Hardware Installation TracerTM MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation TracerTM MP581 Programmable Controller CNT-SVN01C-EN November 2005 Tracer MP581 Programmable Controller Hardware Installation This guide and the information in it are the property of American Standard Inc. and may not be used or reproduced in whole or in part, without the written permission of American Standard Inc. Since Trane has a policy of continuous product improvement, it reserves the right to change design and specification without notice. Although Trane has tested the hardware and software described in this guide, no guarantee is offered that the hardware and software are error free. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change. Trane may have patents or patent applications covering items in this publication. By providing this document, Trane does not imply giving license to these patents. TM ® The following are trademarks or registered trademarks of American Standard Inc.: Rover, Tracer, Tracer Summit, and Trane. TM ® The following are trademarks or registered trademarks of their respective companies or organizations: LonMark and LonTalk from Echelon Corporation. Printed in the U.S.A. © 2005 American Standard All rights reserved CNT-SVN01C-EN Revision history Document number and date CNT-SVN01C-EN November 2005 Description · Binary output ratings corrected · EX2 best wiring practices added · I/O wiring diagrams changed · Contrast adjustment note added · Important note regarding termination board grounding screw added Note: This document, in printed form or as an electronic file on a product CD, is accurate as of its publication date. The electronic version of this document may display a more current publication date and a higher revision level than this document. CNT-SVN01C-EN NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully: WARNING Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION Indicates a situation that may result in equipment or property-damage-only accidents. The following format and symbol conventions appear at appropriate sections throughout this manual: IMPORTANT Alerts installer, servicer, or operator to potential actions that could cause the product or system to operate improperly but will not likely result in potential for damage. Note: A note may be used to make the reader aware of useful information, to clarify a point, or to describe options or alternatives. CNT-SVN01C-EN Contents Chapter 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Additional components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Operator display models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 EX2 expansion modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Power transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Agency listings/compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Tracer MP581 controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Expansion module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Inspection upon receipt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Tracer MP581 with enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Frame-mounted Tracer MP581 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Chapter 2 Installing the frame-mounted Tracer MP581 . . . . . 7 Enclosure requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installing the termination board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Chapter 3 Mounting the enclosure . . . . . . . . . . . . . . . . . . . . . 9 Selecting a mounting location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Operating environment requirements . . . . . . . . . . . . . . . . . . . . . . . . 9 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Mounting the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Chapter 4 Wiring high-voltage ac power . . . . . . . . . . . . . . . . 13 Local power requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Circuit requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Wiring high-voltage power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Chapter 5 Wiring inputs and outputs . . . . . . . . . . . . . . . . . . 17 Input/output wiring guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 CNT-SVN01C-EN v Contents Wire routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Providing low-voltage power for inputs and outputs. . . . . . . . . . . . . . . 19 Screw-terminal locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Wiring universal inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Wiring binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Wiring 010 Vdc analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Wiring 020 mA analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Wiring variable resistance analog inputs . . . . . . . . . . . . . . . . . . . . . 24 Wiring analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Wiring binary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Checking inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Checking thermistor inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Checking resistance temperature detector (RTD) inputs . . . . . . . . . 29 Checking linear resistance inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Checking linear voltage 010 Vdc inputs. . . . . . . . . . . . . . . . . . . . . . 30 Checking linear current 020 mA inputs . . . . . . . . . . . . . . . . . . . . . . 31 Checking binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Checking outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Checking binary outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Checking 010 Vdc analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Checking 020 mA analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Chapter 6 Installing the pressure sensor. . . . . . . . . . . . . . . . 35 Mounting the pressure sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Checking the pressure sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Chapter 7 Wiring Comm5 links . . . . . . . . . . . . . . . . . . . . . . . 39 Wiring and topology recommendations . . . . . . . . . . . . . . . . . . . . . . . . . 39 Recommended wiring practices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Wiring requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Twisted-pair wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Recommended wiring configuration . . . . . . . . . . . . . . . . . . . . . . . . 41 Termination resistance placement for Comm5 links . . . . . . . . . . . . . . . 42 Comm5 physical link repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 When is the link repeater required? . . . . . . . . . . . . . . . . . . . . . . . . . 44 Link repeater guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Link repeater connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Comm5 zone sensor comm jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Zone sensor communication stubs . . . . . . . . . . . . . . . . . . . . . . . . . . 46 vi CNT-SVN01C-EN Contents Verifying communication status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Comm LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Wiring Comm5 to the Tracer MP581 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 EMI/RFI considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Checking the earth ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Sectioning the shield on the Comm5 link . . . . . . . . . . . . . . . . . . . . 51 Chapter 8 Installing the circuit board . . . . . . . . . . . . . . . . . . 53 Chapter 9 Installing the door . . . . . . . . . . . . . . . . . . . . . . . . . 57 Installing the door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Removing the door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Chapter 10 Installing the stand-alone operator display . . . . . 59 Chapter 11 Connecting the portable operator display . . . . . . 63 Using the carrying case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Connecting the operator display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Chapter 12 Setting up the operator display . . . . . . . . . . . . . . 65 Calibrating the operator display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Setting up time and date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Adjusting brightness and contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Chapter 13 Installing EX2 expansion modules . . . . . . . . . . . . 67 Operating environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Storage environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Attaching the terminal strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Mounting the frame-mount module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Mounting the metal-enclosure module . . . . . . . . . . . . . . . . . . . . . . . . . 71 AC-power wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Wiring AC-power to the frame-mount module . . . . . . . . . . . . . . . . 73 Wiring AC-power to the metal-enclosure module. . . . . . . . . . . . . . 73 I/O bus wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Setting the I/O bus addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Input/output terminal wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 CNT-SVN01C-EN vii Contents Universal inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Binary outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Analog output and universal input setup . . . . . . . . . . . . . . . . . . . . . . . . 77 Interpreting EX2 LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Binary output LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Communications LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Chapter 14 Verifying operation and communication . . . . . . . 81 Service Pin button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Interpreting LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Binary output LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Service LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Comm LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 LEDs on the EX2 expansion module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Chapter 15 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Initial troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Binary output troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Analog output troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Universal input troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Chapter 16 Other literature. . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 viii CNT-SVN01C-EN CNT-SVN01C-EN Chapter 1 Overview This guide shows how to install the Tracer MP581 programmable controller. Product description The Tracer MP581 programmable controller provides direct digital control of a variety of heating, ventilation, and air-conditioning (HVAC) equipment. The Tracer MP581 supports the following new- and existingbuilding applications: · Air-handler control, including support of the LonMark® Space Com- fort Controller (SCC) profile and the Discharge Air Controller (DAC) profile · Control of mechanical-room equipment, including cooling towers, pumps, boilers, and heat exchangers · Control of an HVAC network for mid-sized buildings · Nearly any control process with an execution frequency of one second or greater Specifications The Tracer MP581 conforms to the specifications shown in Table 1. Table 1. Tracer MP581 specifications Dimensions 16.5 in. × 14.75 in. × 5.5 in. (see Figure 6 on page 11 (418 mm × 373 mm × 140 mm) for dimensional drawing) Weight 15 lb (7 kg) Operating temperature Frame-mount (without enclosure): From 40°F to 158°F (40°C to 70°C) With enclosure: From 32°F to 122°F (0°C to 50°C) Storage temperature Without display: From 58°F to 203°F (50°C to 95°C) With display: From 13°F to 149°F (25°C to 65°C) Humidity 1090% non-condensing Altitude 6500 ft (2000 m) Installation Category 3 Pollution Degree 2 High-voltage power requirements North America: 98132 Vac, 1 A maximum, 1 phase Other: 196264 Vac, 1 A maximum, 1 phase 1 Chapter 1 Overview Additional components The Tracer MP581 controller requires additional components for certain applications and has several options for adding an operator display. Operator display models The operator display is available in three models (see Figure 1): · Door-mounted operator display · Stand-alone operator display, for mounting up to 150 ft (46 m) from the controller · Portable operator display with carrying case Figure 1. Operator display models Door-mounted operator display Stand-alone operator display Portable operator display Sensors The Tracer MP581 supports the following sensors: · Zone temperature sensors (thermistors and linear resistance for thumbwheels) · Linear 020 mA, such as humidity sensors · Pressure sensors (use only the Trane 5 Vdc pressure-sensor kit--part number 4020 1159) · Linear 010 Vdc, such as indoor air-quality sensors · Resistance temperature detectors (up to four) · Motion sensors, time clocks, and other binary switch devices The Rover service tool is required to configure Tracer MP581 inputs for all types of sensors. Note: The Tracer MP581 supports all Trane zone sensors but does not support fan switches (HIGH, MED, LOW, AUTO, and OFF). 