Download Product Datasheet

HVAC USA - 042N0824

[PDF] Coils for solenoid valves - HVAC USA

Contact Danfoss for delivery of coils for other voltages. Symbol. Description. Enclosure grade. Code no. Cable plug for 6.3 ∞ 0.8 mm. IP 65. 042N0139 spade ...

Coils for solenoid valves

IP 00 with spade connector; IP 65 with cable plug. Ambient temperature. Max. 50°C. Duty rating. Continuous. • Compact. • Windings of class H insulated wire ...

PDF preview unavailable. Download the PDF instead.

Coils- Solenoid ?srsltid=AfmBOooAVBjGO8bRjwQk13hJdZSP8Xp2WoTDJOj8-I2kcroB0-DwdI1W
Data sheet

December 2001

Coils for solenoid valves
DKACV.PD.600.A3.02 520B1131

Coils for industrial valves

Contents

Coil type
A-series, 9 mm system
AB AC AK AL AM AR (EEx mIIT4)
B-series, 13.5 mm system
BA BD BB BE BG BN (hum-free) BO (EEx mIIT4) BP (EEx mIIT4)

Enclosure
IP00, IP65 IP00, IP65 IP00 IP00 IP00 IP65
IP00, IP20, IP65 IP00, IP20, IP65 IP00, IP20, IP65 IP67 IP67 IP67 IP67 IP67

Power consumption

ac

dc

4.5 W 5 W 7 W 10 W 3 W 4 W
7.5 W 9.5 W 6 W 4.8/7 W

9 W 15W 10 W 10 W 12 W 20 W 10 W

15W
18 W 18 W 20 W
10 W 16 W

Page
3 4 5 6 7 8
9 9 10 11 12 13 14 15

Compatibility
X = typical choice · = optional choice for
specific applications

Solenoid valve type
2/2-way Compact EV210A EV220A EV220A with filter

2/2-way High Performance EV210B EV212B EV220B 6-12 EV220B 15-50 EV220B 65-100 EV222B EVI-U / EVSI-U EV250B
3/2-way Compact EV310A
3/2-way High Performance EV310B
Valves for distinct purposes EV215B / EV225B / EV245B EVSIS (UL approved) EV260B
1) NC versions only 2) NO versions only

Coil type

AB AC AK AL AM AR

X1)

X1)

X1)

X

X

·

X

X

X

X

·

XX

BA BD BB BE BG BN BO BP

X

XX

X

X

·

·

·

X

XX

X

·

·

·

·

X

XX

X

X

·

·

·

X

XX

X

X

·

·

·

XX

X

X

·

·

·

X

X

·

·

·

·

See datasheet DKACV.PD.200.G

X

X

X

·

·

·

AB AC AK AL AM AR

X2)

X

X2)

X

X

BA BD BB BE BG BN BO BP

X

X

·

·

·

·

·

·

See specific datasheet See specific datasheet See specific datasheet

2

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

Features

Coils type AB
4.5 W ac 5 W dc

IP 00 IP 65
· Compact · Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +50°C · All usual ac and dc voltages · IP 00 version with 6.3  0.8 mm spade
connectors
· IP 65 version with mounted cable plug

Technical data Ordering

Design Voltage tolerance Power consumption. cut-in Power consumption. holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ± 10% ac: 9.5 VA ac: 6.3 VA. 4.5 W / dc: 5 W Class H according to IEC 85 Spade connectors, 6.3  0.8 mm IP 00 with spade connector; IP 65 with cable plug Max. +50°C Continuous

4.5 W ac 5 W dc

Coil type AB024C AB110C AB230C AB240C AB012D AB024D

Supply voltage 24 V, 50/60 Hz 110 V, 50/60 Hz 220-230 V, 50/60 Hz 240 V, 50/60 Hz
12 V 24 V

Contact Danfoss for delivery of coils for other voltages

Symbol

Description
Cable plug for 6.3  0.8 mm spade connectors

Enclosure grade IP 65

Code no. IP 00
042N0802 042N0804 042N0800 042N0801 042N0806 042N0803
Code no.
042N0139

Dimensions and weight

Weight: 0.05 kg

Without cable plug With cable plug

L 40 mm 56 mm

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

3

IP 00 IP 65
Features

Coils type AC
7.0 W ac 10 W dc

· Compact · Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +50°C · IP 00 version with 6.3  0.8 mm spade
connectors
· IP 65 version with mounted cable plug

