Installation Instructions for the Walking Beam Interlock for PD6 Circuit Breakers and Molded Case Switches

Instruction Leaflet IL012286EN

Contents

  1. Introduction
  2. Installation
  3. Adjustment

Cat # PDG6XWBI3P

1. INTRODUCTION

General Information

The walking beam interlock provides mechanical interlocking between two adjacent PD6 3-Pole breakers to prevent both circuit breakers from being switched ON at the same time. The walking beam interlock assembly is bolted to the rear of the customer's mounting panel. The circuit breakers are then aligned with the mounting panel such that the plungers enter the holes in the back of the breakers as they are secured. Adjustment of the plungers is necessary. Mounting panels that are at least one inch thick are suggested.

Note: Factory modified circuit breakers must be ordered to install the walking beam interlock.

2. INSTALLATION

This instruction leaflet gives detailed procedures for installing the walking beam interlock.

The walking beam interlock assembly must be mounted before the circuit breakers are connected to an electrical system. Installation consists of drilling the mounting panel to accept the circuit breakers and walking beam assembly, installing the walking beam assembly to the panel, and then mounting the circuit breakers to the panel.

2-1. Drill the breaker mounting panel using the dimensions which are provided in Fig 2-1 for mounting the breakers and the walking beam interlock assembly. Dimensions are given in inches and (millimeters).

2-2. Install the walking beam assembly to the panel using 3/8 inch hardware per Figure 2-2. A one inch panel is illustrated; a thinner panel is not recommended because sufficient thickness is needed in order to recess the bolt heads to allow the breakers to be mounted properly.

2-3. Mount the circuit breakers to the front surface of the mounting panel using 3/8 inch hardware. The breakers must be aligned carefully so the plungers enter into the holes in the back of the circuit breakers.

3. ADJUSTMENT

The walking beam interlock must be adjusted before the circuit breakers are connected to an electrical system. Carry out these adjustment procedures as follow:

3-1. Turn one circuit breaker to the ON position and the other to the OFF position.

3-2. Adjust the locknuts on each plunger assembly until there is 1/16 to 3/16 inch free travel of the plungers with either breaker closed. Align the plungers for free operation of the interlock with the beam in any position, with no interference or rubbing which may prevent proper functioning or abnormal wear of the walking beam parts. Torque the locknuts to 10 - 12 ft-lb.

3-3. Carry out a functional check as follows:

3-4. Connect both circuit breakers as required.

Diagrams and Visual Descriptions

Figure 2-1: PD6 Circuit Breaker Mounting Panel Hole Sizes and Dimensions, Viewed from Breaker Side of Panel. This diagram illustrates the required hole sizes and their placement on the mounting panel for the PD6 circuit breakers and the walking beam interlock assembly. It specifies panel thickness, hole diameters, and counterbore depths, along with overall panel dimensions for minimum size requirements.

Figure 2-2: Top View of Walking Beam Assembly. This diagram shows a top-down view of the walking beam assembly installed between two circuit breakers. It indicates the dimensions of the assembly and the breaker handles, highlighting the beam and plunger mechanism.

Figure 2-3: Assembly of Plunger/Socket to Beam. This diagram provides a detailed view of how the plunger/socket assembly connects to the beam. It labels the components including the locknut, lockwasher, large diameter washer, beam, and plunger/socket assembly, emphasizing that the pivot pins must be parallel with the center line of the breakers.

Safety Warnings

WARNING: DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES.

EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.

The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of personnel and equipment, as well as, all general and local health and safety laws, codes, and procedures.

The recommendations and information contained herein are based on Eaton experience and judgment, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Eaton for further information or instructions.

WARNING: BEFORE ATTEMPTING ANY WORK ON CIRCUIT BREAKERS INSTALLED IN AN ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT BREAKERS ARE SWITCHED TO THE OFF POSITION AND THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

Disclaimer and Legal Information

The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility.

This Instruction Booklet is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative.

The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.

NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein.

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com

© 2019 Eaton All Rights Reserved Printed in USA Publication No. IL012286EN Part No. IL012286EN H01

Eaton is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners.

PDF preview unavailable. Download the PDF instead.

power-defense-frame-6-walking-beam-interlock-installation-instructions-il012286en Adobe PDF Library 9.0

Related Documents

PreviewEaton NZM1-4 Molded Case Circuit-Breakers Product Overview
Comprehensive product overview and technical specifications for Eaton NZM1-4 molded case circuit-breakers, including system overviews, technical data, tripping characteristics, and selection guides for industrial and commercial electrical applications.
PreviewNZM2(-4)-XKSA Terminal Cover Installation Instructions
Instructions for installing the NZM2(-4)-XKSA terminal cover for NZM2 Molded Case Circuit Breakers and Switches, including safety precautions and connection guidelines.
PreviewEaton Power Defense Molded Case Circuit Breakers Frame Size 3 (45-600 A) - Product Aid
Detailed product information for Eaton's Power Defense molded case circuit breakers, frame size 3. Includes interrupting ratings, dimensions, weights, terminal specifications, and trip unit options for various applications.
PreviewEaton Molded Case Circuit Breakers: Power Defense, Series G, and Series C
Explore Eaton's comprehensive range of Molded Case Circuit Breakers, including the Power Defense, Series G, and Series C lines. This catalog details product specifications, applications, and ordering information for advanced electrical protection solutions.
PreviewEaton 1498D66G15 Molded Case Circuit Breaker Accessory Handle Mechanism
Discover the Eaton 1498D66G15, a variable depth rotary handle mechanism designed for molded case circuit breakers. This product specification details its features, dimensions, and warranty information.
PreviewEaton PDG32K0600P2YN: Power Defense Circuit Breaker Specifications
Detailed specifications, resources, and documentation for the Eaton PDG32K0600P2YN Power Defense molded case circuit breaker, including technical data, installation guides, and application notes.
PreviewEaton R-Frame Circuit Breakers and Molded Case Switches: Installation Instructions (IL29C107N)
Comprehensive installation, operation, and testing instructions for Eaton R-Frame circuit breakers and molded case switches, including technical specifications and safety guidelines.
PreviewControl Panel Design Guide According to UL 508A
A comprehensive guide to designing control panels in compliance with UL 508A standards, covering feeder mains, group motors, individual motor loads, heater/lighting circuits, power circuit wiring, and control circuits. This document provides essential information for engineers and technicians.