ABB PIHF Harmonic Filters User Manual

Applicable to ACS510/ACS530, ACx580-01/04, ACS880-01/04

1. Manual Introduction

This manual provides essential information for the installation, operation, and maintenance of PIHF Harmonic Filters.

2. Safety Instructions

The safety instructions necessary for the installation, operation, and maintenance of harmonic filter units are described in this chapter. Ignoring these safety instructions may result in personal injury or damage to filters, drives, motors, or other drive equipment. Please read this chapter carefully before operating the filter.

Safety of installation and maintenance

General safety instructions

Warning! All electrical installation and maintenance of harmonic filters shall be performed by qualified electrical engineers.

The harmonic filter and its connecting devices shall be grounded.

Never try any operation on the harmonic filter that has been powered on. After the power supply is cut off, the capacitor of the intermediate circuit shall be discharged for 5 minutes before operating the frequency converter, motor or motor cable. Before starting the operation, a voltage multimeter shall be used to check whether the incoming and outgoing terminals of the harmonic filter have been discharged.

Safety instructions for harmonic filters

  1. PIHF harmonic filter is matched with the frequency converter, which can only be mounted at the power inlet of the frequency converter.
  2. The power of the selected filter shall be matched with that of the frequency converter as far as possible, to obtain the best filtering effect. If not matched, the filter with the higher power can be used for that with the lower power, but the filtering effect may be reduced.
  3. A single PIHF filter can be used to power multiple frequency converters, but the total load shall not exceed the rated power value of PIHF filter.
  4. The reactor in the filter is a heat generating device. It shall be mounted to keep a heat dissipation space of at least 150mm around the filter. When two filters are mounted in parallel, the distance between the filters shall be at least 200mm.
  5. The capacitor in the filter is a temperature-sensitive device, of which the ambient temperature shall be kept below 50 °C.
  6. A reliable ground wire shall be connected for mounting according to the wiring instructions in the circuit diagram.
  7. If the harmonic filter needs to be operated, first measure whether there is any residual dangerous voltage on the incoming and outgoing terminals of the filter.

Grounding

Warning! Ignoring the following instructions may cause personal injury or death, and increase electromagnetic interference and equipment damage.

In any case, the harmonic filter, drive and its connecting equipment shall be grounded to ensure personal safety and reduce electromagnetic radiation and interference.

The size of the grounding conductor shall meet the requirements of local safety regulations.

3. Guide on Installation and Debugging of Filters

The operating principle and structure of the harmonic filter are briefly described in this chapter.

Product overview

The harmonic filter is a low-pass filter that suppresses high-frequency harmonic currents on the input side of the drive. The figure below shows a drive system with harmonic filters.

Wiring diagram of single filter (1.5-250kW)

A schematic diagram shows the wiring of a single PIHF filter connected to an ACS Drive and a motor. The input terminals are labeled -T1, U1, V1, W1. The filter has terminals labeled -F1, U1, V1, W1, U2, V2, W2, -K1, and A1, A2, B1, B2, C1, C2. The output terminals U2, V2, W2 connect to the ACS Drives, which then connect to the motor M (3~).

Wiring diagram of parallel filters (250-400kW)

A schematic diagram shows the wiring of two PIHF filters connected in parallel to an ACS Drive and a motor. The input terminals of both filters are connected to the power supply side (-T1, U1, V1, W1). The output terminals (U2, V2, W2) of both filters are connected to the incoming line side of the frequency converter. Each filter has a contactor (-K1, -K2) connected to its control terminals (A1, A2, B1, B2, C1, C2).

1. The input terminals (U1,V1,W1) of the parallel filter are all connected to the power supply side, and the output terminals (U2,V2,W2) are all connected to the incoming line side of the frequency converter.

2. The over-temperature protection terminals of the parallel filter are connected in series before connection into the frequency converter.

3. Before connecting the contactor, A1-A2, B1-B2, and C1-C2 short-connected plates (short-connected for factory default ) shall be removed, and the rated current of the contactor shall be greater than Ifilter. It is recommended to use AC-3 contactors.

4. When connecting in parallel, the contactors with disconnected capacitors on each filter shall be allocated separately, and it is not allowed to share one contactor with several filters.

5. It is recommended that the cable length between the filter and the frequency converter should not be greater than 10 meters.

