RESIDENTIAL PRODUCT SPECIFICATIONS

HEAT PUMP OUTDOOR UNITS
ML17XP1
Merit® Series
R-410A - 60 Hz
Bulletin No. 211007 January 2023
Supersedes September 2022

SEER2 up to 17.0 / SEER up to 18.6 HSPF2 up to 8.5 / HSPF up to 10.6
1.5 to 5 Tons Cooling Capacity - 18,000 to 58,000 Btuh Heating Capacity - 16,200 to 54,500 Btuh

MODEL NUMBER IDENTIFICATION

ML 17 X P 1 - 036 - 230 A 01

Product Tier ML = Merit® Series

Revision Level

Nominal Efficiency
Refrigerant Type X = R-410A
Unit Type P = Heat Pump Outdoor Unit
Cooling Stages 1 = Single Stage Compressor

Ratings Revision Level
Voltage 230 = 208/230V-1 phase-60Hz
Nominal Cooling Capacity 018 = 1.5 tons 024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons

FEATURE HIGHLIGHTS

B C

G

I

D

F

WITH POREEF3RIMAGEOIRLANTR410A

H
E J

1. Outdoor Coil Fan 2. QuantumTM Coil 3. Expansion Valve - Outdoor Unit 4. Four-Way Reversing Valve 5. High Capacity Liquid Line Drier 6. Scroll Compressor 7. Defrost Control 8. Heavy Gauge Steel Cabinet 9. Refrigerant Line Connections

CONTENTS
Approvals And Warranty .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3 Controls - Order Separately .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7 Dimensions - Unit .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  10 Electrical Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7 Features .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3 Field Wiring  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  9 Installation Clearances  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9 Model Number Identification .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1 Optional Accessories - Order Separately .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  7 Sound Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  9 Specifications .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  7 TXV Substitution .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  11 TXV Usage .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 2

APPROVALS AND WARRANTY
APPROVALS · AHRI Certified to AHRI Standard 210/240-2023 · For AHRI Certified system match-ups and expanded ratings, visit www.LennoxPros.com · ENERGY STAR® certified · Sound rated to AHRI Standard 270-2008 test conditions · Tested in the Lennox Research Laboratory environmental test room · Rated according to U.S. Department of Energy (DOE) test procedures · Units and components UL, NEC, and CEC bonded for grounding to meet safety standards for servicing · ETL certified (U.S. and Canada) · ISO 9001 Registered Manufacturing Quality System
WARRANTY · Compressor:
· Limited five years in residential installations · Limited five years in non-residential installations · All other covered components: · Limited five years in residential installations · Limited one year in non-residential installations NOTE - Refer to Lennox® Basic Limited Warranty at www.Lennox.com for additional details.

FEATURES

APPLICATIONS

· Totally enclosed motor

· 1.5 through 5 ton

· PSC motor (018, 024, 030 and 036 models)

· Sound levels as low as 74 dBA

· ECM motor (042, 048 and 060 models)

· Single phase power supply

· Louvered steel top fan guard

· Vertical air discharge

C QuantumTM Coil

· Applicable to indoor air handlers or gas furnaces with

· Lennox designed and fabricated coil

indoor add-on coils

· Enhanced aluminum alloy tube/enhanced fin coil

· Shipped completely factory assembled, piped, and wired

· Ripple-edged aluminum fins

· Factory tested operated

· Aluminum tube construction

NOTE - When heat pumps are used with gas furnaces, a dual-fuel compatible thermostat or a zone control system with dual-fuel capabilities must be used

· Lanced fins for maximum fin surface exposure · Fin collars grip tubing for maximum contact area

(order separately).

