Friedrich Renaissance™ Commercial F-Series™ RGEDYB Packaged G/E Units

Capacities: 7.5 to 12.5 Tons

Standard Features

Key Specifications and Capacities

Capacities: 7.5, 8.5, 10, 12.5 Tons

Power Options: 208-230 V, 3 PH; 460 V, 3 PH; 575 V, 3 PH

Note: Information provided for pre-sale only. Products will not be produced or shipped until ratings are certified to the Department of Energy.

Unit Dimensions Overview

The diagrams illustrate the physical layout and dimensions of the RGEDYB units. Key dimensions include:

Performance Specifications Table

SpecificationUnitRGEDYB090RGEDYB102RGEDYB120RGEDYB150
Nominal Cooling CapacityBtu/h [kW]90,000 [26.38]102,000 [29.89]120,000 [35.17]150,000 [43.96]
Net Cooling CapacityBtu/h [kW]85,000 [24.9]96,000 [28.13]114,000 [33.4]142,000 [41.61]
Net Sensible CapacityBtu/h [kW]63,750 [18.68]72,000 [21.10]85,500 [25.06]106,500 [31.21]
Net Latent CapacityBtu/h [kW]21,250 [6.23]24,000 [7.03]28,500 [8.35]35,500 [10.40]
Stages of Heating / Cooling2/22/22/22/2
EER/IEER up to11.0/14.611.0/14.611.0/14.610.8/14.0
Nominal AirflowCFM [L/s]3,000 [1,416]3,400 [1,604]4,000 [1,888]5,000 [2,360]
Heat Capacity Code1520
Gas Heating Input (1st Stage / 2nd Stage)Btu/h [kW]105,000/150,000 [30.76/43.95]
Not Available
105,000/150,000 [30.76/43.95]
157,500/225,000 [46.16/65.92]
105,000/150,000 [30.76/43.95]
157,500/225,000 [46.16/65.92]
105,000/150,000 [30.76/43.95]
157,500/225,000 [46.16/65.92]
Estimated Net Weightlbs. [kg]839 [381]868 [364]1,004 [455]1,094 [496]
Estimated Shipping Weightlbs. [kg]878 [398]907 [411]1,043 [473]1,133 [514]

Preliminary information based on preliminary estimates. Not a representation of energy use or efficiency of these models.

Model Number Nomenclature

The model number is constructed using a specific sequence of characters, each representing a feature or configuration:

Base Model: RGEDYB

PositionCodeDescription
1RBrand: Friedrich
2, 3GEUnit Type: Packaged Gas/Electric
4DCabinet Type: Medium Commercial
5YRefrigerant: R-454B
6BEfficiency Level: Standard Efficiency
7, 8, 9090, 102, 120, 150Capacity: 7.5 Ton, 8.5 Ton, 10 Ton, 12.5 Ton
10AMajor Series: 1st Design
11C, D, YVoltage: 208/230V 3PH, 460V 3PH, 575V 3PH
12F, G, HDrive: Belt Drive - VFD Low, Medium, High
13, 1415, 20, 22Heat Capacity: 150,000, 205,000, 225,000 Btu/h
152, BHeat Configuration: 2 Stage, 2 Stage Stainless
16A, B, C, DControl: CoreCommand™, CoreCommand™ & Comfort Alert®, ClearControl™, ClearControl™ & Comfort Alert®
17AMinor Series: 1st Design
18, 19, 20AA0, etc.Option Code (e.g., EC = Economizer, RS = Return Smoke Detector, SS = Supply & Return Smoke Detector, LV = Louver Protection, RH = Reheat, HA = Hinged Access, CC = Coil Coating, DC = Disconnect Switch, LF = Low Ambient & Freeze Stat, NP = Non-Powered Convenience Outlet)

Note: Not all model/option combinations are available. Refer to the product specifications sheet or rapidspec.com for specific details.

Available Accessories

A variety of accessories are available for the RGEDYB series. Some options may require factory installation.

