60-2485 - T874 Multistage Thermostats and Q674 Subbases

Product Data

HBC Technical Communications

60-2485 - T874 Multistage Thermostats and Q674 Subbases

Honeywell Q674B1034 Thermostat Subbase Datasheet

Q674B1034-Honeywell Q674B1034 Heat-Off-Cool Auto-On Thermostat Subbase - Industrial Stores

PDF preview unavailable. Download the PDF instead.

1516752641Q674-DATA
T874 Multistage Thermostats and Q674 Subbases

APPLICATION
These thermostats and subbases provide low voltage control of multistage heating and cooling systems, including heat pump systems.

PRODUCT DATA
FEATURES
· T874 Thermostat has silent, dust-free mercury switches operated by coiled bimetal elements.
· Heat anticipator(s) are adjustable or fixed cooling anticipator(s) are fixed.
· Individual heat and cool levers and scales (most models) for temperature setting located on top of thermostat case.
· Cover thermometer on most T874 Multistage Thermostat models.
· Locking cover and locking lever screws available for T874 Multistage Thermostats.
· VersaguardTM Thermostat Guard or custom key lock thermostat guards available for T874 Multistage Thermostats.
· T874 Thermostat requires a Q674 Subbase.
· Q674 Subbase provides system and fan switching, wiring terminals and mounting base for T874 Multistage Thermostat.
· Adapter plate available for mounting Q674 on wall or horizontal outlet box.
· Light-emitting diodes (LEDs) located on subbase for easy reference.
· Up to three stages each of heating and cooling control possible.
· Models with setpoint restrictions and locking cover with no thermometer available for Department of Defense (DoD) and other special applications.
· Outdoor reset used on some models to improve thermal performance.
Contents
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Understanding Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Cross Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

® U.S. Registered Trademark Copyright © 2001 Honeywell · All Rights Reserved

60- 2485- 8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

SPECIFICATIONS
IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Super Tradeline®/Tradeline® Models
SUPER TRADELINE controls offer features not available on TRADELINE or standard models, and are designed to replace a wide range of Honeywell and competitive controls.
TRADELINE models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. Specifications of SUPER TRADELINE and TRADELINE controls are the same as those of standard models except as noted below.
Super Tradeline Models
T874 THERMOSTAT T874D Thermostat. Provides two stages of heating and two
stages of cooling. Use with Q674A-F Subbases. Y594D (T874D/Q674E/TG504A) Thermostat/Subbase/key
lock cover package. Provides two stages of heating and two stages of cooling. Includes a key lock cover for setpoint protection. Y594G (T874G/Q674F) Thermostat/Subbase package for heat pump. Provides two stages of heating and one stage of cooling. Automatic changeover in heat or cool mode. Available in beige or Premier White® color. Y594R (T874R/Q674L) Thermostat/Subbase package for heat pump. Provides two stages of heating and one stage of cooling. Manual changeover in heat or cool mode. Available in beige or Premier White® color.
SUPER TRADELINE FEATURES: · SUPER TRADELINE package with cross reference label
and special instruction sheet. · SUPER TRADELINE model supplied with locking lever and
locking cover accessories. · Includes adjustable temperature locking stops. · T874D replaces T874A-F TRADELINE or standard models.

Tradeline Models

T874 THERMOSTAT · T874 TRADELINE models provide staged heat and/or cool
operation. See Table 1.

Table 1. Heating and Cooling Stages.

Models Heating Stages Cooling Stages

ABCDE F 1 1 2 2--2 1 2 1 2 2--

· T874A-F are standard models.

TRADELINE FEATURES:
· TRADELINE package with cross reference label and special instruction sheet.
· T874A,C model available with factory stops for DoD applications.
· T874A,C model available with adjustable temperature locking stops.

Q674 SUBBASE Q674 switching subbases provide system and fan switching. See Table 2.

Q674 A B C D E F G J L

Table 2. System and Fan Switching.

System Heat-Auto-Cool Heat-Off-Cool
Off-Auto None
Off-Heat-Auto-Cool Em. Ht.-Off-Heat-Auto-Cool
Off-Auto Em. Ht.-Auto-Off Em. Ht.-Heat-Off-Cool

Fan Auto-On Auto-On Auto-On
None Auto-On Auto-On
None Auto-On Auto-On

TRADELINE FEATURE:
· TRADELINE package with cross reference label and special instruction sheet.
· Q674A-E,G are standard (non-heat pump) models. Q674F,J,L are heat pump models.

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory). 2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada--Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

60-2485--8

2

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Standard Models

T874 THERMOSTATS

Models: See Table 3.
Electrical Rating: 24 to 30 Vac.
Switching: Coiled bimetal elements operate mercury switches.
Temperature Adjustment: Heating and cooling setting levers, with separate scales located on top of thermostat base. Common lever for heating and cooling on T874R; one cooling lever on T874E,V; and one heating lever on T874F,Q.
Dimensions: See Fig. 1.
Temperature: Scale Range: 42° to 88°F (6° to 31°C) standard; optional ranges available.

THERMOSTAT MOUNTED ON SUBBASE

FRONT
5-5/8 (143)

SIDE
3/8 (10)

Thermometer Range: 42° to 88°F (6 to 31°C)
Changeover Differential: 4°F (2°C) minimum between heating and cooling (5°F [3°C] on T874W). Levers can be set apart for greater separation.
Interstage Differential: Standard Models: Mechanical differential is 1°F (0.6°C)
between heating or cooling stages; operating differential is approximately 1.9°F (1°C) between stages in heating or cooling. Special Models: See Table 3. Finish: Beige or Premier White® finish.
Mounting Means: T874 Multistage Thermostat mounts on Q674 Subbase. Subbase mounts horizontally on wall or outlet box. Mounts on vertical outlet box with optional 193121A Adapter Plate Assembly.
SUBBASE
3-9/32 (83)

HEAT 50 60 70 80 50 60 70 80

50 60 70 80 COOL

1-1/2 (38)
3-1/2 (89)

3-7/16 (87)

FAN

AUTO ON

OFF EM. HT. HEAT AUTO COOL

FAN

AUTO ON

OFF EM. HT. HEAT AUTO COOL

1-7/8 (48) 2-3/16 (56)

5-1/8 (130)

M5849

Fig. 1. T874 Thermostat and Q674 Subbase dimensions in in. (mm).

Optional Specifications (T874 Only): Temperature scale ranges are 40° to 75°F (4° to 24°C) heat-
ing and 75° to 90°F (24° to 32°C) cooling with stop; 44° to 68°F (7° to 20°C) heating, 80° to 86°F (27° to 30°C) cooling; 6° to 29°C (43° to 85°F) Celsius scale; 3° to 22°C (38° to 72°F) and 26° to 32°C (78° to 90°F) cooling with stop. Nonadjustable factory-added stop limits heating setpoint to 72°F (22°C) maximum and cooling setpoint to 78°F (26°C) minimum. OEM customer personalization. Locking cover and locking lever (see Thermostat Accessories). Thermostat cover without thermometer. Adjustable locking temperature stops. Voltage heat anticipation for first or second stage heat or both. See Table 3. Fast cycling on heating stage(s) for electric heat applications. C815A Outdoor Thermistor for improved performance on specified models.

Thermostat Accessories: Locking Cover and Locking Lever Assembly: Part no.
194559R with thermometer; 194559S without thermometer. See Fig. 2. Includes cover, screws, and Allen wrench for locking cover. The screws must be used to assure proper operation. Adjustable Lever Stop: Part no. 4074ECK; includes lever stop and screws. Universal VersaguardTM Thermostat Guard: Includes wallplate, ring base, guard cover, tumbler lock, two keys and optional Honeywell logo insert. Double-wall construction provides extra measure of tamper-resistance. Tamperresistant lock; key cannot be removed without being in locked position. Vents in guard base allow airflow for optimum thermostat performance. See form 68-0104 for more information.
-- TG511A1000: Clear cover. -- TG511B1008: Opaque cover. -- TG511D1004: Painted steel (off-white) cover. See
Fig. 2.

3

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
Key Lock Cover: Part no. TG504A replaces existing T874 cover. Mounts on T874 base and covers thermostat settling levers and subbase switches. Includes LED window and two keys. Should not be used with 193121A Adapter Plate.

-- TG504A1025: Blank face, internal thermometer. -- TG504A1033: External thermometer. See Fig. 2.

194559R Locking Cover with Thermometer Allen Wrench

TG504A1033 Key Lock Cover with External Thermometer

TG511D1004 Includes Painted Steel Cover, Opaque Base and Wallplate

Fig. 2. T874 Thermostat accessories.

Table 3. T874 Thermostat Specifications.

Anticipation

System Stages

Heating (Adj) Cooling (Fixed)

Models and Options

Replaces Applications Heat Cool Other Stage 1 Stage 2 Stage 1 Stage 2

T874A--Standard and TRADELINE®. T872A

Standard

1

1 -- 0.1-1.2A -- 0-1.5A --

-- 72°F/78°F (22°C/26°C)setpoint

stops with locking cover.

-- Adjustable anticipator set 0.4A.

-- Adjustable locking temperature

stops (TRADELINE®).

-- 72°F/78°F (22°C/26°C) setpoint

stops with locking cover, no thermometer (for DoDa).

T874B--Standard and TRADELINE. T872B

Standard

1

2 -- 0.1-1.2A -- 0-1.2A 0-1.0A

T874C--Standard and TRADELINE. T872C Standard

2

1 -- 0.1-1.2A 0.1-1.2A 0-1.5A --

-- 72°F/78°F (22°C/26°C)set stops

with locking cover, no thermometer (for DoDa).

-- 12°F (7°C) differential between

H1 and H2 stages (T874C1125).

-- Fast cycling.

0.120.6A

0.120.6A

T874D--Standard and SUPER TRADELINE®. -- Adjustable locking temperature
stops (SUPER TRADELINE).

T872D Standard

2

2 -- 0.1-1.2A 0.1-1.2A 0-1.2A 0-1.0A

T874E--Standard and TRADELINE. T872E 2-Stage Cool -- 2 --

--

-- 0-1.2A 0-1.0A

T874F--Standard and TRADELINE. T872F 2-Stage Heat 2 -- -- 0.1-1.2A 0.1-1.2A --

--

-- Locking cover.

a Department of Defense. b Changeover stage operates with heating. c Fixed voltage type anticipation. d Changeover stage operates with heating; a secondary changeover is provided in cooling switch. e Provides night setback used with standard T874 and timer-operated remote switching. f Manual changeover stage--use Q674B,L subbase.
g Changeover stage operates with cooling.Q674 Subbases

60-2485--8

4

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

-- Fast cycling.

Electric Heat

T874G--Heat pump, cool changeover, with fast cycling.
-- Fixed anticipator for H2.
-- Fast cycling.

T872G Heat Pump or 2 Standard

1

1b

T874H--Use with Q674C.

T872H Heat Pump or 1 Standard

1

1b

T874J--Heat pump.

None Heat Pump 2

1

2d

T874K--Heat pump.

None Heat Pump 2

1

1b

T874L--Heat pump.

None Heat Pump 2

1

--

T874N--Heat pump, heat changeover.

T872N Heat Pump 2

1

1b

T874P--Heat pump.

None Heat Pump 2

1

--

T874Q--Night setback heating.

T872Q

Standard

1e -- --

T874R--Heat pump.

T872R Heat Pumpf 2

1--

T874S--Two-speed compressor heat None Heat Pump 2 pump.

2

1g

T874V--Standard.

None

Standard -- 1 --

T874W--Heat pump and standard. -- Night setback heating.

T872W Heat Pump or 3 Standard

2--

a Department of Defense. b Changeover stage operates with heating. c Fixed voltage type anticipation. d Changeover stage operates with heating; a secondary changeover is provided in cooling switch. e Provides night setback used with standard T874 and timer-operated remote switching. f Manual changeover stage--use Q674B,L subbase.
g Changeover stage operates with cooling.Q674 Subbases

0.120.6A

0.120.6A

0-1.0Ac 0.1-1.2A 0-1.0A

0-1.0Ac

0.1-1.5A
0.120.6A
--

0-1.0A

0-1.0Ae 0-1.5Ac 0-1.0Ac 0.1-1.2A 0-1.5Ac 0-1.5A 0.1-1.2A 0.1-1.2A 0-1.5A 0.1-1.2A 0.1-1.2A 0-1.0A

0.1-1.2A 0.1-1.2A 0-1.5A

0.1-1.2A --

--

0-1.5Ac 0.1-1.2A 0-1.5A 0-1.2Ac 0-1.2Ac 0-1.2A

--

-- 0-1.5A

0-1.2Ab 0-1.2Ac,d 0-1.2A

--
-- -- -- -- -- -- -- -- 0-1.0A -- 0-1.0A

Models: See Table 4.
Electrical Ratings: Switch Contacts: 2.5A at 30 Vac (7.5A inrush). LED Lights (Optional): 30 Vac.
Switches: Two slide switches (one switch on Q674G and K; no switches on Q674D) operated by levers. Switch position is shown on scaleplate.

Mounting: Designed to mount horizontally on an outlet box or the wall. Adapter plate assembly available for mounting on a vertical outlet box (see Subbase Accessory).
Finish: Dark brown or gray.
Dimensions in in. (mm): 3-1/2 (89)height; 5-5/8 (143) width; 5/16 (8) depth. See Fig. 1.

Table 4. Q674 Subbase Specifications.

Models and Options Q674A--Standard and TRADELINE®. -- Indicator LEDs. Q674B--Standard and TRADELINE. -- Provision for fan relay operation from
external fan switch (isolate G terminal). -- Indicator LEDs. Q674C--Standard and TRADELINE. -- Indicator LEDs.
Q674D--Standard and TRADELINE. -- For use when subbase switching is not
required.

Replaces Q672A

Application Standard

Switch Positions

System

Fan

HEAT-AUTO-COOL AUTO-ON

Q672B Q672C Q672D

Standard Heat Pump
Standard Heat Pump
Standard

HEAT-OFF-COOL
OVERRIDE-HEATOFF-COOL OFF-AUTO
OVERRIDE-AUTOOFF None

AUTO-ON AUTO-ON AUTO-ON AUTO-ON
None

5

Use With T874A-D
T874A-D T874G,H,L,R
T874P
T874A-H,W T874K,L,N
T874P T874A-F
60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Q674E--Standard and TRADELINE.
Q674F--Two LED models. -- EM.HT. light. -- Provision for AUTO fan operation in
EM.HT. Q674G--O and B terminals. Q674J--Provision for AUTO fan operation in EM.HT. -- Provision for outdoor thermistor. Q674K--Standard.

Q672E Q672F
Q672G Q672J
Q672K

Q674L--Provision for AUTO fan operation in EM.HT.
-- Indicator LEDs.

Q672L

Q674N--Standard.

Q672N

Q674P--Standard.

Q672P

Q674Q--Standard.

None

Q674R--Standard. -- International symbols.
Q674S--Indicator LED.

None None

Standard Heat Pump
Standard Heat Pump
Standard
Heat Pump
Evaporative Cooler
Heat Pump Fan Coil Fan Coil Standard

OFF-HEAT-AUTO- AUTO-ON COOL

OFF-EM.HT.-HEAT- AUTO-ON AUTO-COOL

OFF-COOL-AUTO- AUTO-ON HEAT-EM.HT.

OFF-AUTO

None

EM.HT.-AUTO-OFF AUTO-ON

EM.HT.-ON-OFF AUTO-ON

SUPL.HT.-ON-OFF AUTO-ON

OFF-HEAT-AUTOCOOL

None

OFF-WOOD-WOOD/ OIL-OIL

None

EM.HT.-HEAT-OFF- AUTO-ON COOL

SUPL.HT.-HEATOFF-COOL

AUTO-ON

EVAP-COOL-OFF- AUTO-ON HEAT

SUPL.HT.-HEATCOOL

AUTO-ON

HEAT-OFF-COOL LO-MED-HION

OFF-COOL

LO-HICONT.

HEAT-COOL

None

T874A-D T874C,D,G,N,S
T874A-F T874A,D,G,J
T874F
T874R,W
T874C T874G T874A T874V T874C

Optional Specifications (Q674 Only): Models available with up to four LEDs; for example, LEDs can
show EM. HT, AUX. HT, SERVICE, CHECK, FILTER, and LOCKOUT. See Fig. 3. System switching marked HEAT-OFF/RESET-COOL for systems requiring impedance relay reset. Available on Q674B only. G terminal isolated on heating to provide fan relay operation from external low voltage fan switch (Q674B only). Auto fan operation on both heat and cool.

L terminal is used for system monitoring devices. Common R terminal for heating/cooling. Changeover in cool or heat mode for heat pumps. Auto fan in EM.HT. for heat pumps.
Subbase Accessory: 193121A Adapter Plate Assembly for mounting on vertical outlet box. Assembly includes adapter ring and cover plate. Use to cover wall marks from replaced thermostat.

T874 Thermostat with One Setpoint Lever

T874 Thermostat with Separate
Heating and Cooling Levers

Fig. 3. Heating, cooling levers and system LED indicators.

Q674 Subbase with Four LEDs

60-2485--8

6

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

MERCURY NOTICE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube. If you have questions, call the Honeywell Customer Response Center at 1-800-468-1502.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Hazardous Voltage. Can damage heating/cooling system. 1. Disconnect power supply before beginning instal-
lation to prevent electrical shock or equipment damage. 2. Do not short across coil terminals on relay. This can burn out thermostat heat anticipator. 3. To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase. 4. Do not overtighten thermostat captive mounting screws because damage to subbase threads can result.
IMPORTANT An incorrectly leveled thermostat will cause the temperature control to deviate from setpoint. It is not a calibration problem.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature.
Do not mount the thermostat where it can be affected by: -- drafts or dead spots behind doors, in corners or under
cabinets. -- hot or cold air from ducts. -- radiant heat from the sun, fireplace, or appliances.

-- concealed pipes and chimneys. -- unheated (uncooled) areas such as an outside wall behind
the thermostat.

Mount Subbase
The subbase can be mounted on a vertical outlet box, horizontal outlet box or directly on the wall.
1. If the subbase is mounted on a vertical outlet box, order Honeywell part no. 193121A Adapter Assembly. See Fig. 4. The assembly includes an adapter ring, two screws and a cover plate to cover marks on the wall. Install the ring and cover plate on the vertical outlet box.

NOTE:

For a wall installation, hold subbase in position and mark holes for anchors. See Fig. 5. Wall anchors must be obtained from local hardware store. Be careful that the wires do not fall back into the wall opening. Set aside subbase. Drill four 3/16 in. (4.8 mm) holes and gently tap anchors into the holes until flush with the wall.

2. Pull wires through the cover plate (if used) and subbase cable opening. See Fig. 6.
3. Secure the cover plate (if used) and subbase with the screws provided. Do not fully tighten the subbase screws.
Level the subbase using a spirit level, see Fig. 7, and firmly tighten subbase mounting screws. The subbase mounting holes provide for minor out-of-level adjustments.

VERTICAL OUTLET BOX 1

MOUNTING SCREWS (2)

ADAPTER RING 2

COVER PLATE 2

1
HORIZONTAL OUTLET BOX

THERMOSTAT

SUBBASE
SUBBASE MOUNTING SCREWS (2)

HEAT

80 70 60 50

COOL 80 70 60 50

THERMOSTAT COVER

CAPTIVE MOUNTING SCREWS (2)

80 70 60 50

1 NOT INCLUDED WITH UNIT. 2 ACCESSORY PART AVAILABLE (193121A).

M6009

Fig. 4. Installing Q674 Subbase on outlet box.

7

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

WALL
WIRES THROUGH WALL OPENING

WALL ANCHORS (2)

MOUNTING HOLES

M926

SUBBASE

MOUNTING SCREWS (2)

Fig. 5. Installing Q674 Subbase on wall.

SPIRIT LEVEL

WIRING TERMINAL

THERMOSTAT CABLE OPENING

All wiring must comply with local electrical codes and ordinances.

IMPORTANT Use 18 gauge, solid-conductor wire whenever possible. If using 18 gauge stranded wire, no more than 10 wires can be used. Do not use larger than 18 gauge wire.

Follow equipment manufacturer wiring instructions when available. To wire subbase, proceed as follows:
1. Connect the system wires to the subbase as shown in the applicable diagram. A letter code is located near each terminal for identification. Typical terminal designation and wiring connections are listed in Table 5. The terminal barrier permits straight or wraparound wiring connection. See Fig. 7. The subbase can require one or more jumpers that may or may not be factory-supplied. See Fig. 8 and the wiring diagrams for specific terminals to be jumpered.

FOR STRAIGHT INSERTION­ STRIP 5/16 IN. (8 MM)

FOR WRAPAROUND­ STRIP 7/16 IN. (11 MM)

POST FOR

MOUNTING

MOUNTING

HOLES (4)

THERMOSTAT (2)

TO SPRING FINGER

CONTACTS ON

THE THERMOSTAT

(UP TO 12)

M927

Fig. 6. Subbase components and leveling procedure.

Wire Subbase
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.

BARRIER SUBBASE TERMINAL SCREW

M928

Fig. 7. Barrier configuration.

CAUTION
Equipment Damage Hazard. Never install more than one wire per terminal unless using factory-supplied jumper with spade terminal.
2. Firmly tighten each terminal screw. 3. Fit wires as close as possible to the subbase. Push
excess wire back into the hole. 4. Plug hole with nonflammable insulation to prevent drafts
from affecting the thermostat.

60-2485--8

8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
JUMPER WIRE (SUPPLIED WITH SOME MODELS) 1

1
1 TWO ADJACENT TERMINALS SHOWN JUMPERED ARE FOR EXAMPLE ONLY. COMPARE WIRING DIAGRAM AND SUBBASE TO IDENTIFY TERMINALS TO BE JUMPERED. M5899

Fig. 8. Jumper adjacent terminals for special system hookup using stripped wire 3/4 in. (19 mm). For nonadjacent terminals and using jumper wire supplied with subbase.

Table 5. Terminal Designationsa

Standard Terminal Designation B E G L O R
RC RH W1 W2 W3
Y1 Y2 Y3 X T

Alternate Designations or Customer Specials
K F
R V
H1, R3 H2, Y, R4
C1, M C2
X1,X2,C A
L, C, H P O
A, A1, A2, Z, C, L

Typical Connection Heating damper motor; changeover valve Emergency heat relay Fan relay coil System monitor Cooling damper motor; changeover valve Power connection to transformer (internally connected for heating and cooling) Power connection to cooling transformer Power connection to heating transformer Stage 1 heating control Stage 2 heating control Stage 3 heating controlb Stage 1 cooling control Stage 2 cooling control Stage 3 cooling control Clogged filter switch or common connection Outdoor thermistor HSII control panel Defrost Momentary circuit, changeover LEDs

a Other terminal designations can be used that are not listed on this table. Refer to the hookup drawing and internal schematic for exact connections.
b W3 controls the auxiliary heat like W2, and allows adding additional stages of auxiliary heat with outdoor thermostats while maintaining the proper second stage anticipation.

9

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 5. Terminal Designationsa

Standard Terminal Designation

Alternate Designations or Customer Specials

Typical Connection

T

External temperature readout, T relay

R1, R2

LO and HI speed fan relays

RS

Cooling contactor

Y

M

Compressor contactor

a Other terminal designations can be used that are not listed on this table. Refer to the hookup drawing and internal schematic for exact connections.
b W3 controls the auxiliary heat like W2, and allows adding additional stages of auxiliary heat with outdoor thermostats while maintaining the proper second stage anticipation.

Outdoor Disconnect
The National Electrical Code requires the installation of a disconnect switch within sight of the outdoor unit of an air conditioner or heat pump. The switch is for the safety of any technician working on the unit. The technician can assure that the unit remains unpowered.
Install and Adjust Stop Brackets
The stop brackets should be installed only if there is a need to restrict the adjustable range of the heating and cooling temperature setpoint levers. If adjustable lever stops are desired, order 4074ECK Envelope Assembly, which contains two adjustable lever stop brackets, one brass insert, one

mounting screw and two locking screws with insulated heads. When installed, the stop brackets limit the movement of the T874 HEAT and COOL levers.
TO INSTALL: 1. Remove the thermostat cover by pulling the bottom edge of the cover upward until it snaps free of the mounting slots. 2. Turn to the back of the T874 Thermostat. Locate the hole for the brass insert in the plastic base below the LED window. 3. Push the brass insert into the hole with finger. 4. Turn to the front of the T874 Thermostat. 5. Place the two stop brackets in position with the tabs in the slot between the HEAT and COOL levers. See Fig. 9.

HEAT LEVER

HOLES FOR INSULATED LOCKING LEVER SCREWS

COOL LEVER

HOLE WITH BRASS INSERT

BRACKET TABS

ADJUSTABLE LOCKING LEVERS

ADJUSTABLE LEVER STOP BRACKETS

BRACKET SLOTS

MOUNTING SCREW

NONADJUSTABLE STOPS
WITH LOCKING LEVER SCREWS 75°F (24°C) MAX. HEAT 75°F (24°C) MIN. COOL

ADJUSTABLE STOPS

NONADJUSTABLE D.O.D. STOPS
72°F (22°C) MAX. HEAT 78°F (26°C) MIN. COOL

Fig. 9. Range limiting and lever locking methods.

M7626

6. Insert the mounting screw into the two slots in the stop brackets and attach to the brass insert. Tighten the screw to pull the brass insert into the back of the ther-

mostat. 7. Loosen the mounting screw enough to free the stop
brackets for adjustment.

60-2485--8

10

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

8. Move the HEAT and COOL levers to the maximum temperature desired.
9. Slide the stop brackets until one rests against the HEAT lever and the other against the COOL lever.
10. Firmly tighten the mounting screw. 11. If the HEAT and COOL levers are to be locked in place
at a specific temperature, use the two insulated head screws supplied instead of the two adjustable lever stop brackets.

ALLEN RETAINING SCREWS (2)

CAUTION
Equipment Damage Hazard. Do not use standard screws that provide metal-tometal contact with the stop brackets. Short circuit and potential equipment damage can result.
Mount Thermostat
1. Remove the thermostat cover by pulling the bottom edge of the cover away from the base until it snaps free of the cover clip.
NOTE: The cover is hinged at the top and must be removed by pulling up at the bottom.
2. Carefully remove and discard the polystyrene packing insert that protects the mercury switches during shipment.
3. If LED indication (EM.HT., CHECK, etc.) is to be used with the Q674 Subbase, install the preprinted insert under the thermostat setpoint scale. To install, push both thermostat setpoint levers to the far ends of the thermostat. Use index finger to gently pull out the plastic setpoint scale about 1/4 in. (6 mm). Position the desired preprinted insert in the space above the LED lights. Reposition setpoint levers.
4. Turn over the thermostat base and note the spring fingers that engage the subbase contacts. Make sure the spring fingers are not bent flat, preventing proper electrical contact with the subbase.
5. Set the heat anticipator indicator(s) to the respective current setting of each stage. See Set The Heat Anticipator section.
6. If the thermostat provides optional locking cover assembly, start the Allen locking screws in the cover with the wrench provided. See Fig. 10.
7. Note the two tabs along the top inside edge of the thermostat base. The tabs fit into corresponding slots on top of the subbase. Mount the thermostat on the subbase.
8. Align the two captive mounting screws in the thermostat base with the posts on the subbase. Tighten both screws. Do not overtighten screws or damage to subbase posts can result.

M956
Fig. 10. Installation of locking cover assembly.
SETTINGS

CAUTION
Equipment Damage Hazard. On systems using a gas valve, never apply a jumper across the valve coil terminals, even temporarily. This can burn out thermostat heat anticipator(s).

Set the Heat Anticipator
Move the indicator to match the primary control current draw. When using a T874 Thermostat with two stages of heating, set each heat anticipator to match its respective primary control current draw. If you cannot find the current rating on the primary control, or if further adjustment is necessary, see NOTE and use the following procedure to determine the current draw of each stage.

The current draw of each heating stage must be measured with the thermostat removed and power on to the heating system.

1. Connect an ac ammeter of appropriate range between the heating terminals of the subbase: a. Stage 1--between W1 and RH or R; b. Stage 2--between W2 and RH or R c. Stage 3--between W3 and RH or R.
2. Move the system switch to HEAT or AUTO. 3. After one minute, read the ammeter and record the
reading: a. Stage 1--__________A; b. Stage 2--__________A; c. Stage 3--__________A.

NOTE:

If equipment cycles too fast, set the indicator to a higher current rating, but not more than one-half division at a time, and recheck the cycle rate. Most conventional two-stage heating equipment is designed to operate at three cycles per hour per stage, and one-stage heating equipment at six cycles per hour, at 50 percent load conditions. When using the T874 Thermostat in heat pump systems, set the heat anticipator at 140 percent of the actual primary control current draw to reduce the cycling rate. See Fig. 11.

11

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Most heat pump systems should cycle 2-1/2 to 3 times per hour.
4. Hang the upper edge of the thermostat cover on top of the thermostat base and swing the cover downward until it engages with the cover clip.
STAGE ONE ANTICIPATOR HEATING CONTROL

.12 .15 .2

.3

1.2.8.6.5 .4

.12 .10

1.2.8.6 .4 .3

.15 .2

STAGE TWO ANTICIPATOR HEATING CONTROL

MOVE INDICATOR TO MATCH CURRENT RATING OF PRIMARY CONTROL

M5069

Fig. 11. Adjustable heat anticipator scales.

Temperature Setting
Move the heating and cooling levers to the desired comfort positions. See Fig. 12. On some models with two stages of heating or cooling, the same lever controls both stages. The minimum differential between heating and cooling setpoints is 4°F (2°C) (5°F [3°C]) on T874W.
If model has optional screws to lock temperature control levers, loosen these screws before making temperature adjustment; tighten the screws when levers are set at desired position.

STAGE 1 HEATING
STAGE 3 HEATING

HEATING LEVER

COOLING LEVER

STAGE 1 COOLING

HEAT--heating system is automatically controlled by the thermostat. Cooling system is off.
AUTO--thermostat automatically changes between heating and cooling system operation, depending on the indoor temperature.
COOL--cooling system is automatically controlled by the thermostat. Heating system is off.
EM.HT.--emergency heat relay is automatically controlled by the thermostat. Cooling system is off. Compressor is de-energized.
SUPL.HT.--supplemental heat relay is energized. Cooling system is off. Compressor is de-energized.
WOOD--heating system is operating with only the woodburning stage.
OIL--heating system is operating with only the oil-burning stage.
WOOD/OIL--wood and oil stages operate sequentially; first the WOOD stage operates, then the OIL stage operates if the WOOD stage cannot handle the load.
EVAP--controls cooling system by water evaporation; see equipment instructions for further information.
OVERRIDE--night setback is disabled. ON--heating system is controlled by the thermostat. EM.
HT. or SUPL. HT. relay is not energized. FAN SWITCH positions control fan operation as follows:
ON or CONT.--fan operates continuously. AUTO--fan operates as controlled by the thermostat in
heat pump systems or conventional cooling mode; fan operates as controlled by the plenum switch in conventional heating mode. LO--fan operates constantly at low speed. MED--fan operates constantly at medium speed. HI--fan operates constantly at high speed.
To move the subbase switches to the desired control positions, use thumb and index finger to slide the lever. The lever must stop over desired function indicator position for proper circuit operation.
Spring return momentary position switching feature is available on selected subbase models. On these models, the fan switch is positioned to the right of the system switch. By moving the fan switch to the far right and releasing it, the ON position circuit makes. The lever springs back on release. This position is not marked on the subbase.

STAGE 2 HEATING

STAGE 2 COOLING

CAPTIVE MOUNTING SCREWS (2)

M7625

Fig. 12. Internal view of T874W (three stages of heating, two stages of cooling).

Subbase Setting
The subbase switching positions control the system operation as described below. SYSTEM SWITCH (see subbase for positions):
OFF--both the heating and cooling systems are off. If the fan switch is at the AUTO position, the cooling fan is also off.

Setting the Adjustable Differential
The adjustable interstage differential feature, on a selected T874D model only, can be identified by the scale and tension screw near the heating and cooling mercury switches. See Fig. 13. On this model, the number of degrees between the making of the first and second stage mercury bulbs is adjustable. This feature is especially useful if the first stage controls the comfort temperature, and the second stage controls the energy savings temperature. Timers, such as the S6005, for insertion between the first and second stage control points must be ordered separately.
Each mark on the scale represents 1°F (0.6°C) The differential is factory set at 2°F (1°C) the differential can be set as high as 12°F (7°C) To set the adjustable interstage differential, loosen the tension screw. See Fig. 13. Slide the adjustable scale to align with the number of degrees desired between stages. Use the lower edge of the tension screw bracket as a guide for alignment. In heating, slide the lever wider apart for a larger differential, or closer together for a

60-2485--8

12

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

smaller differential. In cooling, slide the lever closer together for a larger differential, or wider apart for a smaller differential. While supporting the scale with hand, tighten the tension screw.

IMPORTANT Support the scale with hand while tightening tension screw. See Fig. 13. Failure to do so can result in twisting and damaging bimetal coil.

TENSION SCREW

HEATING SETPOINT LEVER

HEAT
50 60 70 80

FIRST STAGE SWITCH

.2 1.5

SCALE
HEATING
TENSION SCREW ALIGN LOWER EDGE WITH SCALE NOTCH 10°F SCALE
1

1.2 .8 .6 .4 .3
SECOND STAGE (ADJUSTABLE) SWITCH
SLIDE LEVER WIDER APART FOR LARGER DIFFERENTIAL

CAUTION
Equipment Damage Hazard. When the thermostat is used to control a two-stage heating or cooling system, the second stage mercury bulb must never make before the first stage bulb, or severe equipment damage could result. To prevent this problem, provide at least 2°F (1°C) differential between stage-one and stage-two make points. Example: in heating, if stage-one makes at 70°F (21°C) stage-two should make at 68°F (20°C) or lower.
Verify the Adjustment
Heating
Start with the heating setpoint lever all the way to the left. Slowly move the lever to the right, just until the first stage bulb makes (mercury rolls to the right side of the bulb). Note the setting on the temperature scale. Slowly move the lever to the right until the second stage bulb makes. Note the setting on the temperature scale. The difference between the two temperatures is the interstage differential, which should match the number set on the scale with the tension screw.
Cooling
Start with the cooling setpoint lever all the way to the right. Slowly move the lever to the left, just until the first stage bulb makes (mercury rolls to the left side of the bulb). Note the setting on the temperature scale. Slowly move the lever to the left until the second stage bulb makes. Note the setting on the temperature scale. The difference between the two temperatures is the interstage differential, which should match the number set on the scale with the tension screw.
CHECKOUT

COOLING
TENSION SCREW ALIGN LOWER EDGE WITH SCALE NOTCH 4°F SCALE
1

SLIDE LEVER CLOSER TOGETHER FOR LARGER DIFFERENTIAL

1 EACH MARK ON THE SCALE REPRESENTS 1°F (0.6°C). M937
Fig. 13. Set adjustable interstage differential.

Heating
Move the system switch on the Q674 Subbase to HEAT or AUTO. Move the heat lever on the T874 about 10°F (6°C) above room temperature. See Fig. 12. Heating system should start and the fan should run after a short delay. Move the heat lever about 10°F (6°C) below room temperature. The heating equipment should shut off, and the fan should run for a short time, then shut off.
In heat pump applications, sometimes time delays are involved before the compressor and auxiliary heat are activated. This is due to a minimum-off timer, which prevents the compressor from restarting for five minutes from when the thermostat last turned off the compressor, or from when the system first received power.
Cooling

CAUTION
Equipment Damage Hazard. Do not operate cooling if outdoor temperature is below 50°F (10°C). Refer to manufacturer recommendations.

13

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Move the system switch on the Q674 Subbase to COOL or AUTO. Move the cool setting lever on the T874 Multistage Thermostat about 10°F (6°C) below room temperature. See Fig. 12. The cooling equipment and fan should start. If the system has two stages of cooling, both stages should start. Move the cool lever about 10°F (6°C) above room temperature. The cooling equipment and fan should stop.

Fan
Move the system switch to COOL, OFF, or AUTO. If necessary, position both temperature setting levers so that the heating and cooling equipment are off. Move the fan switch to ON or CONT. The fan should run continuously. When the fan switch is in AUTO, LO, MED, or HI position, fan operation is controlled by the heating or cooling system.

Outdoor Reset Thermistor (Where
Applicable)
If the system is supplied with a thermistor, it must be used; if not used, thermostat performance deviates radically from proper operation.

The proper thermistor operation must be verified to ensure the correct operation of the thermostat. Check thermistor operations as follows:
1. Disconnect the T wire on the subbase. 2. Use an ohmmeter to measure resistance between the
T wire and the A subbase terminal. 3. Take outdoor temperature at thermistor location and find
the correct thermistor resistance on the Fig. 14 chart. 4. If the resistance measured in step 2 and the calculated
resistance in step 3 vary by more than 15 percent, the thermistor requires replacement. Contact Honeywell or installing dealer for replacement packaged outdoor thermistor, part no. C815A1005.

THERMISTOR RESISTANCE (ohms)

4600 4400 4200 4000 3800 3600 3400 3200 3000 2800 2600 2400 2200 2000 1800 1600 1400 1200 1000
800 600 400 200
0 -20

C815A THERMISTOR RESISTANCE R = 400 ohms ± 10% AT 77°F (25°C)

0 20 40 60 80 100 120 140

TEMPERATURE OF THERMISTOR (°F)

M1590A

Fig. 14. Thermistor resistance chart.

CALIBRATION

Thermostat
T874 Thermostats are accurately calibrated at the factory. They do not have provision for field calibration.

Thermometer
The thermometer in your thermostat has been accurately calibrated at the factory. The thermometer should only need adjustment if it has been dropped or shifted due to mishandling.
If the setpoint lever and the thermometer reading do not agree, use the following procedure:
1. Remove the thermostat cover by pulling up from the bottom edge of the cover away from the base until it snaps free of the cover clip.
2. Set the thermostat cover on a table near an accurate thermometer.
3. Allow ten minutes for cover thermometer to sense area temperature; compare the readings. Be careful not to touch thermometer or breathe on it.
4. If the readings are the same, replace cover and put the system into operation.
5. If the readings are different, insert a small screwdriver in the thermometer slot and turn it until the thermometers have the same reading. See Fig. 15.
6. Replace thermostat cover and put the system into operation.
M5070
Fig. 15. Thermometer calibration.
UNDERSTANDING CIRCUITS
To understand wiring diagrams, it is important to know what all the symbols mean and how to trace the path of the circuits from the transformer. See Fig. 16 through 25.
Circuit descriptions and terminology are defined as follows: For standard heating-cooling circuits:
Auto changeover--refers to the presence of an AUTO position in the system switching (EX: Q674E with OFFHEAT-AUTO-COOL switching). The thermostat automatically changes between heat and cool modes as indoor temperature changes.
Manual changeover--requires a system switch movement to change mode (EX: Q674B with HEAT-OFF-COOL switching). T874D Multistage Thermostats with 2 heat or 2 cool switches are shown on most standard circuits. Most standard or TRADELINE® subbases (Q674A-E,G) can be used with T874A-F standard or TRADELINE

60-2485--8

14

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

thermostats. The schematics can be field-modified as required (EX: if T874C is being used, eliminate second stage of heat). For heat pump circuits: Cool changeover valve--operates on cooling. The reversing valve or relay is activated either by moving the system switch to COOL (manual changeover) or by a mercury switch that makes on a temperature rise (auto changeover). Heat changeover valve--operates on heating. The reversing valve or relay is activated either by moving the system switch to HEAT (manual changeover) or by a mercury switch that makes on a temperature fall (auto changeover). System monitor relay--optional equipment on some heat pumps includes an R4222P1065 or equivalent. This system monitor relay detects a malfunction in the compressor and indicates the malfunction by activating the EMERGENCY HEAT LED on the Q674 Switching Subbase. The system monitor relay is usually wired into the L terminal on the Q674. Each mercury switch is identified by function: H1--Stage 1 Heating. H2--Stage 2 Heating. H3--Stage 3 Heating. C1--Stage 1 Cooling. C2--Stage 2 Cooling. C3--Stage 3 Cooling. C/O--Changeover (heat pumps).
Each anticipator is identified and each switch affected is named (EX: H1 anticipator, C1 anticipator).
All T874 Multistage Thermostats use mercury switches. Each schematic indicates switch operation by being drawn in the open position with an arrow indicating operation with a temperature RISE or FALL.
One circuit has been selected that is typical of various models used with heat pumps. This circuit has been traced to illustrate the functions performed by these control systems.
Tracing Method:
1. Always begin at the system transformer or R terminal. You may want to draw the switch contacts in each switch position to aid in tracing. Colored pencils are helpful when only one copy of the circuit is available. See Fig. 16 for a description of the hookup symbols and Fig. 17 through 25 for typical hookups.
2. Completely trace only one circuit at a time (for example: heat or cool).
3. Connections are indicated by small dots at the point of intersection. If there is no dot, there is no connection.
4. The left portion of the circuit (the thermostat) contains the mercury switches. The heat switches make on a temperature fall, and the cool switches make on a tem-

perature rise. Fixed anticipation is represented by a zigzag line and adjustable anticipation is a zigzag with an arrow. The resistance of the fixed anticipator is so large it limits current so that a system relay cannot be pulled in from a circuit path going through the fixed anticipator. The relay can be pulled in through an adjustable anticipator because its resistance is generally 0 to 5 ohms. 5. The center portion (the subbase) contains the switches. The fan switch is above the system switch. The small circles on the switch represent the maximum possible contacts available on the Q674 Subbase. The larger circles represent the switch positions available on this particular Q674, with the solid circle representing where it is actually switched on the diagram.
NOTE: Solid circles are not interconnected electrically.
At the right, the relays and contactors are shown, attached to the proper terminals. The terminals are represented by large circles with terminal designations in capital letters. See Table 3 for the meaning of each lettered terminal.
Sometimes power for a fixed anticipator is brought through an off system relay like the changeover relay shown in Fig. 20. This current is kept low by the high resistance of the fixed anticipator so that relay does not pull in.
KEY TO HOOKUP SYMBOLS

TRANSFORMER (24 VAC SECONDARY)
RELAY OR CONTACTOR COIL

RELAY/CONTACTOR CONTACTS
B TERMINAL

LED

MERCURY SWITCH
FIXED ANTICIPATOR HIGH RESISTANCE (TYPICALLY 5 KILOHMS)
ADJUSTABLE ANTICIPATOR LOW RESISTANCE (TYPICALLY 0 TO 5 OHMS)

ODT OUTDOOR THERMOSTAT
EHR EMERGENCY HEAT RELAY
RTD TIME DELAY RELAY
RD DEFROST RELAY CHP PRESSURE SWITCH
LACO LOW AMBIENT CUTOFF
M5848

Fig. 16. Key to hookup symbols.

15

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

SUBBASE

SYSTEM COMPONENTS (HOT) L1 L2 1
R ODT 1

H1 C1
3

4
H2 ANTICIPATOR
5

H2

6

FALL

FAN SWITCH AUTO
ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

W3

W2

AUX. HT. LED (GREEN)

2

X

EM. HT. LED (RED)

L

G O

E

Y

B 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 AUXILIARY HEAT LED AVAILABLE ON SOME MODELS.

RTD 1

EHR 1 ODT 2 EHR 2

RTD 2
RTD 3 RTD 1

SYSTEM

MONITOR

RD

FAN RELAY

COOL CHANGEOVER VALVE

EM. HT. RELAY

LACO

CHP

COMPRESSOR CONTACTOR

M5072A

Fig. 17. Internal schematic and typical hookup of a T874R Thermostat and Q674L Subbase in a heat pump application. The thermostat provides two-stage heating and one-stage cooling manual changeover operates on cooling.

60-2485--8

16

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL
H1 C1

H1/C1 ANTICIPATOR
2
3

H2 FALL

4
H2 ANTICIPATOR
5
6

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO
ON

SYSTEM COMPONENTS

L1

R

(HOT)

ODT 1

L2

1

RTD 1 W3

EHR 1

RTD 2

ODT 2

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

W2 AUX. HT. LED (GREEN)
X EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

LACO Y
B

COMPRESSOR CONTACTOR

CHP M5840

Fig. 18. Tracing the changeover relay circuit.

THERMOSTAT

FALL

H1/ C1 ANTICIPATOR
2

H1 C1 3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

R
RTD 1 W3

ODT 1 EHR 1

L1 (HOT)
L2 1 RTD 2

ODT 2

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E
LACO Y B

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP M5841

Fig. 19. Tracing the heat 1 and anticipation circuit.

17

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1/ C1

ANTICIPATOR

FALL

2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE

SYSTEM COMPONENTS

FAN SWITCH AUTO
ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

R
RTD 1 W3

ODT 1 EHR 1 ODT 2

L1 (HOT)
L2 1 RTD 2

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

LACO Y
B

COMPRESSOR CONTACTOR

CHP M5842

Fig. 20. Tracing the heat 1 anticipation circuit.

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

L1

R

(HOT)

ODT 1

L2 1

RTD 1 W3

EHR 1

RTD 2

ODT 2

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

LACO Y
B

COMPRESSOR CONTACTOR

CHP M5843

Fig. 21. Tracing the heat 2, anticipation and AUX. HT. LED circuit.

60-2485--8

18

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

R RTD 1

ODT 1 EHR 1

L1 (HOT)
L2 1 RTD 2

W3

ODT 2

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E
LACO Y
B

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP M5844

Fig. 22. Tracing the emergency heat and EM. HT. LED circuit.

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO

SYSTEM COMPONENTS

R
RTD 1 W3

ODT 1 EHR 1

L1 (HOT)
L2 1 RTD 2

ODT 2

ON

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E
LACO Y
B

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP M5845

Fig. 23. Tracing the cooling circuit.

19

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

4
H2 ANTICIPATOR
5

H2

6

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH AUTO ON

SYSTEM COMPONENTS

R RTD 1

ODT 1 EHR 1

L1 (HOT)
L2 1 RTD 2

W3

ODT 2

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

LACO Y
B

COMPRESSOR CONTACTOR

CHP M5846

Fig. 24. Tracing the auto fan circuit.

SUBBASE
FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

R
RTD 1 W3

ODT 1 EHR 1 ODT 2

L1 (HOT)
L2 1
RTD 2

W2 AUX. HT. LED (GREEN)
X
EM. HT. LED (RED)
L

RTD 1
SYSTEM MONITOR

G O

E

EHR 2

RTD 3

RD FAN RELAY

CHANGEOVER VALVE

EM. HT. RELAY

LACO Y
B

COMPRESSOR CONTACTOR

CHP M5847

Fig. 25. Tracing the fan on circuit.

60-2485--8

20

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

OPERATION
Heat Anticipation/Cool Anticipation
When controlling a heating unit with a thermostat, the temperature does not remain exactly at the thermostat setpoint, but varies within a certain temperature range. Heat anticipation is added to the thermostat to reduce this range.
The anticipator is a small resistive heater in the thermostat that heats when the system is on (heat mode) or off (cool mode). The heat produced by the anticipator raises the internal bimetal temperature slightly faster than the surrounding room temperature. The thermostat anticipates the need to shut off the heating system sooner than it would if affected by room temperature only.
There are two types of heat anticipation, adjustable and fixed.
Adjustable anticipation is also called current anticipation. See Fig. 26. The heater is in series with the mercury switch and heating primary. The pointer is adjusted to match the current draw of the primary control, and the correct amount of heat is added for proper cycle rates.
L1 L2 (HOT)

H1 ANTICIPATOR

H1 FALL

STAGE 1 HEAT RELAY

M5823

Fig. 26. Adjustable anticipation heater in series with load.

Fixed anticipation is also called voltage anticipation. See Fig. 27. The heater is in parallel with the primary control and is
not affected by the current draw of the primary. It establishes
the proper cycle rate for any application.

L1 L2 (HOT)

FALL

STAGE 1 HEAT RELAY

H1 ANTICIPATOR H1
M5824
Fig. 27. Fixed anticipation heater in parallel with load.

Heat anticipators add heat during the call for heat. Cooling anticipators are activated while the air conditioner is off. See Fig. 28. This heater makes the thermostat think it is warmer than it really is, and brings it on sooner than the bimetal alone would.
L1 L2 (HOT)

RISE C1

STAGE 1 COOL RELAY

C1 ANTICIPATOR

M5825

Fig. 28. Internal cooling anticipation schematic.

Interstage Differential
The mercury switch of each stage of heat makes at a slightly different temperature; that is, the mercury makes the contacts of the first stage bulb at one temperature, and the second stage bulb at another temperature. The difference between these two temperatures is the interstage differential.
Interstage differential is the difference between the two make points when the bulbs are controlled by the heating of the bimetal and the action of the heat anticipator. The interstage differential is 1.9°F (1°C) between the stages of heating or the stages of cooling for most models.
Mechanical differential is the difference between the make and break points of each switch. The mechanical differential for the T874 is 1°F (0.6°C) between the stages of heating or between the stages of cooling for most models.

Droop
The addition of anticipator heat to the bimetal causes a control factor called droop.
As the weather grows colder, the heating appliance must operate longer and more frequently. More heat must be added to the bimetal. The bimetal now thinks it is warmer than it really is, and actual room temperature is controlled at a lower temperature than the setpoint indicates. At 100 percent heat load, this droop can be significant.
The C815A Outdoor Reset Thermistor is used in heat pump systems to minimize droop. Without some method of countering this situation, the occupant could notice the temperature offset.

Outdoor Reset
Some T874/Q674 models are intended for use with the C815A Outdoor Thermistor. The outdoor thermistor provides significantly improved thermostat performance when compared to conventional multistage thermostats. The C815A is usually located in the heat pump condensing unit outdoors.

21

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

CAUTION
Equipment Damage Hazard. Due to calibration techniques used for T874 Thermostats with outdoor reset, the C815A Thermistor must be wired into the system at all times. Failure to do so will result in serious degradation of performance.

Service and Replacement of C815A Outdoor
Thermistor
To check and verify thermistor operation, perform the following steps:
1. Disconnect wire from T terminal on subbase. 2. Measure resistance with ohmmeter across the T sub-
base wire and X subbase terminal. 3. Take outdoor temperature measurement at thermistor
location and find correct thermistor resistance on the chart in Fig. 29. 4. Compare resistance on the chart with measured resistance. Replace C815A if resistance varies more than 15 percent. Contact installing dealer for packaged replacement outdoor thermistor.

THERMISTOR RESISTANCE (ohms)

4600 4400 4200 4000 3800 3600 3400 3200 3000 2800 2600 2400 2200 2000 1800 1600 1400 1200 1000
800 600 400 200
0 -20

C815A THERMISTOR RESISTANCE R = 400 ohms ± 10% AT 77°F (25°C)

0 20 40 60 80 100 120 140

TEMPERATURE OF THERMISTOR (°F)

M1590A

Fig. 29. Thermistor resistance chart.

Features
Two of the features of the T874/Q674 include LED indicators and restricted setpoint.

LED Indicators
The light-emitting diodes (LED) indicators on the subbase light on command when something specific happens in the system. See Fig. 30.
Up to four different LEDs are available. The thermostat has a clear lens window for viewing each LED. On TRADELINE models, a small insert is used so the LED function desired can be selected. This must be done during installation.
A blank insert is factory-installed in some T874 models. To remove it, push both temperature setting levers to the far ends of the thermostat. Use index fingernail to gently pull out the scaleplate a fraction of an inch. Turn thermostat upside-down, and the blank insert falls out.

A strip of four inserts is included with TRADELINE T874. Drop a strip into the recessed area behind the scaleplate so selected LEDs show. Make sure insert is completely seated in recessed area. Let scaleplate pop back; then set levers to desired position. · FILTER LED lights when the filter is clogged and needs
replacement. · CHECK LED lights when something needs to be checked
or done to maintain efficient operation of system. See heating system instructions for CHECK LED meaning. · EM. HT. LED lights when the emergency heat is operating. · SUPL. HT. LED lights when the supplemental heat is operating. · LOCKOUT LED lights when the system is shut down and needs maintenance. · AUXILIARY HEAT LED lights when the auxiliary heat is operating. · SERVICE or MALFUNCTION LED can have several meanings. Consult heating system instructions.
LEDs cannot be replaced or added in the field.
LEDS

80

EM.

AUX

HEAT FILTER SERV. HEAT

50 60 70 80

COOL

M5830
Fig. 30. T874/Q674 LED location.
Restricted Setpoint (DoD)
The Department of Defense (DoD) models are equipped with a restricted setpoint feature for fuel efficiency.
Fixed stops are factory-set so setpoint levers cannot be set above 72°F (22°C) on heating, or below 78°F (26°C) on cooling.
Applications
The T874/Q674 can be applied to standard residential systems for automatic or manual changeover, to commercial rooftop applications, or to heat pump applications.
Changeover on Standard Residential Systems
In a standard residential heating-cooling circuit, changeover between heating and cooling can be done either automatically or manually.
Automatic changeover is done by an AUTO position on the subbase system switch. See Fig. 31. When the switch is in the AUTO position, the thermostat automatically changes between heat and cool modes, depending on the indoor temperature.

60-2485--8

22

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

When enthalpy is low enough, the thermostat and a sensor tell the economizer damper to open to let in cool air from the outside. When enthalpy is high, the thermostat and sensor tell the damper to close. No more outside air comes in, so the air conditioner is used instead.

OFF EM. HT. HEAT AUTO COOL M5828
Fig. 31. System switching for automatic changeover. Automatic changeover is frequently used in areas where there are large temperature differences in 24 hours. Some uses for the automatic changeover feature are in the southern states (cool in the morning and hot in the afternoon) and in commercial applications. Manual changeover requires a system switch movement to change the mode. See Fig. 32. Most manual changeover switches consist of HEAT-OFF-COOL choices. For heating, switch to HEAT. For cooling, switch to COOL. It is not automatic. Manual changeover is often used in areas where the temperature is relatively stable between day and night.
OFF EM. HT. HEAT COOL M5829
Fig. 32. System switching for manual changeover.
Commercial Rooftop Application
The T874 can be used as part of a commercial rooftop application to run mechanical cooling. An economizer is often used as part of a rooftop application to save on air conditioning. See Fig. 33.
OUTDOOR AIR

H205 OR H705 ENTHALPY CONTROL

RETURN AIR

DISCHARGE AIR SENSOR DOWNSTREAM FROM THE EVAPORATOR COIL
M5827A

Fig. 33. Typical commercial rooftop economizer application.

Enthalpy is the temperature and humidity of the air. A more accurate analysis of the suitability for free cooling can be made by monitoring the enthalpy.

