First Co. UC Series Wall Mount Fan Coils

Product Overview and Specifications

Introduction

The First Co. UC Series offers a range of wall mount fan coils designed as upflow indoor air handlers for use with split-system heat pumps or condensing units. These units are compatible with R410A refrigerant and are intended for servicing existing equipment. They provide efficient cooling or heating capabilities, with options for electric heat up to 10 kW or hydronic heating.

Key features include galvanized steel cabinets, insulated construction, sloped condensate pans for proper drainage, and removable doors with captive screws for easy service access. Drain piping flexibility is offered, allowing connections from the bottom, front, left, or right side.

The series includes models such as UCO (Electric Heat w/PSC Motor), UCX (Electric Heat w/ECM Motor), UCOW (Hydronic Heat w/PSC Motor & DX Coil for Cooling), UCOQ (Hydronic Heat w/Circulator Pump & PSC Motor), UCXW (Hydronic Heat w/ECM Motor & DX Coil for Cooling), and UCXRX (Hydronic Heat w/Hi Flow Pump & ECM Motor).

Compatibility Note: First Co. customers are responsible for confirming fan coil model compatibility with selected outdoor units and required expansion valves. Certified indoor/outdoor combinations can be found at www.ahrinet.org or by contacting the factory.

Image of a First Co. UC Series Wall Mount Fan Coil unit.

Full Series Nomenclature

The model numbering system provides detailed configuration information:

Example: 25 UCX 05 X 1 0 A V 0 0 0 F

UNIT SIZE: Indicates cooling capacity (e.g., 18, 19 for 18,000 BTUH, 25 for 24,000 BTUH, 30 for 30,000 BTUH, 37 for 36,000 BTUH).

SERIES: UCO, UCX, etc.

HEAT OPTION: Specifies heating type and capacity (e.g., 00 - No Heat, 03 - 3 KW, W3 - 3 Row HW, R3 - 3 Row Hi Flow Pump HW).

MOTOR TYPE: 0 - PSC, X - ECM Multispeed.

VOLTAGE: 1 - 120/1/60, 2 - 208-230/1/60.

CABINET OPTIONS: 0 - Standard Front Return, B - Bottom Return.

BRAND: F - First Co.

OPTIONS: GENERAL: 0 - Standard, 2 - 2-Way HW Valve, 3 - 3-Way HW Valve, T - Stub Out Tubes.

OPTIONS: SENSORS/SWITCHES: 0 - None / Standard, 1 - Freeze Stat, 2 - Float Switch, 3 - Freeze Stat & Float Switch, 4 - DX Coil Sensor, 5 - DX Sensor & Freeze Stat.

OPTIONS: CONTROL: 0 - Standard, B - Standard Pump Control, T - Time Delay.

METERING DEVICE: C - Chilled Water Coil, V - Non Bleed TXV w/ Check.

REFRIGERANT: A - R410A.

UCO Series: Electric Heat w/PSC Motor

The UCO series features electric heat with a PSC motor, designed as an upflow indoor air handler.

Standard Features:

Optional Features:

Optional accessories include field installed Heater Kits, factory or field installed TXV Kits (non-bleed type), Wall Panels with Captive Screws, Condensate Overflow Switch, Closet Hanger Bracket Kit, and Bottom Return Air Kit.

Physical Dimensions:

UNIT MODELABCDEFFILTER SIZELIQUID LINESUCTION LINE
18-25UC022-1/815-1/8401410.53-5/818 X 183/8 O.D.5/8 O.D.
26/30/31UC022-1/815-1/8401410.53-5/818 X 203/8 O.D.3/4 O.D.
32/37UC022-1/818-1/84314133-5/818 X 243/8 O.D.3/4 O.D.
38UC028-1/8214616-1/2137-1/224 x 243/8 O.D.7/8 O.D.

Performance Data (Electric Heat w/PSC Motor):

Performance Data Tables

Electric Heat Capacity:

UNIT MODELNOM. CFMNOM. COOL BTUHELECTRIC HEAT CAPACITY (kW)ELECTRIC HEAT CAPACITY (BTUH)TOTAL AMPSMIN. AMPACITYMAX. OVERCURRENT PROTECTION
240V208V240V208V240V208V240V208V240V208V
18UC0 0-HK6001800000001.701.70221515
19UC032.31023977811412.7618162020
20UC0353.817065129692319.9728263030
24UC0664.520478153582723.3433293530
25UC08002500086.027304207503530.5544384540
26UC08107.534130255974337.7654476050
31UC00-HK00002.02.0331515
30UC0310003000032.3102397781151518162020
32UC0353.81706512969232029263030
36UC0664.52047815358272434303530
37UC012003600086.02730420750353144394540
38UC08107.53413025597443855486050

