D-EIGOC00103-22 02EN EWAT-B

EWAT-B

NASH

DAE System Control Department

BAS Integration guide

BAS Integration Guide-BACnet protocol name: D-EIGOC00103-22 02EN EWAT-B Product name: EWAT-B Page 3 / 48 Software name: NASH 1. Introduction This document contains information to incorporate a MicroTech III and Microtech 4 Unit Controllers into a building

PDF preview unavailable. Download the PDF instead.

EWAT-B BAS Integration Guide BACNet D-EIGOC00107-24 02 English
BAS Integration guide

BACnet®protocol

Doc. Name:
D-EIGOC00103-22_02EN_EWAT-B
Product Name:
EWAT-B
Control software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

Table of contents

1. Introduction 3 2. About this document 4
2.1 Revision History 4 2.2 Notice 4 2.3 Before starting 4 3. Safety information 5 4. Commission this unit in a BACnet network .................................................................................................................... 6 4.1 General information 6 4.2 BACnet IP module (POL908)....................................................................................................................................................7 4.3 BACnet MS/TP module (POL904.00/STD)................................................................................................................................8 4.4 BACnet / IP software option....................................................................................................................................................10 4.5 BACnet MS/TP software option ..............................................................................................................................................11 5. BACnet integration list 12 5.1 Alarm Codes and Indexes.......................................................................................................................................................24 6. Annex 2 ­ EDE files for BACnet .................................................................................................................................. 42 7. Annex 3 - Microtech PICS for BACnet ......................................................................................................................... 43 7.1 BACnet standardized device profile ........................................................................................................................................43 7.2 BACnet interoperability building blocks supported ..................................................................................................................43 7.3 BACnet standard object types supported ................................................................................................................................44 7.4 BACnet standard object types description...............................................................................................................................44

Product name: EWAT-B

Page 2 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
1. Introduction

Document name:
D-EIGOC00103-22_02EN_EWATB

This document contains information to incorporate a MicroTech® III and Microtech 4 Unit Controllers into a building automation system (BAS) via BACnet® communication protocol.
Microtech III and Microtech 4 are suitable for network integration. Data points accessible from a BACnet® network are made available to a BAS provided that the proper communication module (Microtech III and Microtech 4) or the corresponding software option (Microtech 4) are installed / activated.
Communication settings and the BACnet® properties with corresponding controller data points are described. BACnet® terms are not defined. Refer to the respective specifications for definitions and details.

Product name: EWAT-B

Page 3 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
2. About this document

Document name:
D-EIGOC00103-22_02EN_EWATB

2.1 Revision History

Version D-EIGOC00103-22EN_EWAT-B

Date 2022/03/08

D-EIGOC00103-22_01EN_EWAT-B 21/07/2023 D-EIGOC00107-24_02EN_EWAT-B 12/07/2024

Software Version NASH 2.09.A
NASH_2.11.A NASH_2.14.A

Description
First edition Revision of Object Names and Instances Number for Free-cooling Added Variable Flow
Added Evaporator Fixed Speed Setpoint in Variable Primary Flow
Updated table with Alarm codes and Indexes (paragraph 5.1)

2.2 Notice

© 2014 Daikin Applied Europe, Cecchina, Roma. All rights reserved throughout the world   The following are trademarks or registered trademarks of their respective companies:
· BACnet from American Society of Heating, Refrigerating and Air-Conditioning Engineers, · MicroTech 4 from Daikin Applied Europe.

2.3 Before starting

Application range

This document refers to the following components:

Microtech 4

Controller

POL908.00/STD

BACnet IP module

POL904.00/STD

BACnet MS/TP module

Users
Conventions Abbreviation

Users of this document are intended to be: - BACnet systems integrators - Service Technicians - Plant Engineers - Sales staff
Microtech 4 further in this document when proper will be referred to as "Microtech"

BACnet BSP

Building Automation and Control Network Board Support Package (operating system)

References
Product name: EWAT-B

·
·· ANSI/ ASHRAE 135-2004. "BACnet ­ A Data Communication Protocol for Building Automation and Control Networks". American Society of Heating, Refrigerating and AirConditioning Engineers ­ www.ashrae.org.
· Siemens Building Technologies ­ CB1P3933en ­ BACnet communication modules

Page 4 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
3. Safety information

Document name:
D-EIGOC00103-22_02EN_EWATB

Only personnel qualified in accordance with IEC (International Electrotechnical Commission) recommendations may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit be shut off before any work is begun. Shut off main power supply at the main circuit breaker or isolator.
IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown that the equipment conforms to all applicable codes with respect to electromagnetic compatibility.
RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched off, certain circuits may still be energized, since they may be connected to a separate power source.
RISK OF BURNS: Electrical currents cause components to get hot either temporarily or permanently. Handle power cable, electrical cables and conduits, terminal box covers and motor frames with great care.

Field of application Intended use Electrical installation Wiring Commissioning and maintenance
Faults Storage and transport Disposal

Use BACnet communication modules only for control and monitoring functions in ventilation, air conditioning and refrigeration plants.
Trouble-free and safe product operation of the above products presupposes transport, storage, mounting, installation, and commissioning as intended as well as careful operation.
Fuses, switches, wiring and grounding must comply with local safety regulations for electrical installations.
When wiring, strictly separate AC 230 V mains voltage from AC 24 V safety extralow voltage (SELV) to protect against electrical shock!
Only qualified staff trained accordingly may prepare for use, commission, and maintain BACnet communication modules.
Maintenance of BACnet communication modules generally only means regular cleaning. We recommend removing dust and dirt from system components installed in the control panels during standard service.
Only authorized staff may diagnose and correct faults and recommission the plant. This applies to working within the panel as well (e.g. testing or changing fuses).
Refer to the environmental conditions specified in the respective data sheets for storage and transport. If in doubt, contact your supplier.
Devices contain electrical and electronic components; do not dispose of them in household garbage. Observe all local and applicable laws.

Product name: EWAT-B

Page 5 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

4. Commission this unit in a BACnet network

4.1 General information

Compatibility
Unit controller
Communicatio n modules
BACnet/IP (POL908)

The Microtech controllers are tested according to the BACnet Testing Laboratory (BTL) Test Plan. They are designed to meet the requirements of the BACnet Standard as stated in the Protocol Implementation and Conformance Statement (PICS). However, they are not BTL listed. The PICS is located at the end of the present document.
Microtech 4 controller can be integrated in an interoperable BACnet network provided one of the followings:
a) it is equipped with the proper communication module b) the onboard communication has been made available (software option).
Available communication modules to configure Microtech controllers in BACnet network are:
1. BACnet/IP (dedicated network or shared Ethernet LAN) 2. BACnet MS/TP (Master/Slave Token Passing).
Both communication modules comply with the standardized profile for BACnet equipment (BAAC BACnet Advanced Application Controller).

BACnet MS/TP (POL904)

Communicatio n software option
BACnet/IP

For Microtech 4, BACnet communication is also available 6nboard the controller as a software option.
1. BACnet/IP (dedicated network or shared Ethernet LAN) 2. BACnet MS/TP (Master/Slave Token Passing).
Both communication options comply with the standardized profile for BACnet equipment (BAAC BACnet Advanced Application Controller).

BACnet MS/TP

Product name: EWAT-B

Page 6 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
4.2 BACnet IP module (POL908)
Module description

Document name:
D-EIGOC00103-22_02EN_EWATB

BSP Led
BUS Led Module connection Configuration
Product name: EWAT-B

Part Description 1 Ethernet interface 10/100 Mbit (IEEE 802.3U), RJ45 plug, 8-pin. 2 Status display "BSP" (Board Support Package). 3 Status display "BUS" (bus connections / bus traffic o.k.). 4 Plug connection "Communication extension bus". 5 Microtech controller.

