GATEXPERT INDUSTRIAL DOOR OPERATOR WITH FREQUENCY CONVERSION
USER MANUAL
GK30BP/GK40BP /GK70BP/GK100BP
Website: www.gatexpert.com
E-mail: sales@gatexpert.com
Safety Instruction
- The industrial door operator should be installed and put into operation by qualified personnel. Otherwise, serious personal injury or property damage may occur.
- Installation and wiring must be in accordance with the construction standards and electrical standards, diameter ≥ 1.5mm²; power must have a reliable grounding, ground wire must be reliably connected to the place labeled ground tab, ground lead on the power line is prohibited to be removed; front end of incoming power line should be installed with electrical leakage protector which is in line with national standards.
- This industrial door operator is only allowed to be installed on well-balanced door which has balance spring, otherwise machine may be damaged due to overload.
- Door should be flexible and run without stagnation; The end of door lead rail must be installed with mechanical stop block and buffering booster to prevent the door from rolling out.
- Control unit should be installed on the wall or a post of 1.4 meters away from the ground where the operation of door can be observed to prevent children from inadvertently touching. Keep the remote control well, do not allow children to touch or play in case of any danger. Do not use the remote control when you didn't see the operation of door.
- Before repairing and moving the industrial door operator and its control unit, please cut off the power supply, and make sure that the door has been locked and there is no any risk of falling due to self-weight is null.
- Pedestrian and vehicle are prohibited to go through or stay when the door is running.
- Hand-pulled chain is prohibited to be pulled during the operation of the industrial door operator to prevent the motor from damaged.
- To ensure the safety of pedestrian and vehicle, it's recommended to install the infrared protection and airbag protection devices.
- Please check the safety protection devices and the door running condition from time to time to ensure the safety and stability of door operation.
Thank you for choosing this product!
Appreciate for your trust and support!
Please read this manual carefully before installation!
Please keep this manual properly even after installation!
Contents
1. TECHNICAL PARAMETER TABLE ................................................ 3
2. DIMENSION AND COMPONENT OF INDUSTRIAL DOOR OPERATOR ........................ 4
3. INSTALLATION GUIDE OF INDUSTRIAL DOOR OPERATOR ........................................ 6
4. INDUSTRIAL DOOR OPERATOR WIRING ..................................................................... 10
5. OPERATION INTERFACE ILLUSTRATION ................................................................... 13
6. OPEN AND CLOSED LIMIT SWITCH SETTING ........................................................ 14
7. PARAMETERS SETTING .......................................................................................... 18
8. EXTERNAL ACCESSORIES WIRING ......................................................................... 20
9. REMOTE CONTROL PASSWORD SETTING ............................................................ 23
10. USE OF HAND-PULLED CHAIN .............................................................................. 24
11. COMMON FAULTS AND COUNTERMEASURES ..................................................... 25
12. PACKING LIST ........................................................................................................ 27
Technical Parameter Table of Door Operator
| Model (Three Phase AC220V) | GK30BP | GK40BP | GK70BP | GK100BP | 
|---|---|---|---|---|
| Rated Power | 300W | 400W | 550W | 750W | 
| Torque | 30N.m | 40N.m | 70N.m | 100N.m | 
| No-load Continuous Running Time | 15min | |||
| Max. gate area | 15m² | 20m² | 30m² | 40m² | 
| Model (Three Phase AC380V) | GK60SBP | GK100SBP | GK150SBP | 