· Flared shoulder tubing connections

NOTE - Installer must set heat pump, connect refrigerant lines, and make electrical connections to complete job.
REFRIGERATION SYSTEM
R-410A Refrigerant · Non-chlorine, ozone friendly

· Factory tested under high pressure · Entire coil is accessible for cleaning
High Pressure Switch · Protects the system from high pressure conditions that
can be a result of fan failure or a blocked/dirty coil · Automatic reset

· Unit is factory pre-charged
NOTE - Total system refrigerant charge is dependent on outdoor unit size, indoor unit size and refrigerant line length.
NOTE - Refer to the unit-mounted charging sticker to determine correct amount of charge required.
B Outdoor Coil Fan
· Direct drive fan

Low Pressure Switch · Shuts off unit if suction pressure falls below setting
· Provides loss of charge and freeze-up protection
· Automatic reset
D Expansion Valve - Outdoor Unit
· Designed and sized for heat pump systems
· Sensing bulb senses evaporator suction temperature during heating cycle

· Vertical air discharge

· Fan motor is inherently protected

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 3

FEATURES

REFRIGERATION SYSTEM (continued)
E Four-Way Reversing Valve
· Rapid changeover of refrigerant flow direction from cooling to heating and vice versa
· Operates on pressure differential between outdoor unit and indoor unit of the system
· Factory installed
F High-Capacity Liquid Line Drier
· Factory installed in the liquid line

COMPRESSOR
G Scroll Compressor
· High efficiency with uniform suction flow
· Constant discharge flow, high volumetric efficiency and quiet operation
· Low gas pulses during compression reduces operational sound levels

· Drier traps moisture or dirt · 100% molecular-sieve, bead type, bi-flow drier
Optional Accessories
Check/Expansion Valve Kits · Field installed on certain indoor units

· Compressor motor is internally protected from excessive current and temperature
· Compressor is installed in the unit on resilient rubber mounts for vibration free operation

· See TXV Usage table · Chatleff style fitting
Freezestat · Installs on or near the vapor line of the indoor coil or on
the suction line · Senses suction line temperature · Cycles compressor off when suction line temperature
falls below it's setpoint · Opens at 29°F and closes at 58°F

Scroll Compressor Operation · Two involute spiral scrolls matched together generate a
series of crescent-shaped gas pockets between them
· During compression, one scroll remains stationary while the other scroll orbits around it
· Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates
· As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced

· Installs on or near the discharge line of the evaporator or on the suction line
Refrigerant Line Kits · Refrigerant lines are shipped refrigeration clean
· Lines are cleaned, dried, pressurized and sealed at factory
· Suction line fully insulated

· When the pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls
· During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle
· Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency

· Lines are stubbed at both ends

· Compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to be worked toward the center and discharged

Compressor Crankcase Heater (Factory Installed on 036, 042, 048, 060)
· Protects against refrigerant migration that can occur during low ambient operation

Optional Accessories

Crankcase Heater (Optional for 018, 024, 030 models)
· Protects against refrigerant migration that can occur during low ambient operation

Compressor Sound Cover · Reinforced vinyl compressor cover · 1-1/2 inch thick batt fiberglass insulation · Hook and loop fastening tape on all open edges

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 4

FEATURES
CONTROLS
H Defrost Control
· Control furnished as standard
· Gives a demand defrost cycle whenever system heating performance falls below optimum levels
· Sensing element on coil determines when defrost cycle is required and when to terminate cycle
· Anti-short cycle (5 minutes) incorporated into the board
· Diagnostic LEDs furnished as an aid in troubleshooting
· Conveniently located in control box
Optional Accessories
M30 Smart Wi-Fi Thermostat · Wi-Fi-enabled, electronic 7-day, universal, multi-stage,
programmable, touchscreen thermostat
· 4 Heat/2 Cool
· Auto-changeover
· Dual-fuel control with optional outdoor sensor
· Controls dehumidification during cooling mode and humidification during heating mode
· Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders
· Easy to read 4.3 in. color touchscreen (measured diagonally)
· LCD display with backlight shows the current and set temperature, time, inside relative humidity, system status (operating mode and schedules) and outside temperature (optional outdoor sensor required)
· Smooth Setback Recovery starts system early to achieve setpoint at start of program period
· Compressor short-cycle protection (5 minutes)
· Up to four separate schedules are available plus Schedule IQTM
· One-Touch Away Mode - A quick and easy way to set the cooling and heating setpoints while away
· Smart AwayTM - Uses geo-fencing technology to determine when the homeowner is within a predetermined distance from the home to operate the system when leaving, away and arriving
· Wi-Fi remote monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets
· Smart home automation compatible with Amazon Alexa®, Google Assistant and IFTTT
· Service Dashboard features online real-time monitoring of installed Lennox® smart thermostats
NOTE - See the Lennox® M30 Smart Wi-Fi Thermostat Product Specifications bulletin for more information.

Remote Outdoor Temperature Sensor · Used with the Lennox® M30 Smart Wi-Fi Thermostat · Outdoor sensor allows thermostat to
display outdoor temperature NOTE - Sensor is required for the
Enhanced Dehumidification Accessory (EDA) applications.
Thermostat · Thermostat is not furnished with unit · See Lennox Price Book for selection
Compressor Hard Start Kit · Single-phase units are equipped with a PSC compressor
motor · This type of motor normally doesn't need a potential
relay and start capacitor · For conditions such as low voltage kit may be required
to increase the compressor starting torque
Compressor Low Ambient Cut-Off Switch · Non-adjustable switch (low ambient cut-out) prevents
compressor operation when outdoor temperature is below 35°F · Freezestat Installs on or near the vapor line of the indoor coil or on the suction line · Senses suction line temperature and cycles the compressor off when suction line temperature falls below it's setpoint · Opens at 29°F and closes at 58°F
Indoor Blower Off Delay Relay · Delays the indoor blower-off time during the cooling
cycle
Low Ambient Kit · Air conditioners can operate down to 45°F outdoor air
temperature without additional controls · Allows unit to operate properly down to 30°F NOTE - Crankcase heater and freezestat should be
installed on compressors equipped with a low ambient kit. NOTE - A Compressor Low Ambient Cut-Off should be added to terminate compressor operation below recommended operation conditions.
Mild Weather Kit · Units can operate in the heating mode at outdoor air
temperatures up to 75°F · Field installed kit allows heating operation above 75°F
Monitor Kit - Service Light · Ambient compensating thermistor · Service light thermostat · For thermostats requiring indicator light inputs · For use with thermostats requiring input for indicator lights
ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 5

FEATURES

CONTROLS (continued)
Optional Accessories (continued)
Outdoor Thermostat Kit · An outdoor thermostat can be used to lock out some of
the electric heating elements on indoor units where twostage control is applicable
· Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line
· Thermostat kit and Mounting Box must be ordered separately

CABINET
I · Heavy gauge steel construction
· Louvered heavy gauge steel panels surround unit on all four sides
· Five station metal wash process
· Powder paint finish
· Control box is conveniently located with all controls factory wired
· Corner patch plate allows access to compressor components
· Drainage holes are provided in base section for moisture removal

PermaGuardTM Unit Base · Durable zinc-coated base section resists rust and
corrosion
J Refrigerant Line Connections, Electrical Inlets, Service
Valves · Sweat connection suction and liquid lines
· Located on corner of unit cabinet
· Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system
· Refrigerant line connections and field wiring inlets are located in one central area of the cabinet
· See dimension drawing

Optional Accessories

Unit Stand-Off Kit · Black high density polyethylene feet · Raises unit off of mounting surface · Four feet are furnished per order number

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 6

SPECIFICATIONS

General Data

Model No. ML17XP1-018 ML17XP1-024 ML17XP1-030 ML17XP1-036

Nominal Tonnage

1.5

2

2.5

3

Connections (sweat)

Liquid line OD - in.

3/8

3/8

3/8

3/8

Vapor (Suction) line OD - in.

3/4

3/4

3/4

7/8

¹ Refrigerant
Outdoor Coil

R-410A charge furnished Net face area - sq. ft. Outer coil
Inner coil

6 lbs. 2 oz. 24.5 - - -

6 lbs. 0 oz. 24.5 - - -

7 lbs. 5 oz. 18.7 18.0

8 lbs. 9 oz. 22.2 21.5

Tube diameter - in.

5/16

5/16

5/16

5/16

No. of rows

1

1

2

2

Fins per inch

22

22

22

22

Outdoor Fan

Diameter - in.

22

22

22

26

No. of blades

2

2

2

3

Motor hp

1/8

1/8

1/6

1/5

Cfm

2840

2840

2670

3590

Rpm

825

825

825

825

Watts

127

127

162

200

Shipping Data - lbs. 1 pkg.

