Siemens 9410DC Power and Energy Meter
Model: 9410DC
Manufacturer: Siemens
Product Type: Power and Energy Meter
Official Information: www.usa.siemens.com/pds/9410
Document ID: 7EN05-0336
Safety Precautions
? DANGER / PELIGRO / DANGER / GEFAHR
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
- Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
- Always use a properly rated voltage sensing device to confirm that all power is off.
- Do not exceed the device's ratings for maximum limits.
- Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.
- Never short the secondary of a voltage transformer (VT).
- Never open circuit a current transformer (CT).
- Always use grounded external CTs for current inputs.
Failure to follow these instructions will result in death or serious injury.
Safety Actions:
- Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
- Always use a properly rated voltage sensing device to confirm that all power is off.
Dimensions
Diagram shows overall dimensions and mounting cutout.
| Dimension | Value (mm) | Value (in) |
|---|---|---|
| Overall Height | 105 | 4.13 |
| Overall Width | 96 | 3.78 |
| Depth | 78.5 | 3.09 |
| Base Width | 90.5 | 3.56 |
| Base Height | 90.5 | 3.56 |
| Overall Width (with mounting) | 111 | 4.37 |
| Mounting Cutout (approx.) | 92.0 +0.8 | 3.62 +0.03 |
Note: Adding option modules will increase meter base dimensions.
Minimum clearance between mounted meters: approximately 121 mm (4.76 in) horizontally and 132 mm (5.20 in) vertically.
Mounting
Diagram illustrates panel mounting with a square cutout and clip/screw mechanism.
The device is designed for panel mounting. A square cutout of approximately 92.0 mm x 92.0 mm (3.62 in x 3.62 in) is required. The mounting mechanism uses clips or screws, with a recommended gap of 1-6 mm (0.04 - 0.25 in) for installation.
Wiring
The 9410DC meter supports various wiring configurations for power, voltage, current, and communication.
Control Power
Input voltage ranges:
- AC at 50/60 Hz ± 10%: 90 to 415 V ± 10%
- AC at 400 Hz: 90 to 120 V ± 10%
- DC: 120 to 300 V DC ± 10%
Fuse Requirements: Use 2 A fuses. L1 and L2 are non-polarized. If using an AC power supply with neutral, connect neutral to the meter's L2 terminal. Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the control power. If using a control power transformer, fuse both primary and secondary sides.
Voltage Inputs
Supports various voltage configurations including 1-phase (1PH2W LN, 1PH2W LL, 1PH3W LL with N) and 3-phase (DELTA, WYE) systems.
Maximum voltage at terminals:
| Configuration | UL | IEC |
|---|---|---|
| L-N / L-L (Wye) | ≤ 347 VLN / 600 VLL | ≤ 400 VLN / 690 VLL |
| L-L (Delta) | ≤ 600 VLL | ≤ 600 VLL |
| L-L (Wye with unearthed neutral) | ≤ 600 VLL | ≤ 600 VLL |
| L-N (Single Phase) | ≤ 600 VLN | ≤ 600 VLN |
Current Inputs
Diagrams show 2CT, 3CT, and 4CT configurations for 3-phase current measurement.
Nominal current: 5 A (Class 0.2S) or 1 A (Class 0.5S).
Measured current: 50 mA to 10 A.
Impedance: 0.3 mΩ.
Communication Interfaces
Includes RS-485 and Ethernet (2x ports) for communication.
RS-485: Terminals are labeled D1+, D1-, C. Requires 4-30 V AC or 4-60 V DC power.
Ethernet: CAT5/5e UTP cable recommended.
Terminal Specifications
Table details wire gauge, torque, and maximum wire diameter for various terminals.
| Terminal(s) | Wire Gauge (AWG) | Torque | Max Wire Diameter |
|---|---|---|---|
| I1+, I1-, I2+, I2-, I3+, I3-, I4+, I4- | 16 - 10 AWG | 0.9 - 1.0 Nm (8.0 - 9.0 in·lb) | 8 mm (0.32") MAX |
| V1, V2, V3, Vn | 18 - 12 AWG | 8 mm (0.31 in) ± 1mm (0.040 in) | N/A |
| L1, L2 | N/A | N/A | N/A |
| +, -, ⊚, C (Control Power) | 26 - 18 AWG | 0.5 - 0.6 Nm (4.4 - 5.3 in·lb) | 3 mm (1/8 in) |
| S1+, S1-, S2+, S2-, S3+, S3- (Digital Inputs) | 24 - 18 AWG | 7 mm (0.28 in) ± 1mm (0.040 in) | N/A |
| D1+, D1- (K, Y) (RS-485) | N/A | N/A | N/A |
Description and Operation
The Siemens 9410DC is a power and energy meter designed for industrial and commercial applications. It provides detailed measurements of electrical parameters.
