Application Guide
Vitodens 100-W B1HA/B1KA Residential Boiler

APPLICATION GUIDE
The application examples contained in this document serve as a guideline only. These are not engineered drawings and are not intended to replace project designs provided by a professional engineer. It is the responsibility of the installing contractor to ensure all aspects of the system comply with the local authorities having jurisdiction.
© 2017 by Viessmann. All rights reserved. No part of this book may be used or reproduced in any manner whatsoever without prior written permission. For information, contact: Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo ON, N2V 2G5, Canada Phone: 519-885-6300 Toll Free: 800-387-7373 www.viessmann.ca

PRE-FACE / OVERVIEW
Each day Viessmann heating systems face a wide variety of requirements and challenges here in North America, and around the world. Whether in historically protected homes, modern commercial buildings, or in large facilities, Viessmann products meet every demand and offer solutions for all your needs: wood, oil, or gas fired boilers for both residential and commercial use, from 12,000 BTU to 100,000 MBH (4 kW to 29,307 kW), domestic hot water storage tanks, solar collectors, Biogas technologies, and much more. Viessmann also sets the standard for operational reliability, operating comfort, environmental friendliness and a long service life. All Viessmann products have one thing in common: they are based on a modular technology strategy with one common platform. This way, different product versions can be created to fulfill each customer's specific requirements. In short, Viessmann takes care of all your needs, from start to finish. Part of that is a comprehensive support program: A knowledgeable Viessmann sales representative network, technical training academy, and technical support personnel assist you right from the planning stage through to the installation and start-up phase of a project. With Viessmann you are witnessing intelligent, high-tech boiler technology at work. We have selected some of the most interesting Viessmann applications from across North America for your reference.
1

IDENTIFYING BOILER NOMENCLATURE

B 2 H A ... ... ...

Consecutive Number

Fuel Types

Gas Oil

Efficiency

 Low Temperature

A

F

 Condensing

B

J

 CHP

C

Generation of Boiler
A B

C ...

Segment

Series

P

100

1

200

2

300

3

Heat Only Circuit Combi Combi Comfort Coiled Tubing Tank Stratified Loading Tank Solar Heating For DHW Solar Heating

Wall-Mounted

G

H

J

K

-

L

-

-

Floor Standing

-

R

-

-

S

T

U

V

2

IDENTIFYING APPLICATION CODES
2 VD 2 X 1I HC 1I T 2 ZP 01

Number of boilers in system
Boiler Segment VD Vitodens CU CM Vitocrossal CT VR Vitorond
Segment / Series 1 100 Series 2 200 Series 3 300 Series
Domestic Capability X No DHW I With indirect DHW C On demand DHW T Stratified Loading Tank

Number of heating circuits 1, 2, 3 ... Number of supply water temperatures in the system. Number of zones in the system How system is zoned ZP Pumps ZV Zone Valves TV Thermostatic Radiator Valves C Combination Drawing version
3

RECOMMENDED PRODUCT APPLICATIONS

Application Baseboard / Fan Coil

Typical Supply Temperature
High 160 -190 °F

Vitodens 100
1

Cast Iron Radiator

Medium 140 -160 °F

Panel Radiator

Medium 120 -160 °F

Radiant Floor Heating

Low 80 -120 °F

Indirect DHW

High

1

160 -190 °F

Air Handlers

Medium 180 -120 °F

Vitodens 200/222-F

Vitocrossal 300 CU3A

1

Vitorond 100

2

2

1

Best Choice Possible with limitations Not recommended

1- Limited maximum boiler supply water temperature. 2- Ensure boiler protection to prevent against low return water temperature

Refer to Technical Data Manual of each product for applicable certifications. Technical information subject to change without notice.

4

COMPONENT INDEX
Hydronic Components

Electrical Components

Vitodens 100 accessories kit with pressure relief and purge valves.

Ball valve

Circulator with isolation flanges

Aquastat

Secondary low water cut-off

Low loss header

Thermostatic mixing valve

Radiant infloor manifold

Motorized mixing valve

Outdoor temperature sensor

Panel radiator

Flow check valve

Hot water baseboard radiator

Thermostat

Temperature sensor

Boiler water feed with double back check valve

Air eliminator

Expansion tank

Viessmann vitotrol

Multi-zone control

Purge assembly: (sediment faucet and ball valve)

Zone valve

Hyfronic air handler

24V Zone valve

Circulator

Towel radiator

Viessmann 3-way mixing valve with actuator motor

Plate and frame heat exchanger

120 Volt power

5

6

VITODENS 100

Application #

Application Code

Page

Application 1 -

VD2T 1HC1T1ZP.01

18

Application 2 -

VD2T 1HC1T4ZV.01

22

Application 3 -

VD2T 1HC1T4ZP.01

26

Application 4 -

VD2T 2HC2T2ZP.01

30

Application 5 -

VD2T 3HC3T3ZP.01

34

7

Vitodens 100-W, B1HA/B1KA Technical Data
PRODUCT INFORMATION
6WDQGDUG (TXLSPHQW :DOOPRXQW ERLOHU DQG LQVWDOODWLRQ ILWWLQJV FZ  SVL SUHVVXUH UHOLHI YDOYH SUHVVXUH JDJH JDV VKXWRII YDOYH WZR ILOOGUDLQ YDOYHV DOO PRXQWLQJ KDUGZDUH RXWGRRU WHPSHUDWXUH VHQVRU DQG /3 FRQYHUVLRQ NLW
%RLOHU FURVVVHFWLRQ /HJHQG $ ,QR[5DGLDO VWDLQOHVV VWHHO KHDW H[FKDQJHU
6WDLQOHVV VWHHO 0DWUL; F\OLQGHU EXUQHU %XUQHU EORZHU *DV DQG K\GURQLF FRQQHFWLRQV %RLOHU FRQWURO
8

Vitodens 100-W, B1HA/B1KA Technical Data

PRODUCT INFORMATION

6WDQGDUG KHDWLQJ ERLOHU
&6$ LQSXW 1DWXUDO JDV 1*
&6$ LQSXW /LTXLG SURSDQH *DV /3*
&6$ RXWSXW'2(  KHDWLQJ FDSDFLW\ 1* &6$ RXWSXW'2(  KHDWLQJ FDSDFLW\ /3* 1HW $+5, UDWLQJ  +HDW H[FKDQJHU VXUIDFH DUHD
0LQ JDV VXSSO\ SUHVVXUH 1DWXUDO JDV /3* 0D[ JDV VXSSO\ SUHVVXUH  1DWXUDO JDV DQG /3* $)8( :HLJKW
6KLSSLQJ ZHLJKW
%RLOHU ZDWHU FRQWHQW
%RLOHU PD[ IORZ UDWH 
0D[ RSHUDWLQJ SUHVVXUH PD[ DOORZDEOH ZRUNLQJ SUHVVXUH DW ) & %RLOHU ZDWHU WHPSHUDWXUH  $GMXVWDEOH KLJK OLPLW $+/ UDQJH
 VSDFH KHDWLQJ VWHDG\ VWDWH  '+: SURGXFWLRQ VHWSRLQW