|---|---|---|---|
| Rated Power | 400W | 550W | 750W | 
| Torque | 60N.m | 100N.m | 150N.m | 
| Max. gate area | 25m² | 40m² | 50m² | 
| No-load Continuous Running Time | 15 min | ||
Other Parameters:
| Thermal Protection Temperature | 120°C | 
| Reduction Ratio | 1:58 | 
| No-load Rotation Speed | 24r/min | 
| Lubricating System | Oil-immersed | 
| Noise | ≤55dB | 
| Hand Release Device | Hand-pulled chain | 
| Encoder Type | Single Circle Absolute Encoder | 
| Maximum Travel Limit | Output shaft rotates 20 rounds | 
| Output Shaft Diameter | Φ25.4mm | 
| Environment Temperature | -20°C ~+50°C | 
| Working Duty | S2-15min | 
| Protection Class | IP54 | 
| Operator Dimension(mm) | 232x151x368 | 
| Operator Weight(kg) | 14 | 
Technical Parameter Table of Control Unit
| Model | BPK1075 | BPK3075 | 
|---|---|---|
| Power Supply | AC220V/50Hz | AC380V/50Hz | 
| Remote Control | Available | Available | 
| Applicable Model | GK30BP/40BP/70BP/100BP | GK60SBP/100SBP/150SBP | 
| External Three Button Switch Terminal | Available | Available | 
| External Single Button Switch Terminal | Available | Available | 
| Partial Opening Button Switch Terminal | Available | Available | 
| Interlock Terminal | Available | Available | 
| Infrared Photocell Terminal | Available | Available | 
| Airbag Terminal | Available | Available | 
| Loop Detector Terminal | Available | Available | 
| Small-door Terminal | Available | Available | 
| Multi-function Output Terminal | Available | Available | 
| DC24V Power Terminal | Available | Available | 
| Protection Class | IP54 | IP54 | 
Dimension and Component of Industrial Door Operator
Diagram showing the dimensions of the industrial door operator for models GK40BP/70BP/100BP/100SBP/150SBP. Key dimensions indicated include:
- Overall height: 218 mm
- Width: 274 mm
- Depth (front to back): 357 mm
- Output shaft diameter: Φ25.4mm
- Mounting bracket dimensions and positions are shown.
- The overall shape and key features of the operator are depicted.
Dimension and Component of Industrial Door Operator (GK30BP/60SBP)
Diagram showing the dimensions and components of the industrial door operator for models GK30BP/60SBP. Key dimensions indicated include:
- Overall height: 198 mm
- Width: 252 mm
- Depth (front to back): 335 mm
- Output shaft diameter: Φ25.4mm
- Control unit box dimensions: 128 mm depth, 25 mm height.
Component List:
- 1. Electronic limit switch part
- 2. Gearbox
- 3. Wiring Terminals
- 4. Plastic cover
- 5. Door operator
- 6. Hand-pulled chain
- 7. Release handle
Control Unit Dimension
Diagram showing the dimensions of the control unit. Key dimensions indicated include:
- Height: 330 mm
- Width: 220 mm
- Depth: 149 mm (with mounting bracket 116 mm)
- Front panel dimensions: 297.5 mm height, 195 mm width.
Installation Guide of Industrial Door Operator
This product is commonly used for industrial sectional doors equipped with balance springs. Two installation methods are supported: shaft drive and chain drive. The factory standard configuration is for shaft drive. Chain drive requires appropriate sprocket chain accessories.
Installation Types:
Shaft Drive Installation: Depicts a diagram showing the operator mounted directly to the door shaft.
Chain Drive Installation: Depicts a diagram showing the operator connected via a chain mechanism to the door shaft.
Shaft Drive Installation Components:
- 1. Expansion Screw
- 2. Mounting Bracket
- 3. Mounting Screw
- 4. Door Operator
- 5. Special Flat Key
- 6. Door Shaft
- 7. Fixing Sleeve
Chain Drive Installation Components:
- 1. Driven Wheel
- 2. Door Shaft
- 3. Chain
- 4. Mounting Bracket
- 5. Driving Sprocket
- 6. Driving Sprocket Shaft
- 7. Door Operator
Step 1. Check the door
After the door is installed, adjust the torsion spring. Ensure manual opening and closing are flexible without stagnation. Observe the rotation direction of the rope sheave to confirm it is consistent with the door operator's opening and closing direction.