Color Green

Flashing frequency Steady on

Yellow Red
Red/Yellow
Red

Steady on
Steady on Flashing at 1 Hz (1 second on/ 1 second off) Flashing at 2 Hz (0,5 second on/ 0,5 second off)

Meaning BSP operating and communication with controller working. BSP operating, but no communication with controller. Hardware fault.
Upgrade mode running.
BSP error (software error).

Color Green Yellow Red

Flashing frequency Steady on Steady on Steady on

Meaning Communication active. Initializing Communication interrupted.

Step 1 2 3 4

Action Power off the controller Connect POL908 module to the controller via plug connection (part 4). Connect the TCP/IP bus cable to the POL908. Power on the controller

Step 1 2 3
4

Action Check that BUS led status is steady on green coloured. Navigate the unit's keypad/display to the main menu page and set the "service" password Navigate the unit's keypad/display following the path below: Main menuCommissioningBACNetIP Setup
Set parameters in the table below as needed according to the local network

Parameter Device Instance UDP Port Number DHCP(1) Given IP Address2 Given IP Subnet Mask2 Given Gateway Address2 Unit Support NC Dev 1 NC Dev 2

Default value 1 47808 (BAC0) OFF 127.0.0.1 255.255.255.000 127.0.0.1
English 0 0

Page 7 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

(1) Verify whether DHCP should or should not be enabled. If not, obtain the IP Subnet Mask of the shared network from the network administrator. Then, obtain static IP Addresses for all MicroTech Unit Controllers you are integrating into the shared network. Finally, obtain the address of an IP Router to use for sending IP messages to and from the BACnet IP subnets.
(2) These addresses are used if DHCP (Dynamic Host Configuration Property) is set to Off. For changes to these parameters to take effect, use the keypad/display and set Apply Changes on the BACnet IP Setup menu to Yes. This will cause the power on the unit controller to reset.
4.3 BACnet MS/TP module (POL904.00/STD)
Module description

BSP Led
BUS Led Module connection Configuration procedure
Configuration parameters

Part Description 1 Interface RS485, plug-in terminals with screw/terminal connections. 2 Status display "BSP" (Board Support Package). 3 Status display "BUS" (bus connections / bus traffic o.k.). 4 Plug connection "Communication extension bus". 5 Microtech controller.

Color Green

Flashing frequency Steady on

Yellow Red
Red/Yellow
Red

Steady on
Steady on Flashing at 1 Hz (1 second on/ 1 second off) Flashing at 2 Hz (0,5 second on/ 0,5 second off)

Meaning BSP operating and communication with controller working. BSP operating, but no communication with controller. Hardware fault.
Upgrade mode running.
BSP error (software error).

Color Green Yellow Red

Flashing frequency Steady on Steady on Steady on

Meaning Communication active. Initializing Communication interrupted.

Step 1 2 3 4

Action Power off the controller Connect POL904 module to the controller via plug connection (part 4). Connect the TCP/IP bus cable to the POL908. Power on the controller

Step 1 2 3
4

Action Check that BUS led status is steady on green coloured. Navigate the unit's keypad/display to the main menu page and set the "service" password Navigate the unit's keypad/display following the path below: Main menuCommissioningBACnetMSTP Setup
Set parameters in the table below as needed according to the local network

Parameter Device Instance

Default value variable

Notes
The last 8 digits are computed from the production number and date code.

Product name: EWAT-B

Page 8 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

MSTP Address

24 (0x18)

Baud Rate

38400

Max Master Max Info Frames Unit Support

127 1 English

Document name:
D-EIGOC00103-22_02EN_EWATB

Cycle power after changing it for the changes to take effect.

Baud rate 76800 38400 19200 and lower

Number of devices 64 32 Value not recommended

Recommended value is the number of MS/TP devices (device address) + 1 1, unless device generates high-priority events (alarm, COV, client functionality).

Product name: EWAT-B

Page 9 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol 4.4 BACnet / IP software option

Document name:
D-EIGOC00103-22_02EN_EWATB

Option

1. From the HMI main menu choose:

enabling

Commissioning Configuration Software Options 4 3

2. Select "On" for option #3-BACNet IP

3. Insert the unlock password

4. Apply Changes

2

Option configuration

5. From the HMI main menu choose: Commissioning

6. Select "SW BACNet IP"

6

P

7. Select proper parameters for BACNet IP communication

Parameter Device Instance UDP Port Number DHCP(1) Given IP Address2 Given IP Subnet Mask2 Given Gateway Address2 Unit Support NC Dev 1 NC Dev 2

Default value 1 47808 (BAC0) OFF 127.0.0.1 255.255.255.000 127.0.0.1
English 0 0

(1) Verify whether DHCP should or should not be enabled. If not, obtain the IP Subnet Mask of the shared network from the network administrator. Then, obtain static IP Addresses for all MicroTech 4 Unit Controllers you are integrating into the shared network. Finally, obtain the address of an IP Router to use for sending IP messages to and from the BACnet IP subnets.
(2) These addresses are used if DHCP (Dynamic Host Configuration Property) is set to Off. For changes to these parameters to take effect, use the keypad/display and set Apply Changes on the BACnet IP Setup menu to Yes. This will cause the power on the unit controller to reset.

Product name: EWAT-B

Page 10 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

4.5 BACnet MS/TP software option

Option

1. From the HMI main menu choose:

enabling

Commissioning Configuration Software Options 4 3

2. Select "On" for option #2-BACNet MSTP

2

3. Insert the unlock password

4. Apply Changes

Option configuration

5. From the HMI main menu choose: Commissioning

6. Select "SW BACNet MSTP"

6

P

7. Select proper parameters for BACNet MSTP communication

Parameter Device Instance Address
Baud Rate
Max Master Max Info Frames

Default value variable
0
38400
1 1

Notes

-

MSTP Address

Baud rate

Number of devices

76800

64

38400

32

19200 and lower

Value not recommended

Recommended value is the number of MS/TP devices

(device address) + 1

1, unless device generates high-priority events (alarm, COV, client functionality).

Product name: EWAT-B

Page 11 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
5. BACnet integration list
Description Unit - Control Source Unit - Enabled State Unit - Run Allowed Unit - Capacity Limited Unit - Generic Alarm Evaporator - Water Flow State Unit - Operating State Unit - Enable Setpoint Unit - Alarm Reset Setpoint Unit - Active Operation Mode
Unit - Active Temperature Setpoint Product name: EWAT-B

Type BI

Name CtrlSource

BI EnableOutput

BI RunEnabled

BI UnitLimited

BI AlarmOutput

BI EvapWFlowState

BI UnitOnOff

BV UnitEnableStp

BV ClearAlarm

MV ActMode

AV ActTempStp Page 12 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 3 7 5 6 10 2 4 2 8 2

Range
0 Network 1 Local
0 Disabled 1 Enabled
0 Off 1 Allowed
0 NotLimited 1 Limited
0 NoAlarm 1 Alarm
0 NoFlow 1 Flow
0 ThermoOff 1 ThermoOn
0 Disable 1 Enable
0 None 1 Clear
1 Ice 2 Cool 3 Heat 4 Pursuit

