Temperzone OPA 1410RLTM4FPQD(-Z) Econex Pro

Specifications and Wiring Diagrams

Specifications

ModelOPA 1410RLTM4FPQD(-Z) Econex Pro
ConfigurationHorizontal Supply Air
Item No. (Standard / Opposite Hand)876-141-701 / 876-141-710
Unit c/w Economiser (Standard / Opposite Hand)877-141-701 / 877-141-710
ConfigurationDownward Supply Air
Item No. (Standard / Opposite Hand)876-141-723 / 876-141-732
Unit c/w Economiser (Standard / Opposite Hand)877-141-723 / 877-141-732
Cooling capacity (net) 1146 kW
Cooling capacity (gross) range11.8 ~ 189 kW
Heating capacity 1145 kW
Heating capacity (gross) range12.9 ~ 181 kW
Electrical input - cooling45.1 kW
Electrical input - heating43.2 kW
EER / AEER (cooling) 13.24 / 3.22
COP / ACOP (heating) 13.35 / 3.34
Operating Range (outdoor ambient) - cooling-10°C ~ 50°C
Operating Range (outdoor ambient) - heating-10°C ~ 25°C
Master Controllerc.pCO
Slave ControllersUC8 (x4)
RefrigerantR32
Refrigerant Charge7.1 kg/sys.
Minimum floor area (@2.4m/5m below ceiling diffuser)27 m² / 6 m²
Compressor oil typePOE-46 (NXG5020 or equivalent)
Compressor typeInverter scroll (x4)
Power supply 23 ph. 400V ac 50Hz + N + E
Compressor (3ph.) run amps at rating cond.14.7 A/ph. (x4)
Compressor circuit breaker50 A (x4)
Indoor fan motor sizeEC Plug 3.65kW (x4)
Nominal air flow at rating conditions8 100 l/s
Indoor fan motor (3ph.)4.6 A/ph. (x4)
Outdoor fan motor (3ph.) - full load1.9 A/ph. (x4)
Outdoor fan motor max. ext. static pressure available120 Pa (@12,100 l/s)
Control circuit breaker (internal)4 A
Auxiliary power outlet (1ph.) overload setting10 A
Running amps (total system)69 / 67 / 74 A
Max. running amps (total system)116 / 111 / 121 A
RCD type recommendedtype B, 30mA, 3 pole
Net weight2064 kg
Shipping weight (excl. cowl)2204 kg
Net weight c/w Economiser2154 kg
Accessories:
Remote wired Service Interface Device (pGD1)201-000-379
Filters - rated EU4/G4 disposable019-400-005 600x500x50 (x3)
019-400-007 600x600x50 (x6)
Filters - rated EU4/G4 washable (NZ only)019-000-034 600x500x50 (x3)
019-000-031 600x600x50 (x6)

1 Tested in accordance with AS/NZS 3823

2 Voltage range: 380-440V

3 Filter sizes are nominal; refer to Temperzone for actual measurements.

Dimensions

Diagrams illustrate the physical layout, mounting points, and clearance requirements for the unit. Two main configurations are shown: Horizontal Supply Air and Downward Supply Air.

Horizontal Supply Air Configuration (OPA 1410RLTM4FPQD01(-Z))

This section details the unit's dimensions and point loads for the horizontal supply air configuration. Key dimensions and clearance requirements are provided, including minimum clearances for access and ventilation (e.g., 1000mm, 2000mm, 300mm). A table shows point loads (kg) for different support points (U, V, W, X, Y, Z) for both standard and economiser-equipped units.

ConfigurationU (kg)V (kg)W (kg)X (kg)Y (kg)Z (kg)
Std411339267327349371
c/w Ec.423360297339358377

Notes indicate minimum clearances for ventilation and access, and a recommendation to allow a minimum of 2m between coil faces when multiple units are placed side-by-side.

Downward Supply Air Configuration (OPA 1410RLTM4FPQD23(-Z))

This section presents the dimensional information for the downward supply air configuration. It includes overall dimensions and mounting details, similar to the horizontal configuration, with notes on clearances and side-by-side placement.

Diagrams show the unit's footprint, height, and air intake/outlet positions for the downward supply configuration.

Wiring Diagrams

The wiring diagrams provide a detailed electrical schematic for the Temperzone OPA 1410RLTM4FPQD(-Z) Econex Pro unit. They illustrate the interconnection of various electrical components, control systems, and safety features for proper installation, operation, and maintenance. The diagrams are broken down into multiple sheets, covering different aspects of the unit's electrical system.

