Danfoss 065B2006
Data sheet
Seated valves VRB 3, VRG 3
Description

VRB, VRG valves provide a quality, cost effective solution for most water and chilled applications. These valves may be used with glycol concentrations of up to 50% .
VRG 3 valves: Grey cast iron (GG-25) with external thread.
VRB 3 valves: Red bronze (Rg 5) with internal or external thread.
Main data: · PN 16 · DN 15 - 50 · Connection: internal or external thread · Suitable for water or glycolic water
2 (-10*) ... 120 °C * At temperatures from -10 oC till +2 oC use
stem heater. · Suitable for use with AMV(E) 15, 16, 25, 35,
AMV(E) 25 SU/SD and AMV 323, 423, 523 actuators · Compliance with PED directive 97/23/EC.

Ordering
** The 3-way valve can be used as a 2-way valve by using the: - closing plug (int. thread) or - closing nut (ext. thread) (see accessories below)

3 - way valves (2-way valves**)

Dimensions DN

kvs m3/h

Int. thread - VRB 3

0.63

065B1411

1.0

065B1412

15

1.6

065B1413

2.5

065B1414

4.0

065B1415

20

6.3

065B1420

25

10

065B1425

32

16

065B1432

40

25

065B1440

50

40

065B1450

Code No. Ext. thread - VRB 3
065B1311 065B1312 065B1313 065B1314 065B1315 065B1320 065B1325 065B1332 065B1340 065B1350

Ext. thread - VRG 3 065B1211 065B1212 065B1213 065B1214 065B1215 065B1220 065B1225 065B1232 065B1240 065B1250

Accessories**

Closing plug with gasket for VRB int. thread (GG 25)

Type

Code No.

Closing plug with gasket DN 15 065Z7025

Closing plug with gasket DN 20 065Z7026

Closing plug with gasket DN 25 065Z7027

Closing plug with gasket DN 32 065Z7028

Closing plug with gasket DN 40 065Z7029

Closing plug with gasket DN 50 065Z7030

Closing nut with gasket for VRB / VRG ext. thread (GG 25)

Type

Code No.

Closing nut with gasket DN 15

065Z7001

Closing nut with gasket DN 20

065Z7002

Closing nut with gasket DN 25

065Z7003

Closing nut with gasket DN 32

065Z7004

Closing nut with gasket DN 40

065Z7005

Closing nut with gasket DN 50

065Z7006

SIBC

VD.HC.M1.02 © Danfoss 11/03

1

Data sheet

Seated valves VRB 3, VRG 3

Ordering (continued)
1) At temperatures from -10 oC till +2 oC use stem heater.
2) - Stuffing box - Gland ring - Instructions

Accessories - 3 tailpieces internal thread for VRB / VRG ext. thread (GGG 50)

Rp

DN

Code No.

½

15

065B4107

¾

20

065B4108

1

25

065B4109

1 ¼

32

065B4110

1 ½

40

065B4111

2

50

065B4112

Accessories - stem heater 1)
Type Stem heater 24 V (AMV/AME 15, 16, 25, 35 and valves DN 15 - 50)
Spare parts - stuffing box 2)
Type For valves VRB / VRG DN 15 - 50

Code No. 065B2171
Code No. 065B0008

Technical data

Nominal pressure Control characteristic Medium Medium temperature Control range
Connection

PN 16
LOG: port A-AB; LIN: port B-AB
Circulation water / Glycolic water up to 50 % 2 (-10) ... 120 °C (from -10 oC ... +2 °C with stem heater)
kvs 0.63: min. 30:1 / kvs 1.0 - 4.0: min. 50:1 / DN 20 - DN 50: min. 100:1 VRB 3: internal thread DIN 2999, VRB 3, VRG 3: external thread DIN ISO 228/1

Material: VRG 3
Body
Spindle Cone Gasket

Grey cast iron EN-GJL-250 (GG-25)
Stainless steel
Brass
EPDM

VRB 3 Body Spindle Cone Gasket

Red bronze 2.1096.1 (RG5) Stainless steel Brass EPDM

Leakage loss at closed valve

2 - way valves (A-AB) 3 - way valves (A-AB)
(B-AB)

Max. 0.05% of kvs Max. 0.05% of kvs Max. 1% of kvs

Pressure temperature diagram

PN 16
120
Maximum allowed operating pressure as a function of medium temperature.

