PDF preview unavailable. Download the PDF instead.

mv design guide
Merlin Gerin technical guide Medium Voltage
MV design guide
We do more with electricity.

Design Guide

This guide is a catalogue of technical know-how
intended for medium voltage equipment designers.

Goal
c Presenting and assisting in the selection of MV equipment in conformity with standards. c Providing design rules used to calculate the dimensions or ratings of an MV switchboard.
How?
c By proposing simple and clear calculation outlines to guide the designer step by step. c By showing actual calculation examples. c By providing information on units of measure and international standards. c By comparing international standards.
In summary
This guide helps you to carry out the calculations required to define and determine equipment dimensions and provides useful information enabling you to design your MV switchboard.

Schneider Electric

Merlin Gerin MV design guide

1

MV design guide

General contents

Presentation

5

Metal-enclosed factory-built equipment

5

Voltage

6

Current

8

Frequency

9

Switchgear functions

9

Different types of enclosures

10

Design rules

11

Short-circuit power

11

Short-circuit currents

12

Transformer

13

Synchronous generator

14

Asynchronous motor

14

Reminder

15

Three phase calculation example

17

Busbar calculation

21

Thermal withstand

24

Electrodynamic withstand

27

Intransic resonant frequency

29

Busbar calculation example

31

Dielectric withstand

38

Dielectric strength of the medium

38

Shape of parts

39

Distance between parts

39

Protection index

41

IP code

41

IK code

41

Switchgear definition

45

Medium voltage circuit breaker

45

Current transformer

54

Voltage transformer

61

Derating

64

Units of measure

67

Basic units

67

Common magnitudes and units

67

Correspondence between Imperial units

and international system units (SI)

69

Standards

71

Quoted standards

71

IEC-ANSI comparison

72

References

81

Schneider Electric documentation references

81

Index

83

Schneider Electric

Merlin Gerin MV design guide

3

Presentation

Metal-enclosed, factory-built equipment

To start with, here is some key information on MV switchboards! reference is made to the International Electrotechnical Commission
(IEC).

Introduction
In order to design a medium-voltage cubicle, you need to know the following basic magnitudes: c Voltage c Current c Frequency c Short-circuit power.
The voltage, the rated current and the rated frequency are often known or can easily be defined, but how can we calculate the short-circuit power or current at a given point in an installation?
Knowing the short-circuit power of the network allows us to choose the various parts of a switchboard which must withstand significant temperature rises and electrodynamic constraints. Knowing the voltage (kV) will allow us to define the dielectric withstand of the components. E.g.: circuit breakers, insulators, CT.

Disconnection, control and protection of electrical networks is achieved by using switchgear.
c Metal enclosed switchgear is sub-divided into three types: v metal-clad v compartmented v block.

Schneider Electric

Merlin Gerin MV design guide

5

Presentation

Metal-enclosed, factory-built equipment

Voltage
Operating voltage U (kV)
This is applied across the equipment terminals.
Rated voltage Ur (kV)
Previously known as nominal voltage, this is the maximum rms. (root mean square) value of the voltage that the equipment can withstand under normal operating conditions. The rated voltage is always greater than the operating voltage and, is associated with an insulation level.
Insulation level Ud (kV rms. 1 mn) and Up (kV peak)
This defines the dielectric withstand of equipment to switching operation overvoltages and lightning impulse.
c Ud: overvoltages of internal origin, accompany all changes in the circuit: opening or closing a circuit, breakdown or shorting across an insulator, etc... It is simulated in a laboratory by the rated power-frequency withstand voltage for one minute.
c Up: overvoltages of external origin or atmospheric origin occur when lightning falls on or near a line. The voltage wave that results is simulated in a laboratory and is called the rated lightning impulse withstand voltage.
N.B.: IEC 694, article 4 sets the various voltage values together with, in article 6, the dielectric testing conditions.
Example: c Operating voltage: 20 kV c Rated voltage: 24 kV c Power frequency withstand voltage 50 Hz 1 mn: 50 kV rms. c Impulse withstand voltage 1.2/50 µs: 125 kV peak.

6

Merlin Gerin MV design guide

Schneider Electric

Presentation
Schneider Electric

Metal-enclosed, factory-built equipment

Standards
Apart from special cases, MERLIN GERIN equipment is in conformity with list 2 of the series 1 table in IEC 60 071 and 60 298.

Rated voltage
kV rms.
7.2 12 17.5 24 36

Rated lightning

impulse

withstand voltage 1.2/50 µs 50 Hz

kV peak

list 1 40

list 2 60

60

75

75

95

95

125

145

170

Rated power-frequency withstand voltage

Normal operating voltage

1 minute kV rms. kV rms.

20

3.3 to 6.6

28

10 to 11

38

13.8 to 15

50

20 to 22

70

25.8 to 36

Insulation levels apply to metal-enclosed switchgear at altitudes of less than 1 000 metres, 20°C, 11 g/m3 humidity and a pressure of 1 013 mbar. Above this, derating should be considered. Each insulation level corresponds to a distance in air which guarantees equipment withstand without a test certificate.

Rated voltage kV rms.
7.2 12 17.5 24 36

Rated impulse withstand voltage 1.2/50 µs kV peak 60 75 95 125 170

Distance/earth in air cm
10 12 16 22 32

IEC standardised voltages

U Um

Rated power frequency withstand voltage 50 Hz 1 mm

Rated voltage
20 7.2 60 28 12 75

0.5 Um

t

0

1.2 µs

50 µs

Rated lightning

withstand voltage

38 50 70

17.5 24 36

95 125 170

Ud

Ur

Up

Merlin Gerin MV design guide

7

Presentation

Metal-enclosed, factory-built equipment

Current

Rated normal current: Ir (A)
This is the rms. value of current that equipment can withstand when closed, without exceeding the temperature rise allowed in standards. The table below gives the temperature rises authorised by the IEC according to the type of contacts.

Rated normal current:

Type of mechanism

Max. values

of material

contacts in air

Max. temperature of conductor (°C)

bare copper or copper alloy

75

silver or nickel plated

105

tin-plated

90

bolted connections or equivalent devices

bare copper, bare copper alloy

or aluminium alloy

90

silver or nickel plated

115

tin-plated

105

N.B.: rated currents usually used by Merlin Gerin are: 400, 630, 1 250, 2 500 and 3 150 A.

Max. temp. rise = t°. max. - 40 °C
35 65 50
50 75 65

Examples: c For a switchboard with a 630 kW motor feeder and a 1 250 kVA transformer feeder at 5.5 kV operating voltage. v calculating the operating current of the transformer feeder: Apparent power:
S = UIe

I =

S Ue

1 250 = 5,5 · 1,732

= 130 A

v calculating the operating current of the motor feeder:
cos = power factor = 0.9  = motor efficiency = 0.9

I= P

=

630

= 82 A

Uecos 5.5 · 1.732 · 0.9 · 0.9

Operating current: I (A)
This is calculated from the consumption of the devices connected to the circuit in question. It is the current that really passes through the equipment. If we do not have the information to calculate it, the customer has to provide us with its value. The operating current can be calculated when we know the power of the current consumers.

8

Merlin Gerin MV design guide

Schneider Electric

Presentation
Schneider Electric

Metal-enclosed, factory-built equipment

Minimal short-circuit current: Isc (kA rms.)
(see explanation in "Short-circuit currents" chapter.)

Rms value of maximal short-circuit current: Ith (kA rms. 1 s or 3 s)
(see explanation in "Short-circuit currents" chapter.)

Peak value of maximal short-circuit: Idyn (kA peak)
(value of the initial peak in the transient period) (see explanation in "Short-circuit currents" chapter.)

Frequency fr (Hz)
c Two frequencies are usually used throughout the world: v 50 Hz in Europe v 60 Hz in America. Several countries use both frequencies indiscriminately.

Switchgear functions

Designation and symbol
Disconnecter

function isolates

Current switching

operating

fault

Earthing disconnecter Switch

isolates
switches, does not isolate

(short-circuit closing capacity)


Disconnecter switch

switches

isolates



Fixed circuit breaker

switches





protects

does not isolate

Withdrawable circuit breaker

switches

protects





isolates if withdrawn

Fixed contactor

switches

does not isolate



Withdrawable contactor

switches

isolates if withdrawn



Fuse
protects does not isolate

 (once)

 = YES

Merlin Gerin MV design guide

9

Presentation

Metal-enclosed, factory-built equipment

Characteristics Cubicles

Different enclosure types

Metal-clad

Compartment

Block-type

External walls

metal and always earthed

Number of MV

compartments

 3

Internal partitions

metal and always earthed

Presence of bushings 

Shutters to prevent access

to live compartments



3 indifferent metal or not
possible


Ease of operations

when live





Arcing movement within difficult, but

the cubicle

always possible



 = YES

 2 indifferent metal or not


10

Merlin Gerin MV design guide

Schneider Electric

Design rules

Short-circuit power

Introduction

c The short-circuit power depends directly on the network configuration

Example 1:

and the impedance of its components:

25 kA at an operating voltage of 11 kV lines, cables, transformers, motors... through which the short-circuit

R Zcc L

A

current passes.

c It is the maximum power that the network can provide to an installation

E

Icc

U Zs

during a fault, expressed in MVA or in kA rms for a given operating voltage.

B
Ssc = e · U · Isc

U

:

operating voltage (kV)

Isc

:

short-circuit current (kA rms.) Ref: following pages

The short-circuit power can be assimilated to an apparent power.

c The customer generally imposes the value of short-circuit power on us because we rarely have the information required to calculate it. Determination of the short-circuit power requires analysis of the power flows feeding the short-circuit in the worst possible case.

Example 2:
c Feedback via LV Isc5 is only possible if the transformer (T4) is powered by another source.
c Three sources are flowing in the switchboard (T1-A-T2) v circuit breaker D1 (s/c at A) Isc1 + Isc2 + Isc3 + Isc4 + Isc5
v circuit breaker D2 (c/c at B) Isc1 + Isc2 + Isc3 + Isc4 + Isc5 v circuit breaker D3 (c/c at C) Isc1 + Isc2 + Isc3 + Isc4 + Isc5

Possible sources are:
c Network incomer via power transformers.
c Generator incomer.
c Power feedback due to rotary sets (motors, etc); or via MV/LV transformaters.

T1
Isc1
A D1

63 kV A
Isc2
B D2

T2
Isc3
C D3

10 kV

D6

D4

D5

D7

MT
T3
Isc5

M
Isc4

BT

T4

BT

MT

Schneider Electric

We have to calculate each of the Isc currents.

Merlin Gerin MV design guide

11

Design rules

Short-circuit currents

All electrical installations have to be protected against short-circuits, without exception, whenever there is an electrical discontinuity; which more generally corresponds to a change in conductor cross-section. The short-circuit current must be calculated at each stage in the installation for the various configurations that are possible within the network; this is in order to determine the characteristics that the equipment has to have withstand or break this fault current.

c In order to choose the right switchgear (circuit breakers or fuses) and set the protection functions, three short-circuit values must be known:

v minimal short-circuit current:

Isc = (kA rms)

(example: 25 kA rms)

This corresponds to a short-circuit at one end of the protected link (fault at the end of a feeder (see fig.1)) and not just behind the breaking mechanism. Its value allows us to choose the setting of thresholds for overcurrent protection devices and fuses; especially when the length of cables is high and/or when the source is relatively impedant (generator, UPS).

v rms value of maximal short-circuit current:

2rIsc I peak= Idyn

Ith

Isc

figure 1

R

X

MV cable

Current direct component

Ith = (kA rms. 1 s or 3 s) (example: 25 kA rms. 1 s)
This corresponds to a short-circuit in the immediate vicinity of the upstream terminals of the switching device (see fig.1). It is defined in kA for 1 or 3 second(s) and is used to define the thermal withstand of the equipment.
v peak value of the maximum short-circuit current: (value of the initial peak in the transient period)

- Idyn is equal to:

Idyn = (kA peak) (example: 2.5 · 25 kA = 63.75 kA peak IEC 60 056 or
2.7 · 25 kA = 67.5 kA peak ANSI )
2.5 · Isc at 50 Hz (IEC) or, 2.6 · Isc at 60 Hz (IEC) or, 2.7 · Isc (ANSI) times the short-circuit current calculated at a given point in the network.

It determines the breaking capacity and closing capacity of circuit breakers and switches, as well as the electrodynamic withstand of busbars and switchgear.

- The IEC uses the following values: 8 - 12.5 - 16 - 20 - 25 - 31.5 - 40 kA rms. These are generally used in the specifications.

