TOSHIBA AIR CONDITIONER (MULTI TYPE) Installation Manual

Model types: R32 or R410A

Indoor Unit

Model name:

1-Way Cassette type

For commercial use

Illustration of the 1-Way Cassette indoor unit.

Scan QR code to access installation and owner's manual on website: https://www.toshiba-carrier.co.th/manuals/default.aspx

Manuals are available in multiple languages including English.

1 Accessory parts

The following parts are supplied with the indoor unit:

Part nameQtyShapeUsage
Installation Manual1This manualHand over to customers
Heat insulating pipe2For heat insulation of pipe connecting section
Installation pattern1For confirmation of ceiling opening and indoor unit position
Installation gauge1For positioning of ceiling position
Washer4?️For hanging-down unit
Eccentric washer4For hanging-down unit
Hose band1?For connecting drain pipe
Flexible hose1For adjusting center of drain pipe
Heat insulator1For heat insulation of drain connecting section
Safety Manual1For hand over directly to the customer

Separate sold parts

2 Selection of installation place

WARNING

CAUTION

Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit, a fire may occur.

Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions:

Avoid installing in the following places:

Installation space

Secure the specified space in the figure for installation and servicing.

Diagram showing required installation space with dimensions: 500 mm or more on sides and front, 160 mm or more above, 10 mm or more below.

Selection of installation place

In case of continued operation of the indoor unit under high-humidity conditions, dew may condense and water may drop.

Especially, high-humidity atmosphere (dew point temperature: 23°C or more) may generate dew inside the ceiling.

  1. Unit is installed inside the ceiling with slated roof.
  2. Unit is installed at a location using inside of the ceiling as fresh air take-in path.
  3. Unit is installed in the kitchen.

Advice

If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the indoor unit which come to contact with high-humidity atmosphere.

REQUIREMENT

When the humidity inside the ceiling seems to be higher than 80%, attach a heat insulator to the side (top) surface of the indoor unit. (Use a heat insulator that is 10 mm or more thick.)

3 Installation

CAUTION

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

External dimensions

Diagram showing external dimensions of the indoor unit and panel, including dimensions for ceiling opening and hanging bolt pitch.

Opening a ceiling and installation of hanging bolts

Treatment of ceiling

The ceiling differs according to structure of building. For details, consult your constructor or interior finish contractor.

It is important to reinforce ceiling foundation (frame) and to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.

  1. Cut and remove the ceiling foundation.
  2. Reinforce the cut surface of ceiling foundation, and add ceiling foundation for fixing the end of ceiling board.

Installation of hanging bolt

Use M10 hanging bolts (4 pcs, locally procured). Matching to the existing structure, set pitch according to size in the unit external view.

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Diagram showing installation of hanging bolts in a new concrete slab using insert brackets or anchor bolts.

Steel frame structure

Use existing angles or install new support angles.

Diagram showing installation of hanging bolts using existing or new support angles on a steel frame structure.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Diagram showing installation of hanging bolts in an existing concrete slab using anchors, plugs, or bolts.

Using the installation pattern (accessory)

The installation pattern is provided inside the packaging cap.

Use the installation pattern positioning a ceiling opening and hanging bolts.

Use the installation pattern to position the ceiling opening when hanging a ceiling.

Diagram illustrating the use of the installation pattern for positioning ceiling openings and hanging bolts.

Installation of ceiling opening and hanging bolt

Diagram illustrating the installation of ceiling opening and hanging bolt, including level vial usage.

Installation of ceiling panel (Sold separately)

Install the ceiling panel according to Installation Manual attached with it after piping / wiring work has completed.

Check that installation of indoor unit and ceiling opening part is correct, and then install it.

REQUIREMENT

Wireless type (Sold separately)

The sensor of indoor unit with wireless remote controller can receive a signal by distance within approx. 7 m. Based upon it, determine a place where the remote controller is operated and the installation place.

Installation of remote controller (Sold separately)

For installation of the wired remote controller, follow the Installation Manual attached with the remote controller.

4 Drain piping

CAUTION

Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew dropping. Inappropriate piping work may result in water leakage in the room and wet of furniture.

Piping / Heat insulating material

Materials required for piping and heat insulating:

Flexible hose

Use the attached flexible hose to adjust centre discrepancy of the hard vinyl chloride pipe or to adjust the angle.