5

°C

Read/Write R
R
R
R
R
R
R
W (Prio 8 )
W (Prio 8 )
R
R Software name: NASH

BAS Integration Guide-BACnet protocol
Description Unit - Actual Capacity Unit - Active Capacity Limit Unit - Status
Evaporator Entering Water Temperature Evaporator Leaving Water Temperature Heat Recovery - Enable Setpoint
Heat Recovery - Entering Water Temperature Heat Recovery - Leaving Water Temperature Outside Air Temperature Unit - Average Current Unit - Average Voltage Unit - Active Power Unit Alarm - Warning Index Unit Alarm - Problem Index Unit Alarm - Fault Index Unit Alarm - Warning Code Unit Alarm - Problem Code Unit Alarm - Fault Code

Type AV AV MV

Name ActCapacity ActCapacityLim UnitStatus

AI EvapEntWTemp AI EvapLvgWTemp BV HeatRec'EnableStp
AI HeatRec'EntWTemp AI HeatRec'LvgWTemp AI OutdoorAirTemp AV AvgCurrent AV AvgVoltage AV ActPower AV AVWarningAlarm AV AVProblemAlarm AV AVFaultAlarm AV AVWarningAlarmCode AV AVProblemAlarmCode AV AVFaultAlarmCode

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 2 1 1

Range
%
%
1 Off 2 Start 3 Run 4 PreShutdown 5 Service

1

°C

2

°C

7

0 Disable

1 Enable

177

°C

150

°C

5

°C

993

A

992

V

994

kW

902

0....65534

900

0....65534

901

0....65534

903

0....65534

904

0....65534

905

0....65534

Read/Write R R R
R R W (Prio 8 ) R R R R R R R R R R R R

Product name: EWAT-B

Page 13 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Unit - Operation Mode Setpoint
Unit - Cool Temperature Setpoint Unit - Ice Temperature Setpoint Unit - Heat Temperature Setpoint Unit - Capacity Limit Setpoint Circuit 1 - Condenser Refrigerant Pressure Circuit 1 - Condeser Saturated Temperature Circuit 1 - Evaporator Refrigerant Pressure Circuit 1 - Evaporator Saturated Temperature Circuit 2 - Condenser Refrigerant Pressure Circuit 2 - Condeser Saturated Temperature Circuit 2 - Evaporator Refrigerant Pressure Circuit 2 - Evaporator Saturated Temperature Circuit 1 - Shutdown Alarm
Circuit 2 - Shutdown Alarm
Product name: EWAT-B

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Type MV

Name UnitModeSetpointNetwork

Instance 3

Range
0 NULL 1 Ice 2 Cool 3 Heat 4 Pursuit

AV NetworkCoolTempSetpoint

4

°C

AV NetworkIceTempSetpoint

7

°C

AV NetworkHeatTempSetpoint

6

°C

AV NetworkCapacityLimitSetpoint

3

%

AI C1'CondRefPressure AV C1'CondSatRefTemp AI C1'EvapRefPressure AV C1'EvapSatRefTemp AI C2'CondRefPressure AV C2'CondSatRefTemp AI C2'EvapRefPressure AV C2'EvapSatRefTemp MV C1'ShutdownAlm
MV C2'ShutdownAlm

99

kPa

34

°C

141

kPa

68

°C

100

kPa

35

°C

142

kPa

69

°C

51

1 NoAlarm

2 Alarm

52

1 NoAlarm

2 Alarm

Read/Write W
(Prio 8 )
W (Prio 8)
W (Prio 8)
W (Prio 8)
W (Prio 8)
R R R R R R R R R
R

Page 14 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Unit - Shutdown Alarm
Unit - Heat Recovery Setpoint
Heat Recovery - Operating State
Circ 1 Compressor 1 - Suction Temperature Circ 1 Compressor 1 - Discharge Temperature Circ 1 Compressor 1 - Number of Starts Circ 1 Compressor 1 - Number of Running Hours Circ 1 Compressor 2 - Number of Starts Circ 1 Compressor 2 - Number of Running Hours Circ 1 Compressor 3 - Number of Starts Circ 1 Compressor 3 - Number of Running Hours Circ 2 Compressor 1 - Suction Temperature Circ 2 Compressor 1 - Discharge Temperature Circ 2 Compressor 1 - Number of Starts Circ 2 Compressor 1 - Number of Running Hours Circ 2 Compressor 2 - Number of Starts Circ 2 Compressor 2 - Number of Running Hours Circ 2 Compressor 3 - Number of Starts Circ 2 Compressor 3 - Number of Running Hours Freecooling - Enable Setpoint
Product name: EWAT-B

Type MV

Name U'ShutdownAlm

AV NetworkHeatRecSetpoint

MV HeatRec'State

AI C1'Comp1'SuctTemp AI C1'Comp1'DischTemp AV C1'Comp1'Starts AV C1'Comp1'RunHours AV C1'Comp2'Starts AV C1'Comp2'RunHours AV C1'Comp3'Starts AV C1'Comp3'Hours AI C2'Comp1'SuctTemp AI C2'Comp1'DischTemp AV C2'Comp1'Starts AV C2'Comp1'Hours AV C2'Comp2'Starts AV C2'Comp2'RunHours AV C2'Comp3'Starts AV C2'Comp3'RunHours BV Freecool'EnableStp

Page 15 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 54
49

Range 1 NoAlarm 2 Alarm
°C

42

1 Off

2 Recirculation

3 Regulation

105

°C

63

°C

92

-

74

h

93

-

75

h

94

-

76

h

108

°C

66

°C

95

-

77

h

96

-

78

h

97

-

79

h

28

0 Disable

1 Enable

Read/Write R
W (Prio 8)
R
R R W W W W W W R R W W W W W W W (Prio 8 )

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Freecooling - Status
Freeccoling - Enabled State Freecooling - Circuit 1 Mode
Freecooling - Circuit 2 Mode
Evaporator Pump - Speed Evaporator Pump 1 - Number of Running Hours Evaporator Pump 1 - Operating State Evaporator Pump 2 - Number of Running Hours Evaporator Pump 2 - Operating State
Product name: EWAT-B

Type MV

Name Freecool'Status

MV Freecool'Enabled MV Freecool'C1Mode

MV Freecool'C2Mode

AV EvapPump'Speed AV EvapPump1'RunHours BI EvapPump1'State AV EvapPump2'RunHours BI EvapPump2'State
Page 16 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 31

Range
1 Off 2 Start 3 Mixed 4 FreeCooling 5 Mechanical

32

1 Disabled

2 Enabled

29

1 Mechanical

2 Switching

3 Switching

4 FreeCooling

5 FC Pumpdown

6 FC Off

Read/Write R
R R

30

1 Mechanical

R

2 Switching

3 Switching

4 FreeCooling

5 FC Pumpdown

6 FC Off

296

%

R

112

h

R

8

0 Stop

R

1 Run

113

h

R

9

0 Stop

R

1 Run

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Unit - BACnet Measurement unit setpoint
Unit - Model

Type MV

Units

Name

MV UnitModel

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 4
317

Range
1 Metric 2 English
1 Centrifugal 2 Water Cooled 3 Air Cooled 4 HeatPump 5 Reserved 6 Reserved 7 Reserved 8 Reserved 9 Other

Read/Write W
R

Unit Alarm - Evaporator Entering Temperature Sensor Fault Unit Warning - Setpoint Reset Input Out of Range Unit Warning - Demand Limit Input Out of Range Circuit 1 Warning - Unload for Condenser High Pressure Circuit 2 Warning - Unload for Condenser High Pressure Circuit 1 Warning - Inhibition for Evaporator Low Pressure Circuit 2 Warning - Inhibition for Evaporator Low Pressure Circuit 1 Warning - Unload for Evaporator Low Pressure Product name: EWAT-B