2rIsc Time

N.B.: c A specification may give one value in kA rms and one value in MVA as below: Isc = 19 kA rms or 350 MVA at 10 kV
v if we calculate the equivalent current at 350 MVA we find:
Isc = 350 = 20.2 kA rms e · 10
The difference lies in the way in which we round up the value and in local habits. The value 19 kA rms is probably the most realistic.
v another explanation is possible: in medium and high voltage, IEC 909 applies a coefficient of 1.1 when calculating maximal Isc.
Isc = 1,1 · U = E e · Zcc Zcc
(Cf: example 1, p 12 Introduction). This coefficient of 1.1 takes account of a voltage drop of 10 % across the faulty installation (cables, etc).

12

Merlin Gerin MV design guide

Schneider Electric

Design rules

Short-circuit currents

Transformer
In order to determine the short-circuit current across the terminals of a transformer, we need to know the short-circuit voltage (Usc %).
c Usc % is defined in the following way:

The short-circuit current depends on the type of equipment installed on the network (transformers, generators, motors, lines, etc).

potentiometer

U : 0 to Usc

V primary

secondary

A
I : 0 to Ir

Example: c Transformer 20 MVA c Voltage 10 kV c Usc = 10 % c Upstream power: infinite

Ir =

Sr

= 20 000 = 1 150 A

e U no-load e·10

Isc = Ir = 1 150 = 11 500 A = 11.5 kA U s c 10÷ 100

1 the voltage transformer is not powered: U = 0 2 place the secondary in short-circuit 3 gradually increase voltage U at the primary up to the rated current Ir in the transformer secondary circuit.
The value U read across the primary is then equal to Usc

c The short-circuit current, expressed in kA, is given by the following

equation:

Isc

=

Ir Usc

Schneider Electric

Merlin Gerin MV design guide

13

Design rules

Short-circuit currents

Synchronous generators G (alternators and motors)
Calculating the short-circuit current across the terminals of a synchronous generator is very complicated because the internal impedance of the latter varies according to time.
c When the power gradually increases, the current reduces passing through three characteristic periods: v sub-transient (enabling determination of the closing capacity of circuit breakers and electrodynamic contraints), average duration, 10 ms v transient (sets the equipment's thermal contraints), average duration 250 ms v permanent (this is the value of the short-circuit current in steady state).
c The short-circuit current is calculated in the same way as for transformers but the different states must be taken account of.

Example: Calculation method for an alternator or a synchronous motor c Alternator 15 MVA c Voltage U = 10 kV c X'd = 20 %
Ir = Sr = 15 = 870 A e · U e · 10 000
Isc = Ir = 870 = 4 350 A = 4.35 kA Xcc trans. 20/100

fault appears

courant
Ir
healthy subtransient state state

transient state

Isc time
permanent state

short-circuit

c The short-circuit current is given by the following equation:

Isc =

Ir Xsc

Xsc

:

short-circuit reactance c/c

c The most common values for a synchronous generator are:

State Xsc

Sub-transient X''d 10 - 20 %

Transient X'd 15 - 25 %

Permanent Xd 200 - 350 %

Asynchronous motor
M c For asynchronous motors
v the short-circuit current across the terminals equals the start-up current
Isc z 5 at 8 Ir
v the contribution of the motors (current feedback) to the short-circuit current is equal to:
I z 3  Ir
The coefficient of 3, takes account of motors when stopped and the impedance to go right through to the fault.

14

Merlin Gerin MV design guide

Schneider Electric

Design rules
Schneider Electric

Short-circuit currents

Reminder concerning the calculation of three-phase short-circuit currents

c Three-phase short-circuit

Ssc = 1.1 · U · Isc · e= U2 Zsc

Isc = 1.1· U with e · Zsc

Zsc =

R2 + X2

c Upstream network

Z = U2 Ssc
c Overhead lines R=·L S
c Synchronous generators Z() = X() = U2 · Xsc (%) Sr 100

{R =

0.3 at 6 kV 0.2 at 20 kV

X

0.1 at 150 kV

X = 0.4 /km X = 0.3 /km  = 1.8.10-6  cm  = 2.8.10-6  cm  = 3.3.10-6  cm

HV MV/LV copper aluminium almélec

Xsc turbo exposed poles

sub-transient 10 to 20 % 15 to 25 %

transient 15 to 25 % 25 to 35 %

permanent 200 to 350 % 70 to 120 %

c Transformers
(order of magnitude: for real values, refer to data given by manufacturer)

E.g.:

20 kV/410 V; Sr = 630 kVA; Usc = 4 % 63 kV/11 V; Sr = 10 MVA; Usc = 9 %

Z () =

U2 Sr

·

Usc(%) 100

Sr (kVA) Usc (%)

100 to 3150 4 to 7.5 MV/LV

5000 to 5000 8 to 12 HV/MV

c Cables

X = 0.10 at 0.15 /km three-phased or single-phased

c Busbars

X = 0.15 /km

Merlin Gerin MV design guide

15

Design rules

Short-circuit currents

c Synchronous motors and compensators

Xsc high speed motors low speed motors compensators

Sub-transient 15 % 35 % 25 %

transient 25 % 50 % 40 %

permanent 80 % 100 % 160 %

c Asynchronous motors only sub-transient

Z() = Ir · U2 Id Sr

Isc z 5 to 8 Ir
Isc z 3 Ir,
contribution to Isc by current feedback (with I rated = Ir)

c Fault arcing

Id = Isc 1.3 to 2
c Equivalent impedance of a component through a transformer v for example, for a low voltage fault, the contribution of an HV cable upstream of an HV/LV transformer will be:

R2 = R1( U2 )2 et X2 = X1 (U2 )2

U1

U1

ainsi Z2 = Z1 (U2 )2 U1

This equation is valid for all voltage levels in the cable, in other words, even through several series-mounted transformers.

Power source Ra, Xa

A

HV cable R1, X1

n

LV cable R2, X2

transformer RT, XT impedance at primary

v Impedance seen from the fault location A:



R

=

R2

+

RT n2

+

R1 n2

+

Ra n2

n: transformation ratio

 X = X2 + XT + X1 + Xa n2 n2 n2

c Triangle of impedances Z = (R2 + X2)

Z X

R

16

Merlin Gerin MV design guide

Schneider Electric

Design rules

Short-circuit currents

The complexity in calculating the three-phase short-circuit current
basically lies in determining the impedance value in the network upstream of the fault location.

Example 1:

Network layout

Tr1

Tr2

A

Equivalent layouts Zr

Zt1

Zt2

Za

Z = Zr + Zt1//Zt2 Z = Zr + Zt1 · Zt2
Zt1 + Zt2
Za

Example of a three-phase calculation

Impedance method
All the components of a network (supply network, transformer, alternator, motors, cables, bars, etc) are characterised by an impedance (Z) comprising a resistive component (R) and an inductive component (X) or so-called reactance. X, R and Z are expressed in ohms.
c The relation between these different values is given by:

(cf. example 1 opposite)

Z = (R2 + X2)

c The method involves: v breaking down the network into sections v calculating the values of R and X for each component v calculating for the network: - the equivalent value of R or X - the equivalent value of impedance - the short-circuit current.

c The three-phase short-circuit current is:

Isc

:

U

:

Zsc

:

(cf. example 2 below)

Isc =

U

e · Zsc

short-circuit current (in kA) phase to phase voltage at the point in question before the appearance of the fault, in kV. short-circuit impedance (in ohms)

Zsc = Z//Za Zsc = Z · Za
Z + Za

Example 2: c Zsc = 0.72 ohm c U = 10 kV
Isc = 10 = 21.38 kA e · 0,27

Schneider Electric

Merlin Gerin MV design guide

17

Design rules
Here is a problem to solve!

Short-circuit currents

Exercice data
Supply at 63 kV Short-circuit power of the source: 2 000 MVA
c Network configuration: Two parallel mounted transformers and an alternator.
c Equipment characteristics: v transformers: - voltage 63 kV / 10 kV - apparent power: 1 to 15 MVA, 1 to 20 MVA - short-circuit voltage: Usc = 10 % v Alternator : - voltage: 10 kV - apparent power: 15 MVA - X'd transient: 20 % - X"d sub-transient: 15 %
c Question: v determine the value of short-circuit current at the busbars, v the breaking and closing capacities of the circuit breakers D1 to D7.

Single line diagram

Alternator 15 MVA

63 kV

X'd = 20 %
X''d = 15 % T1
G1

Transformer 15 MVA Usc = 10 %

Transformer

T2

20 MVA

Usc = 10 %

D3

D1

10 kV

D4

D5

D2
Busbars

D6

D7

18

Merlin Gerin MV design guide

Schneider Electric

Design rules
Here is the solution to the problem with the
calculation method

Short-circuit currents

Solving the exercise
c Determining the various short-circuit currents The three sources which could supply power to the short-circuit are the two transformers and the alternator. We are supposing that there can be no feedback of power through D4, D5, D6 and D7. In the case of a short-circuit upstream of a circuit breaker (D1, D2, D3, D4, D5, D6, D7), this then has the short-circuit current flow through it supplied by T1,T2 and G1.
c Equivalent diagram Each component comprises a resistance and an inductance. We have to calculate the values for each component. The network can be shown as follows:

Zr = network impedance

Za = alternator impedance different according to state (transient or subtransient)
Z15 = transformer impedance 15 MVA

Z20 = transformer impedance 20 MVA

busbars

Experience shows that the resistance is generally low compared with, reactance, so we can therefore deduce that the reactance is equal to the impedance (X = Z).
c To determine the short-circuit power, we have to calculate the various values of resistances and inductances, then separately calculate the arithmetic sum:
Rt = R
Xt = X
c Knowing Rt and Xt, we can deduce the value of Zt by applying the equation:
Z = ( R2 + X2)
N.B.: Since R is negligible compared with X, we can say that Z = X.

Schneider Electric

Merlin Gerin MV design guide

19

Design rules

Short-circuit currents

And now here are the results!

Component
Network Ssc = 2 000 MVA U op. = 10 kV

Calculation Zr = U2 = 102 Ssc 2 000

15 MVA transformer (Usc = 10 %) U op. = 10 kV

Z15 = U2 ·Usc = 102· 10

Sr

15 100

20 MVA transformer (Usc = 10 %) U op. = 10 kV

Z20 = U2 ·Usc = 102· 10

Sr

20 100

15 MVA alternator U op. = 10 kV
Transient state (Xsc = 20 %)
Sub-transient state (Xsc = 15 %)
Busbars Parallel-mounted with the transformers

Za = U2 · Xsc Sr
Zat =102 · 20 15 100
Zas =102 · 15 15 100
Z15//Z20 = Z15 · Z20 = 0.67 · 0.5 Z15 + Z20 0.67 + 0.5

Series-mounted with the network and the transformer impedance

Zr + Zet = 0.05 + 0.29

Parallel-mounting of the generator set Transient state
Sub-transient state

Zer//Zat = Zer · Zat = 0.34 · 1.33 Zer + Zat 0.34 + 1.33
Zer//Zat = Zer · Zat = 0.34 · 1 Zer + Zat 0.34 + 1

Z = X (ohms) 0.05 0.67 0.5
Zat = 1.33 Zas = 1 Zet = 0.29 Zer = 0.34
z 0.27 z 0.25

N.B.: a circuit breaker is

defined for a certain breaking

capacity of an rms value in a

steady state, and as a

percentage of the aperiodic

component which depends

on the circuit breaker's

opening time and on R

of the network

X

(about 30 %).

For alternators the aperiodic component is very high; the calculations must be validated by laboratory tests.

Circuit breaker

D4 to D7

Zr

Za

Z15

Z20

Zt = [Zr + (Z15//Z20)]//Za D3 alternator
Zr

Z15

Z20

Equivalent circuit Z (ohm)
transient state Z = 0.27 sub-transient state Z = 0.25
Z = 0.34

Breaking capacity in kA rms. Icc = U2 = 10 · 1
e ·Zsc e Zsc 21.40
17

Closing capacity 2.5 Isc (in kA peak)
21.40 · 2.5 = 53.15
17 · 2.5 = 42.5

Zt = Zr + (Z15//Z20) D1 15 MVA transformer

Zr Za Z20
Zt = (Zr + Z20)//Za D2 20 MVA transformer
Zr Za Z15 Zt = (Zr + Z15)//Za

transient state Z = 0.39 sub-transient state Z = 0.35
transient state Z = 0.47 sub-transient state Z = 0.42

17.9 12.4

14.9 · 2.5 = 37.25 12.4 · 2.5 = 31

20

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

In reality, a busbar calculation involves checking that it provides sufficient thermal and electrodynamic
withstand and non-resonance.