Technical data Ordering

Design Voltage tolerance Power consumption. cut-in Power consumption. holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ± 10% ac: 15.7 VA ac: 10 VA. 7 W / dc: 10 W Class H according to IEC 85 Spade connectors, 6.3  0.8 mm IP 00 with spade connector; IP 65 with cable plug Max. +50°C Continuous

Coil

Supply

type

voltage

AC024C

24 V, 50/60 Hz

7 W ac

AC110C AC230C

110 V, 50/60 Hz 220 - 230 V, 50/60 Hz

AC240C

240 V, 50/60 Hz

10 W dc

AC012D AC024D

12 V 24 V

Contact Danfoss for delivery of coils for other voltages

Symbol

Description
Cable plug for 6.3  0.8 mm spade connectors

Enclosure grade IP 65

Code no. IP 00
042N0823 042N0825 042N0821 042N0822 042N0826 042N0824
Code no.
042N0139

Dimensions and weight

Weight: 0.05 kg

Without cable plug With cable plug

L 40 mm 56 mm

4

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 00 Features

Coils type AK 3.0 W dc

· Compact · Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +50°C · Power consumption: Only 3 W dc · IP 00 version with spade connector in
accordance with DIN 43650, form A
· IP 20 version with protective cap · IP 65 version with mounted cable plug

Technical data

Design Voltage tolerance Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ± 10% dc: 3 W Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP 00: Spade connector; IP 20: Protective cap; IP 65: Cable plug Max. +50°C Continuous

Ordering

3 W dc

Coil type
AK024D

Supply voltage
24 V

Contact Danfoss for delivery of coils for other voltages

Symbol

Description
Protective cap (pack of 100 pcs.)
Cable plug according to DIN 43650-A Pg 11

Enclosure grade IP 20 IP 65

Code no. IP 00
042N0844
Code no. 018Z0282
042N0156

Dimensions and weight

Weight: 0.10 kg

Without cable plug With protective cap With cable plug

L 48 mm 64 mm 72 mm

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

5

IP 00 Features

Coils type AL 4.0 W ac

· Compact · Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +50°C · Power consumption: Only 4 W ac · IP 00 version with spade connector in
accordance with DIN 43650, form A
· IP 20 version with protective cap · IP 65 version with mounted cable plug

Technical data Ordering

Design Voltage tolerance Power consumption cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ± 10% 10 VA ac: 4 W Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP 00: Spade connector; IP 20: Protective cap; IP 65: Cable plug Max. +50°C Continuous

4 W ac

Coil type
AL230C

Supply voltage
230 V ac, 50/60 Hz

Contact Danfoss for delivery of coils for other voltages

Symbol

Description
Protective cap (pack of 100 pcs.)
Cable plug according to DIN 43650-A Pg 11

Enclosure grade IP 20 IP 65

Code no. IP 00
042N0864
Code no. 018Z0282
042N0156

Dimensions and weight

Weight: 0.10 kg

Without cable plug With protective cap With cable plug

L 48 mm 64 mm 72 mm

6

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 00 Features

Coils type AM
7.5 W ac 9.5 W dc

· Compact · Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +50°C · All usual ac and dc voltages · IP 00 version with spade connector in
accordance with DIN 43650, form A
· IP 20 version with protective cap · IP 65 version with mounted cable plug

Technical data Ordering

Design Voltage tolerance Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ± 10% ac: 22.5 VA ac: 15 VA, 7.5 W / dc: 9.5 W Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP 00: Spade connector; IP 20: Protective cap; IP 65: Cable plug Max. +50°C Continuous

Coil

Supply

type

voltage

AM024C

24 V, 50/60 Hz

7.5 W ac

AM110C AM230C

110 V, 50/60 Hz 220-230 V, 50/60 Hz

AM240C

240 V, 50/60 Hz

9.5 W dc

AM012D AM024D

12 V 24 V

Contact Danfoss for delivery of coils for other voltages

Symbol

Description
Protective cap (pack of 100 pcs.)
Cable plug according to DIN 43650-A Pg 11

Enclosure grade IP 20 IP 65

Code no. IP 00
042N0842 042N0845 042N0840 042N0841 042N0848 042N0843
Code no.
018Z0282
042N0156