2 CNT-SVN01C-EN Additional components EX2 expansion modules You can add up to four EX2 expansion modules to a Tracer MP581 controller. Each expansion module adds the following points to a Tracer MP581: · Six universal inputs · Four binary outputs · Four analog outputs The EX2 is available in two packages: · Frame-mount with plastic cover (4950 0499) · Metal enclosure (4950 0500) Figure 2 illustrates the two packages. For dimensions and other information, see Chapter 13, "Installing EX2 expansion modules." Figure 2. EX2 expansion module packages EX2 with metal enclosure EX2 frame-mount package with plastic cover Power transformer The frame-mounted Tracer MP581, which ships without an enclosure, requires a UL-listed Class 2 transformer providing 70 VA at 24 Vac. CNT-SVN01C-EN 3 Chapter 1 Overview Agency listings/compliance This section lists compliance with Conformity European (CE) and Underwriters Laboratories (UL) standards. Tracer MP581 controller CE--Immunity: EN 50090-2-2:1996 CE--Electromagnetic emissions: EN 50090-2-2:1996 EN 61000-3-2:1995 EN 61000-3-3:1995 UL and C-UL listed--Energy management system UL 916 FCC Part 15, Class A Expansion module CE--Immunity: EN 50082-1:1997 EN 50082-2:1995 EN 50090-2-2:1996 EN 61326-1:1997 CE--Electromagnetic emissions: EN 50011-1:1998--Class B EN 50022-1:1998--Class B EN 50090-2-2:1996--Class B EN 61326-1:1997--Class B UL and C-UL listed--Energy management equipment UL 94-5V (UL flammability rating for plenum use) FCC Part 15 Subpart B--Class A 4 CNT-SVN01C-EN Inspection upon receipt Inspection upon receipt Make sure that you have received the correct parts with your Tracer MP581 controller. Visually inspect all parts for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred in shipping should be filed with the carrier. Tracer MP581 with enclosure The Tracer MP581 with enclosure ships with: · Enclosure with pre-mounted termination board · Main circuit board in a plastic frame · Enclosure door · Plastic bag containing four #10 (5 mm) wall anchors and four #10 × 1.5 inch (5 × 40 mm) screws · Installation sheet Frame-mounted Tracer MP581 The frame-mounted Tracer MP581 ships with: · Termination board in a plastic frame · Main circuit board in a plastic frame · Installation sheet Note: The four #8 (4 mm) screws required to mount the framemounted Tracer MP581 are not supplied. Required tools To install the Tracer MP581 controller and check it for proper operation, you will need the following tools: · Drill · Phillips-head screwdriver · Small flat-tip screwdriver (for terminal screws) · Digital multi-meter CNT-SVN01C-EN 5 Chapter 1 Overview 6 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 2 Installing the frame-mounted Tracer MP581 This chapter applies only to the frame-mounted Tracer MP581 controller. You can use the frame-mounted Tracer MP581 to replace older controllers in existing equipment or to mount in new equipment or custom enclosures. Enclosure requirements Before installing the frame-mounted Tracer MP581, make sure that the enclosure or mounting space meets the following minimum requirements: · Minimum clearances as shown in Figure 3 · 24 Vac dedicated power supply · Compliance with National Electrical Code and applicable local elec- trical codes for high-voltage power wiring to the enclosure Note: The Tracer MP581 with enclosure is mounted in a National Electrical Manufacturers Association (NEMA) 1 enclosure. To meet NEMA 4 specifications, you can order the frame-mounted Tracer MP581 (model BMTM000CA0A0) and mount it in a separately purchased NEMA 4 enclosure. Figure 3. Frame-mounted Tracer MP581 minimum clearances 0.5 in. (13 mm) 6 in. (152 mm) for I/O wires 0.5 in. (13 mm) 0.5 in. (13 mm) 3 in. (76 mm) for communications wires 7 Chapter 2 Installing the frame-mounted Tracer MP581 Installing the termination board To install the termination board in a separately purchased enclosure or in other equipment: 1. Remove the controller from its packaging and separate the top and bottom frames. 2. Using the bottom frame (with the termination board) as a template, mark the location of the four mounting holes on the mounting surface (see Figure 4). Figure 4. Frame-mounted dimensions and mounting holes Mounting holes (four locations) 3. Set the controller aside and drill holes for #8 (4 mm) screws at the marked locations. 4. Secure the controller to the mounting surface with #8 (4 mm) screws (not supplied). To install input/output wires, the main circuit board, and other components, follow the instructions in the following chapters. 8 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 3 Mounting the enclosure This chapter describes location requirements and shows how to mount the Tracer MP581 enclosure. Selecting a mounting location Make sure that the location meets the operating environment requirements and clearance requirements described in the following sections. The Tracer MP581 controller must be installed indoors. Trane recommends locating the Tracer MP581 controller: · Near the controlled equipment to reduce wiring costs · Where service personnel have easy access · Where it is easy to see and interact with the operator display · Where public access is restricted to minimize the possibility of tampering or vandalism CAUTION Equipment damage! Install the Tracer MP581 in a location that is out of direct sunlight. Failure to do so may cause the Tracer MP581 to overheat. Operating environment requirements Make sure that the operating environment conforms to the specifications listed in Table 2. Table 2. Operating environment specifications Temperature With enclosure: From 32°F to 122°F (0°C to 50°C) Frame-mount (without enclosure): From 40°F to 158°F (40°C to 70°C) Humidity 1090% non-condensing Altitude 6500 ft (2000 m) High-voltage power North America: 98132 Vac, 1 A maximum, 1 phase requirements Other: 196264 Vac, 1 A maximum, 1 phase Weight Mounting surface must be able to support 25 lb (12 kg) Note: The Tracer MP581 with enclosure is mounted in a National Electrical Manufacturers Association (NEMA) 1 enclosure. To meet NEMA 4 specifications, you can order the frame-mounted Tracer MP581 (model BMTM000CA0A0) and mount it in a separately purchased NEMA 4 enclosure. 9 Chapter 3 Mounting the enclosure Clearances Make sure that the mounting location has enough room to meet the minimum clearances shown in Figure 5. Figure 6 on page 11 shows the dimensions of the Tracer MP581 enclosure. Figure 5. Minimum clearances for enclosure 12 in. (30 cm) 24 in. (60 cm) to fully open door 12 in. (30 cm) 12 in. (30 cm) 50 in. (130 cm) recommended 36 in. (90 cm) 10 CNT-SVN01C-EN Figure 6. Tracer MP581 enclosure dimensions Selecting a mounting location Top view Left view Front view Right view CNT-SVN01C-EN Bottom view Note: Six of the twelve knockouts are dual-sized knockouts for 1-inch (25 mm) and 0.75-inch (19 mm) conduit. 11 Chapter 3 Mounting the enclosure Mounting the enclosure The back of the enclosure is shipped with the termination board installed inside of it. IMPORTANT The termination board should be shipped with the grounding screw installed. Verify this by checking the location shown in Figure 7. The enclosure door is shipped separately. If the door has already been attached to the enclosure back, remove it. To mount the enclosure: 1. Using the enclosure as a template, mark the location of the four mounting holes on the mounting surface (see Figure 7). Figure 7. Enclosure mounting holes Mounting hole (four locations) Termination board grounding screw 2. Set the enclosure aside and drill holes for the screws at the marked locations. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 3. Insert wall anchors if needed. 4. Secure the enclosure to the mounting surface with the supplied #10 (5 mm) screws. 12 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 4 Wiring high-voltage ac power This chapter shows how to wire high-voltage ac power to the enclosure. Local power requirements The Tracer MP581 controller is available in five configurations, described in Table 3. Before wiring high-voltage power, make sure that you have the correct model for local power requirements. You can find the model number on the shipping label or on the product label inside the enclosure. Table 3. Tracer MP581 models Model Number Description BMTM000AA0A0 BMTM000AA0A1 BMTM000BA0A0 BMTM000BA0A1 BMTM000CA0A0 Enclosure, 120 Vac Enclosure, 120 Vac, with operator display Enclosure, 230 Vac, CE-compliant Enclosure, 230 Vac, with operator display, CE-compliant Frame-mounted, 24 Vac, CE-compliant Circuit requirements To ensure proper operation of the Tracer MP581, install the power supply circuit in accordance with the following guidelines: · The Tracer MP581 must receive high-voltage power from a dedicated power circuit. Failure to comply may cause control malfunctions. · A disconnect switch for the dedicated power circuit must be near the controller, within easy reach of the operator, and marked as the disconnecting device for the controller. · High-voltage power-wire conduits or wire bundles must not contain input/output wires. Failure to comply may cause the controller to malfunction due to electrical noise. · High-voltage power wiring must comply with the National Electrical Code (NEC) and applicable local electrical codes. · High-voltage power wiring requires three-wire 120/230 Vac service. Use copper conductors only. Note: The voltage utilization range for the Tracer MP581 transformer is 98132 Vac (120 Vac nominal) or 196264 Vac (230 Vac nominal). The panel detects whether the current is 50 or 60 cycle. 13 Chapter 4 Wiring high-voltage ac power Wiring high-voltage power WARNING Hazardous voltage! Before making electrical connections, lock open the supply-power disconnect switch. Failure to do so could result in death or serious injury. CAUTION Use copper conductors only! Unit terminals are designed to accept copper conductors only. Other conductors may cause equipment damage. IMPORTANT Make sure that you have the correct Tracer MP581 model for 120 Vac or 230 Vac. Table 3 on page 13 lists the available models. To connect high-voltage power wires: 1. Lock open the supply-power disconnect switch. 2. At the top right corner of the enclosure, remove the knockout and install 0.5-inch (13 mm) conduit (see Figure 8). Figure 8. Knockout for high-voltage power wires Power wire entry through knockout for 0.5-inch conduit 3. Open or remove the Tracer MP581 door if it is already installed. 4. Inside of the enclosure at the top-right corner, remove the high-voltage area cover plate. 5. Feed the high-voltage power wires into the enclosure. 14 CNT-SVN01C-EN Wiring high-voltage power 6. Connect the line wire to the L terminal as shown in Figure 9. Figure 9. Terminal block for high-voltage power wires Conduit Ground wire to ground screw Line wire to L terminal Neutral wire to N terminal 7. Connect the neutral wire to the N terminal. 8. Connect the green ground wire to the chassis ground screw. The ground wire should be continuous back to the circuit-breaker panel. 9. Replace the cover plate. WARNING Hazardous voltage! The cover plate must be in place when the controller is operating. Failure to replace the cover plate could result in death or serious injury. 10. On a label, record the location of the circuit-breaker panel and the electrical circuit. Attach the label to the cover plate. CNT-SVN01C-EN 15 Chapter 4 Wiring high-voltage ac power 16 CNT-SVN01C-EN Chapter 5 Wiring inputs and outputs The Tracer MP581 enclosure is designed to simplify the wiring and configuration of inputs and outputs by providing a large space for routing wires and by eliminating the need to manipulate jumpers. Table 4 lists Tracer MP581 inputs and outputs. Table 4. Inputs and outputs Type Number Description Universal inputs Static pressure input Binary outputs Analog outputs 12 Dry-contact binary, thermistor, 020 mA, 010 Vdc, linear resistance. The first four inputs can be used directly with resistance temperature detectors (RTDs). 1 Differential pressure sensor, 5 Vdc, 05 in. wc 6 Powered relay contacts, 12 VA at 24 Vac 6 010 Vdc or 020 mA Input/output wiring guidelines Input/output wiring must meet the following guidelines: · Wiring must conform with the National Electrical Code and local elec- trical codes. · Use only 1822 AWG (1.020.643 mm2), twisted-pair wire with stranded, tinned-copper conductors. · Binary input/output wires must not exceed 1,000 ft (300 m). · Analog input wires must not exceed 300 ft (100 m) for thermistors and 010 Vdc inputs and 1,000 ft (300 m) for 020 mA inputs. · Analog output wires must not exceed 1,000 ft (300 m) for 010 Vdc outputs and 020 mA outputs. · Do not run input/output wires in the same wire bundle with high- voltage power wires. Running input/output wires with 24 Vac power wires is acceptable, but the input wire must be shielded. · Terminate input/output wires before installing the main circuit board (see Chapter 8, "Installing the circuit board"). CNT-SVN01C-EN 17 Chapter 5 Wiring inputs and outputs Wire routing Figure 10 shows how to route input/output wires through the enclosure. It also shows the locations of wire-tie brackets. See Figure 6 on page 11 for knockout locations and dimensions. Metal conduit may be required by local codes when running input/output wires. Note: If your application requires a pressure sensor, install the pressure sensor before wiring other inputs and outputs. (So that the mounting holes are not covered by wires.) For more information, refer to Chapter 6, "Installing the pressure sensor." Figure 10. Wire routing Brackets for wire ties (9 locations) Mounting holes for pressure sensor (sensor will affect wire routing) Recommended communication wire route 18 CNT-SVN01C-EN Providing low-voltage power for inputs and outputs Providing low-voltage power for inputs and outputs The Tracer MP581 controller can provide low-voltage power to inputs and outputs. Figure 11 on page 20 shows the location of the low-voltage screw terminals on the termination board. The following limitations apply: · Four 24 Vdc screw terminals supply a total of up to 250 mA of power. · Two 24 Vac screw terminals supply a total of up to 50 VA of power. The 50 VA of available power supplies both the 24 Vac screw terminals and binary outputs. Note that more than one input or output can receive power from a given screw terminal. The only limitation is the total amount of power supplied. CNT-SVN01C-EN 19 Chapter 5 Wiring inputs and outputs Screw-terminal locations Figure 11 shows screw-terminal locations on the termination board. The top row of screw terminals is for signal wires, and the bottom row of screw terminals is for common wires. To make sure that the wires lie flat, use the wire strip guide on the termination board to strip input/output wires to the correct length. Figure 11. Screw-terminal locations Common terminals Signal terminals 24 Vac power connector Binary outputs 24 Vac power Analog outputs Wire strip guide Universal inputs (IN1IN4 can accept RTDs) 24 Vdc power Comm5 screw terminals Comm5 jack for Rover service tool I/O bus for EX2 expansion modules (formerly labeled Machine Bus) Duct-static pressure connector 20 CNT-SVN01C-EN Wiring universal inputs Wiring universal inputs The Tracer MP581 controller has 12 universal inputs. Use the Rover service tool to configure inputs for analog or binary operation. The common terminals on the Tracer MP581 termination board are connected to the metal enclosure by means of a ground screw. Shield wires should be connected to a common terminal. Table 5 shows the load the Tracer MP581 places on sensors. Table 5. Load placed on sensors Input type Load on sensor Vdc (linear) mA (linear) 21 k 221 Wiring binary inputs Use binary inputs to monitor statuses, such as fan on/off and alarm resets. To wire a binary input: 1. Connect the common wire to a common terminal as shown in Figure 12. Note that because the common terminals are in parallel, you can wire the common wire to any available common terminal. 