Kohler RDT Automatic Transfer Switch

100-400 Amps

Product Overview

The Kohler RDT Automatic Transfer Switch is designed for reliable power transfer between a primary utility source and a backup generator. This document details the features, specifications, ratings, and model designations for the RDT series, covering models from 100 to 400 Amps.

The RDT series offers various configurations, including standard and service entrance models, with options for integrated load centers and advanced control systems like the MPAC® 500.

MPAC® 500 Controller Features

Standard Features

Service Entrance Model Features

Specifications

Environmental Specifications

  • Operating temperature: 20°C to 70°C (-4°F to 158°F).
  • Storage temperature: -40°C to 85°C (-40°F to 185°F).
  • Humidity: 5 to 95% noncondensing.

Contact Ratings

  • Engine start: 1 A @ 30 VDC SPST normally closed (NC).
  • Common fault: 0.5 A @ 125 VAC; 2 A @ 30 VDC SPST normally open (NO).
  • Load control: 10 A @ 120 VAC SPST normally open (NO).
  • Auxiliary contacts (optional): 10 A @ 250 VAC Form C.

Source Sensing

  • Undervoltage dropout: 80%.
  • Undervoltage pickup: 85%.
  • Underfrequency dropout: 90%.
  • Underfrequency pickup: 96%.

Time Delays

Time DelayFactory SettingAdjustment with Accessory Board*
RangeIncrement
Engine start3 seconds1-10 seconds1 second
Transfer from Normal to Emergency3 seconds1-10 seconds1 second
Retransfer from Emergency to Normal6 minutes3-30 minutes3 minutes
Engine cooldown5 minutes1-10 minutes1 minute
Exercise run time20 minutes5-50 minutes5 minutes
Exercise interval1 week1 week/2 week (DIP switch)
Load control connection delay5 minutes5 or 10 minutes (DIP switch)
Failure to acquire Emergency source78 secondsNA
Undervoltage dropout0.5 secondNA
Underfrequency dropout3 secondsNA

* Optional accessory board required for time delay adjustments. NA = not adjustable.

Cable Sizes (AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections)

Switch Size, AmpsRange of Wire Sizes, Cu/AlNeutralGround
Normal (per phase)Emergency (per phase)Load (per phase)
100(1) #14 - 1/0 AWG(1) #14 - 1/0 AWGper customer-supplied branch circuit breakers(5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(Al)(9) #14 - #6 AWG
100 B(1) #14 - 1/0 AWG(1) #6 AWG - 250 KCMILper customer-supplied branch circuit breakers(26) #14 - #4AWG or (2) #14 - 1/0 AWG or (1) #6 - 2/0 AWG(4) #14 - 1/0 AWG
200(1) #6 AWG - 250 KCMIL(1) #6 AWG - 250 KCMILper customer-supplied branch circuit breakers(5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(Al)(9) #14 - #6 AWG
200 B(1) #6 AWG - 250 KCMIL(1) #6 AWG - 250 KCMILper customer-supplied branch circuit breakers(38) #14 - #4 AWG or (3) #14 - 1/0 AWG or (1) #4 AWG - 250 KCMIL(4) #14 - 1/0 AWG
200 BSE(1) #4 - 300 KCMIL(1) #6 - 250 KCMILper customer-supplied branch circuit breakers(4) #12 - 250 KCMIL(Cu) or (4) #10 - 250 KCMIL(Al)(6) #6 - 3/0 AWG
200 SE(1) #4 - 300 KCMIL(1) #6 - 250 KCMIL(1) #6 AWG - 250 KCMIL(5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(Al)(6) #6 - 3/0 AWG
400(2) 1/0 - 250 KCMIL or (1) 4 AWG - 600 KCMIL(3) #4 - 600 KCMIL(6) 1/0 - 250 KCMIL(6) #4 - 600 KCMIL(6) #6 - 3/0 AWG
400 SE(1) #1 - 600 KCMIL or (2) #1 - 250 KCMIL(2) 1/0 - 250 KCMIL or (1) 4 AWG - 600 KCMIL(6) #4 - 600 KCMIL(12) 1/0 - 250 KCMIL(6) #6 - 3/0 AWG

B = Load center model. SE = Service entrance model.