Dimensions and weight

Weight: 0.10 kg

Without cable plug With protective cap With cable plug

L 48 mm 64 mm 72 mm

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

7

IP 65 Features
Technical data Ordering Dimensions

Coils type AR; EEx m II T4
6 W ac 4.8 W dc, 7 W dc

· Compact · The coils are suitable for use in
installations where flammable liquids and
gases are produced, transported or tapped
· Approvals for use in Zone 1 according to
Directive 94/9/EC (ATEX 100A) EN50014
and EN50028
· Grade of enclosure IP 65 to IEC 529 · Supplied with 3, 3.8 or 5.5 m moulded-in
3-core cable

Voltage tolerance Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Media temperature Duty rating

± 10% ac: 6 W, dc: 4.8 W and 7 W Class H according to IEC 85 3, 3.8 or 5.5 m 3-core cable IP 65 Max. +55° C Max. +90° C Continuous

Conformity certification EX DEMKO 99ATEX 125689X

Coil Type

Supply Voltage

6 W ac 6 W ac 7 W dc 4.8 W dc

AR024C AR230C AR024D AR024D

24 V, 50/60 Hz 230 V, 50/60 Hz
24 V dc 24 V dc

Cable
5.5 m 5.5 m 5.5 m 5.5 m

Code no.
042N5525 042N5535 042N5505 042N5515

Moulded-in 3 m, 3-core cable Weight approx. 0.3 kg
Special requirements: The supply must be secured against a too high power consumption in case of a short circuit

8

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 00 Features

Coil type BA and BD
9 W/15 W ac 15 W dc

· Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +40°C and
+50C
· All usual ac and dc voltages · IP 00 version with spade connector in
accordance with DIN 43650, form A
· IP 20 version with protective cap · IP 65 version with mounted cable plug

Technical data Ordering
Dimensions and weight

Design Voltage tolerance
Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 220/380 V ac coils: +10%, ­15%. 230/400 V ac coils: +6%, ­10%. Other ac coils with NC valve: +10%, ­15% Other ac coils with NO valve and all dc coils: ±10% BA ac: 39 VA BD ac: 54 VA ac: 19 VA, 9 W / dc: 29 VA, 15 W Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP 00 with spade connec. IP 20 with protective cap; IP 65 with cable plug Max . +40°C for BA / Max. +50°C for BD Continuous

9 W ac
15 W ac 15 W dc

Coil Type BA024A BA048A BA115A BA230A BA240A BA380A BA024B BA115B BA220B BD024A BD110A BD230A BA012D BA024D

Supply voltage 24 V, 50 Hz 48 V, 50 Hz 115 V, 50 Hz 220-230 V, 50 Hz 240 V, 50 Hz 380-400 V, 50 Hz 24 V, 60 Hz 115 V, 60 Hz 220 V, 60 Hz 24 V, 50 Hz 110 V, 50 Hz 230 V, 50 Hz
12 V 24 V

Contact Danfoss for delivery of coils for other voltages

Symbol

Description

Enclosure grade

Protective cap (pack of 100 pcs.)

IP 20

Cable plug according to DIN 43650-A Pg 11

IP 65

Code no. IP 00
042N7508 042N7510 042N7512 042N7501 042N7502 042N7504 042N7520 042N7522 042N7523 042N7597 042N7599 042N7541 042N7550 042N7551
Code no.
018Z0282
042N0156

DKACV.PD.600.A3.02

Weight: 0.16 kg

Without cable plug With protective cap With cable plug

L 54 mm 71 mm 79 mm

Danfoss A/S 12-2001

9

IP 00, IP 20 IP 65
Features

Coils type BB
10 W ac 18 W dc

· Windings of class H insulated wire moulded
in the coil body
· Ambient temperature: Up to +80°C · All usual ac and dc voltages · IP 00 version with spade connector in
accordance with DIN 43650, form A.
· IP 20 version with protective cap · IP 65 version with mounted cable plug · Most common voltages as clip-on coil

Technical data

Design Voltage tolerance
Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 220/380 V ac coils: +10%, ­15%. 230/400 V ac coils: +6%, ­10%. Other ac coils with NC valve: +10%, ­15% Other ac coils with NO valve and all dc coils: ±10% ac: 44 VA ac: 21 VA, 10 W / dc: 18 W Class H according to IEC 85 Spade connector in accordance with DIN 43650 form A IP 00 with spade connec. IP 20 with protective cap; IP 65 with cable plug Max . +50/+80°C - see table below for details Continuous

