN Code AT+WMBS=<Band> AT+CPIN=xxxx (xxxx = PIN code) Network registration checking AT+CREG? FASTRACK Supreme Plug & Play response Comment +WMBS:<Band>,<ResetFlag> Current selected band OK mode is return OK Band switch is accepted, Plug & Play has to be reset for change to be effective OK Band switch is accepted, Plug & Play has to be reset for change to be effective OK Band switch is accepted and GSMS stack restarted +CME ERROR: 3 Band not allowed OK PIN Code accepted. +CME ERROR: 16 Incorrect PIN Code (with +CMEE = 1 mode) (1*) +CME ERROR: 3 PIN code already entered (with +CMEE = 1 mode) (1*) +CREG: 0,1 FASTRACK Supreme Plug & Play registered on the network. +CREG: 0,2 FASTRACK Supreme Plug & Play not registered on the network, registration attempt. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 44 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 400 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Description Receiving an incoming call Initiate a call Initiate an emergency call Communication loss Hang up AT commands ATA Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play FASTRACK Supreme Plug & Play response Comment +CREG: 0,0 FASTRACK Supreme Plug & Play not registered on the network, no registration attempt. OK Answer the call. ATD<phone number>; OK (Don't forget the « ; » at the end for « voice » call) +CME ERROR: 11 +CME ERROR: 3 ATD112; OK (Don't forget the « ; » at the end for « voice » call) NO CARRIER Communication established. PIN code not entered (with +CMEE = 1 mode). AOC credit exceeded or a communication is already established. Communication established. ATH OK Store the AT&W OK parameters in EEPROM The configuration settings are stored in EEPROM. (1*) The command "AT+CMEE=1" switch to a mode enabling more complete error diagnostics. 5.11 Firmware Upgrade Procedure The firmware upgrade procedure is used to update the firmware embedded into the FASTRACK Supreme. That procedure consists in downloading the firmware into internal memories through the RS232 serial link available on the SUB-D 15-pin connector. Refer to "Firmware upgrade procedure" [8] for a detailed description of this procedure. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 45 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 401 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6 Troubleshooting Fastrack Supreme User Guide Troubleshooting This section of the document describes possible problems encountered when using the FASTRACK Supreme and their solutions. To review other troubleshooting information, refer the `FAQs' (Frequently Asked Questions) page at www.wavecom.com or use the following link: http://www.wavecom.com/support/faqs.php 6.1 No Communication with the FASTRACK Supreme through the Serial Link If the FASTRACK Supreme does not answer to AT commands through the serial link, refer to the table below for possible causes and solutions. Table 12: Solutions for no connection with FASTRACK Supreme through serial link If the Supreme returns Nothing then ask Is the FASTRACK Supreme powered correctly? Is the serial cable connected at both sides? Does the serial cable follow correctly pin assignment shown in paragraph 3.2.1.2. Nothing or non- Is the communication program significant characters properly configured on PC? Is there another program interfering with the communication program (i.e. Conflict on communication port access) Action Make sure the external power supply is connected to the FASTRACK Supreme and provides a voltage in the range of 5.5 V to 32 V. Check the serial cable connection Connect the cable by following pin assignment given in paragraph 3.2.1.1. Ensure the setting of the communication program is fit to setting of FASTRACK Supreme. FASTRACK Supreme factory setting is: Data bits = 8 Parity = none Stop bits = 1 Baud = 115 200 bps. Flow control = hardware Close the interfering program. 6.2 Receiving "ERROR" Message The FASTRACK Supreme returns an "ERROR" message (in reply to an AT command) in the following cases: confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 46 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 402 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting · AT command syntax is incorrect: check the command syntax (refer to "AT Commands Interface Guide" [6]), · AT command syntax is correct, but transmitted with wrong parameters: · Enter the AT+CMEE=1 command in order to change the error report method to the verbose method, which includes the error codes. · Enter again the AT command which previously caused the reception of "ERROR" message in order to get the Mobile Equipment error code. When the verbose error report method is enabled, the response of the FASTRACK Supreme in case of error is as follows: · Either +CME ERROR: <error result code>, · Or +CMS ERROR: <error result code>. Refer to "AT Commands Interface Guide" [6] for error result code description and further details on the AT +CMEE command. Note: It is strongly recommended to always enable the verbose error report method to get the Mobile Equipment error code (enter AT +CMEE=1 command). 6.3 Receiving "NO CARRIER" Message If the FASTRACK Supreme returns a "NO CARRIER" message upon an attempted call (voice or data), then refer to the table below for possible causes and solutions. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 47 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 403 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting Table 13: Solutions for "NO CARRIER" message If the Supreme returns... "NO CARRIER" Then ask... Is the received signal strong enough? Is the FASTRACK Supreme registered on the network? Is the antenna properly connected? Is the band selection correction? "NO CARRIER" (when Is the semicolon (;) entered immediately trying to issue a voice after the phone number in the AT communication) command? Action... Refer to section 5.5 to verify the strength of the received signal. Refer to section 5.9 to verify the registration. Refer to section 8.2.7.3 for antenna requirements. Refer to Section 7.2 for band switch Ensure that the semicolon (;) is entered immediately after the phone number in the AT command. e.g. ATD######; "NO CARRIER" (when Is the SIM card configured for data / fax trying to issue a data calls? communication) Configure the SIM card for data / fax calls (Ask your network provider if necessary). Is the selected bearer type supported by the Ensure that the selected bearer type called party? is supported by the called party. Is the selected bearer type supported by the Ensure that the selected bearer type network? is supported by the network. If no success, try bearer selection type by AT command: AT+CBST=0,0,3 If the FASTRACK Supreme returns a "NO CARRIER" message, you may have the extended error code by using AT command AT+CEER. Refer to the table below for interpretation of extended error code. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 48 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 404 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting Table 14: Interpretation of extended error code Error Code 1 16 17 18 19 21 22 31 50 Diagnostic Unallocated phone number Normal call clearing User busy No user responding User alerting, no answer Call rejected Number changed Normal, unspecified Requested facility not subscribed 68 ACM equal or greater than ACMmax 252 Call barring on outgoing calls 253 Call barring on incoming calls 3, 6, 8, 29, 34, 38, 41, 42, 43, 44, 47, 49, 57, 58, 63, 65, 69, 70, 79, 254 Network causes Hint Check your subscription (data subscription available?). Credit of your pre-paid SIM card expired. See "AT Commands Interface Guide" [6] for further details or call network provider. Note: For all other codes, and/or details, see AT commands documentation [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 49 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 405 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7 Functional Description Fastrack Supreme User Guide Functional Description 7.1 Architecture FASTRACK Supreme Plug & Play BOOT RESET Microphone Speaker SUB HD 15 pins GPIO-21 GPIO-25 V+BATT GROUND Micro-FIT 4 pins RS232 Interface VCC Audio Interface VCC SMA Microphone Internal Quik Wireless CPU® Q2687 Speaker Operating Status DC / DC VCC Power Supply 50 pin IES Interface SIM card Holder Figure 15: Functional architecture confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 50 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 406 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.2 EU and US Bands Fastrack Supreme User Guide Functional Description 7.2.1 General Presentation The FASTRACK Supreme is a quad band Plug & Play. It supports either EU bands (EGSM900/DCS1800) or US bands (GSM850/ PCS1900), depending on the band setting within the Plug & Play. Users are free to switch between EU bands and US bands by simple AT commands when the selected bands are supported. 7.2.2 AT COMMAND for Bands Switch EU/US band is easily switched/checked by AT command AT+WMBS. For detail, please refer to Section 5.7 and 5.8. 7.3 Power Supply 7.3.1 General Presentation The FASTRACK Supreme is supplied by an external DC voltage (V+BATTERY) from +5.5 V to +32 V at 2.2 A. Main regulation is made with an internal DC/DC converter in order to supply all the internal functions with a DC voltage. Correct operation of the FASTRACK Supreme in communication mode is not guaranteed if input voltage (V+BATTERY) falls below 5.5 V. Note: The minimum input voltage specified here is at the FASTRACK Supreme input. Be careful of the input voltage decrease caused by the power cable. See paragraph 8.2.1 for more information. 7.3.2 Protections The FASTRACK Supreme is protected by a 800 mA / 250 V fuse directly bonded on the power supply cable. The FASTRACK Supreme is also protected against voltage over +32 V. Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. 7.4 RS232 Serial Link 7.4.1 General Presentation The RS232 interface performs the voltage level adaptation (V24/CMOS V24/V28) between the internal FASTRACK Supreme Plug & Play (DCE) and the external world (DTE). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 51 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 407 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description The RS232 interface is internally protected (by ESD protection) against electrostatic surges on the RS232 lines. Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. Signals available on the RS232 serial link are: · TX data (CT103/TX), · RX data (CT104/RX), · Request To Send (CT105/RTS), · Clear To Send (CT106/CTS), · Data Terminal Ready (CT108-2/DTR), · Data Set Ready (CT107/DSR), · Data Carrier Detect (CT109/DCD), · Ring Indicator (CT125/RI). FASTRACK Supreme (DCE) CT103 / TX CT104 / RX CT105 / RTS CT106 / CTS CT107 / DSR CT108-2 / DTR CT109 / DCD CT125 / RI DTE Figure 16: RS232 Serial Link signals RS232 interface has been designed to allow flexibility in the use of the serial interface signals. However, the use of TX, RX, CTS and RTS signals is mandatory, which is not the case for DTR, DSR, DCD and RI signals which can be not used. 7.4.2 Autobauding Mode The autobauding mode allows the FASTRACK Supreme to detect the baud rate used by the DTE connected to the RS232 serial link. Autobauding mode is controlled by AT commands. See "AT Commands Interface Guide" [6] for details on this function. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 52 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 408 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.4.3 Pin Description Fastrack Supreme User Guide Functional Description Signal CTXD/CT103 CRXD/CT104 CRTS/CT105 CCTS/CT106 CDSR/CT107 CDTR/CT108-2 CDCD/CT109 CRI/CT125 CT102/GND Sub HD connector I/O I/O type Pin number RS232 STANDARD Description 2 I TX Transmit serial data 6 O RX Receive serial data 12 I RTS Request To Send 11 O CTS Clear To Send 7 O DSR Data Set Ready 8 I DTR Data Terminal Ready 1 O DCD Data Carrier Detect 13 O RI Ring Indicator 9 GND Ground 7.4.4 Serial Port Auto shut down Feature The UART1 can be shut down when there is no activity between the DTE and the FASTRACK Supreme Plug & Play. This can help for improving power consumption performance. Serial Port Auto shut down feature is easily controlled by AT command AT+WASR. AT+WASR=1 for entering the serial port auto shut down mode AT+WASR=0 for exiting the serial port auto shut down mode Refer to "AT Commands Interface Guide" [6] for further information on AT commands. CAUTION: GPIO24 is reserved for serial port auto shut down feature. It is prohibited for customer use. Improper access to GPIO24 by customer may lead to unexpected behavior on UART1 performance. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 53 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 409 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.5 General Purpose Input/Output (GPIO) Fastrack Supreme User Guide Functional Description The FASTRACK Supreme provides two General Purpose Input / Output lines available for external use: GPIO21 and GPIO25. These GPIOs may be controlled by AT commands: · AT+WIOW for a write access to the GPIO value, when the GPIO is used as an output, · AT+WIOR for a read access to the GPIO value, when the GPIO is used as an input. Refer to "AT Commands Interface Guide" [6] for further information on AT commands. After reset, both GPIOs are configured as inputs. The AT+WIOM command has to be used to change this configuration (refer to "AT Commands Interface Guide" [6] for further details). Signal GPIO21 GPIO25 Power Supply connector (4-pin Micro-Fit) 3 4 Pin description I/O I/O Voltage Reset state Description Mulitplex with I/O 2V8 Undefined General Purpose I/O No mux I/O 2V8 Z General Purpose I/O INT1 Notes: · The power supply cable may need to be modified due to the GPIO signals (GPIO21 & GPIO25) available on the 4-pin Micro-FIT connector of the FASTRACK Supreme. · The previous generation M1306B have GPIO4 and GPIO5 being replaced by GPIO21 and GPIO25 respectively, for which both are of LOW level at reset state. 7.6 BOOT This signal must not be connected. Its use is strictly reserved to Wavecom or competent retailers. Caution: Previous generation M1306B has BOOT signal of HIGH level at 2.8V. But the FASTRACK Supreme now of 1.8V BOOT instead. 7.7 RESET 7.7.1 General presentation This signal is used to force a reset procedure by providing low level during at least 200 µs. This signal must be considered as an emergency reset only. A reset procedure is automatically driven by an internal hardware during the power-up sequence. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 54 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 410 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description This signal may also be used to provide a reset to an external device. It then behaves as an output. If no external reset is necessary, this input may be left open, if used (emergency reset), it has to be driven either by an open collector or an open drain output: · RESET pin 14 = 0, for FASTRACK Supreme Reset, · RESET pin 14 = 1, for normal mode. Signal RESET Sub HD 15-Pin connector Pin number 14 Pin description I/O I/O type I/O Open Drain Voltage 1V8 Description FASTRACK Supreme Reset Caution: Previous generation M1306B has RESET signal of HIGH level at 2.8V. But the FASTRACK Supreme now of 1.8V RESET instead. Additional comments on RESET: The RESET process is activated either by the external RESET signal or by an internal signal (coming from a RESET generator). This automatic reset is activated at Power-up. The FASTRACK Supreme remains in RESET mode as long as the RESET signal is held low. Caution: This signal should be used only for "emergency" reset. A software reset is always preferred to a hardware reset. Note: See "AT Commands Interface Guide" [6] for further information on software reset. 7.7.2 Reset Sequence To activate the "emergency" reset sequence, the RESET signal has to be set to low for 200 s minimum. As soon as the reset is done, the AT interface answers "OK" to the application. For this, the application must send AT. If the application manages hardware flow control, the AT command may be sent during the initialization phase. Another solution is to use the AT+WIND command to get an unsolicited status from the FASTRACK Supreme. For further details, refer to AT commands "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 55 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 411 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ~ RESET Fastrack Supreme User Guide Functional Description STA TE OF TH E W ireless W ireless CPU CPU REA D Y RESET m od e IBB+ RF= 2 0 t o 40m A Rt = M in 1 :2 0 0 s or Typ2 = 40m s Ct = Typ :34 m s W ireless CPU ON IBB+ RF< 1 2 0 m A w it h ou t loc u p d at e AT an sw ers " OK" W ireless CPU REA D Y SIM an d n etw ork d ep en d en t Figure 17: Reset sequence diagram 7.8 Audio Audio interface is a standard one for connecting a phone handset. Echo cancellation and noise reduction features are also available to improve the audio quality in case of hand-free application. 7.8.1 Microphone Inputs The microphone inputs are differential ones in order to reject common mode noise and TDMA noise. They already include the convenient biasing for an electret microphone (0.5 mA and 2 Volts) and are ESD protected. This electret microphone may be directly connected to these inputs allowing an easy connection to a handset. The microphone impedance must be around 2 k. AC coupling is already embedded in the Wireless CPU®. The gain of the microphone inputs is internally adjusted and may be tuned from 30 dB to 51 dB using an AT +VGT command (refer to AT commands documentation [6]). Signal CMIC2P CMIC2N Pin description Sub D 15-pin Pin # 4 5 I/O I/O type I Analog I Analog Description Microphone positive input Microphone negative input confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 56 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 412 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description 7.8.2 Speaker Outputs This connection is differential to reject common mode noise and TDMA noise. Speaker outputs are connected to internal push-pull amplifiers and may be loaded down between 32 to 150 Ohms and up to 1 nF (see details in table Speaker gain vs Max output voltage, in "AT Commands Interface Guide" [6]). These outputs may be directly connected to a speaker. The output power may be adjusted by step of 2 dB. The gain of the speaker outputs is internally adjusted and may be tuned using an AT +VGR command (refer to AT commands documentation [6]). Pin description Signal Sub D 15-pin Pin # I/O I/O type Description CSPK2P CSPK2N 10 O Analog Speaker positive output 15 O Analog Speaker negative output confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 57 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 413 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description 7.9 Real Time Clock (RTC) The FASTRACK Supreme has now implemented the Real Time Clock for saving date and time when the Plug & Play is unplugged from the DC power supply through the DC power cable. Item Min Typical Max Charging Time start from fully discharged to fully charged 940 min RTC Time Period* Guarantee Non-guarantee 2475 min 5225 min Remark: The RTC time period is measured from the RTC battery is fully charged before being unplugged from the DC power source. 7.10 FLASH LED The FASTRACK Supreme has a red LED indicator to show the status of the GSM network. For detail description of the various status, please refer to Section 5.3. However, during operation mode of Slow Standby, there will be no network registration and so the red LED indicator will always be ON. It is possible for user to deactivate the LED indication during Slow Standby mode, in order to reduce power consumption. The Flash LED can be deactivated by AT command at+whcnf=1,0 The Flash LED can be activated by AT command at+whcnf=1,1 However, the new setting will be taken into account only after a restart. For detail, please refer to Document[6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 58 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 414 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 8 Technical Characteristics Fastrack Supreme User Guide Technical Characteristics 8.1 Mechanical Characteristics Dimensions Overall Dimension Weight Volume Housing Table 15: Mechanical characteristics 73 x 54.5 x 25.5 mm (excluding connectors) 88 x 54.5 x 25.5 mm 80 grams (FASTRACK Supreme only) < 120 grams (FASTRACK Supreme + bridles + power supply cable) 101.5 cm3 Aluminum profiled The next page gives the dimensioning diagram of the FASTRACK Supreme including the clearance areas to take into account for the FASTRACK Supreme installation. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 59 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 415 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Figure 18: Dimensioning diagram confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 60 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 416 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 8.2 Electrical Characteristics Fastrack Supreme User Guide Technical Characteristics 8.2.1 Power Supply Table 16: Electrical characteristics Operating Voltage ranges 5.5 V to 32 V DC. Maximum current 480 mA Average at 5.5V. 2.1 A Peak at 5.5 V. (TBC) Note: The FASTRACK Supreme is permanently powered once the power supply is connected. The following table describes the consequences of over-voltage and under-voltage with the FASTRACK Supreme. Warning: All the input voltages specification described in this Section are at the FASTRACK Supreme input. While powering the FASTRACK Supreme, take into account the input drop caused by the power cable. With the delivered cable, this input drop is around 700 mV at 5.5 V and 220 mV at 32V. Table 17: Effects of power supply defect If the voltage falls below 5.5 V, is over 32 V (Transient peaks), Is over 32 V (continuous overvoltage) then the GSM communication is not guaranteed. the FASTRACK Supreme guarantees its own protection. the protection of the FASTRACK Supreme is done by the fuse (the supply voltage is disconnected). The fuse is a 800 mA / 250 V FAST-ACTING 5*20mm. See Section 10 for recommended references. The following table provides information on power consumption of the FASTRACK Supreme, assuming an operating temperature of +25 °C and using a 3 V SIM card. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 61 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 417 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.2 Power Consumption The following table provides information on power consumption of the FASTRACK Supreme, assuming an operating temperature of +25 °C and using a 3 V SIM card. GSM GPRS Class 2 I peak I avg I peak I avg I peak I avg I peak I avg Table 18: Power consumption (1*) Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 GSM900: During TX bursts @ PCL5 DCS1800 : During TX bursts @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average @ PCL5 DCS1800 : Average @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 1TX bursts @ PCL5 DCS1800 : During 1TX bursts @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 1TX/1RX @PCL5 DCS1800 : Average 1TX/1RX @PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 2TX bursts @ PCL5 (Gamma 3) DCS1800 : During 2TX bursts @ PCL0 (Gamma 2) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 2TX/3RX @ PCL5 (Gamma 3) DCS1800 : Average 2TX/3RX @ PCL0 (Gamma 2) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 1TX bursts @ PCL8 (Gamma 6) DCS1800 : During 1TX bursts @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 1TX/1RX @ PCL8 (Gamma 6) DCS1800 : Average 1TX/1RX @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V TBC TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC GPRS Class 10 EGPRS Class 2 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 62 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 418 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 EGPRS Class 10 I peak GSM900: During 2TX bursts @ PCL8 (Gamma 6) DCS1800 : During 2TX bursts @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V GSM900 : Average 2TX/3RX @ PCL8 (Gamma 6) I avg DCS1800 : Average 2TX/3RX @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V I avg in Fast Idle mode Page 9 (2*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V I avg in Slow Idle mode Page 9 (3*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V I avg in Fast Standby mode (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V TBC TBC TBC TBC TBC TBC 33 TBC TBC 17 TBC TBC 23 TBC TBC 5 TBC TBC 52 TBC TBC 35 TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 63 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 419 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 I avg in Slow Standby mode (with FLASH LED activated) (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V 24 TBC TBC 8 TBC TBC I avg in Slow Standby mode (with FLASH LED deactivated) (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V TBC TBC TBC 4 TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC (1*):The power consumption might vary by 5 % over the whole operating temperature range (-20 °C to +55 °C). (2*): In this Mode, the RF function is active and the FASTRACK Supreme synchronized with the network, but there is no communication. (3*): In this Mode, the RF function is disabled, but regularly activated to keep the synchronization with the network. This Mode works only when the DTE send AT command to shut down the serial link by software approach (DTE turns DTR in inactive state). (4*): In this Mode, the RF function is disabled, and there is no synchronization with the network. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 64 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 420 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.3 Audio Interface The audio interface is available through the Sub HD 15-pin connector. Table 19: Audio parameters caracteristics Audio parameters Min Typ Max Microphone input current @2 V/2 k 0.5 Absolute microphone input voltage 100 Speaker output current 150 //1 nF 16 Absolute speaker impedance 32 50 Impedance of the speaker amplifier output in 1 differential mode Unit Comments mA mVpp AC voltage mA +/-10 % Table 20: Microphone inputs internal audio filter characteristics Frequency 0-150 Hz 150-180 Hz 180-200 Hz 200-3700 Hz >4000 Hz < -22 dB < -11 dB < -3 dB 0 dB < -60 dB Gain Table 21: Recommended characteristics for the microphone: Feature Value Type Electret 2 V / 0.5 mA Impedance Z = 2 k Sensitivity -40 dB to 50 dB SNR > 50 dB Frequency response compatible with the GSM specifications confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 65 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 421 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Table 22: Recommended characteristics for the speaker: Feature Value Type 10 mW, electro-magnetic Impedance Z = 32 to 50 Sensitivity 110 dB SPL min. (0 dB = 20 µPa) Frequency response compatible with the GSM specifications 8.2.4 General Purpose Input/Output Both GPIO21 and GPIO25 may be interfaced with a component that comply with 3 Volts CMOS levels. Table 23: Operating conditions Parameter I/O type Min Typ Max VIL CMOS VIH CMOS VOL CMOS VOH CMOS IOH IOL Clamping diodes are present on I/O pads. 1.96 V 2.4 V 0.84 V 0.4 V 4mA -4mA Condition IOL = -4 mA IOH = 4 mA 8.2.5 SIM Interface SIM card Table 24: SIM card characteristics 1.8V / 3 V 8.2.6 RESET Signal Table 25: Electrical characteristics Parameter Input Impedance ( R )* Input Impedance ( C ) *Internal pull-up Min Typ Max Unit 330K k 10n nF confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 66 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 422 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Table 26: Operating conditions Parameter Minimum Typ Maximum Unit ~RESET time (Rt) 1 200 µs ~RESET time (Rt) 2 at power up only 20 40 100 ms Cancellation time (Ct) 34 ms VH VIL VIH * VH: Hysterisis Voltage 0.57 0 1.33 V 0.57 V V 1 This reset time is the minimum to be carried out on the ~RESET signal when the power supply is already stabilized. 2 This reset time is internally carried out by the Wireless CPU power supply supervisor only when the Wireless CPU power supplies are powered ON. 8.2.7 RF Characteristics 8.2.7.1 Frequency Ranges Table 27: Frequency ranges Characteristic Frequency TX Frequency RX GSM 850 824 to 849 MHz 869 to 894 MHz E-GSM 900 880 to 915 MHz 925 to 960 MHz DCS 1800 1710 to 1785 MHz 1805 to 1880 MHz PCS 1900 1850 to 1910 MHz 1930 to 1990 MHz confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 67 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 423 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.7.2 RF Performances RF performances are compliant with the ETSI recommendation GSM 05.05. The RF performances for receiver and transmitter are given in the table below. Table 28: Receiver and transmitter RF performances Receiver E-GSM900/GSM850 Reference Sensitivity -104 dBm Static & TUHigh DCS1800/PCS1900 Reference Sensitivity -102 dBm Static & TUHigh Selectivity @ 200 kHz > +9 dBc Selectivity @ 400 kHz > +41 dBc Linear dynamic range 63 dB Co-channel rejection >= 9 dBc Transmitter Maximum output power (E-GSM 900/GSM850) at ambient temperature 33 dBm +/- 2 dB Maximum output power (DCS1800/PCS1900) at ambient temperature 30 dBm +/- 2 dB Minimum output power (E-GSM 900/GSM850) at ambient temperature 5 dBm +/- 5 dB Minimum output power (DCS1800/PCS1900) at ambient temperature 0 dBm +/- 5 dB confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 68 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 424 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.7.3 External Antenna The external antenna is connected to the FASTRACK Supreme via the SMA connector. The external antenna must fulfill the characteristics listed in the table below. Table 29: External antenna characteristics Antenna frequency range Quad-band GSM 850/GSM900/DCS1800/PCS1900 MHz Impedance 50 Ohms nominal DC impedance 0 Ohm Gain (antenna + cable) 0 dBi VSWR (antenna + cable) 2 Note: Refer to Section 10 for recommended antenna. 8.3 Environmental Characteristics The FASTRACK Supreme Plug & Play is compliant with the following operating class. To ensure the proper operation of the FASTRACK Supreme, the temperature of the environment must be within a specific range as described in the table below. Table 30: Ranges of temperature Conditions Operating / Class A Operating / Class B Storage Temperature range -20 °C to +55°C -30 °C to +85°C -40 °C to +85°C Function Status Classification: Class A: The FASTRACK Supreme remains fully functional, meeting GSM performance criteria in accordance with ETSI requirements, across the specified temperature range. Class B: The FASTRACK Supreme remains fully functional, across the specified temperature range. Some GSM parameters may occasionally deviate from the ETSI/PTCRB specified requirements and this deviation does not affect the ability of the FASTRACK Supreme to connect to the cellular network and function fully, as it does within the Class A range. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 69 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 425 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics The detailed climatic and mechanics standard environmental constraints applicable to the FASTRACK Supreme are listed in the table below: Environmental Tests Table 31: Environmental standard constraints Environmental Classes (IEC TR 60721-4) (IEC 60721-3) Tests Standards Storage (IEC 60721-3-1) Class IE13 Transportation (IEC 60721-3-2) Class IE23 Operation Stationary (IEC 60721-3-3) Class IE35 Non-Stationary (IEC 60721-3-7) Class IE73 Cold Dry heat Change of temperature IEC 60068-2-1 : Ab/Ad IEC 60068-2-2 : Bb/Bd IEC 60068-2-14 : Na/Nb Damp heat IEC 60068-2-56 : Cb Damp heat, cyclic 60068-2-30 : Db Variant 1 or 2 Vibration (sinusoidal) IEC 60068-2-6 : Fc Vibration (random) IEC 60068-2-64 : Fh Shock (half-sine) IEC 60068-2-27 : Ea Bump Free fall IEC 60068-2-29 : Eb ISO 4180-2 Drop and topple IEC 60068-2-31 : Ec -25°C, 16 h +70°C, 16 h -33°C to ambient 2 cycles, t1=3 h 1 °C.min-1 +30°C, 93% RH 96 h +40°C, 90% to 100% RH One cycle Variant 2 1-200 Hz 2 m.s-2 0,75 mm 3 axes 10 sweep cycles - - - - - -40°C, 16 h -5°C, 16 h +70°C, 16 h +55°C, 16 h -40°C to ambient 5 cycles, t1=3 h t2<3 min +40°C, 93% RH 96 h minimum +55°C, 90% to 100% RH Two cycles Variant 2 1-500 Hz 10 m.s-2 3,5 mm 3 axes 10 sweep cycles 10-100 Hz / 1,0 m2.s-3 100-200 Hz / -3 dB.octave-1 200-2000 Hz / 0,5 m2.s-3 3 axes 30 min - 250 m.s-2 6 ms 50 bumps vertical direction Two falls in each specified attitude -5°C to ambient 2 cycles, t1=3 h 0,5 °C.min-1 +30°C, 93% RH, 96 h +30°C, 90% to 100% RH Two cycles Variant 2 1-150 Hz 2 m.s-2 0,75 mm 3 axes 5 sweep cycles 50 m.s-2 6 ms 3 shocks 6 directions - - One drop on relevant corner One topple about each bottom edge - -5°C, 16 h +55°C, 16 h -5°C to ambient 5 cycles, t1=3 h t2<3 min +30°C, 93% RH, 96 h +40°C, 90% to 100% RH Two cycles Variant 1 1-500 Hz 10 m.s-2 3,5 mm 3 axes 10 sweep cycles 150 m.s-2 11 ms 3 shocks 6 directions - 2 falls in each specified attitude 0,025 m (<1kg) One drop on each relevant corner One topple on each of 4 bottom edges confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 70 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 426 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Notes: Short description of Class IE13 (For more information see standard IEC 60721-3-1) "Locations without controlled temperature and humidity, where heating may be used to raise low temperatures, locations in buildings providing minimal protection against daily variations of external climate, prone to receiving rainfall from carrying wind". Short description of Class IE23 (For more information, see standard IEC 60721-3-2) "Transportation in unventilated compartments and in conditions without protection against bad weather, in all sorts of trucks and trailers in areas of well developed road network, in trains equipped with buffers specially designed to reduce shocks and by boat". Short description of Class IE35 (For more information see standard IEC 60721-3-3) "Locations with no control on heat or humidity where heating may be used to raise low temperatures, to places inside a building to avoid extremely high temperatures, to places such as hallways, building staircases, cellars, certain workshops, equipment stations without surveillance". Short description of Class IE73 (For more information see standard IEC 60721-3-7) "Transfer to places where neither temperature nor humidity are controlled but where heating may be used to raise low temperatures, to places exposed to water droplets, products can be subjected to ice formation, these conditions are found in hallways and building staircases, garages, certain workshops, factory building and places for industrial processes and hardware stations without surveillance". Warning: The specification in the above table applies to the FASTRACK Supreme product only. Customers are advised to verify that the environmental specification of the SIM Card used is compliant with the FASTRACK Supreme environmental specifications. Any application must be qualified by the customer with the SIM Card in storage, transportation and operation. The use of standard SIM cards may drastically reduce the environmental conditions in which the Product can be used. These cards are particularly sensible to humidity and temperature changes. These conditions may produce oxidation of the SIM card metallic layers and cause, in the long term, electrical discontinuities. This is particularly true in left alone applications, where no frequent extraction/insertion of the SIM card is performed. In case of mobility when the application is moved through different environments with temperature variations, some condensation may appear. These events have a negative impact on the SIM and may favor oxidation. If the use of standard SIM card, with exposition to the environmental conditions described above, can not be avoided, special care must be taken in the integration of the final application in order to minimize the impact of these conditions. The solutions that may be proposed are: · Lubrication of the SIM card to protect the SIM Contact from oxidation. · Putting the FASTRACK Supreme Plug & Play in a waterproof enclosure with desiccant bags. Lubrication of the SIM card had been tested by Wavecom (using Tutela Fluid 43EM from MOLYDUVAL) and gives very good results. If waterproof enclosure with a desiccant solution is used, check with your desiccant retailer the quantity that must be used according to the enclosure dimensions. Ensure humidity has been removed before sealing the enclosure. Any solution selected must be qualified by the customer on the final application. To minimize oxidation problem on the SIM card, its manipulation must be done with the greatest precautions. In particular, the metallic contacts of the card must never be touched with bare fingers or any matter which confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 71 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 427 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics may contain polluted materials liable to produce oxidation (such as, e.g. substances including chlorine). In case a cleaning of the Card is necessary, a dry cloth must be used (never use any chemical substance). 8.4 Conformity The complete product complies with the essential requirements of article 3 of R&TTE 1999/5/EC Directive and satisfied the following standards: Domain Safety standard Efficient use of the radio frequency spectrum EMC Global Certification Forum Certification Criteria PTCRB FCC IC Applicable standard EN 60950 (ed.1999) EN 301 419-(v 4.1.1) EN 301 511 (V 7.0.1) EN 301 4891 (edition 2002) EN 301 489-7 (edition 2002) GCF-CC V3.13.0 8.5 Protections 8.5.1 Power Supply The FASTRACK Supreme is protected by a 800 mA / 250 V fuse directly bonded on the power supply cable. The model of fuse used is: FSD 800 mA / 250 V FAST-ACTING. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 72 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 428 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.5.2 Overvoltage The FASTRACK Supreme is protected against voltage over +32 V. When input voltages exceed +32 V, the supply voltage is disconnected in order to protect the internal electronic components from an overvoltage. 8.5.3 Electrostatic Discharge The FASTRACK Supreme withstands ESD according to IEC 1000-4-2 requirements for all accessible parts of the FASTRACK Supreme except the RF part: · 8 kV of air discharge, · 4 kV of contact discharge. 8.5.4 Miscellaneous Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 73 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 429 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9 Safety recommendations Fastrack Supreme User Guide Safety recommendations 9.1 General Safety It is important to follow any special regulations regarding the use of radio equipment due in particular to the possibility of radio frequency (RF) interference. Please follow the safety advice given below carefully. Switch OFF your Wireless CPU®: · When in an aircraft. The use of cellular telephones in an aircraft may endanger the operation of the aircraft, disrupt the cellular network and is illegal. Failure to observe this instruction may lead to suspension or denial of cellular telephone services to the offender, or legal action or both, · When at a refueling point, · When in any area with a potentially explosive atmosphere which could cause an explosion or fire, · In hospitals and any other place where medical equipment may be in use. Respect restrictions on the use of radio equipment in: · Fuel depots, · Chemical plants, · Places where blasting operations are in progress, · Any other area where signalization reminds that the use of cellular telephone is forbidden or dangerous. · Any other area where you would normally be advised to turn off your vehicle engine. There may be a hazard associated with the operation of your FASTRACK Supreme Plug & Play close to inadequately protected personal medical devices such as hearing aids and pacemakers. Consult the manufacturers of the medical device to determine if it is adequately protected. Operation of your FASTRACK Supreme Plug & Play close to other electronic equipment may also cause interference if the equipment is inadequately protected. Observe any warning signs and manufacturers' recommendations. The FASTRACK Supreme Plug & Play is designed for and intended to be used in "fixed" and "mobile" applications: "Fixed" means that the device is physically secured at one location and is not able to be easily moved to another location. "Mobile" means that the device is designed to be used in other than fixed locations and generally in such a way that a separation distance of at least 20 cm (8 inches) is normally maintained between the transmitter's antenna and the body of the user or nearby persons. The FASTRACK Supreme Plug & Play is not designed for and intended to be used in portable applications (within 20 cm or 8 inches of the body of the user) and such uses are strictly prohibited. 9.2 Vehicle Safety Do not use your FASTRACK Supreme Plug & Play while driving, unless equipped with a correctly installed vehicle kit allowing 'Hands-Free' Operation. Respect national regulations on the use of cellular telephones in vehicles. Road safety always comes first. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 74 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 430 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fastrack Supreme User Guide Safety recommendations If incorrectly installed in a vehicle, the operation of FASTRACK Supreme Plug & Play telephone could interfere with the correct functioning of vehicle electronics. To avoid such problems, make sure that the installation has been performed by a qualified personnel. Verification of the protection of vehicle electronics should form part of the installation. The use of an alert device to operate a vehicle's lights or horn on public roads is not permitted. 9.3 Care and Maintenance Your FASTRACK Supreme Plug & Play is the product of advanced engineering, design and craftsmanship and should be treated with care. The suggestion below will help you to enjoy this product for many years. Do not expose the FASTRACK Supreme Plug & Play to any extreme environment where the temperature or humidity is high. Do not use or store the FASTRACK Supreme Plug & Play in dusty or dirty areas. Its moving parts (SIM holder for example) can be damaged. Do not attempt to disassemble the Wireless CPU®. There are no user serviceable parts inside. Do not expose the FASTRACK Supreme Plug & Play to water, rain or spilt beverages. It is not waterproof. Do not abuse your FASTRACK Supreme Plug & Play by dropping, knocking, or violently shaking it. Rough handling can damage it. Do not place the FASTRACK Supreme Plug & Play alongside computer discs, credit or travel cards or other magnetic media. The information contained on discs or cards may be affected by the Wireless CPU®. The use of third party equipment or accessories, not made or authorized by Wavecom may invalidate the warranty of the Wireless CPU®. Do contact an authorized Service Center in the unlikely event of a fault in the Wireless CPU®. 9.4 Your Responsibility This FASTRACK Supreme Plug & Play is under your responsibility. Please treat it with care respecting all local regulations. It is not a toy. Therefore, keep it in a safe place at all times and out of the reach of children. Try to remember your Unlock and PIN codes. Become familiar with and use the security features to block unauthorized use and theft. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 75 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 431 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10 Recommended Accessories Fastrack Supreme User Guide Recommended Accessories Accessories recommended by Wavecom for the FASTRACK Supreme are given in the table below. Table 32: List of recommended accessories Designation Part number 1140.26 Quad-band antenna MA112VX00 MCA1890 MH/PB/SMA m SMA/FME adaptor Antenna Power adaptor (Europe) EGSTDW P2 EF9W3 24W Out:12 V - 2A In: 100 to 240 V 50/60 Hz 550 mA Mounted with micro-fit connector Fuse F800L250V Supplier ALLGON MAT Equipement HIRSCHMANN PROCOM EGSTDW (for power adaptor) MOLEX (for micro-fit connector)* Shanghai Fullness IESM GPS + USB M13SUE01 WAVECOM IESM IO + USB M13SUE02 WAVECOM IESM IO + USB + GPS M13SUE03 * Information not available for this preliminary version. WAVECOM confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 76 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 432 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11 Online Support Fastrack Supreme User Guide Online Support Wavecom provides an extensive range on online support which includes the following areas of Wavecom's wireless expertise: · the latest version of this document · new versions of our Operating System user guides · comprehensive support for Open AT® · regulatory certifications · carrier certifications · application notes To gain access to this support, simply visit our web site at www.wavecom.com or click on the desire link in Page. Privileged access via user login is provided to Wavecom authorized distributors. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 77 / 77 5 june, 2007 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 433 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual VpCI®-110 Emitter, Patented · Switching equipment · Fuse boxes and power boxes · Medical equipment · Electrical wireways and terminal boxes · Scientific and measuring instruments · Telecommunications equipment · Remote electronics devices · Tool-boxes, parts-storage, and other containers holding metals PRODUCT DESCRIPTION Cortec® VpCI-110 emitters are designed to provide corrosion protection for metal components and parts enclosed in non-ventilated control boxes, cabinets, or tool boxes up to 10 cubic feet (283 liters) in volume. The Vapor phase Corrosion Inhibitor (VpCI) emits vapors which form a molecular layer on internal metal surfaces to protect critical, complex, and expensive electronic equipment and other metal components during operation, shipping, or storage. VpCI-110 is a small foam emitter through which corrosion inhibitors are slowly released, and moisture and air pollutants can enter to be absorbed. It provides long-term protection against corrosion even in the presence of adverse conditions including salt, moisture, airborne contaminants, H2S, SO2, NH3, and others. TYPICAL APPLICATIONS VpCI-110 can be effectively used for: · Operations, packaging, and storage electrical equipment · Marine navigation and communication electronic equipment · Aerospace electrical controls · Electric motors FEATURES · Economical to use · Provides continuous protection for up to 24 months during operation and/or shutdown · Effective in polluted and humid environments · Does not interfere with electrical, optical, or mechanical performance · Multimetal protection · Quick and easy installation · Non-toxic and safe to handle · Compact and space-saving · Free of nitrites, halogens, and phosphates · No spraying, wiping, or dipping required · Low VOC values · Meets Southern California Clean Air Act and other National and local regulations · Self-stick back · Self-stick date label · Accepted by FDA for corrosion protection of electrical and electronic equipment within food processing plants · Canadian Food Inspection Agency acceptance for indirect food contact · NSN 6850-01-456-2971 · Conforms to MIL I-22110C · Federal Standard 101, Ardec Technical Report 9905, Picatinny Arsenal, New Jersey, USA Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 434 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual METHOD OF APPLICATION VpCI-110 is extremely simple and convenient to install. The device should be installed at the earliest possible time. Simply select a space within enclosure where corrosion protection would be useful. Verify the surface is clean and free of debris. Peel off the protective peel strip from the bottom of the device and attach it to the clean surface. VpCI-110 emitters can be installed in any position. For volumes greater than 10 cubic feet (283 liters), use more than one device. If the enclosure is not totally airtight, or if the access doors are opened frequently, replace the VpCI-110 device more often than every 2 years. After periods of heavy maintenance replace the device. For additional protection spray the enclosure very lightly with ElectriCorr® VpCI-238 or VpCI -239. SPECIFICATIONS Packaging Protection Standard Size 12 individually wrapped emitters per carton up to 10 ft3 (283 liters) per device Foam device with adhesive backing 2.5" D x 2" H (6.4 cm D x 5 cm H) FOR INDUSTRIAL USE ONLY KEEP OUT OF REACH OF CHILDREN KEEP CONTAINER TIGHTLY SEALED NOT FOR INTERNAL CONSUMPTION CONSULT MATERIAL SAFETY DATA SHEET FOR MORE INFORMATION LIMITED WARRANTY All statements, technical information and recommendations contained herein are based on tests Cortec Corporation believes to be reliable, but the accuracy or completeness thereof is not guaranteed. Cortec Corporation warrants Cortec® products will be free from defects when shipped to customer. Cortec Corporation's obligation under this warranty shall be limited to replacement of product that proves to be defective. To obtain replacement product under this warranty, the customer must notify Cortec Corporation of the claimed defect within six months after shipment of product to customer. All freight charges for replacement products shall be paid by customer. Cortec Corporation shall have no liability for any injury, loss or damage arising out of the use of or the inability to use the products. BEFORE USING, USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND USER ASSUMES ALL RISK AND LIABILITY WHATSOEVER IN CONNECTION THEREWITH. No representation or recommendation not contained herein shall have any force or effect unless in a written document signed by an officer of Cortec Corporation. THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, EXPRESS, IMPLIED OR STATUTORY, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. IN NO CASE SHALL CORTEC CORPORATION BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. Distributed by: 4119 White Bear Parkway, St. Paul, MN 55110 USA Phone (651) 429-1100, Fax (651) 429-1122 Toll Free (800) 4-CORTEC, E-mail info@cortecvci.com Internet http://www.CortecVCI.com printed on recycled paper 100% post consumer Revised 3/3/09. Cortec Corporation 2001-2009. All rights reserved. Supersedes: 5/31/06 ElectriCorr® and Cortec® are trademarks of Cortec Corporation © 2009, Cortec Corporation. All Rights Reserved. Copying of these materials in any form without the written authorization of Cortec Corporation is strictly prohibited. Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 435 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1.7. TERMINALS, LINKS & OTHER ACCESSORIES PHOENIX CONTACT TCP 10A (0712314) + UK 6-FSI/C (3118203) 10A Miniature Thermal Circuit Breakers PHOENIX CONTACT TCP 4A (0712259) + UK 6-FSI/C (3118203) 4A Miniature Thermal Circuit Breakers PHOENIX CONTACT TCP 2A (0712217) + UK 6-FSI/C (3118203) 2A Miniature Thermal Circuit Breakers PHOENIX CONTACT PIT 2,5 (3209510) Through Terminals (Grey) PHOENIX CONTACT D-ST 2,5 (3030417) Through Terminal Endplate PHOENIX CONTACT PIT 2,5-MT (3210156) Disconnect Terminals (Grey) PHOENIX CONTACT D-PIT 2,5-MT (3211003) Disconnect Terminals Endplate PHOENIX CONTACT UBE (0800310) Group Marker Carrier PHOENIX CONTACT PS-5 (3030983) Test Plug Adapter PHOENIX CONTACT SZS 0.6x3.5 (1205053) Screw Driver PHOENIX CONTACT FBS 20-5 (3030226) Plug-In Bridge PHOENIX CONTACT ZB 5 CUS (0824962) Terminal Numbers WEIDMULLER (8611320000) Adapter MAXON MA.2025 Ethernet Router MAXON C3LA30-BD170F Antenna LUMIFA LF1B-C35-2THWW4 Switchboard LED C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 436 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CLIPSAL NEUTRAL-ACTIVE-METER LINKS CLIPSAL NEUTRAL / ACTIVE / METER LINKS Clipsal Links are produced from Impact Resistant materials to prevent cracking in transit or during installation. The transparent covers enable you to check wiring and locate the sealing screw at a glance. The sealing screw (nylon with brass insert) resists stripping. Voltage and amperage ratings are clearly marked on both the cover and brass bar. All links are available with black or red covers and bases for neutral, active or meter applications as required by local authorities. T-Type - 500 Volt 140 Ampere L4T35 500V 140A 4 Hole Neutral Link with two screws per tunnel. Black base and cover. L4T35R 500V 140A 4 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 28mm. 1 tunnel 8.7mm diameter accommodate 1 x 25mm2 cable. 3 tunnels 7.7mm diameter accommodate 1 x 25mm2 cable. Certificate of Suitability No. CS2252N. L4T35R Mini Links with Cover 500V 100A 2 screws per tunnel. L5 500V 100A 5 Hole Neutral Link with two screws per tunnel. Black base and cover. L5R 500V 100A 5 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 3 tunnels, 6.3mm diameter accommodate 1 x 16mm2. 2 tunnels, 5.8mm diameter accommodate 1 x 16mm2. L5BW 500V 110A 5 Hole Back Wiring Neutral Link with two screws per tunnel. Black base and cover. L5BWR 500V 110A 5 Hole Back Wiring Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 5 tunnels, 7mm diameter accommodate 1 x 25mm2. Transparent black cover, with cut outs. L6R 500V 100A 6 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 3 tunnels, 6.3mm diameter accommodate 1 x 16mm2 cable. 3 tunnels, 5.8mm diameter accommodate 1 x 16mm2 cable. L6/25 500V 110A 6 Hole Neutral Link with 2 screws per tunnel. Black base and cover. L6/25R 500V 110A 6 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 2 tunnels, 7.5mm diameter accommodate 2 x 25mm2 cable. 1 tunnel, 5.5mm diameter accommodates 1 x 16mm2 cable. 3 tunnels, 4.7mm diameter accommodate 3 x 10mm2 cable. Transparent black cover with cut-outs. L7 500V 100A 7 Hole Neutral Link with two screws per tunnel. Black base and cover. L6 500V 100A 6 Hole Neutral Link with 21 two screws per tunnel. Black base and cover. L7 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 437 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 2 Pumps SUPPLIER: MODEL: kW RATING: VOLTAGE: Grundfos 30 Blanck Street Ormeau QLD 4208 Ph: (07) 5540 6700 Fax: (07) 5540 6710 MOB-QUU-3xCRNE 45-2 BOOSTER 7.5kW 415V C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 438 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual GRUNDFOS INSTRUCTIONS BoosterpaQ Hydro MPC Installation and operating instructions Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 439 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions. To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed. GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE. Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction. 2 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 440 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CONTENTS 1. Symbols used in this document 2. Scope of these instructions 3. Product description 4. Nameplate 5. Software label 6. Type key 6.1 Examples of control variants 7. 7.1 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.2 7.3 Installation Mechanical installation Location Pipework Foundation Vibration dampers Expansion joints Electrical installation Start-up 8. Control panel 8.1 Display (pos. 1) 8.1.1 Menu line 8.1.2 Top line 8.1.3 Graphical illustration 8.1.4 Scroll bar 8.1.5 Bottom line 8.2 Buttons and indicator lights 8.2.1 Arrow to the right (pos. 2) 8.2.2 Help (pos. 3) 8.2.3 Up and down (pos. 4 and 5) 8.2.4 Plus and minus (pos. 6 and 7) 8.2.5 Esc (pos. 8) 8.2.6 Home (pos. 9) 8.2.7 Ok (pos. 10) 8.2.8 Indicator lights (pos. 11 and 12) 8.2.9 Contrast (pos. 13) 8.2.10 Back light 9. 9.1 9.2 9.3 9.4 9.4.1 9.4.2 9.4.3 9.4.4 9.4.5 9.4.6 9.4.7 9.4.8 9.5 9.5.1 9.5.2 9.5.3 9.5.4 9.5.5 9.5.6 9.6 9.6.1 9.6.2 9.6.3 9.7 9.7.1 9.7.2 9.7.3 9.7.4 9.7.5 Functions Tree of functions Overview Description of functions Status (1) Current alarms (3.1) System (1.2) Operating mode (1.2.1) Setpoint (1.2.2) Setpoint influence (1.2.3) Measured values (1.2.4) Analog inputs (1.2.5) Pump 1...6 (1.3 to 1.8) Operation (2) Operation (2) System operating mode (2.1.1) Control mode (2.1.2) Setpoints (2.1.3) Individual pump control (2.1.4) Setting of individual operating mode (2.1.4.1 to 2.1.4.6) Alarm (3) Alarm status (3) Current alarms (3.1) Alarm log (3.2) Settings (4) Primary controller (4.1) PI controller (4.1.1) Alternative setpoints (4.1.2) Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) External setpoint influence (4.1.3) Page 4 4 4 5 5 6 6 9 9 9 9 9 9 9 10 10 12 12 12 12 12 12 12 13 13 13 13 13 13 13 13 13 13 13 14 14 17 19 19 19 19 20 20 20 21 21 21 21 22 22 23 25 25 26 27 27 32 32 32 33 33 33 34 34 9.7.6 Setting of influence function (4.1.3.2) 35 9.7.7 Primary sensor (4.1.4) 35 9.7.8 Clock program (4.1.6) 36 9.7.9 Proportional pressure (4.1.7) 36 9.7.10 S-system configuration (4.1.8) 37 9.7.11 Pump cascade control (4.2) 37 9.7.12 Min. time between start/stop (4.2.1) 38 9.7.13 Max. number of starts/hour (4.2.1) 38 9.7.14 Standby pumps (4.2.3) 38 9.7.15 Forced pump changeover (4.2.4) 39 9.7.16 Pump test run (4.2.5) 39 9.7.17 Pilot pump (4.2.6) 40 9.7.18 Pump stop attempt (4.2.7) 40 9.7.19 Pump start and stop speed (4.2.8) 41 9.7.20 Min. performance (4.2.9) 41 9.7.21 Compensation for pump start-up time (4.2.10) 42 9.7.22 Secondary functions (4.3) 42 9.7.23 Stop function (4.3.1) 42 9.7.24 Soft pressure build-up (4.3.3) 44 9.7.25 Emergency run (4.3.5) 45 9.7.26 Digital inputs (4.3.7) 45 9.7.27 Functions of digital inputs (4.3.7.1) 46 9.7.28 Analog inputs (4.3.8) 46 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 47 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) 47 9.7.31 Digital outputs (4.3.9) 48 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) 48 9.7.33 Min., max. and user-defined duty (4.3.14) 49 9.7.34 Min. duty (4.3.14.1) 49 9.7.35 Max. duty (4.3.14.2) 49 9.7.36 User-defined duty (4.3.14.3) 50 9.7.37 Pump curve data (4.3.19) 50 9.7.38 Control source (4.3.20) 51 9.7.39 Fixed inlet pressure (4.3.22) 52 9.7.40 Flow estimation (4.3.23) 52 9.7.41 Monitoring functions (4.4) 52 9.7.42 Dry-running protection (4.4.1) 53 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1) 53 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2) 54 9.7.45 Dry-running protection with level transmitter (4.4.1.3) 54 9.7.46 Min. pressure (4.4.2) 55 9.7.47 Max. pressure (4.4.3) 55 9.7.48 External fault (4.4.4) 56 9.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) 56 9.7.50 Pumps outside duty range (4.4.7) 57 9.7.51 Pressure relief (4.4.8) 57 9.7.52 Functions, CU 351 (4.5) 58 9.7.53 Display language (4.5.1) 58 9.7.54 Display units (4.5.2) 59 9.7.55 Date and time (4.5.3) 60 9.7.56 Passwords (4.5.4) 60 9.7.57 Ethernet (4.5.5) 60 9.7.58 GENIbus number (4.5.6) 61 9.7.59 Software status (4.5.9) 61 9.8 Data communication 62 9.8.1 Ethernet 62 9.8.2 GENIbus 64 10. External variable frequency drive 65 10.1 VLT 2800 65 10.2 Danfoss VLT 8000 factory settings 66 10.3 Danfoss VLT 8000 extended menu programming 66 10.4 Danfoss VLT 8000 factory settings 67 10.5 Danfoss VLT 8000 extended menu programming 67 10.6 Baldor Smart motor settings 68 10.7 VLT FC 202 69 Q-Pulse Id: TMS1594 Active: 18/04/2016 3 Page 441 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11. Fault finding chart 70 12. Maintenance 71 12.1 Pumps 71 12.2 Motor bearings 71 12.3 CU 351 71 13. Frost protection 71 14. Taking out of operation 71 15. Technical data 71 15.1 Pressure 71 15.2 Temperature 72 15.3 Relative humidity 72 15.4 Sound pressure 72 16. Electrical data 72 17. Related documents 72 18. Disposal 72 Warning Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice. 1. Symbols used in this document Warning If these safety instructions are not observed, it may result in personal injury! If these safety instructions are not observed, it Caution may result in malfunction or damage to the equipment! Note Notes or instructions that make the job easier and ensure safe operation. 2. Scope of these instructions These installation and operating instructions apply to Grundfos Hydro MPC booster systems. Hydro MPC is a range of factory-assembled booster systems, ready for installation and operation. 3. Product description As standard, Hydro MPC booster systems consist of two to six CR(E) pumps coupled in parallel and mounted on a common base frame with all the necessary fittings and a control panel. Note A diaphragm tank is required in most installations. 1 9 8 2 7 3 6 5 4 Fig. 1 Hydro MPC booster system Pos. 1 2 3 4 5 6 7 8 9 Description Control panel Nameplate Suction manifold (stainless steel) Isolating valve Base frame (stainless steel) Non-return valve Discharge manifold (stainless steel) Pressure transmitter/pressure gauge Pump Quantity 1 1 1 2 per pump 1 1 per pump 1 12 2 - 6 TM03 1171 1205 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 442 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Hydro MPC booster systems are divided into seven groups based on control variant: Control variant Description -E -ED -ES -EF -EDF -F -S Two to six CRE pumps Two CRE pumps and up to four constant speed CR pumps One CRE pump and up to five constant speed CR pumps Two to six CR pumps connected to external variable frequency drives (VFD) Two CR pumps connected to external variable frequency drives and up to four constant speed CR pumps Up to six CR pumps connected to an external variable frequency drive. The speed-controlled operation alternates between the pumps. Two to six constant speed CR pumps See also section 6.1 Examples of control variants. Hydro MPC booster systems always includes applicationoptimised software for setting the booster system to the application in question. 4. Nameplate The nameplate of the booster system is fitted on the base frame. See position 2 in fig. 1. Pos. Description 1 Type designation 2 Model 3 Serial number 4 Supply voltage 5 Maximum operating pressure in PSI 6 Liquid temperature in °F 7 Maximum flow rate in GPM 8 Minimum head in feet 9 Number of fixed speed and/or auxiliary pumps 10 Motor power in HP for fixed speed pumps 11 Nominal voltage in volts for fixed speed pumps 12 Number of E-pumps 13 Motor power in HP for E-pumps 14 Nominal voltage in volts for E-pumps 15 Number of pilot pumps 16 Motor power in HP for pilot pump 17 Nominal voltage in volts for pilot pump 18 Order number 1924 Options 25 Enclosure type 26 Weight in lbs 27 Approval marks 28 Production location & date code 5. Software label The software label is placed on the back of the CU 351 controller. 1. Control MPC 1 2. C-MPC options 2 3. Hydro MPC 3 4. H-MPC options 4 5. Pump data 5 TM03 1741 3105 TM03 1742 3105 Fig. 2 Nameplate CONFIGURATION STEPS - PLEASE FOLLOW THE NUMBERS Fig. 3 Software label 96586126 Pos. 1 2 3 4 5 Description Control MPC - GSC file number Control MPC options - GSC file numbers Hydro MPC - GSC file number Hydro MPC options - GSC file numbers Pump data - GSC file numbers Note A GSC (Grundfos Standard Configuration) file is a configuration data file. Q-Pulse Id: TMS1594 Active: 18/04/2016 5 Page 443 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6. Type key Example Hydro MPC -ED 2 CRE 5-10 1 CR 5-10 3x460 V, 60Hz Type range Subgroups: Pumps with integrated variable frequency drive: -E, -ED, -ES Pumps with external VFD: -EF, -EDF, -F Constant speed pumps (start/stop): -S Number of pumps with integrated variable frequency drive and pump type Number of constant speed pumps and pump type Supply voltage, frequency 6.1 Examples of control variants Booster systems with motors that include an integrated variable frequency drive (CRE) Hydro MPC-E Hydro MPC booster system with three CRE pumps. Hydro MPC-ED Hydro MPC booster system with two CRE pumps and one constant speed CR pump. Hydro MPC-ES Hydro MPC booster system with one CRE pump and two constant speed CR pumps. TM03 0996 0905 TM03 0994 0905 TM03 0993 0905 PT PT PT One CRE pump in operation. H One CRE pump in operation. H One CRE pump in operation. H TM00 7995 2296 TM00 7995 2296 TM00 7995 2296 Hset Hset Hset Three CRE pumps in operation. H Q Q Q Two CRE pumps and one constant speed One CRE pump and two constant speed CR CR pump in operation. pumps in operation. H H TM00 7998 2296 TM03 0814 0505 TM00 7996 2296 Hset Hset Hset Q Q Q · The MPC-E system maintains a constant · The MPC-ED system maintains a constant · The MPC-ES system maintains a constant pressure through continuous adjustment pressure through continuous adjustment pressure through continuous adjustment of the speed of the pumps. of the speed of two CRE pumps, while the of the speed of the CRE pump. The other · The system performance is adjusted to CR pump is constant speed. pumps are cut in/out according to demand the demand through cutting in/out the · One CRE pump always starts first. If the to achieve a performance corresponding required number of pumps and through pressure cannot be maintained by the to the consumption. parallel control of the pumps in operation. pump, the second CRE pump will be cut · The CRE pump always starts first. If the · Pump changeover is automatic and in. If the two CRE pumps cannot maintain pressure cannot be maintained by the depends on load, operating hours and the pressure, the CR pump will be cut in. pump, one or both CR pumps will be cut fault. · Pump changeover is automatic and in. · All pumps in operation will run at equal depends on load, operating hours and · Changeover among the constant speed speed. fault. pumps is automatic and depends on load, operating hours and fault. 6 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 444 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Booster systems with motors connected to external variable frequency drive (VFD) Hydro MPC-EF Hydro MPC booster system with three CR pumps connected to external variable frequency drives in the control panel. Hydro MPC-EDF Hydro MPC booster system with two CR pumps connected to external frequency converters in the control cabinet and one constant speed CR pump. Hydro MPC-F Hydro MPC booster system with three CR pumps connected to an external frequency converter in the control cabinet. The speed-controlled operation alternates between the pumps. TM03 1265 1505 TM03 0997 0905 TM03 0995 0905 PT PT PT One CR pump in operation. H One CR pump connected to an external variable frequency drive in operation. H One CR pump connected to an external variable frequency drive in operation. H TM00 7995 2296 TM00 7995 2296 TM00 7995 2296 Hset Three CR pumps in operation. H Hset Hset Q Q Q Two CR pumps connected to external One CR pump connected to an external variable frequency drives and one constant variable frequency drive and two constant speed CR pump in operation. speed CR pumps in operation. H H TM00 7998 2296 TM03 0814 0505 TM00 7996 2296 Hset Hset Hset Q Q Q · The MPC-EF system maintains a constant · The MPC-EDF system maintains a · The MPC-F system maintains a constant pressure through continuous adjustment constant pressure through continuous pressure through continuous adjustment of the speed of the pumps. adjustment of the speed of two CR pumps of the speed of the CR pump connected to · The system performance is adjusted to the demand through cutting in/out the required number of pumps and through connected to external variable frequency drives, while the third CR pump is constant speed. the external variable frequency drive. The speed-controlled operation alternates between the pumps. parallel control of the pumps in operation. · One CR pump connected to an external · One CR pump connected to the external · Pump changeover is automatic and depends on load, operating hours and fault. · All pumps in operation will run at equal speed. variable frequency drive always starts variable frequency drive always starts first. If the pressure cannot be maintained first. If the pressure cannot be maintained by the pump, the second CR pump by the pump, one or two constant speed connected to an external variable CR pumps will be cut in. frequency drive will be cut in. If the · Pump changeover is automatic and pressure cannot be maintained by the two depends on load, operating hours and pumps, the constant speed CR pump will fault. be cut in. · Pump changeover is automatic and depends on load, operating hours and fault. Q-Pulse Id: TMS1594 Active: 18/04/2016 7 Page 445 of 1068 TM03 0999 0905 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Booster system with constant speed pumps (on/off) Hydro MPC-S Hydro MPC booster system with three constant speed CR pumps. PT One constant speed CR pump in operation. H Hstop Hset Q Three constant speed CR pumps in operation. H Hstop Hset Q · Hydro MPC-S maintains a pressure differential through cutting in/out the required number of pumps. · The operating range of the pumps will lie between Hset and Hstop (cut-out pressure). · Pump changeover is automatic and depends on load, operating hours and fault. TM03 9204 3607 TM03 9203 3607 8 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 446 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7. Installation Warning Installation and operation must comply with local regulations and accepted codes of good practice. Before installation check that · the booster system corresponds to the one ordered. · no visible parts have been damaged. 7.1 Mechanical installation 7.1.1 Location The booster system must be installed in a well ventilated room to ensure sufficient cooling of the motors and control panel. Note Hydro MPC is not designed for outdoor installation unless protected and must not be exposed to direct sunlight. The booster system must have a 3 feet clearance in front and on the two sides for inspection and dismantling. 7.1.2 Pipework Arrows on the pump base show the direction of flow of water through the pump. The pipework connected to the booster system must be of adequate size. The pipes are connected to the manifolds of the booster system. Either end can be used. Apply sealing compound to the unused end of the manifold and fit the screw cap. For manifolds with flanges, fit a blanking flange with gasket. To achieve optimum operation and minimise noise and vibration, it may be necessary to consider vibration dampening of the booster system. Noise and vibration are generated by the rotations in the motor and pump and by the flow in pipework and fittings. The effect on the environment is subjective and depends on correct installation and the state of the other parts of the system. If booster system is to be installed where first customer on the line is close to the booster system, it is advisable to fit expansion joints on the suction and discharge pipes to prevent vibration being transmitted through the pipework. All nuts should be checked and re-tightened if necessary prior to start-up. The pipes must be fastened to parts of the building to ensure that they cannot move or be twisted. 7.1.3 Foundation The booster system should be positioned on an even and solid surface, for instance a concrete floor or foundation. If the booster system is not fitted with machine shoes, it must be bolted to the floor or foundation. Note As a rule the weight of a concrete foundation should be 1.5 x the weight of the booster system. 7.1.4 Vibration dampers To prevent the transmission of vibrations to buildings, it imay be necessary to isolate the booster system foundation from building parts by means of vibration dampers. The right damper varies from installation to installation, and a wrong damper may increase the vibration level. Vibration dampers should therefore be sized by the supplier of vibration dampers. If the booster system is installed on a base frame with vibration dampers, expansion joints should always be fitted on the manifolds. This is important to prevent the booster system from "hanging" in the pipework. 7.1.5 Expansion joints Expansion joints are installed to · absorb expansions/contractions in the pipework caused by changing liquid temperature · reduce mechanical strains in connection with pressure surges in the pipework · isolate mechanical structure-borne noise in the pipework (only rubber bellows expansion joints). Note Expansion joints must not be installed to compensate for inaccuracies in the pipework such as center displacement of flanges. Fit expansion joints at a distance of minimum 1 to 1 1/2 times the nominal flange diameter from the manifold on the suction as well as on the discharge side. This prevents the development of turbulence in the expansion joints, resulting in better suction conditions and a minimum pressure loss on the pressure side. At high water velocities (> 10 ft/sec) it is advisable to install larger expansion joints corresponding to the pipework. TM03 2154 3805 TM02 4981 1902 - TM02 4979 1902 1 1 2 2 Fig. 4 3 3 Sketch showing the position of expansion joints, pipe supports and machine shoes Pos. Description 1 Expansion joint 2 Pipe support and good location for system isolation valve (not shown) 3 Machine shoe Note Expansion joints, pipe supports and machine shoes shown in the figure above are not supplied with a standard booster system. Fig. 5 Examples of rubber bellows expansion joints without and with limit rods Expansion joints with limit rods can be used to minimise the forces caused by the expansion joints. Expansion joints with limit rods are always recommended for flanges larger than 6 inches. The pipework should be anchored so that it does not stress the expansion joints and the pump. Follow the supplier's instructions and pass them on to advisers or pipe installers. Q-Pulse Id: TMS1594 Active: 18/04/2016 9 Page 447 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.2 Electrical installation Warning The electrical installation should be carried out by an authorized person in accordance with local regulations and the relevant wiring diagram. · The electrical installation of the booster system must comply with enclosure class IP54. · Make sure that the booster system is suitable for the electricity supply to which it is connected. · Make sure that the wire cross-section corresponds to the specifications in the wiring diagram. The connection of the electrical supply, transmitters and external monitoring equipment must be carried out by an authorized electrician in accordance with the NEC, local regulations and the BoosterpaQ wiring diagram. Ensure that the Hydro MPC controls and the pumps are suitable for the electricity supply on which they will be used (see Technical Data). Please read the wiring diagram carefully. According to the NEC, if the motors cannot be seen from the control panel, they must be fitted with a disconnect switch. Any BoosterpaQ that utilizes a variable frequency drive (E, ED, ES, EF, EDF, F) should be connected to an electrical supply with all phase lines electrically symmetrical with respect to ground. A "four wire wye" electrical supply with line impedance between 0.5% - 3% is recommended. If a variable frequency drive is connected to a delta transformer or if line impedance is not within the recommended 0.5% - 3%, the drive may not operate correctly and may not provide optimum performance (excessive faults, erratic behavior, or complete failure). Ask your power company or electrician to determine what type of electrical supply is present. Generator supplied power must meet public utility power quality standards. 7.3 Start-up 1. Have a qualified person check for proper power supply and plumbing connections. Make sure the main power is off. 2. Check that the air pre-charge in the diaphragm tank is 0.7 times the required discharge pressure set-point (0.9 times for MPC-S systems). System pressure must not be applied to the tank connection during the tank precharge process. If water is supplied to the tank from the system, close the tank valve and bleed off the pressure in the tank before the pressurizing process. Prime the system as follows 3. Suction pressure system (pumps are flooded at least as high as the highest part of the pumps) close all discharge manifold pump isolation valves and open all inlet manifold pump isolation valves open the vent plug on top of each pump. It is a small hex head screw in a large vent plug. Air and water will escape from the pump through a small hole in the large vent plug. When the air is out and water is flowing steadily, tighten the small hex head screw on the vent plug to stop the flow. Note If you are filling an empty piping system, do not allow the pumps to run with the discharge valves wide open as cavitation may occur. 4. Suction lift system (the water source is below the pumps or does not flood the pumps to the highest point on the pumps). close all discharge manifold pump isolation valves and open all inlet manifold pump isolation valves for suction lift applications, a foot valve must be placed on the inlet piping at the water source (tank, etc). If there is a fill point above the highest point of the pumps, you may fill the system from this point. If there is no fill point above the highest point of the pumps, remove the large vent plug on each pump. Fill each pump until the water is up to the vent plug, then replace the vent plugs. 5. Ensure all circuit breakers are in the "on" position. 6. Make sure the discharge manifold pump isolation valves are closed. Switch on main power. Caution The pumps may start at this time. 7. At this time "Start-up wizard" may now be ran. Step 8 can be skipped upon completion of "Start-up wizard". If "Start-up wizard" could not be ran or already ran proceed to step 8. 8. Run the "Start-up wizard" again by performing the following: Move top line display to "Settings". If prompted for password enter "6814", next move down to "Functions, CU 351" and press the "OK" button. Now move down to "Run wizard again" and press the "OK" button. 9. Vent the system by opening the vent plug on each pump (as in Step 3, while the pump is running starting in step 18 of the "Start-up wizard".). Venting with the pumps running ensures all air is removed from the suction piping. Do not run the system with the discharge manifold pump isolation valves closed more than five minutes to prevent over-heating of the pump liquid. 10.As pumps stop, check pump rotation. Repeat as necessary. If the area is dark, a flashlight may be required, or remove a coupling guard on each pump for better visibility. Disconnect the main power when removing coupling guards. Warning Do not touch the couplings while the pumps are turning as injury may result. Replace all coupling guards after the rotation check. Disconnect main power when removing and replacing coupling guards (or open service disconnect switches if this option was supplied). If the rotation is incorrect on any 3 phase pumps, switch any 2 of the 3 power main wires supplied to the control panel (L1, L2, L3). If that doesn't correct the rotation, call your Grundfos representative. Note If you are filling an empty piping system, do not allow the pumps to run with the discharge valves wide open as cavitation may occur. 11.Upon completion of venting pumps and checking for correct rotation you are now ready to bring the BoosterpaQ into normal operation. With the discharge manifold isolation valves still closed, partially open each pump discharge isolation valve to allow water to enter into the discharge piping of the BoosterpaQ. Continue the process of filling the discharge piping until discharge piping pressure is approximately at the desired Setpoint pressure of the BoosterpaQ. 12.Open the discharge manifold isolation valves for each pump completely. System is now ready for operation. It may be necessary to clear alarms in the fault log. Follow the steps in paragraph sections 9.6 to clear alarms. 10 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 448 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual INSTALLATION AND STARTUP NOTES Q-Pulse Id: TMS1594 Active: 18/04/2016 11 Page 449 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 8. Control panel 8.1 Display (pos. 1) The control panel in the front cover of the control cabinet features a display, a number of buttons and two indicator lights. The A control panel enables manual setting and monitoring of the B performance of the Hydro MPC. 2 CU 351 3 1 5 4 6 7 8 9 10 11 Fig. 6 Control panel 13 12 Key Pos. 1 2 3 4 5 6 7 8 9 10 11 12 13 Description Display Arrow to the right Help Up Down Plus Minus Esc Home Ok Indicator light, operation (green) Indicator light, fault (red) Contrast TM03 1304 1705 TM03 8947 4807 D C Fig. 7 Display design 8.1.1 Menu line The menu line (A) is illustrated in fig. 7. The display has four main menus: Status: Indication of system status Operation: Change of operating parameters such as setpoint (password option) Alarm: Alarm log for fault finding Settings: Change of settings (password option) 8.1.2 Top line The top line (B) is illustrated in fig. 7. The top line shows · the display number and title (left side) · the selected menu (left side) · the symbol in case of alarm (right side) · the symbol if the service language has been selected (right side). 8.1.3 Graphical illustration The graphical illustration (D) may show a status, an indication or other elements, depending on the position in the menu structure. The illustration may show the entire system or part of it as well as various settings. 8.1.4 Scroll bar If the list of illustration elements exceeds the display, the symbols and will appear in the scroll bar to the right. Use the and buttons to move up and down in the list. 8.1.5 Bottom line The bottom line (C) shows the date and time. 12 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 450 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 8.2 Buttons and indicator lights The buttons (pos. 2 to 10 in fig. 6) on the CU 351 are active when they are illuminated. 8.2.1 Arrow to the right (pos. 2) Press the button to move to the next menu in the menu structure. If you press when the Settings menu is highlighted, you go to the Status menu. 8.2.2 Help (pos. 3) When the button is illuminated, a help text applying to the current display will appear if the button is pressed. Close the text by pressing the button. 8.2.3 Up and down (pos. 4 and 5) Press the and buttons to move up and down in lists. A text can be selected when it is in a box. If a text is marked and the button is pressed, the text above will be marked instead. If the button is pressed, the text below will be marked. If the button is pressed in the last line in the list, the first line will be marked. If the button is pressed in the first line in the list, the last line will be marked. 8.2.4 Plus and minus (pos. 6 and 7) Use the and buttons to increase and reduce values. A value is activated when the button is pressed. 8.2.5 Esc (pos. 8) Use the button to go one display back in the menu. If a value has been changed and the button is pressed, the new value will not be saved. For further information, see section 8.2.7 Ok (pos. 10). If the button is pressed before the button, the new value will be saved. For further information, see section 8.2.7 Ok (pos. 10). 8.2.6 Home (pos. 9) Press the button to return to the Status menu. 8.2.7 Ok (pos. 10) Use the button as an enter button. The button is also used to start the setting of a value. If a value has been changed and the new value will be activated. button is pressed, the 8.2.8 Indicator lights (pos. 11 and 12) The Hydro MPC control panel incorporates a green and red indicator light. The green indicator light is on when the Hydro MPC is in operation.It is flashing if the Hydro MPC has been set to stop. The red indicator light is on if there is an alarm or a warning. The fault can be identified from the alarm list. 8.2.9 Contrast (pos. 13) The contrast in the display can be changed by means of the button: 1. Press . 