Introduction
c The dimensions of busbars are determined taking account of normal operating conditions. The voltage (kV) that the installation operates at determines the phase to phase and phase to earth distance and also determines the height and shape of the supports. The rated current flowing through the busbars is used to determine the cross-section and type of conductors.
c We then ensure that the supports (insulators) resist the mechanical effects and that the bars resist the mechanical and thermal effects due to short-circuit currents. We also have to check that the period of vibration intrinsic to the bars themselves is not resonant with the current period.
c To carry out a busbar calculation, we have to use the following physical and electrical characteristics assumptions:

Busbar electrical characteristics

Ssc

: network short-circuit power*

MVA

Ur

: rated voltage

kV

U

: operating voltage

kV

Ir

: rated current

A

* N.B.: It is is generally provided by the customer in this form or we can calculate it having the short-circuit current Isc and the operating voltage U: (Ssc = e · Isc · U; see chapter on "Shortcircuit currents").

Physical busbar characteristics

S

: busbar cross section

cm2

d

: phase to phase distance

cm

l

: distance between insulators

for same phase

cm

n

: ambient temperature (n  40°C)

°C

( - n) : permissible temperature rise*

profile

:

material

:

arrangement :

flat copper flat-mounted

°C
aluminium edge-mounted

no. of bar(s) per phase

:

* N.B.: see table V in standard ICE 60 694 on the 2 following pages.

In summary:

bar(s) of

x

cm per phase

Schneider Electric

Merlin Gerin MV design guide

21

Design rules

Busbar calculation

Temperature rise
Taken from table V of standard IEC 60 694

Type of device, of material and of dielectric (Cf: 1, 2 and 3) Bolt connected or equivalent devices (Cf: 7) bare copper, bare copper alloy or aluminium alloy in air SF6 * oil silver or nickel plated in air SF6 oil tin-plated in air SF6 oil
* SF6 (sulphur hexafluoride)

Temperature ( - n)

 (°C)

with n = 40°C

90

50

105

65

100

60

115

75

115

75

100

60

105

65

105

65

100

60

1 According to its function, the same device may belong to several categories given in table V. In this case, the admissible values of temperature and temperature rise to take into consideration are the lowest for category concerned.

2 For vacuum switchgear, the limit values of temperature and temperature rise do not apply to vacuum devices. Other devices must not exceed the values for temperature and temperature rise given in table V.
3 All the necessary precautions must be taken so that absolutely no damage is caused to surrounding materials.
7 When contact components are protected in different ways, the temperature and temperature rises that are allowed are those for the element for which table V authorises the highest values.

22

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

Temperature rise
Extract from table V of standard IEC 60 694

Type of device, of material and of dielectric

Temperature ( - n)

(Cf: 1, 2 and 3)

 (°C)

with n = 40°C

Contacts (Cf: 4) copper or bare copper alloy in

air

75

35

SF6 *

90

50

oil

80

40

silver or nickel plated (Cf: 5) in

air

105

65

SF6

105

65

oil

90

50

tin-plated (Cf: 5 and 6) in

air

90

50

SF6

90

50

oil

90

50

* SF6 (sulphur hexafluoride)

1 According to its function, the same device may belong to several

categories given in table V. In this case, the admissible values of

temperature and temperature rise to take into consideration are the

lowest for category concerned.

2 For vacuum switchgear, the limit values of temperature and temperature rise do not apply to vacuum devices. Other devices must not exceed the
values for temperature and temperature rise given in table V.

3 All the necessary precautions must be taken so that absolutely no damage is caused to surrounding materials.

4 When the contact components are protected in different manners, the temperatures and temperature rises that are allowed are those of the element for which table V authorises the lowest values.

5 The quality of coating must be such that a protective layer remains in the contact zone: - after the making and breaking test (if it exists), - after the short time withstand current test, - after the mechanical endurance test, according to specifications specific to each piece of equipment. Should this not be true, the contacts must be considered as "bare".

6 For fuse contacts, the temperature rise must be in conformity with publications concerning high voltage fuses.

Schneider Electric

Merlin Gerin MV design guide

23

Design rules

Busbar calculation

Let's check if the cross-section that has been chosen: ... bar(s) of ... x ... cm per phase satisfies the temperature rises produced by the rated current and by the short-circuit
current passing through them for 1 to 3 second(s).

Thermal withstand...
For the rated current (Ir)
The MELSON & BOTH equation published in the "Copper Development Association" review allows us to define the permissible current in a conductor:
24.9 ( - n)0.61 · S0.5 · p0.39 I = K ·
20 [1+  ( - 20)]

a

P
perimeter of a bar
e e

with: I

: permissible current expressed in amperes (A) derating in terms of current should be considered: - for an ambient temperature greater than 40°C - for a protection index greater than IP5

n

: ambient temperature (n  40°C)

°C

( - n) : permissible temperature rise*

°C

S

: busbar cross section

cm2

p

: busbar perimeter

(opposite diagram)

20

: conductor resistivity at 20°C

: copper:

: aluminium:

cm
1.83 µ cm 2.90 µ cm



: temperature coefficient of the resistivity: 0.004

K

: conditions coefficient

product of 6 coefficients (k1, k2, k3, k4, k5, k6), described below

*(see table V of standard IEC 60 694 in the previous pages)

Definition of coefficients k1, 2, 3, 4, 5, 6:

c Coefficient k1 is a function of the number of bar strips per phase for: v 1 bar (k1 = 1) v 2 or 3 bars, see table below:

e/a 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

no. of bars per phase

k1

2

1.63 1.73 1.76 1.80 1.83 1.85 1.87 1.89 1.91

3

2.40 2.45 2.50 2.55 2.60 2.63 2.65 2.68 2.70

In our case: e/a = the number of bars per phase = giving k1 =

24

Merlin Gerin MV design guide

Schneider Electric

Design rules
Schneider Electric

Busbar calculation

c Coefficient k2 is a function of surface condition of the busbars:

v bare:

k2 = 1

v painted:

k2 = 1.15

c Coefficient k3 is a function of the position of the bars:

v edge-mounted bars:

k3 = 1

v 1 bar base-mounted:

k3 = 0.95

v several base-mounted bars:

k3 = 0.75

c Coefficient k4 is a function of the place where the bars are installed:

v calm indoor atmosphere :

k4 = 1

v calm outdoor atmosphere:

k4 = 1.2

v bars in non-ventilated ducting:

k4 = 0.80

c Coefficient k5 is a function of the artificial ventilation:

v without artificial ventilation:

k5 = 1

v ventilation should be dealt with on a case by case basis and then

validated by testing.

c Coefficient k6 is a function of the type of current: v for a alternatif current of frequency  60 Hz, k6 is a function of the number of bars n per phase and of their spacing.
The value of k6 for a spacing equal to the thickness of the bars:

n

123

k6 1 1 0.98

In our case: n =

giving k6 =

In fact we have:

k =

·

·

·

·

·

=

24.9 (

-

) 0.61 ·

0.5 ·

0.39

I =

·

[1+ 0.004 (

- 20)]

24.9 ( - n)0.61 · S0.5 · p0.39 I = K ·
20 [1+  ( - 20)]

I =

A

The chosen solution

of

·

bar(s) cm per phase

Is appropriate if Ir of the required busbars  I

Merlin Gerin MV design guide

25

Design rules

Busbar calculation

Example: How can we find the value of Ith for a different duration? Knowing: (Ith)2 · t = constant

c

If

Ith 2

=

26.16

kA

rms.

2

s,

what does Ith correspond to for 1

t = 1 s?

(Ith )2 · t = constant 2
(26.16 · 103)2 ·2 = 137 · 107

so Ith = ( constant ) = ( 137 · 107 )

1

t

1

Ith = 37 kA rms. for 1 s 1

c In summary:

v at 26.16 kA rms. 2 s, it corresponds to 37 kA rms. 1 s
v at 37 kA rms. 1 s, it corresponds to 26.16 kA rms. 2 s

For the short-time withstand current (Ith)
c We assume that for the whole duration (1 or 3 seconds): v all the heat that is given off is used to increase the temperature of the conductor v radiation effects are negligible.

The equation below can be used to calculate the short-circuit

temperature rise:

cc = 0.24 · 20 · Ith2 · tk

(n · S)2 · c · 

with: sc c
S n Ith tk 
20
( - n)

: short-circuit temperature rise

: specific heat of the metal copper: aluminium:

0.091 kcal/daN°C 0.23 kcal/daN °C

: busbar cross section

cm2

: number of busbar(s) per phase
: is the short-time withstand current: (maximum short-circuit current, rms value )

A rms

: short-time withstand current duration (1 to 3 s) in s

: density of the metal copper: aluminium:

8.9 g/cm3 2.7 g/cm3

: resistivity of the conductor at 20°C copper: aluminium:

1.83 µ cm 2.90 µ cm

: permissible temperature rise

°C

sc =

sc = 0.24 · (
°C

10-6· (

)2 ·

)2 ·

·

The temperature, t of the conductor after the short-circuit will be:

t = n + (-n) + sc

t =

°C

Check:
t  maximum admissible temperature by the parts in contact with the busbars.
Check that this temperature t is compatible with the maximum temperature of the parts in contact with the busbars (especially the insulator).

26

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

We have to check if the bars chosen withstand the electrodynamic forces.

Idyn

F1

d

F1 Idyn
l

d

h = e/2 H

F1 F
support

Schneider Electric

Electrodynamic withstand

Forces between parallel-mounted conductors
The electrodynamic forces following a short-circuit current are given by the equation:
F1 = 2 l · Idyn2 · 10-8 d

with
F1 Idyn

: force expressed in daN : is the peak value of short-circuit expressed in A,
to be calculated with the equation below:

Idyn = k · Ssc = k · Ith Ue

Ssc

: short-circuit power

Ith

: short-time withstand current

U

: operating voltage

l

: distance between insulators on the same phase

d

: phase to phase distance

kVA A rms kV cm cm

k

: 2.5 for 50 Hz ; 2.6 for 60 Hz for IEC and 2.7 according to ANSI

Giving : Idyn =

A and F1 =

daN

Forces at the head of supports or busducts

Equation to calculate the forces on a support:
F = F1 · H + h H

with

F

: force expressed

daN

H

: insulator height

cm

h

: distance from insulator head

to busbar centre of gravity

cm

Calculation of forces if there are N supports

c The force F absorbed by each support is at most equal to the calculated force F1 (see previous chapter) multiplied by a coefficient kn which varies according to the total number N of equidistant supports that are installed.

v number of supports

= N

v we know N, let us define kn with the help of the table below:

giving F =

(F1)·

(kn) =

daN

N2

3

4

 5

kn 0.5 1.25 1.10 1.14

c The force found after applying a coefficient k should be compared with the mechanical strength of the support to which we will apply a safety coefficient: v the supports used have a bending resistance

F' =

v we have a safety coefficient of

F' F

=

daN check if F' > F

Merlin Gerin MV design guide

27

Design rules

Busbar calculation

phase 1 x
b v
h x'

phase 2

phase 1

v

x

phase 2

b
d h
x'
xx': perpendicular to the plane of vibration

Mechanical busbar strength
c By making the assumption that the ends of the bars are sealed, they are subjected to a bending moment whose resultant strain is:
 = F1· l · v 12 I

with



:

is the resultant strain,
it must be less than the permissible strain
for the bars this is: copper 1/4 hard: 1 200 daN/cm2 copper 1/2 hard: 2 300 daN/cm2 copper 4/4 hard: 3 000 daN/cm2 tin-plated alu: 1 200 daN/cm2

F1 :

force between conductors

daN

l

:

distance between insulators

in the same phase

cm

I/v :

is the modulus of inertia between a bar or a set of bars
(choose the value in the table on the following page)

cm3

v

:

distance between the fibre that is neutral and the fibre with the highest strain (the furthest)

c One bar per phase:

I = b · h3 12
I = b · h2 v6

c Two bars per phase:
I = 2 ( b · h3 + S · d2) 12

I v

2 ( b · h3 = 12
1.5 · h

+ S · d2)

S:

busbar cross section (in cm2)

Check: 

<  Bars Cu or Al

(in daN/cm2)

28

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

Arrangement*
x

S

cm2

m

Cu

daN/cm A5/L

I

cm4

x'

I/v

cm3

x

I

cm4

x'

I/v

cm3

x

I

cm4

x'

I/v

cm3

x

I

cm4

x'

I/v

cm3

x

I

cm4

x'

I/v

cm3

x

I

cm4

x'

I/v

cm3

Choose your cross-section S, linear mass m, modulus of inertia I/v, moment of inertia I for the bars defined below:

100 x 10
10 0.089 0.027

80 x 10
8 0.071 0.022

Busbar dimensions (mm)

80 x 6 80 x 5

80 x 3

4.8 0.043 0.013

4 0.036 0.011

2,4 0.021 0.006

50 x 10
5 0.044 0.014

50 x 8
4 0.036 0.011

50 x 6
3 0.027 0.008

50 x 5
2.5 0.022 0.007

0.83

0.66

0.144 0.083

0.018

0.416

0.213

0.09

0.05

1.66

1.33

0.48

0.33

0.12

0.83

0.53

0.3

0.2

83.33

42.66

25.6

21.33

12.8

10.41

8.33

6.25

5.2

16.66

10.66

6.4

5.33

3.2

4.16

3.33

2.5

2.08

21.66

17.33

3.74

2.16

0.47

10.83

5.54

2.34

1.35

14.45

11.55

4.16

2.88

1.04

7.22

4.62

2.6

1.8

166.66 85.33

51.2

42.66

25.6

20.83

16.66

12.5

10.41

33.33

21.33

12.8

10.66

6.4

8.33

6.66

5

4.16

82.5

66

14.25 8.25

1.78

41.25

21.12

8.91

5.16

33

26.4

9.5

6.6

2.38

16.5

10.56

5.94

4.13

250

128

76.8

64

38.4

31.25

25

18.75

15.62

50

32

19.2

16

9.6

12.5

10

7.5

6.25

*arrangement: cross-section in a perpendicular plane to the busbars (2 phases are shown)

Intrinsic resonant frequency

The intrinsic frequencies to avoid for the busbars subjected to a 50 Hz current are frequencies of around 50 and 100 Hz. This intrinsic frequency is given by the equation:

f = 112 E·I m·l4

Check that the chosen busbars
will not resonate.

f

: resonant frequency in Hz

E

: modulus of elasticity:

for copper = 1.3 · 106 daN/cm2

for aluminium A5/L = 0.67 · 106 daN/cm2

m

: linear mass of the busbar

(choose the value on the table above)

l

: length between 2 supports

or busducts

daN/cm cm

I

: moment of inertia of the busbar cross-section

relative to the axis x'x, perpendicular

to the vibrating plane

cm4

(see formula previously explained or choose the value in the table above)

Schneider Electric

giving

f =

Hz

We must check that this frequency is outside of the values that must be avoided, in other words between 42 and 58 and 80 and 115 Hz.

Merlin Gerin MV design guide

29

Design rules

Busbar calculation

Here is a busbar calculation to check.

Busbar calculation example

Top view
Cubicle 1

Cubicle 2 Cubicle 3

Cubicle 4

Cubicle 5

d d

12 cm

1 cm 5 cm

1 cm 10 cm

d

d

Exercise data

c Consider a switchboard comprised of at least 5 MV cubicles. Each cubicle has 3 insulators(1 per phase). Busbars comprising 2 bars per phase, inter-connect the cubicles electrically.

Busbar characteristics to check:

S

: busbar cross-section (10 ·1)

d

: phase to phase distance

10 cm2 18 cm

l
n ( - n) profile

: distance between insulators on the same phase

70 cm

: ambient temperature

40 °C

: permissible temperature rise 50 °C
(90-40=50)

: flat

material :

busbars in copper 1/4 hard, with a permissible strain  = 1 200 daN/cm2

arrangement: edge-mounted

number of busbar(s) per phase:

2

c The busbars must be able to withstand a rated current Ir = 2,500 A on a permanent basis and a short-time withstand current Ith = 31,500 A rms. for a time of tk = 3 seconds.

c Rated frequency fr = 50 Hz

c Other characteristics:
v parts in contact with the busbars can withstand a maximum temperature of max = 100°C v the supports used have a bending resistance of F' = 1 000 daN

30

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

a

Let's check the thermal withstand
of the busbars!
e e

For the rated current (Ir)

The MELSON & BOTH equation allows us to define the

permissible current in the conductor:

I = K ·

24.9 ( - n)0.61 · S0.5 · p0.39
20 [1+  ( - 20)]

with: I
n

: permissible current expressed in amperes (A)

: ambient temperature

40 °C

( - n) : permissible temperature rise*

50 °C

S

: busbar cross-section

10 cm2

p

: busbar perimeter

22 cm

20

: resistivity of the conductor at 20°C

copper:

1.83 µ cm



: temperature coefficient

for the resistivity:

0.004

K

: condition coefficient

product of 6 coefficients (k1, k2, k3, k4, k5, k6),

described below

*(see table V in standard CEI 60 694 pages 22 and 23)

Definition of coefficients k1, 2, 3, 4, 5, 6:

c Coefficient k1 is a function of the number of bar strips per phase for: v 1 bar (k1 = 1) v 2 or 3 bars, see table below:

e / a

0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20

number of bars per phase

k1

2 1.63 1.73 1.76 1.80 1.83 1.85 1.87 1.89 1.91

3 2.40 2.45 2.50 2.55 2.60 2.63 2.65 2.68 2.70

In our case:

e/a =

0.1

number of bars per phase =

2

giving k1 =

1.80

Schneider Electric

Merlin Gerin MV design guide

31

Design rules
32

Busbar calculation

c Coefficient k2 is a function of the surface condition of the bars:

v bare:

k2 = 1

v painted:

k2 = 1.15

c Coefficient k3 is a function of the busbar position:

v edge-mounted busbars:

k3 = 1

v 1 bar flat-mounted:

k3 = 0.95

v several flat-mounted bars:

k3 = 0.75

c Coefficient k4 is a function of where the bars are installed:

v calm indoor atmosphere:

k4 = 1

v calm outdoor atmosphere:

k4 = 1.2

v bars in non-ventilated ducting:

k4 = 0.80

c Coefficient k5 is a function of the artificial ventilation:

v without artificial ventilation:

k5 = 1

v cases with ventilation must be treated on a case by case

basis and then validated by testing.

c Coefficient k6 is a function of the type of current: v for alternatif current at a frequency of 60 Hz, k6 is a function of the number of busbars n per phase and of their spacing. The value of k6 for a spacing equal to the thickness of the busbars:

n

123

k6 1 1 0.98

In our case: n= 2

giving k6 = 1

In fact, we have: k = 1.80 · 1 · 1 · 0.8 · 1 · 1 = 1.44

24.9 ( 90 - 40 ) 0.61 · 10 0.5 · 22 0.39 I = 1.44 ·
1.83 [1+ 0.004 ( 90 - 20)]

I = K ·

24.9 ( - n)0.61 · S0.5 · p0.39
20 [1+  ( - 20)]

I = 2 689 A

The chosen solution: 2 busbars of 10 · 1 cm per phase
is appropriate:
Ir < I either 2 500 A < 2 689 A

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

Calculation of t must be
looked at in more detail because the required busbars have to withstand
Ir = 2 500 A at most and not 2 689 A.

For the short-time withstand current (Ith)
c we assume that, for the whole duration (3 seconds) : v all the heat given off is used to increase the temperature of the conductor v the effect of radiation is negligible.
The equation below can be used to calculate the temperature rise due to short-circuit:
0.24 · 20 · Ith2 · tk
cc = (n · S)2 · c · 

with:

c

:

specific heat of the metal copper:

0.091 kcal / daN°C

S

: is the cross section expressed in cm2 10 cm2

n

: number of bars per phase

2

Ith : is the short-time withstand current 31 500 A rms.
(rms. value of the maximum shortcircuit current)

tk : short-time withstand current duration (1 to 3 secs)

3

in secs



: density of the metal

copper:

8.9 g/cm3

20 : resistivity of the conductor at 20°C

copper:

1.83 µ cm

( - n): permissible temperature rise

50 °C

v The temperature rise due to the short circuit is:

0.24 · 1.83 10-6· ( 31 500 )2 · 3 cc =
( 2 ·10 )2 · 0.091 · 8.9 cc = 4 °C

The temperature t of the conductor after short-circuit will be:
t = n + (-n) + cc = 40 + 50 + 4 = 94 °C
for I = 2 689 A (see calculation in the previous pages)

Schneider Electric

Merlin Gerin MV design guide

33

Design rules

Busbar calculation

c Let us fine tune the calculation for t for Ir = 2 500 A (rated current for the busbars)

v the MELSON & BOTH equation (cf: page 31), allows us to deduce the following:
I = constant · (-n)0.61 et
Ir= constant · ()0.61

( ) therefore

I= Ir

(-n) 0.61 ()

( ) 2 689
2 500

=

50 ()

0.61

1

( ) 50
 =

2 689 2 500

0.61

50 

= 1.126

 = 44.3 °C

v temperature t of the conductor after short-circuit, for a rated current Ir = 2 500 A is:
t = n +  + cc
= 40 + 44.3 + 4
= 88.3 °C for Ir = 2 500 A

The busbars chosen are suitable because:
t = 88.3 °C is less than max = 100 °C
(max = maximum temperature that can be withstood by the parts in contact with the busbars).

34

Merlin Gerin MV design guide

Schneider Electric

Design rules

Busbar calculation

Let's check the electrodynamic withstand of the busbars.
Schneider Electric

Forces between parallel-mounted conductors

Electrodynamc forces due to the short-circuit current are given by the equation:
F1 = 2 l · Idyn2 · 10-8 d

(see drawing 1 at the start of the calculation example) l : distance between insulators in the same phase d : phase to phase distance
k : 2.5 for 50 Hz according to IEC

70 cm 18 cm

Idyn :

peak value of short-circuit current = k · Ith = 2.5 · 31 500 = 78 750 A

F1 = 2 · (70/18) · 78 7502 · 10-8 = 482.3 daN

Forces at the head of the supports or busducts
Equation to calculate forces on a support :
F = F1 · H + h H

with

F : force expressed in daN H : insulator height

12 cm

h : distance from the head of the insulator

to the busbar centre of gravity

5 cm

Calculating a force if there are N supports
c The force F absorbed by each support is at most equal to the force F1 that is calulated multiplied by a coefficient kn which varies according to the total number N of equi-distant supports that are installed. v number of supports  5 = N
v we know N, let us define kn using the table below:

N2

3

4

 5

kn 0.5 1.25 1.10 1 . 1 4

giving F = 683 (F1)· 1 . 1 4 (kn) = 778 daN

The supports used have a bending resistance F' = 1 000 daN calculated force F = 778 daN.
The solution is OK

Merlin Gerin MV design guide

35

Design rules

Busbar calculation

Mechanical strength of the busbars
Assuming that the ends of the bars are sealed, they are subjected to a bending moment whose resultant strain is:
 = F1· l · v 12 I

with  : is the resultant strain in daN/cm2

l : distance between insulators in the same phase

I/v :

is the modulus of inertia of a busbar or of a set of busbars
(value chosen in the table below)

70 cm 14.45 cm3



=

482.3 · 12

70

·

1 14.45

 = 195 daN / cm2

The calculated resultant strain ( = 195 daN / cm2) is less than the permissible strain for the copper busbars 1/4 hard (1200 daN / cm2) :

The solution is OK

Busbar dimensions (mm)

Arrangement
x
x' x
x' x
x' x
x' x
x' x
x'

S m daN/cm I I/v I I/v I I/v I I/v I I/v I I/v

cm2 Cu A5/L cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3

100 x 10 10 0.089 0.027 0,83 1.66 83.33 16.66 21.66 14.45 166.66 33.33 82.5 33 250 50

36

Merlin Gerin MV design guide

Schneider Electric

Design rules
Let us check that the chosen busbars
do not resonate.

Busbar calculation

Inherent resonant frequency
The inherent resonant frequencies to avoid for busbars subjected to a current at 50 Hz are frequencies of around 50 and 100 Hz. This inherent resonant frequency is given by the equation:

f = 112

E·I m·l4

f : frequency of resonance in Hz
E : modulus of elasticity for copper =

1.3 · 106 daN/cm2

m : linear mass of the bar

0.089 daN/cm

l : length between 2 supports or busducts

70 cm

I : moment of inertia of the busbar section relative to the axis x'x perpendicular to the vibrating plane
(choose m and I on the table on the previous page)

21.66 cm4

( ) f = 112

1.3 · 106 · 21.66 0.089 · 70 4

f = 406 Hz

f is outside of the values that have to be avoided, in other words 42 to 58 Hz and 80 to 115 Hz:
The solution is OK

In conclusion
The busbars chosen, i.e. 2 bars of 10 · 1 cm per phase, are suitable for an Ir = 2 500 A and Ith = 31.5 kA 3 sec.

Schneider Electric

Merlin Gerin MV design guide

37

Design rules

Dielectric withstand

A few orders of magnitude Dielectric strength
(20°C, 1 bar absolute): 2.9 to 3 kV/mm Ionization limit
(20°C, 1 bar absolute): 2.6 kV/mm

c The dielectric withstand depends on the following 3 main parameters: v the dielectric strength of the medium v the shape of the parts v the distance: - ambient air between the live parts - insulating air interface between the live parts.
The dielectric strength of the medium
This is a characteristic of the fluid (gas or liquid) making up the medium. For ambient air this characteristic depends on atmospheric conditions and pollution.

