ED106 Digital Temperature Controller

Model: ED106

Dimensions: 77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension: 71(Length)×29(Width)mm

Features of Function

Specifications

  1. Power supply: 230VAC
  2. Temperature sensor: NTC, double sensors (for cold-room temp. & defrost control), 2m(L)
  3. Range of temperature display: -45~150℃ (-40~150°F) Accuracy: ±1℃ (±2°F) Resolution: 0.1 °C/°F (-19.9~99.9°C/°F)
  4. Range of set temperature: -45~45℃ (-40~113°F) Factory default: 0°C (32°F)
  5. Temperature of the operating environment: -10~60℃ (14~140°F); Relative Humidity: 20%~90%(Non-condensing)
  6. Relay output contact capacity:
    • Compressor: N.O. 16A/250VAC
    • Defrost: N.O. 10A/250VAC
    • Evap.Fan: N.O. 5A/250VAC

Front Panel Operation

  1. Set temperature (compressor stop temperature) adjustment:
    • Press SET button, the set temperature is displayed.
    • Press ▲ (Up) or ▼ (Down) button to modify and store the displayed value. Press SET button to exit the adjustment and display the cold-room temperature.
    • If no more button is pressed within 6 seconds, the cold-room temperature will be displayed. (Set temperature adjustment range: parameter E1~E2)
  2. Manual start/stop defrost: Press ▲ (Up) button and hold for 6 seconds to defrost or stop defrost.
  3. Display the evap.temperature: Press ▲ (Up) button and hold 6 seconds, the evap. Temp.is displayed, after 6 seconds the cold room temp.is resumed to be displayed.
  4. Refrigerating LED: During refrigerating, the LED is on; when the cold-room temp. is constant, the LED is off; during the delay, the LED flashes.
  5. Defrost LED: during defrosting, the LED is on; when it stops defrosting, the LED is off. During the delay display of defrost, the LED flashes.
  6. Evap. Fan LED: the LED is on during fan operation. The LED is off when the Evap.fan stops operation.
  7. Parameters setup:
    • Press SET button and hold for 6 seconds to enter the parameter setup mode while E1 flashes.
    • Press again SET button to select sequentially from the parameters: E2,E3,E4,E5,E6,C1,F0~F9,E1.
    • Press ▲ (Up) or ▼ (Down) button, the value of parameter will be displayed and can be modified and stored.
    • If no more button is pressed within 6 seconds, it will return to normal operation mode.

Parameter Settings

ParameterFunctionSet rangeDefaultParameterFunctionSet rangeDefault
E1Lower setpoint limit-45°C~Set temp.-35°CF3Defrost termination temp.32~86°F / 0~30°C46°F / 8°C
E2Higher setpoint limitSet temp.~45°C / 113°F45°C / 113°FF4Display during defrost0=Normal display / 1=Last value before defrost0
E3Temp. hysteresis1.8~36.0°F / 1~20.0°C7.2°F / 4.0°CF5Fan operating function0=Parallel with comp. / 1=Continuous running except defrost0
E4Comp.start delay time0~10Min2MinF6Dripping time0~30Min2
E5Offset on room temp.-36.0~36.0°F / -20.0~20.0°C0F7Fan operating function after defrost end0=Temperature / 1=Time1
E6Offset on evap. Temp.-36.0~36.0°F / -20.0~20.0°C0F8Fan start-up delay after defrost end0~10Min2
C1Temperature unit0=°C / 1=°F0F9Fan start temperature after defrosting(evaporator)-22~86°F / -30~30°C41°F / 5°C
F0Defrost function0=Electric heater / 1=Hot gas0
F1Max. Defrost duration1~60Min20Min
F2Defrost interval time0~24Hr6Hr