2. Adjust the contrast with and . 8.2.10 Back light If no button is touched for 15 minutes, the back light of the panel will be dimmed, and the first display in the Status menu will appear. Press any button to re-activate the back light. Q-Pulse Id: TMS1594 Active: 18/04/2016 13 Page 451 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9. Functions 9.1 Tree of functions 1. Status 1 Status 3.1 Current alarms 3.1.1 Current alarms 1.2 System 1.2.1 Operating mode 1.2.2 Setpoint 1.2.3 Setpoint influence 1.2.4 Measured values 1.2.5 Analog inputs 1.3 Pump 1 1.4 Pump 2 1.5 Pump 3 1.6 Pump 4 1.7 Pump 5 1.8 Pump 6 2. Operation 3. Alarm 2 Operation 2.1 Further settings 2.1.1 System operating mode 2.1.2 Control mode 2.1.3 Setpoints 2.1.4 Individual pump control 2.1.4. Pump 1...6 3 Alarm status 3.1 Current alarms 3.2 Alarm log Continued on page 15 Key to the four main menus, Status, Operation, Alarm and Settings Status The Status menu shows alarms and the status of system and pumps. Note: No settings can be made in this menu. Operation In the Operation menu, the most basic parameters can be set, such as setpoint, operating mode, control mode and individual pump control. Alarm The Alarm menu gives an overview of alarms and warnings. Alarms and warnings can be reset in this menu. Settings In the Settings menu, it is possible to set various functions: · Primary controller Setting of alternative setpoints, external setpoint influence, primary sensor, clock program, proportional pressure and S-system configuration. · Pump cascade control Setting of min. time between start/stop, max. number of starts/hour, number of standby pumps, forced pump changeover, pump test run, pilot pump, pump stop attempt, pump start and stop speed, min. performance and compensation for pump start-up time. · Secondary functions Setting of stop function, soft pressure build-up, digital and analog inputs, digital outputs, emergency run, min., max. and user-defined duty, pump curve data, flow estimation, control source and fixed inlet pressure. · Monitoring functions Setting of dry-running protection, min. and max. pressure, external fault, limit 1 and 2 exceeded, pumps outside duty range and pressure relief. · Functions, CU 351 Selection of service language, main language and units. Setting of date and time, passwords, Ethernet connection, GENIbus number and software status. 14 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 452 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Continued from page 16 4. Settings 4.1 Primary controller 4.1.1 PI controller 4.1.2 Alternative setpoints 4.1.3 4.1.2.1 Alternative setpoints 2...7 External setpoint influence 4.1.3.1 Set the influence function 4.1.3.2 Setting of influence function 4.1.4 4.1.6 4.1.7 4.1.8 Primary sensor Clock program Proportional pressure S-system configuration 4.2 Pump cascade control 4.2.1 Min. time between start/stop Max. number of starts/hour 4.2.3 Standby pumps 4.2.4 4.2.5 4.2.6 4.2.7 Forced pump changeover Pump test run Pilot pump Pump stop attempt 4.2.8 Pump start and stop speed 4.2.9 Min. performance 4.2.10 Compensation for pump start-up time 4.3 Secondary functions 4.3.1 Stop function 4.3.3 4.3.5 4.3.7 4.3.1.1 Stop parameters Soft pressure build-up Emergency run Digital inputs 4.3.8 Function, DI1..DI3 (CU 351), [10, 12, 14] Function, DI1..DI9 (IO 351-41), [10...46] Function, DI1..DI9 (IO 351-42), [10...46] Analog inputs Setting, analog input AI1..AI3 (CU 351), [51, 54, 57] Function, AI1...AI3 (CU 351), [51, 54, 57] Setting, AI1..AI2 (IO 351-41), [57, 60] Function, AI1..AI2 (IO 351-41), [57, 60] Setting, AI1..AI2 (IO 351-42), [57, 60] Function, AI1..A2 (IO 351-42), [57, 60] 4.3.9 Digital outputs Function, DO1 and DO2 (CU 351), [71, 74] Function, DO1...DO7 (IO 351-41), [77...88] Function, DO1...DO7 (IO 351-42), [77...88] 4.3.14 Min., max. and user-defined duty 4.3.14.1 Min. duty 4.3.14.2 Max. duty 4.3.14.3 User-defined duty 4.3.19 Pump curve data 4.3.23 Flow estimation 4.3.20 Control source 4.3.22 Fixed inlet pressure 4.3.23 Flow estimation 4.4 Monitoring functions 4.4.1 Dry-running protection 4.4.1.1 Pressure/level switch 4.4.1.2 Measurement, inlet pressure 4.4.1.3 Measurement, tank level 4.4.2 Min. pressure 4.4.3 Max. pressure 4.4.4 External fault 4.4.5 Limit 1 exceeded 4.4.6 Limit 2 exceeded 4.4.7 Pumps outside duty range 4.4.8 Pressure relief Q-Pulse Id: TMS1594 Active: 18/04/2016 15 Page 453 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Continued from page 16 4. Settings 4.5 Functions, CU 351 Change language to service language (GB) Run wizard again 4.5.1 4.5.2 Display language Display units 4.5.2.1 4.5.2.2 Units for pressure Units for differential pressure 4.5.2.3 4.5.2.4 4.5.2.5 4.5.2.6 Units for head Units for level Units for flow rate Units for volume 4.5.2.7 4.5.2.8 4.5.2.9 4.5.2.10 Units for specific energy Units for temperature Units for power Units for energy 4.5.3 4.5.4 4.5.5 4.5.6 4.5.9 Date and time Password Ethernet GENIbus number Software status 16 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 454 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.2 Overview Section Display and display number 9.4 Status (1) 9.4.1 Current alarms (3.1) 9.4.2 System (1.2) 9.4.3 Operating mode (1.2.1) 9.4.4 Setpoint (1.2.2) 9.4.5 Setpoint influence (1.2.3) 9.4.6 Measured values (1.2.4) 9.4.7 Analog inputs (1.2.5) 9.4.8 Pump 1...6 (1.3 to 1.8) 9.5 Operation (2) 9.5.1 Operation (2) 9.5.2 System operating mode (2.1.1) 9.5.3 Control mode (2.1.2) 9.5.4 Setpoints (2.1.3) 9.5.5 Individual pump control (2.1.4) 9.5.6 Setting of individual operating mode (2.1.4.1 to 2.1.4.6) 9.6 Alarm (3) 9.6.1 Alarm status (3) 9.6.2 Current alarms (3.1) 9.6.3 Alarm log (3.2) 9.7 Settings (4) 9.7.1 Primary controller (4.1) 9.7.2 PI controller (4.1.1) 9.7.3 Alternative setpoints (4.1.2) 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) 9.7.5 External setpoint influence (4.1.3) 9.7.6 Setting of influence function (4.1.3.2) 9.7.7 Primary sensor (4.1.4) 9.7.8 Clock program (4.1.6) 9.7.9 Proportional pressure (4.1.7) 9.7.10 S-system configuration (4.1.8) 9.7.11 Pump cascade control (4.2) 9.7.12 Min. time between start/stop (4.2.1) 9.7.13 Max. number of starts/hour (4.2.1) 9.7.14 Standby pumps (4.2.3) 9.7.15 Forced pump changeover (4.2.4) 9.7.16 Pump test run (4.2.5) 9.7.17 Pilot pump (4.2.6) 9.7.18 Pump stop attempt (4.2.7) 9.7.19 Pump start and stop speed (4.2.8) 9.7.20 Min. performance (4.2.9) 9.7.21 Compensation for pump start-up time (4.2.10) 9.7.22 Secondary functions (4.3) 9.7.23 Stop function (4.3.1) 9.7.24 Soft pressure build-up (4.3.3) 9.7.25 Emergency run (4.3.5) 9.7.26 Digital inputs (4.3.7) 9.7.27 Functions of digital inputs (4.3.7.1) 9.7.28 Analog inputs (4.3.8) 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) 9.7.31 Digital outputs (4.3.9) 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) 9.7.33 Min., max. and user-defined duty (4.3.14) 9.7.34 Min. duty (4.3.14.1) See page 19 19 19 20 20 20 21 21 21 21 22 22 23 25 25 26 27 27 32 32 32 33 33 33 34 34 35 35 36 36 37 37 38 38 38 39 39 40 40 41 41 42 42 42 44 45 45 46 46 47 47 48 48 49 49 Q-Pulse Id: TMS1594 Active: 18/04/2016 17 Page 455 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Section 9.7.35 9.7.36 9.7.37 9.7.38 9.7.39 9.7.40 9.7.41 9.7.42 9.7.43 9.7.44 9.7.45 9.7.46 9.7.47 9.7.48 9.7.49 9.7.51 9.7.52 9.7.53 9.7.54 9.7.55 9.7.56 9.7.57 9.7.58 9.7.59 Display and display number Max. duty (4.3.14.2) User-defined duty (4.3.14.3) Pump curve data (4.3.19) Control source (4.3.20) Fixed inlet pressure (4.3.22) Flow estimation (4.3.23) Monitoring functions (4.4) Dry-running protection (4.4.1) Dry-running protection with pressure/level switch (4.4.1.1) Dry-running protection with pressure transmitter (4.4.1.2) Dry-running protection with level transmitter (4.4.1.3) Min. pressure (4.4.2) Max. pressure (4.4.3) External fault (4.4.4) Limit 1 and 2 exceeded (4.4.5 and 4.4.6) Pressure relief (4.4.8) Functions, CU 351 (4.5) Display language (4.5.1) Display units (4.5.2) Date and time (4.5.3) Passwords (4.5.4) Ethernet (4.5.5) GENIbus number (4.5.6) Software status (4.5.9) See page 49 50 50 51 52 52 52 53 53 54 54 55 55 56 56 57 58 58 59 60 60 60 61 61 18 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 456 of 1068 TM03 2293 4807 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.3 Description of functions The description of functions is based on the four main menus of the CU 351 control unit: Status, Operation, Alarm and Settings. The functions apply to all control variants unless otherwise stated. 9.4 Status (1) The first status display is shown below. This display is shown when the Hydro MPC is switched on, and it appears when the buttons of the control panel have not been touched for 15 minutes. F G H 9.4.1 Current alarms (3.1) E A Fig. 9 Current alarms Description I In this display, current unreset alarms and warnings are shown. C For further information, see sections 9.6.2 Current alarms (3.1) D B and 9.6.3 Alarm log (3.2). 9.4.2 System (1.2) TM03 8947 4807 Fig. 8 Status Description No settings can be made in this menu. The current value (process value, PV) of the control parameter, usually the discharge pressure, is shown in the upper right corner (G) together with the selected setpoint (SP) (H). The upper half of the display (A) shows a graphic illustration of the Hydro MPC booster system and part of the system. The selected measuring parameters are shown with sensor symbol and current value. In the middle of the display, an information field (I) is shown if any incidents occur. The lower display half (B) shows · the latest current alarm, if any, and the fault cause together with the fault code in brackets · system status with current operating mode and control source · pump status with current operating mode and manual/auto. Note If a fault has occurred, the symbol will be shown in the alarm line (C) together with the cause and fault code, for instance Limit 2 exceeded (191). If the fault is related to one of the pumps, the symbol will also be shown in front of the status line (D) of the pump in question. At the same time, the symbol will be flashing instead of the pump symbol (E). The symbol will be shown to the right in the top line of the display (F). As long as a fault is present, this symbol will be shown in the top line of all displays. To open a menu line, mark the line with . or , and press The display makes it possible to open status displays showing · current alarms · system status · status of each pump. Fig. 10 System Description This display shows the current operational state of the Hydro MPC booster system. It is possible to go to subdisplays showing details. The display makes it possible to open specific displays about · operating mode · setpoint · setpoint influence · measured values · analog inputs. TM03 8946 4807 Q-Pulse Id: TMS1594 Active: 18/04/2016 19 Page 457 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.4.3 Operating mode (1.2.1) 9.4.4 Setpoint (1.2.2) TM03 2272 4807 TM03 2273 4807 Fig. 11 Operating mode Description Here the operating mode of the Hydro MPC booster system is shown as well as from where the Hydro MPC is controlled. Operating modes Hydro MPC has six operating modes: 1. Normal The booster system adapts its performance to the requirement. 2. Max. The pumps run at a constant high speed. Normally, all pumps run at maximum speed. 3. User-defined The pumps run at a constant speed set by the user. Usually it is a performance between Max. and Min. 4. Min. The pumps run at a constant low speed. Normally, one pump is running at a speed of 70 %. 5. Stop All pumps have been stopped. 6. Emergency run The pumps run according to the setting made in the display Emergency run (4.3.5). The performance required in the operating modes Max., Min., User-defined and Emergency run can be set in the Settings menu. See sections 9.7.33 Min., max. and user-defined duty (4.3.14) and 9.7.25 Emergency run (4.3.5). The current operating mode can be controlled from four different sources: Fault, External signal, CU 351 and Bus. Control source Hydro MPC can be set to remote control via an external bus (option). In this case, a setpoint and an operating mode must be set via the bus. In the Settings menu, it is possible to select whether the CU 351 or the external bus is to be the control source. The status of this setting is shown in the display Operating mode. Fig. 12 Setpoint Description This display shows the selected setpoint and whether it comes from the CU 351 or an external bus. The display also shows all seven possible setpoints from CU 351 (for closed- and open-loop control). At the same time, the selected setpoint is shown. As it is a status display, no settings can be made. Setpoints can be changed in the Operation menu. 9.4.5 Setpoint influence (1.2.3) Fig. 13 Setpoint influence Description The selected setpoint can be influenced by parameters. The parameters are shown as percentage from 0 to 100 % or as a pressure measured in bar. They can only reduce the setpoint, as the influence in percentage divided with 100 is multiplied with the selected setpoint: Setpointcurrent(SP) = Setpointselected × Infl.(1) × Infl.(2) × ... The display shows the parameters influencing the selected setpoint and the percentage or value of influence. Some of the possible parameters can be set in the display External setpoint influence (4.1.3). The parameter low flow boost is set as an on/off band as a percentage of the setpoint set in the display Stop function (4.3.1). The parameter is set as a percentage in the display Proportional pressure (4.1.7). Finally the resulting current setpoint (SP) is shown. TM03 8948 4807 20 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 458 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.4.6 Measured values (1.2.4) 9.4.8 Pump 1...6 (1.3 to 1.8) TM03 2268 4807 TM03 2270 4807 Fig. 14 Measured values Description This display gives a general status of all measured and calculated parameters. Note The lines "Power consumption" and "Energy consumption" are only shown in Hydro MPC-E booster systems. 9.4.7 Analog inputs (1.2.5) TM03 8949 4807 Fig. 15 Analog inputs Description The display shows an overview of the analog inputs and the current measured values of each input. See sections 9.7.28 Analog inputs (4.3.8), 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) and 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1). Fig. 16 Pump 1 Description This display shows the operational state of the individual pumps. The pumps may have different operating modes: · Auto Together with the other pumps in automatic operation, the pump is controlled by the PI controller which ensures that the booster system delivers the required performance (pressure). · Manual The pump is not controlled by the PI controller. In manual operation, the pump has one of the following operating modes: Max. The pump runs at a set maximum speed. (This operating mode can only be selected for variable-speed pumps.) Normal The pump runs at a set speed. Min. The pump runs at a set minimum speed. (This operating mode can only be selected for variable-speed pumps.) Stop The pump has been forced to stop. Besides information about the operating mode, it is possible to read various parameters in the status display, such as these: · speed (only 0 or 100 % are shown for mains-operated pumps) · power consumption (only CR(I)E pumps) · energy consumption (only CR(I)E pumps) · operating hours. 9.5 Operation (2) In this menu, the most basic parameters can be set, such as setpoint, operating mode, control mode and forced control of pumps. Q-Pulse Id: TMS1594 Active: 18/04/2016 21 Page 459 of 1068 9.5.1 Operation (2) WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Factory setting The setpoint is a value suitable for the Hydro MPC booster system in question. The factory setting may have been changed in the start-up menu. 9.5.2 System operating mode (2.1.1) A B C TM03 8950 4807 TM03 8951 4807 Fig. 17 Operation Description The column shows the setting range. In closed-loop control, it corresponds to the range of the primary sensor, here 0-16 bar. In open-loop control, the setting range is 0-100 %. At the left hand of the column, the selected setpoint 1 (A) is shown, i.e. the value set in the display. At the right hand of the column, the current setpoint (B) is shown, i.e. the setpoint acting as reference for the PI controller. If no kind of external setpoint influence has been selected, the two values will be identical. The current measured value (discharge pressure) is shown as the grey part of the column (C). See sections 9.7.5 External setpoint influence (4.1.3) and 9.7.6 Setting of influence function (4.1.3.2). Below the display is a menu line for setting of setpoint 1 and selection of operating mode, including the operating modes Normal and Stop. It is possible to select further settings: system operating mode, control mode, setpoints for closed and open loop as well as individual pump control. Setting range Setpoint: Closed-loop control: Open-loop control: Measuring range of the primary sensor 0-100 % Setting via control panel Setpoint: 1. Mark the Operation menu with . 2. Mark Setpoint 1 with or . Set the value with or . 3. Save with . Operating mode: 1. Mark the Operation menu with . 2. Mark operating mode Normal or Stop with or . Save with . Further settings: 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Select one of the settings below with : or , and press · system operating mode (see section 9.5.2) · control mode (see section 9.5.3) · setpoints (see section 9.5.4) · individual pump control (see section 9.5.6). Fig. 18 System operating mode Description Hydro MPC can be set to six different operating modes. Normal is the typical setting. See section 9.4.3 Operating mode (1.2.1). The performance of the operating modes Max., Min., Userdefined and Emergency run can be set in the Settings menu. In the display shown, it is possible to go directly to the Settings menu in order to set the pump performance or the setpoint. Setting range It is possible to select the operating modes Normal, Max., Min., User-defined, Stop and Emergency run. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark System operating mode with . or , and press 4. Select the desired operating mode by marking one of the lines with check boxes with or , and press . 5. In order to set the performance in min., max., user-defined duty or emergency run, mark the desired line at the bottom of the display, and press . See sections 9.7.33 Min., max. and user-defined duty (4.3.14) and 9.7.25 Emergency run (4.3.5). Factory setting Normal. 22 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 460 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.5.3 Control mode (2.1.2) Open loop In open-loop control, the pumps run at a fixed speed. The pump speed is calculated from the performance set by the user (0-100 %). The pump performance in percentage is proportional with the flow rate. Open-loop control is usually used when the booster system is controlled by an external controller which controls the performance via an external signal. The external controller could for instance be a building management system connected to the Hydro MPC. In such cases, the Hydro MPC is like an actuator. See figs 22 and 23. TM03 2283 4807 TM03 2232 3905 Fig. 19 Control mode Description There are two control modes, namely closed and open loop. Examples: Closed loop The typical control mode is closed loop where the built-in PI controller ensures that the booster system delivers the discharge pressure required (setpoint). The performance is based on the setpoint set for closed loop. See figs 20 and 21. Fig. 22 Booster system with external controller (open loop) Flow rate [gpm] TM03 2391 3607 Fig. 20 Booster system controlled by built-in PI controller (closed loop) P [bar] Setpoint Time [sec] Fig. 21 Regulation curve for closed loop Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Control mode with or , and press . 4. Select Closed loop with or , and press . 5. Set the setpoint. See sections 9.5.4 Setpoints (2.1.3) and 9.5.1 Operation (2). TM03 2390 4105 TM03 2231 3905 0 5 Input [%] from external controller Fig. 23 Regulation curve for open loop Flow rate [gpm] 100 75 Flow rate Pump 1 50 Pump 2 Pump 3 Pump 4 25 5 50 70.7 86.6 100 Input [%] from external controller Fig. 24 Regulation curve for Hydro MPC-E in open loop TM03 9977 4807 Q-Pulse Id: TMS1594 Active: 18/04/2016 23 Page 461 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Flow rate [gpm] 100 75 50 25 Flow rate Pump 1 Pump 2 Pump 3 Pump 4 5 50 70.7 86.6 100 Input [%] from external controller Fig. 25 Regulation curve for Hydro MPC-ED in open loop Flow rate [gpm] 100 75 Flow rate Pump 1 50 Pump 2 Pump 3 Pump 4 25 5 50 70.7 86.6 100 Input [%] from external controller Fig. 26 Regulation curve for Hydro MPC-ES in open loop Flow rate [gpm] 100 75 Flow rate 50 Pump 1 Pump 2 Pump 3 25 Pump 4 Input [%] from 5 50 70.7 86.6 100 external controller Fig. 27 Regulation curve for Hydro MPC-S in open loop TM03 9974 4807 TM03 9975 4807 TM03 9976 4807 Correlating open loop input setpoint percentage with number of pumps in operation. Example: MPC system with (4) pumps · Setpoint 0% to 5% = All pumps stopped One pump operation from setpoint from 5% to (1-pump/4pumps) = 50% · Two pump operation from 50% to (2-pump/4-pumps) = 70.7% · Three pump operation from 70.7% to (3-pumps/4-pumps) = 86.6% · Four pump operation from 86.6% to 100% For staging pumps off the cut-out is 2% less then cut-in. Example: staging from 4-pump to 3-pump operation will occur at 84.6% reference signal. Setting range These settings must be made in connection with open loop: · stop of the Hydro MPC booster system · selection of control mode Open loop · setting of setpoint 1, open loop · setting of external setpoint influence · selection of operating mode Normal. Setting via control panel To set an external control source to control the Hydro MPC booster system, proceed as follows: 1. Mark the Operation menu with . 2. Mark the operating mode Stop with or , and press . The check mark in the right box shows that the operation has been stopped. 3. Mark Further settings with or , and press . 4. Mark Control mode with or , and press . 5. Select Open loop with or , and press . 6. Return by pressing twice. 7. Mark Set setpoint 1, open loop with or . 8. Set the setpoint to 100 % with , and save with . 9. Mark the Settings menu with . 10.Mark Primary controller with or , and press . 11.Mark External setpoint influence with . or , and press 12.Mark Go to setting of analog input with press . or , and 13.Select the analog input with or , and press . 14.Select the range of the analog input with or , and press . The selection is indicated by a check mark. 15.Mark Measured input value with or , and press . Now the display 4.3.8.1.1 appears. 16.Select 0-100 % signal with or , and press . 17.Press to return to display 4.3.8.1. 18.Set the minimum sensor value with . or , and save with 19.Set the maximum sensor value with . or , and save with 20.Return by pressing twice. 21.Mark Input value to be influenced by with press . or , and 22.Mark 0-100 % signal with or , and press . 23.Return with . 24.Mark Set the influence function with or , and press . For details, see section 9.7.6 Setting of influence function (4.1.3.2). 25.Mark the menu line for number of points with press . or , and 24 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 462 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 26.Select the required number of points with save with . or , and 27.Mark External input value (point 1) with or . 28.Set the value of the external input value with save with . or , and 29.Mark Reduce setpoint to (point 1) with or . 30.Set the value as a percentage with . or , and save with 31.Repeat 27 to 31 for all chosen points. 32.Return with . 33.Mark Filter time with or , set the time in seconds with or , and save with . 34.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 35.Return by pressing twice. 36.Mark the Operation menu with . 37.Mark the operating mode Normal with or , and press . The check mark in the right box shows that the operation is normal. The booster system can now be controlled by an external controller. Factory setting Closed-loop control. 9.5.4 Setpoints (2.1.3) Fig. 28 Setpoints Description In addition to the primary setpoint 1 (shown in the display 2 in the Operation menu), six alternative setpoints can be set for closedloop control. It is furthermore possible to set seven setpoints for open-loop control. As described in sections 9.7.3 Alternative setpoints (4.1.2) and 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7), it is possible to activate one of the alternative setpoints by means of external contacts. Setting range The setting range of setpoints for closed-loop control depends on the range of the primary sensor. See section 9.7.7 Primary sensor (4.1.4). In open loop control, the setting range is 0 - 100 %. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Setpoints with or , and press . 4. Select the setpoint with or . TM03 8952 4807 TM03 8953 4807 5. Set the setpoint with or , and press . Factory setting Setpoint 1 for closed-loop control is a value suitable for the Hydro MPC in question. The alternative setpoints for closed-loop control are 3 bar. All setpoints for open-loop control are 70 %. 9.5.5 Individual pump control (2.1.4) Fig. 29 Individual pump control Description It is possible to change the operating mode from automatic operation to one of the manual operating modes. Auto The pumps are controlled by the PI controller, ensuring that the booster system delivers the required performance (pressure). Manual The pump is not controlled by the PI controller, but set to one of the following manual operating modes: · Max. The pump runs at a set maximum speed. (This operating mode can only be selected for variable-speed pumps.) · Normal The pump runs at a set speed. · Min. The pump runs at a set minimum speed. (This operating mode can only be selected for variable-speed pumps.) · Stop The pump has been forced to stop. Pumps in manual operation are not part of the normal pump cascade and speed control. The manual pumps are a "disturbance" of the normal control of Hydro MPC. If one or more pumps are in manual operation, Hydro MPC may not be able to deliver the set performance. There are two displays for the function. In the first display, the pump to be set is selected, and in the next display, the operating mode is selected. Setting range All pumps can be selected. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Individual pump control with or , and press . 4. Select the pump with or , and press . Q-Pulse Id: TMS1594 Active: 18/04/2016 25 Page 463 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.5.6 Setting of individual operating mode (2.1.4.1 to 2.1.4.6) TM03 8954 4807 Fig. 30 Setting of individual operating mode Description This display is shown for the individual pumps and makes it possible to set an operating mode. Setting range It is possible to select Auto or Manual as well as the operating mode of the pump for manual operation - Max., Normal, Min. or Stop. For mains-operated pumps only Normal or Stop can be selected. Setting via control panel 1. Mark the Operation menu with . 2. Mark Individual pump control with or , and press . 3. Select the pump with or , and press . 4. Mark Auto or Manual with or , and press . 5. Manual: Select the operating mode with press . or , and 6. Normal: Mark Setpoint with or . Set the speed of the variable-speed pump with and press . or , Factory setting Auto. 26 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 464 of 1068 TM03 2291 4807 Warning( )/alarm( ) Change of operating mode to Reset of alarm Restart Set in the Settings menu Alarm code WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.6 Alarm (3) The Alarm menu gives an overview of alarms and warnings. In this menu, it is possible to reset alarms and to see the alarm log. 9.6.1 Alarm status (3) Fault Fig. 31 Alarm status Description A fault in the Hydro MPC booster system or one of the components monitored can cause an alarm or a warning . Besides the fault signal via the alarm/warning signal relay and the red indicator light on the CU 351, an alarm can also cause a change of operating mode, for instance from Normal to Stop. A warning only causes a fault indication. The table shows the possible causes of fault together with an alarm code number, and whether they result in an alarm or a warning. It also shows to what operating mode the booster system changes in case of alarm, and whether restart of the booster system and reset of the alarm is manual or automatic. The table also shows that the reaction to some of the fault causes mentioned can be set in the Settings menu. See sections 9.7.24 Soft pressure build-up (4.3.3) and 9.7.41 Monitoring functions (4.4) to 9.7.51 Pressure relief (4.4.8). Water shortage Water shortage Pressure high Pressure low Pressure relief Alarm, all pumps External fault Dissimilar sensor signals Fault, primary sensor Fault, sensor Communication fault Phase failure Undervoltage, pump Overvoltage, pump Overload, pump Overtemperature, pump Other fault, pump Internal fault, CU 351 Internal fault, IO 351 VFD not ready Fault, Ethernet Limit 1 exceeded Limit 2 exceeded Pressure build-up fault Pumps outside duty range Pilot pump fault Auto 206 Stop Man/auto X 214 Stop Auto 210 Stop Auto Man X 211 Auto X 219 Stop Auto 203 Auto X 3 Stop Man Auto 204 Stop Auto 89 Auto 88 Auto 10 Auto 2 Auto 7, 40, 42, 73 Auto 32 Auto Auto 48, 50, 51, 54 64, 65, 67 Auto 76, 83 72, Auto 83, 157 Stop Auto 83, 157 Auto 213 Auto 231, 232 Man/auto X 190 Man/auto X 191 Man/auto X 215 Man/auto X 208 Auto 216 Q-Pulse Id: TMS1594 Active: 18/04/2016 27 Page 465 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Alarm (3) continued MPC alarm indication "Protocol description" 1. Phase failure, pump 2. Undervoltage Alarm code 2 7 3. Undervoltage, pump 40 4. Undervoltage, pump 42 5. Undervoltage, pump 73 6. Overvoltage, pump 32 7. Overload, associated device 48 8. Overload, associated device 50 9. Overload, associated device 51 10. Overload, associated device 54 11. Over temperature, pump 65 12. Over temperature, pump 67 Associated device and device no. Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Description/cause Remedy - 1. Check that all three power supply phases are within a 15 V window. HSD = hardware shutdown. There has been a fault, and the permissible number of restarts for the 1. Restore power supply. fault type has been exceeded. 2. Replace terminal box. a) Fault in power supply. a) Terminal box defective. a) Power supply voltage 1. Bring voltage back to is too low at start. prescribed level. a) Faulty power supply at the time of staging on a pump. 1. Restore proper power supply. a) Low supply voltage. b) Power supply failure 1. Restore proper power while motor is supply. running. a) Supply voltage is too 1. Bring voltage back to high at start. prescribed level. a) Heavy overload has caused software shutdown (SSD). 1. Check and possibly reduce load. a) MPF = motor protection function. The built-in motor 1. Check and possibly protection has reduce load/improve detected a sustained cooling. overload (MPF 60 sec. limit)> a) Heavy overload (Imax. very high). Pump blocked at start. 1. Unblock the pump. a) The built-in motor protection has 1. Check and possibly detected a transitory reduce load/improve overload (MPF 3 sec. cooling limit). a) PTC sensor in the motor has signalled over temperature. 1. Check and possibly reduce load/improve cooling. a) Terminal box has indicated over temperature. 1. Check and possibly reduce load/improve cooling. (Temperature during operation can be read via PC Tool Eproducts.) Reset Alarm/warning type1 Action type2 Auto Warning Auto Warning Auto Auto Warning Warning Auto Warning Auto Auto Warning Warning Auto Warning Auto Warning Auto Warning Auto Warning Auto Warning 28 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 466 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MPC alarm indication "Protocol description" 13. Other fault, associated device 14. Limit 1 exceeded 15. Limit 2 exceeded 16. Pressure relief 17. Pressure build-up fault 18. Pumps outside duty range 19. Pilot pump fault Alarm code 76 190 191 219 215 208 216 Associated device and device no. Pump 1-6 Measured parameter Measured parameter System System System Pilot pump Description/cause Remedy Reset Alarm/warning type1 Action type2 Try to reset the fault: 1. Switch off the supply power. a) Internal communication error has occurred in the pump. 2. Wait until all diodes are out. 3. Switch on the supply power. If this does not remedy the fault, replace the terminal box. a) The measured parameter has exceeded the limit set. 1. Remove the cause of the fault. a) The measured parameter has exceeded the limit set. 1. Remove the cause of the fault. a) The monitored pressure could not be reduced sufficiently. 1. Reduce the pressure to below the limit. a) The pressure set cannot be reached within the configured 1. Check limit and pipes. time. a) The pump is running outside the defined 1. Check the system. range. a) Pilot pump fault 1. Check wires. 2. Check the pump. Auto Auto/ manual Auto/ manual Auto Auto/ manual Auto/ manual Auto Warning Alarm/warning Stop/ unchanged Alarm/warning Stop/ unchanged Warning Unchanged Alarm/warning Stop/ unchanged Warning Unchanged Warning Q-Pulse Id: TMS1594 Active: 18/04/2016 29 Page 467 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MPC alarm indication "Protocol description" Alarm code Associated device and device no. Description/cause Remedy Reset Alarm/warning type1 Action type2 20. Water shortage, level 1 *Water shortage, level 1 206 a) The pre-pressure (or the level in the feed tank) is below its programmable warning limit. Auto Warning Unchanged 21. Water shortage, level 2 *Water shortage, level 2 214 a) The pre-pressure (or the level in the feed tank) is below its 1. Check the actual and the programmable corresponding settings. Auto/ warning limit. 2. Check the sensor/switch, Manual b) The pre-pressure wiring and input switch detect water according to the wiring shortage. diagram. Alarm Stop Warning Unchanged 22. Discharge pressure high *Pressure above max. 210 pressure 23. Discharge pressure low *Pressure below min. 211 pressure System a) The system pressure 3. Check the sensor/switch. Alarm is above the Auto/ Fast stop (over programmable highpressure alarm limit. Manual rule min. seq. time) a) The system pressure is below the programmable lowpressure alarm limit. Auto/ Manual Alarm/Warning Stop/ Unchanged 24. All pumps in alarm *All pumps in alarm 203 a) All pumps, set to Auto, is stopped on account of pump alarm Troubleshoot according to the alarm message/code: 1. System 2. Pumps installed Use fault fault finding for the pump. Auto Alarm Stop b) Pumps are not indicating alarm Check the Genibus wires eg. connection, polarisation. 25. External fault signal *External fault signal 003 a) External fault digital input activated. 1. Check the external signal source. 2. Check the digital input according to the wiring diagram Auto/ Manual Alarm/Warning Stop/ Unchanged 26. Inconsistency between sensors *Inconsistency between sensors a) Primary feedback 1. Check the wiring and Primary sensor value input according to the 204 sensor and/or redundant (pressure) is inconsistent with wiring diagram. 2. Check the sensor output sensor redundant feedback according to the sensor value. measured value. Auto Warning Unchanged 27. Primary sensor *Closed loop feedback sensor signal fault 089 Primary sensor a) A fault in the sensor assigned to the feed back control is detected. 1. Check the wiring and input according to the wiring diagram. 2. Check the sensor output according to the measured value. Alarm Stop b) Error in the settings Check the primary sensor of the sensor which is settings assigned to the regulator. Auto 28. Sensor fault *General (measurement) sensor signal fault 088 CU 351 IO 351 as IO module a) The signal 1. Check the wiring and (ex. 4-20 mA) from input according to the one of the analog wiring diagram. sensors is outside the 2. Check the sensor output selected signal according to the range. measured value Warning Unchanged 30 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 468 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MPC alarm indication "Protocol description" Alarm code 29. CU 351 internal fault *Real time clock out of 157 order 30. Ethernet fault *Ethernet: No address 231 from DHCP server 31. Ethernet fault *Ethernet: Auto disabled 232 due to misuse 32. FLASH parameter verification error *FLASH parameter 083 verification error 33. IO 351 internal fault *Hardware fault type 2 080 34. VFD not ready *VFD not ready 213 35. Communication fault *Pump communication fault 010 36. Device alarms From device Associated device and device no. CU 351 IO 351 Pump 1-6 CU 351 Pump 1-6 IO 351 Pump 1-6 Description/cause Remedy a) The real-time clock in Replace the CU 351 CU 351 is out of order. a) No address from DHCP server 1. Communication error. 2. Please contact the a) Auto-disabled due to misuse system integrator. a) Verification error in CU 351 FLASH memory Replace the CU 351 a) IO 351 pump module See current alarms and hardware fault identify the faulty IO 351 b) IO 351 I/O module hardware fault module from the alarm message and replace the module. 1. Check for VFD alarm a) The VFD signal relay do not release the 2. Check the wiring and VFD for operation input according to the wiring diagram. See actual alarms and identify the faulty device from the alarm message. a) No GeniBus 1. Check power supply communication with a device connected to CU 351 2. Check GeniBus cable connection 3. Check, with R100, that the device GeniBus no. is correct. See actual alarms and identify the faulty device a) The device is in alarm from the alarm message. 1. Fault find according to the service instruction for the device. Reset type1 Auto Alarm/warning Action type2 Warning Unchanged 1) Reset type is either fixed as "Auto acknowledge" (Auto) or can be programmed to be Auto or manual ackknowledge (Auto/Man)*. 2) Programmable action types: - Go to operating mode "Stop" (no delay (<0.5 s) between pump disconnections). - Go to operating mode "Min". - Go to operating mode "User-defined". - Go to operating mode "Max". - Set pumps in source mode "Local". - No action (warning only) Q-Pulse Id: TMS1594 Active: 18/04/2016 31 Page 469 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.6.2 Current alarms (3.1) Description Here warnings and alarms are shown. For every warning or alarm, the following is shown: · Whether it is a warning or an alarm . · Where the fault occurred. System, Pump 1, Pump 2, etc. · In case of input-related faults, the input is shown. · What the cause of the fault is, and the alarm code in brackets: Water shortage (214), Max. pressure (210), etc. · When the fault occurred: Date and time. · When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. 9.7 Settings (4) TM03 2293 4807 TM03 2294 4807 Fig. 32 Current alarms Description This submenu shows the following: · Warnings caused by faults that still exist. · Warnings caused by faults that have disappeared, but the warning requires manual reset. · Alarms caused by faults that still exist. · Alarms caused by faults that have disappeared, but the alarm requires manual reset. All warnings and alarms with automatic reset are automatically removed from the menu when the fault has disappeared. Alarms requiring manual reset are reset in this display by pressing . An alarm cannot be reset until the fault has disappeared. For every warning or alarm, the following is shown: · Whether it is a warning or an alarm . · Where the fault occurred: System, Pump 1, Pump 2, etc. · In case of input-related faults, the input is shown. · What the cause of the fault is, and the alarm code in brackets: Water shortage (214), Max. pressure (210), etc. · When the fault occurred: Date and time. · When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. 9.6.3 Alarm log (3.2) The alarm log can store up to 24 warnings and alarms. Fig. 33 Alarm log TM03 2292 4807 Fig. 34 Settings In the Settings menu, it is possible to set the following functions: · Primary controller Setting of PI controller, alternative setpoints, external setpoint influence, primary sensor, clock program, proportional pressure and S-system configuration. · Pump cascade control Setting of min. time between start/stop, max. number of starts/ hour, number of standby pumps, forced pump changeover, pump test run, pilot pump, pump stop attempt, pump start and stop speed, min. performance and compensation for pump start-up time. · Secondary functions Setting of stop function, soft pressure build-up, digital and analog inputs, digital outputs, emergency run, min., max. and user-defined duty, pump curve data, flow estimation, control source and fixed inlet pressure. · Monitoring functions Setting of dry-running protection, min. and max. pressure, external fault, limit 1 and 2 exceeded, pumps outside duty range and pressure relief. · Functions, CU 351 Selection of service language, main language and units. Setting of time and date, passwords, Ethernet connection, GENIbus number and software status. Usually, all these functions are set correctly when the Hydro MPC is switched on. It is only necessary to make settings in this menu if the functionality is to be expanded with for instance alternative setpoints or setpoint influence, or if the settings of the CU 351 are to be adjusted. 32 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 470 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.1 Primary controller (4.1) Fig. 35 Primary controller Description In this menu section, it is possible to set the functions related to the primary controller. It is only necessary to make settings in this menu if the functionality is to be expanded with for instance alternative setpoints, external setpoint influence, clock program or proportional pressure. The following menus can be selected: · PI controller · Alternative setpoints · External setpoint influence · Primary sensor · Clock program · Proportional pressure · S-system configuration. 9.7.2 PI controller (4.1.1) TM03 8955 4807 Setting range · Gain Kp: 30 to 30. Note: For inverse control, set Kp to a negative value. · Integral time Ti: 0.1 to 3600 seconds. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark PI controller with or , and press . 4. Select the gain (Kp) with or . Set the value with or , and save with . Note: Usually it is not necessary to adjust Kp. 5. Select the integral time (Ti) with or , and press . or . Set the time with Factory setting · Kp: 0.5 · Ti: 1 second 9.7.3 Alternative setpoints (4.1.2) TM03 2383 4807 Fig. 37 Alternative setpoints Description This function makes it possible to select up to six setpoints (No 2 to 7) as alternatives to the primary setpoint (No 1). The primary setpoint (No 1) is set in the Operation menu. Every alternative setpoint can be addressed manually to a separate digital input (DI). When the contact of the input is closed, the alternative setpoint applies. If more than one alternative setpoint has been selected and they are activated at the same time, the CU 351 selects the setpoint with the lowest number. Setting range · Six setpoints, No 2 to 7. TM03 2387 4807 Fig. 36 PI controller Description Hydro MPC includes a standard PI controller which ensures that the pressure is stable and corresponds to the setpoint. It is possible to adjust the PI controller if a faster or slower reaction to changes of consumption is required. A faster reaction is obtained if Kp is increased and Ti is reduced. A slower reaction is obtained if Kp is reduced and Ti is increased. Q-Pulse Id: TMS1594 Active: 18/04/2016 33 Page 471 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Factory setting No alternative setpoints have been selected. 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) TM03 2384 4807 Fig. 38 Alternative setpoints 2 to 7 For each alternative setpoint, select the digital input to activate the setpoint. It is possible to set a setpoint for closed loop and for open loop. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Alternative setpoints with or , and press . 4. Select the alternative setpoint with . or , and press 5. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. Set the input and return with . 6. Mark the menu line of the setpoint (closed or open loop) with or . 7. Set the required setpoint with or , and save with . Set both setpoints if Hydro MPC is to be controlled both in open and closed loop. Factory setting No alternative setpoints have been set. 9.7.5 External setpoint influence (4.1.3) TM03 8956 4807 Fig. 39 External setpoint influence Description This function makes it possible to adapt the setpoint by letting measuring parameters influence the setpoint. Typically an analog signal from a flow or temperature transmitter, or a similar transmitter. As an example, the setpoint can be adapted to parameters that can influence the discharge pressure or temperature of the system. The parameters which influence the performance of the booster system are shown as a percentage from 0 to 100 %. They can only reduce the setpoint, as the influence as a percentage divided with 100 is multiplied with the setpoint: Setpointcurrent(SP) = Setpointselected × Infl.(1) × Infl.(2) × ... The influence values can be set individually. A low-pass filter ensures smoothing of the measured value which influences the setpoint. This results in stable setpoint changes. Setting range The following parameters can be selected. · 0-100 % signal · Inlet pressure · Discharge pressure · External pressure · Differential pressure, pump · Differential pressure, external · Flow rate · Tank level, discharge side · Tank level, suction side · Flow pipe temperature · Return pipe temperature · Ambient temperature · Return pipe temperature, external · Differential temperature. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark External setpoint influence with . or , and press 4. Mark Input value to be influenced by with press . Now a list of available parameters appear. or , and 5. Mark the parameter which is to influence the setpoint with or , and press . 6. Return with . 7. Mark Set the influence function with or , and press . For details, see section 9.7.6 Setting of influence function (4.1.3.2). 8. Mark the menu line for number of points with press . or , and 9. Select the required number of points with save with . or , and 10.Mark External input value (point 1) with or . 11.Set the value of the external input value with save with . or , and 12.Mark Reduce setpoint to (point 1) with or . 13.Set the value as a percentage with . or , and save with 14.Repeat points 8 to 13 for all desired parameters. 15.Return with . 16.Mark Filter time with or , set the time in seconds with or , and save with . 34 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 472 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 17.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. Factory setting Setpoint influence is not activated. 9.7.6 Setting of influence function (4.1.3.2) 5. Mark the menu line for number of points with press . or , and 6. Select the required number of points with save with . or , and 7. Mark External input value (point 1) with or . 8. Set the value of the external input value with save with . or , and 9. Mark Reduce setpoint to (point 1) with or . 10.Set the value as a percentage with or , and save with . 11.Repeat points 7 to 10 for all desired parameters. Factory setting External setpoint influence is not activated. 9.7.7 Primary sensor (4.1.4) TM03 2389 4807 Fig. 40 Setting of influence function Description In this menu, you select the relation between the measuring parameter which is to influence the setpoint and the desired influence as a percentage. The relation is set by entering values in a table with maximum eight points by means of the control panel. Example with four points: Setpoint influence [%] TM03 1691 4807 4 100 80 60 3 2 40 20 1 Q [m³/h] 50 Fig. 41 Relation between setpoint influence and flow rate The control unit of the Hydro MPC draws straight lines between the points. A horizontal line is drawn from the minimum value of the relevant sensor (0 m3/h in the example) to the first point. This is also the case from the last point to the sensor's maximum value (example 50 m3/h). Setting range Two to eight points can be selected. Each point contains the relation between the value of the parameter which is to influence the setpoint and the influence of the value. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or 3. Mark External setpoint influence with . 4. Mark Set the influence function with . , and press . or , and press or , and press Fig. 42 Primary sensor Description In this display, select the control parameter of Hydro MPC and the sensor to measure the value. Usually, the control parameter is the discharge pressure which is measured by a sensor fitted on the discharge manifold and connected to analog input AI1 of the CU 351. If another control parameter is selected, the sensor must be connected to AI3 (CU 351) which is then set to one of the chosen parameters listed below. Setting range · Discharge pressure (factory setting) · Differential pressure, external · Differential pressure, pump · Series 2000, differential pressure · External pressure · Differential pressure, inlet · Differential pressure, outlet · Flow rate · Series 2000, flow rate · Flow pipe temperature · Return pipe temperature · Differential temperature · Ambient temperature · Return pipe temperature, external · 0-100 % signal · Not used. TM03 8958 4807 Q-Pulse Id: TMS1594 Active: 18/04/2016 35 Page 473 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual From factory the discharge pressure sensor is connected to AI1 (CU 351). If one of the above parameters is selected, the sensor in question must be connected to AI3 (CU 351) and set in order to function as the primary sensor. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Primary sensor with or , and press . 4. Mark Go to setting of analog input with or , and press . Now the display Analog inputs (4.3.8) appears. Select the analog input (AI) for the primary sensor, and set the parameters for this sensor. Return to display Primary sensor (4.1.4) with . 5. Select the control parameter for the primary sensor with or , and press . Note If the primary parameter is discharge pressure, AI1 (CU 351) must be set to this parameter. If the primary parameter is external pressure or flow rate, AI3 (CU 351) must be set to this parameter. Factory setting The primary parameter is discharge pressure. The sensor is connected to AI1 (CU 351). 9.7.8 Clock program (4.1.6) 5. Mark operating mode Normal or Stop with or , and press . (If Stop is selected, point 7 is skipped.) 6. Mark Setpoint, closed loop with or pressure with or , and save with . Set the . 7. Mark Time (hours, minutes) with or . 8. Set the time with or , and save with . 9. Mark day of week on which the settings are to be activated with or , and press . 10.Mark Activated with or , and press . 11.Return with . 12.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 13.Repeat points 4 to 11 if several events are to be activated. Note: Up to ten events can be set. Factory setting The function is deactivated. 9.7.9 Proportional pressure (4.1.7) TM03 8959 4807 TM03 8990 4807 Fig. 43 Clock program Description With this function, it is possible to set setpoints and day and time for their activation. It is also possible to set day and time for stop of the Hydro MPC system. If the clock program is deactivated, the setpoint of the program will remain active. Setting range · Activation of the function. · Activation and setting of event. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Clock program with or , and press . 4. Mark event 1 with or , and press . Fig. 44 Proportional pressure Description The function can only be activated in pressure-controlled systems and automatically adapts the setpoint set to the current flow rate. The adaptation can be linear or square. See fig. 45. TM03 8960 4807 36 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 474 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Hset Pump curve Setpoint Resultant setpoint, linear Resultant setpoint, square Starting point of proportional pressure control (Influence at 0 flow = x % of Hset) Fig. 45 Proportional pressure The function has these purposes: · to compensate for pressure losses · to reduce the energy consumption · to increase the comfort for the user. Setting range · Activation of the function. · Selection of control mode. · Setting of setpoint influence. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Proportional pressure with or , and press . 4. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 5. Mark Adaptation, linear or square with press . or , and 6. Mark Influence at 0 flow with or or , and save with . . Set the value with Factory setting The function is deactivated. 9.7.10 S-system configuration (4.1.8) TM03 8524 1807 TM03 9205 3607 - TM03 9205 3607 Description The function makes it possible to invert the control of mainsoperated pumps (Hydro MPC-S). That is to set whether pumps are to be started or stopped depending on the current value. A start/stop band must be set in order to use this function. See fig. 47. Normal control: A pump is stopped when the current value becomes higher than Hset + start/stop band. And a pump is started when the current value becomes lower than Hset. See fig. 47. Inverse control: A pump is started when the current value becomes higher than Hset + start/stop band. And a pump is stopped when the current value becomes lower than Hset. See fig. 47. Normal control H [m] Inverse control H [m] Pump stops Pump starts Start/stop band Hset Pump starts Start/stop band Hset Pump stops Time [sec] Time [sec] Fig. 47 Normal and inverse control Setting range · Selection of configuration (normal or inverse control). · Setting of start/stop band. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark S-system configuration with . or , and press 4. Mark Inverse with or , and press . 5. Mark Start/stop band with or . Set the value with or , and save with . Factory setting Normal. 9.7.11 Pump cascade control (4.2) TM03 8961 4807 TM03 8962 4807 Fig. 46 S-system configuration Q-Pulse Id: TMS1594 Fig. 48 Pump cascade control Active: 18/04/2016 37 Page 475 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual In this menu section, it is possible to set the functions connected to pump cascade control. The following menus can be selected: · Min. time between start/stop · Max. number of starts/hour · Standby pumps · Forced pump changeover · Pump test run · Pilot pump · Pump stop attempt · Pump start and stop speed · Min. performance · Compensation for pump start-up time. 9.7.12 Min. time between start/stop (4.2.1) 9.7.13 Max. number of starts/hour (4.2.1) TM03 2367 4807 TM03 2367 4807 Fig. 49 Min. time between start/stop Description This function ensures a delay between the starting/stopping of one pump and the starting/stopping of another pump. The purpose is to prevent hunting when pumps start and stop continuously. Setting range From 1 to 3600 seconds. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or . 3. Mark Min. time between start/stop with press . 4. Mark Min. time between start/stop with press . 5. Set the required minimum time with or . , and press or , and or , and , and save with Factory setting Minimum time between start/stop of pumps: Hydro MPC-E and -EF: 1 second Other variants: 5 seconds Fig. 50 Max. number of starts/hour Description This function limits the number of pump starts and stops per hour for the complete system. It reduces noise emission and improves the comfort of booster systems with mains-operated pumps. Each time a pump starts or stops, the CU 351 calculates when the next pump is allowed to start/stop in order not to exceed the permissible number of starts per hour. The function always allows pumps to be started to meet the requirement, but pump stops will be delayed, if needed, in order not to exceed the permissible number of starts per hour. The time between pump starts must be between the minimum time between start/stop, see section 9.7.12, and 3600/n, n being the set number of starts per hour. Setting range 1 to 1000 starts per hour. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Max. number of starts/hour with . or , and press 4. Mark Max. number of starts/hour with or , and press . 5. Set the permissible number of starts per hour with and save with . or , Factory setting Hydro MPC-E and -EF: 200 starts per hour Other variants: 100 starts per hour Note This function has no influence on Stop function (4.3.1). 9.7.14 Standby pumps (4.2.3) 38 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 476 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Fig. 51 Standby pumps Description This function makes it possible to limit the maximum performance of the Hydro MPC, by selecting one or more pumps as standby pumps. If a three-pump system has one standby pump, maximum two pumps are allowed to be in operation at a time. If one of the two pumps in operation has a fault and is stopped, the standby pump will be started. The performance of the booster system is thus not reduced. The status as standby pump alternates between all pumps. Setting range The number of possible standby pumps in a Hydro MPC booster system is equal to the total number of pumps in the system minus 1. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Standby pumps with or , and press . 4. Select the number of standby pumps with save with . or , and Factory setting The number of standby pumps is set to 0, i.e. function is deactivated. 9.7.15 Forced pump changeover (4.2.4) TM03 2366 4807 Description This function ensures that the pumps run for the same number of operating hours. In certain applications, the requirement remains constant for long periods and does not require all pumps to run. In such situations, pump changeover does not take place naturally, and forced pump changeover may thus be required. Once every 24 hours, the CU 351 checks if any pump running has a larger number of operating hours than pumps that are stopped. If this is the case, the pump will be stopped and replaced by a pump with a lower number of operating hours. Setting range The function can be activated/deactivated. The hour of the day at which the changeover is to take place can be set. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Forced pump changeover with . or , and press 4. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 5. Mark Time for changeover with , and press . 6. Set the time with or , and save with . Factory setting The function is activated. The time is set to 03:00. 9.7.16 Pump test run (4.2.5) TM03 2365 4807 TM03 2364 4807 Fig. 52 Forced pump changeover Fig. 53 Pump test run Description This function is primarily used in situations where the forced pump changeover is deactivated, and/or if the Hydro MPC is set to operating mode Stop, for instance in a period when the system is not needed. In such situations, it is important to test the pumps regularly. The function ensures that · pumps do not seize up during a long standstill due to deposits from the pumped liquid. · the pumped liquid does not decay in the pump. · trapped air is removed from the pump. The pumps start automatically one by one and run for five seconds. Q-Pulse Id: TMS1594 Active: 18/04/2016 39 Page 477 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Note Pumps in the operating mode Manual are not included in the test run. If there is an alarm, the test run will not be carried out. Setting range · Not used. · Once every 24 hours. · Once every 48 hours. · Once a week. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . 3. Mark Pump test run with or 4. Select the interval with or . 5. Activate the function with . or , and press , and press . Factory setting Test runs are set to once every 24 hours. 9.7.17 Pilot pump (4.2.6) Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pilot pump with or , and press . 4. Mark Go to setting of digital output with press . or , and 5. Select a digital output with or , and press . 6. Mark Pilot pump control with . or , and save with 7. Return by pressing twice. 8. Mark Go to setting of digital input with press . or , and 9. Select a digital input or , and press . 10.Mark Pilot pump fault with or , and save with . Factory setting The function is deactivated. 9.7.18 Pump stop attempt (4.2.7) TM03 8963 4807 TM03 8964 4807 Fig. 54 Pilot pump Description The function controls a pilot pump via a digital output. The pilot pump takes over the operation from the main pumps in periods when the consumption is so small that the stop function of the main pumps is activated. See section 9.7.23 Stop function (4.3.1). Via a digital input, the operational state of the pilot pump is monitored, i.e. whether it is operational or in a fault condition. The purpose is to · save energy · reduce the number of operating hours of the main pumps. If the pilot pump cannot keep the pressure by itself, one or more main pumps are started. If only one main pump is started and runs on/off operation, the pilot pump remains cut in. If one or more main pumps run continuously, the pilot pump is cut out. Note If the setpoint of the main pumps is changed, the setpoint of the pilot pump must be changed too. Setting range · See section 9.7.31 Digital outputs (4.3.9). · See section 9.7.26 Digital inputs (4.3.7). Fig. 55 Pump stop attempt Description The function makes it possible to set automatic stop attempts of a pump when several pumps are running. It ensures that the optimum number of pumps is always running, in terms of energy consumption. At the same time, the purpose is to avoid disturbances in connection with automatic stop of pumps. Stop attempts can either take place with a fixed interval set under Interval between stop attempts or by self learning. If self learning is selected, the interval between stop attempts will be increased if repeated attempts to stop the pump fail. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pump stop attempt with or , and press . 4. Mark Self learning or Fixed interval with or , and press . 5. If Fixed interval is selected: 6. Mark Interval between stop attempts with or . 7. Set the interval with or , and save with . 8. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. Factory setting The function is activated. 40 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 478 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.19 Pump start and stop speed (4.2.8) Description The function controls the starting and stopping of pumps. There are two options: 1. Use calculated speed This function ensures that the optimum number of pumps is always running at a desired duty point, in terms of energy consumption. The CU 351 calculates the required number of pumps and their speed. This requires that the differential pressure of the pump is measured by a differential pressure sensor or separate pressure sensors on the inlet and discharge side. When calculated speed has been selected, the CU 351 ignores the percentages set. 2. Use fixed speed The pumps are started and stopped at speeds set by the user. 1. Use calculated speed Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pump start and stop speed with . or , and press 4. Mark Use fixed speed with or , and press . 5. Mark Start of next pump at: 1->2 with or , and press . 6. Set the speed as percentage with or , and save with . Set the other pumps in the same way. 7. Mark Instant pump stop at: 1->0 with . or , and press 8. Set the speed as percentage with or , and save with . Set the other pumps in the same way. Factory setting The function is set to calculated speed. 9.7.20 Min. performance (4.2.9) TM03 8966 4807 TM03 8967 4807 Fig. 56 Calculated pump start and stop speed Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or . 3. Mark Pump start and stop speed with . 4. Mark Use calculated speed with or , and press or , and press , and press . 2. Use fixed speed Fig. 58 Min. performance Description This function ensures circulation in a system. Note that the stop function, if activated, can influence this function. See section 9.7.23 Stop function (4.3.1). Examples: · If 0 or 1 pump has been selected as a minimum, the stop function can stop the pump if there is no or a very small consumption. · If two or more pumps have been selected as a minimum, the stop function is not active. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Min. performance with or , and press . 4. Set Number of pumps with or , and save with . 5. Mark Speed with or and save with . . Set the speed with or , Factory setting The number of pumps is set to 1. The speed in closed loop is set to 25 %. TM03 8965 4807 Fig. 57 Fixed pump start and stop speed Q-Pulse Id: TMS1594 Active: 18/04/2016 41 Page 479 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.21 Compensation for pump start-up time (4.2.10) The display makes it possible to open specific displays regarding: · Stop function (4.3.1) · Soft pressure build-up (4.3.3) · Digital inputs (4.3.7) · Analog inputs (4.3.8) · Digital outputs (4.3.9) · Emergency run (4.3.5) · Min., max. and user-defined duty (4.3.14) · Pump curve data (4.3.19) · Flow estimation (4.3.23) · Control source (4.3.20) · Fixed inlet pressure (4.3.22). 9.7.23 Stop function (4.3.1) TM03 8968 4807 Fig. 59 Compensation for pump start-up time Description The function is used for the system types -ES, -ED, -F and -EDF. The purpose is to avoid disturbances when a mains-operated pump with fixed speed is started. The function compensates for the time it takes a mains-operated pump to reach its full performance after start. The start-up time of the mains-operated pump must be known. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or , and press . 3. Mark Compensation for pump start-up time with or , and press . 4. Set the start-up time with or , and save with . Factory setting The start-up time is set to 0 seconds. 9.7.22 Secondary functions (4.3) Fig. 61 Stop function Description This function makes it possible to stop the last pump if there is no or a very small consumption. The purpose is to · save energy · prevent heating of shaft seal faces due to increased mechanical friction as a result of reduced cooling by the pumped liquid · prevent heating of the pumped liquid. The description of the stop function applies to all Hydro MPC booster systems with variable-speed pumps. Hydro MPC-S will have on/off control of all pumps as described in section 6.1 Examples of control variants. H TM03 2355 4807 TM03 8969 4807 TM03 1692 2705 Hset On/off band Fig. 60 Secondary functions Description Qmin Q Functions that are secondary in relation to the normal operation of the Hydro MPC booster system can be set in this display. On/off Normal operation control Secondary functions are functions that offer additional functionality. Fig. 62 On/off band 42 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 480 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual When the stop function is activated, the operation of Hydro MPC is continuously monitored to detect a low flow rate. When the CU 351 detects no or a low flow rate (Q < Qmin), it changes from constant-pressure operation to on/off control of the last pump in operation. Before stopping, the pump increases the pressure to a value corresponding to Hset + 0.5 x on/off band. The pump is restarted when the pressure is Hset 0.5 x on/off band. See fig. 63. [psi] Stop A B A: Normal operation B: Pressure boosting C: Stop C B C Start Stop = Hset + 0.5 x on/off band Start = Hset 0.5 x on/off band Time [sec] Fig. 63 On/off operation The flow rate is estimated by the CU 351 when the pump is in the stop period. As long as the flow rate is lower than Qmin, the pump will run on/off. If the flow rate is increased to above Qmin, the pump returns to normal operation, Hset. Hset is equal to the current setpoint. See section 9.4.4 Setpoint (1.2.2). Detection of low flow rate Low flow rate can be detected by means of · direct flow measurement with a flowmeter or flow switch · estimation of flow rate by measurement of current pressure and speed. If the booster system is not connected to a flowmeter or flow switch, the stop function will use the estimating function. If the detection of low flow rate is based on flow estimation, a diaphragm tank of a certain size and with a certain precharge pressure is required. Diaphragm tank size Pump type CR(E) 3 CR(E) 5 CR(E) 10 CR(E) 15 CR(E) 20 CR(E) 32 CR(E) 45 CR(E) 64 CR 90 Recommended diaphragm tank size [gallons] -E 4.4 4.4 10.2 34 34 44 86 132 - -ED 4.4 4.4 10.2 34 34 44 86 132 - -ES 4.4 4.4 10.2 34 34 44 86 132 - -EF 4.4 4.4 10.2 34 34 44 86 132 132 -EDF 4.4 4.4 10.2 34 34 44 86 132 132 -F 4.4 4.4 10.2 34 34 44 86 132 132 -S 20 34 62 211 211 317 528 1056 1056 Precharge pressure Hydro MPC-E, -ED, -ES, -EF, -EDF and -F: 0.7 x setpoint. Hydro MPC-S: 0.9 x setpoint. TM03 9292 4807 TM03 9966 4807 During each flow estimation (every 2 minutes), the estimating function will disturb the discharge pressure by ±10 % of the setpoint. If this disturbance is not acceptable, the stop function must be based on direct flow measurement with a flowmeter or flow switch. The minimum flow rate can be set, i.e. the flow rate at which the booster system changes to on/off control of the last pump in operation. If both a flowmeter and a flow switch are connected, the changeover to on/off control is determined by the unit first indicating low flow rate. Setting range On/off band: Min. flow rate: 5 to 30 % 2 to 50 % of the nominal flow rate (Qnom) of one of the pumps. (Can only be set if direct flow measurement by means of flowmeter has been selected.) Setting via control panel System without flow switch or flowmeter 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Stop function with or , and press . 4. Mark Activated with or , and press . The activation is indicated by a check mark in the box. 5. Mark On/off band with or . 6. Set the on/off band with or , and save with . 7. Mark Go to setting of flow stop parameters with and press . Now the display below is shown. or , Fig. 64 Stop parameters 8. Select one of the stop parameters with or , and save with . If Customised settings are selected, the parameters shown in fig. 65 must be set. See examples below. Q-Pulse Id: TMS1594 Active: 18/04/2016 43 Page 481 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1. Mark Go to setting of analog input with or , and press . Now the display Analog inputs (4.3.8) appears. 2. Select the analog input where the flowmeter is connected, and set up the input for the flowmeter by selecting Flow rate. 3. Return to Stop function by pressing twice. 4. Mark Stop limit with or . 5. Set the value with or , and save with . Factory setting The function is activated. On/off band: 25 % Min. flow rate: 30 % of the nominal flow rate of one pump 9.7.24 Soft pressure build-up (4.3.3) TM03 8957 4807 TM03 8970 4807 Fig. 65 Customised settings Note Rule of thumb: Speed reduction = 2 x delta pressure for gradient. Example 1: Increasing the stop limit, Qmin (high flow limit) · Increase the delta pressure for gradient. · Reduce the delta time for gradient (pump stopped). · Reduce the delta time for gradient (pump running). · Increase the speed reduction. Example of increased stop limit Parameter Delta pressure for gradient Delta time for gradient (pump stopped) Delta time for gradient (pump running) Speed reduction Value 6 % 1.5 sec 2.0 sec 10 % Example 2: Reducing the stop limit, Qmin (low flow limit) · Reduce the delta pressure for gradient. · Increase the delta time for gradient (pump stopped). · Increase the delta time for gradient (pump running). · Reduce the speed reduction. Example of reduced flow limit Parameter Delta pressure for gradient Delta time for gradient (pump stopped) Delta time for gradient (pump running) Speed reduction Value 3 % 15.0 sec 25.0 sec 6 % Note The stop limit depends on the tank size. System with flow switch Make the following additional settings: 1. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. 2. Select the digital input where the flow switch is connected with or , and press . 3. Mark Flow switch with or , press and return with . Note An open contact indicates low flow. System with flowmeter Make the following additional settings: Fig. 66 Soft pressure build-up Description The function ensures a smooth start-up of systems with for instance empty pipes. Start-up takes place in two phases. See fig. 67. 1. Filling phase. The pipework is slowly filled with water. When the pressure sensor of the system detects that the pipework has been filled, phase two begins. 2. Pressure build-up phase. The system pressure is increased until the setpoint is reached. The pressure build-up takes place over a ramp time. If the setpoint is not reached within a given time, a warning or an alarm can be given, and the pumps can be stopped at the same time. H [psi] 1. Filling phase 2. Pressure build-up phase Filling time Time [sec] Ramp time Fig. 67 Filling and pressure build-up phases 44 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 482 of 1068 TM03 9037 3207 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Setting range · Activation of the function. · Setting of pump speed. · Setting of number of pumps. · Setting of filling pressure. · Setting of maximum filling time. · Setting of warning or alarm + stop. · Setting of ramp time for the pressure build-up phase. Setting via control panel 1. Mark the Settings menu with 2. Mark Secondary functions with or , and press . 3. Mark Soft pressure build-up with . or , and press 4. Mark Speed with or . 5. Set the value with or , and save with . 6. Mark Number of pumps with or . 7. Set the value with or , and save with . 8. Mark Filling pressure with or . 9. Set the value with or , and save with . 10.Mark Max. time with or . 11.Set the value with or , and save with . 12.Mark Warning or Alarm + stop with . or , and press 13.Mark Ramp time with or . 14.Set the value with or , and save with . 15.Mark Activated, and press . Factory setting The function is deactivated. 9.7.25 Emergency run (4.3.5) 2. Mark Secondary functions with or , and press . 3. Mark Emergency run with or , and press . 4. Mark Go to setting of digital input with press . or , and 5. Select a digital input with or , and press . 6. Mark Emergency run with or , and save with . 7. Return by pressing twice. 8. Mark Go to setting of digital output with press . or , and 9. Select a digital output with or , and press . 10.Mark Emergency run with or , and save with . 11.Return by pressing twice. 12.Mark Setpoint, emergency run with or . 13.Set the value with or , and save with . Note When this function has been set as described above, it can also be activated via the display System operating mode (2.1.1). 9.7.26 Digital inputs (4.3.7) TM03 8971 4807 TM03 2359 4807 Fig. 68 Emergency run Description When this function has been activated, the pumps will keep running regardless of warnings or alarms. The pumps will run according to a setpoint set specifically for this function. In case of sensor fault, both main and standby Caution pumps will run at 100 % speed! Setting range · Setting of digital input (9.7.26 Digital inputs (4.3.7)). · Setting of digital output (9.7.31 Digital outputs (4.3.9)). · Setting of setpoint for emergency run. Setting via control panel 1. Mark the Settings menu with Fig. 69 Digital inputs Description In this menu, the digital inputs of the CU 351 can be set. Each input, except DI1, can be activated and related to a certain function. As standard, the Hydro MPC has three digital inputs. If the Hydro MPC incorporates an IO 351B module (option), the number of digital inputs is 12. In the display, all digital inputs are shown so that their physical position in the Hydro MPC can be identified. Example DI1 (IO 351-41), [10]: DI1: (IO 351-41): [10]: Digital input No 1 IO 351, GENIbus number 41 Terminal No 10 For further information on the connection of various digital inputs, see the wiring diagram supplied with the control cabinet. Setting range The digital input to be set is selected in the display Digital inputs (4.3.7). Note DI1 (CU 351) cannot be selected. Setting via control panel 1. Mark the Settings menu with . Q-Pulse Id: TMS1594 Active: 18/04/2016 45 Page 483 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2. Mark Secondary functions with or , and press . 3. Mark Digital inputs or , and press . 4. Select the digital input with or , and press . 9.7.27 Functions of digital inputs (4.3.7.1) Fig. 70 Functions of digital inputs Description In the displays 4.3.7.1, a function can be related to the digital inputs. Setting range It is possible to select one function in each display: Function Contact activated Not used Min. duty = Operating mode Min. Max. duty User-defined duty External fault = Operating mode Max. = Operating mode Userdefined = External fault Dry-running protection Flow switch Reset of alarm Emergency run Pilot pump fault = Water shortage = Flow rate > Set switch value = Reset alarms = Operating mode Emergency run = Pilot pump fault Alternative setpoint 2 = Setpoint 2 selected Alternative setpoint 3 = Setpoint 3 selected Alternative setpoint 4 = Setpoint 4 selected Alternative setpoint 5 = Setpoint 5 selected Alternative setpoint 6 = Setpoint 6 selected Alternative setpoint 7 = Setpoint 7 selected See the relevant sections for further information about the functions. Generally, a closed contact activates the function selected. TM03 8972 4807 TM03 2356 4807 Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Digital inputs with or , and press . 4. Select the digital input with or , and press . 5. Select the desired function with or , and activate it with . The activation is indicated by a check mark in the box. Factory setting Digital input Function DI1 (CU 351) [10] DI2 (CU 351) [12] External start/stop. Open contact = stop. Note: Input No 1 cannot be changed. Monitoring of water shortage (dry-running protection). Open contact = water shortage (if the Hydro MPC is supplied with this option). Note Monitoring of water shortage requires a pressure switch connected to the Hydro MPC. 9.7.28 Analog inputs (4.3.8) Fig. 71 Analog inputs Description In this display, the analog inputs of the Hydro MPC can be set. Each input can be activated and related to a certain function. As standard, the Hydro MPC has three analog inputs. If the Hydro MPC incorporates an IO 351B module (option), the number of analog inputs is 5. In the display, all analog inputs are shown so that their physical position in the Hydro MPC can be identified. A redundant primary sensor can be fitted as back-up for the primary sensor in order to increase reliability and prevent stop of operation. Note If two sensors are to be redundant, each must have a separate analog input. Example AI1 (CU 351) [51]: AI1: (CU 351): [51]: Analog input No 1 CU 351 Terminal No 51 46 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 484 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Setting range In the display Analog inputs (4.3.8), the analog input to be set is selected. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) Factory setting Analog input Function AI1 (CU 351) [51] AI2 (CU 351) [54] AI3 (CU 351) [57] Discharge pressure Tank precharge pressure (if Hydro MPC is supplied with measurement of tank precharge pressure) Redundant primary sensor (if Hydro MPC is supplied with this option) 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) TM03 2357 4807 TM03 8973 4807 Fig. 72 Analog inputs Description In the displays 4.3.8.1 to 4.3.8.7, analog inputs can be set. Each display is divided into three parts: · Setting of input signal, for instance 4-20 mA · Measured input value, for instance discharge pressure · Measuring range of the sensor/signal transmitter, for instance 0-16 bar. Setting range It is possible to set the following parameters in each display: · Not used · Range of input signal, 0-20 mA, 4-20 mA, 0-10 V · Measured input value · Sensor range. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 5. Mark the setting of the analog input with or , and activate it with . The activation is indicated by a check mark in the box. Note If an analog input is deactivated, the display will only show the top part, i.e. the setting of the analog input. If the input is activated, the middle part, "Measured input value", is shown. This makes it possible to relate a function to the analog input in another display. When the analog input has been related to a function, CU 351 will return to the display for setting of analog inputs. Fig. 73 Analog inputs and measured value Description In the display Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1), a function can be related to the individual analog inputs. Setting range It is possible to select one function per analog input. · Not used · 0-100 % signal · Inlet pressure · Discharge pressure · External pressure · Differential pressure, pump · Flow rate · Tank level, discharge side · Tank level, suction side · System pressure · Differential pressure, external · Tank precharge pressure · Differential pressure, inlet · Differential pressure, outlet · Return pipe temperature, external · Flow pipe temperature · Return pipe temperature · Differential temperature · Ambient temperature · Power, pump 1 to 6 · Power, VFD. Q-Pulse Id: TMS1594 Active: 18/04/2016 47 Page 485 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 5. Set the range of the analog input with or . The activation is indicated by a check mark. , and press 6. Mark Measured input value with or , and press . Now the display 4.3.8.1.1 appears. 7. Select the input with or , and press . 8. Press to return to display 4.3.8.1. 9. Set the minimum sensor value with . or , and save with 10.Set the maximum sensor value with . or , and save with 9.7.31 Digital outputs (4.3.9) Fig. 74 Digital outputs Description In this display, the digital relay outputs of the Hydro MPC can be set. Each output can be activated and related to a certain function. As standard, the Hydro MPC has two digital outputs. If the Hydro MPC incorporates an IO 351B module (option), the number of digital outputs is 9. In the display, all digital outputs are shown so that their physical position in the Hydro MPC can be identified. Example DO1 (IO 351-41) [71]: DO1 (IO 351-41) [71] Digital output No 1 IO 351B, GENIbus number 41 Terminal No 71 For further information on the connection of various digital outputs, see the wiring diagram supplied with the CU 351. Setting range In the display Digital outputs (4.3.9), the digital output to be used is selected. TM03 2333 4807 TM03 8974 4807 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) Fig. 75 Functions of digital outputs Description In the displays Functions of digital outputs (4.3.9.1 to 4.3.9.16), a function can be related to the individual outputs. Setting range It is possible to select one function in each display: · No function · Operation, system · Alarm, system · Warning, system · Ready, system · Water shortage · Min. pressure · Max. pressure · Emergency run · Pilot pump control · Pressure relief valve · Operation, pump 1 to 6 · Alarm, pump 1 to 6 · Alarm, limit 1 exceeded · Warning, limit 1 exceeded · Alarm, limit 2 exceeded · Warning, limit 2 exceeded. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Digital outputs with or , and press . 4. Select the digital output with or , and press . 