Diagram showing correct and incorrect usage of flexible hose for drain piping.

REQUIREMENT

Be sure to perform heat insulation of the drain pipes of the indoor unit. Never forget to perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dew dropping. Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound.

Diagram showing recommended collective piping for drain pipes.
Diagram illustrating the connection of the drain pipe to the indoor unit using the flexible hose and hose band.

Connecting drain pipe

Connect a hard socket (locally procured) to the hard socket of the attached supplied flexible hose. Connect a drain pipe (locally procured) to the connected hard socket.

REQUIREMENT

Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage. It takes some time until the adhesive is dried and hardened. Do not apply stress to the joint with the drain pipe during this time period.

Drain up

When a down-gradient cannot be secured for the drain pipe, drain-up piping is possible.

Diagram illustrating drain-up piping configuration.

Check the draining

In the test run, check that water drain is properly performed and water does not leak from the connecting part of the pipes. Be sure to check draining also when installed in heating period.

Using a pitcher or hose, pour water (1500 to 2000 cc) into the suction port before installation of the ceiling panel.

CAUTION

Pour water gently so that it does not spread around inside the indoor unit, which may cause a malfunction.

Diagram showing the process of checking the draining by pouring water into the unit.

5 Refrigerant piping

CAUTION

When the refrigerant pipe is long, provide support brackets at intervals of 2.5 m to 3 m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.

Permissible piping length and height difference

They vary depending on the outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.

Pipe size

Pipe size (mm)Gas sideLiquid side
09.506.4

Connecting refrigerant piping

Flaring

CAUTION

In case of flaring with the conventional flare tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size.

The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed, there will no "whooshing" sound: This is normal and is not indicative of trouble.

Use two wrenches to connect the indoor unit pipe.

Heat insulating

Diagram showing heat insulation application for refrigerant pipes.

6 Electrical connection

WARNING

CAUTION

REQUIREMENT

Power supply wire and communication wires specifications

Power supply wire and communication wires are locally procured.

For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or burnout may be caused.

For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation Manual attached to the outdoor unit.

Indoor unit power supply

Power supply

Power supplyPower supply wiring
220-240V~, 50 HzBelow 50 m3 x 2.5 mm² (power supply and earth)
208-230V~, 60 Hz

Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the accumulated total current values of the indoor units.

Control wiring, Central controller wiring

Communication line

TU2C-Link models (U series) can be combined with TCC-Link models (other than U series). For details of communication type, refer to the following table.

Communication type and model namesTU2C-Link (U series and future models)TCC-Link (Other than U series)
Communication typeTU2C-LinkTCC-Link
Outdoor unitMMY-MUP***, MMY-SUG***, MCY-MUG***Other than U series
Indoor unitMM*-UP*** (This letter indicates U series model)MM*-AP*** (This letter indicates U series model)
Wired remote controllerRBC-A**U***Other than U series
Wireless remote controller kit & receiver unitRBC-AXU***Other than U series
Remote sensorTCB-TC**U***Other than U series

* Even if the indoor units, the remote controllers, and the central control device are models other than U series, their system diagrams for the wiring specifications are the same as the system diagram above.

Follow the wiring specifications in the table below even when units other than U series are mixed in the indoor units and remote controllers to be connected.

Uv line and Uc line (L2, L3, L4) (2-core shield wire, non-polarity)Uh line (L1) (2-core shield wire, non-polarity)
Wire size :1.0 to 1.5 mm² (Up to 1000 m)1.0 to 1.5 mm² (Up to 1000 m)
2.0 mm² (Up to 2000 m)

• U (v, h, c) line means of control wiring.

• Uv line and Uc line are independent from another refrigerant line. Total length of Uv and Uc lines (L3 + L4) in each refrigerant line is up to 1000 m.

REQUIREMENT

For connection of Uv line / Uc line or Uh line, wire each line using wires with the same type and size. If different wire types and size are mixed and used in a system, communication trouble is caused.

Wiring diagram for U series and other than U series systems.

Control wiring between indoor units, and outdoor unit (L2, L3)

Wire size :
(2-core shield wire, non-polarity)1.25 mm² (Up to 1000 m)

Central control line wiring (L1)

Wire size :
(2-core shield wire, non-polarity)2.0 mm² (Up to 2000 m)

Control wiring between outdoor units (L4)

Wire size :
(2-core shield wire, non-polarity)1.25 to 2.0 mm² (Up to 100 m)

• The length of the communication line (L1 + L2 + L3) means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.