Heat Pump Application
A heat pump system operates much like an air conditioner. However, the heat pump is capable of moving heat in two directions; from inside the home to outdoors for cooling, or from outdoors to inside for heating.
The heat pump can be controlled by separate relay/contactor components, which are energized or de-energized by the T874.
Changeover between heating and cooling for heat pump circuits can be accomplished either manually or automatically.
Manual changeover control requires a system switch movement to change the mode. The reversing valve is activated by moving the system switch to COOL for cooling or to HEAT for heating operation.
Automatic changeover is accomplished by one of the mercury bulb switches in the thermostat. On a system with automatic changeover on cooling, the changeover valve is energized by a mercury switch that makes on a temperature rise. On heating, the changeover valve is energized by a mercury switch that makes on a temperature fall.
A description of the methods used to control heat pumps follows.
Space Temperature Sensing Low Voltage Controls
Control systems for heat pumps usually utilize low voltage control circuits. The variety of control functions required and the relative complexity require a versatile and economical method of control. There are several interlocks and indication functions that would be more difficult and expensive to wire in line voltage circuits. Low voltage controls have the precision and flexibility needed.
The thermostat used is a low voltage device that has good temperature sensitivity and several manual and automatic switching capabilities.
Two-Stage Thermostat
In most installations, the heat pump itself requires auxiliary heat, usually in the form of electric strip heaters, to carry the building heating load at design conditions. Since the heat pump is usually more efficient, the control strategy is to run the heat pump whenever possible and the auxiliary heat only when necessary--during very cold weather or if the heat pump fails. Usually the auxiliary heat is used only below the balance point (temperature at which the heat pump cannot handle heating load by itself).
A two-stage thermostat makes this possible. The two stages make sequentially as the temperature drops. There is a degree or two between stages so that the second stage (the

23

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

one controlling the auxiliary heat) makes only when the heat pump alone cannot handle the load. That is how the strategy of using the most economical heat first is implemented.
Cycling Rate
Normally, thermostat anticipation is set to cycle a fossil fuel furnace about five or six times an hour (at 50 percent load). This provides a reasonable balance between comfort, stability and economy.
A heat pump, being a mechanical refrigeration system, should be cycled at a rate of 2-1/2 to 3 times an hour. With a T874, this is accomplished by setting the anticipator at the total current draw of the controlled device (the contactor and possibly the changeover relay or valve). Most likely, the compressor operates from the first stage of the thermostat.
The second stage normally controls the auxiliary heaters. This heat anticipator can be set for the current draw of the electric heat primary, and produces good control.
Voltage Anticipation
Although not a specific requirement for heat pumps, several models of the T874 have voltage heat anticipation instead of current anticipation.
With voltage anticipation, the amount of heat added to the thermostat is constant no matter which load is connected to it. The anticipator realizes a constant voltage and produces a constant amount of heat during the ON cycle. This allows the cycling rate to be designed into the thermostat. The heat pump manufacturer is assured of correct performance independent of later thermostat adjustments.
Outdoor Reset
Outdoor reset, which a C815A Outdoor Thermistor makes possible, is sometimes applied in heat pump systems to help minimize the effect of the differential between stages. It takes 2°F (1.1°C) change in temperature to bring on the second stage and full heating. Added to a certain amount of droop under high loads, there can be a large offset between the setpoint and room temperature.
Without some method to counteract this situation, the temperature offset from the setpoint could be as much as 6°F (3.3°C) under high load conditions. It is not likely that the occupants accept this variation without making frequent thermostat setting changes.
Outdoor reset has the effect of raising the setpoint at cold outdoor temperatures. Then, even with a few degrees droop, the space temperature stays near the desired setting.
This is done by calibrating the thermostat high by 5°F (3°C)-- the amount of expected offset. This offset compensates for differential and droop at high load factors so the thermostat switches at the setpoint. At warm temperatures, heat is added to the thermostat to compensate for this offset; at cold temperatures, the extra heat is automatically removed. The effect is the same as raising the setpoint as the outdoor temperature goes down.

This is particularly important on the 3-stage T874. The additional stage means that more droop is introduced when the system is in operation. That is the reason the TRADELINE T874W is sold in a package with the outdoor sensor and the correct subbase.
Outdoor Reset--How it Works
The heater in the thermostat is connected in series with a thermistor sensor that measures outdoor temperature. See Fig. 34. In warm weather, the thermistor has very low resistance, permitting a large current flow in the heater, which generates a relatively large amount of heat in the thermostat.
In cold weather, the outdoor sensor has high resistance, which results in low current flow and little or no heat being added to the thermostat. This raises the control point, overcoming the effects of droop and interstage differential.
L1 L2 (HOT)

RESET HEATER

C815A OUTDOOR THERMISTOR SENSOR

M5826
Fig. 34. Location of thermistor.
Changeover
Changeover between heating and cooing can be accomplished either automatically or manually, depending on the application. Changeover can occur in heating or cooling.
The changeover valve is energized as long as the subbase function switch is in the appropriate position when manual changeover is used. If a system manually changes over on cooling, the valve energizes whenever the subbase switch is in the cooling mode.
One of the mercury bulb switches is used for control when the thermostat has automatic changeover. When the automatic changeover is in cooling, the changeover valve is energized when the first stage cooling switch makes. The second stage switch turns on the compressor.
It is more common with new equipment to find that changeover occurs with cooling; that is, the changeover valve is energized to produce cooling.
Whether automatic or manual changeover is used and whether the reversing valve is energized with cooling or with heating, a heat pump system can be controlled by the appropriate T874 Multistage Thermostat.

60-2485--8

24

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Low Temperature Lockouts
Some manufacturers of heat pumps have previously controlled their units so the compressor was locked out below a specified outdoor temperature. This was done because of the stress placed on the compressor by the very cold temperatures, and the fact that efficiency drops off at low temperatures.
Other manufacturers say that although efficiency is low at cold temperatures, the problem of starting the cold compressor is the most critical point. It is more important to keep the compressor running than to shut it off and try to restart it when the temperature warms up to +10°F (-12°C). Also the crankcase heater, which can run only when the compressor is off, compensates for the lower compressor efficiency. So, it is equitable to let the heat pump run even with a coefficient of performance (COP) slightly less than one, rather than to turn it off and have to run the crankcase heater.
NOTE: To determine the COP of a heat pump, use the following formula:
COP = Btu Out/Btu we pay for or Btuh Capacity
Unit Wattage x 3.413 Btu/Watt
Another factor favoring this control strategy is that newer heat pump designs maintain a level of efficiency even at outdoor temperatures well below zero. Some brands do not reach 1.0 COP until -25°F (-32°C).
Virtually all manufacturers now let the heat pump run continuously rather than lock it out at cold temperatures.
Heat Pumps with Dual Compressors
Staging residential sized heat pumps is a requirement that developed from the need to make heat pumps as efficient as possible. One of the methods used to improve overall seasonal efficiency is to reduce the amount of time the machine is operating in a transitional mode. Transitional mode is starting and stopping in addition to recovering from defrost. Under light loads, when the heat pump is cycling on and off, this can be a significant amount of time and can result in a significant efficiency reduction. Capacity control is one way to reduce the cycling rate and improve the efficiency.
Additional capacity control methods used on other refrigeration systems (unloading, multiple compressors) are not as likely to be seen on residential heat pumps.
With a single-stage heat pump, the compressor is normally controlled by the first stage and the auxiliary heat by the second stage. The T874G, N and R Thermostats are used for this purpose.
With a two-stage compressor, the two thermostat switches control the individual compressor stages. Auxiliary heat is controlled along with the compressor stage-two, by the thermostat second stage. It comes on with the compressor high speed if an outdoor thermostat--wired in series with it-- is made. See Fig. 35.

THERMOSTAT HEAT 2 HEAT 1

COMP. STAGE 1

OUTDOOR THERMOSTAT

COMP. STAGE 2

AUXILIARY HEAT

M5838

Fig. 35. Two-stage heat pump with two-stage thermostat.

The outdoor thermostat is set at the balance point with both heat pump stages running. So if the heat pump can control the heating load down to +20°F (-7°C), the auxiliary heat comes on with the second stage of the compressor.

In effect, this control strategy changes the heat input of the second stage, depending on the amount of heat needed. Additional stages of auxiliary heat can be added with or without the control of more outdoor thermostats, See Auxiliary Heat section.

Another way to control a two stage heat pump is with a threestage thermostat. The T874W is designed for this application as well as others. See Fig. 36.

The advantage of this system is that no auxiliary heat is used until there is an actual demand from the controlled space.

THERMOSTAT HEAT 3 HEAT 2 HEAT 1

COMP. STAGE 1
COMP. STAGE 2

AUXILIARY HEAT
M5837
Fig. 36. Two-stage heat pump with three-stage thermostat.
Two speed Heat Pump
One way to control capacity is to use a two-speed compressor. The compressor runs at low speed for stage-one heating and cooling. The compressor runs at the low speed instead of cycling the heat pump on and off under some light load conditions.
The high speed is stage-two cooling. The compressor runs on high speed when loads increase so the low speed can no longer handle the cooling load. This reduces cycling rate and improves capacity.

25

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Defrost Control
In some regions, during half or more of the heating season, the outdoor coil operates below 32°F (0°C) Frost or ice builds up on the outdoor coil of a heat pump similarly to the frost buildup in a household refrigerator. Eventually, this accumulation of ice interferes with efficient heat transfer from the outdoor air to the coil and refrigerant. Defrosting is occasionally required to remove this ice, and restore the heat pump ability to absorb heat from the air.

Defrosting
A heat pump defrosts its outdoor coil by temporarily switching to the cooling mode, which causes hot gas from the compressor to be directed to the outdoor coil instead of to the indoor coil so the heat pump is taking heat from the home to warm up the outdoor coil. Defrosting is the greatest detriment to heat pump efficiency.

Defrost Control Functions
Besides changing over to the cooling mode, defrosting requires several more control initiated actions that follow.

OUTDOOR FAN
When defrosting has begun, it is standard practice to turn off the outdoor fan to speed up the melting process. A separate defrost relay is required to control that fan. See Fig. 37. Other contacts can be needed on the defrost relay to power the changeover valve or power part of the auxiliary heat.

CONTACTOR

COMPRESSOR MOTOR

CONTROLLED BY OUTDOOR DEFROST RELAY FAN MOTOR
M5839
Fig. 37. Outdoor fan with defrost control.
AUXILIARY HEAT DURING DEFROST Most pump manufacturers bring on some auxiliary heat during defrost, although this is not a universal practice. Some rely on the second stage of the thermostat to call for auxiliary heat as needed. Since the heat pump is operating in the cooling mode to defrost, it is delivering cold air to the living space. Auxiliary heat is used to offset this cooling. It requires another normally open contact on the defrost relay. See Fig. 38.

L1 L2 (HOT)
TRANSFORMER

THERMOSTAT HEAT 2 HEAT 1

DEFROST RELAY CONTACT

AUXILIARY HEAT RELAY

M5835

Fig. 38. Auxiliary heat with defrost control.

WHEN TO DEFROST
Timely defrosting is an essential component of effective heat pump operation. Failure to defrost often enough permits too much ice to accumulate on the coil. At the very least, this hurts efficiency; at worst, it results in compressor damage. Insufficient defrosting is a condition the heat pump manufacturer wants very much to avoid.

A 50 percent reduction in outdoor airflow is the maximum that would be tolerated. So the designer of a heat pump would select a control point that puts the system into defrost when airflow through the outdoor coil approaches half its normal level. Restricted airflow causes a greater load on the compressor; the outdoor coil runs colder, suction pressure is lower and the motor runs hotter.

At the other end of the scale, defrosting too often hurts the overall energy efficiency of the system. Consider that in terms of heating the building, defrosting is a big loss. Not only does the system stop heating, but it actually moves heat out of the building. If electric strip heat is used, it is a further waste because its COP is 1.0 and not the 2.0 or more COP realized if the heat is provided by the heat pump.

So, concern for equipment safety suggests fairly frequent defrosting while economy of operation argues for fewer defrost cycles. Since the equipment manufacturer chooses, the balance is usually tipped in favor of more frequent defrosting to avoid the possibility of damaging the compressor.

Auxiliary Heat
Except in warm climates, all air-to-air heat pump installations require auxiliary heat capability. Electric resistance heaters can provide this auxiliary heat.
The electric heaters (sometimes called strip heaters) usually are supplied in 5 kW units or strips (about 17,000 Btu). The indoor unit of the heat pump is designed to accommodate various electric heat units so it can be used in variously sized buildings in different parts of the country.

Two-Stage Thermostat
The most common heat pump control strategy is for the thermostat first stage to switch the compressor and the second stage to switch the auxiliary heat. See Fig. 39.

60-2485--8

26

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT HEAT 2 HEAT 1

COMPRESSOR CONTRACTOR

CONTROLS AT 65°F (18°C)

AUXILIARY HEAT RELAY

CONTROLS AT 63°F (17°C)
M5836

Fig. 39. Auxiliary heat in two-stage thermostat.

This method keeps the auxiliary heat off until the heating load is large enough to demand 100 percent heat pump operation. That demand is measured by the thermostat and is the actual heat requirement of the space. The two-stage thermostat requires about a 2°F (1.1°C) room temperature drop to bring on the second stage.

Stage or Time Modulated Control
There are two different ways to control auxiliary heat, staged or time modulated control.
Outdoor thermostats are used to switch additional increments of electric heat into the thermostat circuit as the outdoor temperature gets lower. All increments of auxiliary heat are still controlled by stage-two of the thermostat but only if the outdoor temperature requires the additional capacity. See Fig. 40.

THERMOSTAT HEAT 2 HEAT 1

COMPRESSOR CONTACTOR

20°F (-7°C) OUTDOOR THERMOSTATS
5°F (-15°C)

AUXILIARY HEAT RELAY 1
AUXILIARY HEAT RELAY 2
AUXILIARY HEAT RELAY 3

M5834

Fig. 40. Outdoor thermostats for auxiliary heat.

The rationale for this system is that it very closely matches the system capacity to the heating load of the building. By calculating the heat loss of a building, the installing contractor can pick the theoretical outdoor temperature at which to permit each additional unit of electric heat to be operated by the second stage of the room thermostat.

The disadvantage of this system is that it can require several outdoor thermostats. Also, since the unit is operating most often at nearly full capacity, the thermostat is on longer which results in more droop, with a little more offset from the thermostat setpoint.
In addition, the capacity is tied to theoretical load, based on heat loss calculations. Normally this is very close to the actual load, but there are times where the second stage is switched on too soon (no harm done) or too late (the building gets cold).
The T874 Thermostat produces time modulated control, which is the on time of the thermostat changing during each cycle as the load changes. The on time of the heating system is directly proportional to the heating load of the building. As an example of the quality of time modulated control, consider the typical gas furnace. It can have a capacity of 100,000 Btu (293 kW), which is controlled On-Off. The output is 100,000 Btu (293 kW) or nothing. A quality thermostat controls so closely that the occupants rarely detect changes in room temperature.
The same is true with 50,000 or 60,000 Btu (146.5 or 178.8 kW) of heat pump auxiliary electric heat. The T874 can provide the same high quality control.
This scheme also eliminates the need for outdoor thermostats and thus offers the manufacturer an opportunity to reduce unit cost. One disadvantage is that a thermostat jiggler can be demanding more kW of strip heat when chilly.
The method any particular manufacturer selects depends on which arguments it finds persuasive and the opinions of its distributors and dealers.
Three-Stage Thermostat
A definite improvement in quality of control and economy can be achieved with a three-stage thermostat (T874W), which is especially true with heat pumps using dual compressors.
Three-stage control permits both the heat pump and the auxiliary heat to be tied directly to the demand of the controlled space. With a two-stage compressor, maximum (100 percent) heat pump operation is required before auxiliary heat is brought on.
Emergency Heat
Some provision is generally required to back up the compressor in the event of a failure during the heating season. In fact, it is quite common to find that local building codes or electric utilities require that a specified percent of the building heating requirements be available from emergency heat--a source other than the heat pump compressor. Almost universally, the source is electric resistance heaters. Typically, the requirement is for 70 or 80 percent of the building heating needs.
Switching to Emergency Heat
Conventional heat pump control (thermostat logic) usually includes a manual subbase switch to bring on the emergency heat.
In one control strategy, the emergency heat relay is turned on by the EM.HT. selector switch on the thermostat subbase. The compressor is prevented from running. The electric heaters are cycled as they normally would be by the second stage of

27

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

the thermostat. A set of contacts on the emergency heat relay is used to bypass each outdoor thermostat so that all electric heat is under immediate thermostat stage-two control. So the emergency heat relay simply bypasses the outdoor thermostats. See Fig. 41.
In the second method, the emergency heat relay is cycled directly by the thermostat mercury bulb. In this hookup, the relay is controlled by the thermostat first stage. The emergency heat relay energizes all of the auxiliary heat relays on a call for heat. See Fig. 42.
So the emergency heat is controlled by the first stage of the thermostat. The emergency heat relay energizes all of the electric strip heaters so the heat and the indoor fan come on together as soon as the first stage calls for heat.
With the first method, the fan remains on (being controlled by the first stage of the thermostat) and the electric heaters cycle on and off with the second stage.
In either case, a subbase indicator light is turned on whenever the function switch is in the emergency heat (EM.HT.) position.

THERMOSTAT

FUNCTION SWITCH

HEAT 2

HEAT 1

COMPRESSOR

OUTDOOR THERMOSTAT

AUXILIARY HEAT RELAY 1
AUXILIARY HEAT RELAY 2

EMERGENCY HEAT RELAY CONTACT

EMERGENCY HEAT RELAY
M5833

Fig. 41. Emergency heat relay that bypasses the outdoor thermostats.

THERMOSTAT

FUNCTION SWITCH

HEAT 2

HEAT 1

24 V
EMERGENCY HEAT RELAY CONTACT
COMPRESSOR

AUXILIARY HEAT RELAY

EMERGENCY HEAT RELAY

M5832

Fig. 42. Emergency heat relay that energizes all of the auxiliary heat relays on a call for heat.

Crankcase Heat
In any mechanical refrigeration system, refrigerant tends to migrate to the coldest part of the equipment and condense there. In a heat pump, this coldest spot could be the compressor because it is usually outdoors. In addition, the oil in the compressor crankcase is capable of absorbing a high concentration of refrigerant. On compressor startup, there are two risks: (1) the liquid refrigerant, which is noncompressible, can be drawn into the cylinder, and (2) considerable oil can be entrained in the refrigerant and swept out of the crankcase through the changeover valve and dispersed in the piping and coils.
So the migration of refrigerant to the crankcase is undesirable because it can interfere with system lubrication and because the liquid refrigerant must be kept from going through the compressor.
Adding a crankcase heater creates enough temperature differential to prevent this migration because the compressor is no longer the coldest part of the system so refrigerant does not migrate to it.

Compressor Fault Relay
Another very simple method of detecting a compressor failure has been developed. It uses the voltage developed across the capacitor in a permanent split capacitor compressor motor.

The principle involved is that virtually all serious problems reduce the voltage across the motor capacitor. By carefully selecting the correct coil voltage, the normally closed relay does not pull in unless the proper voltage builds up across the capacitor, which brings on the SERVICE LED. See Fig. 43.

Here is how it works: · On a call for cooling, the thermostat makes R to Y, the
contactor coil is powered, and the compressor motor turns on. · At the same time, the indicator light is energized. · As the motor gets up to speed--about one second, the
fault relay sees enough voltage to pull in. Its normally closed contact opens and the indicator light goes out. · Anything that prevents the motor from running prevents the fault relay from pulling in.

COMPRESSOR MOTOR

FAULT RELAY

L1 RUN R

C L3

CAP. START S

Y

R

L

X

RISE

LED

L2
L1 (HOT)

CONTACTOR

THERMOSTATSUBBASE

M5831

Fig. 43. Compressor fault relay schematic.

60-2485--8

28

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

CROSS REFERENCE
The following section lists the current T874 Trade replacements for T872 and T874 Multistage Thermostats. It also lists the Q674 Trade replacements for Q672 and Q674 Subbases.
All thermostats listed carry the Honeywell logo unless otherwise noted.
When using the Cross Reference Charts, refer to the following instructions:
1. Locate and identify the existing thermostat and subbase model.
2. Refer to the Model Number column to find the model that matches the existing thermostat and subbase.

3. The Description column identifies certain characteristics of the existing device.
4. The Trade Replacement column identifies the correct replacement device.
5. The Remarks column lists any characteristics or adjustments to be made on the Trade replacement model.
6. The Fig. No. column lists the wiring hookup used for the specific model number. The wiring diagrams follow the Cross Reference section.
7. Refer to the circuit illustration that corresponds with the appropriate number. This figure illustrates the internal electric circuit for the desired model number.

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

T872A

1-stage heat, 1-stage cool

A1006

Standard OEM

T874A1036

A1014

72-78°F (22-26°C) stop; locking cover; no thermometer

T874A1010

Use T874A1176 for Dept. of Defense (DoD) application.

A1022

Heat anticipator set at 0.45A

T874A1036

A1030

0.4A heat anticipator setting

T874A1036

A1048

TRADELINE

T874A1036

A1055

AAF logo; locking cover

T874A1036

A1063

Climatrol logo

T874A1036

A1071

Lennox logo; 0.5A heat anticipator setting

T874A1036

A1089

Melco logo

T874A1036

A1097

Westinghouse logo

T874A1036

A1105

Amana logo; 1.2A heat anticipator setting

T874A1036

A1113

Trane logo

T874A1036

A1121

Airtemp (Chrysler) logo

T874A1036

A1139

Singer logo; no. 02005384

T874A1036

A1147

American Standard logo

T874A1036

A1154

Carrier logo and color; no. HH07AT074

T874A1036

A1162

General Electric logo; no. AY28X097

T874A1036

A1170

Sears logo; no. 4291441

T874A1036

A1188

Command-Aire logo

T874A1036

A1196

Singer logo; Celsius scale; no. 02005521

T874A1036

A1204

Carteret logo

T874A1036

A1212

General Electric; no. AY28X114; 72-78°F (22-26°C) stop

T874A1010

Use T874A1176 for Dept. of Defense (DoD) application.

A1220

Singer logo; no. 050240-01

T874A1036

A1238

Celsius scale

T874A1036

A1246

TRADELINE; locking cover and adjustable locking T874A1150 lever stops

A1253

Trane Comfort Corp

T874A1036

A1261

TRADELINE; 72-78°F (22-26°C) stop; locking cover; no thermometer; meets DoD specs

T874A1176

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

29

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number A1279
A1287
A1295 A1303 A1311 A1329 A1337 A1345 A1352 A1360 A1378 T872B B1005 B1013 B1021 B1039 B1047 B1054 B1062 B1070 B1088 B1096 B1104 B1112 B1120 B1138
B1146 B1153 T872C C1004 C1012 C1020
C1038 C1046 C1053 C1061 C1079
C1087
C1095

Description

T874 Trade Replacementa

General Electric logo; no. AY28X114A; 75°F stop; T874A1010 locking cover; no thermometer.

General Electric; no. AY28X097A; fan current

T874A1036/

shunt for auto fan in heating; heat anticipator set at Q674B1018

0.4A.

Lennox; Celsius scale

T874A1036

Lennox logo; no. 64A0601; meets DoD specs

T874A1176

Envirotron special; Celsius scale

T874A1010

Carrier logo; Celsius scale; no. HH07AT074C

T874A1036

Square D; no. HCD-3; heat anticipator set at 0.2A T874A1036

TRADELINE; Celsius scale

T874A1010

Heat anticipator set 1.2A

T874A1036

Friedrich logo; heat anticipator set at 0.2A

T874A1036

Wesco logo; heat anticipator set at 0.8A

T874A1036

1-stage heat, 2-stage cool

Standard OEM

T874B1019

0.4A heat anticipator setting

T874B1019

TRADELINE

T874B1019

Westinghouse logo

T874B1019

American Standard logo

T874B1019

Climatrol logo

T874B1019

Carrier logo

T874B1019

Trane logo

T874B1019

Fedders logo

T874B1019

Climatrol logo

T874B1019

Carteret logo

T874B1019

Singer logo; no. 050240-03

T874B1019

Celsius scale

T874B1019

Singer logo; no. 02005711; locking cover and lever.

T874B1019

Lennox logo; no. P-8-8895

T874B1019

Lennox logo; Celsius scale

T874B1019

2-stage heat, 1-stage cool

Standard OEM

T874C1018

Heat anticipator set at 0.4A

T874C1018

72-78°F (22-26°C) stop; locking cover; no

T874C1141

thermometer; 42-88°F (6-31°C) setpoint range.

TRADELINE

T874C1018

American Standard logo

T874C1018

Friedrich logo

T874C1018

Lennox logo; no. P-8-8896

T874C1018

Westinghouse logo; stage 1 heat anticipator set at T874C1018 0.75A; stage 2 anticipator set at 1.2A

Fast cycle performance on both heat stages; anticipator range 0.12-0.6A

T874C1018

Payne logo; no. 0.1-0.175

T874C1018

Remarks Use T874A1176 for Dept. of Defense (DoD) application. Set thermostat stage 1 heat anticipator for total of fan and stage 1 primary control current draw.
Use T874C1141 for Dept. of Defense (DoD) application.
Adjust anticipator faster for correct performance.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

60-2485--8

30

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

C1103

Amana logo; anticipator set at 1.2A

T874C1018

C1111

Airtemp (Chrysler) logo

T874C1018

C1129

Day and Night logo; no. 0.1-0.174

T874C1018

C1137

Fast cycle performance on both heat stages

T874C1018

Adjust anticipator faster for correct performance.

C1145

Rheem logo

T874C1018

C1152

Ruud logo

T874C1018

C1160

Climatrol logo

T874C1018

C1178

Wesco logo

T874C1018

C1186

Sears logo

T874C1018

C1194

First Co. logo

T874C1018

C1202

Carrier logo

T874C1018

C1210

Carrier logo; Celsius scale

T874C1018

C1228

0.4A heat anticipator setting

T874C1018

C1236

Carrier logo; no. HH07AT070

T874C1018

C1244

Fraser-Johnson logo

T874C1018

C1251

Trane logo

T874C1018

C1269

Fedders logo

T874C1018

C1277

Climatrol special

T874C1018

C1285

Autogas logo

T874C1018

C1293

Fedders logo

T874C1018

C1301

Climatrol logo

T874C1018

C1319

Command-Aire logo

T874C1018

C1327

Melco logo; lock cover and levers

T874C1018

C1335

Singer logo (Carteret)

T874C1018

C1343

Singer logo; no. 050240-04

T874C1018

C1350

Celsius scale

T874C1018

C1368

12°F (67°C) differential between heat 1 and heat 2

T874C1125

C1376

AAF logo; locking cover; 72-78°F (22-26°C) stop T874C1018

C1384

Servel logo

T874C1018

C1392

TRADELINE; fast cycle performance on both heat T874C1018 stages.

Adjust anticipator faster for correct performance.

C1400

72-78°F (22-26°C) stop; locking cover; no thermometer; meets DoD specs

T874C1141

C1418

Solaron logo

T874C1018

C1426

Lennox logo; no. 42C04; four LEDs

None

C1434

Carrier logo; no. HH07AT070C; Celsius scale

T874C1018

C1442

Goettl logo

T874C1018

C1459

Goettl logo; used with Q672N1001, N1019

None

C1467

Lennox logo; Celsius scale

T874C1018

C1475

Tappan logo; no. 080-13708-37

T874C1018

C1483

Fasco logo; no. 1230-8161

T874C1018

C1491

Lennox logo; no. 64A0501; locking cover; no thermometer; meets DoD specs

T874C1141

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

31

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

C1509

Fedders logo; used with Q672L1102

Y594R1425

Wiring differences (old=new): C=X, K=E; remove Y-W1 jumper.

C1517

Climatrol logo; used with Q672L1102

Y594R1425

Wiring differences (old=new): C=X, K=E; remove Y-W1 jumper.

C1525

Square D logo; no. HCD-2

T874C1018

C1533

Airtemp logo

T874C1018

C1541

Airtemp logo; used with Q672L1102

Y594R1425

Wiring differences (old=new): C=X, K=E; remove Y-W1 jumper.

C1566

TRADELINE; Celsius scale

T874C1018

Replacement has °F scaleplate.

C1574

Whalen special; used with Q672B1269

None

C1582

Lennox; meets DoD

None

C1590

Singer; 8°F (4.4°C) differential between stage 1 and stage 2

T874C1125

Replacement has 2°F (1° C) differential between H1 and H2.

C1608

Singer logo; no. 02005784 8°F (4.4°C) differential T874C1125 between stage 1 and stage 2

Replacement has 2°F (1°C) differential between H1 and H2.

C1616

Celsius scale; stop set at 23°C

None

Add 4074ECK adjustable stop.

C1624

Heat Wave logo; no. 0360-116

T874C1018

C1632

York logo; heat anticipator set at 0.2A

T874C1018

C1640

Heat anticipator set at 0.4A

T874C1018

C1665

Wesco logo; heat anticipator set at 0.8A

T874C1018

C1673

Wards logo; used with Q672B1285, B1293

Gas systems: T874C1018/ Q674B1034

Electric systems: Adjust anticipator faster for correct

T874C1018/

performance.

Q674B1075

C1681

Lechauffage Urbain logo; Celsius scale

T874C1018

C1699

Duotherm logo; used with Q672E1068 or Q672F1000

T874C1018

See subbase description for replacement information.

C1707

Sigler logo; used with Q672N1027

None

C1715

Westinghouse logo

T874C1018

T872D

2-stage heat, 2-stage cool

D1003

Standard OEM

T874D1165

D1011

TRADELINE

T874D1165

D1029

Westinghouse logo

T874D1165

D1037

Climatrol logo

T874D1165

D1045

Lennox logo; no. P-8-8897; used with Q672E1191. T874D1165

D1052

York logo

T874D1165

D1060

Singer logo; no. 02005385

T874D1165

D1078

Rheem logo

T874D1165

D1086

Rudd logo

T874D1165

D1094

York logo; locking cover

T874D1165

D1102

American Standard logo

T874D1165

D1110

ITT logo

T874D1165

D1128

Carrier logo

T874D1165

D1136

No anticipator on stage 1 cool; used with Q672C1029

T874D1165

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

60-2485--8

32

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

D1144

Carrier logo; no. HH07AT072

T874D1165

D1151

General Electric logo; no. AY28X098; 0.4 heat anticipator setting

T874D1165

D1169

Airtemp (Chrysler) logo; used with Q672E1118

T874D1165/ Q674E1049

Wiring differences (old=new): A=W1; set H1 anticipator to 1.2A.

D1177

Trane logo

T874D1165

D1185

Dunham-Bush logo

T874D1165

D1193

Fedders logo

T874D1165

D1201

Climatrol logo

T874D1165

D1219

Command-Aire logo

T874D1165

D1227

Singer logo; no. 02005522; Celsius scale

T874D1165

D1235

Singer logo; (Carteret)

T874D1165

D1243

Friedrich logo

T874D1165

D1250

Singer logo; no. 050240-02

T874D1165

D1268

Airtemp logo

T874D1165

D1276

Celsius scale

T874D1165

D1284

Solaron

T874D1165

D1292

Tokyo Carrier logo; no. HH07AT072C; Celsius scale

T874D1165

D1300

SUPER TRADELINE

T874D1165

D1318

General Electric logo; no. AY28X098A; fan current T874D1165/

shunt for auto fan in heating.

Q674B1075

D1326

General Electric logo; locking cover 72-78°F (22-26°C) stop; fan current shunt for auto fan in heating.

T874D1165

D1334

Lennox logo; Celsius scale

T874D1165

D1342

Tappan logo; no. 080-13708-32

T874D1165

D1359

Singer logo; no. 02005740; Celsius scale; 6.6°C T874D1165 differential between H1 and H2.

Only 2°F (1°C) differential between H1 and H2.

D1367

Friedrich logo; no. 600-580-23

T874D1165

D1375

Singer logo; no. 02005713; Celsius scale; controls None 2 separate heat/cool circuits; used with Q674G1017

D1383

TRADELINE; Celsius scale

T874D1165

D1391

Singer logo; no. 02005712; controls two separate None heat/cool circuits; used with Q674G1017

D1409

12°F (7°C) differential between H1 and H2

T874D1165

D1417

Fedders logo

T874D1165

D1425

Climatrol logo

T874D1165

D1433

Singer logo; no. 02005785; 8°F (4.4°C) differential T874D1165 between H1 and H2

D1441

American Air Filter

T874D1165

D1474

Carrier; no. HH07AT072-03; Celsius scale

T874D1165

T872E

2-stage cool

E1002

Standard OEM

T874E1016

E1010

TRADELINE

T874E1016

E1028

Westinghouse logo

T874E1016

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

33

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number E1036 E1044 E1051 E1069 E1077 E1085 E1093 E1101 E1119 E1127 E1135 E1143 E1150 E1168 T872F F1001 F1019 F1027 F1035
F1043 F1050 F1068 F1076 F1084 F1092 F1100 F1118 F1126
F1134 F1159 F1167 F1175
T872G
G1000
G1018

Description

T874 Trade Replacementa

American Standard logo

T874E1016

York logo; locking cover

T874E1016

ITT logo

T874E1016

Climatrol logo

T874E1016

Airtemp (Chrysler) logo

T874E1016

Lennox logo

T874E1016

Trane logo

T874E1016

Dunham-Bush logo

T874E1016

Fedders logo

T874E1016

Climatrol logo

T874E1016

General Electric logo; no. AY28X108

T874E1016

Lennox logo; Celsius scale

T874E1016

Celsius scale

T874E1016

Airtemp logo

T874E1016

2-stage heat

Standard OEM

T874F1015

TRADELINE

T874F1015

Lennox logo; fast cycle heat anticipator

T874C1018

Luxaire logo; fast cycle performance on both heat T874C1018 stages.

York logo; locking cover; used with M839.

T874C1018

Raehco logo

T874F1015

Fast cycle performance on both heat stages.

T874C1018

Wesco logo

T874F1015

Lennox logo

T874F1015

Auto Gas logo

T874F1015

Celsius scale

T874F1015

Lennox logo; Celsius scale

T874F1015

Stages 1 and 2 heat electrically isolated; used with None Q672D1002

Square D logo; HCD-4

T874F1015

Wesco logo; heat anticipator set at 0.8A

T874F1015

York logo

T874F1015

Oneida Heater logo; no. 30A0287-01; used with T874F1015/

Q672K1012.

Q674K1026

Heat pump models; 2-stage heat, 1-stage cool, 1-stage changeover.

Fast cycle performance stage 2 heat; fixed

Y594G1252

anticipator stage 1 heat and cool; changeover with

cooling; used with Q672F1018.

Adjustable anticipator stage 2 heat; fixed

Y594G1393

anticipator stage 1 heat and cool; changeover with

cooling; used with Q672E1027.

Remarks
M839 draws 0.72A; set adjustable heat anticipator to setting of 0.9A for proper cycle rate.
Wiring differences (old=new): W=W2, X1=X. Wiring differences (old=new): Y1=O, Y2=Y.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

60-2485--8

34

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

G1026

Lennox logo; fast cycle performance; stage 2 heat; None fixed anticipator stage 1 heat and cool; changeover with cooling; used with Q672E1019, F1067.

See subbase description for replacement information.

G1034

Westinghouse logo; adjustable anticipator stage 2 Y594G1252 heat; fixed anticipator stage 1 heat and cool; changeover with cooling; used with Q672F1091, F1141, F1257 or Q672J1013, J1062.

Wiring differences (old=new): W=W2.

G1042

York logo; fixed anticipator on all stages heat and Y594G1567 cool; changeover with cooling; used with Q672J1021.

G1059

TRADELINE; no anticipator stage 2 heat; fixed Y594G1161 anticipator stage 1 heat and cool; changeover with cooling; used with Q672J1039 outdoor reset.

Designed for use on General Electric heat pumps.

G1067

Lennox logo; no. P-8-11222; fast cycle performance; stage 2 heat; fixed anticipator stage 1 heat and cool; changeover with cooling; used with Q672E1142, F1083.

See subbase description for replacement information.

G1075

Carrier logo; adjustable anticipator stage 2 heat; fixed anticipator stage 1 heat and cool; changeover with cooling; used with Q672J1054, L1052.

See subbase description for replacement information.

G1083

Adjustable anticipator stage 2 heat; fixed

Y594G1252

anticipator stage 1 heat and cool; changeover with

cooling; includes shunt to bypass stage 2

anticipator with auxiliary heat relays; used with

Q672F1158.

G1091

Lennox logo; same as T872G1026 except meets DoD specs.

See subbase description for replacement information.

G1109

Tappan logo; no. 080-13708-52; adjustable

Y594G1252

anticipator stage 1 heat and cool; changeover with

cooling; used with Q672F1117.

Wiring differences (old=new): C=X.

G1117

Changeover; used with Q672F1125.

Y594G1252

Wiring differences (old=new): C=X.

G1125

Lennox logo; no. 63A0401; Celsius scale; isolated None auxiliary heat power circuit; fast cycle anticipator stage 2 heat.

G1133

Rheem logo; no. RXMT-B71; adjustable anticipator stage 2 heat; fixed anticipator stage 1 heat and cool; changeover with cooling; includes shunt to bypass stage 2 anticipator with auxiliary heat relays; used with Q672F1158, F1232.

Y594G1252

G1141

Ruud logo; adjustable anticipator stage 2 heat; Y594G1252 fixed anticipator stage 1 heat and cool; changeover with cooling; includes shunt to bypass stage 2 anticipator with auxiliary heat relays; used with Q672F1158.

G1158

Carrier logo; same as T872G1075. Except DoD styling.

See subbase description for replacement information.

G1166

BDP used with Q672F1125.

Y594G1252

Wiring differences (old=new): C=X.

G1174

BDP used with Q672F1125.

Y594G1252

Wiring differences (old=new): C=X.

G1182

Carrier; no. HH07AT071C; Celsius scale; used with Q672L1052, J1054.

See subbase description for replacement information.

G1190

Tappan; no. B13708-57; used with Q672L1078 for None 8 and 10 ton heat pumps with 2 compressors.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

35

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

G1208

Marvair logo; special for Crispaire; used with Q672F1166, F1323.

Y594G1393

G1216

Janitrol logo; no. 26G05; stage 2 heat anticipator Y594G1252 set at 1.2A; used with Q672F1117.

Wiring differences (old=new): C=X.

G1224

TRADELINE; adjustable anticipator stage 2 heat; Y594G1419 fixed anticipator stage 1 heat and cool; changeover in cool; used with Q672F1208.

G1232

Heat Wave (Southwest Mfg.) logo; stage 2 heat anticipator set at 1.2A; used with Q672F1224.

G1240

Lennox; fast cycle anticipator stage 2 heat; used None with Q672F1240.

G1257

Carrier logo; no. HH07AT073; used with Q672L1169 (HH93AZ071).

None

G1265

Addison logo; used with Q672F1265.

Y594G1252

Wiring differences (old=new): C=X.

G1273

Carrier logo; (DoD model); 68°F (20°C) maximum heating; 78°F (26°C) minimum cooling; used with Q672L1052, J1054

See subbase description for replacement information.

G1281

Wesco logo; used with Q672F1265.

Y594G1252

Wiring differences (old=new): C=X.

G1299

York logo; meets DoD specs; used with Q672L1177.

Y594G1567

G1307

Carrier; no. 38EQ1900; Celsius; used with Q672J1054, L1052.

See subbase description for replacement information.

G1315

Luxaire special; stage 2 heat anticipator set to 1.2A; used with Q672F1281.

Y594G1252

G1323

Lennox special; used with Q672L1201 and C815A1013.

None

G1331

York; used with Q672J1021.

Y594G1567

Wiring differences (old=new): X=X1, L=X2, W=E; Y1-W1 and Y2W2 jumpers required.

G1356

Westinghouse; used with Q672L1219.

T874D1165/ Q674F1022

Wiring differences (old=new): X=X1, L=X2, W=E; Y1-W1 and Y2W2 jumpers required.

G1364

York; used with Q672D1077.

None

G1372

Tappan/Janitrol logo; no. B-13708-521; used with Q672F1117.

Y594G1252

Wiring differences (old=new): C=X.

G1398

York logo; no. 025-21454C; used with Q672J1021. Y594G1567

T872H

Heat pump model; 1 stage heat, 1 stage cool, 1 stage changeover.

H1009

Command-Aire logo; fixed anticipator stage 1 heat Y594H1012 and cool; changeover with cooling; used with Q672C1086.

H1017

Friedrich logo.

Y594H1012

H1025

Friedrich logo; Celsius.

Y594H1012

T872M

1 stage heat, 1 stage cool with stage 2 heat factory set at 60°F (16°C).

M1003

Standard OEM; used with Q672D and external switching means.

T874C1125

T874C1125 has 12°F (6.7°C) differential between stage 1 and stage 2 heat.

T872N

Heat pump model; 2-stage heat, 1-stage cool plus changeover, changeover in heat mode.

N1002

None

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

60-2485--8

36

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number

Description

T874 Trade Replacementa

Remarks

N1010

Williamson logo; adjustable anticipator stage 1 and T874N1016/ 2 heat; fixed anticipator stage 1 cool; used with Q674F1220 Q672F1133 or F1315.

N1028

TRADELINE heat mode changeover; used with T874N1016 Q672F1216.

N1036

Bard; used with Q672F1299.

T874N1016/ Q674F1220

N1044

Thermotron logo; 1st stage changeover heat mode; used with Q672F1299.

T874N1016/ Q674F1220

T872Q

1-stage heat; used with another T872 for heating setback.

Q1009

Standard OEM

T874C1125

Q1017

York logo

T874C1125

Replacement only good for 1-stage heat and 1-stage cool applications.

Q1025

ITT logo

None

Q1033

Lennox logo; no. P-8-8899.

None

Q1041

Lennox logo; no. 63A6401.

None

T872R

Heat pump model; 2-stage heat, 1-stage cool, manual changeover.

R1008

Fixed anticipator stage 1 heat and cool; no

Y594R1425

anticipator stage 2 heat; changeover with cooling;

used with Q672B1046.

Wiring differences (old=new): W=W2; W1-Y1 jumper required.

R1016

Addison same as T872R1008; used with Q672B1103.

Y594R1425

Wiring differences (old=new): W=W2; W1-Y1 jumper required.

R1024

Lennox logo; fast cycle stage 2 heat; fixed anticipator stage 1 heat and cool; changeover with cooling; used with Q672B1160 and Q672L1003.

See subbase description for replacement information.

R1032

York logo; fixed anticipator stage 1 and 2 heat and Y594R1664 stage 1 cool; changeover with cooling; used with Q672L1011.

R1040

Lennox logo; fast cycle stage 2 heat; fixed anticipator stage 1 heat and cool; isolated stage 2 heat switch; changeover with cooling; used with Q672B1202 no. P-8-11221, Q672L1029

See subbase description for replacement information.

R1057

TRADELINE; fixed anticipator stage 1 heat and Y594R1763 cool; no anticipator stage 2 heat; changeover on cooling; used with Q672L1037; outdoor reset.

Designed for use on General Electric heat pumps. Wiring differences (old=new): A=T.

R1065

Adjustable anticipator stage 2 heat; fixed

Y594R1243

anticipator stage 1 heat and cool; changeover on

cooling; used with Q672L1045.

R1073

Lennox logo; no. 63A0301; Celsius scale; separate auxiliary heat power circuit; fast cycle stage 2 heat antic.

None

R1081

Ruud logo; same circuit as T872R1065; used with Y594R1243 Q672L1045, L1136.

R1099

Dunham Bush special; used with Q672L1060, L1383.

Y594R1243

R1107

Rheem; no. RXMT-B70; used with Q672L1045, Y594R1243 L1136.

R1115

Friedrich logo; fixed anticipator; used with Q672B1244, L1086.

See subbase description for replacement information.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

37

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 6. T872-T874 Thermostat Cross Reference.

Model Number R1123 R1131
R1149
R1156
R1164 R1172
R1180 R1198 R1206 R1214
R1222
R1230
R1255 R1271
R1297 R1305 R1321 R1339 T872S
S1005
T872T T1004
T872W W1019
W1027
W1035

Description

T874 Trade Replacementa

York logo; no. 025-21453C; Celsius scale.

Y594R1664

Lennox logo; separate auxiliary heat power circuit; None fast cycle stage 2 heat anticipator; outdoor reset; used with Q672L1144, C815A1013.

Westinghouse logo; adjustable stage 2 heat anticipator; cooling changeover; fixed anticipator stage 1 heat and cool; used with Q672L1110, L1128, L1151.

Y594R1243

Marvair logo; used with Q672L1094, L1250.

Y594R1243

Bard; used with Q672L1185. Heil Quaker; used with Q672L1193.

Y594R1243 Y594R1243

York; Celsius; used with Q672L1011. TRADELINE; used with Q672L1227 For use with W89; used with Q672L1235. Intertherm logo; used with Q672L1276.

Y594R1664 Y594R1243 None Y594R1300

York logo; used with C815A1039; adjustable anticipator stage-2 heat; used with Q672L1284

Y594R1672

Amana logo; no. C62397-1; used with Q672L1300, W89.

None

Singer logo; used with Q672L1326 and W89.

None

Westinghouse logo; used with Q672L1375 and W89.

Y594R1664

York; Celsius scale; used with Q672L1011.

None

Used with Q672L1235 and W89.

None

Duotherm logo; used with Q672L1409, and W89. None

Williamson; used with Q672L1391.

Y594R1243

Heat pump model; 2-stage heat plus changeover, 1-stage cool.

Westinghouse logo; adjustable anticipator stage 1 T874C1018/

and 2 heat; fixed anticipator stage 1 heat;

Q674C1058

changeover with heating: used with Q672C1045

1-heat stage, 1-vent and 2-cool stages.

Trane logo; used with Q672B1129.

None

3-heat stages, 2-cool stages, manual changeover

Lennox logo; no. 52C7501; used with Q672L1342 None and C815A1013.

Westinghouse logo; used with Q672L1268 and C815A1021.

None

TRADELINE; used with C815A1043 and Q672B1251.

Y594W1014

Remarks
Wiring differences (old=new): W=W2. Replacement has auto fan in Emergency Heat mode. Wiring differences (old=new): B=X, W=W2.
Wiring differences (old=new): W1=B, Z=L, K=E.
Wiring differences (old=new): V=RC-RH, F=G, C=Y1, Z=B, H2=W2; W1-Y1 jumper required.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and the subbase.

60-2485--8

38

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number

Description

Q674 Trade Replacementa

Remarks

Q672A

System: HEAT-AUTO-COOL, Fan: AUTO-ON

A1005

Standard OEM

Q674A1019

A1013

TRADELINE

Q674A1019

A1021

RC-RH jumper

Q674A1019

RC-RH jumper required.

A1039

RC-RH jumper; Chek Lite

Q674A1019

RC-RH jumper required.

Q672B

System: HEAT-OFF-COOL, Fan: AUTO-ON

B1004

Standard OEM

Q674B1034

B1012

Isolated G terminal.

Q674B1018

B1020

System: HEAT-OFF-RESET-COOL

Q674B1034

Used system off as reset position.

B1038

TRADELINE

Q674B1034

B1046

Heat pump circuit; used with T872R1008.

Y594R1425

Wiring differences (old=new): W1=Y1, W=W2.

B1053

RC-RH jumper

Q674B1034

RC-RH jumper required.

B1061

Chek Lite

Q674B1034

B1079

Auto fan operation in heat and cool.

Q674B1075

B1087

Carrier no. HH93AZ078; RC-RH jumper.

Q674B1075

B1095

Carrier no. HH93AZ084; RC-RH jumper.

Q674B1034

B1103

Addison; heat pump circuit; used with T872R1016.

Y594R1425

Wiring differences (old=new): W=W2; W1-Y1 jumper required.

B1111

Carrier no. HH93AZ080; isolated G terminal. Q674B1018

B1129

Trane special circuit; used with T872T1004. None

B1137

RC-RH jumper; isolated G terminal.

Q674B1018

RC-RH jumper required.

B1145

Fedders special

Q674B1034

RC-RH jumper required.

B1152

Fedders special; auto fan operation in heat and cool.

Q674B1075

B1160

Lennox; heat pump circuit; used with T872R1024; includes compressor lockout in EM. HT.

Y594R1243

Wiring differences (old=new): V-VR=R, M=Y, Y=W2, F=G, R=O.

B1178

General Electric no. AY28X107; auto fan operation in heat and cool.

Q674B1075

B1186

Trane; isolated G terminal; Filter LED.

Q674B1018

B1194

General Electric no. AY28X124; auto fan operation in heat and cool.

Q674B1075

Set T874 stage-1 anticipator for combined load of heat relay and fan relay.

B1202

Lennox no. P-8-11223; heat pump circuit; used Y594R1243 with T872R1040.

Wiring differences (old=new): V-VR=R, M=Y, Y=W2, F=G, R=O.

B1210

None

B1228

General Electric no. BAY28X137; isolated G terminal.

Q674B1018

B1236

Carrier no. HH-93AZ079; RC-RH jumper; LOCKOUT LED indicates compressor lockout switch activated.

Q674B1034

RC-RH jumper; LED cannot be provided in TRADELINE model.

B1244

Friedrich; heat mode changeover; used with T872R1115.

T874C1018/ Q674B1034

Wiring differences (old=new): C=no connection; RC-RH and W1-Y1 jumpers required.

B1251

Used with T872W1035 and C815A1043.

Y594W1014

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

39

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number

Description

Q674 Trade Replacementa

Remarks

B1269

Whalen; Hi-Lo fan switch; constant fan in heat None and cool system switch positions; used with T872C1574.

B1277

Square D no. HCB-5.

Q674B1034

B1285

Wards; RC-RH and F-W3 jumpers; used with T872C1673.

Gas Furnace: T874C1018/ Q674B1034

Electric Furnace: T874C1018/ Q674B1075

Adjust anticipator faster for correct performance.

B1293

Lennox no. 41C96; used with T872C1673.

Same as Q672B1285

Q672C

System: OFF-AUTO, Fan: AUTO-ON

C1003

Standard OEM

Q674C1058

C1011

Westinghouse; RC-RH jumper.

Q674C1058

RC-RH jumper required.

C1029

W1-Y2 jumper; for heat pump; used with T872D1136.

Q674E1049

Replacement has heat/cool system switching.

C1037

Chrysler Airtemp; System: COOL-OFF-AUTO. Q674C1058

C1045

Westinghouse; heat pump; used with T872S1005.

T874C1018/ Q674C1058

Wiring differences (old=new): V=RC-RH, F=G, C=Y1, Z=B, H2=W2; W1-Y1 jumper required.

C1052

Isolated stage 2 heat circuit for dc electric heat Recontrol relay.

Use T874G1246/Q674F1212 which adds HEAT-COOL-EM.HT. system switch.

C1060

Fedders special.

Q674C1058

C1078

General Electric no. AY28X109.

Q674C1058

C1086

Command-Aire; heat pump; used with T872H1009.

Y594H1012

C1102

TRADELINE

Q674C1058

Q672D

System: None. Fan: None.

D1002

Standard OEM; used with T872F1126.

Q674D1040

D1010

Lennox special.

None

D1028

Carrier; RC-RH jumper.

None

D1036

Carrier no. HH93AZ070; RC-RH jumper.

Q674D1040

RC-RH jumper required.

D1044

General Electric no. AY-28X100.

None

D1069

Square D no. HCB-4.

None

D1077

York; used with T872G1364.

None

D1085

TRADELINE

Q674D1040

Q672E

System: OFF-HEAT-AUTO-COOL Fan: AUTO-ON

E1001

Standard OEM

Q674E1049

E1019

Lennox no. P-8-8892; heat pump; cool mode T874D1165/

changeover; used with T872G1026.

Q674B1075

E1027

Heat pump circuit; W1-Y2 jumper; cool mode Y594G1393 changeover; used with T872G1018.

Wiring differences (old=new): Y1=O, Y2=Y.

E1035

Heat pump circuit; W1-Y2 jumper; cool mode Y594G1393 changeover.

Wiring differences (old=new): Y1=O, Y2=Y.

E1043

Heat pump circuit; heat mode changeover.

Q674E1049

Wiring differences (old=new): W1=B, W2=W1; W1-Y1 jumper.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

60-2485--8

40

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number

Description

Q674 Trade Replacementa

Remarks

E1050

TRADELINE

Q674E1049

E1068

RC-RH jumper; used with T872C1699.

Q674E1049

RC-RH jumper required.

E1076

RC-RH internal jumper; EM. HT. LED.

Q674E1049

RC-RH jumper required.

E1084

Carrier no. HH93AZ076; RC-RH jumper.

Q674E1049

RC-RH jumper required.

E1092

Carrier no. HH93AZ082; RC-RH jumper; B terminal; isolated G terminal.

Q674E1049

E1100

General Electric no. AY28X099.

Q674E1049

E1118

Airtemp; heat pump; used with T872D1169.

T874D1165/ Q674E1049

Wiring differences (old=new): A=W1; set H1 anticipator to 1.2A.

E1126

Common R terminal.

Q674E1049

RC-RH jumper required.

E1134

ITT Nesbitt; RC-RH jumper; O and B terminals; Q674E1049 isolated G terminal.

E1142

Lennox no. P-8-11224; heat pump;

Y594G1252

V-VR jumper; cool mode changeover; used with

T872G1067.

Wiring differences (old=new): V-VR=R, Y=W2, R=O, M=Y, F=G.

E1159

Carrier no. HH93AZ077; RC-RH jumper; LOCKOUT LED indicates activation of compressor lockout switch.

Q674E1049

RC-RH jumper required; no LED in TRADELINE model.

E1167

Square D no. HCB-2; Chek Lite.

Q674E1049

E1183

Square D no. HCB-3.

Q674E1049

E1191

Lennox; HIGH and LOW LEDs; used with T872D1045.

Q674E1049

No LEDs on replacement.

Q672F

System: EM. HT.-HEAT-AUTO-COOL-OFF Fan: AUTO-ON.

F1000

With EM. HT. LED; used with T872C1699.

Q674F1022

Remove W3-X2 jumper to E-X2.

F1018

Heat pump; heat mode changeover; Chek Lite; Y594G1252 used with T872G1000.

Wiring differences (old=new): W=W2, X1=X.

F1026

Chek Lite; W2-X2 jumper.

Q674F1022

F1034

Airtemp; EM. HT. LED; RC-RH and X2-E jumpers.

Q674F1022

If RC-RH jumper removed on Q672F1034, Q674F1022 does not replace.

F1042

W2-X2 jumper; Chek Lite.

Q674F1022

F1059

Carrier no. HH93AZ074; EM. HT. LED.

Q674F1022

Remove W2-X2 jumper to E-X2; X terminal same as C.

F1067

Lennox; heat pump; cool mode changeover; EM. HT. LED; used with T872G1026.

None

F1075

Heat pump circuit; EM. HT. LED; 2 terminal; RC- None RH jumper.

F1083

Lennox no. P-8-11225; heat pump;

None

V-VR jumper; cool mode changeover; EM. HT.

LED; used with T872G1067.

F1091

Westinghouse; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; used with T872G1034.

Y594G1252

Wiring differences (old=new): W=W2.

F1109

Airtemp no. 3778567ACC; R-X2 jumper; EM. HT. LED.

Q674F1022

R-X2 jumper required.

F1117

Tappan no. 080-13708-53; heat pump; EM. HT. LED; cool mode changeover; compressor lockout and auto fan in EM. HT.; used with T872G1109, G1216, G1372.

Y594G1252

Wiring differences (old=new): C=X.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

41

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number

Description

Q674 Trade Replacementa

Remarks

F1125

BDP no. 3442DP90; used with T872G1117, G1166, G1174.

Y594G1252

Wiring differences (old=new): C=X.

F1133

Williamson; heat pump; EM. HT. LED; heat mode changeover; compressor lockout in EM. HT.; used with T872N1010.

T874N1016/ Q674F1220

F1141

Westinghouse; EM. HT. LED; auto fan in EM. HT.; used with T872G1034.

Y594G1252

Wiring differences (old=new): W=W2.

F1158

Rheem Ruud; heat pump; EM. HT. LED; cool Y594G1252 mode changeover; compressor lockout in EM. HT.; used with T872G1083, G1133, G1141; auto fan in EM. HT.

F1166

Crispaire; EM. HT. LED; used with T872G1208. Y594G1252

F1174

Carrier no. HH93AZ081; EM. HT. LED.

