Goodman MS15 High-Efficiency Mini-Split System

An overview of the Goodman MS15 series of high-efficiency mini-split systems, featuring R-410A refrigerant and DC Inverter technology.

Product Features

Nomenclature

The model nomenclature indicates key features of the system:

Specifications for Air Conditioners

INDOOR MODELS
OUTDOOR MODELS
MSC093E15AX
MSC093E15MC
MSC123E15AX
MSC123E15MC
MSC183E15AX
MSC183E15MC
MSC243E15AX
MSC243E15MC
AHRI #5677748567774956777505677751
CAPACITIES
CoolingBtu/h9,00012,00018,00022,000
SEER / EER15 / 915 / 915 / 915 / 9
ELECTRICAL DATA
Power SupplyPh-V-Hz115 V~ 60 Hz, 1 Ph208-230 V~ 60 Hz, 1 Ph208-230 V~ 60 Hz, 1 Ph208-230 V~ 60 Hz, 1 Ph
MCAA197.51214
Max FuseA30153025
Moisture RemovalL/h11.21.82.4
Compressor TypeRotaryRotaryRotaryRotary
INDOOR FAN MOTOR
Blower RLA0.630.230.360.56
Blower LRA635174.4124
InputW464358.580.5
Speed (Hi/Mi/Lo)r / min1200 / 1050 / 8501200 / 1050 / 8001250 / 1100 / 8001200 / 1100 / 900
Airflow (Hi/Mi/Lo)m³/h480/420/320600/530/400750/660/4801250/1150/950
Indoor Noise Level (Hi/Mi/Lo)dB(A)39/35/2939/35/3142/39/3147/45/39
OUTDOOR FAN MOTOR
InputW64/4775/66119/96136/130
CapacitoruF32.5 / 6.02.52.5
Speedr / min860 / -- / 660940 / -- / 835860 / -- / 680930 / -- / 830
Airflowm³/h1,4001,9002,3002,700
Outdoor Noise LeveldB(A)56555959
REFRIGERANT DATA
Refrigerant Chargeg900 g650 g850 g1180 g
oz31.822.9329.941.6
Refrigerant TypeR-410AR-410AR-410AR-410A
Design PressureMPa550/340 PSIG550/340 PSIG550/340 PSIG550/340 PSIG
Connection Wiring16#16#16#16#
Thermostat TypeRemote ControlRemote ControlRemote ControlRemote Control
Operation Temperature (Cooling/ Heating) (°C)Indoor≥ 17 / -.≥ 17 / -.≥ 17 / -.≥ 17 / -.
Outdoor-15 ~ 50 / -.-15 ~ 50 / -.-15 ~ 50 / -.-15 ~ 50 / -.
Stuffing Quantity (Set) (20'/40'/40'HQ)111/252/290111/239/27396/200/23170/143/158