BV Unit'OFFEvapEntWTempFail BV BadSetpointResetInput BV BadDemandLimitInput AI C1'UnloadCondPresHi AI C2'UnloadCondPresHi AI C1'InhibitEvapPresLow AI C2'InhibitEvapPresLow AI C1'UnloadEvapPresLow
Page 17 / 48

917

0 NoAlarm

1 Alarm

512

0 NoAlarm

1 Alarm

513

0 NoAlarm

1 Alarm

540

0 NoAlarm

1 Alarm

541

0 NoAlarm

1 Alarm

556

0 NoAlarm

1 Alarm

557

0 NoAlarm

1 Alarm

561

0 NoAlarm

1 Alarm

R R R R R R R R
Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circuit 2 Warning - Unload for Evaporator Low Pressure Evaporator Pump 1 - Fault Evaporator Pump 2 - Fault Unit Alarm - Outside Air Temperature Sensor Fault Circ 1 Comp 1 Alarm - Motor Protection Circ 1 Comp 2 Alarm - Motor Protection Circ 2 Comp 1 Alarm - Motor Protection Circ 2 Comp 2 Alarm - Motor Protection Circ 1 Comp 3 Alarm - Motor Protection Circ 2 Comp 3 Alarm - Motor Protection Circuit 1 Alarm - Condenser Pressure Sensor Fault Circuit 2 Alarm - Condenser Pressure Sensor Fault Circuit 1 Alarm - Condenser High Pressure
Product name: EWAT-B

Type AI

Name C2'UnloadEvapPresLow

BV EvapPump1'Fault

BV EvapPump2'Fault

BV Unit'OFFOATempSenFail

BV C1'Comp1'OFFMtrProtect

BV C1'Comp2'OFFMtrProtect

BV C2'Comp1'OFFMtrProtect

BV C2'Comp2'OFFMtrProtect

BV C1'Comp3'OFFMtrProtect

BV C2'Comp3'OFFMtrProtect

BV C1'OFFCondPresFail

BV C2'OFFCondPresFail

BV C1'OFFCondPresHi

Page 18 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 562 575 576 605 625 626 627 628 629 630 668 670 676

Range 0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm

Read/Write R R R R R R R R R R R R R

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circuit 2 Alarm - Condenser High Pressure Circuit 1 Alarm - Discharge Temperature Sensor Fault Circuit 2 Alarm - Discharge Temperature Sensor Fault Unit Alarm - Evaporator Water Flow Loss Unit Alarm - Evaporator Water Freeze Circuit 1 Alarm - Evaporator Pressure Low Circuit 2 Alarm - Evaporator Pressure Low Circuit 1 Alarm - Evaporator Pressure Sensor Failure Circuit 2 Alarm - Evaporator Pressure Sensor Failure Circuit 1 Alarm - Too many restart Circuit 2 Alarm - Too many restart Unit Alarm - Evaporator Leaving Temperature Sensor Fault Circuit 1 Alarm - Mechanical High Pressure
Product name: EWAT-B

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Type BV

Name C2'OFFCondPresHi

BV C1'OFFDischTempFail

BV C2'OFFDischTempFail

BV Unit'OFFEvapFlowLoss

BV Unit'OFFEvapLvgWTempLow

BV C1'OFFEvapPresLow

BV C2'OFFEvapPresLow

BV C1'OFFEvapPresFail

BV C2'OFFEvapPresFail

BV C1'OFFRestartsAlm

BV C2'OFFRestartsAlm

BV Unit'OFFEvapLvgWTempFail

BV C1'OFFMechPressHi

Instance 678 688 690 701 702 704 706 711 713 742 744 748 760

Range 0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm

Read/Write R R R R R R R R R R R R R

Page 19 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circuit 2 Alarm - Mechanical High Pressure Circ 1 Comp 1 Alarm - Suction Temperature Sensor Fault Circ 2 Comp 1 Alarm - Suction Temperature Sensor Fault Controller Alarm - Circuit 1 Board Offline Controller Alarm - Circuit 2 Board Offline Circuit 1 Alarm - Pumpdown Failure Circuit 2 Alarm - Pumpdown Failure Unit Alarm - External Event Circuit 1 Alarm - No Pressure change at Start Circuit 2 Alarm - No Pressure change at Start Unit Alarm - External Alarm Unit Alarm - Wrong Phase Voltage Circuit 1 Alarm - Gas Leakage
Product name: EWAT-B

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Type BV

Name C2'OFFMechPressHi

BV C1'Comp1'OFFSuctTempFail

BV C2'Comp1'OFFSuctTempSen

BV C1'OFFBoardOffline

BV C2'OFFBoardOffline

BV C1'FailPumpdown

BV C2'FailPumpdown

BV Unit'ExternalEvent

BV C1'OFFNoPresChgAtStart

BV C2'OFFNoPresChgAtStart

BV Unit'OFFExternalAlarm

BV Unit'OFFPhaseVoltage

BV C1'OFFGasLeakage

Instance 762 857 859 723 724 516 517 924 905 906 923 967 844

Range 0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm

Read/Write R R R R R R R R R R R R R

Page 20 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circuit 2 Alarm - Gas Leakage Unit - Electrical Panel Temperature Unit Warning - Electrical Panel Temp Sensor Fault Unit Warning - Electrical Panel High Temperature Circ 2 Compressor 3 - OffAuto Setpoint Circ 2 Compressor 3 - Operating State Circ 2 Compressor 2 - OffAuto Setpoint Circ 2 Compressor 2 - Operating State Circ 2 Compressor 1 - Actual Capacity Circ 2 Compressor 1 - OffAuto Setpoint Circ 2 Compressor 1 - Operating State Circ 1 Compressor 3 - OffAuto Setpoint Circ 1 Compressor 3 - Operating State Circ 1 Compressor 2 - OffAuto Setpoint
Product name: EWAT-B

Type BV

Name C2'OFFGasLeakage

AI SwitchBoxTemp BV Unit'SwitchBoxSensFault

BV Unit'SwitchBoxTempHigh

MV C2'Comp3'OffAutoStp

BV C2'Comp3'State

MV C2'Comp2'OffAutoStp

BV C2'Comp2'State

AV C2'Comp1'ActCapacity MV C2'Comp1'OffAutoStp

BV C2'Comp1'State

MV C1'Comp3'OffAutoStp

BV C1'Comp3'State

MV C1'Comp2'OffAutoStp

Page 21 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 845 187 983 984 1775 1786 445 446 1800 440 441 1814 434 435

Range 0 NoAlarm 1 Alarm
°C 0 NoAlarm 1 Alarm
0 NoAlarm 1 Alarm
1 Off 2 Auto
0 Off 1 On
1 Off 2 Auto
0 Off 1 On
% 1 Off 2 Auto
0 Off 1 On
1 Off 2 Auto
0 Off 1 On
1 Off 2 Auto