Blower Data (CFM vs. External Static Pressure):

MODELMOTOR (HP) (240V)FAN SPEED0.100.200.300.400.50
18UC01/6HIGH880840810790760
19UC0MEDIUM660640630600570
20UC0LOW540520500470440
24UC01/6HIGH850820780750710
25UC0MEDIUM660640610570540
26UC0LOW540520500470430
30UC01/6HIGH840800760710660
31UC0MEDIUM660640610570530
32UC0LOW540510500460420
36UC01/4HIGH870840810780750
37UC0MED-HIGH670650630590560
38UC0MED-LOW560540510480440
LOW550530500470440
1/4HIGH108010451030975920
MEDIUM950940910865820
LOW865855825790745
1/4HIGH910880840790740
MED-HIGH860830790740690
MED-LOW830790750710660
1/4HIGH108010401000950900
MED-HIGH970940900850800
MED-LOW690650600550510
1/2HIGH13001240118011201050
MED-HIGH110010501010960910
MED-LOW980950920880830
1/2HIGH12401180112010701020
MED-HIGH108010401000960910
MED-LOW980950910870820
1/2HIGH14301400137013401290
MED-HIGH12601230120011801160
MED-LOW1000990980970950

Diagram showing a UC Series unit with labels for dimensions A through F, and openings for service access.

UCOW Series: Hydronic Heat w/PSC Motor & DX Coil for Cooling

The UCOW series combines hydronic heating with a PSC motor and a DX coil for cooling, suitable for use with tankless water heaters or boilers.

Features:

Physical Dimensions:

UNIT MODELABCDEFILTER SIZELIQUID LINESUCTION LINE
18-25UC0W22-1/818431812-1/218 X 183/8" O.D.5/8" O.D.
26/31UC0W22-1/818431812-1/218 X 203/8" O.D.3/4" O.D.
32-37UC0W22-1/821431815-1/218 X 243/8" O.D.3/4" O.D.
38UC0W28-1/8214624-1/815-3/424 X 243/8" O.D.7/8" O.D.

Performance Data (Hydronic Heat w/PSC Motor & DX Coil):

Heating Performance and Electrical Data:

UNIT MODELNOMINAL COOLING BTUHP.D. (FT. WATER) (COIL ONLY)HEATING BTUH (1000) AT ENTERING WATER TEMPERATURE (1) Delta-T 20°MIN. CIRCUIT AMPACITYMAX. FUSE OR HACR BREAKER
120°F GPM140°F GPM180°F GPM
18-20UC0W18,0003.319.11.926.82.742.14.2815
2.118.51.925.92.640.74.1
1.217.61.824.62.538.73.9
24-26UC0W24,000 / 18,0003.322.92.332.13.250.45.0815
2.122.12.231.03.148.74.9
1.220.82.129.22.945.94.6
31UC0W30,000 / 24,0003.326.12.636.53.757.35.71115
2.125.02.535.13.555.15.5
1.223.52.432.93.351.75.2
32UC0W30,000 / 24,0003.628.12.839.33.961.76.21115
2.426.92.737.73.859.25.9
1.325.22.535.33.555.45.5
36-38UC0W36,000 / 30,0003.630.93.143.24.367.96.81115
2.429.63.041.34.164.96.5
1.327.52.838.53.960.56.1

Blower Data (CFM vs. External Static Pressure):

UNIT MODELMOTOR H.P. (120V)MOTOR AMPS (120V)FAN SPEED0.100.150.200.250.300.400.50
18/19UC0W1/35.4MED-HIGH790775760745730700670
MED-LOW710695680665650630610
LOW560550540525510490460
20UC0W1/35.4MED-HIGH770750730710690650610
MED-LOW690675660645630590550
LOW540525510495480450420
24/25UC0W1/35.4HIGH840820800780760710660
MED-HIGH770750730710690650610
MED-LOW690665660645630590550
26UC0W1/35.4HIGH860845830810790750700
MED-HIGH780765750735720680640
MED-LOW700685670655640600560
31UC0W1/28.1HIGH107010451020995970920850
MED-HIGH10201000980960940890820
MED-LOW760755750735720680640
32UC0W1/28.1MED-HIGH11401110108010501020960900
MED-LOW900885870855840790740
LOW650645640635630610580
36/37UC0W1/28.1HIGH11601135111010801050990930
MED-HIGH11201095107010451020970900
MED-LOW890875860845830790740
38UC0W1/28.1HIGH1400137513501325130012501200
MED1260124512301210119011501100
LOW109010801070105510401010970

Diagram showing the UC0W unit with labeled dimensions (A-E), water inlet/outlet, high/low voltage connections, liquid/suction lines, and optional drain outlets. Also shows opening dimensions with cover removed.