%RLOHU 0RGHO 1R 0%+ N: 0%+ N: 0%+ N: 0%+ N: 0%+ IW P
´ZF ´ZF
´ZF
OEV NJ OEV NJ 86*
/ *30
/K
SVLJ EDU
) & ) &

%+$  
 
 
 
 
 
 
         
 

%+$         
 

 
         
 

 WR   WR   

 )L[HG KLJK OLPLW )+/ %RLOHU FRQQHFWLRQV %RLOHU KHDWLQJ VXSSO\ DQG UHWXUQ 3UHVVXUH UHOLHI YDOYH '+: WDQN KHDWLQJ VXSSO\UHWXUQ '+: KHDWLQJ 'UDLQ YDOYH 'LPHQVLRQV 2YHUDOO GHSWK
2YHUDOO ZLGWK
2YHUDOO KHLJKW

) &
1370 PDOH 137) IHPDOH
1370 PDOH 1370 PDOH PDOH WKUHDG
LQFKHV PP
LQFKHV PP
LQFKHV PP

´ ´ ´  ´
     

 
´ ´ ´  ´
     

 2XWSXW EDVHG RQ ) & ) & V\VWHP VXSSO\  UHWXUQ WHPSHUDWXUH  1HW $+5, UDWLQJ EDVHG RQ SLSLQJ DQG SLFNXS DOORZDQFH RI   ,I WKH JDV VXSSO\ SUHVVXUH H[FHHGV WKH PD[LPXP JDV VXSSO\ SUHVVXUH YDOXH
D VHSDUDWH JDV SUHVVXUH UHJXODWRU PXVW EH LQVWDOOHG XSVWUHDP RI WKH KHDWLQJ V\VWHP

%.$         
 

 
         
 
´ ´  ´ ´
     

9

Vitodens 100-W, B1HA/B1KA Technical Data

PRODUCT INFORMATION

*DV VXSSO\ FRQQHFWLRQ )OXH JDV  7HPSHUDWXUH DW ERLOHU UHWXUQ WHPSHUDWXUH RI ) &  DW UDWHG IXOO ORDG  DW UDWHG SDUWLDO ORDG 7HPSHUDWXUH DW ERLOHU UHWXUQ WHPSHUDWXUH RI ) & )OXH JDV YDOXH 0DVV IORZ UDWH RI IOXH JDV  DW UDWHG IXOO ORDG

 DW UDWHG SDUWLDO ORDG

$YDLODEOH GUDXJKW

)OXH JDV WHPSHUDWXUH VHQVRU OLPLW $YHUDJH FRQGHQVDWH IORZ UDWH  ZLWK QDWXUDO JDV  7675   )   &

&RQGHQVDWH FRQQHFWLRQ 

%RLOHU IOXH JDV FRQQHFWLRQ  &RPEXVWLRQ DLU VXSSO\ FRQQHFWLRQ  1RLVH OHYHO DW  PHWHU  DW IXOO ORDG  DW SDUWLDO ORDG +LJK DOWLWXGH IDFWRU\ VHW 

FRD[LDO VLQJOH

%RLOHU 0RGHO 1R 1370 PDOH
) & ) &
) &
OEVK NJK OEVK NJK
3D PEDU
) &
86*GD\ /GD\ KRVH QR]]OH  LQ 
LQ PP RXWHU  LQ PP
G% G% IW P

%+$  ´
     
       
 
 
    
 
 

%+$  ´
     
     
 
 


    
 
   

%.$  ´
     
       
 
 
    
 
 

 0HDVXUHG IOXH JDV WHPSHUDWXUH ZLWK D FRPEXVWLRQ DLU WHPSHUDWXUH RI ) &

 %DVHG RQ W\SLFDO ERLOHU F\FOHV LQFOXGLQJ SDUWLDO ORDG FRQGLWLRQV

 5HTXLUHV µ PP WXELQJ 6HH 9LWRGHQV : ,QVWDOODWLRQ ,QVWUXFWLRQV IRU GHWDLOV

 )RU GHWDLOHG LQIRUPDWLRQ UHIHU WR WKH 9LWRGHQV 9HQWLQJ 6\VWHP ,QVWDOODWLRQ ,QVWUXFWLRQV

 )RU  WR  IW  WR  P RSHUDWLRQ D FRQWURO SURJUDPPLQJ FKDQJH LV UHTXLUHG 5HIHU WR WKH ,QVWDOODWLRQ DQG 6HUYLFH ,QVWUXFWLRQV IRU GHWDLOV 1RWH )RU DOWLWXGH RSHUDWLRQ XS WR  IHHW GHUDWH WKH LQSXW FDSDFLW\ E\   IW  P )RU RSHUDWLRQ IURP  WR  IW  WR  P ZLWK WKH HOHFWURQLF DOWLWXGH DGMXVWPHQW PDGH GHUDWH WKH LQSXW FDSDFLW\ E\  IRU HYHU\  IW  P VWDUWLQJ DW  IW  P IRU D WRWDO RI  

/HJHQG ,QSXW FDSDFLW\ DIWHU HOHFWURQLF DOWLWXGH DGMXVWPHQW LV PDGH
10

Vitodens 100-W, B1HA/B1KA Technical Data

PRODUCT INFORMATION

%.$ RQ GHPDQG KRW ZDWHU RSHUDWLRQ
0D[ ,QSXW 1* DQG /3* '+: SURGXFWLRQ RQO\ 0D[ ERLOHU WHPSHUDWXUH GXULQJ '+: SURGXFWLRQ '+: VXSSO\ WHPSHUDWXUH &RQWLQXRXV GUDZ UDWH 
 DW ' W ) .
0D[ IORZ WKURXJK KHDW H[FKDQJHU
0D[LPXP DOORZDEOH ZRUNLQJ SUHVVXUH SRWDEOH ZDWHU 7HVW SUHVVXUH ,QWHJUDWHG SXPS IORZ UDWH '+: SURGXFWLRQ #  IW  P +HDG SUHVVXUH
+HDWLQJ V\VWHP RSHUDWLRQ ZLWK V\VWHP VLGH DGGLWLRQDO GURS LQ SUHVVXUH RI PD[  IW RI ZDWHU  P

%RLOHU 0RGHO 1R 0%+ N:
) & ) &
86*PLQ /K
86*PLQ /K SVL SVL
86*PLQ /K
86*PLQ /K

%.$   
   
     
 
 


 '&: DQG '+: WHPSHUDWXUH ULVH ZRXOG EH SURSRUWLRQDO 0D[LPXP '+: VXSSO\ WHPSHUDWXUH LV ) &

11

Vitodens 100-W, B1HA/B1KA Technical Data
BOILER DIMENSIONS

)URQW YLHZ

6LGH YLHZ

7RS YLHZ

9LWRGHQV : %+$ VHULHV DQG %.$ FRPEL
/HJHQG
&RQGHQVDWH GUDLQ SODVWLF KRVH  µ   PP %RLOHU ZDWHU VXSSO\ 137 öµ PDOH WKUHDG *DV FRQQHFWLRQ 137 öµ PDOH WKUHDG %RLOHU ZDWHU UHWXUQ 137 öµ PDOH WKUHDG &RPEXVWLRQ DLU RSHQLQJ IRU GRXEOH SLSH V\VWHP &RPEXVWLRQ DLU RSHQLQJ IRU FRD[LDO V\VWHP 
  )RU %+$ VHULHV '+: WDQN KHDWLQJ VXSSO\  )RU %.$ FRPEL '+:   )RU %+$ VHULHV '+: WDQN KHDWLQJ UHWXUQ  )RU %.$ FRPEL '&:  2SHQLQJ IRU SUHVVXUH UHOLHI YDOYH