General Wiring Overview

The schematics cover the main power distribution, including connections to circuit breakers for compressors, fans, and control circuits. They detail the integration of the Carel c.pCO controller (UC8) and its associated inputs and outputs for sensors and actuators.

Compressor Module Wiring (CMM)

Wiring for up to four compressor modules (CMM1-CMM4) is shown. Each module is connected to a Variable Speed Drive (VSD) for precise motor control. Connections include power supply, control signals from the UC8 controller, and safety interlocks, routed via terminal blocks (e.g., TB1-TB21) and cables (e.g., CBL10, ETH3).

Fan Motor Wiring (IFM & OFM)

Detailed schematics are provided for Indoor Fan Motors (IFM1-IFM4) and Outdoor Fan Motors (OFM1-OFM4). These diagrams illustrate connections to VSDs, control signals from the UC8 controller, and power supply. Specific wiring notes and terminal connections are provided for different fan manufacturers, including Sanmu, Fanstech, EBM, and Rosenberg fans, highlighting variations in color coding and terminal assignments (e.g., RSB, RSA, GND, VSP/PWM).

Control System and Sensor Connections

The diagrams extensively map the connections to the Carel c.pCO controller (UC8). This includes inputs for various sensors such as ambient temperature, return air (RA) temperature/RH, supply air (SA) temperature/RH, and fresh air (FA) temperature/RH. Connections for optional sensors like CO2 and humidity sensors are also indicated. Terminal blocks (e.g., TB22-TB28, J1-J30) are used for connecting external control devices, BMS interfaces, and communication modules (Ethernet, Modbus).

Optional Features and System Configurations

Wiring details for optional features such as reheat units, economizers, and external controllers are included. The diagrams differentiate between units with and without reheat functionality, specifying the number of Electronic Expansion Valves (EEVs) and modulating valves required.

Key Components and Terminals Mentioned:

Specific notes are provided regarding wire color coding for different fan types and the importance of correct sensor connections for unit performance.

PDF preview unavailable. Download the PDF instead.

OPA 1410RLTM4FPQD(-Z) Specifications 0923 Adobe PDF Library 17.0 Adobe InDesign 18.5 (Macintosh)

Related Documents

PreviewTemperzone Econex Pro OPA 680RLTB2FPQD-Z Specifications and Wiring
Detailed specifications and wiring diagrams for the Temperzone Econex Pro OPA 680RLTB2FPQD-Z horizontal, downward, and upward supply air units. Includes technical data, dimensions, and electrical schematics.
PreviewTemperzone Packaged Rooftop Air Conditioners R32 Econex Series Technical Data
Detailed technical data, specifications, performance charts, and dimensions for Temperzone's R32 Econex and Econex Pro series packaged rooftop air conditioning units, designed for commercial applications.
PreviewtemperZONE OPA Econex Pro Technical Guide: Features, Modes, and Controls
Comprehensive technical guide for temperZONE's OPA Econex Pro series air conditioning units. Covers comfort modes, controller overview, settings, and system information for models OPA 171, 211, 680, 820, 970, 1410, 1710, and 2110.
PreviewTemperzone Ducted Packaged Units: Technical Data for Econex Series R32
Comprehensive technical data for Temperzone's Econex Series R32 Ducted Packaged Units, including specifications, performance data, dimensions, sound levels, and nomenclature for models OPA 680, 820, and 970.
PreviewTemperzone Econex Pro OPA 211RLTFYD(H/V) Specifications and Wiring
This document provides detailed specifications, dimensions, and electrical wiring schematics for the Temperzone Econex Pro OPA 211RLTFYD(H/V) air conditioning unit. It includes technical data on cooling and heating capacities, electrical inputs, operating ranges, refrigerant details, and component specifications, along with comprehensive wiring diagrams for client and internal connections.
PreviewTemperzone Econex Pro Packaged Units: Advanced Humidity Control and Energy Efficiency
Discover the Temperzone Econex Pro Air Cooled Packaged Units, designed for superior humidity control, energy efficiency, and reliability. Featuring R32 refrigerant, inverter compressors, and EC fans, these units offer advanced performance for commercial and industrial applications.
PreviewTemperzone Econex Pro OPA 211RLTFYD(H/V) - Technical Specifications and Wiring
Detailed technical specifications, dimensions, and electrical wiring diagrams for the Temperzone Econex Pro OPA 211RLTFYD(H/V) air conditioning unit, featuring R32 refrigerant and UC8 controller.
PreviewTemperzone OPA 211RLTFY(H/V) Econex Air Conditioner Specifications and Wiring
Detailed specifications, dimensional data, and electrical wiring schematics for the Temperzone OPA 211RLTFY(H/V) Econex air conditioning unit, including component definitions and DIP switch settings.