Diagram illustrating the door mechanism, rope sheave, and mounting points.
Step 2. Determine the installation position
Consider the door operator's dimensions and installation direction. Determine the mounting bracket position, mark the cavity, drill screw holes, and fix the bracket. The bracket can be installed inside or outside the operator; inside installation is recommended for easier disassembly.
Step 3. Trial installing the door operator
Install a fixing sleeve on the door shaft first, then insert the industrial door operator into the door shaft.
Diagram showing the operator being inserted into the door shaft with a fixing sleeve.
Step 4. Pre-fix the industrial door operator
Fix the industrial door operator onto the mounting bracket using 4 hexagon head flange bolts (M10×20). Do not tighten them fully at this stage.
Diagram showing the operator being attached to the mounting bracket with bolts.
Step 5. Find the direction of key slot
First, pull the red handle A downwards to engage the hand-pulled chain mechanism with the main engine (Manual control mode). Rotate the output shaft of the door operator by pulling the hand-pulled chain up and down until the key slot of the output shaft aligns with the key slot of the door shaft.
Diagram illustrating the red handle (A) and the alignment of key slots on the output shaft and door shaft.
Step 6. Mount the flat key and fixing sleeve
Mount the flat key. Keep two fixing sleeves close to the ends of the output shaft. Fasten the two M8 head screws in the key slot of the door shaft to prevent the flat key from loosening or falling off.
Diagram showing the flat key, fixing sleeves, and M8 screws being installed.
Step 7. Tighten the screws, prepare wiring and debugging
Tighten all screws. Finally, pull the green handle B downwards to disengage the hand-pulled chain mechanism from the main machine (Electric control mode).
Industrial Door Operator Wiring
Wiring Between Door Operator and Control Unit
Diagram showing the connection between the door operator and the control unit. The diagram illustrates the main operator unit and the control box, with wires connecting them. Three numbered wires are indicated:
- 1. Motor Wire
- 2. Encoder Wire
- 3. Power Supply Wire
Wiring of Single Phase Operator
Diagram showing the internal wiring of the control unit for a single-phase operator. It depicts the terminal block and connections for power supply, motor, and encoder. Labels for AC220V power supply (U, V, W) and encoder signals (GND, A, B, VCC) are shown with corresponding wire colors (blue, brown, black for motor; white, yellow, red, green for encoder).
- 1. AC220V (single phase) Power Supply Wire
- 2. Motor Wire: U(blue), V(brown), W(black)
- 3. Encoder Wire: GND(white), A(yellow), B(red), VCC(green)
Note: Ensure wirings are tight and well-connected. Tighten the IP plug after wiring. Warning: Do not plug in the power supply wire until all wiring is complete.
Wiring of Three Phases Operator
Diagram showing the internal wiring of the control unit for a three-phase operator. It depicts the terminal block and connections for power supply, motor, and encoder. Labels for AC380V power supply (L1, L2, L3) and encoder signals (GND, A, B, VCC) are shown with corresponding wire colors (blue, brown, black for motor; white, yellow, red, green for encoder).
- 1. AC380V (three phases) Power Supply Wire
- 2. Motor Wire: U(blue), V(brown), W(black)
- 3. Encoder Wire: GND(white), A(yellow), B(red), VCC(green)
Note: Ensure wirings are tight and well-connected. Tighten the IP plug after wiring. Warning: Do not plug in the power supply wire until all wiring is complete.
Operation Interface Illustration
Diagrams illustrating the control panel of the door operator.
Control Panel Layout:
- DIGITAL SCREEN: Displays status and settings (e.g., XX-XX).
- Buttons:- UP (Open indicator light)
- STOP (Stop indicator light)
- DOWN (Close indicator light)
- NEXT
- CONFIRM
- INCREASE (+)
- REDUCE (-)
 
- Indicator Lights: Indicate OPEN, STOP, CLOSE status.