'LPHQVLRQV D µ  PP  ERWK VLGHV RI WKH ERLOHU E öµ  PP F µ  PP G ôµ  PP H µ  PP I µ  PP J öµ  PP K µ  PP L 
µ  PP PLQLPXP M  µ  PP N µ  PP O  µ  PP P  µ  PP

12

Vitodens 100-W, B1HA/B1KA Technical Data
BOILER DIMENSIONS
%+$ VHULHV DQG %.$ Piping connections for Vitodens 100-W, B1HA series and B1KA
/HJHQG  '+: WDQN KHDWLQJ VXSSO\ IRU %+$ ERLOHUV  '+: IRU %.$ ERLOHU  '+: WDQN KHDWLQJ UHWXUQ IRU %+$ ERLOHUV  '&: IRU %.$ ERLOHU
%:5 %RLOHU ZDWHU UHWXUQ %:6 %RLOHU ZDWHU VXSSO\ %' %RLOHU GUDLQ %) %RLOHU ILOO *& *DV FRQQHFWLRQ 359 3UHVVXUH UHOLHI YDOYH 3* 3UHVVXUH JDXJH 9& 9HQWLQJ FRQQHFWLRQ 7* 7HPSHUDWXUH JDXJH 
 )LHOG VXSSOLHG
13

Vitodens 100-W, B1HA/B1KA Technical Data

HEATING CIRCUIT PUMPS
:DWHUVLGH )ORZ ERLOHU FLUFXLW 7KH 9LWRGHQV : LV GHVLJQHG RQO\ IRU FORVHG ORRS IRUFHG FLUFXODWLRQ KRW ZDWHU KHDWLQJ V\VWHPV 3UHVVXUH GURS SULPDU\ FLUFXLW RI 9LWRGHQV :

+HDWLQJ FLUFXLW SXPSV 7KH 9LWRGHQV : %+$%.$ FRPHV ZLWK D EXLOWLQ ERLOHU SXPS $OO RWKHU SXPSV DUH ILHOG VXSSOLHG DQG VKRXOG EH VL]HG EDVHG RQ SUHVVXUH GURS
,03257$17
3XPS VHOHFWLRQ PXVW EH EDVHG RQ DFFXUDWH V\VWHP IORZ DQG SUHVVXUH GURS FDOFXODWLRQV LQFOXGLQJ '+: VL]LQJ

6XSSO\ KHDG SUHVVXUH ZDWHU

)ORZ UDWH
$ ORZORVV KHDGHU PXVW EH XVHG ZKHQ WKH V\VWHP IORZ UDWH H[FHHGV WKH PD[LPXP RU PLQLPXP IORZ UDWH RI WKH 9LWRGHQV : ERLOHU $Q DOWHUQDWLYH PHWKRG PD\ EH XVHG VXFK DV SULPDU\ VHFRQGDU\ SLSLQJ XVLQJ FORVHO\ VSDFHG WHHV
$ ORZORVV KHDGHU RIIHUV DGGLWLRQDO EHQHILWV QRW SURYLGHG E\ D SDLU RI FORVHO\ VSDFHG WHHV 9LHVVPDQQ VWURQJO\ UHFRPPHQGV DQG SUHIHUV WKH XVH RI D ORZORVV KHDGHU RYHU FORVHO\ VSDFHG WHHV

8VH VWDQGDUG IULFWLRQ ORVV PHWKRG IRU SLSH VL]LQJ 2EVHUYH ERLOHU PD[LPXP DQG PLQLPXP IORZ UDWH OLPLWDWLRQV ,I V\VWHP IORZ UDWH H[FHHGV ERLOHU PD[LPXP IORZ UDWH RU LI V\VWHP IORZ UDWH LV XQNQRZQ 9LHVVPDQQ VWURQJO\ UHFRPPHQGV WKH LQVWDOODWLRQ RI D ORZORVV KHDGHU

'RPHVWLF +RW :DWHU 3URGXFWLRQ YLD ,QVWDQWDQHRXV '+: 3ODWH +HDW ([FKDQJHU %.$ 7KH %.$ LV HTXLSSHG ZLWK DQ HOHFWURQLFDOO\ FRQWUROOHG LQVWDQWDQHRXV '+: SODWH KHDW H[FKDQJHU 7KH FRPIRUW FRQWURO IXQFWLRQ LI VHOHFWHG HQVXUHV WKDW WKH LQVWDQWDQHRXV '+: SODWH KHDW H[FKDQJHU LV NHSW ZDUP 7KLV WUDQVODWHV LQWR LPPHGLDWH DYDLODELOLW\ RI GRPHVWLF KRW ZDWHU DW DQ\ UHTXLUHG WHPSHUDWXUH OHYHO
7HFKQLFDO 'DWD '+: 3ODWH +HDW ([FKDQJHU
%.$ KHDW H[FKDQJHU SHUIRUPDQFH
'+: VXSSO\ WHPSHUDWXUH IRU %.$  ZLWK PL[HG ZDWHU

'+: VXSSO\ WHPSHUDWXUH

'+: IORZ UDWH 14

7KLV FKDUW LOOXVWUDWHV WKH FKDQJHV LQ WKH RXWOHW WHPSHUDWXUH VXEMHFW WR WKH IORZ UDWH DW WKH WDS
,I JUHDWHU YROXPH PD[ IORZ UDWH WKURXJK KHDW H[FKDQJHU  *30 RI ZDWHU LV UHTXLUHG FROG ZDWHU QHHGV WR EH PL[HG ZKLFK UHGXFHV WKH RXWOHW WHPSHUDWXUH
&XUYH LV RQO\ DSSOLFDEOH IRU D '&: LQOHW WHPSHUDWXUH RI ) DQG D ERLOHU LQSXW RI  0%+ 9LWRGHQV : %.$ 
0D[ UHFRYHU\ UDWH # '+: WHPSHUDWXUH RI )  *30 0LQ IORZ WKURXJK WKH KHDW H[FKDQJHU IRU ERLOHU VWDUW  *30

Vitodens 100-W, B1HA/B1KA Technical Data
HEATING CIRCUIT PUMPS
%XLOWLQ SXPS *UXQGIRV 836 WKUHH VSHHG KHDWLQJ FLUFXLW'+: SURGXFWLRQ SXPS IRU 9LWRGHQV : %+$  DQG %.$  ERLOHUV LQ WKH IDFWRU\ VHWWLQJ WKH SXPS VSHHG LV SUHVHW WR ¶VSHHG WKUHH·
6SHHG 7KUHH 6SHHG 7ZR
6SHHG 2QH

6XSSO\ +HDG 3UHVVXUH

)ORZ

3XPS 0RGHO 5DWHG YROWDJH 5DWHG FXUUHQW
&DSDFLWRU 3RZHU FRQVXPSWLRQ

*UXQGIRV 836 9$& $ PD[ $ PLQ ) : PD[ : PLQ

  
  