5. Mark the desired function with or , and activate it with . The activation is indicated by a check mark in the box. Factory setting Digital output DO1 (CU 351) [71] DO2 (CU 351) [74] Function Alarm, system Operation, system 48 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 486 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.33 Min., max. and user-defined duty (4.3.14) TM03 2351 4807 Fig. 76 Min., max. and user-defined duty Description Hydro MPC is usually controlled in a closed loop to maintain a discharge pressure. In certain periods, it may be necessary to let the booster system run in open loop at a set pump performance. Setting range The CU 351 makes it possible to change between three operating modes: 1. Min. duty (4.3.14.1). 2. Max. duty (4.3.14.2). 3. User-defined duty (4.3.14.3). Note For each of these modes, the number of operating pumps and the pump performance (speed) can be set. 9.7.34 Min. duty (4.3.14.1) TM03 2354 4807 Fig. 77 Min. duty Description In all booster systems apart from Hydro MPC-S, minimum duty is only possible for variable-speed pumps. In Hydro MPC-S systems, only the number of pumps running at 100 % speed can be set. Setting range · Number of pumps in operation. · Speed as percentage (25 to 100 %) for variable-speed pumps. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark Min. duty with or , and press . 5. Mark Number of pumps in operation, min. duty with or . 6. Set the number with or , and save with . 7. Mark Speed with or . 8. Set the value with or , and save with . Factory setting Number of pumps in operation during min. duty: 1 Speed as percentage for variable-speed pumps: 70 9.7.35 Max. duty (4.3.14.2) TM03 2353 4807 Fig. 78 Max. duty Description The function makes it possible for a set number of pumps to run at maximum performance when the function is activated. Setting range In this display, the number of pumps to run in the operating mode Max. can be set. All pumps run at 100 % speed. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark Max. duty with or , and press . 5. Mark Number of pumps in operation at 100 % speed, max. duty with or . 6. Set the number with or , and save with . Factory setting Number of pumps in operation during max. duty: All pumps (except standby pumps) Q-Pulse Id: TMS1594 Active: 18/04/2016 49 Page 487 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.36 User-defined duty (4.3.14.3) 9.7.37 Pump curve data (4.3.19) TM03 2352 4807 TM03 8975 4807 Fig. 79 User-defined duty Description In this display, it is possible to set a user-defined performance, typically a performance between min. and max. duty. The function makes it possible to set a pump performance by selecting the number of pumps to run and the speed of variablespeed pumps. This function primarily selects the variable-speed pumps. If the number of selected pumps exceeds the number of variable-speed pumps, mains-operated pumps are started too. Setting range · Number of pumps in operation. · Speed as percentage for variable-speed pumps. Note: In Hydro MPC booster systems with only variable-speed pumps, the speed can be set between 25 and 100 %; in booster systems with both variable-speed pumps and mainsoperated pumps the speed can be set between 70 and 100 %. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark User-defined duty with or , and press . 5. Mark Number of pumps in operation, user-defined duty with or . 6. Set the number with or , and save with . 7. Mark Speed with or . 8. Set the value with or , and save with . Factory setting The function is not activated, as the following has been set: Number of pumps in operation during user-defined duty: 0 Fig. 80 Pump curve data Description The CU 351 has a number of functions using these pump data: · Nominal flow rate, Qnom, in m3/h · Nominal head, Hnom, in metres · Max. head, Hmax, in metres · Max. flow rate, Qmax, in m3/h · Power, Q0, 100 % speed, in kW · Power, Q0, 50 % speed, in kW · Nominal power, Pnom, in kW. Note Grundfos can supply hydraulic data for CR, CRI, CRE and CRIE pumps where GSC files can be downloaded directly to the CU 351. Note The electrical data, "Power, Q0, 100 % speed" and "Power, Q0, 50 % speed" must be entered manually. For Grundfos E-pumps, the data of input power (P1) must be entered. The data are read by means of the pump performance curves which can be found in WebCAPS on Grundfos' homepage, www.grundfos.com. See examples in figs 81 to 84. If WebCAPS is not accessible, try to bring a pump into the three duty points: Power, Q0, 100 % speed, Power, Q0, 50 % speed and Nominal power, Pnom. Read the power values in displays 1.3 to 1.8, depending on the pump. See section 9.4.8 Pump 1...6 (1.3 to 1.8). Hmax Hnom Nominal duty point TM03 9993 4807 50 Q-Pulse Id: TMS1594 Qnom Qmax Fig. 81 Reading of Qnom, Hnom, Hmax and Qmax (WebCAPS) Active: 18/04/2016 Page 488 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Duty point, Q0, 100 % speed Power, Q0, 100 % speed Fig. 82 Reading of Power, Q0, 100 % speed (WebCAPS) TM03 9994 4807 Note Qnom and Hnom are the rated duty point of the pumps and usually the duty point with the highest efficiency. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Pump curve data with or , and press . 4. Mark Nominal flow rate Qnom with or . 5. Set the value with or , and save with . 6. Mark Nominal head Hnom with or . 7. Set the value with or , and save with . 8. Mark Max. head Hmax with or . 9. Set the value with or , and save with . 10.Mark Max. flow rate Qmax with or . 11.Set the value with or , and save with . 12.Mark Power, Q0, 100 % speed with or . 13.Set the value with or , and save with . 14.Mark Power, Q0, 50 % speed with or . 15.Set the value with or , and save with . 16.Mark Nominal power Pnom with or . 17.Set the value with or , and save with . 9.7.38 Control source (4.3.20) Duty point, Q0, 50 % speed TM03 9995 4807 Power, Q0, 50 % speed TM03 2342 4807 Fig. 83 Reading of Power, Q0, 50 % speed (WebCAPS) Duty point, Nominal power, Pnom Nominal power, Pnom Fig. 84 Reading of Nominal power, Pnom (WebCAPS) TM03 9996 4807 Fig. 85 Control source Description Hydro MPC can be remote-controlled via an external bus connection (option). See section 9.8.2 GENIbus. Control of the Hydro MPC can also take place via the bus connection. For further information, see section 9.8 Data communication. In this display, the control source, CU 351 or the external bus connection, is selected. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Control source with or , and press . 4. Select the desired control source with with . or , and save Factory setting The control source is CU 351. Q-Pulse Id: TMS1594 Active: 18/04/2016 51 Page 489 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.39 Fixed inlet pressure (4.3.22) TM03 8975 4807 Fig. 86 Fixed inlet pressure Description If the Hydro MPC has a fixed inlet pressure, it can be entered in this display so that the CU 351 can optimise the performance and control of the booster system. Setting range A fixed inlet pressure can be set, and the function can be activated/deactivated. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Fixed inlet pressure with or , and press . 4. Set the inlet pressure with or , and save with . 5. Mark Activated with or , and press . The activation is indicated by a check mark in the box. Factory setting The function is deactivated. 9.7.40 Flow estimation (4.3.23) The loss is caused by non-return valves and pipe bends. To improve the flow estimation of the system, it is necessary to compensate for the difference between the measured and the actual differential pressure across the pump. This is done by entering the head loss in non-return valves and pipe bends at the rated flow rate of one pump. Setting range · 2nd order QH polynomial · 5th order QH polynomial · Power polynomial, QP · Head loss. Note It is possible to select several curve types, as the CU 351 makes a priority based on the data available. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Flow estimation with or , and press . 4. Select the curve type by marking one of the lines at the selection box with or , and press . Factory setting All polynomials are selected. 9.7.41 Monitoring functions (4.4) TM03 8978 4807 Fig. 87 Flow estimation Description As described in section 9.7.37 Pump curve data (4.3.19), the CU 351 can optimise operation according to performance curves and motor data. In this display, curve types are selected which the CU 351 will use for the optimisation if they are available. At large flow rates, there may be a considerable head loss between the pump discharge flange and the pressure sensor. TM03 8977 4807 Fig. 88 Monitoring functions Description Hydro MPC has a series of functions that constantly monitor the operation of the booster system. The primary purpose of the monitoring functions is to ensure that faults do not damage pumps or the system. Setting range The following functions can be selected: · Dry-running protection (4.4.1) · Min. pressure (4.4.2) · Max. pressure (4.4.3) · External fault (4.4.4) · Limit 1 and 2 exceeded (4.4.5 and 4.4.6) · Pumps outside duty range (4.4.7) · Pressure relief (4.4.8). Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Select the function with or , and press . 52 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 490 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.42 Dry-running protection (4.4.1) 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1) TM03 2320 4807 TM03 2329 4807 Fig. 89 Dry-running protection Description Dry-running protection is one of the most important monitoring functions, as bearings and shaft seal may be damaged if the pumps run dry. Grundfos thus always recommends dry-running protection in connection with Hydro MPC booster systems. The function is based on monitoring of the inlet pressure or the level in a possible tank or pit on the suction side. Level switches, pressure switches or analog sensors signalling water shortage at a set level can be used. There are three different methods for detection of water shortage: · Pressure switch on suction manifold or float switch/electrode relay in the supply tank. See section 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1). · Measurement of inlet pressure in the suction manifold by means of an analog pressure transmitter. See section 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2). · Measurement of level in the supply tank by means of an analog level transmitter. See section 9.7.45 Dry-running protection with level transmitter (4.4.1.3). Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Select the method with or , and press . Fig. 90 Dry-running protection with pressure/level switch Description Dry-running protection can take place by means of a pressure switch on the suction manifold or a level switch in a tank on the suction side. When the contact is open, the CU 351 will register water shortage after a time delay of approx. 5 sec. It is possible to set whether the indication is to be just a warning or an alarm stopping the pumps. In the display, it is possible to set whether restart and reset of the alarm is to be automatic or manual. Setting range · Selection of digital input for the function. · Reaction in case of water shortage: Warning or alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Pressure/level switch with or , and press . 5. Mark Go to setting of digital input, and press . Now the display Digital inputs (4.3.7) appears. Set the input to dryrunning protection. Return with . 6. Mark Warning or Alarm + stop with with . or , and save 7. Mark Manual or Auto with or , and save with . Factory setting If the booster system is equipped with a pressure switch for dryrunning protection, it is set to alarm + stop in case of water shortage. Restart: Manual. Q-Pulse Id: TMS1594 Active: 18/04/2016 53 Page 491 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2) 9.7.45 Dry-running protection with level transmitter (4.4.1.3) TM03 8979 4807 TM03 8980 4807 Fig. 91 Dry-running protection with pressure transmitter Description Dry-running protection can take place by means of a pressure transmitter measuring the inlet pressure. It is possible to set two levels of inlet pressure: Warning and alarm + stop. In the display, it is possible to set whether restart and reset of the alarm is to be automatic or manual. Setting range · Selection of analog input for the function. · Activation of the function. · Inlet pressure level for warning. · Inlet pressure level for alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Measurement, inlet pressure with press . or , and 5. Mark Go to setting of analog input, and press . Now the display Analog inputs (4.3.8) appears. Set the input to Inlet pressure, and save with . Return with . 6. Mark Activated with or , and press . 7. Mark Warning with or . Set the level with and save with . or , 8. Mark Alarm + stop with or . Set the level with or , and save with . 9. Mark Manual or Auto with or , and save with . Note If one of the levels is not required, the level value must be the minimum value of the inlet pressure transmitter. This deactivates the function. Factory setting If the booster system is supplied with a pressure transmitter on the suction side, the transmitter has been set. The warning level is 0.5 bar and the alarm level 0.2 bar. The function is activated. Restart: Manual. Fig. 92 Dry-running protection with level transmitter Description Dry-running protection can take place by means of a level transmitter measuring the level in a tank on the suction side. It is possible to set two levels: Warning and alarm + stop. In the display, it is possible to set whether restart and reset of alarms is to be automatic or manual. Setting range · Selection of analog input for the function. · Activation of the function. · Tank level for warning. · Tank level for alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Measurement, tank level with . or , and press 5. Mark Go to setting of analog input, and press . Now the display Analog inputs (4.3.8) appears. Set the input to Tank level, suction side. Return with . 6. Mark Activated with or , and press . 7. Mark Warning with or . Set the level with and save with . or , 8. Mark Alarm + stop with or . Set the level with or , and save with . 9. Mark Manual or Auto with or , and save with . Factory setting The function is deactivated. 54 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 492 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.46 Min. pressure (4.4.2) Factory setting The function is deactivated. 9.7.47 Max. pressure (4.4.3) TM03 8981 4807 TM03 8982 4807 Fig. 93 Min. pressure Description The discharge pressure can be monitored so that the CU 351 can react if the pressure becomes lower than a set minimum level for an adjustable time. The minimum pressure can be monitored if a fault indication is required in situations where the discharge pressure becomes lower than the set minimum pressure. It is possible to set whether the indication is to be just a warning or an alarm stopping the pumps. This may be desirable if Hydro MPC is used for an irrigation system where a very low discharge pressure may be due to pipe fracture and thus an extraordinarily high consumption and a very low counterpressure. In such situations, it is desirable that the booster system stops and indicates alarm. This situation will require a manual reset of alarms. It is possible to set a start-up delay ensuring that the Hydro MPC can build up pressure before the function is activated. It is also possible to set a time delay, i.e. for how long time the discharge pressure may be lower than the set minimum pressure before the alarm is activated. Setting range · Activation of the function. · Minimum pressure level within the range of the primary sensor. · Activation of stop when the pressure falls below the minimum pressure. · Time delay at start-up. · Time delay during operation. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Min. pressure with or , and press . 4. Mark Activated with or deactivate the function. , and press to activate/ 5. Mark Min. pressure with or or , and save with . . Set the pressure with 6. Mark Stop at min. pressure with or to activate/deactivate the function. , and press 7. Mark Time delay of function at start-up with the time with or , and save with . or . Set 8. Mark Time delay of function during operation with or . Set the time with or , and save with . Fig. 94 Max. pressure Description The discharge pressure can be monitored so that the CU 351 can react if the pressure becomes higher than a set maximum level. In certain installations, a too high discharge pressure may cause damage. It may therefore be necessary to stop all pumps for a short period if the pressure is too high. It is possible to set whether the Hydro MPC is to restart automatically after the pressure has dropped below the maximum level, or if the system must be reset manually. Restart will be delayed by an adjustable time. See section 9.7.12 Min. time between start/stop (4.2.1). Setting range · Activation of the function. · Maximum pressure level within the range of the primary sensor. · Manual or automatic restart after fault. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Max. pressure with or , and press . 4. Mark Activated with or deactivate the function. , and press to activate/ 5. Mark Max. pressure with or or , and save with . . Set the pressure with 6. Mark Manual or Auto with or . Activate the function with . Factory setting The function is deactivated. Q-Pulse Id: TMS1594 Active: 18/04/2016 55 Page 493 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.48 External fault (4.4.4) 9.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) TM03 2313 4807 TM03 8983 4807 Fig. 95 External fault Description The function is used when the CU 351 is to be able to receive a fault signal from an external contact. In case of external fault, the CU 351 indicates warning or alarm. In case of alarm, the booster system changes to another manual operating mode, for instance Stop. Setting range · Selection of digital input for the function. · Setting of time delay from closing of the contact until the CU 351 reacts. · Reaction in case of external fault: Warning or alarm and change of operating mode. · Restart after alarm: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark External fault with or , and press . 4. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. Set the input to External fault. Return with . 5. Mark Time delay, fault indication with or time with or , and save with . . Set the 6. Mark Warning with or if only a warning is required in case of external fault. Activate the function with . 7. Select operating mode with or if the booster system is to give alarm and change operating mode in case of external fault. Activate the function with . 8. Mark Manual or Auto with with . or . Activate the function Factory setting The function is deactivated. If the function is activated, the following values have been set from factory: · Time delay: 5 seconds. · Operating mode in case of alarm: Stop. · Restart: Manual. Fig. 96 Limit 1 exceeded Description With this function, the CU 351 can monitor set limits of analog values. It will react if the values exceed the limits. Each limit can be set as a maximum or minimum value. For each of the monitored values, a warning limit and an alarm limit must be defined. The function makes it possible to monitor two different locations in a pump system at the same time. For instance the pressure at a consumer and the pump discharge pressure. This ensures that the discharge pressure does not reach a critical value. If the value exceeds the warning limit, a warning is given. If the value exceeds the alarm limit, the pumps are stopped. A delay can be set between the detection of an exceeded limit and the activation of a warning or an alarm. A delay can also be set for resetting a warning or an alarm. A warning can be reset automatically or manually. It is possible to set whether the system is to restart automatically after an alarm, or if the alarm must be reset manually. Restart can be delayed by an adjustable time. It is also possible to set a startup delay ensuring that the system reaches a steady state before the function becomes active. Setting range · Activation of an analog input for the function. · Selection of the measured value to be monitored. · Setting of limit type (min./max.). · Setting of warning limit. · Setting of alarm limit. Setting via control panel Note Analog inputs must be correctly set before the function is activated. See section 9.7.28 Analog inputs (4.3.8). 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press 3. Mark Limit 1 exceeded or Limit 2 exceeded with and press . or , 4. Mark Go to setting of analog input with press . or , and 5. Select the analog input with or , and press . 6. Mark the setting of the analog input with or , and activate it with . The activation is indicated by a check mark in the box. 56 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 494 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7. Mark Measured value with or the display 4.3.8.1.1 appears. , and press . Now 8. Select the input with or , and press . 9. Press to return to display 4.3.8.1. 10.Set the minimum sensor value with . or , and save with 11.Set the maximum sensor value with . or , and save with 12.Return by pressing twice. 13.Mark Measured value to be monitored with or ., and press . Select the input with or , and press . 14.Return with . 15.Mark Min. limit or Max. limit with . or ., and press 16.Mark Set delays with or , and press 17.Mark Time delay of function at start-up with the time with or , and save with . or . Set 18.Mark Time delay of function during operation with or . Set the time with or , and save with . 19.Mark Time delay of function at reset with or the time with or , and save with . . Set 20.Return with . 21.Mark Set warning limit with or , and press . 22.Mark Activated with or , and press . 23.Mark Warning limit with or or , and save with . . Set the value with 24.Mark Manual or Auto with with . or . Activate the function 25.Return with . 26.Mark Set alarm limit with or , and press . 27.Mark Activated with or , and press . 28.Mark Alarm limit with or . Set the value with or , and save with . 29.Mark Manual or Auto with with . or . Activate the function 30.Return with . 31.Mark Activated with the function. or , and press to activate Factory setting The function is deactivated. 9.7.50 Pumps outside duty range (4.4.7) Description The function gives a warning if the duty point of the pumps moves outside the defined range. For instance, if the inlet pressure becomes lower than a minimum permissible value, thus causing a risk of cavitation for some pump types. The warning is given with a set time delay. It is possible to set whether the warning is to be reset automatically or manually when the duty point comes within the defined duty range. It is also possible to set a relay output to be activated when the warning is given, and to be deactivated when the warning is reset. This function requires that the discharge pressure and the inlet pressure (either measured or configured) or the differential pressure of the pumps is monitored, and that CU 351 contains valid pump data from either a GSC file or from manual input. See section 9.7.37 Pump curve data (4.3.19). Setting range · Activation of the function. · Setting of manual or automatic reset. · Setting of warning delay. Setting via control panel 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press . 3. Mark Pumps outside duty range with . or , and press 4. Mark Manual or Auto with function with . or , and activate the 5. Mark Warning delay with or . Set the time with or , and save with . 6. Mark Activated with the function. or , and press to activate Factory setting The function is deactivated. 9.7.51 Pressure relief (4.4.8) TM03 8984 4807 TM03 8986 4807 Fig. 98 Pressure relief Fig. 97 Pumps outside duty range Q-Pulse Id: TMS1594 Active: 18/04/2016 57 Page 495 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Description The purpose of the function is to reduce the pressure in the pipework by opening a solenoid valve if it exceeds a set limit. If the pressure is not reduced within a given time, the solenoid valve will be closed, and a warning can be given. P [psi] 1: Solenoid valve opens. 2: Solenoid valve closes. 3: Solenoid valve opens. 4: Warning is activated. 5: Solenoid valve closes, and warning is reset. 1 23 45 Valve opening pressure Band Valve opening pressure minus band Fig. 99 Pressure relief Warning Time [sec] delay Setting range · Setting of digital output. · Setting of pressure to be monitored. · Setting of valve opening pressure. · Setting of band for valve opening pressure. · Setting of warning or alarm. · Activation of the function. Setting via control panel 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press . 3. Mark Pressure relief with or , and press . 4. Mark Go to setting of digital output with press . or , and 5. Select a digital output with or , and press . 6. Mark Pressure relief with or , and save with . 7. Return by pressing twice. 8. Mark Pressure to be monitored with . or , and press 9. Mark Discharge pressure, System pressure or External pressure with or , and save with . 10.Return with . 11.Mark Valve opening pressure with or . Set the pressure with or , and save with . 12.Mark Band, valve opening pressure with or pressure with or , and save with . . Set the 13.Mark Warning, Deactivated or Activated with and press . or , 14.Mark Delay with or . Set the time with or , and save with . (Only to be set if warning has been activated.) 15.Mark Activated with function. or , and press activate the Factory setting The function is deactivated. TM03 9206 3607 TM03 2295 4807 9.7.52 Functions, CU 351 (4.5) Fig. 100 Functions, CU 351 Description In this submenu, it is possible to make the basic settings of the CU 351. CU 351 comes with most of these settings, or they are made at start-up and normally not to be changed. The service language, English, can be activated for service purposes. If no buttons are touched for 15 minutes, the display will return to the language selected at start-up or to the language set in section 9.7.53 Display language (4.5.1). Note If the service language is selected, the symbol will be shown to the right of the top line of all displays. Setting range · Activation of service language, British English. · Re-activation of start-up wizard. (After start-up, the wizard is inactive.) · Selection of display language. · Selection of display units. · Setting date and time. · Selection of password for the menus Operation and Settings. · Setting of Ethernet communication. · Setting of GENIbus number. · Reading of software status. 9.7.53 Display language (4.5.1) TM03 8987 4807 Fig. 101 Display language 58 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 496 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Description Here the language for the CU 351 display is selected. Setting range · British English · German · Danish · Spanish · Finnish · French · Greek · Italian · Dutch · Polish · Portuguese · Russian · Swedish · Chinese · Korean · Japanese · Czech · Turkish. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Display language with or , and press . 4. Select language with or , and save with . Factory setting The display language is English. It can be changed at start-up. 9.7.54 Display units (4.5.2) Setting range Parameter Basic setting Possible units SI US Pressure Differential pressure Head Level Flow rate Volume Specific energy Temperature Differential temperature Power Energy bar psi kPa, MPa, mbar, bar, m, psi m psi kPa, MPa, mbar, bar, m, psi m ft m, cm, ft, in m ft m, cm, ft, in m3/h gpm m3/s, m3/h, l/s, gpm, yd3/s, yd3/min, yd3/h m3 gal l, m3, gal, yd3 kWh/m3, Wh/gal, kWh/m3 Wh/gal Wh/kgal, BTU/gal, HPh/gal °C °F K, °C, °F K KK kW HP W, kW, MW, HP kWh kWh kWh, MWh, BTU, HPh Note If units are changed from SI to US or vice versa, all individually set parameters will be changed to the basic setting in question. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Units with or , and press . 4. Select the unit with or , and save with . A check mark shows that the unit has been selected. 5. Select the measuring parameter with or , and press to open the display for the measuring parameter. See the example. TM03 8988 4807 TM03 2310 4807 Fig. 102 Display units Description In this display, it is possible to select units for the various parameters. As basic setting, it is possible to select between SI and US units. It is also possible to select other units for the individual parameters. Fig. 103 Example of selection of display units 6. Select the unit with or , and save with . A check mark shows that the unit has been selected. Factory setting CU 351 has been set to US units from factory. Q-Pulse Id: TMS1594 Active: 18/04/2016 59 Page 497 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.7.55 Date and time (4.5.3) 9.7.56 Passwords (4.5.4) TM03 8989 4807 TM03 2899 4807 Fig. 104 Date and time Description In this display, date and time are set as well as how they are to be shown in the display. The clock has a built-in rechargeable voltage supply which can supply the clock for up to 20 days if the voltage supply to the Hydro MPC is interrupted. If the clock is without voltage for more than 20 days, it must be set again. Setting range The date can be set as day, month and year. The time can be set as a 24-hour clock showing hours and minutes. There are three formats. Examples of format 2005-09-27 13:49 27-09-2005 13:49 9/27/2005 1:49pm It is also possible to select if Sunday or Monday is to be the first day of week. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Date and time with or , and press . 4. Mark Day, Month and Year with or , and set the date with or . Save with . 5. Mark Hours and Minutes with or with or . Save with . , and set the time 6. Select the format with or , and save with . 7. Mark First day of week, Sunday or Monday with or , and save with Factory setting Local time. Note If the booster has been without voltage for more than 20 days since it left the factory, the clock may have returned to the original setting: 01-012005 0:00. Date and time may have been changed during the setting of Hydro MPC. There is no automatic changeover to/from daylight-saving time. Fig. 105 Passwords Description In this display it is possible to limit the access to the Operation and Settings menus by means of a password. If the access is limited, it is not possible to view or set any parameters in the menus. The password must consist of four digits and may be used for both menus. Note If you have forgotten the password(s), contact Grundfos. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Password with or , and press . 4. Mark the password to be activated, and press . 5. Mark Enter password, and press . Now the first digit of the password is flashing. 6. Select the digit with or , and save with . Now the second digit of the password is flashing. 7. Repeat points 4 to 6 if it is necessary to activate the other password. Factory setting Both passwords are deactivated. If a password is activated, the factory setting will be "6814". 9.7.57 Ethernet (4.5.5) Fig. 106 Ethernet 60 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 498 of 1068 TM03 2298 4807 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Description The CU 351 is equipped with an Ethernet connection for communication with a computer, either directly or via Internet. For further information, see section 9.8.1 Ethernet. 9.7.58 GENIbus number (4.5.6) 9.7.59 Software status (4.5.9) TM03 2297 4807 TM03 2296 4807 Fig. 107 GENIbus number Description CU 351 can communicate with external units via an RS-485 interface (option). For further information, see fig. 109 and section 9.8.2 GENIbus. Communication is carried out according to the Grundfos bus protocol, GENIbus, and enables connection to a building management system or another external control system. Operating parameters, such as setpoint and operating mode, can be set via the bus signal. Furthermore, status about important parameters, such as current value and input power, and fault indications can be read from the CU 351. Contact Grundfos for further information. Setting range The number can be set between 1 and 64. Setting via control panel 1. Mark the Settings menu with 2. Mark Functions, CU 351 with 3. Mark GENIbus number with 4. Select the number with or . or , and press . or , and press . , and save with . Factory setting No number is set (""). Fig. 108 Software status Description This display shows the status of the software installed in the CU 351. Furthermore, the version code and the product numbers of configuration files (GSC) read into the unit are shown. As it is a status display, no settings can be made. Q-Pulse Id: TMS1594 Active: 18/04/2016 61 Page 499 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 9.8 Data communication CU 351 is equipped with a hardware enabling communication with external units, such as a computer, via an external GENIbus or Ethernet connection. Third-party gateway Grundfos G100 gateway Intranet External GENIbus connection External GENIbus module (factory option) Ethernet connection Internet TM03 2044 3505 Fig. 109 Data communication via external GENIbus and Ethernet connection 9.8.1 Ethernet Ethernet is the most widely used standard for local networks (LAN). The standardisation of this technology has created some of the easiest and cheapest ways of creating communication between electrical units, for instance between computers or between computers and control units. The web server of the CU 351 makes it possible to connect a computer to the CU 351 via an Ethernet connection. The user interface can thus be exported from the CU 351 to a computer so that the CU 351 and consequently the Hydro MPC booster system can be monitored and controlled externally. Note Grundfos recommends that you protect the connection to the CU 351 according to your safety requirements in consultation with the system administrator. In order to use the web server, you must know the IP address of the CU 351. All network units must have a unique IP address in order to communicate with each other. The IP address of the CU 351 from factory is 192.168.0.102. Alternatively to the factory-set IP address, it is possible to use a dynamic assignment of IP address. This is possible by activating a DHCP (Dynamic Host Configuration Protocol) either directly in the CU 351 or via the web server. See the example in fig. 110. Fig. 110 Example of setting of Ethernet Dynamic assignment of an IP address for the CU 351 requires a DHCP server in the network. The DHCP server assigns a number of IP addresses to the electrical units and makes sure that two units do not receive the same IP address. A traditional Internet browser is used for connection to the web server of the CU 351. If you want to use the factory-set IP address, no changes are required in the display. Open the Internet browser and enter the IP address of the CU 351. TM03 2298 4807 62 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 500 of 1068 TM03 2047 3505 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual In order to use dynamic assignment, the function must be activated. Click Use DHCP in the menu line. A check mark next to the menu line shows that activation has been made. After activation in the display, open the Internet and enter the host name of the CU 351 instead of the IP address. The Internet browser will now try to connect to the CU 351. The host name can be read in the display, but can only be changed by either a GSC- file (configuration file) or via a web server. See Change of network setting on page 63. Note To use DHCP, a host name is required. This is the first display shown when connecting to the CU 351. Fig. 113 Network setting Change of network setting When connection to the web server of the CU 351 has been established, it is possible to change the network setting. TM03 2048 3505 Fig. 111 Connection to CU 351 Factory setting User name: admin Password: admin When user name and password have been entered, a Java Runtime Environment application starts up in the CU 351, provided that it has been installed on the computer in question. If this is not the case, but the computer is connected to Internet, then use the link on the screen to download and install the Java Runtime Environment application. Fig. 114 Change of network setting 1. Press the icon >Network admin. 2. Enter the changes. 3. Press Submit to activate the changes. TM03 2050 3505 TM03 2049 3505 Fig. 112 Display with link to the JavaScript® program The Java Runtime Environment application will then export the CU 351 user interface (including display and operating panel) to the computer screen. It is now possible to monitor and control the CU 351 from the computer. Q-Pulse Id: TMS1594 Active: 18/04/2016 63 Page 501 of 1068 Change of password WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual TM03 2051 3505 Fig. 115 Change of password 1. Press the icon >Change password. 2. Enter the new password. 3. Press Submit to activate the new password. 9.8.2 GENIbus By installing a GENIbus module it is possible to connect a CU 351 to an external network. The connection can take place via a GENIbus-based network or a network based on another protocol via a gateway. See fig. 109. For further information, contact Grundfos. The gateway may be a Grundfos G100 gateway or a third party gateway. For further information on the G100 gateway, see the G100 data booklet (publication number V7139522). 64 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 502 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10. External variable frequency drive External variable frequency drives used in Hydro MPC booster system variants -F, -EF and -EDF come with the manufacturer's factory settings. See tables below. At start-up, the factory settings must be changed to the Grundfos settings in the tables below. In order not to affect the functions of the CU 351 at optimum operation, only the parameters shown should be adjusted. Other parameters should be as set from factory. 10.1 VLT 2800 Press [QUICK MENU] + [+] to access all parameters. Parameter Function Factory setting Value or number in the display of VLT 2 Local/remote operation 3 Local reference 101 Torque characteristics 102 Motor power 103 Motor voltage 104 Motor frequency 105 Motor current 106 Rated motor speed 107 Automatic motor adaptation 128 Thermal motor protection 204 Minimum reference 205 Maximum reference 206 Ramp type 207 Ramp up time 208 Ramp down time 214 Reference function 215 Preset reference 302 Digital input 304 Digital input 305 Digital input6 323 Relay output 406 Automatic restart time 411 Switching frequency * Thermistor function used for thermal protection of LC filter. ** For information about languages available, see relevant documentation. *** Use data from the Hydro MPC booster set. Factory setting of VLT 2800 To recall the factory settings of all parameters, follow one of the procedures below: 1. Set the parameter 620 to (3). 2. Disconnect the power supply. 3. Re-connect the power supply. 4. All parameters are now factory-set except from the fault log. or 1. Disconnect the power supply. 2. Press and hold [QUICK MENU] + [+] + [CHANGE DATA] and re-connect the power supply. All parameters are now factory-set, including the fault log. Grundfos setting Function Value or number in the display of VLT Local/remote operation 0 Local reference Default Torque characteristics 2 Motor power Motor nameplate in kW Motor voltage Motor nameplate Motor frequency Motor nameplate, Hz Motor current Motor nameplate, SFA Rated motor speed Motor nameplate RPM Automatic motor adaptation 2 Thermal motor protection 4 Minimum reference 20 Hz Maximum reference 60 Hz Ramp type 2 Ramp up time 1.5 sec Ramp down time 3 sec Reference function 2 Preset reference 100 Digital input 7 Digital input 0 Digital input6 24 Relay output 1 Automatic restart time Switching frequency 10 sec 4500 Q-Pulse Id: TMS1594 Active: 18/04/2016 65 Page 503 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10.2 Danfoss VLT 8000 factory settings Press [EXTEND MENU] to access all parameters. Parameter 001 002 003 004 005 006 201 202 207 208 323 326 Function Language Motor power Motor voltage Motor frequency Motor current Motor speed Minimum frequency Maximum frequency Ramp up time Ramp down time Relay 1 function Relay 2 function Grundfos setting Value English 0 Motor nameplate Motor nameplate Motor nameplate Motor nameplate (SFA) Motor nameplate (RPM) 20 Hz 60 Hz 1.5 sec 3 sec Ready signal 1 Running 3 10.3 Danfoss VLT 8000 extended menu programming Parameter Function Grundfos setting Value 007 Large readout Frequency [Hz] 3 008 Small display readout Motor voltage [V] 16 009 Small display readout Motor current 5 010 Small display readout Power [Hp] 6 101 Torque characteristics VT low 2 113 Motor Preheater DC Current 0% 117 Motor Thermal Protection ETR Trip 1 4 208 Automatic ramp-down Disable 0 210 Reference type External/preset 2 302 Pin 18 Start 1 303 Pin 19 Reverse and start 2 304 Pin 27 Safety interlock 3 308 Pin 53 Reference 1 309 Term. 53, min. scaling 0.0 V 310 Term. 53, max. scaling 10 V 325 Relay 01, off delay 1 sec. 400 Reset function Automatic reset x 10 6 401 Automatic restart time 5 sec. 407 Switching frequency 4500 408 Interference reduction method Fixed switching freq. 0 016 Lock for data change Locked 1 66 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 504 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10.4 Danfoss VLT 8000 factory settings Press [EXTEND MENU] to access all parameters. Parameter 001 002 003 004 005 006 201 202 207 208 323 326 Function Language Motor power Motor voltage Motor frequency Motor current Motor speed Minimum frequency Maximum frequency Ramp up time Ramp down time Relay 1 function Relay 2 function Grundfos setting Value English 0 Motor nameplate Motor nameplate Motor nameplate Motor nameplate (SFA) Motor nameplate (RPM) 20 Hz 60 Hz 1.5 sec 3 sec Ready signal 1 Running 3 10.5 Danfoss VLT 8000 extended menu programming Parameter Function Grundfos setting Value 007 Large readout Frequency [Hz] 3 008 Small display readout Motor voltage [V] 16 009 Small display readout Motor current 5 010 Small display readout Power [Hp] 6 101 Torque characteristics VT low 2 113 Motor Preheater DC Current 0% 117 Motor Thermal Protection ETR Trip 1 4 208 Automatic ramp-down Disable 0 210 Reference type External/preset 2 302 Pin 18 Start 1 303 Pin 19 Reverse and start 2 304 Pin 27 Safety interlock 3 308 Pin 53 Reference 1 309 Term. 53, min. scaling 0.0 V 310 Term. 53, max. scaling 10 V 325 Relay 01, off delay 1 sec. 400 Reset function Automatic reset x 10 6 401 Automatic restart time 5 sec. 407 Switching frequency 4500 408 Interference reduction method Fixed switching freq. 0 016 Lock for data change Locked 1 Q-Pulse Id: TMS1594 Active: 18/04/2016 67 Page 505 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10.6 Baldor Smart motor settings Section Parameter Level 2 blocks Output limts Output limts Output limts Output limts Miscellaneous Motor data Motor data Level 1 blocks Preset speed Accel Min. output frequency Max. output PK current limit PWM frequency Restart aut/man Motor voltage Motor rated amps Preset speed #1 Accel #1 Decel rate Decel #1 Output Input Input V/Hz and Boost Opto output #1 Operating mode ANA CMD select V/Hz profile Grundfos setting Value 12 Hz 60 Hz Max. of drive 6 kHz Auto 230 V SFA on nameplate 60 Hz CR 3 - CR 10 CR 15 - CR 90 CR 3 - CR 10 CR 15 - CR 90 Ready #1 2 wire / 7 spd Pot. / 0-10 V 67% sqr. law 1.5 sec. 2.0 sec. 3.0 sec. 4.0 sec. 68 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 506 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10.7 VLT FC 202 Press [EXTEND MENU] to access all parameters. Parameter Function Grundfos setting Value 001 002 003 020 021 022 023 024 100 103 121 122 123 124 125 190 302 303 304 310 313 341 342 412 414 419 511 513 540.0 542.0 610 611 614 615 1400 1401 Language Motor Speed Unit Regional Settings Display Line 1.1 Display Line 1.2 Display Line 1.3 Display Line 2 Large Display Line 3 Large Configuration Mode Torque Characteristics Motor Power [HP] Motor Voltage Motor Frequency Motor Current Motor Nominal Speed Motor Thermal Protection Minimum Reference Maximum Reference Reference Function Preset Reference Reference Site Ramp 1 Ramp up Time Ramp 1 Ramp down Time Motor Speed Low Limit [Hz] Motor Speed High Limit [Hz] Max Output Frequency Terminal 19 Digital Input Terminal 29 Digital Input Function Relay Off Delay, Relay Terminal 53 Low Voltage Terminal 53 High Voltage Terminal 53 Low Ref. / Feedb. Terminal 53 High Ref. / Feedb. Switching Pattern Switching Frequency English Hz North America Small Power [hp] Small Motor Voltage Small Motor Current Frequency Speed [RMP] Open Loop Variable Torque Nameplate Nameplate Nameplate Nameplate Nameplate ETR trip 1 0.000 Hz 60.000 Hz Sum 100.00% Remote 1.50 s 3.00 s 0.0 Hz 60.0 Hz 65.0 Hz Start reversing Preset reference on Drive ready 2.00 s 0.00 V 10.00 V 20.000 Hz 60.000 Hz 60 AVM 5.0 kHz 0 1 1 1611 1612 1614 1615 1617 0 1 4 0 1 11 15 2 0 7 Factory setting of VLT FC 100 To recall the factory settings of all parameters, follow one of the procedures below: 1. Select parameter 14-22. 2. Press [OK]. 3. Select "Initialisation" (for NLCP select "2"). 4. Press [OK]. 5. Disconnect the power supply. 6. Reconnect the power supply. 7. All parameters are now factory-set, except RFI 1, protocol, address, baud rate, minimum response delay, maximum response delay, maximum inter-char delay, operating data, historic log and fault log. or 1. Disconnect the power supply. 2. Press and hold [STATUS] + [MAIN MENU] + [OK] and reconnect the power supply. 3. All parameters are now factory-set, except operating hours, the number of power-ups and overtemp's and overvolt's. Q-Pulse Id: TMS1594 Active: 18/04/2016 69 Page 507 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 11. Fault finding chart Warning Before making any connections in pumps, terminal boxes or breaker cabinet, make sure that the electricity supply has been switched off for at least 5 minutes and that it cannot be accidentally switched on. Fault Possible cause Remedy Current pressure is higher than or equal to the setpoint. Wait until the pressure has dropped, or lower the pressure on the discharge side of the Hydro MPC, and check that the pumps start. Electricity supply disconnected. Connect the electricity supply. Main switch cut out. Cut in the main switch. Pumps do not run when started. Main switch is defective. Motor protection is activated. Replace the main switch. Contact Grundfos. Motor is defective. Repair or replace the motor. Pressure transmitter fault - Pressure transmitter is defective. Replace the pressure transmitter. Transmitters with 0-20 mA or 4-20 mA output signals are monitored by the Hydro MPC. - Cable is broken or short-circuited. Repair or replace the cable. The pumps start, but stop immediately. The operating pressure Dry running or no inlet pressure. is not reached. Re-establish the supply of water to the Hydro MPC. When the inlet pressure has been re-established, the pumps will restart after 15 seconds. The Hydro MPC is stopped and cannot restart. Pressure transmitter fault - Pressure transmitter is defective. - Cable is broken or short-circuited. CU 351 fault - Electricity supply disconnected. Replace the pressure transmitter. Transmitters with 0-20 mA or 4-20 mA output signals are monitored by the Hydro MPC. Repair or replace the cable. Connect the electricity supply. - CU 351 defective. Contact Grundfos. Inlet pressure is too low. Unstable water delivery from Suction pipe or pumps partly blocked by Hydro MPC (applies to unstable water impurities. supply). Pumps suck air. Check the suction pipe and possible suction strainer. Clean the suction pipes, strainer or pumps. Check the suction pipe for leakages. Pressure transmitter defective. Replace the transmitter. The valves are closed. Open the valves. Suction pipe or pumps blocked by impurities. Clean the suction pipe or pumps. Pumps are running, but deliver no water. Non-return valve blocked in closed position. Clean the non-return valve. The non-return valve must move freely. Suction pipe leaky. Check the suction pipe for leakages. Air in suction pipe or pumps. Vent and prime the pumps. Check the suction pipe for leakages. The Hydro MPC is unable to reach the setpoint. Too high consumption. Too many standby pumps selected. Pipe fracture or leakage in the system. - Reduce consumption (if possible). - Install a bigger Hydro MPC booster system. Reduce the number of standby pumps. Check the system, and repair damages, if necessary. Leakage from the shaft seal. Shaft seal is defective. Replace the shaft seal. Height adjustment of pump shaft inaccurate. Readjust the shaft height. The pumps are cavitating. Clean the suction pipe/pumps and possibly the suction strainer. Noise. The pumps do not rotate freely (friction resistance) due to inaccurate height adjustment of the pump shaft. Readjust the shaft height. Very frequent starts and stops. Wrong diaphragm tank precharge pressure. Set correct precharge pressure. 70 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 508 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12. Maintenance Warning Before starting work on the pumps, make sure that the electricity supply has been switched off. Lock the main switch with a padlock to ensure that it cannot be accidentally switched on. 12.1 Pumps Pump bearings and shaft seal are maintenance-free. 12.2 Motor bearings Motors without grease nipples are maintenance-free. Motors with grease nipples should be lubricated with a hightemperature lithium-based grease. See the instructions on the fan cover of Grundfos motors. In the case of seasonal operation (motor is idle for more than 6 months of the year), it is recommended to grease the motor when the pump is taken out of operation. 12.3 CU 351 The CU 351 is maintenance-free. It must be kept clean and dry. Protect it against direct sunlight. Furthermore, the CU 351 must not be outside the ambient temperature range. See section 15. Technical data. 13. Frost protection Pumps which are not being used during periods of frost should be drained to avoid damage. Drain the pump by loosening the vent screw in the pump head and by removing the drain plug from the base. Warning Care must be taken to ensure that the escaping water does not cause injury to persons or damage to the motor or other components. In hot water installations, special attention should be paid to the risk of injury caused by scalding hot water. Do not tighten the vent screw and replace the drain plug until the pump is to be used again. 14. Taking out of operation Switch off the main switch to take the booster system out of operation. Warning The conductors in front of the main switch are still energised. Lock the main switch with a padlock to ensure that it cannot be accidentally switched on. Individual pumps are taken out of operation by switching off the corresponding motor-protective circuit breaker, automatic circuit breaker or fuse. 15. Technical data 15.1 Pressure Inlet pressure Hydro MPC booster sets can operate with a positive inlet pressure (precharged pressure system) or with a negative inlet pressure (i.e vacuum at the inlet manifold). Calculation of the inlet pressure is recommended when · water is drawn through long pipes, · water is drawn from depths, · inlet conditions are poor. Note In this installation and operating instruction the term `inlet pressure' is defined as the pressure/ vacuum which can be measured immediately before the booster set. To avoid cavitation, make sure that there is a minimum inlet pressure on the suction side of the booster set. The minimum inlet pressure in bar can be calculated as follows: H = Pb NPSH Hf Hv Hs Pb = Barometric pressure in feet (33.9 feet at sea level). In closed systems, Pb indicates system pressure in feet. Hf = Friction loss in suction piping in feet. (At the highest flow the pump will be delivering). Hv = Vapor pressure in feet. NPSH = Net Positive Suction Head in feet. NPSH can be read from the NPSH curve at the maximum capacity at which the pump will run. (See installation and operating instructions for CR, CRI, CRN). HS = Safety margin = minimum 2 feet. If "H" is calculated as positive, the pump can operate at a suction of maximum "H" feet. If "H" is calculated as negative, an inlet pressure (psia) of minimum "H" feet is required. Maximum inlet pressure Pump 60 Hz CR(E) 5-7 CR(E) 10-3 CR(E) 15-3 CR(E) 20-3 CR(E) 32-2 CR(E) 45-2-1 CR(E) 64-2-1 CR 90-2-1 Maximum inlet pressure [psi] 145 116 145 145 58 145 145 218 Note The maximum inlet pressure is determined by the construction of the pump, such as bearing pressure. For information about other CR pump sizes, see WebCAPS on www.grundfos.com. Operating pressure As standard the maximum operating pressure is 230 psi [16 bar]. On request, Grundfos offers Hydro MPC booster systems with a maximum operating pressure higher than 230 psi [16 bar]. Q-Pulse Id: TMS1594 Active: 18/04/2016 71 Page 509 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 15.2 Temperature Liquid temperature: Ambient temperature: 32 °F to +158 °F 32 °F to +104 °F 15.3 Relative humidity Max. relative humidity: 95 % 15.4 Sound pressure For sound pressure level, see the installation and operating instructions for the CR pumps. The sound pressure level for a number of pumps can be calculated as follows: Lmax = Lmax = Lpump = n= Lpump + (n 1) x 3 Maximum sound pressure level. Sound pressure level for one pump. Number of pumps. 16. Electrical data Supply voltage See nameplate of the Hydro MPC. Backup fuse See the wiring diagram supplied with the Hydro MPC. Digital inputs Open circuit voltage: Closed circuit current: Frequency range: 24 VDC 5 mA, DC 0-4 Hz Note All digital inputs are supplied with PELV voltage (Protective Extra-Low Voltage). Analog inputs Input current and voltage: Tolerance: Repetitive accuracy: Input resistance, current: Input resistance, voltage, CU 351: Input resistance, voltage, IO 351: Supply to sensor: 0-20 mA 4-20 mA 0-10 V ±3.3 % of full scale ±1% of full scale < 250 10 k ±10 % > 50 k ± 10 % 24 V, maximum 50 mA, short-circuit protected Note All analog inputs are supplied with PELV voltage (Protective Extra-Low Voltage). Digital outputs (relay outputs) Maximum contact load: Minimum contact load: 240 VAC, 2 A 5 VDC, 10 mA All digital outputs are potential-free relay contacts. Note Some outputs have a common C terminal. For further information, see the wiring diagram supplied with the Hydro MPC. Inputs for PTC sensor/thermal switch For PTC sensors to DIN 44082. Thermal switches can also be connected. Open circuit voltage: Closed circuit current: 12 VDC ±15 % 2.6 mA, DC Note Inputs for PTC sensors are electrically separated from the other inputs and outputs of the Hydro MPC. 17. Related documents Further product information about Hydro MPC booster systems can be found in the following documents. All documents are available in WebCAPS on Grundfos' homepage, www.grundfos.com. Title Frequency Publication number Product Guide Grundfos Hydro MPC Grundfos CR,CRI,CRN 60 Hz 60 Hz Installation and operating instructions CR, CRI, CRN CRE, CRIE, CRNE, CRKE, SPKE, MTRE, CHIE * 60 Hz 60 Hz Service documentation Service instructions Service kit catalog 50/60 Hz 50/60 Hz Other documentation Wiring diagram** - L-BPQ-PG-01 L-CR-PG-001 L-CP-TL-003 L-MLE-TL-02 96646712 96488862 - * Only relevant for Hydro MPC-E, -ED and -ES booster systems. ** A wiring diagram is supplied with the booster system. 18. Disposal This product or parts of it must be disposed of in an environmentally sound way: 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. 72 Q-Pulse Id: TMS1594 Active: 18/04/2016 Subject to alterations. Page 510 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 3 Valves SUPPLIER: MODEL: Tyco Northgate 88 Frederick Street Northgate Qld 4013 Ph: (07) 3266 2255 Fax: (07) 3260 5221 150 Dia DF R.S Sluice Valve ACC C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 511 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 512 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 513 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 514 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 515 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4 Flowmeter SUPPLIER: Endress & Hauser Australia 2/35 Miles Platting Rd. Eight Mile Plains Qld 4113 Ph: (07) 3457 0200 Fax: (07) 3457 0299 MODEL: DN150 PROMAG 50W1F C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 516 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Operating Instructions Proline Promag 50 Electromagnetic Flow Measuring System 6 BA046D/06/en/03.05 50097090 Valid as of version: V 2.00.XX (Device software) Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 517 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Brief operating instructions Proline Promag 50 Brief operating instructions ! These brief operating instructions show you how to configure the measuring device quickly and easily: Safety instructions Installation Wiring Display and operating elements Commissioning with "QUICK SETUP" You can commission the measuring device quickly and easily, using the special "Quick Setup" menu. It enables to configure important basic functions using the local display, for example display language, measured variables, units engineering, type of signal, etc. The following adjustments can be made separately as necessary: Empty-pipe/full-pipe adjustment for empty pipe detection (EPD) Configuration of current output (active/passive) Customer-specific cofiguration Complex measuring operations necessitate additional functions that you can configure as necessary with the aid of the function matrix, and customize to suit the process parameters. All functions are described in detail, as is the function matrix itself, in the "Description of Device Functions" manual, which is a separate part of this Operating Instruction. Page 7 Page 13 Page 47 Page 61 Page 80 ff. Page 62 Note! Always start trouble-shooting with the checklist on Page 89, if faults occur after commissioning or during operation. The routine takes you directly to the cause of the problem and the appropriate remedial measures. 2 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 518 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 "QUICK SETUP" commissioning "QUICK SETUP" commissioning ENDRESS+HAUSER -+E ESC E ++ HOME-POSITION Quick Setup E+ QS Commission Language Defaults Unit Volume flow Measuring Mode Current Output Freq.-/ Pulse Output Quit Operation Mode Assign Current Current Span Value 20 mA Time Constant Failsafe Mode Frequency Assign Frequency End Value Freq. Value f max Output Signal Time Constant Failsafe Mode Pulse Assign Pulse Pulse Value Pulse Width Output Signal Failsafe Mode Automatic parameterization of the display Quit Quick Setup F06-50xxxxxx-19-xx-xx-en-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 3 Page 519 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual "QUICK SETUP" commissioning Proline Promag 50 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 520 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Contents Contents 1 Safety instructions . . . . . . . . . . . . . . . . . . . 7 1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.2 Installation, commissioning and operation . . . . . . . . 7 1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.5 Notes on safety conventions and icons . . . . . . . . . . . 8 2 Identification . . . . . . . . . . . . . . . . . . . . . . . . 9 2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.1.1 Nameplate of the transmitter . . . . . . . . . . . 9 2.1.2 Nameplate of the sensor . . . . . . . . . . . . . 10 2.1.3 Nameplate, connections . . . . . . . . . . . . . 11 2.2 CE mark, declaration of conformity . . . . . . . . . . . . 11 2.3 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 12 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.1 Incoming acceptance, transport and storage . . . . . . 13 3.1.1 Incoming acceptance . . . . . . . . . . . . . . . . 13 3.1.2 Transport . . . . . . . . . . . . . . . . . . . . . . . . 13 3.1.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 15 3.2.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . 15 3.2.2 Mounting location . . . . . . . . . . . . . . . . . . 15 3.2.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . 17 3.2.4 Vibrations . . . . . . . . . . . . . . . . . . . . . . . . 18 3.2.5 Foundations, supports . . . . . . . . . . . . . . . 19 3.2.6 Adapters . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.2.7 Nominal diameter and flow rate . . . . . . . 20 3.2.8 Length of connecting cable . . . . . . . . . . . 25 3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . 26 3.3.1 Installing the Promag W sensor . . . . . . . . 26 3.3.2 Installing the Promag P sensor . . . . . . . . . 33 3.3.3 Installing the Promag H sensor . . . . . . . . 39 3.3.4 Turning the transmitter housing . . . . . . . 42 3.3.5 Turning the local display . . . . . . . . . . . . . 43 3.3.6 Installing the wall-mount transmitter housing . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3.4 Installation check . . . . . . . . . . . . . . . . . . . . . . . . . 46 4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 4.1 Connecting the remote version . . . . . . . . . . . . . . . 47 4.1.1 Connecting Promag W / P / H . . . . . . . . 47 4.1.2 Cable specifications . . . . . . . . . . . . . . . . . 51 4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 52 4.2.1 Transmitter . . . . . . . . . . . . . . . . . . . . . . . 52 4.2.2 Terminal assignment . . . . . . . . . . . . . . . . 54 4.2.3 HART connection . . . . . . . . . . . . . . . . . . 55 4.3 Potential equalisation . . . . . . . . . . . . . . . . . . . . . . . 56 4.3.1 Standard case . . . . . . . . . . . . . . . . . . . . . 56 4.3.2 Special cases . . . . . . . . . . . . . . . . . . . . . . 57 4.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 59 4.5 Electical connection check . . . . . . . . . . . . . . . . . . . 60 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 61 5.1 Display and operating elements . . . . . . . . . . . . . . . 61 5.2 Brief operating instruction to the function matrix . . 62 5.2.1 General notes . . . . . . . . . . . . . . . . . . . . . 63 5.2.2 Enabling the programming mode . . . . . . . 63 5.2.3 Disabling the programming mode . . . . . . 63 5.3 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 5.4 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 5.4.1 Operating options . . . . . . . . . . . . . . . . . . 66 5.4.2 Current device description files . . . . . . . . 67 5.4.3 Device and process variables . . . . . . . . . . 68 5.4.4 Universal / Common practice HART commands . . . . . . . . . . . . . . . . . . . . . . . . 69 5.4.5 Device status / Error messages . . . . . . . . 74 6 Commissioning . . . . . . . . . . . . . . . . . . . . . 79 6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.1.1 Switching on the measuring device . . . . . 79 6.2 Application-specific commissioning . . . . . . . . . . . . 80 6.2.1 "Commissioning" Quick Setup menu . . . . 80 6.2.2 Empty-pipe/full-pipe adjustment . . . . . . . 81 6.2.3 Current output: active/passive . . . . . . . . . 82 6.3 Data storage device (HistoROM) . . . . . . . . . . . . . . 82 6.3.1 HistoROM/S-DAT (sensor-DAT) . . . . . . . 82 7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . 83 7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 83 7.2 Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . 85 8.1 Device-specific accessories . . . . . . . . . . . . . . . . . . . 85 8.2 Measuring principle-specific accessories . . . . . . . . . 86 8.3 Communication-specific accessories . . . . . . . . . . . . 87 8.4 Communication-specific accessories . . . . . . . . . . . . 87 9 Trouble-shooting . . . . . . . . . . . . . . . . . . . 89 9.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . . 89 9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 90 9.3 Process error messages . . . . . . . . . . . . . . . . . . . . . . 93 9.4 Process errors without messages . . . . . . . . . . . . . . 94 9.5 Response of outputs to errors . . . . . . . . . . . . . . . . . 95 9.6 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 9.7 Removing and installing printed circuit boards . . . . 98 9.8 Replacing the device fuse . . . . . . . . . . . . . . . . . . . 102 9.9 Replacing exchangeable measuring electrodes . . . 103 9.10 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . 105 10 Technical data . . . . . . . . . . . . . . . . . . . . . 107 10.1 Technical data at a glance . . . . . . . . . . . . . . . . . . 107 10.1.1 Application . . . . . . . . . . . . . . . . . . . . . . 107 10.1.2 Function and system design . . . . . . . . . . 107 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 5 Page 521 of 1068 Contents WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10.1.3 Input . . . . . . . . . . . . . . . . . . . . . . . . . . 107 10.1.4 Output . . . . . . . . . . . . . . . . . . . . . . . . . 108 10.1.5 Power supply . . . . . . . . . . . . . . . . . . . . 108 10.1.6 Performance characteristics . . . . . . . . . 109 10.1.7 Operating conditions . . . . . . . . . . . . . . 110 10.1.8 Mechanical construction . . . . . . . . . . . 114 10.1.9 Human interface . . . . . . . . . . . . . . . . . 118 10.1.10 Certificates and approvals . . . . . . . . . . . 118 10.1.11 Ordering information . . . . . . . . . . . . . . 119 10.1.12 Accessories . . . . . . . . . . . . . . . . . . . . . . 119 10.1.13 Supplementary documentation . . . . . . . 119 11 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 522 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 1 Safety instructions 1 Safety instructions 1.1 Designated use The measuring device described in this Operating Manual is to be used only for measuring the flow rate of conductive fluids in closed pipes. A minimum conductivity of 20 µS/cm is required for measuring demineralized water. Most fluids can be metered, provided they have a minimum conductivity of 5 µS/cm, for example: · acids, alkalis, · drinking water, wastewater, sewage sludge, · milk, beer, wine, mineral water, etc. Resulting from incorrect use or from use other than that designated the operational safety of the measuring devices can be suspended. The manufacturer accepts no liability for damages being produced from this. 1.2 Installation, commissioning and operation Note the following points: · Installation, connection to the electricity supply, commissioning and maintenance of the device must be carried out by trained, qualified specialists authorized to perform such work by the facility's owner-operator. The specialist must have read and understood this Operating Manual and must follow the instructions it contains. · The device must be operated by persons authorized and trained by the facility's owner-operator. Strict compliance with the instructions in the Operating Manual is mandatory. · Endress+Hauser will be happy to assist in clarifying the chemical resistance properties of parts wetted by special fluids, including fluids used for cleaning. · If welding work is performed on the piping system, do not ground the welding appliance through the Promag flowmeter. · The installer must ensure that the measuring system is correctly wired in accordance with the wiring diagrams. The transmitter must be grounded, unless the power supply is galvanically insulated. · Invariably, local regulations governing the opening and repair of electrical devices apply. 1.3 Operational safety Note the following points: · Measuring systems for use in hazardous environments are accompanied by separate Ex documen- tation, which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. The symbol on the front of this supplementary Ex documentation indicates the approval and the certification body ( 0 Europe, 2 USA, 1 Canada). · The measuring device complies with the general safety requirements in accordance with EN 61010, the EMC requirements of EN 61326/A1, and NAMUR recommendation NE 21. · Depending on the application, the seals of the process connections of the Promag H sensor require periodic replacement. · The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to this Operating Manual. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 7 Page 523 of 1068 1 Safety instructions WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! # 1.4 Return The following procedures must be carried out before a flowmeter requiring repair or calibration, for example, is returned to Endress+Hauser: · Always enclose a duly completed "Declaration of contamination" form. Only then can Endress+Hauser transport, examine and repair a returned device. · Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/155/EEC. · Remove all residues. Pay special attention to the grooves for seals and crevices which could contain residues. This is particularly important if the substance is hazardous to health, e.g. flammable, toxic, caustic, carcinogenic, etc. Note! You will find a preprinted "Declaration of contamination" form at the back of this manual. Warning! · Do not return a measuring device if you are not absolutely certain that all traces of hazardous substances have been removed, e.g. substances which have penetrated crevices or diffused through plastic. · Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be charged to the owner-operator. # " ! 1.5 Notes on safety conventions and icons The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the factory in a condition in which they are safe to operate. The devices comply with the applicable standards and regulations in accordance with EN 61010 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures". They can, however, be a source of danger if used incorrectly or for other than the designated use. Consequently, always pay particular attention to the safety instructions indicated in this Operating Manual by the following icons: Warning! "Warning" indicates an action or procedure which, if not performed correctly, can result in injury or a safety hazard. Comply strictly with the instructions and proceed with care. Caution! "Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect operation or destruction of the device. Comply strictly with the instructions. Note! "Note" indicates an action or procedure which, if not performed correctly, can have an indirect effect on operation or trigger an unexpected response on the part of the device. 8 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 524 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 2 Identification 2 Identification 2.1 Device designation The "Promag 50" flow measuring system consists of the following components: · Promag 50 transmitter · Promag W, Promag P or Promag H sensor In the compact version, transmitter and sensor form a single mechanical unit; in the remote version they are installed separately. 2.1.1 Nameplate of the transmitter 67 PROMAG 50 1 Order Code: 50P1H-XXXXXXXXXXXX Ser.No.: 12345678901 TAG No.: ABCDEFGHJKLMNPQRST 2 16-62VDC/20-55VAC 50-60Hz 15VA/W 3 EPD/MSU 4 I-OUT (HART), f-OUT STATUS-OUT, STATUS-IN 5 IP67 / NEMA/Type 4X i -20°C (-4°F) <Tamb<+60°C (+140°F) Pat. UK EP 541 878 EP 618 680 Pat. UK 2 084 740 EP 219 725 EP 521 169 Pat. US 5,323,156 5,479,007 Pat. US 4,382,387 4,704,908 5,351,554 Fig. 1: Nameplate specifications for the "Promag 50" transmitter (example) F06-50xxxxxx-18-06-xx-xx-000 1 Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual letters and digits. 2 Power supply / frequency: 16...62 V DC / 20...55 V AC / 50...60 Hz Power consumption: 15 VA / W 3 Additional functions and software: EPD/MSU: with Empty Pipe Detection ECC: with Electrode Cleaning Circuitry 4 Outputs / inputs: I-OUT (HART): with current output (HART) f-OUT: with pulse/frequency output STATUS-IN: with status input (auxiliary input) STATUS-OUT: with status output (switch output) 5 Reserved for information on special products 6 Ambient temperature range 7 Degree of protection Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 9 Page 525 of 1068 2 Identification WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 2.1.2 Nameplate of the sensor PROMAG P 1 Order Code: XXP1H-XXXXXXXXXXXX Ser.No.: 12345678901 2 TAG No.: ABCDEFGHJKLMNPQRST 3 K-factor: 0.5328/-5 DN100 DIN/EN PN16 4 Materials: PFA / 1.4435 5 TMmax.: 150°C/300°F EPD/MSÜ, R/B 6 7 8 -20°C (-4°F)<Tamb<+60°C (+140°F) NEMA/Type4X 9 Pat. US 4,382,387 4,704,908 5,540,103 10 11 Fig. 2: Nameplate specifications for the "Promag" sensor (example) F06-xxxxxxxx-18-05-xx-xx-000 1 Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual letters and digits. 2 Calibration factor: 0.5328; zero point: -5 3 Nominal diameter: DN 100 Pressure rating: EN (DIN) PN 16 bar 4 TMmax +150 °C (max. fluid temperature) 5 Materials: Lining: PFA Measuring electrodes: stainless steel 1.4435 6 Additional information (examples): EPD/MSU: with Empty Pipe Detection electrode R/B: with reference electrode 7 Reserved for information on special products 8 Ambient temperature range 9 Degree of protection 10 Reserved for additional information on device version (approvals, certificates) 11 Flow direction 10 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 526 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 2.1.3 Nameplate, connections 2 Identification See operating manual Betriebsanleitung beachten Observer manuel d'instruction A: active P: passive NO: normally open contact NC: normally closed contact 1 Ser.No.: 12345678912 12 Supply / 4 Versorgung / Tension d'alimentation L1/L+ N/LPE I-OUT (HART) Active: 0/4...20mA, RL max. = 700 Ohm Passive: 4...20mA, max. 30VDC, Ri < 150 Ohm (HART: RL.min. = 250 OHM) f-OUT fmax = 1kHz Passive: 30VDC, 250mA A P 5 Passive: 30VDC, 250mA STATUS-OUT X 3...30VDC, Ri = 5kOhm STATUS-IN X ex-works Version info Update 1 Update 2 6 Device SW: XX.XX.XX 7 Communication: XXXXXXXXXX 8 Revision: XX.XX.XX 9 Date: DD.MMM.YYYY 319475-00XX 10 Fig. 3: Nameplate specifications for Proline transmitter (example) 1 Serial number 2 Possible configuration of current output 3 Possible configuration of relay contacts 4 Terminal assignment, cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC Terminal No. 1: L1 for AC, L+ for DC Terminal No. 2: N for AC, L- for DC 5 Signals present at inputs and outputs, possible configuration and terminal assignment (20...27), see also "Electrical values of inputs/outputs" 6 Version of device software currently installed 7 Installed communication type, e.g.: HART, PROFIBUS PA, etc. 8 Information on current communication software (Device Revision and Device Description), e.g.: Dev. 01 / DD 01 for HART 9 Date of installation 10 Current updates to data specified in points 6 to 9 20(+) / 21(-) 22(+) / 23(-) 24(+) / 25(-) 26(+) / 27(-) 2 3 A0000963 2.2 CE mark, declaration of conformity The devices are designed to meet state-of-the-art safety requirements in accordance with sound engineering practice. They have been tested and left the factory in a condition in which they are safe to operate. The devices comply with the applicable standards and regulations in accordance with EN 61010 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures" and with the EMC reqiurements of EN 61326/A1. The measuring system described in this Operating Manual is therefore in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 11 Page 527 of 1068 2 Identification WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 2.3 Registered trademarks KALREZ ®, VITON ® are registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA TRI-CLAMP ® is a registered trademark of Ladish & Co., Inc., Kenosha, USA HART ® is a registered trademark of HART Communication Foundation, Austin, USA HistoROMTM, S-DAT®, ToF Tool - Fieldtool® Package, Fieldcheck®, Applicator® are registered trademarks of Endress+Hauser Flowtec AG, Reinach, CH 12 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 528 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3 Installation 3.1 Incoming acceptance, transport and storage 3.1.1 Incoming acceptance · Check the packaging and the contents for damage. · Check the shipment, make sure nothing is missing and that the scope of supply matches your order. " # 3.1.2 Transport The following instructions apply to unpacking and to transporting the device to its final location: · Transport the devices in the containers in which they are delivered. · Do not remove the protective plates or caps on the process connections until the device is ready to install. This is particularly important in the case of sensors with PTFE linings. Special notes on flanged devices Caution! · The wooden covers mounted on the flanges before the device leaves the factory protect the linings on the flanges during storage and transportation. Do not remove these covers until immediately before the device is installed in the pipe. · Do not lift flanged devices by the transmitter housing, or the connection housing in the case of the remote version. Transporting flanged devices (DN 300): Use webbing slings slung round the two process connections (Fig. 4). Do not use chains, as they could damage the housing. Warning! Risk of injury if the measuring device slips. The center of gravity of the assembled measuring device might be higher than the points around which the slings are slung. At all times, therefore, make sure that the device does not unexpectedly turn around its axis or slip. Fig. 4: Transporting transmitters with DN 300 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 F06-xxxxxxxx-22-00-00-xx-000 13 Page 529 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Transporting flanged devices (DN 350): Use only the metal eyes on the flanges for transporting the device, lifting it and positioning the sensor in the piping. " Caution! Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing. This would buckle the casing and damage the internal magnetic coils. Fig. 5: Transporting sensors with DN 350 F06-5xFxxxxx-22-xx-xx-xx-001 3.1.3 Storage Note the following points: · Pack the measuring device in such a way as to protect it reliably against impact for storage (and transportation). The original packaging provides optimum protection. · The storage temperature corresponds to the operating temperature range of the measuring transmitter and the appropriate measuring sensors. · The measuring device must be protected against direct sunlight during storage in order to avoid unacceptably high surface temperatures. · Choose a storage location where moisture does not collect in the measuring device. This will help prevent fungus and bacteria infestation which can damage the liner. · Do not remove the protective plates or caps on the process connections until you are ready to install the device. This is particularly important in the case of sensors with PTFE linings. 14 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 530 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3.2 Installation conditions 3.2.1 Dimensions All the dimensions and lengths of the sensor and transmitter are provided in the separate documentation "Technical Information". 3.2.2 Mounting location Correct measuring is possible only if the pipe is full. Avoid the following locations: · Highest point of a pipeline. Risk of air accumulating · Directly upstream a free pipe outlet in a vertical pipeline. Fig. 6: Location F06-5xxxxxxx-11-00-00-xx-000 Installation of pumps Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. Information on the lining's resistance to partial vacuum can be found on Page 113. It might be necessary to install pulse dampers in systems incorporating reciprocating, diaphragm or peristaltic pumps. Information on the measuring system's resistance to vibration and shock can be found on Page 110. Fig. 7: Installation of pumps Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 F06-5xxxxxxx-11-00-00-xx-001 15 Page 531 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Partially filled pipes Partially filled pipes with gradients necessitate a drain-type configuration. The Empty Pipe Detection function (see Page 81) offers additional protection by detecting empty or partially filled pipes. " Caution! Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to install a cleaning valve. Fig. 8: Installation in partially filled pipe F06-5xxxxxxx-11-00-00-xx-002 Down pipes Install a siphon or a vent valve downstream of the sensor in down pipes longer than 5 meters. This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. These measures also prevent the system losing prime, which could cause air inclusions. Information on the lining's resistance to partial vacuum can be found on Page 113. Fig. 9: Measures for installation in a down pipe (a = vent valve; b = siphon) F06-5xxxxxxx-11-00-00-xx-003 16 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 532 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3.2.3 Orientation An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring tube. Promag, nevertheless, supplies a range of functions and accessories for correct measuring of problematic fluids: · Electrode Cleaning Circuit (ECC) for applications with accretive fluids, e.g. electrically conduc- tive deposits "Description of Device Functions" manual. · Empty Pipe Detection (EPD) ensures the detection of partially filled measuring tubes, e.g. in the case of degassing fluids or varying process pressure (see Page 81) · Exchangeable Measuring Electrodes for abrasive fluids (see Page 103) Vertical orientation This is the ideal orientation for self-emptying piping systems and for use in conjunction with Empty Pipe Detection. Fig. 10: Vertical orientation F06-5xxxxxxx-11-00-00-xx-004 Horizontal orientation The measuring electrode plane should be horizontal. This prevents brief insulation of the two electrodes by entrained air bubbles. " Caution! Empty Pipe Detection functions correctly only when the measuring device is installed horizontally and the transmitter housing is facing upward (Fig. 11). Otherwise there is no guarantee that Empty Pipe Detection will respond if the measuring tube is only partially filled or empty. Endress + Hauser Q-Pulse Id: TMS1594 Fig. 11: Horizontal orientation 1 EPD electrode for the detection of empty pipes (not with Promag H, DN 2...4) 2 Measurement electrodes for the signal acquisition 3 Reference electrode for the potential equalisation (not with Promag H) F06-5xxxxxxx-11-00-xx-xx-000 Active: 18/04/2016 17 Page 533 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. Compliance with the following requirements for the inlet and outlet runs is necessary in order to ensure measuring accuracy. · Inlet run 5 x DN · Outlet run 2 x DN Fig. 12: Inlet and outlet runs F06-5xxxxxxx-11-00-00-xx-005 3.2.4 Vibrations Secure the piping and the sensor if vibration is severe. " Caution! It is advisable to install sensor and transmitter separately if vibration is excessively severe. Informa- tion on resistance to vibration and shock can be found on Page 110. > 10 m Fig. 13: Measures to prevent vibration of the measuring device 18 Q-Pulse Id: TMS1594 Active: 18/04/2016 F06-5xxxxxxx-11-00-00-xx-006 Endress + Hauser Page 534 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3.2.5 Foundations, supports If the nominal diameter is DN 350, mount the transmitter on a foundation of adequate load-bearing strength. " Caution! Risk of damage. Do not support the weight of the sensor on the metal casing: the casing would buckle and damage the internal magnetic coils. Fig. 14: Correct support for large nominal diameters (DN 350) F06-5xFxxxxx-11-05-xx-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 19 Page 535 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 3.2.6 Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in largerdiameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids. The nomogram shown here can be used to calculate the pressure loss caused by cross-section reduction: Note! The nomogram applies to fluids of viscosity similar to water. 