Product Overview
The temperzone ISK Series Cassette is a split system air conditioner designed for year-round comfort and economy. It is available in both Reverse Cycle (heat pump) and Cooling Only configurations.
Nominal Cooling Capacities: 7.0 kW - 12.3 kW
Applications:
- Shops: Enhance the selling and working environment, encouraging customers to stay longer and buy more.
- Offices: Provide greater environmental comfort, promoting increased efficiency, productivity, and happier attitudes.
- Clubs: Offer cool comfort for bars, restaurants, and night clubs, encouraging clients to stay longer.
Features and Benefits
General
The ISK Cassette indoor unit, paired with an associated OSA outdoor unit, forms a split system air conditioner suitable for various commercial and public spaces like open office areas, receptions, and showrooms. Its overhead installation saves valuable floor and wall space and avoids the expense of separate ducting, grilles, and diffusers.
Design
The indoor unit is designed for recessed installation within a level ceiling space, centrally located for optimal four-way air distribution. Only the louvred fascia is visible. Its low-profile, elegant design blends harmoniously with room decor. Swing louvre operation prevents stratified air, with options for fixed angles via remote control. Supply air can be ducted to a remote diffuser, and fresh air can be ducted into the unit to mix with room air. The outdoor unit is designed for freestanding or wall mounting.
Comfort
Reverse Cycle systems feature Auto-changeover mode to maintain a preset comfort level by automatically switching between cooling and heating. Manual control of all functions, including one of three fan speeds, is available via a wireless remote control. ?
Economy
The system provides cooling and heating as needed. Reverse cycle models can generate up to 3 kW of heating for every 1 kW of power consumed, offering high efficiency. A programmable start/stop timer adds convenience and economy. Outdoor units are pre-charged with refrigerant, simplifying installation and reducing costs.
Efficiency
The outdoor unit features a high-efficiency scroll compressor and heat exchange coils with inner grooved tubes for improved heat transfer. ?
Quiet Operation
The ISK Cassette emits a quiet whisper of conditioned air due to its carefully designed fan. The compressor is housed in an insulated compartment within the outdoor unit to minimize noise, and the indoor unit is also insulated for noise attenuation. ?
Pre-Heat Cold Draught Protection
The system is designed to prevent cold drafts when switching to heating mode. ?
Ease of Servicing
The air filter is easily accessible for periodic cleaning through a hinged/removable return air panel on the cassette fascia. temperzone provides full technical backup service and readily available spare parts.
Quality Outdoor Cabinet
The outdoor unit is constructed from high-quality galvanised steel with a tough oven-cured polyester powder coating and stainless steel fasteners, built to withstand harsh weather. Outdoor coil fins are epoxy coated for protection in corrosive environments like salt-laden sea air.
Controls and Options
Fingertip Control
An infrared remote control offers versatile and simple operation. Functions include Auto, Heat, Cool, Dry, Fan, and Sleep modes, powered swing louvre, on/off time clock, and manual override. Note: The Heat function is available only on Reverse Cycle systems. ?️
Set & Forget
The ISK system includes a room thermostat. The desired temperature is set via the remote control, and the system manages the rest. In Auto Fan mode, fan speed adjusts based on room and set temperatures.
Optional Equipment
- temperzone HP Fan Speed Controller (4 amp): Recommended for cooling in ambient temperatures below 20°C for extended periods.
- Wall mounting brackets for outdoor units.
Dual-Zone Alternative
Two independently controlled ISK 73Q indoor units can be connected to a single OSA 146 B twin system outdoor unit, allowing for the servicing of two distinct zones.
ISO 9002 Certification
temperzone operates an ISO 9002 certified quality management system. ✅
Split System Configurations
The ISK Cassette series is available in various configurations: Cooling Only or Reverse Cycle; Single and Three Phase systems.
Standard Split Systems
Indoor Unit | Outdoor Unit |
---|---|
ISK 73Q | OSA 73 |
ISK 101Q | OSA 100 |
ISK 101Q | OSA 101 |
ISK 125Q | OSA 126 |
ISK 125Q | OSA 127 |
Twin Split System
Service two zones with two independent thermostats.