2. Connect the shield wire to a common terminal at the termination board and tape it back at the input device. 3. Connect the signal wire to an available input terminal (IN1IN12). 4. Use the Rover service tool to configure the input for binary operation. Figure 12. Wiring a binary input Signal < 1000 ft (300 m) Common Binary switch Tape back shield Shield CNT-SVN01C-EN 21 Chapter 5 Wiring inputs and outputs Wiring 010 Vdc analog inputs Common 010 Vdc analog inputs include indoor air-quality sensors and pressure sensors. To wire a 010 Vdc analog input: 1. Use the shield wire as the common connection, connecting it to a common terminal at the sensor and at the termination board (see Figure 13). 2. Connect the signal wire to an available input terminal (IN1IN12). 3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required. 4. Use the Rover service tool to configure the input for analog operation. Figure 13. Wiring a 010 Vdc analog input 010 Vdc sensor 24 Vdc 010 Vdc out v Common < 300 ft (100 m) 22 CNT-SVN01C-EN Wiring universal inputs Wiring 020 mA analog inputs Common 020 mA analog inputs include humidity sensors and pressure sensors. To wire a 020 mA analog input: 1. For three-wire applications, use a 3-conductor cable with a shield. . For two-wire applications, use a 2-conductor cable with a shield. Connect the shield to a common terminal at the termination board and tape it back at the sensor (see Figure 14). Do not use the shield as the common connection. 2. Connect the signal wire to an available input terminal (IN1IN12). 3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required. 4. Use the Rover service tool to configure the input for analog operation. Figure 14. Wiring 020 mA analog inputs 020 mA sensor (current source) 24 Vdc 020 mA out Common < 1000 ft (300 m) Tape back shield 020 mA sensor (current controller) 24 Vdc 020 mA out < 1000 ft (300 m) CNT-SVN01C-EN 23 Chapter 5 Wiring inputs and outputs Wiring variable resistance analog inputs Variable resistance analog inputs include 10K thermistors, resistance temperature detectors (RTDs), and setpoint thumbwheels on zone sensors. IMPORTANT The Tracer MP581 controller can accept RTDs only on inputs 14. To wire a variable resistance analog input: 1. For three-wire applications, use a 3-conductor cable with a shield(see Figure 15). For two-wire applications, use a 2-conductor cable with a separate shield. Connect the shield to a common terminal board and tape it back at the output device. Do not use the shield wire as a common connection. 2. Connect the signal wire to an available input terminal (IN1IN12). 3. Use the Rover service tool to configure the input for analog operation. Figure 15. Wiring variable resistance analog inputs Variable resistance Signal < 300 ft (100 m) Can accept RTD inputs Common Tape back shield Temperature sensor Signal Trane zone sensor Common < 300 ft (100 m) Setpoint Common Temperature < 300 ft (100 m) 24 CNT-SVN01C-EN Wiring analog outputs Wiring analog outputs The Tracer MP581 controller has six analog outputs. These outputs can be either 010 Vdc outputs or 020 mA outputs. Analog outputs control actuators and secondary controllers. To wire an analog output: 1. For three-wire applications, use the shield wire as the common connection (see Figure 16). For two-wire applications, connect the shield wire to a common terminal at the termination board and tape it back at the output device. 2. Connect the signal wire to an available analog output terminal (AO1AO6). 3. Connect the supply wire to a 24 Vac terminal as required. 4. Use the Rover service tool to configure the analog output. Figure 16. Wiring analog outputs Ac powered actuator 24 Vac Signal Common < 1000 ft (300 m) Tape back shield Signal Common 010 Vdc output Load > 500 < 1000 ft (300 m) Signal < 300 ft i (100 m) Common 020 mA output Load < 500 Tape back shield CNT-SVN01C-EN 25 Chapter 5 Wiring inputs and outputs Wiring binary outputs The Tracer MP581 controller has six binary outputs. These are powered outputs, not dry-contact outputs. IMPORTANT Use pilot relays for dry-contact outputs and when the load current is greater than 0.5 A. Use powered outputs when the load current is less than 0.5 A. Note: When controlling coil-based loads, such as pilot relays, do not forget to account for "inrush" current. Inrush current can be three (or more) times greater than the operating current. You can find information on inrush current for specific types of outputs in their product specifications. To wire a binary output: 1. Connect the common wire to a common terminal as shown in Figure 17. 2. Connect the shield wire to a common terminal at the termination board and tape it back at the output device. 3. Connect the signal wire to an available binary output terminal (BO1BO6). 4. Use the Rover service tool to configure the binary output. Figure 17. Wiring binary outputs Powered output Signal < 1000 ft (300 m) Pilot relay 24 Vac coil Common Tape back shield Signal Common < 1000 ft (300 m) 26 CNT-SVN01C-EN Checking inputs Checking inputs Follow the procedures in this section to test inputs for proper operation. IMPORTANT Perform the tests in this section before providing power to the termination board or installing the main circuit board. Failure to do so will result in incorrect multi-meter readings. To test inputs for proper operation, you need the following tools: · Digital multi-meter · Small flat-tip screwdriver Checking thermistor inputs To check thermistor inputs for proper operation: 1. Make sure that the sensor is connected. 2. Set the multi-meter to measure Vac, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, temperature readings may change erratically. 3. Set the multi-meter to measure Vdc, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, temperature readings may be offset from the expected results. CAUTION Equipment damage! Continue to step 4 only if you completed steps 2 and 3 successfully. Measuring resistance may damage the meter if the voltage is too high. 4. Set the multi-meter to measure resistance. If you completed steps 2 and 3 successfully, measure the resistance across the input at the signal and common screw terminals. The resistance should be between 241 k and 837 , which translates to temperatures of 30°F and 200°F (34°C and 93°C). Specific temperatures and resistances are shown in Table 6 on page 28. CNT-SVN01C-EN 27 Chapter 5 Wiring inputs and outputs Table 6. Temperature and resistance characteristics of sensors Temperature (°F and °C) Thermistor resistance () Balco 375 Platinum 385 Platinum RTD resistance RTD resistance RTD resistance () () () 30°F 20°F 10°F 0°F 10°F 20°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 125°F 150°F 175°F 200°F (34°C) (29°C) (23°C) (18°C) (12°C) (7°C) (1°C) (4°C) (10°C) (16°C) (21°C) (27°C) (32°C) (38°C) (52°C) (66°C) (79°C) (93°C) 241,071 170,041 121,326 87,511 63,769 46,919 34,839 26,221 19,955 15,333 11,889 9,298 7,330 5,824 3,382 2,049 1,296 837 798 816 835 855 875 895 915 936 957 978 1,000 1,022 1,044 1,067 1,125 1,185 1,247 1,311 868 889 910 932 953 975 996 1,017 1,038 1,059 1,080 1,101 1,122 1,143 1,195 1,247 1,299 1,350 865 886 908 930 952 974 996 1,017 1,039 1,061 1,082 1,104 1,125 1,147 1,200 1,254 1,307 1,360 28 CNT-SVN01C-EN Checking inputs Checking resistance temperature detector (RTD) inputs To check RTD inputs for proper operation: 1. Make sure that the sensor is connected. 2. Set the multi-meter to measure Vac, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, temperature readings may change erratically. 3. Set the multi-meter to measure Vdc, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, temperature readings may be offset. CAUTION Equipment damage! Continue to step 4 only if you completed steps 2 and 3 successfully. Measuring resistance may damage the meter if the voltage is too high. 4. Set the multi-meter to measure resistance. If you completed steps 2 and 3 successfully, measure the resistance across the input at the signal and common screw terminals. For a 375 platinum RTD, the resistance should be between 868 and 1350 , which translates to temperatures of 30°F and 200°F (34°C and 93°C). Table 6 on page 28 shows appropriate ranges for other types of RTDs. CNT-SVN01C-EN 29 Chapter 5 Wiring inputs and outputs Checking linear resistance inputs To check linear resistance inputs for proper operation: 1. Make sure that the sensor is connected. 2. Set the multi-meter to measure Vac, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, resistance readings may change erratically. 3. Set the multi-meter to measure Vdc, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, resistance readings may be offset. CAUTION Equipment damage! Continue to step 4 only if you completed steps 2 and 3 successfully. Measuring resistance may damage the meter if the voltage is too high. 4. Set the multi-meter to measure resistance. If you completed steps 2 and 3 successfully, measure the resistance across the input at the signal and common screw terminals. The resistance should be between 100 and 20 k. Checking linear voltage 010 Vdc inputs The following test works only for 010 Vdc inputs that have their own power supply. To check linear voltage 010 Vdc inputs for proper operation: 1. Make sure that the sensor is connected and powered on. 2. Set the multi-meter to measure Vac, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, sensor readings may change erratically. 3. Set the multi-meter to measure Vdc, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be between 0 and 10 Vdc. If the voltage is greater than 10 Vdc, check the connections at the controller. If it is less than 0 Vdc, check the meter and input connections. 4. Force a change in the sensor reading. 5. Use the multi-meter to confirm that the change appears at the correct input on the terminal board. 30 CNT-SVN01C-EN Checking inputs Checking linear current 020 mA inputs To check linear current inputs for proper operation: 1. Make sure that the sensor is connected and powered on. 2. Set the multi-meter to measure Vac, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, sensor readings may change erratically. 3. Set the multi-meter to measure mA, then measure the current across the input at the signal and common screw terminals. The measured current should be between 0 and 20 mA. If the current is greater than 20 mA, check the connections at the controller. If the current is less than 0 mA, check the meter and input connections. 4. Force a change in the sensor reading. 5. Use the multi-meter to confirm that the change appears at the correct input on the terminal board. Checking binary inputs To check binary inputs for proper operation: 1. Make sure that the sensor is connected and powered on. 2. Set the multi-meter to measure Vac, then measure the voltage across the input connections at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, the input readings may change erratically. 3. Set the multi-meter to measure Vdc, then measure the voltage across the input at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, the input readings may be offset. CAUTION Equipment damage! Continue to step 4 only if you completed steps 2 and 3 successfully. Measuring resistance may damage the meter if the voltage is too high. 4. Set the multi-meter to measure resistance. If you completed steps 2 and 3 successfully, measure the resistance across the input. The resistance should be less than 200 when the binary input is closed and greater than 1 k when it is open. CNT-SVN01C-EN 31 Chapter 5 Wiring inputs and outputs Checking outputs Follow the procedures in this section to test outputs for proper operation. IMPORTANT Perform the tests in this section before providing power to the termination board or installing the main circuit board. Failure to do so will result in incorrect multi-meter readings. To test outputs for proper operation, you need the following tools: · Digital multi-meter · Small flat-tip screwdriver Checking binary outputs To check binary outputs for proper operation: 1. Set the multi-meter to measure Vac, then measure the voltage across the binary output at the common and signal screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, the load may turn on and off unexpectedly. Check for the following problems: · A shared power supply may be incorrectly connected. Check the wire to make sure that no additional connections have been made. · The wire may have an induced voltage somewhere along its length. 2. Set the multi-meter to measure Vdc, then measure the voltage across the binary output at the common and signal screw terminals. The measured voltage should be less than 0.1 Vdc. If the it is greater than this, a shared power supply may be incorrectly connected. Check the wire to make sure that no additional connections have been made. CAUTION Equipment damage! Continue to step 3 only if you completed steps 1 and 2 successfully. Measuring resistance may damage the meter if the voltage is too high. 3. Set the multi-meter to measure resistance. If you completed steps 1 and 2 successfully, measure the resistance across the binary output to confirm that there are no shorts and no open circuits. Resistance is load dependent. Pilot relays have a relatively low resistance of less than 1 k, but some actuators have a high resistance. Check to see what kind of binary output is connected before checking for open and short circuits. 32 CNT-SVN01C-EN Checking outputs Checking 010 Vdc analog outputs To check 010 Vdc analog outputs for proper operation: 1. Make sure that the actuator is connected but powered off. 2. Set the multi-meter to measure Vac, then measure the voltage across the analog output at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, the load may turn on and off unexpectedly. Check for the following problems: · A shared power supply may be incorrectly connected. Check along the wire to make sure that no additional connections have been made. · The wire may have an induced voltage somewhere along its length. 