Notifier ACM-30 Annunciator
Generalities
The ACM-30 annunciator allows fire alarm control panels (PCAI) or network control displays (NCD) from the NOTIFIER™ INSPIRE™™ range to be equipped with remote annunciators connected in series. Rows of LEDs locally indicate, within the PCAI or remotely, the status of the system's addressable points. The ACM-30 annunciators are designed to serve as full-function annunciators that can both receive system status information and transmit commands to the control panel. This allows the annunciator to remotely execute control panel functions in addition to displaying system status.
General system functions, such as signal silencing, system reset, and local commands (local acknowledgment and visual indicator test), are accessible via the annunciator's keypad contact points. Each ACM-30 key can be programmed to function with corresponding LEDs or independently. All buttons and LEDs are customizable. There is no fixed system function on the ACM-30. In independent mode, a single ACM-30 can be configured to display up to 60 point indicators.
Communication between the PCAI or NCD and these annunciators is via a two-wire, limited-power serial interface called the AIO bus and can be connected to the main and local bus. The ACM-30 is powered by a separate, limited-power loop from the control panel, which is inherently supervised by these annunciators (loss of power results in an annunciator communication failure to the control panel).
The N16 PCAI supports a maximum of 80 annunciators. Up to 10 ACM-30 annunciators can be configured as routers, with each router supporting up to 15 peripheral ACM-30 annunciators.
The ACM-30 capacitive touch keypad consists of 30 keys, each associated with two LEDs. The LEDs can be programmed for red, green, yellow, white, amber, blue, cyan, or violet. The keypad header features two LEDs and additional buttons intended for use as an online/power LED, system fault LED, visual indicator test button, and silence/acknowledge switch. Each annunciator also contains a local piezoelectric sounder for audible indication of alarm and trouble conditions at each annunciator.
Features
- Command touch keypad option allowing remote control of system relays or silencing, reset, and evacuation
- Color-programmable LEDs
- LEDs can be programmed to display the status of indicator circuits or control relays, as well as system conditions
- LED option to indicate active/trouble circuit status or anomalies, or a denser display option dedicated solely to alarms
- Programmable in independent mode (each contact point and LED associated with distinct points) or cooperative mode (both LEDs indicate the point linked to the contact)
- Alarm and re-acknowledgement with flashing upon the occurrence of new conditions
- Local sounder activated for alarm or trouble conditions, with optional silence/acknowledge button (programmable)
ACM-30 with ABB-1 Enclosure
The ACM-30 is based on hardware modules that allow its configuration to be adapted to specific requirements. Standard backboxes and mounting diagrams, including specific remote cabinets, facilitate the integration of annunciators with other system components. STS-1 anti-tamper security switches are available.
Operation
The ACM-30 provides up to 80 annunciators connected in series to the N16 system, each with a capacity of 62 points, for a total capacity of 4960 points. System alarm and/or trouble conditions can be announced by point or in a grouped or zoned configuration. Control of system operational commands, such as signal silencing, system reset, and local announcement commands (such as local acknowledgment and visual indicator test), can be performed using the module's capacitive touch buttons. Each ACM-30 key and LED is fully configurable using VeriFire tools.
Local or remote power supplies, combined with serial communications, allow the ACM-30 to be positioned virtually anywhere within the protected premises.
Temperature and Humidity Ranges: This system meets NFPA requirements for operation from 0°C to 49°C (32°F to 120°F); and relative humidity (non-condensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the service life of backup batteries and electronic components may be negatively affected by extreme temperature and humidity ranges. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal ambient temperature of 15°C to 27°C (60°F to 80°F).
Power Requirements: 18-30 VDC power supply, 93 mA maximum current. NOTE: The input power must be limited and non-resettable.
Product Range Information
- ACM-30: The ACM-30 annunciator control module includes 62 programmable color LEDs (red, green, yellow, white, orange, blue, cyan, or violet), active, trouble, and disable status LEDs, 32 momentary contact points, a system trouble LED (programmable for other functions), a power/online LED (programmable for other functions), and a local piezoelectric sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions. Includes instructions.