1. Calculate the ratio of the diameters d/D. 2. From the nomogram read off the pressure loss as a function of flow velocity (downstream from the reduction) and the d/D ratio. max. 8° dD [mbar] 100 10 1 8 m/s 7 m/s 6 m/s 5 m/s 4 m/s 3 m/s 2 m/s 1 m/s 0.5 0.6 0.7 0.8 0.9 d / D ! Fig. 15: Pressure loss due to adapters F06-5xxxxxxx-05-05-xx-xx-000 3.2.7 Nominal diameter and flow rate The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum velocity of flow is 2...3 m/s. The velocity of flow (v), moreover, has to be matched to the physical properties of the fluid: · v < 2 m/s: for abrasive fluids such as potter's clay, lime milk, ore slurry, etc. · v > 2 m/s: for fluids producing build-up such as wastewater sludge, etc. Note! Flow velocity can be increased, if necessary, by reducing the nominal diameter of the sensor (see Chap. 3.2.6). 20 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 536 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Promag W Flow rate characteristic values Promag W (SI units) Nominal diameter [mm] 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 700 800 900 1000 - 1200 1400 - 1600 - 1800 - 2000 [inch] 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" 28" 30" 32" 36" 40" 42" 48" 54" 60" 66" 72" 78" Recommended flow rate min./max. full scale value (v ~ 0.3 or 10 m/s) 9...300 dm3/min 15...500 dm3/min 25...700 dm3/min 35...1100 dm3/min 60...2000 dm3/min 90...3000 dm3/min 145...4700 dm3/min 220...7500 dm3/min 20...600 m3/h 35...1100 m3/h 55...1700 m3/h 80...2400 m3/h 110...3300 m3/h 140...4200 m3/h 180...5400 m3/h 220...6600 m3/h 310...9600 m3/h 420...13500 m3/h 480...15000 m3/h 550...18000 m3/h 690...22500 m3/h 850...28000 m3/h 950...30000 m3/h 1250...40000 m3/h 1550...50000 m3/h 1700...55000 m3/h 1950...60000 m3/h 2200...70000 m3/h 2500...80000 m3/h 2800...90000 m3/h 3300...100000 m3/h 3400...110000 m3/h Factory setting Full scale value (v ~ 2.5 m/s) 75 dm3/min 125 dm3/min 200 dm3/min 300 dm3/min 500 dm3/min 750 dm3/min 1200 dm3/min 1850 dm3/min 150 m3/h 300 m3/h 500 m3/h 750 m3/h 1000 m3/h 1200 m3/h 1500 m3/h 2000 m3/h 2500 m3/h 3500 m3/h 4000 m3/h 4500 m3/h 6000 m3/h 7000 m3/h 8000 m3/h 10000 m3/h 13000 m3/h 14000 m3/h 16000 m3/h 18000 m3/h 20500 m3/h 23000 m3/h 28500 m3/h 28500 m3/h Pulse value (~ 2 pulse/s) 0.50 dm3 1.00 dm3 1.50 dm3 2.50 dm3 5.00 dm3 5.00 dm3 10.00 dm3 15.00 dm3 0.025 m3 0.05 m3 0.05 m3 0.10 m3 0.10 m3 0.15 m3 0.25 m3 0.25 m3 0.30 m3 0.50 m3 0.50 m3 0.75 m3 0.75 m3 1.00 m3 1.00 m3 1.50 m3 1.50 m3 2.00 m3 2.00 m3 2.50 m3 2.50 m3 3.00 m3 3.50 m3 3.50 m3 Low flow cutoff (v ~ 0.04 m/s) 1 dm3/min 2 dm3/min 3 dm3/min 5 dm3/min 8 dm3/min 12 dm3/min 20 dm3/min 30 dm3/min 2.5 m3/h 5.0 m3/h 7.5 m3/h 10 m3/h 15 m3/h 20 m3/h 25 m3/h 30 m3/h 40 m3/h 50 m3/h 60 m3/h 75 m3/h 100 m3/h 125 m3/h 125 m3/h 150 m3/h 200 m3/h 225 m3/h 250 m3/h 300 m3/h 325 m3/h 350 m3/h 450 m3/h 450 m3/h Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 21 Page 537 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Flow rate characteristic values Promag W (US units) Nominal diameter [inch] 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" 28" 30" 32" 36" 40" 42" 48" 54" 60" 66" 72" 78" [mm] 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 700 800 900 1000 - 1200 1400 - 1600 - 1800 - 2000 Recommended flow rate min./max. full scale value (v ~ 0.3 or 10 m/s) 2.5...80 gal/min 4...130 gal/min 7...190 gal/min 10...300 gal/min 16...500 gal/min 24...800 gal/min 40...1250 gal/min 60...1950 gal/min 90...2650 gal/min 155...4850 gal/min 250...7500 gal/min 350...10600 gal/min 500...15000 gal/min 600...19000 gal/min 800...24000 gal/min 1000...30000 gal/min 1400...44000 gal/min 1900...60000 gal/min 2150...67000 gal/min 2450...80000 gal/min 3100...100000 gal/min 3800...125000 gal/min 4200...135000 gal/min 5500...175000 gal/min 9...300 Mgal/d 10...340 Mgal/d 12...380 Mgal/d 13...450 Mgal/d 14...500 Mgal/d 16...570 Mgal/d 18...650 Mgal/d 20...700 Mgal/d Factory setting Full scale value (v ~ 2.5 m/s) 18 gal/min 30 gal/min 50 gal/min 75 gal/min 130 gal/min 200 gal/min 300 gal/min 450 gal/min 600 gal/min 1200 gal/min 1500 gal/min 2400 gal/min 3600 gal/min 4800 gal/min 6000 gal/min 7500 gal/min 10500 gal/min 13500 gal/min 16500 gal/min 19500 gal/min 24000 gal/min 30000 gal/min 33000 gal/min 42000 gal/min 75 Mgal/d 85 Mgal/d 95 Mgal/d 110 Mgal/d 120 Mgal/d 140 Mgal/d 175 Mgal/d 175 Mgal/d Pulse value (~ 2 pulse/s) 0.20 gal 0.20 gal 0.50 gal 0.50 gal 1 gal 2 gal 2 gal 5 gal 5 gal 10 gal 15 gal 25 gal 30 gal 50 gal 50 gal 75 gal 100 gal 125 gal 150 gal 200 gal 225 gal 250 gal 250 gal 400 gal 0.0005 Mgal 0.0005 Mgal 0.0005 Mgal 0.0008 Mgal 0.0008 Mgal 0.0008 Mgal 0.001 Mgal 0.001 Mgal Low flow cutoff (v ~ 0.04 m/s) 0.25 gal/min 0.50 gal/min 0.75 gal/min 1.25 gal/min 2.0 gal/min 2.5 gal/min 4.0 gal/min 7.0 gal/min 12 gal/min 15 gal/min 30 gal/min 45 gal/min 60 gal/min 60 gal/min 90 gal/min 120 gal/min 180 gal/min 210 gal/min 270 gal/min 300 gal/min 360 gal/min 480 gal/min 600 gal/min 600 gal/min 1.3 Mgal/d 1.3 Mgal/d 1.3 Mgal/d 1.7 Mgal/d 2.2 Mgal/d 2.6 Mgal/d 3.0 Mgal/d 3.0 Mgal/d 22 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 538 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Promag P Flow rate characteristic values Promag P (SI units) Nominal diameter [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 [inch] 1/2" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" Recommended flow rate min./max. full scale value (v ~ 0.3 or 10 m/s) 4...100 dm3/min 9...300 dm3/min 15...500 dm3/min 25...700 dm3/min 35...1100 dm3/min 60...2000 dm3/min 90...3000 dm3/min 145...4700 dm3/min 220...7500 dm3/min 20...600 m3/h 35...1100 m3/h 55...1700 m3/h 80...2400 m3/h 110...3300 m3/h 140...4200 m3/h 180...5400 m3/h 220...6600 m3/h 310...9600 m3/h Factory setting Full scale value (v ~ 2.5 m/s) 25 dm3/min 75 dm3/min 125 dm3/min 200 dm3/min 300 dm3/min 500 dm3/min 750 dm3/min 1200 dm3/min 1850 dm3/min 150 m3/h 300 m3/h 500 m3/h 750 m3/h 1000 m3/h 1200 m3/h 1500 m3/h 2000 m3/h 2500 m3/h Pulse value (~ 2 pulse/s) 0.20 dm3 0.50 dm3 1.00 dm3 1.50 dm3 2.50 dm3 5.00 dm3 5.00 dm3 10.00 dm3 15.00 dm3 0.025 m3 0.05 m3 0.05 m3 0.10 m3 0.10 m3 0.15 m3 0.25 m3 0.25 m3 0.30 m3 Low flow cutoff (v ~ 0.04 m/s) 0.5 dm3/min 1 dm3/min 2 dm3/min 3 dm3/min 5 dm3/min 8 dm3/min 12 dm3/min 20 dm3/min 30 dm3/min 2.5 m3/h 5.0 m3/h 7.5 m3/h 10 m3/h 15 m3/h 20 m3/h 25 m3/h 30 m3/h 40 m3/h Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 23 Page 539 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Flow rate characteristic values Promag P (US units) Nominal diameter [inch] 1/2" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 Recommended flow rate min./max. full scale value (v ~ 0.3 or ~ 10 m/s) 1.0...27 gal/min 2.5...80 gal/min 4...130 gal/min 7...190 gal/min 10...300 gal/min 16...500 gal/min 24...800 gal/min 40...1250 gal/min 60...1950 gal/min 90...2650 gal/min 155...4850 gal/min 250...7500 gal/min 350...10600 gal/min 500...15000 gal/min 600...19000 gal/min 800...24000 gal/min 1000...30000 gal/min 1400...44000 gal/min Factory setting Full scale value (v ~ 2.5 m/s) 6 gal/min 18 gal/min 30 gal/min 50 gal/min 75 gal/min 130 gal/min 200 gal/min 300 gal/min 450 gal/min 600 gal/min 1200 gal/min 1500 gal/min 2400 gal/min 3600 gal/min 4800 gal/min 6000 gal/min 7500 gal/min 10500 gal/min Pulse value (~ 2 pulse/s) 0.05 gal 0.20 gal 0.20 gal 0.50 gal 0.50 gal 1 gal 2 gal 2 gal 5 gal 5 gal 10 gal 15 gal 25 gal 30 gal 50 gal 50 gal 75 gal 100 gal Low flow cutoff (v ~ 0.04 m/s) 0.10 gal/min 0.25 gal/min 0.50 gal/min 0.75 gal/min 1.25 gal/min 2.0 gal/min 2.5 gal/min 4.0 gal/min 7.0 gal/min 12 gal/min 15 gal/min 30 gal/min 45 gal/min 60 gal/min 60 gal/min 90 gal/min 120 gal/min 180 gal/min Promag H Flow rate characteristic values Promag H (SI units) Nominal diameter [mm] 2 4 8 15 25 40 50 65 80 100 inch] 1/12" 5/32" 5/16" 1/2" 1" 1 1/2" 2" 2 1/2" 3" 4" Recommended flow rate min./max. full scale value (v ~ 0.3 or 10 m/s) 0.06...1.8 dm3/min 0.25...7 dm3/min 1...30 dm3/min 4...100 dm3/min 9...300 dm3/min 25...700 dm3/min 35...1100 dm3/min 60...2000 dm3/min 90...3000 dm3/min 145...4700 dm3/min Full scale value (v ~ 2.5 m/s) 0.5 dm3/min 2 dm3/min 8 dm3/min 25 dm3/min 75 dm3/min 200 dm3/min 300 dm3/min 500 dm3/min 750 dm3/min 1200 dm3/min Factory settings Pulse value (~ 2 pulse/s) 0.005 dm3 0.025 dm3 0.10 dm3 0.20 dm3 0.50 dm3 1.50 dm3 2.50 dm3 5.00 dm3 5.00 dm3 10.00 dm3 Low flow cutoff (v ~ 0.04 m/s) 0.01 dm3/min 0.05 dm3/min 0.1 dm3/min 0.5 dm3/min 1 dm3/min 3 dm3/min 5 dm3/min 8 dm3/min 12 dm3/min 20 dm3/min 24 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 540 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Flow rate characteristic values Promag H (US units) Nominal diameter [inch] 1/12" 5/32" 5/16" 1/2" 1" 1 1/2" 2" 2 1/2" 3" 4" [mm] 2 4 8 15 22 40 50 65 80 100 Recommended flow rate min./max. full scale value (v ~ 0.3 or 10 m/s) 0.015...0.5 gal/min 0.07...2 gal/min 0.25...8 gal/min 1.0...27 gal/min 2.5...65 gal/min 7...190 gal/min 10...300 gal/min 16...500 gal/min 24...800 gal/min 40...1250 gal/min Factory settings Full scale value (v ~ 2.5 m/s) 0.1 gal/min 0.5 gal/min 2 gal/min 6 gal/min 18 gal/min 50 gal/min 75 gal/min 130 gal/min 200 gal/min 300 gal/min Pulse value (~ 2 Pulse/s) 0.001 gal 0.005 gal 0.02 gal 0.05 gal 0.20 gal 0.50 gal 0.50 gal 1 gal 2 gal 2 gal Low flow cutoff (v ~ 0.04 m/s) 0.002 gal/min 0.008 gal/min 0.025 gal/min 0.10 gal/min 0.25 gal/min 0.75 gal/min 1.25 gal/min 2.0 gal/min 2.5 gal/min 4.0 gal/min 3.2.8 Length of connecting cable In order to ensure measuring accuracy, comply with the following instructions when installing the remote version: · Secure the cable run or route the cable in a conduit. Movement of the cable can falsify the measu- ring signal, particularly if the fluid conductivity is low. · Route the cable well clear of electrical machines and switching elements. · Ensure potential equalisation between sensor and transmitter, if necessary. · The permissible cable length Lmax depends on the fluid conductivity (Fig. 16). A minimum conductivity of 20 µS/cm is required for measuring demineralized water. [µS/cm] 200 L max 100 5 10 Fig. 16: Permissible cable length for the remote version Gray shaded area = permissible range Lmax = length of connecting cable in [m] Fluid conductivity in [µS/cm] 100 L max [m] 200 F06-xxxxxxxx-05-xx-xx-xx-006 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 25 Page 541 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3.3 Installation instructions ! 3.3.1 Installing the Promag W sensor Note! Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer. The sensor is designed for installation between the two piping flanges: · Observe in any case the necessary screw tightening torques on Page 28 ff. · The mounting of additional ground disks is described on Page 27. Fig. 17: Installing the Promag W sensor F06-5xFxxxxx-17-05-xx-xx-000 Seals Comply with the following instructions when installing seals: · Hard rubber lining additional seals are always necessary. · Polyurethane lining additional seals are recommended. · For DIN flanges, use only seals according to DIN EN 1514-1. · Make sure that the seals do not protrude into the piping cross-section. " Caution! Risk of short circuit. Do not use electrically conductive sealing compound such as graphite. An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal. Ground cable (DN 25...2000) If necessary, the special ground cable for potential equalisation can be ordered as an accessory (see Page 85). Detailled assembly instructions Page 57 ff. 26 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 542 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Assembly with ground disks (DN 25...300) Depending on the application, e.g. with lined or ungrounded pipes (see Page 56 ff.), it may be necessary to mount ground disks between the sensor and the pipe flange for potential equalisation. Ground disks can be ordered separately as an accessory from Endress+Hauser (see Page 85). " Caution! · In this case, when using ground disks (including seals) the total fitting length increases! All the dimensions are provided in the separate documentation "Technical Information" · Hard rubber lining install additional seals between the sensor and ground disk and between the ground disk and pipe flange. · Polyurethane lining only install additional seals between the ground disk and pipe flange. 1. Place the ground disk and additional seal(s) between the instrument and the pipe flange (Fig. 18). 2. Insert the bolts through the flange holes. Tighten the nuts so that they are still loose. 3. Now rotate the ground disk as shown in Fig. 18 until the handle strikes the bolts. This will center the ground disk automatically. 4. Now tighten the bolts to the required torque (see Page 28 ff.) 5. Connect the ground disk to ground Page 58. Fig. 18: Assembly with ground disks (Promag W, DN 25...300) F06-5xFxxxxx-17-05-xx-xx-001 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 27 Page 543 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Screw tightening torques (Promag W) Note the following points: · The tightening torques listed below are for lubricated threads only. · Always tighten threaded fasteners uniformly and in diagonally opposite sequence. · Overtightening the fasteners will deform the sealing faces or damage the seals. · The tightening torques listed below apply only to pipes not subjected to tensile stress. Promag W Nominal diameter [mm] 25 32 40 50 65 * 65 80 80 100 100 125 125 150 150 200 200 200 250 250 250 300 300 300 350 350 350 400 400 400 450 450 450 500 500 500 EN (DIN) Pressure rating [bar] PN 40 PN 40 PN 40 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 Threaded fasteners 4 x M 12 4 x M 16 4 x M 16 4 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 20 8 x M 16 8 x M 24 8 x M 20 8 x M 24 8 x M 20 12 x M 20 12 x M 24 12 x M 20 12 x M 24 12 x M 27 12 x M 20 12 x M 24 16 x M 27 16 x M 20 16 x M 24 16 x M 30 16 x M 24 16 x M 27 16 x M 33 20 x M 24 20 x M 27 20 x M 33 20 x M 24 20 x M 30 20 x M 33 Max. tightening torque [Nm] Hard rubber - - - - 32 32 40 40 43 59 56 83 74 104 106 70 104 82 98 150 94 134 153 112 152 227 151 193 289 153 198 256 155 275 317 Polyurethane 15 24 31 40 27 27 34 34 36 50 48 71 63 88 91 61 92 71 85 134 81 118 138 118 165 252 167 215 326 133 196 253 171 300 360 28 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 544 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Promag W Nominal diameter EN (DIN) Pressure rating Threaded fasteners [mm] [bar] 600 PN 10 20 x M 27 600 * PN 16 20 x M 33 600 PN 25 20 x M 36 700 PN 10 24 x M 27 700 PN 16 24 x M 33 700 PN 25 24 x M 39 800 PN 10 24 x M 30 800 PN 16 24 x M 36 800 PN 25 24 x M 45 900 PN 10 28 x M 30 900 PN 16 28 x M 36 900 PN 25 28 x M 45 1000 PN 10 28 x M 33 1000 PN 16 28 x M 39 1000 PN 25 28 x M 52 1200 PN 6 32 x M 30 1200 PN 10 32 x M 36 1200 PN 16 32 x M 45 1400 PN 6 36 x M 33 1400 PN 10 36 x M 39 1400 PN 16 36 x M 45 1600 PN 6 40 x M 33 1600 PN 10 40 x M 45 1600 PN 16 40 x M 52 1800 PN 6 44 x M 36 1800 PN 10 44 x M 45 1800 PN 16 44 x M 52 2000 PN 6 48 x M 39 2000 PN 10 48 x M 45 2000 PN 16 48 x M 56 * Designed acc. to EN 1092-1 (not to DIN 2501) Max. tightening torque [Nm] Hard rubber 206 415 431 246 278 449 331 369 664 316 353 690 402 502 970 319 564 701 430 654 729 440 946 1007 547 961 1108 629 1047 1324 Polyurethane 219 443 516 246 318 507 316 385 721 307 398 716 405 518 971 299 568 753 398 618 762 417 893 1100 521 895 1003 605 1092 1261 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 29 Page 545 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Promag W Nominal diameter [mm] [inch] 700 28" 750 30" 800 32" 900 36" 1000 40" 1050 42" 1200 48" 1350 54" 1500 60" 1650 66" 1800 72" 2000 78" AWWA Pressure rating Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Threaded fasteners 28 x 1 1/4" 28 x 1 1/4 28 x 1 1/2" 32 x 1 1/2" 36 x 1 1/2" 36 x 1 1/2" 44 x 1 1/2" 44 x 1 3/4" 52 x 1 3/4" 52 x 1 3/4" 60 x 1 3/4" 64 x 2" Max. tightening torque [Nm] Hard rubber 247 287 394 419 420 528 552 730 758 946 975 853 Polyurethane 292 302 422 430 477 518 531 633 832 955 1087 786 Promag W Nominal diameter [mm] [inch] 25 1" 25 1" 40 1 1/2" 40 1 1/2" 50 2" 50 2" 80 3" 80 3" 100 4" 100 4" 150 6" 150 6" 200 8" 250 10" 300 12" 350 14" 400 16" 450 18" 500 20" 600 24" ANSI Pressure rating [lbs] Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Threaded fasteners 4 x 1/2" 4 x 5/8" 4 x 1/2" 4 x 3/4" 4 x 5/8" 8 x 5/8" 4 x 5/8" 8 x 3/4" 8 x 5/8" 8 x 3/4" 8 x 3/4" 12 x 3/4" 8 x 3/4" 12 x 7/8" 12 x 7/8" 12 x 1" 16 x 1" 16 x 1 1/8" 20 x 1 1/8" 20 x 1 1/4" Max. tightening torque [Nm] Hard rubber - - - - - - 60 38 42 58 79 70 107 101 133 135 128 204 183 268 Polyurethane 7 8 10 15 22 11 43 26 31 40 59 51 80 75 103 158 150 234 217 307 30 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 546 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Promag W Nominal diameter [mm] 25 25 32 32 40 40 50 50 65 65 80 80 100 100 125 125 150 150 200 200 250 250 300 300 JIS Pressure rating Threaded fasteners 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 8 x M 16 10K 4 x M 16 20K 8 x M 16 10K 8 x M 16 20K 8 x M 20 10K 8 x M 16 20K 8 x M 20 10K 8 x M 20 20K 8 x M 22 10K 8 x M 20 20K 12 x M 22 10K 12 x M 20 20K 12 x M 22 10K 12 x M 22 20K 12 x M 24 10K 16 x M 22 20K 16 x M 24 Max. tightening torque [Nm] Hard rubber - - - - - - - - 55 28 29 42 35 56 60 91 75 81 61 91 100 159 74 138 Polyurethane 19 19 22 22 24 24 33 17 45 23 23 35 29 48 51 79 63 72 52 80 87 144 63 124 Promag W Nominal diameter [mm] 80 100 150 200 250 300 350 400 500 600 AS 2129 Pressure rating Table E Table E Table E Table E Table E Table E Table E Table E Table E Table E Threaded fasteners 4 x M 16 8 x M 16 8 x M 20 8 x M 20 12 x M 20 12 x M 24 12 x M 24 12 x M 24 16 x M 24 16 x M 30 Max. tightening torque [Nm] Hard rubber 49 38 64 96 98 123 203 226 271 439 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 31 Page 547 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Promag W Nominal diameter AS 4087 Pressure rating Threaded fasteners [mm] 80 Cl.14 4 x M 16 100 * Cl.14 8 x M 16 150 Cl.14 8 x M 20 200 Cl.14 8 x M 20 250 Cl.14 8 x M 20 300 Cl.14 12 x M 24 350 Cl.14 12 x M 24 400 Cl.14 12 x M 24 500 Cl.14 16 x M 24 600 Cl.14 16 x M 30 * Designed acc. to EN 2129 (not to DIN 4087) Max. tightening torque [Nm] Hard rubber 49 38 52 77 147 103 203 226 271 393 32 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 548 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation " ! 3.3.2 Installing the Promag P sensor Caution! · The protective covers mounted on the two sensor flanges guard the PTFE lining, which is turned over the flanges. Consequently, do not remove these covers until immediately before the sensor is installed in the pipe. · The covers must remain in place while the device is in storage. · Make sure that the lining is not damaged or removed from the flanges. Note! Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer. The sensor is designed for installation between the two piping flanges. · Observe in any case the necessary screw tightening torques on Page 36 ff. · The mounting of additional ground disks is described on Seite 34. Fig. 19: Installing the Promag P sensor F-5xFxxxxx-17-05-xx-xx-000 Seals Comply with the following instructions when installing seals: · Measuring tube linings with PFA or PTFE No seals are required. · In case you use seals with DIN flanges, use only seals according to DIN EN 1514-1. · Make sure that the seals do not protrude into the piping cross-section. " Caution! Risk of short circuit. Do not use electrically conductive sealing compound such as graphite. An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal. Ground cable (DN 15...600) If necessary, a special ground cable for potential equalisation can be ordered as an accessory (see Page 85). Detailled assembly instructions Page 57 ff. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 33 Page 549 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Assembly with ground disks (DN 15...300) Depending on the application, e.g. with lined or ungrounded pipes (see Page 56 ff.), it may be necessary to mount ground disks between the sensor and the pipe flange for the potential equalisation. Ground disks can be ordered separately as an accessory from Endress+Hauser (see Page 85). " Caution! · In this case, when using ground disks (including seals) the total fitting length increases! All the dimensions are provided in the separate documentation "Technical Information". · PTFE and PFA lining only install additional seals between the ground disk and pipe flange. 1. Place the ground disk and the additional seal between the instrument and the pipe flange (Fig. 20). 2. Insert the bolts through the flange holes. Tighten the nuts so that they are still loose. 3. Now rotate the ground disk as shown in Fig. 20 until the handle strikes the bolts. This will center the ground disk automatically. 4. Now tighten the bolts to the required torque (see Page 36 ff.) 5. Connect the ground disk to ground Page 58. Fig. 20: Assembly with ground disks (Promag P, DN 15...300) F06-5xFxxxxx-17-05-xx-xx-001 34 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 550 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation ! " Installing the high-temperature version (with PFA lining) The high-temperature version has a housing support for the thermal separation of sensor and transmitter. The high-temperature version is always used for applications in which high ambient temperatures are encountered in conjunction with high fluid temperatures. The high-temperature version is obligatory if the fluid temperature exceeds +150 °C. Note! You will find information on permissible temperature ranges on Page 111 Insulation Pipes generally have to be insulated if they carry very hot fluids, in order to avoid energy losses and to prevent accidental contact with pipes at temperatures that could cause injury. Guidelines regulating the insulation of pipes have to be taken into account. Caution! Risk of measuring electronics overheating. The housing support dissipates heat and its entire surface area must remain uncovered. Make sure that the sensor insulation does not extend past the top of the two sensor shells (Fig. 21). Fig. 21: Promag P (high-temperature version): Insulating the pipe F06-5xPxxxxx-17-05-00-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 35 Page 551 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Tightening torques for threaded fasteners (Promag P) Note the following points: · The tightening torques listed below are for lubricated threads only. · Always tighten threaded fasteners uniformly and in diagonally opposite sequence. · Overtightening the fasteners will deform the sealing faces or damage the seals. · The tightening torques listed below apply only to pipes not subjected to tensile stress. Promag P Nominal diameter [mm] 15 25 32 40 50 65 * 65 80 80 100 100 125 125 150 150 200 200 200 250 250 250 300 300 300 350 350 350 400 400 400 450 450 450 500 500 EN (DIN) Pressure rating [bar] PN 40 PN 40 PN 40 PN 40 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 Threaded fasteners 4 x M 12 4 x M 12 4 x M 16 4 x M 16 4 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 16 8 x M 20 8 x M 16 8 x M 24 8 x M 20 8 x M 24 8 x M 20 12 x M 20 12 x M 24 12 x M 20 12 x M 24 12 x M 27 12 x M 20 12 x M 24 16 x M 27 16 x M 20 16 x M 24 16 x M 30 16 x M 24 16 x M 27 16 x M 33 20 x M 24 20 x M 27 20 x M 33 20 x M 24 20 x M 30 Max. tightening torque [Nm] PTFE PFA 11 - 26 20 41 35 52 47 65 59 43 40 43 40 53 48 53 48 57 51 78 70 75 67 111 99 99 85 136 120 141 101 94 67 138 105 110 - 131 - 200 - 125 - 179 - 204 - 188 - 254 - 380 - 260 - 330 - 488 - 235 - 300 - 385 - 265 - 448 - 36 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 552 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Promag P Nominal diameter EN (DIN) Pressure rating Threaded fasteners [mm] [bar] 500 PN 25 20 x M 33 600 PN 10 20 x M 27 600 * PN 16 20 x M 33 600 PN 25 20 x M 36 * Designed acc. to EN 1092-1 (not to DIN 2501) Max. tightening torque [Nm] PTFE PFA 533 - 345 - 658 - 731 - Promag P Nominal diameter [mm] [inch] 15 1/2" 15 1/2" 25 1" 25 1" 40 1 1/2" 40 1 1/2" 50 2" 50 2" 80 3" 80 3" 100 4" 100 4" 150 6" 150 6" 200 8" 250 10" 300 12" 350 14" 400 16" 450 18" 500 20" 600 24" ANSI Pressure rating [lbs] Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Threaded fasteners 4 x 1/2" 4 x 1/2" 4 x 1/2" 4 x 5/8" 4 x 1/2" 4 x 3/4" 4 x 5/8" 8 x 5/8" 4 x 5/8" 8 x 3/4" 8 x 5/8" 8 x 3/4" 8 x 3/4" 12 x 3/4" 8 x 3/4" 12 x 7/8" 12 x 7/8" 12 x 1" 16 x 1" 16 x 1 1/8" 20 x 1 1/8" 20 x 1 1/4" Max. tightening torque [Nm] PTFE PFA 6 - 6 - 11 10 14 12 24 21 34 31 47 44 23 22 79 67 47 42 56 50 67 59 106 86 73 67 143 109 135 - 178 - 260 - 246 - 371 - 341 - 477 - Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 37 Page 553 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Promag P Nominal diameter [mm] 15 15 25 25 32 32 40 40 50 50 65 65 80 80 100 100 125 125 150 150 200 200 250 250 300 300 JIS Pressure rating Threaded fasteners 10K 4 x M 12 20K 4 x M 12 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 4 x M 16 10K 4 x M 16 20K 8 x M 16 10K 4 x M 16 20K 8 x M 16 10K 8 x M 16 20K 8 x M 20 10K 8 x M 16 20K 8 x M 20 10K 8 x M 20 20K 8 x M 22 10K 8 x M 20 20K 12 x M 22 10K 12 x M 20 20K 12 x M 22 10K 12 x M 22 20K 12 x M 24 10K 16 x M 22 20K 16 x M 24 Max. tightening torque [Nm] PTFE PFA 16 - 16 - 32 - 32 - 38 - 38 - 41 - 41 - 54 - 27 - 74 - 37 - 38 - 57 - 47 - 75 - 80 - 121 - 99 - 108 - 82 - 121 - 133 - 212 - 99 - 183 - Promag P Nominal diameter [mm] 25 50 AS 2129 Pressure rating Threaded fasteners Table E Table E 4 x M 12 4 x M 16 Max. tightening torque [Nm] PTFE 21 42 Promag P Nominal diameter [mm] 50 AS 4087 Pressure rating Threaded fasteners Cl.14 4 x M 16 Max. tightening torque [Nm] PTFE 42 38 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 554 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3.3.3 Installing the Promag H sensor The Promag H is supplied to order, with or without pre-installed process connections. Pre-installed process connections are secured to the sensor with hex-head threaded fasteners. " Caution! · The sensor might require support or additional attachments, depending on the application and the length of the piping run. When plastic process connections are used, the sensor must be addition- ally supported mechanically. A wall-mounting kit can be ordered separately from Endress+Hauser as an accessory (see Page 85). DN 2...25 A DN 40...100 C B Fig. 22: Promag H process connections (DN 2...25, DN 40...100) F06-xxHxxxxx-17-05-xx-xx-000 A: DN 2...25 / process connections with O-rings: Welding flanges (DIN EN ISO 1127, ODT / SMS), flange (EN (DIN), ANSI, JIS), flange PVDF (EN (DIN), ANSI, JIS), external and internal pipe threads, hose connection, PVC adhesive fitting B: DN 2...25 / process connections with aseptic gasket seals: Weld nipples (DIN 11850, ODT / SMS), Clamp (ISO 2852, DIN 32676, L14 AM7), coupling (DIN 11851, DIN 11864-1, SMS 1145), flange DIN 11864-2 C: DN 40...100 / process connections with aseptic gasket seals: Weld nipples (DIN 11850, ODT / SMS), Clamp (ISO 2852, DIN 32676), L14 AM7), coupling (DIN 11851, DIN 11864-1, ISO 2853, SMS 1145), flange DIN 11864-2 Seals When installing the process connections, make sure that the seals are clean and correctly centered. " Caution! · With metallic process connections, you must fully tighten the screws. The process connection forms a metallic connection with the sensor, which ensures a defined compression of the seal. · With plastic process connections, note the max. torques for lubricated threads (7 Nm). With plastic flanges, always use seals between connection and counter flange. · The seals must be replaced periodically, depending on the application, particularly in the case of gasket seals (aseptic version)! The period between changes depends on the frequency of cleaning cycles, the cleaning temperature and the fluid temperature. Replacement seals can be ordered as accessories Page 85. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 39 Page 555 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Usage and assembly of ground rings (DN 2...25) In case the process connections are made of plastic (e.g. flanges or adhesive fittings), the potential between the sensor and the fluid must be equalised using additional ground rings. If the ground rings are not installed this can affect the accuracy of the measurements or cause the destruction of the sensor through the electrochemical erosion of the electrodes. " Caution! · Depending on the option ordered, plastic disks may be installed at the process connections instead of ground rings. These plastic disks serve only as spacers and have no potential equalization func- tion. In addition, they provide a sealing function at the interface between the sensor and process connection. For this reason, with process connections without ground rings, these plastic disks/seals must not be removed, or must always be installed. · Ground rings can be ordered separately from Endress+Hauser as accessories (see Page 85). When placing the order, make certain that the ground ring is compatible with the material used for the electrodes. Otherwise, there is a risk that the electrodes may be destroyed by electroche- mical corrosion! Information about the materials can be found on Page 117. · Ground rings, including the seals, are mounted within the process connections. Therefore, the fitting length is not affected. 1. Loosen the four hexagonal headed bolts (1) and remove the process connection from the sensor (5). 2. Remove the plastic disk (3), including the two O-ring seals (2, 4). 3. Place one seal (2) in the groove of the process connection. 4. Place the metal ground ring (3) on the process connection. 5. Now place the second seal (4) in the groove of the ground ring. 6. Finally, mount the process connection on the sensor again. With plastic process connections, note the max. torques for lubricated threads (7 Nm). 1 2 3 2 4 Fig. 23: Installing ground rings with a Promag H (DN 2...25) 1 = Hexagonal headed bolts (process connection) 2 = O-ring seals 3 = Ground ring or plastic disk (placeholder) 4 = Sensor Promag H A0002651 40 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 556 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation " ! Welding the sensor into the piping (weld nipples) Caution! Risk of destroying the measuring electronics. Make sure that the welding machine is not grounded via the sensor or the transmitter. 1. Tack-weld the Promag H sensor into the pipe. A suitable welding jig can be ordered separately from Endress+Hauser as an accessory (see Page 85). 2. Remove the threaded fasteners from the process-connection flange. Remove the sensor complete with seal from the pipe. 3. Weld the process connection to the pipe. 4. Reinstall the sensor in the pipe. Make sure that everything is clean and that the seal is correctly seated. Note! · If thin-walled foodstuffs pipes are not welded correctly, the heat could damage the installed seal. It is therefore advisable to remove the sensor and the seal prior to welding. · The pipe has to be spread approximately 8 mm to permit disassembly. Cleaning with pigs If pigs are used for cleaning, it is essential to take the inside diameters of measuring tube and process connection into account. All the dimensions and lengths of the sensor and transmitter are provided in the separate documentation "Technical Information". Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 41 Page 557 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 # 3.3.4 Turning the transmitter housing Turning the aluminum field housing Warning! The turning mechanism in devices with EEx d/de or FM/CSA Cl. I Div. 1 classification is not the same as that described here. The procedure for turning these housings is described in the Ex-specific documentation. 1. Loosen the two securing screws. 2. Turn the bayonet catch as far as it will go. 3. Carefully lift the transmitter housing as far as it will go. 4. Turn the transmitter housing to the desired position (max. 2 x 90° in either direction). 5. Lower the housing into position and re-engage the bayonet catch. 6. Retighten the two securing screws. 2 4 5 1 3 6 Fig. 24: Turning the transmitter housing (aluminum field housing) F06-xxxxxxxx-17-06-xx-xx-000 Turning the stainless-steel field housing 1. Loosen the two securing screws. 2. Carefully lift the transmitter housing as far as it will go. 3. Turn the transmitter housing to the desired position (max. 2 x 90° in either direction). 4. Lower the housing into position. 5. Retighten the two securing screws. 3 4 1 2 5 Fig. 25: Turning the transmitter housing (stainless-steel field housing) F06-xxxxxxxx-17-06-xx-xx-001 42 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 558 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation 3.3.5 Turning the local display 1. Remove the cover of the electronics compartment. 2. Press the side latches on the display module and remove it from the electronics compartment cover plate. 3. Rotate the display to the desired position (max. 4 x 45° in each direction), and place it back into the electronics compartment cover plate. 4. Screw the cover of the electronics compartment firmly onto the transmitter housing. Fig. 26: Turning the local display (field housing) F06-xxxxxxxx-07-xx-06-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 43 Page 559 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3.3.6 Installing the wall-mount transmitter housing There are various ways of installing the wall-mount transmitter housing: · Mounted directly on the wall · Installation in control panel (with separate mounting kit, accessories Page 85) · Pipe mounting (with separate mounting kit, accessories Page 85) " Caution! · Make sure that ambient temperature does not exceed the permissible range (20...+60 °C), (optional -40...+60 °C). Install the device at a shady location. Avoid direct sunlight. · Always install the wall-mount housing in such a way that the cable entries are pointing down. Direct wall mounting 1. Drill the holes as illustrated in Fig. 27. 2. Remove the cover of the connection compartment (a). 3. Push the two securing screws (b) through the appropriate bores (c) in the housing. Securing screws (M6): max. Ø 6.5 mm Screw head: max. Ø 10.5 mm 4. Secure the transmitter housing to the wall as indicated. 5. Screw the cover of the connection compartment (a) firmly onto the housing. b 35 90 c a 192 Fig. 27: Mounted directly on the wall 81.5 c A0001130 44 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 560 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3 Installation Panel installation 1. Prepare the opening in the panel (Fig. 28). 2. Slide the housing into the opening in the panel from the front. 3. Screw the fasteners onto the wall-mount housing. 4. Place the threaded rods in the fasteners and screw them down until the housing is seated tightly against the panel. Afterwards, tighten the locking nuts. Additional support is not necessary. 210 +00.5.5 +0.5 245 0.5 ~110 Fig. 28: Panel Installation (wall-mount housing) A0001131 Pipe mounting The assembly should be performed by following the instructions in Fig. 29. " Caution! If the device is mounted to a warm pipe, make certain that the housing temperature does not exceed +60 °C, which is the maximum permissible temperature. Ø 20...70 Endress + Hauser Q-Pulse Id: TMS1594 Fig. 29: Pipe mounting (wall-mount housing) Active: 18/04/2016 ~155 A0001132 45 Page 561 of 1068 3 Installation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 3.4 Installation check Perform the following checks after installing the measuring device in the pipe: Device condition and specifications Notes Is the device damaged (visual inspection)? - Does the device correspond to specifications at the measuring point, including see Page 107 ff. process temperature and pressure, ambient temperature, minimum fluid conductivity, measuring range, etc.? Installation Notes Does the arrow on the sensor nameplate match the direction of flow through the - pipe? Is the plane of the measuring-electrode axis correct? Horizontal Is the position of the Empty Pipe Detection (EPD) electrode correct? see Page 17 Were all threaded fasteners tightened to the specified torques when the sensor was installed? Were the correct seals installed (type, material, installation)? see Chap. 3.3 Promag W Page 26 Promag P Page 33 Promag H Page 39 Are the measuring-point number and labeling correct (visual inspection)? - Process environment / process conditions Are the inlet and outlet runs to respected? Notes Inlet run 5 x DN Outlet run 2 x DN Is the measuring device protected against moisture and direct sunlight? - Is the sensor adequately protected against vibration (attachment, support)? Acceleration up to 2 g by analogy with IEC 600 68-2-6 (see Page 110) 46 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 562 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring # 4 Wiring Warning! · When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to this Operating Manual. Please do not hesitate to contact your Endress+Hauser representative if you have any questions. · If you use remote versions, connect each sensor only to the transmitter having the same serial number. Measuring errors can occur if the devices are not connected in this way. 4.1 Connecting the remote version # 4.1.1 Connecting Promag W / P / H Warning! · Risk of electric shock. Switch off the power supply before opening the device. Do not install or wire the device while it is connected to the power supply. Failure to comply with this precaution can result in irreparable damage to the electronics. · Risk of electric shock. Connect the protective conductor to the ground terminal on the housing before the power supply is applied. Procedure (Fig. 30, Fig. 31): 1. Transmitter: Loosen the screws and remove cover (a) from the connection compartment. 2. Sensor: Remove cover (b) from the connection housing. 3. Feed signal cable (c) and coil cable (d) through the appropriate cable entries. " Caution! Make sure the connecting cables are secured (see Page 25). Risk of damaging the coil driver. Always switch off the power supply before connecting or disconnecting the coil cable. 4. Preterminate signal cable and coil current cable: Promag W, P Refer to the information on Page 49 Promag H Refer to the information on Page 50 5. Establish the connections between sensor and transmitter in accordance with the wiring diagram: Fig. 30, Fig. 31 wiring diagram inside the cover " Caution! Insulate the shields of cables that are not connected to eliminate the risk of short-circuits with neighboring cable shields inside the sensor connection housing. 6. Transmitter: Secure cover (a) on the connection compartment. 7. Sensor: Secure cover (b) on the connection housing. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 47 Page 563 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 2 1 2 1 wht brn a c b Electrode circuit Meas.signal Pipe EPD S1 E1 E2 S2 GND E S 6 5 7 8 4 37 36 Coil circuit 42 41 yel grn brn d n.c. n.c. n.c. 5 7 4 37 E1 E2 GND E 42 41 Fig. 30: Connecting the remote version of Promag W/P F06-5xFxxxxx-04-xx-xx-en-000 a = cover of the connection compartment, b = cover of the sensor connection housing, c = signal cable, d = coil current cable, n.c. = not connected, insulated cable shields a c b Electrode circuit Meas. signal Pipe EPD S1 E1 E2 S2 GND E S 6 5 7 8 4 37 36 Coil circuit 42 41 yel grn wht d n.c. n.c. n.c. 5 7 4 37 E1 E2 GND E 42 41 DN 40...100 DN 2...25 Fig. 31: Connecting the remote version of Promag H F06-5xHxxxxx-04-xx-xx-de-000 a = cover of the connection compartment, b = cover of the sensor connection housing, c = signal cable, d = coil current cable, n.c. = not connected, insulated cable shields 48 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 564 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring Cable termination for the remote version Promag W / Promag P Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end sleeves (Detail B). " Caution!! When fitting the connectors, pay attention to the following points: · Signal cable Make sure that the cable end sleeves do not touch the wire shield on the sensor side. Minimum distance = 1 mm (exception "GND" = green cable). · Coil current cable Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection. TRANSMITTER Signal cable Coil current cable 17 8 100* 80 50 90* 70 50 10 8 A m m n m n m GND n B n Signal cable A0002643 SENSOR m m m Coil current cable 20* 170* 80 50 17 8 20* 160* 70 50 10 8 A B A0002644 A m GND B n ³1 n n m = Red cable sleeves 1.0 mm = White cable sleeves 0.5 mm * = Stripping for armoured cables only A0002646 A m m m B A0002645 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 49 Page 565 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Cable termination for the remote version Promag H Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end sleeves (Detail B). " Caution!! When fitting the connectors, pay attention to the following points: · Signal cable Make sure that the cable end sleeves do not touch the wire shield on the sensor side. Minimum distance = 1 mm (exception "GND" = green cable). · Coil current cable Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection. · On the sensor side, reverse both cable shields approx. 15 mm over the outer jacket. The strain relief ensures an electrical connection with the connection housing. TRANSMITTER Signal cable Coil current cable 17 8 80 50 70 50 10 8 m m n m n m n GND n A B A0002686 SENSOR Signal cable m m m Coil current cable B A0002684 A 80 15 17 8 70 15 40 8 A ³1 n n GND n B m = Red cable sleeves 1.0 mm = White cable sleeves 0.5 mm A m m B A0002647 A0002648 50 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 566 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring 4.1.2 Cable specifications Coil cable: · 2 x 0.75 mm2 PVC cable with common, braided copper shield (Ø approx. 7 mm) · Conductor resistance: 37 /km · Capacitance: core/core, shield grounded: 120 pF/m · Permanent operating temperature: 20...+80 ° · Cable cross-section: max. 2.5 mm2 Signal cable: · 3 x 0.38 mm2 PVC cable with common, braided copper shield (Ø approx. 7 mm) and individually shielded cores · With Empty Pipe Detection (EPD): 4 x 0.38 mm2 PVC cable with common, braided copper shield (Ø approx. 7 mm) and individually shielded cores · Conductor resistance: 50 /km · Capacitance: core/shield: 420 pF/m · Permanent operating temperature: 20...+80 °C · Cable cross-section: max. 2.5 mm2 1 2 3 4 5 6 7 a b F06-5xWxxxxx-04-11-08-xx-003 Fig. 32: Cable cross-section (a = Signal cable, b = Coil current cable) 1 = Core, 2 = Core insulation, 3 = Core shield, 4 = Core jacket, 5 = Core reinforcement, 6 = Cable shield, 7 = Outer jacket As an option, Endress+Hauser can also deliver reinforced connecting cables with an additional, reinforcing metal braid. We recommend such cables for the following cases: · Directly buried cable · Cables endangered by rodents · Device operation which should comply with the IP 68 standard of protection Operation in zones of severe electrical interference: The measuring device complies with the general safety requirements in accordance with EN 61010, the EMC requirements of EN 61326/A1, and NAMUR recommendation NE 21. " Caution! Grounding is by means of the ground terminals provided for the purpose inside the connection housing. Keep the stripped and twisted lengths of cable shield to the terminals as short as possible. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 51 Page 567 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4.2 Connecting the measuring unit # 4.2.1 Transmitter Warning! · Risk of electric shock. Switch off the power supply before opening the device. Do not install or wire the device while it is connected to the power supply. Failure to comply with this precaution can result in irreparable damage to the electronics. · Risk of electric shock. Connect the protective conductor to the ground terminal on the housing before the power supply is applied (not necessary if the power supply is galvanically isolated). · Compare the specifications on the nameplate with the local voltage supply and frequency. The national regulations governing the installation of electrical equipment also apply. 1. Remove the cover of the connection compartment (f) from the transmitter housing. 2. Feed the power supply cable (a) and signal cables (b) through the appropriate cable entries. 3. Connect the cables in accordance with the wiring diagram: Wiring diagram (aluminium housing) Fig. 33 Wiring diagram (stainless steel housing) Fig. 34 Wiring diagram (wall-mount housing) Fig. 35 Terminal assignment Page 54 4. Screw the cover of the connection compartment (f) firmly onto the transmitter housing. f 27 + 26 b e 25 + 24 b 23 d + 22 21 + 20 a N (L-) 2 c g L1 (L+) 1 a F06-xxxxxxxx-04-06-xx-xx-005 Fig. 33: Connecting the transmitter (aluminium field housing). Cable cross-section: max. 2.5 mm2 a Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC Terminal No. 1: L1 for AC, L+ for DC Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 2027 Page 54 c Ground terminal for protective conductor d Ground terminal for signal cable shield e Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF Tool - Fieldtool Package) f Cover of the connection compartment g Securing clamp 52 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 568 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring 27 + 26 b e 25 + 24 b 23 d + 22 21 a + 20 N (L-) 2 c f L1 (L+) 1 a F06-xxxxxxxx-04-06-xx-xx-006 Fig. 34: Connecting the transmitter (stainless-steel field housing). Cable cross-section: max. 2.5 mm2 a Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC Terminal No. 1: L1 for AC, L+ for DC Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 2027 Page 54 c Ground terminal for protective conductor d Ground terminal for signal cable shield e Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF Tool - Fieldtool Package) f Cover of the connection compartment N (L-) L1 (L+) + + + + e 12 20 2122 2324 25 26 27 ab f a c b d Fig. 35: Connecting the transmitter (wall-mount housing). Cable cross-section: max. 2.5 mm2 a Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC Terminal No. 1: L1 for AC, L+ for DC Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 2027 Page 54 c Ground terminal for protective conductor d Ground terminal for signal cable shield e Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF Tool - Fieldtool Package) f Cover of the connection compartment A0001135 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 53 Page 569 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4.2.2 Terminal assignment Order variant 20 (+) / 21 () 50***-***********W - Terminal No. (inputs / outputs) 22 (+) / 23 () 24 (+) / 25 () - - 50***-***********A - - Frequency output 50***-***********D Status input Status output Frequency output 50***-***********S - - Frequency output Ex i 50***-***********T - - Frequency output Ex i Status input (auxiliary input) galvanically isolated, 3...30 V DC, Ri = 5 k Status output Open collector, max. 30 V DC / 250 mA, galvanically isolated, freely configurable Frequency output (passive) Open collector, galvanically isolated, full scale frequency 2...1000 Hz (fmax = 1.25 kHz) 30 V DC, 250 mA Current output (active/passive) galvanically isolated, active: 0/4...20 mA, RL < 700 (HART: RL 250 ) passive: 4...20 mA, supply voltage Vs: 18...30 V DC, Ri 150 Ground connection, power supply Page 52 ff. 26 (+) / 27 () Current output HART Current output HART Current output HART Current output Ex i active, HART Current output Ex i passive, HART 54 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 570 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring ! 4.2.3 HART connection Users have the following connection options at their disposal: · Direct connection to transmitter by means of terminals 26(+) / 27() · Connection by means of the 4...20 mA circuit Note! · The measuring loop's minimum load must be at least 250 . · After commissioning, make the following settings: CURRENT SPAN function "420 mA HART" or "420 mA (25 mA) HART" · See also the documentation issued by the HART Communication Foundation, and in particular HCF LIT 20: "HART, a technical summary". Connection of the HART handheld communicator ³ 250 W 4 3 -27 +26 2 1 Page Up Bksp Delete Page On # % & 1 Copy G H I 4 P Q R S 7 A B C 2 Paste J K L 5 Insert T UV 8 D E F 3 Hot Key M N O 6 + Hot Key W XY Z 9 , ( )` _ < > + * / .0- 375 FIELD COMMUNICATOR F06-xxxxxxxx-04-xx-xx-xx-007 Fig. 36: Electrical connection of the HART handheld communicator: 1 = HART communicator, 2 = power supply, 3 = shield, 4 = other evaluation devices or PLC with passive input Connection of a PC with an operating software In order to connect a PC with an operating software (e.g. "ToF Tool - Fieldtool Package"), a HART modem (e.g. "Commubox FXA 191") is needed. ³ 250 W 4 1 3 RS 232 5 -27 +26 2 F06-xxxxxxxx-04-xx-xx-xx-008 Fig. 37: Electrical connection of a PC with an operating software: 1 = PC with an operating software, 2 = power supply, 3 = shield, 4 = other evaluation devices or PLC with passive input, 5 = HART modem, e.g. Commubox FXA 191 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 55 Page 571 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4.3 Potential equalisation ! 4.3.1 Standard case Perfect measurement is only ensured when the medium and the sensor have the same electrical potential. Most Promag sensors have a standard installed reference electrode which guarantees the required connection. This usually means that additional potential matching measures are unnecessary. Promag W: Reference electrode is standard Promag P: · Reference electrode is standard for electrode materials 1.4435, Alloy C-22 and tantalum. · Reference electrode is optional for electrode material Pt/Rh. Promag H: · No reference electrode. The metallic process connection provides a permanent electrical connection to the fluid. · If the process connections are made of a synthetic material, ground rings have to be used to ensure that potential is equalised (see Page 40). Ground rings can be ordered with the main product structure or as accessories Page 85. Note! For installation in metal pipes, it is advisable to connect the ground terminal of the transmitter housing to the piping. Also, observe company-internal grounding guidelines. Fig. 38: Potential equalisation by means of the transmitter's ground terminal F06-5xxxxxxx-04-xx-xx-xx-002 " Caution! For sensors without reference electrodes or without metal process terminals, carry out potential equalisation as per the instructions for special cases described below. These special measures are particularly important when standard grounding practice cannot be ensured or extremely strong matching currents are expected. 56 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 572 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring " ! 4.3.2 Special cases Metal, ungrounded piping In order to prevent outside influences on measurement, it is advisable to use ground cables to connect each sensor flange to its corresponding pipe flange and ground the flanges. Connect the transmitter or sensor connection housing, as applicable, to ground potential by means of the ground terminal provided for the purpose (Fig. 39). Caution! Also, observe company-internal grounding guidelines. Note! The ground cable for flange-to-flange connections can be ordered separately as an accessory from Endress+Hauser Page 85. · DN 300: The ground cable is in direct connection with the conductive flange coating and is secured by the flange screws. · DN 350: The ground cable connects directly to the metal transport bracket. 6 mm² Cu DN 300 DN 350 F06-5xxxxxxx-04-xx-xx-xx-003 Fig. 39: Potential equalisation with equalising currents in metallic, non-grounded piping systems Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 57 Page 573 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Plastic pipes and isolating lined pipes Normally, potential is matched using the reference electrodes in the measuring tube. However, in exceptional cases it is possible that, due to the grounding plan of a system, large matching currents flow over the reference electrodes. This can lead to destruction of the sensor, e.g. through electrochemical decomposition of the electrodes. In such cases, e.g. for fibre-glass or PVC piping, it is recommended that you use additional ground disks for potential matching (Fig. 40). Mounting of ground disks Page 27, 34 " Caution! · Risk of damage by electrochemical corrosion. Note the electrochemical insulation rating, if the ground disks and measuring electrodes are made of different materials. · Also, observe company-internal grounding guidelines. Fig. 40: Potential equalisation/ground disks with plastic pipes or lined pipes F06-5xxxxxxx-04-xx-xx-xx-004 Lined pipes (cathodic protection) In such cases, install the measuring instrument without potential in the piping: · When installing the measuring device, make sure that there is an electrical connection between the two piping runs (copper wire, 6 mm2). · Make sure that the installation materials do not establish a conductive connection to the measu- ring device and that the installation materials withstand the tightening torques applied when the threaded fasteners are tightened. · Also comply with the regulations applicable to potential-free installation. Fig. 41: Potential equalisation and cathode protection 1 = isolating transformer power supply, 2 = electrically insulated 58 Q-Pulse Id: TMS1594 Active: 18/04/2016 F06-5xxxxxxx-04-xx-xx-xx-005 Endress + Hauser Page 574 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4 Wiring 4.4 Degree of protection The devices fulfill all the requirements for IP 67. Compliance with the following points is mandatory following installation in the field or servicing, in order to ensure that IP 67 protection is maintained: · The housing seals must be clean and undamaged when inserted into their grooves. The seals must be dried, cleaned or replaced if necessary. · All threaded fasteners and screw covers must be firmly tightened. · The cables used for connection must be of the specified outside diameter (see Page 108). · Firmly tighten the cable entries (Fig. 42). · The cables must loop down before they enter the cable entries ("water trap", Fig. 42). This arrangement prevents moisture penetrating the entry. Always install the measuring device in such a way that the cable entries do not point up. · Remove all unused cable entries and insert plugs instead. · Do not remove the grommet from the cable entry. " ! Fig. 42: Installation instructions, cable entries F06-xxxxxxxx-04-xx-xx-xx-005 Caution! Do not loosen the threaded fasteners of the Promag sensor housing, as otherwise the degree of protection guaranteed by Endress+Hauser no longer applies. Note! The Promag W and Promag P sensors can be supplied with IP 68 rating (permanent immersion in water to a depth of 3 meters). In this case the transmitter must be installed remote from the sensor. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 59 Page 575 of 1068 4 Wiring WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 4.5 Electical connection check Perform the following checks after completing electrical installation of the measuring device: Device condition and specifications Notes Are cables or the device damaged (visual inspection)? - Electrical connection Notes Does the supply voltage match the specifications on the nameplate? 85...260 V AC (45...65 Hz) 20...55 V AC (45...65 Hz) 16...62 V DC Do the cables comply with the specifications? see Page 51, 108 Do the cables have adequate strain relief? - Cables correctly segregated by type? - Without loops and crossovers? Are the power-supply and signal cables correctly connected? See the wiring diagram inside the cover of the terminal compartment Are all screw terminals firmly tightened? - Have the measures for grounding/potential equalisation been correctly implemen- see Page 56 ff. ted? Are all cable entries installed, firmly tightened and correctly sealed? Cables looped see Page 59 as "water traps"? Are all housing covers installed and firmly tightened? - 60 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 576 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation 5 Operation 5.1 Display and operating elements The local display enables you to read all important parameters directly at the measuring point and configure the device. The display area consists of two lines; this is where measured values are displayed, and/or status variables (direction of flow, partially filled pipe, bar graph, etc.). You can change the assignment of display lines to variables at will in order to customize the display to suit your needs and preferences ( see the "Description of Device Functions" manual). +48.25 xx/yy 1 +3702.6 x Esc -+E 2 3 Fig. 43: Display and operating elements A0001141 Liquid-crystal display (1) The backlit, two-line liquid-crystal display shows measured values, dialog texts, error messages and information messages. The display as it appears when normal measuring is in progress is known as the HOME position (operating mode). Upper display line: Shows primary measured values, e.g. volume flow in [ml/min] or in [%]. Lower display line: Shows supplementary measured variables and status variables, e.g. totalizer reading in [m3], bar graph, measuring point designation Push buttons (2) Enter numerical values, select parameters Select different function groups within the function matrix Press the +/- keys simultaneously to trigger the following functions: Exit the function matrix step by step HOME position Press and hold down +/- keys for longer than 3 seconds Return directly to HOME position Cancel data entry Enter push button (3) HOME position Entry into the function matrix Save the numerical values you input or settings you change Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 61 Page 577 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 5.2 Brief operating instruction to the function matrix Note! · See the general notes on Page 63. · Function descriptions see the "Description of Device Functions" manual 1. HOME position F Enter the function matrix 2. Select a function group (e.g. CURRENT OUTPUT 1) 3. Select a function (e.g. TIME CONSTANT) Change parameter / enter numerical values: O S select or enter enable code, parameters, numerical values F save your entries 4. Exit the function matrix: Press and hold down Esc key (X) for longer than 3 seconds HOME position Repeatedly press Esc key (X) return step by step to HOME position Esc -+ E mE p Esc + Esc + >3s o E Esc + E E E E n + E E E E Fig. 44: Selecting functions and configuring parameters (function matrix) 62 Q-Pulse Id: TMS1594 Active: 18/04/2016 A0001142 Endress + Hauser Page 578 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation ! " " 5.2.1 General notes The Quick Setup menu (see Page 80) is adequate for commissioning in most instances. Complex measuring operations on the other hand necessitate additional functions that you can configure as necessary and customize to suit your process parameters. The function matrix, therefore, comprises a multiplicity of additional functions which, for the sake of clarity, are arranged in a number of function groups. Comply with the following instructions when configuring functions: · You select functions as described on Page 62. · You can switch off certain functions (OFF). If you do so, related functions in other function groups will no longer be displayed. · Certain functions prompt you to confirm your data entries. Press OS to select "SURE [ YES ]" and press F again to confirm. This saves your setting or starts a function, as applicable. · Return to the HOME position is automatic if no key is pressed for 5 minutes. Note! · The transmitter continues to measure while data entry is in progress, i.e. the current measured values are output via the signal outputs in the normal way. · If the power supply fails, all preset and parameterized values remain safely stored in the EEPROM. Caution! All functions are described in detail, including the function matrix itself, in the "Description of Device Functions" manual, which is a separate part of this Operating Instruction. 5.2.2 Enabling the programming mode The function matrix can be disabled. Disabling the function matrix rules out the possibility of inadvertent changes to device functions, numerical values or factory settings. A numerical code (factory setting = 50) has to be entered before settings can be changed. If you use a code number of your choice, you exclude the possibility of unauthorized persons accessing data ( see the "Description of Device Functions" manual). Comply with the following instructions when entering codes: · If programming is disabled and the OS key is pressed in any function, a prompt for the code automatically appears on the display. · If "0" is entered as the customer's code, programming is always enabled. · The Endress+Hauser service organisation can be of assistance if you mislay your personal code. Caution! Changing certain parameters such as all sensor characteristics, for example, influences numerous functions of the entire measuring system, particularly measuring accuracy. There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions. 5.2.3 Disabling the programming mode Programming is disabled if you do not press a key within 60 seconds following automatic return to the HOME position. You can also disable programming in the "ACCESS CODE" function by entering any number (other than the customer's code). Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 63 Page 579 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5.3 Error messages Type of error Errors which occur during commissioning or measuring operation are displayed immediately. If two or more system or process errors occur, the error with the highest priority is the one shown on the display. The measuring system distinguishes between two types of error: · System errors: This group comprises all device errors, e.g. communication errors, hardware faults, etc. see Page 90 · Process errors: This group comprises all application errors, e.g. empty pipe, etc. see Page 93 1 P XXXXXXXXXX #000 00:00:05 ! 2 4 5 3 Fig. 45: Error messages on the display (example) 1 Error type: P = process error, S = system error 2 Error message type: $ = fault message; ! = notice message 3 Error designation: e.g. EMPTY PIPE = measuring tube is only partly filled or completely empty 4 Error number: e.g. #401 5 Duration of most recent error occurrence in hours / minutes / seconds A0000991 Error message types Users have the option of weighting certain errors differently, in other words having them classed as "Fault messages" or "Notice messages". You can define messages in this way with the aid of the function matrix see the "Description of Device Functions" manual. Serious system errors, e.g. module defects, are always identified and classed as "fault messages" by the measuring device. Notice message (!) · Displayed as Exclamation mark (!), error type (S: system error, P: process error). · The error in question has no effect on the outputs of the measuring device. Fault message ( $) · Displayed as Lightning flash ( $), error type (S: system error, P: process error). · The error in question has a direct effect on the outputs. The response of the outputs (failsafe mode) can be defined by means of functions in the function matrix (see Page 95). Note! For security reasons, error messages should be output via the status output. 64 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 580 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation ! 5.4 Communication In addition to local operation, the measuring device can be configured and measured values can be obtained by means of the HART protocol. Digital communication takes place using the 420 mA current output HART (see Page 55). The HART protocol allows the transfer of measuring and device data between the HART master and the field devices for configuration and diagnostics purposes. The HART master, e.g. a handheld terminal or PC-based operating programs (such as ToF Tool - Fieldtool Package), require device description (DD) files which are used to access all the information in a HART device. Information is exclusively transferred using so-called "commands". There are three different command groups: Universal commands: All HART device support and use universal commands. The following functionalities are linked to them: · Identify HART devices · Reading digital measured values (volume flow, totalizer, etc.) Common practice commands: Common practice commands offer functions which are supported and can be executed by most but not all field devices. Device-specific commands: These commands allow access to device-specific functions which are not HART standard. Such commands access individual field device information, amongst other things, such as empty/full pipe calibration values, low flow cutoff settings, etc. Note! Promag 50 has access to all three command classes. On Page 69, you will find a list with all the supported "Universal Commands" and "Common Practice Commands". Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 65 Page 581 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 5.4.1 Operating options For the complete operation of the measuring device, including device-specific commands, there are DD files available to the user to provide the following operating aids and programs: Note! The HART protocol requires the "4...20 mA HART" setting (individual options see device function) in the CURRENT SPAN function (current output 1). HART handheld terminal DXR 375 Selecting device functions with a HART Communicator is a process involving a number of menu levels and a special HART function matrix. The HART manual in the carrying case of the HART Communicator contains more detailed information on the device. Operating program "ToF Tool - Fieldtool Package" Modular software package consisting of the service program "ToF Tool" for configuration and diagnosis of ToF level measuring devices (time-of-flight measurement) and evolution of pressure measuring instruments as well as the "Fieldtool" service program for the configuration and diagnosis of Proline flow measuring devices. The Proline flow measuring devices are accessed via a service interface or via the service interface FXA 193 or the HART protocol. Contents of the "ToF Tool - Fieldtool Package": · Commissioning, maintenance analysis · Configuring flowmeters · Service functions · Visualisation of process data · Trouble-shooting · Controlling the "Fieldcheck" tester/simulator Fieldcare FieldCare is Endress+Hauser's FDT-based plant Asset Management Tool and allows the configuration and diagnosis of intelligent field devices. By using status information, you also have a simple but effective tool for monitoring devices. The Proline flow measuring devices are accessed via a service interface or via the service interface FXA 193. Operating program "SIMATIC PDM" (Siemens) SIMATIC PDM is a standardised, manufacturer-independent tool for the operation, configuration, maintenance and diagnosis of intelligent field devices. Operating program "AMS" (Emerson Process Management) AMS (Asset Management Solutions): program for operating and configuring devices 66 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 582 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation 5.4.2 Current device description files The following table illustrates the suitable device description file for the operating tool in question and then indicates where these can be obtained. HART protocol: Valid for software: Device data HART Manufacturer ID: Device ID: HART version data: Software release: Operating program: Handheld terminal DXR 375 ToF Tool - Fieldtool Package Fieldcare / DTM AMS SIMATIC PDM 2.00.XX Function "Device software" 11hex (ENDRESS+HAUSER) 41hex Device Revison 6/ DD Revision 1 Function "Manufacturer ID" Function "Device ID" 03.2005 Sources for obtaining device descriptions: · Use update function of handheld terminal · www.tof-fieldtool.endress.com ( Download Software Device driver) · CD-ROM (Endress+Hauser order number 50097200) · www.endress.com ( Download Software Device driver) · CD-ROM (Endress+Hauser order number 50097200) · www.endress.com ( Download Software Device driver) · CD-ROM (Endress+Hauser order number 50097200) · www.endress.com ( Download Software Device driver) · CD-ROM (Endress+Hauser order number 50097200) Operation via the service protocol Valid for device software: 2.00.XX Function "Device software" Software release: 03.2005 Operating program: Sources for obtaining device descriptions: ToF Tool - Fieldtool Package · www.tof-fieldtool.endress.com ( Download Software Device driver) · CD-ROM (Endress+Hauser order number 50097200) Tester/simulator: Fieldcheck Sources for obtaining device descriptions: · Update by means of ToF Tool - Fieldtool Package via Fieldflash module Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 67 Page 583 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 5.4.3 Device and process variables Device variables: The following device variables are available using the HART protocol: Code (decimal) 0 1 250 251 Device variable OFF (not assigned) Volume flow Totalizer 1 Totalizer 2 Process variables: At the factory, the process variables are assigned to the following device variables: · Primary process variable (PV) Volume flow · Second process variable (SV) Totalizer 1 · Third process variable (TV) not assigned · Fourth process variable (FV) not assigned Note! You can set or change the assignment of device variables to process variables using Command 51 (see Page 73). 68 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 584 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation 5.4.4 Universal / Common practice HART commands The following table contains all the universal and common practice commands supported by Promag 50. Command No. HART command / Access type Universal Commands 0 Read unique device identifier Access type = read Command data (numeric data in decimal form) none 1 Read primary process variable none Access type = read 2 Read the primary process variable none as current in mA and percentage of the set measuring range Access type = read Response data (numeric data in decimal form) Device identification delivers information on the device and the manufacturer. It cannot be changed. The response consists of a 12 byte device ID: Byte 0: fixed value 254 Byte 1: Manufacturer ID, 17 = E+H Byte 2: Device type ID, 65 = Promag 50 Byte 3: Number of preambles Byte 4: Universal commands rev. no. Byte 5: Device-specific commands rev. no. Byte 6: Software revision Byte 7: Hardware revision Byte 8: Additional device information Bytes 9-11: Device identification Byte 0: HART unit code of the primary process variable Bytes 1-4: Primary process variable Factory setting: Primary process variable = Volume flow ! Note! · You can set the assignment of device variables to process variables using Command 51. · Manufacturer-specific units are represented using the HART unit code "240". Bytes 0-3: actual current of the primary process variable in mA Bytes 4-7: Percentage of the set measuring range Factory setting: Primary process variable = Volume flow ! Note! You can set the assignment of device variables to process variables using Command 51. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 69 Page 585 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Command No. HART command / Access type Command data (numeric data in decimal form) 3 Read the primary process variable none as current in mA and four (preset using Command 51) dynamic process variables Access type = read Response data (numeric data in decimal form) 24 bytes are sent as a response: Bytes 0-3: primary process variable current in mA Byte 4: HART unit code of the primary process variable Bytes 5-8: Primary process variable Byte 9: HART unit code of the second process variable Bytes 10-13: Second process variable Byte 14: HART unit code of the third process variable Bytes 15-18: Third process variable Byte 19: HART unit code of the fourth process variable Bytes 20-23: Fourth process variable 6 Set HART shortform address Byte 0: desired address (0...15) Factory setting: · Primary process variable = Volume flow · Second process variable = Totalizer 1 · Third process variable = not assigned · Fourth process variable = not assigned ! Note! · You can set the assignment of device variables to process variables using Command 51. · Manufacturer-specific units are represented using the HART unit code "240". Byte 0: active address Access type = write Factory setting: 0 ! Note! With an address >0 (multidrop mode), the current output of the primary process variable is set to 4 mA. 11 Read unique device identification Bytes 0-5: TAG using the TAG (measuring point designation) Access type = read Device identification delivers information on the device and the manufacturer. It cannot be changed. The response consists of a 12 byte device ID if the given TAG agrees with the one saved in the device: Byte 0: fixed value 254 Byte 1: Manufacturer ID, 17 = E+H Byte 2: Device type ID, 65 = Promag 50 Byte 3: Number of preambles Byte 4: Universal commands rev. no. Byte 5: Device-specific commands rev. no. Byte 6: Software revision Byte 7: Hardware revision Byte 8: Additional device information Bytes 9-11: Device identification 12 Read user message none Bytes 0-24: User message Access type = read ! Note! You can write the user message using Command 17. 70 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 586 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation Command No. HART command / Access type 13 Read TAG, descriptor and date Access type = read Command data (numeric data in decimal form) none 14 Read sensor information on none primary process variable 15 Read output information of pri- none mary process variable Access type = read Response data (numeric data in decimal form) Bytes 0-5: TAG Bytes 6-17: descriptor Bytes 18-20: Date ! Note! You can write the TAG, descriptor and date using Command 18. Bytes 0-2: Sensor serial number Byte 3: HART unit code of sensor limits and measuring range of the primary process variable Bytes 4-7: Upper sensor limit Bytes 8-11: Lower sensor limit Bytes 12-15: Minimum span ! Note! · The data relate to the primary process variable (= volume flow). · Manufacturer-specific units are represented using the HART unit code "240". Byte 0: Alarm selection ID Byte 1: Transfer function ID Byte 2: HART unit code for the set measuring range of the primary process variable Bytes 3-6: upper range, value for 20 mA Bytes 7-10: lower range, value for 4 mA Bytes 11-14: Damping constant in [s] Byte 15: Write protection ID Byte 16: OEM dealer ID, 17 = E+H 16 Read the device production num- none ber Factory setting: Primary process variable = Volume flow ! Note! · You can set the assignment of device variables to process variables using Command 51. · Manufacturer-specific units are represented using the HART unit code "240". Bytes 0-2: Production number Access type = read 17 Write user message Access = write You can save any 32-character long text in the device under this parameter: Bytes 0-23: Desired user message Displays the current user message in the device: Bytes 0-23: Current user message in the device 18 Write TAG, descriptor and date With this parameter, you can store an 8 character TAG, a 16 character descriptor and a date: Access = write Bytes 0-5: TAG Bytes 6-17: descriptor Bytes 18-20: Date Displays the current information in the device: Bytes 0-5: TAG Bytes 6-17: descriptor Bytes 18-20: Date Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 71 Page 587 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Command No. HART command / Access type Command data (numeric data in decimal form) Response data (numeric data in decimal form) Common Practice Commands 34 Write damping value for primary Bytes 0-3: Damping value of the primary process vari- Displays the current damping value in the device: process variable able in seconds Bytes 0-3: Damping value in seconds Access = write Factory setting: Primary process variable = Volume flow 35 Write measuring range of primary Write the desired measuring range: The currently set measuring range is displayed as a process variable Byte 0: HART unit code of the primary process response: variable Access = write Bytes 1-4: upper range, value for 20 mA Byte 0: HART unit code for the set measuring range Bytes 5-8: lower range, value for 4 mA of the primary process variable Bytes 1-4: upper range, value for 20 mA Factory setting: Bytes 5-8: lower range, value for 4 mA Primary process variable = Volume flow ! Note! ! Note! Manufacturer-specific units are represented using the · You can set the assignment of device variables to HART unit code "240". process variables using Command 51. · If the HART unit code is not the correct one for the process variable, the device will continue with the last valid unit. 38 Device status reset (Configura- none none tion changed) Access = write 40 Simulate output current of primary process variable Access = write Simulation of the desired output current of the primary process variable. An entry value of 0 exits the simulation mode: Bytes 0-3: Output current in mA The momentary output current of the primary process variable is displayed as a response: Bytes 0-3: Output current in mA 42 Perform master reset Factory setting: Primary process variable = Volume flow ! Note! You can set the assignment of device variables to process variables using Command 51. none none Access = write 44 Write unit of primary process vari- Set unit of primary process variable. Only unit which The current unit code of the primary process variable is able are suitable for the process variable are transferred to displayed as a response: the device: Access = write Byte 0: HART unit code Byte 0: HART unit code Factory setting: Primary process variable = Volume flow ! Note! Manufacturer-specific units are represented using the HART unit code "240". ! Note! · If the written HART unit code is not the correct one for the process variable, the device will continue with the last valid unit. · If you change the unit of the primary process variable, this has no impact on the system units. 48 Read additional device status none Access = read The device status is displayed in extended form as the response: Coding: see table on Page 74 72 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 588 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation Command No. HART command / Access type 50 Read assignment of the device variables to the four process variables Command data (numeric data in decimal form) none Access = read Response data (numeric data in decimal form) Display of the current variable assignment of the process variables: Byte 0: Device variable code to the primary process variable Byte 1: Device variable code to the second process variable Byte 2: Device variable code to the third process variable Byte 3: Device variable code to the fourth process variable Factory setting: · Primary process variable: Code 1 for volume flow · Second process variable: Code 250 for totalizer 1 · Third process variable: Code 0 for OFF (not assig- ned) · Fourth process variable: Code 0 for OFF (not assig- ned) ! Note! You can set or change the assignment of device variables to process variables using Command 51. 51 Write assignments of the device Setting of the device variables to the four process The variable assignment of the process variables is variables to the four process variables: displayed as a response: variables Byte 0: Device variable code to the primary process Byte 0: Device variable code to the primary process Access = write variable variable Byte 1: Device variable code to the second process Byte 1: Device variable code to the second process variable variable Byte 2: Device variable code to the third process Byte 2: Device variable code to the third process variable variable Byte 3: Device variable code to the fourth process Byte 3: Device variable code to the fourth process variable variable Code of the supported device variables: See data on Page 68 Factory setting: · Primary process variable = Volume flow · Second process variable = Totalizer 1 · Third process variable = OFF (not assigned) · Fourth process variable = OFF (not assigned) 53 Write device variable unit Access = write This command set the unit of the given device variables. Only those units which suit the device variable are transferred: Byte 0: Device variable code Byte 1: HART unit code Code of the supported device variables: See data on Page 68 ! Note! · If the written unit is not the correct one for the device variable, the device will continue with the last valid unit. · If you change the unit of the device variable, this has no impact on the system units. The current unit of the device variables is displayed in the device as a response: Byte 0: Device variable code Byte 1: HART unit code ! Note! Manufacturer-specific units are represented using the HART unit code "240". 