REQUIREMENT

For connection of between indoor and outdoor units line / between outdoor and outdoor units line or central control line, wire each line using wires with the same type and size. If different wire types and size are mixed and used in a system, communication trouble is caused.

Wire connection

Diagram showing wire connection details, including terminal blocks and cord clamps.
  1. Remove the cover of the electrical control box by taking off the mounting screw and pushing the hooking section.
  2. Connect the power supply wire and remote controller wire to the terminal block of the electrical control box.
  3. Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box.
  4. Mount the cover of the electrical control box without pinching wires.
Wiring diagrams for different system configurations.

Remote controller wiring

Be sure to stop the air conditioner before making settings.

Wiring diagram

Wiring diagram for remote controller connection.
In case of one remote controllerIn case of group remote controllers
Total wire length of remote controller wiring and remote controller inter-unit wiringL + L1 + L2 + ... + LnUp to 500 m
Max. length of each remote control wiring between indoor unitsL1, L2, ..., LnUp to 200 m

CAUTION

Max. number of connectable indoor units, and communication type

Outdoor unitIndoor unitCommunication typeMax. number of connectable units
U seriesU seriesTU2C-Link16
U seriesU series *TU2C-Link8
U series*TCC-Link8
U seriesU series *TCC-Link8
U series*TCC-Link8

*: Other than U series

REQUIREMENT

After carrying out installation of additional indoor unit, relocation, or repairing, set the addresses again. For its detail, refer to the Installation Manual attached to the outdoor unit.

Wiring between indoor and outdoor units

NOTE

A wiring diagram below is an example for connection to SMMS-u series. For connecting to other outdoor unit series, refer to the Installation Manual attached to the outdoor unit to be connected.

Wiring example

Wiring example for connecting indoor and outdoor units.

Address setup

Set up the addresses as per the Installation Manual supplied with the outdoor unit.

Wiring on the ceiling panel

According to the Installation Manual of the ceiling panel, connect the connector (20P: White) of the ceiling panel to the connector (CN510: White) on P.C. Board of the electrical control box.

7 Applicable controls

REQUIREMENT

When the air conditioner is used for the first time, it will take some moments after the power has been turned on before the remote controller becomes available for operations: This is normal and is not indicative of trouble.

Applicable controls setup (settings at the site)

Remote controller model name: RBC-ASCU11-E

Basic procedure

Be sure to stop the air conditioner before making settings.

CAUTION

Set only the CODE No. shown in the following table: Do NOT set any other CODE No. If a CODE No. not listed is set, it may not be possible to operate the air conditioner or other trouble with the product may result.

Diagram showing the sequence for setting applicable controls.
  1. Push and hold menu button and [▽] setting button simultaneously for 10 seconds or more.
  2. Each time [▽] [△] setting button is pushed, indoor unit numbers in the group control change cyclically. Select the indoor unit to change settings for. The fan of the selected indoor unit runs. The indoor unit can be confirmed for which to change settings.
  3. Push OFF timer button to confirm the selected indoor unit.
  4. Push the menu button to make CODE No. [**] flash. Change CODE No. [**] with [✔] [A] setting button.
  5. Push the menu button to make Set data [****] flash. Change Set data [****] with [▽] [A] setting button.
  6. Push OFF timer button. By doing so, the setup is completed.
  7. When all the settings have been completed, push ON/OFF button to determine the settings.

Installing indoor unit on high ceiling

When an indoor unit is installed on a ceiling higher than the standard height, make the high-ceiling setting for fan speed adjustment.

Remote controller-less setting

Change the high-ceiling setting with the DIP switch on the receiver section P.C. Board. For details, refer to the manual of the wireless remote controller kit. The settings can also be changed with the switch on the indoor microcomputer P.C. Board.

Change of lighting time of filter sign

According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed.

SET DATAFilter sign lighting time
0000None
0001150 H
00022500 H (Factory default)
00035000 H
000410000 H

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling.

SET DATADetection temp shift value
0000No shift
0001+1°C
0002+2°C (Factory default)
0003+3°C
0004+4°C
0005+5°C
0006+6°C

Group control

In a group control, a remote controller can control up to maximum 8 units.