Q674F1022

F1182

Square D no. HCB-1; Chek Lite; R-X2 jumper; Q674F1022 System: Aux. Heat replaces EM. HT.

R-X2 jumper; add monitor switch between X1 and low side of power.

F1190

EM. HT. LED; X2-E and RC-RH jumpers.

None

F1208

TRADELINE; cool mode changeover; EM. HT. Y594G1419 LED; used with T872G1224.

F1216

TRADELINE; heat mode changeover; EM. HT. T874N1016/

LED; used with T872N1028.

Q674F1220

F1224

Heatwave (Southwest Mfg.); compressor lockout in EM. HT.; EM. HT. LED; used with T872G1232.

Y594G1252

F1232

Rheem; cool mode changeover; EM. HT. and AUX. HEAT LEDs; compressor lockout in EM. HT.; used with T872G1133.

Y594G1252

F1240

Lennox; cool mode changeover; EM. HT. and None SERVICE LEDs; used with T872G1240.

F1257

Westinghouse; cool mode changeover; EM. HT. and AUX. HEAT LEDs; auto fan in EM. HT; used with T872G1034.

Y594G1252

Wiring differences (old=new): W=W2.

F1265

Wesco Addison; Chek and EM. HT. LEDs; used Y594G1252 with T872G1281, G1265.

Wiring differences (old=new): C=X.

F1273

Southwest special; no. 0361-136; W2-X2 jumper.

None

F1281

Luxaire special; used with T872G1315.

Y594G1252

F1299

Bard special; used with T872N1036, N1044.

T874N1016/ Q674F1220

F1315

Williamson special; used with T872N1010.

T874N1016/ Q674F1220

F1323

Crispaire special; used with T872G1208.

Y594G1252

Q672G

System: OFF-AUTO. Fan: None.

G1009

Standard OEM

Q674G1070

G1017

Singer; O-B jumper; used with T872D1375.

Q674G1070

G1025

Includes O and B terminals.

Q674G1070

G1033

General Electric no. AY28X102.

Q674G1070

G1041

Singer no. 02005649; French wording; O-B jumper.

Q674G1070

Less French wording.

G1066

SLI-Mammoth; heat pump; heat mode changeover.

Q674G1070

Connect fan (G) wire to Y1 terminal; B-O and RC-RH jumpers.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

60-2485--8

42

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number G1074
G1082
G1090 Q672H
H1008 Q672J
J1005 J1013
J1021
J1039
J1047 J1054
J1062 Q672K
K1004 K1012 Q672L L1003 L1011
L1029
L1037
L1045

Description

Q674 Trade Replacementa

Singer no. 02005754; X1 and X2 terminals for field-added indicator lights; used with T872D1375.

None

Singer no. 02005792; X1 and X2 terminals for field-added indicator lights; used with T872D1375.

None

TRADELINE; B and O terminals.

Q674G1070

System: OFF-ON Fan: NIGHT INT.-DAY CONT.

Used with T872.

None

System: EM. HT.-AUTO-OFF Fan: AUTO-ON.

With EM. HT. LED; used with T872C or D.

None

Westinghouse; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; used with T872G1034.

Y594G1252

York; heat pump; EM. HT. LED; cool mode

Y594G1567

changeover; compressor lockout and auto fan in

EM. HT.; E-W jumper; used with T872G1042,

G1331, G1398.

Heat pump; EM. HT. and AUX. HEAT LEDs; Y594G1161 cool mode changeover; compressor lockout and auto fan in EM. HT.; used with T872G1059.

Singer no. 02005699; heat pump; EM. HT. LED; Q674F1022 heat mode changeover.

Carrier no. HH93AZ073A; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; used with T872G1075, G1182, G1307.

Y594G1252

Westinghouse; EM. HT. and AUX. HEAT LEDs; Y594G1252 used with T872G1034.

System: OFF-HEAT-AUTO-COOL. Fan: None.

Carrier no. HH93AZ072.

Q674E1049

Oneida Heater no. 30A0288-01; System: OFF- T874F1155/ WOOD-WOOD/OIL-OIL; used with T872F1175. Q674K1026

System: EM. HT.-HEAT-OFF-COOL. Fan: ON-AUTO.

Lennox; heat pump; EM. HT. LED; cool mode Y594R1425 changeover; used with T872R1024.

York; heat pump; EM. HT. LED; cool mode

Y594R1664

changeover; compressor lockout and auto fan in

EM. HT.; used with T872R1032, R1180, R1297.

Lennox no. P-8-11226; heat pump; EM. HT. LED; V-VR jumper; cool mode changeover; compressor lockout in EM. HT.; used with T872R1040.

Y594R1425

Heat pump; EM. HT. and AUX. HT. LEDs; cool Y594R1763 mode changeover; compressor lockout and auto fan in EM. HT.; used with T872R1057.

Rheem; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; auto fan in EM. HT; used with T872R1065, R1081, R1107.

Y594R1243

Remarks
Designed for use on General Electric heat pumps. Wiring differences (old=new): C=X. Wiring differences (old=new): W=W2. Fan switch does not function.
Wiring differences (old=new): V-VR=R, M=Y, Y=W2, F=G, R=O. Wiring differences (old=new): A=T; designed for used on General Electric heat pumps.

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

43

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number

Description

Q674 Trade Replacementa

Remarks

L1052

Carrier no. HH93AZ075; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; used with T872G1075, G1182, G1273, G1307.

Y594R1615

Wiring differences (old=new): C=X.

L1060

Dunham Bush; EM. HT. LED; used with T872R1099.

Y594R1243

L1078

Tappan no. B13708-58; heat pump; EM. HT. LED; cool mode changeover; compressor lockout in EM. HT.; EM. HT. relay provides fan operation in EM. HT.; used with T872G1190.

None

L1086

Friedrich; heat mode changeover; EM. HT. LED; Y594R1243 used T872R1115 with L terminal.

Wiring differences (old=new): X2=E, C=X.

L1094

Crispaire; W2-H jumper; EM. HT. LED; used with T872R1065, R1156.

Y594R1243

Replacement has auto fan in Emergency Heat mode.

L1102

Fedders; heat mode changeover; EM. HT. LED; Y594R1425 used with T872C1509, C1517, C1541.

Wiring differences (old=new): K=E, C=X; remove Y-W1 jumper.

L1110

Westinghouse; EM. HT. LED; used with T872R1149.

Y594R1243

Wiring differences (old=new): W=W2.

L1128

Westinghouse; EM. HT. LED; used with T872R1149.

Y594R1243

Wiring differences (old=new): W=W2.

L1136

Rheem no. 41-20796-07; cool mode

Y594R1243

changeover; EM. HT. and AUX. HT. LEDs; used

with T872R1081, T872R1107.

L1144

Lennox; V-VR jumper; EM. HT. and SERVICE LEDs; isolated stage 2 heat; used with T872R1131, C815A1013.

None

L1151

Westinghouse; AUX. HT. and EM. HT. LEDs; Y594R1243 used with T872R1149.

Wiring differences (old=new): W=W2.

L1169

Carrier no. HH93AZ071; EM. HT. LED; used with T872G1257 (HH07AT073).

None

L1177

York; DoD; EM. HT. LED; used with T872G1299. Y594G1567

L1185

Bard; used with T872R1164.

Y594R1243

L1193

Heil Quaker no. NAXA001TS01; used with T872R1172.

Y594R1243

Wiring differences (old=new): B=X, W=W2.

L1201

Lennox special; no. 1485701; used with T872G1323.

None

L1219

Westinghouse special; used with T872G1356. T874D1165/ Q674F1022

Wiring differences (old=new): X=X1, L=X2, W=E; Y1-W1 and Y2-W2 jumpers required.

L1227

Heat pump; used with T872R1198.

Y594R1243

L1235

Intertherm; used with T872R1206, R1305.

None

L1250

Crispaire special; used with T872R1156 and C815A1021.

Y594R1243

L1268

Westinghouse special; used with T872W1027 None and C815A1021.

L1276

Intertherm special; used with T872R1214.

Y594R1300

Wiring differences (old=new): W1=B, Z=L, K=E.

L1284

York special; used with T872R1222.

Y594R1672

L1300

Amana special; no. C62345-1; used with T872R1230.

None

L1326

Singer; used with T872R1255.

None

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

60-2485--8

44

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 7. Q672-Q674 Subbase Cross Reference.

Model Number L1342
L1375 L1383 L1391 L1409 Q672N N1001
N1019
N1027 Q672P
P1009

Description

Q674 Trade Replacementa

Lennox no. 52C7601; used with T872W1019 None and C815A1013.

Westinghouse; used with T872R1271, W89. None

Dunham Bush; used with T872R1099.

Y594R1243

Williamson; used with T872R1339.

Y594R1243

Duotherm special; used with T872R1321, W89. None

System: OFF-HEAT-COOL-EVAP.

Goettl; heat pump; heat mode changeover; evaporative cooler circuit; Fan: AUTO-ON; System: AUTO; used with T872C1459.

None

Goettl; heat pump; heat mode changeover;

None

evaporative cooler circuit; W1-Y1 jumper; used

with T872C1459.

Siegler special; used with T872C1707.

None

System: EM. HT.-HEAT-COOL.

Carrier special; no. HH93AZ069; used with T872G1075 (HH07AT071).

Y594R1243

Remarks
Replacement has OFF system switch position

a When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.

45

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number T874A
A1002 A1010
A1028 A1036
A1044 A1051 A1069 A1077
A1085 A1093 A1101
A1119
A1127 A1135 A1143 A1150
A1168 A1176
A1184
A1192

Fig.

No.

Description

1-stage heat, 1-stage cool.

44, 65 Honeywell logo; Standard OEM; used with Q674B1331.

44 Honeywell logo; includes Allen wrench and screws to lock cover; non-adjustable range stops set at 72°F (max. heat) and 78°F (min. cool) (22-26°C); field adjustable locking levers.

44 Honeywell logo; heat anticipator factory set at 0.4A.

44 Honeywell logo; TRADELINE® model; includes Allen wrench and screws to lock cover; field adjustable locking levers.

44 Obsolete. AAF/Snyder General logo; part no. 4ELN3006C; °F/°C scaleplate.

44 Lennox logo; part no. 12F9901; °F/°C scaleplate; heat anticipator set at 0.45A.

44 Obsolete. Westinghouse logo; used with Q674A-E,G.

46, 82 Obsolete. Amana Air Conditioning logo; part no. D68535-1; heat anticipator factory set at 1.2A; used with Q674B1075, E1056; used in Y594A1001, A1019.

44, 46, Obsolete. Trane logo; part no. 13510451; used with 55, 66 Q674B1018, B1075, D1008.

44 Obsolete. McQuay logo; part no. 02005935; °F/°C scaleplate.

51, 53 Carrier logo; part no. HH07AT174; used with Q674B.

82 Obsolete. Sears logo; part no. 541. 91441/49. 9144; °F/ °C scaleplate; used with Q674E1007; used in Y594A1068.
44 Obsolete. Climate Control logo; part no. 02005936; °C scaleplate.
44 Fedders multi-logo; part no. THTX-110-WCHA, 88-58-00500-001.
44 Honeywell logo; °C scaleplate.
44 Honeywell logo; TRADELINE model; includes Allen wrench and screws to lock cover; field adjustable locking levers (68°F max. heat, 78°F min. cool).
44 Obsolete. Trane Comfort Corps logo.
44 Honeywell logo; meets DoD specs; includes Allen wrench and screws to lock cover; no thermometer; nonadjustable range stops set at 72°F (max. heat) and 78°F (min. cool) (22-26°C); field adjustable locking levers.
51, 53 Trane logo; part no. BAY28X182; °F/°C scaleplate; automatic fan in heating and cooling modes; heat anticipator set at 0.4A; used with Q674B1141, E1080.

44 Obsolete. Lennox logo; part no. 13F0001; °C scaleplate; heat anticipator factory set at .458A.

Trade Model Replacement
T874A1036 T874A1010

Remarks

T874A1036 T874A1036

T874A1036
T874A1036
T874A1036 T874A1036

Replacement has °F scaleplate.
Replacement has °F scaleplate.

T874A1036

T874A1036 Replacement has °F/°C scaleplate.
Y594C1421 or When using the T874C1036, T874A1036a set stage 1 heat anticipator for
total current draw of fan and stage 1 heat primary.
T874A1036 Replacement has °F scaleplate.

T874A1036 T874A1036

Replacement has °F scaleplate.

T874A1036 T874A1150

Replacement has °F scaleplate.

T874A1036 T874A1176

T874A1036a T874A1036

When used with Q674E1080, set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary; replacement has °F scaleplate.
Replacement has °F scaleplate.

aBoth the thermostat and subbase must be replaced.

60-2485--8

46

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
A1200

Fig.

No.

Description

51, 53 Obsolete. Carrier logo; part no. HH07AT164; °C scaleplate; includes Allen wrench and screws to lock cover; used with Q674B.

A1226
A1234
A1242 A1259 A1267 A1275
A1283

44 Honeywell logo; Honeywell Canada TRADELINE model; °C scaleplate; includes Allen wrench and screws to lock cover.
44 Obsolete. Friedrich Climate Master logo; heat anticipator factory set 1.2A.
44 Obsolete. Friedrich Climate Master logo.
44 Obsolete. Wesco logo; heat anticipator set at 0.8A.
59 Obsolete. McQuay logo; used with Q674Q1004.
44 Obsolete. Lennox logo; part no. 13F0101; meets DoD specifications.
75 McQuay Air Conditioning logo; part no. 03005047; used with Q674C1132 and thermistor to display outdoor temperature.

A1291 A1309 A1317 A1325

64 No logo; three-speed fan; one setpoint lever for heat and cool setpoints; used with Q674Q1012; used in Y594A1126.
44 Obsolete. Arcoaire Air Conditioning and Heating logo; part no. AO2076; includes Allen wrench and screws to lock cover.
44 Obsolete. McQuay logo; part no. 60685301; no scaleplate; used with Q674A-E,G.
75 Obsolete. McQuay logo; part no. 60685401; no scaleplate; used with Q674C1306 and outdoor thermistor to display outdoor temperature.

A1341
A1358 A1366

44 Obsolete. Trane logo; part no. THT-0577; meets DoD specifications.
44 York-Miraco logo.
51, 53 Obsolete. BDP Multi-logo; part no. HH07AT182.

A1374

44 American Standard logo; part no. ASYSTAT610; heat anticipator factory set at 0.4A.

A1390

44 Obsolete. Climate Control logo; part no. 654958804; °F/ °C scaleplate.

A1416

44 Obsolete. Reznor logo; part no. 654758803; °F/°C scaleplate.

A1424

214 Obsolete. Carrier Olympia Series Split System logo; part no. HH07AT194; used with Q674B1455 (HH93AZ208).

A1440

91 Obsolete. Simplex System 2000 logo; heat anticipator factory set at 1.2A; used with Q674G1005; used in Y594A.

A1465

212 Honeywell Trol-A-TempTM logo; Premier White® color; heat anticipator factory set at 0.10A; used with Q674E1379.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement T874A1036a
T874A1036
T874A1036 T874A1036 T874A1036 T874A1036 T874A1176 T874A1036
T874A1036/ Q674B1075a T874A1036
T874A1036 T874A1036
T874A1176 T874A1036 T874A1036a
T874A1036a T874A1036 T874A1036 See OEM for replacement. T874A1036
None

Remarks Set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary; replacement has °F scaleplate. Replacement has °F scaleplate.
Replacement does not have ability to display external temperature or momentary system switch position. Replacement has two levers and 1 speed fan.
Replacement does not have ability to display external temperature or momentary system switch position.
Set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary.
Replacement has °F scaleplate. Replacement has °F scaleplate.
See Trol-A-Temp for replacement.

47

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
A1481
A1507
A1523
A1549 A1556
A1572 A1580 A1598
A1614
A1622
T874B B1001 B1019 B1027 B1035 B1043

Fig.

No.

Description

44 Obsolete. Honeywell logo; Carrier part no. HH621602; includes locking cover and non-adjustable range stops set at 72°F (max. heat) and 78°F (min. cool).

44 Obsolete. Climate-Tel logo; includes Allen wrench and screws to lock cover and non-adjustable range stops set at 72°F (max. heat) and 78°F (min. cool).

224, Obsolete. AAF/Snyder General logo; part no. 225 066804404; °F/°C scaleplate; no cooling anticipation;
used with Q674E1312, C1298.

224, Obsolete. McQuay logo; part no. 066816601; no cooling 225 anticipation; used with Q674E1312, C1298.

51, 53 Carrier logo; part no. HH07AT164-W; °C scaleplate; Premier White® color; includes Allen wrench and screws to lock cover; used with Q674B.

224, Obsolete. McQuay logo; part no. 066816611; Premier 225 White® color; °F/°C scaleplate; no cooling anticipation.

91 California Economizer logo; Premier White® color; heat anticipator factory set at 1.2A.

224, McQuay logo; part no. 073319001; Premier White® 225 color; °F/°C scaleplate; includes Allen wrench, screws to
lock cover and AAF insert.

44 Honeywell logo; TRADELINE® model; °C scaleplate; Premier White® color; includes Allen wrench and screws to lock cover; used with Q674B.

44 Obsolete. York logo; part no. 2TH04703224A; includes Allen wrench and screws to lock cover and nonadjustable range stops set at 72°F (max. heat) and 78°F (min. cool).

1-stage heat, 2-stage cool.

44 Obsolete. Honeywell logo.

44 Honeywell logo; TRADELINE model; includes Allen wrench and screws to lock cover.

44 Obsolete. Westinghouse logo.

44, 46 Obsolete. Trane logo; used with Q674B1018, B1075; used in Y594B1026, B1034.

44 Obsolete. Honeywell logo; °C scaleplate.

B1050

44 Lennox logo; part no. 13F0201; °F/°C scaleplate.

B1068

44 Honeywell logo; Honeywell Canada TRADELINE model; °C scaleplate; includes Allen wrench and screws to lock cover.

B1076

88 Obsolete. Lennox Power Saver Two-Speed logo; part no. 91C7401; °F/°C scaleplate; used with Q674E1155.

B1084

44 Obsolete. Lennox Two-Speed logo; part no. 13F0301; °C scaleplate.

B1092

44 Obsolete. Honeywell logo; Heil Quaker part no. HQ521389HW.

B1100

88 Obsolete. Janitrol logo; part no. CHTS36-60; °F/°C scaleplate; used with Q674E1338; used in Y594B1042.

B1118

44 Honeywell logo; °C scaleplate; used with Q674A-E, G.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement
T874A1036

Remarks

T874A1176

See OEM for replacement.

See OEM for replacement. T874A1036a
See OEM for replacement. T874A1036

Replacement has °F scaleplate; replacement is beige.

See OEM for replacement.

T874A1036 T874A1010

Replacement has °F scaleplate; replacement is beige.

T874B1019 T874B1019

T874B1019 T874B1019

T874B1019 T874B1019 T874B1019

Replacement has °F scaleplate.
Replacement has °F scaleplate.
Replacement has °F scaleplate.

T874B1019 T874B1019 T874B1019

Replacement has °F scaleplate.
Replacement has °F scaleplate.

T874B1019 T874B1019

Replacement has °F scaleplate.
Replacement has °F scaleplate.

60-2485--8

48

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
B1134

Fig.

No.

Description

222 Obsolete. Carrier Synergy 2000 logo; part no. HH07AT199; °C scaleplate; used with Q674E1395 (HH93AZ209).

T874C C1000 C1018
C1026
C1034

2-stage heat, 1-stage cool.
44, 76 Honeywell logo; used with Q674B1075, C1181; used in Y594C1058.
60, 61, Honeywell logo; TRADELINE model; includes Allen 81, 92 wrench and screws to lock cover; used with
Q674C1074.
44 Obsolete. AAF logo; °C scaleplate; includes Allen wrench and screws to lock cover; non-adjustable range stops set at 23°C (max. heat and min. cool) (73°F).
44 Lennox logo; part no. 13F0401; °F/°C scaleplate.

C1042 C1059
C1067 C1075

44 Obsolete. Westinghouse logo; H1 anticipator factory set at.75A; H2 anticipator factory set at 1.2A; used with Q674A-E,G.
44, 142 Obsolete. Amana Air Conditioning logo; part no. D68535-2; H1 anticipator factory set at 1.2A; used with Q674E1056, Q674B1059, Q674F1022; used in Y594C1009, Y594C1017, Y594C1256, Y594C1330.
44 Obsolete. Sears logo; part no. 42. 9297; °F/°C scaleplate.
51, 53 Carrier logo; part no. HH07AT170; used with Q674B1166.

C1083 C1117

44 Obsolete. Trane logo; used with Q674E1007; used in Y594C1082.
44 Honeywell logo; °C scaleplate.

C1125 C1133 C1141
C1158 C1166

60, 61, Obsolete. Honeywell logo; 12°F (6.7°C) differential 92 between stage 1 heat and stage 2 heat; used with Q674G1047.
96 Obsolete. AAF/Snyder General logo; part no. 4ELN7546; no H1 heat anticipation; used with Q674AG,N and Q674C1173.
44 Obsolete. Honeywell logo; meets DoD specs; includes Allen wrench and screws to lock cover; no thermometer; non-adjustable range stops set at 72°F (max. heat) and 78°F (min. cool) (22-26°C); field adjustable locking levers.
44 Obsolete. Solaron special.
51, 53 Obsolete. Carrier logo; part no. HH07AT160; °C scaleplate; includes Allen wrench and screws to lock cover; used with Q674B.

C1174 C1182
C1190

44 Obsolete. Goettl logo.
60 Obsolete. Goettl logo; H1 anticipator factory set at 0.8A; used with Q674N1015.
44 Obsolete. Lennox logo; part no. 13F0501; °C scaleplate.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

T874B1019/ Q674E1049a

Wiring differences (old=new): W1=W; RC-RH jumper required; replacement has no LEDs.

T874C1018 T874C1018

T874C1018 Replacement has °F scaleplate.

T874C1018 T874C1018

Replacement has °F scaleplate.

T874C1018

T874C1018 Replacement has °F scaleplate.
Y594C1421 or When using the T874C1018, T874C1018a set stage 1 heat anticipator for
total current draw of fan and stage 1 heat primary. T874C1018
T874C1018 Replacement has °F scaleplate.
T8611M2025
T874C1018 Must have H1 anticipator set to maximum value.
T874C1141

T874C1018 T874C1018a
T874C1018 T874C1018

Replacement has °F scaleplate; set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary.

T874C1018 Replacement has °F scaleplate.

49

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
C1216 C1224 C1240
C1257
C1265

Fig.

No.

Description

44 Obsolete. Fasco part no. 1230-8197.

105 Obsolete. Square D logo.

44 Honeywell logo; Honeywell Canada TRADELINE model; °C scaleplate; includes Allen wrench and screws to lock cover.

44 Obsolete. Singer part no. 0200-5931; 8°F (4.4°C) differential between H1 and H2 heat.

44 Obsolete. Singer special; °C scaleplate; 5°C (8°F) differential between H1 and H2 heat.

C1273
C1281 C1307 C1315 C1323

44 Honeywell logo; °C scaleplate; includes Allen wrench and screws to lock cover; non-adjustable range stops factory set at 23°C (max. heat and min. cool) (73°F).
44 Obsolete. Heat Wave special.
44 Obsolete. Friedrich Climate Master logo.
44 Obsolete. Wesco logo; heat anticipator factory set at 0.8A.
44 Obsolete. Le Chauffage Urbain special; °C scaleplate.

C1331 C1349 C1372

82, 141 Obsolete. Duotherm logo; used with Q674E or Q674F. 61 Obsolete. Sigler logo; used with Q674N1023. 52 Obsolete. Honeywell logo; used with Q674B1190.

C1398
C1406
C1414
C1422 C1430 C1448

105 Obsolete. Fedders logo; °F/°C scaleplate; used with Q674L1090.
105 Obsolete. Climatrol logo; °F/°C scaleplate; used with Q674L1090.
105 Obsolete. Airtemp logo; °F/°C scaleplate; used with Q674L1090.
187 Obsolete. Honeywell logo; used with Q674B1208. 49 Obsolete. Lennox Zone Master Two-Speed logo; part
no. 25F7201; used with Q674B1224. 110, Obsolete. Lennox logo; part no. 24F5101; meets DoD 190 specifications; requires outdoor reset; used with
Q674L1165, L1355.

C1455 C1463

127 Obsolete. Williamson logo; used with Q674L1322. 82 Obsolete. AAF logo; °C scaleplate.

C1471

56 Obsolete. Mammoth logo; part no. 71120102; used with Q674B1257; used in Y594C1314.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

T874C1018

T874C1018

T874C1018 Replacement has °F scaleplate.

T874C1125 T874C1125 T874C1018

Replacement has 12°F differential between H1 and H2 heat.
Replacement has 12°F differential between H1 and H2 heat; replacement has °F scaleplate.
Replacement has °F scaleplate.

T874C1018 T874C1018 T874C1018

T874C1018 T874C1018 T874C1018 T874C1018/ Q674B1034 T874C1018/ Q674B1075 Y594R1425a
Y594R1425a
Y594R1425a
None T874C1018

Replacement has °F scaleplate.
For systems requiring automatic fan in cooling mode only. For systems requiring automatic fan in heating and cooling. Wiring differences (old=new): K=E, C=X; replacement has °F scaleplate. Wiring differences (old=new): K=E, C=X; replacement has °F scaleplate. Wiring differences (old=new): K=E, C=X; replacement has °F scaleplate.

Y594R1763a
Y594R1243a T874C1018 T874C1018

Wiring differences (new=old): R=V-VR, Y=M, G=F, B-X, W=Y, T=A, O=R, X2=E; Emergency Heat becomes stage 1 heat source.
Replacement has °F scaleplate.

60-2485--8

50

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
C1489
C1497 C1513 C1562 C1570 C1638
C1653
C1661

Fig.

No.

Description

121 Obsolete. Honeywell logo; non-adjustable range stops set at 75°F (max. heat and min. cool) (24°C); used with Q674L1157.

121 Obsolete. Honeywell logo; meets DoD specifications; used with Q674L1157.

44 Obsolete. Borg-Warner multi-logo; part no. 6TH11703124A.

44 Obsolete. Honeywell logo; Heil Quaker part no. HQ712001HW.

45 Obsolete. Williamson logo; used with Q674B1000; used in Y594C1280.

121 Obsolete. Honeywell logo; meets DoD specifications; includes Allen wrench and screws to lock cover; no thermometer; non-adjustable range stops set at 72°F (max. heat) and 78°F (min. cool) (22-26°C); field adjustable locking levers; used with Q674L1561; used in Y594C1322.

70 Obsolete. Fiberglas Canada; °C scaleplate; no H1, H2, or C1 anticipation; used with Q674S1000; used in Y594C1348.

99 Obsolete. McQuay logo; part no. 61202401; °F/°C scaleplate; includes momentary system switch position with spring release; used with Q674C1363.

C1695

45 Obsolete. Miller logo; used with Q674B1000; used in Y594C1355.

C1703

45 Obsolete. Intertherm logo; used with Q674B1000; used in Y594C1363.

C1737

44 Obsolete. Honeywell logo; Carrier part no. HH621603.

C1745

44 Obsolete. AAF/Snyder General logo; part no. 4ELN7919.

C1752

219 Obsolete. McQuay/Snyder General logo; part no. 061202402; 12°F offset between H1 and H2; °F/°C scaleplate; no C1 anticipation; used with Q674C1363.

C1760

44 Bard logo.

C1778

219 Obsolete. AAF/Snyder General logo; part no. 066804405; 12°F offset between H1 and H2; °F/°C scaleplate; no C1 anticipation; used with Q674C1363.

C1794

53 Obsolete. Carrier logo; Canada; part no. HH07AT160-W; Premier White® color; °C scaleplate; includes locking cover.

C1802

246 Obsolete. California Economizer logo; °F/°C scaleplate; used with Q674G1005; used in Y594C1371.

C1810

237 Obsolete. Honeywell logo; TRADELINE model; Premier White® color; used with Q674B1547; used in Y594C1389.

C1844

238 Energy Night logo; used with Q674F1592; used in Y594C1413.

C1851

60 Obsolete. Whalen logo.

C1869

219 McQuay logo; part no. 0073318801 Premier White® color; °F/°C scaleplate.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement Y594C1322a
Y594C1322a T874C1018 T874C1018 T874C1018 Y594C1322a

Remarks

See OEM for replacement.

T874C1125/ Q674B1075a
T874C1018

Replacement has HEAT-OFFCOOL system switching; no momentary system switch position; no LEDs.

T874C1018

T874C1018 T874C1018

T8611M2025

T874C1018
See OEM for replacement.

T874C1018 T874C1018

Set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary.

Y594C1389

Y594R1425
T874C1018 See OEM for replacement.

Jumper E-W2; system switch: EM.HT.-HEAT-OFF-COOL.

51

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

C1877

53 Obsolete. Honeywell logo; TRADELINE model; used with Q674B1554; used in Y594C1421.

Y594D1347 Jumper RC-RH; system switch: OFF-HEAT-AUTOCOOL

T874D

2-stage heat, 2-stage cool.

D1009 166, 82 Obsolete. Honeywell logo; used with Q674F1337, E1007; used in Y594D1222, D1339.

T874D1165

D1017

44, 88 Obsolete. Honeywell logo; TRADELINE model; includes Allen wrench and screws to lock cover; used with Q674A-G and Q674E1155.

T874D1165

D1025

44 Obsolete. Westinghouse logo; H1 anticipator factory set T874D1165 at 0.75A; H2 anticipator factory set at 1.2A.

D1033

44 Lennox logo; part no. 13F0601; °F/°C scaleplate.

T874D1165 Replacement has °F scaleplate.

D1041

53 York logo; part no. 2TH04701524A; used with Q674B1125.

T874D1165

D1058

44 Obsolete. Shiger special.

T874D1165

D1066

44 Obsolete. ITT logo.

T874D1165

D1074

51, 53, Carrier logo; part no. HH07AT172; used with 146 Q674F1030 (HH93AZ174), F1063 (HH93AZ181) or Q674B.

T874D1165a Set H1 anticipator for current draw of fan and stage 1 heat primary.

D1082 44, 46, Trane logo; used with Q674B1018, C1009, B1075, 48, 72 B1133; used in Y594D1024, D1040.

T874D1165

D1090

44 Obsolete. Dunham-Bush logo.

T874D1165

D1108

44 Obsolete. Westinghouse logo.

T874D1165

D1116 76, 89, Obsolete. Comfortmaker logo; part no. 1505-682; °F/°C T874D1165 Replacement has °F

94 scaleplate; used with Q674C1116, E1197, G1104.

scaleplate.

D1124

44 Obsolete. Airtemp special.

T874D1165

D1132

44 Honeywell logo; °C scaleplate.

T874D1165 Replacement has °F scaleplate.

D1140

44 Obsolete. Solaron special.

T874D1165 Replacement has °F scaleplate.

D1157 51, 53, Carrier logo; part no. HH07AT172; °C scaleplate; used 146 with Q674B or Q674F1030, F1063.

T874D1165a

Replacement has °F scaleplate; set H1 anticipator for current draw of fan and stage 1 heat primary.

D1165

82 Honeywell logo; SUPER TRADELINE® model; includes T874D1165 Allen wrench and screws to lock cover, field-adjustable range stops, field-adjustable locking levers.

D1173

51, 53 Trane logo; part no. BAY28X183; heat anticipator factory set at 0.4A.

T874D1165a Set H1 anticipator for current draw of fan and stage 1 heat primary.

D1181

51, 53 Obsolete. General Electric logo; locking cover includes Allen wrench and screws to lock cover and range stops set at 72°F (max. heat) and 78°F (min. cool).

T874D1165a Set H1 anticipator for current draw of fan and stage 1 heat primary.

D1199

44 Obsolete. Lennox logo; part no. 13F0701; °C scaleplate. T874D1165 Replacement has °F scaleplate.

D1207

114 Obsolete. Lennox logo; part no. 24F5201; used with Q674L1199 and C815A1013 or Q674L1389.

T8611M2025 Wiring differences (old=new): (programmable) V-VR=R, Y=W3, X=C, R=O,
M=Y, M2=Y2-W2, F=G; jumper Y2-W2; no outdoor reset needed; use only one system transformer.

aBoth the thermostat and subbase must be replaced.

60-2485--8

52

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
D1215
D1223
D1231

Fig.

No.

Description

44 Obsolete. Friedrich Climate Master logo; part no. AT5415; °F/°C scaleplate.

44 Honeywell logo; Honeywell Canada TRADELINE model; Celsius scale.

44 Obsolete. Honeywell logo; 12°F (7°C) differential between H1 and H2.

D1249 D1256 D1264
D1272

44 Obsolete. Fedders special.
44 Obsolete. Climatrol special.
107 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT173; used with Q674L1116 (HH93AZ171).
51, 53 Obsolete. Carrier logo; part no. HH07AT162-03; °C scaleplate; used with Q674B.

D1280 D1298
D1306 D1314

44 Obsolete. Command-Aire logo.
90, 232 Obsolete. Singer special; °C scaleplate; controls two separate heat/cool circuits; used with Q674D or Q674G1054, G1062.
90, 186 Obsolete. Trane special; part no. 02005949; controls two separate heat/cool circuits; used with Q674G1013.
44 Obsolete. McQuay logo; part no. 02005941; 12°F (6.6°C) differential between H1 and H2.

D1322 D1330

46 Obsolete. Amana logo; part no. D68535-03; used with Q674B1075; used in Y594D1149.
44 Obsolete. Trane logo; part no. 13080242; °C scaleplate.

D1355 D1363

44 Obsolete. Climate Control special; part no. 02005942; °C scaleplate; 6°C (11°F) differential between H1 and H2.
44 Obsolete. McQuay logo; part no. 02005943; 12°F (6.6°C) differential between H1 and H2; 6°F (3.3°C) differential between C1 and C2.

D1405

44 Obsolete. Trane logo; part no. 02005952; 12°F (6.6°C) differential between H1 and H2; 6°F (3.3°C) differential between C1 and C2.

D1413

44 Obsolete. Trane logo; part no. 02005956; 12°F (6.6°C) differential between H1 and H2.

D1421 D1439 D1447 D1454

44 Obsolete. Climate Control special; part no. 02005938; °C scaleplate.
90 McQuay logo; part no. 02005935; used with Q674G1096.
90 Obsolete. Climate Control special; part no. 02005940; °C scaleplate; used with Q674G1096.
51, 53 Obsolete. Carrier logo.

D1462

80 Obsolete. Fedders multi-logo; part no. THTX-220-A0HB, 88-58-00550-001; used with Q674E1205.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

T874D1165 Replacement has °F scaleplate.

T874D1165 Replacement has °F scaleplate.

T874D1165

Replacement has 2°F differential between H1 and H2.

T874D1165

T874D1165

See OEM for replacement.

T874D1165a

Replacement thermostat has °F scaleplate; set H1 anticipator for current draw of fan and stage 1 heat primary.

T874D1165

See OEM for replacement.

See OEM for replacement. T874D1165
T874D1165

Replacement has °F scaleplate; 2°F differential between H1 and H2.

T874D1165 T874D1165 T874D1165
T874D1165
T874D1165 T874D1165 T874D1165

Replacement has °F scaleplate.
Replacement has 2°F differential between H1 and H2.
Replacement has 2°F differential between H1 and H2; 2°F differential between C1 and C2.
Replacement has 2°F differential between H1 and H2; 2°F differential between C1 and C2.
Replacement has 2°F differential between H1 and H2.
Replacement has °F scaleplate.

T874D1165 T874D1165a T874D1165

Replacement has °F scaleplate.
Set H1 anticipator for current draw of fan and stage 1 heat primary.

53

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
D1470
D1488 D1496
D1504
D1512 D1520
D1538 D1553

Fig.

No.

Description

44 Obsolete. York logo; part no. 2TH04701624A; includes Allen wrench and screws to lock cover; °C scaleplate.

44 Obsolete. Risco special.

44 Obsolete. Borg Warner multi-logo; part no. 6TH04701524A; includes Allen wrench and screws to lock cover.

82 York logo; part no. 025-23321-000; °C scaleplate; used with Q674E1007; used in Y594D1180.

44 Honeywell logo; Heil Quaker part no. HQ712002HW.

44 Obsolete. Bard logo; adjustable lever stops set 68°F (max. heat) and 78°F (min. cool).

44 Obsolete. McQuay logo; part no. 02005937.

44 Obsolete. Climate Control special; part no. 02005944; °C scaleplate; 6°C differential between H1 and H2; 3°C differential between C1 and C2.

D1561 D1587 D1595

44 Obsolete. General Electric logo; used with Q674 A-G. 44 Obsolete. Stiles Four Seasons logo. 139 Obsolete. Nepco logo; used with Q674F1394.

D1603 D1611
D1629
D1678

44 Obsolete. Arcoaire logo.
44 Obsolete. No logo; Friedrich part no. AT5411; °F/°C scaleplate.
82 Obsolete. Reznor logo; °F/°C scaleplate; used with Q674E1007; used in Y594D1248.
44 Obsolete. Honeywell logo; Saudi Oger special; °C scaleplate; one setpoint lever; used with Q674A-K.

D1686

98 Obsolete. McQuay logo; part no. 60685501; 8°F (4.4°C) differential between H1 and H2; 6°F (3.3°C) differential between C1 and C2; used with Q674E1312.

D1694

202 Obsolete. McQuay logo; part no. 60685201; used with Q674G1120.

D1702

44 Obsolete. McQuay logo; part no. 60685101.

D1710

44 Trane logo.

D1728

44 York-Miraco logo.

D1744

44 American Standard logo; heat anticipator factory set at 0.4A.

D1751

44 Obsolete. Goettl logo; part no. 372080; range stops set at 68°F (max. heating) and 78°F (min. cooling).

D1769

82 Obsolete. Arcoaire logo; part no. 1506753; °F/°C scaleplate; used with Q674E1346; used in Y594D1297.

D1777

44 Obsolete. Climate Control logo; part no. 65495806; °F/ °C scaleplate.

D1785

82 Obsolete. Comfortmaker logo; part no. 1505753; °F/°C scaleplate; used with Q674E1346; used in Y594D1305.

D1793

44 Obsolete. McQuay logo; part no. 65495805; °F/°C scaleplate.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

T874D1165 Replacement has °F scaleplate.

T874D1165

T874D1165

T874D1165
T874D1165 T874D1165

Replacement has °F scaleplate.

T874D1165 T874D1165
T874D1165 T874D1165 T874D1165/ Q674B1018a T874D1165 T874D1165 T874D1165 T874D1165
T874D1165
See OEM for replacement. T874D1165 T874D1165 T874D1165 T874D1165

Replacement has 2°F differential between H1 and H2; 2°F differential between C1 and C2; replacement has °F scaleplate.
Replacement has HEAT-OFFCOOL system switching; no LEDs.
Replacement has °F scaleplate. Replacement has °F scaleplate. Replacement has °F scaleplate; separate heating and cooling setpoint levers. Replacement has 2°F differential between H1 and H2; 2°F differential between C1 and C2.

T874D1165

T874D1165 T874D1165 T874D1165 T874D1165

Replacement has °F scaleplate.
Replacement has °F scaleplate.
Replacement has °F scaleplate.
Replacement has °F scaleplate.

60-2485--8

54

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
D1801
D1819

Fig.

No.

Description

45, 208 Trol-A-Temp by Honeywell logo; H1 and H2 anticipators set at 0.10A; used with Q674B1463, D1115.

44 Marv Air Com Stat logo; part no. 50059; adjustable interstage between H1 and H2 and between C1 and C2; includes Allen wrench and screws to lock cover; field adjustable range stops; °F/°C scaleplate.

D1827
D1843 D1850 D1868
D1876 D1892 D1918
D1926
D1934 D1942
D1959 D1967 D1975 D1983
D1991

45, 208 Trol-A-Temp by Honeywell logo; Premier White® color; H1 and H2 heat anticipators set at 0.10A; used with Q674B1471, D1123.
45 Obsolete. Janitrol logo; Goodman part no. CHT 90-120; used with Q674B1000; used in Y594D1321.
44 Honeywell logo; Carrier part no. HH621606.
44 Bard logo; part no. 8405-031; H1 and H2 heat anticipators factory set at 0.25A; 5°F interstage differential between H1 and H2 and between C1 and C2; includes Allen wrench and screws to lock cover; field adjustable range stops.
44 Obsolete. AAF/Snyder General logo; part no. 4ELN6981A; °F/°C scaleplate.
44 Obsolete. Climate-Tel logo.
224, Obsolete. AAF/Snyder General logo; °F/°C scaleplate; 225 no cooling anticipation; used with Q674E1312, C1298;
66804407.
226 Obsolete. AAF/Snyder General logo; °F/°C scaleplate; no cooling anticipation; used with Q674G1120; 66804406.
44 Bard logo.
82 Honeywell logo; TRADELINE model; used with Q674E1403; used in Y594D1347; designed to replace York part no. 2TH04701024.
44 Rheem part no. 41-21444-01.
44 Obsolete. Desert Aire logo.
224, Obsolete. McQuay part no. 066816603; °F/°C 225 scaleplate; no cooling anticipation.
226 Obsolete. McQuay part no. 066816602; °F/°C scaleplate; no cooling anticipation; used with Q674G1120.
51, 53 Carrier logo; Premier White® color; °C scaleplate.

D2007

44 Ultra-Zone logo.

D2023

44 Honeywell logo; TRADELINE model; Premier White® color; °C scaleplate; includes locking cover; used with Q674A-K.

D2031

82 Obsolete. Honeywell logo; no cover; used with Q674E1049 and TG504A1025; used in Y594D1354.

D2049

45, 72, Obsolete. Carrier Heat Pump System Control logo; part 55, 66, no. HH07AT236; °F/°C scaleplate; used with Q674B-D,
184 Q674G; used in Y594D.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement
None T874D1165
None

Remarks
See Trol-A-Temp for replacement.
Replacement has a 2°F fixed interstage differential between H1 and H2 and between C1 and C2; replacement has °F scaleplate.
See Trol-A-Temp.

T874D1165

T874D1165 T874D1165

Replacement has 2°F fixed interstage differential between H1 and H2 and between C1 and C2.

T874D1165
T874D1165 See OEM for replacement.

Replacement has °F scaleplate.

See OEM for replacement.

T874D1165 Y594D1347a

T874D1165
T874D1165
See OEM for replacement.
See OEM for replacement.

T874D1165a
T874D1165 T874D1165

Set H1 anticipator for total current draw of fan and stage 1 primary; replacement has °F scaleplate.
Replacement has °F scaleplate and is beige.

T874D1165 or Y594D1354
T874D1165 Replacement has °F scaleplate.

55

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

D2056

44 Obsolete. ComStat logo; part no. 50056; °F/°C scaleplate; adjustable interstage on both heating and cooling; includes locking cover and field-adjustable locking levers.

T874D1165

Replacement has °F scaleplate and 2°F fixed differential in heating and cooling.

D2064

53 Obsolete. Carrier Weathermaker; part no. HH07AT209; stage 1 and 2 heat anticipator factory set 0.1A; taupe color; used with Q674E1445; used in Y594D1412.

T874D1165

Set stage 1 heat anticipator for total current draw of fan and stage 1 heat primary. Replacement is beige.

D2072

53 Obsolete. Carrier Zone Perfect; part no. HH07AT208;

T874D1165 Set stage 1 heat anticipator for

taupe color; used with Q674E1445; used in Y594D1420.

total current draw of fan and

stage 1 heat primary.

Replacement is beige.

D2080 139 Obsolete. Hydroheat logo.

T874D1165/ Replacement system switch: Q674B1018a HEAT-OFF-COOL; no LEDs.

D2098

44 Obsolete. Honeywell logo; °F scaleplate; one setpoint lever; used with Q674D1008; used in Y594D1438.

T874D1165

Replacement has °F scaleplate and two setpoint levers

D2106

44 Obsolete. Honeywell logo; °C scaleplate; one setpoint lever; used with Q674D1008; used in Y594D1446.

T874D1165

Replacement has °F scaleplate and two setpoint levers.

D2114

44 Obsolete. Bard logo; °C scaleplate.

T874D1165 Replacement has °F scaleplate.

D2122

224, Obsolete. McQuay 225

T874D2023 Replacement has °C scaleplate.

T874D1165 Replacement has °F scaleplate.

D2130 226 Obsolete. McQuay

See OEM for replacement.

D2148

44 Obsolete. Dry Aire Systems logo; °F/°C scaleplate.

T874D1165

D2155

139 Hydroheat logo; Premier White® color; °F/°C scaleplate; T874D1165/ Replacement system switch:

used with Q674F1634.

Q674B1018a HEAT-OFF-COOL; no LEDs.

D2163

208 Obsolete. Amana logo; part no. P1217501F; °F/°C scaleplate.

T874D1165

D2171

44 Obsolete. Amana logo; part no. P1217701F; °F/°C scaleplate.

T874D1942

D2189

44 Armstrong logo; part no. 01142A024; °F/°C scaleplate; includes Air Ease insert.

T874D1165

D2197

44 Liebert logo; part no. 138968P3; °F/°C scaleplate; interstage differential between H1 and H2 and between C1 and C2; includes Allen wrench and screws to lock cover; field-adjustable locking levers.

T874D1165

D2205

44 Aaon logo; Premier White® color; °F/°C scaleplate.

T874D1165

T874E

0-stage heat, 2-stage cool.

E1008

44 Obsolete. Honeywell logo.

T874E1016

E1016

44 Honeywell logo; TRADELINE model; includes Allen wrench and screws to lock cover; field-adjustable locking levers.

T874E1016

E1024

44 Obsolete. Westinghouse logo.

T874E1016

E1032

44 Lennox logo; part no. 13F0901; °F/°C scaleplate.

T874E1016 Replacement has °F scaleplate.

E1040

72 Obsolete. Trane logo; used with Q674C1009; used in Y594E1015.

T874E1016

aBoth the thermostat and subbase must be replaced.

60-2485--8

56

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
E1081

Fig.

No.

Description

44 Trane logo; part no. BAY28X186; °F/°C scaleplate.

E1099

44 Obsolete. Lennox logo; part no. 13F1001; °C scaleplate.

E1107

44 Honeywell logo; °C scaleplate.

E1123 E1149 E1156
E1164 E1206 E1230 T874F F1007 F1015
F1023 F1031
F1049

44 Obsolete. Amana logo; part no. D68535-4. 44 Obsolete. York logo; part no. 2TH04701724A. 44 Obsolete. Borg Warner multi-logo; part no.
6TH04701724A. 44 Obsolete. E. A. Juffali & Bros. logo. 44 Obsolete. Trane logo. 44 Obsolete. Climar logo.
2-stage heat, 0-stage cool. 44 Honeywell logo. 44 Honeywell logo; TRADELINE model; includes Allen
wrench and screws to lock cover; field-adjustable locking levers. 44 Obsolete. Lennox logo; part no. 13F1101. 44 Obsolete. Honeywell logo; °C scaleplate; used with 40003440-001 wallplate; used in Y594F1022. 44 Obsolete. Lennox logo; °C scaleplate.

F1056 F1072 F1098 F1106 F1114
F1122 F1130
F1148 F1155 T874G G1006

55, Obsolete. Honeywell logo; stages 1 and 2 heat 66 electrically isolated; used with Q674D1008.
44 Obsolete. Wesco logo; heat anticipator factory set at 0.8A.
189 Obsolete. Lennox logo; used with Q674D1008 to control an M839.
95 Obsolete. Oneida logo; part no. 30A0287-02; used with Q674K1018 on combination wood and oil applications.
44 Honeywell logo; Honeywell Canada TRADELINE model; °C scaleplate; includes Allen wrench and screws to lock cover; field-adjustable locking levers.
62 Obsolete. Honeywell logo; two heat setpoint levers; used with Q674B1307.
72, 91 Obsolete. Reznor logo; °F/°C scaleplate; used with Q674C, D, or G; used with Q674C1009, G1005; used in Y594F1048.
44 Obsolete. Trane logo; part no. THT 0584.
95 Honeywell logo; used with Q674K1026 on combination wood and oil applications.
Heat pump models; 2-stage heat, 1-stage cool; 1­stage changeover.
84, 155 Obsolete. Honeywell logo; used with Q674E1015.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement
T874E1016
T874E1016
T874E1016
T874E1016 T874E1016 T874E1016

Remarks
Replacement has °F scaleplate.
Replacement has °F scaleplate.
Replacement has °F scaleplate.

T874E1016 T874E1016 T874E1016

T874F1015 T874F1015

T874F1015 T874F1015
T874F1015
None

Replacement has °F scaleplate.
Replacement has °F scaleplate.

T874F1015

T874F1015 T874F1155

Set H1 and H2 anticipators to lowest settings.

T874F1015 Replacement has °F scaleplate.

T874F1015/ Q674D1040
T874F1015

Replacement has no LED.
Replacement has °F scaleplate.

T874F1015 T874F1155

Y594G1252a Wiring differences (old=new): R=O, M=Y, F=G, V=R, Y=W2; E-W2 jumper required.

57

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
G1014
G1022
G1048

Fig.

No.

Description

86, 150 Obsolete. Lennox logo; part no. 24F5801; °F/°C scaleplate; H2 anticipator factory set at 0.25A for fast cycle performance; changeover in cooling mode; independent heating and cooling circuits; used with Q674E1148, F1113.

86, 150 Obsolete. Lennox logo; part no. 24F5701; °F/°C scaleplate; H2 anticipator factory set at 0.25A for fast cycle performance; changeover in cooling mode; independent heating and cooling circuits; used with Q674E1148, F1113.

153, Obsolete. Westinghouse logo; H2 anticipator factory set 159 at 1.2A; used with Q674F1121, J1019.

G1055
G1071
G1089 G1097 G1105 G1113 G1121
G1139 G1147 G1154

161 Carrier Heat Pump System Control logo; part no. HH07AT171; H2 anticipator factory set at 0.8A; changeover in cooling mode; used with Q674J1035 (HH93AZ173).
50, 103, Obsolete. Carrier Heat Pump System Control logo; 126, meets DoD specifications; H2 anticipator factory set at 183 0.8A; used with Q674P1005 (HH93AZ169), L1041 (HH93AZ175), B1158, or J1050.
154 Obsolete. Marvair logo; special for Crispaire; H2 anticipator factory set at 1.2A; used with Q674F1204; used in Y594G1153.
155 Obsolete. Honeywell logo; Rheem part no. ZXMT-B79; used with Q674F1238 (41-20797-14).
153 Obsolete. Heat Wave (Southwest Mfg.) logo; H2 anticipator factory set at 1.2A; used with Q674F1170.
103 Obsolete. Carrier Heat Pump System Control logo; meets DoD specifications; H2 anticipator factory set at 0.8A; used with Q674L1041.
103 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT161; °C scaleplate; H2 anticipator factory set at 0.8A; includes Allen wrench and screws to lock cover.
143, Obsolete. Honeywell logo; used with Q674B1240, 234 C1108.
148 Obsolete. Honeywell logo; changeover in cooling mode; used with Q674F1139.
84, 139 Obsolete. Lennox logo; used with Q674E1015, F1105.

G1162

155 Obsolete. Lennox logo; meets DoD specifications; used with Q674F.

G1170

160 Obsolete. York logo; part no. 2TH11702424A; H2 anticipator is fixed; used with Q674J1027; used in Y594G1013.

G1188

147 Obsolete. Honeywell logo; Keeprite/Westinghouse special; H2 anticipator factory set 1.2A; °C scaleplate; changeover in cooling mode; used with Q674F1295.

G1196

160 Obsolete. York logo; °C scaleplate; changeover in cooling mode; used with Q674J1027; used in Y594G1138.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

Y594G1252a

Wiring differences (old=new): R=O, M=Y, F=G, Y=W2, V-VR=R (must use single transformer).

Y594G1252a

Wiring differences (old=new): R=O, M=Y, F=G, Y=W2, V-VR=R (must use single transformer).

Y594G1252a None

Wiring differences when replacing T874G/Q674J1019 (old=new): W=W2.
See subbase description for replacement information.

Y594G1419 Wiring differences (old=new): C=X; jumper Y1-W1.

Y594G1393a Wiring differences (old=new): A=L.
Y594G1252a
Y594G1252a
Y594G1419a Wiring differences (old=new): C=X; jumper Y1 -W1.
Y594G1419a Wiring differences (old=new): C=X; jumper Y1-W1.

None Y594G1252a Y594G1252a Y594G1419a

See subbase description for replacement information.
Wiring differences (old=new): C=X.
See subbase description for replacement information.
W1-Y1 jumper required.

Y594G1567a

Y594G1252a Wiring differences (old=new): S=L.
Y594G1567a

60-2485--8

58

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

G1204

162 Honeywell logo; designed for use on Trane heat pumps; Y594G1161a Designed for use on Trane

no H2 anticipation; changeover in cooling mode; used

heat pumps.

with Q674J1043 and C815A1005; used in Y594G1161.

G1212

155 Obsolete. Honeywell logo; H2 anticipator factory set at 0.2A; changeover in cooling mode; includes shunt to bypass H2 anticipator with W3 heat relays; used with Q674F1238.

Y594G1252a

G1220

235 Obsolete. Rheem logo; part no. RXMT-C71; changeover Y594G1252a in cooling mode; used with Q674F1238.

G1238

155 Obsolete. Ruud logo; part no. UXMT-C71; changeover in cooling mode; used with Q674F1238.

Y594G1252a

G1246

Obsolete. Honeywell logo; changeover in cooling mode.

155 Used with Q674F1212; used in Y594G1195, G1252, G1369.

Y594G1252a

170 Used with Q674F1410; used in Y594G1393.

Y594G1393a

G1261 58, 157 Obsolete. Borg-Warner; used with Q674D1032, F1253.

None

See subbase description for replacement information.

G1279 58, 157 Obsolete. Bryant logo; used with Q674D1032, F1253.

None

See subbase description for replacement information.

G1287 58, 157 Obsolete. Wesco logo; used with Q674D1032, F1253.

None

See subbase description for replacement information.

G1295

58 Obsolete. York logo; part no. 2TH11702724A; used with T874D1165/ Wiring differences (old=new):

Q674D1032.

Q674D1040 Y=Y2, O=Y1, W=W2; jumper

W1-Y2.

G1345

160 Obsolete. York logo; part no. 2TH11702624A; °C scaleplate; used with Q674J1027.

Y594G1575a

G1352

73 Obsolete. Command-Aire logo; 12°F differential between H1 and H2 for night setback; used with Q674C1066.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; RL jumper required; no night setback.

T8600D1004 Wiring differences (old=new): (programmable) Y1=O, Y2=Y, L=RH; RC-RH
jumper required; includes night setback.

G1378

79 Obsolete. Mammoth logo; H2 anticipator factory set at Y594H1012a Wiring differences (old=new):

0.8A; 12°F differential between H1 and H2 for night

R1=none, R2=L; R-L jumper

setback; °F/°C scaleplate; used with Q674C1124; used

required; no night setback.

in Y594G1294.

T8090A1007/ Includes night setback; W-Y Q682A1038a jumper required. (programmable)

G1402

129 Obsolete. York part no. 2TH11702824A; meets DoD specifications; used with Q674L1363.

Y594R1425a Wiring differences (old=new): W=W2, X=E, B=X; jumper Y-W1.

