Overview
This document provides the specifications for Unitronics UniStream™ I/O expansion modules. These modules are compatible with UniStream™ programmable logic controllers. They can be mounted on the back of the UniStream™ HMI to create an all-in-one HMI+PLC unit, or installed on a standard DIN rail using a local expansion kit. Installation guides are available in the technical library at: www.pl-systems.fr.
Model Reference
This datasheet references the models presented in the following tables:
Part | UID-0808R | UID-0016R | UID-0808T | UID-0016T | UID-1600 |
Inputs | 8 | 8 | 8 | 16 | 16 |
Type | Pnp or Npn, 24VDC | Pnp or Npn, 24VDC | Pnp or Npn, 24VDC | Pnp or Npn, 24VDC | Pnp or Npn, 24VDC |
Outputs | 8 | 16 | 8 | 16 | 16 |
Type | Relay, 24VDC (power) | Transistor, Pnp, 24VDC | |||
Isolation | All inputs and outputs are isolated |
Inputs | UID-1600 | UID-0808R, UID-0808T |
Number of inputs | 16 | 8 |
Type | Npn or Pnp | Npn or Pnp |
Isolation group | Four groups of 4 inputs each | Two groups of 4 inputs each |
Isolation voltage | ||
Bus group | 500VAC for 1 minute | |
Group to group | 500VAC for 1 minute | |
Input to input within the group | None | |
Nominal voltage | 24VDC @ 6mA | |
Input voltage | ||
Npn/Pnp | ON state: 15-30VDC, 4mA minimum OFF state: 0-5VDC, 1mA maximum | ON state: 15-30VDC, 4mA minimum OFF state: 0-5VDC, 1mA maximum |
Nominal impedance | 4kΩ | 4kΩ |
Filter | Adjustable between 1 and 32 ms (individually per group) |
Outputs
Outputs | UID-0808R | UID-0016R | UID-0808T | UID-0016T |
Number of outputs | 8 | 16 | 8 | 16 |
Output type | Relay, SPST-NO (Form A) | Transistor, Pnp | ||
Isolation groups | Two groups of 4 outputs each | Four groups of 4 outputs each | One group of 8 outputs | One group of 16 outputs |
Isolation voltage | ||||
Bus group | 1,500VAC for 1 minute | 1,500VAC for 1 minute | 500VAC for 1 minute | 500VAC for 1 minute |
Group | 1,500VAC for 1 minute | |||
Output to group | None | None | None | None |
Output supply | ||||
Bus | 1,500VAC for 1 minute | 500VAC for 1 minute | 500VAC for 1 minute | |
Current | 2A maximum per output (Resistive load) | 0.5A maximum per output. UID-0016T: total output current for 04-07 and 012-015 must not exceed 2A. | ||
Voltage | 250VAC / 30VDC maximum | See output supply specifications | ||
Minimum load | 1mA, 5VDC | Maximum 0.5V | ||
ON voltage drop | - | 10μA maximum | ||
OFF leakage current | - | |||
Switching time | Maximum 10ms | Activate/deactivate: 80µs max. (Load resistance < 4kΩ) | ||
Short-circuit protection | None | Yes | ||
Lifespan (1) | 100k operations with maximum load |
Output Supply | ||||
UID-0808R | UID-0016R | UID-0808T | UID-0016T | |
Normal operating voltage | 24VDC | 24VDC | 24VDC | 24VDC |
Operating voltage | 20.4 – 28.8VDC | 20.4 – 28.8VDC | 20.4 – 28.8VDC | 20.4 – 28.8VDC |
Maximum current consumption | 40mA@24VDC | 80mA@24VDC | 30mA@24VDC(2) | 60mA@24VDC(2) |
I/O / COM Bus | |||||
UID-0808R | UID-0016R | UID-0808T | UID-0016T | UID-1600 | |
Maximum Bus consumption | 100mA | 90mA | 110mA | 120mA | 100mA |
LED Indicators
LED | Input State | Output State |
Input LED | Green | Input State |
Output LED | Green | Output State |
Status LED | A triple color LED. Indications are as follows: | |
Color | LED State | Status |
Green | On | Normal Operation |
Slow Blink | Startup | |
Fast Blink | OS Initialization | |
Green/Red | Slow Blink | Configuration Incompatibility |
Red | Slow Blink | No I/O exchange |
Fast Blink | Communication Error | |
Orange | Fast Blink | OS Update |
Environment
Parameter | Specification |
Protection | IP20, NEMA1 |
Operating temperature | -20°C to 55°C |
Storage temperature | -30°C to 70°C |
Relative Humidity (HR) | 5% to 95% (non-condensing) |
Operating altitude | 2,000m |
Shock | IEC 60068-2-27, 15G, 11ms duration |
Vibration | IEC 60068-2-6, 5Hz to 8.4Hz, constant amplitude of 3.5 mm, 8.4Hz to 150Hz, 1G acceleration. |
Dimensions
Dimensions | UID-0808R | UID-0016R | UID-0808T | UID-0016T | UID-1600 |
Weight | 0.15 Kg | 0.17 Kg | 0.13 Kg | 0.13 Kg | 0.13 Kg |
Size | Identical for all models, as shown in the images below |
Top View
[Diagram showing top view of the module with dimensions]
Side View
[Diagram showing side view of the module with dimensions]
Front View
[Diagram showing front view of the module with dimensions]
Notes
- The lifespan of relay contacts depends on their usage and installation. The installation guide provides the procedure, which must be followed, for using relay contacts with long cables or inductive loads.
- Current consumption does not include load current.
The information contained in this document reflects the products at the time of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion and without notice, to discontinue or change the features, designs, materials and other specifications of its products, permanently or temporarily, or to withdraw its product range from the market.
All information in the document is provided without warranty of any kind, either express or implied, including but not limited to any implied warranties of merchantability or fitness for a particular purpose and non-infringement. Unitronics assumes no responsibility for any consequences arising from the use or interpretation of its information.
The names, brands, logos and service marks presented in the document, including their design, are the property of Unitronics (1989) (R"G) Ltd or third parties. You are not authorized to use them without the prior written consent of Unitronics or the third party that owns them.
PL Systems Unitronics France - info@pl-systems.fr
Version: 08/02/2016