Read/Write R R R R W R W R R W R W R W

Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circ 1 Compressor 2 - Operating State
Circ 1 Compressor 1 - Actual Capacity Circ 1 Compressor 1 - OffAuto Setpoint
Circ 1 Compressor 1 - Operating State
Unit - Number of Circuits Unit - Number of Compressors Unit - Number of Tons Circuit 2 - Evaporator Superheat Active Setpoint Circuit 1 - Evaporator Superheat Active Setpoint Circuit 2 - Evaporator Superheat Temperature Circuit 1 - Evaporator Superheat Temperature Unit - Active Energy Unit - Power Factor Variable Flow - Plant Differential Pressure Varibale Flow - Water Bypass Valve State
Varibale Flow - Plant Differential Pressure setpoint Variable Flow - Plant Delta Temperature Variable Flow - Plant Delta Temperature Setpoint Variable Flow - Evaporator Fixed Speed Setpoint Circuit 2 - Expansion Valve Position Circuit 2 - Fan Speed Circuit 2 - Condenser Approach Temperature
Product name: EWAT-B

Type BV

Name C1'Comp2'State

AV C1'Comp1'ActCapacity MV C1'Comp1'OffAutoStp

BV C1'Comp1'State

AV NrCircuits AV NrCompressors AV UnitTons AV C2'EvapSuperheatStpVal AV C1'EvapSuperheatStpVal AV C2'EvapSuperheat AV C1'EvapSuperheat AV ActEnergy AV PowerFactor AI VarFlow'LoadDPres MV VarFlow'WBypVlvSta

AV VarFlow'LoadDPresStpt AV VarFlow'DeltaTemp AV VarFlow'DeltaTempStp AV VarFlow'EvapFixSpeedStp AV C2'ExpValvePos AV C2'FanSpeed AV C2'CondApproach

Page 22 / 48

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 436
1840 430
431
1855 1856 1857 1896 1897 1898 1899 990 991 1905 1906
1909 1911 1913 1915 208 209 210

Range 0 Off 1 On
% 1 Off 2 Auto
0 Off 1 On
1...2 1...3 tons dK dK dK dK kWh kPa 1 Closed 2 Opened
kPa °Dc °Dc % % % dK

Read/Write R
R W
R
R R R R R R R R R W R
W R W W R R R
Software name: NASH

BAS Integration Guide-BACnet protocol
Description Circuit 2 - Evaporator Approach Temperature Circuit 2 - Fan Staging Circuit 1 - Expansion Valve Position Circuit 1 - Fan Speed Circuit 1 - Condenser Approach Temperature Circuit 1 - Evaporator Approach Temperature Circuit 1 - Fan Staging

Type AV AV AV AV AV AV AV

Name C2'EvapApproach C2'FanStatus C1'ExpValvePos C1'FanSpeed C1'CondApproach C1'EvapApproach C1'FanStatus

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Instance 211 1997 168 169 170 171 1997

Range dK -% % dK dK --

Read/Write R R R R R R R

Product name: EWAT-B

Page 23 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWAT-B

5.1 Alarm Codes and Indexes

Premise

Unit communicates to BAS the status alarm through Codes and Indexes. Those are grouped in 3 level of alarm

Levels of Alarm
Index Code

The three levels of alarms are as it follows:

Level Warning Problem
Fault

Description They are notifications from unit or equipment of an incorrect status They are notifications from unit or equipment of a status that does allow unit to work properly They are notifications from unit or equipment (circuits, Compressors, Sensors, etc) that can cause stop of the unit or specific equipement

Index describes the general cause of the notification

Code describes which equipment or device of the unit is generating a notification

CODE 257 513 769 1025 1281 1537 1829 1833 1837 1861 1865 1869
Product name: EWAT-B

INDEX 1 2 3 4 5 6
7

LEVEL Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning

Device Unit Unit Unit Unit Unit Unit C1.Comp1 C1.Comp2 C1.Comp3 C2.Comp1 C2.Comp2 C2.Comp3

Description Condenser Entering Water Temperature Sensor Failure Evaporator Entering Water Temperature Sensor Failure Liquid Line Refrigerant Temperature Sensor Failure Condenser Leaving Water Temperature Sensor Failure (STOP if Heat) Evaporator pump maintenance Condenser pump maintenance
Compressor maintenance #n

Page 24 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWAT-B

CODE 2049 2305 2561 2817 3105 3137 3329 3585 3841 4128 4160 4352 6177 6209 6433 6465 6689 6721 7201 7233 7461 7465 7493 7497 7681 9729
Product name: EWAT-B

INDEX 8 9 10 11 12 13 14 15 16 17 24
25
26
28
29
30 38

LEVEL Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning

Device Unit Unit Unit Unit Circuit 1 Circuit 2 Unit Unit Unit Circuit 1 Circuit 2 Unit Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C1.Comp1 C1.Comp2 Unit Unit

Description Bad setpoint override input Bad demand limit input Power Loss While Running Unit Power Restore Circuit Failed Pumpdown External Event Bad Current Limit Input Option Controller Communication Failed Low Refrigerant Charge Chiller network Communication Failure Economizer Pressure Sensor Fault #n
Economizer Temperature Sensor Fault #n
Economizer EXV Motor Fault
Economizer EXV Module Communications Fault
Hot Gas Bypass Fault
Energy Meter Commununication Failure Heat Recovery Entering Water Temperature Sensor Fault

Page 25 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWAT-B

CODE 9985 10241 10497 10785 10817 11009 11265 11553 11585 11777 12033 12289 12545 12801 13057 13313 16418 16450 16642 16898 17186 17218 17410 17698 17730 18178
Product name: EWAT-B

INDEX 39 40 41
42
43 44
45
46 47 48 49 50 51 52
64
65 66
67
68
69
71

LEVEL Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Warning Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem

Device Unit Unit Unit Circuit 1 Circuit 2 Unit Unit Circuit 1 Circuit 2 Unit Unit Unit Unit Unit Unit Unit Circuit 1 Circuit 2 Unit Unit Circuit 1 Circuit 2 Unit Circuit 1 Circuit 2 Pump 1

Description Heat Recovery Leaving Water Temperature Sensor Fault SwitchBox Temperature High SwitchBox Temperature Sesnor Fault

Defrost EXV Motor Fault

Heat Recovery EWT or LWT freeze Heat Recovery Water Temperature Inverted

Liquid Refrigerant Temperature Sensor Fault

Smart Grid Communication Failure Glycol Free EWT Sensor Fault Glycol Free LWT Sensor Fault Glycol Pump Alarm Glycol Pump Communication Fail System Lwt Remote Alarm (Bivalent option) Domestic Hot Water Temperature Sensor Fault

Power Loss While Running

START INHIBITED - Ambient Temperature Low INHIBIT LOAD ­ Condenser Pressure High

INHIBIT LOAD ­ Condenser Pressure High

UNLOAD ­ Condenser Pressure High

UNLOAD ­ Condenser Pressure High

PUMP START ATTEMPTED - Condenser Pump #1 Failure

Page 26 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWAT-B

CODE 18434 18722 18754 18946 19202 19490 19522 19714 20002 20034 20262 20266 20294 20298 20513 20545 20738 20994 21250 21542 21546 21574 21578 21763 22050 22082
Product name: EWAT-B

INDEX 72 73 74 75 76 77 78
79
80 81 82 83
84
85 86

LEVEL Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem Problem

Device Pump 2 Circuit 1 Circuit 2 Unit Unit Circuit 1 Circuit 2 Unit Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Pump 1 Pump 2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit Circuit 1 Circuit 2

Description PUMP START ATTEMPTED - Condenser Pump #2 Failure INHIBIT LOAD - Discharge Temperature High NO EWT RESET - Entering Evaporator Temperature Sensor Failure INHIBIT LOAD - Evaporator Pressure Low INHIBIT LOAD - Evaporator Pressure Low UNLOAD - Evaporator Pressure Low UNLOAD - Evaporator Pressure Low
UNLOAD - Compressor Motor Current High
UNLOAD - Discharge Temperature High PUMP START ATTEMPTED - Evaporator Pump #1 Failure PUMP START ATTEMPTED - Evaporator Pump #2 Failure (Check Chiller Display for Cause)
INHIBIT LOAD - Compressor Motor Current High
UNLOAD - Power Holes INHIBIT FREECOOLING - Wrong Valve Position

