INSTALLATION INSTRUCTIONS

BCE3M & BCS3M SERIES AIR HANDLER

These instructions must be read and understood completely before attempting installation.

Safety Alert Symbol

! This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.

CAUTION

The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

WARNING

Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation.

To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.

TABLE OF CONTENTS

Shipping and Packing List

Package 1 of 1 contains the following:

Check equipment for shipping damage. If found, immediately report damage to the last carrier. Check the unit rating plate to confirm that delivered unit matches order.

Manufactured By: Advanced Distributor Products A Lennox International, Inc. Company 1995 Air Industrial Park Road Grenada, MS 38901

GENERAL

These air handlers are designed for indoor installation only. As shipped, the unit is ready for installation in either upflow or horizontal left-hand or right-hand air discharge applications. Downflow applications can be accomplished by purchasing the available downflow kit (96W37 for 1.5 ton, 96W38 for the 2 and 2.5 ton, 97W95 for the 3 ton, and 97W96 for the 3.5 through 5 ton). All units may be installed with optional ECB25 field-installed electric heat and a matched outdoor unit. All units come with a orifice metering device installed.

Unit Dimensions - Inches (mm)

Refer to the diagram for front and side views with dimensions labeled A through J.

Dimension-018-024-030-036-042-048/-060
inchesmminchesmminchesmminchesmminchesmminchesmm
A3896540-1/2102943109248121948121952-1/21334
B1538118-1/247018-1/247021-7/855621-7/855621-7/8556
C225592255922559225592666026660
D61526152615212-1/43116-1/41596-3/8162
E11279143571640618-7/847917-7/845415-1/4387
F3-5/8925-1/21405-1/21405-3/41463-1/4833-1/483
G1025413-1/234313-1/234316-7/842916-7/842916-7/8429
H17-3/445117-3/445117-3/445117-3/445121-3/455221-3/4552
J3-5/8925-1/21405-1/21405-3/41464-5/81176-3/8162
Supply Air Opening Width174321743217432174322153321533
Supply Air Opening Depth1333015-1/241916-1/241919-7/850519-7/850519-7/8505
Return Air Opening Width12-1/2318164061640619-3/849219-3/849224-3/4629
Return Air Opening Depth20-3/452720-3/452720-3/452720-3/452724-3/462924-3/4629

Requirements

WARNING Excessive Weight Hazard - Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.

IMPORTANT These units are designed to match, and must be used with, outdoor units as rated. The indoor sections are manufactured with a orifice metering device installed to provide optimum refrigerant control and system performance with a variety of different capacities of outdoor units.

CAUTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.

These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation. Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.

In addition to conforming to manufacturer's installation instructions and local municipal building codes, installation of Allied air handler units (with or without optional electric heat), MUST conform with National Fire Protection Association (NFPA) standards: “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA No. 90A) and "Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA No. 90B).

All models are designed for indoor installation only. The installation of the air handler, field wiring, duct system, etc. must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.

WARNING Danger of explosion. Keep flammable materials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46 cm) above the floor for a garage installation. Failure to follow these instructions can result in death, explosion, or fire.

NOTES:

Installation Clearances

NON-DUCTED RETURN CLOSET INSTALLATION

The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.

Louvers or return air grilles are field supplied. Local codes may limit application of systems without a ducted return to single story buildings.

When these unit are installed in a closet with a louvered return opening, the minimum open area for the louvers will be:

If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.

If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air.

INSTALLATION

General Information

WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.

These units are factory assembled and configured for installation in upflow or horizontal left hand air discharge applications.

Each unit consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance.

For ease in installation, it is best to make any necessary coil configuration changes before setting air handler in place.

For all performance testing, units must be tested in the upflow orientation with the horizontal drain pan removed.

Refrigerant Metering Device

These units are equipped with a orifice metering device.