G1410

155 Obsolete. Borg-Warner multi-logo; part no. 6TH11703024A; used with Q674F1311.

T874G1246a or Y594G1252a

G1428

160 Obsolete. Borg-Warner multi-logo; part no. 6TH11702424A; used with Q674J1027; used in Y594G1229.

Y594G1567a

G1436

58 Obsolete. Borg-Warner multi-logo; part no. 6TH11702724A.

T874D1165/ Wiring differences (old=new): Q674D1040 Y=Y2, O=Y1, W=W2; jumper
W1-Y2.

aBoth the thermostat and subbase must be replaced.

59

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

G1444

160 Obsolete. ROCA logo; °C scaleplate; used with Q674J1027.

Y594G1567a Replacement has °F scaleplate.

G1451

155 Obsolete. BDP multi-logo; part no. HH641502; used with T874G1246a or

Q674F1212; used in Y594G1245.

V594G1252a

G1469

194 Obsolete. No logo; Addison special; used with Q674F1345; used in Y594G1344.

Y594G1252a Wiring differences (old=new): Y1=O, C=X, W1=Y1, X=L.

G1485

163 Obsolete. AAF logo; part no. 4ELN-7839; °F/°C

Y594G1393a No night setback or

scaleplate; 10°F differential between H1 and H2 for night

momentary reset switch.

setback and momentary RESET system switch position; T8611G1004 Includes night setback; no

used with Q674C1199.

(programmable) momentary reset switch.

G1493

167 Obsolete. Honeywell logo; Rheem part no. 41-20797-18; Y594G1526a used with Q674F1360.

G1501

195 Obsolete. Coleman logo; part no. 3600-375; changeover Y594G1252a Wiring differences (old=new):

in cooling mode; used with Q674F1378.

L1=L; changeover in cooling

only.

G1535

163 Obsolete. AAF/Snyder General logo; 4ELN7839 °F/°C Y594G1393a No night setback or

scaleplate; 10°F differential between H1 and H2 for night

momentary reset switch.

setback and momentary RESET system switch position; used with Q674C1199.

T8611G1004 Includes night setback. (programmable)

G1543

194 Obsolete. Addison logo; Weather King part no. 8403197; used with Q674F1345; used in Y594G1328.

Y594G1252a Wiring differences (old=new): Y1=O, C=X, W1=Y, X=L.

G1568

160 Obsolete. Luxaire logo; part no. 026-00068-000; °C

Y594G1367a Replacement has °F

scaleplate; used with Q674J1126; used in Y594G1351.

scaleplate.

G1576

169 Obsolete. Coleman logo; part no. 3600-373; changeover Y594G1633a in heating and cooling mode; used with Q674F1402; used in Y594G1377.

G1584

73 Obsolete. No logo; Friedrich part no. AT5784; 8°F (4.4°C) differential between H1 and H2; used with Q674C1223.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; L-R jumper required; no night setback.

T8611G1004 Includes night setback. (programmable)

G1592

155 Obsolete. Arcoaire logo; used with Q674F1212; used in T874G1246a or

Y594G1385.

Y594G1252a

G1600

199 Obsolete. Honeywell logo; meets DoD specifications; used with Q674F1428; used in Y594G1401.

Y594G1419a Wiring differences (old=new): jumper W1-Y1.

G1618

73 Obsolete. Honeywell logo; 12°F differential between H1 Y594H1012a Wiring differences (old=new):

and H2 for night setback; used with Q674C1256.

Y1=O, Y2=Y, L=R, R=none;

L-R jumper required; no night

setback.

T8600C1162 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; includes night setback.

G1626

167 Honeywell logo; used with Q674F1436; used in Y594G1526.

None

G1642

227 Honeywell logo; TRADELINE model; meets DoD specifications; used with Q674F1444; used in Y594G1419.

Y594G1419a

aBoth the thermostat and subbase must be replaced.

60-2485--8

60

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

G1659

177 Obsolete. Mammoth logo; 0.8A maximum current

Y594H1012a Wiring differences (old=new):

through B or O terminal; 12°F differential between H1

R2=L, R1=none; L-R jumper

and H2 for night setback; used with Q674C1330; used in

required; no night setback.

Y594G1427.

T8611G1004 Includes night setback.

(programmable)

G1675

174 Obsolete. American Standard logo; part no. ASYSTAT650; used with Q674J1142; used in Y594G1443.

Y594G1161a

G1691

176 Obsolete. Command Aire logo; part no. P1013-0060; 12°F (6.6°C) differential between H1 and H2 for night setback; used with Q674C1389, C1397.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, R=none; L-R jumper required; no night setback.

T8611G1004 Includes night setback. (programmable)

G1717

175 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT102N; used with Q674J1167; used in Y507J1201.

Y594G1252a

Wiring differences (old=new): C=X, D=L; replacement has AUX. HEAT and EM. HEAT LEDs.

G1741

227 Honeywell logo; TRADELINE model; includes factory set range stops at 68°F (max. heat) and 78°F (min. cool); Premier White® color; used with Q674F1477; used in Y594G1476.

Y594G1476a

G1758

211 Trol-A-Temp by Honeywell logo; Premier White® color; changeover is provided by Trol-A-Temp zone panel; used with Q674F1485; used in Y594G1492.

None

See Trol-A-Temp for replacement.

G1774

216 Obsolete. Comfortmaker logo; part no. 1505756; used with Q674J1175; used in Y594G1500.

Y594G1252a Wiring differences (old=new): E=W2, W1=W3, X=E, C=X.

G1782

216 Obsolete. Arcoaire logo; part no. 1506756; used with Q674J1175; used in Y594G1518.

Y594G1252a Wiring differences (old=new): E=W2, W1=W3, X=E, C=X.

G1790

161 Obsolete. Carrier logo; Premier White® color; °C scaleplate; includes Allen wrench and screws to lock cover; used with Q674J1191.

Y594G1252a Wiring differences (old=new): C=X; replacement has °F scaleplate.

G1816

163 Climate Master logo; part no. AT5716; °F/°C scaleplate; Y594G1393a No momentary reset switch. 10°F differential between H1 and H2 and momentary RESET system switch position.

G1824

227 Honeywell logo; Australian TRADELINE model; Premier Y594G1476a White® color; °C scaleplate; used with Q674F1477; used in Y594G1534.

G1832

231 Obsolete. Intertherm logo; used with Q674F1519; used in Y594G1542.

Y594G1252a Replacement has auto changeover in cooling mode only.

G1840

231 Obsolete. Miller logo; used with Q674F1519; used in Y594G1559.

Y594G1252a Replacement has auto changeover in cooling mode only.

G1857

229 Obsolete. Lennox logo; °C scaleplate; Premier White® color; used with Q674F1535; used in Y594G1583.

Y594G1161a Wiring differences (old=new): E=X2, C=B, L=F.

G1865

160 Honeywell logo; TRADELINE model; designed to

Y594G1567a

replace Y594G1013 (York part no. 2TH11702424),

Y594G1229 (York part no. 6TH11702424), and York part

no. 2TH117704124); used with Q674J1209; used in

Y594G1567.

aBoth the thermostat and subbase must be replaced.

61

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

G1873

160 Obsolete. Honeywell logo; TRADELINE model; Premier Y594G1567a Replacement is beige. White® color; designed to replace Y594G1013 (York part no. 2TH11702424), Y594G1229 (York part no. 6TH11702424), and York part no. 2TH117704124); used with Q674J1225; used in Y594G1575.

G1881 167 Rheem; part no. 41-20797-18.

Y594G1526a

G1899

169 Obsolete. Amana; part no. 10574101; used with Q674F1550; used in Y594G1591.

Y594G1633a

G1915

155 Econar logo; used with Q674F1212; used in Y594G1609.

Y594G1252a

170 Used with Q674F1410.

Y594G1393a

G1923

176 Trane logo; part no. X13510599010; H2 make 12°F below H1 make.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, R=none; L-R jumper required; no night setback.

T8611G1004 Includes night setback. (programmable)

G1931

155, Obsolete. Honeywell logo; Premier White® color; °C 170 scaleplate; used with Q674F1568.

None

See subbase description for replacement information.

G1949

73 Obsolete. Carrier Heat Pump System Control logo; part Y594H1012a Wiring differences (old=new):

no. HH07AT204; °F/°C scaleplate; H2 make 8°F below

Y1=O, Y2=Y, L=R, R=none; R-

H1 make; used in Y594.

L jumper required; no night

setback.

T8600D1004 Wiring differences (old=new): (programmable) Y1=O, Y2=Y, L=RH; RC-RH
jumper required; includes night setback.

G1956 30, 103, Obsolete. Carrier logo; Canada; Premier White® color; 126, °C scaleplate; includes locking cover. 183

Y594G1476 Replacement has °F scaleplate.

G1964

160 York logo; Canada; Premier White® color; °C scaleplate; Y594G1575a Replacement has °F

used in Y594G1625.

scaleplate.

G1972

169 Honeywell logo; TRADELINE model; used with Q674F1584; used in Y594G1633.

Y594G1633a

G1980

169 Obsolete. Amana logo; part no. 10574103; used with Q674F1600; used in Y594G1641.

Y594G1633a Wiring differences (old=new): W3=W2.

G1998

155 Obsolete. Tempstar logo (Inter-City Products); used in Y594G1658; used with Q674F1212.

Y594G1252a

G2004

103 Honeywell logo; TRADELINE model; used with Q674L; Y594G1666 used in Y594G.

161 Used with Q674J1274; used in Y594G1674.

Y594G1674

G2046

155, WaterFurnace logo; part no. TA21H03; Premier White® 170 color; °F/°C scaleplate; used with Q674F1667; used in
Y594G1716.

Y594G1716

T874H

Heat pump model; 1-stage heat, 1-stage cool, 1-stage changeover in cool.

H1005

74 Obsolete. Command Aire logo; used with Q674C1041.

Y594H1012a Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required.

H1013

74 Obsolete. Friedrich part no. AT5813; °C scaleplate; used Y594H1012a Wiring differences (old=new):

with Q674C1041.

Y1=O, Y2=Y; L-R jumper

required; replacement has °F

scaleplate.

aBoth the thermostat and subbase must be replaced.

60-2485--8

62

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
H1021

Fig.

No.

Description

74 Obsolete. Friedrich Climate Master logo; part no. AT5821; °F/°C scaleplate; used with Q674C1041.

H1039 H1054

79 Obsolete. Mammoth logo; °F/°C scaleplate; used with Q674C1124; used in Y594H1004.
74 Obsolete. No logo; Friedrich part no. AT5854; used with Q674C1041.

H1062 H1070 H1088 H1096 H1112

164 Honeywell logo; used with Q674C1249; used in Y594H1012.
172, Obsolete. Carrier Heat Pump System Control logo; part 173 no. HH07AT166; °C scaleplate; used with Q674B1406
(HH93AZ200) or Q674C1322 (HH93AZ199).
172, Obsolete. Carrier Heat Pump System Control logo; part 173 no. HH07AT167; used with Q674B1406 (HH93AZ200)
or Q674C1322 (HH93AZ199).
177 Obsolete. Mammoth Water Source Heat Pump logo; °F/ °C scaleplate; changeover stage 0.8A maximum; used B or O terminal; used with Q674C1330.
74 No logo; Friedrich part no. AT5812; used with Q674C1355.

H1120 H1138

205 Obsolete. Command Aire logo; part no. P1013-0055; used with Q674C1389, C1397.
221 Obsolete. Climate Master logo; part no. AT5838; used with Q674C1470.

H1146 205 Trane logo; part no. X13510598010.

H1153

173 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT167; °F/°C scaleplate; used with Q674C1322; used in Y594H1053.

H1161

74 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT203; °F/°C scaleplate; used with Q674C1496; used in Y594H1038.

T874J

Heat pump model. 2-stage heat, 1-stage cool.

J1002

124, Obsolete. Carrier Heat Pump System Control logo; part 144, no. HH07AT175; used with Q674J1068 (HH93AZ183), 206, Q674J1159 (HH93AZ196), Q674L1074 (HH93AZ186), 207 Q674L1637 (HH93AZ195).

J1010

124, Obsolete. BDP multi logo; part no. 34427DP124/P272171 2471; used with Q674J1084, L1371.

J1028

124, Obsolete. Carrier Heat Pump System Control logo; part 144, no. HH07AT165; °C scaleplate; used with Q674J1068 206, (HH93AZ183), Q674J1159 (HH93AZ196), Q674L1074 207 (HH93AZ186), Q674L1637 (HH93AZ195).

J1036

124, Obsolete. Miller logo; part no. 9132230; used with 171 Q674J1217.

J1044

124, Obsolete. Intertherm logo; part no. 9132240; used with 171 Q674J1217.

J1051

124, Obsolete. Carrier logo; part no. HH07AT165-W; Premier 144 White® color; °C scaleplate.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement Y594H1012a
Y594H1012a Y594H1012a Y594H1012a
None None Y594H1012a Y594H1012a Y594H1012a Y594H1012a Y594H1012a None Y594H1012a
None
None None
T8511G1021 T8511G1021
None

Remarks Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required; replacement has °F scaleplate. Wiring differences (old=new): R1=R, R2=L. Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required.
See subbase description for replacement information.
See subbase description for replacement information.
Wiring differences (old=new): R1=R, R2=L; L-R jumper required. Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required. Wiring differences (old=new): Y1=O, Y2=Y. Wiring differences (old=new): Y1=O, Y2=Y; replacement has MALFUNCTION LED only. Wiring differences (old=new): Y1=O, Y2=Y. See subbase description for replacement information.
Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required.
See subbase description for replacement information.
See subbase description for replacement information. See subbase description for replacement information.
See subbase description for replacement information.

63

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

J1069

124, Obsolete. Honeywell logo; TRADELINE model; used 144, with Q674J1282; used in Y594J1019. 206, 207

T8511G1021

J1077

124, Obsolete. Nordyne logo; part no. 9148300; °F/°C 171 scaleplate.

T8511G1021

T874K

Heat pump model; 2-stage heat, 1-stage cool, automatic changeover in heat.

K1001

77 Obsolete. LSI Mammoth logo; used with Q674C1090.

Y594G1419a

Wiring differences (old=new): RH-RC=R, W1=B, W3=W2, W2=W1; remove Y1-W1 jumper.

K1019

181 Obsolete. McQuay/Snyder General logo; part no.

Y594G1252a Wiring differences (old=new):

60687301; °F/°C scaleplate; H1 anticipator set at 0.83A;

C=X, W=B, A=L; jumper

8°F interstage differential between H1 and H2 for night

E-W2; no night setback.

setback; used with Q674C1280.

T8611G1004 Wiring differences (old=new):

(programmable) C=X, W=B, A=X2; jumper X2-

R; remove external time clock;

includes night setback.

K1027

181 Obsolete. AAF/Snyder General logo; part no.

Y594G1252a Wiring differences (old=new):

066804403; °F/°C scaleplate; H1 anticipator set at

C=X, W=B, A=L; jumper

0.83A; 8°F interstage differential between H1 and H2 for

E-W2; no night setback.

night setback; used with Q674C1280.

T8611G1004 Wiring differences (old=new):

(programmable) C=X, W=B, A=X2; jumper

X2-R; remove external time

clock; includes night setback.

T874L

Heat pump model; 2-stage heat, 1-stage cool, changeover in cool.

L1000

198 Obsolete. Carrier logo; part no. HH07AT176; used with Y594G1419a E-W2 jumper required. Q674E1270 (HH93AZ189).

L1018

138, Obsolete. Carrier Multiplex System logo; part no. 165 HH07AT178; used with Q674B1356 (HH93AZ192) or
Q674C1264 (HH93AZ193).

See OEM for replacement.

L1026

198 Obsolete. Honeywell logo; BDP part no. P272-2786; used with Q674E1304.

Y594G1419a E-W2 jumper required.

L1034

203 Obsolete. McQuay logo; part no. 60687201; °F/°C

Y594G1419a Wiring differences (old=new):

scaleplate; H1 anticipator factory set at 0.83A; used with

Y=Y1, W=B, A=X1; remove

Q674C1280.

Y1-W1 jumper.

L1059

215, Obsolete. Carrier logo; part no. HH07AT192; used with 213 Q674B1448 (HH93A2202) or Q674C1413
(HH93AZ204).

See OEM for replacement.

L1067

203 Obsolete. AAF/Snyder General logo; part no. 066804402; H1 anticipator factory set at 0.83A; used with Q674C1280.

Y594G1419a Wiring differences (old=new): Y=Y1, W=B, A=X1; remove Y1-W1 jumper.

L1075

203 Obsolete. McQuay logo; part no. 073318601; Premier White® color; °F/°C scaleplate; includes AAF insert.

See OEM for replacement.

T874N

Heat pump model; 2-stage heat; 1-stage cool plus changeover; changeover in heat mode.

N1008

178 Obsolete. Williamson logo; used with Q674F1196; used T874N1016 in Y594N1007.

N1016

178 Honeywell Heat Pump Thermostat logo; used with Q674F1220.

T874N1016

N1024

179, Bard logo; H1 and C1 anticipation fixed; used with 217 Q674F1261.

None

See subbase description for replacement information.

aBoth the thermostat and subbase must be replaced.

60-2485--8

64

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

N1040

179 Obsolete. Honeywell logo; H1 and C1 anticipation fixed; used with Q674F1261; used in Y594N1015.

None

N1057

178 Obsolete. Intertherm logo; part no. 9111882; used with Q674F1220; used in Y594N1023.

T874N1016

N1065

178 Obsolete. Miller logo; Nordyne part no. 9122240; used with Q674F1220; used in Y594N1031.

T874N1016

T874P

Heat pump model; 2-stage heat, 1-stage cool, automatic changeover in cool.

P1006

57, 78 Obsolete. McQuay logo; part no. 860-442725B-00; 8°F (4.4°C) interstage differential between H1 and H2; used with Q674B1273, C1140.

None

See subbase description for replacement information.

P1014

78 Obsolete. Friedrich/Climate Master logo; °F/°C

T8600D2028 Wiring differences (old=new):

scaleplate; 8°F (4.4°C) differential between H1 and H2 (programmable) L=R, W=O; W-Y jumper

for night setback; used with Q674C1207.

required; includes night

setback.

P1022

97 Obsolete. Friedrich/Climate Master logo; part no. AT5922; °F/°C scaleplate; 8°F (4.4°C) differential between H1 and H2 for night setback; used with Q674C1215.

None

See subbase description for replacement information.

P1030

97 Obsolete. No logo; Friedrich part no. AT5930; 8°F (4.4°C) differential between H1 and H2 for night setback; used with Q674C1215.

None

See subbase description for replacement information.

P1055

68, 97 Obsolete. Carrier Heat Pump System Control logo; part no. HH07AT205; °F/°C scaleplate; heat interstage differential 8°F (4.4°C).

None

See subbase description for replacement information.

T874Q

1-stage heat; used with another T874 for night setback.

Q1005

44 Honeywell logo.

T874A1036

Q1013

44 Obsolete. Lennox logo; part no. 13F1201; °F/°C scaleplate.

T874A1036 Replacement has °F scaleplate.

Q1021

44 Obsolete. Lennox logo; part no. 13F1301; °C scaleplate. T874A1036 Replacement has °F scaleplate.

T874R

Heat pump model; 2-stage heat, 1-stage cool, manual changeover.

R1004

47 Obsolete. Honeywell logo; used with Q674B1042; used Y594R1243a Wiring differences (old=new):

in Y594R1029.

W1=W2.

R1012

47 Obsolete. Honeywell logo; Addison heat pump; used with Q674B1109.

Y594R1243a Wiring differences (old=new): W1=W2.

R1020

102 Obsolete. Lennox logo; part no. 24F5401; °F/°C

Y594R1243a Wiring differences (old=new):

scaleplate; H1 and C1 anticipators are fixed; auxiliary

M=Y, F=G, V-VR=R, Y=W2,

heat circuit powered by separate transformer; used with

R=O; replacement has °F

Q674L1025.

scaleplate.

R1038

102 Obsolete. Lennox logo; °C scaleplate; H1 and C1 anticipators are fixed; auxiliary heat circuit powered by separate transformer; used with Q674L1025.

Y594R1243a

Wiring differences (old=new): M=Y, F=G, V-VR=R, Y=W2, R=O; replacement has °F scaleplate.

R1046

120, Obsolete. York logo; part no. 2TH11702224A; H2 101 anticipator is fixed; used with Q674L1272 in Y594R1011
or with Q674L1094.

Y594R1664a

R1053

109 Obsolete. Honeywell logo; H2 anticipator is fixed; used Y594R1763a Designed for use on Trane

with Q674L1140; used in Y594R1136.

heat pumps.

R1061

104 Obsolete. Honeywell logo; H2 anticipator is field adjustable; changeover in cooling; used with Q674L1082.

Y594R1243a Replacement has auto fan in Emergency Heat mode.

aBoth the thermostat and subbase must be replaced.

65

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
R1079 R1087 R1095 R1103 R1111
R1129 R1137
R1145 R1152 R1160 R1178
R1186 R1194 R1202
R1210 R1228
R1236 R1244 R1251
R1269
R1285 R1301

Fig.

Trade Model

No.

Description

Replacement

Remarks

123 Obsolete. Ruud logo; part no. UXMT-C70; used with Q674L1157.

Y594R1243a

120 Obsolete. Honeywell logo; Special for Dunham Bush; use with Q674L.

Y594R1664a

123 Obsolete. Rheem logo; part no. RXMT-C70; used with Q674L1157.

T874R1152/ Y594R1243a

104 Obsolete. Westinghouse logo; used with Q674L.

Y594R1243a

116, Obsolete. Marvair logo; H2 anticipator factory set at 104 1.2A; used with Q674L1215, L1082; used in
Y594R1128.

Y594R1243a Replacement has auto fan in Emergency Heat mode.

113 Bard logo; used with Q674L1181.

Y594R1243a Wiring differences (old=new): X1=X.

108, Obsolete. Honeywell logo; Heil Quaker part no. 125 HQ711597HW; used with Q674L1132; used in
Y594R1110.

Y594R1292a

120 Obsolete. York logo; °C scaleplate; H2 anticipator is fixed; used with Q674L1272; used in Y594R1102.

Y594R1664a

115 Honeywell logo; used with Q674L1207, L1033; used in Y594R1243a Y594R1243.

182 Obsolete. Honeywell Advanced Heat Pump System logo; used with Q674L1298 and W89.

None

110, Obsolete. Lennox logo; part no. 24F5601; °F/°C 111 scaleplate; auxiliary heat circuit powered by separate
transformer; fast cycle stage H2 anticipator; requires outdoor reset and independent circuits; used with Q674L1165, L1355.

Y594R1763a Wiring differences (old=new): V-VR=R, M=Y, F=G, X=B, Y=W, A=T, R=O, E=X2.

182 Obsolete. Honeywell Advanced Heat Pump System logo; used with Q674L1231 and W89.

None

115 Obsolete. Amana logo; used with Q674L1249 and W89. Y594R1243a

201 Obsolete. Intertherm logo; part no. 9111871; used with Q674L1264 or Q674L1595; used in Y594R1185.

Y594R1672a Wiring differences (old=new): W2=W, Z=no connection,
K=X, W=G, W1=H, X=B.

101 Obsolete. Roca logo; °C scaleplate; used with Q674L1017.

Y594R1243a Wiring differences (old=new): W=W2, X=L, B=X.

120 Obsolete. York logo; part no. 2TH11702524A; °C scaleplate; used with Q674L1272 and C815A1005; used in Y594R1144.

Y594R1672a

115 Obsolete. Williamson logo; includes Allen wrench and screws to lock cover; used with Q674L1348.

T874R1152

115 Obsolete. Westinghouse logo; used with Q674L1314 and W89.

T874R1152/ Y594R1243a

120 Obsolete. York logo; part no. 2TH11702324A; H2 anticipator is fixed; used with Q674L1272 and C815A1039.

Y594R1672a

122 Obsolete. Fedders multi logo; part no. THTX-120-HEHB 88-58-00540-001; used with Q674L1066; used in Y594R1037.

Y594R1615a Wiring differences (old=new): K=E, C=X, W1=B, Z=L.

123 Obsolete. Honeywell logo; Rheem part no. 41-20796-15; Y594R1243a used with Q674L1157.

113 Obsolete. Comfortmaker logo; part no. 1505-714; used Y594R1243a Wiring differences (old=new):

with Q674L1181; used in Y594R1417.

X1=X.

aBoth the thermostat and subbase must be replaced.

60-2485--8

66

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
R1319 R1327
R1335
R1343
R1350 R1368 R1376 R1384
R1392 R1400 R1426
R1434 R1442 R1459 R1467 R1475 R1483 R1491 R1509 R1517 R1525 R1541 R1558 R1566

Fig.

Trade Model

No.

Description

Replacement

Remarks

191 Obsolete. Carrier part no. 42QH400083; used with Q674B1281 on two speed fan applications.

See OEM for replacement.

120 Obsolete. Borg-Warner multi-logo; part no. 6TH11702224A; used with Q674L1272; used in Y594R1193.

Y594R1672a

106 Obsolete. BDP multi-logo; part no. HH641501; H2

Y594R1243a

anticipator factory set 1.2A; used with Q674L1405; used

in Y594R1201.

133 Obsolete. Fedders multi-logo; part no. THTX-120-HEHC 88-58-0056-001; used with Q674L1413; used in Y594R1219.

Y594R1425a Wiring differences (old=new): K=E, C=X1, Z=L; remove Y1-W1 jumper.

113 Obsolete. Honeywell logo; used with Q674L1181.

Y594R1243a Wiring differences (old=new): X1=X.

125 Obsolete. Coleman logo; part no. 3600-368; used with Q674L1421; used in Y594R1235.

Y594R1797a

115 Honeywell logo; °C scaleplate; used with Q674L1207. T874R1152

131, Obsolete. Carrier Heat Pump System Control logo; part 135 no. HH07AQ170; used with Q674L (HH93AZ187),
Q674L (HH93AZ197), or Q674L (HH93AZ198).

Y594G1243a Wiring differences (old=new): C=X.

128 Obsolete. Williamson logo; used with Q674L1447; used Y594R1425a Wiring differences (old=new):

in Y594R1250.

A=L.

113 Obsolete. LSI part no. 104710001; used with Q674L1181, L1462.

See subbase description for replacement information.

136 Obsolete. Trane Weathertron Heat Pump logo; part no. BAYSTAT339 (WY28X0112); °F/°C scaleplate; used with Q674L1496; used in Y594R1284.

Y594R1763a

134 Ruud logo; part no. 41-20796-32; used with Q674L1504; Y594R1300a used in Y594R1649.

134 Rheem logo; part no. 41-20796-28; used with Q674L1504; used in Y594R1631.

Y594R1300a

134 Obsolete. Honeywell logo; Rheem part no. 41-20796-25; Y594R1300a used with Q674L1504.

108 Honeywell logo; used with Q674L1512; used in Y594R1292.

Y594R1292a

123 Honeywell logo; scale range 42°F to 88°F; used with Q674L1520; used in Y594R1300.

Y594R1300a

130 Obsolete. Comfortmaker logo; °F/°C scaleplate; used

Y594R1763a Wiring differences (old=new):

with Q674L1538 and C815A1005; used in Y594R1318.

W1=W, E=X2, X=F, C=B.

137 Obsolete. Honeywell logo; TRADELINE model; used with Q674L1553; used in Y594R1326.

Y594R1615a

47 Obsolete. Slant/Fin logo; used with Q674B1042; used in Y594R1243a Wiring differences (old=new):

Y594R1334.

W1=W2.

130 Obsolete. Arcoaire logo; part no. 150671; used with Q674L1538 and C815A1005; used in Y594R1342.

Y594R1763a Wiring differences (old=new): W1=W, E=X2, X=F, C=B.

113 Obsolete. Arcoaire logo; used with Q674L1181; used in Y594R1243a Wiring differences (old=new):

Y594R1359.

X1=X.

67 Obsolete. Goettl logo; part no. 372071; used with Q674B1349.

Y594R1300a

134 Obsolete. Universal Parts logo; part no. 41-20796-45; used with Q674L1504; used in Y594R1623.

Y594R1300a

130 Obsolete. Honeywell logo; used with Q674L1538 and C815A1005; used in Y594R1375.

Y594R1763a Wiring differences (old=new): W1=W, E=X2, X=F, C=B.

aBoth the thermostat and subbase must be replaced.

67

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Number
R1574
R1582
R1590

Fig.

No.

Description

132 Obsolete. Comfortmaker logo; part no. 1505739; used with Q674L1538; used in Y594R1383.

132 Obsolete. Arcoaire logo; part no. 150739; used with Q674L1538; used in Y594R1391.

115 Obsolete. Refac logo; used with Q674L1207.

R1608

119 Obsolete. Honeywell logo; Intertherm heat pump; used with Q674L1264; used in Y594R1409.

R1616 R1624

168 Honeywell logo; SUPER TRADELINE® model; used with Q674L1587; used in Y594R1425.
200 Obsolete. Honeywell logo; used with Q674L1595; used in Y594R1433.

R1632 R1640 R1657
R1673 R1699

134 Obsolete. Honeywell logo; used with Q674L1603.
115 Obsolete. Hitecsa logo; °C scaleplate; H2 anticipator factory set at 1.2A; used with Q674L1207.
136 Obsolete. American Standard logo; part no. ASYSTAT651; requires outdoor reset; used with Q674L1611; used in Y594R1441.
108 Heil logo; part no. 1060321, HAXB004TW01; used with Q674L1132; used in Y594R1466.
119 Obsolete. Miller logo; used with Q674L1264; used in Y594R1482.

R1707 R1715 R1723
R1731
R1749 R1814 R1822 R1830 R1855

209 Trol-A-Temp by Honeywell logo; Premier White® color; used with Q674L1678; used in Y594R1490.
209 Trol-A-Temp by Honeywell logo; used with Q674L1186; used in Y594R1508.
218 Obsolete. No logo; Snyder General part no. 654958B07; °F/°C scaleplate; used with Q674L1702 and C815A1005; used in Y594R1516.
108 Obsolete. Inter-City Products logo; part no. HQ11477909HW; used with Q674L1132; used in Y594R1524.
108 Tempstar logo; part no. 1060322, TAXB004TW01; used with Q674L1132; used in Y594R1532.
108 Obsolete. Honeywell logo; Keeprite part no. THPC; °C scaleplate; used with Q674L1132; used in Y594R1607.
230 Honeywell logo; TRADELINE model; used with Q674L1710; used in Y594R1615.
134 Obsolete. Addison logo; WeatherKing part no. 4120796-61; used with Q674L1504; used in Y594R1656.
228 Obsolete. Lennox logo; Premier White® color; °C scaleplate; outdoor reset required (use C815A1005); used with Q674L1728; used in Y594R1714.

R1871

120 Honeywell logo; designed to replace Y594R1011 (York part no. 2TH11702224); used with Q674L1736; used in Y594R1664.

aBoth the thermostat and subbase must be replaced.

Trade Model Replacement

Remarks

Y594R1243a Wiring differences (old=new): C=X, X=L, W=W2.

Y594R1243a Wiring differences (old=new): C=X, X=L, W=W2.

T874R1152/ Replacement has °F Y594R1243a scaleplate.

Y594R1763a Wiring differences (old=new): W2=W, X=B, Z=F, K=X2, W1=O.

Y594R1425a

Y594R1243a
Y594R1243a Y594R1243a Y594R1763a

Wiring differences (old=new): X=B, Z=F, W2=W, K=X2, W1=O.
Replacement has °F scaleplate.

Y594R1292a

Y594R1763a
None None Y594R1672a

Wiring differences (old=new): W2=W, X=B, Z=F, K=X2, W1=O.
See Trol-A-Temp for replacement.
See Trol-A-Temp for replacement.
Wiring differences (old=new): W1=W, X=X2, C=B.

Y594R1292a

Y594R1292a

Y594R1292a Y594R1615a

Replacement has °F scaleplate.

Y594R1300a

Y594R1763a Y594R1664a

Wiring differences (old=new): Y1=Y, L=F, W1=W, E=X2, C=B; replacement has °F scaleplate.

60-2485--8

68

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

R1889

120 Honeywell logo; designed to replace Y594R1151 (York part no. 2TH11702324), Y594R1193 (York part no. 6TH11702224), and York part no. 2TH11704024; used with Q674L1736 and C815A1054; used in Y594R1672.

Y594R1672a

R1897

230 Honeywell logo; Premier White® color; used with Q674L1751; used in Y594R1680.

Y594R1680a

R1905

120 Obsolete. Honeywell logo; Premier White® color; designed to replace Y594R1151 (York part no. 2TH11702324), Y594R1193 (York part no. 6TH11702224), and York part no. 2TH11704024; used with Q674L1777 and C815A1054; used in Y594R1698.

Y594R1672a Replacement is beige.

R1913

120 Obsolete. Honeywell logo; Premier White® color; designed to replace Y594R1011 (York part no. 2TH11702224); used with Q674L1777; used in Y594R1706.

Y594R1664a Replacement is beige.

R1921

115 Obsolete. Econar logo; used with Q674L1207; used in Y594R1722.

Y594R1243a

R1939

197 American Standard logo (Trane); part no. ASYSTAT651A; includes outdoor reset; used with Q7674L1801; used in Y594R1748.

Y594R1763a

R1947

168 Obsolete. Inter-City Products logo; part no. HQ1149406HW; used with Q674L1819; used in Y594R1755.

Y594R1425a

R1954

197 Honeywell logo; TRADELINE model; includes outdoor reset; used with Q674L1827; used in Y594R1763.

Y594R1763a

Direct replacement for Y594R1748 (T874R1939/ Q674L1801) American Standard logo (ASYSTAT 651A) and Y594R1136 (T874R1053/Q674L1140).

R1962

115 Obsolete. Consolidated Industries logo; part no.

Y594R1680a Includes CHECK LED.

9036100; Premier White® color; used with Q674L1843;

used in Y594R1771.

R1970

120 York logo; Canada; Premier White® color; °C scaleplate; Y594R1672a Replacement has °F

used in Y594R1789; used with C815A1039.

scaleplate.

R1988

125 Honeywell logo; TRADELINE model; used with Q674L1868; used in Y594R1797.

Y594R1797

Direct replacement for Y594R1235 (T874R1368/ Q674L1421) Evcon/Coleman part no. 3600-368.

R2002

245 Obsolete. Amana Air Conditioning logo; part no. 10574102; used in Y594R1805.

Y594R1797 Wiring differences (old=new): C/X=X.

R2010

245 Obsolete. Amana Air Conditioning logo; part no. 10574104.

Y594R1797 Wiring differences (old=new): C/X=X, W3=W2.

R2028

209 Obsolete. York logo; part no. 2TH11703424A; used with Y594R1797 Q674L1918 in Y594R1821.

R2036 134 Ruud logo; °C scaleplate; used with Q674L1504.

See OEM for replacement.

T874S

2-stage heat, 3-stage cool.

S1001

223 Obsolete. Carrier Synergy 2000 Heat Pump System Control logo; used with Q674F1501.

T8611M2025 Includes night setback. (programmable) or see OEM for
direct replacement.

T874V

1-stage cool.

V1008

69 Obsolete. No logo; Carrier part no. HH07AT177; used with Q674R1003.

T874A1036

aBoth the thermostat and subbase must be replaced.

69

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 8. T874 Cross Reference.

Model Fig. Number No.

Description

Trade Model Replacement

Remarks

T874W

3-stage heat, 2-stage cool, manual changeover.

W1007

118 Obsolete. Honeywell logo; Westinghouse special; used T8611M2025 Includes night setback.

with Q674L1256.

(programmable)

W1015

54 Honeywell logo; used with Q674B1216 and C815A1005; T874W1015 used in Y594W1014.

W1023

233 Obsolete. Lennox Advanced Heat Pump System logo; used with Q674L1280 and W89.

T874W1015

W1031

140 Obsolete. No logo; Rheem part no. 41-20797-20; used T8611M2025 Includes night setback. with Q674L1546 and C815A1005; used in Y594W1022. (programmable)

W1049

100 Obsolete. McQuay logo; part no. 61202501; 12°F interstage differential between H2 and H3 for night setback; used with Q674C1363.

T8611M2025 Includes night setback. (programmable)

W1056

220 Obsolete. McQuay/Snyder General logo; part no.

See OEM for

1202501; 12°F differential between H2 and H3 for night replacement.

setback; used with Q674C1363 (61202502).

W1064

220 Obsolete. AAF/Snyder General logo; part no. 066804408; 12°F differential between H2 and H3 for night setback; used with Q674C1363 (66804408).

See OEM for replacement.

W1072

140 Obsolete. Honeywell logo (Inter-City Products); used in T8611M2025 Includes night setback.

Y594W1030.

(programmable)

W1080

220 McQuay logo; part no. 073318901; Premier White® color; 12°F differential between H2 and H3 for night setback.

None

W1106

247 Obsolete. Addison logo; part no. 843-277; °F/°C scaleplate; used with Q674L1934 in Y594W1055.

T8611M2025

T874Y

Heat pump model; 2-stage heat, 2-stage cool, heat or cool auto changeover.

Y1005

210 Obsolete. Mammoth Water Source Heat Pump logo; used with Q674E1353; used in Y594Y1004.

See OEM for replacement.

Y1013

248 Obsolete. WaterFurnace logo; part no. TA21H03; Premier White® color; °F/°C scaleplate; used with Q674F1675 (32003081).

See OEM for replacement.

aBoth the thermostat and subbase must be replaced.

60-2485--8

70

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

Q674A

System: HEAT-AUTO-COOL; Fan: AUTO-ON

A1001

71 Standard OEM.

Q674A1019

A1019

71 TRADELINE® model; used with T874A-D.

Q674A1019

A1035

71 Obsolete. Trane part no. BAS-0435; used with T874A-D. Q674A1019

A1043

71 Honeywell logo; TRADELINE model;

Q674A1019

A1050

71 Obsolete. Standard OEM.

Q674A1043

Q674B

System: HEAT-OFF-COOL; Fan: AUTO-ON

B1000

45 Standard OEM; used with T874C1570, C1695, C1703, Q674B1034 D1843; used in Y594C1363.

B1018

44 Standard OEM; used with T874B1035, D1082; used in Q674B1018 Y594B1026, D1016.

B1026

45 Obsolete. System: HEAT-OFF-RESET-COOL.

Q674B1034

B1034

45 TRADELINE

Q674B1034

B1042

47 Obsolete. Used with T874R1004, R1509; used in Y594R1029, R1334.

Y594R1243a Wiring differences (old=new): W1=W2.

B1059

45 Obsolete. Factory installed RC-RH jumper; used with T874C1059; used in Y594C1256.

Q674B1034 Field wire RC-RH.

B1075

46 Auto fan in heating and cooling mode; used with T874B1035, C1000, D1082; used in Y594D1040.

Q674B1075

B1083

51 Obsolete. Carrier part no. HH93AZ178; factory installed RC-RH jumper.

Q674B1075a One system transformer only.

B1091

45 Obsolete. Carrier part no. HH93AZ184; factory installed RC-RH jumper.

Q674B1034

B1109

47 Obsolete. Addison heat pump; used with T874R1012.

Y594R1243a Wiring differences (old=new): W1=W2.

B1117

44 Obsolete. Carrier part no. HH93AZ180; factory installed RC-RH jumper.

Q674B1018a

B1125

53 Obsolete. York part no. 2TB04700324A; used with T874D1041.

Q674B1075a Jumper RC-RH; replacement has no LOCKOUT LED.

B1133

48 Obsolete. Includes FILTER LED; used with T874D1082; used in Y594D1156.

Q674B1018

B1141

51 Trane part no. BAY28X185; automatic fan operation in heat and cool mode.

Q674B1075

Set T874 H1 anticipator for combined load of heat relay and fan relay.

B1158

50 Obsolete. Used with T874G1071.

T874C1018/ W1-Y1 and RH-RC jumpers Q674B1018a required.

B1166

249 Carrier part no. HH93AZ179; factory installed RC-RH jumper; LOCKOUT LED; used with T874C1075 (HH07AT170).

Y594C1421 or Replacement only requires Q674B1075a one transformer and has no
LOCKOUT LED.

B1190

52 Obsolete. Wards special; factory installed RH-RC and Gas Furnace:

F-W3 jumpers; used with T874C1372.

Q674B1034

Electric Furnace: Q674B1075

B1208 187 Obsolete. Used with T874C1422.

None

B1216

54 Used with T874W1015 and C815A1005; used in Y594W1014.

Q674B1216

B1224

49 Obsolete. Lennox part no. 25F7301; four LEDs; used with T874C1430.

Q674B1034 Replacement has no LEDs.

a Both the thermostat and subbase must be replaced.

71

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number B1240
B1257
B1273
B1281
B1299 B1307 B1315
B1331 B1349 B1356 B1372 B1380 B1398 B1406
B1414 B1448 B1455 B1463 B1471 B1513 B1521
B1539 B1547

Fig.

Q674 Trade

No.

Description

Replacement

Remarks

234 Obsolete. Northrup heat pump; AUX HEAT LED; used with T874G1139.

Y594G1252a

Wiring differences (old=new): Y1=Y2, W1=W2; EM HT system switch position is not operational.

56 Obsolete. LSI-Mammoth; RESET LED; automatic fan operation in heat and cool modes; used with T874C1471; used in Y594C1314.

Q674B1075 Replacement has no LED.

57 Obsolete. McQuay part no. 860-442727B-00; System: T874A1036/ Wiring differences (old=new): OVERRIDE-HEAT-OFF-COOL; used with T874P1006. Q674B1075a Y=Y1, L=R, W=O; jumper Y1W1; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

191 Obsolete. Carrier no. 42QH400103; System: HEATOFF-COOL; Fan: LOW-HI-CONT; international symbols on switches; used with T874R1319.

See OEM for replacement.

46 Obsolete. Heil Quaker part no. HQ521714HW.

Q674B1075

62 Obsolete. Includes two LEDs; used with T874F1122.

T874F1015/ Replacement has no LEDs. Q674D1040a

68 Obsolete. Friedrich part no. AQ5215; OVERRIDE and T8600D2028 Wiring differences (old=new):

SERVICE LEDs; used with T874P1022, P1030.

(programmable) L=R, W=O; W-Y jumper

required; set dual fuel switch

to electric heat; night setback.

65 Obsolete. Includes two LEDs; used with T874A1002. Q674B1034 Replacement has no LEDs.

67 Obsolete. Goettl part no. 372072; used with T874R1541.

Y594R1300a

138 Obsolete. Carrier part no. HH93AZ192; used with T874L1018 (HH07AT178).

See OEM for replacement.

44 Obsolete. Trane part no. BAS-0427; used with T874A-D. Q674B1018

46 Obsolete. Trane part no. BAS-0426; used with T874A-D. Q674B1075

48 Obsolete. Trane part no. BAS-0431; FILTER LED; used Q674B1034 Replacement has no LEDs. with T874A-D.

172 Obsolete. Carrier part no. HH93AZ200; FAULT and CHECK FILTER LEDs; used with T874H1070 (HH07AT166), T874H1088 (HH07AT167) or T874H1153 (HH07AT167); used in Y594H1046.

T874A1150/ Wiring differences (old=new): Q674B1075a Y=Y1; jumper W1-Y1;
replacement has no LEDs.

51 American Standard (Trane) part no. ASYSTAT1617.

Q674B1075

215 Obsolete. Carrier part no. HH93A2202; Fan: Lo-MedHigh-On; used with T874L1059.

See OEM for replacement.

214 Obsolete. Carrier part no. HH93AZ208; Fan: Lo-Med- See OEM for

High-On; used with T874A1424 (HH07AT194).

replacement.

45 Trol-A-Temp; used with T874D1801.

None

See Trol-A-Temp.

45 Trol-A-Temp; used with T874D1827.

None

See Trol-A-Temp.

53 Obsolete. TRADELINE; exact replacement for Q674B1125 (York part no. 2TB04700324).

Q674B1075 Jumper RC-RH; replacement has no LOCKOUT LED.

53 Obsolete. Carrier Canada part no. HH93AZ179-W; gray color; includes LOCKOUT LED and removable jumpers between RC and RH terminals.

Q674B1075

Jumper RC-RH; replacement has no LOCKOUT LED; beige color.

45 Obsolete. Carrier part no. HH93AZ139; used with T874D2049; used in Y594D1370.

Q674B1034

237 Obsolete. TRADELINE; gray color; used with T874C1810; used in Y594C1389.

Y594C1389

a Both the thermostat and subbase must be replaced.

60-2485--8

72

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

B1554

82 Obsolete. TRADELINE; includes LOCKOUT LED and removable jumpers between RC and RH terminals; used with T874C1877; used in Y594C1421.

Y594D1347

Jumper RH-RC; system switch: Off-HEAT-AUTOCOOL.

B1562

45 Obsolete. Amana logo; part no. P1217701F; removable jumpers between RC and RH terminals.

Q674B1034

B1570

45 Obsolete. Armstrong logo; part no. 03299A18.

Q674B1034 Replacement is beige.

B1588

45 Obsolete. Standard OEM.

Q674B1034 Replacement is beige.

Q674C

System: OFF-AUTO; Fan: AUTO-ON

C1009

72 Standard OEM; used with T874D1082; used in Y594D1024.

Q674C1058

C1017

Obsolete. Includes factory-installed RC-RH jumper; used with T874A,F,Q.

Q674C1058

C1033

72 Trane part no. BAY28X187.

Q674C1058

C1041

74 Obsolete. Command Aire heat pump; used with T874H1005, H1054.

Y594H1012a Wiring differences (old=new): Y1=O, Y2=Y; W-Y jumper required.

C1058

72 TRADELINE

Q674C1058

C1066

73 Obsolete. Command Aire heat pump; used with T874G1352.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; RL jumper required; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) Y1=O, Y2=Y, L=R; W-Y
jumper required; night setback.

C1074

81 Obsolete. Used with T874C1018.

Q674C1058 Jumper W2-Y1 and RH-RC.

C1090

77 Obsolete. LSI-Mammoth heat pump; used with T874K1001.

Y594R1419a

Wiring differences (old=new): RH-RC=R, W1=B, W3=W2, W2=W1; remove Y1-W1 jumper.

C1108

143 Obsolete. Northrup special; AUX HEAT LED; used with Y594R1243a Wiring differences (old=new):

T874G1139.

Y1=Y, W1=W2, C=X.

C1116

76 Obsolete. McQuay part no. 02005959; two LEDs; used Q674C1058 Replacement has no LEDs. with T874D1116.

C1124

79 Obsolete. LSI-Mammoth heat pump; RESET LED; used with T874G-H; used in Y594G-H.

Y594G1294 T8600D2028

C1132

75 Obsolete. McQuay part no. 03005049; spring return momentary system switch position; used with T874A1283.

See OEM for replacement.

C1140

78 Obsolete. McQuay no. 860-442728B-00; System: OVERRIDE-AUTO-OFF; used with T874P1006.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

C1157

72 Obsolete. York part no. 2TB04700124A.

Q674C1058

C1165

192 Obsolete. McQuay part no. 03005050; spring return momentary system switch position.

See OEM for replacement.

C1173

96 Obsolete. American Air Filter part no. 4ELN-8787; used Q674C1058 Replacement has no LEDs. with T874C1133.

C1181

76 Obsolete. California heat pump; used with T874C1000. Q674C1058

C1199

163 Obsolete. American Air Filter part no. 4ELN-8788; two LEDs; spring return momentary system switch position; used with T874G1485, G1535.

T8600D2028

No momentary reset switch.

a Both the thermostat and subbase must be replaced.

73

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

C1207

78 Obsolete. Friedrich; System: OVERRIDE-AUTO-OFF; T8600D2028 Wiring differences (old=new):

used with T874P1014.

(programmable) L=R, W=O; W-Y jumper

required; night setback.

C1215

97 Obsolete. Friedrich part no. AQ5315; System: OVERRIDE-AUTO-OFF; OVERRIDE and SERVICE LEDs; used with T874P1022, P1030.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

C1223

73 Obsolete. Friedrich part no. AQ5323; used on systems requiring night setback contacts; used with T874G1584.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; RL jumper required; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

C1249

164 Includes MALFUNCTION LED; used with T874H1062; Y594H1012a used in Y594H1012.

C1256

73 Obsolete. Used with T874G1618.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; RL jumper required; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

C1264

165 Obsolete. Carrier part no. HH93AZ193; used with T874L1018 (HH07AT178).

See OEM for replacement.

C1280

181, Obsolete. McQuay heat pump; part no. 60687401; 203 COMP FAULT LED; used with T874K1019, L1034.

T8600D2028 See thermostat description for replacement information.

C1298

76, Obsolete. McQuay part no. 60684801; SERVICE LED; See OEM for

225 used with T874A1523, A1549, D1918.

replacement.

C1306

75 Obsolete. McQuay part no. 60685001; SERVICE LED; See OEM for spring return momentary system switch position; used replacement. with T874A1325.

C1314

72 Obsolete. Trane part no. BAS-0429; used with T874A-F. Q674C1058

C1322

173 Obsolete. Carrier part no. HH93AZ199; FAULT and CK FILTER LEDs; used with T874H1070 (HH07AT166), T874H1088 (HH07AT167) or T874H1153 (HH07AT167); used in Y594H1053.

Y594H1012a Wiring differences (old=new): 2=X.

C1330

177 Obsolete. LSI-Mammoth part no. 71115201; RESET LED; used on systems with night setback contacts; used with T874G1659, H1096; used in Y594G1427, H1020.

Y594H1012a Wiring differences (old=new): R1=R; R2=L.

C1355

74 Friedrich part no. AQ355; SERVICE LED; used with T874H1112.

Y594H1012a Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required.

C1363

99 Obsolete. McQuay part no. 61202601; SERVICE LED; T874C1125/ Replacement has HEAT-OFF-

auto fan in heat and cool mode; used with T874C.

Q674B1075a COOL.

219 Obsolete. Used with T874C.

See OEM for replacement.

220 Obsolete. Used with T874W.

See OEM for replacement.

100 Obsolete. Used with T874W.

T8611M2025 Includes night setback. (programmable)

C1371

72 American Standard part no. ASYSTAT616.

Q674C1058

a Both the thermostat and subbase must be replaced.

60-2485--8

74

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

C1389

205, Obsolete. Command Aire part no. P1099-0021; two 176 LEDs; used with T874G-H.

None

See thermostat description for replacement information.

C1397

205, Obsolete. Command Aire part no. P1099-0023; used 171 with T874G-H.

None

See thermostat description for replacement information.

C1413

213 Obsolete. Carrier part no. HH93AZ204; Fan: Lo-MedHigh-On; used with T874L1059.

See OEM for replacement.

C1439

217 Obsolete. Bard part no. 8404-016; used with T874N1024.

See OEM for replacement.

C1454

163 Obsolete. Climate Master part no. AQ5354; two LEDs; Y594G1393a No momentary reset switch. spring return momentary system switch position.

C1462

25 Climate Master Special.

Q674C1058 Replacement has no LEDs.

C1470

221 Obsolete. Climate Master part no. RQ5370; used with T874H1138.

Y594H1012a Wiring differences (old=new): Y1=O, Y2=Y; replacement has MALFUNCTION LED only.

C1496

74 Obsolete. Carrier part no. HH93AZ213; includes SERVICE LED; used with T874H1161; used in Y594H1038.

Y594H1012a Wiring differences (old=new): Y1=O, Y2=Y; L-R jumper required.

C1504

83 Obsolete. Carrier part no. HH93AZ214; used in Y594.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; RL jumper required; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) Y1=O, Y2=Y, L=R; W-Y
jumper required; night setback.

C1512

97 Obsolete. Carrier part no. HH93AZ216; System: Override-Auto-Off; includes two LEDs; used in Y594.

T8600D2028 Wiring differences (old=new): (programmable) L=R, W=O; W-Y jumper
required; night setback.

C1520

72 Obsolete. Carrier part no. HH93AZ210; used with T874D2049; used in Y594D1388.

Q674C1058

C1538

163 Climate Master part no. AQ5354; System: Off-AutoOverride; includes two LEDs and momentary spring position.

Y594G1393 No momentary reset switch.

C1546

76, Obsolete. McQuay part no. 060684802; gray color; 225 includes one LED.

Q674C1058 Replacement has no LEDs; beige color

C1553

181, Obsolete. McQuay logo; part no. 073319901; includes Q674C1058 Replacement is beige. 203 one LED.

C1561

76 McQuay logo; part no. 073319701; includes one LED. See OEM for replacement.

C1579

99, McQuay logo; part no. 073320001; includes one LED. See OEM for

100

replacement.

C1595

72 Obsolete. Standard OEM.

Q674C1058

Q674D

System: None; Fan: None

D1008 55, 66 Obsolete. Used with T874D1082, F1056; used in Y594D1057.

Q674D1040

D1016

55 Obsolete. Carrier part no. HH93AZ170; RC-RH jumper. Q674D1040 RC-RH jumper required.

D1032

58 Obsolete. Borg-Warner; used with T874G.

T874D1165/ Wiring differences (old=new): Q674D1040a Y=Y2, O=Y1, W=W2; jumper
W1-Y2 required.

D1040

55 TRADELINE

Q674D1040

D1057 55, 66 Obsolete. York part no. 2TB04700424A.

Q674D1040

a Both the thermostat and subbase must be replaced.

75

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number
D1065

Fig.

No.

Description

63 Obsolete. Includes two LEDs; used with T874F1122.

D1099 D1107
D1115 D1123 D1156
D1164
D1172
D1180 D1198

55, 66 Obsolete. Trane part no. BAS-0430; used with T874A-F.
55, 66 Obsolete. Snyder General part nos. 654958801/ 1520503/ 4ELN30070.
208 Trol-A-Temp; used with T874D1801.
208 Trol-A-Temp; gray color; used with T874D1827.
55 Obsolete. Gray color; includes removable jumper between RC and RH terminals.
66 Obsolete. Carrier part no. HH93AZ211; used in Y594D1440.
208 Obsolete. Amana logo; part no. P121501F; removable jumpers between RC and RH terminals.
55 Obsolete. York logo; part no. 2TH04703224A.
55, 66 Obsolete. Standard OEM.

Q674E E1007 E1015

System: OFF-HEAT-AUTO-COOL; Fan: AUTO-ON
82 Used with T874D1504; used in Y594D1180.
84 Obsolete. Lennox heat pump; used with T874G1006, G1154.

E1049
E1056
E1064 E1072
E1080 E1098 E1106

193 TRADELINE; used with T874D2031 and TG504A1025; used in Y594D1354.
82 Obsolete. Amana part no. D68535-7; used with T874C1059, C1331; used in Y594C1009.
83 Obsolete. RC-RH jumpered internally; EM HEAT LED.
82 Carrier part no. HH93AZ176; RC-RH jumpered internally.
82 Trane part no. BAY28X184.
85 Obsolete. Used with T874A-D.
185 Obsolete. ITT Nesbitt.

E1114 E1122 E1148

87 Carrier part no. HH93AZ177; RC-RH jumper; LOCKOUT LED to indicate compressor lockout; used with HH07AT series thermostats.
83 Obsolete. Square D part no. 63600-002-10; CHECK LED.
86 Obsolete. Lennox heat pump; used with T874G1014, G1022.

E1155 E1197

88 Obsolete. Lennox part no. 91C7501; HIGH and LOW LEDs; used with T874B1076, D1017.
89 Obsolete. McQuay part no. 02005961; two LEDs; used with T874D1116.

E1205

80 Obsolete. Fedders special; SERVICE LED; used with T874D1462.

E1213

82 York part no. 2TB04700224A.

E1221

82 Heil Quaker part no. HQ712003HW.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement
T874F1015/ Q674D1040a
Q674D1040
Q674F1040.

Remarks Replacement has no LEDs.

None None Q674D1040

See Trol-A-Temp. See Trol-A-Temp. Replacement is beige color.