Remote controller sensor

The temperature sensor of the indoor unit senses room temperature usually. Set the remote controller sensor to sense the temperature around the remote controller. Select items following the basic operation procedure (1→2→3→4→5→6). Specify [32] for the CODE No. in Procedure 3. Select the following data for the SET DATA in Procedure 4.

SET DATARemote controller sensor
0000Not used (factory default)
0001Used

When flashes, the remote controller sensor is defective. Select the SET DATA [0000] (not used) or replace the remote controller.

8 Test run

Before test run

  1. By using insulation tester (500VΜΩ), check that resistance of 1MΩ or more exists between the terminal block L to N and the earth (grounding). If resistance of less than 1MΩ is detected, do not run the unit.
  2. Check the valve of the outdoor unit being opened fully.

Requirements for turning thermostat OFF

Cooling operation

Heating operation

Execute a test run

In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.

CAUTION

Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.

9 Maintenance

CAUTION

Before maintenance, be sure to turn off the leakage breaker.

Cleaning of air filter

Cleaning of panel and air filter

Preparation:

  1. Turn off the air conditioner by the remote controller.
  2. Open the air inlet grille. Slide the hook of the air inlet grille outward, and open the air inlet grille slowly while holding it.
Diagram showing how to open the air inlet grille.
  1. Close the air inlet grille. Close the air inlet grille, slide the hook inward, and fix the air inlet grille securely.

Use a vacuum cleaner to remove dust from the filters or wash them with water.

Clean the panel and air filter with water:

Cleaning of air filters

If the air filters are not cleaned, it not only reduce the cooling a performance of air conditioner but causes a failure in the air conditioner such as water falling in drops.

Preparation:

  1. Stop the operation by remote controller.
  2. Dismount the air filter.
Diagram showing how to remove the air filter.

CAUTION

REQUIREMENT

Be sure to clean the heat exchanger with pressurized water. If a commercially available detergent (strong alkaline or acid) cleaning agent is used, the surface treatment of the heat exchanger will be marred, which may degrade the self cleaning performance. For details, contact the dealer.

10 Troubleshooting

If a problem occurs with the air conditioner, the OFF timer indicator alternately shows the check code and the indoor UNIT No. in which the problem occurred.

Diagram showing the display of check code and indoor unit number.

Troubleshooting history and confirmation

You can check the troubleshooting history with the following procedure if a problem occurs with the air conditioner. (The troubleshooting history records up to 4 incidents.) You can check it during operation or when operation is stopped. If you check the troubleshooting history during OFF timer operation, the OFF timer will be canceled.

  1. Push the OFF timer button for over 10 seconds and the indicators appear as an image indicating the troubleshooting history mode has been entered. If [ Service check] is displayed, the mode enters in the troubleshooting history mode.
  2. [01: Order of troubleshooting history] appears in the temperature indicator. The OFF timer indicator alternately shows the [check code] and the [indoor UNIT No.] in which the problem occurred.
  3. Each time the setting button is pushed, the recorded troubleshooting history is displayed in sequence. The troubleshooting history appears in order from [01] (newest) to [04] (oldest).

CAUTION

In the troubleshooting history mode, DO NOT push the Menu button for over 10 seconds, doing so deletes the entire troubleshooting history of the indoor unit.

Check method

On the wired remote controller, central control remote controller and the interface P.C. Board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. Board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.

The following list shows each check code. Find the check contents from the list according to part to be checked.