Upflow Application

  1. The air handler must be supported on the bottom only and set on solid floor or field supplied support frame. Securely attach the air handler to the floor or support frame.
  2. If installing a unit in an upflow application, remove the horizontal drain pan. IMPORTANT: The horizontal drain pan is not required in upflow air discharge installations; its removal provides the best efficiency and air flow.
  3. Place the unit in the desired location and level it. Connect return and supply air plenums as required using sheet metal screws.
  4. Install units that have no return air plenum on a stand that is at least 14" from the floor. This will allow proper air return.

Refer to Figure 1 for Upflow Configuration.

Horizontal Applications

IMPORTANT When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right- or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.

Suspending Horizontal Unit

Refer to Figure 2 for details on suspending a horizontal unit using angle iron or sheet metal.

NOTE: When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.

NOTE: This unit may be installed in left-hand or right-hand air discharge horizontal applications. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.

Left-Hand Discharge

  1. Determine knockouts required for drain line connections.
  2. With access door removed, knock out drain line opening for installing drain lines.
  3. Set unit so that it is sloped toward the drain pan end of the unit (see Figure 10).
  4. The horizontal configuration is shown in Figure 3.
  5. If the unit is suspended, the entire length of the cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch to avoid damaging the coil or filter. See Figure 2. Use sheet metal screws to connect the return and supply air plenums as required.

Right-Hand Air Discharge

For horizontal right-hand air discharge, the following field modifications are required:

  1. Remove and set aside blower and coil access covers.
  2. Remove bracket(s) securing pan(s) to unit as illustrated in Figures 4 and 5.

Refer to Figure 4 for "Remove Main Drain Pan Mounting Bracket (-018 through -036)" and Figure 5 for "Remove both Horizontal & Main Drain Pan Brackets".

  1. Remove coil assembly, bottom drain pan and horizontal drain pan as one assembly from the air handler.
  2. Move the horizontal drain pan to the opposite side of the coil. Be sure drain holes toward the back of the unit are plugged. Remove the plugs from the front drain pan ports.
  3. Re-install modified coil/drain pan assembly in air handler in the same orientation as before (Figures 6 and 7).

Refer to Figure 6 for "Install Main Drain Pan Mounting Bracket (-18 through -036)" and Figure 7 for "Install both Horizontal & Main Drain Pan Brackets".

6. Remove two screws securing the blow-off prevention bracket. Rotate the brackets 180° and reinstall using the same screws. See Figure 8.

Refer to Figure 8 for "Blow-Off Prevention Plate" showing Horizontal Left (Factory Default) and Horizontal Right configurations.

IMPORTANT

On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.

Typical Main and Overflow Drain

Refer to Figure 9 for a diagram of the typical main and overflow drain configuration.

NOTE - WHEN A air handler IS LOCATED ABOVE a FINISHED SPACE the secondary drain pan must have a larger footprint than the air handler.

WHEN A COIL IS LOCATED ABOVE a FINISHED SPACE, A 3/4" (19.1MM) SECONDARY DRAIN LINE MUST BE:

TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES GENERALLY, TWO INCHES (51 MM).

1 ALLIED p-tRAP 49p66 REQUIRES A LARGER INSTALLATION SPACE than the j-tRAP 91 P90.

2 pipe niPPle provided in bag assembly Sch 80, 3/4" I. D. x 5"-34K7401 (1): Cut the pipe in half and use it to route the main dra

DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)

IMPORTANT

A field-fabricated secondary drain pan, with a drain pipe to the outside of the building, is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes may require a secondary drain pan for any horizontal installation.

The air handler is provided with 3/4" NPT condensate drain connections.

Sloping the Drain

Make sure the unit is sloped (similar to the slope shown in Figure 10) so that the drain pan will empty completely without water standing in the pan.

Refer to Figure 10 for "Sloping the Drain" illustration.