2

VD.HC.M1.02 © Danfoss 11/03

SIBC

Data sheet

Seated valves VRB 3, VRG 3

Max. closing pressure and recommended p (VRB / VRG)

Valve

Int.

Ext.

AMV(E) 15 AMV(E) 16

DN thread thread Stroke

500 N

300 N

ISO 7/1 ISO 228/1 mm

15

Rp 1/2

G 1

10

16

9

20

Rp 3/4

G 11/4

15

11

4

25

Rp 1

G 11/2

15

6

2

32

Rp 11/4

G 2

15

3

1

40

Rp 11/2

G 21/4

15

2

-

50

Rp 2

G 23/4

15

1

-

Actuator type

AMV(E) 25 - 1000 N

AMV(E) 35, AMV 323

AMV(E) 25 SU/SD - 450 N

600 N

max. closing pressure (bar)

16 [16]

16

16 [10]

13

16 [5]

8

9.0 [2.5]

5

6.0 [2]

3

3.0 [0.5]

2

AMV 423, 523 1200 N
16 16 16 12 8 5

NOTE: Max. p is the physical limit of differential pressure the valve will close against.

pressure is smaller than 4 bar than the recommended p is the same as closing p.

The recommended p is based on the generation of noise, plug erosion etc. Max. recommended p is 4 bar. If max. closing

Values in parantheses [ ] are based on the force of the actuator AMV(E) 25 SU/SD only.

Valve characteristics

Valve characteristics log (2-way)

Valve characteristics log/lin (3-way)

SIBC

VD.HC.M1.02 © Danfoss 11/03

3

Data sheet Installation
Disposal

Seated valves VRB 3, VRG 3

Hydraulic connections Mount according to flow direction as indicated on valve body, AB is always the outlet port; inlets are A (two port) or A and B (three port).
Valve mounting Before mounting the valve be sure that the pipes are clean and free from swarf. It is essential that the pipes are lined up squarely with the valve at each connection and that they are free from vibrations. Install the motorized control valves with the actuator in a vertical or horizontal position but not upside down. Leave sufficient clearance to facilitate the dismantling of the actuator from the valve body for maintenance purposes. The valve must not be installed in an explosive atmosphere or at an ambient temperature higher than 50 °C or lower than 2 °C. It must not be subject to steam jets, water jets or dripping liquid.
Note that the actuator may be rotated up to 360° with respect to the valve body by loosening the retaining fixture. After this operation retighten.
Hydraulic diagrams for applications of 3-way mixing valves Note the valve must only be used as a mixing valve, and is not suitable for diverting (with one inlet and two outlet ports). Where this function is required, the valve should be mounted in the return line, as Fig. 2.
Note that if the pump is installed before the A port of the below valve arrangement, then excessive valve hammering will occur thus causing an overload of the actuator.

ð

)

)*

*

ð

Fig. 1 Mixing valve used in mixing application.
ð

*

)*

)

ð ð

Fig. 2 Mixing valve used in diverting application.

The valve must be dismantled and the elements sorted into various material groups before disposal.

4

VD.HC.M1.02 © Danfoss 11/03

SIBC

Data sheet

Seated valves VRB 3, VRG 3

Control valve sizing diagram for fluids

SIBC

VD.HC.M1.02 © Danfoss 11/03

5

Data sheet
Control valve sizing diagram for fluids (continued)

Seated valves VRB 3, VRG 3

Examples

1 For fluids with specific gravity of 1 (e.g. water)

2 For fluids with specific gravity different from 1

Design data: Flow rate: 6 m3/h System pressure drop: 55 kPa
Locate the horizontal line representing a flow rate of 6 m3/h (line A-A). The valve authority is given by the equation:
p1 Valve authority, a = p1 + p2
Where: p1= pressure drop across the fully open valve p2= pressure drop across the rest of the circuit with a full open valve

Design data: Flow rate: 6 m3/h of fluid, S.G. 0.9 System pressure drop: 10 kPa
For this example, the left hand axis of the diagram must be ignored. Starting from the RH axis, the flow rate of 6 m3/h is located (point E). The intersection of the diagonal line from point E with a vertical line from S.G. = 0.9 gives the starting point for the effective flow rate line F-F. The process then continues as for Example 1, so 10 kPa intersects F-F nearest to the kvs 16 diagonal. The intersection of F-F with kvs 16 gives a valve pressure drop of 12.7 kPa (point G).