Indoor Unit | Outdoor Unit |
---|---|
ISK 73Q (x2) | OSA 146 B |
Single Phase System
(Refer to specific model configurations above)
Dimensions (mm)
Fig. 1: ISK 73Q - 125Q Cassette Indoor Units
MODEL | A | B | C | D | E | F |
---|---|---|---|---|---|---|
ISK 73Q | 290 | 180 | 230 | 165 | 350 | 185 |
ISK 101Q | 340 | 230 | 280 | 215 | 380 | 175 |
ISK 125Q | 340 | 230 | 280 | 215 | 380 | 175 |
Note: The manufacturer reserves the right to make changes to specifications at any time without notice or obligation. Certified data is available on request.
Fig. 2: OSA 73 - 146 Outdoor Units
MODEL | A | B | C | D | E | F |
---|---|---|---|---|---|---|
OSA 73 | 885 | 380 | 655 | 515 | 350 | 185 |
OSA 100 | 935 | 410 | 695 | 585 | 380 | 175 |
OSA 101 | 935 | 410 | 695 | 585 | 380 | 175 |
OSA 126 | 970 | 440 | 800 | 610 | 420 | 180 |
OSA 127 | 970 | 440 | 800 | 610 | 420 | 180 |
OSA 146 | 1135 | 480 | 800 | 725 | 430 | 200 |
Note: OSA 146 has refrig. conn's at each end.
Pipe Length Capacity Loss
On Cooling Cycle Due to Pressure Drop.
MODEL | PIPE SIZE (mm) | EQUIVALENT LINE PIPE LENGTH (m) | ADDITIONAL PIPE LENGTH TO ALLOW PER BEND | |||||||
---|---|---|---|---|---|---|---|---|---|---|
Liquid | Suction | 5 | 10 | 15 | 20 | 30 | Suction Pipe Size OD | Long 90° Radius | ||
ISK 73Q | 10 | 16 | 2% | 4% | 6.5% | 9% | 13% | 16 mm | 0.30 m | |
ISK 101Q | 10 | 16 | 2.5% | 5% | 8% | 11% | 15% | 19 mm | 0.43 m | |
ISK 125Q | 10 | 19 | 1.2% | 2.5% | 3.8% | 5% | 8% | 22 mm | 0.46 m | |
13 | 19 | 1.6% | 3.2% | 4.7% | ||||||
13 | 22 | 0.8% | 1.6% | 2.4% | 3.2% | 4.7% |
Specifications
Split System - Reverse Cycle Options
ISK 73Q / OSA 73R | ISK 101Q / OSA 100R | ISK 101Q / OSA 101R | ISK 125Q / OSA 126R | ISK 125Q / OSA 127R | ISK 73Q (x2) / OSA 146RB | |
---|---|---|---|---|---|---|
Cooling Capacity (Total) *2 (kW) | 7.0 | 10.1 | 10.1 | 12.3 | 12.3 | 7.0 (x2) |
Heating Capacity *3 (kW) | 7.5 | 10.5 | 10.5 | 13 | 13 | 7.5 (x2) |
E.E.R. / C.O.P. (Cooling) | 11.5 / 3.4 | 10.5 / 3.1 | 10.5 / 3.1 | 11.5 / 3.4 | 11.5 / 3.4 | 11.5 / 3.4 |
Power Source (volts / phases) | 230 / 1 | 230 / 1 | 400 / 3 | 230 / 1 | 400 / 3 | 230 / 1 |
Recom'd Max. Line Length (m) | 30 | 30 | 30 | 30 | 30 | 30 (x2) |
Max. Height Separation Between Indoor & Outdoor Units (Reverse Cycle Systems) (m) | 12 | 12 | 12 | 12 | 12 | 12 |
Running Amps (Total) / External Fuse (A) | 9.1 / 25 | 14.5 / 32 | 5.7/ph. / 25 | 16 / 32 | 6.3/ph. / 25 | 9.1 / 30 (x2) |
Indoor Units
ISK 73Q | ISK 101Q | ISK 101Q | ISK 125Q | ISK 125Q | ISK 73Q (x2) | |
---|---|---|---|---|---|---|
Air Flow (l/s) - Low | 220 | 300 | 300 | 330 | 330 | 220 |
Air Flow (l/s) - Med | 255 | 360 | 360 | 385 | 385 | 255 |
Air Flow (l/s) - High | 300 | 433 | 433 | 460 | 460 | 300 |
Sound Pressure dB(A) (SPL) *4 - Low | 39 | 39 | 39 | 41 | 41 | 39 |
