Schneider Electric TM1730 Series Industrial Controllers
This document provides technical specifications, wiring diagrams, safety instructions, and mounting guidelines for the Schneider Electric TM1730 series of industrial controllers.
Safety Warnings
[DANGER] HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power from all equipment, including connected devices, before removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires, unless specified otherwise in the appropriate hardware guide.
- Always use a properly rated voltage sensing device to confirm power is off where and when indicated.
- Replace and secure all covers, accessories, hardware, cables, and wires, and confirm that a proper ground connection exists before applying power to the unit.
- Use only the specified voltage when operating this equipment and any associated products.
- Failure to follow these instructions will result in death or serious injury.
[WARNING] UNINTENDED EQUIPMENT OPERATION
- Use appropriate safety interlocks where personnel and/or equipment hazards exist.
- Install and operate this equipment in an enclosure appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
- Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
- Do not disassemble, repair, or modify this equipment.
- Do not connect any wiring to reserved, unused connections, or to connections designated as No Connection (N.C.).
- Failure to follow these instructions can result in death, serious injury, or equipment damage.
[WARNING] POTENTIAL OF OVERHEATING AND FIRE
- Do not connect the equipment directly to line voltage.
- Use only isolating SELV, Class 2 power suppliers/transformers to supply power to the equipment.
- Failure to follow these instructions can result in death, serious injury, or equipment damage.
California Proposition 65 Warning:
This product can expose you to chemicals including lead and lead compounds which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.
Ensure that all equipment used and systems designed comply with all applicable local, regional, and national laws. Failure to follow these instructions can result in death, serious injury, or equipment damage.
Product Overview
The TM1730 series offers various models of industrial controllers with different features, including display capabilities, digital and analog I/O, and communication ports.
| Reference | Description | Display | Digital Outputs | Digital Inputs | Analog Outputs | Analog Inputs | Communication Ports | Power Supply |
|---|---|---|---|---|---|---|---|---|
| TM1730BM22R | M173 Optimized Blind 22 I/Os | No | 5 | 6 | 4 | 7 | CAN Expansion bus | 24Vac/Vdc |
| TM173ODM22R | M173 Optimized Display 22 I/Os | Yes | 5 | 6 | 4 | 7 | USB (type C), RS-485 serial ports | 24Vac/Vdc |
| TM173ODM22S | M173 Optimized Display 22 I/Os, 2 SSR | Yes | 3 + 2 SSR | 6 | 4 | 7 | USB (type C), RS-485 serial ports | 24Vac/Vdc |
| TM173ODEM22R(1) | M173 Optimized Display 22 I/Os, EEVD | Yes | 5 | 6 | 4 | 7 | USB (type C), RS-485 serial ports | 24Vac/Vdc |
| TM173OFM22R(1) | M173 Optimized Flush mounting 22 I/Os | Yes | 5 | 6 | 4 | 7 | USB (type C) | 24Vac/Vdc |
| TM173OFM22S(1) | M173 Optimized Flush mounting 22 I/Os, 2 SSR | Yes | 3 + 2 SSR | 6 | 4 | 7 | USB (type C), RS-485 serial ports | 24Vac/Vdc |
| TM173DLED(1) | M173 Optimized Remote Display LED | Yes | - | - | - | - | * | * (Powered by the controller) |
(1) Available soon. Contact Sales and Technical Support for models availability.
Component Labels:
- 1 - Digital outputs
- 2 - Power supply
- 3 - Display
- 4 - Enter key
- 5 - Escape key
- 6 - USB (Type C)
- 7 - Analog inputs
- 8 - Valve driver output (only for TM173ODEM22R model)
- 9 - Clip-on lock for 35-mm (1.38 in.) top hat section rail (DIN rail)
- 10 - Connector for remote display
- 11 - Digital inputs
- 12 - Serial port RS-485
- 13 - Analog outputs
- 14 - CAN Expansion bus
- 15 - Navigation keys
- 16 - Connector to communication module
- 17 - Battery backup socket connector (only for TM173ODEM22R model)
Mounting Instructions
The TM1730 series controllers can be mounted using two primary methods:
DIN Rail Mounting
Mounting on a 35 mm (1.38 in.) top hat section rail (DIN rail) using appropriate brackets (e.g., NSYSDR200, NSYDPR200T, NSYSDR200BD).
