KSSAE241A
LG SB SZ StdEfficiency WallMounted R32 KSSAE241A 2024 12 19 152258 Job Name/Location: Date: PO No.: Architect: Engr: Rep:
(Company)
For: File
Resubmit
Approval Other
GC: Mech:
(Project Manager)
Tag No.:
KSSAE241A
R32 Single Zone Standard Efficiency Wall Mounted
Outdoor Unit (ODU) - KUSAE241A, Indoor Unit (IDU) - KNSAE241A
Performance: Cooling:
Cooling Capacity (Min~Rated~Max) (Btu/h) SEER2 EER2
SEER - Seasonal Energy Efficiency Ratio
Heating:
3,685 ~ 21,200 ~ 24,500
18 12
EER - Energy Efficiency Ratio
Heating Capacity (Min~Rated~Max) (Btu/h) HSPF2 Max. Heating @ Indoor 70°F DB Outdoor 19°F DB / 17°F WB Outdoor 6°F DB / 5°F WB
HSPF - Heating Seasonal Performance Factor Cooling Nominal Test Conditions: Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB / 75°F WB
3,685 ~ 22,000 ~ 25,260 8.3
Heating Nominal Test Conditions: Indoor: 70°F DB / 60°F WB Outdoor: 47°F DB / 43°F WB
17,700 13,800
Electrical:
Power Supply (V¹/Hz/Ø) MOP (A) MCA (A) Cooling Rated Amps (A) Heating Rated Amps (A) Compressor (A) Fan Motor (IDU + ODU) (A) Cooling Power Input (kW) (Min~Rated~Max @95°F) (kW) Heating Power Input (kW) (Min~Rated~Max @47°F) (kW)
MOP - Maximum Overcurrent Protection
208-230/60/1 20 15
10.1 10.6 10.0 0.6 + 0.4
0.24 ~ 1.767 ~ 2.8
0.24 ~ 2.02 ~ 2.6
MCA - Minimum Circuit Ampacity
Piping:
Liquid Line (in., O.D.) Vapor Line (in., O.D.) Additional Refrigerant (oz./ft.) Min. / Max. Pipe Length (ft.)² Piping Length (no add'l refrig., ft.) Max. Elevation (ft.)
1/4 1/2 0.22 9.8 / 65.6 24.6 32.8
Features:
· 24-Hour on/off timer
· Built-in Wi-Fi via ThinQTM app
· Two-way (up / down) auto swing · Inverter (variable speed
· Auto changeover
compressor)
· Auto restart
· Self-cleaning indoor coil
· Jet cool/Jet heat
· Sleep mode
· Smart Care
· Ultra-quiet operation
· Smart Diagnosis
Operating Range: Outdoor Unit: Cooling (°F DB) Heating (°F WB)
Indoor Unit: Cooling (°F WB) Heating (°F DB)
14 ~ 118 5 ~ 65
53 ~ 75 60 ~ 86
System Data:
Refrigerant Type Refrigerant Control Refrigerant Charge (lbs.) ODU Sound Pressure (Cooling / Heating) (±1 dB[A])³ IDU Sound Pressure Cooling (H/M/L/Sleep) (±1 dB[A])³ Heating (H/M/L) (±1 dB[A])³ ODU Net / Shipping Weight (lbs.) IDU Net / Shipping Weight (lbs.) Heat Exchanger Coating
R32 EEV 2.43
55 / 55
48 / 43 / 38 / 32 48 / 43 / 38 92.6 / 102.5 26 / 30 GoldFinTM
Fan:
ODU Type IDU Type Fan Speeds (Fan/Cool/Heat) Quantity (ODU + IDU) Motor/Drive ODU Max. Air Flow Rate (CFM) IDU Air Flow Cooling, Max/H/M/L (CFM) Heating, Max/H/M/L (CFM) Dehumidification (pts./hr.)
Propeller Cross Flow
6 / 6 / 6 1 + 1
Brushless Digitally Controlled/Direct 1,730
689 / 512 / 459 / 371 653 / 565 / 477 / 388
3.38
Notes:
1. Acceptable operating voltage: 187V-253V. 2. Piping lengths are equivalent. 3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745. 4. All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied and must be a minimum of four-conductor, 14 AWG, stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes. 5. See Engineering Manual for sensible and latent capacities. 6. Power wiring cable size must comply with the applicable local and national code. 7. The indoor unit comes with a dry helium charge. 8. This data is rated 0 ft. above sea level, with 24.6 ft. of refrigerant line and a 0 ft. level difference between
outdoor and indoor units. 9. Must follow installation instructions in the applicable LG installation manual.
Included Accessories: · Wireless Remote Controller -- AKB76044207
Controller Options:
MultiSITETM CRC* Controllers Simple Remote Controllers Standard III Remote Controllers Deluxe Remote Controller Dry Contacts
Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps (excluding ductless systems) must be matched with appropriate coil components to meet ENERGY STAR® criteria. Ask your contractor for details or visit www.energystar.gov. (ENERGY STAR and the ENERGY STAR mark are registered trademarks owned by the U.S. Environmental Protection Agency.)
For a complete list of available accessories, contact your LG representative. For continual product development, LG reserves the right to change specifications without notice.
SB_SZ_StdEfficiency_WallMounted_R32_KSSAE241A_2024_12_19_152258
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com
Page 1 of 3
Job Name/Location:
KSSAE241A
R32 Single Zone Standard Efficiency Wall Mounted Outdoor Unit (ODU) - KUSAE241A, Indoor Unit (IDU) - KNSAE241A
Tag No.: Date: PO No.:
For continual product development, LG reserves the right to change specifications without notice.
SB_SZ_StdEfficiency_WallMounted_R32_KSSAE241A_2024_12_19_152258
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com
Page 2 of 3
Job Name/Location:
KSSAE241A
R32 Single Zone Standard Efficiency Wall Mounted Outdoor Unit (ODU) - KUSAE241A, Indoor Unit (IDU) - KNSAE241A
Tag No.: Date: PO No.:
SB_SZ_StdEfficiency_WallMounted_R32_KSSAE241A_2024_12_19_152258
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com
Page 3 of 3
Adobe PDF Library 17.0; modified using iTextSharp 4.1.6 by 1T3XT Adobe InDesign 19.5 (Windows)