LG PREMTA201 Deluxe Wired Remote Controller
Controller w/Built-in Wi-Fi & LG ThinQ® Compatibility
Electrical
Power Supply: 12VDC Power From Indoor Unit
Operating Environment
Operating Temperature: 32°F ~104°F (0°C ~ 40°C)
Storage Temperature: -4°F ~ +140°F (-20°C ~ +60°C)
Humidity Operating Temperature: 0 ~ 90% (RH)
Humidity Storage Temperature: 0 ~ 90% (RH)
Unit Data
Dimensions: 4.72" H x 4.72" W x 0.59" D
Maximum Number of Indoor Units (per controller): 16
Maximum Number of Controllers (per group): 1
Features
- Wi-Fi with ThinQ Capability
- Function Code Settings
- Function Code Search Tool
- Date and Time Display
- Room Temperature Display
- Humidity Display
- Operation - On / Off
- Modes - Auto / Cool / Dry / Heat / Fan Only
- Cooling and Heating Temperature Setpoints
- Energy Management
- Installation Wizard - Commercial / Residential Applications
- Proximity Sensor
- AI Smart Care
- Fan Speeds - Auto / Low / Med / High / Power
- ERV Compatibility
- Static Pressure Installer Setting
Optional Accessories
- PZCWRC1 - 33-foot Extension Cable Assembly
- PZCWRCG3 - Group Control Cable Kit
Connectivity
LG Communications: 1 Channel for V-Net, Wi-Fi with ThinQ Capability
Communications Cable Specifications (V-Net)
Type: Three (3) Conductor, Stranded, Twisted, Unshielded
Size: AWG 22-3
Length: Up to 164 feet
Controller Wiring
Wiring Diagram: A diagram shows the controller's internal wiring with terminals labeled GND / SIG / 12V.
Installation Notes
- Available functions / features may differ based on connected system.
- Communication cable can be extended to a maximum of 164 feet by using field-supplied wire or the Wired Remote Group Control Cable Assembly (PZCWRCG3) or Wired Remote Extension Cable (PZWRC1), maximum of four (4).
- Must follow installation instructions in the applicable LG installation manual.
Attaching the Controller to the Back Cover
A diagram illustrates how to attach the controller to its back cover. It shows a hook mechanism for mounting and indicates that the back cover can be removed for power wiring access.
Diagram showing the back cover attachment with a hook and power wiring access.