Q674D1040

Q674D1040

Q674D1040
T874D1165/ Q674D1040

Replacement is beige color.

Q674E1049 Y594G1252a
Q674E1049

Wiring differences (old=new): R=O, M=Y, F=G, V=R, Y=W2; E-W2 jumper required.

Q674E1049 RC-RH jumper required.

Q674E1049 Q674E1049 RC-RH jumper required.

Q674E1049 Q674E1049 See OEM for replacement. Q674E1049

RC-RH jumper required.
RC-RH jumper required; replacement has no LED.

Q674E1049 Replacement has no LED.

Y594G1252a Q674E1049

Wiring differences (old=new): R=O, M=Y, F=G, Y=W2, V-VR=R; must use single transformer.
Replacement has no LEDs.

Q674E1049 Q674E1049

Wiring differences (old=new): D=O; replacement has no LEDs.
Replacement has no LEDs.

Q674E1403 Q674E1049

60-2485--8

76

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number E1262 E1270 E1304 E1312 E1320 E1338
E1346
E1353 E1379 E1395

Fig.

No.

Description

82 Lennox part no. 13F1701.

198 Obsolete. Carrier part no. HH93AZ189; used with T874L1000 (HH07AT176).

82 Obsolete. BDP part no. P272-1887; used with T874L1026.

224 Obsolete. McQuay part no. 60684901; one LED; used with T874A1523, A1549, D1686, D1918.

82 Obsolete. Trane part no. BAS-0434.

88 Obsolete. Goodman part no. CHTS36-60; HIGH and LOW LEDs; used with T874B1100; used in Y594B1042.

82 Obsolete. Snyder General part nos. 1505753/1506753/ 654958B02; used with T874D1769; used in Y594D1297.

210 Obsolete. Mammoth; used with T874Y1005; used in Y594Y1004.

212 Trol-A-Temp by Honeywell; used with T874A1465.

222 Obsolete. Carrier part no. HH93AZ209; used with T874B1134 (HH07AT199).

E1403 E1411
E1429
E1445 E1460 E1478

82 TRADELINE; designed to replace York 2TH04701024; used with T874D1942; used in Y594D1347.
82 Obsolete. Carrier Canada part no. HH93AZ176-W; gray color; removable jumper between RC and RH terminals.
87 Carrier Canada part no. HH93AZ177-W; gray color; includes LOCKOUT LED; removable jumper between RC and RH terminals.
82 Obsolete. Carrier part no. HH93AZ217-W; gray color; removable jumper between RC and RH terminals.
224 McQuay logo; part no. 073319801; includes one LED.
82 Obsolete. Armstrong logo; part no. 03299A19.

E1486

82 Obsolete. Standard OEM.

Q674F F1006 F1022 F1030 F1048

System: EM.HT.-HEAT-AUTO-COOL-OFF; Fan: AUTO-ON
141 Obsolete. Includes EM HEAT LED; used with T874C1331.
142 Includes LED and field selectable inserts; used with T874C1059; used in Y594C1017, C1330.
146 Carrier part no. HH93AZ174; SUPL HEAT LED; used with T874D1074 (HH07AT172).
149 Obsolete. Includes EM HEAT LED and auxiliary power terminal Z.

F1063

146 Obsolete. Carrier part no. HH93AZ181; SUPL HEAT LED; used with T874D1074 (HH07AT172).

F1071

142 Obsolete. Square D part no. 63600-002-11; CHECK LED.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement
Q674E1049
Y594G1419a

Remarks E-W2 jumper required.

Y594G1419a E-W2 jumper required.

Q674E1049 Replacement has no LEDs.

Q674E1049 Q674E1049 Replacement has no LEDs.

Q674E1049

T8611M2025

None T874B1019/ Q674E1049a
Y594D1347a

See Trol-A-Temp.
Wiring differences (old=new): W1 =W; RC-RH jumper required; replacement has no LEDs.

Q674E1049 RC-RH jumper required. Replacement is beige color.

Q674E1049 Q674E1049

RC-RH jumper required. Replacement has no LOCKOUT LED and is beige color.
RC-RH jumper required. Replacement is beige color.

Q674E1049 Q674E1049

RC-R jumper required. Replacement is beige color.
RC-R jumper required. Replacement is beige color.

Q674F1022 Jumper E-X2.

Q674F1022

Q674F1022 Q674F1022
Q674F1022 Q674F1022

Wiring differences (old=new): C=X1, X=X2.
Replacement does not include Z terminal and only requires one transformer.
Wiring differences (old=new): C=X1, X=X2.

77

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number F1089
F1097 F1105

Fig.

No.

Description

152 Obsolete. Includes EM HEAT LED; X2-E and RC-RH jumpers.

142 Obsolete. Southwest special; W2-X2 jumper.

145 Obsolete. Lennox heat pump; EM HEAT LED; used with T874G1154.

F1113

150 Obsolete. Lennox heat pump; part no. 24F6201; V-VR jumper; EM HEAT LED; changeover in cooling; used with T874G1014, G1022.

F1121

153 Obsolete. Westinghouse heat pump; EM HEAT LED; used with T874G1048.

F1139

148 Obsolete. Tappan heat pump; EM HEAT LED; auto fan in emergency heat mode; used with T874G1147.

F1162

151 Obsolete. Crispaire heat pump; EM HEAT LED; used with T874G.

F1170

153 Obsolete. Heatwave (Southwest Mfg.) heat pump; EM HT LED; used with T874G1105.

F1188

153 Obsolete. Luxaire heat pump.

F1196

178 Obsolete. Williamson; EM HEAT and SERVICE LEDs; used with T874N1008; used in Y594N1007.

F1204

154 Obsolete. Special for Crispaire; EM HEAT and COMP FAULT LEDs; used with T874G1089; used in Y594G1153.

F1212

155 Includes AUX HEAT and EM HEAT LEDs; used with T874G1246, G1451, G1592, G1915; used in Y594G1252.

F1220 178 Used with T874N1016; used in Y594N.

F1238

155 Obsolete. Rheem part no. 41-20797-14; AUX HEAT and EM HEAT LEDs; used with T874G1097, G1212, G1220, G1238.

F1246

156 Obsolete. Westinghouse heat pump; EM HEAT and AUX HEAT LEDs; auto fan in emergency heat mode; changeover in cooling mode.

F1253

157 Obsolete. Wesco/Addison heat pump; used with T874G1261, G1279, G1287.

F1261

179 Includes two LEDs; used with T874N1024; used in Y594N.

F1279

158 Obsolete. Westinghouse heat pump; two LEDs; used with T874G.

F1295

147 Obsolete. Keeprite/Westinghouse heat pump; SERVICE, AUX HEAT and EM HEAT LEDs; used with T874G1188.

F1311

155 York heat pump; AUX HEAT and EM HEAT LEDs; used with T874G1410.

F1329

142 Obsolete. Heil Quaker part no. HQ712005HW; one LED and field selectable inserts.

F1337

166 Obsolete. WeatherKing heat pump; two LEDs and field selectable inserts; used with T874D1009; used in Y594D1222.

F1345

194 Obsolete. Addison heat pump; EM HEAT and CHECK LEDs; used with T874G; used in Y594G.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement
Q674F1022

Remarks

Q674F1022 Y594G1252a Y59461252a
Y594G1252a

Wiring differences (old=new): V=R, Y=W2, F=G, X2=X, R=O, M=Y; L-E jumper required.
Wiring differences (old=new): R=O, M=Y, F=G, Y=WC, V=VR=R; must use single transformer.

Y594G1252a Y594G1393a

Wiring differences (old=new): C=X.

Y594G1252a

Y594G1252a Q674F1220

Y594G1393a Wiring differences (old=new): A=L.

Q674F1212 or Y594G1252a

Q674F1220 Y594G1252a

Y594G1252a

Y594G1252a Y594G1419a Y594G1252a Y594G1252a
Y594G1252a

Wiring differences (old=new): Y1=O, C=X, W1=Y, X=L.
Wiring differences (old=new): L=X2, Y=Y1.
Wiring differences (old=new): L1=L.
Wiring differences (old=new): S=L; replacement does not include A or T terminals.

Q674F1022

Q674F1022 Y594G1252a

Wiring differences (old=new): R=RC-RH; replacement has no LEDs.
Wiring differences (old=new): Y1=O, C=X, W1=Y, X=L.

60-2485--8

78

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number F1360 F1378
F1394
F1402 F1410 F1428 F1436
F1444 F1451 F1477 F1485
F1501 F1519
F1535 F1543 F1550 F1568 F1584
F1592
F1600 F1634
F1667

Fig.

Q674 Trade

No.

Description

Replacement

Remarks

167 Obsolete. Rheem part no. 41-20797-17; AUX HEAT and EM HEAT LEDs; used with T874G1493.

Y594G1526a

195 Obsolete. Includes EM HEAT and AUX HEAT LEDs; used with T874G1501.

Y594G1252a Wiring differences (old=new): L1=L; changeover in cooling only.

139 Obsolete. Nepco heat pump; HEAT PUMP and AUX HEAT LEDs; System: AUX HEAT-HEAT PUMP-2 STAGE HEAT-OFF-COOL; used with T874D1595.

T874D1165/ Replacement has HEAT-OFFQ674B1018a COOL system switching and
no LEDs.

169 Obsolete. Coleman heat pump; two LEDs; used with T874G1576; used in Y594G1377.

Y594G1633a

170 Used with T874G1246, G1915; used in Y594G1393.

Y594G1393a

199 Obsolete. Used with T874G1600; used in Y594G1401. Y594G1419a Wiring differences (old=new): jumper W1-Y1.

167 Includes AUX HEAT and EM HEAT LEDs; changeover in heating mode; used with T874G1626; used in Y594G1526.

None

227 Includes AUX HEAT, EM HEAT and CHECK LEDs; used with T874G1642; used in Y594G1419.

Y594G1419a

204 Obsolete. York part no. 2TB047700524A; one LED and Q674F1012 Wiring differences (old=new):

field selectable inserts.

X2=X; X1=B.

227 TRADELINE; gray color; used with T874G1741, G1824; used in Y594G1476, G1534.

Y594G1476a

211 Trol-A-Temp by Honeywell; changeover is provided by Trol-A-Temp zone panel; used with T874G1758; used in Y594G1492.

None

See Trol-A-Temp.

223 Obsolete. Carrier two-speed compressor heat pump; T8611M2025 Includes night setback.

used with T874S1001.

(programmable)

231 Obsolete. Nordyne; used with T874G1832, G1840; used in Y594G1542, G1559.

Y594G1252a Replacement has auto changeover in cooling mode only.

229 Obsolete. Lennox heat pump; gray color; used with T874G1857; used in Y594G1583.

Y594G1161a Wiring differences (old=new): E=X2, C=B, L=F.

204 Obsolete. TRADELINE

Q674F1022 Wiring differences (old=new): X2=X, X1=B.

243 Obsolete. Amana part no. 10573901; includes two LEDs; used with T874G1899; used in Y594G1591.

Y594G1633

155 Obsolete. Gray color; includes two LEDs; used with only T874G1931.

Y594G1476 Y1-W1 jumper required.

169 TRADELINE; includes two LEDs; used with T874G1972; used in Y594G1633. Direct replacement for Coleman/Evcon Y594G1377 (T874G1576/ Q674D1402); Coleman part no. 3600-373.

Y594G1633a

238 Heat Controller; Fan: AUTO-ON; System: AUX HEATHEAT PUMP- 2 STAGE HEAT-OFF-COOL; includes two LEDs; used with T874C1844; used in Y594C1413.

Y594R1425

E-W2 jumper required; system switch: EM.HT.-HEAT-OFFCOOL.

169 Obsolete. Amana part no. 10573903; includes two LEDs; used with T874G1980; used in Y594G1641.

Y594G1633 Wiring differences (old=new); W3=W2.

139 Standard OEM; System: AUX HEAT-HEAT PUMP2 STG HEAT-OFF-COOL; includes two LEDs; used with T874D2155.

Y594G1716

155 WaterFurnace logo; part no. TA21H03; System: OFFAUTO-HEAT-EM HT; includes two LEDs; used with T874G2046.

Y594G1716

a Both the thermostat and subbase must be replaced.

79

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number F1675
Q674G G1005 G1013

Fig.

No.

Description

248 Obsolete. WaterFurnace logo; part no. TA21H03; includes four LEDs.

System: OFF-AUTO; Fan: None

184 Obsolete. Used in Y594F1063.

186 Obsolete. Climate Control; used with T874D1298.

G1021
G1047 G1054
G1062

91 Obsolete. Includes O and B terminals; used with T874A-F,Q or T874D1082; used in Y594D1032.
92 Obsolete. Used with T874C1018, C1125.
188 Obsolete. Singer part no. 0200-5963; used with T874D1298.
232 Obsolete. Singer; used with T874D1298.

G1070

91 TRADELINE

G1088

92 Obsolete. LSI-Mammoth part no. 71120201; used with T874C.

G1096

90 Obsolete. Climate Control part no. 02005958; used with T874D1439, D1447.

G1104

94 Obsolete. McQuay part no. 0200-5963; two LEDs; used with T874D1116.

G1120

202, Obsolete. McQuay part no. 60684701; two SERVICE 226 LEDs; no fan switching; used with T874D1694, G1926.

G1138

91 Obsolete. Trane part no. BAS-0433; used with T874A-F.

G1153

184 Obsolete. Carrier part no. HH93AZ212; used in Y594D1396.

G1161 184 Gray color.

G1179

202 Obsolete. McQuay logo; part no. 073319601; includes two LEDs.

Q674J

System: EM.HT.-AUTO-OFF; Fan: AUTO-ON

J1001

180 Obsolete. Singer heat pump part no. 02005964; EM HEAT LED; changeover heat mode.

J1019

159 Obsolete. Westinghouse heat pump; EM HT LED; System: EM.HT.-ON-OFF; used with T874G1048.

J1027

160 Obsolete. York part no. 025-22291; EM HEAT LED; auto fan in emergency heat mode; changeover in cool mode; used with T874G1170, G1196, G1428, G1345, G1444; used in Y594G1013, G1138, G1229.

J1035

161 Carrier heat pump; part no. HH93AZ173; System: SUPL.HT.-ON-OFF; SUPL HEAT LED; used with T874G1055 (HH07AT171).

J1043

162 TRADELINE heat pump model; designed for use on Trane heat pumps; AUX HT and EM HT LEDs; auto fan in emergency heat; changeover in cooling mode; used with T874G1204 and C815A1008; used in Y594G1161.

J1050

183 Obsolete. Westinghouse heat pump; EM HEAT and AUX HEAT LEDs; used with T874G1071.

J1068

144 Obsolete. Carrier heat pump; part no. HH93AZ183; used with T874J1002 (HH07AT175) or T874J1028 (HH07AT165).

J1076

180 Obsolete. McQuay part no. 02005964; two LEDs; used with T874A,D.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement See OEM for replacement.
Q674G1070 See OEM for replacement. Q674G1070
T8611 See OEM for replacement. See OEM for replacement. Q674G1070 See OEM for replacement. See OEM for replacement. See OEM for replacement. See OEM for replacement. Q674G1070 Q674G1070
Q674G1070 Q674G1161
See OEM for replacement. Y594G1252a
Y594G1567a
Y594G1674a
Q674J1043 or Y594G1161a
Y594G1674a
Y594J1019
Q674F1022

Remarks
Replacement is beige color. Replacement has no LEDs. Wiring differences (old=new): W=W2. Designed for use on Trane heat pumps. Replacement has no LEDs.

60-2485--8

80

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number J1084 J1118
J1126 J1142 J1159 J1167
J1175
J1191 J1209
J1217 J1225
J1241 J1258 J1266 J1274 J1282 Q674K K1000 K1018

Fig.

Q674 Trade

No.

Description

Replacement

Remarks

171 Obsolete. BDP heat pump; part no. 34427DP126, P272-1879; EM HEAT LED; used with T874J1010.

Y594J1019 Wiring differences (old=new): W1=W2, F=L.

196 Obsolete. Carrier heat pump; part no. HH93AZ188; SUPL HEAT LED; System: SUPL.HT.-ON-OFF; used with T874G1055 (HH07AT171).

Y594G1674

Wiring differences (old=new): C=X;Y1=W1; jumper required; no auto fan in emergency heat.

160 Obsolete. Luxaire no. 026-00068-000; EM HEAT LED; Y594G1567a used with T874G1568; used in Y594G1351.

174 Obsolete. American Standard part no. WY28X0250; AUX HEAT and EM HEAT LEDs; used with T874G1675; used in Y594G1443.

Y594G1161a

206 Obsolete. Carrier heat pump; part no. HH93AZ196; used with T874J1002 (HH07AT175) or T874J1028 (HH07AT165).

Y594J1019

175 Obsolete. Carrier heat pump; MANUAL, AUTO, HEAT PUMP and DEFROST LEDs; System: SUPL HEATON-OFF; used with T874G1717; used in Y507J1201.

Y594G1252a

Wiring differences (old=new): C=X, D=L; replacement has AUX HEAT and EM HEAT LEDs.

216 Obsolete. Snyder General part nos. 1505756, 1506756; CHECK, AUX HEAT and SYSTEM LEDs; used with T874G1774, G1782; used in Y594G1500, G1518.

Y594G1252a Wiring differences (old=new): E=W2, W1=W3, X=E, C=X.

161 Obsolete. Carrier heat pump; gray color; used with T874G1790.

Y594G1252a Wiring differences (old=new): C=X; replacement has °F scaleplate.

160 TRADELINE; designed to replace Y594G1013 (York part no. 2TH11702424), Y594G1229 (York part no. 6TH11702424) and York part no. 2TH11704124; used with T874G1865; used in Y594G1567.

Y594G1567a

171 Obsolete. Nordyne part no. 9132250; used with T874J1036, J1044.

Y594J1019 Wiring differences (old=new): F=L.

160 Obsolete. TRADELINE; gray color; designed to replace Y594G1013 (York part no. 2TH11702424), Y594G1229 (York part no. 6TH11702424) and York part no. 2TH11704124; used with T874G1873; used in Y594G1575.

Y594G1567a Replacement is beige.

144 Obsolete. Carrier Canada part no. HH93AZ183-W; gray color; System: SUPL HT-ON-OFF; includes one LED.

See OEM for replacement.

161 Obsolete. Carrier Canada part no. HH93AZ173-W; gray color; System: SUPL HT-ON-OFF; includes one LED.

Y594G1674a Replacement is beige color.

160 York Canada; gray color; includes EM HT LED; used in Y594G1567a Y594G1625.

161 TRADELINE; System: SUPL HT-ON-OFF; includes

Y594G1674

one LED; used with T874G2004; used in Y594G1674.

244 Obsolete. TRADELINE; System: SUPL HT-ON-OFF; includes SUPL HT LED; used with T874J1069; used in Y594J1019.

(Recontrol) T8511G1021

System: OFF-HEAT-AUTO-COOL; Fan: None

93 Obsolete. Carrier part no. HH93AZ172; RC-RH jumper. Q674E1049 Fan switch is not operational.

95 Obsolete. Oneida Heater part no. 3040284-02; System: OFF-WOOD-WOOD/OIL-OIL; used with T874F1106.

Q674K1026

a Both the thermostat and subbase must be replaced.

81

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number K1026 K1034 K1042
Q674L L1017
L1025
L1033 L1041
L1066 L1074
L1082 L1090
L1108 L1116 L1132
L1140 L1157
L1165
L1173 L1181

Fig.

No.

Description

95 System: OFF-WOOD-WOOD/ OIL-OIL; used with T874F1155.

93 Obsolete. Snyder General part no. 4ELN-7920.

93 Obsolete. Carrier part no. HH93AZ172-W; gray color; includes removable jumper between RC and RH terminals.

System: EM.HT.-HEAT-OFF-COOL; Fan: ON-AUTO

101 Obsolete. York heat pump; EM HEAT LED; cooling mode changeover; compressor lockout; auto fan in EM.HT; used with T874R1046.

102 Obsolete. Lennox heat pump; part no. 24F6101; EM. HEAT LED; V-VR jumper; used with T874R1020, J1038.

115 Obsolete. Rheem heat pump; EM HEAT LED; used with T874R1152.

103 Obsolete. Carrier heat pump; part no. HH93AZ175; SUPL HEAT LED; used with T874G1055 (HH07AT171), G1071 (HH93AZ175), G1113.

122 Obsolete. Fedders heat pump; used with T874R1269; used in Y594R1037.

124 Obsolete. Carrier heat pump; part no. HH93AZ186; SUPL HT LED; used with T874J1002 (HH07AT175) or T874J1028 (HH07AT165).

104 Obsolete. Crispaire heat pump; W2-H jumper; EM HEAT LED; used with T874R1061, R1111.

105 Obsolete. Fedders heat pump; EM HEAT LED; changeover in heat mode; used with T874C1398, C1406, C1414.

106 Obsolete. Westinghouse; EM HEAT LED.

107 Obsolete. Carrier part no. HH93AZ171; SUPL HEAT LED; used with T874D1264 (HH07AT173).

108 Heil Quaker part no. HQ711598; used with T874R1137, R1673, R1731, R1749, R1814; used in Y594R1110, R1466, R1524, R1532, R1607.

109 Obsolete. Includes EM HEAT and AUX HEAT LEDs; used with T874R1053; used in Y594G1136.

115 Obsolete. Rheem part no. 41-20796-14; EM HEAT and AUX HEAT LEDs; used with T874R.

121 Obsolete. Used with T874C.

123 Obsolete. Used with T874R.

110 Obsolete. Lennox no. 24F5901; factory installed V-VR jumper; EM HEAT and SERVICE LEDs; stage 2 heat is isolated; used with T874C1448, R1178 and C815A1013.

112 Obsolete. Westinghouse; AUX HEAT and EM HEAT LEDs.

113 Used with T874R1129; used in Y594R.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement
Q674K1026

Remarks

Q674E1049 Fan switch is not operational. Q674E1049 Fan switch is not operational.

Y594R1243a Wiring differences (old=new): W=W2, X=L, B=X.

Y594R1243a Y594R1243a

Wiring differences (old=new): M=Y, F=G, V-VR=VR, Y=W2, R=O.

Y594G1419 Wiring differences (old=new): C=X, jumper Y1=W1.

Y594R1615a Y594J1001

Wiring differences (old=new): K=E, C=X, W1=B, Z=L.

Y594R1243a Y594R1425a

Replacement has auto fan in emergency heat mode.
Wiring differences (old=new): K=E, C=X.

Y594R1243a
See OEM for replacement.
Y594R1292a

Y594R1763a Q674L1207a

Designed for use on Trane heat pumps.

Y594C1322a Y594R1243a Y594R1763a

Wiring differences (old=new): V-VR=R, M=Y, F=G, X=B, Y=W, A=T, R=O, E=X2.

Y594R1243a

Y594R1243a Wiring differences (old=new): X1=X.

60-2485--8

82

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

L1199

114 Obsolete. Lennox no. 24F6001; used with T874D1207 T8611M2025 Wiring differences (old=new):

and C815A1013.

(programmable) V-VR=R, Y=W3, X=C, R=O,

M=Y, M2=Y2-W2, F=G;

jumper Y2-W2; no outdoor

reset needed; use only one

system transformer.

L1207

115 Used with T874R1152, R1590, R1640, R1921; used in Q674L1207 or

Y594R1243, R1706.

Y594R1243a

L1215

116 Obsolete. Crispaire heat pump; used with T874R1111; used in Y594R1128.

Y594R1243a

Replacement has auto fan in emergency heat mode. Wiring differences (old=new): A=L; set anticipator to 1.2.

L1223

117 Obsolete. Westinghouse special.

See OEM for replacement.

L1231

182 Obsolete. Used with T874R1186 and W89.

None

L1249

115 Obsolete. Used with T874R1194 and W89.

Y594R1243a

L1256

118 Obsolete. Westinghouse special; used with T874W1007.

T8611M2025 Includes night setback. (programmable)

L1264

119 Obsolete. Intertherm heat pump; EM HEAT and SERV Y594R1672a or Wiring differences (old=new):

LEDs; used with T874R1202, R1608, R1699; used in Y594R1763a W2=W, X=B, Z=no

Y594R1185, R1409, R1482.

connection, K=X, W1=H.

L1272

120 Obsolete. York part no. 025-22290; used with T874R1046, R1145; used in Y594R1011, R1102; used with T874R1228, R1251 R1327 and C815A1039; used in Y594R1144, R1151, R1193.

Y594R1672a

L1280

233 Obsolete. Lennox no. 52C7601; used with T874W1023 Y594W1014a and W89.

L1298

182 Obsolete. Singer heat pump; used with T874R1160 and W89.

See OEM for replacement.

L1314

115 Obsolete. Westinghouse heat pump; used with T874R1244 and W89.

Q674L1207 or Y594R1243a

L1322

127 Obsolete. EM HEAT and AUX HEAT LEDs; used with T874C1455.

Y594R1243a

L1330

120 Obsolete. York heat pump; used with T874R.

Y594R1664a Wiring differences (old=new): L=X, X=B.

L1348

115 Obsolete. Williamson heat pump; used with T874R1236.

Q674L1207

L1355

111, Obsolete. Lennox part no. 31F3201; V-VR jumper; 190 used with T874C1448, R1178 and C815A1015.

Y594R1763a Wiring differences (old=new): V-VR=R, M=Y, F=G, X=B, Y=W, A=T, R=O, E=X2.

L1363

129 Obsolete. York heat pump; EM HEAT LED; used with T874G1402.

Y594R1425a Wiring differences (old=new): W=W2, X=E, B=X; jumper YW1.

L1371

124 Obsolete. BDP heat pump; part no. 34427DP125, P272-1878; EM HEAT LED; used with T874J1010.

Y594J1001 Wiring differences (old=new): W1=W2, F=L.

L1389

114 Obsolete. Lennox part no. 41F6501; V-VR jumper; used with T874D1207.

T8611M2025 Wiring differences (old=new): (programmable) V-VR=R, Y=W3, X=C, R=O,
M=Y, M2=Y2-W2, F=G; jumper Y2-W2; no outdoor reset needed; use only one system transformer.

L1397

103 Obsolete. Carrier part no. HH93AZ185A; SUPL HEAT Y594G1393a Wiring differences (old=new):

LED.

C=X.

a Both the thermostat and subbase must be replaced.

83

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

L1405

106 Obsolete. BDP heat pump; part no. HH641501; used with T874R1335; used in Y594R1201.

Y594R1243a

L1413

133 Obsolete. Fedders heat pump; used with T874R1343; used in Y594R1219.

Y594R1425a Wiring differences (old=new): K=E, C=X, Z=L; remove W1-Y jumper.

L1421

125 Obsolete. Coleman heat pump; used with T874R1368; Y594R1797a used in Y594R1235.

L1439

131 Obsolete. Carrier part no. HH93AZ187; SUPL HEAT LED; System: SUPL HT-HEAT- COOL; used with T874R1384 (HH07AQ170).

Q674L1207 or Wiring differences (old=new): Y594G1393a C=X.

L1447

128 Obsolete. Williamson heat pump; three LEDs; used with T874R1392; used in Y594R1250.

Y594R1425a Wiring differences (old=new): A=L.

L1454

131 Obsolete. Carrier part no. HH93AZ197; SUPL HEAT LED; used with T874R1384 (HH07AQ170).

Y594R1393a Wiring differences (old=new): C=X.

L1462

113 Obsolete. LSI heat pump; part no. 104710002; used with T874R1400.

Y594R1243a Wiring differences (old=new): X1=X.

L1496

136 Obsolete. Trane heat pump; used with T874R1426; used in Y594R1284.

Y594R1763a

L1504

134 Rheem part no. 41-20796-24; used with T874R1442, R1434, R1459; used in Y594R1631, R1649, R1854.

Y594R1300a

L1512

108 Includes two LEDs; used with T874R1467; used in Y594R1292.

Y594R1292a

L1520

123 Includes EM HEAT and AUX HEAT LEDs; used with T874R1475; used in Y594R1300.

Y594R1300a

L1538

130 Obsolete. Snyder General heat pump; used with T874R1483, R1517, R1566 and C815A1005; used in Y594R1318, R1342, R1375.

Y594R1763a Wiring differences (old=new): C=B, W1=W, E=X2, X=F.

132 Obsolete. Used with T874R1574, R1582; used in Y594R1383, R1391.

Y594R1243a Wiring differences (old=new): C=X, X=L, W=W2.

L1546

140 Obsolete. Rheem part no. 41-20797-21; three LEDs; used with T874W1031 and C815A1005; used in Y594W1022.

T8611M2025 Includes night setback. (programmable)

L1553

137 Obsolete. Includes three LEDs; used with T874R1491; Y594R1615a used in Y594R1326.

L1561

121 Obsolete. Used with T874C1638; used in Y594C1322. Y594C1322a Use Y594C1322 when T874C is used.

123 Obsolete. Used with T874R.

Y594R1243a Use Y594R1243 when T874R is used.

L1579

135 Obsolete. Carrier heat pump; part no. HH93AZ198; SUPL HEAT LED; used with T874R1384 (HH07AQ170).

Y594R1243a Wiring differences (old=new): C=X.

L1587

168 Used with T874R1616; used in Y594R1425.

Y594R1425a

L1595

200, Obsolete. Miller heat pump; used with T874R1624 or Y594R1243a or

201 T874R1202; used in Y594R1433.

Y594R1763a

L1603

134 Obsolete. Used with T874R1632.

Y594R1243a

L1611

136 Obsolete. American Standard heat pump; part no. WY28X235; used with T874R1657; used in Y594R1441.

Y594R1763a

L1637

207 Obsolete. Carrier heat pump; part no. HH93AZ195; used with T874J1002 (HH07AT175) or T874J1010 (HH07AT165).

Y594J1001a

a Both the thermostat and subbase must be replaced.

60-2485--8

84

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Fig. Number No.

Description

Q674 Trade Replacement

Remarks

L1678

209 Trol-A-Temp by Honeywell; gray color; used with T874R1707; used in Y594R1490.

None

See Trol-A-Temp.

L1686

209 Trol-A-Temp by Honeywell; used with T874R1715; used in Y594R1508.

None

See Trol-A-Temp.

L1702

132 Obsolete. Snyder General heat pump; part no. 654958B07; used with T874R1723 and C815A1005; used in Y594R1516.

Y594R1672a Wiring differences (old=new): C=B, W1=W, X=X2.

L1710

230 Used with T874R1822; used in Y594R1615.

Y594R1615a

L1728

228 Obsolete. Lennox; gray color; used with T874R1855; used in Y594R1714.

Y594R1763a Wiring differences (old=new): Y1=Y, L=F, W1=W, E=X2, C=B.

L1736

120 Designed to replace Y594R1011 (York part no. 2TH11702224); used with T874R1871; used in Y594R1664.

Y594R1664a

Designed to replace Y594R1151 (York part no. 2TH11702324), Y594R1193 (York part no. 6TH11702224) and York part no. 2TH11704024; used with T874R1889 and C815A1054; used in Y594R1672.

Y594R1672a

L1751

230 Gray color; used with T874R1897, used in Y594R1680.

Y594R1680a

L1769

124 Obsolete. Nordyne part no. 9132260; used with T874J. See OEM for replacement.

L1777

120 Obsolete. Gray color; designed to replace Y594R1151 (York part no. 2TH11702324), Y594R1193 (York part no. 6TH11702224) and York part no. 2TH11704024; used with T874R1905 and C815A1059; used in Y594R1698.

Y594R1672a Replacement is beige.

Designed to replace Y594R1011 (York part no. 2TH11702224); used with T874R1913; used in Y594R1706.

Y594R1664a Replacement is beige.

L1785

103 Obsolete. Carrier part no. HH93AZ175-W; Canada; gray color; System: Supl Ht-Heat-Off-Cool; includes one LED.

Y594G1476a Wiring differences (old=new): C=X; Y1-W1 jumper required.

L1793

124 Obsolete. Carrier Canada part no. HH93AZ186-W; gray color; Fan: Auto-On; System: Supl Ht-Heat-OffCool; includes one LED.

Y594J1019a

L1801

197 American Standard (Trane) part no. THT1225; includes Y594R1763a two LEDs; used with T874R1939; used in Y594R1748.

L1819

168 Obsolete. Inter-City Products part no. HQ1149407HW; includes three LEDs; used with T874R1947; used in Y594R1755.

Y594R1425a

L1827

197 TRADELINE; includes two LEDs; used with T874R1954; used in Y594R1763; direct replacement for Trane/American Standard Y594R1748 (T874R1939/Q674L1801) Trane part no. ASYSTAT 631A, Y594R1136 (T874R1053/Q674L1140).

Y594R1763a

L1835

140 Obsolete. Inter-City Products; includes three LEDs; used in Y594W1030.

T8611M2025a Includes night setback. (programmable)

L1843

115 Obsolete. Consolidated Industries part no. 9036100; gray color; includes two LEDs; used with T874R1962; used in Y594R1771.

Y594R1680a Includes CHECK LED.

L1850

120 York Canada; gray color; includes one LED; used with Y594R1672a T874R1970; used in Y594R1789.

a Both the thermostat and subbase must be replaced.

85

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 9. Q674 Subbase Cross Reference.

Model Number L1868
L1876 L1884 L1892
L1900
L1918 L1934 Q674N N1015 N1023 Q674P P1005

Fig.

No.

Description

125 TRADELINE; includes two LEDs; used with T874R1988; used in Y594R1797; direct replacement for Evcon/Coleman Y594R1235 (T874R1368/ Q674L1421) Coleman part no. 3600-368.

245 Obsolete. Amana part no. 10573902; includes two LEDs; used with T874R2002; used in Y594R1805.

245 Obsolete. Amana part no. 10573904; includes two LEDs; used with T874R2010; used in Y594R1813.

103 Obsolete. TRADELINE; System: SUPL HT-HEATOFF-COOL; includes one LED; used with T874G2004; used in Y594G1666; direct replacement for Carrier Y507J1011 (T874G1055/Q674L1041) Carrier part no. HH07AT171/HH93AZ175.

241 Obsolete. TRADELINE; System: SUPL HT-HEATOFF-COOL; includes SUPL HT LED; used with T874J1069; used in Y594J1001; direct replacement for Carrier T874J1028/Q674J1068 (Carrier part no. HH07AT165/HH93AZ183), Carrier T874J1002/ Q674J1068 (Carrier part no. HH07AT175/ HH93AZ183).

125 Obsolete. York logo; part no. 2TH11703424A; includes two LEDs; used with T874R2028 in Y594R1821.

123 Obsolete. Addison logo; part no. 843-277; includes three LEDs; used with T874W1106 in Y594W1055.

System: OFF-HEAT-COOL-EVAP; Fan: AUTO-ON

60 Obsolete. Goettl heat pump; changeover in heat mode; evaporative cooler circuit; used with T874C1182.

61 Obsolete. Sigler heat pump; evaporative cooler circuit; used with T874C1349.

System: SUPL HT-HEAT-COOL; Fan: AUTO-ON

126 Obsolete. Carrier heat pump; part no. HH93AZ169; used with T874G1071 (HH07AT171).

Q674Q Q1004

System: HEAT-OFF-COOL; Fan: LOW-MED-HI-ON 59 Obsolete. McQuay special; used with T874A1267.

Q1012 Q674R
R1003
Q674S S1000
Q674W W1006

64 Used with T874A1291.
System: OFF-COOL; Fan: LO-HI-CONT
69 Obsolete. Carrier part no. HH93AZ190; international symbols on fan and switches; used with T874V1008 (HH07AT177).
System: HEAT-COOL; Fan: None
70 Obsolete. Fiberglas; Canada; SERVICE LED; used with T874C1653; used in Y594C1348.
System: OFF-ON; Fan: LO-MED-HI
240 Obsolete. Snyder General part no. 044271801.

a Both the thermostat and subbase must be replaced.

Q674 Trade Replacement
Y594R1797a

Remarks

Y594R1797 Y594R1797 Y594G1674

Wiring differences (old=new): C/X=X.
Wiring differences (old=new): C/X=X, W3=W2.
Replacement has auto changeover.

Y594J1019 Replacement has auto changeover.

Y594R1797a T8611M2025

See OEM for replacement.
See OEM for replacement.

Y594G1419a

Wiring differences (old=new): C=X; jumper Y1-W1; replacement has OFF-EM HTHEAT-AUTO-COOL system switching.

See OEM for replacement.
None

See OEM for replacement.

See OEM for replacement.
See OEM for replacement.

60-2485--8

86

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 10. Y594 Cross Reference.

Model Number Y594A A1001
A1019
A1035
A1043
A1050
A1068
A1126 A1159

Fig.

No.

Description

46 Obsolete. Amana part no. D68535-11; contains T874A1077, Q674B1075.
82 Obsolete. Amana part no. P68535-12; contains T874A1077, Q674E1056.
44 Obsolete. Trane part no. 268-0187-1; contains T874A1085, Q674B1018.
46 Obsolete. Trane part no. 268-0201-5; contains T874A1085, Q674B1075.
55, 66 Obsolete. Trane part no. 268-0201-3; contains T874A1085, Q674D1008.
82 Obsolete. Sears part no. 42-9144; contains T874A1119, Q674E1007.
64 Contains T874A1291, Q674Q1012.
91 Obsolete. Contains T874A1440, Q674G1005.

A1167 A1175 A1191 Y594B B1026 B1034 B1042 Y594C C1009 C1017 C1058

184 California Economizer; Premier White® color; contains T874A1580 and Q674G1161.
55 Obsolete. York logo; part no. 2TH04703224; contains T874A1622, Q674D1180.
46 Obsolete. Amana logo: part no. P6853524R; contains T874A1002, Q674B1075.
44 Trane part no. BAYSTAT012; contains T874B1035, Q674B1018.
46 Obsolete. Trane part no. 163-552-1; contains T874B1035, Q674B1075.
88 Obsolete. Goodman part no. CHTS36-60; contains T874B1100, Q674E1338.
82 Obsolete. Amana part no. D68535-9; contains T874C1059, Q674E1056.
142 Obsolete. Amana part no. D68535-10; contains T874C1059, Q674F1022.
46 Obsolete. Contains T874C1000, Q674B1075.

C1082 C1256 C1280 C1314

82 Obsolete. Trane part no. 166-162-1; contains T874C1083, Q674E1007.
45 Obsolete. Amana part no. D68535-16; contains T874C1059, Q674B1059.
45 Obsolete. Williamson; contains T874C1570, Q674B1000.
56 Obsolete. LSI; contains T874C1471, Q674B1257.

C1322

121 Obsolete. Contains T874C1638, Q674L1561.

C1330

142 Obsolete. Amana part no. D68535-21; contains T874C1059, Q674F1022.

a Both the thermostat and subbase must be replaced.

Trade Model Replacementa
T874A1036/ Q674B1075 T874A1036/ Q674E1049 T874A1036/ Q674B1018 T874A1036/ Q674B1075 T874A1036/ Q674D1040 T874A1036/ Q674E1049
None T874A1150/ Q674G1070 T874A1036/ Q674G1070 T874A1010/ Q674D1040 T874A1036/ Q674B1075
T874B1019/ Q674B1018 T874B1019/ Q674B1075 T874B1019/ Q674E1049
T874C1018/ Q674E1049 T874C1018/ Q674F1022 T874C1018/ Q674B1075 T874C1018/ Q674E1049 T874C1018/ Q674B1034 T874C1018/ Q674B1034 T874C1018/ Q674B1018 Y594C1322 T874C1018/ Q674F1022

Remarks
Replacement is beige color.
No LEDs on replacement. Jumper RC-RH. Jumper RC-RH. Jumper RC-RH; no RESET LED on replacement.

87

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Model Number
C1348

Table 10. Y594 Cross Reference.

Fig.

No.

Description

70 Obsolete. Fiberglas; contains T874C1653, Q674S1000.

Trade Model Replacementa
T874C1000/ Q674B1075

C1355 C1363

45 Obsolete. Nordyne "Miller" part no. 9122250; contains T874C1695, Q674B1000.
45 Obsolete. Nordyne "Intertherm" part no. 911100001; contains T874C1703, Q674B1000.

T874C1018/ Q674B1034
T874C1018/ Q674B1075

C1371 C1389 C1413 C1421 C1439 Y594D D1016 D1024 D1032 D1040 D1057 D1149 D1156 D1180 D1222

184 Obsolete. California Economizer; contains T874C1802 and Q674G1005.
237 Obsolete. TRADELINE; Premier White® color; contains T874C1810 and Q674B1547.
238 Heat Controller "Energy Night" logo; contains T874C1844 and Q674F1592.
249 Obsolete. TRADELINE; contains T874C1877 and Q674B1554.
T874C1869 and Q674C1579.

T874C1018/ Q674G1070 Y594C1389
Y594R1425
Y594D1347
None

44 Obsolete. Trane part no. 268-0201-2; contains T874D1082, Q674B1018.
72 Trane part no. BAYSTAT010; contains T874D1082, Q674C1009.
91 Obsolete. Trane part no. BAYSTAT011; contains T874D1082, Q674G1021.
46 Amana part no. P68535-19R; contains T874D1082, Q674B1075.
55, 66 Obsolete. Trane part no. BAYSTAT007; contains T874D1082, Q674D1008.
46 Obsolete. Amana part no. P68535-20C; contains T874D1322, Q674B1075.
48 Obsolete. Trane part no. BAYSTAT013; contains T874D1082, Q674B1133.
82 York part no. 025-23321-000; contains T874D1504, Q674E1007.
166 Obsolete. WeatherKing; contains T874D1009, Q674F1337.

T874D1165/ Q674B1018
T874D1165/ Q674C1058
T874D1165/ Q674G1070
T874D1165/ Q674B1075
T874D1165/ Q674D1040
T874D1165/ Q674B1075
T874D1165/ Q674B1018
T874D1165/ Q674E1049
T874D1165/ Q674F1022

D1248

82 Obsolete. Reznor part no. 93437; contains T874D1629, Q674E1007.

D1297

82 Obsolete. ArcoAire part no. 1506753; contains T874D1769, Q674E1346.

D1305

82 Obsolete. Comfortmaker part no. 1505753; contains T874D1785, Q674E1346.

D1321

45 Obsolete. Goodman part no. CHT 90-120; contains T874D1843, Q674B1000.

D1339

82 Obsolete. Nordyne part no. 5471180; contains T874D1009, Q674E1007.

a Both the thermostat and subbase must be replaced.

T874D1165/ Q674E1049
T874D1165/ Q674E1049
T874D1165/ Q674E1049
T874D1165/ Q674B1034
T874D1165/ Q674E1049

Remarks Wiring differences (old=new): Y=Y1; jumper RC-RH and Y1W1; replacement has no SERVICE LED; replacement has fan switching and HEATOFF-COOL system switching.
Wiring differences (old=new): Y=Y1; jumper RC-RH; Y1-W; replacement has no SERVICE LED.
E-W2 jumper required; system: EM.HT.-Heat-Off-Cool. Replacement has auto changeover; jumper RH-RC.
Replacement has no FILTER LED.
Wiring differences (old=new): R=RH; jumper RC-RH; replacement has no EM.HT. or AUX. HT. LEDs.

60-2485--8

88

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Model Number D1347 D1354 D1370 D1388 D1396 D1404 D1412
D1420
D1438 D1446

Table 10. Y594 Cross Reference.

Fig.

No.

Description

82 TRADELINE® contains T874D1942, Q674E1403.

82 SUPER TRADELINE® contains T874D2031 (no cover), Q674E1049, and TG504A with two keys.

45 Obsolete. Carrier part no. 50QE90022101; contains T874D2049 and Q674B1539.

72 Obsolete. Carrier part no. 50QE90023101; contains T874D2049 and Q674C1520.

184 Obsolete. Carrier part no. 50QE90025101; contains T874D2049 and Q674G1153.

55, 66 Obsolete. Carrier part no. 50QE90024101; contains T874D2049 and Q674D1164.

82 Obsolete. Carrier "Weathermaker" part no. HH07AT209; taupe color; contains T874D2064 and Q674E1445.

82 Obsolete. Carrier "Zone Perfect" part no. HH07AT208; taupe color; contains T874D2072 and Q674E1445.

55, 66 Obsolete. Contains T874D2098 and Q674D1008.

55, 66 Obsolete. Contains T874D2106 and Q674D1008.

Trade Model Replacementa
Y594D1347 Y594D1354
T874D1165/ Q674B1034 T874D1165/ Q674C1058 T874D1165/ Q674G1070 T874D1165/ Q674D1040 T874D1165/ Q674E1049
T874D1165/ Q674E1049
T874D1165/ Q674D1040 T874D1165/ Q674D1040

D1453

208 Obsolete. Amana logo; part no. P1217501F; contains T874D2163 and Q674D1172.

D1461

45 Obsolete. Amana logo; part no. P1217701F; contains T874D2171 and Q674B1562.

Y594E

E1015

72 Obsolete. Trane part no. BAYSTAT015; contains T874E1040, Q674C1009.

Y594F

F1022

44 Obsolete. Contains T874F1031 and 40003440-001 wallplate with installed diode.

F1048

72 Obsolete. Reznor part no. 93436; contains T874F1130, Q674C1009.

F1063

91 Obsolete. Reznor part no. 93435; contains T874F1130, Q674G1005.

Y594G

G1013

160 Obsolete. York part no. 2TH11702424; contains T874G1170, Q674J1027.

G1138

160 Obsolete. York part no. 025-22286; contains T874G1196, Q674J1027.

G1153

154 Obsolete. Crispaire part no. HP10-51; contains T874G1089, Q674F1204.

G1161

162 Contains T874G1204, Q674J1043.

G1195

155 Obsolete. Heil Quaker part no. HQ521387HW; contains T874G1246, Q674F1212.

G1229

160 Obsolete. York part no. 6TH11702424; contains T874G1428, Q674J1027.

G1245

155 Obsolete. BDP part no. HH641502; contains T874G1451, Q674F1212.

G1252

155 TRADELINE; contains T874G1246, Q674F1212.

a Both the thermostat and subbase must be replaced.

T874D1165/ Q674D1040 T874D1942/ Q674B1034
T874B1019/ Q674C1058
T874F1015
T874F1015/ Q674C1058 T874F1015/ Q674G1070
Y594G1567
Y594G1567
Y594G1252
Y594G1161 Y594G1252
Y594G1567
Y594G1252
Y594G1252

Remarks
Replacement has °F scaleplate. Replacement has °F scaleplate. Replacement has °F scaleplate. Replacement has °F scaleplate. Replacement is beige color. Replacement is beige color. Replacement has 2 setpoint levers. Replacement has °F scaleplate and 2 setpoint levers.
Wiring differences (old=new): A=L.

89

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Model Number G1294
G1328
G1344
G1351
G1369 G1377
G1385
G1393 G1419 G1427
G1443
G1476
G1492

Table 10. Y594 Cross Reference.

Fig.

Trade Model

No.

Description

Replacementa

79 Obsolete. LSI; contains T874G1378, Q674C1124.

See OEM for replacement.

194 Obsolete. Addison part no. 8403-197; contains T874G1543, Q674F1345.

Y594G1252

194 Obsolete. Heat Controller part no. 7601-110B; contains T874G1469, Q674F1345.

Y594G1252

160 Obsolete. Luxaire part no. 026-00068-000; contains T874G1568, Q674J1126.

Y594G1567

155 Obsolete. Contains T874G1246, Q674F1212.

Y594G1252

169 Obsolete. Coleman part no. 3600-373; contains T874G1576, Q674F1402.

Y594G1633

155 Obsolete. ArcoAire; contains T874G1592, Q674F1212.

Y594G1252

170 Obsolete. Contains T874R1393, Q674L1454.

Y594G1393

227 TRADELINE; contains T874G1642, Q674F1444.

Y594G1419

177 Obsolete. Mammoth part no. 73034101; contains T874G1659, Q674C1330.

See OEM for replacement.

174 Obsolete. American Standard (Trane) part no. ASYSTAT650; contains T874G1675, Q674J1142.

Y594G1161

227 TRADELINE; same as Y594G1419 except Premier White® color; contains T874G1741, Q674F1477.

Y594G1476

211 Trol-A-Temp; contains T874G1758, Q674F1485.

None

G1500

216 Obsolete. Comfortmaker part no. 1505756; contains T874G1774, Q674J1175.

G1518

216 Obsolete. ArcoAire part no. 1506756; contains T874G1782, Q674J1175.

G1526

167 TRADELINE; contains T874G1626, Q674F1436.

G1534

227 TRADELINE; °C; white; Australia; contains T874G1824, Q674F1477.

G1542

231 Obsolete. Intertherm part no. 9129290; contains T874G1832, Q674F1519.

G1559

231 Obsolete. Miller part no. 9129310; contains T874G1840, Q674F1519.

G1567

160 TRADELINE; contains T874G1865, Q674J1209.

G1575

160 Obsolete. TRADELINE; same as Y594G1567 except Premier White® color; contains T874G1873, Q674J1225; direct replacement for York 2TH11702424 (Y594G1013 contains T874G1170/ Q674J1027) and 6TH11702424 (Y594G1229 contains T874G1428/Q674J1027).

G1583

229 Obsolete. Lennox Canada part no. 97E78; contains T874G1857, Q674F1535.

G1591

243 Obsolete. Amana part no. 10636701; contains T874G1899 and Q674F1550.

G1609

155 Obsolete. Econar; contains T874G1915 and Q674F1212.

a Both the thermostat and subbase must be replaced.

See OEM for replacement. See OEM for replacement.
None None Y594G1252 Y594G1252 Y594G1567 Y594G1567
Y594G1161 Y594G1633 Y594G1252

Remarks H2 is night setback. Wiring differences (old=new): Y1=O, X=L, C=X. Wiring differences (old=new): Y1=O, X=L, C=X; W1=Y.
H2 is night setback.
See Trol-A-Temp for replacement.
Cooling changeover only. Cooling changeover only. Replacement is beige.
Wiring differences (old=new): E=X2, C=B, L=F.

60-2485--8

90

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 10. Y594 Cross Reference.

Model Number G1617
G1625 G1633
G1641 G1658 G1666
G1674
G1716 Y594H
H1004 H1012 H1020 H1038 H1046 H1053 Y594J J1001

Fig.

Trade Model

No.

Description

Replacementa

Remarks

73 Obsolete. Carrier part no. 50QE90020101; contains T874G1949 and Q674C1504.

Y594H1012a

Wiring differences (old=new): Y1=O, Y2=Y, L=R, R=none; R-L jumper required; no night setback.

T8600D2028 Wiring differences (old=new): (programmable) Y1=O, Y2=Y, L=R; W-Y jumper
required; night setback.

160 York Canada part no. 2TH11702524; contains T874G1964 and Q674J1266.

Y594G1567a Replacement has °F scaleplate.

169 TRADELINE; contains T874G1972 and Q674F1584; direct replacement for Y594G1377 (T874G1576/Q674F1402) Evcon/Coleman part no. 3600-373.

Y594G1633a

169 Obsolete. Amana part no. 10636703; contains T874G1980 and Q674F1600.

Y594G1633 Wiring differences (old=new): W3=W2.

155 Obsolete. Tempstar "Inter-City Products" part no. 1149910; contains T874G1998 and Q674F1212.

Y594G1252

103 Obsolete. TRADELINE; manual changeover; contains T874G2004 and Q674L1892; direct replacement for Y507J1011 (T874G1055/ Q674L1041) Carrier part no. 99TZ90041106 (HH07AT171/HH93AZ1750).

Y594G1674 Replacement has auto changeover.

161 TRADELINE; automatic changeover; contains T874G2004 and Q674J1274; direct replacement Y507J1003 (T874G1055/Q674J1035) Carrier part no. 99TZ90040106 (HH07AT171/HH93AZ173).

Y594G1674

155 WaterFurnace logo; part no. TA21H03; contains T874G2046 and Q674F1667.

Y594G1716

79 Obsolete. LSI part no. 73033901; contains T874H1039 and Q674C1124.
164 Contains T874H1062 and Q674C1249; replaces T874H1005/Q674C1041.
177 Obsolete. Mammoth part no. 71117101; contains T874H1096 and Q674C1330.
74 Obsolete. Carrier part no. 50QE90019101; contains T874H1161 and Q674C1496.
172 Obsolete. Carrier part no. 50QE90026101; contains T874H1153 and Q674B1406.
173 Obsolete. Carrier part no. 50QE90027101; contains T874H1153 and Q674C1322.

T8600D2028 H2 is night setback.

Y594H1012

Y594H1012
Y594H1012a
T874A1130/ Q674B1075a Y594H1012a

Wiring differences (old=new): R1=R, R2=L; use jumper provided.
Wiring differences (old=new): X1=O, Y2=Y; L-R jumper required.
Wiring differences (old=new): Y=Y1; W1-Y1 jumper required; replacement has no LEDs.
Wiring differences (old=new): Z=X.

241 Obsolete. TRADELINE; manual changeover; contains T874J1069 and Q674L1900; direct replacement for T874J1002 or T874A1028 used with Q674L1074 or Q674L1637 (HH07AT175 or HH07AT165 used with HH93AZ186 or HH93AZ195).

(Recontrol) T8511G1021

a Both the thermostat and subbase must be replaced.

91

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Model Number J1019
Y594N N1007 N1015

Table 10. Y594 Cross Reference.

Fig.

No.

Description

244 Obsolete. TRADELINE; automatic changeover; contains T874J1069 and Q674J1282; direct replacement for T874J1002 or T874J1028 used with Q674J1068 or Q674J1159 (HH07AT175 or HH07AT165 used with HH93AZ183 or HH93AZ196).

Trade Model Replacementa
(Recontrol) T8511G1021

178 Obsolete. Williamson part no. 75-189; contains T874N1008 and Q674F1196.
179 Obsolete. Contains T874N1040 and Q674F1261.

T874N1016/ Q674F1196
Y594G1419a

N1023
N1031
Y594P P1005

178 Obsolete. Intertherm part no. 9111882; contains T874N1057 and Q674F1220.
178 Obsolete. Nordyne "Miller" part no. 9122240; contains T874N1065 and Q674F1220.

T874N1016/ Q674F1220
T874N1016/ Q674F1220

97 Obsolete. Carrier part no. 50QE90021101; contains T8600D2028 T874P1055 and Q674C1512.

Y594R R1011 R1029 R1037 R1102 R1110 R1128 R1136 R1151 R1185

120 Obsolete. York part no. 2TH11702224; contains T874R1046 and Q674L1272.
47 Obsolete. Bryant; contains T874R1004 and Q674B1042.
122 Obsolete. Fedders part no. 88-58-00540-001; contains T874R1269 and Q674L1066.
120 Obsolete. York part no. 025-22285-000; contains T874R1145 and Q674L1272.
108 Obsolete. Heil Quaker part no. HQ712004HW; contains T874R1137 and Q674L1132.
116 Obsolete. Crispaire part no. HP9-51; contains T874R1111 and Q674L1215.
109 Obsolete. Contains T874R1053 and Q674L1140.
120 Obsolete. York part no. 2TH11702324; contains T874R1251, Q674L1272 and C815A1039.
201 Obsolete. Intertherm part no. 9111871; contains T874R1202 and Q674L1264.

Y594R1664 Y594R1243 Y594R1615 Y594R1664 Y594R1292 Y594R1243 Y594R1763 Y594R1672 Y594R1672

R1193 R1201 R1219

120 Obsolete. York part no. 6TH11702224; contains T874R1327 and Q674L1272.
106 Obsolete. BDP part no. HH641501; contains T874R1335 and Q674L1405.
133 Obsolete. Fedders part no. 88-58-00560-001; contains T874R1343 and Q674L1413.