3. Set the multi-meter to measure Vdc, then measure the voltage across the analog output at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, a shared power supply may be incorrectly connected. Check along the wire to make sure that no additional connections have been made. CAUTION Equipment damage! Continue to step 4 only if you completed steps 2 and 3 successfully. Measuring resistance may damage the meter if the voltage is too high. 4. Set the multi-meter to measure resistance. If you completed steps 2 and 3 successfully, measure the resistance across the analog output at the signal and common screw terminals. The resistance should be greater than 500 . (The analog output will not be able to reach 10 Vdc if the load resistance is less than 500 .) CNT-SVN01C-EN 33 Chapter 5 Wiring inputs and outputs Checking 020 mA analog outputs To check 020 mA analog outputs for proper operation: 1. Make sure that the actuator is connected but powered off. 2. Set the multi-meter to measure Vac, then measure the voltage across the analog output at the signal and common screw terminals. The measured voltage should be less than 0.1 Vac. If the voltage is greater than this, the load may turn on and off unexpectedly. Check for the following problems: · A shared power supply may be incorrectly connected. Check along the wire to make sure that no additional connections have been made. · The wire may have an induced voltage somewhere along its length. 3. Set the multi-meter to measure Vdc, then measure the voltage across the analog output at the signal and common screw terminals. The measured voltage should be less than 0.1 Vdc. If the voltage is greater than this, a shared power supply may be incorrectly connected. Check along the wire to make sure that no additional connections have been made. 34 CNT-SVN01C-EN Chapter 6 Installing the pressure sensor This chapter shows how to install a pressure sensor in the Tracer MP581 controller. To simplify installation of the pressure sensor, mount and wire it before wiring inputs and outputs. Mounting the pressure sensor IMPORTANT Use only pressure sensors with non-conductive plastic cases with the Tracer MP581 controller. Pressure sensors with conductive plastic cases may generate incorrect data. To ensure proper results, order the Trane pressure-differential 5 Vdc sensor kit (part number 4020 1159). To mount the pressure sensor in the Tracer MP581 enclosure: 1. Open or remove the enclosure door. 2. Use the supplied #6 (3.5 mm) mounting screws to mount the pressure sensor to the mounting holes shown in Figure 18. Figure 18. Mounting the pressure sensor Pressure sensor mounting holes CNT-SVN01C-EN 3. Connect the pressure-sensor cable to the duct-static connector on the termination board as shown in Figure 19 on page 36. The duct-static connector fits only one way. If you have difficulty connecting the cable, rotate it 180° and try again. 35 Chapter 6 Installing the pressure sensor 4. Run the high and low input tubes to an appropriate place in the duct. Figure 19. Wiring the pressure sensor Duct-static connector 36 CNT-SVN01C-EN Checking the pressure sensor Checking the pressure sensor You can check the pressure sensor for proper operation only after supplying power to the controller and installing the main circuit board. You will need a digital multi-meter to complete the check. To check the pressure sensor for proper operation: 1. Make sure that the main circuit board has been installed and power has been provided to the controller. 2. Make sure that the pressure-sensor is connected to the duct-static input on the termination board. 3. Set the digital multi-meter to measure dc voltage. 4. Connect the multi-meter to the input as shown in Figure 20 and dis- cussed in table Table 7. Figure 20. Connecting the multi-meter to the duct-static input CNT-SVN01C-EN Green Black Red Duct-static connector on termination board 5. Make sure that the multi-meter readings fall within the ranges shown in Table 7. If a reading is not within the expected range, check for faulty connections or a faulty pressure sensor. Table 7. Expected voltages for the pressure sensor input Multi-meter () lead at Multi-meter (+) lead at Measured dc voltage Green (ground) Green (ground) Red (in) Black (out) 4.85.2 Vdc 0.245.2 Vdc 37 Chapter 6 Installing the pressure sensor 38 CNT-SVN01C-EN Chapter 7 Wiring Comm5 links The Tracer MP581 controller interacts with a Tracer Summit building automation system (BAS) and other LonTalk Comm5 controllers through a Comm5 communication link. This chapter describes how wire Comm5 links. For more information on connecting a Tracer MP581 to a Tracer Summit BAS, see the Tracer Summit Hardware and Software Installation guide (BMTW-SVN01D-EN). Wiring and topology recommendations Trane GCS has updated its recommendations for Comm5 wiring and topology. These recommendations are different than originally published Comm5 installation practices. The following information summarizes the wiring and topology recommendations: · 22 AWG Level 4 unshielded communication wire recommended for most Comm5 installations · Shielded Level 4 wire is recommended for the Comm5 Tracker and for all communication wiring on the VariTrac CCP (see Appendix) · Comm5 link limits: 4500 feet, 60 devices maximum (without repeater) · Termination resistors are required --105 ohms at each end for Level 4 wire --82 ohms at each end for Trane "purple" wire · Comm5 topology should be daisy chain · Zone sensor communication stubs limited to 8 per link, 50 feet each maximum · One repeater can be used for an additional 4500 feet, 60 devices, 8 communication stubs CNT-SVN01C-EN 39 Chapter 7 Wiring Comm5 links Recommended wiring practices Follow these guidelines when installing communication wire: · All wiring must comply with the National Electrical Code (NEC) and local codes. · Although Comm5 does not require polarity sensitivity, Trane GCS recommends keeping polarity consistent throughout the site. · Make sure that 24 Vac power supplies are consistent in how they are grounded. Avoid sharing 24 Vac between Comm5 controllers. · Avoid overtightening cable ties and other forms of cable wraps. This can damage the wires inside the cable. · Do not run Comm5 cable alongside or in the same conduit as 24 Vac power. This includes the conductors running from triac-type inputs. · In open plenums, avoid running wire near lighting ballasts, especially those using 277 Vac. · Use a daisy chain configuration · Use termination resistors as described in "Termination resistance placement for Comm5 links" on page 42 · Insulate termination-resistor leads. · Use only one type of communication wire--do not mix different types of wire. 40 CNT-SVN01C-EN Wiring requirements Wiring requirements Twisted-pair wire The recommended Comm5 communication-link wiring is 22-gauge, Level 4, twisted-pair wire. The wire can be either shielded or unshielded. However unshielded wire is recommended for most installations. You can also use low capacitance, 18-gauge, shielded, twisted-pair with stranded, tinned-copper conductors (Trane "purple" wire). The maximum wire length for Comm5 communication links is 4,500 ft (1,400 m). Recommended wiring configuration Comm5 communication-link wiring must be installed in a daisy-chain configuration (see Figure 21 and Figure 22 on page 42). Figure 21. Daisy chain configuration System Panel Device Device Device Figure Note: · Maximum wire length for Comm5 is 4,500 ft (1,400 m). (Comm5 wire length limitations can be extended through the use of a link repeater. See "Comm5 physical link repeater" on page 44.) · For termination resistor placement, see "Termination resistance placement for Comm5 links" on page 42. CNT-SVN01C-EN 41 Chapter 7 Wiring Comm5 links Figure 22. Alternate daisy chain configuration Device Repeater Device Device Device System panel Device Device Figure Note: · Repeater with system panel in the middle of the link · Maximum wire length for Comm5 is 4,500 ft (1,400 m) on each side of the repeater · For termination resistor placement, see "Termination resistance placement for Comm5 links" on page 42 Termination resistance placement for Comm5 links Termination resistors are required at each end of Comm5 communication daisy chain links. To correctly place termination resistors follow these guidelines: · Terminate a daisy chain configuration with a resistor at each end of the link (see Figure 23 on page 43): --22 AWG Level 4 wire 105 , 1%, 1/4 Watt --18 AWG Trane "purple" wire 82 , 1%, 1/4 Watt · If a repeater is used, each link of the configuration that is created by the repeater requires termination resistors (see Figure 24 on page 43). · Trane recommends that only one type of wire be used for the Comm5 communication link. · A set of as-built drawings or a map of the communication wire layout should be made during installation. Any sketch of the communication layout should feature the terminating resistor placement. 42 CNT-SVN01C-EN Termination resistance placement for Comm5 links Figure 23. Daisy chain resistor placement Termination resistor System panel Device Device Device Termination resistor Figure Note: · 105 , 1%, 1/4 Watt for 22 AWG, Level 4 · 82 , 1%, 1/4 Watt for 18 AWG, Trane "purple' wire Figure 24. Alternate daisy chain resistor placement Termination resistor Device Termination resistor Device Repeater Device System panel Termination resistor Device Device Termination resistor Device Figure Note: · Maximum wire length for the entire configuration Comm5 is 4,500 ft (1,400 m) · Maximum wire length for Comm5 is 4,500 ft (1,400 m) (Comm5 wire length limitations can be extended through the use of a link repeater, see "Comm5 physical link repeater" on page 44) CNT-SVN01C-EN 43 Chapter 7 Wiring Comm5 links Comm5 physical link repeater A Comm5 link repeater regenerates the signal on a Comm5 link. The configurations on either side of the repeater should be daisy chain. Both link segments require proper termination (see Figure 24). When is the link repeater required? A link repeater is required when: · The total wire length is greater than the maximum wire run length of 4,500 ft (1400 m). · More than 60 devices are connected to a link. This total does not include the BCU, the link repeater, and the temporary use of a service tool on the same link. · More than eight zone sensor communication stubs (maximum 50 ft) are required on a Comm5 link (see "Comm5 zone sensor comm jack" on page 46). Link repeater guidelines Follow these guidelines when using link repeaters: · Only one link repeater can be used on a link. · The use of a repeater doubles the maximum allowable wire length. For example, when a repeater is used with a daisy chain configuration, the total wire length can be 9,000 ft (3,800 m) (with half the wire length on either side of the repeater). · The link repeater is limited to 60 devices on either side of the link. · The link repeater requires an earth ground. The installer should be aware of this before making any power connections. Link repeater connections The recommended shield connections are shown in Figure 25. Use these connections for instances where shielded communication wire is used. For an example of using a repeater to create an extended daisy chain configuration see Figure 26 on page 45. Follow these guidelines when using a repeater: · Read the Comm5 repeater installation, 3270 3285 information that comes with the link repeater. · For information about terminating daisy chain configurations, see "Termination resistance placement for Comm5 links" on page 42. · Shield-drain wires entering the repeater should be connected to a ter- minal marked with a capacitor symbol. The entering shield-drain wire must be connected to earth ground at the system panel. · Shield-drain wires leaving the repeater should be connected to the repeater terminal marked with an earth ground symbol. 44 CNT-SVN01C-EN Figure 25. Comm5 shield repeater connection Comm5 physical link repeater Entering shield Figure 26. Comm5 daisy chain repeater connection and shielded wire System Panel * A continuous shield is required when shielded wire is used. If unshielded communication wire is used, no shield connections are necessary. At each controller, splice shield wire and tape back to prevent grounding. Connect shield wire to earth ground at system panel and repeater. **The value of the termination resistor is dependent on the wire type: 105-ohm for 22 AWG, Level 4 wire and 82-ohm for 18 AWG, Trane "purple" wire. CNT-SVN01C-EN 45 Chapter 7 Wiring Comm5 links Comm5 zone sensor comm jack Many Trane zone sensor models include a communication jack. When properly wired to the communication terminals on the unit controller, the communication jack provides easy access to both the controller and the entire Comm5 link. This enables you to access the status and configuration information of any controller on the link using the Rover service tool. The recommended wire between the controller and the communication jack is 22-gauge, Level 4 wire; or 18-gauge, shielded, twisted-pair with stranded, tinned-copper conductors (Trane "purple" wire). Thermostat wire is not recommended for the communication jack. Zone sensor communication stubs The wire that runs between the controller and zone sensor is commonly referred to as the communication stub. Figure 27 shows an example of communication stubs on a Comm5 link when a repeater is used. Note: · Only 8 stubs can be used per Comm5 link. To add more stubs to the link, a repeater is necessary. Up to 8 stubs may be used on each side of the repeater (16 total stubs). · Each communication stub must not exceed 50 feet in length. Figure 27. Communication stubs used with a repeater System panel Repeater Device Device Device Device Device Device Comm stub Comm stub Figure Note: · Maximum wire length on either side of the repeater is 4,500 ft (1,400 m). · The link repeater is limited to 60 devices on either side of the link. · *Termination resistors placed at the end of each link. The resistance value of the termination resistor is 105-ohm resistor for Level 4 wire at each end of the link. For Trane "purple" wire use an 82-ohm resistor at each end of the link. 46 CNT-SVN01C-EN Verifying communication status Verifying communication status The information in this section will help you to interpret LED status lights on the Comm5 system panel. Comm LED The yellow Comm LED indicates the communication status of the Comm5 controller. Table 8 describes Comm LED activity. Table 8. Yellow Comm LED LED activity LED is off continuously LED blinks LED is on continuously Explanation The controller is not detecting any communication (normal for standalone applications). The controller detects communication (normal for communicating applications, including data sharing). An abnormal condition that may occur during discovery. The LED may flash fast enough to look as if it is on continuously. If this LED activity occurs at any other time, the site may have excessive radio frequency interference (RFI). CNT-SVN01C-EN 47 Chapter 7 Wiring Comm5 links Wiring Comm5 to the Tracer MP581 IMPORTANT When installing the Tracer MP581 controller in areas of high electromagnetic interference (EMI) and radio frequency interference (RFI), follow the additional installation instructions in "EMI/RFI considerations" on page 50. Note: Although Comm5 links are not polarity sensitive, we recommend that you keep polarity consistent throughout the site. To wire the Comm5 link: 1. At the first Tracer MP581 on the link, complete the following steps: · Connect the shield wire to a ground, either at a common terminal on the termination board or on the main circuit board (see Figure 28 and Figure 29 on page 49). If you choose to ground the shield wire to the main board, use a #6 (3.5 mm) screw (not supplied) to secure the shield wire. · Connect the white wire to the first (or third) Comm5 screw termi- nal as shown in Figure 28. · Connect the black wire to the second (or fourth) Comm5 screw terminal. · If this is the first Comm5 controller on the daisy chain, place a 100 termination resistor across the Comm5 screw terminals. Figure 28. Grounding on the termination board Shield wire Note: Place a 100 termination resistor at the first and last Comm5 device on the daisy chain. 