Functional Devices Network Compatible Relays
RIBTW2401B-BC
Enclosed BACnet® MS/TP Network Relay Device; One Binary Output (20 Amp Relay SPDT + Override); One Binary Input (Dry Contact, Class 2); 24 Vac/dc or 120 Vac Power Input, Optional End of Line Resistor (EOL) Included.
Wiring Diagram:
Diagram shows connections for Binary Input (Dry Contact), MS/TP communication lines (A, B), 24 Vac/dc power, and relay contacts (Common, N/O, N/C). Includes DIP switches for Baud Rate, MS/TP Address, and Relay Override.
RIBTW2402B-BC
Enclosed BACnet® MS/TP Network Relay Device; One Binary Output (20 Amp Relay SPDT + Override); One Binary Input (Dry Contact, Class 2); 24 Vac/dc or 208-277 Vac Power Input, Optional End of Line Resistor (EOL) Included.
Wiring Diagram:
Diagram shows connections for Binary Input (Dry Contact), MS/TP communication lines (A, B), 24 Vac/dc or 208-277 Vac power, and relay contacts (Common, N/O, N/C). Includes DIP switches for Baud Rate, MS/TP Address, and Relay Override.
Image shows the physical unit with its enclosure, ports, and labeling.
SPECIFICATIONS
General Specifications
- # Relays & Contact Type: One (1) SPDT Continuous Duty Coil
- Expected Relay Life: 10 million cycles minimum mechanical
- Operating Temperature: -30 to 140° F
- Humidity Range: 5 to 95% (noncondensing)
- Operate Time: 18ms
- Green LED: Network Communication
- Red LED: Relay Status
- Dimensions: 4.00" x 4.00" x 1.80" with .50" NPT Nipple
- Wires: 16", 600V Rated
- Approvals: UL Listed, UL916, C-UL
- Housing Rating: UL Accepted for Use in Plenum, NEMA 1
- Gold Flash: No
- Relay Override Switch: DIP Switch Control
- Network Media: Twisted Pair 22-24AWG, shielded recommended
- Terminations: Functional Devices product installed at both ends of the MS/TP network - Use 120 Ω end of line resistors. All other cases - Follow instructions from the device installed at the end of the MS/TP network.
- Polarity: Network is polarity sensitive
- Baud Rate: 9600, 19200, 38400, 57600, 76800, 115200 (DIP Switch Selectable)
Contact Ratings
- 20 Amp Resistive @ 277 Vac
- 20 Amp Ballast @ 277 Vac
- 16 Amp Electronic Ballast @ 277 Vac (N/O)
- 10 Amp Tungsten @ 120 Vac (N/O)
- 1110 VA Pilot Duty @ 277 Vac
- 770 VA Pilot Duty @ 120 Vac
- 2 HP @ 277 Vac
- 1 HP @ 120 Vac
Power Input Ratings
- 81 mA @ 24 Vdc
- 111 mA @ 24 Vac
- 96 mA @ 120 Vac (RIBTW2401B-BC)
- 121 mA @ 208-277 Vac (RIBTW2402B-BC)
Power Input
- 24 Vac/dc; 120 Vac; 50/60 Hz (RIBTW2401B-BC)
- 24 Vac/dc; 208-277 Vac; 50/60 Hz (RIBTW2402B-BC)
BACnet® Details
- MS/TP Address & Baud Rate must be set prior to power up via DIP switches.
- Device ID will default to 277XXX where XXX is the MS/TP Address.
- Examples: MS/TP Address - 004, Device ID - 277004; MS/TP Address - 121, Device ID - 277121
- Device ID can be changed via network command. Once changed, it will no longer default to 277XXX. (MS/TP Address & Device ID must be unique.)
- This model utilizes: BO 1 (Relay output), BI 1 (Dry contact binary input).
- Device Instance changed via Object Identifier Property of Device Object
- PIC Statement available on website: http://www.functionaldevices.com/pdf/pics/RIBTW240xB-BC_PICS.pdf
DIP Switch Configuration
DIP Switches for Baud Rate and MS/TP Address
DIP SWITCHES* | BAUD RATE | DIP SWITCHES* | RELAY STATE** | |||
---|---|---|---|---|---|---|
8 | 9 | 10 | 11 | 12 | ||
0 | 0 | 0 | 9600 | 1 | 0 | Auto |
0 | 0 | 1 | 19200 | X | 1 | Override on |
0 | 1 | 0 | 38400 | 0 | 0 | Override off |
0 | 1 | 1 | 57600 | |||
1 | 0 | 0 | 76800 | |||
1 | 0 | 1 | 115200 |
*0 = Open ; 1 = Closed
**Device must be powered for override
All other combinations = 9600 baud
Notes
- When connecting 24 Vac to both the RIB(s) and a half-wave device, damage to device can occur. Option 1: Use separate transformers for each device. Option 2: Add diode between devices, see Option 2 note below.
Diagram illustrates Option 2 for 24 Vac interconnection with a diode.
Binary Input Usage
Dry contact binary input is a general purpose input that is not tied to the relay internally. Can be used with any dry contact switching device, such as a current sensor, to report back to the network.