Wired remote controller displayCheck codeOutdoor unit 7-segment display Auxiliary codeWireless remote controller Sensor block display of receiving unit Operation Timer Ready FlashCheck code nameJudging device
E01-Communication trouble between indoor unit and remote controller (Detected at remote controller side)Remote controller
E02-Remote controller transmission troubleRemote controller
E03-Communication trouble between indoor unit and remote controller (Detected at indoor unit side)Indoor unit
E04-Communication circuit trouble between indoor / outdoor unit (Detected at indoor unit side)Indoor unit
E06No. of indoor units in which sensor has been normally receivedCommunication circuit trouble between indoor / outdoor unit (Detected at outdoor unit side)IVF
E06Duplicated indoor unit addressesDuplicated indoor unit addressesIndoor unit. I/F
E07Duplicated master remote controllersRemote controller
E08Communication trouble between indoor unit MCUIndoor unit
E08Indoor unit
E09Communication trouble between Application control kit and indoor unitApplication control kit
E10Automatic address start trouble
E11No indoor unit during automatic addressingIVF
E1201: Indoor / Outdoor units communicationCapacity over / No. of connected indoor unitsIVF
E1202: Outdoor / Outdoor units communicationIVF
E15Communication trouble between indoor unit and Flow Selector unitIndoor unit
E1600: Capacity overCommunication trouble between header and follower unitsIndoor unit
E1601: No. of connected unitsIVF
E17Other line connected during automatic addressIVF
E1800: Header is not detectedSending trouble in communication between outdoor unitsI/F
E19Trouble in number of heat storage units (trouble with reception)
E1902: Two or more header unitsDuplicated follower outdoor addressesIVF
E2001: Outdoor unit of other line connectedDecrease of No. of connected outdoor unitsI/F
E2002: Indoor unit of other line connectedFollower outdoor unit troubleIVF
E23Inverter communication troubleIVF
E25Indoor unit TCJ sensor troubleIndoor unit
E25Indoor unit TC2 sensor troubleIndoor unit
E26No. of outdoor units which received signal normallyIndoor unit TC1 sensor troubleIndoor unit
E28Detected outdoor unit numberTD1 sensor troubleI/F
E28TD2 sensor troubleI/F
E31TE1, TE2 or TE3 sensor troubleIVF
F01TL1, TL2 or TL3 sensor troubleIVF
F02TO sensor troubleIVF
F03TG1, TG2 or TG3 sensor troubleIVF
F04F04Indoor unit TA sensor troubleIndoor unit
F05F05TF sensor troubleIndoor unit
F0601: TE1 sensorTS1 or TS3 sensor troubleI/F
F0602: TE2 sensor
F0603: TE3 sensor
F0701: TL1 sensorTH sensor troubleCompressor inverter
F0702: TL2 sensor
F0703: TL3 sensor
F0801: TG1 sensorOutdoor unit temp. sensor miswiring (TE, TL)IVF
F0802: TG2 sensor
F0803: TG3 sensor
F0901: TS1 sensorOutdoor unit pressure sensor miswiring (Pd, Ps)IVF
F0903: TS3 sensor
F0904: TS3 sensor disconnect
F10TD3 sensor troubleIVF
F11Ps sensor troubleI/F
F12F12Pd sensor troubleIVF
F131*: Compressor 1 sideIndoor unit other troubleIndoor unit
F132*: Compressor 2 side
F15F15Occupancy sensor troubleIndoor unit
F16F16Indoor unit EEPROM troubleIVF
F22F22Compressor break downCompressor inverter
F23F23Compressor trouble (lock)Compressor inverter
F24F24Current detect circuit system troubleCompressor inverter
F29Comp. 1 case thermostat operationIVF
F30F30TD1 sensor miswiringI/F
F31F31Low pressure protective operationI/F