%XLOWLQ SXPS *UXQGIRV 836 UHVLGXDO KHDG SUHVVXUH 5HVLGXDO KHDG RI EXLOWLQ SXPS DW VSHHG  IDFWRU\ VHW

3HUIRUPDQFH FKDUW FRXUWHV\ RI *UXQGIRV

6XSSO\ +HDG 3UHVVXUH

)ORZ

15

Vitodens 100-W, B1HA/B1KA Technical Data

SYSTEM DESIGN CONSIDERATIONS

,1 7+( &20021:($/7+ 2) 0$66$&+86(776  WKLV SURGXFW VKDOO EH LQVWDOOHG E\ D OLFHQVHG SOXPEHU
RU JDV ILWWHU  WKH IOH[LEOH FRQQHFWRU LI XVHG PD\ QRW H[FHHG µ  DQ\ OHYHO W\SH VKXWRII XVHG PXVW EH RI WHH KDQGOH W\SH
%RLOHU ORFDWLRQ
$V D GLUHFW YHQW DSSOLDQFH WKH 9LWRGHQV : PD\ EH LQVWDOOHG IRU URRP DLU LQGHSHQGHQW RSHUDWLRQ VHDOHG FRPEXVWLRQ GLUHFW YHQW UHJDUGOHVV RI VL]H DQG YHQWLODWLRQ PHWKRG RI WKH URRP LQ ZKLFK LW LV ORFDWHG
7KH 9LWRGHQV : PD\ EH LQVWDOOHG IRU H[DPSOH LQ WKH PDLQ OLYLQJ DUHD RI D KRXVH LQ QRQYHQWLODWHG XWLOLW\ URRPV FXSERDUGV FORVHWV DQG DOFRYHV ZLWK QR FOHDUDQFH UHTXLUHG IURP FRPEXVWLEOH PDWHULDOV DV ZHOO DV LQ DWWLFV ZLWK D GLUHFW RXWOHW IRU WKH IOXH JDVIUHVK DLU V\VWHP )ROORZ DOO ORFDO DQG QDWLRQDO FRGHV
)OXH JDV V\VWHP
9LHVVPDQQ FRD[LDO 336 3RO\SURS\OHQH  IODPH UHWDUGDQW FRQFHQWULF IOXH JDVIUHVK DLU V\VWHPV DQG WZRSLSH VWDLQOHVV VWHHO&39& V\VWHPV IRU URRP DLU LQGHSHQGHQW RSHUDWLRQ VHDOHG FRPEXVWLRQ DQG VLGH ZDOO YHQWLQJ DUH WHVWHG WR $16, =  &6$  VWDQGDUGV ODWHVW HGLWLRQ DQG DUH FHUWLILHG WRJHWKHU ZLWK WKH 9LWRGHQV : ERLOHU DV D FRQVWUXFWLRQDO XQLW 7KH 9LWRGHQV : ERLOHU PD\ DOVR EH YHQWHG YHUWLFDOO\ RU KRUL]RQWDOO\ XVLQJ D PHWDOOLF $/& VSHFLDO VWDLQOHVV VWHHO RU QRQPHWDOOLF &39& VLQJOHZDOO URRP DLU GHSHQGHQW YHQWLQJ V\VWHP 8/8/& OLVWHG IRU FDWHJRU\ ,9
)RU D PRUH GHWDLOHG GHVFULSWLRQ RI WKH GLUHFW YHQW DQG VLQJOHZDOO YHQW V\VWHP SOHDVH UHIHU WR WKH 9LWRGHQV 9HQWLQJ 6\VWHP ,QVWDOODWLRQ ,QVWUXFWLRQV

6\VWHP OD\RXW
 7KH PD[ ERLOHU ZDWHU WHPSHUDWXUH IRU  VSDFH KHDWLQJ LV ) & '+: SURGXFWLRQ LV ) &
7R PLQLPL]H GLVWULEXWLRQ ORVVHV 9LHVVPDQQ UHFRPPHQGV WKDW WKH KHDWLQJ DQG GRPHVWLF KRW ZDWHU V\VWHPV EH EDVHG RQ D PD[LPXP ERLOHU VXSSO\ WHPSHUDWXUH RI ) &
 'XH WR WKH ORZ UHWXUQ WHPSHUDWXUHV UHTXLUHG IRU JDV FRQGHQVLQJ DYRLG WKH XVH RI PL[LQJ YDOYHV LQ WKH KHDWLQJ FLUFXLW ZKHQHYHU SRVVLEOH
,I PL[LQJ YDOYHV DUH UHTXLUHG HJ IRU PXOWLFLUFXLW V\VWHPV RU XQGHUIORRU KHDWLQJ V\VWHPV RQO\ ZD\ PL[LQJ YDOYHV PD\ EH XVHG
'R QRW XVH ZD\ PL[LQJ YDOYHV LQ D V\VWHP ZLWK FRQGHQVLQJ ERLOHUV
:DWHU FRQQHFWLRQV
9LWRGHQV : ERLOHUV FDQ EH XVHG LQ DQ\ IXOO\ SXPSHG KRW ZDWHU KHDWLQJ V\VWHP 0LQLPXP V\VWHP SUHVVXUH LV  SVLJ  EDU
&KHPLFDO FRUURVLRQ SURWHFWLRQ SURGXFWV &RUURVLRQ GRHV QRW W\SLFDOO\ RFFXU LQ VHDOHG KHDWLQJ V\VWHPV ZKLFK KDYH EHHQ FRUUHFWO\ LQVWDOOHG DQG DUH FRUUHFWO\ RSHUDWHG
0DQ\ PDQXIDFWXUHUV RI SODVWLF SLSHV UHFRPPHQG WKH XVH RI FKHPLFDO DGGLWLYHV ,Q WKLV FDVH RQO\ FRPPHUFLDOO\ DYDLODEOH FRUURVLRQ SURWHFWLRQ SURGXFWV WKDW KDYH EHHQ DSSURYHG IRU ERLOHUV ZLWK GRPHVWLF KRW ZDWHU KHDWLQJ YLD VLQJOHZDOO KHDW H[FKDQJHUV LQVWDQWDQHRXV SODWH KHDW H[FKDQJHUV RU '+: WDQNV PD\ EH XVHG

)OXH JDV WHPSHUDWXUH SURWHFWLRQ
9LHVVPDQQ FRD[LDO 336 3RO\SURS\OHQH  IODPH UHWDUGDQW IOXH SLSHV XVHG IRU WKH 9LWRGHQV : DUH UDWHG IRU PD[ IOXH JDV WHPSHUDWXUHV RI XS WR ) &
)OXH JDV WHPSHUDWXUH SURWHFWLRQ LV DOVR LQFOXGHG DOWKRXJK WKH PD[LPXP SHUPLVVLEOH IOXH JDV WHPSHUDWXUH ZLOO QRW EH H[FHHGHG LQ DQ\ RSHUDWLQJ FRQGLWLRQ RU LQ WKH HYHQW RI PDOIXQFWLRQLQJ