185

185

185

220

ELECTRICAL DATA

Line voltage data - 60 Hz - 1 ph

3 Maximum overcurrent protection (MOCP) amps

4 Minimum circuit ampacity (MCA)

Compressor

Rated load amps

Locked rotor amps

208/230V-1ph 20 13.6 10.3 45.7

208/230V-1ph 25 15.1 11.5 59.5

208/230V-1ph 25 15.6 11.7 71.3

208/230V-1ph 30 17.8 13.1 83.1

Outdoor Fan Motor

Full load amps

0.7

0.7

1.0

1.4

CONT ROLS - ORDER S EPARATELY

M30 Smart Wi-Fi Thermostat

15Z69

·

·

·

·

Remote Outdoor Temperature Sensor

X2658

·

·

·

·

OPT ION AL AC C ES S ORI ES - ORDER S EPARATELY

Compressor Crankcase Heater

93M04

·

·

·

Compressor Hard Start Kit

LG 88M91

·

·

·

Copeland 10J42

·

Compressor Sound Cover

18J42

·

·

·

·

Compressor Low Ambient Cut-Off

45F08

·

·

·

·

Freezestat

3/8 in. tubing 93G35

·

·

·

·

5/8 in. tubing 50A93

·

·

·

·

Indoor Blower Off Delay Relay

58M81

·

·

·

·

5 Low Ambient Kit

54M89

·

·

·

·

Mild Weather Kit

11B97

·

·

·

·

Monitor Kit - Service Light

76F53

·

·

·

·

Outdoor

Thermostat 10Z23

·

·

·

·

Thermostat Kit

Mounting Box 31461

·

·

·

·

Refrigerant

3/8 x 3/4 x 3/8 - 20 ft. 89J56

Line Sets (Liq. x Suc. OD

3/8 x 3/4 x 3/8 - 30 ft. 3/8 x 3/4 x 3/8 - 40 ft.

89J57 89J58

·

·

·

x Insulation

3/8 x 3/4 x 3/8 - 50 ft. 89J59

Thickness - Length)

3/8 x 7/8 x 3/8 - 30 ft. 89J60

3/8 x 7/8 x 3/8 - 40 ft. 89J61

·

3/8 x 7/8 x 3/8 - 50 ft. 89J62

Unit Stand-Off Kit

94J45

·

·

·

·

NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and
additional refrigerant charge required. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Crankcase Heater and Freezestat are recommended with Low Ambient Kit.

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 7

SPECIFICATIONS

General Data

Model No. Nominal Tonnage

ML17XP1-042 3.5

ML17XP1-048 4

ML17XP1-060 5

Connections (sweat)

Liquid line OD - in.

3/8

Vapor (Suction) line OD - in.

7/8

3/8

3/8

7/8

1-1/8

¹ Refrigerant

R-410A charge furnished

10 lbs. 2 oz.

9 lbs. 2 oz.

10 lbs. 4 oz.

Outdoor Coil

Net face area- sq. ft. Outer coil Inner coil

24.93 24.13

24.93 24.13

29.09 28.16

Tube diameter - in.

5/16

5/16

5/16

No. of rows

2

2

2

Fins per inch

22

22

22

Outdoor Fan

Diameter - in.

26

26

26

No. of blades

3

3

3

Motor hp

1/3

1/3

1/3

Cfm

4110

4110

4060

Rpm

825

825

825

Watts

213

213

224

Shipping Data - lbs. 1 pkg.