AccessoryModel NumberAccessoryModel Number
BACnet® Communication CardRXRX-AY01Motorized Fresh Air Damper DDCRXRF-ADC1
Carbon Dioxide Sensor (Wall Mount)RXRX-AR02Outdoor Coil Louver Kit - 7.5 & 8.5 TonRXRX-ADD04A
Comfort Alert (1 Per Compressor)RXRX-AZ02Outdoor Coil Louver Kit - 10 & 12.5 TonRXRX-ADD04B
Dual Enthalpy Kit (for Honeywell® JADETM)RXRX-BV01Power Exhaust (230V) Convertible MicroMetlRXRX-CDF01C
Dual Enthalpy Kit DDC (for Honeywell DDC)RXRX-BV02Power Exhaust (460V) Convertible MicroMetlRXRX-CDF01D
Dual Enthalpy, Temperature and Humidity Sensor (for Siemens®)PD555460Horizontal RRS (230V) Horizontal RRSRXRX-RDF03C
Economizer Universal DDC Interface KitRXRX-DDC01Horizontal RRS (230V) Vertical RRSRXRX-RDF03C
Economizer, Single EnthalpyHorizontal RRS (460V) Horizontal RRSRXRX-MDF01C
Horizontal Downflow MicroMetl Economizer, Siemens ControlsRXRD-11MDDAM3Horizontal RRS (460V) Vertical RRSRXRX-MDF03C
RRS Rooftop Systems® EconomizerRXRD-41MDDAM3Roofcurb AdapterRXRX-DDCAE
DDC MicroMetl Economizer, Honeywell DDC ControllerRXRD-01MDDBM3Roofcurb, 14"RXRX-DGC14
MicroMetl Economizer, Siemens ControlsRXRD-11MDHAM3Roofcurb, 14" WeldedRXKG-SD14
RRS Rooftop Systems EconomizerRXRD-41MDHAM3Roofcurb, 24"RXRX-DGC24
DDC MicroMetl Economizer, Honeywell DDC ControllerRXRD-01MDHBM3Roofcurb, 24" WeldedRXKG-SD24
Economizer, No Controls (Downflow/Vertical) MicroMetl Economizer, No Controls, Belimo® ActuatorRXRD-31MDDAM3Room Humidity SensorRHC-ZNS4
Flue DiverterRXRX-DFG04Room Temperature and Relative Humidity SensorRHC-ZNS5
Freeze Stat KitRXRX-AM01Smoke Detector Kit, ReturnRXRX-BS03
LonWorks® Communication CardRXRX-AY02Smoke Detector Kit, Return/SupplyRXRX-BS04
Low-Ambient Control KitRXRZ-A04Unfused Service DisconnectRXRX-BP01
LP Conversion KitRXGJ-FP39Unwired Convenience OutletRXRX-BN01
Manual Fresh Air DamperRXRF-ADA1UV-C Light Kit for 208/230VRXRX-UVC22C
MERV 8 Filter 7.5 & 8.5 TonRXMF-M08A22020UV-C Transformer Kit for 460V or 575VRXRX-UVCTC
MERV 8 Filter 10 & 12.5 TonRXMF-M08A22520
MERV 13 Filter 7.5 & 8.5 TonRXMF-M13A22020
MERV 13 Filter 10 &12.5 TonRXMF-M13A22520

PDF preview unavailable. Download the PDF instead.

RGEDYB Pre-Sale MFR-1132 ?hsLang=en Adobe PDF Library 17.0 Adobe InDesign 19.4 (Windows)

Related Documents

PreviewFriedrich Breeze™ Outdoor Inverter Heat Pump Condenser Installation and Operation Manual
Installation and operation manual for Friedrich Breeze™ Outdoor Inverter Heat Pump Condensers. Covers safety, installation, operation, maintenance, and troubleshooting for models WFPU17Z243C-1, WFPU18Z363C-1, WFPU18Z483C-1, WFPU17Z603C-1.
PreviewFriedrich Renaissance™ RACCYB Packaged Air Conditioners | 3-6 Tons Product Overview
Detailed product overview of Friedrich Renaissance™ Commercial F-Series™ RACCYB packaged air conditioners, covering capacities from 3 to 6 tons. Includes standard features, technical specifications, model nomenclature, and available accessories.
PreviewFriedrich Floating Air Series Ductless Mini-Split Installation and Operation Manual
This comprehensive guide provides essential information for the installation and operation of Friedrich Floating Air Series ductless split single zone indoor wall-mounted air conditioning units. It covers safety precautions, installation procedures, room size restrictions, clearances, piping, electrical connections, startup, and operation for models using R-32 and R-454B refrigerants.
PreviewFriedrich Ductless Split Indoor Unit Installation & Operation Manual
This manual offers detailed instructions for the installation and operation of Friedrich's Ductless Split Indoor Wall-Mounted Units. It covers models designed for R-32 and R-454B refrigerants, providing essential safety precautions, step-by-step installation procedures, and operational guidance.
PreviewFriedrich VRP: Variable Refrigerant Packaged Heat Pumps for Lodging & Multifamily
Explore the Friedrich VRP series, offering VRF performance with single-package simplicity. Discover advanced features like Precision Inverter technology, low-ambient heating, superior humidity control, and IAQ solutions for lodging and multifamily applications.
PreviewFriedrich VRP Variable Refrigerant Packaged Heat Pump Product Profile
Discover the Friedrich VRP, an innovative and intelligent Variable Refrigerant Packaged Heat Pump system. It provides superior cooling, efficient heating, advanced humidity control, and optional fresh air integration, ensuring optimal comfort and energy savings with its Precision Inverter technology.
PreviewFriedrich CCV18A30A Room Air Conditioner Specifications | ENERGY STAR Certified
Detailed specifications for the Friedrich CCV18A30A ENERGY STAR certified room air conditioner, including energy efficiency, cooling capacity, dimensions, and certification details.
PreviewFriedrich Zoneaire Select R-32 Series PTAC Service Manual
This service manual provides detailed technical information, troubleshooting guides, and repair procedures for Friedrich Zoneaire Select R-32 Series PTAC and Heat Pump units, including standard chassis models.