Sound Pressure dB(A) (SPL) *4 - Med | 40 | 45 | 45 | 46 | 46 | 40 |
Sound Pressure dB(A) (SPL) *4 - High | 44 | 48 | 48 | 48 | 48 | 44 |
Motor Input (High Speed) (W) | 90 | 110 | 110 | 150 | 150 | 90 (x2) |
Holding Charge | dry air | |||||
Heat Exchanger Type | aluminium slit plate fins to expanded inner grooved copper tube | |||||
Indoor Fan Type | high static mixed flow turbo | |||||
Weight (incl. fascia) (kg) | 37 | 43 | 43 | 45 | 45 | 37 (x2) |
Outdoor Units
OSA 73R | OSA 100R | OSA 101R | OSA 126R | OSA 127R | OSA 146RB | |
---|---|---|---|---|---|---|
Sound Pressure (SPL) *5 (dB(A)) | 45 | 49 | 49 | 51 | 51 | 48 |
Refrigerant | HCFC-22 (R22) | |||||
Heat Exchanger Type | aluminium corrugated plate fins to expanded inner grooved copper tube | |||||
Outdoor Fan Type | propeller | |||||
Finish | tan polyester powder coat | |||||
Weight (kg) | 72 | 87 | 83 | 87 | 89 | 143 |
Notes:
- Capacities are for close coupled systems. Allowance must be made for pipe length, pipe size and bends.
- *1 All of the above systems are available in Cooling Only versions, except the OSA 100R.
- *2 Nominal Cooling Capacity based on: Indoor Entering Air Temperature 27°C D.B., 19°C W.B.; Outdoor Entering Air Temperature 35°C D.B.
- *3 Nominal Heating Capacity based on: Indoor Entering Air Temperature 21°C D.B.; Outdoor Entering Air Temperature 8.3°C D.B., 6.1°C W.B.
- *4 Sound Pressure Level (SPL) for Indoor Units is measured 1.5 m from supply air outlet in an anechoic chamber.
- *5 Sound Pressure Level (SPL) for Outdoor Units is measured 3 m from exhaust air fans.
Materials and specifications subject to change without notice due to the manufacturer's ongoing research and development programme.
Contact Information
Available from:
temperzone limited
Head Office, Auckland: 38 Tidal Rd, Mangere, N.Z. Private Bag 93303, Otahuhu, NEW ZEALAND. Email: sales@temperzone.co.nz Website: www.temperzone.biz
temperzone australia pty ltd
Head Office, Sydney: 7A Bessemer St PO Box 6448, Delivery Centre, Blacktown, NSW 2148, AUSTRALIA. Email: sales@temperzone.com.au
Regional Offices:
- AUCKLAND: Ph. 0-9-279 5250, Fax 0-9-275 5637
- WELLINGTON: Ph. 0-4-569 3262, Fax 0-4-566 6249
- CHRISTCHURCH: Ph. 0-3-379 3216, Fax 0-3-379 5956
- SYDNEY: Ph. (02) 8822-5700, Fax (02) 8822-5711
- ADELAIDE: Ph. (08) 8333-1833, Fax (08) 8333-1844
- MELBOURNE: Ph. (03) 9551-7422, Fax (03) 9551-8550
- BRISBANE: Ph. (07) 3399-2544, Fax (07) 3399-2577
- SINGAPORE: Ph. SNG 6733 4292, Fax SNG 6235 7180
- HONG KONG: Ph. HK 2833 6381, Fax HK 2834 0050
- NEWCASTLE: Ph. (02) 4962-1155, Fax (02) 4961-5101
- PERTH: Ph. (08) 9314-3844, Fax (08) 9314-3855
- TOWNSVILLE: Ph. (07) 4773-9566, Fax (07) 4773-9166
- HOBART: Ph. (03) 6272-0066, Fax (03) 6272-0506
ISO 9002 CERTIFIED
© temperzone limited 2003