Y594R1664 Y594R1243 Y594R1425

R1235

125 Obsolete. Coleman part no. 3600-368; contains T874R1368 and Q674L1421.

R1243

115 TRADELINE; contains T874R1152 and Q674L1207.

R1250

128 Obsolete. Williamson part no. 75-191; contains T874R1392 and Q674L1447.

R1284

136 Obsolete. Trane part no. BAYSTAT339; contains T874R1426 and Q674L1496.

a Both the thermostat and subbase must be replaced.

Y594R1797
Y594R1243 Y594R1425
Y594R1763

Remarks
Wiring differences (old=new): L=X2, Y=Y1.
Wiring differences (old=new): Y=Y1, W=O; Y1-W1 jumper required.
Wiring differences (old=new): W1=W2. Wiring differences (old=new): K=E, C=X, W1=B, Z=L.
Wiring differences (old=new): A=L.
Wiring differences (old=new): W2=W, X=B, Z=no connection, K=X, W1=H.
Wiring differences (old=new): K=E, C=X, Z=L; remove factory installed jumper.
Wiring differences (old=new): A=L.

60-2485--8

92

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Model Number R1292 R1300 R1318 R1326 R1334 R1342 R1359 R1375 R1383 R1391 R1409

Table 10. Y594 Cross Reference.

Fig.

Trade Model

No.

Description

Replacementa

108 Contains T874R1467 and Q674L1512; replaces Y594R1110 (T874R1137/Q674L1132).

Y594R1292

123 Contains T874R1475 and Q674L1520.

Y594R1300

130 Obsolete. Comfortmaker part no. 1505721; contains T874R1483, Q674L1538 and C815A1005.

Y594R1763

137 Obsolete. SUPER TRADELINE; contains T874R1491 and Q674L1553.

Y594R1615

47 Obsolete. Slant Fin; contains T874R1509 and Q674B1042.

Y594R1243

130 Obsolete. ArcoAire part no. 1506721; contains T874R1517, Q674L1538 and C815A1005.

Y594R1763

113 Obsolete. ArcoAire part no. A02074; contains T874R1525 and Q674L1181.

Y594R1243

130 Obsolete. Contains T874R1566, Q674L1538 and C815A1005.

Y594R1763

132 Obsolete. Comfortmaker part no. 1505739; contains T874R1574 and Q674L1538.

Y594R1243

132 Obsolete. ArcoAire part no. 1506739; contains T874R1582 and Q674L1538.

Y594R1243

119 Obsolete. Intertherm part no. 6244630; contains T874R1608 and Q674L1264.

Y594R1763

R1417 R1425 R1433

113 Obsolete. Comfortmaker part no. 1505-735; contains T874R1301 and Q674L1181.
168 SUPER TRADELINE; contains T874R1616 and Q674L1587.
200 Obsolete. Miller part no. 9115900; contains T874R1624 and Q674L1595.

Y594R1243 Y594R1425 Y594R1243

R1441 R1466 R1482

136 Obsolete. American Standard (Trane) part no. ASYSTAT651; contains T874R1657 and Q674L1611.
108 Heil Quaker part no. 1060321; model no. HAXB004TW01; contains T874R1673 and Q674L1132.
119 Obsolete. Nordyne "Miller" part no. 9122230; contains T874R1699 and Q674L1264.

Y594R1763 Y594R1292 Y594R1763

R1490

209 Trol-A-Temp; contains T874R1707 and Q674L1678.

None

R1508

209 Trol-A-Temp; contains T874R1715 and Q674L1686.

None

R1516

132 Obsolete. Snyder General part no. 654958B07; contains T874R1723, Q674L1702 and C815A1005.

R1524

108 Obsolete. Inter-City Products part no. HQ1147925HW; contains T874R1731 and Q674L1132.

R1532

108 Heil Quaker part no. 1060322; model no. TAXB004TW01; contains T874R1749 and Q674L1132.

R1607

108 Obsolete. Keeprite THPC; contains T874R1814 and Q674L1132.

a Both the thermostat and subbase must be replaced.

Y594R1763 Y594R1292 Y594R1292 Y594R1292

Remarks
Wiring differences (old=new): W1=W, E=X2, X=F, C=B.
Wiring differences (old=new): W1=W2. Wiring differences (old=new): W1=W, E=X2, X=F, C=B. Wiring differences (old=new): X1=X. Wiring differences (old=new): W1=W, E=X2, X=F, C=B. Wiring differences (old=new): W=W2, C=X, X=L. Wiring differences (old=new): W=W2, C=X, X=L. Wiring differences (old=new): W2=W, X=B, Z=F, K=X2, W1=O. Wiring differences (old=new): X1=X.
Wiring differences (old=new): W2=W, X=B, Z=F, K=X2, W1=O.
Wiring differences (old=new): W2=W, X=B, Z=F, K=X2, W1=O. See Trol-A-Temp for replacement. See Trol-A-Temp for replacement. Wiring differences (old=new): W1=W, C=B, X=X2.

93

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 10. Y594 Cross Reference.

Model

Fig.

Number

No.

Description

R1615

230 TRADELINE; contains T874R1822 and Q674L1710; replaces Y594R1326 (T874R1491/ Q674L1553).

R1623

134 Obsolete. Rheem Universal Parts part no. 4120796-46; contains T874R1558 and Q674L1504.

R1631

134 Rheem part no. 41-20796-29; contains T874R1442 and Q674L1504.

R1649

134 Ruud part no. 41-20796-33; contains T874R1434 and Q674L1504.

R1656

134 Obsolete. WeatherKing part no. 41-20796-64; contains T874R1830 and Q674L1504.

R1664

120 TRADELINE; contains T874R1871 and Q674L1736; direct replacement for York 2TH11702224 (Y594R1011 contains T874R1046/ Q674L1272).

R1672

120 TRADELINE; contains T874R1889, Q674L1736 and C815A1054; direct replacement for York 2TH11702324 (Y594R1151 contains T874R1251/ Q674L1272/C815A1039) and 6TH11702224 (Y594R1193 contains T874R1327/Q674L1272).

R1680

230 TRADELINE; same as Y594R1615 except Premier White® color; contains T874R1897 and Q674L1751; direct replacement for Y594R1326 (T874R1491/Q674L1553).

R1698

120 Obsolete. TRADELINE; Premier White® color; contains T874R1905, Q674L1777 and C815A1054.

R1706

120 Obsolete. TRADELINE; same as Y594R1664 except Premier White® color; contains T874R1913 and Q674L1777; direct replacement for Y594R1011 (T874R1046/Q674L1272) York part no. 2TH11702224.

R1714

228 Obsolete. Lennox part no. 97E79; Canada; Premier White® color; contains T874R1855 and Q674L1728.

R1722

115 Obsolete. Econar; contains T874R1921 and Q674L1207.

R1748

197 American Standard (Trane) part no. ASYSTAT651A; contains T874R1939 and Q674L1801.

R1755

168 Obsolete. Inter-City Products part no. HQ1149376HW; contains T874R1947 and Q674L1819.

R1763

197 TRADELINE: contains T874R1954 and Q674L1827; direct replacement for Y594R1136 (T874R1053/Q674L1140), Y594R1748 (T874R1939/Q674L1801) Trane part no. ASYSTAT651A, Y594R1441 (T874R1657/ Q674L1611) Trane part no. ASYSTAT651.

R1771

115 Obsolete. Consolidated Industries part no. 9036100; contains T874R1962 and Q674L1843.

R1789

120 York Canada part no. 2TH11701524; contains T874R1970 and Q674L1850.

a Both the thermostat and subbase must be replaced.

Trade Model Replacementa
Y594R1615 Y594R1300 Y594R1300 Y594R1300 Y594R1300 Y594R1664
Y594R1672
Y594R1680
Y594R1672 Y594R1664
Y594R1763 Y594R1243a Y594R1763a Y594R1425a Y594R1763
Y594R1680a Y594R1672a

Remarks
Replacement is beige. Replacement is beige. Wiring differences (old=new): Y1=Y, L=F, W1=W, E=W2, C=B.
Includes CHECK LED. Replacement has °F scaleplate.

60-2485--8

94

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

Table 10. Y594 Cross Reference.

Model Number R1797
R1805 R1813 R1821 R1839 R1854 Y594W W1014 W1022 W1030
W1055 Y594Y
Y1004 Y1012

Fig.

No.

Description

125 TRADELINE; contains T874R1988 and Q674L1868; direct replacement for Y594R1235 (T874R1368/Q674L1421) Evcon/Coleman part no. 3600-368).

245 Obsolete. Amana part no. 10636702; contains T874R2002 and Q674L1876.

245 Obsolete. Amana part no. 10636704; contains T874R2010 and Q674L1884.

125 Obsolete. York logo; part no. 2TH11703424A; contains T874R2028 and Q674L1918.

134 Rudd logo; part no. 41-20796-48; contains T874R2036 and Q674L1504.

123 Obsolete. Rheem logo; part no. 41-20796-47; contains T874R1996 and Q674L1504.

Trade Model Replacementa
Y594R1797a

Remarks

Y594R1797 Y594R1797 Y594R1797

Wiring differences (old=new): C/X=X.
Wiring differences (old=new): C/X=X, W3=W2.

See OEM for replacement.
Y594R1300

54 Contains T874W1015, Q674B1216 and C815A1005.

Y594W1014

140 Obsolete. Rheem part no. 41-20797-19; contains T874W1031, Q674L1546 and C815A1005.

T8611M2025.

68 Obsolete. Inter-City Products part no. 1072350;

T8611M2025 Includes night setback.

contains T874W1072, Q674L1835 and C815A1005 (programmable)

Outdoor Thermistor.

247 Obsolete. Addison logo; part no. 843-277; contains T874W1106, Q674L1934 and C815A1005.

T8611M2025

210 Obsolete. Mammoth part no. 71117301; contains T874Y1005 and Q674E1353.
248 Obsolete. WaterFurnace logo; part no. TA21H03; contains T874Y1013 and Q674F1675.

See OEM for replacement.

a Both the thermostat and subbase must be replaced.

95

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
WIRING DIAGRAMS

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 FALL
H1 ANTICIPATOR

4

FALL

H2
6 H2 ANTICIPATOR

8 C1 RISE
9

FAN SWITCH
AUTO ON
SYSTEM SWITCH
HEAT OFF COOL

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 JUMPER RH, RC FOR SINGLE TRANSFORMER.

RH HEAT RELAY 1
W1
HEAT RELAY 2 W2
HEAT CHANGEOVER VALVE B

2

COOL CHANGEOVER VALVE

O

FAN RELAY G

COMPRESSOR CONTACTOR 2
Y2

COMPRESSOR CONTACTOR 1
Y1

RC

L1 (HOT) L2
1
NOTE: Model ing No. T874A T874B T874C T874D T874E T874D
L2 L1 (HOT) 1

Heating Cool-

Bulbs H1 H1 H1,H2 H1,H2
H1,H2

Bulbs C1 C1,C2 C1 C1,C2 C1,C2

M2903

Fig. 44. Schematic and hookup of T874A,B,C,D,E,F with Q674B. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 FALL H1 ANTICIPATOR
4

FAN SWITCH
AUTO
ON

RH

L1 (HOT)

3

HEAT RELAY 1

L2

W1

1

HEAT RELAY 2

W2

HEAT CHANGEOVER VALVE

B

FALL

H2 6
H2 ANTICIPATOR

8 C1 RISE
9

SYSTEM SWITCH
HEAT OFF
COOL

X1

O
COOL CHANGEOVER VALVE

G

2

FAN RELAY

Y2

10 C1 ANTICIPATOR

COMPRESSOR CONTACTOR 2

RISE

C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y1
COMPRESSOR CONTACTOR 1 RC

L2
L1 (HOT) 1

2 JUMPER RH, RC FOR SINGLE TRANSFORMER.

3 OPTIONAL LED ON SOME MODELS.

M933C

Fig. 45. Schematic and hookup of T874C,D with Q674B. Used in standard applications.

60-2485--8

96

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 FALL H1 ANTICIPATOR
4

FAN SWITCH
AUTO
ON

HEAT RELAY 1 W1
HEAT RELAY 2 W2
HEAT CHANGEOVER VALVE
B

FALL RISE
RISE

H2 6
H2 ANTICIPATOR
8 C1
9

SYSTEM SWITCH
HEAT OFF
COOL

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
O COOL CHANGEOVER VALVE
G FAN RELAY
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

Fig. 46. Schematic and hookup of T874A,B,D with Q674B. Used in standard applications.

L1 (HOT) L2
1
M2904

.
THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

C1

FALL

1 H1/C1 ANTICIPATOR
2
3

4

FAN SWITCH
AUTO ON
SYSTEM SWITCH

O COOL CHANGEOVER VALVE
G FAN RELAY
R

L1 (HOT)
L2 1

FALL

HEAT 5
OFF
COOL H2
6
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

W1 AUX. HT. RELAY
Y COMPRESSOR CONTACTOR

M2906

Fig. 47. Schematic and hookup of T874R with Q674B. Used in heat pump applications.

97

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

1 H1 FALL
H1 ANTICIPATOR

4

H2

H2

6

FALL

ANTICIPATOR

8 C1 RISE
9

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2

FAN SWITCH
AUTO ON
SYSTEM SWITCH
HEAT OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 CLOGGED FILTER, SERVICE SWITCH.

SYSTEM COMPONENTS

HEAT RELAY 1 W1
FAN RELAY G

L1 (HOT) L2
1

EXTERNAL FAN SWITCH
RC
HEAT RELAY 2
W2
HEAT CHANGEOVER VALVE
B
RH 2
X1 FILTER LED (RED)
O COOL CHANGEOVER VALVE
Y1
COMPRESSOR CONTACTOR 1
Y2
COMPRESSOR CONTACTOR 2

L2 L1 (HOT) 1
M2905

Fig. 48. Schematic and hookup of T874D with Q674B. Used in standard applications.

60-2485--8

98

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H2 FALL

H1 ANTICIPATOR
1
4 H2 ANTICIPATOR

6 FALL H1
8 C1 ANTICIPATOR

9

C1 10
RISE

FAN SWITCH AUTO ON
SYSTEM SWITCH
HEAT OFF
COOL

HEAT LED (RED)

HEAT RELAY 1 W1
BLOWER RELAY G
R HEAT RELAY 2
W2

T

COOL LED (YELLOW)

COMPRESSOR CONTACTOR

Y1

L1 (HOT)
L2 1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L LO SPEED LED (GREEN)
C HI SPEED LED (GREEN
H

HSII CONTROL PANEL

Fig. 49. Schematic and hookup of T874C with Q674B. Used in standard applications.

L1 (HOT) L2
M5945

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1
ANTICIPATOR

O
COOL CHANGEOVER VALVE

H1

FALL

2 FAN SWITCH

4

AUTO

ON

Y
COMPRESSOR CONTRACTOR

FALL

H2

H2 ANTICIPATOR

6

CO

8

SYSTEM SWITCH

RISE C1 RISE

9 C1 ANTICIPATOR

HEAT OFF
COOL

10 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

G AUX. HT. RELAY
W2

FAN RELAY

L2

R

L1

1 (HOT)

M8000

Fig. 50. Schematic and hookup of T874G with Q674B. Used in heat pump applications.

99

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
1 H1 ANTICIPATOR
3
4

FAN SWITCH
AUTO
ON

W1 G RC
2

HEAT RELAY 1
FAN RELAY
L1 (HOT) 1 L2 HEAT RELAY 2

6 FALL
H2 H2 ANTICIPATOR

C1 RISE
RISE

8
9 C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

SYSTEM SWITCH
HEAT OFF
COOL

W2
B 3
RH O 3 Y1
Y2

HEAT CHANGEOVER VALVE
COOL CHANGEOVER VALVE COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2

C2 1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FIELD WIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER. 3 B, O TERMINALS ON SOME MODELS.

L1 L2 (HOT)

M5944

Fig. 51. Schematic and hookup of T874D with Q674B. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL

H1 ANTICIPATOR 1
4 5

FAN SWITCH AUTO
ON

W1 HEAT RELAY 1
G
RC 3
W3 2

FAN RELAY
L1 (HOT) L2
1

6

W2

H2

FALL

H2 ANTICIPATOR

F

SYSTEM SWITCH
RH HEAT

B OFF

8

COOL

C1 RISE

9

O

C1 ANTICIPATOR

Y1

10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 OPTIONAL FIELD WIRE JUMPER. W3 AND F TO BE JUMPERED EXCEPT FOR TWO STAGE GAS APPLICATION.

3 FIELD WIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

HEAT RELAY 2
COMPRESSOR CONTACTOR
M5999

Fig. 52. Schematic and hookup of T874C with Q674B. Used in standard applications.

60-2485--8

100

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR
FALL H1 4

FAN SWITCH AUTO ON

HEAT RELAY 1 W1
HEAT RELAY 2 W2

FALL

H2 6
H2 ANTICIPATOR
8

RISE

C1

9

SYSTEM SWITCH
HEAT
OFF
COOL

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
G FAN RELAY
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

Fig. 53. Schematic and hookup of T874D with Q674B. Used in standard applications.

L1 (HOT) L2 1
M3202A

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

1 H1 ANTICIPATOR
H1 2
H2 ANTICIPATOR

FALL

3

H3 4
H3 ANTICIPATOR

5

FALL

H2

6

RESET HEATER

RISE C1

8 C1 ANTICIPATOR

FAN SWITCH AUTO
ON
SYSTEM SWITCH HEAT
OFF COOL

1 R C815A THERMISTOR
T

L1 (HOT) L2

W1 HEAT RELAY 1
W2 HEAT RELAY 2
W3 HEAT RELAY 3
B HEAT CHANGEOVER VALVE
G FAN RELAY

RISE

10 C2 ANTICIPATOR
11

C2
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

O COOL CHANGEOVER VALVE
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1
M3674

Fig. 54. Schematic and hookup of T874W with Q674B. Used in standard applications.

101

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL 1
H1 ANTICIPATOR

FALL

4

H2 ANTICIPATOR

3 5

6 H2
8

C1 RISE
9

C2 RISE

C1 ANTICIPATOR 10
C2 ANTICIPATOR
11

NO FAN SWITCH
NO SYSTEM SWITCH

RH 3
B HEAT RELAY 1
W1
HEAT RELAY 2 W2
2 COMPRESSOR CONTACTOR 2
Y2 COMPRESSOR CONTACTOR 1
Y1
RC

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 JUMPER RC, RH FOR SINGLE TRANSFORMER.

3 B AND 5 TERMINALS AVAILABLE ON SOME MODELS.

L1 (HOT) L2 1
L2 L1 (HOT)
M3667A

Fig. 55. Schematic and hookup of T874A,D,F with Q674D. Used in standard applications.

SUBBASE

SYSTEM COMPONENTS

1 FALL H1
H1 ANTICIPATOR 4
H2 ANTICIPATOR 6

FAN SWITCH
AUTO
ON

X RESET LED (RED)
G
R

RESET FAN RELAY

AUX. HT. RELAY W2

H2 FALL 8

9

C1 ANTICIPATOR

C1

RISE

10

11

SYSTEM SWITCH
HEAT
OFF
COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

B B RELAY
O O RELAY
Y2 COMPRESSOR CONTACTOR 1
Y1

Fig. 56. Schematic and hookup of T874C with Q674B. Used in standard applications.

L1 (HOT) L2
1
M5975

60-2485--8

102

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H2

1
2 H1 ANTICIPATOR
3

FAN SWITCH AUTO ON

Y
COMPRESSOR CONTACTOR G

FAN RELAY

R

CLOSED-DAY B RELAY

OPEN-NITE

1

B

L

4

SYSTEM

SWITCH

5

OVERRIDE

6

CO

RISE

H1

8

HEAT OFF
COOL

S JUMPER 2
P

RISE

9 C1 ANTICIPATOR

C1

10

COOL CHANGEOVER VALVE W
T

1 POWERSUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 JUMPER HONEYWELL SUPPLIED, FIELD INSTALLED.

M8004

L1 (HOT)
L2

Fig. 57. Schematic and hookup of T874P with Q674B. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2 H1 ANTICIPATOR

H1 FALL

3

Y
NO FAN SWITCH

ECONOMIZER PACKAGE

4

RH

Y

O

O

FALL

H2 ANTICIPATOR 6

W

W2

H2

8

NO SYSTEM

SWITCH

RISE

9

B

C1 ANTICIPATOR

CO 10

RC

O

C1 RISE

CONTROL

PANEL

M3722

Fig. 58. Schematic and hookup of T874G with Q674D. Used in standard applications.

103

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR

1
SYSTEM SWITCH
HEAT

FALL H1

OFF

4

COOL

8

RISE C1
9
C1 ANTICIPATOR
10

LO MED HIGH

ON

FAN SWITCH

W1 HEAT RELAY 1
B
R
G1 K1 RELAY
G2 K2 RELAY
O

1 L2

L1 (HOT) L2
L1

K1

K1

K2 K2

K2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y1
COMPRESSOR CONTACTOR

HI

MED LO

3 SPEED FAN SCHEMATIC

M3729

Fig. 59. Schematic and hookup of T874A with Q674Q. Used in fan coil applications.

THERMOSTAT

H1 ANTICIPATOR

1

FALL
H1 4

SUBBASE
FAN SWITCH AUTO ON

SYSTEM COMPONENTS
L1 (HOT) L2 1 W1
COOL RELAY CONTACT FAN RELAY G
R

FALL H2

6 H2 ANTICIPATOR
8

RISE

9

SYSTEM SWITCH
EVAP COOL
OFF HEAT

C1
C1 ANTICIPATOR 10
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ELEC. HT. RELAY W2
CHANGEOVER VALVE B
COMPRESSOR CONTACTOR Y1
EVAPORATOR RELAY Y2
M2863

Fig. 60. Schematic and hookup of T874C with Q674N. Used in evaporative cooler applications.

60-2485--8

104

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1

1

H1 ANTICIPATOR 4

FALL H2 ANTICIPATOR 6
H2

RISE

8

C1 9

10 C1 ANTICIPATOR

FAN SWITCH
AUTO ON
SYSTEM SWITCH
EVAP. COOL
OFF HEAT

COMPRESSOR CONTACTOR Y1
FAN RELAY G
R
ELEC. HT. RELAY W2
EVAPORATOR RELAY Y2
CHANGEOVER RELAY O

1 L1 (HOT)
L2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M2862

Fig. 61. Schematic and hookup of T874C with Q674N. Used in evaporative cooler applications.

THERMOSTAT
FALL H2
1 H2 ANTICIPATOR
4
FALL H1
8 9
H1 ANTICIPATOR 10

SUBBASE FAN SWITCH AUTO
ON

SYSTEM SWITCH
HEAT OFF
COOL

YELLOW GREEN

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS
FAN RELAY G

W2 AUX. HT. RELAY
R

C WOOD/COAL RELAY
W1
COMPRESSOR CONTACTOR
X2
EXTERNAL COOLING THERMOSTAT (SUCH AS T87 F)

X1

Y

R

L2 L1 (HOT) 1
M3723A

Fig. 62. Schematic and hookup of T874F with Q674B. Used in wood/coal applications.

105

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H2 H2 ANTICIPATOR
FALL H1

NO FAN
SWITCH 1

4

NO

SYSTEM

SWITCH

8

YELLOW GREEN

AUX. HT. RELAY W2 R C W1

1
HEAT/COOL SWITCH

WOOD/COAL

9

RELAY

H1 ANTICIPATOR 10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M3725

L1 (HOT)
L2

Fig. 63. Schematic and hookup of T874F with Q674D. Used in wood/coal applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENT

1
H1 ANTICIPATOR

H1

2

FALL

2

3

4

C1

5

ANTICIPATOR

RISE C1

SYSTEM SWITCH
HEAT OFF
COOL
FAN SWITCH
LO MED HIGH
ON

W1
HEAT RELAY 1 B

B RELAY

R
K1 RELAY G1

1
L1 (HOT) L2

L2

L1

G2
O RELAY O

K2 RELAY

K1

K1

K2

K2 K2

COMPRESSOR CONTACTOR Y1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 SINGLE SETPOINT LEVER AND BIMETAL.

HI

LO

MED

3-SPEED FAN SCHEMATIC M8005

Fig. 64. Schematic and hookup of T874A with Q674Q. Used in fan coil applications.

60-2485--8

106

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1 ANTICIPATOR 4

FALL

6

H1

FAN AUTO SWITCH
ON

W1 NO. 1 HEAT RELAY
W2 B HEAT DAMPER
RH

8

9

RISE C1

10 C1 ANTICIPATOR
11

SYSTEM SWITCH
HEAT
OFF
COOL

RC COOL DAMPER
O
G FAN RELAY
Y2

NO. 1 COMP. RELAY

FILTER LED (RED)

Y1
X1 SERVICE LED (YELLOW)
X2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Fig. 65. Schematic and hookup of T874A with Q674B. Used in standard applications.

L1 (HOT) L2
L1 (HOT) L2
1
M5976

THERMOSTAT

H1 H2

1 H1 ANTICIPATOR

4 FALL
5

FALL

6

H2 ANTICIPATOR 8

9

10

SUBBASE
NO FAN SWITCH
NO SYSTEM SWITCH

SYSTEM COMPONENTS HEAT RELAY 1 W1

HEAT RELAY 2 W2
RH

L1 (HOT)
L2 1

L1

RC

(HOT)

L2 1

Y2

11

Y1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M7011

Fig. 66. Schematic and hookup of T874A,D,F with Q674D. Used in standard applications.

107

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1 C1
FALL

2 H1/C1 ANTICIPATOR
3

4

5
FALL H2
6

FAN SWITCH AUTO
ON
SYSTEM SWITCH
HEAT OFF

X FAN RELAY
G

L1

R

(HOT)

1 L2

HEAT CHANGEOVER VALVE B

W2 AUX. HT. RELAY

COOL

COMPRESSOR CONTACTOR

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5998

Fig. 67. Schematic and hookup of T874R with Q674B. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H2 FALL
RISE CO C1

1

3

H1

ANTICIPATOR

2

3

4 5

6 H1
8 RISE

9
C1 ANTICIPATOR 10

FAN SWITCH AUTO
ON
SYSTEM SWITCH OVERRIDE
HEAT OFF
COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 JUMPER HONEYWELL SUPPLIED, FIELD INSTALLED.
3 H2 MAKE OFFEST 8° F BELOW H1 MAKE.

OVERRIDE LED (RED)

Y
COMPRESSOR CONTACTOR G
FAN RELAY C

CLOSED-DAY OPEN-NITE
R
SERVICE LED (RED)
B
L
X

L2 L1 (HOT) 1
B RELAY

S

COMPRESSOR

FAULT

JUMPER 2

P

COOL CHANGEOVER VALVE

W

T M101A

Fig. 68. Schematic and hookup of T874P with Q674B. Used in heat pump applications.

60-2485--8

108

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
RISE 8
C1

FAN SWITCH LO
AUTO HI
CONT.

SUBBASE

SYSTEM SWITCH OFF COOL

SYSTEM COMPONENTS

Z RELAY Z

G FAN RELAY

R

L1

(HOT) 1

L2

9

10

C1 ANTICIPATOR

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COOL RELAY M107A

Fig. 69. Schematic and hookup of T874V with Q674R. Used in fan coil applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 FALL
4

NO FAN SWITCH

SERVICE LED (RED)

S
COMPRESSOR FAULT

H2 FALL
H1 FALL

6

W2

SYSTEM SWITCH

8

HEAT

COOL

R

9

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

AUX. HT. RELAY
COMPRESSOR CONTACTOR

1 L2 L1 (HOT)
M1402A

Fig. 70. Schematic and hookup of T874C with Q674S. Used in heat pump applications.

109

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

H1 FALL
4

FALL

H2 6
H2 ANTICIPATOR
8

RISE

C1 9
10 C1 ANTICIPATOR

FAN SWITCH AUTO ON
SYSTEM SWITCH
HEAT AUTO COOL

CHECK 3

RH HEAT RELAY 1
W1
HEAT RELAY 2 W2

X1

G

2

FAN RELAY

Y2

COMPRESSOR CONTACTOR 2

RISE

C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y1
COMPRESSOR CONTACTOR 1 RC

2 JUMPER RH, RC FOR SINGLE TRANSFORMER.

3 OPTIONAL LED ON SOME MODELS.

L1 (HOT) L2
1
L2 L1 (HOT) 1 M932B

Fig. 71. Schematic and hookup of T874A-D with Q674A. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR

1

H1

FALL

4

6

FALL

H2 ANTICIPATOR H2

8
RISE C1
9
C1 ANTICIPATOR 10

FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF AUTO

C2 ANTICIPATOR 11

C2

RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 JUMPER TERMINALS RC-RH FOR SINGLE SYSTEM TRANSFORMER ONLY.

3 B,O TERMINALS ON SOME MODELS.

RH

2

W1

HEAT RELAY 1

W2 HEAT RELAY 2
B 3 HEAT DAMPER
O COOL DAMPER

G FAN RELAY

Y2
COMPRESSOR CONTACTOR 2

Y1

COMPRESSOR

2

CONTACTOR 1

RC

L1 (HOT) L2
1
1 L2 L1 (HOT) M5122A

Fig. 72. Schematic and hookup of T874D,E,F with Q674C. Used in standard applications.

60-2485--8

110

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H ANTICIPATOR 2
H1
3

4 SETBACK FALL
6

FAN SWITCH AUTO
ON

Y1 REVERSING VALVE RELAY
Y2 COMPRESSOR CONTACTOR
G FAN RELAY

RISE RISE

8 9 CO
10
C ANTICIPATOR C1

SYSTEM SWITCH
OFF
AUTO

OPEN-NIGHT CLOSED-DAY
R
SETBACK RELAY
L

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L2 L1 1 (HOT)
M7008

Fig. 73. Schematic and hookup of T874G with Q674C. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

2 H1 ANTICIPATOR
3

4

FAN SWITCH AUTO
ON

Y1 COOL CHANGEOVER VALVE
FAN RELAY G R

8

RISE CO

9 C1 ANTICIPATOR
10

SYSTEM SWITCH
OFF
AUTO

RISE C1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 SERVICE LED ON SELECT MODELS.

Y2
COMPRESSOR CONTACTOR B

1

O

L1 L2

(HOT)

2

X

SERVICE LED (YELLOW)

COMPRESSOR FAULT

C

M3680A

Fig. 74. Schematic and hookup of T874H with Q674C. Used in heat pump applications.

111

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR

1 SYSTEM SWITCH OFF
AUTO

FILTER LED (YELLOW)

W1
3 X

HEAT RELAY

4
H1 FALL 8

RISE C1

9
C1 ANTICIPATOR
10

11 THERMISTOR
12

FAN SWITCH AUTO
ON 2

A SERVICE LED (RED)
G
R

FAN RELAY

O MOMENTARY CIRCUIT
O
Y
COMPRESSOR CONTACTOR
T EXTERNAL TEMP. READOUT
T

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE. 3 FILTER LED ON SELECT MODELS.

M5731

Fig. 75. Schematic and hookup of T874A with Q674C. Used in standard applications.

1
L1 (HOT) L2

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

H1

FALL

4

FAN SWITCH
AUTO
ON

FALL H2

6 H2 ANTICIPATOR

8 C1

RISE 9

SYSTEM SWITCH
OFF

RISE C2

10 C1 ANTICIPATOR
11

AUTO

C2 ANTICIPATOR

2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

3

FILTER LED (YEL)

SERVICE LED (RED)

2 FOR T874C, DELETE C2.

3 FILTER LED ON SELECT MODELS.

W1
HEAT RELAY 1 W2
HEAT CHANGEOVER VALVE B
RH

HEAT RELAY 2
L2 L1 1 (HOT)

RC
COOL CHANGEOVER VALVE O

L1 (HOT)
L2 1

G
Y2 COMPRESSOR CONTACTOR 2
Y1

FAN RELAY
COMPRESSOR CONTACTOR 1

X

A M7025

Fig. 76. Schematic and hookup of T874A-D with Q674C. Used in standard applications.

60-2485--8

112

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

CO H2
H1

1 FALL
3

FALL 4

FALL

6

H1 ANTICIPATOR

FAN SWITCH
AUTO
ON

RISE C1

8
9 C1 ANTICIPATOR
10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 JUMPER RH AND RC FOR SINGLE TRANSFORMER SYSTEM.

SYSTEM SWITCH
OFF
AUTO

RESET LED (RED)

X1 FAN RELAY
G

RH

L1 (HOT)

2

L2 1

HEAT CHANGEOVER VALVE W1 HEAT RELAY 2
W3 HEAT RELAY 1
W2 "B" RELAY
B

RC
O COMPRESSOR CONTACTOR
Y1

L1 (HOT) L2 1 "O" RELAY
M4729

Fig. 77. Schematic and hookup of T874K with Q674C. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H2

FALL

2 H1

ANTICIPATOR

3

4

FAN SWITCH
AUTO
ON

5

6

SYSTEM

SWITCH

CO H1

OVERRIDE

RISE C1
RISE

8
9 C1 ANTICIPATOR
10

AUTO OFF

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 JUMPER HONEYWELL SUPPLIED, FIELD INSTALLED.

Y COMPRESSOR CONTACTOR
G FAN RELAY
C
R SETBACK CONTACT
B HEAT CHANGEOVER VALVE
L
S JUMPER 2
P REVERSING VALVE
W

Fig. 78. Schematic and hookup of T874P with Q674C. Used in heat pump applications.

L1 (HOT) L2
1
M7026

113

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

1 H1 ANTICIPATOR

H1

FALL

4

6

H2

FALL

3 8

9 CO

RISE

C1
ANTICIPATOR 10

SUBBASE
FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF AUTO

RESET LED (RED)

SYSTEM COMPONENTS RESET X

G FAN RELAY
R1 2 SETBACK CONTACT
R2 COOL CHANGEOVER VALVE
O
COMPRESSOR CONTACTOR
Y

L1 (HOT)
L2 1

C1

RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 SETBACK CONTACT ON Q674C1124.

3 H2 ON T874G.

M7027

Fig. 79. Schematic and hookup of T874G,H with Q674C. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL 1
H1

W1

HEAT RELAY 1

CONTACTOR COMPRESSOR 1

H1 ANTICIPATOR

FAN SWITCH

4

AUTO

ON

Y1
G RC FAN RELAY

H2 ANTICIPATOR

6

H2

FALL

8 RISE
C1
9
C1 ANTICIPATOR 10

C2 ANTICIPATOR

C2

11

SYSTEM OFF SWITCH
HEAT
AUTO COOL

2 W2
RH

HEAT RELAY 2

C SERVICE LED (RED)
Z

COMPRESSOR

FAULT

COMPRESSOR

CONTACTOR 2

Y2

RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 OPTIONAL FIELDWIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

M5997

Fig. 80. Schematic and hookup of T874D with Q674E. Used in standard applications.

L1 (HOT)
L2 1

60-2485--8

114

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL
H1 1

CHANGEOVER RELAY
W1

4

FALL

H2 ANTICIPATOR

6

H2 8

RISE C1
9

FAN SWITCH
AUTO ON
SYSTEM SWITCH OFF

C1 ANTICIPATOR 10

AUTO

1 POWER SUPPLY. PROVIDE DISCONECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

B
FAN RELAY
G

R

W2

COMPRESSOR

CONTACTOR

Y1

1
L1 L2 (HOT)

M5981

Fig. 81. Schematic and hookup of T874C with Q674C. Used in heat pump applications.

THERMOSTAT
FALL H1 1
H1 ANTICIPATOR
4 H2 ANTICIPATOR

SUBBASE
FAN SWITCH
AUTO ON

SYSTEM COMPONENTS

RH HEAT RELAY 1
W1

L1 (HOT)
L2 1

2 HEAT RELAY 2
W2

FALL

6

H2

8

RISE

C1 9
C1 ANTICIPATOR
10

C2 ANTICIPATOR 11

SYSTEM SWITCH
OFF HEAT AUTO COOL

1 POWER SUPPLY. PROVIDE DISCONNECT

MEANS AND OVERLOAD PROTECTION

C2

AS REQUIRED.

RISE

2 JUMPER RC, RH FOR SINGLE TRANSFORMER.

3 O AND B TERMINALS ON SELECTED MODELS.

O 3
B FAN RELAY
G COMPRESSOR CONTACTOR 2
Y2
COMPRESSOR CONTACTOR 1 Y1
RC

L2 1
L1 (HOT)
M934

Fig. 82. Schematic and hookup of T874A,C,D with Q674E. Used in standard applications.

115

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
L1 (HOT) 1 L2

H1 ANTICIPATOR 1
FALL
H1

4 H2 ANTICIPATOR

FALL

H2

6

FAN SWITCH
AUTO
ON

HEAT RELAY 1 W1
COMPRESSOR CONTACTOR 1 Y1
FAN RELAY G
RC HEAT RELAY 2
W2

8

RISE

RH

C1 OFF
9 HEAT

C1 ANTICIPATOR 10

AUTO COOL

CHECK LED (RED)
X1
Y2

COMPRESSOR CONTACTOR 2

C2 ANTICIPATOR 11

RISE C2

1 POWER SUPPLY. PROVIDE DISCONECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L2 1
L1 (HOT)

M5982

Fig. 83. Schematic and hookup of T874G with Q674C. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR
2
H1 FALL 4

FAN SWITCH AUTO
ON

H2 ANTICIPATOR 6

FALL H2
CO RISE

8
C1 ANTICIPATOR 9

SYSTEM SWITCH
OFF
HEAT

RISE C1

AUTO 10
COOL
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R

COOL CHANGEOVER VALVE

OUTDOOR FAN RELAY

DEFROST SWITCH

DEFROST RELAY

M

HIGH PRESSURE SWITCH

COMPRESSOR CONTACTOR

F

DEFROST RELAY

FAN RELAY

V

DEFROST AUX. HT.

RELAY

RELAY

Y

L2 1
L1 (HOT)

M4666

Fig. 84. Schematic and hookup of T874G with Q674E. Used in heat pump applications.

60-2485--8

116

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

1

H1

ANTICIPATOR

FALL

4

6 FALL
H2 ANTICIPATOR H2
8
RISE C1
9

RISE

C1 ANTICIPATOR
10
C2 ANTICIPATOR
11

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF HEAT AUTO COOL

W1 COMPRESSOR CONTACTOR 1
Y1
G
R

HEAT RELAY 1
FAN RELAY L1 (HOT) L2 1

HEAT RELAY 2 W2
COMPRESSOR CONTACTOR 2 Y2

C2

1 POWER SUPPLY. PROVIDE DISCONECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5983

Fig. 85. Schematic and hookup of T874A-D with Q674E. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1
2
FALL H1
3

FAN SWITCH
AUTO
ON

5

H2

FALL

6 H2 ANTICIPATOR

RISE CO
C1

8 SYSTEM SWITCH

C1 ANTICIPATOR 9

OFF HEAT

AUTO 10
COOL
RISE 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L1 (HOT)
1 L2

R

COOL CHANGEOVER VALVE

D. F. O.

DEFROST SWITCH

DEFROST RELAY

M

HIGH PRESSURE SWITCH
F

COMPRESSOR CONTACTOR

FAN RELAY V

DEFROST RELAY CONTACT Y
DEFROST RELAY CONTACT
VR

AUX. HT. RELAY
1 L2 L1
M4667 (HOT)

Fig. 86. Schematic and hookup of T874G with Q674E. Used in heat pump applications.

117

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1

FALL

H1 ANTICIPATOR 4

H2 ANTICIPATOR FALL

H2

6

RISE 8
C1

RISE C2

9
C1 ANTICIPATOR 10
C2 ANTICIPATOR 11

FAN SWITCH AUTO
ON

W1
HEAT RELAY 1 Y1
COMPRESSOR CONTACTOR 1

G FAN RELAY
RC

L1 (HOT) 1 L2

SYSTEM SWITCH

W2

B

2

HEAT RELAY 2

OFF HEAT AUTO COOL

RH
X
C LOCKOUT LED (RED)
Y2

SYSTEM FAULT CONTACT

L2 1
L1 (HOT)

COMPRESSOR CONTACTOR 2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FIELDWIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

M4668

Fig. 87. Schematic and hookup of T874D with Q674E. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

FAN

H1

SWITCH

ANTICIPATOR

H1

FALL

AUTO

4

ON

FALL H2 ANTICIPATOR 6
H2

RISE 8
C1

RISE C2

9
C1 ANTICIPATOR 10
C2 ANTICIPATOR 11

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM SWITCH
OFF HEAT
AUTO COOL

W1

HEAT RELAY 1 G

FAN RELAY RC

1
L1 (HOT) L2

W2 HEAT RELAY 2

RH
X HIGH LED (RED)

L2 1
L1 (HOT)

Y2 LOW LED (GREEN)
Y1

COMPRESSOR CONTACTOR 2

COMPRESSOR CONTACTOR 1

Fig. 88. Schematic and hookup of T874B,D with Q674E. Used in standard applications.

M4669

60-2485--8

118

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR
FALL H1
4

AUTO FAN SWITCH ON

B HEAT RELAY 1 HEAT CHANGEOVER VALVE
W1 COMPRESSOR CONTACTOR 1
Y1 FAN RELAY

6

G

H2 ANTICIPATOR H2
FALL
8 C1

RISE

9
10 C1 ANTICIPATOR

SYSTEM SWITCH
OFF HEAT AUTO
COOL

FILTER LED (YEL)
SERVICE LED (RED)

RC HEAT RELAY 2
W2 RH
X
A

L1 (HOT) L2 1
L1 (HOT) L2
1
COMPRESSOR CONTACTOR 2

11

Y2

C2 ANTICIPATOR

C2

RISE

COOL CHANGEOVER VALVE O

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M7023

Fig. 89. Schematic and hookup of T874D with Q674E. Used in standard applications.

THERMOSTAT 1
H1 ANTICIPATOR

SUBBASE
FILTER LED (YEL) SERVICE LED (RED)

H1 H2

FALL 4

5 6

FALL

H2 ANTICIPATOR 7

8

C1 RISE
9

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

10 C1 ANTICIPATOR

11

C2 ANTICIPATOR

C2

RISE

12

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FILTER LED (YEL)
SERVICE LED (RED)

SYSTEM COMPONENTS

X2
A2 HEAT RELAY 1
W1
X1

A1

W2 T RELAY
T

HEAT RELAY 2

RC HEAT CHANGEOVER VALVE
B
RH COOL CHANGEOVER VALVE
O
Y2 COMPRESSOR CONTACTOR 1
Y1

L1 (HOT) L2
1
L1 (HOT) L2
1 COMPRESSOR CONTACTOR 2
M7022

Fig. 90. Schematic and hookup of T874D with Q674G. Used in standard applications.

119

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

FALL H1 4

FALL

H2 6
H2 ANTICIPATOR
8

RISE

C1

9

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 JUMPER RH, RC FOR SINGLE TRANSFORMER.

RH HEAT RELAY 1
W1
HEAT RELAY 2 W2

B HEAT DAMPER

O

2

COOL DAMPER

Y2

COMPRESSOR CONTACTOR 2

Y1
COMPRESSOR CONTACTOR 1 RC

L1 (HOT) L2
1
L2 L1 (HOT) 1 M3201B

Fig. 91. Schematic and hookup of T874A-F,Q with Q674G. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1
3
FALL H1
4
H2 ANTICIPATOR 6

FALL H2
8

C1 RISE

9
C1 ANTICIPATOR 10

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

W1 CHANGEOVER RELAY
B
W2 FAN RELAY
G

Y1
COMPRESSOR CONTACTOR
R
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

1 L2
L1 (HOT)
M6008A

Fig. 92. Schematic and hookup of T874C with Q674G. Used in heat pump applications.

60-2485--8

120

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
1 H1 ANTICIPATOR
4
6

NO FAN SWITCH

HEAT FAN RELAY W1
HEAT RELAY W2

H2

H2

FALL ANTICIPATOR

SYSTEM

RH

SWITCH

8

OFF

RISE C1

HEAT

AUTO Y1
9 COOL
C1 ANTICIPATOR

10

RC

C2 ANTICIPATOR

RISE

11

Y2

C2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

L1 (HOT) L2 1
COMPRESSOR CONTACTOR 1
L1 (HOT) L2
1
COMPRESSOR CONTACTOR 2
M4664

Fig. 93. Schematic and hookup of T874D with Q674K. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

NO FAN SWITCH

FALL H1
4
6
H2 ANTICIPATOR H2
FALL
8 C1
RISE 9
10 C1 ANTICIPATOR

SYSTEM SWITCH
OFF
AUTO

11

C2

RISE

C2 ANTICIPATOR

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

B
HEAT CHANGEOVER VALVE

W1 HEAT RELAY 2
W2
RH
RC FILTER LED (YELLOW)

HEAT RELAY 1
L2 1 L1 (HOT)
L1 (HOT) L2 1

X

A SERVICE LED (RED)
Y1

COMPRESSOR CONTACTOR 2

Y2

COMPRESSOR CONTACTOR 1

COOL CHANGEOVER VALVE O "T" RELAY
T
M7013

Fig. 94. Schematic and hookup of T874D with Q674G. Used in standard applications.

121

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTATS

SUBBASE

SYSTEM COMPONENTS

1 FALL
H1 ANTICIPATOR 2
H1 3
4
FALL 5
H2 H2 ANTICIPATOR
6

NO FAN SWITCH
SYSTEM SWITCH
OFF WOOD WOOD/OIL
OIL

L1

R

(HOT)

L2 1

W2 OIL LED (RED)
X WOOD LED (GREEN)
W1

OIL RELAY WOOD RELAY

1 POWER SUPPLY. PROVIDE DISCONECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5984

Fig. 95. Schematic and hookup of T874F with Q674K. Used in wood/oil applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

FALL

1 FAN SWITCH
AUTO
ON 4

W1

NO. 1 HEAT RELAY

W2

HEAT

NO. 2

DAMPER

HEAT RELAY

B

FALL H2
C1 RISE

6
H2 ANTICIPATOR 8

9
10 C1 ANTICIPATOR
11

SYSTEM SWITCH
OFF
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ON LED (YELLOW)
SERVICE LED (RED)

L2

RH

L1

(HOT)

1

RC

O FAN RELAY COOL DAMPER
G

NO. 1 COMPRESSOR

Y2

CONTACTOR

Y1

X L2

A

L1

(HOT)

C

M104A

Fig. 96. Schematic and hookup of T874C with Q674C. Used in standard applications.

60-2485--8

122

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

1

3

H2

2

H1

ANTICIPATOR

3

4

5

RISE

6

CO H1

8 C1
RISE

9

FAN SWITCH AUTO
ON
SYSTEM SWITCH OVERRIDE
AUTO OFF

OVERRIDE LED (RED)

Y

COMPRESSOR CONTACTOR

G

C
CLOSED-DAY OPEN-NITE

FAN RELAY L2

R
SERVICE LED (RED)
B B RELAY
L

L1 (HOT) 1

X
COMPRESSURE FAILURE S
JUMPER 2

10 C1 ANTICIPATOR 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

P
W COOL CHANGEOVER VALVE

2 JUMPER HONEYWELL SUPPLIED, FIELD INSTALLED. 3 H2 MAKE OFFEST 8° F BELOW H1 MAKE.

M100A

Fig. 97. Schematic and hookup of T874P with Q674C. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

H1

FALL

4

FALL H2

6 H2 ANTICIPATOR

8 C1

RISE
RISE C2

9
10 C1 ANTICIPATOR
11

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF HEAT AUTO COOL

SERVICE LED (RED)

A

W1
HEAT RELAY 1 W2
CHANGEOVER RELAY B
RH

SYSTEM MONITOR HEAT RELAY 2
L2 L1 1 (HOT)

RC
CHANGEOVER RELAY O

L1 (HOT)
L2 1

G
Y2 COMPRESSOR CONTACTOR 2
Y1

FAN RELAY
COMPRESSOR CONTACTOR 1

C2 ANTICIPATOR

2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 T874A IS SINGLE-STAGE (NO W2 OR Y2).

M5106A

Fig. 98. Schematic and hookup of T874D with Q674E. Used in standard applications.

123

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

W1

HEAT RELAY 1

3 2

FALL

4

H1

OFF AUTO

SYSTEM SWITCH

HEAT RELAY 2 W2

5

W3

6

4

H2 ANTICIPATOR

FALL

H2

7

C1 RISE 3

8
9 C1 ANTICIPATOR
10

FAN SWITCH
AUTO
ON
2

5

THERMISTER

11

12 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE.

Y2
SERVICE LED (RED)
A

G FAN RELAY
R

MOMENTARY O CIRCUIT
COMPRESSOR RELAY
Y1

T

EXTERNAL

TEMP.

T

READOUT

L2
L1 (HOT) 1

4 H3 OFFSET 12°F FROM H2 FOR NIGHT SETBACK. 5 THERMISTOR INTERNAL TO THERMOSTAT.

M531

3 H1 AND C1 ARE DPST SWITCHES.

Fig. 99. Schematic and hookup of T874C with Q674C. Used in standard applications.

60-2485--8

124

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

3 2

FALL

4

H1

5

FALL

H3 4

H2 ANTICIPATOR

6

H2

FALL

3 C1

RISE

C2 ANTICIPATOR
7
8
9

C2 RISE

10 C2 ANTICIPATOR

OFF AUTO
FAN SWITCH
AUTO ON 2

SYSTEM SWITCH

W1

HEAT RELAY 1

SERVICE LED (RED)

W2 HEAT RELAY 3
W3

HEAT RELAY 2

Y2 COMPRESSOR CONTACTOR 2
A

G FAN RELAY
R
MOMENTARY O CIRCUIT
COMPRESSOR RELAY Y1

L2
L1 (HOT) 1

5

THERMISTER

11

12 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE.
3 H1 AND C1 ARE DPST SWITCHES.

T

EXTERNAL

TEMP.

T

READOUT

4 H3 OFFSET 12°F FROM H2 FOR NIGHT SETBACK. 5 THERMISTOR INTERNAL TO THERMOSTAT.

M532

Fig. 100. Schematic and hookup of T874W with Q674C. Used in standard applications.

THERMOSTAT

SUBBASE

2

H1/C1

H1

ANTICIPATOR

C1

FALL

3

4

5

H2 FALL

6
H2 ANTICIPATOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

AUTO ON
FAN SWITCH
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

SYSTEM COMPONENTS
COOL CHANGEOVER VALVE O
G FAN RELAY
R

W
X EM. HT. LED (RED)
B

AUX. HT. RELAY

L1 (HOT) L2
1

COMPRESSOR CONTACTOR
M3718A Y

Fig. 101. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

125

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

FALL

1 H1/C1 ANTICIPATOR
2

H1

C1

3

4

5

FALL H2

6

H2 ANTICIPATOR

7
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FIELD WIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

COMPRESSOR OVERLOAD CONTACTOR SWITCH

HIGH

INTERNAL

PRESSURE

THERMOSTAT SWITCH

M

F
V
Y
2 E EM. HT. LED (RED) X VR R

FAN RELAY

OUTDOOR THERMOSTAT

SUPPL. ELEC. HT. RELAY

EM. HT. RELAY CONTACT

TIME DELAY FAN RELAY

EM. HT. RELAY

COOL CHANGEOVER VALVE

L1 L2 (HOT)

1

L1 L2 1 (HOT)

M4726

Fig. 102. Schematic and hookup of T874J,R with Q674L. Used in heat pump applications.

60-2485--8

126

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
1 H1 ANTICIPATOR

2

H1

FALL

4

SUBBASE
FAN SWITCH
AUTO ON

SYSTEM COMPONENTS

COOL CHANGEOVER VALVE O

1 L1 (HOT)
L2

G

R

FAN RELAY

OUTDOOR THERMOSTAT

W2 HEAT RELAY 1

FALL H2

6

H2 ANTICIPATOR

RISE CO
C1 RISE

8
9 C1 ANTICIPATOR
10

SYSTEM SWITCH
SUPL. HT. HEAT OFF COOL

E
2 L SUPL. HT. LED (RED) C
Y

HEAT RELAY HEAT RELAY 2 CONTACT 1
HEAT RELAY HEAT RELAY 3 CONTACT 2 COMPRESSOR FAULT
COMPRESSOR CONTACTOR 1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS 2 N.O. SWITCH ­ INSTALLER ADDED, TO LIGHT SUPL. HT. LED

AND OVERLOAD PROTECTION AS REQUIRED.

WHEN COMPRESSOR OPERATION IS NOT NORMAL.

M4665

Fig. 103. Schematic and hookup of T874G with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

C1

FALL

2
H1/C1 ANTICIPATOR
3

4

5 H2 ANTICIPATOR

6

FALL

H2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OPTIONAL FIELD WIRE JUMPER TO CYCLE AUXILIARY HEAT RELAY H1 INSTEAD OF H2 (FASTER RESPONSE).

FAN SWITCH
AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

E EM. HT. LED (RED)
X B R W2 2 H
Y
G
O

EM. HT. RELAY

"B" RELAY AUX. HT. RELAY
COMPRESSOR CONTACTOR

L1 (HOT)
L2 1

YR

COM G

R8233B W

ELEC. HT. RELAY

O

EH

M4728

Fig. 104. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

127

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

2

H1

FALL

FAN SWITCH AUTO ON

FAN RELAY G
HEAT RELAY 2 W2
K

4

L

6 FALL
H2 ANTICIPATOR H2
8

RISE C1

C1 ANTICIPATOR 10

SYSTEM SWITCH EM. HT.
HEAT
OFF
COOL

EM. HT. LED (RED)

SYSTEM MONITOR SWITCH
C

R RHI

Y

W1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1

EM. HT. RELAY IHRI
COMPRESSOR CONTRACTOR
HEAT RELAY 1

L1 L2 (HOT)

M8384

Fig. 105. Schematic and hookup of T874C with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1

C1

2 H1/C1 ANTICIPATOR
3

4

5

6

H2

FALL

H2 ANTICIPATOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN SWITCH AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

EM. HT. LED (RED)

COOL CHANGEOVER VALVE O

FAN RELAY

G

R

L1 (HOT)

L2 1

AUX. HT. RELAY W2

X
Y EM. HT. RELAY
E

COMPRESSOR CONTACTOR
M4724

Fig. 106. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

128

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1 FALL

2
H1 ANTICIPATOR
3
4 H2 ANTICIPATOR

5 H2
FALL 8

C1 RISE

C1 ANTICIPATOR 10
C2 ANTICIPATOR

11

C2

RISE

SUBBASE
FAN SWITCH AUTO
ON

SYSTEM COMPONENTS
COOL CHANGEOVER VALVE O

FAN RELAY

G

OUTDOOR THERMSTAT

SUPPL. HT. RELAY

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

Y1 EM. HT. RELAY CONTACT

COMPRESSOR CONTACTOR 2

E
L EM. HT. LED (RED)
C

EM. HT. RELAY COMP.
FAILURE

L1

R

(HOT)

1 L2

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR 1

Fig. 107. Schematic and hookup of T874D with Q674L. Used in heat pump applications.