Display Functions:
- Opening status display
- Working mode display
- Input status display
The screen displays modes like "OP-H1".
Open and Closed Limit Switch Setting
This section details the procedure for setting the open and closed limit switches using the control panel.
- Initial State: After powering on, the digital screen displays "E-04", indicating that the limit switches have not been set.
- Enter Setup Mode: Press and hold the "NEXT" button for 3 seconds. The digital display will change to "00000".
- Enter Password: Enter the password "21000" by pressing "+" twice, then "NEXT" once, then "+" once, and finally "CONFIRM" once. The digital display will show "P1".
Setting Open Limit Switch
- Enter Parameter Mode: Press "CONFIRM" once. The display will show "P1-F1". Press "CONFIRM" again. The display will show "-- --".
- Check Opening Direction: Briefly press the "OPEN" button to check the door's opening direction.
- Set Open Limit: If the direction is correct, press and hold the "OPEN" button. The digital display will flash "-- --" while setting the open limit switch position.
- Correcting Direction: If the opening direction is wrong, press and hold the "STOP" button until the display shows "F" (forward) or "r" (reverse) to change the running direction. After changing the direction, press and hold "OPEN" to set the open limit switch position.
Setting Closed Limit Switch
- Confirm Open Limit: Release the "OPEN" button when the motor reaches the desired open limit position. Press "CONFIRM". The display will show the encoder value for 1 second, then "-- --", indicating the open limit is set and ready for closed limit setting.
- Set Closed Limit: Press and hold the "CLOSE" button until the gate reaches the proper closed limit position. Release the button, then press "CONFIRM". The display will show the encoder value for 1 second, then "P1-F2", indicating the closed limit switch has been set.
- Return to Primary Menu: Press "NEXT" twice to return to the primary menu. The operator is now ready for use.
Working Mode Setting
This section describes how to set the operating mode (Automatic or Manual).
Press and hold the "-" button for 4 seconds to select manual or automatic control mode.
- Automatic (A):- Press "OPEN". The door moves to the open limit switch position.
- After the programmed auto-close time, the door automatically closes to the closed limit switch position.
- (Factory default auto-close time is 0. For automatic closing function, set parameter P1-F6 first).
 
- Manual (H):- Press "OPEN". The door moves to the open limit switch position.
- Press "CLOSE". The door moves to the closed limit switch position.
 
After setting the mode, check the door's running condition. If satisfactory, no further settings are needed. If not, adjust relative parameters.
Note:
- Adjust the door operator using the buttons on the control unit.
- Perform trial runs after adjustment to ensure everything is correct.
- Mount the control unit on a post at a height of 1.4 meters from the ground to keep it away from children.
Input Status:
| No. | Instruction | 
|---|---|
| 1 | Stop | 
| 2 | Open | 
| 3 | Close | 
| 4 | Photo Sensor | 
| 5 | Air Bag | 
| 6 | Loop Detector | 
| 7 | Partial Opening | 
| 8 | Single Cycle | 
| 9 | Interlock | 
Parameters Setting
P1
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P1-F1 | Electronic limit switch setting | ||
| P1-F2 | Opening frequency | 30-80 | 50 | 
| P1-F3 | Closing frequency | 30-80 | 50 | 
| P1-F4 | Soft Start Distance | 15-100 | 40 | 
| P1-F5 | Slow Stop Distance | 15-100 | 50 | 