Note: Data is subject to change. Refer to the transfer switch dimension drawings and wiring diagrams for planning and installation.

Withstand and Close-On Ratings (WCR)

Service Entrance Transfer Switch Ratings

The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker.

Switch Rating, AmpsWCR, RMS Symmetrical Amps at 240 VAC
20022,000
40035,000

Contactor Ratings with Coordinated Circuit Breakers

The transfer switches are UL listed at 240 VAC maximum. The following table lists contactor withstand current ratings (WCR) for 100-400 ampere non-service entrance rated switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. Suitable for control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full-load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of switch rating.

Switch Rating, AmpsVoltage, max.WCR, RMS Symmetrical AmpsManufacturerType or ClassMaximum Size, Amps
10024010,000Any Breaker *Any Breaker (0.025 seconds max.)
20065,000GETHLC4350
Eaton/Cutler-HammerHMC800
40024042,000GETHKM3F1200
35,000Any BreakerAny Breaker (0.05 seconds max.)

* For higher WCR values, contact the factory for additional specific breaker ratings.

Codes and Standards

The ATS meets or exceeds the requirements of the following specifications:

Weights and Dimensions

Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings.

Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg (5 lbs.) or 10% (whichever is larger) to the weight shown.

AmpsLoad CenterEnclosure TypeWeight kg (lb.)Transfer Switch Dimensions H x W x D, mm (in.)Dimension Drawing
100NoneNEMA 1 (steel)7 (15)610 x 330 x 154 * (24.0 x 13.0 x 6.0) *ADV-8437
100 B16 circuits18 (40)914 x 406 x 154 (36.0 x 16.0 x 6.0)ADV-9181
200None7 (15)610 x 330 x 154 * (24.0 x 13.0 x 6.0) *ADV-8438
200 B24 circuitsNEMA 1 (steel)21 (45)914 x 406 x 154 (36.0 x 16.0 x 6.0)ADV-9182
100None7 (15)613 x 340 x 177 (24.1 x 13.4 x 7.0)ADV-8440
100 B16 circuits8 (18)917 x 416 x 177 (36.1 x 16.4 x 7.0)ADV-9183
200NoneNEMA 3R (aluminum)7 (15)613 x 340 x 177 (24.1 x 13.4 x 7.0)ADV-8441
200 B24 circuits8 (18)917 x 416 x 177 (36.1 x 16.4 x 7.0)ADV-9184
200 SENone12 (26)858 x 473 x 163 (33.8 x 18.6 x 6.4)ADV-8444
200 BSE42 circuits32 (70)967 x 762 x 165 (38.1 x 30.0 x 6.5)ADV-9185
400NoneNEMA 3R (aluminum)40 (89)1222 x 560 x 269 (48.1 x 22.0 x 10.6)ADV-9769
400 SENone59 (130)1448 x 628 x 329 (57.0 x 24.7 x 12.9)ADV-9767

B = Load center model. SE = Service entrance model.

* Can be recess-mounted between 16 in. O.C. wall studs.

Accessories

Additional Accessories for Service Entrance Models

Surge Suppressor Specifications

Nominal Voltage (V ±15%)Max. Discharge Current (kA)Phase SplitPolesUL VPR 3rd Ed (L-N/N-G/L-G) (kV)Limiting Voltage, (L-N/N-G/L-G) (kV)Short Circuit Withstand Current (kA)Maximum Continuous Operating Voltage (VAC)
at 3kAat 10kA
240 / 1204030.6 / 1.2 / 0.70.6 / 0.4 / 0.60.8 / 0.7 / 0.8200175 / 350

Kohler® Model Designation Key

This chart explains the Kohler® transfer switch model designation system. The sample model designation shown is for a Model R service entrance rated automatic transfer switch that uses a standard-transition contactor with MPAC® 500 electrical controls rated at 240 Volts/60 Hz with 2 poles, 3 wires, and solid neutral in a NEMA 3R enclosure with a current rating of 200 amperes and no load center.