UCOQ Series: Hydronic Heat w/Circulator Pump & PSC Motor

The UCOQ series is designed for hydronic heating with a circulator pump and PSC motor, compatible with gas-fired water heaters or boilers.

Features:

Physical Dimensions:

UNIT MODELABCDEFILTER SIZELIQUID LINESUCTION LINE
18-25UC0Q22-1/818431812-1/218 X 183/8" O.D.5/8" O.D.
26/31UC0Q22-1/818431812-1/218 X 203/8" O.D.3/4" O.D.
32-37UC0Q22-1/821431815-1/218 X 243/8" O.D.3/4" O.D.
38UC0Q28-1/8214624-1/815-3/424 X 243/8" O.D.7/8" O.D.

Performance Data (Hydronic Heat w/Circulator Pump & PSC Motor):

Performance Data:

UNIT MODELNOMINAL COOLING BTUHHEATING BTUH (1000) ENTERING TEMPERATURE Delta -T 20°F & GPMAMPS (MOTOR) (120V)AMPS Low Flow Bronze BumpAMPS Med. Flow Cast Iron PumpMIN. CIRCUIT AMPACITYMAX. FUSE OR HACR BREAKER
120°F GPM140°F GPM180°F GPM
18-20UC0Q18,00018.5 1.925.9 2.65.40.750.54815
24-26UC0Q24,000/ 18,00022.1 2.231.0 3.15.40.750.54815
30-31UC0Q30,000/ 24,00025.0 2.535.1 3.58.10.750.541115
32UC0Q30,000 / 24,00027.0 2.737.7 3.88.10.750.541115
36/37UC0Q36,000/30,00029.6 3.041.3 4.18.10.750.541115
38UC0Q36,000 / 30,00032.3 3.245.3 4.58.10.750.541115

Diagram showing the UC0Q unit with labeled dimensions (A-E), water inlet/outlet, high/low voltage connections, liquid/suction lines, and optional drain outlets. Also shows opening dimensions with cover removed.

UCX Series: Electric Heat w/ECM Motor

The UCX series features electric heat with an ECM motor, offering higher efficiency.

Features:

Physical Dimensions:

UNIT MODELABCDEFFILTER SIZELIQUID LINESUCTION LINE
19-25UCX22-1/815-1/8401410-1/23-5/818 X 183/8 O.D.5/8 O.D.
26, 31UCX22-1/815-1/8401410-1/23-5/818 X 203/8 O.D.3/4 O.D.
32, 37UCX22-1/818-1/84314133-5/818 X 243/8 O.D.3/4 O.D.
38UCX28-1/8214616-1/2137-1/224 x 243/8 O.D.7/8 O.D.

Performance Data (Electric Heat w/ECM Motor):

Performance Data Tables

Electric Heat Capacity:

UNIT MODELNOM. CFMNOM. COOL BTUHELECTRIC HEAT CAPACITY (kW)ELECTRIC HEAT CAPACITY (BTUH)TOTAL AMPSMIN. AMPACITYMAX. OVERCURRENT PROTECTION
240V208V240V208V240V208V240V208V240V208V
19UCX6001800032.310236682415.313.620182020
20UCX43.0136481023619.517.225222525
25UCX80024000/1800053.8170611364823.620.830273030
26UCX64.5204731535527.824.435313535
31UCX100030000/2400086.0272972047336.131.646405040
107.5341212559144.538.956496050
32UCX120036000/3000032.310236682416.614.921192520
37UCX43.0136481023620.818.526243025
38UCX53.8170611364824.922.132283530
64.5204731535529.125.737334035
86.0272972047337.432.947425045
107.5341212559145.840.258506050

Blower Data (CFM vs. External Static Pressure):

MODELMOTOR HPFAN SPEED TAPBHPNOM. AMPS0.100.200.300.400.50
19UCX1/350.231.9850800770730690
20UCX40.161.2680650610570540
30.131.0610570530490460
25UCX1/350.332.41030970930890850
26UCX40.252.1890830810780760
30.191.5770710680640610
20.151.2670600570530500
31UCX1/240.502.8119010901040980930
30.372.6112010601010960910
20.272.0940880860830790
10.211.5820760730700670
32UCX3/440.412.912501190115011201070
30.352.510901030990960920
20.251.5980910870840810
10.191.0870790740700670
37UCX3/450.753.914501330126011901120
40.413.112501190115011201070
30.332.310901030990960920
20.271.9980910870840810
38UCX3/450.533.514001350132012901230
40.472.813101250123012001180
30.382.111601100107010401000
20.341.810901020990960930

Diagram showing a UCX unit with labels for dimensions A through F, and openings for service access.

UCXW Series: Hydronic Heat w/ECM Motor & DX Coil for Cooling

The UCXW series combines hydronic heating with an ECM motor and a DX coil for cooling, offering enhanced efficiency.

Features:

Physical Dimensions:

UNIT MODELABCDEFILTER SIZELIQUID LINESUCTION LINE
12-25UCX-HW22-1/818431812-1/218 X 183/8" O.D.5/8" O.D.
26/31UCX-HW22-1/818431812-1/218 X 203/8" O.D.3/4" O.D.
32/37UCX-HW22-1/821431815-1/218 X 243/8" O.D.3/4" O.D.
38UCX-HW28-1/8214624-1/815-3/424 X 243/8" O.D.7/8" O.D.

Performance Data (Hydronic Heat w/ECM Motor & DX Coil):

Performance Data:

UNIT MODELNOM. COOLING BTUHP.D. FT. WTR. COIL ONLYHEATING BTUH (1000) AT ENTERING WATER TEMPERATURE Delta-T 20°F & GPMMOTOR SPEED TAP CONNECTION
120°F GPM140°F GPM180°F GPMHIGH SPD (VIO LEAD)LOW SPD (GRY LEAD)
12UCXW12,0003.311.41.116.01.625.12.5GRYVIO
2.111.11.115.61.624.52.51
1.210.81.115.11.523.72.4
19/20UCXW18,0003.319.11.926.82.742.14.221
2.118.51.925.92.640.74.1
1.217.61.824.92.538.73.9
25/26UCXW24,000 / 18,0003.322.92.332.13.250.45.032
2.122.12.231.03.148.74.91
1.220.82.129.22.945.94.6
31/32UCXW30,000 / 24,0003.326.12.636.53.757.35.732
2.125.02.535.13.555.15.51
1.223.52.432.93.351.75.2
37/38UCXW36,000 / 30,0003.628.12.839.33.961.76.232
2.426.92.737.73.859.25.91
1.325.22.535.33.555.45.5
3.630.93.143.24.367.96.832
2.429.63.041.34.164.96.51
1.327.52.838.53.960.56.1

Blower Data (CFM vs. External Static Pressure):

UNIT MODELMOTOR H.P. (120V)MOTOR AMPS (120V)BHPRUNNING AMPSSPEED TAP0.100.150.200.250.300.400.50
12UCXW1/43.5.111.6WHT575555540525505465425
.091.3GRY525505490470450405360
19/20UCXW1/34.8.243.0VIO300275250225200155--
.212.63690675660645630600570
.161.72650630610590570540510
.364.11530510490470450420390
25/26UCXW1/26.8.232.43880865850835820790760
.171.72670655640625610580550
.505.11570550530515500470440
31UCXW1/26.8.343.63930910890870850810760
.222.12800785770750730700690
.374.21610595580565550510480
32UCXW3/48.4.242.6310101000990975960930900
.202.02790775760745730700670
.756.71700685670650630600560
37UCXW3/48.4.495.531250123012101190117011201070
.374.02111010951080106510501020990
.475.61940925910895880850820
38UCXW3/48.4.385.231240123012201205119011601130
.252.32110010901080106510501020990
.252.31860845830815800760730

Diagram showing the UCXW unit with labeled dimensions (A-E), water inlet/outlet, high/low voltage connections, liquid/suction lines, and optional drain outlets. Also shows opening dimensions with cover removed.

UCXRX Series: Hydronic Heat w/Hi Flow Pump & ECM Motor

The UCXRX series is designed for high efficiency with a hi-flow pump and ECM motor, specifically for use with tankless water heaters, providing both domestic hot water and space heating.

