Resideo VisionPRO® TH8000 Series Touch-screen Programmable Thermostat

Installation Guide

Note: This document is for obsolete models. Current VisionPRO models start with TH8110R, TH8320R, TH8321R, or TH8321WF.

This manual covers the following models:

(Pull thermostat from wallplate and turn over to find model number)

System Types Supported:

This thermostat contains a Lithium battery which may contain Perchlorate material. Perchlorate Material–special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate.

Need Help?

For assistance with this product please visit http://customer.resideo.com or call Resideo Customer Care toll-free at 1-800-468-1502.

© 2021 Resideo Technologies, Inc. All rights reserved.

Wallplate Installation

  1. Separate wallplate from thermostat.
  2. Mount wallplate as shown below.

To remove the thermostat from the wallplate, grasp the top and bottom of the wallplate and pull to remove the thermostat.

Drilling Instructions:

  • Drill 3/16" holes for drywall.
  • Drill 7/32" holes for plaster.

Diagram Description: Shows wallplate with wire hole, mounting screws, and wall anchors.

Installation Requirements

Must be installed by a trained, experienced technician.

  • Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Safety Notices

CAUTION: ELECTRICAL HAZARD

Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE

If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.

Power Options

Diagram Description: Shows terminal layouts for Conventional and Heat Pump systems, and indicates where to insert batteries for primary or backup power. For 24VAC primary power, connect the common side of the transformer to the "C" terminal.

Wiring: Remove the factory-installed jumper only for two-transformer systems. Push excess wire back into the wall opening. Plug the wall opening with non-flammable insulation.

Terminal Designations

Shaded areas below apply only to TH8320/TH8321.

Conventional Terminal Letters:

TerminalDescription
RHeating power. Connect to secondary side of heating system transformer.
RcCooling power. Connect to secondary side of cooling system transformer.
CCommon wire from secondary side of cooling transformer (if 2 transformers).
W1st stage heat relay.
W22nd stage heat relay.
Y1st stage compressor contactor.
Y22nd stage compressor contactor.
GFan relay.
S1Optional outdoor or remote sensor.
S2Optional outdoor or remote sensor.

Heat Pump Terminal Letters:

TerminalDescription
RHeating power. Connect to secondary side of heating system transformer.
RcCooling power. Connect to secondary side of cooling system transformer.
CCommon wire from secondary side of cooling system transformer.
Y1st stage compressor contactor.
Y22nd stage compressor contactor.
Aux/EAuxiliary/Emergency heat relay.
GFan relay.
LHeat pump reset (powered continuously when System is set to Em Heat; system monitor when set to Heat, Cool or Off).
O/BChangeover valve for heat pumps.
S1Optional outdoor or remote sensor.
S2Optional outdoor or remote sensor.

Wiring Guide - Conventional Systems

Shaded areas below apply only to TH8320/TH8321.

1H/1C System (1 transformer)

TerminalConnection
RcPower [1]
R[R+Rc joined by jumper]
WHeat relay
YCompressor contactor
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

1H/1C System (2 transformers)

TerminalConnection
RcPower (cooling transformer) [1, 2]
RPower (heating transformer) [1, 2]
WHeat relay
YCompressor contactor
GFan relay
C24VAC common [3, 4]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Heat Only System

TerminalConnection
RcPower [1]
R[R+Rc joined by jumper]
WHeat relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Heat Only System (Series 20)

TerminalConnection
Rc[R+Rc joined by jumper]
RSeries 20 valve terminal "R" [1]
WSeries 20 valve terminal "B"
YSeries 20 valve terminal "W"
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Heat Only System With Fan

TerminalConnection
RcPower [1]
R[R+Rc joined by jumper]
WHeat relay
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Cool Only System

TerminalConnection
RcPower [1]
R[R+Rc joined by jumper]
YCompressor contactor
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

2H/2C System (1 transformer)

TerminalConnection
Y2Cool relay 2
W2Heat relay 2
RcPower [1]
R[R+Rc joined by jumper]
WHeat relay 1
YCool relay 1
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

2H/2C System (2 transformers)

TerminalConnection
Y2Cool relay 2
W2Heat relay 2
RcPower (cooling transformer) [1, 2]
RPower (heating transformer) [1, 2]
WHeat relay 1
YCool relay 1
GFan relay
C24VAC common [3, 4]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Notes:

  • [1] Power supply. Provide disconnect means and overload protection as required.
  • [2] Remove jumper for 2-transformer systems.
  • [3] Optional 24VAC common connection.
  • [4] Common connection must come from cooling transformer.

Wiring Guide - Heat Pump Systems

Shaded areas below apply only to TH8320/TH8321.

1H/1C Heat Pump (no auxiliary heat)

TerminalConnection
RcPower [1]
R[R+Rc joined by jumper]
O/BChangeover valve [5]
YCompressor relay
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

2H/1C Heat Pump (with auxiliary heat)

TerminalConnection
LEquipment monitor [6, 7]
Aux/EAuxiliary/Emergency heat relay (Heat 2)
RcPower [1]
R[R+Rc joined by jumper]
O/BChangeover valve [5]
YCompressor relay
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

2H/2C Heat Pump (no auxiliary heat)

TerminalConnection
Y2Compressor 2 relay
RcPower [1]
R[R+Rc joined by jumper]
O/BChangeover valve [5]
YCompressor 1 relay
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

3H/2C Heat Pump (with auxiliary heat)

TerminalConnection
Y2Compressor 2 relay
LEquipment monitor [6, 7]
Aux/EAuxiliary/Emergency heat relay (Heat 2)
RcPower [1]
R[R+Rc joined by jumper]
O/BChangeover valve [5]
YCompressor 1 relay
GFan relay
C24VAC common [3]
S1Optional outdoor/remote sensor
S2Optional outdoor/remote sensor

Notes:

  • [1] Power supply. Provide disconnect means and overload protection as required.
  • [3] Optional 24VAC common connection.
  • [5] O/B set to control as either O or B in installer setup.
  • [6] If L terminal is used, 24VAC common (terminal C) must be connected.
  • [7] Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor when set to Heat, Cool, or Off).

Mounting and Setup

Remove Tab and Mount Thermostat

Remove the tab from the thermostat. Align the pins on the back of the thermostat with the slots in the wallplate, then push gently until the thermostat snaps into place.

Diagram Description: Shows the thermostat with a tab being removed, and then being attached to the wallplate.

Set Date and Time

Use the [up-arrow] and [down-arrow] buttons to set the date (year, month, day) and time. Press DONE to save changes and exit.

Diagram Description: Shows the thermostat display with buttons for setting date and time.

Installer Setup

  1. Press the SYSTEM button.
  2. Press and hold the SYSTEM and HEAT buttons until the display changes.
  3. Change settings as required (see pages 7-9).

Diagram Description: Shows the thermostat display during the installer setup process, indicating buttons to press and settings to change.

Installer Setup Functions

Shaded areas below apply only to TH8320/TH8321.

Setup Functions and Settings:

Function CodeFunction NameSettings & Options (factory default in bold)
0120Year (first two digits)20 (2001-2099)
21 (2100-2178)
0130Year (second two digits)12 (2012)
[Other options: 00-99]
0140Month6 [Other options: 1-12]
0150Date15 [Other options: 1-31]
0160Schedule format4 7-day programming
0 Non-programmable
0170System type1 1 heat/1 cool conventional
2 1 heat/1 cool heat pump (no aux. heat)
3 Heat only (2-wire systems)
4 Heat only with fan
5 Hot water Series 20 system (power to open & close zone valves/normally open zone valves)
6 Cool only
7 2 heat/1 cool heat pump (with aux. heat)
8 2 heat/2 cool multistage conventional
9 2 heat/1 cool multistage conventional
10 1 heat/2 cool multistage conventional
11 2 heat/2 cool heat pump (no aux. heat)
12 3 heat/2 cool heat pump (with aux. heat)
0180Fan control (heating)0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)
0190Changeover valve (O/B terminal)0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0200Auxiliary heat0 Electric backup heat
1 Fossil fuel backup heat
0210External fossil fuel kit1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)
02201st stage compressor cycle rate3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
02302nd stage compressor cycle rate3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0240First stage heat cycle rate (CPH= cycles per hour)5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0250Second stage heat cycle rate (CPH)5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0260Third stage heat cycle rate (CPH)9 Electric auxiliary heat or electric furnaces
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
5 Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0280Backlight0 Backlight on for approx. 8 seconds after keypress
1 Backlight always on low intensity, full bright after keypress (requires 24VAC connection)
0300Manual/Auto changeover0 Manual changeover (Heat/Cool/Off)
1 Automatic changeover (Heat/Cool/Auto/Off)
0310Auto changeover deadband3 Heat/cool temperature 3°F apart (1.5°C) ** See page 11
[Other options: 2-9 (2°F to 9°F/1.5 °C to 5°C)]
0320Temperature display0 Fahrenheit
1 Celsius
0330Daylight savings2 Auto-change to daylight savings time (2007 and beyond, for areas that use the new 2007 DST calendar)
1 Auto-change to daylight savings time (through 2006, and for areas that do not use the new 2007 DST calendar)
0 Daylight savings time is turned off
0340Remote sensor0 No remote sensor
1 Outdoor sensor (display only)
2 Outdoor control sensor (select heat pumps) ** See page 11
3 Indoor sensor
0350Heat pump compressor lockout0 No heat pump compressor lockout
[Other options: 15, 20, 25, 30, 35, 40°F (-9.5°C to 7°C)]
0360Heat pump auxiliary lockout0 No heat pump auxiliary lockout
[Other options: 40, 45, 50, 55, 60°F (4.5°C to 15.5°C)]
0380Dehumidification control0 No dehumidification control
1 Thermostat controls dehumidification with air conditioner ** See page 11
0500Furnace filter change reminder0 Off
1 10-day run time (about 1 month)
2 30-day run time (about 3 months)
3 60-day run time (about 6 months)
4 90-day run time (about 9 months)
5 120-day run time (about 1 year)
6 365-day run time (about 3 years)
0510Humidifier pad change reminder0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days
0520UV lamp change reminder0 Off
1 365 calendar days
0530Adaptive Intelligent Recovery™1 On ** See page 11
0540Program periods0 Off
4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)
0580Compressor protection5 5 minute compressor off time ** See page 11
[Other options: 0, 1, 2, 3 or 4-minute off time]
0600Heat temperature range stop90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4.5°C to 32°C)]
0610Cool temperature range stop50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (10.5°C to 37°C)]
0640Clock format12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")
0650Extended fan timer (heat)0 Off
90 Fan runs for 90 seconds after call for heat ends
0660Extended fan timer (cool)0 Off
90 Fan runs for 90 seconds after call for cooling ends
0670Keypad lock0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fully locked
0680Heat temperature control2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Choose if room does not reach set temperature
0690Cool temperature control2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Choose if room does not reach set temperature
0700Temperature display offset0 Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]
0710RESET0 No reset
1 Reset installer options & program schedule to factory default (only date and time settings are retained)

Installer System Test

During installer setup, press the [up-arrow] repeatedly until "Test" appears.

Diagram Description: Shows the thermostat display changing from settings to a "TEST" screen.

Press the [up-arrow] or [down-arrow] to select the test, and press the [up-arrow] or [down-arrow] to change the status. Press DONE to terminate testing.

System Test Descriptions:

System TestSystem Status
1 Cooling system0 Compressor and fan turn off
1 Compressor and fan turn on
2 Second stage compressor turns on
2 Fan system0 Fan turns off
1 Fan turns on
3 Heating system0 Heat and fan turn off
1 Heat turns on (fan on if Function 0170 is set for heat pump, or if Function 0180 is set to "1") ** See page 6
2 Second stage heat turns on
3 Third stage heat turns on
4 Emergency heating system0 Heat and fan turn off
1 Heat and fan turn on

CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

Special Functions

Shaded areas below apply only to TH8320/TH8321.

  • Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees apart. If function 0380 is set to On, the heat and cool settings must be at least 5 degrees apart.
  • Remote Sensor (Setup Function 0340): If an optional outdoor sensor is installed, the thermostat can display the outside temperature. If an optional remote indoor sensor is installed, the thermostat will display the temperature at the sensor location (the internal sensor in the thermostat is not used).
  • Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
  • Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before restarting, to prevent damage. During this time, the message "Wait" flashes on the display.
  • Dehumidification control (Setup Function 0380): TH8321 models monitor the indoor humidity level and automatically activate the cooling system to reduce humidity by lowering the temperature by up to 3 degrees below the current cool setting.
  • Heat Pump Temperature Lockout (with fossil-fuel backup): If the thermostat is installed with an optional outdoor sensor, you can select a compressor lockout temperature (Function 0350). When the outdoor temperature is below the lockout temperature, only the auxiliary heat operates. When the outdoor temperature is above the lockout temperature, only the compressor operates.
  • Heat Pump Temperature Lockouts (with electric heat backup): If the thermostat is installed with an optional outdoor sensor, you can select a compressor lockout temperature (Function 0350) and/or an auxiliary heat lockout temperature (Function 0360). When the outdoor temperature is below the compressor lockout temperature, only the auxiliary heat operates. When the outdoor temperature is above the auxiliary lockout temperature, only the compressor operates. If the outdoor temperature is between the compressor and auxiliary lockout temperatures, both the compressor and auxiliary heat can operate.

Accessories & Replacement Parts

Please contact your distributor to order replacement parts.

  • Outdoor temperature sensor: Part Number C7089U1006
  • Remote indoor temperature sensor: Part Number C7189U1005
  • Cover plate*: Part Number 32003796-001

*Use to cover marks left by old thermostats.

Specifications

Temperature Ranges:

  • Heat: 40° to 90°F (4.5° to 32°C)
  • Cool: 50° to 99°F (10° to 37°C)

Operating Ambient Temperature:

  • 0° to 120°F (-18° to 48.9°C)

Shipping Temperature:

  • -30° to 150°F (-34° to 66°C)

Operating Relative Humidity:

  • 5% to 90% (non-condensing)

Physical Dimensions:

  • 4-9/16" H x 6" W x 1-3/8" D
  • 116 mm H x 152 mm W x 35 mm D

Electrical Ratings:

TerminalCurrentVoltage (50/60Hz)Running
W Heating (Powerpile)20-30 Vac0.02-1.0 A
750 mV DC100 mA DC
W2 Heating20-30 Vac0.02-0.6 A
Y Cooling20-30 Vac0.02-1.0 A
Y2 Cooling20-30 Vac0.02-0.6 A
Aux/E Aux. heat Emergency heat20-30 Vac0.02-1.0 A
O/B Changeover20-30 Vac0.02-0.6 A
L Heat pump reset20-30 Vac0.02-0.6 A

Need Help?

For assistance with this product please visit http://customer.resideo.com or call Resideo Customer Care toll-free at 1-800-468-1502.

Resideo

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502

© 2021 Resideo Technologies, Inc. All rights reserved.

Models: TH8000 Series, Touch-screen Programmable Thermostat

File Info : application/pdf, 12 Pages, 731.99KB

PDF preview unavailable. Download the PDF instead.

69-2693 Adobe PDF Library 15.0

Related Documents

PreviewT6 Pro Programmable Thermostat User Guide
Comprehensive user guide for the T6 Pro Programmable Thermostat, covering installation, operation, programming, troubleshooting, and warranty information. Learn how to set schedules, manage system modes, and optimize energy usage.
PreviewRound™ Smart Thermostat TH8732WF, RCH9300WF, RCH9310WF Professional Install Guide
A professional installation guide for the Round™ Smart Thermostat, covering models TH8732WF, RCH9300WF, and RCH9310WF. This guide details system compatibility, safety precautions, installation steps, wiring configurations, and setup procedures for trained technicians.
PreviewResideo FocusPRO S200 Smart Thermostat User Guide (TH2320WF4011) - Operation & Troubleshooting
Comprehensive user guide for the Resideo FocusPRO S200 Smart Thermostat (model TH2320WF4011). Covers thermostat controls, system and fan operation settings, time/date setup, program schedules, and troubleshooting common issues.
PreviewFocusPRO TH5000 Series Non-Programmable Digital Thermostat Installation Guide
Installation guide for the FocusPRO TH5000 Series Non-Programmable Digital Thermostat, covering models TH5110D, TH5220D, and TH5320U. Includes system types, wiring diagrams, installer setup, and specifications.
PreviewResideo FocusPRO 6000 Thermostat: Quick Start Guide
A concise guide to setting the time, day, and program schedule for the Resideo FocusPRO 6000 thermostat, including instructions for overriding the program schedule. Also includes Spanish instructions.
PreviewTH4000 Series Programmable Thermostat Operating Manual
This operating manual provides instructions for the TH4000 Series Programmable Thermostat, covering features, programming, and system settings for optimal energy savings.
PreviewResideo FocusPRO 6000 5-1-1 Day Programmable Thermostat
Discover the Resideo FocusPRO 6000, a 5-1-1 day programmable thermostat offering energy savings, a large backlit display, and RedLINK wireless capabilities for enhanced comfort and control. Learn about its features, part numbers, and upgrade options.
PreviewST9120U Universal Electronic Fan Timers Installation Guide
Detailed installation and wiring instructions for the Resideo ST9120U Universal Electronic Fan Timers, covering application, specifications, and troubleshooting for HVAC systems.