M4727

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 C1
FALL

H1/C1 ANTICIPATOR
2
3

4

FALL

5

H2 6
H2 ANTICIPATOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN SWITCH
AUTO ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

R

L1

(HOT)

L2 1

FAN RELAY

G

AUX. HT. RELAY
W
AUX. HT. LED (YELLOW)
B EM. HT. LED (RED)

X COOL CHANGEOVER VALVE
O

COMPRESSOR CONTACTOR

Y

M4725

Fig. 108. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

129

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT 1

SUBBASE

SYSTEM COMPONENTS AUX. HT. RELAY
W

H1 C1
FALL

2
H1/ C1 ANTICIPATOR
3

4

5 RESET HEATER

FAN SWITCH
AUTO
ON

AUX. HT. LED (GREEN)
B
EM. HT. LED (RED)
F
G
COMPRESSOR FAILURE
R

FAN RELAY
L1 (HOT) L2
1

H2 FALL
6
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM SWITCH
EM. HT. HEAT OFF
COOL

X2
OUTDOOR THERMOSTAT T

COOL CHANGEOVER VALVE

OUTDOOR THERMISTOR

O

COMPRESSOR CONTACTOR
Y

M5071
Fig. 109. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

130

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

RESET 1

H1 FALL

2 H1 ANTICIPATOR
3
4

5
H2 FALL
6 H2 ANTICIPATOR
7

C1 RISE

8
C1 ANTICIPATOR
10

FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT. HEAT OFF COOL

V
2
VR COMPRESSOR CONTACTOR

L1 (HOT) L2
1
INTERNAL THERMOSTAT

M

FAN RELAY

OVERLOAD SWITCH

HI PRESSURE SWITCH

F SERVICE

SERVICE L LED (RED)

OUTDOOR THERMOSTAT

SUPL. ELEC. HT. RELAY

S 3
Y

EM. HT. RELAY CONTACT

TIME DELAY FAN RELAY

ELEC. HT. RELAY
E
EM. HT. LED (YELLOW)
X C815A OUTDOOR THERMISTOR
A COOL CHANGEOVER VALVE
R

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 REMOVE FACTORY INSTALLED V-VR JUMPER WHEN CONNECTING A TWO TRANSFORMER SYSTEM.

3 REMOVE FACTORY-INSTALLED S-Y JUMPER TO DISABLE SERVICE LIGHT.

Fig. 110. Schematic and hookup of T87C,R with Q674L. Used in heat pump applications.

M2854

131

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1

C1

FALL

1 RESET HEATER
2 H1/ C1 ANTICIPATOR
3
4
5

SUBBASE
FAN SWITCH AUTO ON

SYSTEM COMPONENTS

V 2
VR

1
L1 (HOT)
L2

COMPRESSOR CONTACTOR

INTERNAL THERMOSTAT

M

OVERLOAD SWITCH

HIGH PRESSURE SWITCH

F

FAN RELAY

SERVICE

L SERVICE
LED (RED)

OUTDOOR THERMOSTAT

EM. HT. RELAY

6
7 H2 FALL
H2 ANTICIPATOR

SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

Y
E EM. HT. LED (YELLOW)
X
A
R

EM. HT. RELAY

EM. HT. RELAY

SUPPL. ELEC. HT. RELAY

C815A OUTDOOR THERMISTOR
COOL CHANGEOVER VALVE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 REMOVE FACTORY INSTALLED V-VR JUMPER WHEN CONNECTING A TWO TRANSFORMER SYSTEM.

M2851

Fig. 111. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

132

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1

C1

2
H1/C1 ANTICIPATOR
3 4

5 H2 ANTICIPATOR
6

H2

FALL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN SWITCH
AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

O
G
R COMPRESSOR FAILURE
L1

COOL CHANGEOVER VALVE
FAN RELAY
L1 (HOT) L2 1

EM. HT. LED (RED)
X
AUX. HT. LED (GREEN) AUX. HT. RELAY
W2 COMPRESSOR CONTACTOR
Y EM. HT. RELAY
E M8383

Fig. 112. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

133

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1/C1 ANTICIPATOR
1

2

H1

C1

3

FALL

4

H2

FALL

5

H2 ANTICIPATOR

6

7

FAN SWITCH
AUTO ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
HEAT EM. HT. RELAY CONTRACTOR 3

L1 (HOT)
L2 1

EM. HT. RELAY

W3

OUTDOOR THERMOSTAT

HEAT CONTRACTOR 2

DEFROST RELAY

HEAT

HIGH LIMIT

W2

CONTRACTOR 1 SWITCH

B CHECK LED (GREEN)
L X2
X1 EM. HT. LED (RED)
E
G
Y LOW AMBIENT CUTOFF
O

DEFROST RELAY

REVERSING VALVE

OPTIONAL COMP. FAILURE DEVICE

EM. HT. RELAY FAN RELAY

COMPRESSOR CONTACTOR

HIGH PRESSURE SWITCH

COOL CHANGEOVER VALVE

M4720

Fig. 113. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

134

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

RESET HEATER

1
H1 ANTICIPATOR
2

3

H1
FALL 4

5
H2 FALL
6 H2 ANTICIPATOR
7

RISE C1

8
C1 ANTICIPATOR
10

RISE C2

C2 ANTICIPATOR

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN SWITCH AUTO
ON

M2 OUTDOOR THERMOSTAT
M
FAN RELAY
F

HIGH SPEED COMPRESSOR CONTACTOR
LOW SPEED COMPRESSOR CONTACTOR

V
R 2
L

L1 (HOT) L2
1
COOL CHANGEOVER SERVICE VALVE

SYSTEM SWITCH EM. HT.
HEAT
OFF
COOL

X EM. HT. LED (YELLOW)
E OUTDOOR THERMOSTAT
VR
SERVICE LED (RED)
Y
EM. HT. RELAY
C815A OUTDOOR THERMISTOR A

EM. HT. RELAY
SUPPL. ELEC. HT. RELAY
SUPPL. ELEC. HT. RELAY

2 REMOVE FACTORY INSTALLED V-VR JUMPER WHEN CONNECTING A TWO TRANSFORMER SYSTEM.

M2853

Fig. 114. Schematic and hookup of T874D with Q674L. Used in heat pump applications.

135

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

SUBBASE

SYSTEM COMPONENTS (HOT) L1 L2 1
R ODT 1

H1 C1
3

4
H2 ANTICIPATOR
5

H2

6

FALL

FAN SWITCH AUTO
ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

W3

W2

AUX. HT. LED (GREEN)

2

X

EM. HT. LED (RED)

L

G O

E

Y

B 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 AUXILIARY HEAT LED AVAILABLE ON SOME MODELS.

RTD 1

EHR 1 ODT 2 EHR 2

RTD 2
RTD 3 RTD 1

SYSTEM MONITOR RD

FAN RELAY

COOL CHANGEOVER VALVE

EM. HT. RELAY

LACO

CHP

COMPRESSOR CONTACTOR

M5072A

Fig. 115. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

136

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

C1

FALL

2 H1/C1 ANTICIPATOR
3
4

5 H2 ANTICIPATOR
6

FAN SWITCH
AUTO ON
SYSTEM SWITCH

E
X EM. HT. LED (RED)
B
R
W2 2 H

EM. HT. RELAY
AUX. HT. RELAY COMPRESSOR CONTACTOR

H2 FALL
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OPTIONAL FIELD WIRE JUMPER TO CYCLE AUXILIARY HEAT RELAY WITH H1 INSTEAD OF H2 (FASTER RESPONSE).

EM. HT. HEAT OFF COOL

A COMP. FAULT LED (YELLOW)
Y G
O

L1 (HOT) L2
1

YR COM
G R8233B

W

ELEC.

HT. RELAY

O

EH

M2857

Fig. 116. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

137

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2
FALL H1 H1 ANTICIPATOR 3 4

FAN SWITCH
AUTO
ON

R
ENTHALPY CONTROL RELAY B
HEAT RELAY CONTACT 1 G
ECONOMIZER RELAY

DEFROST RELAY

L1 (HOT)
L2 1

DEFROST SWITCH

MOTOR 3
OUTDOOR FAN RELAY 1

H2 ANTICIPATOR 5
FALL H2 6
8 C1 RISE

ENTHALPY CONTROL
2
ENTHALPY CONTROL RELAY 2

DEFROST SWITCH RELAY

TM1

TM2

LOW AMBIENT THERMOSTAT 1

OUTDOOR FAN RELAY 2
1ST STAGE LOW PRESSURE LIMIT

OUTDOOR FAN RELAY 3

1ST STAGE

Y1 ENTHALPY

SHORT CYCLE CONTROL

MOTOR 1

CONTROL RELAY 1

TIME DELAY HEATER

C1 ANTICIPATOR 10

TIME DELAY

Y2

2ND STAGE

SHORT

CYCLE 2ND STAGE LOW CONTROL PRESSURE LIMIT

MOTOR 2

C2 ANTICIPATOR
11
C2 RISE

SYSTEM SWITCH
EM. HT.
HEAT OFF
COOL

W
LED (GREEN)
X

L SERVICE LED (RED)

SERVICE

DEFROST RELAY
OUTDOOR THERMOSTAT
DEFROST RELAY

HEAT RELAY 1

O
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COOL CHANGEOVER VALVE
M7755

2 OPTIONAL ECONOMIZER HOOKUP (DOTTED LINES).

Fig. 117. Schematic and hookup of T874D with Q674L. Used in heat pump applications.

60-2485--8

138

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1
FALL 2
H2
FALL H1 ANTICIPATOR H2 ANTICIPATOR 3 4 H3 ANTICIPATOR
5
FALL H3 6
8
C1 RISE
9
C1 ANTICIPATOR
C2 ANTICIPATOR
10
C2 RISE

FAN SWITCH AUTO ON
SYSTEM SWITCH EM. HT. HEAT
OFF COOL

11
RESET HEATER 12
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OPTIONAL ECONOMIZER HOOKUP (DOTTED LINES).

R ECONOMIZER RELAY
B HEAT RELAY CONTACT 1
G
ENTHALPY CONTROL
2

DEFROST RELAY

L1 (HOT)
L2 1

ECONOMIZER RELAY
DEFROST SWITCH

MOTOR 3
OUTDOOR FAN RELAY 1
DEFROST RELAY

DEFROST SWITCH RELAY

TM1

TM2

OUTDOOR THERMOSTAT 1

ECONOMIZER RELAY 2

OUTDOOR FAN RELAY 2
1ST STAGE LOW PRESSURE LIMIT

OUTDOOR FAN RELAY 3

1ST STAGE

Y1 ECONOMISER

SHORT CYCLE CONTROL

MOTOR 1

RELAY 1

TIME DELAY

HEATER

TIME DELAY RELAY

Y2

2ND STAGE

DEFROST RELAY

2ND STAGE LOW PRESSURE LIMIT

SHORT CYCLE CONTROL

MOTOR 2

W AUX. HEAT LED (GREEN)
O

DEFROST RELAY CONTACT

AUXILIARY HEAT RELAY

DEFROST RELAY CONTACT

COOL CHANGEOVER VALVE

X EM. HEAT LED (RED)
E
A

C815 OUTDOOR THERMISTOR

EMERGENCY HEAT RELAY
M7756

Fig. 118. Schematic and hookup of T874W with Q674L. Used in heat pump applications.

139

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
RESET HEATER
1

SUBBASE

SYSTEM COMPONENTS
L1 L2 (HOT) 1 C815A OUTDOOR THERMISTOR T

H2 ANTICIPATOR 2
3

FAN SWITCH AUTO
ON

W2 AUX. HT. RELAY
G FAN RELAY
R

H1 C1
FALL

4
5
C1 ANTICIPATOR
6

11

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

X
SERVICE LED (YELLOW)
Z

SERVICE

EM. HT. LED (RED)

EM. HT. RELAY

K COMPRESSOR CONTACTOR

Y

H2

12

W1

FALL

H1 ANTICIPATOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

HEAT CHANGEOVER RELAY

M5955

Fig. 119. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

2

FALL H1/C1

H1

C1

ANTICIPATOR

3

4 5

FAN SWITCH
AUTO ON

FALL H2

6 H2
ANTICIPATOR

SYSTEM SWITCH EM. HT.
HEAT
OFF

EM. HT. LED (RED)

COOL
11 RESET HEATER
12 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS
L1 L2 (HOT)

FAN RELAY 1 G
R AUX. HT. RELAY
W

H "H" RELAY
B

X
EM. HT. RELAY T

C815A1039 THERMISTOR O
CHANGEOVER VALVE (COOL)

Y
COMPRESSOR CONTACTOR

M3173B

Fig. 120. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

140

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
2 H1 ANTICIPATOR
3
H1 FALL
4 5 H2 ANTICIPATOR
6

SUBBASE
FAN SWITCH
AUTO ON

SYSTEM COMPONENTS

R COMPRESSOR FAILURE
ODT1

L1 (HOT)
L2 1

EHR1

RTD2

L EM. HT. LED (RED)

RTD1

X

ODT2 EHR2

RTD3

H2 FALL
8 C1 ANTICIPATOR
10
C1 RISE

SYSTEM SWITCH EM. HT.
HEAT
OFF
COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

AUX. HT. LED (GRN)
W2 RD
G
O
E
LACO Y

RTD1

FAN RELAY

COOL CHANGEOVER VALVE

EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP

HEAT CHANGEOVER VALVE B
M7012

Fig. 121. Schematic and hookup of T874C with Q674L. Used in heat pump applications.

141

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2 FALL

H1 C1

H1/C1 ANTICIPATOR

3

FAN SWITCH
AUTO
ON

FAN RELAY G

L2 1

R

L1

(HOT)

W2 AUX. HT. RELAY

4

FALL H2

5
H2 ANTICIPATOR
6

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM SWITCH EM. HT.
HEAT
OFF
COOL

K
L EM. HT. LED (YELLOW)
C
SERVICE LED (RED)
Y
W1 Z SERVICE

EM. HT. RELAY CO
COMPRESSOR CONTACTOR
CHANGEOVER VALVE
M8379

Fig. 122. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

142

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

C1

FALL

2 H1/C1 ANTICIAPTOR
3
4

5

H2 FALL

H2 ANTICIPATOR
6

FAN SWITCH
AUTO
ON

8
10
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 CONNECT CHANGEOVER RELAY TO B FOR HEAT CHANGEOVER, TO O FOR COOL CHANGEOVER.

SYSTEM SWITCH EM. HT.
HEAT
OFF COOL

RTD 1

ODT 1 EHR 1 ODT 2

RTD 2

L1

L2

(HOT)

1

EHR 2

RTD 3

R
L
EM. HT. LED (RED)
X AUX. HT. LED (GREEN)
W2

COMPRESSOR MONITOR
RTD 1

G
O E
LACO Y
B

RD

FAN RELAY

2 COOL CHANGEOVER VALVE
EM. HT. RELAY

CHP

COMPRESSOR

2

CONTACTOR

HEAT CHANGEOVER VALVE
M1030A

Fig. 123. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

143

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
L1 L2 (HOT)

1

FALL H1
FALL

2
3 H1 ANTICIPATOR
4 H2 ANTICIPATOR
5

FAN SWITCH
AUTO
ON

R
Y G
2 W2
EM. HT. OR SUPL. HT. LED (RED)

COMPRESSOR CONTACTOR
FAN RELAY HEAT RELAY 1 OUTDOOR THERMOSTAT

H2 6

RISE CO

8
9 C1 ANTICIPATOR
10

RISE

C1

CO

11

12

SYSTEM SWITCH EM. HT. OR SUPL. HT.
HEAT
OFF
COOL

L

HEAT RELAY HEAT RELAY 2

2

CONTACT 1

C

HEAT RELAY CONTACT 2 HEAT RELAY 3

E

X

"P" RELAY

"X" RELAY

P

O COOL CHANGEOVER VALVE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ON MODELS INCLUDING EXTERNAL JUMPER, W2=W1 AND L=F.

M8003

Fig. 124. Schematic and hookup of T874J with Q674L. Used in heat pump applications.

60-2485--8

144

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

2

H1/C1 ANTICIPATOR
3

H1 FALL
FALL

C1

4
H2 ANTICIPATOR

H2

6

FAN SWITCH
AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SYSTEM COMPONENTS

R

L
EM. HT. LED (RED)
3
W3

AUX. HT. RELAY

2 X AUX. HT. LED (GRN)
W2

AUX. HT. RELAY

FAN RELAY G

L1 (HOT) L2
1

COOL CHANGEOVER VALVE O
E

EM. HT. RELAY
Y COMPRESSOR CONTACTOR
B "B" RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TERMINAL LABELED C/X ON SOME MODELS.
3 W3 TERMINAL AVAILABLE ON SOME MODELS ONLY.

M3683A

Fig. 125. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

145

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
1 H1 ANTICIPATOR

2

H1

FALL

4

FALL

6

H2

H2 ANTICIPATOR

8

CO C1 ANTICIPATOR

RISE

9

10

C1

RISE

SUBBASE
FAN SWITCH
AUTO ON
SYSTEM SWITCH SUPL. HT.
HEAT COOL

SYSTEM COMPONENTS
COOL CHANGEOVER VALVE O

L1 (HOT)
L2 1

FAN RELAY G
R OUTDOOR THERMOSTAT
W2 HEAT RELAY 1

E 2
L SUPL. HT. LED (RED)
C

HEAT RELAY HEAT RELAY 2 CONTACT 1
HEAT RELAY HEAT RELAY 3 CONTACT 2

Y 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 N.O. SWITCH INSTALLER ADDED, TO LIGHT EM. HT. LED WHEN COMPRESSOR OPERATION IS NOT NORMAL.

COMPRESSOR CONTACTOR 1

Fig. 126. Schematic and hookup of T874G with Q674P. Used in heat pump applications.

M4722

THERMOSTAT

SUBBASE

FALL H1

2 H1 ANTICIPATOR
3

FALL

4 H2 ANTICIPATOR
5

H2 6

RISE 8
C1

10
C1 ANTICIPATOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN SWITCH AUTO ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

SYSTEM COMPONENTS

R RTD1
W3

ODT1 EHR1

L1 (HOT)
L2 1

ODT2

RTD2

RTD1 W2

EHR2

RTD3

AUX.HT. LED (GREEN)

X

EM. HT. COMPRESSOR LED (RED) FAILURE

RD

L

G

FAN RELAY

O EM. HT.
COOL CHANGEOVER RELAY
VALVE E

COMPRESSOR

LACO

CONTACTOR

CHP

Y

B

M5652A

Fig. 127. Schematic and hookup of T874C with Q674L. Used in heat pump applications.

60-2485--8

146

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1/C1 ANTICIPATOR
2

H1

C1

3

FALL

4
H2 ANTICIPATOR 5

H2 6

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SUBBASE
FAN SWITCH
AUTO ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

R
A SERVICE LED (RED)
W3

SYSTEM COMPONENTS

RD RTD1

ODT1 EHR1

L1 (HOT)
L2 1

ODT2

RTD2

RTD1 W2

EHR2

RTD3

AUX. HT. LED (GREEN)

X

EM. HT.

LED

SYSTEM

(YELLOW) MONITOR

RD

L

FAN RELAY

G

O

COOL CHANGEOVER EM. HT. RELAY

VALVE

E

COMPRESSOR

LACO

CONTACTOR

CHP

Y

B M5653A

Fig. 128. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

H1 FALL

2
H1 ANTICIPATOR 3

SUBBASE
FAN AUTO SWITCH
ON

SYSTEM COMPONENTS

FAN RELAY G

L1

R

(HOT) 1

L2

4 H2 ANTICIPATOR FALL
6 H2
RISE

SYSTEM SWITCH
EM. HT.
HEAT
OFF

W EM. HT. RELAY
X
B EM. HT. LED (RED)

AUX. HT. RELAY

COOL

CO

8

COOL CHANGEOVER VALVE

RISE C1

9

O

C1

ANTICIPATOR

10

Y

COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M102A

Fig. 129. Schematic and hookup of T874G with Q674L. Used in heat pump applications.

147

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

H1

C1

FALL

H1/C1 ANTICIPATOR
3

4

5

H2 FALL

6 H2 ANTICIPATOR

11

FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

RESET 12
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FACTORY-INSTALLED JUMPER.

AUX. HT. LED (YELLOW)
CHECK LED (RED)

O COOL CHANGEOVER VALVE

G

FAN RELAY

R

L1 (HOT)

L2 1

W1

2 EM. HT. RELAY
E
X

COMPRESSOR FAILURE

C

C815A OUTDOOR THERMISTOR SYSTEM LED (GREEN)
T

COMPRESSOR CONTACTOR

Y

M1628A

Fig. 130. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

148

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
H1/C1 ANTICIPATOR 2

SUBBASE
FAN AUTO SWITCH
ON

SYSTEM COMPONENTS

L1 (HOT)

L2

R

1

3

H1

C1

FALL

RESET HEATER

4

6

H2 ANTICIPATOR

H2

FALL

SYSTEM SWITCH
SUPL. HT.
HEAT 2
COOL

W2
L C SUPL. HT. LED (RED) G
O

HCR 1
ODT FAN RELAY
COOL CHANGEOVER VALVE

E

Y 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FOR Q674L1454,

IS "OFF".

HCR 2

HCR 3

COMPRESSOR CONTACTOR

HCR 1

HCR 2

M4723

Fig. 131. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

149

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

FALL

H1

C1

H1/C1 ANTICIPATOR
3

4

H2 FALL

5
6 H2 ANTICIPATOR

FAN SWITCH AUTO
ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

11

O

COOL CHANGEOVER

VALVE

FAN RELAY

G

R

3R

L1 (HOT)
1
L2

W1
AUX. HT. LED (YELLOW) 2

E

EM. HT. LED (RED)
SYSTEM LED (GREEN)

4R
X
C C815A OUTDOOR THERMISTOR

SEQ 2

SEQ 1

EM. HT. RELAY 4R

5R

HPS

4R

12

T

RESET Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 REMOVE JUMPER FOR INDEPENDENT CONTROL OF W1 AND E TERMINALS.

COMPRESSOR CONTACTOR

4R M1858

Fig. 132. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1
H1/C1 ANTICIPATOR
2

H1

C1

FALL

3 4
5
6 H2 ANTICIPATOR H2 FALL

FAN SWITCH
AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN

G

RELAY

L1 (HOT) R L2 1

K AUX. HT.

EM. HT.

RELAY

RELAY W2

EM. HT. LED (YEL)

L
COMPRESSOR C FAILURE

Z RESET LED (RED)
W1
Y

CO

W1 RELAY

COMPRESSOR CONTACTOR

M2018

Fig. 133. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

150

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

RTD 1

ODT 1

1

H1

C1

FALL

2

EHR 1 ODT 2

RTD 2

H1/C1 ANTICIPATOR
3
4
H2 ANTICIPATOR
5

6

FALL

H2

8

10

FAN SWITCH AUTO
ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

G R
W2 AUX. HT. LED (GREEN)
E COMP. FAILURE
L EM. HT. LED (RED)
B
X
LACO Y

EHR 2

RDT 3

FAN RELAY

L1 (HOT) 1 L2

RTD 1

EM. HT. RELAY

RD
CHANGEOVER VALVE (HEAT)

COMPRESSOR CONTACTOR

CHP

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CHANGEOVER VALVE (COOL) O

M106A

Fig. 134. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

151

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
H1/C1 ANTICIPATOR
2

FAN SWITCH
AUTO
ON

SUBBASE

3

H1

C1

RESET

FALL

HEATER

4

6
H2 ANTICIPATOR H2 FALL

SYSTEM SWITCH SUPL. HT.
HEAT
OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
W2
L SUPL. HT. LED (RED)
C G
O

SYSTEM COMPONENTS
L1 (HOT) L2 1
HCR 1

ODT

HCR 1

HCR 2

FAN RELAY
COOL CHANGEOVER VALVE

E

HCR 2 Y

HCR 3

COMPRESSOR CONTACTOR

M2017

Fig. 135. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

1
C1 ANTICIPATOR
H1 ANTICIPATOR
2

H1

C1

FALL

3
4 RESET
5
6

SUBBASE
FAN SWITCH
AUTO ON

AUX. HT. LED (GRN)
EM. HT. LED (RED)

SYSTEM COMPONENTS

G

FAN RELAY W

U1

AUX. HEAT RELAY

B F COMP.
FAILURE
R T

2
L2
L1 (HOT)

H2 FALL

SYSTEM SWITCH EM. HT.
HEAT
OFF COOL

1 FIELD REMOVABLE JUMPER
2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

X2 O.D. STAT

C815A OUTDOOR THERMISTOR

COOL CHANGEOVER
VALVE O

COMPRESSOR CONTACTOR
Y

M2012

Fig. 136. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

152

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

RTD 1

ODT 1

1

H1

C1

FALL

2

EHR 1 ODT 2

RTD 2

H1/C1 ANTICIPATOR
3
4 H2 ANTICIPATOR
5

FAN SWITCH
AUTO ON

FALL

H2

6
SYSTEM SWITCH
EM. HT. HEAT

W3
G R

W2
AUX. HT. LED (GREEN)
E

EM. HT. LED (RED)

COMP. FAILURE
L
CHECK LED (RED)
B

EHR 2

RDT 3

FAN RELAY

L1 (HOT) 1 L2

RTD 1

EM. HT. RELAY

RD

CHANGEOVER VALVE (HEAT)

OFF COOL

X
LACO Y

COMPRESSOR CONTACTOR

CHP

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CHANGEOVER VALVE (COOL) O

Fig. 137. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

M105A

153

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL

1 2
H1 ANTICIPATOR

3

FAN SWITCH
AUTO ON

J R1 NO2
S SOLIENOID RELAY
G
R 2

S1 RELAY S1 NC
FAN RELAY
L1 (HOT) L2
1

FALL

4 H2 ANTICIPATOR

5 H2
7 RISE
8 C1
9 C1 ANTICIPATOR
10

SYSTEM SWITCH HEAT
OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FIELD REMOVABLE JUMPER

C H2
R1 NC1 H1
R2 NO1
O

AUX. HT. RELAY
COMPRESSOR CONTACTOR
REVERSING VALVE
R1 RELAY M103A

Fig. 138. Schematic and hookup of T874L with Q674B. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1
H1 ANTICIPATOR
2 FALL H1
4

H2 ANTICIPATOR

6

H2

FALL

8

RISE

C1

C1 ANTICIPATOR

10 C2 ANTICIPATOR

AUTO FAN ON SWITCH
SYSTEM SWITCH AUX. HT. HEAT PUMP 2 STG. HEAT
OFF COOL

11

C2

RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

FAN RELAY G

R

L1

(HOT)

L2

B

1

W1

HEAT PUMP LED (GREEN)

COMPRESSOR RELAY
AUX. HT. RELAY

W2

AUX. HT LED (RED)
C
O

COOL CHANGEOVER VALVE

Y1

COMPRESSOR CONTACTOR 1 Y2

COMPRESSOR CONTACTOR 2

M4730

Fig. 139. Schematic and hookup of T874D with Q674F. Used in heat pump applications.

60-2485--8

154

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

1 FALL
H1 ANTICIPATOR H1
2

FALL

H2 H2 ANTICIPATOR 3

FALL

H3 ANTICIPATOR 4
H3 5

SUBBASE
FAN SWITCH AUTO ON

SYSTEM COMPONENTS
L1 (HOT) L2
1 T

C815A OD THERMISTOR W3

AUX. HT.

U

LED

(GREEN)

G

AUX. HT. RELAY

EM. HT.

R

LED (RED)

FAN RELAY

6 RESET

RISE 8
C1 9

C1 ANTICIPATOR 10

RISE

C2 ANTICIPATOR 11

C2

12

SYSTEM SWITCH
EM.HT.
HEAT
OFF COOL

E
L CHECK LED (RED)
X

COMPRESSOR MONITOR

EM. HT. RELAY

B 2
O Y1 Y2

HEAT CHANGEOVER RELAY
COOL CHANGEOVER RELAY
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 CONNECT CHANGEOVER RELAY TO 'O' TERMINAL FOR CHANGEOVER IN COOLING OR TO 'B' TERMINAL FOR CHANGEOVER IN HEATING.
Fig. 140. Schematic and hookup of T874W with Q674L. Used in heat pump applications.

M156A

155

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL 1

H1

H1

ANTICIPATOR

4

FALL

6

H2 H2
ANTICIPATOR

C1
C2 RISE

RISE
8
9
C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

R HEAT RELAY 1
W1 FAN RELAY
G

W2 EM. HT. LED (RED)
X2
E

HEAT RELAY 2 EM. HT. RELAY

COMPRESSOR CONTACTOR 2
Y2 COMPRESSOR CONTACTOR 1
Y1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M8376

Fig. 141. Schematic and hookup of T874C with Q674F. Used in standard applications.

L1 (HOT)
L2 1

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
1 H1 ANTICIPATOR
4

FAN SWITCH
AUTO
ON

L1

R

(HOT)

L2 1

W1 HEAT RELAY 1

H2 ANTICIPATOR

W2

6 FALL H2

SYSTEM SWITCH

B
X2 CHECK LED (RED) X1

HEAT RELAY 2

RISE
C1 8
9 C1 ANTICIPATOR
10

OFF EM. HT.
HEAT AUTO COOL

E EM. HT. RELAY
G FAN RELAY
Y2 COMPRESSOR CONTACTOR 2

C2

Y1

ANTICIPATOR

11

COMPRESSOR

CONTACTOR 1

O

RISE C2

1 POWER SUPPLY. PROVIDE DISCONECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5985

Fig. 142. Schematic and hookup of T874C,D with Q674F. Used in standard applications.

60-2485--8

156

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

1 H1 ANTICIPATOR
2

4 FALL

6 H2
H2 ANTICIPATOR

RISE

8

CO
C1 RISE

9 C1 ANTICIPATOR
10

Y1
FAN SWITCH
AUTO G
ON R

SYSTEM SWITCH

OFF

AUTO

W1

C AUX. HT. LED (RED)
O
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR
FAN RELAY
L1 (HOT) L2
1
AUX. HT. RELAY
COOL CHANGEOVER VALVE
M8378

Fig. 143. Schematic and hookup of T874G with Q674B. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
L1 L2 (HOT)

FALL
H1 2
3

H1 ANTICIPATOR 4
H2 ANTICIPATOR
5 H2 FALL
6

RISE CO

8
9 C1 ANTICIPATOR
10

RISE

C1

CO

11

FAN SWITCH AUTO
ON
SYSTEM SWITCH SUPL. HT.
ON OFF

R Y G W2
SUPP. HT. LED (RED)
L C E
X P
O

1 COMPRESSOR CONTACTOR
FAN RELAY
HEAT RELAY 1 OUTDOOR THERMOSTAT
HEAT RELAY HEAT RELAY 2 CONTACT 1

HEAT RELAY HEAT RELAY 3 CONTACT 2

"P" RELAY

"X" RELAY

COOL CHANGEOVER VALVE

12

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5956

Fig. 144. Schematic and hookup of T874J with Q674J. Used in heat pump applications.

157

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS (HOT) L1 L2

H1

FALL

H1 ANTICIPATOR
1
2
4

FAN SWITCH
AUTO ON

1

V

DEFROST RELAY

SUP. ELEC. HT. RELAY

Y OUTDOOR

THERMOSTAT

TIME DELAY

EM. HT. RELAY FAN RELAY

FALL

H2

ANTICIPATOR

6

H2 FALL
CO

8 9 C1 ANTICIPATOR

SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

10

RISE C1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN RELAY F
E EM. HT. LED (RED)

EM. HT. RELAY

COOL CHANGEOVER
VALVE R

COMPRESSOR CONTACTOR
M

INTERNAL THERMOSTAT

OVERLOAD

HIGH PRESSURE SWITCH
M8375

Fig. 145. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1 FALL

H1 ANTICIPATOR
H2 FALL

3
4 H2 ANTICIPATOR
6

FAN SWITCH
AUTO
ON

W1 EHR
LPCO Y1
RVR RVR
G
R ODT 3

C1 RISE
RISE C2

8
SYSTEM SWITCH
OFF

W2 EHT

ODT 2

9 C1 ANTICIPATOR
10
C2 ANTICIPATOR
11

SUPL. HT.

HEAT AUTO COOL

E
X SUPL. HEAT C LED (RED)

SUPL. HT. RELAY
DFR 2

Y2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

EHR

REVERSING RELAY

DFR 2

COMPRESSOR CONTACTOR 1

FAN RELAY

HEAT RELAY 2

L1 (HOT) L2
1

HEAT RELAY 1 HEAT RELAY 3

COMPRESSOR CONTACTOR 2
M7010

Fig. 146. Schematic and hookup of T874D with Q674F. Used in heat pump applications.

60-2485--8

158

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL
FALL H2

2 H1 ANTICIPATOR
3
4
5 H2 ANTICIPATOR
6

8 CO

RISE

9

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF COOL AUTO HEAT EM. HT.

RISE C1

C1 ANTICIPATOR
10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 CONNECT TO Y OR W TERMINAL WITH FACTORY INSTALLED JUMPER.

A MODE SIGNAL
1 3
2

SERVICE LED (RED)
AUX. HT. LED (GRN)
EM. HT. LED (YEL)

G FAN RELAY
R
S2

L1 (HOT) L2
1

W3 HEAT RELAY 1
W2

HEAT RELAY 2

X

COOL

L

CHANGEOVER

VALVE

O COMPRESSOR
CONTACTOR

Y

EM. HT. RELAY

E

T MODE SIGNAL

3 JUMPER FACTORY INSTALLED.

M7024

Fig. 147. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

2

H1

FALL

4

FAN SWITCH
AUTO
ON

COOL CHANGEOVER VALVE O

DEFROST BLOWER SPEED

RELAY

RELAY

BLOWER RELAY G

L1

R

(HOT)

L2 1

FALL H2

CO

RISE

C1

RISE

6
H2 ANTICIPATOR 8

SYSTEM SWITCH
OFF
EM. HT.

EM. HT.

W2

LED

(RED)

DEFROST RELAY AUX. HT. RELAY
EM. HT. RELAY

HEAT

E

9

AUTO

C

C1 ANTICIPATOR
10

COOL

LOCKOUT THERMOSTAT
Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COOL CONTRACTOR
M8382

Fig. 148. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

159

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
FALL 1
H1 H1 ANTICIPATOR

4 FALL

H2

H2

6

ANTICIPATOR

RISE

8

C1

RISE
3 C2

9 C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

FAN SWITCH AUTO
ON
SYSTEM SWITCH

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OPTIONAL FIELD WIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.
3 FOR Q674F1048, DELETE C2 STAGE.

OFF EM. HT.
HEAT AUTO COOL

SUBBASE

W1 Y1
G W2
EMR2

SYSTEM COMPONENTS

EMR4

2R

1R

4R2 EMR4

2R2 5R
3R

THERMAL SWITCHES FOR HEATING ELEMENTS HTR 1

HTR 2

HTR 3 EMR3

EM. HT. LED

RC 2
X1

OUTDOOR THERMOSTAT

3R1 Z

EMR1 EMR1
RH

EM. HT. RELAY

E

L1

(HOT) L2

1 L1 L2

(HOT)

1

M8380

Fig. 149. Schematic and hookup of T874C with Q674F. Used in heat pump applications.

60-2485--8

160

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
H1 ANTICIPATOR 1

SUBBASE R

SYSTEM COMPONENTS COOL CHANGEOVER VALVE

FALL 2
H1
3
FALL 5
H2 H2 ANTICIPATOR

FAN SWITCH AUTO
ON

COMPRESSOR CONTACTOR
M

INTERNAL THERMOSTAT

OVERLOAD SWITCH
FAN RELAY F

HI PRESSURE SWITCH

OUTDOOR THERMOSTAT
Y

SUPL. ELEC. HT. RELAY

EM. HT. RELAY CONTACT

TIME DELAY FAN RELAY

6 RISE
8 C1

RISE CO

9
C1 ANTICIPATOR

SYSTEM SWITCH
OFF EM. HT.
HEAT COOL AUTO

E EM. HEAT LED (RED)
X SYSTEM MONITOR
VR

TIME DELAY FAN RELAY
1 L1 HOT L2

10
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2
V
2 REMOVE FACTORY INSTALLED V-VR JUMPER WHEN CONNECTING A TWO TRANSFORMER SYSTEM.

L2 1
L1 HOT
M2852A

Fig. 150. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

161

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
H1 ANTICIPATOR
1

SUBBASE

SYSTEM COMPONENTS

L1 L2 (HOT)

R

1

EM. HT. RELAY CONTACT 1

2 FALL H1
4
6 H2 ANTICIPATOR
FALL H2
8 CO
RISE 9

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

W2 EM. HT. LED (RED)
E 2
X H
Y
G
O

C1 ANTICIPATOR

10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

C1

RISE

PROTECTION AS REQUIRED.

2 OPTIONAL FIELD WIRE JUMPER TO CYCLE W2 WITH H1 IN EM. HT. (FASTER RESPONSE).

T6031 REFRIGERATON/ TEMPERATURE CONTROLLER
EM. HT.
EM. HT. RELAY

R8233B

Y

R

G

W

COM
EM. HT.

O FAN

C

DF RS

COMPRESSOR CONTACTOR
SEQUENTIAL RELAY

1

L1

L2

(HOT)

REVERSING SOLENOID

FAN M4710

Fig. 151. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

162

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

1 FALL H1 H1 ANTICIPATOR
4

FALL

H2 ANTICIPATOR

6

H2

RISE C1
RISE C2

8
9 10 C1 ANTICIPATOR
11 C2 ANTICIPATOR

SUBBASE
FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

SYSTEM COMPONENTS
1 L1 L2 (HOT)
HEAT RELAY
W1 COMPRESSOR CONTRACTOR 1
Y1 FAN RELAY
G

RC

3

HEAT RELAY 2

W2

RH EM. HT. RELAY
E

EM. HEAT LED (RED)

B 2
X2

X1

O

COMPRESSOR CONTRACTOR 2

Y2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY SUPPLIED FIELD INSTALLED JUMPER TO E-X2 FOR CONSTANT POWER TO EM HT LIGHT IN EM HT POSITION. 3 OPTIONAL FIELDWARE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

1
L1 L2 (HOT) M8377

Fig. 152. Schematic and hookup of T874D with Q674F. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

FALL

1 H1 ANTICIPATOR
2
4

AUTO
ON
FAN SWITCH

COOL CHANGEOVER VALVE O
FAN RELAY
G L1 (HOT) L2 1

R

OUTDOOR

THERMOSTAT

FALL C1 CO

H2 RISE RISE 1

6 H2 ANTICIPATOR
8

SYSTEM SWITCH
OFF
EM. HT.
HEAT

W2 AUX. HT. RELAY

E

AUX. HT. RELAY CONTACT

EM. HT. RELAY

9
C1 ANTICIPATOR 10

AUTO COOL

EM. HT. LED (RED)
X
Y

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR

M8381

Fig. 153. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

163

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

1 H1 ANTICIPATOR
2
H1 4

H2 ANTICIPATOR 6
H2 FALL
8

CO RISE

9 H1 ANTICIPATOR
10

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

R W2
E EM. HT. LED (RED)
X 2 H
A COMP. FAULT LED (YELLOW)
Y G
O

C1 RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OPTIONAL FIELD WIRE JUMPER TO CYCLE W2 WITH H1 IN EM. HEAT(FASTER RESPONSE).

1
L1 L2 (HOT)

EM. HT. RELAY CONTACT 1

T6031 REFRIGERATION TEMPERATURE CONTROLLER

EM. HT.

EM. HT. RELAY
COMPRESSOR CONTACTOR

YR

COM

G

R8233B

SEQUENTIAL RELAY

W

EH

O FAN
C DF RS

L1 L2 (HOT)

FAN

REVERSING SOLENOID

M2858

Fig. 154. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

164

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1 ANTICIPATOR 2
3

H1

FALL

4

H2

ANTICIPATOR

H2

5

FALL

6

8

9

RISE CHANGEOVER

C1 ANTICIPATOR
10

RISE

C1

SUBBASE
FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF COOL AUTO HEAT EM. HT.

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 W3 TERMINAL ON SELECT MODELS.

SYSTEM COMPONENTS

R RTD1
2 W3 W2

OTD1 EHR1 ODT2 EHR2

L1 (HOT) L2 1 RTD2
RTD3

AUX. HT. LED (GRN)
X

EM. HT.

L

LED (RED)

G

O E Y

RTD1

SYSTEM MONITOR

FAN RELAY

RD LACO

COOL CHANGEOVER VALVE
EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP

M1589

Fig. 155. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

165

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

ANTICIPATOR

FALL

1

H1 2

FAN SWITCH
ON
ON

L1 L2 (HOT) 1 COOL CHANGEOVER VALVE
O
FAN RELAY G
R

4 FALL

H2 H2 ANTICIPATOR

6

RISE

8

CO 9

RISE

C1 ANTICIPATOR 10

SYSTEM SWITCH
OFF
EM. HT. HEAT
AUTO
COOL

OUTDOOR THERMOSTAT
E

AUX. HT. RELAY CONTACT

EM. HT. RELAY

EM. HT. LED (RED)

L1
COMPRESSOR FAILURE

X EM. HT. LED (GREEN)
W2

AUX. HT. RELAY

COMPRESSOR CONTACTOR C1
Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5720

Fig. 156. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
FALL H2 CO
RISE
C1 RISE

2 H1 ANTICIPATOR
3
4 H2 ANTICIPATOR
6
8
9 C1 ANTICIPATOR
10

FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

COOL CHANGEOVER VALVE
Y1

FAN RELAY G

R

CHECK LED (GREEN)
X

DEFROST RELAY

W2 E EM. HT. LED (RED) C1
W1

LOCKOUT RELAY
HI PRESSURE SWITCH

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

1 L1 (HOT) L2
TIME DELAY RELAY 2
TIME DELAY RELAY 1
COMPRESSOR CONTACTOR
M2860

Fig. 157. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

166

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
L1 (HOT) L2 1

1 H1 ANTICIPATOR

O COOL CHANGEOVER VALVE

H1 FALL

2

FAN

SWITCH

AUTO

ON

E EM. HT. RELAY

G

2

FAN RELAY

4

B

H2

FALL

6 H2 ANTICIPATOR

8 CO RISE
C1 ANTICIPATOR 9
C1 RISE 10

SYSTEM SWITCH
OFF
EM. HT. HEAT
AUTO
COOL

R

HEAT CHANGEOVER VALVE

W2 AUX. HT. RELAY

L1
EM. HT. LED (RED)

COMPRESSOR FAILURE

AUX. HT. LED (GREEN)

X
Y COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 B TERMINAL ON SELECT MODELS.

M5721

Fig. 158. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

167

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

H1 FALL

FAN SWITCH

AUTO

2

OFF

4

FALL H2

6
H2 ANTICIPATOR 8

SYSTEM SWITCH

COOL CHANGEOVER VALVE
O L1 L2 (HOT) 1
FAN RELAY
G
HEAT RELAY CONTACT

R
W
OUTDOOR THERMOSTAT
E

AUX. HT. RELAY
HEAT RELAY EM. HT. CONTACT RELAY

RISE CO
RISE C1

9
C1 ANTICIPATOR 10

EM.HT. AUTO
OFF

EM. HT. LED (RED)
X
Y

LIMIT

COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5722

Fig. 159. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
FALL H2

2
H1 ANTICIPATOR 3 4
H2 ANTICIPATOR 5

FAN SWITCH
AUTO
ON

O COOL CHANGEOVER VALVE

G FAN RELAY
R

L1 (HOT)
L2 1

W AUX. HT. RELAY

RISE CO
RISE C1

6

8
9 C1 ANTICIPATOR
10

SYSTEM SWITCH
EM. HT. AUTO OFF

X
EM. HT. LED (RED)
B
Y

EM. HT. RELAY
COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M5723

Fig. 160. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

60-2485--8

168

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR
2 H1 FALL
4

FAN SWITCH
AUTO
ON

COOL CHANGEOVER VALVE O

1
L1 (HOT) L2

G

R

FAN RELAY

OUTDOOR THERMOSTAT
W2
EM. HT. RELAY 1

FALL RISE

H2

6

H2 ANTICIPATOR

8 CO

RISE

C1 ANTICIPATOR

9

C1

10

SYSTEM SWITCH
SUPL. HT. ON OFF

E 2
L SUPL. HT. LED (RED)
C
Y

EM. HT. RELAY EM. HT. RELAY 2 CONTACT 1

EM. HT. RELAY EM.HT.

CONTACT 2

RELAY 3

COMPRESSOR CONTACTOR 1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS 2 N.O. SWITCH -- INSTALLER ADDED, TO LIGHT EM. HT. LED

AND OVERLOAD PROTECTION AS REQUIRED.

WHEN COMPRESSOR OPERATION IS NOT NORMAL.

M5724

Fig. 161. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

169

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THEROMSTAT

1 FALL
H1 2
H1 ANTICIPATOR

3

FALL

4

H2

5

RESET HEATER 6

RISE

8

CO

9

SUBBASE
FAN SWITCH AUTO
ON

SYSTEM SWITCH EM. HT.
AUTO OFF

AUX. HT. LED (GREEN)
EM. HT. LED (RED)

SYSTEM COMPONENTS
C815A OUTDOOR THERMISTOR T

FAN RELAY
G COOL CHANGEOVER VALVE
O

R
OUTDOOR THERMOSTAT X2
W

1 L1 (HOT) L2
AUX. HT. RELAY

B EM. HT. RELAY
F

RISE C1

C1

10

ANTICIPATOR

1

Y
COMPRESSOR CONTACTOR POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5725

Fig. 162. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

60-2485--8

170

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR
1

H1

FALL

4

H2
ANTICIPATOR 6

FALL

1 H2

CO FALL

C1 RISE

8
9
10 C1 ANTICIPATOR

FAN SWITCH AUTO
ON
SYSTEM SWITCH
AUTO OFF RESET
1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 H2 HAS 10¡F FIXED SETBACK FROM H1 ON T874G1485, 0-12¡F ADJUSTABLE ON T874G1535.
3 RESET IN MOMENTARY POSITION, SPRING RETURN TO OFF UPON SWITCH RELEASE.

L2
L1 (HOT)
1

HEAT DAMPER B
HEAT RELAY 1 W1
FAN RELAY G

HEAT RELAY 2 W2
R

S1

RESET CIRCUIT

COOL CHANAGEOVER VALVE

O

S2

RESET CIRCUIT

Y SERVICE LED (RED)
X ON LED (YELLOW)
A
C

COMPRESSOR RELAY
M1820C

Fig. 163. Schematic and hookup of T874G with Q674C. Used in standard applications.

171

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1 ANTICIPATOR

2

O

FALL H1
RISE CO
RISE C1

3

Y

FAN SWITCH

AUTO

4

ON

G

6

R

8
9 C1 ANTICIPATOR

SYSTEM SWITCH OFF AUTO

2
L MALFUNCTION LED (RED)
B

10

X

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 R-L JUMPER SUPPLIED BY HONEYWELL.

L1 (HOT) L2
COOL CHANGEOVER VALVE
COMPRESSOR CONTACTOR
FAN RELAY
HEAT CHANGEOVER VALVE
MALFUNCTION SWITCH
M5726

Fig. 164. Schematic and hookup of T874H with Q674C. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1
FALL H1
3 2
H1 ANTICIPATOR 3
4 H2 ANTICIPATOR

FAN SWITCH
AUTO
ON

L1
(HOT) 1 L2

J

R1 N.O.2

S1 RELAY

S

2

SOLENOID RELAY

S1 N.C.

G

R

FAN RELAY

5

H2

FALL

7

8

3
C1 RISE

9
C1 ANTICIPATOR
10

SYSTEM SWITCH
OFF
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FIELD REMOVABLE JUMPER. 3 H1 AND C1 ARE DPST SWITCHES.

C

H2

AUX. HT. RELAY R1 N.C.1

COMPRESSOR CONTACTOR

H1

R2 N.O. 1

REV. VALVE

R1 RELAY O
M5727

Fig. 165. Schematic and hookup of T874L with Q674C. Used in heat pump applications.

60-2485--8

172

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1 1
H1 ANTICIPATOR

4

FALL

6

H2

H2 ANTICIPATOR
8 RISE C1
9

10 C1 ANTICIPATOR

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

W1

AUX. HT. LED (GREEN)

EM. HT. LED

X

(RED)

W2

RH

L1 (HOT) L2 1
HEAT RELAY 1
HEAT RELAY 2

L
SYSTEM MONITOR E

EM. HT. RELAY

G
FAN RELAY RC
COMRESSOR CONTACTOR 1
Y1

C2 ANTICIPATOR

11

Y2

RISE C2
1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMRESSOR CONTACTOR 2
L2 1
L1 (HOT) M5728

Fig. 166. Schematic and hookup of T874D with Q674F. Used in standard applications.

173

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1 ANTICIPATOR 2

H1 3

FAN SWITCH

R RTD 1

ODT 1

(HOT) L1 L2 1

EHR 1

RTD 2

ODT 2

4
H2 ANTICIPATOR

AUTO ON

EHR 2

H2 FALL
FALL

5

SYSTEM SWITCH

OFF

7

EM. HT.

HEAT

W2

AUX. HT. LED (GREEN)

X

EM. HT. LED (RED)

COMPRESSOR FAILURE

RD

L

G

CHANGEOVER 8
9

AUTO COOL

B HEAT CHANGEOVER VALVE
E

10 C1 ANTICIPATOR

LACO Y

EHT1

C1 RISE

COMPRESSOR CONTACTOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

RTD 3 RTD 1
FAN RELAY EM. HT. RELAY
CHP M1592A

Fig. 167. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

174

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR
1
C ANTICIPATOR 2

FAN SWITCH
AUTO ON

H1

C

FALL

3

4

5

H2

ANTICIPATOR

H2

6

FALL

SYSTEM SWITCH
EM. HT. HEAT OFF COOL

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 REMOVE JUMPER WHEN W1 RELAY IS USED. 3 FACTORY-INSTALLED JUMPER.

W3 W3 RELAY

O

COOL CHANGEOVER

VALVE

L

COMPRESSOR

MONITOR

FAN RELAY

G

EM. HT. LED (RED)
AUX. HT. LED (GRN)

R

W2 AUX. HT. RELAY

E EM. HT. RELAY

X

3 HEAT

X2

CHANGEOVER VALVE

B

W1 RELAY W1

2

COMPRESSOR RELAY

Y

L1 (HOT) L2
1
M5067

Fig. 168. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

175

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

1 H1 ANTICIPATOR
2

H1

4
6 H2 ANTICIPATOR
H2 FALL

RISE 8

C1

9

C1 ANTICIPATOR 10
11 RISE CO
12

SUBBASE

SYSTEM COMPONENTS

FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

O
COOL CHANGEOVER VALVE G

B 3
W3
R

FAN RELAY B RELAY
AUX HT. RELAY

E
EM. HT. RELAY L
EM. HT. LED (RED)
2 X AUX. HT. LED (GREEN)
AUX. HT. RELAY
W2

L1 (HOT)
L2 1

Y
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TERMINAL LABELED C/X ON SOME MODELS. 3 W3 TERMINAL ON SOME MODELS ONLY.

COMPRESSOR CONTACTOR
M5986A

Fig. 169. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

176

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL

2 H1 ANTICIPATOR
3
4 5

FAN SWITCH
AUTO ON

6
H2 ANTICIPATOR

H2 FALL
CO

8 9 C1 ANTICIPATOR

SYSTEM SWITCH
OFF
EM. HT. 3
HEAT
AUTO
COOL

RISE 10
RISE
C1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 ON SOME MODELS, Y TERMINAL MAY BE LABELED Y1. 3 EMERGENCY HEAT RUNS CONTINUOUSLY WHEN SWITCH IN IN EM. HT. POSITION.

W3
W3 RELAY W1

W1 RELAY

B RELAY B
G

FAN RELAY

R
W2 AUX. HT. LED (GREEN)

AUX. HT. RELAY

X

EM. HT. LED (RED)

L

COMPRESSOR FAULT

E COOL CHANGEOVER VALVE

EM. HT. RELAY

O COMPRESSOR

2

CONTACTOR

Y

M5987A

Fig. 170. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

L1 (HOT)
L2 1

177

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

R 2

FALL

H1

3

FAN SWITCH

Y

H1 ANTICIPATOR

AUTO

G

4

ON

H2 ANTICIPATOR

5
FALL H2
6

W1 EM. HT. LED (RED)
F

CO RISE

8 9
C1 ANTICIPATOR 10

SYSTEM SWITCH EM. HT.
AUTO

C 2
E
X

OFF

P 11

C1

RISE

CO

O

12

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 EXTERNAL JUMPER SUPPLIED BY HONEYWELL.

L1

(HOT)

L2

1

O.D.T.

COMPRESSOR CONTACTOR

FAN RELAY

HCR1

HCR1

HCR2

HCR2

HCR3

"X" RELAY "P" RELAY

COOL CHANGEOVER VALVE

M5729

Fig. 171. Schematic and hookup of T874J with Q674J. Used in heat pump applications.

FALL

THERMOSTAT
2 H1 ANTICIPATOR
3 4

H1
RISE CO

8 C1 ANTICIPATOR
9
10
11

SUBBASE FAN SWITCH AUTO
ON
SYSTEM SWITCH HEAT
OFF COOL

G R

O

FAULT

LED

2

(RED)

C

CHECK

FILTER

3

LED (YELLOW)

SYSTEM COMPONENTS
FAN RELAY
COOL CHANGEOVER VALVE
L1 (HOT) L2
1

C1 RISE

12

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR

Fig. 172. Schematic and hookup of T874H with Q674B. Used in heat pump applications.

M1401

60-2485--8

178

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

FALL

THERMOSTAT
2 H1 ANTICIPATOR
3 4

H1
RISE CO

8 C1 ANTICIPATOR
9
10
11

SUBBASE FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF AUTO

G R

O

FAULT

LED

2

(RED)

C

CHECK

FILTER

3

LED (YELLOW)

SYSTEM COMPONENTS
FAN RELAY
COOL CHANGEOVER VALVE
L1 (HOT) L2
1

C1 RISE

12

Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR

Fig. 173. Schematic and hookup of T874H with Q674C. Used in heat pump applications.

M1400

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 HA
2

3

H1

FALL

4 H2 ODA
5
FALL

6

FAN SWITCH
AUTO
ON

C1

8

RISE 9

CA 10
C2

SYSTEM SWITCH
EM. HT.
AUTO
OFF

RISE 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2 REMOVABLE JUMPER.

FAN RELAY G
EM.. HT. RELAY X2

T C815A OUTDOOR THERMISTOR
R
"F" RELAY
F

1
L1 (HOT) L2

W

EM. HT.

LED (RED)

2

AUX. HT. RELAY

U AUX. HT. LED (GREEN)
B
O

COOL CHANGEOVER VALVE

COMPRESSOR CONTACTOR

Y M1403

Fig. 174. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

179

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

2 FALL

FALL

4
H2 ANTICIPATOR
6

FAN

ON

SWITCH

AUTO

O COOL
FAN RELAY CHANGEOVER VALVE

G

L1

R

(HOT)

L2 1

O.D.T.

H.C.R. 1

W2

H.C.R. 1 H.C.R.2

8

C1 ANTICIPATOR

9

RISE

CO

10

SYSTEM SWITCH SUPL. HT.
ON
OFF

RISE

HEAT PUMP

C1

(GRN)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

AUTO (YEL)

E
L MANUAL (RED)
C

Y DEFROST (RED)
D

H.C.R. 2 H.C.R.3
COMPRESSOR CONTACTOR
M2112A

Fig. 175. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

2 H1 ANTICIPATOR

H1

Y1 COOL CHANGEOVER VALVE

3

Y2

FALL SETBACK
2 RISE CO
RISE C1
1

4
6 8 9 10 C1 ANTICIPATOR

AUTO
ON FAN SWITCH
SYSTEM SWITCH
OFF AUTO

COMPRESSOR CONTACTOR
G FAN RELAY
OPEN-NIGHT CLOSED-DAY R
SETBACK RELAY L

X1 LED

3

C

LED X2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 SETBACK STAGE OFFSET 12°F (7°C) FROM H1 STAGE.