The dielectric strength of air depends on the following ambient conditions
c Pollution Conductive dust can be present in a gas, in a liquid, or be deposited on the surface of an insulator. Its effect is always the same: reducing the insulation performances by a factor of anything up to 10!
c Condensation Phenomena involving the depositing of droplets of water on the surface of insulators which has the effect of locally reducing the insulating performance by a factor of 3.
c Pressure The performance level of gas insulation, is related to pressure. For a device insulated in ambient air, altitude can cause a drop in insulating performance due to the drop in pressure. We are often obliged to derate the device.
c Humidity In gases and liquids, the presence of humidity can cause a change in insulating performances. In the case of liquids, it always leads to a drop in performance. In the case of gases, it generally leads to a drop (SF6, N2 etc.) apart from air where a low concentration (humidity < 70%) gives a slight improvement in the overall performance level, or so called "full gas performance"*.
c Temperature The performance levels of gaseous, liquid or solid insulation decrease as the temperature increases. For solid insulators, thermal shocks can be the cause of micro-fissuration which can lead very quickly to insulator breakdown. Great care must therefore be paid to expansion phenomena: a solid insulator expands by between 5 and 15 times more than a conductor.
* We talk about "full gas" insulation.
Pollution level
Pollution may originate: from the external gaseous medium (dust), initial lack of cleanliness, possibly the breaking down of an internal surface, pollution combined with humidity causes electrochemical conduction which will worsen discharge phenomena. Its scope can be a constraint of the external medium (exposure to external elements).

38

Merlin Gerin MV design guide

Schneider Electric

Design rules

Dielectric withstand

Air ionization

The shape of parts
This plays a key role in switchgear dielectric withstand. It is essential to eliminate any "peak" effect which would have a disastrous effect on the impulse wave withstand in particular and on the surface ageing of insulators:

Ozone production

Breakdown of moulded insulator surface skin

V

0

d

U

Distance between parts
Ambient air between live parts
c For installations in which, for various reasons, we cannot test under impulse conditions, the table in publication IEC 71-2 gives, according to the rated lightning impulse withstand voltage, the minimum distances to comply with in air either phase to earth or phase to phase.
c These distances guarantee correct withstand for unfavourable configurations: altitude < 1 000 m.
c Distances in air* between conductive parts that are live and structures which are earthed giving a specified impulse withstand voltage under dry conditions:

Rated lightning impulse withstand voltage
Up (kV) 40 60 75 95 125

Minimum distance in air phase to earth and phase to phase d (mm) 60 90 120 160 220

The values for distances in air given in the table above are minimum values determined by considering dielectric properties, they do not include any increase which could be required to take account of design tolerances, short circuit effects, wind effects, operator safety, etc.
*These indications are relative to a distance through a single air gap, without taking account of the breakdown voltage by tracking across the surfaces, related to pollution problems.

Schneider Electric

Merlin Gerin MV design guide

39

Design rules

Dielectric withstand

U

Lf O

Insulating air interface between live parts
c There are 4 severity levels of pollution, given in the table below, according to IEC 60 815*:

Lf : tracking path

Pollution level I-low
II-medium
III-high IIII-very high

Example of characteristic environments v industry free zone with very low density of housing equipped with heating installations v zones with low density of industry or housing but frequently subjected to wind and/or rain v agricultural regions 1 v mountain regions v all these zones can be located at distances of at least 10 km from the sea and must not be exposed to wind blowing in from the sea 2
v zones with industries producing particularly polluting smoke and/or with an average density of housing equipped with heating installations v zones with a high density of housing and/or industries but subjected frequently to winds and/or to rainfall v zones exposed to a sea wind, but not too close to the coast (at a distance of at least several kilometres) 2
v zones with a high density of industries and suburbs of major cities with a high density of polluting heating installations v zones situated near to the sea, or at least exposed to quite high winds coming in from the sea 2
v generally fairly small areas, subjected to conductive dust and to industrial smoke producing conductive deposits that are particularly thick v generally fairly small areas, very close to the coast and exposed to mist or to very high winds and to pollutants coming from the sea 2 v desert zones characterise by long periods without rain, exposed to high winds carrying sand and salt and subjected to regular condensation.
*IEC 60 815 guides you in choosing insulators for polluted environments 1 The use of sprayed fertilisers or the burning of harvested land can lead to a higher level of pollution due to dispersion by the winds 2 The distances to the waters edge depends on the topography of the coast region and the extreme conditions of wind.

40

Merlin Gerin MV design guide

Schneider Electric

Design rules
Temperature derating must be
considered.

Protection Index
The IP code
Introduction
Protection of people against direct contact and protection of equipment against certain external influences is required by international standards for electrical installations and products (IEC 60 529). Knowing the protection index is essential for the specification, installation, operation and quality control of equipment.
Definitions
The protection index is the level of protection provided by an enclosure against access to hazardous parts, the penetration of solid foreign bodies and of water. The IP code is a coding system to indicate the protection index.
Applicational scope
It applies to enclosures for electrical equipment with a rated voltage of less than or equal to 72.5 kV. It does not concern the circuit breaker on its own but the front panel must be adapted when the latter is installed within a cubicle (e.g. finer ventilation grills).
The various IP codes and their meaning
A brief description of items in the IP code is given in the table on the following page.

Schneider Electric

Merlin Gerin MV design guide

41

Design rules

Protection index

Item
Code letter first characteristic figure

Figures or letters IP
0 1

Meaning for protection of equipment
against penetration of solid foreign bodies (not protected) diameter  50 mm

2

diameter  12.5 mm

3

diameter  2.5 mm

4

diameter  1 mm

5

protected against dust

6

sealed against dust

second characteristic figure
0 1

against penetration of water with detrimental effects (not protected) vertical water drops

2

water drops (15° inclination)

3

rain

4

water projection

of people
against access to hazardous parts with (not protected) back of the hand

Representation
Ø 50mm

finger tool wire wire

Ø 12,5mm
X
~ Ø 2,5mm
Ø 1mm

wire

15° 60°

5
6
7
8
additional letter (optional) A B C D
additional letter (optional) H M S W

spray projection

high power spray projection

temporary immersion

prolonged immersion

additional information specific to: high voltage equipment movement during the water testing stationary during the water testing bad weather

against access to hazardous parts with: back of the hand finger tool wire

42

Merlin Gerin MV design guide

Schneider Electric

Design rules
Schneider Electric

Protection Index

IK code

Introduction
c Certain countries felt the need also to code the protection provided by enclosures against mechanical impact. To do this they added a third characteristic figure to the IP code (the case in Belgium, Spain, France and Portugal). But since the adoption of IEC 60 529 as the European standard, no European country can have a different IP code.

c Since the IEC has up to now refused to add this third figure to the IP code, the only solution to maintain a classification in this field was to create a different code. This is a subject of a draft European standard EN 50102: code IK.

c Since the third figure in various countries could have different meanings and we had to introduce additional levels to cover the main requirements of product standards, the IK indices have a different meaning to those of the previous third figures (cf. table below).

Previous 3rd figures of the

IK code

IP code in NF C 20-010 (1986)

IP XX1

IK 02

IP XX3

IK 04

IP XX5

IK 07

IP XX7

IK 08

IP XX9

IK 10

NB: to limit confusion, each new index is given by a two figure number.

Definitions
c The protection indices correspond to impact energy levels expressed in joules v hammer blow applied directly to the equipment v impact transmitted by the supports, expressed in terms of vibrations therefore in terms of frequency and acceleration
c The protection indices against mechanical impact can be checked by different types of hammer: pendulum hammer, spring-loaded hammer or vertical free-fall hammer (diagram below).

striker

latching mechanism

relief cone support

pedulum pivot

arming button

attaching support

fall height specimen

Merlin Gerin MV design guide

43

Design rules

Protection index

The various IK codes and their meaning

IK code energies in joules radius mm 1 material 1 steel = A 2 polyamide = P 3 hammer
pendulum spring loaded 4 vertical

IK 01 0.15 10 P

IK 02 0.2 10 P









 = yes

IK 03 0.35 10 P
 

IK 04 0.5 10 P
 

IK 05 0.7 10 P
 

IK 06 1 10 P
 

IK 07 2 25 A
 

IK 08 5 25 A
 

IK 09 10 50 A
 

IK 10 20 50 A
 

N.B.:
1 of the hammer head 2 Fe 490-2 according to ISO 1052, hardness 50 HR to 58 HR according to ISO 6508 3 hardness HR 100 according to ISO 2039-2

44

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Medium voltage circuit breaker

IEC 60 056 and ANSI C37-06 define on one hand the operating conditions,
the rated characteristics, the design and the manufacture; and on the other hand
the testing, the selection of controls and installation.

Introduction
c The circuit breaker is a device that ensures the control and protection on a network. It is capable of making, withstanding and interrupting operating currents as well as short-circuit currents.
c The main circuit must be able to withstand without damage: v the thermal current = short-circuit current during 1 or 3 s v the electrodynamic current:
2.5 · Isc for 50 Hz (IEC) 2.6 · Isc for 60 Hz (IEC) 2.7 · Isc (ANSI), for a particular time constant (IEC) v the constant load current.
c Since a circuit breaker is mostly in the "closed" position, the load current must pass through it without the temperature running away throughout the equipment's life.

Characteristics
Compulsory rated characteristics
c Rated voltage c Rated insulation level c Rated normal current c Rated short-time withstand current c Rated peak withstand current c Rated short-circuit duration c Rated supply voltage for opening and closing devices and auxiliary circuits c Rated frequency c Rated short-circuit breaking current c Rated transient recovery voltage c Rated short-circuit making current c Rated operating sequence c Rated time quantities.

Special rated characteristics
c These characteristics are not compulsory but can be requested for specific applications: v rated out-of-phase breaking current, v rated cable-charging breaking current, v rated line-charging breaking current, v rated capacitor bank breaking current, v rated back-to-back capacitor bank breaking current, v rated capacitor bank inrush making current, v rated small inductive breaking current.

Rated voltage (cf. § 4.1 IEC 60 694)
The rated voltage is the maximum rms. value of the voltage that the equipment can withstand in normal service. It is always greater than the operating voltage.
c Standardised values for Ur (kV) : 3.6 - 7.2 -12 - 17.5 - 24 - 36 kV.

Schneider Electric

Merlin Gerin MV design guide

45

Switchgear definition

Upeak (%) 100 90
50
1.2 µs
10
50 µs
Standardised wave 1.2/50 µs

t (µs)

46

Medium voltage circuit breaker

Rated insulation level (cf. § 4.2 IEC 60 056 and 60 694)
c The insulation level is characterised by two values: v the impulse wave withstand (1.2/50 µs) v the power frequency withstand voltage for 1 minute.

Rated voltage
(Ur in kV) 7.2 12 17.5 24 36

Impulse withstand voltage (Up in kV) 60 75 95 125 170

Power frequency withstand voltage (Ud in kV) 20 28 38 50 70

Rated normal current (cf. § 4.4 IEC 60 694)
With the circuit breaker always closed, the load current must pass through it in compliance with a maximum temperature value as a function of the materials and the type of connections. IEC sets the maximum permissible temperature rise of various materials used for an ambient air temperature of no greater than 40°C (cf. § 4.4.2 table 3 IEC 60 694).

Rated short-time withstand current (cf. § 4.5 IEC 60 694)

Ssc

:

U

:

Isc

:

Isc = Ssc e ·U
short-circuit power operating voltage short-circuit current

(in MVA) (in kV) (in kA)

This is the standardised rms. value of the maximum permissible short-circuit current on a network for 1 or 3 seconds. c Values of rated breaking current under maximum short-circuit (kA): 6.3 - 8 - 10 - 12.5 - 16 - 20 - 25 - 31.5 - 40 - 50 kA.

Rated peak withstand current (cf. § 4.6 IEC 60 694) and making current (cf. § 4.103 IEC 60 056)
The making current is the maximum value that a circuit breaker is capable of making and maintaining on an installation in short-circuit. It must be greater than or equal to the rated short-time withstand peak current. Isc is the maximum value of the rated short-circuit current for the circuit breakers' rated voltage. The peak value of the short-time withstand current is equal to:
2.5 · Isc for 50 Hz 2.6 · Isc for 60 Hz 2.7 · Isc for special applications.

Rated short-circuit duration (cf. § 4.7 IEC 60 694)
The rated short-circuit is equal to 1 or 3 seconds.

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Medium voltage circuit breaker

t

t'

Isc

Ir time

O CO

CO

Rated supply voltage for closing and opening devices and auxiliary circuits (cf. § 4.8 IEC 60 694)
c Values of supply voltage for auxiliary circuits: v for direct current (dc): 24 - 48 - 60 - 110 or 125 - 220 or 250 volts, v for alternating current (ac): 120 - 220 - 230 - 240 volts.
c The operating voltages must lie within the following ranges: v motor and closing release units:
-15% to +10% of Ur in dc and ac v opening release units:
-30% to +10% of Ur in dc -15% to +10% of Ur in ac v undervoltage opening release unit:

the release unit gives the command and forbids closing

0 %

35 %

the release unit

must not have

an action

U

70 %

100 %

(at 85%, the release unit must enable the device to close)

Rated frequency (cf. § 4.9 IEC 60 694)
Two frequencies are currently used throughout the world: 50 Hz in Europe and 60 Hz in America, a few countries use both frequencies. The rated frequency is either 50 Hz or 60 Hz.

