DocumentDocumentDELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION Phone: 833-2-PDQTEC | www.pdqlocks.com OVERVIEW Armed: When armed, this device activates an internal blocking mechanism to prevent exiting the door from the inside until the proper release sequence has been completed. Release Delay: When an attempt is made to open the door from the inside, the device sounds an alarm and initiates a countdown. Free Exit: Upon completion of the Release Delay countdown, the device will release the push bar and allow free exit from the door until it is reset. An alarm will continue to sound until the device is reset. Fire Contacts: The power supply for this device must be connected to a fire alarm to cut power to the device, allowing immediate egress in the event of an emergency. *IMPORTANT* Local regulations and building codes may dictate specific requirements for the installation and usage of these devices. 1 2 3 4 5 6 Box Contents: 1. Exit device equipped with Delayed Egress 2. Installation Instruction, Delayed Egress Instruction, Door Template 3. Strike 4. Strike Screwpack 5. Device Screwpack 6. End Cap 7. 8 pin wiring harness with leads 8. 2 pin wiring harness with leads 9. Warning signage for door 7 8 9 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION Phone: 833-2-PDQTEC | www.pdqlocks.com DEFINITIONS Fire Alarm Power Supply Usage: Required by Code Power supply must be wired to cut power to the DE device on activation of fire alarm. The example wiring diagram in this manual shows how device should be wired if using our PS220 power supply. A UL 294 rated power supply providing a minimum of 1 Amp at 24VDC (+/-10%) with fire alarm link is required. Inhibit Contact Usage: Optional Type: Normally Open Contact closure allows free egress/ingress without sounding the alarm. After Inhibit completes, the system resets automatically when contact position conditions are satisfied (door position switch and optional latch monitor switch). Inhibit is usually wired to an access control system to allow entry from the outside or exit from the inside without alarming the device. When not used for Inhibit, this input can be used to reset a device in alarm. Door Position Switch (DPS) Usage: Preferred Type: Normally Closed The Door Position Switch input senses door opening. If the door has been opened without using the Inhibit feature, the internal alarm will sound. The DPS contact must be closed to arm the device including after inhibit has been used. If not used, bypass DPS by closing circuit. Relay Contacts Usage: Optional Type: SPDT Opens or closes contact upon system arming. Can be used to signal security system when device is armed. Relay contacts will change state when device alarms and during Inhibit. Nuisance Delay Configurable: Immediate, 1 second The Nuisance Delay starts from the first moment the push bar is pressed. If set to Immediate, the device will immediately begin the Release Delay. If set to 1 second, the device will sound a beep when pressed. If the device is released before 1 second it will return to the previous, armed state. If held for longer than 1 second the device will proceed to the Release Delay. This is useful in public areas where the device may be accidentally activated. Release Delay Configurable: 15 seconds, 30 seconds When the Release Delay is initiated, the push bar will remain locked and a warning beep will sound for the configured number of seconds (less any time already occupied by the Nuisance Delay). Once started, the Release Delay sequence cannot be stopped and the device will allow egress after the configured time has passed. Rearm Delay Configurable: Immediate, 1 second, 5 seconds, 15 seconds The time the device waits to arm following arming with the Key Switch or Inhibit Input. The device will arm when door closes (and DPS is satisfied) and the rearm delay has completed. Rearm delay can also be set to 15 seconds to allow door to close after Inhibit when DPS is not used. 