Function Details

  1. Temperature control:
    • After the delay time, the compressor starts operating when cold-room temperature ≥ (set temp.+Hysteresis), and will be off when cold-room temperature < set temp.
    • To protect the compressor, it can re-start unless the time when the compressor stops every time is longer than the delay time (Parameter E4).
  2. Defrosting function: when F0=0, it means defrost by electric heater; when F0=1, it means defrost by hot gas.
    • Enter defrosting: it defrosts only if the temp. of the evap.sensor is less than defrost termination temperature (parameter F3).
    • Exit defrosting: when the temp. of the evap.sensor > the temp. of defrost termination or the defrost duration ends, it will exit the defrost state.
      When the defrost interval time is set to "00", the function of automatic defrosting will be cancelled.
    • Defrost by electric heater: after working for a defrosting interval time, it will automatically enter defrosting state. The defrosting LED will turn on, the compressor will stop, the electric heater will work and the evaporation fan will stop. After defrosting, the electric heater will stop working, and after dripping time F6 it will enter normal temperature control mode, if cold-room temperature > (set temp. + Hysteresis), the compressor will start.
    • Defrost by electric heater: after working for a defrosting interval time, it will automatically enter defrost state. The defrosting LED will turn on, the compressor and switch valve will be connected. After defrosting, the compressor will stop. After dripping time, the switch valve will be disconnected and enter normal temperature control mode, if cold-room temperature > (set temp. + Hysteresis), the compressor will start.
  3. Fan control:
    • Fan start mode is decided by parameter F5, when F5=0, the fan and the compressor operate synchronously, the compressor starts, the fan will start, the compressor stops the fan will stop.
    • When F5=1, the fan will operate all along and will stop when defrosting. After defrosting, the fan delay start mode is decided by parameter F7; when F7=1, defrosting ends, the fan will start after delay time (parameter F8 set value); when F7=0, after defrosting, the fan start will be decided by parameter F9, only when evaporator defrosting sensor temperature < parameter F9, the fan will start.
  4. Display during defrost:
    • When setting the parameter F4=1, the room temp. is locked during defrost, and the last value before defrost is displayed. When defrost ends, normal display will be resumed after 20 minutes delay of room temp. display (or when cold-room temperature < set temp.). The defrost LED flashes during the delay.
  5. Abnormal work mode:
    • When room sensor is short circuited or overheated (more than 150℃ /150°F), "HH" is displayed; when room sensor is open-circuited or temperature is too low (less than -45°C/-45°F), "LL" is displayed. At that time the compressor automatically enters time working mode by the cycle of 45 minutes on and 15 minutes off.
    • When Evap. sensor fails or exceeds the displayed range, the defrost termination will be just controlled by the defrost duration. (Parameter F1)

Notes for Installation

  1. The sensor cable leads must be kept separately from main voltage wires in order to avoid high frequency noise induced. Separate the power supply of the loads from the power supply of the controller.
  2. When installation the probe shall be placed with the head upward and the wire downward; The evaporator probe must be installed between the fins of the evaporator in the area, where probably the ice is the thickest. Don't place the evaporator probe near the electric heater.
  3. The temperature controller can not be installed in the area with water drops.

Accessories for the temperature controller

  1. Two pc of temperature sensor
  2. One pc of installation stand
  3. One pc of cover panel and one pc of 3x10mm screw

Circuit Diagram

+-------------------------------------------------+
| Input/Output Terminals (16A 5A 10A / 250VAC)    |
|                                                 |
| 1 (L: Live/230V Input)                          |
| 2 (Load: Compressor Output)                     |
| 3 (Load: Evap. Fan Output)                      |
| 4 (Load: Defrost Output)                        |
| 5 (N: Neutral/230V Input)                       |
|                                                 |
| Sensor Terminals                                |
| 8 (Evap. Sensor Input)                          |
| 9 (Cold-room Sensor Input)                      |
| 10 (230VAC Output)                              |
| 11 (Not Used)                                   |
| 12 (Not Used)                                   |
|                                                 |
| Power Supply: ~230V (Connects to Terminals 1 & 5) |
+-------------------------------------------------+

PDF preview unavailable. Download the PDF instead.

K1059730238 pdfFactory Pro www.fineprint.cn pdfFactory Pro 3.22 (Windows XP Professional Chinese)

Related Documents

Preview4 Knob RGBW LED RF Controller (Model V4-K) - User Manual and Specifications
Comprehensive user manual and technical specifications for the V4-K 4-channel RGBW LED RF Controller. Details features, installation, operation, dimming modes, and remote control functions.
PreviewModern Retractable Ceiling Fan with LED Light
A stylish and functional modern retractable ceiling fan featuring an integrated LED light, designed to enhance dining and living spaces. This fan combines air circulation with ambient lighting for a comfortable and elegant atmosphere.
PreviewPortable Desk Fan with LED Light and Digital Display
A compact and stylish portable desk fan featuring adjustable speed settings, an integrated LED light ring, and a clear digital display showing the fan speed. Ideal for personal cooling in offices, bedrooms, or any workspace.
PreviewDigital Wireless Weather Station Operating Instructions
Operating instructions for the BJ8240B Digital Wireless Weather Station, covering setup, functions, and troubleshooting.
PreviewDurable and Flexible Cold-Resistant Tarpaulin
High-quality tarpaulin designed for flexibility and resistance to cold temperatures, preventing hardening. Features antioxidant properties and stable physical and chemical performance.
Preview18 Inch Stand Fan Product Specifications
Technical specifications for the 18 Inch Stand Fan, detailing its metal grill, voltage range (110-240V), power consumption (45W), 5 blades, and 3 speed settings.
PreviewDigital Camera Specifications and Features
Detailed specifications for a digital camera, including optical performance, video output, imager details, IR LED, storage, hardware buttons, operation modes, power, system settings, size, weight, and package contents.
PreviewHigh-Speed Fan for Efficient Air Circulation
This document provides information about a high-speed fan designed for effective air circulation. It highlights the fan's performance and features.