Application

The flush-mounted room operating unit with setpoint adjustment and occupancy button is used for individual temperature control in living, hotel, and office rooms. The device with 4 control buttons and LCD can be integrated into the most common switch ranges. It is available in many color versions and suitable for design-oriented facilities. Depending on the type, it is also possible to control continuous valves for heating or cooling. The removable terminal block allows pre-wiring.

Types Available

Room operating unit temperature - aktiv 2x 0..10 V (temperature & set point)

Printing type 1:

Printing type 3:

Security Advice – Caution

The installation and assembly of electrical equipment should only be performed by authorized personnel.

The product should only be used for the intended application. Unauthorized modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.

Please comply with:

Product Testing and Certification

Declaration of conformity

The declaration of conformity of the products are available on our website: www.thermokon.de/direct/en-gb/categories/wrf06-lcd

Notes on Disposal

The crossed-out wheelie bin symbol indicates that the product or removable batteries must not be disposed of with household or commercial waste. Within the EU, you are legally obliged to dispose of the product separately and appropriately in accordance with the national laws of your country. Alternatively, please contact your supplier or Thermokon Sensortechnik GmbH. Further information can be found at: www.thermokon.com

Mounting Advise Room Sensors

The accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.

During Assembly:

Assembly not recommended in:

General Remarks Concerning Sensors

Especially with regard to passive sensors in 2-wire conductor versions, the wire resistance of the supply wire has to be considered. If necessary, the wire resistance has to be compensated by the follow-up electronics. Due to self-heating, the wire current affects the measurement accuracy, so it should not exceed 1 mA.

When using lengthy connection wires (depending on the cross section used) the measuring result might be falsified due to a voltage drop at the common GND-wire (caused by the voltage current and the line resistance). In this case, 2 GND-wires must be wired to the sensor - one for supply voltage and one for the measuring current.

Sensing devices with a transducer should always be operated in the middle of the measuring range to avoid deviations at the measuring end points. The ambient temperature of the transducer electronics should be kept constant. The transducers must be operated at a constant supply voltage (±0,2 V). When switching the supply voltage on/off, onsite power surges must be avoided.

Build-up of Self-Heating by Electrical Dissipative Power

Sensors with electronic components always have a dissipative power, which affects the temperature measurement of the ambient air. The dissipation in active temperature sensors shows a linear increase with rising operating voltage. This dissipative power has to be considered when measuring temperature. In case of a fixed operating voltage (±0,2 V) this is normally done by adding or reducing a constant offset value.

Thermokon transducers can be operated with variable operating voltages. The transducers are set at the factory with a reference operating voltage of 24 V =. At this voltage, the expected measuring error of the output signal will be the least. Other operating voltages can cause a measurement deviation changing power loss of the sensor electronics.

A recalibration can be carried out directly on the unit or via a software variable (app or bus).

Remark: Occurring draught leads to a better carrying-off of dissipative power at the sensor. Thus temporally limited fluctuations might occur upon temperature measurement.

Technical Data

ParameterValue
Measuring valuestemperature
Output voltage2x 0..10 V, min. load 1 kΩ
Power supply15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumptiontyp. 0,8 W (24 V =) | 2,5 VA (24 V ~)
Measuring range temperature+32..+122 °F
Accuracy temperature±0,5 K (typ. at 21 °C)
Display2x digital input for floating contact, for activation of messages on the LCD display
DisplayLCD 34x21 mm, monochrome
EnclosurePC, pure white brilliant, pure white matt, aluminium, anthracite, frame color may differ slightly
ProtectionIP30 according to EN 60529
Connection electricalterminal block, max. 15AWG pluggable
Ambient condition+32..+122 °F, max. 85% rH non-condensing
Mountingflush mounted in standard EU box (Ø=2.36 in.)
Connection Plan