Rated operating sequence (cf. § 4.104 IEC 60 056)
c Rated switching sequence according to IEC, O - t - CO - t' - CO. (cf: opposite diagram)

O

:

CO

:

represents opening operation represents closing operation followed immediately by an opening operation

c Three rated operating sequences exist: v slow: 0 - 3 mn - CO - 3 mn - CO v quick 1: O - 0.3 s - CO - 3 mn - CO v quick 2: O - 0.3 s - CO - 15 s - CO
N.B.: other sequences can be requested.
c Opening/closing cycle Assumption: O order as soon as the circuit breaker is closed.

open position
energising of closing circuit

current flows
opening-closing duration
making-breaking duration contacts are touching in all poles and order O
current starts to flow in first pole

displacement of contacts
time
final arc extinction in all poles separation of arcing contacts in all poles

Schneider Electric

Merlin Gerin MV design guide

47

Switchgear definition

Medium voltage circuit breaker

c Automatic reclosing cycle Assumption: C order as soon as the circuit breaker is open, (with time delay to achieve 0.3 sec or 15 secs or 3 min).

closed position

displacement of contacts
open position

current flows

making-breaking duration opening-closing duration
remaking duration reclosing duration
final arc extinction in all poles

separation of arc contacts in all poles and order C
energising of opening release unit

current flows

time

the contacts are touching in all poles
the contacts touch in the first pole

start of current flow in the first pole

Example 1: c For a circuit breaker with a minimum opening duration of 45 ms (Top) to which we add 10 ms (Tr) due to relaying, the graph gives a percentage of the aperiodic component of around 30 % for a time constant 1 = 45 ms:
-(45 + 10)
%DC = e 45 = 29.5 %

Example 2:
c Supposing that % DC of a MV circuit breaker is equal to 65% and that the symmetric short-circuit current that is calculated (Isym) is equal to 27 kA. What does Iasym equal?

Iasym = Isym

} 1 + 2( %DC )2 [A] 100

= 27 kA 1 + 2 (0.65)2

= 36.7 kA

c Using the equation [A], this is equivalent to a symmetric short-circuit current at a rating of:

36.7 kA 1.086 = 33.8 kA

for a %DC of 30%.

c The circuit breaker rating is greater than 33.8 kA.According to the IEC, the nearest standard rating is 40 kA.

Rated short-circuit breaking current (cf. § 4.101 IEC 60 056)
The rated short-circuit breaking current is the highest value of current that the circuit breaker must be capable of breaking at its rated voltage.

c It is characterised by two values: v the rms. value of its periodic component, given by the term: "rated short-circuit breaking current" v the percentage of the aperiodic component corresponding to the circuit breaker's opening duration, to which we add a half-period of the rated frequency. The half-period corresponds to the minimum activation time of an overcurrent protection device, this being 10 ms at 50 Hz.

c According to IEC, the circuit breaker must break the rms. value of the periodic component of the short-circuit (= its rated breaking current) with the percentage of asymmetry defined by the graphs below.

Percentage of the aperiodic component (% DC) as a function of the time interval ()

% DC

100

90

80

70

4= 120 ms

60
(alternating time constant)

50

40

30

20

1= 45 ms

10

(standardised time constant)

 (ms)

0 10 20 30 40 50 60 70 80 90

t : circuit breaker opening duration (Top), increased by half a period at the power frequency (r)

c As standard the IEC defines MV equipment for a %DC of 30%, for a peak value of maximum current equal to 2.5 · Isc at 50 Hz or 2.6 · Isc at 60 Hz. In this case use the 1 graph.

48

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Medium voltage circuit breaker

I (A)
IMC

IAC IDC

c For low resistive circuits such as generator incomers, %DC can be higher, with a peak value of maximum current equal to 2.7 · Isc. In this case use the 4 graph. For all constants of between 1 and 4, use the equation:
-(Top + Tr) % DC = 100 · e 1, ..., 4

c Values of rated short-circuit breaking current: 6.3 - 8 - 10 - 12.5 - 16 20 - 25 - 31.5 - 40 - 50 - 100 kA.

c Short-circuit breaking tests must meet the five following test sequences:

Sequence

% Isym.

1

10

2

20

3

60

t (s)

4

100

5*

100

* for circuit breakers opening in less than 80 ms

% aperiodic
component %DC  20  20  20  20 according to equation

IMC

:

IAC

:

Idc

:

%DC

:

making current periodic component peak value (Isc peak) aperiodic component value % asymmetry or aperiodic component:

- (Top + Tr)

IDC

 (1, ..., 4)

· 100 = 100 · e

IAC

c Symmetric short-circuit current (in kA): Isym = IAC r
c Asymmetric short-circuit current (in kA):

Iasym2 = I2AC + I2DC

Iasym = Isym 1 + 2( %DC )2 100
Rated Transient Recovery Voltage (TRV) (cf. § 4.102 IEC 60 056)
This is the voltage that appears across the terminals of a circuit breaker pole after the current has been interrupted. The recovery voltage wave form varies according to the real circuit configuration. A circuit breaker must be able to break a given current for all recovery voltages whose value remains less than the rated TRV.
c First pole factor For three-phase circuits, the TRV refers to the pole that breaks the circuit initially, in other words the voltage across the terminals of the open pole. The ratio of this voltage to a simple voltage is called the first pole factor, it is equal to 1.5 for voltages up to 72.5 kV.

Schneider Electric

Merlin Gerin MV design guide

49

Switchgear definition

Medium voltage circuit breaker

U (kV) Uc

0 td
t3

t (µs)

X1

AB

X2

G U1

U2 G

UA - UB = U1 - (-U2) = U1 + U2 si U1 = U2 so UA - UB = 2U

c Value of rated TRV v the TRV is a function of the asymmetry, it is given for an asymmetry of 0%.

Rated voltage
(Ur in kV) 7.2 12 17.5 24 36

TRV value
(Uc in kV) 12.3 20.6 30 41 62

Time
(t3 in µs) 52 60 72 88 108

Delay
(td in µs) 8 9 11 13 16

Increase rate (Uc/td in kV/µs) 0.24 0.34 0.42 0.47 0.57

Uc = 1.4 · 1.5 · r · Ur = 1.715 Ur e

td = 0.15 t3
v a specified TRV is represented by a reference plot with two parameters and by a segment of straight line defining a time delay.

Td

:

t3

:

Uc

:

TRV increase rate:

time delay time defined to reach Uc peak TRV voltage in kV Uc/t3 in kV/µs

Rated out-of-phase breaking current (cf. § 4.106 IEC 60 056)
When a circuit breaker is open and the conductors are not synchronous, the voltage across the terminals can increase up the sum of voltages in the conductors (phase opposition).
c In practice, standards require the circuit breaker to break a current equal to 25% of the fault current across the terminals, at a voltage equal to twice the voltage relative to earth.
c If Ur is the rated circuit breaker voltage, the recovery voltage (TRV) at power frequency is equal to: v 2e Ur for networks with a neutral earthing arrangement v 2.5e Ur for other networks.
c Peak values for TRV for networks other than those with neutral earthing:

e Uc = 1.25 · 2.5 · · Ur
r

Rated voltage (Ur in kV) 7.2 12 17.5 24 36

TRV value (Uc in kV) 18.4 30.6 45 61 92

Time
(t3 in µs) 104 120 144 176 216

Rate of increase (Uc/td in kV/µs) 0.18 0.26 0.31 0.35 0.43

50

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

L GU

AB Ic C

X1 GU
C1 C2 C3 Schneider Electric

Medium voltage circuit breaker

Rated cable-charging breaking current (cf. § 4 .108 IEC 60 056)
The specification of a rated breaking current for a circuit breaker located at the head of no-load cables is not compulsory and is considered as not being necessary for voltages less than 24 kV.

c Normal rated breaking current values for a circuit breaker located at the head of no-load cables:

Rated voltage
(Ur in kV) 7.2 12 17.5 24 36

Rated breaking current for no-load cables (Ic in kA) 10 25 31.5 31.5 50

Rated line-charging breaking current (cf. § 4.107 IEC 60 056)
The specification of a rated breaking current for a circuit breaker switch situated at the head of no-load lines is limited to overhead, three-phased lines and to a rated voltage  72 kV.

Rated single capacitor bank breaking current (cf. § 4.109 IEC 60 056)
The specification of a breaking current for a circuit breaker switch located upstream of capacitors is not compulsory. Due to the presence of harmonics, the breaking current for capacitors is equal to 0.7 times the device's rated current.

Rated current (A) 400 630 1250 2500 3150

Breaking current for capacitors (A) 280 440 875 1750 2200

By definition

pu =Ur r e

c The normal value of over-voltage obtained is equal to 2.5 pu, this being: 2.5 · Ur r e

Rated back-to-back capacitor bank breaking current (cf. § 4.110 IEC 60 056)
The specification of a breaking current for multi-stage capacitor banks is not compulsory.
c If n is equal to the number of stages, then the over-voltage is equal to:

2n · pu with pu = Ur r

2n + 1

e

Merlin Gerin MV design guide

51

Switchgear definition

Medium voltage circuit breaker

U
Um Uc
Uf

Up Ud
t
Uif

52

Rated capacitor bank inrush making current (cf. § 4.111 IEC 60 056)
The rated closing current for capacitor banks is the peak current value that the circuit breaker must be capable of making at the rated voltage. The value of the circuit breaker's rated closing current must be greater than the making current for the capacitor bank. In service, the frequency of the pick-up current is normally in the region of 2 - 5 kHz.

Rated small inductive breaking current (cf. § 4.112 IEC 60 056)
The breaking of a low inductive current (several amperes to several tens of amperes) causes overvoltages. The type of circuit breaker will be chosen so that the overvoltages that appear do not damage the insulation of the current consumers (transformer, motors).

c The figure opposite shows the various voltages on the load side

Uf

:

Uc

:

Um

:

Uif

:

Up

:

Ud

:

instantaneous network voltage value network voltage at the moment of breaking extinction point overvoltage relative to earth maximum overvoltage relative to earth maximum peak-to-peak amplitude of the overvoltage due to restrike.

c Insulation level of motors
IEC 60 034 stipulates the insulation level of motors. Power frequency and impulse withstand testing is given in the table below (rated insulation levels for rotary sets).

Insulation Between turns

Test at 50 (60) Hz rms. value

Relative to earth

(2 Ur + 5) kV 2Ur + 1  2(2Ur + 1)  0 14 kV  28 kV  0

Impulse test
(4 Ur + 5) kV 4.9 pu + 5 = 31 kV at 6.6 kV (50% on the sample) increase time 0.5 µs (4 Ur + 5) kV 4.9 pu + 5 = 31 kV at 6.6 kV increase time 1.2 µs

1 kV/s

t

0 1 mn

Normal operating conditions (cf. IEC 60 694)
For all equipment functioning under other conditions than those described below, derating should be carried out (see derating chapter). Equipment is designed for normal operation under the following conditions:

c Temperature 0°C Instantaneous ambient minimal maximal average daily maximum value

Installation
Indoor -5°C +40°C 35°C

Outdoor -25°C +40°C 35°C

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Medium voltage circuit breaker

Rated voltage Ur (kV) 3.6 7.2
12
17.5
24
36

c Humidity Average relative humidity for a period 24 hours 1 month
c Altitude The altitude must not exceed 1 000 metres.

Indoor equipment
95% 90%

Electrical endurance
The electrical endurance requested by the recommendation is three breaking operations at Isc. Merlin Gerin circuit breakers are capable of breaking Isc at least 15 times.

Mechanical endurance
The mechanical endurance requested by the recommendation is 2 000 switching operations. Merlin Gerin circuit breakers guarantee 10 000 switching operations.

Co-ordination of rated values (cf. § IEC 60 056)

Rated short-circuit breaking current Isc (kV) 10 16 25 40 8 12.5 16 25 40 8 12.5 16 25 40 50 8 12.5 16 25 40 8 12.5 16 25 40 8 12.5 16 25 40

Rated current in continuous service

Ir (A) 400
630

400

400

630

630

630

400

400

630

630

630

400

630

630

630

400

630

630

630

630 630 630

1250 1250 1250

1600 1600

2500 2500

3150

1250 1250 1250 1250

1600 1600 1600

2500 2500

3150

1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250

1600 1600 1600 1600
1600
1600 1600

2500 2500 2500
2500
2500 2500

3150 3150
3150
3150

1250 1250 1250 1250

1600 1600 1600

2500 2500

3150

Schneider Electric

Merlin Gerin MV design guide

53

Switchgear definition

Current transformer

Please note! Never leave a CT in
an open circuit.