48 CNT-SVN01C-EN Wiring Comm5 to the Tracer MP581 Figure 29. Grounding on the main circuit board Shield wire 2. At the next Tracer MP581 (or other Comm5 controller) on the link: · Connect the white wires to the first and third Comm5 screw ter- minals as shown in Figure 30 on page 49. · Connect the black wires to the second and fourth Comm5 screw terminals. · Splice together the bare shield wires and tape them. 3. At the last controller on the Comm5 link: · Connect the white wire to the first Comm5 screw terminal. · Connect the black wire to the second Comm5 screw terminal. · Cut back and tape the shield wire to prevent grounding. · Place a 100 termination resistor across the Comm5 screw terminals. Figure 30. Connecting Comm5 wires at the Tracer MP581 CNT-SVN01C-EN Splice shield wires and tape back 49 Chapter 7 Wiring Comm5 links EMI/RFI considerations Take care to isolate HVAC controllers from electromagnetic interference (EMI) and radio frequency interference (RFI). Such interference can be caused by radio and TV towers, hospital diagnostic equipment, radar equipment, electric power transmission equipment, and so on. In addition, take care to prevent the Tracer MP581 controller from radiating EMI and/or RFI. The Tracer MP581 is equipped with EMI/RFI filters that trap RFI to ground. In most situations, a good earth ground will reduce EMI/RFI problems by acting as a drain for EMI and RFI. If the Tracer MP581 is receiving or radiating interference, make sure that the earth ground is good. Do not assume that the building conduit is an adequate ground. Checking the earth ground Though a proper earth ground is especially important in areas of high EMI or RFI, always check the quality of the ground, regardless of location. WARNING Hazardous voltage! The cover plate must be in place when the controller is operating. Failure to replace the cover plate could result in death or serious injury. WARNING Hazardous voltage! If the earth ground has a voltage of more than 4 Vac, use a different ground. Failure to do so could result in death or serious injury. To check the quality of the earth ground: 1. Open the enclosure door. 2. Inside of the enclosure at the top-right corner, remove the high-volt- age area cover plate. 3. Measure the ac voltage between the earth ground and the neutral ter- minal, as shown in Figure 31 on page 51. Ideally, the voltage should be 0 Vac. Find a different ground if the voltage exceeds 4 Vac. A higher voltage may result in: · Danger to people touching the enclosure · Erratic communications (Because the Comm5 shield connection, typically attached to the earth ground, becomes ineffective as a noise drain.) · Erratic equipment operation (Because noise may affect voltage levels at the inputs--the controller interprets input noise as changes in temperature, humidity, pressure, and so on.) 4. Replace the cover plate. 50 CNT-SVN01C-EN Figure 31. Checking the earth ground EMI/RFI considerations Sectioning the shield on the Comm5 link In areas with high RFI, you can section the Comm5 link shield between Comm5 devices to reduce interference in the link. To section the Comm5 link shield: 1. At the first Comm5 controller on the link, ground the shield to an earth ground. 2. Where the link enters the Tracer MP581, cut back and tape the shield. 3. Where the link leaves the Tracer MP581, ground the shield to an earth ground. The earth ground can be either a common terminal for any of the universal inputs or the lower-left mounting hole of the circuit board (shown in Figure 32). Figure 32. Grounding Comm5 wire Grounding locations for Comm5 wire CNT-SVN01C-EN 51 Chapter 7 Wiring Comm5 links 52 CNT-SVN01C-EN Chapter 8 Installing the circuit board The main circuit board is not installed in the Tracer MP581 enclosure when it ships. You can store the circuit board in the office while the enclosure is mounted and wired. After wiring has been completed, connect the circuit board to the termination board. To install the circuit board: 1. Open the enclosure door. 2. Verify that the 24 Vac power cable is not connected to the termination board (see Figure 35 on page 55). 3. Hold the top plastic frame, which holds the circuit board, at a 90° angle to the bottom frame as shown in Figure 33. Figure 33. Connecting the cables CNT-SVN01C-EN 53 Chapter 8 Installing the circuit board 4. Connect the 60-pin cable to the 60-pin slot, then connect the 20-pin cable to the 20-pin slot (see Figure 33 on page 53). The connectors fit only one way. If you have difficulty connecting them, make sure that the plastic grooves line up with the slots. 5. Align the snaps on the top frame with the mounting locks on the bottom frame, as shown in Figure 34, then push the two frames together. You will hear a click when the frames connect. Figure 34. Connecting the frames 6. For controllers with an operator display, connect the operator-display cable to the circuit board (see Figure 35 on page 55). 7. Locate the 24 Vac power connector on the termination board (see Figure 35). Remove the mating plug with screw terminals. 8. Attach the 24 Vac power-supply cable to the screw terminals on the mating plug. 9. Connect the mating plug to the 24 Vac power connector on the termination board. The green status LED should light up. 10. Check status LEDs according to Chapter 14, "Verifying operation and communication." 54 CNT-SVN01C-EN Installing the circuit board Figure 35. Cable termination and Status LED locations 24 Vac power connector LEDs Operator-display connector CNT-SVN01C-EN 55 Chapter 8 Installing the circuit board 56 CNT-SVN01C-EN Chapter 9 Installing the door This chapter shows how to install and remove the enclosure door. Installing the door To install the enclosure door: 1. Unpack the door and check for missing or damaged parts. Check to make sure that the magnetic latches and touch screen (if ordered) are installed. Check for any cracks in the plastic. 2. Hold the door at a 90° angle from the enclosure as shown in Figure 36. Figure 36. Aligning the enclosure door Operator-display connectors CNT-SVN01C-EN 57 Chapter 9 Installing the door 3. Align the hinge pegs on the door with the hinge holes on the enclosure. 4. Gently lower the door until it rests securely in the hinge holes. 5. Verify that the door swings freely on the hinges and that the magnetic latches hold the door securely when it is closed. 6. For doors with an operator display, connect the operator-display cable to the operator-display connectors (see Figure 36 on page 57). Removing the door Remove the door to simplify wiring or when upgrading the controller with a door-mounted operator display. To remove the enclosure door: 1. Open the door to a 90° angle from the enclosure. 2. For doors with an operator display, disconnect the operator-display cable from operator display. 3. Lift the door to pull the hinges from the hinge holes. 58 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 10 Installing the stand-alone operator display With the attached cable, the stand-alone operator display can be mounted up to 10 ft (3 m) from the Tracer MP581 controller. You can extend this distance up to 150 ft (46 m) using four-conductor wire and the included pig-tail connectors. See the installation sheet (3270 3338), which ships with the operator display, for instructions. The dimensions of the stand-alone operator display are shown in Figure 37. Figure 37. Stand-alone operator display dimensions Top view 10.25 in (260 mm) 2.25 in (58 mm) 8.75 in. (222 mm) Front view Bottom view Side view 59 Chapter 10 Installing the stand-alone operator display CAUTION Equipment damage! To clean the operator display, use a cloth dampened with commercial liquid glass cleaner. Spraying water or cleansers directly on the screen may result in equipment damage. Note: You do not need to power down the Tracer MP581 when connecting the operator display. To install the stand-alone operator display: 1. Unsnap the gray plastic backing from the operator display. 2. Carefully disconnect the operator-display cable from the connector inside the operator display. 3. Use the plastic backing as a template to mark the position of the four mounting holes on the mounting surface (see Figure 38). Figure 38. Operator-display mounting holes Mounting hole (four locations) 4. Set the plastic backing aside and drill holes for #8 (4 mm) screws or #8 wall anchors. 5. Secure the plastic backing to the wall with #8 (4 mm) mounting screws (not supplied). 6. Connect the operator-display cable to the operator display, then snap the operator display to the plastic backing. The connector fits only one way. If you have difficulty connecting it, rotate the cable 180° and try again. 7. Run the operator-display cable to the Tracer MP581, affixing it to the wall with wiring staples or wire mold. 8. Feed the cable into the Tracer MP581 enclosure. 60 CNT-SVN01C-EN Installing the stand-alone operator display 9. Attach the operator-display cable to the operator-display connector on the circuit board (see Figure 39). The operator display receives power from the Tracer MP581 and turns on automatically when it is connected to the controller. Figure 39. Operator-display connector on the Tracer MP581 Operator-display connector CNT-SVN01C-EN 61 Chapter 10 Installing the stand-alone operator display 62 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 11 Connecting the portable operator display The portable operator display is used for temporary connections to Tracer MP581 controllers. You do not need to power down the Tracer MP581 when connecting the operator display. The portable operator display includes a 10 ft (3 m) cable with connector that is stored in the storage compartment of the carrying bag. The cable cannot be disconnected from the operator display. CAUTION Equipment damage! To clean the operator display, use a cloth dampened with commercial liquid glass cleaner. Spraying water or cleansers directly on the screen may result in equipment damage. IMPORTANT You cannot use the portable operator display for time clock scheduling. To provide scheduling, you must use a permanently-connected doormounted operator display, stand-alone operator display, or Tracer Summit system. Using the carrying case Always keep the operator display in its padded carrying bag. Close the protective display cover when the operator display is not in use. Feed the operator-display cable into the main compartment of the carrying case, then through the hole in the back of the carrying case into the storage compartment. Connecting the operator display To connect the portable operator display: 1. Open the Tracer MP581 enclosure door. 2. Attach the operator-display cable to the operator-display connector on the circuit board (see Figure 39 on page 61). The operator display receives power from the Tracer MP581 and turns on automatically when it is connected to the controller. 63 Chapter 11 Connecting the portable operator display 64 CNT-SVN01C-EN Chapter 12 Setting up the operator display This chapter shows how to calibrate the operator-display touch screen and how to adjust the brightness and contrast. To set up the operator display screens and security, see the Tracer MP580/581 Programmable Controller Programming guide (CNT-SVP01C-EN). CAUTION Equipment damage! To clean the operator display, use a cloth dampened with commercial liquid glass cleaner. Spraying water or cleansers directly on the screen may result in equipment damage. Calibrating the operator display To calibrate the operator display: 1. On the home screen, press the Setup button. The Setup menu appears. 2. Press the page down button to view the next screen. 3. Press the Calibrate Touch Screen button. A calibration screen appears. CAUTION Equipment damage! Do not allow the operator display to come in contact with sharp objects. 4. Touch the target using a small, pliable, blunt object, such as a pencil eraser. Hold until the beeping stops. A second calibration screen appears. 5. Again, touch the target with the object. Hold until the beeping stops. The Setup menu appears. 6. Press the Home button. The home screen appears. CNT-SVN01C-EN 65 Chapter 12 Setting up the operator display Setting up time and date To change the time for the operator display: 1. On the home screen, press the Setup button. The Setup menu appears. 2. Press the Change Time button to view the next screen. 3. Using the buttons, type the time using the format hh:mm, where hh is the hour and mm is the minute. Press either the AM or PM button, as appropriate. 4. If you make a mistake, press Clear and start again. To accept the changes, press OK. To change the date for the operator display: 1. On the home screen, press the Setup button. The Setup menu appears. 2. Press the Change Date button to view the next screen. 3. Press the forward and back arrows to move the cursor from day to month to year. Use the buttons to type the appropriate date. 4. If you make a mistake, press the Reset button. To accept the changes, press OK. Adjusting brightness and contrast To adjust the brightness and contrast of the operator display: 1. On the home screen, press the Setup button. The Setup menu appears. 2. Press the page down button to view the next screen. 3. Press the Adjust Brightness and Contrast button. The Brightness and Contrast screen appears. 4. To increase the brightness, press the buttons along the top row, in sequence, from left to right. To decrease the brightness, press the buttons from right to left. 5. To increase the contrast, press the buttons along the bottom row, in sequence, from left to right. To decrease the contrast, press the buttons from right to left. 6. Press the Home button. The home screen appears. Note: Contrast adjustment is not available on all computer display models. 66 CNT-SVN01C-EN CNT-SVN01C-EN Chapter 13 Installing EX2 expansion modules The EX2 is a field-installed expansion module for the Tracer MP581 programmable controller. Up to four expansion modules can be connected to a Tracer MP581. Each EX2 adds the following inputs and outputs to a Tracer MP581: · Six universal inputs · Four binary outputs · Four analog outputs The EX2 is available in two different packages: frame-mount with plastic cover (4950 0499) or metal enclosure (4950 0500). (See Figure 40 and Figure 41 on page 68.) The frame-mount package includes: · EX2 circuit board fastened to a metal backplate · Removable plastic cover The enclosure package includes: · EX2 circuit board fastened to the back piece of the metal enclosure · Removable metal cover Operating environment Make sure that the operating environment conforms to the specifications listed in Table 9. Dimensions and clearances are illustrated in Figure 40 and Figure 41 on page 68. Table 9. Operating environment specifications Temperature From 40°F to 158°F (40°C to 70°C) Humidity 595%, non-condensing Power 1930 Vac (24 Vac nominal) 50/60 Hz 10 VA main board and 12 VA max per binary output Mounting Weight (frame-mount) Mounting surface must be able to support 2 lb (1 kg) Mounting Weight (metal enclosure) Mounting surface must be able to support 8 lb (4 kg) Altitude 6,500 ft (2,000 m) Installation Category 3 Pollution Degree 2 67 Chapter 13 Installing EX2 expansion modules Figure 40. Dimensions and clearances for frame-mount EX2 1 in. (25 mm) 4 in. (102 mm) 5.625 in. (143 mm) 4 in. (102 mm) 6.31 in. (160 mm) 4 in. (102 mm) 6.875 in. (175 mm) 5.375 in. (137 mm) Clearances Dimensions 1 in. (25 mm) Figure 41. Dimensions and clearances for metal-enclosure EX2 1 in. (25 mm) 1.875 in. (48 mm) 9 in. (229 mm) 2 in. (51 mm) 7 in. (178 mm) 2 in. (51 mm) 2 in. (51 mm) 6.5 in. (165 mm) 0.28 in. (7 mm) 9 in. (229 mm) 24 in. (610 mm) 10.37 in. (263 mm) width with cover 1 in. (25 mm) Clearances Dimensions 1 in. (25 mm) 2.25 in. (58 mm) 10.25 in. (260 mm) width without cover 68 CNT-SVN01C-EN Storage environment Storage environment The storage environment must meet the following requirements: · Temperature: From 40°F to 185°F (40°C to 85°C) · Relative humidity: 595%, non-condensing Mounting location Trane recommends locating the EX2 module: · In an environment protected from the elements · Where public access is restricted to minimize the possibility of tam- pering or vandalism · Near the controlled equipment to reduce wiring costs · Where it is easily accessible for service personnel Attaching the terminal strips For both the frame-mount and metal-enclosure modules, attach the terminal strips to the circuit board. If you need to replace the circuit board, you can transfer the terminal strips to the new board without rewiring. To attach the terminal strips: 1. Make sure that the enclosed plastic bag contains three terminal strips. 2. Align the plastic guides on the terminal strips with the slots in the receptors, then push the terminal strips into place. Figure 42. Terminal strip locations Universal inputs terminal strip Binary outputs terminal strip Analog outputs terminal strip CNT-SVN01C-EN 69 Chapter 13 Installing EX2 expansion modules Mounting the frame-mount module CAUTION Equipment damage! Mount the EX2 module with the cover on to avoid damaging the circuit board during installation. To mount the frame-mount module: 1. Using the module as a template, mark the location of the two mount- ing holes on the mounting surface (Figure 43). 2. Set the module aside and drill holes for the screws at the marked locations. 3. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 4. Insert wall anchors if needed. 5. Secure the module to the mounting surface with #10 (5 mm) screws (not included). Attach the frame-mount module securely so that it can withstand the vibrations of associated heating, ventilation, and air-conditioning (HVAC) equipment. Figure 43. Mounting the frame-mount EX2 70 CNT-SVN01C-EN Mounting the metal-enclosure module Mounting the metal-enclosure module To mount the enclosure: 1. Unscrew the two screws on the front of the enclosure and remove the cover. 2. Using the enclosure as a template, mark the location of the four mounting holes on the mounting surface (Figure 44). 3. Set the enclosure aside and drill holes for the screws at the marked locations. 4. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 5. Insert wall anchors if needed. 6. Secure the enclosure to the mounting surface with #10 (5 mm) screws (not included). Figure 44. Mounting the metal-enclosure EX2 CNT-SVN01C-EN 71 Chapter 13 Installing EX2 expansion modules AC-power wiring Use 16 AWG copper wire for ac-power wiring. All wiring must comply with National Electrical Code and local codes. Use a UL-listed Class 2 power transformer supplying a nominal 24 Vac (1930 Vac). The transformer must be sized to provide adequate power to the EX2 module (10 VA) and outputs (a maximum of 12 VA per binary output). Please read the warnings and cautions before proceeding. WARNING Hazardous voltage! Before making line voltage electrical connections, lock open the supplypower disconnect switch. Failure to do so could result in death or serious injury. WARNING Hazardous voltage! Make sure that the 24 Vac transformer is properly grounded. Failure to do so could result in death or serious injury. CAUTION Equipment damage! Complete input/output wiring before applying power to the EX2 module. Failure to do so may cause damage to the module or power transformer due to inadvertent connections to power circuits. CAUTION Equipment damage! To prevent module damage, do not share 24 Vac between modules. 72 CNT-SVN01C-EN AC-power wiring Wiring AC-power to the frame-mount module Please read the preceding warnings and cautions. To connect ac-power to the frame-mount module: 1. Connect the ground wire from the 24 Vac transformer (not included) to the GND terminal shown in Figure 45. 2. Connect the power wire to the 24V terminal. Figure 45. Power and ground terminals 24 Vac Transformer Earth ground Wiring AC-power to the metal-enclosure module Please read the preceding warnings and cautions. To connect ac-power wiring to the enclosure: 1. Remove the cover of the enclosure. 2. Remove the knockout for the 0.5 in. (13 mm) conduit from the enclo- sure and attach the conduit. 3. Feed the power wire into the enclosure. 4. When mounting on dry wall or other non-conductive surface, connect an earth ground to the earth-ground screw on the enclosure (Figure 46). 5. Connect the ground wire from the 24 Vac transformer (not included) to the GND terminal shown in Figure 46. 6. Connect the power wire to the 24V terminal. 7. Replace the cover of the enclosure. Figure 46. Power and ground terminals Earth-ground screw CNT-SVN01C-EN 73 Chapter 13 Installing EX2 expansion modules I/O bus wiring The EX2 communicates with the Tracer MP581 and up to three other EX2 modules on an IEEE-485 link. This link must be a daisy chain. Typically, the Tracer MP581 is at one end of the daisy chain, but any device can be at the ends of the link (Figure 47 and Figure 48 on page 75). Wiring for the I/O bus must meet the following requirements: · All wiring must be in accordance with the National Electrical Code and local codes. · Use level 4 unshielded wire · Consistent polarity (the I/O bus is polarity sensitive). · Total I/O wiring length cannot exceed 1000 ft (300 m). · Do not use any terminating resistors on the I/O bus wiring. Figure 47. I/O bus wiring example 1 Tracer MP581 EX2 EX2 EX2 EX2 Up to 1000 ft (300 m) 74 CNT-SVN01C-EN Figure 48. I/O bus wiring example 2 Setting the I/O bus addresses Setting the I/O bus addresses Each EX2 on the link with the Tracer MP581 must have a unique address. Configure the address using the DIP switches on the EX2 circuit board (Figure 49, page 76). The address must match the expansion module number as specified on the Unit tab for the MP580/581 in Rover. Table 10 on page 76 shows the DIP switch settings for expansion modules 1 through 4. CNT-SVN01C-EN 75 Chapter 13 Installing EX2 expansion modules Figure 49. DIP switch on board . Table 10. EX2 DIP switch settings EX2 module D1 D2 1 Off Off 2 Off On 3 On Off 4 On On Note: Cyle power to the EX2 (dipswitches can only be read during power up). Input/output terminal wiring All input/output terminal wiring for the EX2 module must meet the following requirements: · All wiring must be in accordance with the National Electrical Code and local codes. · Use only 1822 AWG, stranded, tinned-copper, shielded, twisted-pair wire. · Binary output wiring must not exceed 1,000 ft (300 m). · Binary input and 420 mA input wiring must not exceed 1,000 ft (300 m). · Thermistor input, RTD input, and 010 Vdc input wiring must not exceed 300 ft (100 m). · Analog and 24 Vdc output wiring distances depend on the specifica- tions of the receiving unit. Use shielding for analog and 24 Vdc outputs. · Do not run input/output wires in the same wire bundle with ac-power wires. The EX2 module has four binary outputs, four analog outputs, and six universal inputs. 76 CNT-SVN01C-EN CNT-SVN01C-EN Analog output and universal input setup Universal inputs Each of the six universal inputs may be configured as: · Binary · Thermistor · 020 mA · 010 Vdc · Resistance temperature detectors (RTDs) (only inputs 1 and 2) Table 11 shows the load the Tracer MP581 places on sensors. Table 11. Load placed on sensors Input type Load on sensor Vdc (linear) mA (linear) 21 k 221 Binary outputs The four binary outputs are form A (SPST) relay outputs. These relays are not dry contacts; they switch 24 Vac. A pilot relay is required for any application using dry contacts. Relays connected to the binary outputs on the EX2 cannot exceed 12 VA or 0.5 A current draw at 24 Vac. Analog outputs Each of the four analog outputs may be configured as either of the following: · 010 Vdc · 020 mA Analog output and universal input setup Configure each analog output and universal input using a LonTalk service tool, such as Trane's Rover service tool. The service tool requires the Tracer MP581 software plug-in to configure an EX2. EX2 modules receive their configuration information from the Tracer MP581 controller they communicate with. You can do online configuration with the Rover Comm5 service tool, or you can do offline configuration with Rover Configuration Builder. In either case, the EX2 modules will not receive their configuration until they are communicating with a configured Tracer MP581 controller. The inputs are factory configured to be thermistor. Analog outputs are configured for voltage. Figure 50 on page 78 shows how to wire some common sensor types and output devices. 77 Chapter 13 Installing EX2 expansion modules Figure 50. Typical input/output terminal wiring diagram for the EX2 expansion module I/O bus terminals (see "I/O bus wiring" on page 74) 78 CNT-SVN01C-EN Interpreting EX2 LEDs Interpreting EX2 LEDs The information in this section will help you interpret LED activity on the EX2 expansion module. Figure 51 shows the location of each LED. Figure 51. LED locations on the EX2 Binary output LEDs CNT-SVN01C-EN Status LED TX and RX communications LEDs Binary output LEDs The LEDs labeled LD2 through LD5 indicate the status of the four binary outputs. Table 12 describes binary output LED activity. Note: Each binary output LED reflects the status of the output relay on the circuit board. It may or may not reflect the status of the equipment the binary output is controlling. Field wiring determines whether the state of the binary output LED also applies to the status of the end device. Table 12 describes the LED states. Table 12. Binary output LEDs LED activity LED is on continuously LED is off continuously Explanation The relay output is energized. The relay output is de-energized or there is no power to the board. 79 Chapter 13 Installing EX2 expansion modules Status LED The Status LED on the EX2 module operates differently from the status LED on Comm5 devices. Table 13 describes EX2 Status LED activity. Table 13. Status LED LED activity Explanation LED is on continuously LED blinks twice LED blinks once LED is off continuously Power is on and the unit is operating normally. The EX2 has not received its configuration from the Tracer MP580/581. Use the Rover service tool to make sure that the Tracer MP580/581 is correctly configured for use with the EX2 module. Check the I/O bus wiring. The EX2 is not communicating on the I/O bus. Check the communications LEDs described in Table 14 for more information. Either the power is off or the controller has malfunctioned. Communications LEDs The LEDs labeled TX and RX indicate the communication status of the EX2 module. Table 14 describes the LED activity. Table 14. Communications LEDs LED activity Explanation Both LEDs blink regularly Both LEDs are off continuously RX LED blinks, TX LED is off RX LED is on continuously, TX LED is off The EX2 is communicating with the Tracer MP580/581 on the I/O bus. (If the LEDs blink normally but the EX2 is not working properly, make sure that I/O bus addresses are not duplicated.) The EX2 is not communicating on the I/O bus. Either the I/O bus wiring is faulty or the Tracer MP580/581 has not been configured to use the EX2 module. Use the Rover service tool to configure the Tracer MP580/581 for use with the EX2 module. The EX2 is receiving communications from the Tracer MP581 (either for itself or another EX2) but cannot send communications. Either the module is not configured in the Tracer MP580/ 581 or its I/O bus address is incorrect. Use the Rover service tool to configure the Tracer MP580/581 for use with the EX2 module. Make sure the DIP switches are set for the correct I/O bus address ("Setting the I/O bus addresses" on page 75). Polarity is reversed on the I/O bus wiring. Swap the wires at the plus (+) and minus () I/O bus screw terminals on the EX2 module. 80 CNT-SVN01C-EN Chapter 14 Verifying operation and communication This chapter describes the location and function of the Service Pin button and the light-emitting diodes (LEDs) on the Tracer MP581 controller. Service Pin button The Service Pin button is located on the main circuit board as shown in Figure 52. Use the Service Pin button to: · Identify a device · Add a device to the active group · Verify PCMCIA communications · Make the green Status LED "wink" to verify that the controller is communicating on the link Refer to the Rover Operation and Programming guide, EMTX-SVX01D-EN, for information on how to use the Service Pin button. Figure 52. Service Pin button and LED locations BO1BO6 LEDs (green) Service LED (red) Service Pin button Comm LED (yellow) Status LED (green) CNT-SVN01C-EN 81 Chapter 14 Verifying operation and communication Interpreting LEDs The information in this section will help you interpret LED activity. The location of each LED is shown in Figure 52 on page 81. Binary output LEDs The BO1BO6 LEDs indicate the status of the six binary outputs. Table 15 describes binary output LED activity. Note: Each binary output LED reflects the status of the output relay on the circuit board. It may or may not reflect the status of the equipment the binary output is controlling. Field wiring determines whether the state of the binary output LED also applies to the status of the end device. Table 15 describes the LED states. Table 15. Binary output LEDs LED activity LED is on continuously LED is off continuously Explanation The relay output is energized. The relay output is de-energized or there is no power to the board. Service LED The red Service LED indicates whether the controller is operating normally. Table 16 describes Service LED activity. Table 16. Red Service LED LED activity Explanation LED is off continuously when power is applied to the controller The controller is operating normally. LED is on continuously when power is applied to the controller The controller is not working properly, or someone is pressing the Service Pin button. LED flashes once every second The controller is not executing the application software because the network connections and addressing have been removed.1 1 Restore the controller to normal operation using the Rover service tool. Refer to EMTX-SVX01D-EN for more information. 82 CNT-SVN01C-EN LEDs on the EX2 expansion module Status LED The green Status LED indicates whether the controller has power applied to it. Table 17 describes Status LED activity. Table 17. Green Status LED LED activity Explanation LED is on continuously Power is on (normal operation). LED blinks (¼ second on, The auto-wink option is activated, and the ¼ second off for 10 seconds) controller is communicating.1 LED blinks rapidly Flash download is being received. LED is off continuously Either the power is off or the controller has malfunctioned. 1 By sending a request from the Rover service tool, you can request the controller's green LED to blink ("wink"), a notification that the controller received the signal and is communicating. Comm LED The yellow Comm LED indicates the communication status of the Tracer MP581 controller. Table 18 describes Comm LED activity. Table 18. Yellow Comm LED LED activity Explanation LED is off continuously LED blinks LED is on continuously The controller is not detecting any communication (normal for stand-alone applications). The controller detects communication (normal for communicating applications, including data sharing). An abnormal condition that may occur during discovery. The LED may flash fast enough to look as if it is on continuously. If this LED activity occurs at any other time, the site may have excessive radio frequency interference (RFI). LEDs on the EX2 expansion module For an explanation of the LEDs on the EX2 expansion module, refer to "Interpreting EX2 LEDs" on page 79. CNT-SVN01C-EN 83 Chapter 14 Verifying operation and communication 84 CNT-SVN01C-EN Chapter 15 Troubleshooting This chapter outlines general troubleshooting steps that you should perform if there is a problem with the operation of the equipment controlled by the Tracer MP581 controller. If you encounter operational problems with the Tracer MP581 controller, you must first perform initial troubleshooting steps; see "Initial troubleshooting" on page 86. After you have performed the initial troubleshooting steps, refer to specific sections in this chapter to further diagnose the following operational problems: · If a binary output is not turning on the equipment wired to it, see "Binary output troubleshooting" on page 87. · If an analog output is not working correctly, see "Analog output trou- bleshooting" on page 88. · If you see a universal input value that appears incorrect, see "Univer- sal input troubleshooting" on page 89. CNT-SVN01C-EN 85 Chapter 15 Troubleshooting Initial troubleshooting Always perform the initial troubleshooting steps listed in Table 19 before moving on to the specific area of trouble. Perform the steps in the order they are listed. Table 19. Initial troubleshooting steps Step number Action Probable cause Step 1 Step 2 Step 3 Step 4 Look at the red Service LED. If it is flashing once per second, the controller is not executing the application software because the network connections and addressing have been removed. For a complete explanation of the behavior of this LED, see "Interpreting LEDs" on page 82. Use the Rover service tool to restore normal operation. See the Rover Operation and Programming guide, EMTX-SVX01D-EN, for more information. Look at the green Status LED. It should be on continuously during normal operation. A blinking Status LED indicates abnormal behavior for the Tracer MP581. For a complete explanation of the behavior of this LED, see "Interpreting LEDs" on page 82. Set the multi-meter to measure ac voltage. Measure the voltage across the 24 Vac power terminals on the Tracer MP581 termination board (with ac power connected). The location of the 24 Vac power terminals is shown in Figure 11 on page 20. If you see approximately 24 V (2030 V) on those terminals, the board is receiving adequate input power. Disconnect the ac wires from the input power terminals. Set the multi-meter to measure ac voltage. Measure the voltage across the ac wires. If you see approximately 0 V, the board is not receiving the power it needs to run. Tracer MP581 is not configured Tracer MP581 circuit board problem Tracer MP581 circuit board problem or programming error Input power problem 86 CNT-SVN01C-EN Binary output troubleshooting Binary output troubleshooting If a binary output is not turning on the equipment wired to it, follow the troubleshooting steps in Table 20. Perform the steps in the order they are listed. The troubleshooting steps assume the equipment connected to the binary output is off when you think it should be on. The steps are nearly the same if the equipment is on when you think it should be off. Table 20. Binary output troubleshooting of external wiring Step number Action Probable cause Step 1 Step 2 Step 3 Step 4 Perform the initial troubleshooting steps described in Table 19 on page 86 and verify general board operation is okay. Inspect the wiring. Is there a good connection between the wire and the terminal blocks? Look for shorts or opens. Check wire splices. Set the multi-meter to measure ac voltage. Measure the voltage across the binary output terminals on the Tracer MP581. If you see approximately 24 V, the problem lies beyond the Tracer MP581. Is the wiring to the equipment good? Is there a pilot relay and is it functioning correctly? Is a Hand-Off-Auto (HOA) switch overriding the equipment? If you see approximately 0 V, proceed to the next step. Remove the wires from the binary output terminals and measure the voltage again. If you see 24 V, there is a wiring or equipment problem external to the Tracer MP581. If you still see approximately 0 V, the Tracer MP581 is commanding the output to be off and you need to investigate the Tracer MP581 further. See Table 21. General board problem Wiring problem Wiring problem Wiring problem If the binary output is still not turning on the equipment wired to it, follow the additional troubleshooting steps in Table 21. These steps will help you assess the configuration and operation of the binary output. Table 21. Binary output troubleshooting of configuration and operation Step number Action Probable cause Step 1 Step 2 Step 3 Connect the Rover service tool to the Comm5 communication link, start the Rover service tool, and select the Tracer MP581 that you are troubleshooting from the Active Group Tree. The device plug-in for the selected Tracer MP581 appears with the Active Device view screen displayed in the workspace. See the Rover Operation and Programming guide, EMTX-SVX01D-EN, for more information. If the binary output is on an EX2 expansion module, verify that communications are up between the Tracer MP581 and the expansion module. See the Unit tab in the Status display for the Tracer MP581 in Rover. Check the operating status to determine what is controlling the binary outputs. If the operator display or Rover is controlling the binary output, release the override. If a program is controlling the binary output, use the debug mode to investigate the program. -- Communication failure with expan- sion board Override or programming error CNT-SVN01C-EN 87 Chapter 15 Troubleshooting Analog output troubleshooting If an analog output is not controlling the equipment wired to it, follow the troubleshooting steps in Table 22. Perform the steps in the order they are listed. Table 22. Analog output troubleshooting of external wiring Step number Action Probable cause Step 1 Step 2 Step 3 Perform the initial troubleshooting steps described in Table 19 on page 86 and verify general board operation is okay. Inspect the wiring. Is there a good connection between the wire and the terminal blocks? Look for shorts or opens. Pay particular attention to wire splices. For a 010 Vdc analog output, set the multi-meter to measure Vdc. Measure across the analog output terminals. The valid range is from 0 Vdc to 10 Vdc. Use either the operator display or the Rover service tool to override the analog output to a known value. For a 020 mA analog output, set the multi-meter to measure mA. This may require that the meter connections be changed. Measure across the analog output terminals. This effectively shunts all current through the multimeter. If controlling an actuator, it should move to the 0 mA position. The valid range is from 0 mA to 20 mA. Use either the operator display or the Rover service tool to override the analog output to a known value. For either type of output, set the multimeter to read Vac. Measure across the analog output. The multimeter should show less than 0.1 Vac. General board problem Wiring problem Wiring problem If the analog output is still not turning on the equipment wired to it, follow the additional troubleshooting steps in Table 23. These steps will help you assess the configuration and operation of the binary output. Table 23. Analog output troubleshooting of configuration and operation Step number Action Probable cause Step 1 Step 2 Step 3 Connect the Rover service tool to the Comm5 communication link, start the Rover service tool, and select the Tracer MP581 that you are troubleshooting from the Active Group Tree. The device plug-in for the selected Tracer MP581 appears with the Active Device view displayed in the workspace. See the Rover Operation and Programming guide, EMTX-SVX01D-EN, for more information. If the analog output is on an EX2 expansion module, verify that communications are up between the Tracer MP581 and the expansion module. See the Unit tab in the Status display for the Tracer MP581 in Rover. Check the operating status to determine what is controlling the analog outputs. If the operator display or Rover is controlling the analog output, release the override. If a program is controlling the analog output, use the debug mode to investigate the program. -- Communication failure with expan- sion board Override or programming error 88 CNT-SVN01C-EN Universal input troubleshooting Universal input troubleshooting If you see a universal input value that appears incorrect, follow the troubleshooting steps in the following tables: · Table 24 describes steps you can take using the Rover service tool to troubleshoot inputs. You do not have to be at the controller to use the device plug-in to view the inputs; however, the Rover service tool must be communicating on the Comm5 link. · Table 25 describes troubleshooting inputs with a multi-meter at the controller. Table 24. Troubleshooting universal inputs using the device plug-in Step number Action Probable cause Step 1 Step 2 Step 3 Step 3 Connect the Rover service tool to the Comm5 communication link, start the Rover service tool, and select the Tracer MP581 that you are troubleshooting from the Active Group Tree. The device plug-in for the selected Tracer MP581 appears with the Active Device view displayed in the workspace. See the Rover Operation and Programming guide, EMTX-SVX01D-EN, for more information. If the universal input is on an EX2 expansion module, verify that communications are up between the Tracer MP581 and the expansion module. See the Unit tab in the Status display for the Tracer MP581 in Rover. On the Inputs tab, check the value of each universal input. The raw value is displayed for each input in the adjacent column. If the input does not show the value you expect, proceed to the next step to verify the input configuration. Click the Configuration button, then click the Inputs tab. For the universal input you are troubleshooting, view the Input Type. If it is not correct, select the correct type from the drop-down list and type values in the other configuration fields. Click the Download button, then click the Save button. If the configuration is correct for the input you are troubleshooting, proceed to Table 25. -- Communication failure with expan- sion board -- Input configuration problem Table 25. Troubleshooting universal inputs using a multi-meter at the controller Step number Action Probable cause Step 1 Step 2 Step 3 Perform the initial troubleshooting steps described in Table 19 on page 86 and verify that general board operation is okay. Inspect the wiring. Is there a good connection between the wire and the terminal blocks? Look for shorts or opens. Pay particular attention to wire splices. What type of universal input are you investigating? · For thermistor, proceed to Table 26 on page 90. · For binary, proceed to Table 27 on page 90. · For 020 mA, proceed to Table 28 on page 91. · For 010 Vdc, proceed to Table 29 on page 91. General board problem Wiring problem -- CNT-SVN01C-EN 89 Chapter 15 Troubleshooting Table 26. Universal input troubleshooting with a thermistor input Step number Action Step 1 Step 2 Set the multi-meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. Verify the voltage you