H17 H25
Wired remote controller displayCheck codeOutdoor unit 7-segment display Auxiliary codeWireless remote controller Sensor block display of receiving unit Operation Timer Ready FlashCheck code nameJudging device
H171*: Compressor 1 side 2*: Compressor 2 sideCompressor trouble (Step out)I/F
H25-TD3 sensor miswiringIVF
J02-Indoor unit overflow troubleIndoor unit
J03-Outdoor heat exchanger freezing troubleI/F
J10J10Detected indoor unit addressIndoor unit fan motor troubleIndoor unit
J11-Outdoor liquid back detection troubleI/F
J29Detected indoor unit addressGas leak detectionI/F
J30J30Injection circuit troubleI/F
J31-Discharge temp. TD2 troubleI/F
L02L02Detected indoor unit addressDischarge temp. TD3 troubleI/F
L03-4-way valve inverse troubleI/F
L04L04High-pressure protective operationI/F
L05-Outdoor unit fan inverter troubleFan inverter
L06L06No. of indoor units with priorityIPM short protection troubleCompressor inverter
L07-Compressor position detective circuit system troubleCompressor inverter
L08L08Detected indoor unit addressOther indoor unit troubleIndoor unit
L09-(Group follower indoor unit trouble)
L10L10
L11L11Detected indoor unit address
L12L12
L13L13Detected indoor unit address
L14L14Detected indoor unit address
L17L17Detected indoor unit address
L18L18Detected indoor unit address
L20-
L2201: Duplication of Flow Selector unit address
L24L2402: Indoor unit operation mode priority setting
L28L28
L29L29*1 Inverter quantity information
L30L30Detected indoor unit address
L31-
P01-
P03P031*: Compressor 1 side 2*: Compressor 2 side
P04P041*: Compressor 1 side 2*: Compressor 2 side
P05P051*: Compressor 1 side 2*: Compressor 2 side
P07P071*: Compressor 1 side 2*: Compressor 2 side
P10P10Detected indoor unit addressIndoor unit overflow troubleIndoor unit
P11P11Outdoor heat exchanger freezing troubleI/F
P12-Indoor unit fan motor troubleIndoor unit
P13P1301: TS condition 02: TD conditionOutdoor liquid back detection troubleI/F
P15P1501: PMV5 02: PMV6Gas leak detectionI/F
P16P1603: SV7Injection circuit troubleI/F
P17P17Discharge temp. TD2 troubleI/F
P18P180#: 4-way valvesDischarge temp. TD3 troubleI/F
P19P191#: 4-way valve1 2#: 4-way valve2 * Put in outdoor unit No. in [#] mark.4-way valve inverse troubleI/F
P20P20High-pressure protective operationI/F
P22P221*: Compressor 1 side 2*: Compressor 2 sideOutdoor unit fan inverter troubleFan inverter
P26P261*: Compressor 1 side 2*: Compressor 2 sideIPM short protection troubleCompressor inverter
P29P291*: Compressor 1 side 2*: Compressor 2 sideCompressor position detective circuit system troubleCompressor inverter
P31-Other indoor unit trouble (Group follower indoor unit trouble)Indoor unit

• For details about check codes determined with an Interface P.C. Board or an Inverter P.C. Board, refer to the Installation Manual of the outdoor unit.

11 Specifications

ModelSound power level (dBA) Cooling HeatingWeight (kg) Main unit (Ceiling panel)
MMU-UP0031YHP-E* *14 (4)
MMU-UP0051YHP-E* *14 (4)
MMU-UP0071YHP-E* *14 (4)
MMU-UP0091YHP-E* *14 (4)
MMU-UP0121YHP-E* *14 (4)

* Under 70 dBA

12 Notice code

Illustration of the Notice code mark on the remote controller display.

How to check Notice CODE No.

  1. Stop the operation of the air conditioner and push the Menu button and OFF timer button at the same time for 10 seconds or more.
  2. The unit number of the indoor unit is displayed at the bottom left of the screen. Change it with the [▽] [A] setting button and push the OFF timer button to confirm.
  3. The history number is displayed in the center of the screen, and the Notice CODE No. is displayed in the lower left. You can switch the history with the setting button (a maximum of 5 notice codes).
  4. Push the ON / OFF button to return to the operation stop screen.

Notice code list

Notice CODE No.ItemContent
203Flow Selector unit battery deadThe battery kit connected to the Flow Selector unit has reached the end of its life.
204Leak detector life advance displayThe leak detector will soon reach the end of its life.

Declaration of Conformity

Manufacturer: Toshiba Carrier (Thailand) Co., Ltd

TCF holder: TOSHIBA CARRIER EUROPE S.A.S

Hereby declares that the machinery described below:

Generic Denomination: Air Conditioner

Model / type: MMU-UP0031YHP-E, MMU-UP0051YHP-E, MMU-UP0071YHP-E, MMU-UP0091YHP-E, MMU-UP0121YHP-E

Commercial name: Super Modular Multi System Air Conditioner, Super Heat Recovery Multi System Air Conditioner, Mini-Super Modular Multi System Air Conditioner (MiNi-SMMS series)

Complies with the provisions of the Machinery Directive (Directive 2006/42/EC) and the regulations transposing into national law

Name: Masaru Takeyama

Position: GM, Quality Assurance Dept.

Date: 2 November, 2021

Place Issued: Thailand

NOTE: This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer's consent.

Declaration of Conformity

Manufacturer: Toshiba Carrier (Thailand) Co., Ltd

TCF holder: TOSHIBA CARRIER UK LTD.

