R 4321/4322
Page: 1 / 2

Wiring diagram: Issue: 04/2009

7308 6720618975

Proj. no.: Mat. no.:

Boiler control panel R4321/4322

US Signal hours run Signal fault Boiler water temp. controller (TR) Burner enable L via safety equipment 105 warmer colder Signal hours Output voltage L1 Burner close/off Burner open/on

Note!
Installation, circuit breaker, main shutoff switch, emergency shutoff switch and protective measures in accordance with local regulations. Please note! Never use ground wire (green/yellow) for controls purposes. Verify that power is connected to the appropriate terminals. This control must be hard wired.
1) Contact opens when the selected temperature is exceeded. 2) The total current for each power circuit (L1, L2) must not exceed 10A.
This value must be adhered to. Verify maximum current draw after start-up in order to avoid damage to the device! 3) Please note! Only one MEC2 can be allocated to each control panel. The MEC2 can be plugged into the control panel or room wall-mounted using the wall installation kit (optional) wired to the ZM or FM module. 4) Terminal for optional external safety equipment. Interrupts the burner only! 5) When connecting multiple ECOCAN-BUS components, the S1 hook switches (termination on the NM482) of the two outermost ECOCAN-BUS devices must be closed. 6) L2: fuse protection of the modules in slots A, 1, and 2 L1: fuse protection of the modules in slots 3 and 4
B

Boiler module ZM434

Controller module CM431

Slots 3 & 4 for FM modules

Slots 1 & 2 for FM modules

Power module NM482 (behind the controller module)

MEC23) or boiler display

AUT 0
max

AUT 0

1

2

A

B

3

4

60 50

90 80 70 AUT

Connector socket for external service units BUS (internal)

Switching states

M

Switch position

Stage 1 Stage 2/ modulating

k1 k2 k3

Button

Button

pressed pressed

AUT
0
max l+ll

Control mode

Control mode hotter

Control mode colder

M
Switch (PK) (SR) (SR)
position k4 k5 k6 0

AUT

Control mode

Control mode

Control mode

= warmer = colder

Control voltage 120V Extra-low voltage for sensors

A

Controller module CM431

Power module NM482

ECO BUS 123

5) S1

Netz NL

L1 N N L2

ECOCAN-BUS AWG18 shieled

AUT

Operation

1a 1b 2a 2b

1

2

Fuses
each 10AT 2) 6)

L1 L2

Manual

1

reset

2

3

high limit (STB) 1)

1b 1a 1

NL
Power supply for additional FM module at slot 3 (4)

Boiler water

2 4 temperature

1

controller (TR) 1)

Boiler module ZM434

AUT 0 max

l+ll

k1

Input autom. control

1

k2

k3

M
AUT
0

k4

k5

k6

Netz NL N1 2 3

4 5 6 7 8 9 10 11 12 13

ES FG FZ FK FA BF UBR UPU
121212121212- +- +
-+

Power supply for additional FM module at slot 1 or 2
NL

AWG18

SI

NL

17 18 19

AWG12

/PE N L
Mains
120V 60Hz Max. permissible fuse rating
20AT on site

Component 1
Component 2

4)
23 1
23 1

Connection example for safety
components (on site)

BR 4 8 9 10 11 12
4 8 9 10 11 12 N B4 S3 T1 T2 L1
Gas/oil burner Burner connection stage 1
max. 8A2) (BR)

SG 4567
Terminals for
vent damper (SG)

UE N1 2 3 4
Terminals for
flue gas monitoring (UE)

SR 41 43 44
AWG14
41 43 44 N
Return temp. actuator (SR) 120V max 5A 2)

PK 61 63

BR II 36 37 38 39

AWG14

N
ML
Boiler pump (PK) 120V
max 5A 2)

36 37 38 39 B5 T6 T7 T8
Burner connection stage 2 or connection for modulating burner (BRII)

-+ 12

12

External Flue gas fault input temp. sensor (zero volt) (FG)
(ES) or input fuel changeover two-fuel burner 5VDC 10mA

Auxiliary temp. sensor
(FZ)

12

Boiler water temp. sensor
(FK)

Outdoor Remote control

temp. sensor MEC2 3)

(FA)

or BFU

(BF)

Voltage output 0-10V burner (UBR)

M
Voltage output 0-10V pump (UPU)

For system example, see back of page

Boiler control panel R4321/4322

Proj. no.: Mat. no.:

7308 6720618975

Wiring diagram: Issue: 04/2009

R 4321/4322
Page: 2 / 2

System example 1

FA

BF

AWG18

ES

Mains AWG14

AWG18

AWG18

R 4321

AWG14 AWG18

UBR AWG18 BR

FK BR

AWG18
FZ
M SR

Buderus Thermostream boiler or LT boiler with base line temperature
Example of the connection of a Thermostream boiler or LT boiler with low-end temperature
control via a separate boiler circuit actuator (SR).

System example 3

FA

BF

AWG18

ES

AWG18
Mains AWG14
R 4321

AWG18 AWG18 AWG14
AWG18

UBR AWG18 BR

FK BR

UPu
FZ PK 1)

Legend:
BF remote control MEC2 or BFU BR burner ES external fault input (dry contact) FA outdoor temperature sensor FK boiler water temperature sensor FZ auxiliary temperature sensor PK boiler pump SR return temperature actuator UPu voltage output 0-10V pump UBr voltage output 0-10V burner

Buderus LT boiler
Example of connecting a low temperature boiler. Low temperature boilers require heating circuit actuators to control the operating conditions.

1)

A boiler circuit pump may be controlled when using low loss headers. Terminal UPu only required for modulating boiler circuit pump (0-10V).

System example 2
FA
AWG18

AWG18
Mains AWG14

R 4321

FK

BrII

BR

BR

BF ES

AWG18
AWG14 AWG14

AWG18

UPu

FZ PK

M SR

Buderus Thermostream boiler
Example for integration of Thermostream boilers. Control via boiler actuator. Terminal UPu only required for modulating boiler circuit pump.

System example 4

FA
AWG18

AWG18
Mains AWG14

R 4321

FK

BrII

BR

BR

BF ES

AWG18 AWG14
AWG14 AWG18
PK FZ

M SR

Buderus LT boiler with minimum return temperature
Example for integration of boilers with return temperature control.
Control via separate boiler actuator (SR).

US