8QGHUIORRU KHDWLQJ V\VWHPV
)RU XQGHUIORRU KHDWLQJ V\VWHPV 9LHVVPDQQ UHFRPPHQGV WKH XVH RI SODVWLF WXELQJ ZLWK DQ R[\JHQ GLIIXVLRQ EDUULHU LQ RUGHU WR SUHYHQW WKH GLIIXVLRQ RI R[\JHQ WKURXJK WXELQJ
,I SODVWLF WXELQJ ZLWKRXW DQ R[\JHQ GLIIXVLRQ EDUULHU LV XVHG LQ XQGHUIORRU KHDWLQJ V\VWHPV 9LHVVPDQQ UHFRPPHQGV WKDW VXFK V\VWHPV EH VHSDUDWHG IURP WKH ERLOHU ZLWK D KHDW H[FKDQJHU

/RZ ZDWHU FXWRII
$ ORZ ZDWHU FXWRII PD\ EH UHTXLUHG E\ ORFDO FRGHV ,I WKH ERLOHU LV LQVWDOOHG DERYH WKH UDGLDWLRQ OHYHO D ORZ ZDWHU FXWRII GHYLFH RI DSSURYHG W\SH PXVW EH LQVWDOOHG LQ DOO LQVWDQFHV $Q DSSURYHG ORZ ZDWHU FXWRII GHYLFH WKDW PHHWV JRYHUQPHQW DQG ORFDO UHJXODWLRQV PXVW EH SURYLGHG E\ WKH KHDWLQJ FRQWUDFWRU
'R QRW LQVWDOO DQ LVRODWLRQ YDOYH EHWZHHQ WKH ERLOHU DQG WKH ORZ ZDWHU FXWRII 7KH 9LWRGHQV : ERLOHU KDV D EXLOWLQ IORZ VZLWFK ZKLFK PD\ EH DFFHSWHG E\ ORFDO FRGHV LQ OLHX RI D ORZ ZDWHU FXWRII

:DWHU &RQGLWLRQV IRU '+: %.$  0HGLD S+ YDOXH  WR  JO\FRO PD[  '+: PD[ KDUGQHVV &KORULGH XS WR  PJ/
+DUGQHVV XS WR  SSP  PD[  NJP OLPH GHSRVLW

16

Vitodens 100-W, B1HA/B1KA Technical Data

SYSTEM DESIGN CONSIDERATIONS

2[\JHQ GLIIXVLRQ EDUULHU XQGHUIORRU WXELQJ
7KH ERLOHU ZDUUDQW\ GRHV QRW FRYHU OHDNV UHVXOWLQJ IURP FRUURVLRQ FDXVHG E\ WKH XVH RI XQGHUIORRU SODVWLF WXELQJ ZLWKRXW DQ R[\JHQ GLIIXVLRQ EDUULHU 6XFK V\VWHPV PXVW KDYH WKH QRQR[\JHQ GLIIXVLRQ EDUULHU WXELQJ VHSDUDWHG IURP WKH ERLOHU ZLWK D KHDW H[FKDQJHU
9LHVVPDQQ UHFRPPHQGV WKH XVH RI XQGHUIORRU SODVWLF WXELQJ ZLWK DQ R[\JHQ GLIIXVLRQ EDUULHU
:DWHU TXDOLW\
7UHDWPHQW IRU ERLOHU IHHG ZDWHU VKRXOG EH FRQVLGHUHG LQ DUHDV RI NQRZQ SUREOHPV VXFK DV ZKHUH D KLJK PLQHUDO FRQWHQW DQG KDUGQHVV H[LVW ,Q DUHDV ZKHUH IUHH]LQJ PLJKW RFFXU DQ DQWLIUHH]H PD\ EH DGGHG WR WKH V\VWHP ZDWHU WR SURWHFW WKH V\VWHP 3OHDVH DGKHUH WR WKH VSHFLILFDWLRQV JLYHQ E\ WKH DQWLIUHH]H PDQXIDFWXUHU
'R QRW XVH DXWRPRWLYH VLOLFDWH EDVHG DQWLIUHH]H 3OHDVH REVHUYH WKDW DQ DQWLIUHH]HZDWHU PL[WXUH PD\ UHTXLUH D EDFNIORZ SUHYHQWHU ZLWKLQ WKH DXWRPDWLF ZDWHU IHHG DQG LQIOXHQFH FRPSRQHQWV VXFK DV GLDSKUDJP H[SDQVLRQ WDQNV UDGLDWLRQ HWF 0D[LPXP DQWLIUHH]H FRQWHQW LV  IRU WKH %+$   DQG  IRU WKH %.$  'R QRW XVH DQWLIUHH]H RWKHU WKDQ VSHFLILFDOO\ PDGH IRU KRW ZDWHU KHDWLQJ V\VWHPV
7KH V\VWHP PD\ DOVR FRQWDLQ FRPSRQHQWV ZKLFK PLJKW EH QHJDWLYHO\ DIIHFWHG E\ DQWLIUHH]H
&KHFN WRWDO V\VWHP IUHTXHQWO\ ZKHQ ILOOHG ZLWK DQWLIUHH]H $GYLVH V\VWHP RSHUDWRUXOWLPDWH RZQHU WKDW V\VWHP LV ILOOHG ZLWK D JO\FRO PL[
7KH KHDWLQJ FRQWUDFWRU PXVW SURYLGH D 06'6 0DWHULDO 6DIHW\ 'DWD 6KHHW IRU WKH DQWLIUHH]H XVHG WR WKH V\VWHP RSHUDWRUXOWLPDWH RZQHU

:DUUDQW\
2XU ZDUUDQW\ GRHV QRW FRYHU GDPDJHV UHVXOWLQJ IURP WKH IROORZLQJ
 LQVWDOODWLRQ RU VHUYLFH E\ XQTXDOLILHG DQG XQOLFHQVHG SHUVRQQHO
 DWWHPSWLQJ WR SHUIRUP DQ\ UHSDLU ZRUN RQ WKH ERLOHU RWKHU WKDQ WKDW PHQWLRQHG LQ WKH ERLOHU OLWHUDWXUH
 WDPSHULQJ ZLWK RU DWWHPSWLQJ WR UHDGMXVW WKH IDFWRU\ VHWWLQJV RI WKH FRPELQDWLRQ JDV YDOYH
 OHDNV UHVXOWLQJ IURP FRUURVLRQ FDXVHG E\ WKH XVH RI XQGHUIORRU SODVWLF WXELQJ ZLWKRXW DQ R[\JHQ GLIIXVLRQ EDUULHU
)RU GHWDLOHG ZDUUDQW\ LQIRUPDWLRQ SOHDVH UHDG ZDUUDQW\ VKHHW VXSSOLHG ZLWK SURGXFW

7RWDO RXWSXW 0%+ 7RWDO +DUGQHVV SSP DV &D&2

!  7RWDO >  > 

!  WR >  > 

! 

>

7KH S+ YDOXH RI WKH KHDWLQJ ZDWHU VKRXOG EH EHWZHHQ  DQG 

17

18

Vitodens 100-W
Low Loss Header
P3

APPLICATION 1
Closely Spaced Tees
P3

Notes/Comments
1. Hydraulically separating the flow of the boiler and system with closely spaced tees or a low loss header, ensures that the boiler and system flows do not affect each other.
2. Refer to component index on Page 5. 3. Since the primary circulator is integrated into boiler,
field installation of a boiler circulator is not required. 4. If not using the DHW ports on the boiler, installer is
required to cap before filling boiler.