- ABB-1: The annunciator backbox-1 (black) allows for surface or semi-flush mounting of an ACM-30. It features knockouts provided for use with 0.5" (1.27 cm) conduit. The annunciator attaches directly to the trim plate. 10.95 in (27.8 cm) height x 9.19 in (23.34 cm) width x 3.9 in (9.9 cm) depth.
- ABB-2: The annunciator backbox-2 (black) allows for surface or semi-flush mounting of two ACM-30 annunciator control units. Knockouts are provided for use with 0.5" (1.27 cm) conduit. The annunciators attach directly to the trim plate. 10.93 in (27.8 cm) height x 15.79 in (40.1 cm) width x 4.61 in (11.7 cm) depth.
- DP-T2A: ABF-1DB(C). Recessed alarm cabinet with door. Requires ACM-1DB-RTO for mounting an ACM-30. Trim plate for touchscreen and two ACM-30 annunciators to be installed in a CAB-5 series cabinet. Modules mount directly to the threaded studs of the DP-T2A.
- DP-T2A-CB4: Trim plate for touchscreen and two ACM-30 annunciators to be installed in a CAB-4 series cabinet. Modules mount directly to the threaded studs of the DP-T2A-CB4.
- DP-4A: The DP-4A trim plate allows for the installation of one to four ACM-30 annunciators in the CAB-5 series cabinet. The annunciators mount directly to the threaded studs of the DP-4A.
- DP-4A-CB4: The trim plate for annunciator panels (black) allows for the installation of one to four ACM-30 annunciators in the cabinet. The DP-4A-CB4 hinges onto the CAB-4 series cabinet. Modules mount directly to the threaded studs of the DP-4A-CB4.
- ABP-1: The annunciator blanking plate is a flat, black trim plate designed to cover unused module locations in backboxes or trim panels. Studs for a variety of module mounting options are available.
- STS-1: The STS-1 anti-tamper security switch prevents activation of router contact points or any peripheral device while the door is closed. The anti-tamper switch kit includes hardware for mounting to the ABB-1 or ABB-2.
- ACM-1DB-RTO: Adapter plate for mounting an ACM-30 in an ABF-1DB, replacing the ACM-24AT or ACM48A.
Agency Listings and Approvals
The file numbers mentioned below relate to specific listings for the modules discussed in this document. In some cases, certain modules or applications may not yet be listed by approval agencies or may be pending approval. Please consult NOTIFIER for the status of the latest approval.
- UL/ULC Listed: S635
- FM Approved: FM23FPUS0095
- CSFM: 7165-0028:0516
- FDNY: COA#001761
- Seismic Certified per IBC 2024: VMA-45894-01C
- OSHPD Approved: OSP-0072
Standards and Codes
The following listings and approvals apply to the NCD. In some cases, certain modules or applications may not yet be listed by approval agencies or may be pending approval. For current product approval status, please contact the factory.
- UL 864, 10th Edition (Control Units and Accessories for Fire Alarm Systems).
- UL2017 (General-Purpose Signaling Devices and Systems)
- UL 2610 (Commercial Residential Security System Control Units and Systems)
- ULC-S527-19 (Control Units and Accessories for Fire Alarm Systems)
- Must be installed in accordance with NFPA 72 of the National Fire Protection Associations
Panel Compatibility
- N16 Series
- NCD
Installation
The link between ACM-30 annunciators and the main fire alarm control panel is via an EIA-485 multipoint loop, eliminating the need for complex and costly wiring. Four wires are required: two for EIA-485 communications (twisted pair) and two for regulated 24 VDC power. All field wiring terminations use removable compression-type terminal blocks for ease of installation, wiring, and circuit testing.
The ACM-30 can be used to manually select speaker and telephone circuits. In this application, they are typically mounted in the main control near the microphone and telephone handset.
For remote announcement applications, the modules are typically mounted in special ABB enclosures.