Ordering

10 W ac 18 W dc

Coil Type BB024A BB115A BB230A BB240A BB380A BB024B BB110C BB230C BB012D BB024D

Ambient Temperature max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +50°C max. +50°C max. +50°C max. +50°C

Supply voltage 24 V, 50 Hz 115 V, 50 Hz 220-230 V, 50 Hz 240 V, 50 Hz 380-400 V, 50 Hz 24 V, 60 Hz 110 V, 50/60 Hz 220-230 V, 50/60 Hz
12 V 24 V

Contact Danfoss for delivery of coils for other voltages

Code no. IP 00
042N7408 042N7412 042N7401 042N7402 042N7404 042N7415 042N7430 042N7432 042N7456 042N7457

Clip-on
018F7358 018F7361 018F7351 018F7352
018F7360 018F7363

Symbol

Description
Protective cap (pack of 100 pcs.)
Cable plug according to DIN 43650-A Pg 11

Enclosure grade IP 20 IP 65

Code no. 018Z0282 042N0156

Dimensions and weight

Weight: 0.24 kg

Without cable plug With protective cap With cable plug

L 62 mm 77 mm 85 mm

10

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 67 Features

Coils type BE
10 W ac 18 W dc

· Clip-on version · Encapsulated coils with long operation life · Ambient temperature: Up to +80°C · Suitable for moist environments · All usual ac and dc voltages · IP 67 version with terminal box · IP 67 version 1 m 3-core flying lead · Can be fitted without tools · Can only be removed with tool

Technical data

Design Voltage tolerance
Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 220/380 V ac coils: +10%, ­15%. 230/400 V ac coils: +6%, ­10%. Other ac coils with NC valve: +10%, ­15% Other ac coils with NO valve and all dc coils: ±10% ac: 44 VA ac: 21 VA, 10 W / dc: 18 W Class H according to IEC 85 Terminal box; Pg 13.5 ­ or 1 m 3-core flying lead IP 67 Max . +50/+80°C, see table below for details Continuous

Ordering Dimensions and weight

10 W ac 18 W dc

Coil Type
BE024A BE048A BE115A BE240A BE240A BE380A BE024B BE115B BE220B BE110C BE230C BE012D BE024D

Ambient temperature
max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +80°C max. +50°C max. +50°C max. +50°C max. +50°C

Supply voltage
24 V, 50 Hz 48 V, 50 Hz 115 V, 50 Hz 220-230 V, 50 Hz 240 V, 50 Hz 380-400, 50 Hz 24 V, 60 Hz 115 V, 60 Hz 220 V, 60 Hz 110 V, 50/60 Hz 220-230 V, 50/60 Hz
12 V 24 V

Code no.

With terminal box With cable

018F6707

018F6257

018F6709

018F6259

018F6711

018F6261

018F6701

018F6251

018F6702

018F6252

018F6703

018F6253

018F6715

018F6265

018F6710

018F6260

018F6714

018F6264

018F6730

018F6280

018F6732

018F6282

018F6756

018F6757

Contact Danfoss for delivery of coils for other voltages

O-ring
Terminal box with LED indication

Application
Coil enclosures 48-220 V dc
24-250 V, 50/60 Hz

Code no. 018F0094 018Z0089

DKACV.PD.600.A3.02

Weight: 0.30 kg

With terminal box With 1 m cable

Danfoss A/S 12-2001

L 94 mm 65 mm
11

IP 67 Features

Coils type BG
12 W ac 20 W dc

· Clip-on version · Encapsulated coils with long operation life · Ambient temperature: Up to +80°C · All usual ac and dc voltages · Suitable for moist environments · IP 67 version with terminal box · Can be fitted without tools · Can only be removed with tool

Technical data Ordering

Design Voltage tolerance
Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 220/380 V ac coils: +10%, ­15%. 230/400 V ac coils: +6%, ­10%. Other ac coils with NC valve: +10%, ­15% Other ac coils with NO valve and all dc coils: ±10% ac: 44 VA ac: 21 VA, 10 W / dc: 18 W Class H according to IEC 85 Terminal box; Pg 13.5 IP 67 Max . +80°C Continuous

12 W ac 20 W dc

Coil Type BG024A BG110A BG230A BG240A BG380A BG024B BG110B BG220B BG012D BG024D

Contact Danfoss for delivery of coils for other voltages

Supply voltage 24 V, 50 Hz 110 V, 50 Hz 220-230 V, 50 Hz 240 V, 50 Hz 380-400 V, 50 Hz 24 V, 60 Hz 110 V, 60 Hz 220 V, 60 Hz 12 V 24 V

Description

Application

Code no.