Specifications for Heat Pumps

INDOOR MODELSMSH093E15AXMSH123E15AXMSH183E15AXMSH243E15AX
OUTDOOR MODELSMSH093E15MCMSH123E15MCMSH183E15MCMSH243E15MC
AHRI #5677752567775356777545677755
CAPACITIES
Cooling / HeatingBtu/h9,000 / 9,00012,000 / 12,00018,000 / 18,00022,000 / 22,000
SEER / EER15 / 915 / 915 / 915 / 9
HSPF8.28.28.28.2
ELECTRICAL DATA
Power SupplyPh-V-Hz208-230V 60 Hz, 1Ph208-230V 60 Hz, 1Ph208-230V 60 Hz, 1Ph208-230V 60 Hz, 1Ph
MCAA197.51214
Max FuseA30153025
Moisture RemovalL / h11.21.82.4
Compressor TypeRotaryRotaryRotaryRotary
INDOOR FAN MOTOR
Blower RLA0.630.230.360.56
Blower LRA635174.4124
InputW464358.580.5
Speed (Hi/Mi/Lo)r / min1200 / 1050 / 8501200 / 1050 / 8001250 / 1100 / 8001200 / 1100 / 900
Airflow (Hi/Mi/Lo)m³ / h480/420/320600/530/400750/660/4801250/1150/950
Indoor Noise Level (Hi/Mi/Lo)dB(A)39/35/2939/35/3142/39/3147/45/39
OUTDOOR FAN MOTOR
InputW64/4775/66119/96136/130
CapacitoruF32.5 / 6.02.52.5
Speedr / min860 / -- / 660940 / -- / 835860 / -- / 680930 / -- / 830
Airflowm³ / h1,4001,9002,3002,700
Outdoor Noise LeveldB(A)56555959
REFRIGERANT DATA
Refrigerant Chargeg900 g650 g850 g1180 g
oz31.822.9329.941.6
Refrigerant TypeR-410AR-410AR-410AR-410A
Design PressureMPa550/340 PSIG550/340 PSIG550/340 PSIG550/340 PSIG
Connection Wiring16#16#16#16#
Thermostat TypeRemote ControlRemote ControlRemote ControlRemote Control
Operation Temperature (Cooling/ Heating) (°C)Indoor≥ 17 / ≤ 30≥ 17 / ≤ 30≥ 17 / ≤ 30≥ 17 / ≤ 30
Outdoor-15 ~ 50 /-15 ~ 30-15 ~ 50 /-15 ~ 30-15 ~ 50 /-15 ~ 30-15 ~ 50 /-15 ~ 30
Stuffing Quantity (Set) (20'/40'/40'HQ)111/252/290111/239/27396/200/23170/143/158

Air Conditioning Dimensions & Shipping Weights

Indoor Unit Dimensions:

INDOOR MODELMSC092E15AXMSC123E15AXMSC183E15AXMSC243E15AX
OUTDOOR MODELMSC092E15MCMSC123E15MCMSC183E15MCMSC243E15MC
INDOOR UNITS
Dimensions (W*H*D)mm inch680 x 178 x 255
26.77 x 7.01 x 10.04
770 x 188 x 255
30.31 x 7.40 x 10.04
905 x 198 x 275
35.63 x 7.80 x 10.83
1030 x 218 x 315
40.55 x 8.58 x 12.40
Packing (W*H*D)mm inch745 x 255 x 330
29.33 x 10.04 x 12.99
835 x 265 x 330
32.87 x 10.43 x 12.99
970 x 270 x 345
38.19 x 10.63 x 13.58
1115 x 395 x 300
43.90 x 15.55 x 11.81
Net/Gross weightlb (Kg)15.5/ 17.6 (7 / 8)16.5/ 20.95 (7.5 / 9.5)19.85/ 25.35 (9 / 11.5)90.35/ 137.35 (41 / 62.3)
OUTDOOR UNITS
Dimensions (W*H*D)mm inch660 x 265 x 540
25.98 x 10.43 x 21.26
780 x 250 x 540
30.71 x 9.84 x 21.26
760 x 285 x 590
29.92 x 11.22 x 23.23
845 x 320 x 700
33.27 x 12.60 x 27.56
Packing (W*H*D)mm inch790 x 355 x 620
31.10 x 13.98 x 24.41
910 x 335 x 585
35.83 x 13.19 x 23.03
887 x 355 x 645
34.92 x 13.98 x 25.39
965 x 395 x 755
37.99 x 15.55 x 29.72
Net/Gross weightlb (Kg)62.85/ 69.5 (28.5 / 31.5)66.15/ 70.55 (30 / 32)82.65/88.15 (37.5 / 40)103.6/ 111.35 (47 / 50.5)
PIPING
Max. pipe lengthm / ft20 / 65.620 / 65.625 / 8225 / 82
Max. Level differencem / ft8 / 26.258 / 26.2510 / 35.810 / 35.8
Piping (Liquid / Gas)mm (inch)Φ6.35 / Φ9.52(1/4" / 1/4")Φ6.35 / Φ9.52(1/4" / 1/4")Φ6.35 / Φ12.7(1/4" / 1/4")Φ9.52 / Φ15.9(1/4" / 1/4")

Outdoor Unit Installation Dimensions:

MODELOutdoor Unit DimensionsMounting Dimensions
Inches/mm (L1xHxW1)L2 (mm)W2 (mm)
MS*09*E1526" x 21" x 10.5"
660 x 540 x 265
19"
481
11"
276
MS*12*E1531" x 21" x 10"
780 x 540 x 250
21.5"
549
11"
276
MS*18*E1530" x 23" x 11"
760 x 590 x 285
21"
530
11.5"
290
MS*24*E1533" x 27.5" x 12.5"
840 x 700 x 320
22"
560
13"
335

Heat Pump Dimensions & Shipping Weights

Indoor Unit Dimensions:

INDOOR MODELMSH092E15AXMSH123E15AXMSH183E15AXMSH243E15AX
OUTDOOR MODELMSH092E15MCMSH123E15MCMSH183E15MCMSH243E15MC
INDOOR UNITS
Dimensions (W*H*D)mm680x178x255770x188x255905x198 x2751030x218x315
inch26.77x7.01x10.0430.31x7.40x10.0435.63x7.80x10.8340.55x8.58x12.40
Packing (W*H*D)mm745x255x330835x265x330970x270x3451115x395x300
inch29.33x10.04x12.9932.87x10.43x12.9938.19x10.63x13.5843.90x15.55x11.81
Net/Gross weightlb (Kg)15.5/ 17.6 (7 / 8)16.5/ 20.95 (7.5 / 9.5)19.85/ 25.35 (9 / 11.5)90.35/ 137.35 (41 / 62.3)
OUTDOOR UNITS
Dimensions (W*H*D)mm660x265x540780x250x540760x285x590845x320x700
inch25.98x10.43x21.2630.71x9.84x21.2629.92x11.22x23.2333.27x12.60x27.56
Packing (W*H*D)mm790x355x620910x335x585887x355x645965x395x755
inch31.10x13.98x24.4135.83x13.19x23.0334.92x13.98x25.3937.99x15.55x29.72
Net/Gross weightlb (Kg)62.85/ 69.5 (28.5 / 31.5)66.15/ 70.55 (30 / 32)82.65/ 88.15 (37.5 / 40)103.6/ 111.35 (47 / 50.5)
PIPING
Max. pipe lengthm / ft20 / 65.620 / 65.625 / 8225 / 82
Max. Level differencem / ft8 / 26.258 / 26.2510 / 35.810 / 35.8
Piping (Liquid / Gas)mm(")Φ6.35/Φ9.52(¼"/¾")Φ6.35/Φ9.52(¼"/¾")Φ6.35/Φ12.7(¼"/½")Φ9.52/Φ15.9(¾"/¾")

Outdoor Unit Installation Dimensions

MODELOutdoor Unit DimensionsMounting Dimensions
Inches/mm (L1xHxW1)L2 (mm)W2 (mm)
MS*09*E1526" x 21" x 10.5"
660 x 540 x 265
19"
481
11"
276
MS*12*E1531" x 21" x 10"
780 x 540 x 250
21.5"
549
11"
276
MS*18*E1530" x 23" x 11"
760 x 590 x 285
21"
530
11.5"
290
MS*24*E1533" x 27.5" x 12.5"
840 x 700 x 320
22"
560
13"
335

Refrigerant Line & Charge Chart

MODELPIPE SIZELINE SET LENGTH PROVIDED WITH UNITMAX ELEVATIONMAX. LENGTH OVERALLAdditional Refrig, PER FOOT OF
ADDITIONAL LINE
VAPORLIQUID
INCHES (M)INCHES (M)[Feet (M)]B [Feet (M)]A [Feet (M)]
MSC093E15MC3/8" (Ø9.53)1/4" (Ø6.35)16 (5)26 (8)66 (20)0.2 oz. (20g)
MSC123E15MC3/8" (Ø9.53)1/4" (Ø6.35)16 (5)26 (8)66 (20)0.2 oz. (20g)
MSC183E15MC1/2" (Ø12.7)1/4" (Ø6.35)16 (5)33 (10)82 (25)0.2 oz. (20g)
MSC243E15MC5/8" (Ø15.9)3/8" (Ø9.53)16 (5)33 (10)82 (25)0.4 oz. (40g)
MSH093E15MC3/8" (Ø9.53)1/4" (Ø6.35)16 (5)26 (8)66 (20)0.2 oz. (20g)
MSH123E15MC3/8" (Ø9.53)1/4" (Ø6.35)16 (5)26 (8)66 (20)0.2 oz. (20g)
MSH183E15MC1/2" (Ø12.7)1/4" (Ø6.35)16 (5)33 (10)82 (25)0.2 oz. (20g)
MSH243E15MC5/8" (Ø15.9)3/8" (Ø9.53)16 (5)33 (10)82 (25)0.4 oz. (40g)