| P1-F6 | Auto-close Delay Time | 0-999 seconds | 0 | 
| P1-F8 | Height of partial opening | 0-100 | 50 | 
| P1-F9 | Inch move for opening | 0=continuous; 1=Inch | 0 | 
| P1-A1 | Inch move for closing | 0=continuous; 1=Inch | 0 | 
| P1-A2 | Inch Speed | 10-50 | 30 | 
| P1-A3 | Pre-stop before arriving at the open limit switch position | 0-200 | 40 | 
| P1-A4 | Pre-stop before arriving at the closed limit switch position | 0-200 | 40 | 
| P1-A5 | Holding frequency | 0.0-15.0 | 2.0 | 
| P1-A6 | Restore to factory setting of P1 | 0=No; 1=Yes | 0 | 
P2
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P2-F1 | Stop of external switch | 0=NO; 1=NC | 0 | 
| P2-F2 | Partial opening | 0=NO; 1=NC | 0 | 
| P2-F3 | Single cycle | 0=NO; 1=NC | 0 | 
| P2-F4 | Photo sensor | 0=NO; 1=NC | 0 | 
| P2-F5 | Loop detector | 0=NO; 1=NC | 0 | 
| P2-F6 | Airbag | 0=NO; 1=NC; 2=Pulse | 0 | 
| P2-F7 | Multi-function of F1 | 0=NO; 1=NC | 0 | 
| P2-F8 | Multi-function of F2 | 0=NO; 1=NC | 0 | 
| P2-F9 | ILIN | 0=NO; 1=NC | 0 | 
| P2-A1 | ILOUT | 0=NO; 1=NC | 0 | 
| P2-A2 | DIND | 0=NO; 1=NC | 0 | 
| P2-A3 | Restore to factory setting of P2 | 0=No; 1=Yes | 0 | 
P3
| Default | |||
|---|---|---|---|
| P3-F1 | F1 | Close | 0 | 
| Fault output | 1 | 0 | |
| Door in running output | 2 | ||
| Door completely open in place output | 3 | ||
| Door partially open in place output | 4 | ||
| Not open limit switch output | 5 | ||
| Closed in place output | 6 | ||
| Not closed limit switch output | 7 | ||
| Photo sensor signal output | 8 | ||
| Airbag signal output | 9 | ||
| Loop detector signal output | 10 | ||
| Air curtain signal output | 11 | ||
| force on | 12 | ||
| P3-F2 | F2 | Same as P3-F1 | |
| P3-F3 | Inter-lock function | 0=Disable; 1=Enable | 0 | 
| P3-F4 | Limit height of infrared photocell valid | 1-1500 | 100 | 
| P3-F5 | Limit height of airbag valid | 1-1500 | 0 | 
| P3-F6 | Locked rotor time | 1-7 | 4 | 
| P3-F7 | fall back when encountering obstacles | 0-99 | 99 | 
| P3-F8 | Remote Control Mode Selection | 0=single button; 1=triple button | 1 | 
| P3-F9 | Automatic anti-freeze operation | 0-999 minutes (0 = canceled) | 0 | 
| P3-A1 | Restore to factory setting of P3 | 0=No; 1=Yes | 0 | 
| P3-A2 | Downtime Decline | 0 = upper limit position automatically closes ; 1 = non-lower limit position automatically closes | 1 | 
| P3-A3 | Commutation delay time | 0.1-2.0s | 0.5 | 
P4
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P4-F1 | Alarm of running over the open limit switch | 10-200 | 80 | 
| P4-F2 | Alarm of running over the closed limit switch | 10-200 | 100 | 
| P4-F3 | Display backlight selection | 0=60sec. automatically energy saving; 1=always on | 0 | 
| P4-F4 | Open limit switch position check | Read only | |
| P4-F5 | Closed limit switch position check | Read only | |
| P4-F6 | Current positon check | Read only | |
| P4-F7 | Infrared positon check | Read only | |
| P4-F8 | Restore to factory setting of P4 | 0=No; 1=Yes | 0 | 
P5 (Initial password: 00000)
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P5-F1 | Change your password | 00000-99999 | 00000 | 
| P5-F2 | Total running times setting | 0-99999 | 99999 | 
| P5-F3 | Total running days setting | 0-99999 | 99999 | 
| P5-F4 | Total running days checking | Read only | |
| P5-F5 | Total running times checking | Read only | |
| P5-F6 | Restore to factory setting of P1- P4 | 0=No; 1=Yes | 0 | 
External Accessories Wiring
1. External three-buttons switch terminal: "STOP" terminal type is NO by default, if you need NC type, please modify the setting of "P2-F1" to be "1".