59 Write number of preambles in This parameter sets the number of preambles which As a response, the current number of the preambles is response message are inserted in the response messages: displayed in the response message: Access = write Byte 0: Number of preambles (2...20) Byte 0: Number of preambles Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 73 Page 589 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 5.4.5 Device status / Error messages You can read the extended device status, in this case, current error messages, via Command "48". The command delivers information which are partly coded in bits (see table below). Note! You can find a detailed explanation of the device status and error messages and their elimination on Page 90 ff. Byte Bit 0-0 0-1 0-2 0-3 0-4 0-5 0-6 0-7 1-0 1-1 1-2 1-3 1-4 1-5 1-6 1-7 2-0 2-1 2-2 2-3 2-4 2-5 2-6 2-7 3-0 3-1 3-2 3-3 3-4 3-5 3-6 3-7 4-0 4-1 4-2 4-3 4-4 Error No. 001 011 012 not assigned not assigned not assigned not assigned not assigned not assigned 031 032 not assigned not assigned 051 not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned 111 121 not assigned not assigned not assigned not assigned not assigned not assigned 251 261 Short error description ( Page 90 ff. ) Serious device error Measuring amplifier has faulty EEPROM Error when accessing data of the measuring amplifier EEPROM S-DAT: defective or missing S-DAT: Error accessing saved values I/O board and the amplifier board are not compatible. Totalizer checksum error I/O board and the amplifier board are not compatible. Internal communication fault on the amplifier board. No data reception between amplifier and I/O board 74 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 590 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 5 Operation Endress + Hauser Q-Pulse Id: TMS1594 Byte Bit 4-5 4-6 4-7 5-0 5-1 5-2 5-3 5-4 5-5 5-6 5-7 6-0 6-1 6-2 6-3 6-4 6-5 6-6 6-7 7-0 7-1 7-2 7-3 7-4 7-5 7-6 7-7 8-0 8-1 8-2 8-3 8-4 8-5 8-6 8-7 9-0 9-1 9-2 9-3 9-4 9-5 9-6 9-7 Error No. not assigned not assigned not assigned 321 not assigned not assigned not assigned not assigned not assigned not assigned 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned Short error description ( Page 90 ff. ) Coil current of the sensor is outside the tolerance. Flow buffer: The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds. Frequency buffer: The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds. Pulse buffer: The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds. Current output: flow is out of range. Frequency output: flow is out of range. Pulse output: the pulse output frequency is out of range. Active: 18/04/2016 75 Page 591 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Byte Bit 10-0 10-1 10-2 10-3 10-4 10-5 10-6 10-7 11-0 11-1 11-2 11-3 11-4 11-5 11-6 11-7 12-0 12-1 12-2 12-3 12-4 12-5 12-6 12-7 13-0 13-1 13-2 13-3 13-4 13-5 13-6 13-7 14-0 14-1 14-2 14-3 14-4 14-5 14-6 Error No. not assigned not assigned not assigned not assigned not assigned not assigned not assigned 401 not assigned not assigned 461 not assigned 463 not assigned not assigned not assigned not assigned 474 not assigned not assigned not assigned not assigned not assigned 501 502 not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned 601 not assigned not assigned not assigned Short error description ( Page 90 ff. ) Measuring tube partially filled or empty EPD calibration not possible because the fluid's conductivity is either too low or too high. The EPD calibration values for empty pipe and full pipe are identical, therefore incorrect. Maximum flow value entered is overshot. New amplifier software version is loaded. Currently no other commands are possible. Upload and download of device files. Currently no other commands are possible. Positive zero return active 76 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 592 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Byte Bit 14-7 15-0 15-1 15-2 15-3 15-4 15-5 15-6 15-7 16-0 16-1 16-2 16-3 16-4 16-5 16-6 16-7 17-0 17-1 17-2 17-3 17-4 17-5 17-6 17-7 18-0 18-1 18-2 18-3 18-4 18-5 18-6 18-7 Error No. 611 612 613 614 621 622 623 624 631 632 633 634 641 642 643 644 not assigned not assigned not assigned not assigned not assigned not assigned not assigned not assigned 671 672 673 674 691 692 not assigned not assigned not assigned Short error description ( Page 90 ff. ) Simulation current output active Simulation frequency output active Simulation pulse output active Simulation status output active Simulation status input active Simulation status input active Simulation status input active Simulation status input active Simulation of response to error (outputs) active Simulation of volume flow active 5 Operation Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 77 Page 593 of 1068 5 Operation WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 78 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 594 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 6 Commissioning 6 Commissioning 6.1 Function check Make sure that all final checks have been completed before you start up your measuring point: · Checklist for "Installation check" Page 46 · Checklist for "Electrical connection check" Page 60 6.1.1 Switching on the measuring device Once the connection checks (see Page 60) have been successfully completed, it is time to switch on the power supply. The device is now operational. The measuring device performs a number of post switch-on self-tests. As this procedure progresses the following sequence of messages appears on the local display: ! PROMAG 50 START UP ... DEVICE SOFTWARE V XX.XX.XX SYSTEM OK OPERATION Start-up message Current software version Beginning of normal measuring mode Normal measuring mode commences as soon as start-up completes. Various measured-value and/or status variables (HOME position) appear on the display. Note! If start-up fails, an error message indicating the cause is displayed. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 79 Page 595 of 1068 6 Commissioning WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 ! 6.2 Application-specific commissioning In the case of measuring devices without a local display, the individual parameters and functions must be configured via the configuration program, e.g. ToF Tool - Fieldtool Package. If the measuring device is equipped with a local display, all the important device parameters for standard operation can be configured quickly and easily by means of the "Commissioning" Quick Setup menu. · Quick Setup "Commissioning", Page 3 ff. 6.2.1 "Commissioning" Quick Setup menu This Quick Setup menu guides you systematically through the setup procedure for all the major device functions that have to be configured for standard measuring operation. Note! In the case of measuring devices without a local display, the individual parameters and functions must be configured by means of a configuration program, such as ToF Tool - Fieldtool Package from Endress+Hauser. ENDRESS+HAUSER - + E ESC E ++ HOME-POSITION Quick Setup E+ QS Commission Language Defaults Unit Volume flow Measuring Mode Current Output Freq.-/ Pulse Output Quit Operation Mode Assign Current Current Span Value 20 mA Time Constant Failsafe Mode Frequency Assign Frequency End Value Freq. Value f max Output Signal Time Constant Failsafe Mode Pulse Assign Pulse Pulse Value Pulse Width Output Signal Failsafe Mode Automatic parameterization of the display Quit Quick Setup Fig. 46: Quick Setup for commissioning 80 Q-Pulse Id: TMS1594 Active: 18/04/2016 F06-50xxxxxx-19-xx-xx-en-000 Endress + Hauser Page 596 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 6 Commissioning " ! 6.2.2 Empty-pipe/full-pipe adjustment Flow cannot be measured correctly unless the measuring tube is completely full. This status can be permanently monitored using the Empty Pipe Detection: · EPD = Empty Pipe Detection (with the help of an EPD electrode) · OED = Open Electrode Detection (Empty Pipe Detection with the help of the measuring electro- des, if the sensor is not equipped with an EPD electrode or the orientation is not suitable for using EPD). Caution! A detailed description and other helpful hints for the empty-pipe/full-pipe adjustment procedure can be found in the separate "Description of Device Functions" Manual: · EPD/OED ADJUSTMENT Carrying out the adjustment. · EPD Switching on and off EPD/OED. · EPD RESPONSE TIME Input of the response time for EPD/OED. Note! · The EPD function is not available unless the sensor is fitted with an EPD electrode. · The devices are already calibrated at the factory with water (approx. 500 µS/cm). If the fluid conductivity differs from this reference, empty-pipe/full-pipe adjustment has to be performed again on site. · The default setting for EPD/OED when the devices are delivered is OFF; the function has to be activated if required. · The EPD/OED process error can be output by means of the configurable status output. Performing empty-pipe and full-pipe adjustment (EPD/OED) 1. Select the appropriate function in the function matrix: HOME F R PROCESS PARAMETER F R EPD/OED ADJUSTMENT 2. Empty the piping. In case of an EPD adjustment, the wall of the measuring tube should be wetted with fluid for the adjustment procedure but this is not the case with an OED adjustment. 3. Start empty-pipe adjustment: Select "EMPTY PIPE ADJUST" or "OED EMPTY ADJUST" and press F to confirm. 4. After empty-pipe adjustment, fill the piping with fluid. 5. Start full-pipe adjustment: Select "FULL PIPE ADJUST" or "OED FULL ADJUST" and press F to confirm. 6. Having completed the adjustment, select the setting "OFF" and exit the function by pressing F . 7. Now select the "EPD" function. Switch on Empty Pipe Detection by selecting the following settings: EPD Select ON STANDARD or ON SPECIAL and press F to confirm. OED Select OED and confirm with F . " Caution! The adjustment coefficients must be valid before you can activate the EPD/OED function. If adjustment is incorrect the following messages might appear on the display: FULL = EMPTY The adjustment values for empty pipe and full pipe are identical. In cases of this nature you must repeat empty-pipe or full-pipe adjustment! ADJUSTMENT NOT OK Adjustment is not possible because the fluid's conductivity is out of range. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 81 Page 597 of 1068 6 Commissioning WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 # 6.2.3 Current output: active/passive The current output is configured as "active" or "passive" by means of various jumpers on the I/O board. Warning! · Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. · Wait at least 10 minutes for heat to dissipate before opening an Ex-rated device. 1. Switch off power suppy. 2. Remove the I/O board Page 98, 100 3. Position the jumper according to Fig. 47. " Caution! Risk of destroying the measuring device. Set the jumpers exactly as shown in Fig. 47. Incorrectly set jumpers can cause overcurrents that would destroy either the measuring device or external devices connected to it. 4. Installation of the I/O board is the reverse of the removal procedure. 1 2 Fig. 47: Configuring the current output (I/O board) 1 Active current output (Factory setting) 2 Passive current output A0001044 6.3 Data storage device (HistoROM) At Endress+Hauser, the term HistoROM refers to various types of data storage modules on which process and measuring device data are stored. 6.3.1 HistoROM/S-DAT (sensor-DAT) The S-DAT is an exchangeable data storage device in which all sensor relevant parameters are stored, i.e., diameter, serial number, calibration factor, zero point. 82 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 598 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 7 Maintenance 7 Maintenance The Promag 50 flow measuring system requires no special maintenance. 7.1 Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing and the seals. 7.2 Seals The seals of the Promag H sensor must be replaced periodically, particularly in the case of gasket seals (aseptic version). The period between changes depends on the frequency of cleaning cycles, the cleaning temperature and the fluid temperature. Replacement seals (accessories) Page 85. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 83 Page 599 of 1068 7 Maintenance WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 84 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 600 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 8 Accessories 8 Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. The Endress+Hauser service organisation can provide detailed information on the order codes of your choice. 8.1 Device-specific accessories Accessory Transmitter Promag 50 Description Transmitter for replacement or for stock. Use the order code to define the following specifications: Approvals Degree of protection / version Cable type for the remote version Cable entries Display / power supply / operation Software Outputs / inputs Order code 50XXX - XXXXX * * * * * * * * Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 85 Page 601 of 1068 8 Accessories WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 8.2 Measuring principle-specific accessories Accessory Description Mounting kit for transmitter Promag 50/53 Mounting kit for wall-mounted housing (remote version). Suitable for: Wall mounting Post mounting Installation in control panel Order code DK5WM - * Cable for remote version Ground cable for Promag W, P Ground disk for Promag W, P Mounting kit for Promag H Adapter connection for Promag A, H Ground rings for Promag H Set of seals for Promag H Wall-mounting kit for Promag H Welding jig for Promag H Mounting set for aluminium housings. Suitable for pipe mounting (3/4"...32") Coil and signal cables, various lengths. Reinforced cable on request. A set consists of two ground cables. DK5CA - * * DK5GC - * * * Ground disk for potential equalisation DK5GD - * * * Mounting kit for Promag H, comprising: 2 process connections Threaded fasteners Seals DKH * * - * * * Adapter connections for installing Promag 50 H instead of Promag 30/33 A or Promag 30/33 H DN 25. DK5HA - * * * * * If the process connections are made of PVC or PVDF, ground rings are necessary to ensure that potential is matched. Set of ground rings, comprising: 2 ground rings DK5HR - * * * For regular replacement of the seals of the Promag H DK5HS - * * * sensor. Wall-mounting kit for the Promag H sensor DK5HM - * * Weld nipple as process connection: welding jig for installation in pipe. DK5HW - * * * 86 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 602 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 8 Accessories 8.3 Communication-specific accessories Accessory HART Communicator DXR 375 hand-held terminal Description Order code Hand-held terminal for remote parameterisation and for fetching measured values via the current output HART (4...20 mA). DXR375 - * * * * Contact your Endress+Hauser representative for more information. 8.4 Communication-specific accessories Accessory Applicator ToF Tool - Fieldtool Package Fieldcheck Description Order code Software for selecting and configuring flowmeters. Applicator can be downloaded from the Internet or ordered on CD-ROM for installation on a local PC. Contact your Endress+Hauser representative for more information. DKA80 - * Modular software package consisting of the service program "ToF Tool" for configuration and diagnosis of ToF level measuring devices (time-of-flight measurement) and the "Fieldtool" service program for the configuration and diagnosis of Proline flow measuring devices. The Proline flow measuring devices are accessed via a service interface or via the service interface FXA 193. DXS10 - * * * * * Contents of the "ToF Tool - Fieldtool Package": Commissioning, maintenance analysis Configuring flowmeters Service functions Visualisation of process data Trouble-shooting Controlling the "Fieldcheck" tester/simulator Contact your Endress+Hauser representative for more information. Tester/simulator for testing flowmeters in the field. When used in conjunction with the "ToF Tool Fieldtool Package" software package, test results can be imported into a database, printed and used for official certification. DXC10 - * * Contact your Endress+Hauser representative for more information. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 87 Page 603 of 1068 8 Accessories WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 88 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 604 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting 9 Trouble-shooting 9.1 Trouble-shooting instructions Always start trouble-shooting with the checklist below, if faults occur after start-up or during operation. The routine takes you directly to the cause of the problem and the appropriate remedial measures. Check the display No display visible and no output signals present. 1. Check the power supply terminals 1, 2 2. Check the power line fuse Page 102 85...260 V AC: 0.8 A slow-blow / 250 V 20...55 V AC and 16...62 V DC: 2 A slow-blow / 250 V 3. Measuring electronics defective order spare parts Page 97 No display visible, but output signals are present. 1. Check whether the ribbon-cable connector of the display module is correctly plugged into the amplifier board Page 99, 101 2. Display module defective order spare parts Page 97 3. Measuring electronics defective order spare parts Page 97 Display texts are in a foreign lan- Switch off power supply. Press and hold down both the OS buttons and switch on guage. the measuring device. The display text will appear in English (default) and is dis- played at maximum contrast. Measured value indicated, but no signal at the current or pulse output Measuring electronics defective order spare parts Page 97 Error messages on display Errors which occur during commissioning or measuring operation are displayed immediately. Error messages consist of a variety of icons: the meanings of these icons are as follows (example): Error type: S = system error, P = process error Error message type: $ = fault message, ! = notice message EMPTY PIPE = Type of error, e.g. measuring tube is only partly filled or completely empty 03:00:05 = duration of error occurrence (in hours, minutes and seconds) # 401 = error number " Caution!! · See the information on Page 64! · The measuring system interprets simulations and positive zero return as system errors, but displays them as notice message only. Error number: No. 001 399 No. 501 699 System error (device error) has occurred Page 90 Error number: No. 401 - 499 Process error (application error) has occurred Page 93 Other error (without error message) Some other error has occurred. Diagnosis and rectification Page 94 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 89 Page 605 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 " ! 9.2 System error messages Serious system errors are always recognised by the instrument as "Fault message", and are shown as a lightning flash ( $) on the display. Fault messages immediately affect the inputs and outputs. Simulations and positive zero return, on the other hand, are classed and displayed as notice messages. Caution! In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair. The procedures on Page 8 must be carried out before you return a flowmeter to Endress+Hauser. Always enclose a duly completed "Declaration of contamination" form. You will find a preprinted blank of the this form at the back of this manual. Note! The listed error message types below correspond to the factory setting. Also observe the information on Page 64 and 95. No. Error message / Type Cause Remedy / spare part S = System error $ = Fault message (with an effect on the outputs) ! = Notice message (without an effect on the outputs) No. # 0xx Hardware error 001 S: CRITICAL FAILURE $: # 001 Serious device error Replace the amplifier board. Spare parts Page 97 011 S: AMP HW EEPROM $: # 011 Amplifier: Defective EEPROM Replace the amplifier board. Spare parts Page 97 012 S: AMP SW EEPROM $: # 012 Amplifier: Error accessing EEPROM data The EEPROM data blocks in which an error has occurred are displayed in the "TROUBLESHOOTING" function. Press Enter to acknowledge the errors in question; default values are automatically inserted instead of the errored parameter values. ! Note! The measuring device has to be restarted if an error has occurred in a totalizer block (see error No. 111 / CHECKSUM TOTAL). 031 S: SENSOR HW DAT $: # 031 Sensor DAT: 1. S-DAT is defective. 2. S-DAT is not plugged into the amplifier board or is missing. 1. Replace the S-DAT. Spare parts Page 97 Check the spare part set number to ensure that the new, replacement DAT is compatible with the measuring electronics. 2. Plug the S-DAT into the amplifier board Page 99, 101 032 S: SENSOR SW DAT $: # 032 Sensor: Error accessing the calibration values stored in the S-DAT. 1. Check whether the S-DAT is correctly plugged into the amplifier board Page 99, 101 2. Replace the S-DAT if it is defective. Spare parts Page 97. Before replacing the DAT, check that the new, replacement DAT is compatible with the measuring electronics. Check the: Spare part set number Hardware revision code 3. Replace measuring electronics boards if necessary. Spare parts Page 97 90 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 606 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting No. Error message / Type No. # 1xx Software error Cause Remedy / spare part 101 S: GAIN ERROR AMP $: # 101 Gain deviation compared to reference gain is grea- Replace amplifier board. ter than 2%. Spare parts Page 97 111 S: CHECKSUM TOTAL $: # 111 Totalizer checksum error 1. Restart the measuring device 2. Replace the amplifier board if necessary. Spare parts Page 97 121 S: A / C COMPATIB. !: # 121 Due to different software versions, I/O board and amplifier board are only partially compatible (possibly restricted functionality). Module with lower software version has either to be actualizied by FieldTool with the required software version or the module has to be replaced. ! Note! The indication on the display as notice message appears only for 30 seconds (with listing in "Previous system condition" function). This condition can occur if only one electronics board has been exchanged; the extended software functionality is not available. The previously existing software functionality is still working and the measurement possible. Spare parts Page 97 No. # 2xx Error in DAT / no communication 251 S: COMMUNICATION I/O Internal communication error on the amplifier $: # 251 board. Remove the amplifier board. Spare parts Page 97 261 S: COMMUNICATION I/O No data reception between amplifier and I/O $: # 261 board or faulty internal data transfer. No. # 3xx System limits exceeded Check the BUS contacts 321 S: TOL. COIL CURR. $: # 321 Sensor: Coil current is out of tolerance. 1. Remote version: Switch off the power supply before connecting or discon-necting the cable of the coil (terminals 41/42). 2. Remote version: Switch off power supply and check wiring of terminals 41/42 Page 47 ff. 3. Switch off the power supply and check the connectors of the coil cable Page 99, 101 4. Replace measuring electro-nics boards if necessary. Spare parts Page 97 339 S: STACK CUR OUT n ... !: # 339...342 342 343 S: STACK FREQ. OUT n ... !: # 343...346 346 The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds. 1. Change the upper or lower limit setting, as applicable. 2. Increase or reduce flow, as applicable. Recommendations in the event of fault category = FAULT MESSAGE ($): Configure the fault response of the output to "ACTUAL VALUE" (see Page 95), so that the temporary buffer can be cleared. Clear the temporary buffer by the measures described under Item 1. 347 S: STACK PULSE OUT n ... !: # 347...350 350 The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds. 1. Increase the setting for pulse weighting 2. Increase the max. pulse frequency, if the totalizer can handle a higher number of pulses. 3. Reduce flow Recommendations in the event of fault category = FAULT MESSAGE ($): Configure the fault response of the output to "ACTUAL VALUE" (see Page 95), so that the temporary buffer can be cleared. Clear the temporary buffer by the measures described under Item 1. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 91 Page 607 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 No. Error message / Type 351 S: CURRENT RANGE n ... !: # 351...354 354 355 S: FREQ. RANGE n ... !: # 355...358 358 359 S: PULSE RANGE n ... !: # 359...362 362 Cause Current output: Flow is out of range. Frequency output: Flow is out of range. Pulse output: Pulse output frequency is out of range. Remedy / spare part 1. Change the upper or lower limit setting, as applicable. 2. Increase or reduce flow, as applicable. 1. Change the upper or lower limit setting, as applicable. 2. Increase or reduce flow, as applicable. 1. Increase the setting for pulse weighting 2. When selecting the pulse width, choose a value that can still be processed by a connected counter (e.g. mechanical counter, PLC etc.). Determine the pulse width: Variant 1: Enter the minimum duration that a pulse must be present at the connected counter to ensure its registration. Variant 2: Enter the maximum (pulse) frequency as the half "reciprocal value" that a pulse must be present at the connected counter to ensure its registration. Example: The maximum input frequency of the connected counter is 10 Hz. The pulse width to be entered is: ----------1----------2 10 Hz = 50 ms No. # 5xx Application error 3. Reduce flow. 501 S: SW.-UPDATE ACT. !: # 501 New amplifier or communication (I/O module) software version is loaded. Currently no other functions are possible. Wait until the procedure is finished. The device will restart automatically. 502 S: UP-/DOWNLOAD ACT Up- or downloading the device data via configura- Wait until the procedure is finished. !: # 502 tion program. Currently no other functions are possible. No. # 6xx Simulation mode active 601 S: POS. ZERO-RETURN !: # 601 Positive zero return active " Caution!! This message has the highest display priority! Switch off positive zero return 611 S: SIM. CURR. OUT. n ... !: # 611...614 614 Simulation current output active Switch off simulation 621 SIM. FREQ. OUT. n ... !: # 621...624 624 Simulation frequency output active Switch off simulation 631 S: SIM. PULSE n ... !: # 631...634 634 Simulation pulse output active Switch off simulation 641 S: SIM. STAT. OUT n ... !: # 641...644 644 Simulation status output active Switch off simulation 671 S: SIM. STATUS IN ... !: # 671...674 674 Simulation status input active Switch off simulation 92 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 608 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting No. Error message / Type 691 S: SIM. FAILSAFE !: # 691 692 S: SIM. VOL. FLOW !: # 692 698 S: DEV. TEST ACT. !: # 698 Cause Simulation of response to error (outputs) active Remedy / spare part Switch off simulation Simulation of volume flow active Switch off simulation The measuring device is being checked on site via the test and simulation device. ! 9.3 Process error messages Process errors can be defined as either "Fault" or "Notice" messages and can thereby be weighted differently. Determination of this is done via the function matrix (see the "Description of Device Functions" Manual). Note! The error types listed in the following correspond to the factory settings. Also observe the information on Page 64 ff. and 95. No. Error message / Type Cause Remedy P = Process error $ = Fault message (with an effect on the outputs) ! = Notice message (without an effect on the outputs) 401 EMPTY PIPE $: # 401 Measuring tube partially filled or empty 1. Check the process conditions of the plant 2. Fill the measuring tube 461 ADJ. NOT OK !: # 461 EPD/OED calibration not possible because the fluid's conductivity is either too low or too high. The EPD/OED function cannot be used with fluids of this nature. 463 FULL = EMPTY $: # 463 The EPD/OED calibration values for empty pipe and full pipe are identical, therefore incorrect. Repeat calibration, making sure procedure is correct Page 81 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 93 Page 609 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9.4 Process errors without messages Symptoms Rectification Remark: You may have to change or correct certain settings in functions in the function matrix in order to rectify the fault. The functions outlined below, such as DISPLAY DAMPING, for example, are described in detail in the "Description of Device Functions" manual. Flow values are negative, even though the fluid is flowing forwards through the pipe. 1. Remote version: Switch off the power supply and check the wiring Page 47 ff. If necessary, reverse the connections at terminals 41 and 42 2. Change the setting in the "INSTALLATION DIRECTION SENSOR" function accordingly Measured-value reading fluctuates even though flow is steady. 1. Check grounding and potential equalization Page 56 ff. 2. Check the fluid for presence of gas bubbles. 3. In the "TIME CONSTANT" function (current output) increase the value 4. In the "DISPLAY DAMPING" function increase the value Measured-value reading shown on display, even though the fluid is at a standstill and the measuring tube is full. 1. Check grounding and potential equalization Page 56 ff. 2. Check the fluid for presence of gas bubbles. 3. Activate the "LOW FLOW CUTOFF" function, i.e. enter or increase the value for the switching point. Measured-value reading on display, even though measuring tube is empty. 1. Perform empty-pipe/full-pipe adjustment and then switch on Empty Pipe detec- tion Page 81 2. Remote version: Check the terminals of the EPD cable Page 47 ff. 3. Fill the measuring tube. The current output signal is always 4 mA, irrespective of the flow signal at any given time. 1. Select the "BUS ADDRESS" function and change the setting to "0". 2. Value for creepage too high. Reduce corresponding value in the "Low flow cutoff" functions (ON-/OFF-VALUE). The fault cannot be rectified or some other fault not described above has arisen. In these instances, please contact your Endress+Hauser service organization. The following options are available for tackling problems of this nature: Request the services of an Endress+Hauser service technician If you contact our service organization to have a service technician sent out, please be ready to quote the following information: Brief description of the fault Nameplate specifications (Page 9 ff.): order code, serial number Returning devices to Endress+Hauser The procedures on Page 8 must be carried out before you return a flowmeter requiring repair or calibration to Endress+Hauser. Always enclose a duly completed "Declaration of Conformity" form with the flowmeter. You will find a preprinted form at the back of this manual. Replace transmitter electronics Components in the measuring electronics defective order spare parts Page 97 94 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 610 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting ! 9.5 Response of outputs to errors Note! The failsafe mode of totalizers, current, pulse and frequency outputs can be customized by means of various functions in the function matrix. You will find detailed information on these procedures in the "Description of Device Functions" manual. Positive zero return and failsafe mode: You can use positive zero return to set the signals of the current, pulse and frequency outputs to their fallback value, for example when measuring has to be interrupted while a pipe is being cleaned. This function takes priority over all other device functions: simulations, for example, are suppressed. Failsafe mode of outputs and totalizers Process/system error is current Positive zero return is activated " Caution!! System or process errors defined as "Notice messages" have no effect whatsoever on the inputs and outputs. See the information on Page 64 ff. Current output MINIMUM CURRENT The current output will be set to the lower value of the signal on alarm level depending on the setting selected in the CURRENT SPAN (see the "Description of Device Functions" manual). Output signal corresponds to "zero flow" MAXIMUM CURRENT The current output will be set to the higher value of the signal on alarm level depending on the setting selected in the CURRENT SPAN (see the "Description of Device Functions" manual). HOLD VALUE Measured value display on the basis of the last saved value preceding occurrence of the fault. ACTUAL VALUE Measured value display on the basis of the current flow measurement. The fault is ignored. Pulse output FALLBACK VALUE Signal output no pulses Output signal corresponds to "zero flow" ACTUAL VALUE Fault is ignored, i.e. normal measured-value output on the basis of ongoing flow measurement. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 95 Page 611 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Failsafe mode of outputs and totalizers Process/system error is current Positive zero return is activated Frequency output FALLBACK VALUE Signal output 0 Hz Output signal corresponds to "zero flow" FAILSAFE LEVEL Output of the frequency specified in the FALÌLSAFE VALUE function. HOLD VALUE Last valid value (preceding occurrence of the fault) is output. ACTUAL VALUE Fault is ignored, i.e. normal measured-value output on the basis of ongoing flow measurement. Totalizer STOP The totalizers are paused until the error is rectified. Totalizer stops ACTUAL VALUE The fault is ignored. The totalizers continue to count in accordance with the current flow value. HOLD VALUE The totalizers continue to count the flow in accordance with the last valid flow value (before the error occurred). Status output In the event of a fault or power supply failure: Status output non-conductive No effect on status output 96 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 612 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting ! 9.6 Spare parts Chap. 9.1 contains a detailed trouble-shooting guide. The measuring device, moreover, provides additional support in the form of continuous self-diagnosis and error messages. Fault rectification can entail replacing defective components with tested spare parts. The illustration below shows the available scope of spare parts. Note! You can order spare parts directly from your Endress+Hauser service organisation by providing the serial number printed on the transmitter's nameplate (Page 9 ff.). Spare parts are shipped as sets comprising the following parts: · Spare part · Additional parts, small items (threaded fasteners, etc.) · Mounting instructions · Packaging 1 2 3 4 5 Fig. 48: Spare parts for Promag 50 transmitter (field and wall-mounted housings) 1 Power supply board (85...260 V AC, 20...55 V AC, 16...62 V DC) 2 Amplifier board 3 I/O board 4 S-DAT (sensor data memory) 5 Display module F06-50xxxxxx-03-06-06-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 97 Page 613 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 # 9.7 Removing and installing printed circuit boards Field housing: removing and installing printed circuit boards (Fig. 49) Warning! · Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. · Risk of damaging electronic components (ESD protection). Static electricity can damage electronic components or impair their operability. Use a workplace with a grounded working surface purpose-built for electrostatically sensitive devices! · If you cannot guarantee that the dielectric strength of the device is maintained in the following steps, then an appropriate inspection must be carried out in accordance with the manufacturer's specifications. · When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions. 1. Unscrew cover of the electronics compartment from the transmitter housing. 2. Remove the local display (1) as follows: Press in the latches (1.1) at the side and remove the display module. Disconnect the ribbon cable (1.2) of the display module from the amplifier board. 3. Remove the screws and remove the cover (2) from the electronics compartment. 4. Remove power supply board and I/O board (4, 6): Insert a suitable tool into the holes (3) provided for the purpose and pull the board clear of its holder. 5. Remove amplifier board (5): Disconnect the plug of the electrode signal cable (5.1) including S-DAT (5.3) from the board. Loosen the plug locking of the coil current cable (5.2) and gently disconnect the plug from the board, i.e. without moving it to and fro. Insert a thin pin into the hole (3) provided for the purpose and pull the board clear of its holder. 6. Installation is the reverse of the removal procedure. " Caution! Use only original Endress+Hauser parts. 98 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 614 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting 4 5 3 6 5.1 3 5.3 5.2 3 2 1.2 1 1.1 Fig. 49: Field housing: removing and installing printed circuit boards 1 Local display 1.1 Latch 1.2 Ribbon cable (display module) 2 Screws of electronics compartment cover 3 Aperture for tool, removal/installation 4 Power supply board 5 Amplifier board 5.1 Electrode signal cable (sensor) 5.2 Coil current cable (sensor) 5.3 S-DAT (sensor data memory) 6 I/O board A0002657 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 99 Page 615 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 # Wall-mounted housing: removing and installing printed circuit boards (Fig. 50) Warning! · Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. · Risk of damaging electronic components (ESD protection). Static electricity can damage electronic components or impair their operability. Use a workplace with a grounded working surface, purpose-built for electrostatically sensitive devices. · If you cannot guarantee that the dielectric strength of the device is maintained in the following steps, then an appropriate inspection must be carried out in accordance with the manufacturer's specifications. · When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions. 1. Remove the screws and open the hinged cover (1) of the housing. 2. Remove screws of the electronics module (2). Then push up electronics module and pull it as far as possible out of the wall-mounted housing. 3. Disconnect the following cable plugs from amplifier board (7): Electrode signal cable plug (7.1) including S-DAT (7.3) Plug of coil current cable (7.2). To do so, loosen the plug locking of the coil current cable and gently disconnect the plug from the board, i.e. without moving it to and fro. Ribbon cable plug (3) of the display module 4. Remove the screws and remove the cover (4) from the electronics compartment. 5. Remove the boards (6, 7, 8): Insert a suitable tool into the hole (5) provided for the purpose and pull the board clear of its holder. 6. Installation is the reverse of the removal procedure. " Caution! Use only original Endress+Hauser parts. 100 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 616 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting 1 2 6 3 4 7 5 8 7.1 7.3 5 3 7.2 5 Fig. 50: Wall-mounted housing: removing and installing printed circuit boards 1 Housing cover 2 Electronics module 3 Ribbon cable (display module) 4 Cover of electronics compartment (3 screws) 5 Aperture for tool, removal/installation 6 Power supply board 7 Amplifier board 7.1 Electrode signal cable (sensor) 7.2 Coil current cable (sensor) 7.3 S-DAT (sensor data memory) 8 I/O board F06-50xxxxxx-03-03-06-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 101 Page 617 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 # 9.8 Replacing the device fuse Warning! Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. The main fuse is on the power supply board (Fig. 51). The procedure for replacing the fuse is as follows: 1. Switch off power supply. 2. Remove the power supply board Page 98, 100 3. Remove cap (1) and replace the device fuse (2). Use only fuses of the following type: Power supply 20...55 V AC / 16...62 V DC 2.0 A slow-blow / 250 V; 5.2 x 20 mm Power supply 85...260 V AC 0.8 A slow-blow / 250 V; 5.2 x 20 mm Ex-rated devices see the Ex documentation. 4. Assembly is the reverse of the disassembly procedure. " Caution! Use only original Endress+Hauser parts. 2 1 Fig. 51: Replacing the device fuse on the power supply board 1 Protective cap 2 Device fuse A0001148 102 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 618 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting 9.9 Replacing exchangeable measuring electrodes The Promag W sensor (DN 350...2000) is available with exchangeable measuring electrodes as an option. This design permits the measuring electrodes to be replaced or cleaned under process conditions (see Page 104). F06-5xWxxxxx-00-05-xx-xx-000 Fig. 52: Apparatus for replacing exchangeable measuring electrodes (Replacing Page 104) a Allen screw b Handle c Electrode cable d Knurled nut (locknut) e Measuring electrode f Stop cock g Retaining cylinder h Locking pin (for handle) i Ball-valve housing j Seal (retaining cylinder) k Coil spring Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 103 Page 619 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Removing the electrode 1 Loosen Allen screw (a) and remove the cover. Installing the electrode 1 Insert new electrode (e) into retaining cylinder (g) from below. Make sure that the seals at the tip of the electrode are clean. 2 Remove electrode cable (c) secured to handle (b). 2 Mount handle (b) on the electrode and insert locking pin (h) to secure it in position. ". Caution!! Make sure that coil spring (k) is inserted. This is essential to ensure correct electrical contact and correct measuring signals. 2 Loosen knurled nut (d) by hand. This knurled nut acts as a locknut. 2 Pull the electrode back until the tip of the electrode no longer protrudes from retaining cylinder (g). 3 Remove electrode (e) by turning handle (b). The 3 Screw the retaining cylinder (g) onto ball-valve electrode can now be pulled out of retaining cylin- housing (i) and tighten it by hand. Seal (j) on the der (g) as far as a defined stop. cylinder must be correctly seated and clean. #. Warnung! Risk of injury. Under process conditions (pressure in the piping system) the electrode can recoil suddenly against its stop. Apply counter-pressure while releasing the electrode. ! Note! Make sure that the rubber hoses on retaining cylinder (g) and stop cock (f) are of the same color (red or blue). 4 Close stop cock (f) after pulling out the electrode as far as it will go. #. Warnung! Do not subsequently open the stop cock, in order to prevent fluid escaping. 4 Open stop cock (f) and turn handle (b) to screw the electrode all the way into the retaining cylinder. 5 Remove the electrode complete with retaining cylinder (g). 5 Screw knurled nut (d) onto the retaining cylinder. This firmly locates the electrode in position. 6 Remove handle (b) from electrode (e) by pressing out locking pin (h). Take care not to lose coil spring (k). 6 Use the Allen screw to secure electrode cable (c) to handle (b). ". Caution!! Make sure that the machine screw securing the electrode cable is firmly tightened. This is essential to ensure correct electrical contact and correct measuring signals. 7 Remove the old electrode and insert the new elec- 7 Reinstall the cover and tighten (a) Allen screw. trode. Replacement electrodes can be ordered separately from Endress+Hauser. 104 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 620 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 9 Trouble-shooting 9.10 Software history Date Software version Changes to software 03.2005 2.00.XX Software expansion: New / revised functionalities New functionalities: DEVICE SOFTWARE Device software displayed (NAMUR-recommendation 53) Unit US Kgal 11.2004 Amplifier: 1.06.01 Communication module: 1.04.00 Software update relevant only for production 10.2003 Amplifier: 1.06.00 Communication module: 1.03.00 Software expansion: Language groups Flow direction pulse output selectable New functionalities: Second Totalizer Adjustable backlight (display) Operation hours counter Simulation function for pulse output Access code for counter Reset function (fault history) Up-/download with FieldTool 08.2003 Communication module: 1.02.01 Software expansion: New / revised functionalities Special documentation: Current span NAMUR NE 43 Failsafe mode function Trouble-shooting function System and process error messages Response of status output 08.2002 Amplifier: 1.04.00 Software expansion: New / revised functionalities Special documentation: Current span NAMUR NE 43 EPD (new mode) Failsafe mode function Acknowledge fault function Trouble-shooting function System and process error messages Response of status output 03.2002 Amplifier: 1.03.00 Software expansion: Suitability for custody transfer measurement Promag 50/51 06.2001 Amplifier: 1.02.00 Communication module: 1.02.00 Software expansion: New functionalities: New functionalities: General instrument functions "OED" software function "Pulse width" software function Operating Instructions 50097090/03.05 50097090/10.03 50097090/10.03 50097090/08.03 50097090/08.02 none 50097090/06.01 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 105 Page 621 of 1068 9 Trouble-shooting WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Date Software version Changes to software 09.2000 Amplifier: 1.01.01 Communication module: 1.01.00 Software expansion: Functional adaptations 08.2000 Amplifier: 1.01.00 Software expansion: Functional adaptations 04.2000 Amplifier: 1.00.00 Communication module: 1.00.00 Original software Compatible with: FieldTool Commuwin II (version 2.05.03 and higher) HART Communicator DXR 275 (from OS 4.6) with Rev. 1, DD 1. Operating Instructions none none 50097090/04.00 ! Note! Usually, an upload or download between the different software versions is only possible with a special service software. 106 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 622 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data 10 Technical data Application Measuring principle Measuring system Measured variable Measuring range Operable flow range Input signals 10.1 Technical data at a glance 10.1.1 Application · Measuring the flow rate of fluids in closed piping systems. · A minimum conductivity of 5 µS/cm is required for measuring; the minimum conductivity required in the case of demineralised water is 20 µS/cm. · Applications in measuring, control and regulation technology Liner specific applications: · Promag W (DN 25...2000): Polyurethane lining for applications with cold water and for slightly abrasive fluids. Hard rubber lining for all applications with water (especially for trinking water) · Promag P (DN 15...600): PTFE lining for standard applications in chemical and process industries. PFA lining for all applications in chemical and process industries; especially for high process temperatures and applications with temperature shocks. · Promag H (DN 2...100): PFA lining for all applications in chemical, process and food industries; especially for high process temperatures, for applications with temperature shocks and for applications with CIP or SIP cleaning processes. 10.1.2 Function and system design Electromagnetic flow measurement on the basis of Faraday's Law. The measuring system consists of a transmitter and a sensor. Two versions are available: · Compact version: transmitter and sensor form a single mechanical unit. · Remote version: transmitter and sensor are installed separately. Transmitter: · Promag 50 Sensor: · Promag W (DN 25...2000) · Promag P (DN 15...600) · Promag H (DN 2...100) 10.1.3 Input Flow rate (proportional to induced voltage) Typically v = 0.01...10 m/s with the specified measuring accuracy Over 1000 : 1 Status input (auxiliary input): U = 3...30 V DC, Ri = 5 k, galvanically isolated Configurable for: totalizer reset, positive zero return Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 107 Page 623 of 1068 10 Technical data Output signal Signal on alarm Load Switching output Low flow cutoff Galvanic isolation Electrical connections Cable entry Cable specifications Supply voltage WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10.1.4 Output Current output: active/passive selectable, galvanically isolated, time constant selectable (0.01...100 s), full scale value selectable, temperature coefficient: typically 0.005% o.f.s./ °C; resolution: 0.5 µA · active: 0/4...20 mA, RL < 700 (for HART: RL 250 ) · passive: 4...20 mA, supply voltage Vs: 18...30 V DC, Ri 150 Pulse / frequency output: passive, open collector, 30 V DC, 250 mA, galvanically isolated · Frequency output: full scale frequency 2...1000 Hz (fmax = 1250 Hz), on/off ratio 1:1, pulse width max. 10 s · Pulse output: pulse value and pulse polarity selectable, pulse width configurable (0.5...2000 ms) · Current output failsafe mode selectable (e.g. to NAMUR recommendation NE 43) · Pulse/frequency output failsafe mode selectable · Status output "non-conductive" by fault or power supply failure Details Page 95 see "output signal" Status output: Open collector, max. 30 V DC / 250 mA, galvanically isolated Configurable for: error messages, Empty Pipe Detection (EPD/OED), flow direction, limit values Switch points for low flow cutoff are selectable All circuits for inputs, outputs, and power supply are galvanically isolated from each other. 10.1.5 Power supply see Page 47 ff. Power-supply and signal cables (inputs/outputs): · Cable entry M20 x 1.5 (8...12 mm) · Sensor cable entry for armoured cables M20 x 1.5 (9.5...16 mm) · Threads for cable entries 1/2" NPT, G 1/2" Connecting cable for remote version: · Cable entry M20 x 1.5 (8...12 mm) · Sensor cable entry for armoured cables M20 x 1.5 (9.5...16 mm) · Threads for cable entries 1/2" NPT, G 1/2" see Page 51 85...260 V AC, 45...65 Hz 20...55 V AC, 45...65 Hz 16...62 V DC 108 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 624 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Power consumption Power supply failure Potential equalisation Reference operating conditions Maximum measured error AC: <15 VA (including sensor) DC: <15 W (including sensor) Switch-on current: · max. 13.5 A (< 50 ms) at 24 V DC · max. 3 A (< 5 ms) at 260 V AC Lasting min. 1 power cycle · EEPROM saves measuring system data if power supply fails · S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number, calibration factor, zero point, etc.) see Page 56 ff. 10.1.6 Performance characteristics To DIN EN 29104 and VDI/VDE 2641: · Fluid temperature: +28 °C ± 2 K · Ambient temperature: +22 °C ± 2 K · Warm-up time: 30 minutes Installation: · Inlet run >10 x DN · Outlet run > 5 x DN · Sensor and transmitter grounded. · Sensor centered relative to the pipe. Pulse output: · ± 0.5% o.r. ± 1 mm/s (o.r. = of reading) · Option: ± 0.2% o.r. ± 2 mm/s (o.r. = of reading) Current output: plus typically ± 5 µA Supply-voltage fluctuations have no effect within the specified range. Repeatability [%] 2.5 2.0 0.5 % 1.5 0.2 % 1.0 0.5 0 0 1 2 4 6 v [m/s] Fig. 53: Max. measured error in % of reading max. ± 0.1% o.r. ± 0.5 mm/s (o.r. = of reading) 8 10 F06-5xxxxxxx-05-xx-xx-xx-000 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 109 Page 625 of 1068 10 Technical data WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10.1.7 Operating conditions Installation Installation instructions Any orientation (vertical, horizontal) Restrictions and additional installation instructions see Page 15 ff. Inlet and outlet runs Inlet run: typically 5 x DN Outlet run: typically 2 x DN Length of connecting cable For the remote version the permissible cable length Lmax depends on the conductivity of the medium Page 25. A minimum conductivity of 20 µS/cm is required for measuring demineralized water. Environment Ambient temperature ! " Transmitter: · Standard: 20...+60 °C · Optional: 40...+60 °C Note! At ambient temperatures below 20 °C the readability of the display may be impaired. Sensor: · Flange material carbon steel: 10...+60 °C · Flange material stainless steel: 40...+60 °C Caution! It is not allowed to use the device beyond the min. and max. lining specified temperature values ( "Medium temperature range"). Note the following points: · Install the device at a shady location. Avoid direct sunlight, particularly in warm climatic regions. · If both fluid and ambient temperatures are high, install the transmitter at a remote location from the sensor ( "Medium temperature range"). Storage temperature The storage temperature corresponds to the operating temperature range of the measuring transmitter and the appropriate measuring sensors. Degree of protection · Standard: IP 67 (NEMA 4X) for transmitter and sensor · Optional: IP 68 (NEMA 6P) for remote version of Promag W and P sensor Shock and vibration resistance Acceleration up to 2 g by analogy with IEC 60068-2-6 (high-temperature version: no data available) CIP cleaning Promag W: not possible Promag P: possible (note max. temperature) Promag H: possible (note max. temperature) SIP cleaning Promag W: not possible Promag P: possible with PFA (note max. temperature) Promag H: possible (note max. temperature) Electromagnetic compatibility (EMC) To EN 61326/A1 and NAMUR recommendation NE 21. 110 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 626 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Process Medium temperature range The permissible fluid temperature depends on the lining of the measuring tube: Promag W 0...+80 °C for hard rubber (DN 65...2000) 20...+50 °C for polyurethane (DN 25...2000) Promag P 40...+130 °C for PTFE (DN 15...600), for restrictions refer to diagrams 20...+180 °C for PFA (DN 25...200), for restrictions refer to diagrams HT TA [°C] 60 40 20 0 PFA -20 m PTFE -40 -40 -20 0 20 40 60 80 100 120 140 160 180 TF [°C] Fig. 54: Compact version Promag P (with PFA or PTFE lining) TA = ambient temperature, TF = fluid temperature, HT = high-temperature version, with insulation = Temperature range from 10 °C to 40 °C is valid for stainless steel flanges only A0002660 Endress + Hauser Q-Pulse Id: TMS1594 HT TA [°C] 60 40 20 0 PFA -20 m PTFE -40 -40 -20 0 20 40 60 80 100 120 140 160 180 TF [°C] Fig. 55: Remote version Promag P (with PFA or PTFE lining) TA = ambient temperature, TF = fluid temperature, HT = high-temperature version, with insulation = Temperature range from 10 °C to 40 °C is valid for stainless steel flanges only A0002671 Active: 18/04/2016 111 Page 627 of 1068 10 Technical data WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Conductivity Limiting medium pressure range (nominal pressure) Promag H Sensor: · DN 2...25: 20...+150 °C · DN 40...100: 20...+150 °C Seal: · EPDM: 20...+130 °C · Silicone: 20...+150 °C · Viton: 20...+150 °C · Kalrez: 20...+150 °C Minimum conductivity: · 5 µS/cm for fluids generally · 20 µS/cm for demineralised water Note that in the case of the remote version, the requisite conductivity is also influenced by the length of the connecting cable Page 25. Promag W · EN 1092-1 (DIN 2501): PN 6 (DN 1200...2000), PN 10 (DN 200...2000), PN 16 (DN 65...2000), PN 25 (DN 200...1000), PN 40 (DN 25...150) · ANSI B16.5: Class 150 (1...24"), Class 300 (1...6") · AWWA: Class D (28...78") · JIS B2238: 10K (DN 50...300), 20K (DN 25...300) Promag P · EN 1092-1 (DIN 2501): PN 10 (DN 200...600), PN 16 (DN 65...600), PN 25 (DN 200...600), PN 40 (DN 15...150) · ANSI B16.5: Class 150 (1/2...24"), Class 300 (1/2...6") · JIS B2238: 10K (DN 50...300), 20K (DN 15...300) Promag H: The permissible nominal pressure depends on the process connection and seal: · 40 bar: flange, weld nipple (with O-ring seal) · 16 bar: all other process connections 112 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 628 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Pressure tightness (liner) Promag W Nominal diameter [mm] [inch] 25...1000 1...40" 65...2000 3...78" Measuring tube lining Polyurethane Hard rubber Resistance of measuring tube lining to partial vacuum Limit values for abs. pressure [mbar] at various fluid temperatures 25 °C 50 °C 80° C 100 °C 130 °C 150 °C 180 °C 0 0 - - - - - 0 0 0 - - - - Promag P Nominal diameter Measuring tube lining [mm] [inch] 15 1/2" PTFE 25 1" PTFE / PFA 32 - PTFE / PFA 40 1 1/2" PTFE / PFA 50 2" PTFE / PFA 65 - PTFE / PFA 80 3" PTFE / PFA 100 4" PTFE / PFA 125 - PTFE / PFA 150 6" PTFE / PFA 200 8" PTFE / PFA 250 10" PTFE 300 12" PTFE 350 14" PTFE 400 16" PTFE 450 18" PTFE 500 20" PTFE 600 24" PTFE * No value can be quoted. Resistance of measuring tube lining to partial vacuum Limit values for abs. pressure [mbar] at various fluid temperatures 25 °C 80 °C 100 °C 130 °C 150 °C 180 °C 0 0 0 100 0 / 0 0 / 0 0 / 0 100 / 0 / 0 / 0 0 / 0 0 / 0 0 / 0 100 / 0 / 0 / 0 0 / 0 0 / 0 0 / 0 100 / 0 / 0 / 0 0 / 0 0 / 0 0 / 0 100 / 0 / 0 / 0 0 / 0 * 40 / 0 130 / 0 / 0 / 0 0 / 0 * 40 / 0 130 / 0 / 0 / 0 0 / 0 * 135 / 0 170 / 0 / 0 / 0 135 / 0 * 240 / 0 385 / 0 / 0 / 0 135 / 0 * 240 / 0 385 / 0 / 0 / 0 200 / 0 * 290 / 0 410 / 0 / 0 / 0 330 * 400 530 400 * 500 630 470 * 600 730 540 * 670 800 Partial vacuum is impermissible Limiting flow Pressure loss Promag H Nominal diameter [mm] [inch] 2...100 1/12...4" Measuring tube lining PFA Resistance of measuring tube lining to partial vacuum Limit values for abs. pressure [mbar] at various fluid temperatures 25 °C 80 °C 100 °C 130 °C 150 °C 180 °C 0 0 0 0 0 0 see Page 20 · No pressure loss if the sensor is installed in a pipe of the same nominal diameter (Promag H: only DN 8 and larger). · Pressure losses for configurations incorporating adapters according to DIN EN 545 Page 20 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 113 Page 629 of 1068 10 Technical data Design / dimensions Weight WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10.1.8 Mechanical construction All the dimensions and lengths of the sensor and transmitter are provided in the separate documentation "Technical Information". Weight data of Promag W in kg Nominal diameter Compact version Remote versin (without cable) [mm] [inch] EN (DIN) /AS* JIS ANSI/AWWA EN (DIN) /AS* Sensor JIS ANSI / AWWA Wall housin g 25 1" 7.3 7.3 7.3 5.3 5.3 5.3 6.0 PN 40 PN 40 32 1 1/4" 8.0 7.3 6.0 5.3 6.0 40 1 1/2" 9.4 8.3 9.4 7.4 6.3 7.4 6.0 50 2" 10.6 9.3 10.6 8.6 7.3 8.6 6.0 65 2 1/2" 12.0 11.1 10.0 9.1 6.0 80 3" 14.0 12.5 14.0 12.0 10.5 12.0 6.0 PN 16 10K Class 150 PN 16 10K Class 150 100 4" 16.0 14.7 16.0 14.0 12.7 14.0 6.0 125 5" 21.5 21.0 19.5 19.0 6.0 150 6" 25.5 24.5 25.5 23.5 22.5 23.5 6.0 200 8" 45 41.9 45 43 39.9 43 6.0 250 10" 65 69.4 75 63 67.4 73 6.0 300 12" 70 72.3 110 68 70.3 108 6.0 350 14" 115 175 113 173 6.0 400 16" 135 205 133 203 6.0 450 18" 175 255 173 253 6.0 PN 10 PN 10 500 20" 175 285 173 283 6.0 600 24" 235 405 233 403 6.0 700 28" 355 400 353 398 6.0 30" 460 458 6.0 800 32" 435 550 433 548 6.0 900 36" 575 800 573 798 6.0 1000 40" 700 900 698 898 6.0 42" 1100 1098 6.0 1200 48" 850 1400 848 1398 6.0 PN 6 Class D PN 6 Class D 54" 2200 2198 6.0 1400 1300 1298 6.0 60" 2700 2698 6.0 1600 1700 1698 6.0 66" 3700 3698 6.0 1800 72" 2200 4100 2198 4098 6.0 78" 4600 4598 6.0 2000 2800 2798 6.0 Transmitter Promag (compact version): 3.4 kg (Weight data valid for standard pressure ratings and without packaging material) * Flanges according AS are only available for DN 80, 100, 150...400, 500 and 600 114 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 630 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Weight data of Promag P in kg Nominal diameter Compact version Remote version (without cable) [mm] [inch] EN (DIN) JIS /AS* ANSI EN (DIN) /AS* Sensor JIS ANSI Wall housing 15 1/2" 6.5 6.5 6.5 4.5 4.5 4.5 6.0 25 1" 7.3 7.3 7.3 5.3 5.3 5.3 6.0 PN 40 PN 40 32 1 1/4" 8.0 7.3 6.0 5.3 6.0 40 1 1/2" 9.4 8.3 9.4 7.4 6.3 7.4 6.0 50 2" 10.6 9.3 10.6 8.6 7.3 8.6 6.0 65 2 1/2" 12.0 11.1 10.0 9.1 6.0 PN 16 10K Class 150 PN 16 10K Class 150 80 3" 14.0 12.5 14.0 12.0 10.5 12.0 6.0 100 4" 16.0 14.7 16.0 14.0 12.7 14.0 6.0 125 5" 21.5 21.0 19.5 19.0 6.0 150 6" 25.5 24.5 25.5 23.5 22.5 23.5 6.0 200 8" 45 41.9 45 43 39.9 43 6.0 250 10" 65 69.4 75 63 67.4 73 6.0 300 12" 70 72.3 110 68 70.3 108 6.0 PN 10 PN 10 350 14" 115 175 113 173 6.0 400 16" 135 205 133 203 6.0 450 18" 175 255 173 253 6.0 500 20" 175 285 173 283 6.0 600 24" 235 405 233 403 6.0 Transmitter Promag (compact version): 3.4 kg High-temperature version: +1.5 kg (Weight data valid for standard pressure ratings and without packaging material) * Flanges according AS are only available for DN 25 and 50 Weight data of Promag H in kg Nominal diameter Compact version Remote version (without cable) [mm] [inch] DIN Sensor Wall housing 2 1/12" 5.2 2.5 6.0 4 5/32" 5.2 2.5 6.0 8 5/16" 5.3 2.5 6.0 15 1/2" 5.4 2.6 6.0 25 1" 5.5 2.8 6.0 40 1 1/2" 6.5 4.5 6.0 50 2" 9.0 7.0 6.0 65 2 1/2" 9.5 7.5 6.0 80 3" 19.0 17.0 6.0 100 4" 18.5 16.5 6.0 Transmitter Promag (compact version): 3.4 kg (Weight data valid for standard pressure ratings and without packaging material) Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 115 Page 631 of 1068 10 Technical data Materials WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Promag W Transmitter housing: · Compact housing: powder coated die-cast aluminium · Wall-mounted housing: powder coated die-cast aluminium Sensor housing: · DN 25...300: powder-coated die-cast aluminium · DN 350...2000: painted steel (Amerlock 400) Measuring tube: · DN < 350: stainless steel 1.4301 or 1.4306/304L; non-stainless flange material with Al/Zn protective coating · DN > 300: stainless steel 1.4301/304; non-stainless flange material with Amerlock 400 paint Flange: · EN 1092-1 (DIN 2501): 316L / 1.4571; RSt37-2 (S235JRG2) / C22 / FE 410W B (DN < 350: with Al/Zn protective coating; DN > 300 with Amerlock 400 paint) · ANSI: A105, F316L (DN < 350 with Al/Zn protective coating, DN > 300 with Amerlock 400 paint) · AWWA: 1.0425 · JIS: RSt37-2 (S235JRG2) / H II / 1.0425 / 316L (DN < 350 with Al/Zn protective coating, DN > 300 with Amerlock 400 paint) · AS 2129: (DN 150, 200, 250, 300, 600) A105 or RSt37-2 (S235JRG2) (DN 80, 100, 350, 400, 500) A105 or St44-2 (S275JR) · AS 4087: A105 or St44-2 (S275JR) Ground disks: : 1.4435/316L or Alloy C-22 Electrodes: 1.4435 or Alloy C-22, tantalum Seals: Seals to DIN EN 1514-1 Promag P Transmitter housing: · Compact housing: powder coated die-cast aluminium or stainless steel field housing · Wall-mounted housing: powder coated die-cast aluminium Sensor housing: · DN 15...300: powder-coated die-cast aluminium · DN 350...600: painted steel (Amerlock 400) Measuring tube: · DN < 350: stainless steel 1.4301 or 1.4306/304L; non-stainless flange material with AI/Zn protective coating · DN > 300: stainless steel 1.4301/304; non-stainless flange material with Amerlock 400 paint Flange: · EN 1092-1 (DIN 2501): 316L / 1.4571; RSt37-2 (S235JRG2) / C22 / FE 410W B (DN < 350: with Al/Zn protective coating, DN > 300 with Amerlock 400 paint) · ANSI: A105, F316L (DN < 350 with Al/Zn protective coating, DN > 300 with Amerlock 400 paint) · JIS: RSt37-2 (S235JRG2) / H II / 1.0425 / 316L (DN < 350 with Al/Zn protective coating, DN > 300 with Amerlock 400 paint) · AS 2129: (DN 25) A105 or RSt37-2 (S235JRG2) (DN 50) A105 oder St44-2 (S275JR) · AS 4087: A105 or St44-2 (S275JR) 116 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 632 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Material load diagram Fitted electrodes Ground disks: 1.4435/316L or Alloy C-22 Electrodes: 1.4435, platinum/rhodium 80/20 or Alloy C-22, tantalum Seals: Seals to DIN EN 1514-1 Promag H Transmitter housing: · Compact housing: powder coated die-cast aluminium or stainless-steel field housing 1.4301/316L · Wall-mounted housing: powder coated die-cast aluminium Sensor housing: 1.4301 Wall mounting (holder panel): 1.4301 Measuring tube: stainless steel 1.4301 or 1.4306/304L Flange: · All connections stainless-steel 1.4404/316L · Flanges (EN (DIN), ANSI, JIS) made of PVDF · Adhesive fitting made of PVC Ground rings: 1.4435/316L, Option: tantalum, Alloy C-22 Electrodes: · Standard: 1.4435 · Option: Alloy C-22, tantalum, platinum/rhodium 80/20 (up to DN 25 only) Seals: · DN 2...25: O-ring (EPDM, Viton, Kalrez) or gasket seal (EPDM, silicone, Viton) · DN 40...100: gasket seal (EPDM, silicone) The material load diagrams (pressure-temperature graphs) for the process connections are to be found in the following documents: · Technical Information "Promag 50/53W" (TI 046D/06/en) · Technical Information "Promag 50/53P" (TI 047D/06/en) · Technical Information "Promag 50/53H" (TI 048D/06/en) Promag W: Measuring, reference and EPD electrodes · Standard available with 1.4435, Alloy C-22, tantalum · Optional: exchangeable measuring electrodes made of 1.4435 (DN 350...2000) Promag P: Measuring, reference and EPD electrodes · Standard available with 1.4435, Alloy C-22, tantalum, platinum/rhodium 80/20 · Optional: measuring electrodes made of platinum/rhodium 80/20 Promag H: Measuring electrodes and EPD electrodes · Standard available with 1.4435, Alloy C-22, tantalum, platinum/rhodium 80/20 · DN 2...4: without EPD electrode Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 117 Page 633 of 1068 10 Technical data Process connections Surface roughness Display elements Operating elements Language group Remote operation Ex Approvals WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Promag W: Flange connection: EN 1092-1 (DIN 2501); DN 65 PN 16 and DN 600 PN 16 exclusively to EN 1092-1, ANSI, AWWA, JIS, AS Promag P: Flange connection: EN 1092-1 (DIN 2501); DN 65 PN 16 and DN 600 PN 16 exclusively to EN 1092-1, ANSI, JIS, AS Promag H: · With O-ring: weld nipples (DIN EN ISO 1127, ODT / SMS), flanges (EN (DIN), ANSI, JIS), PVDF flanges (EN (DIN), ANSI, JIS), external pipe thread, internal pipe thread, hose connection, PVC adhesive fittings · With gasket seal: weld nipples (DIN 11850, ODT / SMS), clamps (ISO 2852, DIN 32676, L14 AM7), threaded fasteners (DIN 11851, DIN 11864-1, ISO 2853, SMS 1145), flanges (DIN 11864-2 · PFA liner: 0.4 µm · Electrodes: 1.4435, Alloy C-22: 0.3...0.5 µm Tantalum, platinum/rhodium: 0.3...0.5 µm · Process connection Promag H: 0.8 µm (all data relate to parts in contact with medium) 10.1.9 Human interface · Liquid-crystal display: illuminated, two lines with 16 characters per line · Custom configurations for presenting different measured values and status variables · 2 totalizers · At ambient temperatures below 20 °C the readability of the display may be impaired · Local operation with three push buttons (, +, E) · "Quick Setup" menus for straightforward commissioning Language groups available for operation in different countries: · Western Europe and America (WEA): English, German, Spanish, Italian, French, Dutch and Portuguese · Eastern Europe and Scandinavia (EES): English, Russian, Polish, Norwegian, Finnish, Swedish and Czech · South and east Asia (SEA): English, Japanese, Indonesian You can change the language group via the operating program "ToF Tool - Fieldtool Package." Operation via HART protocol 10.1.10 Certificates and approvals Information about currently available Ex versions (ATEX, FM, CSA) can be supplied by your Endress+Hauser Sales Center on request. All explosion protection data are given in a separate documentation which is available upon request. 118 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 634 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 10 Technical data Sanitary compatibility Promag W: No applicable approvals or certification Promag P: No applicable approvals or certification Promag H: · 3A authorization and EHEDG-tested · Seals in conformity with FDA (except Kalrez seals) Pressure Equipment Directive Measuring devices with a nominal diameter smaller than or equal to DN 25 correspond to Article 3(3) of the EC Directive 97/23/EC (Pressure Equipment Directive) and have been designed and manufactured according to good engineering practice. Where necessary (depending on the medium and process pressure), there are additional optional approvals to Category II/III for larger nominal diameters. CE mark The measuring system is in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Other standards and guidelines EN 60529 Degrees of protection by housing (IP code) EN 61010 Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures EN 61326/A1 (IEC 6326) Electromagne8tic compatibility (EMC requirements) NAMUR NE 21 Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment. NAMUR NE 43 Standardisation of the signal level for the breakdown information of digital transmitters with analogue output signal. NAMUR NE 53 Software of field devices and signal-processing devices with digital electronics. 10.1.11 Ordering information The Endress+Hauser service organisation can provide detailed ordering information and information on specific order codes on request. 10.1.12 Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor (see Page 85). The Endress+Hauser service organisation can provide detailed information on request. 10.1.13 Supplementary documentation · System Information Promag (SI 028D/06/en) · Technical Information Promag 50/53W (TI 046D/06/en) · Technical Information Promag 50/53P (TI 047D/06/en) · Technical Information Promag 50/53H (TI 048D/06/en) · Description of Device Functions Promag 50 (BA 049D/06/en) · Supplementary documentation on Ex-ratings: ATEX, FM, CSA, etc. Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 119 Page 635 of 1068 10 Technical data WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 120 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 636 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 11 Index 11 Index A Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Adapters (installation of sensors) . . . . . . . . . . . . . . . . . . . . 20 Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Applicator (selection and configuration software) . . . . . . . 87 Auxiliary input see Status input B Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97, 99, 101 C Cable entries degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 59 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Cable specifications (remote version) cable length, conductivity . . . . . . . . . . . . . . . . . . . . . . 25 Cable termination of Promag H . . . . . . . . . . . . . . . . . . 50 Cable termination Promag W, P . . . . . . . . . . . . . . . . . 49 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Calibration factor (default) . . . . . . . . . . . . . . . . . . . . . . . . 10 Cathode protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 CE mark (declaration of conformity) . . . . . . . . . . . . . . . . . 11 CIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Cleaning CIP /SIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Code entry (function matrix) . . . . . . . . . . . . . . . . . . . . . . 63 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Commissioning Quick Setup menu . . . . . . . . . . . . . . . 80 configure current output (active/passive) . . . . . . . . . . 82 empty pipe and full pipe calibration (EPD/OED) . . . . . 81 Commubox FXA 191, electrical connection . . . . . . . . . . . 55 Communication (HART) . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Conditions for operation . . . . . . . . . . . . . . . . . . . . . . . . . 110 Conductivity of fluid, minimum . . . . . . . . . . . . . . . . . . . 112 Connection see Electrical connection Current output configuration (active/passive) . . . . . . . . . . . . . . . . . . . 82 electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 54 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 D Data storage (S-DAT) . . . . . . . . . . . . . . . . . . . . . . . . 82, 97 Declaration of conformity (CE mark) . . . . . . . . . . . . . . . . 11 Declaration of contamination . . . . . . . . . . . . . . . . . . . . . . . 8 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . 59, 110 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Device description files . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Device functions see "Description of Device Functions" manual Device fuse, replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Display display and operating elements . . . . . . . . . . . . . . . . . . 61 turning the display . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Documentation for hazardous areas (Ex) . . . . . . . . . . . . . . . 7 Down pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 E Electrical connection cable specifications (remote version) . . . . . . . . . . . . . . 51 Commubox FXA 191 . . . . . . . . . . . . . . . . . . . . . . . . . 55 degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 59 HART handheld communicator . . . . . . . . . . . . . . . . . . 55 length of connecting cable . . . . . . . . . . . . . . . . . . . . . . 25 post-connection check (checklist) . . . . . . . . . . . . . . . . 60 potential equalisation . . . . . . . . . . . . . . . . . . . . . . . . . 56 remote version (connecting cable) . . . . . . . . . . . . . . . . 47 terminal assignment, transmitter . . . . . . . . . . . . . . . . . 54 transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Electrode Cleaning Circuitry see "Description of Device Functions" manual Electrodes EPD electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . 17, 81 exchanging replaceable electrodes . . . . . . . . . . . . . . . 103 fitted electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 measuring electrode plane . . . . . . . . . . . . . . . . . . . . . . 17 reference electrode (potential equalisation) . . . . . . . . . 56 Electromagnetic compatibility (EMC) . . . . . . . . . . . 51, 110 Electronics board . . . . . . . . . . . . . . . . . . . . . . . 97, 99, 101 Empty Pipe Detection (EPD/OED) empty-pipe/full-pipe adjustment . . . . . . . . . . . . . . . . . 81 EPD electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 general information . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Error limits see Measuring accuracy Error messages display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 error message types . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 process errors (application errors) . . . . . . . . . . . . . . . . 94 system errors (device errors) . . . . . . . . . . . . . . . . . . . . 90 Error response of outputs / totalizers . . . . . . . . . . . . . . . . 95 Error types (system and process errors) . . . . . . . . . . . . . . . 64 Ex certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Ex documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Exchange device fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 measuring electrodes . . . . . . . . . . . . . . . . . . . . . . . . . 103 printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . 98 F Failsafe mode (failure response) . . . . . . . . . . . . . . . . . . . . . 95 Fieldcare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 FieldCheck (tester and simulator) . . . . . . . . . . . . . . . . . . . 87 Flow rate / nominal diameter . . . . . . . . . . . . . . . . . . . . . . 20 Fluid conductivity, minimum . . . . . . . . . . . . . . . . . . . . . . 25 Fluid pressure range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Fluid temperature ranges . . . . . . . . . . . . . . . . . . . . . . . . 111 Foundations (for sensors with DN > 300) . . . . . . . . . . . . . 19 Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 121 Page 637 of 1068 11 Index WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 Frequency output electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 54 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Function descriptions see "Description of Device Functions" manual Function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Functions, function groups . . . . . . . . . . . . . . . . . . . . . . . 62 Fuse, replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 G Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Ground disks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 mounting (Promag P) . . . . . . . . . . . . . . . . . . . . . . . . . 34 mounting (Promag W) . . . . . . . . . . . . . . . . . . . . . . . . 27 potential equalisation . . . . . . . . . . . . . . . . . . . . . . . . . 58 Ground rings (Promag H) mounting, application area . . . . . . . . . . . . . . . . . . . . . 40 potential equalisation . . . . . . . . . . . . . . . . . . . . . . . . . 56 H HART command groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 55 Handheld terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Hazardous substances . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 High-temperature version (Promag P) installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 temperature ranges . . . . . . . . . . . . . . . . . . . . . . . . . 111 HOME position (operating mode) . . . . . . . . . . . . . . . . . . 61 I Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Inlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Input variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Installation dimensions . . . . . . . . . . . . . . . . . 15, 27, 41 Installation check (checklist) . . . . . . . . . . . . . . . . . . . . . . 46 Installation conditions adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 down pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 foundations (DN > 300) . . . . . . . . . . . . . . . . . . . . . . . 19 inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . 18 installation of pumps . . . . . . . . . . . . . . . . . . . . . . . . . 15 location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 orientation (vertical, horizontal) . . . . . . . . . . . . . . . . . 17 partially filled pipes, drains . . . . . . . . . . . . . . . . . . . . . 16 vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Installing sensor adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 foundations (DN > 300) . . . . . . . . . . . . . . . . . . . . . . . 19 ground disks (Promag P) . . . . . . . . . . . . . . . . . . . . . . 34 ground disks (Promag W) . . . . . . . . . . . . . . . . . . . . . . 27 ground rings (Promag H) . . . . . . . . . . . . . . . . . . . . . . 40 Promag H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Promag H with weld nipples . . . . . . . . . . . . . . . . . . . 41 Promag P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Promag P, high-temperature version . . . . . . . . . . . . . . 35 Promag W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Installing the wall-mount housing . . . . . . . . . . . . . . . . . . 44 Insulation of pipes (Promag P) . . . . . . . . . . . . . . . . . . . . . 35 L Limiting flow see Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . 113 Local display see Display Low flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 M Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Material load curves . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Measuring accuracy deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 reference conditions . . . . . . . . . . . . . . . . . . . . . . . . . 109 repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Measuring electrodes see electrodes Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Measuring tube lining, resistance to partial vacuum . . . . . . . . . . . . . . 113 lining, temperature range . . . . . . . . . . . . . . . . . . . . . 111 Medium see Fluid ... N Nameplate Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Nominal diameter / flow rate . . . . . . . . . . . . . . . . . . . . . 20 Nominal pressure see Fluid pressure range O OED (Open Electrode Detection) see Empty Pipe Detection . . . . . . . . . . . . . . . . . . . . . . 81 Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Operation device description files . . . . . . . . . . . . . . . . . . . . . . . . 67 display and operating elements . . . . . . . . . . . . . . . . . . 61 Fieldcare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 HART commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 HART handheld terminal . . . . . . . . . . . . . . . . . . . . . . 66 ToF Tool - Fieldtool Package (configuration and service software) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Order code Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Ordering code accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 122 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 638 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 11 Index Outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Output variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Outputs, response to errors . . . . . . . . . . . . . . . . . . . . . . . . 95 P Partial vacuum, lining . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Performance characteristics see Measuring accuracy Positive zero return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Potential equalisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Pressure loss adapters (reducers, expanders) . . . . . . . . . . . . . . . . . . 20 general information . . . . . . . . . . . . . . . . . . . . . . . . . . 113 resistance to partial vacuum, lining . . . . . . . . . . . . . . 113 Printed circuit boards, removing and installing . . . . . . . . . 98 Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Process error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 process errors without message . . . . . . . . . . . . . . . . . . 94 Programming mode disable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Pumps, location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Q Quick Setup menu for "Commissioning" . . . . . . . . . . . . . 80 R Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Registrierte Warenzeichen . . . . . . . . . . . . . . . . . . . . . . . . 12 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Repeatability (measuring accuracy) . . . . . . . . . . . . . . . . . 109 Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 S Safety icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Safety of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Safety regulation form (e.g. for repairs) see Declaration of contamination Sanitary compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 Screw tightening torques for Promag H (with plastic process connections) . . . . . 39 for Promag P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 for Promag W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 S-DAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 S-DAT (HistoROM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Seals Promag H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Promag P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Promag W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 temperature ranges (Promag H) . . . . . . . . . . . . . . . . . 112 Sensor installation see Installing sensor Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 10, 11 Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 SIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Software amplifier display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 versions (history) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Status input electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 54 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Status output electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 54 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 System error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 T Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Temperature ranges ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . 110 fluid temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . 110 ToF Tool - Fieldtool Package . . . . . . . . . . . . . . . . . . . 66, 87 Transmitter electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 52 installing the wall-mount housing . . . . . . . . . . . . . . . . 44 length of connecting cable (remote version) . . . . . . . . . 25 turning the field housing (aluminum) . . . . . . . . . . . . . . 42 turning the field housing (stainless steel) . . . . . . . . . . . 42 Transporting the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 V Vibrations measures to prevent vibrations . . . . . . . . . . . . . . . . . . 18 shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 W Wall-mount housing, installing . . . . . . . . . . . . . . . . . . . . . 44 Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Welding work grounding welding equipment . . . . . . . . . . . . . . . . . . . 41 Promag H with weld nipples . . . . . . . . . . . . . . . . . . . . 41 Wiring see Electrical connection Endress + Hauser Q-Pulse Id: TMS1594 Active: 18/04/2016 123 Page 639 of 1068 11 Index WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Proline Promag 50 124 Q-Pulse Id: TMS1594 Active: 18/04/2016 Endress + Hauser Page 640 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Declaration of Contamination Erklärung zur Kontamination Because of legal regulations and for the safety of our employees and operating equipment, we need the "declaration of contamination", with your signature, before your order can be handled. Please make absolutely sure to include it with the shipping documents, or - even better - attach it to the outside of the packaging. Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die unterschriebene "Erklärung zur Kontamination", bevor Ihr Auftrag bearbeitet werden kann. Legen Sie diese unbedingt den Versandpapieren bei oder bringen Sie sie idealerweise außen an der Verpackung an. Type of instrument / sensor Geräte-/Sensortyp _______________________________________ Serial number Seriennummer ___________________ Process data/Prozessdaten Medium and warnings Warnhinweise zum Medium Temperature / Temperatur _________ [°C] Pressure / Druck __________ [ Pa ] Conductivity / Leitfähigkeit _________ [ S ] Viscosity / Viskosität __________ [mm2/s] Medium /concentration Identification flammable toxic Medium /Konzentration CAS No. entzündlich giftig Process medium Medium im Prozess Medium for process cleaning Medium zur Prozessreinigung corrosive ätzend harmful/ irritant gesundheitsschädlich/ reizend other * harmless sonstiges* unbedenklich Returned part cleaned with Medium zur Endreinigung * explosive; oxidising; dangerous for the environment; biological risk; radioactive * explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv Please tick should one of the above be applicable, include security sheet and, if necessary, special handling instructions. Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen. Reason for return / Grund zur Rücksendung _____________________________________________________________ __________________________________________________________________________________________________ __________________________________________________________________________________________________ Company data /Angaben zum Absender Company /Firma ________________________________ ______________________________________________ Address / Adresse ______________________________________________ ______________________________________________ Contact person / Ansprechpartner ______________________ Department / Abteilung ______________________________ Phone number/ Telefon ______________________________ Fax / E-Mail _______________________________________ Your order No. / Ihre Auftragsnr. _______________________ We hereby certify that the returned parts have been carefully cleaned. To the best of our knowledge they are free from any residues in dangerous quantities. Hiermit bestätigen wir, dass die zurückgesandten Teile sorgfältig gereinigt wurden, und nach unserem Wissen frei von Rückständen in gefahrbringender Menge sind. _____________________________________________ (place, date / Ort, Datum) ______________________________________________ (Company stamp and legally binding signature) (Firmenstempel und rechtsverbindliche Unterschrift) P/SF/Konta VIII Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 641 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual www.endress.com/worldwide BA046D/06/en/03.05 50097090 FM+SGML6.0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 642 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 5 Generator SUPPLIER: MODEL: Eneraque 1937 Ipswich Road Rocklea QLD 4106 Ph: 1800 636 744 Fax: (07) 3434 3593 TRAILER MOUNTED DPAS50 GENSET PERKINS/LEROY SOMER 34941 C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 643 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 J&P RICHARDSON TRAILER MOUNTED DPAS 50 GENSET PERKINS / LEROY SOMER 34941 OPERATION & MAINTENANCE MANUAL Active: 18/04/2016 Page 644 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Document Control REVISION A DATE 19/03/2013 PREPARED BY Noel Rosario APPROVED BY Ray Verburgt Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 645 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 STANDBY SERIES GENERATOR SET USERS MANUAL Active: 18/04/2016 Page 646 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1.0 WELCOME ...................................................................................................................3 2.0 BASIC SAFETY RULES ................................................................................ 4 3.0 DESCRIPTION OF GENERATOR SET .......................................................................6 3.1 SOUND INSULATION ......................................................................................................9 3.2 CONTROL PANEL .........................................................................................................10 3.3 ELECTRICAL CONFIGURATION ..................................................................................11 3.4 RETENTION BATH ........................................................................................................12 4.0 INSTALLATION OF THE GENERATOR SET............................................................13 4.1 UNLOADING AND TRANSPORT ..................................................................................13 4.2 INSTALLATION PRINCIPLES .......................................................................................14 4.3 VENTILATION AND COOLING......................................................................................16 4.4 FUEL 16 4.4.1 Automatic fuel transfer system ............................................................................16 4.5 EXHAUST.......................................................................................................................16 4.6 GENERATOR SET STARTUP.......................................................................................17 4.7 ELECTRICAL CONNECTION ............................................................................. 18 4.7.1.1 Installation of CONTROL section: ............................................................20 4.7.1.2 Installation of ELECTRICAL POWER section:.........................................22 4.7.1.3 Earthing: ...................................................................................................23 4.7.1.4 Motorized changeover switches: ..............................................................23 STORAGE ............................................................................................................................. 24 5.0 STARTUP ...................................................................................................................25 5.1 POWER FACTOR AND GENERATOR SETS ...............................................................26 5.2 LIGH LOAD OPERATION ON DIESEL ENGINES ........................................................26 6.0 OPERATION MANUAL ..............................................................................................27 1 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 647 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.1 CONTROL PANEL COMPONENTS ..............................................................................27 6.2 GECO ANALOG CONTROL MODULE..........................................................................29 6.3 GPM-2 ANALOG CONTROL MODULE .........................................................................36 6.4 DEEP SEA 7310/7320 DIGITAL CONTROL MODULE .................................................42 6.5 DEEP SEA 5510/5520 DIGITAL CONTROL MODULE .................................................59 6.6 INTELIGENNT DIGITAL CONTROL MODULE ...............................................................77 7.0 MAINTENANCE OF GENERATOR SET ...................................................................86 7.1 PRIOR TO MAINTENANCE...........................................................................................86 7.2 DURING MAINTENANCE ..............................................................................................86 7.3 MAINTENANCE CHART ................................................................................................88 8.0 TROUBLESHOOTING ...............................................................................................89 9.0 PROTECTION FROM THE ENVIRONMENT ............................................................90 10.0 WARRANTY ...............................................................................................................91 11.0 NOISE LEVEL ............................................................................................................91 12.0 DECLARATION OF CONFORMITY ................................................................. 92 13.0 APPENDIX 1: FIGURES ............................................................................................92 14.0 APPENDIX 2: IMAGE INDEX.....................................................................................95 15.0 APPENDIX 3: PRE-DELIVERY INSPECTION DOCUMENT .....................................97 16.0 APPENDIX 4: FIGURES IN DEEP SEA CONTROL CARDS. ...................................99 17.0 APPENDIX 5: NOISE EMISSIONS ..........................................................................101 Q-Pulse Id: TMS1594 Active: 18/04/2016 2 Page 648 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1.0 WELCOME Thank you for choosing an Eneraque generator set. The purpose of this manual is to familiarize the user on how to use and work with the electrical generator, its components and maintenance. We recommend a carefully reading this document prior to working with the equipment to ensure its correct use. Save this manual for future reference and if the generator set is resold be sure to include the manual along with the unit. The following is a general description of the unit and the information necessary for installation, operation and preventive maintenance. Additionally, you should have received a specific user manual for the Engine and Alternator, electrical setup, a set of keys, ATS (upon order), silencer or exhaust tube and flexible tube (supplied separately for open-skid units). Should you have any problem with the equipment provided, please contact the distributor directly. Eneraque, in a constant effort towards product improvement, shall revise its manuals and include improvements made to the supplied units. Thus the information contained in this document is subject to change without prior notice and without obligation to update. Q-Pulse Id: TMS1594 Active: 18/04/2016 3 Page 649 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 2.0 BASIC SAFETY RULES Safety precautions and recommendations for handling the Electrical Generator supplied by Eneraque 1. Do not allow the unit to be used by non-authorized personnel or minors not accompanied by an adult. 2. Use the necessary individual protection equipment. 3. Ground the machine and ATS panel. 4. Make sure there is sufficient lighting on the genset and on the control panels. 5. Do not install the open-skid electrical generator outdoors: risk of electrocution and non-functioning. 6. The connection should be made by a qualified electrician in accordance with current norms and regulations. An incorrectly made connection can cause electrical feedback with electrocution hazards for anyone working with the mains power supply. The mains connection should always be made using an automatic transfer switch (ATS); if none has been supplied, contact your distributor or Eneraque. 7. The supply line between the generator set and the consumers should be protected by means of a differential relay for protection against earth leakage. 8. The electrical installation between the generator unit and ATS should be protected using electromagnetic circuit breaker for protection against short circuits and overcurrents. The circuit breaker is supplied optionally by Eneraque. 9. Do not operate the unit with the doors open: risk of electrocution, burns or entrapment. 10. The exhaust system produces enough heat to ignite certain materials. 11. Do not inhale exhaust gases produced by the unit. 12. Do not touch the engine or the exhaust while the generator set is operating as this could produce serious burns. 13. Ensure proper ventilation in the area where the generator is installed in order to guarantee sufficient flow of cooling air. 14. Do not refuel while the engine is running or in poorly ventilated areas. 15. Know how to stop the unit in case of emergency. 16. The fuel used is flammable and volatile. 17. Do not overfill the tank and make sure it is closed properly after filling. Use extreme precaution if fuel is spilled: the vapors and the fuel itself are flammable. Clean the area completely before starting up the unit. 18. Do not smoke or bring any flames or sparks in the vicinity of the electrical generator: risk of explosions. 19. If you notice abnormal behavior by the generator set, stop the unit, locate, examine and resolve the potential failure of the unit prior to restarting. Contact our technical services department if needed. 4 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 650 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 20. Keep the unit at least one meter away from buildings or other units. 21. Be cautious when switching or installing batteries as they contain acids which are highly hazardous. Avoid spills and use protection to avoid contact with the skin and eyes. In case of contact, rinse thoroughly with water and contact a doctor immediately. 22. In case of ingestion of battery acid, drink large amounts of water and milk and contact a doctor immediately. 23. Use only distilled water in the battery: tap water reduces its life expectancy. 24. If a battery is filled above the maximum level, the electrolytes will spill out; if this happens, clean the area quickly to avoid corrosion of the parts it has come in contact with. 25. Frequently clean the unit to avoid obstructions or the entry of foreign elements into the unit (dust, moisture, etc.). 26. Regularly inspect the unit's electrical cables. 27. Prolonged contact with used oil can cause skin cancer. Wash your hands after working with the generator. 28. Avoid oil spills on both the inside and outside of the generator. In case of an oil spill on the inside of the unit, clean it properly as it could potentially become a flammable material. Q-Pulse Id: TMS1594 Active: 18/04/2016 5 Page 651 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.0 DESCRIPTION OF GENERATOR SET General overview of the generator set and its different configurations manufactured by Eneraque. Image 1- Generator set with sound proof canopy. Image 2- Generator set without canopy Q-Pulse Id: TMS1594 Active: 18/04/2016 6 Page 652 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Image 3- Detailed view of Image 1 1) Coolant tank hatch 2) Side access door 3) Fuel tank cap 4) Exhaust silencer 5) Engine 6) Shock absorbers 7) Base frame 8) Base support 9) Canopy 10) Electrical Panel Doors 11) Ventilation grill 12) Lifting frame and eyebolt 13) Control panel 14) Alternator 15) Electrical power panel 16) Battery 17) Fuel tank 7 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 653 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Image 4- Detailed view of Image 2 1) Lifting frame 2) Engine 3) Shock absorbers 4) Base frame 5) Fuel tank 6) Base support 7) Control panel 8) Electrical power panel (optional) 9) Alternator 10) Battery Q-Pulse Id: TMS1594 Active: 18/04/2016 8 Page 654 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.1 SOUND INSULATION The supplied unit may be: Soundproofed. Includes sound-insulating canopy. Open skid. Please keep in mind that in compliance with current regulations may require that proper room sound insulation will be provided for this model. (See 4.2 INSTALLATION) Each Electrical Generator is provided with a sticker indicating the level of noise output produced and the need to use hearing protection. Noise output 90 dBA Noise output 114 dBA Use of hearing protection required. The noise level has been measured according to the European directive 2000/14/EC and in compliance with the maximum levels established by directive 2005/88/EC. Please consider the local and national regulations that could be more restribe. In any case it the intaller and owner responsabity to comply with the current legislation Q-Pulse Id: TMS1594 Active: 18/04/2016 9 Page 655 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.2 CONTROL Panel The unit provided may be controlled by different modules depending on the type of function it has been designed to perform. The following is an example of a control panel with Inteligen NT which contains all of the electrical and mechanical options available. Image 5- Generic Control Panel 1-3 .Electrical Gaugues 6 Indication lamps (green, red, yellow) 4 Hour meter 7 Mode Swicht 5 Earth elakage relay (It may be installed inside the electrical panel) 8-> Engien Gaugues 10 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 656 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.3 ELECTRICAL CONFIGURATION The supplied unit may be one of three types: The generator unit is supplied with automatic transfer switch (ATS). The generator unit is supplied without ATS. Note that its installation is required. Image 6- Load Transfer diagram Note: PCCB = Power Control Circuit Breaker ATS may be with contactors, motorized changeover switch or motorized circuit breakers Standby by signal. The Electrical Generator is supplied without ATS stands idle until it receives a signal from an autonomous external system which monitors the mains and controls the automatic transfer switch for startup. Q-Pulse Id: TMS1594 Active: 18/04/2016 11 Page 657 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3.4 retention bath The generator set may include a built-in retention bath to prevent spills from the unit--such as fuel, oil or coolant--with a capacity of 110% with respect to the total volume of liquids. It is the responsibility ot the installer and the owner to take the 1 2 2 3 1 Image 7- Retention Bath 1) 4 drain plugs, 2 on each side of the pan 2) Slots for inserting forklift arms 3) Retention bath level senders (optional) Q-Pulse Id: TMS1594 Active: 18/04/2016 12 Page 658 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.0 INSTALLATION OF THE GENERATOR SET In this part of the manual it is described how to install a "generic" generator set composed of a diesel engine, alternator and electrical panel. Please follow the current regulations when installing a generator set. 4.1 UNLOADING AND TRANSPORT When unloading an generator set, certain minimum conditions should be observed in terms of safety and efficiency. The loading and transport of the unit should be done by qualified personnel. The floor must be capable of supporting the full weight of the Generator and the forklift. Make sure that the battery is disconnected. Make sure that the fuel tank is empty. Place the arms of the forklift below the chassis at an equal distance with respect to the lifting frame. With a hoist, raise the unit using the lifting frame eyebolt. The image below shows a drawing of a generator unit which includes a frame with a single lifting point. Image 8- Lifting frame Q-Pulse Id: TMS1594 Active: 18/04/2016 13 Page 659 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.2 Installation Principles Premises The following considerations must be kept in mind: the fuel supply, ventilation of the premises, the output and direction of the exhaust gases and the noise produced. Dimensions The dimensions should allow for the various required maintenance or disassembly operations. A minimum of one meter should be left on all sides of the generator to allow for the doors to be opened. Openings The premises should have an entrance that is large enough for the generator to pass through and openings large enough for ventilation (fresh-air intake and radiator hot air outlet), with the appropriate surface area based on the generator's output, the premises' cooling system and the soundproofing system used. Eneraque does not recommend installing canopied units in closed spaces. If the unit must be installed in a enclosed space, it is recommended to use an open-skid model and soundproof the work area, in keeping with the current fire-prevention regulations. The following image shows a typical installation of an open-skid unit in a closed space. Image 9- Detailed view of installation of an open-skid unit Air intake grill. Will be at least 1.4 times the surface area of the engine's radiator panel. Smoke exhaust line. This will be explained in more detail later. 14 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 660 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Silencer. Must be firmly installed and fastened to a stable structure. Smoke exhaust outlet. Smoke must flow out through a point which impedes its reentry into the space where the working unit is installed. Radiator air outlet grill. Will be at least 1.25 times the surface area of the engine's radiator panel. Cooling air channel. Prevents re-entry of hot air into the space where the unit is installed. Optional external fuel tank. The tank may or may not be supplied by Eneraque. Auxiliary fuel pump, SAB-BE-EV system. Optional accessory for filling of the generator set day tank from an external large-capacity tank. Fuel line, adequate for transporting fuel and complies with current regulations. Q-Pulse Id: TMS1594 Active: 18/04/2016 15 Page 661 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.3 Ventilation and cooling The heat produced by the generator's thermal engine must be evacuated from the premises. The heat is generated by the cooling of the cylinders, the radiation from the engine block, the exhaust pipe, the cooling of the alternator and the radiator air output. Insufficient ventilation could produce an increase in the ambient temperature of the premises and cause the generator to lose engine power or even shut down. 4.4 Fuel In keeping with current regulations, special attention should be paid to the storage of fuel, which is classified as a hazardous product. The installation of the generator will include a day tank and an optional fuel storage tank. Depending on the output of the generator, the fuel tank may be external instead of being built into the base frame. The tank should be installed within a maximum distance (see the Engine manufacturer's manual). The installation will be carried out according to current regulations. 4.4.1 Automatic fuel transfer system The unit may include a self-suction, eccentric fuel transfer pump (SAB-BE) with self-adjusting blades. Includes a recirculation bypass valve. The pump has an internal removable 352 micron filter, which must be used. If the unit is positioned beyond the recommended distance to the fuel storage tank, the pump should be dismounted and placed near the external tank. The pump will function if the generator set is running; it has an OFF/AUTO switch located on the door of the unit's control panel. 4.5 Exhaust Pressure drop, insulation, suspension and sound levels should all be taken into account. The compensators and flexible pipes used in the installation will absorb the displacement of the unit (due to dilations and vibrations). The units supplied by ENerqaue may or may not include a rain cap. The units are equipped with two holes on the underside to prevent internal water accumulation. The optimun muffler locations are, first, directly behind the exhaust manifold, and secondly at 2/5 or 4/5 of the total exhaust system length. The reason for this are the existing standing waves, especially for long exhaust systems, when the natural pipe frequency is in resonance with the fundamental engine frequency or one of its harmonics. The worst muffler locations in order of valve are 1/3, 3/5 or at the end of the system. Q-Pulse Id: TMS1594 Active: 18/04/2016 16 Page 662 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The best muffler locations in order of values are The worst muffler locations in order of value are exhaust system length (elbows may be considered as straight portions). L = total Note: In installations where it is required, the exhaust pipe diameter must be increased. If the installation isn´t correct, seriously engine damage can be caused. 4.6 Generator set startup The startup system used by the generator set is electrical and consists of a 12 or 24 V electric engine powered by one or more batteries, usually lead. Low temperatures make engine cranking difficult. Startup failure (three attempts without success) entails the stopping of the motor and, as a result, of the entire generator unit. In order to avoid it, and to ensure correct startup of the generator set at any temperature, preheating of the entire unit is made (heating of coolant water) by means of a boiler powered by mains. This system will work automatically, by a thermostat (setup in factory from 40 to 60ºC) and it will be correctly indicated on the control panel by a lamp.. Sometimes the unit can be supplied with dry batteries. The placement into service of the this batteries should be done by removing the vent caps and filling each cell using sulfuric acid with a density of 1.28 (or 1.23 in tropical countries). Let it sit for at least 20 minutes and check the electrolyte level (25 mm above the plates; never fill to the brim). Finally put the caps back on. It is recommended that protective eyewear and gloves be worn when adding battery acid. Make sure that there is nearby access to tap water in order to wash any areas that come into contact with the acid. All operations must be performed with the utmost precaution and safety as indicated in this Manual. (Be especially careful with potential short circuits that could occur when coming in contact with the unit's metallic objects). Q-Pulse Id: TMS1594 Active: 18/04/2016 17 Page 663 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.7 Electrical connection These connections should be made while following a number of safety measures: Use the proper individual protection equipment to ensure complete safety while performing the electrical installation. Set the control module switch to the OFF position. Make sure the emergency button has been pressed. Verify that the battery is disconnected. Swich off main power Before beginning the installation of the unit provided, make sure that it meets your particular needs for voltage and frequency. Handle cables with maximum precaution as they could be live voltaged. The ground installation of the generator set and ATS must be performed correctly. Ground onnections should be identified by the following icon: . The unit manufactured by Eneraque may or may not be supplied with ATS (depends on electrical configuration: see section 3.3); if it is not supplied, it must be added by the customer. The ATS is comprised of electrical switchgear. The ATS will prevent simultaneous supply by the mains and the generator set. There are three kinds of different control switchgear used in GESAN automatic transfer switch systems: Contactors: mechanically and electrically interlocked to control mains and generator set output. They are manufactured from 40A to 125A. Motor operated changeover switches: built by two mechanical interlocked switches. They are manufactured from 160A to 3150A. Motor operated circuit breakers: two mechanical and electrical interlocked circuit breakers. They are supplied only on customer request. Q-Pulse Id: TMS1594 Active: 18/04/2016 18 Page 664 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The following diagram shows a basic ATS setup. GENERATOR SET MAINS AUTOMATIC TRANSFER SWITCH (ATS) Image 10- ATS setup The electrical installation of the ATS is performed in two separate steps: first, the installation of the CONTROL section (control and management of mains and ATS) and second, the ELECTRICAL POWER section (transmission of electrical energy). The following diagram shows the connections of a typical ATS manufactured by Eneraque. LOADS Q-Pulse Id: TMS1594 Active: 18/04/2016 19 Page 665 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual CONTROL CONNECTIONS ON ATS PANEL GECO module only Image 11- Diagram of ATS Panel 4.7.1.1 Installation of CONTROL section: The installation of the Control section can be done in three different ways: 1) ATS supplied by Eneraque. 2) ATS not supplied by Eneraque. 3) Unit is a "Standby by signal" type. Q-Pulse Id: TMS1594 Active: 18/04/2016 POWER CONNECTIONS ON ATS PANEL 20 Page 666 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1) ATS provided by Eneraque. Connect the terminals R S T N on the control panel installed on the generator and the terminals numbered 37, 40, 41 and 44 (for the GECO module, also connect 45, 46 and 47) to the terminals on the ATS panel with the same numbering. CAUTION: Do not mistake control terminals R S T N with the electrical power terminals R S T N (see the connections diagram preceding the installation instructions for the control and electrical power sections). In making these connections, you must use an 8-wire conductor (or 11-wire for the GECO module) of 1.5mm²,. This cable is not provided with the generator set. The maximum distance between the control panel and the ATS panel should be 25m for a 1.5mm² cross section and a generator set power of 650 kVA. In case of higher power or distance, increase the cross section to avoid excessive voltage drop. 2) ATS not supplied by Eneraque. Check the user manual of the corresponding ATS and follow these steps: Connect the terminals R S T N of the control panel (referential mains voltage) to the input of the electric company mains. Connect the terminals numbered 37 to 47 to the ATS control panel (check the electrical setup on the generator set control panel). Make sure that the electrical and mechanical interlocking is completed correctly. Also make sure that the ATS that you want to install is compatible with the generator unit provided. Assembly is typically done with contactors; for motorized switches please check with Enerque. The cable cross section must be appropriate for your installation. Q-Pulse Id: TMS1594 Active: 18/04/2016 21 Page 667 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 3) Generator unit is "Standby by signal" type: Neither the generator set will monitor the mains nor control the ATS: these must be controlled by the user's management system. The terminals through which the generator set receives the startup signal are 184 and 185, which should be voltfree. The generator set uses terminals 120 and 121 to return a volt-free signal when the voltage and frequency of the generator set are correct. Terminals R S T N should be connected to a mains input prior to the ATS, as these terminals provide the power supply for the engine block heater and battery maintainer. The cable cross section should be appropriate for your installation. 4.7.1.2 Installation of ELECTRICAL POWER section: A diagram of a connection can be seen in image 17. The ELECTRICAL POWER installation may be done in two ways: 1) ATS supplied by Eneraque Connect the generator's current output terminals U V W N to the ATS terminals U V W N. Connect the electric company's power control switch (PCS) to terminals R S T N. Then connect terminals X Y Z N to the installation for which you want to guarantee electrical power. 2) ATS not supplied by Eneraque or the generator set is the "Standby via signal" type. Connect the generator's current output terminals U V W N to the input of the ATS on the generator set. Check the manual of your ATS. This installation should be performed by qualified personnel, who should determine the conductor section to be used. Remember that you must ground the unit according to the current regulations in effect where the installation is performed. Q-Pulse Id: TMS1594 Active: 18/04/2016 22 Page 668 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4.7.1.3 Earthing: Ensure that the generator set, including mobile ones, is effectively grounded (earthed) in accordance with every relevant regulation, electrical code, standard or other requirement, prior to start operations. The electrical resistant of earthing installation must be enough low in order to allow earth leakage protection systems to work properly and to limit the voltage in exposed conductive parts, to avoid dangers to people or goods. Check regularly this value to avoid its increasing. To avoid the transfer of currents or voltages from other electrical systems (for example, high voltage network), independence between grounding systems must be guaranteed. 4.7.1.4 Motorized changeover switches: Mototized changeover switches are a kind of special designed control switchgear for electrical networks transfer, which simplify the equipment and control wiring needed. Motorized changeover switches can also be manually operated. They include a handle key to network switching in case of emergency when any power source is available. For security purposes, the changeover switch can be padlocked in position 0 (then manual operations are impossible and electrical controls are disabled). For additional information, please consult manufacturer manual. Q-Pulse Id: TMS1594 Active: 18/04/2016 23 Page 669 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual STORAGE If you think your generator will be inactive for a long period of time, follow these instructions: Switch the control module to the OFF position. Press the emergency stop button to avoid future involuntary startups when connecting. Empty the fuel tank. Leave the battery disconnected. Avoid storing the unit in spaces with high dust accumulation or excessive humidity. Do not use pressurized water when cleaning the unit. Check your engine manual for care instructions; the manual has been provided together with this document. Check your alternator manual for maintenance instructions; the manual has been provided together with this document. Q-Pulse Id: TMS1594 Active: 18/04/2016 24 Page 670 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5.0 STARTUP Prior to start up the generator set, follow these steps listed below: Check levels: oil, coolant and fuel. Turn the battery isolator switch to the ON position. Release the emergency push button if it has been pressed. Connect to the mains power and verify that the voltage indicator is giving an adequate reading. Check circuit breaker is on After completing the pre-startup tasks, make sure that the generator's control module switch is in the desired position. For this reason, the user should carefully read about the operation of the control module in section 6 of the OPERATION MANUAL. It is recommendable to run a simulation of mains failure to verify that the unit is functioning properly. Prior to start up the generator set or after changing generator set location, follow these steps listed below: Check the genset right mechanical balance and the right contact of every base support with the floor. Check and retighten, when necessary, engine-alternator coupling to base frame screws. Check and retighten, when necessary, radiator to base frame and radiator to motor screws. Check and adjust, when necessary, the fan belt and battery charger alternator belt alignment. If generator set output is over 750 kVA, this recommendation turns into mandatory. Please, contact with your distributor to request specific information to make this task. Check canopy sealing material, especially in the roof. Clean and reseal when necessary. Check battery connections, and retighten, clean and grease when necessary. Q-Pulse Id: TMS1594 Active: 18/04/2016 25 Page 671 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 5.1 POWER FACTOR AND GENERATOR SETS The power factor (cos ) of the generator set loads must be determined. Lagging power factor below 0,8 can overload the generator. It can work properly from 0,8 to 1 lagging power factor. Special attention must be given to installation with power factor corrections equipment (based on capacitors) in order to avoid leading power factor. This could prompt the generator set to voltage instability and could result in dangerous overvoltages. Whenever generator set is supplying the load, any power factor correction equipment must be switched off. 5.2 LIGH LOAD OPERATION ON DIESEL ENGINES If an engine is operated on a load less than 25-30% of it's rated output, certain symptoms will be observed which may be cause for concern. The engine is designed to run up to a maximum power and so the size of the piston, the wall loading of the piston rings, etc., are designed for this. When an engine is run at light load then the energy put into the cylinder is low and cnsequently the cylinder pressure is lower and so is the temperature. The result is the piston to bore clearance is increased allowing more oil to pass the piston and be burnt, which is indicated by high oil consumption. With lower preasures the sealing capacity of the rings is lower, also it is not ideal for bedding in the rings and can cause bore glazing, which reduces oil control. Oil will start to appear from the manifolds from the bearing arrangement in the turbocharger. Turbochargers are fitted to an engine to increase power by supplying more air to the cylinders. When running a turbocharger, air is sucked in, which can have vacuum levels up to 500 mm H2O, with pressure ratios of 3:1. The compressor seals are designed to work most efficiently when the turbocharger compressor is operating at its' most efficient point. If the engine is running at low powers then the turbocharger is running at low speed (no energy from the exhaust because the fuel inlet to the engine is low) and the inlet vacuum is low resulting in poor turbocharger seal loading and pull over of oil from the bearing assembly. This oil is mixed with the air and pumped into the manifolds where some separates from the air when it collides with the inside of the manifold. The manifold gaskets will become impregnated with oil, eventually this will show as an oil leak from the manifold mating surfaces. Black smoke will be produced from the exhaust outlets, due to poor combustion at light load, as excess fuel is pumped through into the exhaust system, resulting in soot being expelled into the exhaust system. A further result is that of abnormal carbon build-up on the valves, piston crowns and exhaust ports. Thus the normal service interval of 2500 hours between top overhauls may be reduced. Fuel dilution of the lubricating oil will also occure. It is therefore recommended that the following precautions are observed :- Running on light load should be avoided or reduced to a minimum period. If weekly exercising on no load is carried out, the running period should be kept down to maximum 15 minutes or until the battery charge rate returns to normal. Every year the engine / generating set should be run on full load for four (4) hours, to burn off accumulations of carbon in the engine and exhaust system. This may require a "dummy" load. The load should be built-up gradually from zero over the four hour run. 26 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 672 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.0 OPERATION MANUAL The generator set you purchased was designed for standby use, which means that it will mainly be operational when the mains voltage is inadequate. Therefore it is necessary to connect the mains to the unit's ATS as well as to the generator set (see section 4 Installation). The following is a description of the different variable elements, according to the generator set chosen. 6.1 CONTROL panel components Ammeter: Measures the current (A), by means of a switch, of the different phases of the generator set. Frequency meter: Indicates the frequency of the generator set (Hz). Voltmeter: Indicates the voltage (V) of the main power supply or generator set, depending on the position of the voltmeter switch (Ph-Ph, Ph-N). Voltmeter Switch This switch allows for voltage measurement by phase of the main power supply or the generator set. Hour meter: Indicates number of hours worked by the generator set. The two digits in red on the right indicate hundredths of hours. Hours are indicated in white from the third digit on. Q-Pulse Id: TMS1594 Active: 18/04/2016 27 Page 673 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Battery voltmeter. Indicates current voltage of battery. Engine block heater lamp (warming up): Amber light. Indicates engine block heating system is turned on. Turns on and off automatically according to the setup of the thermostat. Battery voltage failure lamp (GECO module only). Red light. Indicates alternator battery charge failure. Emergency stop button: Pressing this button brings the generator set to an immediate stop. To cancel, turn to the left, when the end of the emergency situation has been confirmed. Gauges indicating engine parameters: Oil Pressure Battery charger current Engine Temperature Fuel Level Activated by temperature and fuel button when generator set is stopped. When the generator is operating, the gauges show the corresponding levels. Diagnostic Button: Allows engine parameters to be checked when generator set is stopped (electronically controlled engines). Also gives a readout of the generator's different alarms. Differential: Protection against earth leakage of one phase, switching off the generator set circuit breaker. 28 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 674 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.2 GECO Analog Control Module Image 12- GECO Digital Control Module The following is an explanation of each of the items shown on the GECO control module; this module is for generator units with/without ATS: Q-Pulse Id: TMS1594 Active: 18/04/2016 29 Page 675 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual NUMBER (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) SYMBOL DESCRIPTION IDENTIFICATION Startup failure/No voltage or frequency detected/Emergency button Red LED pushed Low oil pressure Red LED High temperature/Low coolant level Red LED Overload Red LED Low fuel level Load test mode Test mode Automatic mode OFF/RESET mode SERV-1/START mode SERV-2/START mode Battery voltage OK Battery charging Red LED Different module operational modes Green LED Constant red: batteries charging/Flashing red light: batteries fully charged. Mains correct Green LED Mains contactor Yellow LED on indicates contactor closed Q-Pulse Id: TMS1594 Active: 18/04/2016 30 Page 676 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Yellow LED on indicates (16) Power supply to loads supply to loads Yellow LED on indicates (17) Generator Contactor contactor closed (18) (19) Generator voltage and frequency correct Green LED indicates correct voltage and frequency Q-Pulse Id: TMS1594 Active: 18/04/2016 31 Page 677 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The GECO module has six operating modes, differentiated in automatic mode (AUTO) and manual mode (MAN), which can be configured using the module switch (numbers 6-11 on the control module's descriptive panel). AUTOMATIC mode (8), (normal operating mode): When mains failure occurs, the GECO module registers this by turning off LED indicators (13) and (14), at which point the mains contactor closes, LED indicator (15) turns off and the command is sent to turn on the unit. There will be a maximum of three startup attempts lasting 20 seconds each, with a 10 second pause between each. Once the unit has started up, if the generator set voltage is correct LED indicators (18) and (19) will be turned on, at which point the electrical generator's contactor closes and LED indicators (16) and (17) will be turned on, and the customer's installation receives a power supply until the mains power returns. If all three startup attempts have been unsuccessful, LED indicator will be given, lasting 120 seconds. (1) will be lit and an acoustic signal Upon return of the mains power, LED indicator (14) on the control module will be lit and the unit's shutdown sequence begins, which lasts approximately 60 seconds (in order to check the stability of the mains power) following the return of the mains power, the generator set contactor will be disconnected, which in turn shuts off LED indicators (16) and (17), followed by the closing of the mains power contactor and the illuminating of LED indicators (16) and (17). From this moment, the unit will continue operating for 120 seconds at no load before stopping completely to cool the engine. If the mains power fails during the shutdown sequence, the operating cycle will be repeated, thus guaranteeing adequate electrical supply. On this control module in automatic mode, two additional selections can be made (in addition to the automatic option, seen previously): 32 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 678 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual LOAD TEST mode (6): with the switch turned to this position, a simulation is made of mains failure and the load is transferred to the generator set. If the switch is turned to another option while correct voltage and frequency levels exist, the loads will be transferred to the mains power. NO LOAD TEST mode (7): this option simulates a mains failure: no loads are transferred to the generator set. If a mains failure occurs during this operation, the loads will be transferred to the generator unit. This mode will terminate if another option is selected. Note: For terminating test modes, it is recommendable to turn the switch to OFF/RESET and then turn the switch to the AUTO position. MANUAL mode (3 different modes) OFF/RESET mode performs two functions, the first of which is to stop the unit whether it is in manual mode (MAN) or automatic mode (AUTO); the second function is to cancel the active alarms, allowing for a new startup of the generator set. SERV-1/START mode (10): when turning the switch to this option, the unit startup is ordered (manual operation of the generator unit); if it is operating in this mode and a mains failure occurs, the generator set will not supply energy to the loads. SERV-2/START mode (11): when turning the switch to this option, the unit startup is ordered (manual operation of the generator unit) and LED (17) is lit. If the generator stops in this mode, the loads would not be transferred to the mains power. The alarms are automatically set. If a TEST has been run, both in automatic mode (AUTO) or in manual mode (MAN), to stop the generator set turn the control module switch to the OFF mode (9); once the engine is stopped the switch can be set to a new operating mode. Finally, if the red STOP button is pressed, an emergency stop will take place. If the switch is turned to a position other than OFF, LED indicators activated. (1) and (15) will light up and an acoustic signal will be Note: If the emergency stop button is pushed while the generator unit is stopped (in the OFF position of the control module), the GECO control module will not give any indication of this, however the unit will not start up. Q-Pulse Id: TMS1594 Active: 18/04/2016 33 Page 679 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual INDICATOR LIGHTS: (12) This control module includes a 2 ampere battery charger; receives power supply from external transformer connected to the mains power. LED will turn on when battery voltage is correct. (13) LED is lit while batteries are charging. Lit only when connection with the mains power exists. LED illuminated intermittently when battery voltage is correct. ALARMS: The alarms of the GECO module are showed by means of LED indicators. There are two alarm types, one which issues the stop command and one which does not; if it is the first of these, move the switch to the OFF position (9) and fix whatever caused the alarm and select the desired option. (1) Indicates startup failure. Either voltage or frequency is not detected or the emergency stop button has been pressed; in both cases the LED indicator (1) will turn on and the control module will issue a stop command to the generator unit. To stop the alarm, turn the control module switch to the OFF/RESET position (9). (2) Indicates low oil pressure. LED indicator (2) will turn on and the control module will issue a stop command to the generator unit. To stop the alarm, turn the control module switch to the OFF/RESET position (9). (3) Indicates high engine coolant temperature or low coolant level. LED indicator (3) will turn on and the control module will issue a stop command to the generator unit. To stop the alarm, turn the control module switch to the OFF/RESET position (9). Q-Pulse Id: TMS1594 Active: 18/04/2016 34 Page 680 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (4) Indicates overload of the generator unit. LED indicator (4) will light up and the control module will issue a stop command to the generator unit. To stop the alarm, turn the control module switch to the OFF/RESET position (9). Open the electrical panel door and check the status of the circuit breaker. Check the reason for the overload and reset. Close the electrical panel door. Put the module in AUTO mode. (5) Indicates low fuel level; LED indicator (5) will be lit. System warning; must respond accordingly. Q-Pulse Id: TMS1594 Active: 18/04/2016 35 Page 681 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.3 GPM-2 Analog Control Module This module is for "Standby by signal" type generators. Image 13- GPM-2 Control Module Q-Pulse Id: TMS1594 Active: 18/04/2016 36 Page 682 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual NUMBER (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) SYMBOL DESCRIPTION Unit startup failure / Alternator failure Battery charge failure IDENTIFICATION Flashing red light: three startup failures. Continuous red light: voltage failure or low frequency. Flashing red light: charge failed. Continuous red light: unit stopped. Low oil level Flashing red light: low oil level. Continuous red light: unit stopped. Low level / High coolant temperature Flashing red light: high temperature. Continuous red light; low level. Overload Flashing red light: unit overload. Low fuel level Flashing red light: low fuel level. Emergency stop / Overspeed Flashing red light: emergency stop. Continous red light: overspeed. Remote startup mode Green LED Unit warming up Yellow LED Stop signal Maintenance signal Flashing red light: cool-down time. Continuous red light: stop command issued. Flashing blue light: maintenance required Maintenance reset button / Ignition button Button Unit startup button Manual Mode Button MAN 37 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 683 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (15) Key position for stopping unit STOP (16) Automatic mode AUTO (17) Programmable alarm Flashing or continuous red light: user-defined. The GPM-2 control module has three positions: STOP, automatic (AUTO) and manual (MAN). Key selectable (numbers 14 through 16 of the descriptive chart on the control module). AUTOMATIC mode (AUTO): When key is turned to the automatic mode position, unit will sit idle until receiving an external startup command. If mains failure occurs, the external mains monitoring system will issue a signal to the generator set, which will begin to operate, supplying the necessary electric power.. At the moment in which the external startup signal is received, while the key is in the AUTO position, the LED indicator for low oil level will light up, as well as the alternator battery voltage indicator and AUTO TEST LED (numbers 3, 2 and 8 of the descriptive panel on the control module, respectively). There will be a maximum of three startup attempts lasting 10 seconds each, with a 10 second pause between each. After three unsuccessful startup attempts, LED indicator (1) will turn on. If the unit was operating in automatic mode and the mains failure is resolved, once the external signal disappears 60 seconds will pass in order for the engine to be cooled; during these 60 seconds the LED indicator (10) will flash and later it will be continuously displayed and the engine will stop, with the LED indicator light remaining for 20 seconds. If the mains power fails during the shutdown sequence, the operating cycle will be repeated, thus guaranteeing adequate electrical supply. NO LOAD TEST mode (Manual): When key is turned to the manual mode, LED indicators for low oil level (3) and alternator battery charge indicator (2) will be turned on. To start up the unit, press the START button (13). If the key selection has been made on the generator unit and this button is not pushed in 20 seconds, the control module will shut off the system; the startup signal will be cut off when LED indicators for low oil level (3) and alternator battery charge (2) turn on; the startup signal will also be cut off when the frequency exceeds 20 Hz. 38 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 684 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual LOAD TEST mode (Manual): It must be done using the external ATS controller with the control module in automatic mode. INDICATOR LIGHTS: (8) Indicates remote startup; continuous green light turns on when unit is operating remotely. (9) Indicates unit is warming up; continuous yellow light turns on when unit is being heated. (10) Indicates stop signal. Flashing: indicates engine cooling time. Continuous: control module issues a stop command to the Engine; stays lit for 20 seconds following the complete stopping of the engine. (11) Indicates maintenance. Flashing light; the first time the light turns on after 50 operating hours and afterwards every 150 hours. To reset the maintenance hour meter, the generator set must be running; turn the key to the STOP position while pressing down the button (12) until the control module becomes completely deactivated. (12) Ignition button. When key is turned to manual mode and START button is not pushed before 20 seconds, the control module will shut off the system in order to avoid battery discharging. But some engine maintenance tasks require electrical supply from battery to electronic engine components when the engine is not running. To get it, with the key in STOP position, press the button (12) and without releasing it turn the key to the MAN position Q-Pulse Id: TMS1594 Active: 18/04/2016 39 Page 685 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARMS: The following is a chart describing the possible alarms of the GPM-2 module: NUMBER (1) (2) (3) (4) (5) (6) (7) SYMBOL DESCRIPTION IDENTIFICATION Unit startup failure / Alternator failure If the light is flashing, generator is shut down. If light is continuous, indicates low frequency. If it unit runs below rated frequency for more than 30 seconds, it is shut down. Alternator battery charge failure If light is continuous and the engine is stopped, indicates ignition. If light is flashing, indicates failure and the control module issues unit stop command. Low oil pressure If light is continuous and the engine is stopped, indicates ignition. If light is flashing, indicates failure and the control module issues unit stop command. Low level / High coolant temperature If light is continuous, indicates low coolant level and module issues unit stop command. If light is flashing, indicates high coolant temperature and the control module issues unit stop command. Overload Light will flash and indicate that the circuit breaker is tripped; module issues stop unit command. Low fuel level If light is flashing, indicated WARNING. If light is continuous, module issues unit stop command. Emergency stop / Overspeed If light is continuous, module issues unit stop command, indicating an emergency stop (emergency button activated). If the light is flashing, module issues unit stop command, indicating engine high speed. Q-Pulse Id: TMS1594 Active: 18/04/2016 40 Page 686 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual If the light is continuous, indicates WARNING. (17) Programmable alarm If light is flashing, module issues unit stop command. Note: If at any point 3 or more LED indicators turn on, it could indicate low battery level. Q-Pulse Id: TMS1594 Active: 18/04/2016 41 Page 687 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.4 DEEP SEA 7310/7320 Digital Control Module MODULE 7320 9 10 8 11 12 7 1 2 3 4 5 6 Image 14- Deep Sea 7320 Control Module Q-Pulse Id: TMS1594 Active: 18/04/2016 42 Page 688 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MODULE 7310 A NUMBER (1) SYMBOL Image 15- Deep Sea 7310 Control Module DESCRIPTION IDENTIFICATION Stop button. Red LED (2) MANUAL mode button Red LED (3) TEST mode button Green LED (available on model 7320 only) (4) AUTOMATIC mode button Red LED (5) Mute alarm / Lamp test button Q-Pulse Id: TMS1594 Active: 18/04/2016 43 Page 689 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (6) Generator set start up button (7) "Transfer to generator" button Green LED on when generator set is available (8) Configurable LED indicators. Red LED (9) Status generator set display. (10) Menu navigator (11) "Transfer to mains" button Green LED (available on Model 7320 only) (12) Status of ATS for mains Left LED on: mains closed / Right and generator set. LED on: generator closed. (A) "Open generator" button LED on: generator set is supplying loads. Deep Sea 7320 is an automatic control module that monitors the main power supply; if a mains failure occurs, generator set will start up and loads are transferred. This control module also allows the option of manual startup. The user can also control all of the generator unit's parameters as well as the status of mains power supply. This model is supplied with standby generator sets with or without ATS. Deep Sea 7310 control module is supplied with "standby by signal" type units. AUTOMATIC mode (AUTO): This is the normal operating mode. The automatic mode is activated by pressing the button will turn on, indicating that it is operational. (4), at which point the LED at the top of the button 44 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 690 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (7320) If the mains power supply fails for longer than the unit's programmed period, the LED that the mains power is available will be turned off. (11) indicating (7310) If a mains failure occurs, the external management system should send a startup signal to the generator set, at which point the LED indicating remote startup active (8) turns on and the startup process of the generator set begins. The engine will start; if it should fail, there will be a maximum number of startup attempts (3). If all three startup attempts have been unsuccessful, the information screen will display a startup alarm: When mains power is restored (or when the remote startup signal disappears) there will be a period of time in which the engine will continue operating at no load to cool down before stopping completely. If a mains failure occurs or remote startup signal appears again during the no-load operating period (cool-down period), the generator set would begin the startup process again. Press (1) or the emergency stop button to intentionally stop the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 45 Page 691 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MANUAL mode: The manual mode is activated by pressing the button turn on, indicating that it is operational. (2), at which point the LED at the top of the button will Press (6) to start up the unit. If a mains failure occurs, a remote startup signal is received or "transfer to generator" button (7) is pressed, loads will be transferred to the generator set. Once the load has been transferred to the generator, It will not be automatically transferred back to the mains supply. Loads can be manually transfer back to mains pressing "transfer to mains" button (11) (7320) or pressing "open generator" button (A) (7310). To terminate this mode, press the button (4). Once button (4) is pressed and there is adequate mains power supply (without the remote startup signal activated), the shutdown sequence will begin as described in the automatic mode. Press (1) or the emergency stop button to intentionally stop the unit. LOAD TEST mode (7320): A test for proper functioning of the generator set can be done pressing (3). To start up, press the start button (6). In this operating mode, a mains failure is simulated, with the loads being transferred to the generator set. To terminate this mode, press the button (4). Once button (4) is pressed and there is adequate mains power supply (without the remote startup signal activated), the shutdown sequence will begin as described in the automatic mode. After this period of time, the load will be carried by the mains power. 46 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 692 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Press (1) or the emergency stop button to intentionally stop the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 47 Page 693 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARMS: Press (5) to silence the audible alarm and acknowledge the common alarm LED. By default, the information screen will show the status screen and if an alarm occurs, the screen will display the following: Alarm 1 of a total of 2 present alarms Alarm type (shutdown or warning) Alarm description. Example: High engine temperature If shutdown occurs while a warning is active, the screen will cycle through the active alarms: The warnings do not entail generator unit shutdown. Q-Pulse Id: TMS1594 Active: 18/04/2016 48 Page 694 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual INCIDENT ALARM Warning Charge failure ALARM Warning Battery under voltage ALARM Warning Battery over voltage ALARM Warning Fail to Stop ALARM Warning Auxiliary inputs ALARM DESCRIPTIONS Charge alternator voltage not detected Battery voltage beyond established limits After shutdown command, engine continues running. Could also indicate faulty oil pressure sender Auxiliary inputs can be configured and will display the message as written by the user ALARM Warning Low fuel level ALARM Warning CAN ECU error ALARM Warning kW overload ALARM Warning Earth fault ALARM Fuel level below established limits Engine ECU has detected a warning alarm. The exact error is also indicated on module display (only for electronic engines). The total kW are above the warning setting. The earth fault current is above alarm settings (only under customer request) Indicates "out of balance" current loading of the generator set. 49 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 695 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Warning Negative phase sequence ALARM Warning Low oil Pressure ALARM Warning Engine high temperature ALARM Warning Engine low temperature ALARM Warning Underspeed ALARM Warning Overspeed ALARM Warning Generator over frequency ALARM Warning Generator under frequency ALARM Warning Generator over voltage ALARM Warning Generator under voltage ALARM Warning Low oil pressure, below established limit Engine temperature beyond established limits Engine speed beyond established limits Generator set frequency beyond established limits Generator set voltage beyond established limit Current of the generator set output beyond established limits 50 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 696 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual High Current INCIDENT ALARM Shutdown Earth fault ALARM Shutdown Failed to Start ALARM Shutdown Emergency stop ALARM Shutdown Low oil pressure ALARM Shutdown High temperature ALARM Shutdown Phase rotation ALARM Shutdown Overspeed ALARM Shutdown Underspeed ALARM Shutdown Generator over frequency DESCRIPTION OF SHUTDOWNS The earth fault current is above shutdown settings (only under customer request) Engine does not start, three attempts made. Controlled shutdown of the unit. It will not be functional until the emergency stop button has been reset. Oil pressure below established limit Engine temperature above established limit The phase rotation is different to the configured direction Engine speed beyond established limits Generator set frequency beyond established limits 51 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 697 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARM Shutdown Generatp or under frequency ALARM Shutdown Generator over voltage ALARM Generator set voltage beyond established limit Shutdown Generator under voltage ALARM Shutdown Faulty oil pressure sender Oil pressure sender open circuit ALARM Shutdown Auxiliary input An active auxiliary input configured as a shutdown will cause the engine to shutdown. The display shows the text as configured by the user. ALARM Shutdown Loss o speed signal The speed signal from magnetic pick up as not received by the module. ALARM Shutdown ECU data fail The module conficured for CAN operation and doesn´t detect data on datalink ALARM Shutdown ECU shutdown Engine ECU has detected a shutdown alarm. The exact error is also indicated on module display (only for electronic engines). ALARM Shutdown The total kW are above the shutdown setting. kW overload ALARM Shutdown Indicates "out of balance" current loading of the generator set. Negative phase sequence ALARM Current of the generator set output beyond established limits 52 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 698 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Shutdown High Current trip Note: If the established limit for shutdown is exceeded, a corresponding alarm screen will be displayed and on the configurable LED indicator (8) the Common Shutdown alarm will appear. INCIDENT DESCRIPTION OF ELECTRICAL TRIPS ALARM Electrical trip Generator over current Generator set current above electrical trip setting. ALARM Electrical trip Auxiliary inputs Auxiliary inputs can be configured and will display the message as written by the user ALARM Electrical trip kW overload The total kW are above electrical trip setting. ALARM Electrical trip Earth fault The earth fault current is above electrical trip settings (only under customer request) ALARM Electrical trip Negative phase sequence Indicates "out of balance" current loading of the generator set. Note: Electrical trips are latching and stop the generator set but in a controlled manner. Firstly de-energise the "close generator" output to remove the load from the generator set, and later, cool down and shutdown the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 53 Page 699 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Typical LCD Display Screens Indicates that the generator set will respond to either a mains failure or an active remote start. Indicates that generator set is in automatic mode and has been initiated after a mains failure has been detected. Indicates generator set running normally in automatic mode. Also indicates the average line to neutral voltage (L-N), the highest of the three phase currents, the rated frequency, average line-to-line voltage (LL) and total kilowatts. Measurement Parameter Display Screens: Coolant temperature in degrees (ºC) Celsius and degrees Fahrenheit (ºF) Displays engine oil pressure in Bar, PSI and kPa. All three generator line currents. Event Log: To view the event log, press the following button repeatedly until the LCD display the event log. It registers the shutdown alarms occurring in the generator unit. A screen similar to this is shown: "On September 12, 2007, at 08:25:46, the unit detected that the oil pressure was below the minimum level and has shut down the generator. It´s the event 1 of a total of 50 logged events" To move from one event to the next, press . To exit the main screen, press . 54 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 700 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Note: Warning alarms are not logged. Displaying information: Pressing this button: . Page order: Status display Instrument display (engine, generator and mains) Alarms display ECU DTCs (electronic engines only) Event Log Scheduler (if enabled) About It is possible to scroll through the different display screens by pressing the next page button: . Once selected, the page will remain on the screen until the user selects a different page or after a period of inactivity for the control module, at which point the status display appears. If no buttons are pressed upon entering an instrumentation page, the instruments will be displayed automatically. Q-Pulse Id: TMS1594 Active: 18/04/2016 55 Page 701 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Alternatively, by pressing on or buttons, the user can scroll through all the instruments on a particular screen. This disables autoscroll. When autoscroll is disabled, if no buttons are pressed the display will return to the status page. To re-enable autoscroll, press on or buttons to scroll to the title of the instrument page. If an alarm becomes activated while viewing instruments, the Alarms page will be automatically displayed. Instrument page content: Engine Engine speed Oil pressure Coolant temperature Engine battery volts Run time Oil temperature* Coolant temperature* Inlet temperature* Exhaust temperature* Fuel temperature* Turbo pressure* Fuel pressure* Fuel consumption* Fuel used* Fuel level* Auxiliary sensors (if fitted and configured) Engine mantenience due (if configured) Engine ECU link* * When connected to suitably configured and compatible engine ECU. Q-Pulse Id: TMS1594 Active: 18/04/2016 56 Page 702 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Generator Generator AC voltage L-N Generator AC voltage L-L Generator frequency Generator current Generator earth current (under customer request) Generator load (kW) Generator load (kVA) Generator power factor Generator load (kVAr) Generator load (kWh, kWAh, kVArh) Generator phase sequence Mains (DSE 7320 only) Mains voltage L-N Mains voltage L-L Mains frequency About Module type Application version USB ID unique identifier for PC USB connection Analogue measurements version Firmware update bootloader version If the following appears in an instrument display: *****, this means that the engine can't provide this parameter; the control module, however, does provide this option. If the following appears in an instrument display: ####### with the generator set in OFF/AUTOMATIC mode (with the engine stopped), this means that the control module is not connected to the engine. Press this button (6) to display the given value. 57 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 703 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Alarm LED: Remote start on load Overload pre-alarm Common alarms Common shutdown Editing the current Date and Time: The date and time are adjustable. When the battery is disconnected, the date and time are frozen; when the battery is reconnected, the date and time shown will be from the last time the battery was disconnected. The date and time reflected in the Event Log will be taken from the configuration according to the following steps: Press and simultaneously, then enter the correct PIN number using or buttons to select the right figure, and using and to move from one figure to another. Finally press button Press until the Display seccion. Press until "Current date and time". When "Current Date and Time" appears, press the button. The figures will start to flash. Press or to adjust to the desired values. Press the button to confirm the value entered. Press and hold to exit the editor at any time. Q-Pulse Id: TMS1594 Active: 18/04/2016 58 Page 704 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.5 DEEP SEA 5510/5520 Digital Control Module 9 10 8 11 12 7 1 2 3 4 5 6 Image 16- Deep Sea 5520 Control Module Q-Pulse Id: TMS1594 Active: 18/04/2016 59 Page 705 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual A NUMBER (1) SYMBOL Image 17- Deep Sea 5510 Control Module DESCRIPTION IDENTIFICATION Stop button. Red LED (2) MANUAL mode button Red LED (3) TEST mode button Green LED (available on Model 7320 only) (4) AUTOMATIC mode button Red LED (5) Mute alarm button Q-Pulse Id: TMS1594 Active: 18/04/2016 60 Page 706 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (6) Generator set start up button (7) "Transfer to generator" button Green LED on when generator set is available (8) Configurable LED indicators. Red LED (9) Status generator set display. (10) Menu navigator (11) "Transfer to mains" button Green LED (available on Model 7320 only) (12) Status of ATS for mains Left LED on: mains closed / Right and generator set. LED on: generator closed. (A) "Open generator" button LED on: generator set is supplying loads. Deep Sea 5520 is an automatic control module that monitors the main power supply; if a mains failure occurs, generator set will start up and loads are transferred to generator, synchronising and paralleling with mains when it is correct again. This control module also allows the option of manual startup. The user can also control all of the generator unit's parameters as well as the status of mains power supply. This model is supplied with standby generator sets which need synchronise and parallel with mains, with or without ATS. Deep Sea 5510 control module is supplied with generator set design for multi-set systems (several genset working in parallel. Another control device must monitor the mains and order the switch. Q-Pulse Id: TMS1594 Active: 18/04/2016 61 Page 707 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual AUTOMATIC mode (AUTO): This is the normal operating mode. The automatic mode is activated by pressing the button will turn on, indicating that it is operational. (4), at which point the LED at the top of the button (5520) If the mains power supply fails for longer than the unit's programmed time, the LED that the mains power is available will be turned off. (11) indicating (5510) If a remote start signal gets to the generator set, the LED indicating remote startup active (8) turns on and the startup process of the generator set begins. The engine will start; if it should fail, there will be a maximum number of startup attempts (3). If all three startup attempts have been unsuccessful, the information screen will display a startup alarm: Once the engine is running and stabilized the mains breaker is opened and generator breaker is closed (5520). Once the engine is running and stabilized, the generator set will first synchronise to the bus before closing generator breaker (5510). When mains power is restored, the generator set is synchronised and paralleled with the mains. When parallel time is expired, the generator set will ramp the remaining load to the mains, and generator breaker is opened. There will be a period of time in which the engine will continue operating at no load to cool down before stopping completely (5520). When remote start is removed the generator set will ramp the load to remaining sets. The generator breaker will be opened. There will be a period of time in which the engine will continue operating at no load to cool down before stopping completely (5510). If a mains failure occurs or remote startup signal appears again during the no-load operating period (cool-down period), the generator set would begin the startup process again. Press (1) or the emergency stop button to intentionally stop the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 62 Page 708 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MANUAL mode: The manual mode is activated by pressing the button turn on, indicating that it is operational. (2), at which point the LED at the top of the button will Press (6) to start up the unit. When engine is running and stabilized, the generator available led is on. If a mains failure occurs or "transfer to generator" button (7) is pressed, the generator set is synchronized and paralleled with mains. If "transfer to generator" button (7) is pressed while in parallel, the loads will be ramped to the generator set and mains breaker will be opened. If later "transfer to mains" button (11) is pressed, the generator set is re-synchronised with the mains and return to parallel operation. If "transfer to mains" button (11) is pressed while in parallel, the generator breaker will be open and loads transferred to the mains (5520). If a remote start signal is applied or "transfer to generator" button (7) is pressed, the generator is synchronised to the bus and then generator breaker is closed. If "open generator" button pressed, the load is ramped on the remaining generators and the generator circuit is opened (5510). (A) is To terminate this mode, press the button (4). Once button (4) is pressed and there is adequate mains power supply or without the remote startup signal activated, the shutdown sequence will begin as described in the automatic mode. Press (1) or the emergency stop button to intentionally stop the unit. 63 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 709 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual LOAD TEST Mode (5520): Press (3) to test for proper functioning of the generator set. To start up, press the start button (6). When the engine is running and stabilized, the generator set is synchronized with the mains and the generator breaker is closed. The loads will then be ramped from mains to the generator set. To terminate this mode, press the button (4). Once button (4) is pressed and there is adequate mains power supply, the shutdown sequence will begin as described in the automatic mode. After this period of time, the load will be carried by the mains power. Press (1) or the emergency stop button to intentionally stop the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 64 Page 710 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARMS: Press (5) to silence the audible alarm and acknowledge the common alarm LED. By default, the information screen will show the status screen and if an alarm occurs, the screen will display the following: Alarm 1 of a total of 2 present alarms Alarm type (shutdown or warning) Alarm description. Example: High engine temperature If shutdown occurs while a warning is active, the screen will cycle through the active alarms: The warnings do not entail generator unit shutdown. Q-Pulse Id: TMS1594 Active: 18/04/2016 65 Page 711 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual INCIDENT ALARM Warning Charge failure ALARM Warning Battery low voltage ALARM Warning Battery high voltage ALARM Warning Auxiliary inputs ALARM DESCRIPTIONS Charge alternator voltage not detected Battery voltage beyond established limits After shutdown command, engine continues running. Could also indicate faulty oil pressure sender Auxiliary inputs can be configured and will display the message as written by the user Fuel level below established limits ALARM Warning Engine low temperature ALARM Warning Generator failed to open ALARM Warning Mains failed to open ALARM Warning Engine coolant temperature below warning setting. Feedback doesn´t confirm that generator breaker is opened. Feedback doesn´t confirm that mains breaker is opened. Feedback doesn´t confirm that mains breaker is closed. Q-Pulse Id: TMS1594 Active: 18/04/2016 66 Page 712 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Mains failed to close ALARM Warning The setting time without maintenance has been exceed. Maintenance due ALARM Warning The generator set can´t synchronise Failed to synchronise ALARM Warning Generator phase sequence wrong A bus phase rotaion error has been detected. ALARM Warning A mains phase rotation error has been detected. Mains phase sequence wrong ALARM Warning Negative phase sequence Indicates "out of balance" current loading of the generator set. ALARM Warning MSC link doesn´t allow modules communicate correctly. MSC data error ALARM Warning MSC too few sets The number of modules on the MSC link is below the warning setting. ALARM Warning CAN ECU error Engine ECU has detected a warning alarm. The exact error is also indicated on module display (only for electronic engines). Low oil pressure, below established limit ALARM Warning Engine high temperature Engine temperature beyond established limits Q-Pulse Id: TMS1594 Active: 18/04/2016 67 Page 713 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARM Warning Engine low temperature Engine speed beyond established limits ALARM Warning Generator over frequency ALARM Warning Generator under frequency ALARM Warning Generator over voltage ALARM Warning Generator under voltage ALARM Warning Loss of excitation Generator set frequency beyond established limits Generator set voltage beyond established limit Loss of excitation on the alternator ALARM Warning Insufficient capacity The generator set is overloaded when paralleling with mains. Current of the generator set output beyond established limits Q-Pulse Id: TMS1594 Active: 18/04/2016 68 Page 714 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual INCIDENT DESCRIPTION OF SHUTDOWNS Engine does not start, three attempts made. Controlled shutdown of the unit. It will not be functional until the emergency stop button has been reset. Oil pressure below established limit Engine temperature above established limit Engine speed beyond established limits ALARM Shutdown Generator over frequency ALARM Generator set frequency beyond established limits Shutdown Generator under frequency ALARM Shutdown Generator over voltage ALARM Generator set voltage beyond established limit Shutdown Generator under voltage ALARM Shutdown Faulty oil pressure sender Oil pressure sender open circuit Q-Pulse Id: TMS1594 Active: 18/04/2016 69 Page 715 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ALARM Shutdown Auxiliary input ALARM Shutdown Magnetic pickup open circuit ALARM Shutdown Loss of speed signal ALARM Shutdown CAN data fail ALARM Shutdown CAN ECU fail ALARM Shutdown kW overload ALARM Shutdown Generator earth fault ALARM Shutdown Air flap closed ALARM Shutdown Negative phase sequence ALARM Shutdown MSC old units on bus ALARM Shutdown An active auxiliary input configured as a shutdown will cause the engine to shutdown. The display shows the text as configured by the user. The speed signal from magnetic pick up as not received by the module. The speed signal is not received by the module during cranking. The module conficured for CAN operation and doesn´t detect data on datalink Engine ECU has issued a shutdown alarm. The total kW are above the shutdown setting. Earth fault current is above the shutdown settings. Engine air intake flap is closed. Inbalance in the load current of each phase above shutdown setting. An incompatible module on the MSC link. ID error on MSC link. 70 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 716 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual MSC ID error ALARM Shutdown MSC link is not detected. MSC failure ALARM Shutdown Loss of excitation on alternator. Loss of excitation Note: If the established limit for shutdown is exceeded, a corresponding alarm screen will be displayed and on the configurable LED indicator (8) the Common Shutdown alarm will appear. INCIDENT ALARM Electrical trip Auxiliary inputs ALARM Electrical trip Generator high current ALARM Electrical trip Generator reverse power ALARM Electrical trip Generator short circuit ALARM Electrical trip Mains reverse power ALARM Electrical trip DESCRIPTION OF ELECTRICAL TRIPS Auxiliary inputs can be configured and will display the message as written by th user Output current above the electrical trip setting. Reverse power current above the electrical trip setting. A generator short circuit has been detected. The power exported to the mains is above the setting. Loss of excitation on alternator. Q-Pulse Id: TMS1594 Active: 18/04/2016 71 Page 717 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Loss of excitation ALARM Electrical trip Insufficient capacity The generator set is overloaded when paralleling with mains. ALARM Electrical trip Generator failed to close Feedback doesn´t confirm that generator breaker is closed. ALARM Electrical trip Negative phase sequence Indicates "out of balance" current loading of the generator set. Note: Electrical trips are latching and stop the generator set but in a controlled manner. Firstly de-energise the "close generator" output to remove the load from the generator set ,and later, cool down and shutdown the unit. Q-Pulse Id: TMS1594 Active: 18/04/2016 72 Page 718 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Typical LCD Display Screens Indicates that the generator set will respond to either a mains failure or an active remote start. Indicates that generator set is in automatic mode and has been initiated after a mains failure has been detected. L) and total kilowatts. Indicates generator set running normally in automatic mode. Also indicates the average line to neutral voltage (L-N), the highest of the three phase currents, the rated frequency, average line-to-line voltage (L- Measurement parameter display screens: Coolant temperature In degrees (ºC) celsius and degrees fahrenheit (ºF) Displays engine oil pressure in Bar, PSI and kPa. All three generator line currents. Event Log: To view the event log, press the page button be automatically scrolled down. repeatedly until the LCD display the event log. The records will The event log registers the shutdown alarms occurring in the generator unit. A screen similar to this is shown: "On September 12, 2007, at 08:25:46, the unit detected that the oil pressure was below the minimum level and has shut down the generator. It´s the event 1 of a total of 50 logged events". To exit the another page, press . Note: Warning alarms are not logged. 