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION Phone: 833-2-PDQTEC | www.pdqlocks.com INTERFACE Key Switch · The Key Switch Arms or Disarms the device. · Turning the Key Switch counter-clockwise arms the device (following the Rearm Delay) · Turning the Key Switch clockwise Disarms the device immediately Status Indicator LED · Armed Solid Red LED · Disarmed / Alarmed Red LED is off · Inhibit Active Red LED is off Internal Alarm · Nuisance Delay Active Short continuous beep · Release Delay Initiated Long continuous beep · Alarming Pulsing Beep Internal Alarm Status Indicator LED Key Switch GANG INHIB REL PWR CONFIGURATION REX LBM STAT Factory Setting DS3 Rearm Delay Immediate 1 Second 5 Seconds 15 Seconds DS2 Release Delay 15 Second Delay 30 Second Delay DS1 - Nuisance Delay 1 Second Delay Immediate 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION WIRING EXAMPLE Phone: 833-2-PDQTEC | www.pdqlocks.com INHIB REL Cylinder Switch Board in Filler DE Main Board in Tail of Exit Device Power Wiring 2 Pin Connector Accessory Wiring 8 Pin Connector Red ( 24V + ) Black ( 24V - ) Brown ( Relay COM ) Blue ( Relay N/O ) Gray ( Relay N/C ) Green ( Input COM ) Orange ( DPS ) Yellow ( Inhibit ) White ( Future Use ) Violet ( Future Use ) Power Transfer 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION OUTPUT +- FIRE +- BATTERY +- Phone: 833-2-PDQTEC | www.pdqlocks.com To Fire Alarm 12 IN OUT IN OUT IN NO C + - NO C + - +- To 2 Pin Connector Power Transfer PS220 Power Supply OUTPU T +- FIRE +- BATTE RY +- 1 2 IN IN NO C + - IN IN NO C + - IN +- Fire Alarm External Device Door Position Switch (NC) Card Reader (NC) 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION TROUBLESHOOTING Phone: 833-2-PDQTEC | www.pdqlocks.com 5 6 2 4 REX LBM STAT PWR INHIB REL 3 *IMPORTANT* For device to arm, the following must be true: PWR, REX, LBM, STAT must be lit 1 INHIB must not be lit Description Status Troubleshooting 1 PWR On = Power Present Off = No Power Present Check power to key switch board Ensure key switch is in ON position Ensure fire alarm link is closed at the power supply Check all connections 2 INHIB On = Inhibit Engaged Ensure circuit is a Normally Open and is in the open state Off = Inhibit not Engaged Check all connections 3 LBM/DPS On = Loop Closed Off = Loop Open Ensure sure latch is extended Ensure Door Position Switch is Normally Closed and in closed state Check all connections 4 REX On = Loop Closed Off = Loop Open Make sure push pad is not depressed Check all connections 5 RELAY On = Armed State Off = Not Armed 6 STAT On = Armed Off = Not Armed Check all connections Power needs to be present, and all inputs need to be in their normal state (INHIB/REX/DPS/LBM) Check all connections 639434 Rev3 10/11/23 DELAYED EGRESS INSTRUCTION FOR ALL 6300/6400 EXITS WITH DE OPTION Phone: 833-2-PDQTEC | www.pdqlocks.com ELECTRICAL SPECIFICATIONS Power Supply Requirements: · UL 294 rated · 1 Amp at 24VDC +/-10% · Fire alarm link to cut power to DE device when active Description Color Red 2 Pin Harness Black Brow n Blue Gray 8 Pin Harness Green Orange Yellow White / Violet Function Specification Wire Type and Distance 24VDC + 24VDC - 1 AMP Inrush, 250 mA holding 18 gauge up to 300' Relay Common Relay NO Relay NC Security Relay Output Common 22 gauge up to 98.5' for signal contacts Security Relay Output Normally Open 18 gauge up to 98.5' for power contacts Relay rated 1Amp @ 24VDC Security Relay Output Normally Closed Input Common Input Common Ground Door Position Switch Input DPS Normally Closed 22 gauge up to 500' Inhibit Input Inhibit Normally Open Future Use CERTIFICATIONS · Listed for UL305 "Panic" · Listed for UL10C "Fire Exit Hardware" (for devices ordered with fire rating only) · Listed for UL294 "Controlled Egress Equipment and Systems or Delayed Egress Equipment and Systems", Access Control Endurance Level I · Certified to ANSI/BHMA A156.3 Grade 1 · Meets International Building Code (IBC) for Delayed Egress and Controlled Egress Systems. · Meets requirements of the BAA as a COTS product manufactured in the United States 639434 Rev3 10/11/23