INSTALL CONDENSATE DRAIN

  1. Remove the appropriate drain knockouts. If necessary, remove the indoor coil assembly from the cabinet.
  2. Connect primary drain line connection to the primary drain pan connection. The primary drain connection is flush with the bottom of the inside of the pan. Secondary connection is raised above the bottom of the inside of the pan.
  3. If the auxiliary drain line is to be used, remove the plug and route the drain line so that water draining from the outlet will be easily noticed by the homeowner. The auxiliary drain line does not required venting or a trap. Refer to local codes.
  4. After removal of drain pan plugs, check the drain port to see if holes have been drilled. If not drilled, use a 19/32" bit to drill out the primary drain hole; use a 3/8" drill bit for the secondary drain hole. Remove all drill shavings.
  5. Make sure drain ports and drain pan are free of all debris.
  6. Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. Ib. to prevent water leaks or seepage from the drain pan.
  7. Install a 2” trap in the primary drain lines as close to the unit as practical (see figure 9). Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.

NOTE: Horizontal runs must have an anti-siphon air vent (standpipe) installed ahead of the horizontal run (See Figure 9). An extremely long horizontal run may require an oversized drain line to eliminate air trapping.

NOTE: Do not operate air handler without a drain trap. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will prevent positive drainage without a proper trap.

  1. Route the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 24" clearance is required for filter, coil, or blower removal and service access.

NOTE: Check local codes before connecting the drain line to an existing drainage system. Insulate the drain lines where sweating could cause water damage.

TEST CONDENSATE DRAIN

Test the drain pan and drain line after installation:

  1. Pour several quarts of water into drain pan, enough to fill drain trap and line.
  2. Check to make sure the drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the end of the primary drain line.
  3. Correct any leaks found.

Duct System and Filters

DUCT SYSTEM

The air handler is provided with flanges for the connection of the plenum and ducts. The air handler is equipped with flanges that can form a filter rack for the installation of the air filter, or the filter may be installed as part of the return air duct system.

Supply and return duct system must be adequately sized to meet the system's air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1” thick insulation with a vapor barrier in conditioned areas or 2" minimum in unconditioned areas.

Unit Air Filter Size Chart

ModelNominal Filter Size
-01812" X 20" X 1
-02415" X 20" X 1
-03618" X 20" X 1
-042,-048 and -06018" X 24" X 1

Supply plenum should be the same size as the flanged opening provided around the blower outlet and should extend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.

INSTALLING DUCT SYSTEM

Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).

Connect supply air duct to the flange on top of the air handler. If an isolation connector is used, it must be nonflammable.

A return air duct system is recommended. If the unit is installed in a confined space or closet, a return connection must be run, full size, to a location outside the closet.

Connecting Refrigerant Lines

Refrigerant lines must be connected by a qualified technician in accordance with established procedures.

IMPORTANT Refrigerant lines must be clean, dehydrated, refrigerant-grade copper lines. Air handler coils should be installed only with specified line sizes for approved system combinations.

Handle the refrigerant lines gently during the installation process. Sharp bends or possible kinking in the lines will cause a restriction.

Do not remove the caps from the lines or system connection points until connections are ready to be completed.

  1. Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit. Run the lines in as direct a path as possible avoiding unnecessary turns and bends.
  2. Make sure that the suction line is insulated over the entire exposed length and that neither suction nor liquid lines are in direct contact with floors, walls, duct system, floor joists, or other piping.
  3. Connect the suction and liquid lines to the evaporator coil.
  4. To avoid damaging the rubber grommets in the cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
  5. Braze using an alloy of silver or copper and phosphorus with a melting point above 100°F. NOTE: Do not use soft solder.
  6. Reinstall the rubber grommets after brazing is finished.
  7. Make sure outdoor unit has been put in place according to the Installation Instructions and is connected to the refrigerant lines.

Sealing the Unit

Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow-off problems. This is especially important when the unit is installed in an unconditioned area.

WARNING There must be an airtight seal between the bottom of the air handler and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (ie., water heater), or carbon monoxide-producing device (ie., wood fireplace) is installed.

IMPORTANT When sealing the cabinet, be sure to seal closed any space around the holes where the drain lines exit the cabinet using duct tape and/or Permagum. Warm air must not be allowed to enter through any gaps or holes in the cabinet.