Features:

Performance Data (Hydronic Heat w/Hi Flow Pump & ECM Motor):

Performance Data:

UNIT MODELNOM. CFMHTG. GPM (NOM.)HEATING BTUH (1000) AT ENTERING WATER TEMPERATURE (1) Delta - T 20°F & GPMTOTAL AMPS (MOTOR) (120V)TOTAL AMPS (PUMP) (120V)MIN. CIRCUIT AMPACITYMAX. CIRCUIT PROTEC- TION
120°F130°140°F150°F160°F
12UCXRX275411.3 1.113.6 1.415.9 1.418.1 1.820.4 2.03.5.84615
19/20UCXRX450415.6 1.618.8 1.921.9 1.925.0 2.528.2 2.84.8.84715
25/26UCXRX610419.1 1.922.9 2.326.7 2.330.5 3.134.3 3.46.8.841015
31UCXRX730421.3 2.125.6 2.629.9 2.634.2 3.438.5 3.96.8.841015
32UCXRX730422.7 2.327.3 2.731.8 2.736.3 3.640.9 4.18.4.841215
37UCXRX1050428.3 2.834.0 3.439.7 3.445.4 4.551.1 5.18.4.841215
38UCXRX1050430.6 3.136.7 3.742.8 3.748.9 4.955.0 5.58.4.841215

Blower Data (CFM vs. External Static Pressure):

UNIT MODELMOTOR H.P. (120V)MOTOR AMPS (120V)BHPRUNNING AMPSSPEED TAP0.100.150.200.250.300.400.50
12UCXRX1/43.5.111.6WHT575555540525505465425
.091.3GRY525505490470450405360
19/20UCXRX1/34.8.243.0VIO300275250225200155--
.212.63690675660645630600570
.161.72650630610590570540510
.364.11530510490470450420390
25/26UCXRX1/26.8.232.43880865850835820790760
.171.72670655640625610580550
.505.11570550530515500470440
31UCXRX1/26.8.343.63930910890870850810760
.222.12800785770750730700690
.374.21610595580565550510480
32UCXRX3/48.4.242.6310101000990975960930900
.202.02790775760745730700670
.756.71700685670650630600560
37UCXRX3/48.4.495.531250123012101190117011201070
.374.02111010951080106510501020990
.475.61940925910895880850820
38UCXRX3/48.4.385.231240123012201205119011601130
.252.32110010901080106510501020990
.252.31860845830815800760730

Diagram showing the UCXRX unit with labeled dimensions (A-E), water inlet/outlet, high/low voltage connections, liquid/suction lines, and optional drain outlets. Also shows opening dimensions with cover removed.

Accessories

Various optional accessories are available for the UC Series fan coils, including:

Detailed part numbers and dimensions for these accessories are provided in the tables within each series section.

v1 Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)

Related Documents

Preview First Co. UC Series Wall Mount Fan Coils: Product Specifications and Features
Comprehensive overview of First Co.'s UC Series Wall Mount Fan Coils, detailing specifications, features, nomenclature, and accessories for models UCO, UCX, UCOW, UCOQ, UCXW, and UCXRX.
Preview First Co. HCX Series Fan Coils: Technical Specifications and Features
Detailed specifications for the First Co. HCX Series of multi-position fan coils. This document covers models compatible with R410A, offering various configurations for heat pump, DX, electric heat, and hot water applications, with PSC and ECM motor options.
Preview First Co. HCX Series Multi-Position Fan Coils - Technical Specifications
Discover the First Co. HCX Series of multi-position fan coils, engineered for efficient heat pump, DX, and hot water heating applications. This document details specifications, features, and performance data for models including HCX, HCXX, HCXQ, HCXR, HCXW, and their variants, compatible with R32 and R454B refrigerants. Find more information at www.firstco.com and www.ahridirectory.org.
Preview First Co. RR Series Vertical High Rise Fan Coils | Specifications and Data
Comprehensive specifications, dimensions, performance data, and installation details for the First Co. RR Series Vertical High Rise Fan Coils, including models BLTX, BFRX, BFTX, and more. Explore features, capacities, and electrical data for HVAC applications.
Preview First Co. MB Series Fan Coil Specifications and Features
Detailed specifications, features, and performance data for the First Co. MB Series fan coil units, including blower data, dimensions, heating, and cooling capacities. Learn about optional Autospeed 24V thermostat.
Preview First Co. HBX/HCX Series Air Handler: Specifications, Features, and Model Guide
Explore the First Co. HBX/HCX Series air handlers, featuring versatile upflow/horizontal configurations, heat pump or DX cooling, electric heat options, and up to 15 SEER efficiency. This document details standard features, components, cabinet specifications, blower data, electrical data, model numbers, and accessories.
Preview First Co. UCQBR Series Air Handlers - Technical Specifications
Comprehensive technical specifications for the First Co. UCQBR Series Wall and Closet Air Handlers. This document details features, performance data, dimensions, model numbers, and optional accessories for units designed to work with tankless water heaters.
Preview First Co. HBC(X) Series Fan Coil Units - Technical Specifications and Performance Data
Comprehensive technical specifications, physical data, cooling and heating capacities, blower performance, and accessory information for the First Co. HBC(X) Series horizontal fan coil units.