Electrical diagram

The figure below shows the electrical diagram of harmonic filters. It illustrates the input terminals U1, V1, W1 connected to inductors L1 and L2, with output terminals U2, V2, W2. Terminals A1, B1, C1 are connected to A2, B2, C2 respectively, and also to a capacitor C. The diagram indicates input and output connections.

Model label

The model label for PIHF-0030-4-10 shows ABB branding, product name, technical specifications like 400VAC, 30A, 50Hz, THDI < 10%, IP00, weight 48kg, origin China. It also includes a serial number and a breakdown of the model number format: PIHF-xxxx-x-xx, indicating Harmonic content (10=10%), Rated voltage (4=400V), Rated current (0004=4A), and Product (PIHF harmonic filter).

Mechanical installation

The protection degree of PIHF harmonic filter is IP00. The filter shall be installed in a suitable housing or cabinet to ensure safety. The filter adopts natural cooling. Please keep a heat dissipation space of at least 150mm around the filter. If the filters are installed in parallel, the installation distance between the filters shall be at least 200mm. There shall be enough fresh cooling air for use, and hot air can freely escape from the filter housing or cabinet.

Electrical connection

S1...S4 Terminal Connections:

No.Terminal No.Description
1U1/V1/W1PIHF filter input terminal
2U2/V2/W2PIHF filter output terminal
3A1/B1/C1/A2/B2/C2PIHF filter loop control terminal (external contactor control)
4T1/T2Overheat protection switch terminal
5Protective earthingProtective earthing

S5...S6 Terminal Connections:

No.Terminal No.Description
1U1/V1/W1PIHF filter input terminal
2U2/V2/W2PIHF filter output terminal
3A1/B1/C1/A2/B2/C2Filter branch bypass control terminal of PIHF filter (external contactor control)
4T1/T2Overheat protection switch terminal
5Protective earthingProtective earthing

*For the use of bypassing the filter branch, after removing the short wiring of A1-A2, B1-B2, and C1-C2, the user selects the appropriate control contactor according to the Ifilter current value in the selection information.

*Overheating protection terminals T1- T2 can be connected to the frequency converter as overheating protection signals. In the normal state, it is normally closed. When the temperature limit of the overheat protection is reached, the state will turn to off.

Typical power cable specifications (copper) and wiring torque

A table lists typical power cable specifications and wiring torque for various PIHF harmonic filter models. It includes columns for Harmonic filter model, Incoming and outgoing line terminal, Capacitor switching terminal, Temperature control terminal, and PE, along with corresponding cable sizes and torque values.

Parameter setting

Under the default setting of ACS510, parameter 26.19 (enabling or disabling the DC voltage regulator) is used for disabling. The DC voltage regulator prevents voltage oscillation in the DC bus of the frequency converter due to motor load or weak grid. When the filter is matched with ACS510, set parameter 26.19 to ENABLE to reduce bus oscillation. For ACS530/ACx580/ACS880, use parameters 97.48 and 227.17.

Model information

A selection information table provides model details for PIHF harmonic filters across different drive series (ACS510, ACS530, ACx580, ACS880). It maps PIHF model numbers to specific frame sizes for each drive type.

Maximum, heat dissipation and noise level

A table details the maximum current (Imax), maximum power (Pmax), filter branch current (Ifilter), noise level, heat dissipating capacity, and CFM for various PIHF harmonic filter models. A note advises matching the filter power to the frequency converter power for optimal filtering effect.

Technical data

This chapter describes the technical specifications of the harmonic filter, including operating conditions, frame size, and parameter settings.

* In a typical motor drive system, the THDI can be reduced to less than 19% at any load ratio. Under 100% load ratio, the THDI can be controlled below 10%.

A graph shows the relationship between Load (%) on the x-axis and THDI (%) and Power Factor on the y-axes. THDI starts high and decreases as load increases, while Power Factor starts low and increases with load.

Frame size

A table lists the frame size, dimensions (H, W, D in mm), and weight (kg) for various PIHF harmonic filter models. Another table provides installation dimensions (W, W1, W2, D, H, H1, a1, a2, C1..C4, C5) for each frame size.

Product outline drawing (S1 to S4)

Schematic diagrams illustrate the physical outline and dimensions of PIHF harmonic filters for frame sizes S1 to S4, showing front, side, and top views with key dimensions labeled.