73 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 719 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Displaying Information: Press the button to move to the required page. The LCD display the page title and then automatically start scrolling the various instruments until the user change to another page. It is also possible to scroll to different instruments using or buttons. Instrument page content: Engine speed Oil pressure Coolant temperature Fuel level Battery voltage/charge alt volts Engine run time/number of starts Next maintenance (if enable) Generator AC voltage L-N Generator AC voltage L-L Generator frequency Generator current Generator earth current (under customer request) Generator load (kW) Generator load (kVA) Generator power factor Generator load (kVAr) Generator load (kWh, kWAh, kVArh) Generator phase sequence Mains voltage L-N Mains voltage L-L Mains frequency Q-Pulse Id: TMS1594 Active: 18/04/2016 74 Page 720 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Enhance engine instrumentation (when supported by electronic engine ECU): Oil temperature* Coolant temperature* Inlet manifold temperature* Exhaust temperature* Turbo pressure* Fuel pressure* Fuel consumption* Total fuel used* Alarm LED: Remote start on load Overload pre-alarm Common alarms Common shutdown Editing the current Date and Time: The date and time are adjustable. When the battery is disconnected, the date and time are frozen; when the battery is reconnected, the date and time shown will be from the time the battery was disconnected. The date and time reflected in the Event Log will be taken from the configuration according to the following steps: Press and simultaneously, then enter the correct PIN number using + or - buttons and then press to select the next figure. Q-Pulse Id: TMS1594 Active: 18/04/2016 75 Page 721 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual The LCD will then display: CONFIGURATION. To view the different configuration functions press the + or buttons. Pressing the button will enter in edit mode. The parameter being changed will flash. Pressing + or buttons will change the parameter to the desired value. Press to save the change. Press and hold to exit the editor at any time. Q-Pulse Id: TMS1594 Active: 18/04/2016 76 Page 722 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 6.6 INTELIGENNT Digital Control Module Image 18- INTELIGENNT Digital Control Module Q-Pulse Id: TMS1594 Active: 18/04/2016 77 Page 723 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual # SYMBOL DESCRIPTION IDENTIFICATION (1) Scrolls through OFFMANAUTTEST different operating (2) modes OFFMANAUTTEST (3) Deactivates audible alarm (4) Fault reset Acknowledges faults and alarms (5) Start button In manual mode (6) Stop button In manual mode (7) MCB ON/OFF Opens and closes MCB in manual mode (8) GCB ON/OFF Opens and closes GCB in manual mode Exit from atual screen (9) (without save changes if editing) (10) Selects on-screen Increases value value, setpoint, history record or (11) increase/decrease Decreases value setpoint value (12) Moves history record Increases value displayed columns to the right/left, 5% increase/decrease of (13) edited setpoint,s value Decreases value or go out/into alarm list (14) Enter button Confirms on-screen value Q-Pulse Id: TMS1594 Active: 18/04/2016 78 Page 724 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual (15) Mains power status Green if mains power correct Red light flashes if mains failure occurs (16) Mains failure and generator set doesn´t run; continuous if generator is operating, turns off when Mains power restored. (17) Generator present voltage Green led is on if unit voltage is present and within limits. (18) Generator set failure Flashing Red LED indicates alarm (19) State of GCB Green led is on if GCB is closed. Flashes during synchronization with mains. (20) State of MCB Green led is on if MCB is closed Flashes during reverse synchronization with mains. (21) State of bus Green led is on if bus voltage is correct NOTE: GCB = Generator Circuit Breaker; MCB = Mains Circuit Breaker. The InteliGenNT module contains a main menu screen and the following seven submenu screens: Alarmlist Measurement Measurement I/O History Setpoints User/Password Languages Pressing several times the main menu is displayed. To enter in a submenu, scroll up and down using (10) or (11) buttons and press (14) button. To display the different instruments or parameters on each 79 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 725 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual screen menu, press (9) button. (10) or (11) buttons. To come back to a previous menu screen, press . The alarmlist screen display the alarms detected by the module. Pressing aknowledged. button (4) faultls and alarms are The measurement screen displays the parameters measured on the engine; if the engine uses an electronic management system, many additional parameters can be displayed. In addition to these parameters, measurements can be displayed for fuel level, oil pressure, current, voltage, frequency, run hours and battery charge level. The measurement I/O screen display the status of digital inputs and outputs and the measured parameter of analogue inputs (senders). The history screen menu displays the log of alarms that have occurred in the generator unit. It also logs the opening and closing of the mains circuit breaker as well as the starting and shutting down of the generator unit. The setpoints menu screen displays the adjustment parameters already configured; it is not necessary to edit any of these. The users/password screen allows to define users and passwords. The languages screen allows to change the display language AUTOMATIC mode (AUTO): If a mains failure is detected, the InteliGenNT module will open the MCB (main circuit breaker). Startup command is issued to generator set. If generator voltage is within the established limits, the LED indicator (17) will be on and the control module closes the GCB (generator circuit breaker). Once mains power has been restored, synchronization between mains and generator occurs; then the MCB is closed, causing the generator to discharge, followed by the opening of the GCB. When mains power is restored, there will be a period of time during which the engine continues operating at no load to cool down before stopping completely. Note: If (4) is pressed following a disconnection alarm, the engine could automatically start without any warning. NO-LOAD TEST mode (MANUAL): Press the START button (5) to start up the generator set. When the generator voltage is within the established limits, the LED indicator (17) will be on. To stop the unit, press STOP (6). Q-Pulse Id: TMS1594 Active: 18/04/2016 80 Page 726 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual LOAD TEST mode (TEST): This operating mode is used for generator set start test is the mains is OK or to transfer the load to the generator set when a mains failure is announced in advance. To stop this mode, change to another mode by means of the buttons (1) or (2). Q-Pulse Id: TMS1594 Active: 18/04/2016 81 Page 727 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual OFF mode: The generator set will not start. Even if we press the buttons START ON/OFF (8), the generator will not respond. (5), STOP (6) , GCB ALARMS: The InteliGenNT control module includes the following warnings: INCIDENT STORED IN HISTORY RECORD Startup sequence initiated Startup of Gen-Set Shutdown of the Gen-Set Gen-Set stops Electrical Generator circuit breaker closed GCB connected Electrical Generator circuit breaker opened GCB disconnected Some GCB in group was opened (in MINT) Other GCB trip Mains circuit breaker closed MCB connected Mains circuit breaker opened MCB disconnected Time mode has been changed TimeModeChngd STARTUP INFO AMF Startup GenSetMF start AMF Stop GenSetMF stop Remote startup by binary input (SPM, SPtM) GenSetRemStart Remote stop by binary input (SPM, SPtM) GenSetRemStop System startup by binary input (MINT, MEXT) GenSetSysStart System stop by binary input (MINT, MEXT) GenSetSysStop Peak start (SPtM) GenSet PKstart Peak stop (SPtM) GenSet PKstop Q-Pulse Id: TMS1594 Active: 18/04/2016 82 Page 728 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual ENGINE EVENT SPECIFICATION ALARM Electrical Generator Startup failure Sd Start Fail Electrical Generator Overspeed Sd Overspeed Electrical Generator Underspeed Sd Underspeed SD Stop fail Sd Stop Fail Emergency Stop Emergency Stop RPM Pickup fail SdPickupFail Battery voltage warning Wrn Batt volt Battery is discharged Sd Batt flat HISTORY Sd Start Fail Sd Overspeed Sd Underspeed Sd Stop Fail Emergency Stop SdPickupFail Wrn Batt volt 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 83 Page 729 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual GENERATOR EVENT SPECIFICATION HISTORY Generator phase 1 overvoltage Unl Vg1 Over Generator phase 1 undervoltage Unl Vg1 Under Generator phase 2 overvoltage Unl Vg2 Over Generator phase 2 undervoltage Unl Vg2 Under Generator phase 3 overvoltage Unl Vg3 Over Generator phase 3 undervoltage Unl Vg3 Under Generator Overfrequency Unl Fgen Over Generator Underfrequency Unl Fgen Under Generator voltage unbalance Unl Vgen Unbal Generator overload UnlGen Overload Load surge protection LoadSurge Reverse power Unl Rev Pwr Synchronization timeout Stp SyncTO Ground fault protection Unl EarthFltC Failure of generator circuit breaker GCB fail Generator short circuit protection Unl Short Igen Generator IDMT protection Unl IDMT Generator current unbalance Unl Igen Unbal Voltage on mains terminals (SPM) UnlCounterVolt Bus voltage error (MINT) Unl BusMeasErr Q-Pulse Id: TMS1594 Active: 18/04/2016 84 Page 730 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual PHASE SEQUENCE EVENT SPECIFICATION ALARM Generator phase L1 is inverted GEN L1 neg Generator phase L2 is inverted GEN L2 neg Generator phase L3 is inverted GEN L3 neg Wrong generator phase sequence G ph opposed Wrong generator phase sequence and phase L1 is inverted G ph + L1 neg Wrong generator phase sequence and phase L2 is inverted G ph + L2 neg Wrong generator phase sequence and phase L3 is inverted G ph + L3 neg Mains phase L1 is inverted B L1 neg Mains phase L2 is inverted B L2 neg Mains phase L3 is inverted B L3 neg Wrong mains phase sequence B ph opposed Wrong mains phase sequence and phase L1 is inverted B ph + L1 neg Wrong mains phase sequence and phase L2 is inverted B ph + L2 neg Wrong mains phase sequence and phase L3 is inverted B ph + L3 neg HISTORY 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 85 Page 731 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.0 MAINTENANCE OF GENERATOR SET You must make sure that the person who will perform this duty is qualified to do so and uses the appropriate individual protection equipment. 7.1 prior to maintenance You must first: Switch Control Module to the OFF position. Press the emergency stop button. Disconnect the battery; use the battery isolator switch. To cut Mains voltage, switch off the 10 A circuit breaker in the ATS panel supplied by Eneraquw. If made by another manufacturer, make sure that this cut is done properly before handling the unit. 7.2 during maintenance Preventive maintenance tasks are necessary to preserve the unit; doing so will result in optimum performance. Be sure to verify the following items: While the engine is cold, the oil level should be between the minimum and maximum values. If it is below the minimum, add Engine oil. NOTE: With the GPM-2 and InteliGenNT modules, at 50 hours run notice will be given to change the oil. The recommended oil is 15W40. The radiator water level should be adequate. The fuel level in the tank should be sufficient for the service to be performed. The generator control panel is equipped with a fuel gauge, which will be functional whenever the electrical panel is receiving power. Always refuel in a well ventilated area with the engine stopped. Closely inspect the connections and the electrical circuit, for both the mechanical and electrical sections. Check carefully for possible liquid leaks. If a leak is detected, find its source and resolve the problem. If your unit has a retention bath, drain it (see section 3.4 RETENTION BATH). The air inlet and outlet vents should be completely unobstructed to allow for free circulation of cooling air. Check the state of the unit's radiator and clean if necessary. Make sure the exhaust tube is not obstructed. Check the battery's connection terminals and electrolyte level (if necessary, add demineralized or distilled water). Acid should never be added. The battery should be recharged if the terminal voltage is below 12.3 V. 86 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 732 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual If the battery needs recharging after being taken out of the unit, remove the vent caps and charge battery with direct current only. Connect the charger's positive (+) cable to the battery's positive (+) terminal and the charger's negative (-) cable to the battery's negative (-) terminal. Recharge battery with a current equivalent to 1/10 the rated capacity (Ah). Battery is fully charged when acid density is 1.28. Before completing recharging process: turn off charger before disconnecting battery and check electrolyte level. If the battery is discharged and you want to perform an emergency startup with the battery from another generator, first check the tightness of the discharged battery's terminals. Stop the engines of both units and connect the two positive terminals of the batteries first and then connect the negative terminal of the charged battery to a metal area on the disabled unit (ground). Start up the auxiliary unit and then the unit being repaired. Disconnect the cables in reverse order to avoid a short circuit. Finally, fully charge the battery. While performing preventive maintenance tasks it is advisable to wear protective eyewear and gloves during all operations involving the handling of battery acid. Make sure there is nearby access to tap water in order to wash all potentially affected areas. Remember to always perform all operations with the utmost precaution and safety as indicated in this Manual. (Pay special attention to the risk of short circuits that could be caused by coming in contact with the unit's metallic objects.) Q-Pulse Id: TMS1594 Active: 18/04/2016 87 Page 733 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 7.3 FREQUENCY maintenance chart MAINTENANCE OPERATION Perform a mains failure simulation; the unit should supply power to consumers for one hour. For parallel units, check the connection and the load sharing. Review the connections of the startup battery, clean and cover with vaseline. Make sure the battery charger is functioning properly. Make sure fuel pump is functioning properly. MONTHLY Check fuel level on the main fuel tank. Check coolant and oil levels. Make sure smoke extractor is functioning properly. Make sure all of the electrical panel lights are functioning properly. Make sure the ATS functions properly in transfers. Check the state of all of the gauges and indicators on the electrical panel. Check the engine manufacturer's manual for specific tasks. Start up the engine manually three times, noting each time the voltage and density readings for each of the battery's elements. If any of the voltage readings varies significantly from those of the battery's other elements, do not perform the remaining manual engine startups. EVERY 6 MONTHS Fully charge the battery and check the electrolyte level. Make sure there are no leaks in the coolant tubes. Make sure that all of the unit's alarms display correctly. Check the engine manufacturer's manual for specific tasks. Clean the outside of the fuel tank and check the diesel pipes. Clean radiator, change antifreeze. YEARLY Clean and lube the water pump and fan. Make sure meters are correct. Clean control panel and tighten the panel's connections. Verify that the antivibration feet, fittings and belts are in proper condition. 88 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 734 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Make sure that vibration and noise levels comply with the current regulations. Make sure noise emission level is compliant with the current regulations. Check the engine manufacturer's manual for specific tasks. EVERY 3 YEARS Replace startup batteries. 8.0 TROUBLESHOOTING Engine does not start In the electrical panel Engine starts INCIDENT Starter does not turn LIKELY CAUSE 1.-Defective battery 2.-Defective starting system Starter functioning properly 1.-Faulty voltage detector on control module 2.-Low fuel level Stops with cause 1.-Emergency has occurred Stops for no apparent reason 1.-Emergency not indicated due to faulty LED indicator Does not stop when emergency occurs 1.-Defective stopping system Generator does not stop when in stop position 1.-Faulty control unit 2.-Defective Stopping System 1.-Overspeed High voltage at no load 2.-Alternator failure SOLUTION 1.-Replace battery 2.-Replace starting system 3.-Contact technical service. 1.-Contact technical service. 2.-Refill fuel tank 1.-Take appropriate measures 1.-Contact technical service. 1.-Press emergency stop button 2.-Contact technical service. 1.-Press emergency stop button 2.-Contact technical service. 1.-Contact technical service. 1.-Underspeed Low voltage at no load 2.-Alternator failure Correct voltage but low 1.-Heavy load when on load 2.-Underspeed on load 1.-Contact technical service. 1.-Reduce power of loads 2.-Contact technical service. 89 Originating in engine's interior Unit in operation Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 735 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Voltage unstable 3.-Alternator failure 1.-Voltage meter damaged 2.-Engine unsteady 3.-AVR damaged Strange noise inside the unit 1.-Various causes 1.-Contact technical service. 1.-Make sure nothing is preventing the unit from functioning properly. 2.-Contact technical service. 9.0 PROTECTION FROM THE ENVIRONMENT Once the generator set has been installed, it is necessary to remove the packaging, accessories, electrical tools, etc., that were used during the installation process. When it is time to dispose of the batteries, in keeping with environmental regulations it is advisable to take them to an authorized recycling center. For a cleaner environment, recycle all possible items and be sure to not throw electrical components in with the regular garbage so as to comply with european directive 2002/96/EC. These items should be stored separately until being taken for ecological recycling. Q-Pulse Id: TMS1594 Active: 18/04/2016 90 Page 736 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 10.0 WARRANTY The electrical generator warranty covers an entire year, starting from the date it is installed. This should be communicated to Eneraque. (hereinafter "the manufacturer"), in writing, via fax or email. The following information must be included: MODEL, SERIAL NUMBER and INSTALLATION DATE. If the manufacturer is not informed of the installation within a maximum of sixty days from the invoice date, the latter shall be considered the effective start date of the warranty period. If for any reason the installation is not possible within the first sixty days following the invoice date, the manufacturer must be informed thereof in writing. Thus no warranty claims shall be accepted if the manufacturer is not in possession of the aforementioned correspondence. The warranty of the electrical generator will cover any faulty components or assembly not caused by improper use, handling or modification. The warranty does not cover breakdowns caused by connecting the electrical generator to devices not installed or supplied by the manufacturer. Also excluded are breakdowns and damages caused by prolonged or improper storage; should this occur, please see the manufacturer's user manuals. The warranty for the electrical generator shall cover ONLY the replacement parts and labor necessary for the repair of the generator by personnel authorized by the manufacturer. Traveling, kilometers traveled and other expenses deriving from the repair of a generator under warranty are excluded from the warranty coverage and in no case shall the manufacturer be responsible for these covering these expenses, which shall be paid in cash. The decision to accept or reject a warranty shall be made by the manufacturer. In the case of engine and alternator breakdowns, the warranty shall be granted by the provider of said components, according to the particular warranty conditions of those components. The manufacturer reserves the option to request that the faulty element be returned. In such case, all costs related to said return shall be covered by the customer. The warranty for a repair made during the warranty period shall have the same expiration date as the warranty for the electrical generator. The warranty does not cover damage caused by terrorist attacks, natural disasters, sabotage or incidents of a similar nature. If any of the provisions set out does not comply with the legislation of a certain country, the importer is required to notify the manufacturer thereof prior to carrying out the sale transaction. 11.0 NOISE LEVEL Generator sets manufactured by Eneraque produce different acoustic levels depending on the output and soundproofing of the generator set. The noise output is indicated on a sticker affixed to the unit's base frame. Note: If you work near the unit for any extended period of time, it is advisable to use hearing protection. 91 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 737 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 12.0 DECLARATION OF CONFORMITY Eneraque shall deliver a CE "declaration of conformity" form along with the unit, in compliance with the referenced regulations or standardized documents. 13.0 APPENDIX 1: FIGURES Detail of the unit's Identification Label: Q-Pulse Id: TMS1594 [1] Model DVAS 360 E [2] Rated output: 260 kW [3] Power factor: 0.8 [4] Rated frequency: 50Hz Rated figures reduce in altitudes above 1,000m and surrounding temperatures above 40ºC [5] Rated voltage: 400Im/23a0Vge 19- Identification Label [6] Product class: G1 [7] Weight: 4,499 kg [8] Serial no.: 164936 [9] 92 Manufacture date: 01/02/06 Active: 18/04/2016 Page 738 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual # LABELED ITEM DESCRIPTION D => Engine uses Diesel fuel at 1500/1800 rpm V => Engine manufacturer is (V)olvo, (P)erkins, (C)ummins, Mitsubis(H)I or M(T)U. W => The generator set is designed to operate at 60 Hz (1) DVAS 360 E A => The generator set is automatic S => The generator set is soundproofed 360 => Commercial name E => Indicates generator set is standby type (2) Rated power Rated power of generator set expressed in kW. (3) Power factor Indicates power factor of generator set (4) Rated frequency Rated frequency of generator set (Hertz) (5) Rated voltage Rated voltage of generator set (Volts) (6) Product class When withstanding a load, engine will perform according to catalogued response times per ISO 8528 (7) Weight Total weight of generator set (8) Serial no. Serial number of generator manufacture (9) Manufacture date Manufacture date of generator set (10) CE marking indicates that generator set complies with the relevant directives Q-Pulse Id: TMS1594 Active: 18/04/2016 93 Page 739 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Image 20 Placing in operation Image 26: Image 21 Caution with generatorImsagtea2r7t: up Image 22 General warning IMPORTANT CAUTION PLACING IN OPERATION: 1.-Make sure "Battery Shutoff" switch is ImagCeLOS2E3D Undefined Warning Notice 2.-Check engine's water and oil levels. THIS ELECTRICAL GENERATOR COULD START UP WITHOUT PRIOR WARNING Image 24ToEpelerfocrmtrMiAcINaTElNHANaCEz, aturrndthe230 Image 25 Electrical Hazard Volts 400 Volts BATTERY SHUTOFF SWITCH to the OPEN position. 3.-Connect earth pin to a suitable point on the ground. 4.-Make sure electrical power circuit breaker is OPEN. Image 26 Lifting point 5.-Connect cables to connection terminals on circuit breaker. Image 27 Possible battery leakage Image 28 Electrical grounding 6.-Start up ELECTRICAL GENERATOR. 7.-Make sure Voltage and Frequency are correct. Imag8e.-Se2t E9lectNricaol Pisoweer sowiutchtpto uCLtOS9E0D dB position. Image 30 Noise output 114 dB Image 31 Use of hearing protection required BATTERY ISOLATOR Image 32 Coolant Flush Image 33 Oil draining Image 34 Battery Isolator 94 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 740 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 14.0 APPENDIX 2: IMAGE INDEX Image 1- Generator set with sound proof canopy. ............................................................................................6 Image 3- Detailed view of Image 1 ....................................................................................................................7 Image 4- Detailed view of Image 2 ....................................................................................................................8 Image 5- Interior of a soundproofed Electrical Generator ................................ Error! Bookmark not defined. Image 6- Generic Control Panel ......................................................................................................................10 Image 7- Control Panel of GECO Control Module............................................ Error! Bookmark not defined. Image 8- Control Panel of the GPM-2 Control Module..................................... Error! Bookmark not defined. Image 9- Control Panel of the Deep Sea Control Module ................................ Error! Bookmark not defined. Image 10- Control Panel of the InteliGenNT Control Module............................. Error! Bookmark not defined. Image 11- Load Transfer diagram ...................................................................................................................11 Image 13- Lifting frame....................................................................................................................................13 Image 14- Detailed view of installation of an open-skid unit ...........................................................................14 Image 15- SAB-BE Pump ................................................................................. Error! Bookmark not defined. Image 16- ATS setup .......................................................................................................................................19 Image 17- Diagram of ATS Panel....................................................................................................................20 Image 18- GECO Digital Control Module ........................................................................................................29 Image 19- GPM-2 Control Module...................................................................................................................36 Image 20- Deep Sea 7320 Control Module .....................................................................................................42 Image 21- Deep Sea 7310 Control Module .....................................................................................................43 Image 22- Deep Sea 5520 Control Module .....................................................................................................59 Image 23- Deep Sea 5510 Control Module .....................................................................................................60 Image 24- INTELIGENNT Digital Control Module .............................................................................................77 Image 25- Identification Label..........................................................................................................................92 Image 26 Placing in operation .........................................................................................................................94 Image 27 Caution with generator startup ........................................................................................................94 Image 28 General warning ..............................................................................................................................94 Image 29 Undefined Warning Notice...............................................................................................................94 Image 30 Electrical Hazard 230 Volts .............................................................................................................94 Image 31 Electrical Hazard 400 Volts .............................................................................................................94 Image 32 Lifting point ......................................................................................................................................94 Image 33 Possible battery leakage..................................................................................................................94 95 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 741 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Image 34 Electrical grounding .........................................................................................................................94 Image 35 Noise output 90 dB ..........................................................................................................................94 Image 36 Noise output 114 dB ........................................................................................................................94 Image 37 Use of hearing protection required ..................................................................................................94 Image 38 Coolant Flush...................................................................................................................................94 Image 39 Oil draining.......................................................................................................................................94 Image 40 Battery Isolator.................................................................................................................................94 Q-Pulse Id: TMS1594 Active: 18/04/2016 96 Page 742 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 15.0 APPENDIX 3: PRE-DELIVERY INSPECTION DOCUMENT ITEMS TO BE CHECKED First checks Verify the right positioning of the genset Verify that air inlet is enough and according Verify that the hot air outlet from the engine is forwarded outside Verify that the exhaust outlet is piped outside Verify that the genset identifying plate is legible Verify that the alternator identifying plate is legible Verify that the engine identifying plate is legible Verify stickers and warning labels Verify the cabling and genset connexions Verify the earthling of the equipment Before starting the equipment Verify oil level and its conditions Verify fuel level Verify coolant level Verify air filter conditions Verify bolts, nuts and its tightness Verify lights and LEDs from the control panel Verify Battery isolator Verify and re*tight battery terminals Starting of the genset Verify exhaust emission colour Verify there is not strange noises from engine/alternator Verify fuel pipes and flanges OK LP (OK) KO 97 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 743 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Verify that the control card is operating OK Verify phase sequence from genset is equal to Mains Mains Failure Verify the genset start when Mains is cut Verify the ATS closes genset contactor Verify that the genset keeps frequency and voltage on load Verify that, when Mains is back, the control card detects voltage Verify Mains contactors closed Verify genset stops after cooling period END Working mode and installation is OK Explain to the user the working mode Genset Voltage w/o load: Genset Frequency w/o load Remarks Leyend: Ok = Accepted, OK LP = Low problem, OK KO = Remove from service R = Repaired N/A = Not applicable In case that an installation is faulty the client must be informed, so the faults can be solved Predelivery inspection done by Company: Final User: Company: Signed: ID: Q-Pulse Id: TMS1594 Signed: ID: Active: 18/04/2016 98 Page 744 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 16.0 APPENDIX 4: FIGURES IN DEEP SEA CONTROL CARDS. Pictograms DEEP SEA PICTOGRAMS Descripcion Remote Start Auto Start inhibit Common Alarm Common Shutdown Overcurrent Pre-alarm GCB Trip Differential Trip GCB-Differential Trip Q-Pulse Id: TMS1594 Active: 18/04/2016 99 Page 745 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Low coolant level Low fuel level High Engine Temperature Frecuency 60Hz Remote Stop Fuel Filter Alarm Q-Pulse Id: TMS1594 Active: 18/04/2016 100 Page 746 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 17.0 APPENDIX 5: NOISE EMISSIONS Model DCAS 700 E DCAS 860 E DPAS 10 E DPAS 10 E MF DPAS 110 E DPAS 15 E DPAS 15 E MF DPAS 150 E NC DPAS 230 E DPAS 25 E DPAS 25 E MF DPAS 275 E DPAS 35 E MF NC DPAS 400 E DPAS 450 E DPAS 50 E NC DPAS 500 E DPAS 550 E DPAS 65 E NC DPAS 700 E DPAS 90 E NC DVAS 140 E DVAS 165 E Sound Pressure (dB) at 10 m. Sound Power (dB) 77 105 77 105 70 90 70 90 69 97 70 90 70 90 69 97 69 97 70 90 70 90 69 97 62 90 69 97 70 98 66 94 66 94 75 103 66 94 77 105 66 94 69 97 69 97 101 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 747 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DVAS 200 E DVAS 220 E DVAS 275 E DVAS 330 E DVAS 360 E DVAS 410 E DVAS 450 E DVAS 505 E DVAS 550 E DVAS 630 E DVAS 700 E DZAS 165 E DZAS 25 E DZAS 35 E DZAS 45 E 69 97 69 97 69 97 69 97 69 97 69 97 70 98 66 94 66 94 69 97 69 97 69 97 66 94 66 94 66 94 Q-Pulse Id: TMS1594 Active: 18/04/2016 102 Page 748 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 749 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 750 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 751 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 752 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 753 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 754 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 755 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 756 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 757 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 758 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 759 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 760 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 761 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 762 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 763 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 764 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 765 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 766 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 767 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 768 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 769 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 770 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 771 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 772 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 773 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 774 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 775 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 776 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 777 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 778 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 779 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 780 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 781 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 782 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 783 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 784 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 785 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 786 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 787 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 788 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 789 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 790 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 791 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 792 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 793 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 794 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 795 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 796 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 797 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 798 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 799 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 800 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 801 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 802 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 803 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 804 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 805 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 806 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 807 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 808 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 809 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 810 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 811 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 812 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 813 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 814 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 815 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 816 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 817 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 818 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 819 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 820 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 821 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 822 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 823 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 824 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 825 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 826 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 827 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 828 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 829 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 830 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 831 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 832 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSECONTROL® DSE7000 Series Control Module 057-074 Author : Anthony Manton Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 833 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail: sales@deepseaplc.com Website: www.deepseaplc.com DSE Model 7000 series Control and Instrumentation System Operators Manual © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder's written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. The DSE logo and the names DSEUltra, DSEControl, DSEPower, DSEExtra, DSEMarine and DSENet are UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice. Amendments since last publication Amd. No. Comments Clarification of notation used within this publication. NOTE: CAUTION! WARNING! Highlights an essential element of a procedure to ensure correctness. Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment. Indicates a procedure or practice, which could result in injury to personnel or loss of life if not followed correctly. 2 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 834 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual TABLE OF CONTENTS Section Page 1 BIBLIOGRAPHY............................................................................................... 6 2 INTRODUCTION .............................................................................................. 6 3 SPECIFICATIONS ............................................................................................ 7 3.1 PART NUMBERING ........................................................................................................7 3.1.1 MODEL NAMING......................................................................................................7 3.1.2 SHORT NAMES .......................................................................................................7 3.1 POWER SUPPLY REQUIREMENTS...............................................................................8 3.2 TERMINAL SPECIFICATION..........................................................................................8 3.3 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING .................................9 3.4 GENERATOR CURRENT SENSING...............................................................................9 3.5 INPUTS ...........................................................................................................................9 3.5.1 DIGITAL INPUTS......................................................................................................9 3.5.2 ANALOGUE INPUTS..............................................................................................10 3.5.3 CHARGE FAIL INPUT ............................................................................................11 3.5.4 MAGNETIC PICKUP...............................................................................................11 3.6 OUTPUTS .....................................................................................................................11 3.6.1 OUTPUTS A & B ....................................................................................................11 3.6.2 OUTPUTS C & D ....................................................................................................11 3.6.3 OUTPUTS E,F,G & H .............................................................................................11 3.7 COMMUNICATION PORTS ..........................................................................................12 3.8 DSENET® .....................................................................................................................12 3.9 ACCUMULATED INSTRUMENTATION ........................................................................12 3.10 DIMENSIONS AND MOUNTING................................................................................13 3.10.1 FIXING CLIPS ........................................................................................................14 3.10.2 CABLE TIE FIXING POINTS ..................................................................................15 3.10.3 SILICON SEALING GASKET..................................................................................15 3.11 APPLICABLE STANDARDS......................................................................................16 4 INSTALLATION.............................................................................................. 17 4.1 USER CONNECTIONS .................................................................................................17 4.2 TERMINAL DESCRIPTION...........................................................................................18 4.2.1 DC SUPPLY, FUEL AND START OUTPUTS..........................................................18 4.2.2 ANALOGUE SENSOR............................................................................................18 4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION........................................................19 4.2.4 LOAD SWITCHING AND GENERATOR VOLTAGE SENSING ..............................20 4.2.5 MAINS VOLTAGE SENSING..................................................................................20 4.2.6 GENERATOR CURRENT TRANSFORMERS.........................................................21 4.2.7 CONFIGURABLE DIGITAL INPUTS .......................................................................22 4.2.8 PC CONFIGURATION INTERFACE CONNECTOR ...............................................22 4.2.9 RS485 CONNECTOR .............................................................................................23 4.2.10 RS232 CONNECTOR .............................................................................................23 4.3 TYPICAL WIRING DIAGRAMS .....................................................................................24 4.3.1 7210 AUTOSTART CONTROLLER ........................................................................24 4.3.2 7220 AMF CONTROLLER ......................................................................................25 4.3.3 7310 AUTOSTART CONTROLLER ........................................................................26 4.3.4 7320 AMF CONTROLLER ......................................................................................27 4.4 ALTERNATIVE TOPOLOGIES .....................................................................................28 4.4.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION................................28 4.4.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT MEASURING.....................29 4.4.3 SINGLE PHASE WITHOUT EARTH FAULT MEASURING.....................................30 4.4.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT MEASURING ...31 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 3 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 835 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.4.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT MEASURING ...................32 4.4.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT MEASURING ...33 4.4.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING ...................34 4.4.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING .............35 4.5 CT LOCATION..............................................................................................................36 5 DESCRIPTION OF CONTROLS.................................................................... 37 5.1 DSE7210 / DSE7310 AUTOSTART CONTROL MODULE............................................37 5.2 DSE7220 / DSE7320 AMF CONTROL MODULE ..........................................................39 5.3 QUICKSTART GUIDE...................................................................................................41 5.3.1 STARTING THE ENGINE.......................................................................................41 5.3.2 STOPPING THE ENGINE ...................................................................................... 41 5.4 VIEWING THE INSTRUMENTS ....................................................................................42 5.4.1 INSTRUMENT PAGE CONTENT ........................................................................... 43 5.4.2 CAN ERROR MESSAGES ..................................................................................... 44 5.5 VIEWING THE EVENT LOG .........................................................................................45 5.6 USER CONFIGURABLE INDICATORS ........................................................................45 5.7 CONTROLS ..................................................................................................................46 6 OPERATION .................................................................................................. 48 6.1 AUTOMATIC MODE OF OPERATION..........................................................................49 6.1.1 WAITING IN AUTO MODE.....................................................................................49 6.1.2 STARTING SEQUENCE......................................................................................... 49 6.1.3 ENGINE RUNNING ................................................................................................ 50 6.1.4 STOPPING SEQUENCE ........................................................................................ 50 6.2 MANUAL OPERATION .................................................................................................51 6.2.1 WAITING IN MANUAL MODE ................................................................................51 6.2.2 STARTING SEQUENCE......................................................................................... 51 6.2.3 ENGINE RUNNING ................................................................................................ 52 6.2.4 STOPPING SEQUENCE ........................................................................................ 52 6.3 TEST MODE OF OPERATION .....................................................................................53 6.3.1 WAITING IN TEST MODE......................................................................................53 6.3.2 STARTING SEQUENCE......................................................................................... 53 6.3.3 ENGINE RUNNING ................................................................................................ 54 7 PROTECTIONS ............................................................................................. 55 7.1 WARNINGS................................................................................................................... 56 7.2 ANALOGUE PRE-ALARMS .......................................................................................... 57 7.3 HIGH CURRENT WARNING ALARM............................................................................57 7.4 SHUTDOWNS...............................................................................................................58 7.5 HIGH CURRENT SHUTDOWN ALARM ........................................................................59 7.6 ELECTRICAL TRIPS ....................................................................................................59 8 FRONT PANEL CONFIGURATION............................................................... 60 8.1 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR ........................60 8.1.1 EDITING A PARAMETER....................................................................................... 61 8.1.2 ADJUSTABLE PARAMETERS ............................................................................... 62 8.2 ACCESSING THE `RUNNING' CONFIGURATION EDITOR.........................................63 8.2.1 EDITING A PARAMETER....................................................................................... 63 8.2.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR) ............................................. 63 9 COMMISSIONING.......................................................................................... 64 9.1.1 PRE-COMMISSIONING ......................................................................................... 64 10 FAULT FINDING ......................................................................................... 65 11 FACTORY DEFAULT CONFIGURATION .................................................. 67 12 MAINTENANCE, SPARES, REPAIR AND SERVICING ............................. 71 12.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ............................71 12.1.1 DSE7200 SERIES .................................................................................................. 71 12.1.2 DSE7300 SERIES .................................................................................................. 72 12.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE .........................................72 12.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE .................................72 4 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 836 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 12.4 EXPANSION MODULES............................................................................................73 13 WARRANTY ................................................................................................ 74 14 DISPOSAL................................................................................................... 74 14.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ...........................74 14.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) .......................................74 15 APPENDIX................................................................................................... 75 15.1 IDMT TRIPPING CURVES (TYPICAL) ......................................................................75 15.2 SENSOR WIRING RECOMMENDATIONS ................................................................76 15.2.1 EARTH RETURN SENSORS..................................................................................76 15.2.2 INSULATED RETURN SENSORS..........................................................................76 15.3 CAN INTERFACE .....................................................................................................76 15.4 COMMUNICATIONS OPTION CONNECTIONS ........................................................77 15.4.1 DESCRIPTION .......................................................................................................77 15.4.2 PC TO CONTROLLER (DIRECT) CONNECTION...................................................77 15.5 ENCLOSURE CLASSIFICATIONS ............................................................................78 Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 5 Active: 18/04/2016 Page 837 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com DSE PART 053-026 053-027 053-028 053-029 057-004 057-077 057-082 057-083 057-084 DESCRIPTION 7210 installation instructions 7220 installation instructions 7310 installation instructions 7320 installation instructions Electronic Engines and DSE wiring manual DSE7000 Series configuration software manual DSE2130 input expansion manual DSE2157 output expansion manual DSE2548 annunciator expansion manual 2 INTRODUCTION This document details the installation and operation requirements of the DSE7000 Series modules, part of the DSEControl® range of products. The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes. This is not a controlled document. You will not be automatically informed of updates. Any future updates of this document will be included on the DSE website at www.deepseaplc.com The DSE 7000 series is designed to provide differing levels of functionality across a common platform. This allows the generator OEM greater flexibility in the choice of controller to use for a specific application. The DSE 7000 series module has been designed to allow the operator to start and stop the generator, and if required, transfer the load to the generator either manually (via fascia mounted push-buttons) or automatically. Additionally, the DSE7320 automatically starts and stops the generator set depending upon the status of the mains (utility) supply. The user also has the facility to view the system operating parameters via the LCD display. The DSE 7000 module monitors the engine, indicating the operational status and fault conditions, automatically shutting down the engine and giving a true first up fault condition of an engine failure by a COMMON AUDIBLE ALARM. The LCD display indicates the fault. The powerful ARM microprocessor contained within the module allows for incorporation of a range of complex features: · Text based LCD display (supporting multiple languages). · True RMS Voltage, Current and Power monitoring. · Engine parameter monitoring. · Fully configurable inputs for use as alarms or a range of different functions. · Engine ECU interface to electronic engines. Using a PC and the 7000 series configuration software allows alteration of selected operational sequences, timers and alarm trips. Additionally, the module's integral fascia configuration editor allows adjustment of a subset of this information. A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and sockets. 6 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 838 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 3 SPECIFICATIONS 3.1 PART NUMBERING Product type DSE 7210 Autostart Module 7210 DSE 7220 Automatic Mains Failure Module 7220 DSE 7310 Autostart Module 7310 7210 - 001 - 00 Variant Standard 00 product Hardware revision Revision 1 001 DSE 7320 Automatic Mains Failure Module 7320 At the time of this document production, there are no variants of this product and there have been no revisions of the module hardware. 3.1.1 MODEL NAMING 72 10 Series DSE 7200 series 72 DSE 7300 series 73 3.1.2 SHORT NAMES Short name DSE7000 DSE7x10 DSE7x20 DSE72x0 DSE73x0 Function Autostart (remote start) and manual start 10 Autostart, manual start and start upon mains failure 20 (AMF) Description All modules in the DSE7000 Series All Autostart modules in the DSE7000 Series All AMF modules in the DSE7000 Series All modules in the DSE7200 series All modules in the DSE7300 series Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 7 Active: 18/04/2016 Page 839 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 3.1 POWER SUPPLY REQUIREMENTS Minimum supply voltage Cranking dropouts Maximum supply voltage Reverse polarity protection Maximum operating current Maximum standby current 8V continuous Able to survive 0V for 50mS providing the supply was at least 10V before the dropout and recovers to 5V afterwards. 35V continuous (60V protection) -35V continuous DSE7200 / DSE7300 160mA at 24V 340mA at 12V DSE7200 / DSE7300 80mA at 24V 160mA at 12V Plant supply instrumentation display Range Resolution Accuracy 0V-70V DC (note Maximum continuous operating voltage of 35V DC) 0.1V 1% full scale 3.2 TERMINAL SPECIFICATION Connection type Min cable size Max cable size Screw terminal, rising clamp, no internal spring 0.5mm² (AWG 24) 2.5mm² (AWG 10) 8 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 840 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 3.3 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING Measurement type Sample Rate Harmonics Input Impedance Phase to Neutral Phase to Phase Common mode offset from Earth Resolution Accuracy Minimum frequency Maximum frequency Frequency resolution Frequency accuracy True RMS conversion 5KHz or better Up to 10th or better 300K ph-N 15V to 333V AC (max) 25V to 576V AC (max) 100V AC (max) 1V AC phase to neutral 2V AC phase to phase ±1% of full scale phase to neutral ±2% of full scale phase to phase 3.5Hz 75.0Hz 0.1Hz ±0.2Hz 3.4 GENERATOR CURRENT SENSING Measurement type Sample Rate Harmonics Nominal CT secondary rating Maximum continuous current Overload Measurement Absolute maximum overload Burden common mode offset Resolution Accuracy True RMS conversion 5KHz or better Up to 10th or better 1A or 5A 5A 3 x Nominal Range setting 50A for 1 second 0.5VA (0.02 current shunts) ±2V peak plant ground to CT common terminal 0.5% of 5A ±1% of Nominal (1A or 5A) (excluding CT error) 3.5 INPUTS 3.5.1 DIGITAL INPUTS Number Arrangement Low level threshold High level threshold Maximum input voltage Minimum input voltage Contact wetting current Open circuit voltage DSE72x0 6 DSE73x0 8 Contact between terminal and ground 2.1V minimum 6.6V maximum +50V DC with respect to plant supply negative -24V DC with respect to plant supply negative 7mA typical 12V typical Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 9 Active: 18/04/2016 Page 841 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 3.5.2 ANALOGUE INPUTS Oil Pressure Measurement type Arrangement Measurement current Full scale Over range / fail Resolution Accuracy Max common mode voltage Display range Resistance measurement by measuring voltage across sensor with a fixed current applied Differential resistance measurement input 15mA 240 270 1-2 PSI / 0.1 Bar +/-2% of full scale resistance excluding transducer error ±2V 0-200 PSI / 13.7 bar subject to limits of the sensor Coolant Temperature Measurement type Arrangement Measurement current Full scale Over range / fail Resolution Accuracy Max common mode voltage Display range Resistance measurement by measuring voltage across sensor with a fixed current applied Differential resistance measurement input 10mA 480 540 1°C, 2°F +/-2% of full scale resistance excluding transducer error ±2V 0°C -140°C, 32°F - 284°F Depending on sensor Fuel Level Measurement type Arrangement Measurement current Full scale Over range / fail Resolution Accuracy Max common mode voltage Display range Resistance measurement by measuring voltage across sensor with a fixed current applied Differential resistance measurement input 10mA 480 540 1% +/-2% of full scale resistance excluding transducer error ±2V 0-250% Flexible Sensor NOTE : Flexible sensor is not available on DSE7200 series controllers Measurement type Arrangement Measurement current Full scale Over range / fail Resolution Accuracy Max common mode voltage Display range Resistance measurement by measuring voltage across sensor with a fixed current applied Differential resistance measurement input 10mA 480 540 1% +/-2% of full scale resistance excluding transducer error ±2V 0-250% 10 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 842 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 3.5.3 CHARGE FAIL INPUT Minimum voltage Maximum voltage Resolution Accuracy Excitation Output Power Current at 12V Current at 24V 0V 35V (plant supply) 0.2V ± 1% of max measured voltage Active circuit constant power output 2.5W Nominal @12V and 24V 210mA 10mA 3.5.4 MAGNETIC PICKUP Type Minimum voltage Max common mode voltage Maximum voltage Maximum frequency Resolution Accuracy Flywheel teeth Differential input 0.5V RMS ±2V Clamped to ±70V by transient suppressers, dissipation not to exceed 1W. 10,000Hz 6.25 RPM ±25 RPM 10 to 500 3.6 OUTPUTS 3.6.1 OUTPUTS A & B Type Rating Normally used for Fuel / Start outputs. Fully configurable for other purposes if the module is configured to control an electronic engine. Supplied from Emergency Stop terminal 3. 15A @ 35V 3.6.2 OUTPUTS C & D Type Rating Voltage free relays, fully configurable, normally used for generator / mains load switch control. 8A @ 250 V AC 3.6.3 OUTPUTS E,F,G & H Type Rating Fully configurable, supplied from DC supply terminal 2. 3A @ 35V Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 11 Active: 18/04/2016 Page 843 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 3.7 COMMUNICATION PORTS USB Port Serial Communication (not available on DSE7200 series) RS232 Port (not available on DSE7200 series) RS485 Serial (not available on DSE7200 series) CAN Port USB2.0 Device for connection to PC running DSE configuration suite only RS232 and RS485 are fitted but do NOT provide independent operation Non Isolated port Max Baud rate 115K baud subject to S/W TX, RX, RTS, CTS, DSR, DTR, DCD Male 9 way D type connector Isolated Data connection 2 wire + common Half Duplex Data direction control for Transmit (by s/w protocol) Max Baud Rate 19200 External termination required (120R) Max common mode offset 70V (on board protection transorb) Engine CAN Port Standard implementation of `Slow mode', up to 250K bits/s Non Isolated. Internal Termination provided (120) 3.8 DSENET® DSENet® is the interconnection cable between the host controller and the expansion module(s) and must not be connect to any device other than DSE equipment designed for connection to the DSENet® NOTE : DSENet® is not available on DSE7200 series controllers. Cable type Cable characteristic impedance Recommended cable Maximum cable length DSENet® topology DSENet® termination Maximum expansion modules Two core screened twisted pair 120 Belden 9841 Belden 9271 1000m (1km) when using Belden 9841 or direct equivalent. 500m (0.5km) when using Belden 9271 or direct equivalent. Bus with no stubs (spurs) 120. Fitted internally to host controller. Must be fitted externally to the `last' expansion module by the customer . Refer to host controller documentation NOTE : As a termination resistor is internally fitted to the host controller, the host controller must be the `first' unit on the DSENet®. A termination resistor MUST be fitted to the `last' unit on the DSENet®. For connection details, you are referred to the section entitled `typical wiring diagram' elsewhere in this document. 3.9 ACCUMULATED INSTRUMENTATION NOTE : When an accumulated instrumentation value exceeds the maximum number as listed below, it will reset and begin counting from zero again. Engine hours run Number of starts Maximum 99999 hrs 59 minutes (approximately 11yrs 4months) 1,000,000 (1 million) 12 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 844 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 3.10 DIMENSIONS AND MOUNTING DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4" x 7.1" x 1.6") PANEL CUTOUT 220mm x 160mm (8.7" x 6.3") WEIGHT 0.7kg (1.4lb) Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 13 Active: 18/04/2016 Page 845 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 3.10.1 FIXING CLIPS The module is held into the panel fascia using the supplied fixing clips. · Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip. · Insert the three `prongs' of the fixing clip into the slots in the side of the 7000 series module case. · Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are inside their allotted slots. · Turn the fixing clip screws clockwise until they make contact with the panel fascia. · Turn the screws a little more to secure the module into the panel fascia. Care should be taken not to over tighten the fixing clip screws. Fixing clip Fixing clip fitted to module NOTE:- In conditions of excessive vibration, mount the module on suitable anti-vibration mountings. 14 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 846 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 3.10.2 CABLE TIE FIXING POINTS Integral cable tie fixing points are included on the rear of the module's case to aid wiring. This additionally provides strain relief to the cable loom by removing the weight of the loom from the screw connectors, thus reducing the chance of future connection failures. Care should be taken not to overtighten the cable tie (for instance with cable tie tools) to prevent the risk of damage to the module case. Cable tie fixing point With cable and tie in place 3.10.3 SILICON SEALING GASKET The supplied silicon gasket provides improved sealing between the 7000 series module and the panel fascia. The gasket is fitted to the module before installation into the panel fascia. Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal. Sealing gasket Gasket fitted to module Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 15 Active: 18/04/2016 Page 847 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 3.11 APPLICABLE STANDARDS BS 4884-1 BS 4884-2 BS 4884-3 BS EN 60068-2-1 (Minimum temperature) BS EN 60068-2-2 (Maximum temperature) BS EN 60950 BS EN 61000-6-2 BS EN 61000-6-4 BS EN 60529 (Degrees of protection provided by enclosures) UL508 NEMA rating (Approximate) IEEE C37.2 (Standard Electrical Power System Device Function Numbers and Contact Designations) This document conforms to BS4884-1 1992 Specification for presentation of essential information. This document conforms to BS4884-2 1993 Guide to content This document conforms to BS4884-3 1993 Guide to presentation -30°C (-22°F) +70°C (158°F) Safety of information technology equipment, including electrical business equipment EMC Generic Immunity Standard (Industrial) EMC Generic Emission Standard (Industrial) IP65 (front of module when installed into the control panel with the supplied sealing gasket) IP42 (front of module when installed into the control panel WITHOUT being sealed to the panel) 12 (Front of module when installed into the control panel with the supplied sealing gasket). 2 (Front of module when installed into the control panel WITHOUT being sealed to the panel) Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor devices and software programs. The 7000 series controller is device number 11L-7000 (Multifunction device protecting Line (generator) 7000 series module). As the module is configurable by the generator OEM, the functions covered by the module will vary. Under the module's factory configuration, the device numbers included within the module are : 2 Time delay starting or closing relay 6 Starting circuit breaker 27AC AC undervoltage relay 27DC DC undervoltage relay 30 annunciator relay 42 Running circuit breaker 50 instantaneous overcurrent relay 51 ac time overcurrent relay 52 ac circuit breaker 53DC exciter or dc generator relay 54 turning gear engaging device 59AC AC overvoltage relay 59DC DC overvoltage relay 62 time delay stopping or opening relay 63 pressure switch 74 alarm relay 81 frequency relay 86 lockout relay In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice. 16 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 848 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4 INSTALLATION The DSE7000 Series module is designed to be mounted on the panel fascia. For dimension and mounting details, see the section entitled Specification, Dimension and mounting elsewhere in this document. 4.1 USER CONNECTIONS To aid user connection, icons are used on the rear of the module to help identify terminal functions. An example of this is shown below. NOTE : Availability of some terminals depends upon module version. Full details are given in the section entitled Terminal Description elsewhere in this manual. Terminals 39-46 Terminals 47-50 Terminals 51-55 Terminals 60-67 RS485 connection RS232 connection USB Connection Terminals 1-11 Terminals 15-19 Terminals 22-30 Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 17 Active: 18/04/2016 Page 849 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.2 TERMINAL DESCRIPTION 4.2.1 DC SUPPLY, FUEL AND START OUTPUTS PIN No 1 DESCRIPTION DC Plant Supply Input (Negative) 2 DC Plant Supply Input (Positive) 3 Emergency Stop Input 4 Output relay A (FUEL) 5 Output relay B (START) 6 Charge fail / excite 7 Functional Earth 8 Output relay E 9 Output relay F 10 Output relay G 11 Output relay H CABLE SIZE 2.5mm² AWG 13 2.5 mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 1.0mm² AWG 18 1.0mm² AWG 18 1.0mm² AWG 18 1.0mm² AWG 18 NOTES (Recommended Maximum Fuse 15A anti-surge) Supplies the module (2A anti-surge requirement) and Output relays E,F,G & H Plant Supply Positive. Also supplies outputs 1 & 2. (Recommended Maximum Fuse 20A) Plant Supply Positive from terminal 3. 15 Amp rated. Fixed as FUEL relay if electronic engine is not configured. Plant Supply Positive from terminal 3. 15 Amp rated. Fixed as START relay if electronic engine is not configured. Do not connect to ground (battery negative). If charge alternator is not fitted, leave this terminal disconnected. Connect to a good clean earth point. Plant Supply Positive from terminal 2. 3 Amp rated. Plant Supply Positive from terminal 2. 3 Amp rated. Plant Supply Positive. from terminal 2. 3 Amp rated. Plant Supply Positive from terminal 2. 3 Amp rated. NOTE:- Terminals 12 to 14 are not fitted to the DSE7200/DSE7300 series controller. NOTE:- When the module is configured for operation with an electronic engine, FUEL and START output requirements may be different. Refer to Electronic Engines and DSE Wiring for further information. Part No. 057-004. 4.2.2 ANALOGUE SENSOR PIN No 15 DESCRIPTION Sensor Common Return 16 Oil Pressure Input 17 Coolant Temperature Input 18 Fuel Level input 19 Flexible sensor (not available on 7200 series controller) CABLE SIZE 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 NOTES Return feed for sensors* Connect to Oil pressure sensor Connect to Coolant Temperature sensor Connect to Fuel Level sensor Connect to additional sensor (user configurable) NOTE:- Terminals 20 and 21 are not fitted to the 7200/7300 series controller. NOTE*:- If using single terminal sensors refer to the Appendix section entitled "Sensor wiring recommendations" elsewhere in this manual. 18 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 850 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION PIN No 22 23 24 25 26 27 28 29 30 DESCRIPTION Magnetic pickup Positive Magnetic pickup Negative Magnetic pickup screen CAN port H CAN port L CAN port Common + SCR CABLE SIZE 0.5mm² AWG 20 0.5mm² AWG 20 Shield 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 NOTES Connect to Magnetic Pickup device Connect to Magnetic Pickup device Connect to ground at one end only Use only 120 CAN approved cable Use only 120 CAN approved cable Use only 120 CAN approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable NOTE:- Terminals 31 to 38 are not fitted to the 7200 / 7300 controller NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is earthed at one end ONLY. NOTE:- Screened 120 impedance cable specified for use with CAN must be used for the CAN link and the Multiset comms link. DSE stock and supply Belden cable 9841 which is a high quality 120 impedance cable suitable for CAN use (DSE part number 016-030) NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should be left unconnected. Engine speed is transmitted to the 7000 series controller on the CAN link. Refer to Electronic Engines and DSE Wiring for further information. Part No. 057-004. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 19 Active: 18/04/2016 Page 851 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.2.4 LOAD SWITCHING AND GENERATOR VOLTAGE SENSING PIN No 39 DESCRIPTION Output relay C 40 Output relay C 41 Output relay D 42 Output relay D 43 Generator L1 (U) voltage monitoring 44 Generator L2 (V) voltage monitoring input 45 Generator L3 (W) voltage monitoring input 46 Generator Neutral (N) input CABLE SIZE 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 1.0mm² AWG 18 1.0mm² AWG 18 1.0mm² AWG 18 1.0mm² AWG 18 NOTES Normally configured to control mains contactor coil (Recommend 10A fuse) Normally configured to control mains contactor coil Normally configured to control generator contactor coil (Recommend 10A fuse) Normally configured to control generator contactor coil Connect to generator L1 (U) output (AC) (Recommend 2A fuse) Connect to generator L2 (V) output (AC) (Recommend 2A fuse) Connect to generator L3 (W) output (AC) (Recommend 2A fuse) Connect to generator Neutral terminal (AC) NOTE:- The above table describes connections to a three phase, four wire alternator. For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual. 4.2.5 MAINS VOLTAGE SENSING PIN No 47 DESCRIPTION Mains L1 (R) voltage monitoring 48 Mains L2 (S) voltage monitoring 49 Mains L3 (T) voltage monitoring 50 Mains Neutral (N) input CABLE SIZE 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 NOTES Connect to Mains L1 (R) incoming supply (AC) (Recommend 2A fuse) Connect to Mains L1 (S) incoming supply (AC) (Recommend 2A fuse) Connect to Mains L1 (T) incoming supply (AC) (Recommend 2A fuse) Connect to Mains N incoming supply (AC) NOTE:- Terminals 47-50 are not fitted to the 7210 / 7310 controller. 20 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 852 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.2.6 GENERATOR CURRENT TRANSFORMERS WARNING!:- Do not disconnect this plug when the CTs are carrying current. Disconnection will open circuit the secondary of the C.T.'s and dangerous voltages may then develop. Always ensure the CTs are not carrying current and the CTs are short circuit connected before making or breaking connections to the module. NOTE:- The 7000 series module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden of the 7000 series controller, the cable length being used and any other equipment sharing the CT. If in doubt, consult your CT supplier. PIN No 51 DESCRIPTION CT Secondary for Gen L1 52 CT Secondary for Gen L2 53 CT Secondary for Gen L3 Connection to terminals 54 & 55 CABLE SIZE 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 NOTES Connect to s1 secondary of L1 monitoring CT Connect to s1 secondary of L2 monitoring CT Connect to s1 secondary of L3 monitoring CT The function of terminals 54 and 55 change position depending upon wiring topology as follows : Type 7200 series All Topology Pin No 54 Description DO NOT CONNECT 55 Common for CTs connected to L1,L2,L3 No earth fault measuring 54 DO NOT CONNECT 55 Common for CTs connected to L1,L2,L3 7300 series Restricted earth fault measuring 54 Common for CTs connected to L1,L2,L3,N 55 Connect to CT on the neutral conductor Un-restricted earth fault measuring 54 (Earth fault CT is fitted in the neutral to earth link) 55 DO NOT CONNECT Common for CTs connected to L1,L2,L3 CABLE SIZE 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 2.5mm² AWG 13 NOTE:- Terminals 56 to 59 are not fitted to the 7200 / 7300 series controller. NOTE:- Take care to ensure correct polarity of the CT primary as shown below. If in doubt, check with the CT supplier. CT labelled as p1, k or K To Load To Supply CT labelled as p2, l or L Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 21 Active: 18/04/2016 Page 853 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.2.7 CONFIGURABLE DIGITAL INPUTS PIN No 60 61 62 63 64 65 66 67 DESCRIPTION Configurable digital input A Configurable digital input B Configurable digital input C Configurable digital input D Configurable digital input E Configurable digital input F Configurable digital input G (not available on 7200 series) Configurable digital input H (not available on 7200 series) CABLE SIZE 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 0.5mm² AWG 20 Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative NOTES NOTE:- Terminals 66 to 69 are not fitted to the 7200 series controller. NOTE:- Terminals 68 and 69 are not fitted to the 7300 series controller. 4.2.8 PC CONFIGURATION INTERFACE CONNECTOR This configuration cable is the same as normally used between a PC and a USB printer! DESCRIPTION Socket for connection to PC with 7xxx series PC software. CABLE SIZE 0.5mm² AWG 20 NOTES This is a standard USB type A to type B connector. NOTE:- The USB connection cable between the PC and the 7000 series module must not be extended beyond 5m (5yds). For distances over 5m, it is possible to use a third party USB extender. Typically, they extend USB up to 50m (yds). The supply and support of this type of equipment is outside the scope of Deep Sea Electronics PLC. CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the recommended number of USB devices to the PC. For further information, consult your PC supplier. CAUTION!: This socket must not be used for any other purpose. 22 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 854 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.2.9 RS485 CONNECTOR NOTE:- RS485 connector is not fitted to the 7200 series controller. PIN No A B SCR NOTES Two core screened twisted pair cable. 120 impedance suitable for RS485 use. Recommended cable type - Belden 9841 Max distance 1000m (1km) when using Belden 9841 or direct equivalent. Location of RS485 connector 4.2.10 RS232 CONNECTOR Location of RS232 connector NOTE:- RS232 connector is not fitted to the 7200 series controller. PIN No 1 2 3 4 5 6 7 8 9 NOTES Received Line Signal Detector (Data Carrier Detect) Received Data Transmit Data Data Terminal Ready Signal Ground Data Set Ready Request To Send Clear To Send Ring Indicator View looking into the male connector on the 7000 series module Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 23 Active: 18/04/2016 Page 855 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.3 TYPICAL WIRING DIAGRAMS 4.3.1 7210 AUTOSTART CONTROLLER 3 phase, 4 wire 24 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 856 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.3.2 7220 AMF CONTROLLER 3 phase, 4 wire Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 25 Active: 18/04/2016 Page 857 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.3.3 7310 AUTOSTART CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing the neutral conductor `before' the neutral CT allows the module to read earth faults `after' the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor `after' the neutral CT allows the module to read earth faults `before' the CT only (Restricted to generator / upstream of the CT) 26 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 858 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.3.4 7320 AMF CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing the neutral conductor `before' the neutral CT allows the module to read earth faults `after' the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor `after' the neutral CT allows the module to read earth faults `before' the CT only (Restricted to generator / upstream of the CT) Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 27 Active: 18/04/2016 Page 859 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.4 ALTERNATIVE TOPOLOGIES The 7000 controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This section details connections for alternative AC topologies. Ensure to configure the 7000 series controller to suit the required topology. NOTE:- Further details of module configuration are contained within the DSE7000 Series configuration software manual (DSE part number 057-077) 4.4.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. 28 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 860 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.4.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault measuring not available on 7200 series controllers. NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. NOTE:- Earthing the neutral conductor `before' the neutral CT allows the module to read earth faults `after' the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor `after' the neutral CT allows the module to read earth faults `before' the CT only (Restricted to generator / upstream of the CT) Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 29 Active: 18/04/2016 Page 861 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.4.3 SINGLE PHASE WITHOUT EARTH FAULT MEASURING NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. 30 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 862 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.4.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault measuring not available on 7200 series controllers. NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. NOTE:- Earthing the neutral conductor `before' the neutral CT allows the module to read earth faults `after' the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor `after' the neutral CT allows the module to read earth faults `before' the CT only (Restricted to generator / upstream of the CT) Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 31 Active: 18/04/2016 Page 863 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.4.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT MEASURING NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. 32 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 864 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.4.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault measuring not available on 7200 series controllers. NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. NOTE:- Earthing the neutral conductor `before' the neutral CT allows the module to read earth faults `after' the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor `after' the neutral CT allows the module to read earth faults `before' the CT only (Restricted to generator / upstream of the CT) Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 33 Active: 18/04/2016 Page 865 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.4.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. 34 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 866 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 4.4.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault measuring not available on 7200 series controllers. NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ DSE7310 autostart controllers. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 35 Active: 18/04/2016 Page 867 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 4.5 CT LOCATION NOTE:- CT Location is not applicable to the DSE7210 / DSE7310 autostart controllers. There are two possible locations for the current transformers in the system: 1) Generator : The CTs are used to measure and display generator current only. The typical wiring diagrams in the preceding section all show the CT measuring the generator load. For clarity, an example is shown below. 