Page 27 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWAT-B

CODE 22274
22530
22786
23042 23298 23554 23810 24066
1027
5671 5675 5703 5707 6691 6723 6947 6979 9251 9283 26151 26155 26407 26411 26663
Product name: EWAT-B

INDEX 87 88 89 90 91 92 93 94 4
22
26
27
36
102
103 104

LEVEL Problem
Problem
Problem
Problem Problem Problem Problem Problem
Fault
Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Device Unit
Unit
Unit
Unit Unit Unit Unit Unit
Unit
C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C1.Comp1 C1.Comp2 C1.Comp1

Description DATACENTER MODULE - SAF Side - Top Temperature Sensor Fault DATACENTER MODULE - SAF Side - Top Left Temperature Sensor Fault DATACENTER MODULE - SAF Side - Top Right Temperature Sensor Fault DATACENTER MODULE - PLC Side - Temperature Sensor Fault DATACENTER MODULE - SAF Side - Bottom Temperature Sensor Fault DATACENTER MODULE - SAF Side - Relative Humidity Sensor Fault DATACENTER MODULE - Module Communication Fail Pump Water Low Pressure (Outlet side) UNIT SHUTDOWN - Condenser Leaving Water Temperature Sensor Failure (If Watercooled Heatpump)
COMPRESSOR SHUTDOWN - Oil Sump Temperature High
CIRCUIT SHUTDOWN - Eco EXV Alarm
CIRCUIT SHUTDOWN - Fans Fault Alarm
CIRCUIT SHUTDOWN - EXV Alarm
COMPRESSOR SHUTDOWN - Discharge Pressure Sensor Fault
COMPRESSOR SHUTDOWN - Suction Pressure Low COMPRESSOR SHUTDOWN - Discharge Pressure High

Page 28 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 26667 27943 27947 31015 31019 32551 32555 32583 32587 32771 33063 33067 33095 33099 33059 33091 33795 34087 34091 34119 34123 34083 34115 34343 34347 34375
Product name: EWAT-B

INDEX 109 121
127 128 129
129 132 133
133 134

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp2 C1.Comp1 C1.Comp2 C1.Comp1 C1.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1

Description COMPRESSOR SHUTDOWN - Surge Temperature COMPRESSOR SHUTDOWN - Suction Pressure Sensor Fault
COMPRESSOR SHUTDOWN - Low pressure ratio UNIT SHUTDOWN - Outside Air Temperature Sensor Fault COMPRESSOR SHUTDOWN - Motor Overload Trip
CIRCUIT SHUTDOWN - Motor Current High UNIT SHUTDOWN - Motor Protector Trip COMPRESSOR SHUTDOWN - Motor Protector Trip
CIRCUIT SHUTDOWN - Motor Protector Trip COMPRESSOR SHUTDOWN - VFD Current High

Page 29 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 34379 34599 34603 34631 34635 34855 34859 34887 34891 35111 35115 35143 35147 35367 35371 35399 35403 35623 35627 35655 35659 35879 35883 35911 35915 36099
Product name: EWAT-B

INDEX 135 136 137 138 139 140 141

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit

Description COMPRESSOR SHUTDOWN - Motor Temperature High #n COMPRESSOR SHUTDOWN - VFD Temperature Sensor Fault COMPRESSOR SHUTDOWN - Phase Loss COMPRESSOR SHUTDOWN - Phase Reversal COMPRESSOR SHUTDOWN - VFD Overvoltage COMPRESSOR SHUTDOWN - VFD Undervoltage UNIT SHUTDOWN - Condenser Pressure Sensor Fault

Page 30 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 36391 36395 36423 36427 36387 36419 36611 36867 37155 37187 37415 37419 37447 37451 37671 37675 37703 37707 37927 37931 37959 37963
38147
38403 38659 38915 Product name: EWAT-B

INDEX 142
142 143 144 145
146
147
148
149 150 151 152

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault
Fault
Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Unit Unit Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2
Unit
Unit Unit Unit
Page 31 / 48

Description
COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault #n
CIRCUIT SHUTDOWN - Condenser Pressure Sensor Fault #n UNIT SHUTDOWN - Condenser Water Flow Loss UNIT SHUTDOWN - Condenser Pressure High CIRCUIT SHUTDOWN - Condenser Pressure High #n
COMPRESSOR SHUTDOWN - Current High with Compressor OFF #n
COMPRESSOR SHUTDOWN - Discharge Temperature Sensor Fault #n
COMPRESSOR SHUTDOWN - Discharge Temperature High #n
UNIT SHUTDOWN - Condenser Entering Water Temperature Sensor Fault UNIT SHUTDOWN - Evaporator Water Flow Loss UNIT SHUTDOWN - Evaporator LWT or EWT Low (Freeze) UNIT SHUTDOWN - Evaporator Pressure Low
Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 39207 39211 39239 39243 39203 39235 39427 39719 39723 39751 39755 39715 39747 39975 39979 40007 40011 40231 40235 40263 40267 40483 40515 40739 40771 40963
Product name: EWAT-B

INDEX 153 153 154 155 155 156
157 158 159 160

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Unit

Description COMPRESSOR SHUTDOWN - Evaporator (or Suction) Pressure Low #n CIRCUIT SHUTDOWN - Evaporator Pressure Low UNIT SHUTDOWN - Evaporator Pressure Sensor Fault COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor Fault #n CIRCUIT SHUTDOWN - Evaporator Pressure Sensor Fault #n COMPRESSOR SHUTDOWN - Ground Fault Trip #n
COMPRESSOR SHUTDOWN - Lift Pressure Low #n CIRCUIT SHUTDOWN - Liquid Line Pressure Sensor Fault #n CIRCUIT SHUTDOWN - Liquid Line Temperature Sensor Fault #n UNIT LOCKOUT - Number of Allowed Re-Starts Exceeded

Page 32 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 41255 41259 41287 41291 41251 41283
41475
41731
42023 42027 42055 42059 42019 42051 42243 42535 42539 42567 42571 42531 42563 42791 42795 42823 42827
Product name: EWAT-B

INDEX 161
161 162 163 164
164 165 166
166
167

LEVEL Fault Fault Fault Fault Fault Fault
Fault
Fault
Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2
Unit
Unit
C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2

Description
COMPRESSOR LOCKOUT - Number of Allowed Restarts Exceeded #n
CIRCUIT LOCKOUT - Number of Allowed Restarts Exceeded #n UNIT SHUTDOWN - Evaporator Leaving Water Temperature Sensor Fault UNIT SHUTDOWN - Evaporator Entering Water Temperature Sensor Fault COMPRESSOR SHUTDOWN - Evaporator Leaving Water Temperature Sensor Fault #n
CIRCUIT SHUTDOWN - Evaporator Leaving Water Temperature Sensor Fault #n UNIT SHUTDOWN - Mechanical High Pressure Trip
COMPRESSOR SHUTDOWN - Mechanical High Pressure Trip #n
CIRCUIT SHUTDOWN - Mechanical High Pressure Trip #n
COMPRESSOR SHUTDOWN - Oil Net Pressure Low #n