Make sure the liquid line and suction line entry points are sealed with either Armaflex material or with Permagum. Permagum may also be used to seal around the main and auxiliary drains and around open areas of electrical inlets.

Electrical Connections

WARNING Electric shock hazard! - Disconnect all power supplies before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.

WARNING ELECTRIC SHOCK HAZARD Can cause injury or death.

Foil-faced insulation has conductive characteristics similar to metal. Be sure there are no electrical connections within a 1/2" of the insulation. If the foil-faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause person al injury or death.

Refer to Figure 11 for "Making Electrical Connections".

208 VOLT CONVERSION

  1. Disconnect all power supplies.
  2. Remove the air handler access panel.
  3. Using the wiring diagram located on the unit access panel as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.

WARNING Electrically ground air handler. Connect ground wire to ground terminal marked “GND”. Failure to do so can result in death or electrical shock.

Low Voltage Connections (3-Speed PSC Motor)

Refer to Figure 12 for wiring diagrams for Cooling-Only Application, Cooling Application with Electric Heat, Heat-Only Application, and Heat Pump Application with Electric Heat.

*NOTE - Connect common wire only if required (Refer to the appropriate thermostat installation instructions)

Airflow - Cooling Blower Speed

The cooling blower speed is factory configured to provide correct airflow for an outdoor unit that matches the maximum cooling capacity rating of the air handler. If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. Refer to blower performance chart, Table 2.

WARNING ELECTRIC SHOCK HAZARD! Disconnect all power supplies before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.

  1. Disconnect all power supplies.
  2. Remove the air handler access panel.
  3. Locate pin number 2 on the blower relay. Two black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in-line splice connecting to a red wire.
  4. Remove the wire going to the 4-pin blower motor connector from the splice.
  5. Connect the blower lead [Red (La), Black (HI)] onto the splice from the 4-pin blower motor connector. NOTE: Reuse the factory-installed plastic cap on whichever wire is not used.
  6. Replace all panels.
  7. Reconnect power.

CHANGE BLOWER SPEED

NOTE: Refer to wiring diagram located on the unit access panel and blower performance (Table 2).

Blower Performance (3-Speed PSC) -240V (CFM @ ESP. -in. w.c.)

Air Handler ModelBlower Speed.10" WC.20" WC.30" WC.40" WC.50" WC
18Low (Red)510495475420325
Med (Blue)670650630595505
High (Black)905865820770705
24Low (Red)630625615610580
Med (Blue)885875850820780
High (Black)1130110010701010950
30Low (Red)900865830780740
Med (Blue)107510601030985940
High (Black)12401210117011351085
36Low (Red)1160114011151085990
Med (Blue)15001445138513001200
High (Black)16601575149514051390
42Low (Red)13251315130012751225
Med (Blue)14901465144013951315
High (Black)18201770169016001500
48Low (Red)17751710165015651470
Med (Blue)19951895180016851560
High (Black)20701970185017191595
60Low (Red)16751630158015201450
Med (Blue)19651925187518001695
High (Black)21402085200018951795

Blower Performance (CFM vs. ESP inches H2O)

Check-out Procedures

NOTE: Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions.

PRE-START-UP CHECKS

CHECK BLOWER OPERATION

CHECK COOLING OPERATION

CHECK ELECTRIC HEATER (IF USED)

Operation

COOLING (COOLING ONLY OR HEAT PUMP)

When the thermostat calls for cooling, 24 volts is put on the blower time-delay relay coil and then the indoor blower relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.

On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The reversing valve remains energized as long as the thermostat selector switch is in the COOL position.)

At the completion of the cooling demand the indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.

HEATING (ELECTRIC HEAT ONLY)

When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer can be connected with the first sequencer to W on the thermostat subbase, or they may also be connected to a second stage on the subbase.

HEATING (HEAT PUMP)

When the thermostat calls for heating, 24 volts is put on the blower time-delay relay coil. Then normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor. Circuit R and G energizes the blower relay, starting the indoor blower motor.

