Installation Guide for NOTIFIER models including: NCM-W, NCM-F, NCM-W Network Communications Module, Network Communications Module, Communications Module, Module

Click here to download

Notifier NCM Installation - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 5 Pages, 1.10MB

?tmstv=1676603749
12 Clintonville Road Northford, CT 06472-1653 USA www.notifier.com
NCM Installation Document
Network Communications Module NCM-W, NCM-F
PN 51533:A1 03/27/03 ECN 03-171
1 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control products to NOTI·FIRE·NETTM. There are two types of NCMs available: NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.

1.1 The Network Communications Module for Wire (NCM-W)

Ground Fault Detection Switches and Network End-of-Line Termination Resistor Switches
Diagnostic LEDs

EF B TERM B

LED10 1 LED10 0

A HI LED6

B HI LED7

RCDA RCDB

LED4

LE D2

STATA STATB

LED3

LE D5

RECON PULSE1

LED1

LE D8

RE SET POW ER

SW101 SW 102 ON OFF SW103 SW 100 ON OFF

EF A TERM A J3 J2

LCM A

NUP2 NUP1

Not used

SW1

LCMTERM AA
OFF ON SW2

Figure 1 NCM-W

LCM B
NCM-w.cdr

Channel A & B Connections
Network Connection Ports (NUP)

· Supports twisted-pair wire medium. · NFPA Style 4 (Class B) operation or NFPA Style 7 (Class
A) operation. · Two programmable data thresholds. · Transformer coupling provides electrical isolation
between nodes. · Pluggable terminal wiring with strain relief. · Pluggable service connector (feeds signal directly
through) in the event that power must be removed from a node. · 312.5 Kbaud transmission rate. · Data is regenerated at each node. · Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer · Enables software and database upload/download over NOTI·FIRE·NETTM. · Refer to the NOTI·FIRE·NETTM Manual (Network Version 4.0 and Higher) for wiring length and threshold information.

1.2 The Network Communications Module for Fiber (NCM-F)

Diagnostic LEDs
Not used

Figure 2 NCM-F

NCM-f.cdr

Channel A & B Connections
Network Connection Ports (NUP)

· Supports fiber-optic medium. · NFPA Style 4 (Class B) or Style 7 (Class A) operation. · Data is immune to all environmental noise. · Optical isolation prevents ground loops. · NOTI·FIRE·NETTM fiber optic medium. · Fiber type:
· 62.5/125 micrometers (multimode, 8 dB limit) · 50/125 micrometers (multimode, 4.2 dB limit) · Wavelength (1): 820 nanometers. (Use standard 850 nm fiber.) · Connectors: ST® Style (ST® is a registered trademark of AT&T). · 312.5 Kbaud transmission rate. · Data is regenerated at each node. · Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer. · Enables software and database upload/download over NOTI·FIRE·NETTM.

NCM Installation PN 51533:A1 03/27/03

www.PDF-Zoo.com

firealarmresources.com

2 Installing the NCM

2.1 Interconnecting the NCM-W
When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as shown in Figure 4. NCM-W port-to-port wiring is not polarity sensitive. The use of Port A or Port B is arbitrary. An NCM-W may be connected to any of the following devices:
· MIB-W · MIB-WF · NAM-232W · NCM-W (in another panel) · NCS-W network connection · RPT-W · RPT-WF
For information regarding these devices, refer to the documentation listed in Table 4 "Supplemental Documentation".

From last node, Port A

To next node, Port B

EF B TERM B

BA
EF A TE RM A

EF B TERM B

BA
EF A TE RM A

SW101 SW10 2 ON OFF SW103 SW10 0 ON OFF SW101 SW10 2 ON OFF SW103 SW10 0 ON OFF
NCM-w-connex.cdr

Note: Wiring from the NCM-W that is installed outside the building: · Cannot exceed 1000m (3280 ft.). · Must be in conduit and is to be buried in a trench separate from any power lines. · Cannot cross any power lines.
Figure 3 The NCM-W

TB100-1

CH-A (+)

Channel-A Driver/Receiver

TB100-2

CH-A (-)

Channel-A Driver/Receiver

TB100-3 TB100-4 TB100-5

CH-B (+) CH-B (-) Earth Ground

Channel-B Driver/Receiver Channel-B Driver/Receiver

Table 1 NOTI·FIRE·NETTM Connections: NCM-W

Switch Functions: Ground Fault Detection and Line Termination

The NCM-W provides two sets of switches to simplify network setup; in Figure 4 all are in the "off" position.

EF B TERM B

EF A TERM A

· Enable ground fault detection by setting switches "on": SW103 for Channel A, and SW101 for Channel B.

· Activate on-board end-of-line resistors by

setting switches "on": SW100 for Channel A;

SW102 for Channel B.

Figure 4 NCM-W Switches

Note: Correct configuration depends on your network

design; refer to the NOTI·FIRE·NETTM Manual (Network Version 4.0 and Higher).