GND 1 10 GND

DI1 2 9 DI1

DI2 3 8 DI2

GND 4 7 A01

UB+ 5 6 A02

0..10 V | Temperatur 0..+50 °C

0..10 V | Sollwert 0..+50 °C

Function Buttons
  1. Press any menu button once to turn on the LCD backlight.
  2. Press the or key once to enter the setpoint adjustment.
  3. Press the or key again to change the setpoint.
  4. Accepting the set setpoint: push-button or 10 sec no interaction
  5. Abort: Esc key setpoint adjustment is cancelled

Configuration Menu

The configuration menu allows the user to make subsequent changes to basic settings. The configuration menu is opened by simultaneously pressing the and the Esc key (both outer keys) for approx. 5 seconds. The following parameters can be changed: minimum setpoint adjustment, maximum setpoint adjustment, basic setpoint (after reset), setpoint change per push-button operation. In addition, it is possible to recalibrate the temperature sensor by entering an offset in the event of measurement inaccuracies.

Display

The following symbols can be activated and displayed. The symbols depend on the type and function of the device.

Disfunction

Set point adjustment

Text messages

Only with printing type 1: occupied/unoccupied

Measuring value

Window "open"

Dew point

Dimensions (In.)

Front View: 55 mm width, 55 mm height

Side View: 30 mm depth

Back View (for mounting): 71 mm width, 71 mm height, 9 mm depth

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany tel: +49 2778 6960-0 fax: -400 www.thermokon.com email@thermokon.com

WRF06_LCD_2V_Datasheet_en-us.docx © 2025

PDF preview unavailable. Download the PDF instead.

a55e605078c25c306 Adobe PDF Library 25.1.51

Related Documents

PreviewThermokon SR06 LCD (868 MHz) Technical Data Sheet
Technical data sheet for the Thermokon SR06 LCD (868 MHz) radio room thermostat with LCD display, temperature, and optional humidity sensor. Details product features, technical specifications, installation guidelines, and configuration options.
PreviewThermokon NOVOS 5 x (LCD) RS485 Modbus Room Operating Unit Datasheet
Datasheet for the Thermokon NOVOS 5 x (LCD) RS485 Modbus room operating unit. This device measures temperature, humidity, CO2, and VOC, offering advanced features for indoor climate control in commercial and public spaces. Details include technical specifications, application notes, and configuration options via RS485 Modbus.
PreviewSR06 LCD (868 MHz) Room Operating Unit Datasheet
Datasheet for the Thermokon SR06 LCD (868 MHz) wireless surface-mounted room operating unit with display, temperature sensor, and optional humidity sensor. Learn about its features, technical specifications, application, and installation.
PreviewThermokon NOVOS 3 x LRW: LoRaWAN Room Operating Unit Datasheet
Datasheet for the Thermokon NOVOS 3 x LRW, a LoRaWAN room operating unit for temperature, humidity, and optional CO2 and occupancy detection. Includes technical specifications, application notes, mounting advice, and product certifications.
PreviewThermokon RDF-IR (LCD) RS485 Modbus Datasheet - Infrared Temperature Sensor
Datasheet for the Thermokon RDF-IR (LCD) RS485 Modbus ceiling sensor, detailing its application, technical specifications, configuration, and dimensions for surface temperature measurement.
PreviewThermokon NOVOS 3 (EPD) RS485 Modbus Room Sensor Datasheet
Datasheet for the Thermokon NOVOS 3 (EPD) RS485 Modbus room sensor, detailing its application, available types, technical specifications, mounting instructions, connection plans, configuration options, display features, and DIP switch settings for temperature, humidity, CO2, and VOC monitoring.
PreviewThermokon SR65 rH 902 MHz Wireless Sensor Datasheet
Technical datasheet for the Thermokon SR65 rH 902 MHz wireless sensor, detailing its application, technical specifications, guidelines for solar energy storage, humidity sensor notices, and configuration with airConfig.
PreviewThermokon SAB05 EasySens Datasheet: Wireless Radiator Valve Actuator
Detailed datasheet for the Thermokon SAB05 EasySens wireless radiator valve actuator. Learn about its application in building automation, technical specifications, mounting, configuration, and operational features for room temperature control.