Hereby declares that the machinery described below:

Generic Denomination: Air Conditioner

Model / type: MMU-UP0031YHP-E, MMU-UP0051YHP-E, MMU-UP0071YHP-E, MMU-UP0091YHP-E, MMU-UP0121YHP-E

Commercial name: Super Modular Multi System Air Conditioner, Super Heat Recovery Multi System Air Conditioner, Mini-Super Modular Multi System Air Conditioner (MiNi-SMMS series)

Complies with the provisions of the Supply of Machinery (Safety) Regulations 2008

Name: Masaru Takeyama

Position: GM, Quality Assurance Dept.

Date: 2 November, 2021

Place Issued: Thailand

NOTE: This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer's consent.

Warnings on Refrigerant Leakage

Check of Concentration Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.

Refrigerant R32

The refrigerant R32 which is used in the air conditioner is mildly flammable. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard. The refrigerant R 32 does not have the toxicity of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. If this appliance is connected with the outdoor unit containing R32 refrigerant, refer to the Installation and Owner's Manual attached to the outdoor unit.

Refrigerant R410A

The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of space, individual control, energy conservation by curtailing heat and carrying power etc.

Most importantly, the multi air conditioner system is able to hold a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

In a room where the concentration may exceed the limit imposed by the local regulation, create an opening with adjacent rooms, or install mechanical ventilation or isolation, combined with a gas leak detection device, which complies with the local regulatory requirements.

The concentration calculation method is as given below. Please note the concentration limit between R32 and R410A refrigerant differs.

Total amount of refrigerant (kg) / Min. volume of the indoor unit installed room (m³) ≤ Concentration limit (kg/m³)

Refrigerant Concentration Limit shall be in accordance with local regulations.

NOTE 2

The standards for minimum room volume are as follows.

  1. No partition (shaded portion)
Diagram illustrating minimum room volume standards.
  1. When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Diagram illustrating effective opening for ventilation.
  1. If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Diagram illustrating room volume considerations for interconnected systems.

▼ NOTE 1

If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.

For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.

Diagram illustrating refrigerant charge amounts in different rooms.

▼ NOTE 3

System compliance has been completed to IEC 60335-2-40 Ed6. If EN378 compliance is required please refer separately to EN378 for guidance.

13 Appendix

Work instructions

The existing R22 and R410A piping can be reused for inverter R32 product installations.

WARNING

Confirming the existence of scratches or dents on the existing pipes and confirming the reliability of the pipe strength are conventionally referred to the local site. If the specified conditions can be cleared, it is possible to update existing R22 and R410A pipes to those for R32 models.

Basic conditions needed to reuse existing pipes

Check and observe the presence of three conditions in the refrigerant piping works.

  1. Dry (There is no moisture inside of the pipes.)
  2. Clean (There is no dust inside of the pipes.)
  3. Tight (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should not be reused as they are. Clean the existing pipes or exchange them with new pipes.

  1. When a scratch or dent is heavy, be sure to use new pipes for the refrigerant piping works.
  2. When the existing pipe thickness is thinner than the specified "Pipe diameter and thickness," be sure to use new pipes for the refrigerant piping works.

The operating pressure of refrigerant is high. If there is a scratch or dent on the pipe or a thinner pipe is used, the pressure strength may be inadequate, which may cause the pipe to break in the worst case.

Pipe diameter and thickness (mm)
Pipe outer diameter06.409.5Ø12.7Ø15.9
Thickness0.80.80.81.0
R32, R410A
R22
  1. When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and the pipes were not repaired and refilled.
  2. When refrigerant cannot be recovered using a refrigerant recovery unit.
  3. When a commercially available dryer is attached to the existing pipes.
  4. When the existing air conditioner is removed after refrigerant has been recovered.

Check if the oil is judged to be clearly different from normal oil.

The winding-insulation of the compressor may deteriorate.

NOTE The above descriptions are results have been confirmed by our company and represent our views on our air conditioners, but do not guarantee the use of the existing pipes of air conditioners that have adopted R32, R410A in other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows:

Placement locationTermCuring manner
Outdoors1 month or morePinching
Less than 1 monthPinching or taping
IndoorsEvery timePinching or taping

Are there scratches or dents on the existing pipes?