Flush Panel Mounting
Mounting on a panel using special brackets provided. Dimensions for various models are specified for flush mounting.
Wiring and Connections
Power Supply
The controllers can be powered by ~24Vac or 20-38Vdc. Connections are made via CN7 and CN6 connectors.
A Type T fuse rated at 1.25 A is recommended for the power supply.
Digital Outputs (CN6)
Various models offer different types of digital outputs, including relay SPST (3 A @ 250 Vac) and SSR (0.5 A @ 240 Vac).
Digital Inputs (CN9)
Provides digital input terminals (D11 to D16) and a ground (GND) connection.
Analog Outputs (CN8)
Provides analog output terminals (AO1 to AO4).
Analog Inputs (CN10)
Supports various analog input types including NTC, PTC, Pt1000 sensors, and current/voltage signals (0-20mA, 4-20mA, 0-10V, 0-5V ratiometric). Maximum current limits are specified for 5Vdc and 24Vdc outputs.
Communication Interfaces
RS-485 (CN2, CN3)
Supports Modbus SL communication. Requires a 120 Ω terminal resistor if it is the end device of the bus.
CAN Expansion Bus (CN1)
Supports CAN expansion bus communication. Requires a 120 Ω terminal resistor if it is the end device of the bus.
USB (Type A and Type C)
USB ports are available for connection to PCs or USB pen drives, compatible with EcoStruxure Machine Expert HVAC V1.6 or later.
Valve Outputs (CN5)
Provides valve outputs (VMOT, W±) with built-in protection against overload and short-circuit (only for TM173ODEM22R model).
LED Indicators and Operation
The controllers feature LED indicators for status and operating modes.
LED States and Operating Modes
- Alarm: Red
- Heating: Green
- Cooling: Green
- Standby: White
- Defrost: White
- Economy: White
- Edit Mode: White
- Time: White
- Temperature: White
- Pressure: White
Additional indicators show units of measure (e.g., %, units) and utility functions.
Functions P1-P4
- P1: Function 1
- P2: Function 2
- P3: Function 3
- P4: Function 4
- 1, 2, 3, 4: Utilities / Circuits / Services / Utility Programs
Technical Data
Standards Compliance
The product complies with harmonized Standards EN 60730-1 and EN 60730-2-9.
Environmental and Operating Conditions
- Construction: Electronic automatic Incorporated Control
- Purpose of control: Operating control (non-safety related)
- Environmental front panel rating: Open Type
- Degree of protection: IP20
- Method of mounting: See page 4
- Type of action: 1.B/1.Y
- Pollution degree: 2 (Normal)
- Overvoltage category: II
- Rated impulse voltage: 2500 V
- Ambient operating temperature: -20...+65 °C (-4...+149 °F) for TM173OB/D, -20...+55 °C (-4...+131 °F) for TM173ODEM22R, -30...+70 °C (-22...+158 °F) for TM173OFM22.
- Humidity: 5...95% (non-condensing)
- Transportation and storage temperature: -30...+70 °C (-22...+158 °F)
Power and Consumption
- Power supply: 24 Vac (±10%) 50/60 Hz or 20...38 Vdc
- Power draw: 10 W
Disposal
The equipment (or product) must be subjected to separate waste collection in compliance with the local legislation on waste disposal.
Hazardous Substances
The following table indicates the presence of hazardous substances according to SJ/T 11364. 'O' indicates compliance with GB/T 26572 limits, 'X' indicates exceeding limits.
| Part Name | Lead (Pb) | Mercury (Hg) | Cadmium (Cd) | Hexavalent Chromium (Cr(VI)) | PBB | PBDE |
|---|---|---|---|---|---|---|
| Metal parts | X | O | O | O | O | O |
| Plastic parts | O | O | O | O | O | O |
| Electronic circuits | X | O | O | O | O | O |
| Contacts | O | O | O | O | O | O |
| Cables & cabling accessories | O | O | O | O | O | O |
This table is made according to SJ/T 11364. 'O' indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. 'X' indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572.
Manufacturer Information
Eliwell Controls s.r.l.
Via dell'Industria, 15 - Zona Industriale Paludi
32016 Alpago (BL) ITALY
Phone: +39 0437 986 111
Technical helpline: +39 0437 986 300
Website: www.eliwell.com
UK Authorized Representative:
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom