Resideo VisionPRO® TH8000 Series Touch-screen Programmable Thermostat
Installation Guide
Note: This document is for obsolete models. Current VisionPRO models start with TH8110R, TH8320R, TH8321R, or TH8321WF.
This manual covers the following models:
- TH8110U: For 1 Heat/1 Cool systems
- TH8320U: For up to 3 Heat/2 Cool systems
- TH8321U: For up to 3 Heat/2 Cool systems with dehumidification
(Pull thermostat from wallplate and turn over to find model number)
System Types Supported:
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, highefficiency furnaces, heat pumps, steam, gravity
- Heat only – two-wire systems, power to open and close zone valves (Series 20), and normally open zone valves
- Heat only with fan
- Cool only
- 750 mV heating systems
This thermostat contains a Lithium battery which may contain Perchlorate material. Perchlorate Material–special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate.
Need Help?
For assistance with this product please visit http://customer.resideo.com or call Resideo Customer Care toll-free at 1-800-468-1502.
© 2021 Resideo Technologies, Inc. All rights reserved. To remove the thermostat from the wallplate, grasp the top and bottom of the wallplate and pull to remove the thermostat. Drilling Instructions: Diagram Description: Shows wallplate with wire hole, mounting screws, and wall anchors. Must be installed by a trained, experienced technician. CAUTION: ELECTRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power before beginning installation. MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal. Diagram Description: Shows terminal layouts for Conventional and Heat Pump systems, and indicates where to insert batteries for primary or backup power. For 24VAC primary power, connect the common side of the transformer to the "C" terminal. Wiring: Remove the factory-installed jumper only for two-transformer systems. Push excess wire back into the wall opening. Plug the wall opening with non-flammable insulation. Shaded areas below apply only to TH8320/TH8321. Shaded areas below apply only to TH8320/TH8321. Notes: Shaded areas below apply only to TH8320/TH8321. Notes: Remove the tab from the thermostat. Align the pins on the back of the thermostat with the slots in the wallplate, then push gently until the thermostat snaps into place. Diagram Description: Shows the thermostat with a tab being removed, and then being attached to the wallplate. Use the [up-arrow] and [down-arrow] buttons to set the date (year, month, day) and time. Press DONE to save changes and exit. Diagram Description: Shows the thermostat display with buttons for setting date and time. Diagram Description: Shows the thermostat display during the installer setup process, indicating buttons to press and settings to change. Shaded areas below apply only to TH8320/TH8321. During installer setup, press the [up-arrow] repeatedly until "Test" appears. Diagram Description: Shows the thermostat display changing from settings to a "TEST" screen. Press the [up-arrow] or [down-arrow] to select the test, and press the [up-arrow] or [down-arrow] to change the status. Press DONE to terminate testing. CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly. Shaded areas below apply only to TH8320/TH8321. Please contact your distributor to order replacement parts. *Use to cover marks left by old thermostats. For assistance with this product please visit http://customer.resideo.com or call Resideo Customer Care toll-free at 1-800-468-1502. Resideo Resideo Technologies, Inc. © 2021 Resideo Technologies, Inc. All rights reserved.Wallplate Installation
Installation Requirements
Safety Notices
Power Options
Terminal Designations
Conventional Terminal Letters:
Terminal Description R Heating power. Connect to secondary side of heating system transformer. Rc Cooling power. Connect to secondary side of cooling system transformer. C Common wire from secondary side of cooling transformer (if 2 transformers). W 1st stage heat relay. W2 2nd stage heat relay. Y 1st stage compressor contactor. Y2 2nd stage compressor contactor. G Fan relay. S1 Optional outdoor or remote sensor. S2 Optional outdoor or remote sensor. Heat Pump Terminal Letters:
Terminal Description R Heating power. Connect to secondary side of heating system transformer. Rc Cooling power. Connect to secondary side of cooling system transformer. C Common wire from secondary side of cooling system transformer. Y 1st stage compressor contactor. Y2 2nd stage compressor contactor. Aux/E Auxiliary/Emergency heat relay. G Fan relay. L Heat pump reset (powered continuously when System is set to Em Heat; system monitor when set to Heat, Cool or Off). O/B Changeover valve for heat pumps. S1 Optional outdoor or remote sensor. S2 Optional outdoor or remote sensor. Wiring Guide - Conventional Systems
1H/1C System (1 transformer)
Terminal Connection Rc Power [1] R [R+Rc joined by jumper] W Heat relay Y Compressor contactor G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 1H/1C System (2 transformers)
Terminal Connection Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] W Heat relay Y Compressor contactor G Fan relay C 24VAC common [3, 4] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Heat Only System
Terminal Connection Rc Power [1] R [R+Rc joined by jumper] W Heat relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Heat Only System (Series 20)
Terminal Connection Rc [R+Rc joined by jumper] R Series 20 valve terminal "R" [1] W Series 20 valve terminal "B" Y Series 20 valve terminal "W" C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Heat Only System With Fan
Terminal Connection Rc Power [1] R [R+Rc joined by jumper] W Heat relay G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Cool Only System
Terminal Connection Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 2H/2C System (1 transformer)
Terminal Connection Y2 Cool relay 2 W2 Heat relay 2 Rc Power [1] R [R+Rc joined by jumper] W Heat relay 1 Y Cool relay 1 G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 2H/2C System (2 transformers)
Terminal Connection Y2 Cool relay 2 W2 Heat relay 2 Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] W Heat relay 1 Y Cool relay 1 G Fan relay C 24VAC common [3, 4] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Wiring Guide - Heat Pump Systems
1H/1C Heat Pump (no auxiliary heat)
Terminal Connection Rc Power [1] R [R+Rc joined by jumper] O/B Changeover valve [5] Y Compressor relay G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 2H/1C Heat Pump (with auxiliary heat)
Terminal Connection L Equipment monitor [6, 7] Aux/E Auxiliary/Emergency heat relay (Heat 2) Rc Power [1] R [R+Rc joined by jumper] O/B Changeover valve [5] Y Compressor relay G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 2H/2C Heat Pump (no auxiliary heat)
Terminal Connection Y2 Compressor 2 relay Rc Power [1] R [R+Rc joined by jumper] O/B Changeover valve [5] Y Compressor 1 relay G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor 3H/2C Heat Pump (with auxiliary heat)
Terminal Connection Y2 Compressor 2 relay L Equipment monitor [6, 7] Aux/E Auxiliary/Emergency heat relay (Heat 2) Rc Power [1] R [R+Rc joined by jumper] O/B Changeover valve [5] Y Compressor 1 relay G Fan relay C 24VAC common [3] S1 Optional outdoor/remote sensor S2 Optional outdoor/remote sensor Mounting and Setup
Remove Tab and Mount Thermostat
Set Date and Time
Installer Setup
Installer Setup Functions
Setup Functions and Settings:
Function Code Function Name Settings & Options (factory default in bold) 0120 Year (first two digits) 20 (2001-2099)
21 (2100-2178)0130 Year (second two digits) 12 (2012)
[Other options: 00-99]0140 Month 6 [Other options: 1-12] 0150 Date 15 [Other options: 1-31] 0160 Schedule format 4 7-day programming
0 Non-programmable0170 System type 1 1 heat/1 cool conventional
2 1 heat/1 cool heat pump (no aux. heat)
3 Heat only (2-wire systems)
4 Heat only with fan
5 Hot water Series 20 system (power to open & close zone valves/normally open zone valves)
6 Cool only
7 2 heat/1 cool heat pump (with aux. heat)
8 2 heat/2 cool multistage conventional
9 2 heat/1 cool multistage conventional
10 1 heat/2 cool multistage conventional
11 2 heat/2 cool heat pump (no aux. heat)
12 3 heat/2 cool heat pump (with aux. heat)0180 Fan control (heating) 0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)0190 Changeover valve (O/B terminal) 0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating0200 Auxiliary heat 0 Electric backup heat
1 Fossil fuel backup heat0210 External fossil fuel kit 1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)0220 1st stage compressor cycle rate 3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]0230 2nd stage compressor cycle rate 3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]0240 First stage heat cycle rate (CPH= cycles per hour) 5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]0250 Second stage heat cycle rate (CPH) 5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]0260 Third stage heat cycle rate (CPH) 9 Electric auxiliary heat or electric furnaces
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
5 Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]0280 Backlight 0 Backlight on for approx. 8 seconds after keypress
1 Backlight always on low intensity, full bright after keypress (requires 24VAC connection)0300 Manual/Auto changeover 0 Manual changeover (Heat/Cool/Off)
1 Automatic changeover (Heat/Cool/Auto/Off)0310 Auto changeover deadband 3 Heat/cool temperature 3°F apart (1.5°C) ** See page 11
[Other options: 2-9 (2°F to 9°F/1.5 °C to 5°C)]0320 Temperature display 0 Fahrenheit
1 Celsius0330 Daylight savings 2 Auto-change to daylight savings time (2007 and beyond, for areas that use the new 2007 DST calendar)
1 Auto-change to daylight savings time (through 2006, and for areas that do not use the new 2007 DST calendar)
0 Daylight savings time is turned off0340 Remote sensor 0 No remote sensor
1 Outdoor sensor (display only)
2 Outdoor control sensor (select heat pumps) ** See page 11
3 Indoor sensor0350 Heat pump compressor lockout 0 No heat pump compressor lockout
[Other options: 15, 20, 25, 30, 35, 40°F (-9.5°C to 7°C)]0360 Heat pump auxiliary lockout 0 No heat pump auxiliary lockout
[Other options: 40, 45, 50, 55, 60°F (4.5°C to 15.5°C)]0380 Dehumidification control 0 No dehumidification control
1 Thermostat controls dehumidification with air conditioner ** See page 110500 Furnace filter change reminder 0 Off
1 10-day run time (about 1 month)
2 30-day run time (about 3 months)
3 60-day run time (about 6 months)
4 90-day run time (about 9 months)
5 120-day run time (about 1 year)
6 365-day run time (about 3 years)0510 Humidifier pad change reminder 0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days0520 UV lamp change reminder 0 Off
1 365 calendar days0530 Adaptive Intelligent Recovery™ 1 On ** See page 11 0540 Program periods 0 Off
4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)0580 Compressor protection 5 5 minute compressor off time ** See page 11
[Other options: 0, 1, 2, 3 or 4-minute off time]0600 Heat temperature range stop 90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4.5°C to 32°C)]0610 Cool temperature range stop 50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (10.5°C to 37°C)]0640 Clock format 12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")0650 Extended fan timer (heat) 0 Off
90 Fan runs for 90 seconds after call for heat ends0660 Extended fan timer (cool) 0 Off
90 Fan runs for 90 seconds after call for cooling ends0670 Keypad lock 0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fully locked0680 Heat temperature control 2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Choose if room does not reach set temperature0690 Cool temperature control 2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Choose if room does not reach set temperature0700 Temperature display offset 0 Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]0710 RESET 0 No reset
1 Reset installer options & program schedule to factory default (only date and time settings are retained)Installer System Test
System Test Descriptions:
System Test System Status 1 Cooling system 0 Compressor and fan turn off
1 Compressor and fan turn on
2 Second stage compressor turns on2 Fan system 0 Fan turns off
1 Fan turns on3 Heating system 0 Heat and fan turn off
1 Heat turns on (fan on if Function 0170 is set for heat pump, or if Function 0180 is set to "1") ** See page 6
2 Second stage heat turns on
3 Third stage heat turns on4 Emergency heating system 0 Heat and fan turn off
1 Heat and fan turn onSpecial Functions
Accessories & Replacement Parts
Specifications
Temperature Ranges:
Operating Ambient Temperature:
Shipping Temperature:
Operating Relative Humidity:
Physical Dimensions:
Electrical Ratings:
Terminal Current Voltage (50/60Hz) Running W Heating (Powerpile) 20-30 Vac 0.02-1.0 A 750 mV DC 100 mA DC W2 Heating 20-30 Vac 0.02-0.6 A Y Cooling 20-30 Vac 0.02-1.0 A Y2 Cooling 20-30 Vac 0.02-0.6 A Aux/E Aux. heat Emergency heat 20-30 Vac 0.02-1.0 A O/B Changeover 20-30 Vac 0.02-0.6 A L Heat pump reset 20-30 Vac 0.02-0.6 A Need Help?
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502