Viessmann Paromat-Simplex Technical Data

Part No. and prices: see Price List

Product Overview

The Viessmann Paromat-Simplex is a modulating oil/gas boiler designed as a three-pass boiler. It is suitable for operation with modulating boiler water temperature and can also be used with constant boiler water temperature.

Type: PS

Output Range: 80 to 460 kW

Certifications: CE designation in accordance with current EC directives. Certified in accordance with DIN ISO 9001 (Certificate Reg. No. 12 100 5581).

Technical Specifications

The following table details the technical specifications for various models of the Paromat-Simplex boiler:

Technical DataUnit80105130170225285345405460
Rated outputkW80105130170225285345405460
Rated thermal loadkW88115143187247313379445505
Flue gas resistancePa45606590120200210250270
Boiler shell dimensions (Length)mm109712971218143714681602169918991899
Boiler shell dimensions (Width)mm577577668668749749825825825
Boiler shell dimensions (Height incl. connections)mm121712171348134814111411156515651565
Total weight (Boiler shell with insulation and boiler control unit)kg408464555655816----
Capacity, boiler waterltr129159222259275308420665630
Max. flow temperature (= safety temperature)°C120120120120120120120120120
Max. working pressurebar444444444
Flue gas temperature (gross) at rated output°C195195195195195195195195195
Flue gas mass flow rate at rated outputkg/h136179222290383486588690784
Standby loss at rated output and heating water temperature 75/60 °C%0.410.300.280.230.150.140.130.130.13
Flue pipe, ODmm180180200200200200250250250
Gas volume0.1560.1900.2520.3030.4060.4490.5440.6140.621

*1 Boiler door and flue gas collector removed.

*2 Values for calculating design of chimney according to DIN 4705 (for boilers without the necessary draught), at rated output, based on 13.0% CO2 for light fuel oil, 10.0% CO2 for natural gas and heating water temperatures of 75/60 °C.

*3 Flue gas temperature measured at 20 °C combustion air temperature.

Dimensions and Connections

Diagrams illustrating the dimensions and connection points for the Viessmann Paromat-Simplex boilers are provided. Key connection points include:

Detailed dimensions (a, b, c, d, e, f, g, h, k) are provided in tables for different output ranges (80-170 kW and 225-460 kW).

Minimum Clearances

Clearances are specified for boiler installation, including space for maintenance and burner removal. The boiler door can be mounted to swing left or right.

Burner Connection

For boilers up to 130 kW, the burner connection specifications (hole circle, blast tube opening) conform to standard European dimensions (EN 226). For boilers from 170 kW, specific dimensions for hole circle and blast tube opening are provided. Burner connection can be prepared at the factory upon request.

Pressure Drop (Primary Circuit)

Paromat-Simplex boilers are suitable for fully pumped heating systems. A graph illustrates the pressure drop in the primary circuit based on flow rate.

Standard Delivery and Control Options

Standard Delivery: Includes boiler shell with mounted boiler door, bolted clean-out cover, mating flanges, levelling bolts, sight glass closure, gaskets, insulation, and cleaning brush. A boiler control unit is also included.

Control Options:

Accessories for the Boiler (Safety Equipment)

Available safety accessories include:

Each accessory lists part numbers, specifications, and TÜV part codes.

Operating Conditions

The document outlines operating conditions for both modulating and constant boiler water temperature modes, detailing requirements for heating water flow, boiler return temperature, minimum boiler water temperature, burner operation (two-stage and modulating), and reduced/weekend operation.

Notes on Planning

Raising the Return Temperature: Recommended to ensure minimum return temperature using suitable control facilities. Divicon heating circuit distributors and separate return temperature raising units are available.

Chimney Stack: Flue gases must be discharged safely, protected from cooling to prevent condensate. The stack must be matched to the boiler's low flue gas temperature.

Adding a Flue Gas Heat Exchanger: Condensing flue gas via a stainless steel heat exchanger is recommended to exploit condensing technology benefits. Refer to technical guides for details.

Boiler Location: Avoid rooms with polluted air (halogenated hydrocarbons), high dust, or high humidity. The room must be frost-protected and well-ventilated. Precautions are necessary for rooms with air pollution.

Warranty: Warranty does not cover damage due to dewpoint corrosion from low boiler water and/or return temperatures, or from unsuitable water for filling/replenishing.

Safety Equipment: A type-tested safety valve is mandatory for compliance with design approval conditions.

Standard Efficiency: Achieves 94% efficiency with 75/60 °C heating system temperatures, based on DIN 4702-8 which accounts for all boiler losses.

Heating Circuits: For underfloor heating, use impermeable plastic pipes (DIN 4726) or system separation with heat exchangers. Modulating boilers require connection via a mixing valve for underfloor heating and large water content circuits.

Mounting a Suitable Burner: Burner must match the boiler's rated output and flue gas resistance. Burner head material must withstand operating temperatures up to 500 °C. Oil pressure jet burners must comply with EN 267, and gas pressure jet burners with EN 676 and CE designation.

Adjustment of the Burner: Oil or gas throughput must be set to the boiler's stated output rating.

Low Water Indicator: Viessmann Paromat-Simplex boilers are equipped with safety cut-outs that prevent overheating due to low water, eliminating the need for an additional low water indicator in many cases.

PDF preview unavailable. Download the PDF instead.

5822009VDP00002 1 ? Acrobat Distiller 4.05 for Windows Interleaf, Inc.

Related Documents

PreviewViessmann VITOROND® 100 Oil Boiler: Efficient Heating Technology
Explore the Viessmann VITOROND® 100 oil-fired cast iron boiler, highlighting its efficient triple-pass heat exchanger, advanced Vitotronic control options, and user-friendly design for optimal home comfort and energy savings. Includes detailed specifications and benefits.
PreviewVitocrossal 200 CI2 Installation Instructions
Comprehensive installation instructions for the Viessmann Vitocrossal 200 CI2 gas condensing boiler series. This guide covers safety, regulatory requirements, preinstallation steps, system layout, venting options, and general information for heating contractors.
PreviewViessmann Vitodens 300 Gas Fired Condensing Boiler Datasheet and Installation Guide
Comprehensive datasheet and installation information for the Viessmann Vitodens 300 series gas-fired condensing boilers, covering specifications, benefits, installation procedures, and accessories.
PreviewViessmann Vitodens 100-W Boiler: Operating Instructions and Safety Guide
Comprehensive operating instructions and safety guidelines for the Viessmann Vitodens 100-W B1HA/B1KA gas-fired condensing boiler. Learn about installation, operation, maintenance, and troubleshooting.
PreviewViessmann Vitodens 050-W Gas Condensing Boiler - Features and Specifications
Discover the Viessmann Vitodens 050-W, a wall-mounted gas condensing boiler offering efficient heating, compact design, and smart control options. Learn about its Inox-Radial heat exchanger, MatriX-Plus burner, and ViCare app integration.
PreviewViessmann Vitodens 100-W Installation and Start-up Guide
A guide for licensed professional heating contractors on the installation and start-up of Viessmann Vitodens 100-W, B1HA/B1KA wall-mounted, gas-fired condensing boilers. Covers unpacking, dimensions, piping, venting, electrical connections, and basic operation.
PreviewVitodens 200-W B2HA Installation Instructions
Comprehensive installation instructions for the Viessmann Vitodens 200-W B2HA series gas-fired condensing boiler, covering safety, general information, setup, and connections.
PreviewVitodens 100-W Operating Instructions
Comprehensive operating instructions for the Viessmann Vitodens 100-W wall-mounted, gas-fired condensing boiler, covering installation, operation, troubleshooting, and maintenance.