12V 7Ah

Resources | ExpertPower Direct

Download

EXP1270 12V 7Ah | ExpertPower Direct

PDF preview unavailable. Download the PDF instead.

EXP1270-Specs ?v=
EXP1270 (12V 7Ah)

Specification
Cells Per Unit Voltage Per Unit Nominal Capacity Weight Internal Resistance Terminal Max. Discharge Current Short Circuit Current Design Life Max. Charging Current
Reference Capacity

Standby Use Voltage Cycle Use Voltage Operating Temperature Range Normal Operating Temperature Range Self Discharge

Container Material

Dimensions

5.94

2.56

3.70 3.94 1.70
0.31 0.13

6
12
7Ah@20hour-rate to 1.80V per cell @77°F
Approx. 4.50 lbs (Tolerance±3.0%)
Approx. 32 m 
F1
70A (5 sec)
350A
6~8 years (Float charging)
2.1 A C3 5.42AH C5 6.11AH C10 6.54AH C20 7.00AH 13.7V~13.9V @ 77°F Temperature Compensation: -3mV/°C/Cell 14.6 V~14.8V @ 77°F Temperature Compensation: -4mV/°C/Cell Discharge: -4°F~140°F Charge: 32°F~122°F Storage: -4°F~140°F
77°F±41°F
EXP Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 77°F, after which recharging is recommended. The monthly self-discharge ratio is less than 3% at 77°F. Please ensure that you charge the batteries before using them.
A.B.S. UL94-HB, UL94-V0 Optional.

The EXP series is a general-purpose battery with a designed life of 6~8 years in oat service. It meets the standards of IEC, JIS, BS, GB/T, and YD/T. With advanced AGM valve-regulated technology and high-purity raw materials, the EXP series battery maintains high consistency for better performance and reliable standby service life. It is suitable for UPS/EPS, medical equipment, emergency lighting, and security system applications.
MH 61046

0.006 2.59

5.94 ± 0.06in

2.56 ± 0.06in

3.70 ± 0.06in

0.03

3.94 ± 0.06in

Value

F1 TERMINAL

Unit: inch

Constant Current Discharge Characteristics : A (77°F)

Constant Power Discharge Characteristics : WPC (77°F)
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values. The battery must be fully charged before the capacity test. The C20 should reach 95% after the first cycle and 100% after the third cycle.

EXP1270 (12V 7Ah)
Discharge CharacteristicsCurve

Charge Characteristic Curve For Standby Use

Cycle Life In Relation To Depth Of Discharge Temperature Effects On Capacity Effect Of Temperature On Long Term Life

Relationship Between Charging Voltage And Temperature
Cycle use 2.43~2.47VPC 25oC (77oF)

Float charging 2.28~2.32VPC 25oC (77oF)

Storage Characteristics

32oF

104oF 86oF

68oF

50oF

Life Characteristics Of Standby Use

Life Expectancy (Years)

(Note) All above information shall be changed without prior notice, ExpertPower reserves the right to explain and update the latest infomation.


Adobe PDF library 16.07