Product outline drawing (S5,S6)

Schematic diagrams illustrate the physical outline and dimensions of PIHF harmonic filters for frame sizes S5 and S6, showing front, side, and top views with key dimensions labeled.

Parallel Installation Diagram

For models requiring parallel installation, the wall-mounted mode is recommended. The installation distance between filters should be at least 200mm to ensure sufficient heat dissipation space. The diagram shows recommended clearances around the filters.

Further information

Product and service inquiries

Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to abb.com/search channels.

Product training

For information on ABB product training, navigate to new.abb.com/service/training.

Providing feedback on ABB Drives manuals

Your comments on our manuals are welcome. Navigate to new.abb.com/drives/manuals-feedback-form.

Document library on the Internet

You can find manuals and other product documents in PDF format on the Internet at abb.com/drives/documents.

Contact us

Visit www.abb.com/drives or www.abb.com/drivespartners.

ABB Beijing Drive Systems Co., Ltd.
Beijing 100015, P.R.China,
Address: Building 401, No. A-10, Jiuxianqiao Beilu, Chaoyang District, Beijing
Tel: +86 10 58217788
Fax: +86 10 58217618
24h x 365d technical hotline: +86 400 810 8885
Website: www.abb.com.cn/drives

Contact information of sales representative offices across the country:

ABB Branches in Shanghai
Shanghai, China 200023
16F, HongKong Prosperity Tower, No.763 Mengzi Road, Huangpu District
Tel: +86 21 2328 8888
Fax: +86 21 2328 8678

ABB Branches in Shenyang
Shenyang, Liaoning Province, China 110001
16F, Tower 2, City Plaza, No.206 Nanjing North Street, Heping District
Tel: +86 24 3132 6688
Fax: +86 24 31326699

ABB Branches in Urumqi
Urumqi, Xinjiang, China 830002
6B, Cnina Development Bank Tower, Zhongquan Square, No.339 Zhongshan Road
Tel: +86 991 283 4455
Fax: +86 991 281 8240

ABB Branches in Chongqing
Chongqing, China 400021
6F, Block A, Neptune Tech Building, No.62 Starlight Road, Northern New District
Tel: +86 023 6788 5732
Fax: +86 023 62805369

ABB Branches in Guangzhou
Guangzhou, China 519623
Unit 01-06A, 29F, Pearl River Tower, No.15 Zhujiang West Road, Zhujiang New Town
Tel: +86 20 3785 0688
Fax: +86 20 37850608

ABB Branches in Chengdu
Chengdu, Sichuan, China 610041
T1-8F, Raffles Plaza, No.3, Section 4, Renmin South Road
Tel: +86 28 8526 8800
Fax: +86 2885268900

ABB Branches in Xiamen
Xiamen, Fujian Province, China 361009
No. 559, Weili Road, Information and Photoelectricity Park, Huli Torch High-tech Zone
Tel: +86 592 630 3058
Fax: +86 5926303531

ABB Branches in Kunming
Kunming, Yunnan Province, China 650032
Room 2404, Master Building, No.1 Chongren Street
Tel: +86 871 6315 8188
Fax: +86 871 6315 8186

ABB Branches in Shenzhen
Shenzhen, Guangdong Province, China 518031
Rooom 1504A, AVIC Center, No.1018 Huafu Road, Futian District
Tel: +86 755 8831 3038
Fax: +86 755 8831 3033

ABB Branches in Zhengzhou
Zhengzhou, Henan Province, China 450007
1006 Room, Tower A, Yuda World Trade Center, No.220 Zhongyuane Road
Tel: +86 371 6771 3588
Fax: +86 371 6771 3873

ABB Branches in Hangzhou
Hangzhou, Zhejiang Province, China 310000
8F, Huarun Building A, No.1366 Qianjiang Road
Tel: +86 571 8763 3967
Fax: +86 571 8790 1151

ABB Branches in Guiyang
Guiyang, Guizhou, China 550022
10F, Building 5, Century JinYuan Shopping Center, No.6 Jinyang South Road, Guanshanhu District
Tel: +86 851 8221 5890
Fax: +86 851 8221 5900

ABB Branches in Xi'an
Xi'an, Shaanxi Province, China, 710075
3F, No.158, Wenjing Road, Economic and Technological Development Zone
Tel: + 86 29 8575 8288
Fax: +86 29 8575 8299