Diagram showing the wiring for an external three-buttons switch with terminals for COM, Signal, UP, DOWN, STOP, PART, ILIN, ILOUT. Labels indicate "three-buttons switch".
Diagram Description: An illustration of a three-button switch wiring interface, showing connections for UP, DOWN, STOP, PART, ILIN, ILOUT, and COM signals.
2. External partial opening button switch terminal: terminal type is NO, if you need NC type, please modify the setting of "P2-F2" to be "1". The height of partial opening can be adjusted under setting "P1-F8".
Diagram showing the wiring for a partial opening button switch with terminals for COM, Signal, UP, DOWN, STOP, PART, ILIN, ILOUT. Labels indicate "partial opening".
Diagram Description: An illustration of a partial opening button switch wiring interface, showing connections for COM, Signal, and other relevant terminals.
3. External single cycle button switch terminal: terminal type is NO, if you need NC type, please modify the setting "P2-F3" to be "1".
Diagram showing the wiring for a single cycle button switch with terminals for COM, Signal, UP, DOWN, STOP, PART, ILIN, ILOUT. Labels indicate "Single cycle".
Diagram Description: An illustration of a single cycle button switch wiring interface, showing connections for COM, Signal, and other relevant terminals.
4. Safety photocell terminal: terminal type is NO, if you need NC type, please modify the setting of "P2-F4" to be "1". The valid height of photocell can be adjusted under "P3-F4".
Diagram showing the wiring for a safety photocell, with separate sections for Emitter and Receiver. Terminals include COM, Power positive, Power negative, Signal, IR, EDGE, LOOP, DIND.
Diagram Description: An illustration of safety photocell wiring, showing connections for the emitter (power positive, power negative) and receiver (signal, COM, power positive, power negative, IR, EDGE, LOOP, DIND).
5. Safety airbag terminal: There are 2 signal types of safety airbag: level signal and pulse signal, factory default is level single in NO type, if require NC type or pulse signal, you can change it under setting of "P2-F6". The valid height of airbag can be adjusted under "P3-F5".
Diagram showing the wiring for a safety airbag with terminals for COM, Power positive, Power negative, Signal, IR, EDGE, LOOP, DIND.
Diagram Description: An illustration of safety airbag wiring, showing connections for signal, COM, power positive, power negative, and other relevant terminals.
Diagram showing the wiring for a loop detector with terminals for COM, Power positive, Power negative, Signal, IR, EDGE, LOOP, DIND.
Diagram Description: An illustration of loop detector wiring, showing connections for signal, COM, power positive, power negative, and other relevant terminals.
6. Loop detector terminal: default is NO, if require NC, please modify the setting of "P2-F5" to be "1". Loop detector signal is only vaild under automatic control mode, invalid under manual control mode.
7. Small door interlock terminal: default is NO, if require NC, please modify the setting of "P2-A2" to be "1".
Diagram showing the wiring for a small door interlock with terminals for COM, Signal, GND, DIND, +24V, IR, EDGE, LOOP, ILIN, ILOUT.
Diagram Description: An illustration of small door interlock wiring, showing connections for signal, COM, and other control terminals.
Diagram showing the wiring for a relay terminal with terminals for COM, COM1, COM2, F1, F2, Signal.
Diagram Description: An illustration of relay terminal wiring for external accessories, showing connections for COM, COM1, COM2, F1, F2, and Signal.
8. Relay terminal output: default is NO, if require NC type, please modify the setting of "P2-F7" or "P2-F8"to be "1". Output logic function can be selected under "P3-F1" and "P3-F2".