This is intended to provide a secondary circuit with a current proportional to the primary current.
Transformation ratio (Kn)
Kn = Ipr = N2 Isr N1
N.B.: current transformers must be in conformity with standard IEC 185 but can also be defined by standards BS 3938 and ANSI.
c It comprises one or several primary windings around one or several secondary windings each having their own magnetic circuit, and all being encapsulated in an insulating resin.
c It is dangerous to leave a CT in an open circuit because dangerous voltages for both people and equipment may appear across its terminals.
Primary circuit characteristics according to IEC standards
Rated frequency (fr)
A CT defined at 50 Hz can be installed on a 60 Hz network. Its precision is retained. The opposite is not true.

Rated primary circuit voltage (Upr)
c General case:
Rated CT voltage  rated installation voltage
The rated voltage sets the equipment insulation level (see "Introduction" chapter of this guide). Generally, we would choose the rated CT voltage based on the installation operating voltage U, according to the chart:

Core balance CT cable or busduct
(sheathed or not sheathed busduct)

U

3.3 5 5.5 6 6.6 10 11 13.8 15 20 22 30 33

Upr

7.2 kV

12 kV

insulator air
insulator

17.5 kV

24 kV

36 kV
c Special case: If the CT is a core balance CT installed on a busduct or on a cable. The dielectric insulation is provided by the cable or busducting insulation and the air located between them. The core balance CT is itself insulated.

54

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Current transformer

Example:
A thermal protection device for a motor has a setting range of between 0.6 and 1.2 · IrTC. In order to protect this motor, the required setting must correspond to the motor's rated current.
c If we suppose that Ir for the motor = 45 A, the required setting is therefore 45 A;
v if we use a 100/5 CT, the relay will never see 45 A because: 100 · 0.6 = 60 > 45 A.
v if on the other hand, we choose a CT 75/5, we will have:
0.6 < 45 < 1.2 75
and therefore we will be able to set our relay.This CT is therefore suitable.

Primary operating current (Ips)

An installation's primary operating current I (kA) (for a transformer feeder for example) is equal to the CT primary operating current (Ips) taking account of any possible derating.

c If:

S

:

U

:

P

:

Q

:

Ips

:

apparent power in kVA primary operating voltage in kV active power of the motor in kW reactive power of capacitors in kvars primary operating current in A

c We will have: v incomer cubicle

Ips = S e· U

v generator set incomer v transformer feeder

Ips = S e· U

v motor feeder

Ips = S e· U

Ips =

P

e · U · cos · 



:

motor efficiency

If you do not know the exact values of  and , you can take as an initial approximation: cos  = 0.8 ;  = 0.8.

v capacitor feeder 1.3 is a derating coefficient of 30% to take account of temperature rise due to capacitor harmonics.
Ips = 1.3 · Q e ·U
v bus sectioning The current Ips of the CT is the greatest value of current that can flow in the bus sectioning on a permanent basis.

Rated primary current (Ipr)
The rated current (Ipr) will always be greater than or equal to the operating current (I) for the installation.
c Standardised values: 10 -12.5 - 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 and their multiples and factors.
c For metering and usual current-based protection devices, the rated primary current must not exceed 1.5 times the operating current. In the case of protection, we have to check that the chosen rated current enables the relay setting threshold to be reached in the case of a fault.
N.B.: current transformers must be able to withstand 1.2 times the rated current on a constant basis and this as well must be in conformity with the standards.

Schneider Electric

Merlin Gerin MV design guide

55

Switchgear definition

Current transformer

In the case of an ambient temperature greater than 40°C for the CT, the CT's nominal current (Ipn) must be greater than Ips multiplied by the derating factor corresponding to the cubicle. As a general rule, the derating is of 1% Ipn per degree above 40°C. (See "Derating" chapter in this guide).

Example:
c Ssc = 250 MVA c U = 15 kV

Ith 1 s =

Ssc · 10 3 = 250 · 10 3 = 9 600 A U · e 15 · e

Rated thermal short-circuit current (Ith)
The rated thermal short-circuit current is generally the rms. value of the installation's maximum short-circuit current and the duration of this is generally taken to be equal to 1 s.
c Each CT must be able to withstand the short-circuit current which can flow through its primary circuit both thermally and dynamically until the fault is effectively broken.
c If Ssc is the network short-circuit power expressed in MVA, then:
Ith = Ssc U · e
c When the CT is installed in a fuse protected cubicle, the Ith to use is equal to 80 Ir.
c If 80 Ir > Ith 1 s for the disconnecting device, then Ith 1 s for the CT = Ith 1 s for the device.

Overcurrent coefficient (Ksi)
Knowing this allows us to know whether a CT will be easy to manufacture or otherwise.

c It is equal to:

Ksi = Ith 1 s Ipr

c The lower Ksi is, the easier the CT will be to manufacture.
A high Ksi leads to over-dimensioning of the primary winding's section. The number of primary turns will therefore be limited together with the induced electromotive force; the CT will be even more difficult to produce.

Order of magnitude ksi Ksi < 100 100 < Ksi < 300
100 < Ksi < 400 400 < Ksi < 500 Ksi > 500

Manufacture
standard sometimes difficult for certain secondary characteristics difficult limited to certain secondary characteristics very often impossible

A CT's secondary circuit must be adapted to constraints related to its use, either in metering or in protection applications.

56

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Current transformer

Example: c Cable section: c Cable length (feed/return): c Consumed power by the cabling:
Schneider Electric

Secondary circuit's characteristics according to IEC standards
Rated secondary current (Isr) 5 or 1 A?
c General case: v for local use Isr = 5 A v for remote use Isr = 1 A
c Special case: v for local use Isr = 1 A
N.B.: Using 5 A for a remote application is not forbidden but leads to an increase in transformer dimensions and cable section, (line loss: P = R I 2).
Accuracy class (cl)
c Metering: class 0.5 c Switchboard metering: class 1 c Overcurrent protection: class 10P sometimes 5P c Differential protection: class X c Zero-sequence protection: class 5P.

2.5 mm2 5.8 m 1 VA

Real power that the TC must provide in VA
This is the sum of the consumption of the cabling and that of each device connected to the TC secondary circuit.

c Consumption of copper cabling (line losses of the cabling), knowing that: P = R.I2 and R = .L/S then:
(VA) = k · L S

k = 0.44 :

k = 0.0176 :

L

:

S

:

if Isr = 5 A if Isr = 1 A length in metres of link conductors (feed/return) cabling section in mm2

c Consumption of metering or protection devices. Consumption of various devices are given in the manufacturer's technical data sheet.

Rated output
Take the standardised value immediately above the real power that the CT must provide.
c The standardised values of rated output are: 2.5 - 5 - 10 - 15 - 30 VA.

Safety factor (SF)
c Protection of metering devices in the case of a fault is defined by the safety factor SF. The value of SF will be chosen according to the current consumer's short-time withstand current: 5  SF  10. SF is the ratio between the limit of rated primary current (Ipl) and the rated primary current (Ipr).
SF = Ipl Ipr
c Ipl is the value of primary current for which the error in secondary current = 10 %.

Merlin Gerin MV design guide

57

Switchgear definition
58

Current transformer

c An ammeter is generally guaranteed to withstand a short-time current of 10 Ir, i.e. 50 A for a 5 A device. To be sure that this device will not be destoyed in the case of a primary fault, the current transformer must be saturated before 10 Ir in the secondary. A safety factory of 5 is suitable.
c In accordance with the standards, Schneider Electric CT's have a safety factor of 10. However, according to the current consumer characteristic a lower safety factor can be requested.

Accuracy limit factor (ALF)
In protection applications, we have two constraints: having an accuracy limit factor and an accuracy class suited to the application. We will determine the required ALF in the following manner:

Definite time overcurrent protection. c The relay will function perfectly if:

ALF real of CT > 2 · Ire Isr

Ire

:

Isr

:

relay threshold setting rated secondary current of the CT

c For a relay with two setting thresholds, we will use the highest threshold, v For a transformer feeder, we will generally have an instantaneous high threshold set at 14 Ir max., giving the real ALF required > 28 v for a motor feeder, we will generally have a high threshold set to 8 Ir max., giving a real ALF required > 16.

Inverse definite time overcurrent protection
c In all cases, refer to the relay manufacturer's technical datasheet. For these protection devices, the CT must guarantee accuracy across the whole trip curve for the relay up to 10 times the setting current.

ALF real > 20 · Ire
c Special cases: v if the maximum short-circuit current is greater than or equal to 10 Ire:

ALF

real

>

20

·

Ire Isr

Ire

:

relay setting threshold

v if the maximum short-circuit current is less than 10 Ire:

ALF real > 2 ·

Isc secondary Isr

v if the protection device has an instantaneous high threshold that is used, (never true for feeders to other switchboards or for incomers):

ALF real > 2 · Ir2 Isr

Ir2

:

instantaneous high setting threshold for the module

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

relay

CT

G

CT

relay

CT

M

CT

Schneider Electric

Current transformer

Differential protection
Many manufacturers of differential protection relays recommend class X CT's.

c Class X is often requested in the form of: Vk  a . If (Rct + Rb + Rr)
The exact equation is given by the relay manufacturer.

Values characterising the CT

Vk

:

a

:

Knee-point voltage in volts asymmetry coefficient

Rct

:

max. resistance in the secondary winding in Ohms

Rb

:

Rr

:

loop resistance (feed/return line) in Ohms resistance of relays not located in the differential part

of the circuit in Ohms

If

:

maximum fault current seen by the CT

in the secondary circuit for a fault outside of the zone

to be protected

If = Isc Kn

Isc

:

Kn

:

primary short-circuit current CT transformation ratio

What values should If be given to determine Vk?
c The short-circuit current is chosen as a function of the application: v generator set differential v motor differential v transformer differential v busbar differential.

c For a generator set differential: v if Isc is known: Isc short-circuit current for the generator set on its own
If = Isc Kn
v if the Ir gen is known: we will take
If = 7 · Ir gen Kn
v if the Ir gen is unknown: we will take If = 7 · Isr (CT) Isr(CT) = 1 or 5 A

c For motor differential: v if the start-up current is known: we will take
Isc = I start-up

If

=

Isc Kn

v if the Ir motor is known: we will take

If =

7 · Ir Kn

v if the Ir motor is not known: we will take If = 7 · Isr (CT)

Reminder

Ir

:

Isr(TC) = 1 or 5 A rated current

Merlin Gerin MV design guide

59

Switchgear definition
CT relay
CT

Current transformer
c For a transformer differential The Isc to take is that flowing through the CT's for a current consumer side fault. In all cases, the fault current value If is less than 20 Isr(CT). v if we do not know the exact value, we will take:
If = 20 Isr(CT) c For busbar differential v the Isc to take is the switchboard Ith
If = Ith Kn
c For a line differential The Isc to take is the Isc calculated at the other end of the line, therefore limited by the cable impedance. If the impedance of the cable is not known, we will take the switchboard Ith.

60

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Voltage transformer

We can leave a voltage transformer in an open circuit without any danger
but it must never be short-circuited.

The voltage transformer is intended to provide the secondary circuit with a secondary voltage that is proportional to that applied to the primary circuit.
N.B.: IEC standard 60 186 defines the conditions which voltage transformers must meet.
It comprises a primary winding, a magnetic core, one or several secondary windings, all of which is encapsulated in an insulating resin.

Characteristics

The rated voltage factor (KT)
The rated voltage factor is the factor by which the rated primary voltage has to be multiplied in order to determine the maximum voltage for which the transformer must comply with the specified temperature rise and accuracy recommendations. According to the network's earthing arrangement, the voltage transformer must be able to withstand this maximum voltage for the time that is required to eliminate the fault.

Normal values of the rated voltage factor

Rated voltage

Rated

Primary winding connection mode

factor 1.2

duration continuous

and network earthing arrangement phase to phase on any network neutral point to earth for star connected transformers in any network

1.2

continuous

phase to earth in an earthed

neutral network

1.5

30 s

1.2

continuous

phase to earth in a network

without an earthed neutral with

1.9

30 s

automatic elimination of earthing faults

1.2

continuous

phase to earth in an isolated neutral network

without automatic elimination of earthing faults,

1.9

8 h

or in a compensated network with an extinction coil

without automatic elimination of the earthing fault

N.B.: lower rated durations are possible when agreed to by the manufacturer and the user.

Generally, voltage transformer manufacturers comply with the following values: VT phase/earth 1.9 for 8 h and VT phase/phase 1.2 continuous.

