TREND IQ4NC, IQ422 Controllers

Installation Instructions - Configuring

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

CONTENTS

  1. Before starting Configuration
  2. Installation - Configuring
  3. Connect to IQ4
  4. Reset to Defaults
  5. Disposal

1 BEFORE STARTING CONFIGURATION

Install the IQ4NC, IQ422

Refer to: IQ4NC, IQ422 Installation Instructions - Mounting (TG201264)

Install SET on PC / Laptop

Refer to: SET Manual (TE200147)

Prepare Ethernet Network (if using Ethernet)

Install DHCP Server

If the IP address settings (IP address, subnet mask, default router, WINS and DNS servers' addresses) are to be supplied by a DHCP server, ensure one is installed on the Ethernet segment to which IQ4 is connected.

Install WINS Server

If host names are being used for IP addressing across a router, a WINS server must be installed.

Install DNS Server

If email alarms are being sent, and the email server address is identified by internet domain name, a DNS server must be installed.

Additional Documentation Required

  • SET Manual (TE200147)
  • IP Tool Manual (TE200638)
  • IQTool Monitor Applet Manual (TE201298)
  • IQTool Addresser Applet Manual (TE201299)
  • IQ4 Configuration Manual (TE201263)

Note: PDF copies are included with SET installation in the following folder: C:\...\Trend Control Systems\Documentation

Read & Agree to End User Licence Agreement

Refer to: IQ4NC, IQ422 Installation Instructions - Mounting (TG201264)

2 INSTALLATION - CONFIGURING

Step 1: Switch Off

Ensure the power is switched off before proceeding.

Step 2: Access Unit

Open the unit's access panel. WARNING: Opening the panel may expose dangerous voltages.

Step 3: Isolate I/O

Isolate all Input/Output connections. WARNING: The connecting leads may be connected to supplies. Isolate before touching.

Step 4: Open Rotating Covers

Open the rotating covers on the unit.

Step 5: Disconnect I/O

Disconnect all Input/Output connections. Leave Power, Ethernet, Current loop Lan, USB, RS232, and MS/TP connected (where appropriate).

Step 6: Record Serial Number and Location

Record the serial number and location of the unit for future reference. This information is typically found on a label on the unit.

Step 7: Select Terminator Switch Position (IQ4NC using MS/TP network only)

For IQ4NC units on an MS/TP network, ensure the terminator switch is set correctly. Refer to IQ422, IQ4NC Installation Instructions - Mounting (TG201264) for details of terminator use. The switch can be set to 'Terminator in circuit' or 'Terminator out of circuit'.

Step 8: Connect PC / Laptop

Connect your PC or Laptop to the IQ4NC/IQ422 either via an Ethernet Hub/Switch or using a direct connection. For direct connection, a standard Ethernet cable is used. For hub/switch connection, a standard Ethernet cable (Cat 5e twisted pair, max 100m) is used. Note: To connect with SET, a vCNC is required. SET can connect when on a different subnet. Other connection methods are detailed in the 'Connect to IQ4' section.

Step 9: Close Rotating Covers

Close the rotating covers on the unit.

Step 10: Switch On

Switch the unit on. The unit will perform a self-test, indicated by LEDs illuminating for several seconds.

Step 11: Check Watchdog/Power LEDs

Normal operation indication: Watchdog LED should be ON, and the Input power supply LED should be ON.

Fault indications: If the Watchdog LED is OFF or flashing, the device may be faulty or require a reset to defaults. If the Input power supply LED is OFF, check the input power supply.

Note: All LEDs illuminate for several seconds after switch on.

Step 12: Check Ethernet LEDs (if Ethernet is connected)

Normal operation indication: The OK LED (green) and RX LED (yellow) should illuminate.

Fault indications: If the OK LED is OFF, check the Ethernet connection. If the RX LED is OFF, check the Ethernet connection.

Note: All LEDs illuminate for several seconds after switch on.

Step 13: Connect to IQ4NC, IQ422 Using SET / IP Tool

Find the IQ4NC, IQ422 by its MAC address shown on the serial label. Use the SET software or the IP Tool software for configuration. Refer to the SET Manual (TE200147) and IP Tool Manual (TE200638).

The IP Tool interface displays device information such as MAC address, IP address, subnet mask, and device mode. You can configure settings like device mode (Auto-ip-DHCP or Auto-ip-switch), IP address, subnet mask, default router, and WINS server.

Step 14: Set up IP Addressing Details (if using Ethernet)

Use IP Tool to choose either static (fixed) or dynamic (DHCP) addressing.

Dynamic (DHCP) Addressing (default):

When set to dynamic (DHCP) addressing, the unit automatically obtains its IP addressing details from the network's DHCP server. If no DHCP server is found, the unit defaults to link/local mode.

Static (Fixed) Addressing:

When set to static (fixed) addressing, the IP addressing details must be configured manually. If email alarms are being sent, and the email server address is identified by internet domain name, then a DNS server must also be specified.

Step 15: Set up Virtual CNC (if required)

A Virtual CNC must be set up if connection to a supervisor, tool or display is required. Use IP Tool to set up the address and port number of the vCNC. IQ4NCs have 4 vCNCs enabled by default; IQ422s do not have any vCNCs enabled.