2) Load : The CTs are used to measure and display generator current when the generator is on load and mains current when the mains is on load. The module display automatically changes to display the current in the relevant instrumentation page. This example shows the CTs in the `load' for a three phase delta system but the same philosophy is applicable to the other topologies. 36 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 868 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 5 DESCRIPTION OF CONTROLS The following section details the function and meaning of the various controls on the module. 5.1 DSE7210 / DSE7310 AUTOSTART CONTROL MODULE Menu navigation buttons Main status and instrumentation display Four configurable LEDs Open generator (manual mode only) Select Stop mode Select Manual mode Select Auto mode Close generator (manual mode only) Start engine (when in manual mode) Mute alarm / Lamp test Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 37 Active: 18/04/2016 Page 869 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- "Generator on load" LED has two modes of operation depending upon the configuration of the controllers digital inputs. 1) Digital input configured for "Generator closed auxiliary" The LED illuminates when the generator closed auxiliary input is active The LED shows the state of the auxiliary contact. 2) There is NO input configured for "Generator closed auxiliary" (factory default setting) The LED illuminates when the 7x20 gives the loading signal to the generator The LED shows the state of the 7x20's loading request. 38 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 870 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 5.2 DSE7220 / DSE7320 AMF CONTROL MODULE Menu navigation buttons Main status and instrumentation display Four configurable LEDs Transfer to mains (manual mode only) Select Stop mode Continued overleaf.... Select Manual mode Select Test on load mode Select Auto mode Transfer to generator (manual mode only) Start engine (when in manual mode) Mute alarm / Lamp test Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 39 Active: 18/04/2016 Page 871 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual Mains Available LED. On when the mains is within limits and able to take load. Close Mains LED. On When The Generator Is Required To Be On Load. Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- "Generator on load" LED has two modes of operation depending upon the configuration of the controllers digital inputs. 3) Digital input configured for "Generator closed auxiliary" The LED illuminates when the generator closed auxiliary input is active The LED shows the state of the auxiliary contact. 4) There is NO input configured for "Generator closed auxiliary" (factory default setting) The LED illuminates when the 7x20 gives the loading signal to the generator The LED shows the state of the 7x20's loading request. NOTE:- "Mains on load" LED has two modes of operation depending upon the configuration of the controllers digital inputs. 5) Digital input configured for "Mains closed auxiliary" The LED illuminates when the mains closed auxiliary input is active The LED shows the state of the auxiliary contact. 6) There is NO input configured for "Mains closed auxiliary" (factory default setting) The LED illuminates when the 7x20 gives the loading signal to the mains The LED shows the state of the 7x20's loading request. 40 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 872 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 5.3 QUICKSTART GUIDE This section provides a quick start guide to the module's operation. 5.3.1 STARTING THE ENGINE First, select manual mode... ...then press the Start button to crank the engine. NOTE:- For further details, see the section entitled `OPERATION' elsewhere in this manual. 5.3.2 STOPPING THE ENGINE Select Stop/Reset mode. The generator is stopped. NOTE:- For further details, see the section entitled `OPERATION' elsewhere in this manual. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 41 Active: 18/04/2016 Page 873 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 5.4 VIEWING THE INSTRUMENTS It is possible to scroll to display the different pages of information by repeatedly operating the next page button. Once selected the page will remain on the LCD display until the user selects a different page or after an extended period of inactivity, the module will revert to the status display. If no buttons are pressed upon entering an instrumentation page, the instruments will be displayed automatically subject to the setting of the Scroll Delay. Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll or buttons. The `autoscroll' is disabled. To re-enable `autoscroll' press the or Engine). buttons to scroll to the `title' of the instrumentation page (ie When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer. If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator's attention to the alarm condition. Page order:- Status, Engine, Generator, Mains, Alarms, ECU DTCs (electronic engines only), Event log, Scheduler (if enabled), About. First page - Press to change to the next page - Status Engine If you want to view one of the instruments towards the end of the list, it may be quicker to scroll up through the instruments rather than down! Press to change to the next page - Generator 42 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 874 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 5.4.1 INSTRUMENT PAGE CONTENT Engine · Engine Speed · Oil Pressure · Coolant Temperature · Engine Battery Volts · Run Time · Oil Temperature* · Coolant Pressure* · Inlet Temperature* · Exhaust Temperature* · Fuel Temperature* · Turbo Pressure · Fuel Pressure* · Fuel Consumption* · Fuel Used* · Fuel Level* · Auxiliary Sensors (If fitted and configured) · Engine Maintenance Due (If configured) · Engine ECU Link* *When connected to suitably configured and compatible engine ECU. For details of supported engines see `Electronic Engines and DSE wiring' (DSE Part number 057-004) Generator · Generator Voltage (ph-N) · Generator Voltage (ph-ph) · Generator Frequency · Generator Current · Generator Earth Current · Generator Load (kW) · Generator Load (kVA) · Generator Power Factor · Generator Load (kVAr) · Generator Load (kWh, kVAh, kVArh) · Generator Phase Sequence Mains (DSE7220/DSE7320 only) · Mains Voltage (ph-N) · Mains Voltage (ph-ph) · Mains Frequency About · Module Type · Application Version · USB ID unique identifier for PC USB connection · Analogue Measurements Version · Firmware Update Bootloader Version Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 43 Active: 18/04/2016 Page 875 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 5.4.2 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7000 series controller displays alarm status messages from the ECU. Alarm ECU Warning Type of alarm as reported by the ECU Warning Type of alarm that is triggered in the DSE module (ie Warning or Shutdown) Press to access the list of current active Engine DTCs (Diagnostic Trouble Codes). Engine DTCs Water Level Low Xxx,xxx,xxx The code interpreted by the module shows on the display as a text message. Additionally, the manufactures code is shown. NOTE:- For details on these code meanings, refer to the ECU instructions provided by the engine manufacturer, or contact the engine manufacturer for further assistance. NOTE:- For further details on connection to electronic engines please refer to Electronic engines and DSE wiring. Part No. 057-004 44 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 876 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 5.5 VIEWING THE EVENT LOG Event log 1/50 Oil Pressure Low Shutdown 12 Sep 2007, 08:25:46 Number of present alarms. This is event 1 of a total of 50 logged events. The 7000 series modules maintains a log of the last 50 shutdown alarms (7200 series logs 30 shutdown alarms) to enable the operator or engineer to view the past alarms history. The event log only includes shutdown and electrical trip alarms logged; The event log does not contain Warning alarms. If All warnings are latched is configured, the event log will capture warning alarms. For more details consult the 7xxx series configuration software manual. Once the log is full, any subsequent shutdown alarms will overwrite the oldest entry in the log. Hence, the log will always contain the most recent shutdown alarms. The module logs the alarm, along with the date and time of the event in the format shown in this example. To view the event log, repeatedly press the next page button until the LCD screen displays the Event log. Press down to view the next most recent shutdown alarm: Continuing to press down cycles through the past alarms after which the display shows the most recent alarm and the cycle begins again. To exit the event log and return to viewing the instruments, press the next page button. 5.6 USER CONFIGURABLE INDICATORS These LEDs can be configured by the user to indicate any one of 100+ different functions based around the following:· Indications - Monitoring of a digital input and indicating associated functioning user's equipment - Such as Battery Charger On or Louver's Open, etc. · WARNINGS and SHUTDOWNS - Specific indication of a particular warning or shutdown condition, backed up by LCD indication - Such as Low Oil Pressure Shutdown, Low Coolant level, etc. · Status Indications - Indication of specific functions or sequences derived from the modules operating state - Such as Safety On, Preheating, Panel Locked, Generator Available, etc. User configurable LEDs Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 45 Active: 18/04/2016 Page 877 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 5.7 CONTROLS Stop / Reset This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will automatically instruct the changeover device to unload the generator (`Close Generator' becomes inactive (if used)). The fuel supply de-energises and the engine comes to a standstill. Should a remote start signal be present while operating in this mode, a remote start will not occur. Manual This mode allows manual control of the generator functions. Once in Manual mode the module will respond to the start button, start the engine, and run off load. If the engine is running off-load in the Manual mode and a remote start signal becomes present, the module will automatically instruct the changeover device to place the generator on load (`Close Generator' becomes active (if used)). Upon removal of the remote start signal, the generator remains on load until either selection of the `STOP/RESET' or `AUTO' modes. For further details, please see the more detailed description of `Manual operation' elsewhere in this manual. Auto This button places the module into its `Automatic' mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and mains supply status and once a start request is made, the set will be automatically started and placed on load. Upon removal of the starting signal, the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event. For further details, please see the more detailed description of `Auto operation' elsewhere in this manual. Test (DSE7220/DSE7320 only) This button places the module into its `Test' mode. This allows an on load test of the generator. Once in Test mode the module will respond to the start button, start the engine, and run on load. For further details, please see the more detailed description of `Test operation' elsewhere in this manual. Start This button is only active in STOP/RESET or MANUAL mode. Pressing this button in manual or test mode will start the engine and run off load (manual) or on load (test). Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly configured and fitted to a compatible engine ECU) Mute / Lamp Test This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature/ When correctly configured and fitted to a compatible engine ECU, pressing this button in STOP/RESET mode after pressing the START "passive" alarms on the engine ECU. button (to power the ECU) will cancel any 46 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 878 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual Transfer to generator Allows the operator to transfer the load to the generator (when in Manual mode only) Open generator (DSE7210/DSE7310 only) Allows the operator to open the generator (when in Manual mode only) Transfer to mains (DSE7220/DSE7320 only) Allows the operator to transfer the load to the mains (when in Manual mode only) Menu navigation Used for navigating the instrumentation, event log and configuration screens. For further details, please see the more detailed description of these items elsewhere in this manual. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 47 Active: 18/04/2016 Page 879 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 6 OPERATION The following description details the sequences followed by a module containing the standard `factory configuration'. Remember that if you have purchased a completed generator set or control panel from your supplier, the module's configuration will probably have been changed by them to suit their particular requirements. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field. 48 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 880 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 6.1 AUTOMATIC MODE OF OPERATION NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate auto mode be pressing the pushbutton. An LED indicator beside the button confirms this action. Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user intervention. 6.1.1 WAITING IN AUTO MODE If a starting request is made, the starting sequence will begin. Starting requests can be from the following sources : · Mains supply out of limits (DSE7220/7320 only) · Activation of an auxiliary input that has been configured to remote start · Activation of the inbuilt exercise scheduler. 6.1.2 STARTING SEQUENCE To allow for `false' start requests such as mains brownouts, the start delay timer begins. Should all start requests be removed during the start delay timer, the unit will return to a stand-by state. If a start request is still present at the end of the start delay timer, the fuel relay is energised and the engine will be cranked. NOTE:- If the unit has been configured for CAN, compatible ECU's will receive the start command via CAN. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt is made. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and the display shows Fail to Start. When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be derived from the main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by PC using the 7000 series configuration software). Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect underspeed or overspeed). NOTE:- If the unit has been configured for CAN, speed sensing is via CAN. After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 49 Active: 18/04/2016 Page 881 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 6.1.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load. DSE7210/DSE7310 - The generator will be placed on load. DSE7220/DSE7320 - Load will be transferred from the mains supply to the generator NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine. If all start requests are removed, the stopping sequence will begin. 6.1.4 STOPPING SEQUENCE The return delay timer operates to ensure that the starting request has been permanently removed and isn't just a short term removal. Should another start request be made during the cooling down period, the set will return on load. If there are no starting requests at the end of the return delay timer, the load is transferred back from the generator to the mains supply and the cooling timer is initiated. The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly important where turbo chargers are fitted to the engine. After the cooling timer has expired, the set is stopped. 50 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 882 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 6.2 MANUAL OPERATION NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate Manual mode be pressing the pushbutton. An LED indicator beside the button confirms this action. Manual mode allows the operator to start and stop the set manually, and if required change the state of the load switching devices. 6.2.1 WAITING IN MANUAL MODE When in manual mode, the set will not start automatically. To begin the starting sequence, press the button. 6.2.2 STARTING SEQUENCE NOTE:- There is no start delay in this mode of operation. The fuel relay is energised and the engine is cranked. NOTE:- If the unit has been configured for CAN, compatible ECU's will receive the start command via CAN. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt is made. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and the display shows Fail to Start. When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be derived from the main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by PC using the 7000 series configuration software). Additionally, rising oil pressure can be used disconnect the starter motor (but cannot detect underspeed or overspeed). NOTE:- If the unit has been configured for CAN, speed sensing is via CAN. After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 51 Active: 18/04/2016 Page 883 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 6.2.3 ENGINE RUNNING In manual mode, the load is not transferred to the generator unless a `loading request' is made. A loading request can come from a number of sources. · Pressing the transfer to generator button · Mains supply out of limits (DSE7220/DSE7320 only) · Activation of an auxiliary input that has been configured to remote start on load · Activation of the inbuilt exercise scheduler if configured for `on load' runs. NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine. Once the load has been transferred to the generator, it will not be automatically transferred back to the mains supply. To manually transfer the load back to the mains either: · Press the transfer to mains button (DSE7220/DSE7320 only) · Press the Open Generator button (DSE7210/DSE7310 only) · Press the auto mode button to return to automatic mode. 6.2.4 STOPPING SEQUENCE In manual mode the set will continue to run until either : · The stop button is pressed The set will immediately stop · The auto button is pressed. The set will observe all auto mode start requests and stopping timers before beginning the Auto mode stopping sequence. 52 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 884 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 6.3 TEST MODE OF OPERATION NOTE:- Test Mode is only applicable to DSE7220/DSE7320 controllers. NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action. Test mode will start the set and transfer the load to the generator to provide a Test on load function. 6.3.1 WAITING IN TEST MODE When in test mode, the set will not start automatically. To begin the starting sequence, press the button. 6.3.2 STARTING SEQUENCE The set begins to crank. NOTE:- If the unit has been configured for CAN, compatible ECU's will receive the start command via CAN. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt is made. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and the display shows Fail to Start. When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be derived from the main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by PC using the 7000 series configuration software). Additionally, rising oil pressure can be used disconnect the starter motor (but cannot detect underspeed or overspeed). NOTE:- If the unit has been configured for CAN, speed sensing is via CAN. After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 53 Active: 18/04/2016 Page 885 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 6.3.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load. Load will be automatically transferred from the mains supply to the generator. NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine. In test mode, the set will continue to run on load until either: · The stop button is pressed The set will immediately stop · The auto button is pressed. The set will observe all auto mode start requests and stopping timers before beginning the Auto mode stopping sequence. 54 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 886 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 7 PROTECTIONS When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will illuminate. The audible alarm can be silenced by pressing the Mute button The LCD display will jump from the `Information page' to display the Alarm Page Alarm 1/2 Warning Low oil pressure Number of present alarms. This is alarm 1 of a total of 2 present alarms The type of alarm. E.g. Shutdown or warning The nature of alarm, eg Low oil pressure The LCD will display multiple alarms E.g. "High Engine Temperature shutdown", "Emergency Stop" and "Low Coolant Warning". These will automatically scroll round in the order that they occurred; In the event of a warning alarm, the LCD will display the appropriate text. If a shutdown then occurs, the module will again display the appropriate text. Example:- Alarm 1/2 Warning Oil pressure Low Alarm 2/2 Shutdown Coolant Temperature High Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 55 Active: 18/04/2016 Page 887 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 7.1 WARNINGS Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition. Example Alarm 1/1 Charge Failure Warning In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and shutdowns. By default, warning alarms are self-resetting when the fault condition is removed. However enabling `all warnings are latched' will cause warning alarms to latch until reset manually. This is enabled using the 7000 series configuration suite in conjunction with a compatible PC. Display CHARGE FAILURE BATTERY UNDER VOLTAGE BATTERY OVER VOLTAGE FAIL TO STOP Reason The auxiliary charge alternator voltage is low as measured from the W/L terminal. The DC supply has fallen below the low volts setting level for the duration of the low battery volts timer The DC supply has risen above the high volts setting level for the duration of the high battery volts timer The module has detected a condition that indicates that the engine is running when it has been instructed to stop. AUXILIARY INPUTS LOW FUEL LEVEL CAN ECU ERROR NOTE:- `Fail to Stop' could indicate a faulty oil pressure sensor - If engine is at rest check oil sensor wiring and configuration. Auxiliary inputs can be user configured and will display the message as written by the user. The level detected by the fuel level sensor is below the low fuel level setting. The engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module's display. 56 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 888 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 7.2 ANALOGUE PRE-ALARMS The following alarms are termed `pre-alarms' as they pre-warn the operator of a potentially more serious alarm condition. For instance, if the engine temperature rises past the pre alarm level, a warning condition will occur to notify the operator. If the temperature falls below this level, then the alarm ceases, and the set will continue to run as normal. However if the temperature continues to rise until the coolant temperature trip point is reached, the warning is escalated and a high coolant temperature shutdown is initiated. Example Alarm 1/1 Oil Pressure Low Warning By default, analogue pre alarms are self-resetting when the fault condition is removed. However enabling `all warnings are latched' will cause warning alarms to latch until reset manually. This is enabled using the 7000 series configuration suite in conjunction with a compatible PC. Display LOW OIL PRESSURE ENGINE HIGH TEMPERATURE ENGINE LOW TEMPERATURE OVERSPEED UNDERSPEED GENERATOR OVER FREQUENCY GENERATOR UNDER FREQUENCY GENERATOR OVER VOLTAGE GENERATOR UNDER VOLTAGE ECU WARNING Reason The module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired. The module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired. The module detects that the engine coolant temperature has fallen below the high engine temperature pre-alarm setting level. The engine speed has risen above the overspeed pre alarm setting The engine speed has fallen below the underspeed pre alarm setting The generator output frequency has risen above the pre-set pre-alarm setting. The generator output frequency has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. The generator output voltage has risen above the pre-set pre-alarm setting. The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. The engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module's display. If the module is configured for CAN and receives an "error" message from the engine control unit, `Can ECU Warning" is shown on the module's display and a warning alarm is generated. 7.3 HIGH CURRENT WARNING ALARM GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a warning alarm initiates. The module shows Alarm Warning High Current. If this high current condition continues for an excess period, then the alarm escalates to a shutdown condition. For further details of the high current alarm, please see High Current Shutdown Alarm. By default, High Current Warning Alarm is self-resetting when the overcurrent condition is removed. However enabling `all warnings are latched' will cause the alarm to latch until reset manually. This is enabled using the 7000 series configuration suite in conjunction with a compatible PC. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 57 Active: 18/04/2016 Page 889 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 7.4 SHUTDOWNS Shutdowns are latching alarms and stop the Generator. Clear the alarm and remove the fault then press Stop/Reset to reset the module. Example Alarm 1/1 Oil Pressure Low Shutdown NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains, it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and similar `delayed alarms', as the oil pressure will be low with the engine at rest). Display FAIL TO START EMERGENCY STOP Reason The engine has not fired after the preset number of start attempts The emergency stop button has been depressed. This a failsafe (normally closed to battery positive) input and will immediately stop the set should the signal be removed. Removal of the battery positive supply from the emergency stop input will also remove DC supply from the Fuel and Start outputs of the controller. NOTE:- The Emergency Stop Positive signal must be present otherwise the unit will shutdown. LOW OIL PRESSURE ENGINE HIGH TEMPERATURE OVERSPEED The engine oil pressure has fallen below the low oil pressure trip setting level after the Safety On timer has expired. The engine coolant temperature has exceeded the high engine temperature trip setting level after the Safety On timer has expired. The engine speed has exceeded the pre-set trip NOTE:-During the start-up sequence, the overspeed trip logic can be configured to allow an extra trip level margin. This is used to prevent nuisance tripping on start-up - Refer to the 7000 series configuration software manual under heading `Overspeed Overshoot' for details. UNDERSPEED GENERATOR OVER FREQUENCY GENERATOR UNDER FREQUENCY GENERATOR OVER VOLTAGE GENERATOR UNDER VOLTAGE OIL PRESSURE SENSOR OPEN CIRCUIT AUXILIARY INPUTS LOSS OF SPEED SIGNAL ECU DATA FAIL ECU SHUTDOWN The engine speed has fallen below the pre-set trip after the Safety On timer has expired. The generator output frequency has risen above the preset level The generator output frequency has fallen below the preset level The generator output voltage has risen above the preset level The generator output voltage has fallen below the preset level The oil pressure sensor is detected as not being present (open circuit) An active auxiliary input configured as a shutdown will cause the engine to shut down. The display shows the text as configured by the user. The speed signal from the magnetic pickup is not being received by the DSE controller. The module is configured for CAN operation and does not detect data on the engine Can datalink, the engine shuts down. The engine ECU has detected a shutdown alarm and has informed the DSE module of this situation. The exact error is also indicated on the module's display. 58 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 890 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 7.5 HIGH CURRENT SHUTDOWN ALARM GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the adjustable trip a warning alarm occurs. This warning will continue for a period depending upon the level of overload placed on the generator, and the configuration setting for Generator High Current in the 7000 series configuration software. For instance, the factory default settings for Generator High Current allow for a loading of the generator to 110% for one hour. That is to say if the generator load level exceeds the trip point by 10%, a warning alarm will occur while the overload condition exists. If the load level does not drop to normal levels within one hour, the set stops, with the 7000 series module displaying either a shutdown or electrical trip alarm depending upon module configuration. High current shutdown is a latching alarm and stops the Generator. Remove the fault then press Stop/Reset to reset the module. NOTE:- Higher overload levels will result in a faster acting shutdown condition. For instance with the factory default configuration, an overload level twice that of the trip level (typically 200%) will result in a Generator High Current shutdown condition after 36 seconds. For details of the relationship between the overload and the shutdown time, please see the Appendix section of this manual. 7.6 ELECTRICAL TRIPS Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module will de-energise the `Close Generator' Output to remove the load from the generator. Once this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down the engine. The alarm must be accepted and cleared, and the fault removed to reset the module. Example Alarm 1/1 Generator Current High Electrical Trip Electrical trips are latching alarms and stop the Generator. Remove the fault then press Stop/Reset the module. to reset Display GENERATOR OVER CURRENT AUXILIARY INPUTS Reason If a generator output in excess of the high current alarm point, a warning alarm occurs. If this high current condition continues for an excess period, then the alarm escalates to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the high current alarm, please see High Current Shutdown Alarm. If an auxiliary input configured as an electrical trip is active, the appropriate message will be displayed as configured by the user. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 59 Active: 18/04/2016 Page 891 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 8 FRONT PANEL CONFIGURATION This configuration mode allows the operator limited customising of the way the module operates. Use the module's navigation buttons to traverse the menu and make value changes to the parameters: Previous page Increase value / next item Next page Decrease value / next item Accept 8.1 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset Press the Stop/Reset and Info buttons simultaneously. If a module security PIN has been set, the PIN number request is then shown : button. Press , the first `#' changes to `0'. Press (up) or (down) to adjust it to the correct value. Press (right) when the first digit is correctly entered. The digit you have just entered will now show `#' for security. Repeat this process for the other digits of the PIN number. You can press move back to adjust one of the previous digits. (left) if you need to When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed : 60 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 892 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 8.1.1 EDITING A PARAMETER Enter the editor as described above. Press the (left) or (right) buttons to cycle to the section you wish to view/change. Press the (up) or (down) buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the (up) or (down) buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. To exit the editor at any time, press and hold the button. NOTE: - When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: - The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: - More comprehensive module configuration is possible using the 7xxx series PC configuration software. Please contact us for further details. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 61 Active: 18/04/2016 Page 893 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 8.1.2 ADJUSTABLE PARAMETERS Front Panel Configuration Editor Section DISPLAY ENGINE GENERATOR MAINS Mains settings only applicable to DSE7220 and DSE7320 controllers. TIMERS DSE7220 / DSE7320 only DSE7220 / DSE7320 only Parameter as shown on display Contrast Language LCD Page Timer Auto Scroll Delay Current Date and time Oil Pressure Low Shutdown Oil Pressure Low Pre Alarm Coolant Temperature Low Warning Coolant Temperature High Pre Alarm Coolant Temperature High Shutdown Start Delay Timer Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Engine Under Speed Shutdown Engine Under Speed Shutdown Engine Under Speed Warning Engine Under Speed Warning Engine Over Speed Warning Engine Over Speed Warning Engine Over Speed Shutdown Engine Speed Overshoot Delay Engine Speed Overshoot Fail To Stop Delay Battery Under Voltage Warning Battery Under voltage Warning Delay Battery Under Voltage Charge Alternator Failure Warning Battery Over Voltage Warning Delay Battery Over Voltage Warning Charge Alternator Failure Warning Charge Alternator Failure Warning Droop control Droop control Generator Under Voltage Shutdown Generator Under Voltage Pre Alarm Generator Over Voltage Pre Alarm Generator Over Voltage Shutdown Generator Under Frequency Shutdown Generator Under Frequency Pre Alarm Generator Over Frequency Pre Alarm Generator Over Frequency Shutdown Full Load Rating Delayed Over Current Delayed Over Current AC System CT Primary CT Secondary Generator Transient Delay Mains Under Voltage Trip Mains Over Voltage Trip Mains Under Frequency Trip Mains Over Frequency Trip Mains Transient Delay Return Delay Mains Transfer Time Auto Scroll Delay LCD Page Timer Start Delay Timer Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Speed Overshoot Delay Fail To Stop Delay Battery voltage Low Warning Delay Battery Voltage High Warning Delay Generator Transient Delay Mains Transient Delay Return Delay Mains Transfer Time Factory Settings 53% English 5m 2s hh:mm 1.03bar 1.17bar 70ºC 90ºC 95ºC 5s 0s 10s 10s 10s 0s 0s 0s 1m Inactive 1260RPM Inactive 1350RPM Inactive 1650RPM 1710RPM 2s 0s 30s Active 1m 10V Active 1m 30V Active 6V Disable (Compatible engine ECUs only) 4% (Compatible engine ECUs only) 184V 196V 265V 276V 40Hz 42Hz 55Hz 57Hz 500A Active 100% 3 Phase, 4 Wire 600A 5A 0s 184V 276V 45Hz 55Hz 2s 30s 0.7s 2s 5m 5s 0s 10s 10s 10s 0s 0s 0s 1m 2s 30s 1m 1m 0s 2s 30s 0.7s 62 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 894 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 8.2 ACCESSING THE `RUNNING' CONFIGURATION EDITOR The `running' editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered. Press and hold the button to enter the running editor. 8.2.1 EDITING A PARAMETER Enter the editor as described above. Press the (left) or view/change. (right) buttons to cycle to the section you wish to Press the (up) or (down) buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the (up) or required value. (down) buttons to change the parameter to the Press to save the value. The parameter ceases flashing to indicate that it has been saved. To exit the editor at any time, press and hold the button. 8.2.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR) Running Editor (Factory default settings are shown in bold italicised text) Sectio Parameter as shown on display Factory Setting nDISPLAY Contrast 50% Language English Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 63 Active: 18/04/2016 Page 895 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 9 COMMISSIONING 9.1.1 PRE-COMMISSIONING Before the system is started, it is recommended that the following checks are made:- 10.1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the system. Check all mechanical parts are fitted correctly and that all electrical connections (including earths) are sound. 10.2. The unit DC supply is fused and connected to the battery and that it is of the correct polarity. 10.3. The Emergency Stop input is wired to an external normally closed switch connected to DC positive. NOTE:- If Emergency Stop feature is not required, link this input to the DC Positive. The module will not operate unless either the Emergency Stop is fitted correctly OR terminal 3 is connected to DC positive. 10.4. To check the start cycle operation, take appropriate measures to prevent the engine from starting (disable the operation of the fuel solenoid). After a visual inspection to ensure it is safe to proceed, connect the battery supply. Select "MANUAL" and then press "START" the unit start sequence will commence. 10.5. The starter will engage and operate for the pre-set crank period. After the starter motor has attempted to start the engine for the pre-set number of attempts, the LCD will display `Failed to start. Select the STOP/RESET position to reset the unit. 10.6. Restore the engine to operational status (reconnect the fuel solenoid). Select "MANUAL" and then press "START". This time the engine should start and the starter motor should disengage automatically. If not then check that the engine is fully operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now run up to operating speed. If not, and an alarm is present, check the alarm condition for validity, then check input wiring. The engine should continue to run for an indefinite period. It will be possible at this time to view the engine and alternator parameters - refer to the `Description of Controls' section of this manual. 10.7. Select "AUTO" on the front panel, the engine will run for the pre-set cooling down period, then stop. The generator should stay in the standby mode. If not check that there is not a signal present on the Remote start input. 10.8. Initiate an automatic start by supplying the remote start signal (if configured). The start sequence will commence and the engine will run up to operational speed. Once the generator is available a load transfer will take place (if configured), the Generator will accept the load. If not, check the wiring to the Generator Contactor Coil (if used). Check the Warming timer has timed out. 10.9. Remove the remote start signal. The return sequence will begin. After the pre-set time, the generator is unloaded. The generator will then run for the pre-set cooling down period, then shutdown into its standby mode. 10.10.Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging functions. For details of this procedure see section entitled Front Panel Configuration Editing the date and time. 10.11.If, despite repeated checking of the connections between the 7000 series controller and the customer's system, satisfactory operation cannot be achieved, then the customer is requested to contact the factory for further advice on:- INTERNATIONAL TEL: +44 (0) 1723 890099 INTERNATIONAL FAX: +44 (0) 1723 893303 E-mail: Support@Deepseaplc.com Website : www.deepseaplc.com 64 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 896 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 10 FAULT FINDING SYMPTOM Unit is inoperative Read/Write configuration does not operate Unit shuts down Unit locks out on Emergency Stop Intermittent Magnetic Pick-up sensor fault Low oil Pressure fault operates after engine has fired High engine temperature fault operates after engine has fired. Shutdown fault operates Warning fault operates Fail to Start is activated after preset number of attempts to start Continuous starting of generator when in AUTO Generator fails to start on receipt of Remote Start signal. POSSIBLE REMEDY Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse. Check DC supply voltage is not above 35 Volts or below 9 Volts Check the operating temperature is not above 70°C. Check the DC fuse. If no Emergency Stop Switch is fitted, ensure that a DC positive signal is connected to the Emergency Stop input. Check emergency stop switch is functioning correctly. Check Wiring is not open circuit. Ensure that Magnetic pick-up screen only connects to earth at one end, if connected at both ends, this enables the screen to act as an aerial and will pick up random voltages. Check pickup is correct distance from the flywheel teeth. Check engine oil pressure. Check oil pressure switch/sensor and wiring. Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the 73x0 Module and is correctly configured. Check engine temperature. Check switch/sensor and wiring. Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the 7000 series module. Check relevant switch and wiring of fault indicated on LCD display. Check configuration of input. Check relevant switch and wiring of fault indicated on LCD display. Check configuration of input. Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speedsensing signal is present on the 7000 series module's inputs. Refer to engine manual. Check that there is no signal present on the "Remote Start" input. Check configured polarity is correct. Check the mains supply is available and within configured limits (DSE7220/DSE7320 only) Check Start Delay timer has timed out. Check signal is on "Remote Start" input. Confirm correct configuration of input is configured to be used as "Remote Start". Pre-heat inoperative Starter motor inoperative Engine runs but generator will not take load Check that the oil pressure switch or sensor is indicating low oil pressure to the controller. Depending upon configuration, then set will not start if oil pressure is not low. Check wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct. Check wiring to starter solenoid. Check battery supply. Check battery supply is present on the Starter output of module. Ensure that the Emergency Stop input is at Positive. Ensure oil pressure switch or sensor is indicating the "low oil pressure" state to the 7300 series controller. Check Warm up timer has timed out. Ensure generator load inhibit signal is not present on the module inputs. Check connections to the switching device. Note that the set will not take load in manual mode unless there is an active remote start on load signal. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 65 Active: 18/04/2016 Page 897 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual SYMPTOM Incorrect reading on Engine gauges Fail to stop alarm when engine is at rest Module appears to `revert' to an earlier configuration POSSIBLE REMEDY Check engine is operating correctly. Check sensor and wiring paying particular attention to the wiring to terminal 47 (refer to appendix). Check that sensor is compatible with the 7000 series module and that the module configuration is suited to the sensor. When editing a configuration using the PC software it is vital that the configuration is first `read' from the controller before editing it. This edited configuration must then be "written" back to the controller for the changes to take effect. When editing a configuration using the fascia editor, be sure to press the Accept button to save the change before moving to another item or exiting the fascia editor Set will not take load Ensure the generator available LED is lit Check that the output configuration is correct to drive the load switch device and that all connections are correct. Inaccurate generator measurements on controller display Remember that the set will not take load in manual mode unless a remote start on load input is present or the close generator button is pressed. Check that the CT primary, CT secondary and VT ratio settings are correct for the application. Check that the CTs are wired correctly with regards to the direction of current flow (p1,p2 and s1,s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2). Remember to consider the power factor. Ie (kW = kVA x powerfactor) The 7000 series controller is true RMS measuring so gives more accurate display when compared with an `average' meter such as an analogue panel meter or some lower specified digital multimeters. Accuracy of the controller is better than 1% of full scale. Ie Gen volts full scale is 333V ph-n so accuracy is ±3.33V (1% of 333V). NOTE:- The above fault finding is provided as a guide check-list only. As the module can be configured to provide a wide range of different features, always refer to the source of your module configuration if in doubt. 66 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 898 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 11 FACTORY DEFAULT CONFIGURATION NOTE:- Flexible sensor not available on DSE7200 series controllers. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 67 Active: 18/04/2016 Page 899 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual NOTE:- The following timers are not available on DSE7210 / DSE7310 controllers: - Mains Transient Delay - Transfer time 68 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 900 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual NOTE:- Mains settings are not available on DSE7210 / DSE7310 controllers. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 69 Active: 18/04/2016 Page 901 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual NOTE:- Communications settings are not available on DSE7200 series controllers. 70 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 902 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 12 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE7000 Series controller is designed to be Fit and Forget. As such, there are no user serviceable parts within the controller. In the case of malfunction, you should contact your original equipment supplier (OEM). 12.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE 12.1.1 DSE7200 SERIES If you require additional plugs from DSE, please contact our Sales department using the part numbers below. 7000 series terminal designation 1-11 15-18 22-30 39-46 47-50 51-56 60-65 60-67 Plug description 11 way 5.08mm 4 way 5.08mm (DSE7200 series only) 9 way 5.08mm 8 way 7.62mm 4 way 7.62mm (Not fitted to DSE7210) 6 way 5.08mm 6 way 5.08mm (DSE7200 series only) 8 way 5.08mm (DSE7300 series only) PC Configuration interface lead (USB type A type B) Part No. 007-451 007-100 007-167 007-454 007-171 007-446 007-379 007-164 016-125 NOTE:- Terminal 19 is not fitted to DSE72000 series controllers. NOTE:- Mains sensing (Terminals 47-50) is not fitted on DSE7210 autostart controller. NOTE:- RS485 connector is not fitted to the 7200 series controller. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 71 Active: 18/04/2016 Page 903 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 12.1.2 DSE7300 SERIES If you require additional plugs from DSE, please contact our Sales department using the part numbers below. 7000 series terminal designation 1-11 15-19 22-30 39-46 47-50 51-56 60-67 RS485 Plug description 11 way 5.08mm 5 way 5.08mm 9 way 5.08mm 8 way 7.62mm 4 way 7.62mm (Not fitted to DSE7310) 6 way 5.08mm 8 way 5.08mm (DSE7300 series only) 3 way 5.08mm PC Configuration interface lead (USB type A type B) Part No. 007-451 007-445 007-167 007-454 007-171 007-446 007-164 007-174 016-125 NOTE:- Mains sensing (Terminals 47-50) is not fitted on DSE7310 autostart controller. 12.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE Item Description 7000 series fixing clips (packet of 4) Part No. 020-294 12.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE Item Description 7000 series silicon sealing gasket Part No. 020-507 72 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 904 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 12.4 EXPANSION MODULES NOTE:- Expansion modules are not compatible with the DSE7200 series controllers. NOTE:- A maximum of twenty (20) expansion modules can be connected to the DSENet. Item Description DSE Part numbers Sales literature Operator manual Model DSE2130 expansion input module provides additional analogue and digital inputs for use with the 7320 controller. 055-060 057-082 Up to 4 DSE2130s can be fitted to the 73x0 module at one time. Model DSE2157 expansion relay module provides eight additional voltage free relays for use with the 73x0 controller 055-061 057-083 Up to 10 DSE2157s can be fitted to the 73x0 module at one time. Model DSE2548 expansion LED module provides additional LED indications for use with the 73x0 controller. Up to 10 DSE2548s can be fitted to the 73x0 module at one time. 055-062 057-084 Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 73 Active: 18/04/2016 Page 905 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 13 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, you are referred to your original equipment supplier (OEM). 14 DISPOSAL 14.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) Directive 2002/96/EC If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of WEEE separately from your other waste. 14.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) Directive 2002/95/EC:2006 To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB & PBDE´s) Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s Department of Trade and Industry RoHS REGULATIONS Guide (Para 11). Despite this exemption DSE has been carefully removing all non RoHS compliant components from our supply chain and products. When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into DSE production. This is a process that is almost complete and is being phased through different product groups. 74 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 906 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 15 APPENDIX 15.1 IDMT TRIPPING CURVES (TYPICAL) NOTE:- The factory default settings of tripping curve 36 and trip level of 100% of full load allows for the set to run at 110% of full load for one hour. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 75 Active: 18/04/2016 Page 907 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 15.2 SENSOR WIRING RECOMMENDATIONS 15.2.1 EARTH RETURN SENSORS Connection Name Terminal Number Sensor common Oil pressure Sensor 15 NOTE:- . It is important that terminal 15 (sensor common) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel, and must 16 be a sound electrical connection to the sensor bodies. Coolant temperature sensor Fuel level sensor 17 NOTE:- . If you use PTFE insulating tape on the sensor thread when using earth return sensors, ensure you do not insulate the entire thread, as this will prevent the sensor body from being earthed via the engine block. 18 Flexible Sensor (Not fitted to 7200 series) 19 15.2.2 INSULATED RETURN SENSORS Connection Name Terminal Number Sensor common Oil pressure Sensor 15 NOTE:- . It is important that terminal 15 (sensor common) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel. 16 Coolant temperature sensor 17 Fuel level sensor 18 Flexible Sensor (Not fitted to 7200 series) 19 15.3 CAN INTERFACE Modules are fitted with the CAN interface as standard and are capable of receiving engine data from engine CAN controllers compliant with the CAN standard. CAN enabled engine controllers monitor the engines operating parameters such as engine speed, oil pressure, engine temperature (among others) in order to closely monitor and control the engine. The industry standard communications interface (CAN) transports data gathered by the engine controller interface (CAN). This allows generator controllers such as the DSE 73x0 range to access these engine parameters with no physical connection to the sensor device. NOTE:- For further details for connections to CAN enabled engines and the functions available with each engine type, refer to the manual Electronic Engines and DSE Wiring. Part No. 057-004 76 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 908 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual 15.4 COMMUNICATIONS OPTION CONNECTIONS 15.4.1 DESCRIPTION The 7000 series configuration software allows the controller to communicate with a PC. The computer connects to the module as shown below. The operator is then able to control the module, starting or stopping the generator, selecting operating modes, etc. The various operating parameters (such as output volts, oil pressure, etc.) of the remote generator can be viewed. 15.4.2 PC TO CONTROLLER (DIRECT) CONNECTION To connect a 7000 series module to a PC the following items are required: - · 7000 series module · 7000 series configuration software (Supplied on configuration suite software CD). · USB cable Type A to Type B. NOTE:- The DC supply must be connected to the module for configuration by PC. NOTE:- Refer to 7xxx software Manual for further details on configuring, monitoring and control. Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 77 Active: 18/04/2016 Page 909 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control and Instrumentation System Operators Manual 15.5 ENCLOSURE CLASSIFICATIONS IP CLASSIFICATIONS 7000 series specification under BS EN 60529 Degrees of protection provided by enclosures IP65 (Front of module when module is installed into the control panel with the optional sealing gasket). IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) First Digit Second Digit Protection against contact and ingress of solid objects Protection against ingress of water 0 No protection 0 No protection 1 Protected against ingress solid objects with a diameter 1 Protection against dripping water falling vertically. No of more than 50 mm. No protection against deliberate harmful effect must be produced (vertically falling drops). access, e.g. with a hand, but large surfaces of the body are prevented from approach. 2 Protected against penetration by solid objects with a diameter of more than 12 mm. Fingers or similar objects prevented from approach. 2 Protection against dripping water falling vertically. There must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15°from it s normal position (drops falling at an angle). 3 Protected against ingress of solid objects with a 3 Protection against water falling at any angle up to 60° diameter of more than 2.5 mm. Tools, wires etc. with a from the vertical. There must be no harmful effect (spray thickness of more than 2.5 mm are prevented from water). approach. 4 Protected against ingress of solid objects with a diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach. 4 Protection against water splashed against the equipment (enclosure) from any direction. There must be no harmful effect (splashing water). 5 Protected against harmful dust deposits. Ingress of 5 Protection against water projected from a nozzle against dust is not totally prevented but the dust must not the equipment (enclosure) from any direction. There must enter in sufficient quantity to interface with satisfactory be no harmful effect (water jet). operation of the equipment. Complete protection against contact. 6 Protection against ingress of dust (dust tight). Complete protection against contact. 6 Protection against heavy seas or powerful water jets. Water must not enter the equipment (enclosure) in harmful quantities (splashing over). 78 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 910 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual DSE Model 7000 Series Control & Instrumentation System Operators Manual NEMA CLASSIFICATIONS 7000 series NEMA Rating (Approximate) 12 (Front of module when module is installed into the control panel with the optional sealing gasket). 2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are approximate only. 1 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt. IP30 2 Provides a degree of protection against limited amounts of falling water and dirt. IP31 3 Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure. IP64 3R Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure. IP32 4 (X) IP66 Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion). 12/12K Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids. IP65 13 Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants. IP65 Q-Pulse Id: TMS1594 Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 1 21/01/2008 ADM 79 Active: 18/04/2016 Page 911 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 912 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 913 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 914 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 915 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 916 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 917 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 918 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 919 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 920 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 921 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 922 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 923 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 924 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 925 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 926 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 927 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 928 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 929 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 930 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 931 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 932 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 933 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 934 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 935 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 936 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 937 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 938 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 939 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual SPARE PARTS & SERVICE Service & Maintenance History Serial No.: Page No.: Date Eng. Hr. Scope of Work Completed Serviced by PLEASE DIRECT ALL SPARE PARTS, SERVICE AND MAINTENANCE ENQUIRIES TO ENERAQUE 1937 IPSWICH ROAD, ROCKLEA, QLD 4106 PO BOX 3306, TINGALPA BC. QLD 4173 T 1800 636 744 / F +61 7 3434 3593 FOR EMERGENCY SERVICE CALL 1800 636 744 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 940 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 6 Test Results C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 941 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 942 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 943 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 944 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 945 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 946 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 947 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 948 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 949 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 950 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 951 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 952 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 953 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 954 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 955 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 956 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 957 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 958 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 959 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 960 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 961 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 962 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 963 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 964 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 965 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 966 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 967 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 968 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 969 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 970 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 971 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 972 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 973 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 974 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 975 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 976 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 977 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 978 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 979 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 980 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 981 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 982 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 983 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 984 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 985 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 986 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 987 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 988 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 989 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 990 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 991 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 992 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 993 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 994 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 995 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 996 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 997 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 998 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 999 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1000 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1001 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1002 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1003 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1004 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1005 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1006 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1007 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1008 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1009 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1010 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1011 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1012 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1013 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1014 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1015 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1016 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1017 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1018 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1019 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1020 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1021 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1022 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1023 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Compliance Certificate for building Design or Specification 15 NOTE This is to be used for the purposes of section 10 of the Building Act 1975 and/or section 46 of the Building Regulation 2006. RESTRICTION: A building certifier (class B) can only give a compliance certificate about whether building work complies with the BCA or a provision of the QDC. A building certifier (Class B) can not give a certificate regarding QDC boundary clearance and site cover provisions. 1. Property description This section need only be completed if details of street address and property description are applicable. EG. In the case of (standard/generic) pool design/shell manufacture and/or patio and carport systems this section may not be applicable. The description must identify all land the subject of the application. The lot & plan details (eg. SP / RP) are shown on title documents or a rates notice. If the plan is not registered by title, provide previous lot and plan details. 2. Description of component/s certified Clearly describe the extent of work covered by this certificate, e.g. all structural aspects of the steel roof beams. Street address (include no., street, suburb / locality & postcode) Sieb Street KILCOY Lot & plan details (attach list if necessary) In which local government area is the land situated? Pump well and valve pit plus aluminium cover to pump well Postcode 3. Basis of certification Detail the basis for giving the certificate and the extent to which tests, specifications, rules, standards, codes of practice and other publications, were relied upon. AS3996 : 2006 - Australian Standard Load Classifications - Class B AS1170.2 - 2002 Loading Code AS/NZS1664.1 - 1997 Aluminium Structures AS3600 - 2001 Concrete Structures Principles of structural mechanics LOCAL GOVERNMENT USE ONLY Date received Q-Pulse Id: TMS1594 Reference Number/s Active: 18/04/2016 Approved form 15 Version 2 11/11 Page 1024 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Form 15 continued 4. Reference documentation Clearly identify any relevant documentation, e.g. numbered structural engineering plans. Hughes, Beal and Wright Pty Ltd drawings 2013-067-1C, 2C, 3A, 4A, 5A, 6A, 7A, Drawings 1 and 12 dated the latter five dated 18/08/13 5. Building certifier reference number Building certifier reference number 6. Competent person details A competent person for building work, means a person who is assessed by the building certifier for the work as competent to practise in an aspect of the building and specification design, of the building work because of the individual's skill, experience and qualifications in the aspect. The competent person must also be registered or licensed under a law applying in the State to practice the aspect. If no relevant law requires the individual to be licensed or registered to be able to give the help, the certifier must assess the individual as having appropriate experience, qualifications or skills to be able to give the help. If the chief executive issues any guidelines for assessing a competent person, the building certifier must use the guidelines when assessing the person. Name (in full) Peter Geoffrey Wright Company name (if applicable) Hughes, Beal and Wright Pty Ltd Phone no. business hours 07 3814 4993 Mobile no. 0418 745 342 Email address peterwright01@optusnet.com.au Postal address 11 Wilkie Avenue REDBANK PLAINS Licence or registration number (if applicable) RPEQ 1193 7. Signature of competent person This certificate must be signed by the individual assessed by the building certifier as competent. Signature Contact person Peter Wright Fax no. Postcode 4301 Date 13 December 2013 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1025 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Version 4 March 2013 Form 16--Inspection Certificate / Aspect Certificate / QBSA Licensee Aspect Certificate NOTE 1. Indicate the type of certificate This form is to be used for the purposes of section 10(c) and 239 of the Building Act 1975 and/or sections 32, 35B, 43, 44 and 47 of the Building Regulation 2006. Inspection Certificate for The stages of assessable building work are listed in section 24 of the Building Regulation 2006 or as conditioned by the building certifier. An aspect of building work is part of a stage (e.g. waterproofing). Stage of building work (for single detached class 1a or class 10 building or structure) (indicate the stage) ________________________________________ Aspect of building work (indicate the aspect) Pump and valve pit QBSA Licensee Aspect Certificate Scope of the work Scope of the work covered by the licence class under the Queensland Building Services Authority Regulation 2003 for the aspect being certified, e.g. scope of work for a waterproofing licence is "installing waterproofing materials or systems for preventing moisture penetration". An aspect being certified may include "wet area sealing to showers". 2. Property description The description must identify all land the subject of the application. The lot & plan details (eg. SP / RP) are shown on title documents or a rates notice. If the plan is not registered by title, provide previous lot and plan details. Street address (Include no., street, suburb / locality & postcode) Sieb Street KILCOY Lot & plan details (Attach list if necessary) In which local government area is the land situated? 3. Building/structure description Building/structure description Postcode Class of building / structure LOCAL GOVERNMENT USE ONLY DATE RECEIVED REFERENCE NUMBER/S Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1026 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 4. Description of component/s certified Clearly describe the extent of work covered by this certificate, e.g. all structural aspects of the steel roof beams. 5. Basis of certification Detail the basis for giving the certificate and the extent to which tests, specifications, rules, standards, codes of practice and other publications, were relied upon. Prefabricated Concrete Pump Pit floor and wall reinforcing gages prior to placement in excavations. Prefabricated Concrete Pump Pit roof reinforcement in place prior to placement of concrete. Prefabricated Concrete Valve Pump Pit floor and wall reinforcing gages prior to placement of concrete. The floor and wall reinforcement was of the specified size and spacing. The reinforcement in the pump pit lit was of the required size, spacing and in the correct location prior to casting concrete. 6. Reference documentation Clearly identify any relevant documentation, e.g. numbered structural engineering plans. Hughes, Beal and Wright Pty Ltd drawings 2013-067-1C, 2C, 3A, 4A, 5A, 6A, 7A, dated 18/08/13 7. Building certifier reference number and development approval number Building certifier reference number Development approval number 8. Building Certifier, competent person or QBSA licensee details A competent person must be assessed as competent before carrying out the inspection. The builder for the work cannot give a stage certificate of inspection. A competent person is assessed by the building certifier for the work as competent to practice in an aspect of the building and specification design, because of the individual's skill, experience and qualifications. The competent person must be registered or licensed under a law applying in the State to practice the aspect. If no relevant law requires the individual to be licensed or registered, the certifier must assess the individual as having appropriate experience, qualifications or skills to be able to give the help. If the chief executive issues any guidelines for assessing a competent person, the building certifier must use the guidelines when assessing the person. Name (in full) Peter Wright Company name if applicable Hughes, Beal & Wright Pty Ltd Contact person Peter Wright Phone no. business hours 07 3814 4993 Mobile no. Fax no. Email address peterwright01@optusnet.com.au Postal address 11 Wilkie Avenue REDBANK PLAINS Postcode 4301 Licence class Licence number RPEQ 1193 Date approval to inspect received from building certifier 9. Signature of building certifier, competent person or QBSA licensee Note: A building certifier must sign this form for temporary swimming pool fencing under section 4 of Schedule 1 of QDC MP 3.4. Signature Date 13 December 2013 Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1027 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1028 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1029 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1030 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1031 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1032 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1033 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1034 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1035 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1036 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1037 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1038 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1039 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1040 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1041 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1042 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1043 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual Q-Pulse Id: TMS1594 Active: 18/04/2016 Page 1044 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 7 "AS INSTALLED" Drawings C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 1045 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: WB196 RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H SEIB STREET, KILCOY H WATER BOOSTER I I SITE COVER SHEET NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE ELECTRICAL DRAWING INDEX 13 14 Active: 18/04/2016 J SHEET No. 1 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Page 1046 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE BLOCK DIAGRAM 13 14 Active: 18/04/2016 J SHEET No. 2 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Page 1047 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 3 OF 16 AC POWER DISTRIBUTION QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. SCHEMATIC DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1048 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 4 OF 16 PUMP POWER & CONTROL QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. SCHEMATIC DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1049 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 5 OF 16 DC POWER DISTRIBUTION QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. SCHEMATIC DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1050 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE COMMON CONTROLS SCHEMATIC DIAGRAM J SHEET No. 6 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 13 14 15 16 Active: 18/04/2016 Page 1051 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE CONSTRUCTION MANAGER 8 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 7 OF 16 RTU DIGITAL INPUTS QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. TERMINATION DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1052 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 8 OF 16 RTU DIGITAL OUTPUTS QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. & ANALOGUE INPUTS TERMINATION DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1053 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 9 OF 16 PUMPS CONTROL QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. TERMINATION DIAGRAM D 13 14 15 16 Active: 18/04/2016 Page 1054 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE SWITCHBOARD EQUIPMENT LIST 13 14 Active: 18/04/2016 J SHEET No. 10 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Page 1055 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE CONSTRUCTION MANAGER 8 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE CABLE SCHEDULE 13 14 Active: 18/04/2016 J SHEET No. 11 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Page 1056 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE SWITCHBOARD LABLE SCHEDULE 13 14 Active: 18/04/2016 J SHEET No. 12 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Page 1057 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 13 OF 16 SWITCHBOARD QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. CONSTRUCTION NOTES AND DETAILS D 13 14 15 16 Active: 18/04/2016 Page 1058 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 14 OF 16 SWITCHBOARD QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. GENERAL ARRANGEMENT D 13 14 15 16 Active: 18/04/2016 Page 1059 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 15 OF 16 SWITCHBOARD QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. GENERAL ARRANGEMENT D 13 14 15 16 Active: 18/04/2016 Page 1060 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE CONSTRUCTION MANAGER 8 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 15 OF 16 SWITCHBOARD QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. GENERAL ARRANGEMENT D 13 14 15 16 Active: 18/04/2016 Page 1061 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J C 12.13 AMEND PUMP ID B 10.13 AS CONSTRUCTED D 12.13 AS INSTALLED DATE AMENDMENT 1 2 Q-Pulse Id: TMS1594 P.C. P.C. L.L. M.F. L.L. M.F. 3 FUNDING DESIGN W.O. No. QUUXXX SOA XXXXX-XXX FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED LIEN LE DRAFTING CHECK LUCAS WEDLEY CAD FILE Q.U.U. FILE No. 4 5 6 LUCAS WEDLEY DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 24/01/13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB196 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE SWITCHBOARD SITE ARRANGEMENT 13 14 J SHEET No. 16 OF 16 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. D 15 16 Active: 18/04/2016 Page 1062 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 EDGE OF ROAD A A B B C C D D EDGE OF DRIVEWAY E E QUU F F POWER POLE No.P101048 AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J 4 9-13 AS CONSTRUCTED P.C. P.C. 3 8-13 ADD THRUST BLOCK & NOTE P.C. P.C. 2 5-13 VENT INDUCT & EDUCT PIPE MODIFIED P.C. P.C. DATE AMENDMENT 1 2 3 Q-Pulse Id: TMS1594 FUNDING DESIGN W.O. No. QUU065 SOA C1011-045 FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED P. CRISTEA DRAFTING CHECK P. HOUSTON CAD FILE 486-4-9-1194-030-2 Q.U.U. FILE No. B. CLARKE DESIGN ORIGINAL SIGNED BY DESIGN CHECK 4 5 6 7 20-2-13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB065 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE SITE LAYOUT 13 14 Active: 18/04/2016 J SHEET No. 1 OF 5 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. 4 15 16 Page 1063 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J 4 9-13 AS CONSTRUCTED P.C. P.C. 3 8-13 ADD THRUST BLOCK & NOTE P.C. P.C. 2 5-13 VENT INDUCT & EDUCT PIPE MODIFIED P.C. P.C. DATE AMENDMENT 1 2 3 Q-Pulse Id: TMS1594 FUNDING DESIGN W.O. No. QUU065 SOA C1011-045 FUNDED BY Q.U.U. ( 9) EXTERNAL ( ) 4 DRAFTED DRAFTING CHECK CAD FILE Q.U.U. FILE No. P. CRISTEA P. HOUSTON 486-4-9-1194-031-2 5 6 B. CLARKE DESIGN ORIGINAL SIGNED BY DESIGN CHECK 7 20-2-13 R.P.E.Q. No. DATE APPROVED BY R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE SIGNATURE DATE 10 WB065 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE PIPEWORK LAYOUT 13 14 J SHEET No. 2 OF 5 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. 4 15 16 Active: 18/04/2016 Page 1064 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J 4 8-13 AS CONSTRUCTED P.C. P.C. 3 9-13 ADDED THRUST BLOCK & NOTE P.C. P.C. 2 5-13 VENT INDUCT & EDUCT PIPE MODIFIED P.H. P.H. DATE AMENDMENT 1 2 3 Q-Pulse Id: TMS1594 FUNDING DESIGN W.O. No. QUU065 SOA C1011-045 FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED P. CRISTEA DRAFTING CHECK P. HOUSTON CAD FILE 486-4-9-1194-032-2 Q.U.U. FILE No. B. CLARKE DESIGN ORIGINAL SIGNED BY DESIGN CHECK 4 5 6 7 20-2-13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE CONSTRUCTION MANAGER 8 9 SIGNATURE DATE 10 WB065 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE PIPEWORK LAYOUT 13 14 J SHEET No. 3 OF 5 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. 4 15 16 Active: 18/04/2016 Page 1065 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A B B C C D D E E F F AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J 4 9-13 AS CONSTRUCTED P.C. P.C. 3 8-13 ADDED THRUST BLOCK & NOTE P.C. P.C. 2 5-13 VENT INDUCT & EDUCT PIPE MODIFIED P.C. P.C. DATE AMENDMENT 1 2 3 Q-Pulse Id: TMS1594 FUNDING DESIGN W.O. No. QUU065 SOA C1011-045 FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED P. CRISTEA DRAFTING CHECK P. HOUSTON CAD FILE 486-4-9-1194-033-2 Q.U.U. FILE No. B. CLARKE DESIGN ORIGINAL SIGNED BY DESIGN CHECK 4 5 6 7 20-2-13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB065 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE J SHEET No. 4 OF 5 PUMP FOUNDATION DETAIL QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. & MATERIAL LIST 4 13 14 15 16 Active: 18/04/2016 Page 1066 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 EDGE OF ROAD A A B B C C D D EDGE OF DRIVEWAY E E QUU F F POWER POLE No.P101048 AS CONSTRUCTED DETAILS I CERTIFY THAT THE "AS CONSTRUCTED" DETAILS G SHOWN ON THIS PLAN ARE A TRUE AND ACCURATE G RECORD OF THE WORKS. SIGNED: DATE: NAME of SIGNATORY: RPEQ No. or LICENCE: COMPANY NAME: START DATE: FINISH DATE: H H I I NAME SIGNATURE DATE QUEENSLAND URBAN UTILITIES DELEGATE (AUTHORISED FOR 12 MONTHS FROM DATE SHOWN) J 4 9-13 AS CONSTRUCTED P.C. P.C. 3 8-13 ADDED THRUST BLOCK & NOTE P.C. P.C. 2 5-13 VENT INDUCT & EDUCT PIPE MODIFIED P.C. P.C. DATE AMENDMENT 1 2 3 Q-Pulse Id: TMS1594 FUNDING DESIGN W.O. No. QUU065 SOA C1011-045 FUNDED BY Q.U.U. (9) EXTERNAL ( ) DRAFTED P. CRISTEA DRAFTING CHECK P. HOUSTON CAD FILE 486-4-9-1194-034-2 Q.U.U. FILE No. B. CLARKE DESIGN ORIGINAL SIGNED BY DESIGN CHECK 4 5 6 7 20-2-13 R.P.E.Q. No. DATE APPROVED BY SIGNATURE DATE R.P.E.Q. No. DATE 8 CONSTRUCTION MANAGER 9 SIGNATURE DATE 10 WB065 ASSET/PROJECT SEIB STREET - KILCOY WATER BOOSTER 11 12 DRAWING TITLE SITE LAYOUT & LAND CONTOURS 13 14 Active: 18/04/2016 J SHEET No. 5 OF 5 QUEENSLAND URBAN UTILITIES DRAWING No. AMEND. 4 15 16 Page 1067 of 1068 WB196 Seib Street Water Booster - JPR - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 8 Service and Maintenance This product is designed to operate under specific environmental, supply and load conditions. Should these conditions change, consult a licenced electrician or electrical engineer before operating this product. These procedures are to be performed only by a licenced electrician as they may expose live equipment. The Switchgear and Controlgear Assembly is essentially maintenance free, however the following safety measures and routine maintenance is recommended. Where fitted, ensure cabinet vents and filters are clear and clean. During operation, ensure all doors and covers are secure and closed. All faults are to be investigated and repaired by an appropriately licenced electrician. All components to be operated in accordance with manufacturers data. The protective devices within switchboards are designed to operate in the event of a short circuit or overload condition. In the event of these devices operating under such conditions the device or devices must be inspected and tested by a suitably trained person to ascertain its condition prior to reconnecting the protective device to the supply. Periodic checks should ensure The switchboard is clean and free of any contaminants, which could reduce the insulation properties of the switchboard. All entries are sealed to ensure no vermin can enter. There is no evidence of overheating, arcing or moisture. The earthing system is maintained and is adequate to allow correct operation of protective devices. Insulation resistance is maintained to appropriate levels. Check terminations for correct tension. Test operation of protective devices. Re-calibrate instrument loops as required. Refer to AS-INSTALLED electrical drawings for details of protection equipment settings. No special tools or equipment are required to perform routine maintenance. C63100-WB065_Manual_DRAFT.doc Revision 0 Q-Pulse Id: TMS1594 Active: 18/04/2016 Date: February 18, 2014 Page 1068 of 1068ScanSoft PDF Create! 6