ABB Branches in Wuhan
Wuhan, Hubei Province, China 430060
21F, Wuhan Wanda Center, No.96 Linjiang Road, Wuchang District
Tel: + 86 27 8839 5888
Fax: +86 27 8839 5999

ABB Branches in Fuzhou
Fuzhou, Fujian Province, China 350028
706-709 Room, Tower A1, Cangshan Wanda Plaza,
Tel: + 86 591 8785 8224
Fax: +86 591 8781 4889

ABB Branches in Harbin
Harbin, Heilongjiang Province, China 150090
14F, Chenneng Building, No.99-9 Changjiang Road, Nangang District, Harbin
Tel: + 86 451 5556 2291
Fax: +86 451 5556 2295

ABB Branches in Lanzhou
Lanzhou, Gansu Province, China 730030
23F, Zhongguang Mansion, No.87 Zhangye Road, Chengguan District
Tel: + 86 931 818 6466
Fax: +86 931 818 6755

ABB Branches in Jinan
Jinan, Shandong Province, China 250011
Room 8601, 6F, Huaneng Building, No.17 Quancheng Road
Tel: + 86 531 8609 2726
Fax: +86 531 8609 2724

ABB Branches in Changsha
Changsha, Hunan Province, China 410005
Suite 12B01, Ping He Tang Commercial Building, No.88 Huangxing Middle Road
Tel: +86 731 8268 3005
Fax: +86 731 8444 5519

PDF preview unavailable. Download the PDF instead.

3ABD00045569 PIHF Harmonic Filters user manual EN RevD Acrobat Distiller 20.0 (Windows)

Related Documents

PreviewABB ACS880 ATEX Safe Disconnection Function Application Guide
This application guide from ABB provides comprehensive information on implementing the ATEX-certified Safe disconnection function, specifically option +Q971, for ABB's ACS880 industrial drives. It is designed for professionals involved in the installation, commissioning, use, and servicing of these systems, focusing on motor thermal protection in potentially explosive atmospheres and adhering to ATEX and UKEX directives.
PreviewManuel d'installation des Convertisseurs de Fréquence ABB ACS880-01
Ce manuel d'installation fournit des instructions détaillées pour la configuration, le montage et le raccordement des convertisseurs de fréquence industriels ABB ACS880-01. Il est destiné aux techniciens qualifiés et aux ingénieurs responsables de l'installation, de la mise en service et de la maintenance de ces équipements, couvrant les consignes de sécurité, le montage, les raccordements électriques (CEI et NEC), la mise en route et la maintenance.
PreviewABB ACS880-204 IGBT Supply Modules Hardware Manual
Comprehensive hardware manual for ABB ACS880-204 IGBT supply modules. This guide covers installation, operation, maintenance, technical specifications, and ordering information for industrial drive systems.
PreviewABB PCS100 SFC Static Frequency Converter Technical Catalogue
Technical catalogue detailing the ABB PCS100 SFC Static Frequency Converter, including system overview, sub-assemblies, control features, selection and sizing, product range, technical specifications, layout plans, power module types, input termination locations, options, and examples of systems.
PreviewABB Power Capacitors and Harmonic Filters Buyer's Guide
Comprehensive guide to ABB's power capacitors and harmonic filters, covering reactive power compensation and harmonic filtering solutions for transmission and distribution grids, as well as industrial applications. Learn about product selection, technical specifications, and service conditions.
PreviewABB ACS880-204LC IGBT Supply Modules Hardware Manual
Comprehensive hardware manual for ABB ACS880-204LC IGBT supply modules, covering installation, operation, electrical details, and technical specifications for industrial applications.
PreviewABB ACS880-01 Приводы: Руководство по монтажу и вводу в эксплуатацию
Подробное руководство по монтажу, установке и вводу в эксплуатацию промышленных приводов ABB ACS880-01. Включает информацию по технике безопасности, электрическому и механическому монтажу, а также вводу в эксплуатацию.
PreviewImplementing Safely-Limited Speed Function with ABB ACS880-01 and AC500-S
Technical guide on implementing a safely-limited speed (SLS) function using ABB's ACS880-01 industrial drive and AC500-S safety PLC, adhering to safety standards like EN/IEC 62061 and EN ISO 13849-1.