Pressure Drop B1HA

Application Code VD1X 1HC1T1ZP.01

19

Vitodens 100-W
Pre-Wired
Notes/Comments
1. Items to the left of the dotted vertical line are factory wired connections. Items wired to the right of the line are field wired.
2. If outdoor weather compensation is not being used, installation of the outdoor temperature sensor is not necessary.

 

APPLICATION 1
Field Wiring
WZ
 
^ W W
sZ d Z

, dZ

UG 3DUW\ 3XPS 5HOD\

5

:

 9$&

7 7 &20

/(' ,1',&$7256
32:(5 =21( 

 9$& ,1387

&20 12

1&

1+   

1&

12 &20



KZZ ^Z
Application Code VD1X 1HC1T1ZP.01

B1HA Boiler Setup
This particular application represents a low mass boiler with a single system loop. Because the system flow requirements may vary, or fall outside of the parameters of the boiler flow, it is recommended to hydraulically separate the system flow from the boiler flow. This can be achieved by using a low loss header or closely spaced tees on the system loop. Upon a call for heat from an external demand such as a thermostat the boiler circulator and the system circulator will be initiated. To program the boiler for this type of application, please complete the following procedure:

Function

Step #

Description

Application Code VD1X 1HC1T1ZP.01

Adjust the Boiler Setpoint Temperature:

1

(No Outdoor Sensor

Connected)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required boiler water temperature is displayed.
Press OK to confirm.

Set and Outdoor Reset Curve: (With Outdoor Sensor Connected)

OR
1 2 3

Tap the x/y button until the begins flashing.
Press OK.
Using the chart below, select the number of the desired reset curve for your application. (value shown on the boiler display will depend on whether the boiler is set to °F or °C)

%RLOHU ZDWHU RU VXSSO\ WHPSHUDWXUH

2XWGRRU WHPSHUDWXUH

4

Press the x/y until the required curve is selected and press OK.

*For more informaiton on how to reconfigure the boiler, please reference page 40.
20

B1HA Boiler Setup Notes/Comments
21

22

Vitodens 100

APPLICATION 2
P4 P3

Notes/Comments
1. A thermostatic mixing valve should be installed to protect the radiant floor heating from receiving excessive hot water.
2. Component Index on pages 5.
3. Since the boiler circulator is integrated, field installation of a circulator is not required for the boiler or indirect DHW.
4. When using a Viessmann AirflowPLUS, the P3 circulator is integrated and controlled by the air handler.

Pressure Drop B1HA

Application Code VD1I 2HC2T2ZP.01

Vitodens 100
Pre-Wired

APPLICATION 2
)LHOG :LULQJ
Field Wiring

, dZ

WZ
, W

UG 3DUW\ 3XPS 5HOD\

5

:

 9$&

7 7 &20

/(' ,1',&$7256
32:(5 =21( 

 9$& ,1387

&20 12

1&

1+  

1&

12 &20



 

K

,t ^Z



 

Notes/Comments

sZ d Z

1. If an aquastat is being used instead of a DHW sensor, reconfiguration of the control will be necessary. Refer to page 40
2. If outdoor weather compensation is not being used, installation of the outdoor temperature sensor is not necessary.

KZZ ^Z

 , ,  Z

Application Code VD1l 2HC2T2ZP.01

23

B1HA Boiler Setup
In this application, you can see a Vitodens 100 paired with an indirect water heater and 2 zones. A safety device such as a thermostatic mixing valve should be added to the infloor circuit to protect the radiant heating from the higher supply water temperatures required for the air handler. This application will prioritize the DHW by diverting flow from the system to the indirect DHW using the diverting valve integrated into the boiler. To set up the boiler for this application you will need to complete the following:

Application Code VD1X 1HC1T1ZP.01

Function
Adjust the Boiler Setpoint Temperature: (No Outdoor Sensor Connected)
Set and Outdoor Reset Curve: (With Outdoor Sensor Connected)

Step #
1 2 3 4
OR 1 2 3

Description
Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required boiler water temperature is displayed.
Press OK to confirm.
Tap the x/y button until the begins flashing.
Press OK.
Using the chart below, select the number of the desired reset curve for your application. (value shown on the boiler display will depend on whether the boiler is set to °F or °C)

%RLOHU ZDWHU RU VXSSO\ WHPSHUDWXUH

2XWGRRU WHPSHUDWXUH

4

Press the x/y until the required curve is selected and press OK.

Set DHW Temperature: (Not available if using

1

an aquastat)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required DHW temperature is displayed.
Press OK to confirm.

*For more informaiton on how to reconfigure the boiler, please reference page 40.
24

B1HA Boiler Setup Notes/Comments
25

26

Vitodens 100

APPLICATION 3
P3 P4

*

Notes/Comments
1. A thermostatic mixing valve should be installed to protect the radiant floor heating from receiving excessive hot water.
2. Component Index on pages 5.
3. Since the boiler circulator is integrated, field installation of a circulator is not required for the boiler or indirect DHW.
4. The B1KA has an integrated expansion vessel built into the boiler that will be sufficient for most systems. If your system requires a larger expansion tank, a secondary tank can be installed on the system.(*)

Pressure Drop B1HA

Application Code VD1C 2HC2T2ZP.01

Vitodens 100
Pre-Wired

APPLICATION 3
)LHOG :LULQJ
Field Wiring

, dZ

WZ
, W
 

UG 3DUW\ 3XPS 5HOD\

5

:

 9$&

7 7 &20

/(' ,1',&$7256
32:(5 =21( 

 9$& ,1387

&20 12

1&

1+  

1&

12 &20



 , ,  Z

 

Notes/Comments
1. When using a Viessmann Airflow Plus, the P4 pump is integrated and controlled by the air handler.
2. If outdoor weather compensation is not being used, installation of the outdoor temperature sensor is not necessary.

sZ d Z

KZZ ^Z
Application Code VD1C 2HC2T2ZP.01

27

B1HA Boiler Setup
Similar to the previous application, this system incorporates a Vitodens 100 Combi boiler. With on demand domestic hot water, this offers an alternative solution to installing a storage type indirect water heater. The integrated circulator and diverting valve allow the boiler to switch from heating and provide up to 3.7GPM of on-demand DHW. To set up the boiler for this application, you will need to complete the following steps:

Application Code VD1C 2HC2T2ZP.01

Function
Adjust the Boiler Setpoint Temperature: (No Outdoor Sensor Connected)
Set and Outdoor Reset Curve: (With Outdoor Sensor Connected)

Step #
1 2 3 4
OR 1 2 3

Description
Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required boiler water temperature is displayed.
Press OK to confirm.
Tap the x/y button until the begins flashing.
Press OK.
Using the chart below, select the number of the desired reset curve for your application. (value shown on the boiler display will depend on whether the boiler is set to °F or °C)

%RLOHU ZDWHU RU VXSSO\ WHPSHUDWXUH

2XWGRRU WHPSHUDWXUH

4

Press the x/y until the required curve is selected and press OK.