NO

Is it possible to operate the existing air conditioner?

YES

After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer, recover the refrigerant.

For cleaning the pipes and recovering oil

* Refrigerant recovery: Pump down method

Remove the existing air conditioner from the piping and carry out flushing (nitrogen pressure 0.5 MPa) to remove any remains inside of the pipe.

Note: In case of twin pipes, also be sure to flush the branching pipe.

Was largely discolored oil or a large quantity of remains discharged?

(When the oil deteriorates, the color of the oil changes to a muddy or black color.)

NO

Connect the indoor / outdoor units to the existing pipe.

YES

Existing pipes: Cannot be used. Use new pipes.

NO

Nitrogen gas pressure 0.5 MPa

(If there is discharge of remains, it is judged that a large quantity of remains are present.)

YES

Clean the pipes or use new pipes.

Piping necessary to change the flare nut / machining size due to pipe compression

1) Flare nut width: H (mm)

06.409.5Ø12.7Ø15.9
For R32, R410A17222629
For R22Same as above

2) Flare machining size: A (mm)

06.409.5Ø12.7Ø15.9
For R32, R410A9.113.216.619.7
For R229.013.016.219.4

Becomes a little larger for R32, R410A

Do not apply refrigerator oil to the flare surface.

Models: MMU-UP0031YHP-E, MMU-UP0051YHP-E, MMU-UP0071YHP-E, MMU-UP0091YHP-E, MMU-UP0121YHP-E, MMU-UP0031YHP-E Air Conditioning, MMU-UP0031YHP-E, Air Conditioning, Conditioning

File Info : application/pdf, 26 Pages, 3.84MB

PDF preview unavailable. Download the PDF instead.

20231103 IM 1127650113 00 R32-R410a MMU-UP YHP-E 003-012 EN

References

Acrobat Distiller 10.0.0 (Macintosh)

Related Documents

PreviewToshiba R410a SHRMu Heat Recovery VRF CDU Product Bulletin
Product bulletin detailing the new Toshiba R410a SHRMu Heat Recovery VRF Outdoor Unit, including features, model names, specifications, and combinations.
PreviewTOSHIBA R-32 Digital Inverter Heat Pumps Product Bulletin
Product bulletin detailing TOSHIBA's new R-32 Digital Inverter heat pumps for light commercial applications, including specifications for various indoor unit types like Compact Cassette, 4-Way Cassette, Slim Ducted, and Ducted systems, as well as twin system configurations.
PreviewToshiba e-STUDIO Multifunctional Systems: Quick Start Guide
A quick start guide for Toshiba e-STUDIO multifunctional digital color and digital systems, covering basic operations like copying, scanning, faxing, and printing.
PreviewToshiba Split Type Air Conditioner Owner's Manual
This owner's manual provides detailed instructions for operating and maintaining Toshiba split-type air conditioners, including safety precautions, feature explanations, troubleshooting, and maintenance procedures for models RAS-B05 to RAS-18J2KVG-E and RAS-05 to RAS-18J2AVG-E.
PreviewToshiba R32 Residential Multi-Split Air Conditioning Systems: Product Catalog & Specifications
Explore the Toshiba R32 residential multi-split air conditioning systems. Find detailed specifications, model compatibility, and features for DAISEIKAI 9, SHORAI, SEIYA, SILVERSTONE, Cassette Slim, and Low-Profile Ducted units.
PreviewTOSHIBA e-STUDIO Printing Guide for Multifunctional Digital Systems
This guide provides detailed instructions for printing with TOSHIBA e-STUDIO Multifunctional Digital Systems and Multifunctional Digital Color Systems, covering setup, driver configuration, and various printing options for Windows and Mac OS.
PreviewToshiba SHORAI EDGE: A+++ Energy Efficient Air Conditioner with Advanced Comfort Features
Discover the Toshiba SHORAI EDGE, an air conditioner offering A+++ energy efficiency, innovative HADA CARE technology for enhanced comfort, and exceptionally quiet operation. Explore its sleek design, advanced inverter technology, and smart control options for optimal home climate management.
PreviewToshiba Concealed Duct Air Conditioner Installation Manual - MMD-UP Series
Comprehensive installation manual for Toshiba MMD-UP series concealed duct air conditioners, covering installation, piping, electrical connections, and troubleshooting for commercial use.