If the room temperature should continue to fall, the circuit between R and W1 is completed by the second-stage heat room thermostat. Circuit R-W1 energizes a heat sequencer. The completed circuit will energize supplemental electric heat (if applicable). Units with a second heat sequencer can be connected with the first sequencer to W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat subbase.

EMERGENCY HEAT (HEATING HEAT PUMP)

If the selector switch on the thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat subbase so that the electric heat control will transfer to the first-stage heat on the thermostat. This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position.

Maintenance

IMPORTANT Do not operate system without a filter. A filter is required to protect the coil, blower, and internal parts from excessive dirt and dust. The filter is placed in the return duct by the installer.

Cabinet Insulation

IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation. Insulation loses its insulating value when wet, damaged, separated or torn.

Matte- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and subsequently, component failure.

REPAIRING DAMAGED INSULATION

Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.

If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.

Refer to Figure 13 for "Repairing Insulation" details.

Start-Up and Performance Checklist (Horizontal Configuration)

Complete the checklist for horizontal configuration installation.

Installing Contractor's Name: ____________________ Installing Date: _______________

Installing Contractor's Phone: ____________________ Air Handler Model #: _______________

Job Address: _________________________________________________________________

Refer to Figure 14 for the checklist items.

Start-Up and Performance Checklist (Upflow Configuration)

Complete the checklist for upflow configuration installation.

Installing Contractor's Name: ____________________ Installing Date: _______________

Installing Contractor's Phone: ____________________ Air Handler Model #: _______________

Job Address: _________________________________________________________________

Refer to Figure 15 for the checklist items.

EQUIPMENT LIMITED WARRANTY

APPLIES IN U.S.A. AND CANADA ONLY

FAILURE TO MAINTAIN YOUR EQUIPMENT WILL VOID THIS WARRANTY

COVERED EQUIPMENT

The following Allied Air Enterprises heating and cooling equipment is covered by the Limited Warranty:

Condensing Units: 4SCU13, 4SCU14, 4SCU16, 4SCU18, 4AC13, 4AC14

Heat Pumps: 4SHP13, 4SHP14, 4SHP16, 4SHP18, 4HP13, 4HP14, 4HP16, 4HP18

Gas Furnaces: FPBB, A97, A96, A95, A952V, A93, A80, 95G2, 95G2V, 95G1, 92G1, 80G2, 80G1

Oil Furnaces: L83UF, L83BR, L83BF, L83HF, L83HR, L83HF

Electric Furnaces: EFC, EFV

Evaporator Coils: EC, EU, EH, EM

Air handlers: BCS2M, BCS3, BCE3

Package Equipment: 4PCE13, 4PCE15, 4PGE13, 4PGE15, 4PHP13, 4PHP15, RGE13, RPGE13, RHP13, RCE13, RPHP13, RPCE13

Unit Heaters: LF24 (30,000 to 75,000 Btuh units)

PARTS and COMPRESSOR COVERAGE

The covered equipment, parts and compressor are warranted by Allied Air for a period of five (5) years from the date of the original installation, when installed in a residential application (which includes homes, duplexes, apartments and condominiums). For non-residential applications, the covered equipment and parts are warranted for a period of one (1) year and compressor is warranted for five (5) years from the date of the original installation. If, during this period, a covered component fails because of a manufacturing defect, Allied Air will provide a free replacement part to the owner through a licensed service contractor utilizing an Allied Air distributor. The purchaser must pay shipping charges and all other costs of warranty service. Allied Air will not pay labor involved in diagnostic calls or in removing, repairing, servicing or replacing parts. Such cost may be covered by a separate warranty provided by the installer.

HEAT EXCHANGER EXTENDED COVERAGE

All covered heat exchangers are warranted by Allied Air for a period of twenty (20) years from the date of original installation, when installed in a residential application. Heat exchangers in all non-residential applications are warranted for a period of ten (10) years. LF24 (30,000 to 75,000 Btuh) units are covered for the following: Aluminized heat exchanger - Ten (10) years.

