Mitsubishi PUZ-A24NHA7 PCA-A24KA8 Submittal

Mitsubishi PUZ-A24NHA7 PCA-A24KA8 - 24k BTU Cooling Heating - P-Series Ceiling Suspended Air Conditioning System - 21.0 SEER2

PDF preview unavailable. Download the PDF instead.

44298c4a4e079e6e6a9b1fdcae818323
Job Name: System Reference:

PCA-A24KA8 & PUZ-A24NHA7
24,000 BTU/H CEILING-SUSPENDED INDOOR UNIT 24,000 BTU/H HEAT PUMP UNIVERSAL OUTDOOR

Indoor Unit Outdoor Unit

Date:

PCA-A24KA8 PUZ-A24NHA7

INDOOR UNIT FEATURES · Airflow settings for high and low ceiling applications · Knock-out for outside-air intake · Optional i-see SensorTM for air distribution and energy saving · Auto fan speed mode · Filter status indicator · Easy-to-clean, washable filter · Suspends from ceiling for quick and easy installation · Ideal for larger retail stores, classrooms, and restaurants · Multiple control options available:  kumo cloud® smart device app for remote access  Third-party interface options  Wired or wireless controllers
OUTDOOR UNIT FEATURES · Variable speed INVERTER-driven compressor · Pre-charged with refrigerant volume for piping length up to 70 ft · Low ambient cooling down to 0°F providing 100% capacity · 24-hour continuous operation (cooling mode) · High pressure protection · Fast restart · Superior energy and operational efficiency · Seacoast protection*  External Outer Panel: Phosphate coating + Acrylic-Enamel coating  Fan Motor Support: Epoxy resin coating (at edge face)  Separator Assembly Valve Bed: Epoxy resin coating (at edge face)  Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.  Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing *Seacoast protection standard from 2022 production

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PCA-A24KA8 & PUZ-A24NHA7

test
Cooling at 95°F1 Heating at 47°F2 Heating at 17°F3 Heating at 5°F4 Efficiency
Electrical
Indoor Unit
Indoor Unit Operating Temperature Range

Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Moisture Removal Sensible Heat Factor Power Factor [208V / 230V] Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Power Factor [208V / 230V] Maximum Capacity Rated Capacity Maximum Power Input Rated Power Input Maximum Capacity Maximum Power Input SEER2 EER21 HSPF2 [IV] COP at 47°F2 COP at 17°F at Maximum Capacity3 COP at 5°F at Maximum Capacity4 ENERGY STAR® Certified Voltage, Phase, Frequency Guaranteed Voltage Range Voltage: Indoor - Outdoor, S1-S2 Voltage: Indoor - Outdoor, S2-S3 Short-circuit Current Rating [SCCR] Recommended Fuse/Breaker Size (Outdoor) Recommended Wire Size [Indoor - Outdoor] Power Supply MCA Fan Motor Full Load Amperage Fan Motor Output Fan Motor Type Airflow Rate at Cooling, Dry Airflow Rate at Cooling, Wet Airflow Rate at Heating, Dry Sound Pressure Level [Cooling] Sound Pressure Level [Heating] Drain Pipe Size Coating on Heat Exchanger External Finish Color Unit Dimensions Package Dimensions Unit Weight Package Weight Cooling Intake Air Temp [Maximum / Minimum]* Heating Intake Air Temp [Maximum / Minimum]

BTU/H BTU/H BTU/H
W W Pints/h
% BTU/H BTU/H BTU/H
W W % BTU/H BTU/H W W BTU/H W
V AC V AC V DC
kA A AWG
A A W
CFM CFM CFM dB[A] dB[A] In. [mm]
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F °F

24,000 24,000 10,000 1,960 1,960
5.8 0.73 94.7 / 94.7 28,000 26,000 8,800 2,230 1,800 94.3 / 94.3 17,900 15,400 1,770 1,700 14,900 1,900 21.0 12.2 9.2 4.23 2.97 2.3 Yes 208/230, 1, 60 198 - 253 208/230 24
5 25 14 Indoor unit is powered by the outdoor unit 1.0 0.54 95 DC Motor 530­565­600­670 495­530­565­635 530­565­600­670 33­35­37­40 33­35­37­40 1-1/32 [26] -- White Munsell 6.4Y 8.9/0.4 50-3/8 x 26-3/4 x 9-1/16 [1,280 x 680 x 230] 53-7/64 x 30 x 12-41/64 [1,349 x 760 x 321] 71 [32] 80 [36] 90 DB, 73 WB / 66 DB, 59 WB 82 DB / 50 DB

NOTES:

AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

(Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB

3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Conditions

4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. » Wind baffles required to operate below 23°F DB in cooling mode. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PCA-A24KA8 & PUZ-A24NHA7

test
Outdoor Unit
Outdoor Unit Operating Temperature Range Refrigerant Piping

MCA MOCP Fan Motor Full Load Amperage Fan Motor Output Airflow Rate [Cooling / Heating] Refrigerant Control Defrost Method Coating on Heat Exchanger Sound Pressure Level, Cooling1 Sound Pressure Level, Heating2 Compressor Type Compressor Model Compressor Rated Load Amps Compressor Locked Rotor Amps Compressor Oil [Type // Charge] External Finish Color Base Pan Heater Unit Dimensions Package Dimensions Unit Weight Package Weight Cooling Air Temp [Maximum / Minimum]* Heating Air Temp [Maximum / Minimum] Heating Thermal Lock-out / Re-start Temperatures** Type Pre-Charged Refrigerant Amount Maximum Pre-Charged Piping Length Additional Refrigerant Charge Per Additional Piping Length Gas Pipe Size O.D. [Flared] Liquid Pipe Size O.D. [Flared] Maximum Piping Length Maximum Height Difference Maximum Number of Bends

A A A W CFM
dB(A) dB(A)
A A oz.
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F °F °F
Lbs, oz Ft. [m] oz./Ft. [g/m] In.[mm] In.[mm] Ft. [m] Ft. [m]

19.0 26 0.4 86 1940 / 1940 LEV Reverse Cycle Blue Fin Coating*** 47 48 INVERTER-driven twin rotary SNB172FWHM1 7 11.0 FV50S // 23 Ivory Munsell 3Y 7.8/1.1 N/A 37-13/32 x 13 (+1-3/16) x 37-1/8 [950 x 330 (+30) x 943] 40-15/16 x 17-11/16 x 40-11/16 [1040 x 450 x 1033] 153 [69] 179 [81] 115 DB / 0 DB 70 DB, 59 WB / -4 DB, -4 WB -13 / -4 R410A 7.0, 11.0 70.0 [20.0] 0.7 [50] 5/8 [15.88] 3/8 [9.52] 165 [50] 100 [30] 15

NOTES:

AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

(Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB

3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Conditions

4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. » Wind baffles required to operate below 23°F DB in cooling mode. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT ACCESSORIES: PCA-A24KA8

Control Interface
Remote Sensor Wired Remote Controller
Wireless Remote Controller
Condensate Disconnect Switch Filter Lineset

CN24 Relay Kit IT Extender kumo station® for kumo cloud® Procon BACnet® and Modbus® Interface Remote Operation Adapter Thermostat Interface USNAP Adapter Flush Mount Remote Temperature Sensor Remote Temperature Sensor Wireless temperature and humidity sensor for kumo cloud® Deluxe Wired MA Remote Controller Simple Ductless Wired Remote Controller Simple MA Remote Controller Touch MA Controller kumo touchTM RedLINKTM Wireless Controller Lockdown bracket for remote controller Wireless MA Receiver Wireless MA Remote Controller Wireless Receiver Kit Wireless Receiver Kit with i-See sensorTM Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H (30A/600V/UL) [fits 2" X 4" utility box] - Black 65% Medium Efficiency Filter (MERV 8) 10' x 3/8" x 10' x 5/8" Lineset (Twin-Tube Insulation) 100' x 3/8" x 100' x 5/8" Lineset (Twin-Tube Insulation) 15' x 3/8" x 15' x 5/8" Lineset (Twin-Tube Insulation) 30' x 3/8" x 30' x 5/8" Lineset (Twin-Tube Insulation) 50' x 3/8" x 50' x 5/8" Lineset (Twin-Tube Insulation) 65' x 3/8" x 65' x 5/8" Lineset (Twin-Tube Insulation)

NOTES: PAC-SF40RM-E (Unable to use with wireless remote controller)

  CN24RELAY-KIT-CM3   PAC-WHS01IE-E   PAC-WHS01HC-E   PAC-UKPRC001-CN-1   PAC-SF40RM-E   PAC-US445CN-1   PAC-WHS01UP-E   PAC-USSEN002-FM-1   PAC-SE41TS-E   PAC-USWHS003-TH-1   PAR-40MAAU   PAC-SDW01RC-1   PAC-YT53CRAU-J   PAR-CT01MAU-SB   MHK2   RCMKP1CB   PAR-FA32MA-W   PAR-FL32MA-E   PAR-SL93B-E   PAR-SA92MW-E   X87-721   X87-835   COMBI   TAZ-MS303   PAC-SH89KF-E   MPLS385812T-10   MPLS385812T-100   MPLS385812T-15   MPLS385812T-30   MPLS385812T-50   MPLS385812T-65

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Air Outlet Guide Centralized Drain Pan Control/Service Tool Hail Guards M-NET Converter
Mini-Split Wire Mounting Pad
Stand
Wind Baffle

OUTDOOR UNIT ACCESSORIES: PUZ-A24NHA7
Air Outlet Guide (1 Piece) Centralized Drain Pan Drain Pan Control/Service Tool M- & P-Series Maintenance Tool Cable Set USB/UART Conversion Cable (Required for all laptop connection) Hail Guard M-NET Converter M-NET Converter 14 Gauge, 4 wire MiniSplit Cable--250 ft. roll 14 Gauge, 4 wire MiniSplit Cable--50 ft. roll 16 Gauge, 4 wire MiniSplit Cable--250 ft. roll 16 Gauge, 4 wire MiniSplit Cable--50 ft. roll Condensing Unit Mounting Pad: 24" x 42" x 3" 18" Single Fan Stand 24" Single Fan Stand Condenser Wall Bracket Condenser Wall Bracket - Stainless Steel Finish Outdoor Unit Stand -- 12" High Front Wind Baffle Rear Wind Baffle Side Advanced Wind Baffle