SW101 SW102 ON OFF SW103 SW100 ON OFF ncm-w-switches.cdr

2
www.PDF-Zoo.com

NCM Installation PN 51533:A1 03/27/03
firealarmresources.com

2.2 Interconnecting the NCM-F
When connecting consecutive nodes/repeaters, note that fiber cable must exit one board on transmit (TX) and enter the next node/repeater on receive (RX). Also, note that the fiber-optic pair (RX, TX) from port A of one Node/Repeater may be connected to either Port A or Port B of another node/repeater (refer to Figure 5). An NCM-F may be connected to any of the following devices:
· MIB-F · MIB-WF · NAM-232F · Another NCM-F · Network connection for NCS-F · RPT-F · RPT-WF
For information regarding these devices, refer to the NAM-232 and Repeater manuals listed in Table 4 "Supplemental Documentation".
Note: See the NOTI·FIRE·NETTM Manual (Network Version 4.0 and Higher) for maximum fiberoptic cable attenuation.

J202 J201 J200 J202 J201 J200
NCM-f-connex.cdr

RX

TX

RX

TX

J203

RX

TX

RX

TX

J203

RxB TxB RxA TxA

Channel Channel

B

A

RxB TxB RxA TxA

Channel Channel

B

A

Figure 5 NCM-F Connection

J200

CH A

Transmit

J201

CH A

Receive

J202

CH B

Transmit

J203

CH B

Receive

Table 2 NOTI·FIRE·NETTM Connections: NCM-F

2.3 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. There are two solutions for this situation.
1. In any network, an RPT-WF may be used as an interface between wire and fiber.
2. In a network that uses an AFP1010 or AM2020, a MIB-WF may also be used as the interface between wire and fiber.
See 1.2 "The Network Communications Module for Fiber (NCM-F)" for requirements and restrictions on the use of fiber optic cable. See the NOTI·FIRE·NETTM Manual (Network Version 4.0 and Higher) for a discussion of all compatible configurations.

NCM Installation PN 51533:A1 03/27/03

3

www.PDF-Zoo.com

firealarmresources.com

3 Diagnostic Indicators
The NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system connection. Refer to Table 3 for a list of diagnostic indicators and their descriptions. Refer to Figure 6 for location of the diagnostic indicators.

A HI (NCM-W only) RCD A STATA
RECON RESET

A HI B HI RCDA RCDB STATA STATB RECON PULSE1 RESET POWER

B HI (NCM-W only) RCD B STATB PULSE1 POWER

NCM-LEDS.cdr

Figure 6 Diagnostic Indicator Locations

LED Indicator A HI (NCM-W only) B HI (NCM-W only) RCD A
RCD B
STATA
STATB
RECON
PULSE1
RESET POWER

LED Color LED Description

Green

Illuminates to indicate the NCM-W Port A is set for high threshold.

Green

Illuminates to indicate the NCM-W Port B is set for high threshold.

Green Green

Illuminates when the NCM is receiving data from NOTI·FIRE·NETTM on Port A.
Illuminates when the NCM is receiving data from NOTI·FIRE·NETTM on Port B.

Yellow

Illuminates when the NCM has not received valid data from NOTI·FIRE·NETTM on Port A for at least 16 seconds.

Yellow Yellow Green

Illuminates when the NCM has not received valid data from NOTI·FIRE·NETTM on Port B for at least 16 seconds.
Illuminates when a reconfiguration on NOTI·FIRE·NETTM is in progress.
Illuminates when the NCM is transmitting data to NOTI·FIRE·NETTM.

Yellow Green

Illuminates when the microcontroller fails. Illuminates when +5 VDC is available

Table 3 Diagnostic Indicator Functions and Colors

4
www.PDF-Zoo.com

NCM Installation PN 51533:A1 03/27/03
firealarmresources.com

4 Door-Mounting
Both NCM-W and NCM-F can be installed in any panel circuit module position; see your control panel installation manual. Additionally, the NCM-W can be door-mounted on the ADP-4B Dress Panel on a single-space blank plate (BMP-1) for mounting in a CAB-4 Series cabinet.
Note: The module cannot be mounted in the ADP-4B Dress Panel when a front slot of the CHS-4 or CHS-4N is occupied, or when either of the two front right positions of the CHS-M2 is occupied. Always be certain there is enough clearance to close the cabinet door when this installation is used.

ADP4-door-module.cdr

Single-space blank plate
Mount a single-space blank plate onto the ADP-4B Dress Panel.

Fasten module to the plate with four screws (included).

5 Supplemental Documentation

The table below provides a list of document sources (manuals) containing additional information regarding the NCM and products that it can connect to. The NOTIFIER document (DOC-NOT) chart provides the current document revision.

For information on... Networking
Off-line Programming Utility Compatible Devices Cabinets & Chassis

Refer to...

Part No.

NOTI·FIRE·NETTM Manual (for Network Version 4.0 and Higher) Onyx NCS Network Control Station (for Network Version 4.0 and Higher) NCS Network Control Station (for Network Version 4.0) NFS-640 Installation
Operations Programming NCA Network Control Annunciator Media Interface Board (MIB) Manual NAM-232 Network Adaptor Module RPT - W/WF/F Repeaters for NOTI·FIRE·NETTM

51584 51658 51585 51332 51333 51334 51482 50255 50038 50256

VeriFireTM Tools CD on-line help file

VeriFire-TCD

Device Compatibility Document

15378

CAB-3/CAB-4 Series Installation Document BMP-1 Product Installation Document Also see your panel's Installation Manual

15330 51119

Table 4 Supplemental Documentation

Note: For module mounting instructions, refer to the documentation for your control panel

NCM Installation PN 51533:A1 03/27/03

5

www.PDF-Zoo.com