Component Identification
Diagram shows the meter's front and rear views with labeled components A-U.
- A Voltage inputs
- B Control power
- C Digital inputs
- D Revenue lock LED: Indicates revenue lock status (Off: Not locked, On: Locked).
- E Status LED (2): Indicates device status (On green: Normal operation, Off: Unpowered).
- F Revenue lock switch
- G Digital output
- H Sealing gasket
- I Infrared energy pulsing LED
- J Energy pulsing LED
- K RS-485 interface
- L Current inputs
- M Ethernet (2x ports)
- N Date/time display
- O Revenue lock icon
- P Alarm icon
- Q Display: Shows real-time data (e.g., 1.439 kW, 0.661 kVAR, 1.584 kVA).
- R Navigation icons
- S Navigation buttons
- T Home button
- U Alarm LED: Indicates alarm status (Off: No active alarms, On: Acknowledged active alarm, Flashing: Unacknowledged active alarm).
Meter Operation LEDs
- Revenue Lock LED (D): Off = Not revenue locked; On = Revenue locked; Flashing = Power cycle required.
- Status LED (E): Off = Unpowered; On green = Normal operation.
- Alarm LED (U): Off = No active alarms; On = Acknowledged active alarm; Flashing = Unacknowledged active alarm.
Setup and Verification
Basic Setup
Default password is '0'.
To change regional settings (language):
- Press Home to access the main menu.
- Navigate to Setup Menu > Language Setup.
- Use the Edit buttons to change the displayed language.
To perform basic setup:
- Navigate to Setup Menu > Meter Setup.
- Edit meter parameters to match your power system and electrical wiring.
To perform communications setup:
- Navigate to Setup Menu > Communications Setup.
- Select IP Address Setup and edit IP parameters as assigned by your network administrator.
- Select COM1 Setup and edit settings to match your RS-485 network.
Verification
Use the front panel buttons to navigate to the real-time data screens and verify that the meter readings are correct.
Specifications
Detailed technical specifications for the Siemens 9410DC meter:
Control Power
- AC at 50/60 Hz ± 10%: 90 to 415 V ± 10%
- AC at 400 Hz: 90 to 120 V ± 10%
- DC: 120 to 300 V DC ± 10%
- Burden values (meter only): AC (45-65 Hz) max. 7.2 W / 18 VA; AC (400 Hz) max. 4.5 W / 8 VA; DC max. 6 W.
- Burden values (fully optioned meter): AC (45-65 Hz) max. 18 W / 36 VA; AC (400 Hz) max. 18 W / 28 VA; DC max. 17 W.
- Overvoltage category: III
Voltage Inputs
- Measured voltage: 57 to 400 V L-N / 100 to 690 V L-L (Wye) or 100 to 600 V L-L (Delta or Wye with unearthed neutral)
- Frequency: 50/60 Hz ± 15%, 400 Hz ± 10%
- Overload: 600 V L-N or 1035 V L-L
- Impedance: 5 MΩ
- Measurement category: III
- Electromagnetic environmental class: E2
- Mechanical environmental class: M1
Current Inputs
- Nominal: 5 A (Class 0.2S) or 1 A (Class 0.5S)
- Measured current: 50 mA to 10 A
- Starting current: 5 mA
- Withstand: 20 A continuous, 50 A @ 10 sec/hr, 500 A @ 1 sec/hr
- Impedance: 0.3 mΩ
- Burden: 0.024 VA at 10 A
Digital Output
- Type: Form A
- Reference voltage: 40 V
- Maximum voltage: 30 V AC / 60 V DC
- Maximum current: 75 mA
Status Inputs
- Type: Externally excited
- Reference voltage: 40 V
- Maximum voltage: 30 V AC / 60 V DC
- ON state: 4 to 30 V AC / 4 to 60 V DC
- OFF state: 0 to 1.7 V AC / 0 to 2.5 V DC
Ethernet
- Cable type: CAT5/5e UTP (use unshielded cable only)
Environment
- Operating temperature: -25 to 70 °C (-13 to 158 °F)
- Relative humidity: 5% to 95% RH non-condensing
- Maximum dewpoint: 37 °C (99 °F)
- Storage temperature: -40 to 85 °C (-40 to 185 °F)
- Pollution degree: 2
- Altitude: < 3000 m (9843 ft) above sea level
- Enclosure rating: IP30 meter body (except connectors), IP54 front display
- For UL Type 12 applications, install meter on a flat surface of a Type 12 enclosure.
- Not suitable for wet locations.
- For indoor use only.