Page 33 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 43047 43051 43079 43083 43303 43307 43335 43339 43559 43563 43591 43595 43815 43819 43847 43851 44071 44075 44103 44107 44327 44331 44359 44363 44583 44587
Product name: EWAT-B

INDEX 168 169 170 171 172 173 174

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2

Description COMPRESSOR SHUTDOWN - Oil Feed Temperature High #n COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #n COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor Fault #n COMPRESSOR SHUTDOWN - Oil Level Low #n COMPRESSOR SHUTDOWN - Oil Delta Pressure High #n COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault #n COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor Fault #n

Page 34 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 44615 44619 44839 44843 44871 44875 45059 45091 45123 45351 45355 45383 45387 45607 45611 45639 45643 45863 45867 45895 45899 46119 46123 46151 46155 46375
Product name: EWAT-B

INDEX 175 176 177 178 179 180 181

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1

Description
COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor Fault #n UINT SHUTDOWN - Phase Voltage Monitoring Alarm CIRCUIT SHUTDOWN - Phase Voltage Monitoring Alarm COMPRESSOR SHUTDOWN - Starter Fault #n COMPRESSOR SHUTDOWN - No Starter Transition #n COMPRESSOR START ABORT - Oil Pressure Low #n COMPRESSOR SHUTDOWN - Subcooling Low #n

Page 35 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 46379 46407 46411 46631 46635 46663 46667 46887 46891 46919 46923 46883 46915 47143 47147 47175 47179 47399 47403 47431 47435 47619 47911 47915 47943 47947
Product name: EWAT-B

INDEX
182 183 183 184 185 186 187

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2

Description COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Running #n COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Starting #n
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault #n
CIRCUIT SHUTDOWN - Suction Temperature Sensor Fault #n
COMPRESSOR START ABORT - Vanes Alarm #n
COMPRESSOR SHUTDOWN ­ Motor Fault #n UNIT SHUTDOWN - Mechanical Low Pressure Trip COMPRESSOR SHUTDOWN - Mechanical Low Pressure Trip #n

Page 36 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 47907 47939 48131 48163 48195 48419 48451 48675 48707 48935 48939 48967 48971 49155 49411 49667
49923
50179
50435 50691 50983 50987 51015 51019 51239
Product name: EWAT-B

INDEX 187
188
189 190
191
192 193 194 195 196 197 198
199
200

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault
Fault
Fault
Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device Circuit 1 Circuit 2 Unit Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit Unit Unit
Unit
Unit
Unit Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1

Description CIRCUIT SHUTDOWN - Mechanical Low Pressure Trip #n
Controller board offline #n (Circuit number describe Control board number. 0=Unit alarm for Extension modules other than Circuits extension)
CIRCUIT SHUTDOWN - No Pressure Change After Start
CIRCUIT SHUTDOWN - No Pressure at Startup
COMPRESSOR SHUTDOWN - Slide position sensor Fault #n
UNIT STOP - Emergency Stop Alarm UNIT STOP - Evaporator Water Temperatures Inverted UNIT STOP - External Alarm UNIT SHUTDOWN - Evaporator Leaving Water Temperature 1 Sensor Fault UNIT SHUTDOWN - Evaporator Leaving Water Temperature 2 Sensor Fault UNIT SHUTDOWN - Evaporator 1 Freeze Protection UNIT SHUTDOWN - Evaporator 2 Freeze Protection
COMPRESSOR SHUTDOWN - VFD Fault #n
COMPRESSOR SHUTDOWN - VFD Temperature High #n

Page 37 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 51243 51271 51275 51495 51499 51527 51531 51751 51755 51783 51787 52007 52011 52039 52043 52263 52267 52295 52299 52519 52523 52551 52555 52739 52771 52803
Product name: EWAT-B

INDEX
201 202 203 204 205 206

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit Circuit 1 Circuit 2

Description
COMPRESSOR SHUTDOWN - VFD Communication Error #n COMPRESSOR SHUTDOWN - VFD Temperature Low #n COMPRESSOR SHUTDOWN - VFD Undergrid COMPRESSOR SHUTDOWN - VFD Overgrid COMPRESSOR SHUTDOWN - Discharge Superheat Low #n UNIT SHUTDOWN - Gas Leakage CIRCUIT SHUTDOWN - Gas Leakage

Page 38 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 52995 53251 53507 53763 54019 54275 54531 54787 55043 55335 55339 55367 55371 55591 55595 55623 55627 55847 55851 55879 55883 56103 56107 56135 56139 56323
Product name: EWAT-B

INDEX 207 208 209 210 211 212 213 214 215
216
217
218
219
220

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device Unit Unit Unit Unit Unit Unit Unit Unit Unit C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2 Unit

Description UNIT SHUTDOWN - Battery Mode UNIT SHUTDOWN - High Pitch (Marine) UNIT SHUTDOWN - High Roll (Marine) UNIT SHUTDOWN - Pitch Sensor Fault (Marine) UNIT SHUTDOWN - Roll Sensor Fault (Marine) UNIT SHUTDOWN - Evaporator Differenital Pressure Sensor Fault UNIT SHUTDOWN - Evaporator Differenital Pressure High UNIT SHUTDOWN - Condenser Differenital Pressure Sensor Fault UNIT SHUTDOWN - Condenser Differenital Pressure High
COMPRESSOR SHUTDOWN - VFD Card Temperature High
COMPRESSOR SHUTDOWN - RLA High
COMPRESSOR SHUTDOWN - RLA Low
COMPRESSOR SHUTDOWN - Surge Alarm
UNIT SHUTDOWN - Evaporator Water Differential Pressure Low

Page 39 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 56579 56835 57091 57347 57635 57667 57895 57899 57927 57931
58147
58179 58403 58435 58663 58667 58671 58675 58695 58699 58703 58707 58915 58947 59139
Product name: EWAT-B

INDEX 221 222 223 224 225
226
227 228
229
230 231

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault
Fault
Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Document name:
D-EIGOC00103-22_02EN_EWAT-B

Device Unit Unit Unit Unit Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C2.Comp1 C2.Comp2
Circuit 1
Circuit 2 Circuit 1 Circuit 2 C1.Comp1 C1.Comp2 C1.Comp3 C1.Comp4 C2.Comp1 C2.Comp2 C2.Comp3 C2.Comp4 Circuit 1 Circuit 2 Unit

Description UNIT SHUTDOWN - Condenser Water Differential Pressure Low UNIT SHUTDOWN - Unit or Compressor not configured UNIT SHUTDOWN - Power Availability Alarm (Marine) UNIT SHUTDOWN - Freecooling water valves feedback Alarm CIRCUIT SHUTDOWN - Freeccoling Valves Feedback Alarm
COMPRESSOR SHUTDOWN - VFD Components to be replaced
CIRCUIT SHUTDOWN - Fans Communication Fail CIRCUIT SHUTDOWN - Anti-Chattering Alarm
CIRCUIT SHUTDOWN - Comp X Alarm
CIRCUIT SHUTDOWN - Ssh Low Limit Alarm UNIT SHUTDOWN - Tank Water Temp Sensor fault

Page 40 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

CODE 59651 59907 60163
60419 60675 60963 60995 61187 61443 61699 61955

INDEX 233 234 235 236 237
238
239 240 241 242

LEVEL Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault

Device Unit Unit Unit Unit Unit Circuit 1 Circuit 2 Unit Unit Unit Unit

Document name:
D-EIGOC00103-22_02EN_EWAT-B
Description UNIT SHUTDOWN - Condenser LWT or EWT (freeze) UNIT SHUTDOWN - Changeover Valve hardware Alarm UNIT SHUTDOWN - Changeover Valve feedback Alarm UNIT SHUTDOWN - Beluga Pump Fault Alarm UNIT SHUTDOWN - Beluga Pump Modbus Communication Alarm
CIRCUIT SHUTDOWN - Cx Drift Suction Temperature
UNIT SHUTDOWN - Glycol Free Freezing UNIT SHUTDOWN - Water Over Heat Alarm UNIT SHUTDOWN - Domestic Hot Water Alarm UNIT SHUTDOWN - Pump Water Low Pressure (outlet side)

Product name: EWAT-B

Page 41 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
6. Annex 2 ­ EDE files for BACnet

Document name:
D-EIGOC00103-22_02EN_EWATB

Premise
EDE file from BACnet IP module (POL908.00)

The EDE files are created by the BACnet server each time the server is started. Download and import new files if s any change in controller configuration is done. Some BACnet objects could be no more available or new objects could be added. Also change in BACnet settings affect the new EDE file.