Designation PartDescriptionSample Code
ModelR: Model R automatic transfer switchR
MechanismD: Specific-breaker ratedD
TransitionT: Standard transitionT
Electrical ControlsC: MPAC® 500 (Microprocessor ATS Control)C
Voltage/FrequencyF: 240 Volts/60 Hz (A jumper on the controller allows conversion to 50 Hz)F
Number of Poles/WiresN: 2-pole, 3-wire, solid neutralN
EnclosureA: NEMA 1 (steel) *
C: NEMA 3R (aluminum)
C
Current RatingNumbers indicate the current rating of the switch in amperes:
0100: 100 amps
0200: 200 amps
0400: 400 amps
0200
Load CenterA: Without load center
B: With load center (not available on 400 amp models)
A
Service EntranceSE: Service entrance model (200 and 400 amp models available)
Blank: Not rated for service entrance
SE

* NEMA 1 only: 100 and 200 amp models without load centers can be recess-mounted between wall studs. Optional wall-mount bezel available.

Contact Information:
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444
KOHLERPower.com

Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler® generator distributor for availability.

© 2021 Kohler Co. All rights reserved.

PDF preview unavailable. Download the PDF instead.

v1 Acrobat Distiller 21.0 (Windows)

Related Documents

PreviewKohler RDT Automatic Transfer Switch: Features, Specifications, and Model Guide
Comprehensive guide to Kohler RDT Series Automatic Transfer Switches (100-400 Amps), detailing features, environmental specifications, contact ratings, time delays, cable sizes, withstand ratings, codes, dimensions, accessories, and model designation.
PreviewKohler RDT Automatic Transfer Switch: 100-400 Amps Technical Specifications
Explore the features and specifications of the Kohler RDT Automatic Transfer Switch, available in 100-400 Amp models. Details on MPAC 500 controller, standard and service entrance configurations, and compliance with industry standards.
PreviewKohler RXT Automatic Transfer Switch: Features, Specs, and Models (100-400 Amps)
Explore the Kohler RXT Automatic Transfer Switch, a reliable solution for automatic power transfer. This document details features, specifications, available models, dimensions, and ratings for the 100-400 Amp range.
PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Detailed information on the Kohler RXT Automatic Transfer Switch, including standard features, technical specifications, environmental conditions, cable sizes, withstand and close-on ratings, dimensions, weights, and available models. Designed for use with Kohler RDC2/DC2 generator sets.
PreviewKohler Automatic Transfer Switches Product Guide
A comprehensive product guide detailing Kohler's Automatic Transfer Switches (ATS), including custom configuration options, controller features (MPAC1200, MPAC1500), and different ATS types like Standard, Bypass-Isolation, and Service-Entrance.
PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Models
Comprehensive overview of the Kohler RXT Automatic Transfer Switch (100-400 Amps), detailing standard features, available models, interface boards, specifications, dimensions, and model designation for standby power systems.
PreviewKohler KEP Automatic Transfer Switches: Service Entrance Rated
Explore the features and specifications of Kohler's KEP Series Automatic Transfer Switches, designed for service entrance applications. This document details standard features, controller capabilities, ratings, dimensions, and codes for these robust power switching units.
PreviewKohler KSS Automatic Transfer Switches: Features, Ratings, and Specifications
Comprehensive technical specifications for Kohler KSS Standard Specific-Breaker Rated Automatic Transfer Switches. Details features, controller options (MPAC 750, MPAC 1200), electrical ratings, dimensions, circuit breaker compatibility, accessories, and model designation.