Step 16: Set up IQ4NC Communication Mode (if using IQ4NC)

Connect a PC directly to the IQ4 using an Ethernet cable. Access the controller's web pages via a web browser and select Modules > Networks to display the NC Configuration Wizard. Choose the desired network configuration (e.g., Ethernet Internetwork to MS/TP Lan, Ethernet Internetwork to Current Loop Lan, etc.). Refer to the IQ Web User Guide (TC201256).

Note: The IQ4NC has a Lan to connect to the internetwork and cannot join another Lan on the internetwork.

Step 17: Check Trend Current Loop Network (if current loop network being used)

Normal operation indication: TX LED (yellow) and RX LED (yellow) should be ON.

Fault indications: Check previous device on network (RX), check next device on network (TX), or set baud rate manually if TX/RX flashes for more than 30s.

Note: All LEDs illuminate for several seconds after switch on.

Step 18: Check MS/TP Network (If IQ4NC using MS/TP network)

Normal operation indication: TX LED (yellow) and RX LED (yellow) should be ON.

Fault indications: Check MS/TP connection and baud rate (RX, TX).

Step 19: Set up Ethernet Access Across Routers (if required)

If the LAN is to be built across routers, specify details of devices on each subnet in the Remote Trend Devices list using IP Tool. It is recommended that at least two devices from each subnet are specified. Ticking the checkbox next to the list retains it in IP Tool for easy copying to other devices.

Step 20: Set up Trend Addressing

Lan of IQ4s on current loop: Run SET, right-click the Lan of IQ4s in the System View, select 'Address IQ4 Device' to run the IQTool Addresser Applet. Use 'Automatic Discovery' or 'Manual Discovery'.

Single IQ4 or Lan of IQ4s on Ethernet: Use IP Tool to set the address (ensuring it is unique on the Lan) and Lan number.

Lan of IQ4 and pre IQ4 controllers on current loop: Run SET, right-click the Lan of IQ4s in the System View and select 'Address IQ4 Device'. Add the IQ4 to the grid manually by specifying the serial number and address.

Note: IQ4s are given a factory address and Lan number. Changing these may require resetting the IQ4.

Step 21: Write Details on Label

Record the unit's details, including MAC Address, Part No., and IP Address (or Hostname if DHCP), on the provided label.

Step 22: Set up Baud Rate (current loop network of IQ4s only)

Set one IQ4 to a specific baud rate using SET's IQTool Monitor Applet to ensure other IQ4s select the required rate. Autobaud can be disabled.

Step 23: Set up Additional Trend Addressing (if required)

Set the Supervisor Port or USB Engineering Port using SET's IQTool Monitor Applet if the controller needs to provide connection to the network for supervisors and tools.

Step 24: Check LAN OK LED (not IQ4NC)

Normal operation indication: LAN OK LED is ON ('Lan built OK' or 'Attempting to build Lan').

Fault indication: If the LAN OK LED is OFF, the device is faulty. If it flashes for longer than 2 minutes, the Lan/internetwork cannot be built. Check baud settings and connections. If it remains OFF after switching on other devices, check network cabling.

Note: It is normal for the Lan OK LED to extinguish for up to 1 min after detecting baud rate, then illuminate.

Step 25: Download Strategy

Configure the strategy using SET and test using SET's simulation mode. Use SET to download the strategy and backdrop file. An Ethernet connection is required for backdrop file downloads. Strategy download is not recommended over current loop with baud rate <9k6. SET will set the controller's date and time to that of the PC during download.

Step 26: Check IQ422 or IQ4NC on BACnet (If /BAC or IQ4NC and BACnet protocol communications required)

Use SET to check that IQ4's BACnet functionality is operating correctly by verifying its presence in the System View on its BACnet network.

Step 27: Test Inputs (Not IQ4NC/.../00)

Follow the sequence: Switch off, Open covers, Re-connect inputs, Close covers, Switch on. Verify correct operation.

Step 28: Test Outputs (Not IQ4NC/.../00)

Follow the sequence: Switch off, Open covers, Re-connect outputs, Close covers, Switch on. Verify correct operation.

Step 29: Connect Supervisors/Tools/Display Panels

Connect PCs for supervisors, tools, and displays as described in 'Connect to IQ4'. Connections can be made directly to the controller via RS232 Local Supervisor Port, USB Local Engineering Port, or Ethernet port, or over the Trend network.

Step 30: Backup Strategy

Use SET to upload the strategy and compare it with the strategy held by SET. An Ethernet connection is required for uploading strategy and backdrop files.

Step 31: Close Rotating Covers

Close the rotating covers on the unit.

Step 32: Close Panel

Close the unit's access panel.

3 CONNECT TO IQ4

Step 1: Switch Off

Ensure the power is switched off.

Step 2: Open Rotating Covers

Open the rotating covers on the unit.

Step 3: Make Connection

Connection to IQ4 can be made directly via the RS232 Local Supervisor Port, USB Local Engineering Port, or Ethernet Port. Connection can also be made over a network (Ethernet).