O-ring

Coil enclosure

018F0094

Code no. IP 67
018F6807 018F6811 018F6801 018F6802 018F6803 018F6815 018F6813 018F6814 018F6856 018F6857

Dimensions and weight

Weight: 0.50 kg

With terminal box

L 112 mm

12

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 67 Features

Coils type BN
20 W ac Hum-free coil

· Clip-on version · Windings of class H insulated wire moulded
in the coil body
· For installations sensitive to noise, such as
heating systems
· Ambient temperature: Up to +50°C · Built-in rectifier · Suitable for moist environments · Available with 1 m 3-core flying lead · Coil enclosure: IP 67

Technical data

Design Voltage tolerance Power consumption, cut-in Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating

In accordance with VDE 0580 ±10% ac: 24 VA ac: 26 VA Class H according to IEC 85 1 m 3-core flying lead; Pg 13.5 IP 67 Max . +50°C Continuous

Ordering

20 W ac O-rings

Coil type
BN230C

Supply voltage 220-230 V, 50/60 Hz
Coil enclosure

Dimensions and weight

Code no. IP 67
018F7301
018F0094

Weight: 0.60 kg

With 1 m cable

L 112 mm

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

13

IP 67 Features

Coils type BO; Eex m II T4
10 W ac 10 W dc

· For explosion-risk environments, such as
where flammable liquids and gases are
produced, transported or tapped
· Approvals for use in Zone 1 according to
Directive 94/9/EC (ATEX 100A) EN50014
and EN50028
· Medium temperature: Up to +90°C · Ambient temperature: Up to +40°C · IP 67 version with 5 m 3-core flying lead · Seal kit as accessory for extremely wet and
aggressive environments (please contact
Danfoss)

Technical data Ordering

Voltage tolerance Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Duty rating Media temperature

±10% ac: 10 W / dc: 10 W Class H according to IEC 85 5 m 3-core flying lead IP 67 Max . +40°C Continuous Max . +90°C

10 W ac 10 W dc

Coil Type BO024C BO048C BO110C BO230C BO240C BO024D

Supply voltage 24 V, 50/60 Hz 48 V, 50/60 Hz 110 V, 50/60 Hz 220 - 230 V, 50/60 Hz 240 V, 50/60 Hz
24 V

Code no.

Standard

SEV-approval

018Z6595

018Z6585

018Z6594

018Z6584

018Z6593

018Z6583

018Z6592

018Z6582

018Z6591

018Z6581

018Z6596

018Z6586

Description Seal kit

Application Wet environment

Code no. 018Z0090

Dimensions and weight

Weight: 0.60 kg

14

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

IP 67 Features

Coils type BP; EEx m II T4 16 W dc

· The coils are suitable for use in
installations where flammable liquids and gases are produced, transported or tapped
· Approved for use in Zone 1 according to
Directive 94/9/EC (ATEX 100A) EN50014 and EN50028
· Grade of enclosure IP 67 · Supplied with 3 m moulded-in 3-core
cable

Technical data Ordering Dimensions

Voltage tolerance Power consumption, holding Insulation of coil windings Connection Enclosure, IEC 529 Ambient temperature Media temperature Duty rating

± 10% dc: 16 W Class H according to IEC 85 3 m 3-core cable IP 67 Max. +55° C Max. +90° C Continuous

Conformity certification EX DEMKO 99ATEX 125688X

16 W dc

Coil Type
BP024D

Supply Voltage
24 V dc

Connection 3 m

Code no. 018Z6633

Description Seal kit

Application Wet environment

Code no. 018Z0090

Moulded-in 3 m, 3-core cable Weight approx. 0.33 kg
Special requirements: The supply must be secured against a too high power consumption in case of a short circuit

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

15

Coils for solenoid valves

16

DKACV.PD.600.A3.02

Danfoss A/S 12-2001

Produced by G1 advertising agency

01.12.MR.JN.PS


Acrobat Distiller 4.05 for Windows