250

250

260

ELECTRICAL DATA

Line voltage data - 60 Hz - 1 ph

208/230V-1ph

208/230V-1ph

208/230V-1ph

2 Maximum overcurrent protection (MOCP) amps

40

50

50

3 Minimum circuit ampacity (MCA)

25.9

33.9

32.5

Compressor

Rated load amps

18.6

25

23.9

Locked rotor amps

110

120

124.5

Outdoor Fan Motor

Full load amps

2.4 - 2.6

2.4 - 2.6

2.4 - 2.6

CONT ROLS - ORDER S EPA RATELY

M30 Smart Wi-Fi Thermostat

15Z69

·

·

·

Remote Outdoor Temperature Sensor

X2658

·

·

·

OP T ION AL ACCES S ORI ES - ORDER S EPARATELY

Compressor Hard Start Kit

Copeland 88M91

·

LG 10J42

·

·

Compressor Sound Cover

18J42

·

·

·

Compressor Low Ambient Cut-Off

45F08

·

·

·

Freezestat

3/8 in. tubing 93G35

·

·

·

5/8 in. tubing 50A93

·

·

·

Indoor Blower Off Delay Relay

58M81

·

·

·

4 Low Ambient Kit

54M89

·

·

·

Mild Weather Kit

11B97

·

·

·

Monitor Kit - Service Light

76F53

·

·

·

Outdoor

Thermostat 10Z23

·

·

·

Thermostat Kit

Mounting Box 31461

·

·

·

Refrigerant

3/8 x 7/8 x 3/8 - 30 ft. 89J60

Line Sets

3/8 x 7/8 x 3/8 - 40 ft. 89J61

·

·

(Liq. x Suc. OD

3/8 x 7/8 x 3/8 - 50 ft. 89J62

x Insulation Thickness - Length)

3/8 x 1-1/8 x 3/8 - 30 ft. 3/8 x 1-1/8 x 3/8 - 50 ft.

X0570 73P91

·

Unit Stand-Off Kit

94J45

·

·

·

NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and
additional refrigerant charge required. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Crankcase Heater and Freezestat are recommended with Low Ambient Kit.

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 8

SOUND DATA

1 Model

Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ
125 250 500 1000 2000 4000 8000

1 Sound ² Estimated Sound Pressure Level at

Rating Distance From Unit (dBA at distance in ft.)

Number

(dBA)

3

5

10

15

50

018

56.5

62

68.0 71.5 66.0 57.0

50

74

67

62

56

53

42

024

56.0

62

66.5 71.0

66

60

55.0

74

67

62

56

53

42

030

56.0

64

69.5 70.0

65

59

52.5

74

67

62

56

53

42

036

59

68

71.5 68.5

66

61

54

75

68

63

57

54

43

042

62

71.0 74.5 72.5

70

63

55.5

78

71

66

60

57

46

048

61

70.5 75.5 73.0

70

64

56.0

79

72

67

61

58

47

060

61.5 70.0 73.0

71

71

68

63

79

73

68

62

59

48

NOTE - the octave sound power data does not include tonal correction. 1 Tested according to AHRI Standard 270-2008 test conditions. 2 Estimated sound pressure level at distance based on AHRI Standard 275-2010 method for equipment located on the ground, roof, or on side of building wall with no
adjacent reflective surface within 9.8 feet. Sound pressure levels will increase based on changes to assumptions. For other applications, refer to AHRI Standard 275.

FIELD WIRING

A - Two Wire Power (see Electrical Data) B - Two or Three Wire Power (size to heater capacity) C - Twelve Wire Low Voltage 18 ga. minimum
Fourteen Wire Low Voltage with Optional Outdoor Thermostat D - Eight Wire Low Voltage 18 ga. minimum Ten Wire Low Voltage with Optional Outdoor Thermostat
NOTE - Field Wiring Not Furnished All wiring must conform to NEC or CEC and local electrical codes.

DISCONNECT SWITCH
(By Others)
A
OPTIONAL OUTDOOR THERMOSTAT
LENNOX OUTDOOR
UNIT

OPTIONAL ELECTRIC
HEAT LENNOX INDOOR UNIT
D

B
DISCONNECT SWITCH
(By Others) THERMOSTAT
(Optional)
C

INSTALLATION CLEARANCES

NOTES: Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
(914 mm)
Clearance to one of the remaining two sides may be 12 in.
(305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.

See NOTES

See NOTES

See NOTES

CONTROL See NOTES BOX

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 9

DIMENSIONS - UNIT

INLET

AIR

INLET AIR

INLET

AIR

TOP VIEW

INLET
AIR
SUCTION LINE CONNECTION LIQUID LINE CONNECTION

4-3/8 (111)

4-3/8 (111)

4-3/8 (111)
OPTIONAL UNIT STAND-OFF KIT (4)
(Field Installed)
COIL DRAIN OUTLETS (Around perimeter of base)
6-3/8 (162)

COMPRESSOR

4-3/8 (111)

4-3/8 (111)

6-3/8 (162)

4-3/8 (111)