measured falls into the gray area of the curve in Figure 53 for the current temperature. If you do not see the voltage reading appropriate for the current temperature, you have a sensor wiring problem. If you do see the correct voltage for the current temperature, proceed to the next step. Disconnect the sensor wires from the input terminals. Set the multi-meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. The voltage should be 4.755.25 Vdc (see Table 30 on page 92). If you do not see a reading in that range, the Tracer MP581 has a circuit board problem. Figure 53. Voltage measured across terminals vs. temperature Probable cause Sensor wiring problem Circuit board problem Voltage (Vdc) Voltage (Vdc) Temperature (oF) Temperature (oC) Figure Note: The correct region is shown in gray. A range of measurements is shown due to the variability of reference voltages and thermistors. Table 27. Universal input troubleshooting with a binary input Step number Action Probable cause Step 1 Disconnect the sensor wires from the input terminals. Set the meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. The voltage should be 16.0018.00 Vdc (see Table 30 on page 92). If you do not see a reading in that range, the Tracer MP581 has a circuit board problem. Circuit board problem 90 CNT-SVN01C-EN Universal input troubleshooting Table 28. Universal input troubleshooting with a 020 mA input Step number Action Step 1 Step 2 Set the multi-meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. Verify the voltage you measured falls on the curve shown in Figure 54 for the input current. If you do not see the voltage appropriate for the mA reading, you have a sensor wiring problem. If you do see the correct voltage for the mA reading, proceed to the next step. Disconnect the sensor wires from the input terminals. Set the multi-meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. The voltage should be 0.100.13 Vdc (see Table 30 on page 92). If you do not see a reading in that range, the Tracer MP581 has a circuit board problem. Figure 54. Voltage measured across terminals vs. input current Probable cause Sensor wiring problem Circuit board problem Measured voltage (Vdc) Current (mA) Table 29. Universal input troubleshooting with a 010 Vdc input Step number Action Step 1 Disconnect the sensor wires from the input terminals. Set the multi-meter to read dc voltage. Measure the voltage across the terminals for the input you are troubleshooting. The voltage should be 3.13.8 Vdc (see Table 30 on page 92). If you do not see a reading in that range, the Tracer MP581 has a circuit board problem. Probable cause Circuit board problem CNT-SVN01C-EN 91 Chapter 15 Troubleshooting Table 30. Voltage measurements at universal inputs (no sensor connected) Input type Expected value Acceptable range Thermistor Binary Current Voltage 5.00 Vdc 17.00 Vdc 0.116 Vdc 3.43 Vdc 4.75 to 5.25 Vdc 16.00 to 18.00 Vdc 0.100 to 0.130 Vdc 3.10 to 3.80 Vdc 92 CNT-SVN01C-EN Chapter 16 Other literature The below literature is available in electronic format through e-Library, a community page located on the My Standard intranet site. Unless otherwise stated, the literature is also available in hard copy format, which can be ordered through your local Trane office. · PID Control in Tracer Controllers Applications Guide, CNT-APG002-EN. Describes how to set up proportional, integral, and derivative control loops and provides examples. · Rover Operation and Programming guide, EMTX-SVX01E-EN. Describes how to install and use the Rover service software. Rover is required to configure a Tracer MP581 and to create and edit Tracer graphical programs. This document is available in electronic format only. · Tracer Graphical Programming Applications Guide, CNT-APG001-EN. A tutorial for learning Tracer graphical programming. · Tracer MP580/581 Programmable Controller Programming guide, CNT-SVP01C-EN. Describes how to assemble graphical programs, how to configure the controller, and how to create bindings with other Comm5 devices. · Tracer MP580/581 Programmable Controllers product catalog, CNT-PRC002-EN. Describes the features and specifications of the controller. CNT-SVN01C-EN 93 Chapter 16 Other literature 94 CNT-SVN01C-EN CNT-SVN01C-EN Index Numerics 010 Vdc inputs check-out procedure, 30 troubleshooting, 91 wiring, 22 010 Vdc outputs check-out procedure, 33 troubleshooting, 88 wiring, 25 020 mA inputs check-out procedure, 31 troubleshooting, 91 wiring, 23 020 mA outputs check-out procedure, 34 troubleshooting, 88 wiring, 25 24 Vac power and Comm5 wiring, 40 and input/output wiring, 17 connector location, 20 for frame-mounted Tracer MP581, 7 grounding, 40 screw terminals, description, 19 screw-terminal location diagram, 20 total supply for inputs and outputs, 19 24 Vdc power screw terminals, description, 19 screw-terminal location diagram, 20 total supply for inputs and outputs, 19 A ac power, see high-voltage power additional components, 2 adjusting brightness and contrast for the operator display, 66 agency listing/compliance, 4 altitude specification, 1 analog inputs check-out procedures, 2731 troubleshooting, 8992 wiring, 2224 wiring guidelines, 17 wiring zone sensors, 24 See also universal inputs analog outputs check-out procedures, 3334 EX2 module, 3, 67, 77 overview, 17 screw-terminal location diagram, 20 troubleshooting, 88 wiring, 25 wiring guidelines, 17 applications, 1 B binary inputs check-out procedure, 31 troubleshooting, 8992 wiring, 21 wiring guidelines, 17 See also universal inputs binary outputs check-out procedure, 32 EX2 module, 3, 67, 77 inrush current, 26 LEDs, 82 overview, 17 powered outputs, 26 screw-terminal location diagram, 20 troubleshooting, 87 wiring, 26 wiring guidelines, 17 board, circuit, see circuit board books for the Tracer MP581, 93 brackets for wire ties, 18 C calibrating the operator display, 65 CE compliance, 4 check-out procedures, 2734, 37 010 Vdc inputs, 30 010 Vdc outputs, 33 020 mA inputs, 31 020 mA outputs, 34 analog inputs, 2731 analog outputs, 3334 binary inputs, 31 binary outputs, 32 linear resistance inputs, 30 pressure sensors, 37 resistance temperature detectors, 29 thermistor inputs, 27 circuit board installing, 5355 LED locations, 81 circuit requirements, 13 clearances 95 Index for enclosure, 10 for EX2 modules, 68 for frame-mounted Tracer MP581, 7 Comm5 and 24 Vac power wires, 40 and LonTalk, 39 and Tracer Summit BAS, 39 grounding to reduce EMI/RFI, 50 jack location, 20 LED, 83 LED location, 81 polarity sensitivity, 40, 48 screw-terminal location diagram, 20 termination resistors, 40, 42 wiring, 3949 wiring guidelines, 3940 zone sensor communication stubs, 46 compliance information, 4 components, additional, 2 conductor requirements, 13 conduit sizes, 11, 14 connector 24 Vac power, 20, 55 duct-static pressure, 20, 35 operator-display cable, 55, 57 stand-alone operator display, 60 current, inrush, 26 D DAC profile, 1 daisy chain configuration for networks, 40 dimensions diagram for enclosure, 11 diagram for frame-mount, 8 for EX2 modules, 68 for Tracer MP581 models, 1 DIP switches for EX2, 75 Discharge Air Controller (DAC) profile, 1 distance, maximum for input/output wires, 17, 76 door, installing, 5758 duct-static connector, 35, 37 knockout for high-voltage power, 14 knockout sizes and locations, 11 list of parts, 5 mounting, 12 NEMA specifications, 7, 9 removing the door, 58 routing wires, 18 EX2 expansion module, 6778 AC-power wiring, 7273 additional points, 3, 67 dimensions, 68 DIP switch settings, 75 I/O bus wiring, 74 mounting frame-mount module, 70 mounting metal-enclosure module, 71 operating environment, 67 storage environment, 69 execution frequency, 1 expansion module, see EX2 expansion module F frame-mounted Tracer MP581 24 Vac power, 7 clearances, 7 enclosure requirements, 7 installing, 78 list of parts, 5 model number, 13 frequency, execution, 1 G grounding the controller, 50 guidelines for Comm5 wiring, 3940 for high-voltage power wiring, 13 for input/output wiring, 17 for routing wires, 18 for selecting a mounting location, 9 guidelines for EX2 module, 76 guides for the Tracer MP581, 93 E electromagnetic interference, 48, 50 electronics board, see circuit board EMI, 48 enclosure clearances, 10 dimensions, 11 installing the door, 5758 H high-voltage power and input/output wiring, 17 circuit requirements, 13 knockout location and size, 14 screw-terminal locations, 15 wiring, 1415 wiring diagram, 15 humidity sensors, 23 humidity specification, 1, 9 I I/O bus for EX2, 74 indoor air-quality sensors, 22 input tubes for pressure sensors, 36 input/output wiring guidelines, 17 inputs, see analog inputs, binary inputs, universal inputs inrush current, 26 installation category, 1 installing circuit board, 5355 Comm5 links, 3949 enclosure, 12 enclosure door, 5758 EX2 frame-mount module, 70 EX2 metal-enclosure module, 71 frame-mounted Tracer MP581, 78 high-voltage power wire, 1415 portable operator display, 63 pressure sensors, 3536 stand-alone operator display, 59 61 termination board in separately purchased enclosure, 8 K knockouts for high-voltage power, 14 sizes and dimensions, 11 L LEDs binary outputs, 82 Comm (yellow), 83 EX2 module, 7980 locations, 81 Service (red), 82 Status (green), 83 length, maximum for input/output wires, 17, 76 linear current inputs, see 020 mA inputs linear resistance inputs, 30 list of parts, 5 literature for the Tracer MP581, 93 location for mounting, 9 LonMark Discharge Air Controller (DAC) profile, 1 Space Comfort Controller (SCC) profile, 1 96 CNT-SVN01C-EN Index LonTalk, 39 M machine bus, see I/O bus, 74 minimum clearances for enclosure, 10 for EX2 modules, 68 for frame-mounted Tracer MP581, 7 model numbers, 13 mounting enclosure, 12 EX2 frame-mount module, 70 EX2 metal-enclosure module, 71 frame-mounted Tracer MP581, 8 location requirements, 9 pressure sensors, 3536 multi-meter, expected readings, 27 34, 37, 8692 N National Electrical Code, 7, 13, 17, 40 National Electrical Manufacturers Association (NEMA) specifications, 7, 9 networks daisy chain configuration, 40 termination resistors, 40 wiring, 3949 O operating environment, 1, 9, 67 operator display adjusting brightness and contrast, 66 calibrating, 65 connector locations, 55, 57 installing the portable model, 63 installing the stand-alone model, 5961 ordering number EX2 module, 3 pressure sensor, 2 Tracer MP581, 13 outputs, see analog outputs, binary outputs P part number EX2 module, 3 pressure sensor, 2 Tracer MP581, 13 parts, list of, 5 pilot relays, 26 polarity sensitivity, 40, 48 pollution specification, 1 power 24Vac/24Vdc requirements, 19 for EX2 module, 7273 high-voltage requirements, 1, 9, 13 transformer, 2, 13 See also 24 Vac power, 24 Vdc power, high-voltage power powered outputs, 26 pressure sensors connector location, 20, 35 input tubes, 36 installing, 3536 overview, 2 technical description, 17 when to wire, 18 wiring, 22, 23 R radio frequency interference, 48, 50 reference material, 93 removing the door, 58 required tools, 5 requirements Comm5 wiring, 3940 conductors, 13 enclosure for frame-mounted Tracer MP581, 7 high-voltage power, 1, 9, 13 input/output wiring, 17 mounting, 9, 69 National Electrical Code, 7, 13, 17, 40 operating environment, 1, 9, 67 polarity, 40, 48 storage, 1, 69 weight, 1, 9, 67 resistance characteristics of sensors, 28 resistance temperature detectors check-out procedure, 29 wiring, 24 resistors for Comm5 links, 42 RFI, 48, 50 routing wires, 18 Rover service tool, 77, 81, 8688 S SCC profile, 1 scheduling, 63 screw terminals 24 Vac power, 19 24 Vdc power, 19 Comm5, 20 high-voltage power, 15 location diagram, 20 sensors installing pressure sensors, 3536 overview, 2 resistance characteristics, 28 wiring pressure sensors, 22, 23 wiring zone sensors, 24 Service LED, 82 Service Pin button, 81 Space Comfort Controller (SCC) profile, 1 specifications agency listing/compliance, 4 altitude, 1, 67 dimensions, 1, 68 enclosure for frame-mounted Tracer MP581, 7 high-voltage power requirements, 1, 9 humidity, 1, 9, 67 input/output wiring, 17 installation category, 1, 67 NEMA, 7, 9 operating environment, 1, 9 pollution, 1, 67 power transformer, 2 storage, 1, 69 temperature, 9, 67 weight, 1, 9, 67 status indicators for operation and communication, 7980, 8183 Status LED, 83 storage specifications, 1, 69 strip guide for input/output wires, 20 T temperature specifications operating environment, 1, 9, 67 storage, 1, 69 terminals, see screw terminals termination board connecting to circuit board, 53 installing in separately purchased enclosure, 8 termination resistors for Comm5 links, 40, 42 testing, see check-out procedures thermistor inputs check-out procedure, 27 troubleshooting, 90 wiring, 24 time clock, 63 tools, required, 5 Tracer Summit BAS and the Comm5 link, 39 installation literature, 39 transducer, see pressure sensors transformer, power, 2, 13 CNT-SVN01C-EN 97 Index troubleshooting, 8592 010 Vdc inputs, 91 020 mA inputs, 91 analog outputs, 88 binary outputs, 87 initial steps, 86 Service Pin button, 81 thermistor inputs, 90 universal inputs, 8992 tubes for pressure sensors, 36 U UL listing, 4 universal inputs check-out procedures, 2731 EX2 module, 3, 67, 77 screw-terminal location diagram, 20 troubleshooting, 8992 types, 17 wiring, 2124 wiring guidelines, 17 See also analog inputs, binary inputs strip guide, 20 variable resistance inputs, 24 wire-tie bracket locations, 18 zone sensors, 24 wiring diagrams 010 Vdc analog input, 22 020 mA analog inputs, 23 analog outputs, 25 binary input, 21 binary outputs, 26 Comm5 link, 48, 49 EX2 module, 78 high-voltage power, 15 screw-terminal location diagram, 20 variable resistance analog inputs, 24 Z zone sensors, 2, 24, 46 V Vac power, see 24 Vac power variable resistance inputs, wiring, 24 Vdc power, see 24 Vdc power voltage expected multi-meter readings, 2734, 37, 8692 utilization range, 13 W weight specifications, 1, 9 wire ties, locations for, 18 wiring 010 Vdc inputs, 22 020 mA inputs, 23 analog inputs, 2224 analog outputs, 25 binary inputs, 21 binary outputs, 26 Comm5 links, 3949 Comm5 wiring guidelines, 3940 EX2 inputs and outputs, 76 EX2 module I/O bus, 74 guidelines for input/output wiring, 17 high-voltage power, 1415 length of input/output wires, 17 pressure sensors, 22, 23 routing in enclosure, 18 98 CNT-SVN01C-EN Literature Order Number CNT-SVN01C-EN File Number PL-ES-CNT-SVN01C-EN-1105 Supersedes CNT-SVN01B-EN May 2003 Trane A business of American Standard Companies www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com Stocking Location Inland Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.Acrobat Distiller 7.0 (Windows)