9. Two doors interlock: connect terminal "ILIN"of control unit 1 to terminal "ILOUT" of control unit 2. Connect terminal "ILOUT"of control unit 1 to terminal "ILIN" of control unit 2. Connect terminal "COM" of control unit 1 to terminal "COM" of control unit 2. Please remember to change the parameter of "P3-F3" to be 1 if you enable this two doors interlock function.
Diagram showing the wiring for two doors interlock between Control unit 1 and Control unit 2. Terminals include ILIN, ILOUT, COM, UP, DOWN, STOP, PART.
Diagram Description: An illustration detailing the interlock wiring between two control units, showing connections for ILIN, ILOUT, and COM terminals.
Diagram showing the wiring for an Alarm lamp. Terminals BL, BN are shown, with a label "220V Alarm lamp".
Diagram Description: An illustration of alarm lamp wiring, indicating connections for BL and BN terminals for a 220V alarm lamp.
10. Alarm lamp terminal: Alarm lamp should be 220V, wire to BL and BN terminals.
Remote Control Password Setting
a. Remote control pairing:
Press AN button on the receiver, LED light will flash once, press any one of the buttons on the remote (normally button A), LED light will flash for 4 seconds then off, remote control pairing is complete. If require to pair another remote control please repeat the above pairing steps, each PC board can be paired with 25 remote controls in max.
Diagram showing a receiver with an AN button and LED, and a remote control with buttons A, B, C, D. A "Pairing Button" is also indicated.
Diagram Description: An illustration of the remote control pairing process, showing the receiver's AN button and LED, and the remote control buttons.
Note: Only need to pair "button A", the pairing of the remote control is finished meanwhile.
b. Remote control delete:
Press and hold AN button on the receiver, LED light will be on, release the button until the LED light is off, all paired remote controls are deleted.
Note: Recommended to operate the remote control deletion first and re-pair the remote before you use the operator for security consideration.
Remote Control Mode
1. Parameters Setting: The P3-F8 Default is 0. The receiver DIP Switch Setting: OFF. Remote Control in Single Button Mode.
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P3-F8 | Remote Control Mode Selection | 0=single button; 1=triple button | 0 | 
2. Parameters Setting: The P3-F8 Default is 1. The receiver DIP Switch Setting: ON. Remote Control in Three Buttons Mode.
| No. | Parameters | Value Range | Default | 
|---|---|---|---|
| P3-F8 | Remote Control Mode Selection | 0=single button; 1=triple button | 1 | 
Usage of Hand-Pulled Chain
When you need to manually open or close the industrial door, the hand-pulled chain is required.
Before pulling the chain, fully pull the red handle A in the hand-pulled chain mechanism to engage it with the main machine. The protection switch inside the mechanism will automatically cut off the power supply. The chain can then be pulled.
The chain should be pulled continuously and evenly to avoid damage.
When you need to electrically open or close the industrial door, fully pull the green handle B in the hand-pulled mechanism first to disengage it from the main machine. The protection switch will reset, allowing normal electric operation. Please fix the hand-pulled chain on the wall properly when not in use.
Diagram showing the hand-pulled chain mechanism with handles A (red) and B (green).
Diagram Description: Illustration of the hand-pulled chain mechanism, highlighting the red handle (A) for engaging manual mode and the green handle (B) for disengaging manual mode and returning to electric operation.
Notes on Hand-Pulled Chain Usage:
- After using the chain, if the digital display shows "E--11", you cannot open or close the door electrically. This is because the protection switch has not been reset. Fully pull the green handle (B) to disengage the mechanism from the main machine; the control unit will function properly until "E--11" is off.
- The hand-pulled chain should only be used in special circumstances, such as power failure, and not for long-term normal operation.
Note: Check monthly if the travel of opening or closing has changed, if limit positions are accurate and reliable, and if the door is well-balanced. Make adjustments if necessary. If required, consult professional personnel for maintenance and debugging.