Set DHW Temperature: (Not available if using

1

an aquastat)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required DHW temperature is displayed.
Press OK to confirm.

*For more informaiton on how to reconfigure the boiler, please reference page 40.
28

B1HA Boiler Setup Notes/Comments
29

30

Vitodens 100

APPLICATION 4

P3

Z4 Z3 Z2 Z1
Notes/Comments
1. Component Index on pages 5. 2. A variable speed circulator will automatically adjust
to opening and closing zones. This ensures proper flow regardless of how many zones are open. 3. If a fixed speed circulator is being used in this application, it would be necessary to install a differential pressure bypass valve. This ensures a correct flow through a zone under changing loads.

Pressure Drop B1HA

Application Code VD1l 1HC1T4ZV.01

Vitodens 100
Pre-Wired

APPLICATION 4
Field Wiring

WZ

W
s
dZ
& ^
s

,t ^Z
 
  ^

 

Notes/Comments
1. If using a fixed speed pump, it is recommended that a zone control relay be installed to control the operation of the pump and zone valves.
2. If outdoor weather compensation is not being used, installation of the outdoor temperature sensor is not necessary.

sZ d Z

Z  Z  Z  Z 
KZZ ^Z
Application Code VD1l 1HC1T4ZV.01

31

B1HA Boiler Setup

In this system you have a Vitodens 100 with indirect water heater and a four zone system controlled via zone valves. Upon a call for heat a zone valve opens, closing the end switch on the valve, and initiates the boiler. In the event there is a call for DHW, the boilers internal pump and diverting valve, will redirect the water to the indirect water heater. This allows the boiler to commit all energy produced to the production of domestic hot water. Once satisfied, the diverting valve will return to its home position and continue supplying heat to the heating system until satisfied. To set up the boiler for this application you will need to complete the following:

Application Code VD1I 1HC1T4ZV.01

Function

Step #

Description

Adjust the Boiler Setpoint Temperature:

1

(No Outdoor Sensor

Connected)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required boiler water temperature is displayed.
Press OK to confirm.

OR

Set and Outdoor Reset Curve: (With Outdoor Sensor Connected)

1

Tap the x/y button until the begins flashing.

2

Press OK.

3

Using the chart below, select the

number of the desired reset curve for

your application.

(value shown on the boiler display will depend

on whether the boiler is set to °F or °C)

%RLOHU ZDWHU RU VXSSO\ WHPSHUDWXUH

2XWGRRU WHPSHUDWXUH

4

Press the x/y until the required curve is selected and press OK.

Set DHW Temperature: (Not available if using

1

an aquastat)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required DHW temperature is displayed.
Press OK to confirm.

*For more informaiton on how to reconfigure the boiler, please reference page 40.
32

B1HA Boiler Setup Notes/Comments
33

34

Vitodens 100

APPLICATION 5

P5

P3

P6

P4

Notes/Comments
1. Component Index on pages 5. 2. Always consider the electrical consumption
associated with zoning a system with circulators. Often there are more efficient alternatives which could be considered when designing a system. 3. Since the primary circulator is integrated into boiler, field installation of a boiler circulator is not required for the boiler and indirect DHW.

Pressure Drop B1HA

Application Code VD1l 1HC1T4ZP.01

Vitodens 100
Pre-Wired

APPLICATION 5
Field Wiring
WZ

Z Z Z Z









,t ^Z
 

6/$9( 35,25,7<
5(6(7 35,0$5< 3803
3267 385*( 35,25 3527(&7 3803 (;(5&,6(
 6(&   :. /2: /,0,7 =&

0$67(5 2)) 1250$/ 2)) 2)) 2)) 2))  0,1   +5 2))

;; 0$,1 (1' 6:,7&+
$&&(6625< 3257

)86(  $03

)86(  $03

)86(  $03

5:& 5:& 5:&
=21( =21( =21(
7+(50267$76  9$&
DZ )285 =21( (;3$1'$%/( 6:,7&+,1* 5(/$<
ZZ

5:& =21(

)86(  $03

)86(  $03

)86(  $03

 1(7
/(' ,1',&$7256
32:(5 =21(  =21(  =21(  =21( 

 9$&

 92/7 &,5&8/$7256

=& =5 35,0$5< =21( =21( =21(

++1+1+1+1+

=21( 1+

65 (;3

,1387  9$& 1+

 

Notes/Comments

dsZZZ

1. If an aquastat is being used instead of a DHW sensor, reconfiguration of the control will be necessary. Refer to page 40
2. If outdoor weather compensation is not being used, installation of the outdoor temperature sensor is not necessary.

KZZ ^Z

W W W W

WZ

Application Code VD1l 1HC1T4ZP.01

35

B1HA Boiler Setup

Similar to the previous application, this system utilizes circulators instead of zone valves. Upon a call for heat, the multizone control initiates the associated circulator and sends a signal to the boiler's. Once the boiler has received this signal, the integrated boiler pump starts and the boiler fires. If there is a call for DHW during a heating cycle, the boiler's integrated diverting valve will transition into DHW mode and a new target setpoint will be established. Once the DHW tank is satisfied, the diverting valve will switch back into heating mode and supply heat to the low loss header. To set up the boiler for this application you will need to complete the following:

Application Code VD1I 1HC1T4ZP.01

Function

Step #

Description

Adjust the Boiler Setpoint Temperature:

1

(No Outdoor Sensor

Connected)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required boiler water temperature is displayed.
Press OK to confirm.

OR

Set and Outdoor Reset Curve: (With Outdoor Sensor Connected)

1

Tap the x/y button until the begins flashing.

2

Press OK.

3

Using the chart below, select the

number of the desired reset curve for

your application.

(value shown on the boiler display will depend

on whether the boiler is set to °F or °C)

%RLOHU ZDWHU RU VXSSO\ WHPSHUDWXUH

2XWGRRU WHPSHUDWXUH

4

Press the x/y until the required curve is selected and press OK.

Set DHW Temperature: (Not available if using

1

an aquastat)

2

3

4

Tap the x/y button until the begins flashing.
Press OK. Press the x/y until the required DHW temperature is displayed.
Press OK to confirm.

*For more informaiton on how to reconfigure the boiler, please reference page 40.
36

B1HA Boiler Setup Notes/Comments
37

38

Vitodens 100

MICROLOAD

Application Code
Microload
Notes/Comments
1. Component Index on pages 5. 2. To ensure correct operation, install
flow check valves according to this diagramheating and DHW.

What is a Microload?
A Microload is typically considered a zone that has an output substantially less than the boiler's lowest firing rate. Even when firing at its lowest input, the boiler will short cycle putting added stress on all the components and decreasing efficiency.

Vitodens 100

MICROLOAD

Application Code Microload

Solution
Piping a "Microload" in this manner, prevents the boiler from short cycling. Upon a call for heat, the circulator starts up and draws heat out of the indirect water heater. As the temperature in the water heater decreases, the boiler senses this drop in temperature and proceeds to heat the tank back up. Because of the larger volume of water, this extends the boiler's run cycle and allows it to operate at a more efficient state.