  PAC-SG59SG-E   PAC-SG63DP-E   PAC-SG64DP-E   PAC-SK52ST   M21EC0397   M21EC1397   HG-A6   PAC-SJ85MA-E   PAC-SJ95MA-E   S144-250   S144-50   S164-250   S164-50   ULTRILITE2   QSMS1801M   QSMS2401M   QSWB2000M-1   QSWBSS   QSMS1201M   WB-PA5   WB-RE5   WB-SD5

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

1-13/16(46)

3(76)

[FRONT VIEW]
3
Ceiling

INDOOR UNIT DIMENSIONS: PCA-A24KA8

1 4

1/16(1)

1/16(2)

2-7/16(62)
6

1-7/16(37)

4-3/4(121)

2 7

1/16(2)

46-3/16(1173)

1/16(2)

2

When drain socket 9-3/16(233) is installed

9-11/16(246) Drainage

1 2 3 4
6 7

and i-see sensor
i-see sensor

9/16 14

9-3/16(233) 9-11/16(246)

When drain socket is installed
Drainage

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT DIMENSIONS: PUZ-A24NHA7

FREE
Min. 500 <19-11/16>
Min. 100 <3-15/16> Max. 30 <1-3/16>

1 FREE SPACE (Around the unit)
The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc.

2 SERVICE SPACE
Dimensions of space needed for service access are shown in the below diagram.

Min. 10mm <3/8> Min. 500mm <19-11/16>

Min. 10mm <3/8>
Min.100mm <3-15/16>

Min. 10 <13>
Service space Min. 500 <19-11/16>

Example of Notes

Handle for moving

1 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F) 2 ... Refrigerant LIQUID pipe connection (FLARE) ø 9.52(3/8F)
*1... Indication of STOP VALVE connection location.

Air Intake

3 FOUNDATION BOLTS

4 PIPING-WIRING DIRECTIONS

Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.)

Piping and wiring connections can be made from 4 directions: FRONT,Right,Rear and Below.

<Foundation bolt height>

175 <6-7/8>
Side Air Intake

Rear Air Intake
600<23-5/8> Installation Feet

2-U Shaped notched holes (Foundfation Bolt M10<W3/8>) 175<6-7/8>

19 <3/4> 370<14-9/16> 417 <1-1/32>

330 <13>

FOUNDATION
Rear Air Intake Handle for moving

28<1-3/32>

25 <31/32>

Air Discharge

70 <2-3/4> 57<2-1/4>

61<2-13/32> 40<19/32> 0 53<2-3/32>
41 <1-5/8>

2-12×36 oval holes (Foundation Bolt M10<W3/8>)

Handle Side Air Intake for moving

950 <37-13/32> 322<12-11/16> Earth terminal

LTeerftm..in. aPloCwoenrnseucptpiolynswiring Reight ... Indoor/Outdoor wiring
Service panel Handle for moving

1 2

*1 431<16-31/32> *1 447<17-5/8>
669<26-11/32>

943 <37-1/8> 473 <18-5/8> 23 <29/32>

Piping knockout Hole Details

Power supply wiring hole (2-ø27knockout) Front trunking hole 40<1-9/16> (knockout)

45 <1-25/32>

Right piping hole (knockout)
75 <2-31/32>

Power supply wiring hole (2- ø27knockout)

Right trunking hole (knockout)

40<1-9/16>

45<1-25/32>

73 <2-7/18> 63 <2-1/2>
55 <2-3/16>

63 <2-1/2>

63<2-1/2> 55 <2-3/16>

73 <2-7/8>

Front piping hole (knockout)

<3ø-952/8>
92<3-5/8> 65 <2-9/16>

19<3/4>

ø 92 <3-5/8>
92 <3-5/8> 55 <2-3/16>

Power supply wiring hole (2- ø27<1-1/16>knockout) 40<1-9/16> Rear trunking hole (knockout)
ø92 <3-5/8>
Rear piping hole (knockout)
92 <3-5/18> 65 <2-9/16>

Set the attachment to the When installing the conduit, inner side of each panel.
1/2 Conduit attachment 2-ø22.2<7/8>
40<1-9/16>
74<2-19/32>

31<1-7/32>

71 <2-13/16>

71<2-13/16>

Front piping cover Rear piping cover

Bottom piping hole (knockout)

219 <8-5/8>

81<3-3/16>

30 <1-3/16>

220

145

145

145

<8-21/32> <5-23/32><5-23/32><5-23/32>

Drain hole (5- ø33<1-5/16>)

27 23 <29/32> <1-1/16> 92 <3-5/8>

23 <29/32> 27<1-1/16>

73 <2-7/18>

27<1-1/16>

23 <29/32>

FORM# PCA-A24KA8 & PUZ-A24NHA7 - 202402 Specifications are subject to change without notice.

1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com
© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