EDE files from POL908 module can be exported via ftp as it follows:

Step 1 2
3

Action Connect POL908 module to the controller via plug connection. Connect to the POL908 TCP/IP port the bus cable from:
· a LAN if DHCP of the module is set to ON · a PC with static IP address if DHCP of the module is set to OFF Set proper IP address and Subnet mask of the module and apply changes. i.e.

IP

192.168.1.45

Subnet mask 255.255.255.0

4 Open a resource explorer instance and type the module IP address. i.e. ftp://192.168.1.45/Temp. In the folder "Temp" the EDE files in .csv format are available:

EDE file from both modules:
BACnet MS/TP (POL904.00)
BACnet IP (POL908.00)

Step 1 2 3
4

Action Connect POL904/908 module to the controller via plug connection. Connect PC to POL904 by mean of a RS485-USB converter or to POL908 by mean of ethernet cable. A BACnet explorer tool is needed in order to access the module and export the
EDE files from it. Freeware tools are available on the internet, i.e. YABE From YABE the EDE export option is available in functions menu.

Product name: EWAT-B

Page 42 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol
7. Annex 3 - Microtech PICS for BACnet
7.1 BACnet standardized device profile

Document name:
D-EIGOC00103-22_02EN_EWATB

7.2 BACnet interoperability building blocks supported

Data sharing

Data Sharing ­ ReadProperty-A Data Sharing ­ ReadProperty-B Data Sharing ­ ReadPropertyMultiple-A Data Sharing ­ ReadPropertyMultiple-B Data Sharing ­ WriteProperty-A Data Sharing ­ WriteProperty-B Data Sharing ­ WritePropertyMultiple-B Data Sharing ­ COV-B Data Sharing ­ COV-A

DS-RP-A DS-RP-B DS-RPM-A DS-RPM-B DS-WP-A DS-WP-B DS-WPM-B DS-COV-B DS-COV-A

Alarm and event management

Alarm and Event ­ Notification Internal-B Alarm and Event ­ AcknowledgeAlarm-B Alarm and Event ­ Information-B Alarm and Event ­ Alarm Summary-B Alarm and Event ­ Event-Enrollment Summary-B

AE-N-I-B AE-ACK- B AE-INFO-B AE-ASUM-B AE-ESUM-B

Scheduling

Scheduling ­ Internal-B Scheduling ­ External-B

SCHED-I-B SCHED-E-B

Trending

Trending-Viewing and Modifying Trends Internal-B Trending-Automated Trend Retrieval-B

T-VMT-I-B T-ATR-B

Device management
Product name: EWAT-B

Device Management ­ Dynamic Device Binding-A Device Management ­ Dynamic Device Binding-B Device Management ­ Dynamic Object Binding-B Device Management ­ DeviceCommunicationControl-B Device Management ­ TimeSynchronization-B Device Management ­ UTCTimeSynchronization-B Device Management ­ ReinitializeDevice-B Device Management ­ List Manipulation-B Device Management ­ Object Creation and Deletion-B

DM-DDB-A DM-DDB-B DM-DOB-B DM-DCC-B DM-TS-B DM-UTC-B DM-RD-B DM-LM-B DM-OCD-B

Page 43 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Device Management ­ Backup and Restore-B

Network management

Network Management-Connection Establishment-A

7.3 BACnet standard object types supported

Document name:
D-EIGOC00103-22_02EN_EWATB
DM-BR-B
NM-CE-A

7.4 BACnet standard object types description

Analog Input
Product name: EWAT-B

Property supported Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Units Max_Pres_Value Min_Pres_Value Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class
High_Limit
Low_Limit

Writable Range restrictions X

X

X

X

0 .. maxReal

X

Min_Pres_Value <= x <=Max_Pres_Value And High_Limit > Low_Limit

X

Min_Pres_Value <= x <=Max_Pres_Value And

Page 44 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

Analog Output
Analog Value
Product name: EWAT-B

Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Property supported Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Units Max_Pres_Value Min_Pres_Value Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class
High_Limit
Low_Limit
Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps
Property supported Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Units Max_Pres_Value Min_Pres_Value Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class
High_Limit
Low_Limit
Deadband Limit_Enable

High_Limit > Low_Limit

X

0 .. maxReal

X

X

Writable Range restrictions X

X

X

X

0 .. maxReal

X

Min_Pres_Value <= x <=Max_Pres_Value And High_Limit > Low_Limit

X

Min_Pres_Value <= x <=Max_Pres_Value And High_Limit > Low_Limit

X

0 .. maxReal

X

X

Writable Range restrictions

X

Depends on the Unit

X

X

X

0 .. maxReal

X

Min_Pres_Value <= x <=Max_Pres_Value And High_Limit > Low_Limit

X

Min_Pres_Value <= x <=Max_Pres_Value And High_Limit > Low_Limit

X

0 .. maxReal

X

Page 45 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

Analog Value (setpoints) Binary Input
Binary Output
Product name: EWAT-B

Event_Enable

X

Acked_Transitions

Notify_Type

Event_Time_Stamps

Property supported

Writable

Object_Identifier

Object_Name

Object_Type

Present_Value

X(1)

Units

Status_Flags

COV_Increment

X

Out_Of_Service

X(1)

Event_State

(1) Writeable if Out_Of_Service=True

Range restrictions Depends on the Unit 0 .. maxReal

Property supported

Writable

Object_Identifier

Object_Name

Object_Type

Description

Present_Value

X(1)

Status_Flags

Out_Of_Service

X

Event_State

Inactive_Text

Active_Text

Polarity

X

Notification_Class

Reliability

Acked_Transitions

Event_Enable

X

Alarm_Value

X

Notify_Type

Time_Delay

Event_Time_Stamps

Elapsed-active-time

X

Time-of-active-time-reset

(1) Writeable if Out_Of_Service=True

Range restrictions Only 0

Property supported Object_Identifier Object_Name Object_Type Description Present_Value Status_Flags Out_Of_Service Event_State Inactive_Text Active_Text Notification_Class Reliability Acked_Transitions Event_Enable Notify_Type Time_Delay Event_Time_Stamps

Writable Range restrictions X X
X

Page 46 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Polarity

X

Feedback_Value

Priority_Array

Relinquish_Default

X

Elapsed-active-time

X

Time-of-active-time-reset

Only 0

Document name:
D-EIGOC00103-22_02EN_EWATB

Product name: EWAT-B

Page 47 / 48

Software name: NASH

BAS Integration Guide-BACnet protocol

Document name:
D-EIGOC00103-22_02EN_EWATB

The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A.. Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..