39

How-To Guide

/HJHQG
Pressure gage
" LCD display unit
 Power switch ON/OFF
/HJHQG A Display value or fault code B Temperature in °F/°C (with the display value) C Heating mode D DHW heating E Display value or fault code F Fault indicator G Burner fault reset H Temperature in °F/°C (with the display value) I On-screen buttons J Commissioning setting active (only for contractors) K DHW comfort function active (only for B1KA) L Current burner output (each bar = 20%) M DHW comfort function not active (only for B1KA) N Service setting active (only for B1HA) O Burner in operation

Operation

Step #

Description

Put Boiler into Emissions Test/ Service

1

Mode:

2

3

4

OR

Access 14 Parameter Options:

1

2

3

Tap the MODE button until the SERV begins flashing. Press OK. Press the x/y until the required firing rate is displayed. Press OK to confirm.
Press the MODE button until CONFI begins flashing. Press OK ,and P will appear in the left hand display. Press the x/y until the display reaches 12 and press OK. This now gives the user access to the various functional changes below.

40

How-To Guide

,WHP  
  
      

)XQFWLRQ

6HWWLQJ 2SWLRQV

'HVFULSWLRQ

)LOOLQJ

  )LOO PRGH 2))   )LOO PRGH 21

$IWHU SUHVVLQJ ¶2.· WKH ILOOLQJ IXQFWLRQ LV DFWLYH 7KLV SURFHVV ZLOO DXWRPDWLFDOO\ WHUPLQDWH DIWHU  PLQ

5HGXFH PD[ KHDWLQJ RXWSXW

 /RZ ILUH     0RGXODWLRQ 5DQJH     +LJK ILUH  

´7KH PD[ KHDWLQJ RXWSXW FDQ EH DGMXVWHG DFFRUGLQJ WR WKH UHTXLUHPHQWV RI WKH V\VWHP 7KH DGMXVWHG KHDWLQJ RXWSXW VKRXOG EH WHVWHG E\ PHDVXULQJ WKH JDV WKURXJKSXW

$OWLWXGH VHWWLQJ
)XHO 7\SH 3DUDPHWHU UHVHW

   RU  IW  P   'R 1RW $GMXVW   !  IW  P   1DWXUDO *DV   /3*   9LWRGHQV : %.$   9LWRGHQV : %+$   9LWRGHQV : %+$   'R 1RW $GMXVW

´$GMXVWV WKH ERLOHU IRU KLJK DOWLWXGH RSHUDWLRQ
´7KH JDV W\SH FDQ EH FRQYHUWHG IURP QDWXUDO JDV WR /3* &RQYHUVLRQ NLW LV UHTXLUHG 7KH SDUDPHWHU LV IL[HG EDVHG RQ WKH ERLOHU W\SH DQG VL]H :KHQ UHSODFLQJ WKH ERLOHU FRQWURO UHIHU WR ERLOHU UDWLQJ RQ WKH ERLOHU WR VHW PRGHO DQG VL]H $IWHU DGMXVWLQJ WKH SDUDPHWHU F\FOH WKH ERLOHU SRZHU DQG YHULI\ WKH SDUDPHWHU VHWWLQJ

2XWGRRU 7HPS 6HQVRU %XWWRQ 7RQH
%DFNOLJKW 'LVSOD\  6WDQGE\ 0RGH

  17& . 2KP   'R QRW $GMXVW   2Q   2II   'LPPHG   2II QR EDFN

´7KH ULJKW RXWVLGH WHPS VHQVRU KDV WR EH DGMXVWHG
´7KH VLJQDO WRQH IRU GLVSOD\ RSHUDWLRQ FDQ EH VZLWFKHG RII ´7KH GLVSOD\ EDFNOLJKWLQJ IRU VWDQGE\ LV HLWKHU GLPPHG RU RII

'LVSOD\ &RQWUDVW 

(FR&RPIRUW %.$ 2QO\

  (FR   &RPIRUW

7KH GLVSOD\ FRQWUDVW LV DGMXVWDEOH IURP  WR  7KH KLJKHU WKH YDOXH WKH JUHDWHU WKH FRQWUDVW
´7KH FRPIRUW IXQFWLRQ PDNHV '+: DYDLODEOH IDVWHU DW WKH VHOHFWHG VHW '+: WHPSHUDWXUH 2QO\ DYDLODEOH 9LWRGHQV : %.$

7HPSHUDWXUH 8QLW   &   )

´7KH WHPSHUDWXUH GLVSOD\HG FDQ EH VHW WR & &HOVLXV WR ) )DKUHQKHLW

'+: VHQVRU W\SH   '+: 7HPS 6HQVRU 17& ´7KH ERLOHU HLWKHU ZRUNV ZLWK D WDQN VHQVRU 17&

%+$

. 2KP

N2KP  6XSSOLHG RU ZLWK D WDQN DTXDVWDW ILHOG

  $TXDVWDW 'U\ &RQWDFW VXSSOLHG

'HIDXOW 6HWWLQJ
 
 
      

41

The Viessmann Group
The Viessmann Group is one of the leading international manufacturers of heating, industrial and refrigeration systems. Founded in 1917, the family business employs approximately 12,000 employees worldwide and generates 2.25 billion Euro in annual group sales.
Viessmann has a strong international outlook ­ it maintains 22 production companies in 11 countries, subsidiaries and representatives in 74 countries, and a total of 120 sales offices worldwide. Exports account for 54 percent of sales.

and DHW storage tanks ­ all designed to achieve superior performance, reliability and energy savings.
Accountability for the environment and society, fairness when dealing with business partners as well as the pursuit of perfection and maximum efficiency in all business transactions are key values for Viessmann ­ as a company, and as individuals. This, together with the products and services we offer, allows us to offer our customers the benefit and added value of a strong brand.

For three generations, Viessmann has been providing comfortable, efficient and environmentallyresponsible heating solutions, tailored to the needs of the market. With ongoing research and development and a focus on product innovation, Viessmann has pioneered technologies that have continuously set standards and made the company into a technological innovator and pacesetter of the entire industry.
With the current comprehensive product range, Viessmann is offering a multi-level program of high-tech, state-of-the-art heating products. Wall-mounted gas-fired condensing boilers, floor-standing oil ­ or gasfired hot water heating boilers, solar thermal systems, control technology

Viessmann Manufacturing Company Inc. 750 McMurray Rd. Waterloo, ON N2V 2G5, Canada 1-800-387-7373 info@viessmann.ca www.viessmann.ca
Viessmann Manufacturing Company Inc. 6350 204th St. Langley, BC V2Y 2V1, Canada 1-877-853-3288 info-bc@viessmann.ca www.viessmann.ca
Viessmann Manufacturing Company Inc. USA 45 Access Rd. Warwick, RI 02886, USA 1-800-288-0667 info@viessmann-us.com www.viessmann.com

42

Global presence, local commitment.
43

Viessmann Manufacturing Company Inc. Waterloo, ON Canada 1-800-387-7373 www.viessmann.ca
Viessmann Manufacturing Company Inc. USA Warwick, RI 02886, USA 1-800-288-0667 info@viessmann-us.com www.viessmann.com

Technical information subject to change without notice. Printed in Canada

579 6123 -01 03/2017


Acrobat Distiller 9.0.0 (Windows)