Connect Directly to Controller

PC via Ethernet Port

Use a standard Ethernet cable (Cat 5e twisted pair, max 100m). Connection use: IPTool, SET (requires vCNC), Web Browser (requires vCNC), Supervisor (requires vCNC).

PC via Local Engineering Port (USB)

Use a Micro B USB cable. Connection use: IPTool, SET, Web Browser, Supervisor.

PC via Local Supervisor Port (RS232)

Use a Cable/EJ101442 with a 9 way female D type connector. Connection use: IPTool, SET, Web Browser, Supervisor. Note: If local supervisor port address is '0' (default), communication is limited to the IQ4. If non-zero, communication is possible over the entire network.

IQView8 via Local Supervisor Port (RS232)

Use a CABLE/EJ105650 RJ11. IQView8 requires its own power supply. Connection use: IPTool, SET, Web Browser, Supervisor.

Connect via Ethernet Network

Ensure the IQ4 is connected to the Ethernet network. Connect the PC to the same Ethernet network. Use a standard Ethernet cable (Cat 5e twisted pair, max 100m). Connection use: IPTool, SET (requires vCNC), Web Browser (requires vCNC), Supervisor (requires vCNC).

To make a connection with SET, a supervisor or display, ensure a vCNC is available in a Trend device on the same Ethernet Trend network and connect to the vCNC as described in the supplied documentation. If connecting with IP Tool, the PC should be on the same Ethernet segment as the IQ4. To make a connection with a web browser, run the web browser on the device and access the IQ4's IP address or host name.

4 RESET TO DEFAULTS

Step 1: Open Panel

Switch Off, Isolate I/O, Open Panel, Open Rotating Covers, and Disconnect I/O as per steps (1) to (5) of the 'Installation Configuring' section.

Step 2: Close Rotating Covers

Close the rotating covers.

Step 3: Reset Controller

Press and hold down the service button. The service button LED will flash. While continuing to hold down the button, switch on the controller. Ensure the button remains pressed for 2 to 5 seconds after power is switched on. Do not switch off the controller for at least 1 minute. The strategy, user modules (passwords, PINs etc), alarm logs, and plots are cleared down. Certain parameters are reset to defaults, including Lan number, outstation address, IP addressing mode, IP address, subnet mask, UDP port, identifier, Router 1, remote Trend devices, and Virtual VCNC. Backdrop files are unchanged, and time and date are left at their current settings. WARNING FOR /230 versions: Hazardous voltages exist in this area when the unit is powered. This operation should only be performed after taking suitable precautions.

Step 4: Re-configure Controller

Re-configure the controller as described in these instructions.

Step 5: DISPOSAL

WEEE Directive: At the end of their useful life, the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

5 DISPOSAL

WEEE Directive: At the end of their useful life, the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com

©2014 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems Limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 897-3900 Fax: (425) 869-8445 www.trend-americas.com

PDF preview unavailable. Download the PDF instead.

Ii IQ4NC IQ422 Adobe PDF Library 9.9

Related Documents

PreviewTREND IQ4NC Controllers: Technical Data Sheet
Technical data sheet for TREND IQ4NC controllers, detailing features, specifications, network modes, and compatibility for building management systems.
PreviewIQ4NC DDC-Stationen: Datenblatt
Das Datenblatt für die IQ4NC DDC-Stationen von Trend, das detaillierte Informationen zu Hardware, Funktionen, Netzwerkmodi und Spezifikationen bietet.
PreviewIQ5, IQ5-IO Controller & I/O Modules Installation Instructions
This document provides detailed installation and configuration instructions for Trend IQ5 and IQ5-IO Controller & I/O Modules. It covers initial setup, network configuration, addressing, feature licensing, and troubleshooting.
PreviewTREND IQ422 DDC-Station Datasheet
Datasheet for the TREND IQ422 DDC-Station, detailing its electrical specifications, hardware features, communication protocols, and installation guidelines.
PreviewTrend IQ4NC Controllers Data Sheet
This data sheet provides detailed information on the Trend IQ4NC Controllers, including their features, physical specifications, functionality, network modes, hardware components, firmware, compatibility, disposal, installation, order codes, and environmental specifications. The IQ4NC series controllers enable Trend networks to connect across various media like Ethernet, MS/TP, and Trend current loop, offering flexibility in building automation systems.
PreviewTREND IQ4/IO I/O Expansion Modules Installation and Mounting Guide
Comprehensive installation and mounting instructions for TREND IQ4/IO I/O Expansion Modules. Covers box contents, storing, installation procedures, wiring, and disposal.
PreviewTrend T1 Router: User Manual and Safety Instructions
This comprehensive manual provides essential operating instructions, technical data, and safety guidelines for the Trend T1 router, a powerful tool for woodworking and plastic applications. Learn about its features, maintenance, and safe usage practices.
PreviewTONN8 Configuration Manual: A Comprehensive Guide
This manual provides detailed instructions for configuring the TONN8 device, including hardware setup, software configuration using IQVISION, system integration, security measures, and backup/restore procedures. It is designed for users familiar with the Niagara 4 framework.