Common Faults and Countermeasures
| No. | Trouble | Possible Cause | Countermeasures | 
|---|---|---|---|
| 1 | The digital screen is off. | The power supply is not connected or the wires is loose. | Tighten the screw of the wiring and re-power on. | 
| The emergency stop terminal is loose or emergency stop button is not reset. | Reinsert the emergency stop terminal or reset the emergency stop button. | ||
| Power has input, while transformer without voltage output. Transformer has damaged in transit. | Replace the circuit board. | ||
| 2 | E-01 Input phase-loss | Phase-loss of three phases power supply. | Check with a multimeter which phase is lost, and re-wire. | 
| 3 | E-02 Output phase-loss | Main circuit phase-loss | Check motor winding | 
| 4 | E-03 Encoder disconnect | Encoder was not connected or wrongly connected. | Re-connect the encoder. | 
| 5 | E-04 Limit switch abnormal | Up and down limit switch was not set or was set over the travel. | Re-set the limit switch. | 
| Short acceleration or deceleration times | Increase acceleration or deceleration time | ||
| 6 | E-05 overcurrent | Phase to phase short circuit or earth fault | Check wiring, replace motor | 
| Sudden load fluctuations | Reduced load fluctuations | ||
| ground fault | Verify wiring and machine grounding | ||
| 7 | E-07 Maintenance notice | Damaged IGBT module | Contact Agents | 
| Exceed the scheduled running cycles or time | Please contact supplier for solution. | ||
| 8 | E-08 Motor stalling | The door is meeting obstacles, motor can't drive the door caused motor stalling. | Deformation of the track, find the point of obstruction of the door body and eliminate it. | 
| 9 | E-09 phase sequence | Grid voltage too low | Check grid voltage | 
| 10 | E-10 overpressurization | Deceleration time too short, high descent frequency | Longer deceleration time, lower frequency | 
| Abnormal input voltage | Check input voltage | ||
| Output Out-of-Phase | Check motor and control board wiring | ||
| Controller power is low | Optional higher power control board | ||
| 11 | E-11 Thermal protection | Thermal protection or hand chain protection | Waiting for the motor to cool down. Pull up and down chain to reset the switch | 
| 12 | E-12 Door in door mode abnormal | The smaller door is open or damaged. | Close the smaller door to enable it's normal running. Make sure the wiring between DIND and COM are good. | 
| 13 | E-13 frequency conversion overload | Acceleration time is too short | Increase acceleration time | 
| The load is too big. | Use of higher power control boards | ||
| 14 | E-14 Motor overload | Motor blocked | Checking the door body | 
| overload | Replacement of high torque motors | ||
| Continuous low speed operation of the motor | Increased frequency of operation | ||
| 15 | E-15 frequency conversion overheating | Inverter board overheating protection | Reduced frequency of use | 
| 16 | E-16 Excessive torque increase | Torque boost parameter too high | Downward torque increase value | 
| 17 | E-17 Inverter board failure | Inverter board damage | Contact Agent | 
| 18 | E-21 Limit Learning Fault | No lower limit learning | Relearning the lower limit | 
| 19 | Remote control does not work | Remote control indicator light does not light up | Battery replacement | 
| Transmitter and receiver mismatch | Reset the remote control password | 
PACKING LIST
Door Operator Packing List
| No. | Name | Qty. | Note | 
|---|---|---|---|
| 1 | Door operator | 1 | |
| 2 | Mounting bracket | 1 | |
| 3 | Fixing sleeve | 2 | Contain M6×10 fastening screw | 
| 4 | Special flat key | 1 | 6x70 | 
| 5 | Hexagon bolts | 4 | M10x20 | 
| 6 | User manual | 1 | |
| 7 | Motor four-core wire | 1 | 5 meter | 
| 8 | Limit switch four-core wire | 1 | 5 meter | 
Control Unit Packing List
| No. | Name | Qty. | Note | 
|---|---|---|---|
| 1 | Control unit | 1 | |
| 2 | Remote control | 2 | 