Lifelight Instruction Sheet

mjd@clevertronics.com.au

Maxwell AU 133 Sub Zero Installation Instructions – Eye Lighting Australia

Maxwell AU 133 Sub Zero – Eye Lighting Australia

PDF preview unavailable. Download the PDF instead.

Maxwell AU Sub-Zero Installation & Maintenance Supplement
Clevertronics Clever-test
The Clevertronics Clever-test Lifelight (LLIFEM-PRO-SA-CT) can be programmed to perform 90 minute discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a 5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until LED Test Switch indicator flashes rapidly). Refer Clever-test Operation Guide for more information. Once the test has been completed, maintenance personnel then view the Status Indicator of each fitting to determine a pass or failure:

SOLID GREEN (not flashing)
SLOW YELLOW FLASH (2s Yellow, 2s Off) VERY SLOW YELLOW & Green (4s Yellow, 1s Green)
FAST YELLOW & Green FLASH (0.5s Yellow, 0.5s Green)

NORMAL ­ The luminaire is in a normal state charging and awaiting next discharge test.
TESTING ­ The luminaire is currently performing a test.
RECENTLY PASSED ­ The luminaire has previously tested and passed. This indication remains for 5 days after the completion of the test and then changes to SOLID Green to indicate a normal state. FAILED LAST TEST ­ The luminaire has previously tested and failed to remain illuminated for the required duration. This indication will remain until the required maintenance work has been completed and the luminaire passes a subsequent discharge test.

Zoneworks and DATA Monitored Options

Lifelights with part numbers LLIFEM-PRO-SA-ZW, LLIFEM-PRO-SA-DATA are fitted with Zoneworks communications modules (nodes).These fittings are monitored using either Powerline Carrier Technology that utilising the power cable to provide data communication or a dedicated data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each Lifelight. Zoneworks Lifelights can be commissioned by a single push of the test switch, or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of the Lifelight during testing and normal operation:

State

LED Operation

Commissioned

LED on Solid (Green)

Un-commissioned

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)

Emergency Light Test In Progress LED flashes at 3s On (Yellow) & 0.5s Off

In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of a Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA version)

DALI EM Option

Lifelights with part numbers LLIFEM-PRO-SA-DALI are fitted with DALI modules (nodes) that facilitate connection and integration to 3rd Party Lighting Control Systems. Before installing the LLIFE-PRO-DALI please confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The LLIFE-PRO-DALI will be addressed and configured into the control system by the Lighting Control System Commissioning Technicians and not Clevertronics.

State

LED Operation

Commissioned/ Un-commissioned LED on Solid (Green)

Emergency Light Test in progress LED flashes at 1s On (Yellow) & 1s Off

"IDENTIFY COMMAND"

Fitting goes into emergency mode for 10 seconds

A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network OR a 5/6way "structured wiring system" lead and plug facilitating the power and DALI connection. DALI connections are marked as Da Da.

SAMMODE
MAXWELL SUB-ZERO REMOTE MAINTAINED
Installation & Maintenance Supplement
Sammode Lighting Australia Pty Ltd 15 Industrial Avenue WACOL QLD 4076 Phone: 61 (0) 7 3335 3504 Fax: 61 (0) 7 3335 3522

Designed in Australia to comply with the requirements of AS2293.3: 2005, AS/NZS CISPR15: 2011

Models:

Testing Options: xx=

MAXWELL SUB-ZERO MAINTAINED 184190 CT

Clevertest

ZW

Zoneworks

DATA Zoneworks DATA

DALI DALI
Spare Parts: LLIFEM-PRO-SASAMEMIPRM-xx-FIT

1530230

Battery, 3.3 Volt 5Ah Li-ion

LLIFEM-PRO-SA-CKIT13V300C

PCA: Lifelight Control-SA 300mA CT10142Lx

Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, ensure that the electricity supply has been switched off and isolated. Installation must be carried out in accordance with the relevant Australian and International Standards.

Upgrading a LLIFEM-PRO-SA LED Driver to Clever-test, Zoneworks (incl. DATA) or DALI EM
All L10 Lifelight Pro LED Driver (LLIFEM-PRO-SA) can be upgraded to Clever-test, Zoneworks, Zoneworks DATA or DALI EM.
When upgrading simply insert the relevant smart node board.
Installation: Emergency Fitting
Refer to the Maxwell Installation Instruction for specific mounting hardware and methods for the fitting body.
Refer to Supplementary Installation Instruction below for proper alignment of the gear tray and diffuser image.
1. Install the fitting mounting straps per the Maxwell Instruction. 2. Install the diffuser tube to the mounting straps. 3. Connect power to the gear tray terminal block. 4. Apply power and test the fitting operation. 5. Install the LED gear tray in the tube. 6. Align the RED arrow on the end cap with the RED arrow on the mounting bracket which
corresponds to the mounting (Ceiling or Wall) of the fitting.
Installation: Remote Enclosure
1. 1. Remove the enclosure cover. 2. 2. Remove the gear tray. 3. 3. Use the enclosure base to mark out the (4) mounting holes. 4. 4. Install the enclosure base using appropriate fixings. 5. 5. Route power to the fitting and connect to the terminal block. 6. 6. Route the LED drive output from the terminal block to the exit fitting. 7. 7. Apply power and test the fitting operation.

Ceiling Mount

Wall Mount

Enclosure Base

Initial Testing:

When the fitting is connected to the un-switched active, it must be allowed to charge the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the following tests:

 During the first commissioning test the emergency lamp must illuminate for at least 2 hours after disconnection from the main supply. The results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation and once completed, the unit must pass a subsequent test.

 Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.

 Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-maintained operation).

Below are a list of common problems and their possible causes:

Fault: Check:

The Green LED indicator is not illuminated. A.C. is connected and is turned on. Battery is connected. Test Switch for damage.

Fault: Check:

Lamp does not illuminate in emergency mode. A.C. is connected. Lamp is correctly inserted. Battery is connected

Fault: Lamp illuminates in emergency mode, but only stays on for a short period. Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to spacing tables for installation positions):

CEILING MOUNT WALL MOUNT

C0=D63, C90=D32, C180=D63, C270=D32 C0=D25, C90=C25, C180=B10, C270=C25

Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or "cycled". The Li-ion battery in the Lifelight has been selected to give excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.

Warranty:
The manufacturer warrants the goods against defects solely due to faulty parts or workmanship of the manufacturer for a period of 48 months from the date of purchase. This warranty covers the repair or replacement of the goods at the discretion of the manufacturer, upon the goods being returned to the nearest branch of the manufacturer at the clients cost. Any other warranty or guarantee, expressed or implied, to the extent permitted by law, is expressly excluded. The manufacturer shall not be liable for any costs or consequential losses that may arise through the use of any of the manufacturers' products. Installation or operation of this product in a manner NOT complying with this instruction leaflet will automatically void any and all warranties.

1940994

V1.0 May 2017