The ideal valve would give a pressure drop equal to the system pressure drop (i.e. an authority of 0.5):
If p1 = p2, a = p1/2* p1 = 0.5
In this example an authority of 0.5 would be given by a valve having a pressure drop of 55 kPa at that flow rate (point B). The intersection of line A­A with a vertical line drawn from B lies between two diagonal lines; this means that no ideally-sized valve is available. The intersection of line A­A with the diagonal lines gives the pressure drops stated by real, rather than ideal, valves. In this case, a valve with kvs 6.3 would give a pressure drop of 90.7 kPa (point C):

90.7 hence valve authority = 90.7 +55 = 0.62 The second largest valve, with kvs 10, would give a pressure drop of 36 kPa (point D):

36 hence valve authority = 36+55 = 0.395

Generally, for a 3 port application, the smaller valve would be selected (resulting in a valve authority higher than 0.5 and therefore improved controlability). However, this will increase the total pressure and should be checked by the system designer for compatibility with available pump heads, etc. The ideal authority is 0.5 with a preferred range of between 0.4 and 0.7.

6

VD.HC.M1.02 © Danfoss 11/03

SIBC

Data sheet

Seated valves VRB 3, VRG 3

Dimensions VRB / VRG + AMV(E) 15, 16, 25, 35

G **

G **

Rp *

G**
Rp (see ordering, part accessories, page 2)

VRG 3 / VRB 3 (as 2-way valves)

Type

DN

VRB

15

VRB

20

VRB

25

VRB

32

VRB

40

VRB

50

VRB / VRG 15

VRB / VRG 20

VRB / VRG 25

VRB / VRG 32

VRB / VRG 40

VRB / VRG 50

Connection

L

L1

H

H1

H2

H3 Weight

mm mm mm mm mm mm kg

*int. Rp 1/2 *int. Rp 3/4 *int. Rp 1 *int. Rp 11/4 *int. Rp 11/2 *int. Rp 2 **ext. G 1

80

-

47 214 - 202 0.7

80

-

55 215 - 203 1.1

95

-

60 215 - 203 1.4

112 -

66 222 - 210 2.0

132 -

75 226 - 214 2.9

160 -

85 232 - 220 4.3

80 128 40 214 64 202 1.0

**ext. G 11/4 80 128 55 215 79 203 1.2

**ext. G 11/2 95 151 60 215 88 203 1.4

**ext. G 2

112 178 66 222 99 210 1.8

**ext. G 21/4 132 201 75 226 110 214 2.5 **ext. G 2 3/4 160 234 85 232 122 220 3.7

* Rp ... internal thread DIN 2999 ** G ... external thread DIN ISO 228/1

VRB / VRG + AMV 323/423/523

Type

DN

VRB

15

VRB

20

VRB

25

VRB

32

VRB

40

VRB

50

VRB / VRG 15

VRB / VRG 20

VRB / VRG 25

VRB / VRG 32

VRB / VRG 40

VRB / VRG 50

Connection

L mm

L1

H

mm mm

H1 mm

H2 mm

*int. Rp 1/2

80

-

47 266

-

*int. Rp 3/4

80

-

55 266

-

*int. Rp 1

95

-

60 266

-

*int. Rp 11/4 112

-

66 272

-

*int. Rp 11/2 132

-

75 276

-

*int. Rp 2 160

-

85 282

-

**ext. G 1 80 128 40 266 64

**ext. G 11/4 80 128 55 266 79 **ext. G 11/2 95 151 60 266 88 **ext. G 2 112 178 66 272 99

**ext. G 21/4 132 201 75 276 110 **ext. G 2 3/4 160 234 85 282 122

Weight kg 0.7 1.1 1.4 2.0 2.9 4.3 1.0 1.2 1.4 1.8 2.5 3.7