Heat Exchanger Availability: If a replacement heat exchanger is no longer available for a unit covered by this Limited Warranty, Allied Air will allow a credit toward the purchase of an equivalent Allied Air furnace (at the current suggested distributor's cost).

NOTE: If the date of original installation cannot be verified, the warranty period will be deemed to begin ninety (90) days after the date of manufacture. The LF24 unit heaters are not eligible for the extended warranty coverage.

EXCLUDED COMPONENTS

The following components are expressly not covered by this Limited Warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles, unit accessories and any parts not affecting unit operation

CARE OF EQUIPMENT

All new Allied Air units must be properly installed, operated and maintained in accordance with the unit installation, operation and maintenance instructions provided with each Allied Air unit. Failure to maintain the equipment per Allied Air instructions will void this Limited Warranty.

WARRANTY PROCEDURE

When service or warranty parts are required:

  1. Call a local licensed service dealer or contractor.
  2. If the installing dealer is unable to provide warranty service, check online at www.alliedair.com.
  3. Be prepared to furnish the following information:
    • a. complete model and serial number;
    • b. proof of required periodic maintenance, installation date and location; and
    • c. an accurate description of the problem.

WARRANTY LIMITATIONS

  1. This Limited Warranty is void if the covered equipment is removed from the original installation site.
  2. This Limited Warranty does not cover damage or defect resulting from:
    • a. flood, wind, fire, lightning, mold, or installation and operation in a corrosive atmosphere, or otherwise in contact with corrosive materials (chorine, fluorine, salt, recycled waste water, urine, fertilizers, or other damaging substances or chemicals); accident, or neglect or unreasonable use or operation of the equipment including operation of electrical equipment at voltages other than the range specified on the unit nameplate (includes damages caused by brownouts);
    • b. modification, change or alteration of the equipment, except as directed in writing by Allied Air;
    • c. operation with system components (indoor unit, outdoor unit and refrigerant control devices) which are not an AHRI match or meet the specifications recommended by Allied Air;
    • d. operation of furnaces with return air temperatures of less than 60°F (16°C) or operation of a furnace field installed downstream from a cooling coil; and
    • e. use of contaminated refrigerant or refrigerant not compatible with the unit.

The installation of replacement parts under the terms of this Limited Warranty does not extend the original warranty period.

Allied Air makes no express warranties other than the Limited Warranty specified above. All implied warranties, including the implied warranties of merchantability and fitness for a particular purpose, are excluded to the extent legally permissible. Should such exclusion or limitation of this Limited Warranty be unenforceable, such implied warranties are in any event limited to a period of one (1) year. Liability for incidental and consequential damages is excluded. Some states do not allow limitation of incidental damages, so these limitations or exclusions may not apply to you. Allied Air will not pay electricity or fuel costs, or increases in electricity or fuel costs, for any reason whatsoever, including additional or unusual use of supplemental electric heat. This Limited Warranty does not cover lodging expenses or labor charges.

Allied Air shall not be liable for any default or delay in performance under this Limited Warranty caused by any contingency beyond its control.

This Limited Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

NOTE TO CUSTOMER: Please complete information below and retain this warranty for your records and future reference.

Outside Unit Model Number: _______________ Serial Number: _______________ Installed Date: _______________

Furnace / Air Handler: _______________ Serial Number: _______________ Installed Date: _______________

Indoor Coil Model Number: _______________ Serial Number: _______________ Installed Date: _______________

Installing Company Name: ____________________ Phone: ____________________

Installing Company Address: _________________________________________________________________ State/Province: ________ Zip/Postal Code: ________

5-YEAR LIMITED EXTENDED PARTS WARRANTY

Allied Air Enterprises Inc. ("Allied Air") provides its air conditioning and heating products with a Standard Limited Parts Warranty for five (5) years. This additional 5-Year Limited Extended Parts Warranty is in addition to and is intended to supplement Allied Air's Standard Limited Parts Warranty. As such, Allied Air provides for a total of 10-years of limited warranty coverage (Standard Limited Parts Warranty plus additional 5-Year Limited Extended Parts Warranty).

This 5-Year Limited Extended Parts Warranty applies only to the original purchaser of the equipment and cannot be transferred. If during the coverage period, a covered part fails because of a defect in materials or workmanship under normal use and maintenance, Allied Air will provide a free replacement part to the purchaser through a licensed service contractor utilizing an authorized Allied Air distributor. The purchaser must pay shipping costs and all other costs of warranty service. Allied Air will not pay labor involved in diagnostic calls or in removing, repairing, servicing or replacing parts.

EXTENDED COVERAGE - PARTS/COMPRESSORS

Covered equipment and parts are warranted by Allied Air for a total of 10 YEARS (Standard Limited Parts Warranty) from installation, except as provided below

HEAT EXCHANGERS

Covered residential heating equipment's heat exchanger is warranted by Allied Air for a LIMITED LIFETIME from date of original installation, except as provided below.

EXCLUDED COMPONENTS -

The following components are expressly not covered by this 5-Year Limited Extended Parts Warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles, unit accessories, R-22 compressors, and any parts not affecting unit operation.

REQUIREMENTS FOR EXTENDED COVERAGE-

  1. The unit is an Armstrong Air, AirEase, Ducane, or Concord branded unit;
  2. The unit is installed in a residential application, which is an owner-occupied single-family residence. No commercial applications are allowed;
  3. The unit is properly registered at www.alliedair.com with Allied Air within 60-days after the original date of installation or occupancy. To register, follow the directions and complete the online warranty registration at www.alliedair.com. For customer inquiries, contact Allied Air at 1-800-448-5872.
  4. The unit is part of a complete ARI matched system and installed by a state certified or licensed contractor in accordance with the unit installation, operation, and maintenance instructions provided with the unit.
  5. Coils and air handlers are covered only when they are branded Armstrong, AirEase, Ducane, Concord or ADP and are purchased and newly installed as a system along with a qualifying unit. Except for ADP-branded products, coverage of other third party coils and air handlers are specifically excluded from this 5-Year Limited Extended Parts Warranty.
  6. Installation of the unit takes place on or after October 3, 2008.

If this 5-Year Limited Extended Warranty does not apply, then parts are warranted under the Standard Limited Parts Warranty for a period of 5 YEARS and heat exchangers for 20 YEARS. If the Standard Limited Parts Warranty periods differ from the original warranty certificate, the periods stated on the original warranty certificate apply.

This 5-Year Llimited Extended Parts Warranty does not apply to, and no warranty is offered by Allied Air, on any unit ordered over the internet. Proof of purchase may be required.

Any part replaced pursuant to this 5-Year Limited Extended Parts Warranty is warranted only for the unexpired portion of the limited extended warranty term remaining for the original part. The installation of replacement parts under the terms of this 5-Year Limited Extended Parts Warranty does not extend the warranty period.

Steps for obtaining replacement parts under this 5-Year Limited Extended Parts Warranty:

If you suspect a defect in your equipment, please contact the installer of the unit to obtain assistance. If unsuccessful, please contact an Allied Air dealer or distributor in your area. If unable to obtain local assistance, refer to Allied Air's website (www.alliedair.com) or contact Allied Air at 800-448-5872.

Allied Air is specifically not responsible for:

  1. Damage or repairs required as a result of flood, fire, wind, lightening strike (to the home or unit), corrosive atmosphere, contact with corrosive material (chlorine, fluorine, salt, recycled waste water, fertilizers or other damaging substances) or other conditions beyond the control of Allied Air;
  2. Use of parts, accessories, or refrigerant not compatible with the unit;
  3. Modification, change or alteration of the unit, except as expressly directed in writing by Allied Air;
  4. Improper use, accident, neglect or unreasonable use or operation of the unit, including operation of electrical equipment at voltages other than the range specified on the unit nameplate;
  5. Operation with system parts (indoor unit, outdoor unit and refrigerant control devices) which are not AHRI matched or do not meet the specifications recommended by Allied Air;
  6. Damage or repairs required as a consequence of faulty or installation or application;
  7. Normal maintenance as described in the installation and operating manual, such as cleaning of coils, filter cleaning and/or replacement and lubrication; and
  8. Changes in the appearance or sound of the unit that do not affect its performance.