3 LEDS ON SOME MODELS.

M5730

L2 1
L1 (HOT)

Fig. 176. Schematic and hookup of T874G with Q674C. Used in standard applications.

60-2485--8

180

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1 ANTICIPATOR

1

H1 FALL
4

SUBBASE

FAN SWITCH
AUTO
ON

X RESET LED (RED)
G

SYSTEM COMPONENTS LOCKOUT (RESET) RELAY
FAN RELAY

3

H2

FALL

CO RISE

6 SYSTEM SWITCH

OFF

7

AUTO

8 9

R1
R2
2 B
2 O

HEAT CHANGEOVER VALVE
COOL CHANGEOVER VALVE

RISE

C1 ANTICIPATOR

Y

10

COMPRESSOR

CONTACTOR

C1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 USE EITHER 'B' OR 'O' ONLY FOR SYSTEM CHANGEOVER. 0.8A AT 30 VAC MAXIMUM LOAD CURRENT.

3 SECOND STAGE HEAT MAKES 12oF (7oC) AFTER FIRST STAGE HEAT TO PROVIDE SETBACK

M114C

Fig. 177. Schematic and hookup of T874G,H with Q674C. Used in standard applications.

L1 (HOT) L2
1

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL
H1 1
H1 ANTICIPATOR
3

4

FALL

6 H2 H2 ANTICIPATOR

8 C0

RISE

9
C1 ANTICIPATOR 10

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF COOL AUTO HEAT EM.HT.

W1
W2
R L SERVICE LED (RED) X EM, HT. LED (YELLOW) G
C

K 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CHANGEOVER RELAY AUX.HT. RELAY L1 (HOT) 1 L2
FAN RELAY COMPRESSOR RELAY
EM.HT. RELAY M18623

Fig. 178. Schematic and hookup of T874N with Q674F. Used in heat pump applications.

181

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1
H1 ANTICIPATOR
2

W1
DEFROST RELAY

OUTDOOR THERMOSTAT

REVERSING VALVE

EM.HT. RELAY CONTACT

HEAT RELAY 2

H1 FALL
4
H2 ANTICIPATOR
5
H2 FALL
6

FAN SWITCH AUTO ON

8

RISE C1

9 C1 ANTICIPATOR
CO 10

SYSTEM SWITCH
OFF
EM. HT.
HEAT AUTO
COOL

EM.HT. RELAY CONTACT
W3

HEAT RELAY 3

FAN RELAY G

R
W2
E EM. HT. LED (RED)
X CHECK
LED (GREEN)
L
Y

1

L1

(HOT)

L2

HEAT RELAY 1

EM. HT. RELAY

HIGH PRESSURE SWITCH

OPTIONAL COMPRESSOR FAILURE DEVICE
COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M3686

Fig. 179. Schematic and hookup of T874N with Q674F. Used in heat pump applications.

60-2485--8

182

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

R-11

FAN DELAY RELAY

L1 L2 (HOT)
1

FALL
H1
H1 ANTICIPATOR

1
FAN SWITCH
AUTO ON

W1 R-10
Y1
G R-1

R-11

CHANGEOVER VALVE

ELEC. HT. RELAY STG. 1

COMPRESSOR

R-8

CONTACTOR

R-6

OVERLOAD

FAN RELAY R-6

4

FALL H1

H2

ANTICIPATOR

6

8

C1 RISE

RISE C2

9 C1 ANTICIPATOR
10
C2 ANTICIPATOR

SYSTEM SWITCH
EM. HT. AUTO OFF

11

R-2

R

W2
E EM. HT. LED (RED)
X2
2
FILTER LED (YELLOW)

R-10 R-6

R-3 Y2

ELEC. HT. RELAY STG. 2

EM. HT. RELAY

R-5

T2

R-5
RANDOM START R-8 (OPT.)

(HEAT PUMP OPERATION) R-10
(BIOLERLESS OPERATION ) R-11

X1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FILTER LED ON SOME MODELS.

M5957

Fig. 180. Schematic and hookup of T874A,D with Q674J. Used in heat pump applications.

183

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENT

FALL 2

CO 3

H2

FALL

4

FALL 6

H1

H1

ANTICIPATOR

8

RISE

C1 9
C1 ANTICIPATOR

10

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF AUTO

TIME CLOCK

L1 L2 (HOT)
1

Y
COMPRESSOR RELAY

G
FAN RELAY R

W

W2
COMPRESSOR FAULT LED (RED)

REVERSING VALVE
COMPRESSOR FAULT

A

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M18587

Fig. 181. Schematic and hookup of T874K with Q674C. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL
H2 FALL

H1/C ANTICIPATOR H2 ANTICIPATOR
RESET

1

2 FAN SWITCH
3 AUTO

4

ON

5

6 SYSTEM SWITCH
EM. HT.

HEAT OFF

COOL

T
W2
G R
E B EM. HT. LED (YELLOW) X SERVICE LED (RED) L O Y

OUTDOOR RESET AUX. HT.
FAN

EM. HT. EM. HT. LIGHT

W89 HEAT PUMP CONTROL PANEL

SERVICE LIGHT COOL/HEAT
COMPRESSOR

M3951

Fig. 182. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

184

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

1 H1 ANTICIPATOR
2

FALL H2

4 H2 ANTICIPATOR
6

RISE CO
RISE C1

8
9 C1 ANTICIPATOR
10

FAN SWITCH
AUTO ON
SYSTEM SWITCH
EM. HT. ON
OFF

O COOL CHANGEOVER VALVE
G 2BH FAN RELAY

R O. D. S.

1BH

SH

E

L1 EM. HT. LED (RED)
X AUX. HT. LED (GREEN)
W

COMPRESSOR FAILURE
1BH

Y
COMPRESSOR CONTACTOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

1
L1 L2 (HOT)
M3950

Fig. 183. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR
1 FALL
H1

FALL H2

4
H2 ANTICIPATOR
6

RISE C1

8
9
C1 ANTICIPATOR
10 C2 ANTICIPATOR

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

HEAT RELAY 1 W1
W2 HEAT RELAY 2
RH RC
COMPRESSOR CONTACTOR 1 Y1

1
L2
L1 (HOT)
L1 (HOT) L2 1

RISE C2

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y2
COMPRESSOR CONTACTOR 2

M3953

Fig. 184. Schematic and hookup of T874A,F with Q674G. Used in standard applications.

185

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
H1 ANTICIPATOR
FALL H1

SUBBASE
1 FAN AUTO SWITCH ON

SYSTEM COMPONENTS

HEAT RELAY W1

L1 L2 (HOT)
1

G FAN RELAY
RC

FALL H2

4 H2 ANTICIPATOR
6

RISE C1
RISE C2

8
9 C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

SYSTEM SWITCH
OFF HEAT AUTO COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

W2 HEAT RELAY 2
RH
IGNITION RELAY B

COMPRESSOR CONTACTOR 1
Y1

Y2

COMPRESSOR

CONTACTOR 2

1

L1 L2 (HOT)

M3954

Fig. 185. Schematic and hookup of T874D with Q674E. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1

H1

1

ANTICIPATOR

4

FALL H2

5 H2 ANTICIPATOR
6

7

RISE C1

8
9 C1 ANTICIPATOR
10

RISE C2

11 C2 ANTICIPATOR
12

NO FAN SWITCH
SYSTEM SWITCH
OFF
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

W1 HEAT RELAY 1
RH HEAT RELAY 2
W2 FAN RELAY
B
FAN RELAY O
RC
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

1 L2 L1 (HOT)
L2 L1 (HOT) 1
M3955

Fig. 186. Schematic and hookup of T874D with Q674G. Used in standard applications.

60-2485--8

186

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
2
H1 ANTICIPATOR
3

4 H2 ANTICIPATOR
5
FALL H2

RISE

C1

8

C1 ANTICIPATOR
10

FAN SWITCH
HIGH LOW
SYSTEM SWITCH HEAT
OFF COOL

R4

HEAT RELAY 2 R3

HEAT RELAY 1 R2

HI SPEED FAN RELAY

R1 LO SPEED
C FAN RELAY

HIGH

HIGH

LR

PRESSURE TEMP.

SWITCH

SWITCH

R5

COOL

LOCKOUT

X CONTACTOR RELAY

R

1 L2
L1 (HOT)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

M3956

Fig. 187. Schematic and hookup of T874C with Q674B. Used in standard applications.

THERMOSTAT

H1 ANTICIPATOR FALL
1
H1

FALL H2

4
5 H2 ANTICIPATOR
6

7

SUBBASE
NO FAN SWITCH

SYSTEM COMPONENTS

HEAT RELAY 1

W1

1

RH HEAT RELAY 2

L2
L1 (HOT)

W2

T

RISE

8

C1

9

RISE C2

C1 ANTICIPATOR
10
11 C2 ANTICIPATOR
12

SYSTEM SWITCH
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN RELAY B
O
RC Y2
COMPRESSOR CONTACTOR 2 Y1 COMPRESSOR CONTACTOR 1

L2 L1 (HOT) 1
M3958

Fig. 188. Schematic and hookup of T874D with Q674G. Used in standard applications.

187

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1
1

4

ANTICIPATOR

FALL

5

H2 6

8 9 10 11

NO FAN SWITCH
NO SYSTEM SWITCH

W1

B

M839 MOTOR

L1

W2

Y

L2

RH

R

RC

Y2 Y1

M3960

Fig. 189. Schematic and hookup of T874F with Q674D. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 RESET

H1 ANTICIPATOR

FALL

2

H1 3

4

H2 FALL

5 H2 ANTICIPATOR
6

7

RISE C1

8 C1 ANTICIPATOR
10

FAN SWITCH AUTO
ON
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

V
2 VR

OG

IN STAT

M

COMPRESSOR CONTACTOR

F SERVICE

RELAY

FAN RELAY

L

HI PR

3

O. D. S.

EM. HT. RELAY

SERVICE LED (RED)

EM. HT.

ELEC. HT. RELAY

Y

E
EM. HT. LED (YELLOW)

ELEC. HT. RELAY

X

A
C815A OUTDOOR THERMISTOR

R 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 OPTIONAL REMOVABLE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

COOL CHANGEOVER VALVE

3 WIRE JUMPER FOR SERVICE LIGHT.

1 L1 (HOT) L2 L1 (HOT) L2
1
M3978

Fig. 190. Schematic and hookup of T874C with Q674L. Used in heat pump applications.

60-2485--8

188

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

FAN

FALL H1/C1

SWITCH

H1

C1

ANTICIPATOR

AUTO LO

3

HI

CONT.

FALL H2

4
H2 ANTICIPATOR
6

SYSTEM SWITCH

HEAT

Z "Z" RELAY
O COOL CHANGEOVER VALVE
G FAN RELAY
R AUX. HT. RELAY
W2
C
W1 HEAT RELAY

OFF

COOL

COOL RELAY
Y

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L2 L1 (HOT) 1
M3965

Fig. 191. Schematic and hookup of T874R with Q674B. Used in heat pump applications.

THERMOSTAT
H1 ANTICIPATOR FALL
1 H1

FALL H2

4 H2 ANTICIPATOR
6

RISE C1
8
9
C1 ANTICIPATOR
10
C2 ANTICIPATOR

SUBBASE

OFF AUTO

SYSTEM SWITCH

FAN SWITCH
AUTO
ON 2

SYSTEM COMPONENTS HEAT RELAY 1 W1

FILTER LED (YELLOW)
SERVICE LED (RED)

HEAT RELAY 2 W2
X A

G

R

FAN RELAY

O MOMENTARY
O CIRCUIT COMPRESSOR CONTACTOR 1
Y1

L2
L1 (HOT) 1

RISE C2

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y2
COMPRESSOR CONTACTOR 2

2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE.

M3959

Fig. 192. Schematic and hookup of T874D with Q674C. Used in standard applications.

189

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 H1 ANTICIPATOR

FALL H1

4

FALL

H2 6
H2 ANTICIPATOR

FAN SWITCH
AUTO
ON

RH
W1 HEAT RELAY 1
W2 HEAT RELAY 2
B CHANGEOVER RELAY (HEAT)

8

RISE

C1

9

10 C1 ANTICIPATOR

SYSTEM SWITCH
OFF
HEAT
AUTO
COOL

RISE

C2 ANTICIPATOR 11
C2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 JUMPER RH, RC FOR SINGLE TRANSFORMER.

O

CHANGEOVER

2

RELAY (COOL)

G

FAN RELAY

Y2
COMPRESSOR CONTACTOR 2

Y1
COMPRESSOR CONTACTOR 1 RC

Fig. 193. Schematic and hookup of T874D with Q674E. Used in standard applications.

L1 (HOT) L2 1
1 L2 L1 (HOT) M3203B

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

FALL H1

H1 ANTICIPATOR
3

4

AUTO
ON FAN SWITCH

Y1
G
R CHECK LED (GREEN)

COOL FAN RELAY CHANGEOVER VALVE
DR TDR 2

FALL H2

H2 ANTICIPATOR
6

X

HBTH

W2

RISE CO

8
9 C1 ANTICIPATOR
10

RISE C1

SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

E
C EM. HT. LED (RED)
W1

TDR 1

COMPRESSOR CONTACTOR

HPA

1
L1 L2 (HOT)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M3977

Fig. 194. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

60-2485--8

190

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1 ANTICIPATOR 1
H1
2

4

H2

H2

6

FALL

ANTICIPATOR

8 CO RISE
9

C1 ANTICIPATOR 10

FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

EM. HT. LED (RED)
AUX. HT. LED (GREEN)

RISE

C1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COOL CHANGEOVER VALVE
O
FAN RELAY
G "B" RELAY
B

R

EM. HT.

RELAY

E

L COMPRESSOR FAULT
X
W2 AUX. HT. RELAY
Y COMPRESSOR CONTACTOR

L1 (HOT) L2
1
M2974

Fig. 195. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1 ANTICIPATOR 1
H1
2

4

H2

H2

6

FALL

ANTICIPATOR

8 CO RISE
9

C1 ANTICIPATOR 10

FAN SWITCH AUTO
ON

SYSTEM SWITCH
SUPL. HT. ON
OFF

SUPL. HT. LED (RED)

RISE

C1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COOL CHANGEOVER VALVE
O
FAN RELAY
G

L1 (HOT) L2
1

R

H.C.R.1

W2 O.D.T.
E H.C.R.1 H.C.R.2

L
H.C.R.2 H.C.R.3 C

Y

COMPRESSOR CONTACTOR

M2975

Fig. 196. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

191

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

2

H1

C1

FALL

3

4

H2

FALL

5

6

11

AUTO ON FAN SWITCH
SYSTEM SWITCH EM. HT. HEAT
OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FIELD REMOVABLE JUMPER.

AUX. HT. LED (GREEN)
EM. HT. LED (RED)

G

FAN RELAY W

2 U

AUX. HEATER RELAY

B COMPRESSOR MONITOR
F
R

1
L1 (HOT) L2

T

X2
OUTDOOR THERMOSTAT O
COMPRESSOR RELAY Y

OUTDOOR THERMISTOR
COOL CHANGEOVER VALVE
M2970

Fig. 197. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

1 H1 FALL
H1 ANTICIPATOR 3

4

H2

H2

6

FALL

ANTICIPATOR

7 C1 RISE
8

9
10 C2 ANTICIPATOR

FAN SWITCH
AUTO ON
SYSTEM SWITCH
OFF HEAT AUTO COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS

STAGE 1 HEAT RELAY W1

L1 (HOT) L2
1

COMPRESSOR CONTACTOR
Y1

FAN RELAY G

R
STAGE 2 HEAT RELAY
W2

M2976

Fig. 198. Schematic and hookup of T874L with Q674E. Used in standard applications.

60-2485--8

192

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

H1 ANTICIPATOR 2
H1
3

H2 FALL

4
H2 ANTICIPATOR
5

FAN SWITCH AUTO
ON
SYSTEM SWITCH

8 CO
RISE 9
C1 ANTICIPATOR 10

OFF EM. HT.
HEAT AUTO COOL

RISE

C1

11

12
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

AUX. HT. LED (GREEN)
EM. HT. LED (RED)
CHECK LED (RED)

W3 RELAY W3
FAN RELAY G
R AUX. HT. RELAY
W2
EM. HT. RELAY E
COMPRESSOR FAULT L
X
B HEAT CHANGEOVER VALVE O
COOL CHANGEOVER RELAY Y
COMPRESSOR CONTACTOR

L1 (HOT) L2
1
M2977

Fig. 199. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 RISE

1 C1
H2 ANTICIPATOR
2

FAN SWITCH AUTO

T OUTDOOR THERMOSTAT
W2

L1 (HOT) L2
1
SEQ 2

FALL

3 4

H2

5

C1 ANTICIPATOR

6

11
H1 ANTICIPATOR 12

ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

SERVICE LED (YELLOW)
EM. HT. LED (RED)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

OUTDOOR THERMOSTAT
FAN RELAY
G

R

X SERVICE
Z

SEQ 1

K COMPRESSOR
CONTACTOR

Y HEAT CHANGEOVER
VALVE W1

M2978

Fig. 200. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

193

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 RISE

RESET
1 C1 H2
ANTICIPATOR
2

FAN SWITCH AUTO

C815A OUTDOOR THERMISTOR
T
W2

OUTDOOR THERMOSTAT

L1 (HOT) L2
1
SEQ 2

RISE

3

4

H2

5

C1 ANTICIPATOR

6

11
H1 ANTICIPATOR 12

ON
SYSTEM SWITCH EM. HEAT
HEAT OFF
COOL

SERVICE LED (YELLOW)
EM. HT. LED (RED)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN RELAY

OUTDOOR THERMOSTAT

G

R

X SERVICE
Z

K COMPRESSOR
CONTACTOR

SEQ 1

Y HEAT CHANGEOVER VALVE
W1 M2979

Fig. 201. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL
1 H1 ANTICIPATOR
4

5

H2

FALL

H2

6

ANTICIPATOR

7

C1

8

RISE

9

RISE

10 C1 ANTICIPATOR
11
C2 12
C2 ANTICIPATOR

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

SERVICE LED (RED)

A2
HEAT RELAY 1 W1 SERVICE LED (RED)

A1
HEAT RELAY 2 W2
"T" RELAY T
RC FAN RELAY B
B
RH FAN RELAY O
O
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

Fig. 202. Schematic and hookup of T874D with Q674G. Used in standard applications.

L1 (HOT) L2
1
1 L1 (HOT) L2
M2980

60-2485--8

194

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

CO FALL
2

3

FALL RISE

4 H1
6 H1 ANTICIPATOR
8 C1
9

FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF AUTO

COMP. FAULT (RED)

COMPRESSOR CONTACTOR Y
FAN RELAY
G
R HEAT CHANGEOVER VALVE
W

W2

COMPRESSOR

FAULT

A

10 C1 ANTICIPATOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L1 (HOT) L2
1
M2981

Fig. 203. Schematic and hookup of T874L with Q674C. Used in heat pump applications.

THERMOSTAT
1 H1 FALL H1 ANTICIPATOR

SUBBASE
FAN SWITCH
AUTO ON

SYSTEM COMPONENTS

HEAT RELAY 1 W1
HEAT RELAY 2 W2

L1 (HOT) L2
1

R

4

H2

H2

6

FALL

ANTICIPATOR

8 C1 RISE
9

10 C1 ANTICIPATOR

SYSTEM SWITCH
OFF
EM. HT.
HEAT
AUTO
COOL

LED (RED)

X2
B EM. HT. RELAY
E
FAN RELAY G
COMPRESSOR CONTACTOR 2 Y2
COMPRESSOR CONTACTOR 1

Y1 C2 ANTICIPATOR
11

RISE

C2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 LED IS NOT LABELED. JUMPER W2 TO X FOR AUXILIARY HEAT INDICATION. JUMPER E TO X FOR EMERGENCY HEAT INDICATION. CONNECT SYSTEM MONITOR TO X TO IDENTIFY WHEN SYSTEM NEEDS TO BE CHECKED.

M2982A

Fig. 204. Schematic and hookup of T874D with Q674F. Used in standard applications.

195

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

FALL

H1 ANTICIPATOR 2
H1
3

4 6

SUBBASE
FAN SWITCH AUTO
ON

SYSTEM COMPONENTS
COOL CHANGEOVER VALVE Y1
COMPRESSOR CONTACTOR Y2
FAN RELAY G
R

L1 (HOT) L2
1

RISE

8 CO
9 C1 ANTICIPATOR
10

SYSTEM SWITCH
OFF
AUTO

L
LED (RED)
X1

LED (RED)

C2 X2

RISE

C1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 LEDS ON SOME MODELS.

M2983

Fig. 205. Schematic and hookup of T874H with Q674C. Used in heat pump applications.

THERMOSTAT

SUBBASE

FALL

2 H1
H1 ANTICIPATOR 3

H2 FALL

4 H2 ANTICIPATOR
5
6

RISE

8 CO
9 C1 ANTICIPATOR
10

FAN SWITCH AUTO
ON
SYSTEM SWITCH SUPL. HT.
ON OFF

R Y
G W2 SUPL. HT. LED (RED)
L
C E

11 O
12

RISE C1

CO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

SYSTEM COMPONENTS

COMPRESSOR CONTACTOR

L1 (HOT) L2
1

FAN RELAY H.C.R.1

O.D.T. H.C.R.1 H.C.R.2

H.C.R.2 H.C.R.3

COOL CHANGEOVER VALVE

M2984

Fig. 206. Schematic and hookup of T874J with Q674J. Used in heat pump applications.

60-2485--8

196

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

R

H1 H1 ANTICIPATOR

FAN SWITCH

FALL

Y

3

AUTO

H2 FALL
RISE

4 H2 ANTICIPATOR
5
6
8 CO
9

ON
SYSTEM SWITCH SUPL. HT.
HEAT

G W2
SUPL. HT. LED (RED)
L
C

C1 ANTICIPATOR 10

OFF

E

COOL 11

O 12

RISE C1

CO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR
FAN RELAY
H.C.R.1

L1 (HOT) L2
1

O.D.T. H.C.R.1 H.C.R.2

H.C.R.2 H.C.R.3

COOL CHANGEOVER VALVE

M2985

Fig. 207. Schematic and hookup of T874J with Q674L. Used in heat pump applications.

THERMOSTAT
1 H1 FALL H1 ANTICIPATOR
4

SUBBASE
NO FAN SWITCH

SYSTEM COMPONENTS
HEAT RELAY 1 W1
HEAT RELAY 2 W2

L1 (HOT) L2
1

RH

5

H2

H2

6

FALL

ANTICIPATOR

8 C1 RISE
9

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2

NO SYSTEM SWITCH

2
RC
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

1
L1 (HOT) L2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 RC-RH REMOVABLE JUMPER WHEN SPECIFIED.

M2986

Fig. 208. Schematic and hookup of T874D with Q674D. Used in standard applications.

197

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

C1

R
EM. HT. LED (RED)
L

EM. HT. RELAY

RISE

H1/C1 ANTICIPATOR
2
3
4
6

FALL

H2 ANTICIPATOR H2

FAN SWITCH AUTO ON
SYSTEM SWITCH EM. HEAT
HEAT OFF
COOL

AUX. HT. LED (GREEN)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

X AUX. HT. RELAY
W2
FAN RELAY G
COOL CHANGEOVER VALVE O
EM. HT. RELAY E
COMPRESSOR CONTACTOR Y
'"B" RELAY B

L1 (HOT) L2
1
M2987

Fig. 209. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

FALL

1

H1 ANTICIPATOR

2

3

FAN SWITCH
AUTO
ON

FAN RELAY G
COOL R CHANGEOVER
VALVE O

HCO

CCO

FALL 4

H2

H2

6

FALL

ANTICIPATOR

8

C1 RISE
9

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11

SYSTEM SWITCH
OFF
HEAT
AUTO
COOL

FILTER B LED (YELLOW)
F

HEAT CHANGEOVER VALVE

RESET LED (RED)

L
COMPRESSOR CONTACTOR 1 Y1

COMPRESSOR CONTACTOR 2
Y2

RISE

C2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L1 (HOT) L2
1
M2988

Fig. 210. Schematic and hookup of T874Y with Q674E. Used in heat pump applications.

60-2485--8

198

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

FALL

H1 ANTICIPATOR 2
H1
3

4

H2

H2

6

FALL

ANTICIPATOR

8

RISE C1

C1 ANTICIPATOR
10

FAN SWITCH AUTO
ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

AUX. HT. LED (GREEN)
EM. HT. LED (RED)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS

W1 RELAY W1
FAN RELAY G
R AUX. HT. RELAY
W2

L1 (HOT) L2
1

X
L COMPRESSOR FAULT
Y1 COMPRESSOR CONTACTOR

M2989

Fig. 211. Schematic and hookup of T874G with Q674F. Used in standard applications.

THERMOSTAT

1 H1 FALL
H1 ANTICIPATOR

4

H2

H2

6

FALL

ANTICIPATOR

8 C1 RISE
9

RISE

10 C1 ANTICIPATOR
C2 ANTICIPATOR 11
C2

SUBBASE

SYSTEM COMPONENTS

FAN SWITCH
AUTO
ON

HEAT RELAY 1 W1
HEAT RELAY 2 W2
RH

L1 (HOT) L2
1

SYSTEM SWITCH
OFF HEAT AUTO COOL

2
RC FAN RELAY
G
Y2 COMPRESSOR CONTACTOR 2
Y1 COMPRESSOR CONTACTOR 1

1
L1 (HOT) L2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 RC -RH REMOVABLE JUMPER WHEN SPECIFIED.

M2990

Fig. 212. Schematic and hookup of T874A with Q674E. Used in standard applications.

199

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

FALL

2 H1
H1 ANTICIPATOR 3

4

H2 FALL

5 H2 ANTICIPATOR

SYSTEM SWITCH
OFF
AUTO

RELAY 1 N.O. 2
H1

S1 RELAY

L1 (HOT) L2
1

COMPRESSOR S1

CONTACTOR

RELAY N.C.

Y

R

RISE

7
8 CO
9
10 C1 ANTICIPATOR

FAN SWITCH
LO MED HIGH
ON

C FIELD
REMOVABLE
JUMPER H2

AUX. HT. RELAY

CHECK LED (RED)

L R1 RELAY N.C. 1

COMPRESSOR CONTACTOR

R2 RELAY N.O 1

COOL CHANGEOVER VALVE

O

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R1 RELAY
K1 RELAY
G1 K2 RELAY
G2 M2991

Fig. 213. Schematic and hookup of T874L with Q674C. Used in heat pump applications.

60-2485--8

200

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

H1

1

FALL

H1 ANTICIPATOR

2 C1 ANTICIPATOR
3

4
C1 RISE
5

11

SYSTEM SWITCH
HEAT OFF
COOL
FAN SWITCH
LO MED HIGH
ON

12
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS
L1 (HOT) L2
1

AUX. HT. RELAY H1

R R1 RELAY
O

COOL

CHANGEOVER

L

VALVE

C CHECK LED (RED)

R2 RELAY N.O. 1

COMPRESSOR CONTACTOR

COMPRESSOR CONTACTOR S1 RELAY N.C.

Y

K1 RELAY

G1 K2 RELAY

G2 M2992

Fig. 214. Schematic and hookup of T874A with Q674B. Used in standard applications.

201

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

1

FALL

2 H1
H1 ANTICIPATOR 3

4

H2 FALL

5 H2 ANTICIPATOR

RISE

7
8
C1 9
10 C1 ANTICIPATOR
11

SUBBASE
SYSTEM SWITCH
HEAT OFF
COOL
FAN SWITCH
LO MED HIGH
ON

12
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS

RELAY 1 N.O. 2
H1

S1 RELAY

L1 (HOT) L2
1

COMPRESSOR S1

CONTACTOR

RELAY N.C.

Y

R

C FIELD
REMOVABLE
JUMPER H2

AUX. HT. RELAY

CHECK LED (RED)

L COMPRESSOR
R1 RELAY N.C. 1 CONTACTOR

R2 RELAY N.O. 1

COOL CHANGEOVER VALVE

O

R1 RELAY
K1 RELAY
G1 K2 RELAY
G2 M2993

Fig. 215. Schematic and hookup of T874L with Q674B. Used in heat pump applications.

60-2485--8

202

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
COOL CHANGEOVER VALVE O

H1 FALL

1 H1 ANTICIPATOR
2

FAN SWITCH AUTO
ON

G FAN RELAY
R

L2
L1 1 (HOT)

4

3R

SEQ 2

6 FALL H2
H2 ANTICIPATOR

SYSTEM SWITCH

W1

AUX. HT.

LED

2

(YELLOW)

E

4R

SEQ 1
EM. HT. RELAY

RISE 8
CO 9

EM. HT. AUTO OFF

X
CHECK LED (RED)
C

4R 5R

SYSTEM

10

LED

(GREEN)

C1

ANTICIPATOR RISE

Y

C1

COMPRESSOR

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTACTOR

2 REMOVE JUMPER FOR INDEPENDENT CONTROL OF W1 AND E TERMINALS.

HPS 4R

4R M1629

Fig. 216. Schematic and hookup of T874G with Q674J. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

H1 FALL

2 H1 ANTICIPATOR

D. P. W1

W3
4 FAN SWITCH

AUTO

G

5

H2

ON

ANTICIPATOR

R

H2 FALL
C1 RISE CO

6
SYSTEM SWITCH
OFF 8
AUTO
9

W2 X CHECK LED (GREEN) L
Y

C1 ANTICIPATOR 10

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

HEAT CHANGEOVER VALVE

ODT EHR

HEAT CONTACTOR #2

EHR

HEAT CONTACTOR #3
1 FAN RELAY
HEAT CONTACTOR #1

L2
L1 (HOT)

OPTIONAL COMPRESSOR FAILURE

COMPRESSOR CONTACTOR
M5900

Fig. 217. Schematic and hookup of T874N with Q674C. Used in heat pump applications.

203

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

H1/C1 ANTICIPATOR
3

H1 FALL
FALL

C1

4
H2 ANTICIPATOR

H2

6

FAN SWITCH
AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

R

L
EM. HT. LED (RED)
3
W3

AUX. HT. RELAY

2 X AUX. HT. LED (GRN)
W2

AUX. HT. RELAY

FAN RELAY G

COOL CHANGEOVER VALVE O
E

L1 (HOT) L2
1

EM. HT. RELAY
Y COMPRESSOR CONTACTOR
B "B" RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TERMINAL LABELED C/X ON SOME MODELS.
3 W3 TERMINAL AVAILABLE ON SOME MODELS ONLY.

M3683A

Fig. 218. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

204

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

CONTROL MODULE

1

H1

FALL

2

H1 ANTICIPATOR

FALL
3 H2
C1

4 5 6

H2

7

ANTICIPATOR

8

SYSTEM SWITCH
OFF AUTO
FAN SWITCH AUTO
ON

W1 HEAT RELAY 1
W2 HEAT RELAY 2
W3

Y2
A SERVICE LED (RED)
G
R

FAN RELAY
L1 (HOT) L2 1

RISE

2 9

O

MONENTARY CIRCUIT

10 Y1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

COMPRESSOR CONTACTOR 1

2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE.

3 H2 OFFSET 12oF FROM H1.

M5901

Fig. 219. Schematic and hookup of T874C with Q674C. Used in standard applications.

205

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1
H1 FALL 2
H1 ANTICIPATOR

H3 H2

4
5
FALL
6 H2 ANTICIPATOR FALL
7

C1

RISE

8

9 10

RISE C2

SYSTEM SWITCH
OFF AUTO
FAN SWITCH
AUTO ON 2

SERVICE LED (RED)

CONTROL MODULE HEAT RELAY #1
W1 HEAT RELAY #2
W2 HEAT RELAY #3
W3 COMPRESSOR CONTACTOR #2
Y2 SYSTEM MONITOR
A

FAN RELAY G

L2

1

R

L1

(HOT)

MOMENTARY

O

CIRCUIT

COMPRESSOR CONTACTOR #1 Y1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 MOMENTARY POSITION. SPRING RETURN TO "ON" UPON SWITCH RELEASE.

M5929

Fig. 220. Schematic and hookup of T874W with Q674C. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL

2 H1 ANTICIPATOR
3
4

FAN SWITCH AUTO ON

RISE

CO

8

9

C1 ANTICIPATOR 10

C1

RISE

SYSTEM SWITCH
OFF AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Y1 COOL CHANGEOVER VALVE
G FAN RELAY
R COMPRESSOR CONTACTOR
Y2
B

O
X SERVICE LED (YELLOW)
X1
C
FILTER LED (RED) X2

24 VAC

1 L2 L1 (HOT)
M5902

Fig. 221. Schematic and hookup of T874H with Q674C. Used in heat pump applications.

60-2485--8

206

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 2
FALL

H1

3

4

8

C1 RISE
C2 RISE

9 C1 ANTICIPATOR
10
C2 ANTICIPATOR
11

FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF HEAT AUTO COOL

R

SYSTEM

MONITOR

1

L FAN RELAY
G

W

MALFUNCTION HEAT RELAY LED (RED)

C

LOW SPEED LED (GREEN)

HIGH SPEED LED (YELLOW)
Y1

COMPRESSOR CONTACTOR 1

COMPRESSOR CONTACTOR 2
Y2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Fig. 222. Schematic and hookup of T874B with Q674E. Used in standard applications.

L1 (HOT) L2
M5920

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

H1

H1

FALL ANTICIPATOR

3

4

H2

H2 ANTICIPATOR

FALL

5

7
RISE C1 8

C2 RISE
CO

9
C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

FAN SWITCH AUTO
ON
SYSTEM SWITCH OFF EM. HT. HEAT AUTO COOL

R

L G

W2

AUX. HT. LED (RED)

E
MALFUNCTION LED (RED)
C

LOW SPEED LED (GREEN)

HIGH SPEED LED (YELLOW)

Y1

Y2

L1 (HOT) L2 1 FAN RELAY
AUX. HT. RELAY
EM.HT. RELAY
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2

RISE 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

O COOL CHANGEOVER VALVE
M5923

Fig. 223. Schematic and hookup of T874S with Q674F. Used in heat pump applications.

207

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

1

H1

H1 ANTICIPATOR
4

H2 ANTICIPATOR

H2

6

FALL

8 C1 RISE
9
10 11

FAN SWITCH
AUTO ON
SYSTEM SWITCH OFF HEAT AUTO COOL

B W1 Y1
G RC
W2 RH SERVICE LED (RED) A
Y2

CONTROL MODULE HEAT CHANGEOVER VALVE
HEAT RELAY #1
COMPRESSOR CONTACTOR #1
FAN RELAY
L1 (HOT) L2
1 HEAT RELAY #2
L1 (HOT) L2
1 SYSTEM MONITOR
COMPRESSOR CONTACTOR #2

C2

RISE

COOL CHANGEOVER VALVE O

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5927

Fig. 224. Schematic and hookup of T874A,D with Q674E. Used in standard applications.

60-2485--8

208

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL

1

W1

H1 W2

H1

FAN

ANTICIPATOR

SWITCH

B

AUTO

4

ON

RH

H2

6

ANTICIPATOR

RC

H2

FALL

O

SYSTEM

8

SWITCH

G

C1 RISE 9

OFF

AUTO

Y2

10

11 Y1

C2

RISE

SERVICE LED (RED)
A

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CONTROL MODULE HEAT RELAY #1
HEAT RELAY #2
HEAT DAMPER
L1 (HOT) 1 L2 L2
1 L1 (HOT) COOL DAMPER
FAN RELAY
COMPRESSOR CONTACTOR #2
COMPRESSOR CONTACTOR #1
SYSTEM MONTIOR
M5928

Fig. 225. Schematic and hookup of T874D with Q674C. Used in standard applications.

209

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL
H1 1
H1 ANTICIPATOR

NO FAN SWITCH

A2 SERVICE LED (RED)
W1
SERVICE LED (RED)
A1

4

W2

5
T 6

H2

RC

H2

FALL ANTICIPATOR

SYSTEM

SWITCH

7

B

OFF

8

AUTO

RH

C1 RISE

9

O

10

Y2 11

C2

RISE

12

Y1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

CONTROL MODULE SYSTEM MONITOR
HEAT RELAY #1
SYSTEM MONITOR
HEAT RELAY #2
T RELAY
L1 (HOT) 1 L2 FAN RELAY B
L2 L1 1 (HOT) FAN RELAY O
COMPRESSOR CONTACTOR #2
COMPRESSOR CONTACTOR #1
M5930

Fig. 226. Schematic and hookup of T874G with Q674G. Used in standard applications.

60-2485--8

210

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1

CO (HEAT)

FALL

2 H1
ANTICIPATOR

FAN SWITCH
AUTO ON

W3 FAN RELAY
G

W3 RELAY

1
L1 L2 (HOT)

3

R

FALL

4

H2
5
H2 ANTICIPATOR
H1 FALL 6

CO

8

(COOL)

9

RISE

RISE

10 C1 ANTICIPATOR
C1
11

SYSTEM SWITCH OFF EM. HT. HEAT
AUTO COOL

W2
E AUX. HT. LED (GREEN) X1

EM. HT. RELAY

CHECK LED (RED)
X2
EM. HT. LED (RED)

AUX. HT. RELAY
COMPRESSOR FAULT

X COOL CHANGEOVER RELAY
O

B
W1 RELAY W1

HEAT CHANGEOVER RELAY

2
Y1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 W1 - Y1 JUMPER IS Y TERMINAL; REMOVE JUMPER WHEN W1 RELAY IS USED.

COMPRESSOR CONTACTOR

M1230B

Fig. 227. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

211

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS
L1 L2 (HOT)
1

1

H1

C1 FALL

2

H1/C1 ANTICIPATOR 3

4 H2 ANTICIPATOR
5 FALL H2
6

FAN SWITCH
AUTO
ON

EM. HT. HEAT OFF

SYSTEM SWITCH

SENSOR LED (RED)
2
AUX. HT. LED (GREEN)

R Y1
COMP. RELAY G
L

O.L.

IN. STAT.

HI. PRO.

FAN RELAY

SERVICE

O.D.S. W1
EM. HT. E
EM. HT. LED (YELLOW)

EM. HT. RELAY
ELECTRIC HEAT RELAY
ELECTRIC HEAT RELAY

C
C815A OUTDOOR THERMISTOR

COOL

T

11

RESET

O

12

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 REMOVABLE JUMPER (INSTALLED).

COOL CHANGEOVER VALVE
M3259

Fig. 228. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

60-2485--8

212

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

R

L1

(HOT) 1

L2 1

H1 ANTICIPATOR 2

H2 ANTICIPATOR 3

H1

FALL

4

5

FAN SWITCH
AUTO
ON

COMP. RELAY

O.L.

Y1

IN. STAT.

HI. PRO

G
SERVICE LED (RED) L

FAN RELAY SERVICE

H2 CO

FALL 6
RESET

RISE

8

RISE

9 C1 ANTICIPATOR
10

SYSTEM SWITCH
OFF
EM. HT.
HEAT
COOL
AUTO

AUX. HT. LED (GREEN)

2 W1

O.D.S.

EM. HT. E
EM. HT. LED (YELLOW)

C

T

EM. HT. RELAY

ELECTRIC HT. RELAY

ELECTRIC HT. RELAY

C815A OUTDOOR THERMISTOR

C1 11 O
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 REMOVABLE JUMPER (INSTALLED).

COOL CHANGEOVER VALVE

M3264

Fig. 229. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

H1 ANTICIPATOR
1
C ANTICIPATOR 2

H1

C

FALL

3

4

H2 FALL

5
H2 ANTICIPATOR
6

FAN SWITCH
AUTO ON
SYSTEM SWITCH
EM .HT. HEAT OFF COOL

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

SYSTEM COMPONENTS

W3 RELAY W3

O
L CHECK LED (RED)
G
R

COOL CHANGEOVER VALVE
COMPRESSOR MONITOR
FAN RELAY
1

L1 (HOT)
L2

EM. HT. LED (RED)
AUX. HT. LED (GREEN)

W2 AUX. HT. RELAY

E EM. HT. RELAY
X

B

HEAT

CHANGEOVER VALVE

Y
COMPRESSOR RELAY

M5068

Fig. 230. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

213

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

H1 FALL

H1 ANTICIPATOR
3

4

H2 ANTICIPATOR 5

H2

FALL

8

FAN SWITCH AUTO
ON
SYSTEM SWITCH

EM. HT. LED (RED)

O
L COMPRESSOR FAULT
G
R EM. HT. RELAY
E

COOL CHANGEOVER VALVE
FAN RELAY

1

L1

(HOT)

L2

9
C1 ANTICIPATOR
10

C1

RISE

11

12

OFF EM. HT.
HEAT AUTO COOL

X AUX. HT. LED (GREEN)
W2

AUX. HT. RELAY

2 B

HEAT CHANGEOVER VALVE

W3 RELAY W3
Y

COMPRESSOR RELAY

H1

CO

RISE

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ONLY TERMINAL B OR O TO BE USED. 0.8A MAX.

M5152

Fig. 231. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR FALL
1 H1
4

FALL H2

5 H2 ANTICIPATOR
6

7

NO FAN SWITCH

HEAT RELAY 1

W1 1

RH
HEAT RELAY 2 W2

L2
L1 (HOT)

T

RISE

8

C1

9

RISE C2

C1 ANTICIPATOR
10
11 C2 ANTICIPATOR
12

SYSTEM SWITCH
OFF
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

FAN RELAY B
O
RC Y2
COMPRESSOR CONTACTOR 2 Y1 COMPRESSOR CONTACTOR 1

L2 L1 (HOT) 1
M3957

Fig. 232. Schematic and hookup of T874D with Q674G. Used in standard applications.

60-2485--8

214

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

1 H1 ANTICIPATOR
2 H2 ANTICIPATOR
3

FALL

4

H3

5 H3 ANTICIPATOR
FALL

H2

6

RISE C1

8
9 C1 ANTICIPATOR

RISE C2

10 C2 ANTICIPATOR
11

RESET 12

AUTO ON
FAN SWITCH
SYSTEM SWITCH
EM. HT. HEAT OFF COOL

COMPRESSOR HIGH SPEED Y1 AUX. HT. W2
FAN G R

EM. HT. E

B

EM. HT. LED (YELLOW)
EM. HT. LIGHT X

SERVICE LED (RED)
L
O
Y
T

SERVICE LIGHT
COOL CHANGEOVER
COMPRESSOR LOW SPEED
OUTDOOR RESET

W89 HEAT PUMP CONTROL PANEL
M3952

Fig. 233. Schematic and hookup of T874W with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

H1 ANTICIPATOR
1
2

FALL H2
RISE CO

4 H2 ANTICIPATOR
6
8
9

RISE C1

10 C1
ANTICIPATOR

FAN SWITCH
AUTO ON
SYSTEM SWITCH
HEAT OFF
COOL

COMPRESSOR CONTACTOR Y1
FAN RELAY G
R

W1 AUX. HT. RELAY
C

AUX. HEAT LED (RED)

COOL CHANGEOVER VALVE

O

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L2 L1 (HOT) 1
M3961

Fig. 234. Schematic and hookup of T874G with Q674B. Used in heat pump applications.

215

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

H1 ANTICIPATOR 2
3

H1

FALL

4

SUBBASE
FAN SWITCH
AUTO ON

SYSTEM COMPONENTS

R RTD1

OTD1

L1 (HOT)
L2 1

EHR1

RTD2

W2 ODT2

H2 ANTICIPATOR
5

AUX. HT. LED (GRN)

EHR2

RTD3

FALL

H2

8

9

RISE CHANGEOVER

C1 ANTICIPATOR
10

RISE

C1

SYSTEM SWITCH
OFF
COOL AUTO HEAT
EM. HT.

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

EM. HT. LED (RED) X
L G
O E Y

RTD1 RD
LACO

SYSTEM MONITOR

FAN RELAY

COOL CHANGEOVER VALVE
EM. HT. RELAY

COMPRESSOR CONTACTOR

CHP M7064

Fig. 235. Schematic and hookup of T874G and Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS CONTROL MODULE

1 H1 ANTICIPATOR

H1

FALL

4

FAN SWITCH
AUTO
ON

W1
HEAT RELAY 1 W2
HEAT DAMPER

HEAT RELAY 2

B

FALL H2

6 H2 ANTICIPATOR

8 C1

RISE 9
10 RISE
11 C2

SYSTEM SWITCH
OFF
AUTO

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

RH

1

RC

1

COOL DAMPER

O

SERVICE LED (RED)

G
Y2 COMPRESSOR RELAY 2
Y1
A

FAN RELAY
COMPRESSOR RELAY 1

M7570

Fig. 236. Schematic and hookup of T874A-D with Q674C. Used in standard applications.

60-2485--8

216

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

FALL H1
FALL

2
3 H2 ANTICIPATOR
4
5 H2
6

8 C1
RISE 10

FAN SWITCH AUTO
ON
SYSTEM SWITCH
HEAT OFF COOL

R
G B LOW LED (YELLOW) W1 HI LED (GREEN) W2

C1 ANTICIPATOR Y
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

L1 (HOT) L2 1 FAN RELAY
HEAT 1
HEAT 2
COMPRESSOR CONTACTOR
M7716

Fig. 237. Schematic and hookup of T874C with Q674B. Used in standard applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

1

ANTICIPATOR

2

H1

FALL

4
6
H2 ANTICIPATOR
FALL H2

C1 RISE

8
C1 ANTICIPATOR

FAN SWITCH AUTO ON
SYSTEM SWITCH
AUX. HT. HT. PUMP 2 STAGE HT.
OFF COOL

X CHECK LED (RED)
G

FAN RELAY R
B RELAY

L1 (HOT)
L2 1

B
HEAT PUMP RELAY

W1 AUX. HT.
RELAY

W2 AUX. HT. LED (RED)
C
2
O

COOL CHANGEOVER VALVE

10 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER BETWEEN TERMINALS W1 AND Y1.

Y1
COMPRESSOR CONTACTOR

M7719

Fig. 238. Schematic and hookup of T874C with Q674F. Used in heat pump applications.

217

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 FALL C1
H2 FALL

1 H1 ANTICIPATOR
2
3 4 5 6

11 RESET

FAN SWITCH AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

AUX. HT. LED (GREEN)
EM. HT. LED (RED)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FIELD REMOVABLE JUMPER.

G FAN RELAY
W 2
U
B COMPRESSOR MONITOR
F
R OUTDOOR SENSOR
T

AUX. HT. RELAY
L1 (HOT) L2
1

X2

COOL

CHANGEOVER

OUTDOOR

VALVE

THERMOSTAT

O

COMPRESSOR CONTACTOR

Y M7744

Fig. 239. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1

1

ANTICIPATOR

4
H1 FALL

SYSTEM OFF
2 ON

8

FAN

LO

C1 RISE
9
C1 ANTICIPATOR
10

MED HI

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 FAN CONTINUOUS IN ON POSITION.

W1
HEAT RELAY

B B RELAY

L1

R

(HOT)

L2 1

G1 K1 RELAY
G2 K2 RELAY
Y1 COMPRESSOR CONTACTOR

L2

L1

K1

K1

K2

K2

K2

HI MED LO

3 SPEED FAN SCHEMATIC

M7745

Fig. 240. Schematic and hookup of T874A with Q674W. Used in standard applications.

60-2485--8

218

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

2
H1 ANTICIPATOR
3 H1

FALL

4

H2 ANTICIPATOR

5

FAN SWITCH AUTO ON

6 H2

FALL

8
C1 ANTICIPATOR
9

CO 10
RISE

11

C1 RISE

CO 12

SYSTEM SWITCH SUPL. HT.
HEAT
OFF COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
Y
G
W2 SUPL. HEAT LED (RED)
L C

SYSTEM COMPONENTS

L1 (HOT)
L2 1

COMPRESSOR CONTACTOR

FAN RELAY

HEAT CHANGEOVER VALVE NO. 1

O.D.T.

HEAT

HEAT

CHANGEOVER CHANGEOVER

VALVE NO. 1 VALVE NO. 2

E HEAT

HEAT

CHANGEOVER CHANGEOVER

VALVE NO. 2

VALVE NO. 3

X X RELAY
P

P RELAY

O

COOL CHANGEOVER

VALVE

M7742

Fig. 241. Schematic and hookup of T874J with Q674L. Used in heat pump applications.

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR

1

H1

FALL

4

6

H2 ANTICIPATOR H2

FALL

8

RISE C0

9 C1 ANTICIPATOR

FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF AUTO OVERRIDE 2

10
RISE C1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 OVERRIDE IS MOMENTARY POSITION. SPRING RETURN TO (OFF) UPON SWITCH RELEASE.

B HEAT DAMPER

W1 HEAT RELAY 1
G HEAT RELAY 2
W2
R

FAN RELAY
L1 (HOT) L2 1

S1

OVERRIDE

CIRCUIT

CHANGEOVER

VALVE

O

S2

OVERRIDE CIRCUIT

Y
SERVICE LED (RED)

COMPRESSOR RELAY

X

ON LED (YEL)

A

C

M7212

Fig. 242. Schematic and hookup of T874G with Q674C. Used in standard applications.

219

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

FALL H1

1 H1 ANTICIPATOR
2

4
6 H2 ANTICIPATOR
H2 FALL

RISE 8

C1

9

C1 ANTICIPATOR

10
11 RISE CO
12

FAN SWITCH AUTO ON
SYSTEM SWITCH
OFF EM. HT.
HEAT AUTO COOL

O COOL CHANGEOVER VALVE
G
FAN RELAY B
B RELAY

R

E
L EM. HT. LED (RED)

EM. HT. RELAY

2 X
AUX. HEAT LED (GREEN)
AUX. HEAT RELAY
W2

L1 (HOT)
L2 1

Y
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TERMINAL LABELED C/X ON SOME MODELS.

COMPRESSOR CONTACTOR
M7715

Fig. 243. Schematic and hookup of T874G with Q674F. Used in heat pump applications.

THERMOSTAT

SUBBASE

2
H1 ANTICIPATOR
3 H1

FALL

4

H2 ANTICIPATOR

5

FAN SWITCH AUTO ON

6 H2

FALL

8 C1 ANTICIPATOR
9
CO 10
RISE

11

C1 RISE

CO 12

SYSTEM SWITCH SUPL. HT.
ON OFF

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

R
Y
G
W2 SUPL. HEAT LED (RED)
L C

SYSTEM COMPONENTS

L1 (HOT)
L2 1

COMPRESSOR CONTACTOR

FAN RELAY

HEAT CHANGEOVER VALVE NO. 1

O.D.T.

HEAT

HEAT

CHANGEOVER CHANGEOVER

VALVE NO. 1 VALVE NO. 2

E

HEAT

HEAT

CHANGEOVER CHANGEOVER

VALVE NO. 2

VALVE NO. 3

X

X RELAY P

P RELAY

O

COOL CHANGEOVER

VALVE

M7743

Fig. 244. Schematic and hookup of T874J with Q674J. Used in heat pump applications.

60-2485--8

220

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2 H1/C1 ANTICIPATOR

3

H1

FALL

C1

4
6 H2 ANTICIPATOR
FALL H2

FAN SWITCH AUTO ON
SYSTEM SWITCH EM. HT.
HEAT OFF
COOL

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 TERMINAL LABELED C/X ON SOME MODELS.

O COOL CHANGEOVER VALVE
G
FAN RELAY B
B RELAY R

E
L EM. HT. LED (RED)

EM. HT. RELAY

2 X
AUX. HT. LED (GREEN)
AUX. HT. RELAY
W2

Y
COMPRESSOR CONTACTOR

Fig. 245. Schematic and hookup of T874R with Q674L. Used in heat pump applications.

L1 (HOT) L2 1
M7718

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

H1 ANTICIPATOR 1

H1

FALL

4

6

H2 ANTICIPATOR
H2 FALL 8

NO FAN SWITCH
SYSTEM SWITCH
OFF AUTO

C1

RISE

9

10

11
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

W1 HEAT RELAY 1
W2 HEAT RELAY 2
RH

L2
L1 1 (HOT)

RC
Y1 COOL CHANGEOVER
Y2 VALVE

L1 (HOT) L2 1
M7717

Fig. 246. Schematic and hookup of T874C with Q674G. Used in standard applications.

221

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

1 FALL
H1 ANTICIPATOR H1
2

FALL

H2 H2 ANTICIPATOR 3

FALL

H3 ANTICIPATOR 4
H3 5

6 RESET

RISE 8
C1 9

C1 ANTICIPATOR 10

RISE

C2 ANTICIPATOR 11

C2

12

FAN SWITCH AUTO ON
SYSTEM SWITCH
EM.HT. HEAT OFF COOL

T

C815A OUTDOOR THERMISTOR
W3

AUX. HEAT LED (GREEN)

AUX. HT. RELAY

G

R EM. HEAT LED (RED)
E
X1 CHECK LED (YELLOW)
C
B

FAN RELAY
EM. HT. RELAY
CHANGEOVER RELAY (HEAT) 2
CHANGEOVER RELAY (COOL)

O

X2 COMPRESSOR CONTACTOR 1
Y1 COMPRESSOR CONTACTOR 2
Y2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 CONNECT CHANGEOVER RELAY TO 'O' TERMINAL FOR CHANGEOVER IN COOLING OR TO 'B' TERMINAL FOR CHANGEOVER IN HEATING.

Fig. 247. Schematic and hookup of T874W with Q674L. Used in heat pump applications.

L1 (HOT) L2
1
M6999

60-2485--8

222

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT

SUBBASE

SYSTEM COMPONENTS

2

H1

H1

FALL ANTICIPATOR

3

4

H2

H2 ANTICIPATOR

FALL

5

7
RISE C1 8

C2 RISE
CO

9
C1 ANTICIPATOR
10 C2 ANTICIPATOR
11

FAN SWITCH AUTO
ON
SYSTEM SWITCH OFF EM. HT. HEAT AUTO COOL

R

L G

W2

AUX. HT. LED (RED)

E
MALFUNCTION LED (RED)
C

LOW SPEED LED (GREEN)

HIGH SPEED LED (YELLOW)

Y1

Y2

L1 (HOT) L2 1 FAN RELAY
AUX. HT. RELAY
EM.HT. RELAY
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2

RISE 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

O COOL CHANGEOVER VALVE
M5923

Fig. 248. Schematic and hookup of T874Y with Q674F. Used in heat pump applications.

223

60-2485--8

T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES

THERMOSTAT
FALL H1
1 H1 ANTICIPATOR
3

4

FALL

6 H2 H2 ANTICIPATOR

SUBBASE
FAN SWITCH
AUTO ON

W1
G
RC 2 W2
B SERVICE LED (RED)
C

SYSTEM COMPONENTS HEAT RELAY 1 FAN RELAY
HEAT RELAY 2 HEAT DAMPER

X

SYSTEM

8

SWITCH

L1
(HOT) 1 L2

RH

C1

HEAT

COOL DAMPER

RISE

9

OFF

O

RISE C2

C1 ANTICIPATOR 10
C2 ANTICIPATOR
11

COOL

COMPRESSOR CONTACTOR 1 Y1
COMPRESSOR CONTACTOR 2 Y2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FIELD WIRE JUMPER TO ALLOW SINGLE SYSTEM TRANSFORMER.

M18622

Fig. 249. Schematic and hookup of T874C with Q674B. Used in heat pump applications.

Home and Building Control
Honeywell 1985 Douglas Drive North Golden Valley, MN 55422

Home and Building Control
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9

60-2485--8 J.H. Rev. 3-01

Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.

www.honeywell.com


Acrobat Distiller 5.0.5 (Windows)