Power Supply Data

MODELPOWER SUPPLYMCAMOCAWG (Min) CONNECTING CABLE
MSC093E15MC230 V, 60 Hz, 1 Ph8.015.016 #
MSC123E15MC230 V, 60 Hz, 1 Ph8.015.016 #
MSC183E15MC230 V, 60 Hz, 1 Ph12.030.016 #
MSC243E15MC230 V, 60 Hz, 1 Ph14.025.016 #
MSH093E15MC230 V, 60 Hz, 1 Ph8.015.016 #
MSH123E15MC230 V, 60 Hz, 1 Ph8.015.016 #
MSH183E15MC230 V, 60 Hz, 1 Ph12.030.016 #
MSH243E15MC230 V, 60 Hz, 1 Ph14.025.016 #

PDF preview unavailable. Download the PDF instead.

msh183e15mc Adobe InDesign CS6 (Macintosh) Adobe PDF Library 10.0.1

Related Documents

PreviewGoodman Mini-Split Systems: High-Efficiency Ductless Air Conditioning and Heat Pumps
Explore Goodman's MS Series ductless mini-split systems, offering high-efficiency air conditioning and heat pump solutions. Featuring advanced inverter technology for optimal comfort, savings, and performance, these systems are ideal for various residential and professional applications. Includes detailed specifications and warranty information.
PreviewGoodman Mini-Split System Units: High-Efficiency Air Conditioning and Heat Pumps
Explore the Goodman brand's high-efficiency ductless mini-split air conditioning and heat pump systems, offering complete room comfort with easy-to-use remote control and advanced inverter technology. Learn about features, benefits, and specifications.
PreviewTips for Selecting Matched HVAC Components and Line Sets
Comprehensive guide on selecting and matching air conditioning and heat pump components, including evaporator coils and refrigeration line sets, for optimal system performance, efficiency, and longevity. Covers sizing, installation tips, and brazing best practices.
PreviewGoodman MSC/MSH 15 & 19 SEER Air Conditioner & Heat Pump Installation and Operations Manual
Detailed installation and operations manual for Goodman MSC/MSH series split type room air conditioners and heat pumps, covering 15 SEER and 19 SEER models. Includes safety instructions, installation procedures for indoor and outdoor units, refrigerant piping, electrical connections, leak testing, system evacuation, and test running.
PreviewGoodman Split System Air Conditioners: R-410A & R-32 Product Overview and Specifications
Explore Goodman's range of split system air conditioners, featuring R-410A and new R-32 models. This document provides an overview of key features, SEER2 ratings, compressor types, and technical specifications for models like GXV9S, GXV6S, GLXT7C, GLXS5B, GLXS4M, GLXS4B, and GLXS3B.
PreviewGoodman CPLE Series 10 SEER Split System Heat Pump Product Specifications
Detailed product specifications for the Goodman CPLE Series 10 SEER Split System Heat Pump. This document includes comprehensive information on standard features, cabinet construction, air handler and coil compatibilities, available accessories, detailed specifications, electrical data, unit dimensions, and extensive cooling and heating performance ratings for models ranging from 1½ to 5 Ton.
PreviewGoodman GSZ13/SSZ14 Split System Heat Pumps R-410A Service Instructions
Service manual for Goodman GSZ13 and SSZ14 split system heat pumps using R-410A refrigerant. Includes detailed information on blowers, coils, accessories, safety, operation, and troubleshooting for HVAC professionals.
PreviewGoodman SSZ 14 SEER Split System Heat Pumps Technical Manual
Technical manual for Goodman SSZ 14 SEER Split System Heat Pumps, covering product identification, design, specifications, performance data, and wiring diagrams for HVAC technicians.