This 5-Year Limited Extended Parts Warranty is an extension of Allied Air's Standard Limited Parts Warranty. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ON THIS PRODUCT IS LIMITED IN DURATION TO THE TERM OF THIS LIMITED EXTENDED WARRANTY. Some states and provinces do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

ALLIED AIR SHALL IN NO EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO EXTRA UTILITY EXPENSES OR DAMAGES TO PROPERTY. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you

The parties intend this writing as a final expression of their agreement with respect to warranties. Allied Air makes no other warranty beyond that which is expressly contained in this writing.

Allied Air shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control, including the unavailability of replacement parts.

This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.

1 Excludes residents of states or provinces where registration requirements are prohibited, such as California and Quebec. Residents of these states or provinces may either register as noted above or provide proof of when the unit was purchased and installed, such as an original invoice from the contractor with the Owner's name, address, purchase date, serial and model number.

PDF preview unavailable. Download the PDF instead.

Allied Air 13Z01 Installation Instruction Sheet Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)

Related Documents

Preview4SCU13LE 13 SEER Split System Air Conditioner Specifications
Detailed specifications for the 4SCU13LE 13 SEER Split System Air Conditioner, including components, design, compressor, cabinet, coils, warranty, physical and electrical data, unit dimensions, sound ratings, accessories, refrigeration data, and cooling performance ratings.
Preview95G2UHV Gas Furnace Installation Instructions
Comprehensive installation instructions for the 95G2UHV Warm Air Gas Furnace, covering upflow, horizontal, direct vent, and non-direct vent configurations. Includes safety information, parts arrangement, building code compliance, and detailed installation procedures.
PreviewInstallation and Maintenance Instructions for Allied Air 4SHP13 Series Split System Heat Pump
Comprehensive guide for the installation, startup, operation, and maintenance of the Allied Air 4SHP13 Series Split System Heat Pump. Includes safety warnings, electrical wiring, refrigerant piping, charging procedures, and warranty information.
PreviewAllied Air 7AH2AE Residential Air Handler Specifications
Comprehensive product specifications, features, technical data, and installation guidelines for the Allied Air 7AH2AE series residential air handlers, covering capacities from 1.5 to 5 tons and optional electric heat up to 25 kW.
Preview4SHP13LB 13 SEER Split System Heat Pump Product Specifications
Product specifications and performance data for the Allied Air Enterprises 4SHP13LB 13 SEER Split System Heat Pump, detailing compressor, cabinet, coil, design, accessories, warranty, and comprehensive cooling and heating performance ratings.
PreviewAllied Air Enterprises 97G2V Two Stage Variable Speed Gas Furnace Specifications
Explore the detailed specifications, features, and performance data for the Allied Air Enterprises 97G2V Two Stage Variable Speed Gas Furnace, including technical dimensions and operational capabilities.
PreviewAllied Air Enterprises New Furnace Platform Accessory Specification Sheet Fall 2010
This document provides detailed specifications for the new furnace platform accessories from Allied Air Enterprises, including products from Armstrong Air, AirEase, Ducane, and Concord for Fall 2010. It covers various furnace models, their features, and corresponding catalog numbers, along with installation and accessory information.
PreviewAllied Air Enterprises Equipment Limited Warranty
This document outlines the limited warranty provided by Allied Air Enterprises for their heating and cooling equipment, including coverage details, exclusions, and procedures for claims. It covers both a standard limited parts warranty and an extended 5-year limited parts warranty for residential applications.