TOP VIEW BASE SECTION

A

A

OUTDOOR COIL FAN

DISCHARGE AIR

CB

COMPRESSOR

SIDE VIEW

ELECTRICAL INLETS
2 (51) 3/4 (19)

SUCTION AND
LIQUID LINE CONNECTION

2-3/4 (70)

OPTIONAL UNIT STANDOFF KIT (4)
(FIELD INSTALLED)

SIDE VIEW

Model
018 024 030 036 042 048 060

A

in.

mm

28-1/4

718

28-1/4

718

28-1/4

718

32-1/4

817

32-1/4

817

32-1/4

817

32-1/4

817

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 10

B in. 43-1/4 43-1/4 33-1/4 33-1/4 37-1/4 37-1/4 43-1/4

mm 1099 1099 845 845 946 946 1099

C in. 42-1/2 42-1/2 32-1/2 32-1/2 36-1/2 36-1/2 42-1/2

mm 1080 1080 826 826 927 927 1080

TXV USAGE

Use this table for C35, CH23 and CR33 Field Installed TXV Match-Ups

Model

Order No.

018

12J18

024

12J18

030

12J18

036

12J19

042

12J20

048

12J20

060

12J20

CX35 and CHX35 coils and all Lennox air handlers are shipped with a factory installed TXV.
C35 coils - Replace the factory installed RFC orifice with the expansion valve listed.
CH23 and CR33 - Use the expansion valve listed.

AHRI STANDARD 210/240-2023
Standard Ratings relating to cooling or heating capacities shall be net values, including the effects of circulating-fan heat, but not including supplementary electric heat. Power input used for calculating efficiency shall be the Total Power.
Standard Ratings of units which do not have indoor aircirculating fans furnished as part of the model, i.e., Coilonly System, shall be established by subtracting from the total cooling capacity 1,505 Btu/h per 1,000 SCFM, and by adding the same amount to the heating capacity for nonmobile-home, non-Space Constrained units. Total Power for both heating and cooling shall be increased by 441 W per 1,000 SCFM of indoor air circulated.

TXV SUBSTITUTION

A general guide for replacing the factory installed TXV if the indoor unit (coil/air handler) is larger or smaller than the outdoor unit.

Outdoor Unit Size Tons

Indoor Unit

TXV

TXV

Size Tons Furnished Replacement

018 1.5 30/36 2.5/3 12J19

12J18

018 1.5

36

3

12J19

12J18

018 1.5

42

3.5

12J20

12J18

018 1.5

48

4

12J20

12J18

018 1.5

49

4

12J20

12J18

018

1.5 50/60 4/5

12J20

12J18

018

1.5 51/61 4/5

12J20

12J18

018 1.5

60

5

12J20

12J18

024

2

42

3.5

12J20

12J18

024

2

48

4

12J20

12J18

024

2

49

4

12J20

12J18

024

2 50/60 5

12J20

12J18

024

2 51/61 5

12J20

12J18

024

2

60

5

12J20

12J18

030 2.5

42

3.5

12J20

12J18

030 2.5

43

3.5

12J20

12J18

030 2.5

48

4

12J20

12J18

030 2.5

49

4

12J20

12J18

036

3

24

2

12J18

12J19

036

3

30

2.5

12J18

12J19

042 3.5

24

2

12J18

12J20

042 3.5

30

2.5

12J18

12J20

042 3.5 30/36 3

12J19

12J20

042 3.5

36

3

12J19

12J20

048

4 30/36 2.5/3 12J19

12J20

048

4

36

3

12J19

12J20

TXV Ranges:

12J18 - 1 .5 to 2.5 ton systems - Use on 2.5 ton (030) and lower systems.

12J19 - 3 ton systems - Use down to 2 ton (024) systems.

12J20 - 3 .5 to 5 ton systems - Use down to 3 ton (036) systems.

ML17XP1 - 1.5 to 5 Ton Heat Pump / Page 11

REVISIONS
Section Optional Accessories

Description Updated Line Sets available.

Visit us at www.Lennox.com For the latest technical information, www.LennoxPros.com Contact us at 1-800-9-LENNOX

NOTE - Due to Lennox' ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.

Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.

Installation and service must be performed by a qualified installer and servicing agency.