Rated primary voltage (Upr)
c According to their design, voltage transformers will be connected:
v either phase to earth

v or phase to phase

3000 V / 100 V

e

e

Upr = U e

3000 V / 100 V

Upr = U

Schneider Electric

Merlin Gerin MV design guide

61

Switchgear definition

Voltage transformer

Rated secondary voltage (Usr)
c For phase to phase VT the rated secondary voltage is 100 or 110 V.
c For single phase transformers intended to be connected in a phase to earth arrangement, the rated secondary voltage must be divided by e.
E.g.: 100V e
Rated output
Expressed in VA, this is the apparent power that a voltage transformer can provide the secondary circuit when connected at its rated primary voltage and connected to the nominal load. It must not introduce any error exceeding the values guaranteed by the accuracy class. (S = eUI in three-phase circuits)
c Standardised values are: 10 - 15 - 25 - 30 - 50 - 75 - 100 - 150 - 200 - 300 - 400 - 500 VA.

Accuracy class
3P 6P

Accuracy class
This defines the limits of errors guaranteed in terms of transformation ratio and phase under the specified conditions of both power and voltage.

Measurement according to IEC 60 186 Classes 0.5 and 1 are suitable for most cases, class 3 is very little used.

Application not used industrially precise metering everyday metering statistical and/or instrument metering metering not requiring great accuracy

Accuracy class 0.1 0.2 0.5 1 3

Protection according to IEC 60 186 Classes 3P and 6P exist but in practice only class 3P is used.

c The accuracy class is guaranteed for values: v of voltage of between 5% of the primary voltage and the maximum value of this voltage which is the product of the primary voltage and the rated voltage factor (kT x Upr) v for a secondary load of between 25% and 100% of the rated output with a power factor of 0.8 inductive.

Voltage error as ± %

between 5% Upr

between 2%

and kT · Upr 3

and 5% Upr 6

6

12

Phase shift in minutes

between 5% Upr

between 2%

and kT · Upr 120

and 5% Upr 240

24

480

Upr = rated primary voltage kT = voltage factor phase shift = see explanation next page

62

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Voltage transformer
Transformation ratio (Kn)
Kn = Upr = N1 for a TT Usr N2
Voltage ratio error
This is the error that the transformer introduces into the voltage measurement.
voltage error (%) = (kn Usr - Upr)·100 Upr
Kn = transformation ratio
Phase error or phase-shift error
This is the phase difference between the primary voltage Upr and the secondary voltage Usr. IT is expressed in minutes of angle.
The thermal power limit or rated continuous power
This is the apparent power that the transformer can supply in steady state at its rated secondary voltage without exceeding the temperature rise limits set by the standards.

Schneider Electric

Merlin Gerin MV design guide

63

Switchgear definition

Derating

Example of application:
Can equipment with a rated voltage of 24 kV be installed at 2500 metres? The impulse withstand voltage required is 125 kV. The power frequency withstand 50 Hz is 50 kV. 1 mn.
c For 2500 m: v k is equal to 0.85 v the impulse withstand must be 125/0.85 = 147.05 kV v the power frequency withstand 50 Hz must be 50/0.85 = 58.8 kV
c No, the equipment that must be installed is: v rated voltage = 36 kV v impulse withstand = 170 kV v withstand at 50 Hz = 70 kV
N.B.: if you do not want to supply 36 kV equipment, we must have the appropriate test certificates proving that our equipment complies with the request.

Introduction
The various standards or recommendations impose validity limits on device characteristics. Normal conditions of use are described in the "Medium voltage circuit breaker" chapter. Beyond these limits, it is necessary to reduce certain values, in other words to derate the device.
c Derating must be considered: v in terms of the insulation level, for altitudes of over 1 000 metres v in terms of the rated current, when the ambient temperature exceeds 40°C and for a protection index of over IP3X, (see chapter on "Protection indices"). These different types of derating can be accumulated if necessary.
N.B.: there are no standards specifically dealing with derating. However, table V § 442 of IEC 60 694 deals with temperature rises and gives limit temperature values not to be exceeded according to the type of device, the materials and the dielectric used.

Insulation derating according to altitude
Standards give a derating for all equipment installed at an altitude greater than 1 000 metres. As a general rule, we have to derate by 1.25 % U peak every 100 metres above 1 000 metres. This applies for the lightning impulse withstand voltage and the power frequency withstand voltage 50 Hz - 1 mn. Altitude has no effect on the dielectric withstand of circuit breakers in SF6 or vacuum, because they are within a sealed enclosure. Derating, however, must be taken account of when the circuit breaker is installed in cubicles. In this case, insulation is in air.
c Merlin Gerin uses correction coefficients: v for circuit breakers outside of a cubicle, use the graph below v for circuit breakers in a cubicle, refer to the cubicle selection guide (derating depends on the cubicle design).
Exception of the Mexican market: derating starts from zero metres (cf. dotted line on the graph below).

Correctilon coefficient k 1

0.9

0.8

0.7

0.6

0.5 0

1000

2000

3000

4000

altitude in m 5000

64

Merlin Gerin MV design guide

Schneider Electric

Switchgear definition

Derating
Derating of the rated current according to temperature
As a general rule, derating is of 1 % Ir per degree above 40°C. IEC standard 60 694 § 442 table 5 defines the maximum permissible temperature rise for each device, material and dielectric with a reference ambient temperature of 40°C.
c In fact, this temperature rise depends on three parameters: v the rated current v the ambient temperature v the cubicle type and its IP (protection index).
Derating will be carried out according to the cubicle selection tables, because conductors outside of the circuit breakers act to radiate and dissipate calories.

Schneider Electric

Merlin Gerin MV design guide

65

Units of measure

Names and symbols of SI units of measure

Magnitude
Basic units length mass time electrical current thermodynamic temperature2 quantity of material light intensity
Additional units angle (plane angle) solid angle

Basic units
Symbol of the magnitude1 Unit

l, (L) m t I T n I, (Iv)

metre kilogramme second ampere kelvin mole candela

, ,  ... , ()

radian steradian

Symbol of the unit Dimension

m

L

kg

M

s

T

A

I

K



mol

N

cd

J

rad

N/A

sr

N/A

Common magnitudes and units

Name

Symbol

Magnitude: space and time

length

l, (L)

area
volume plane angle

A, (S)
V , ,  ...

solid angle time

, () t

speed

v

rad/s

acceleration

a

angular speed



angular acceleration



Magnitude: mass

mass

m

linear mass mass per surface area mass per volume volume per mass concentration

1 A' (s)  v B

density

d

Magnitude: periodic phenomena

period

T

frequency

f

phase shift



wavelength



power level

Lp

Dimension SI Unit: name (symbol)

Comments and other units

L

metre (m)

L2

metre squared (m2)

L3

metre cubed (m3)

N/A

radian (rad)

N/A

steradian (sr)

T

second (s)

L T-1

metre per second (m/s)

centimetre (cm): 1 cm = 10-2 m (microns must no monger be used, instead the micrometre (µm)) are (a): 1 a = 102 m2 hectare (ha): 1 ha = 104 m2 (agricult. meas.)
gradian (gr): 1 gr = 2 rad/400 revolution (rev): 1 tr = 2 rad degree(°):1°= 2 rad/360 = 0.017 453 3 rad minute ('): 1' = 2 rad/21 600 = 2,908 882 · 10-4 rad second ("): 1" = 2 rad/1 296 000 = 4.848 137 · 10-6 rad
minute (mn) hour (h) day (d) revolutions per second (rev/s): 1 tr/s = 2

L T-2

metre per second squared

acceleration due to gravity:

(m/s2)

g = 9.80665 m/s2

T-1

radian per second (rad/s)

T -2

radian per second squared (rad/s2)

M
L-1 M L-2 M L-3 M L3 M-1 M L-3
N/A

kilogramme (kg)

gramme (g) : 1 g = 10-3 kg ton (t) : 1 t = 103 kg

kilogramme per metre (kg/m)

kilogramme per metre squared (kg/m2)

kilogramme per metre cubed (kg/m3)

metre cubed per kilogramme (m3/kg)

kilogramme per metre cubed (kg/m3)

concentration by mass of component B (according to NF X 02-208)

N/A

T

second (s)

T-1

hertz (Hz)

N/A

radian (rad)

L

metre (m)

N/A

decibel (dB)

1 Hz = 1s-1, f = 1/T
use of the angström (10-10 m) is forbidden. Use of a factor of nanometre (109 m) is recommended  = c/f = cT (c = celerity of light)

e1 the symbol in brackets can also be used 2 the temperature Celsius t is related to the themrodynamic temperature T by the relationship: t = T - 273.15 K

Schneider Electric

Merlin Gerin MV design Guide

67

Units of measure

Names and symbols of SI units of measure

Name

Symbol

Magnitude: mechanical force weight moment of the force

F G, (P, W) M, T

surface tension

, 

work

W

energy

E

power

P

pressure

, 

p

dynamic viscosity

, µ

kinetic viscosity



quantity of movement

p

Magnitude: electricity

current

I

electrical charge

Q

electrical potential

V

electrical field

E

electrical resistance

R

electrical conductivity

G

electrical capacitance

C

electrical inductance

L

Magnitude: electricity, magnetism

magnetic induction

B

magnetic induction flux magnetisation

 Hi, M

magnetic field

H

magneto-motive force

F, Fm

resistivity



conductivity



permittivity



active

P

apparent power

S

reactive power

Q

Magnitude: thermal

thermodynamic

T

temperature

temperature Celsius

t, 

energy

E

heat capacity

C

entropy

S

specific heat

c

capacity

thermal conductivity



quantity of heat

Q

thermal flux



thermal power

P

coefficient of thermal

hr

radiation

Dimension SI Unit: name (symbol)

Comments and other units

L M T-2
L2 M T-2
M T-2 L2 M T-2 L2 M T-2
L2 M T-3 L-1 M T-2
L-1 M T-1 L2 T-1 L M T-1

Newton

1 N = 1 m.kg/s2

Newton-metre (N.m)
Newton per metre (N/m) Joule (J) Joule (J)
Watt (W) Pascal (Pa)
Pascal-second (Pa.s) metre squared per second (m2/s) kilogramme-metre per second (kg.m/s)

N.m and not m.N to avoid any confusion with the millinewton 1 N/m = 1 J/m2
1 J : 1 N.m = 1 W.s Watthour (Wh) : 1 Wh = 3.6 · 103 J (used in determining electrical consumption)
1 W = 1 J/s 1 Pa = 1 N/m2 (for the pressure in fluids we use bars (bar): 1 bar = 105 Pa) 1 P = 10-1 Pa.s (P = poise, CGS unit) 1 St = 10-4 m2/s (St = stokes, CGS unit)
p = mv

I
TI L2M T-3 I-1 L M T-3 I-1 L2 M T-3 I-2 L-2 M-1 T3 I2 L-2 M-1 T4 I2 L2 M T-2 I-2

Ampere (A) Coulomb (C) Volt (V) Volt per metre (V/m) Ohm () Siemens (S) Farad (F) Henry (H)

1 C = 1 A.s 1 V = 1 W/A
1  = 1 V/A 1 S = 1 A/V = 1-1 1 F = 1 C/V 1 H = 1 Wb/A

M T -2 I-1 L2 M T-2 I-1 L-1 I L-1 I
I L3 M T-3 I-2 L-3 M-1 T3 I2 L-3 M-1 T4 I2 L2 M T-3 L2 M T-3 L2 M T-3

Tesla (T) Weber (Wb) Ampere per metre (A/m) Ampere per metre (A/m) Ampere (A) Ohm-metre (.m) Siemens per metre (S/m) Farad per metre (F/m) Watt (W) Voltampere (VA) var (var)

1 T = 1 Wb/m2 1 Wb = 1 V.s
1 µ.cm2/cm = 10-8 .m
1 W = 1 J/s 1 var = 1 W


 L2 M T-2 L2 M T-2 -1 L2 M T-2 -1 L2 T-2 -1
L M T-3 -1 L2 M T-2 L2 M T-3 L2 M T-3 M T-3 -1

Kelvin (K)
degree Celsius (°C) Joule (J) Joule per Kelvin (J/K) Joule per Kelvin (J/K) Watt per kilogramme-Kelvin (J/(kg.K)) Watt per metre-Kelvin (W/(m.K)) Joule (J) Watt (W) Watt (W) Watt per metre squared-Kelvin (W/(m2.K))

Kelvin and not degree Kelvin or °Kelvin t = T - 273.15 K
1 W = 1 J/s

68

Merlin Gerin MV design guide

Schneider Electric

Units of measure

Names and symbols of SI units of measure

Correspondence between Imperial units and international system units (SI)

Magnitude acceleration calory capacity heat capacity magnetic field thermal conductivity energy energy (couple) thermal flux
force length
mass
linear mass
mass per surface area
mass per volume moment of inertia pressure pressure - strain
calorific power surface area temperature
viscosity
volume

Unit foot per second squared British thermal unit per pound British thermal unit per cubit foot.degree Fahrenheit British thermal unit per (pound.degree Fahrenheit) oersted British thermal unit per square foot.hour.degree Fahrenheit British thermal unit pound force-foot pound force-inch British thermal unit per square foot.hour British thermal unit per second pound-force foot inch (1) mile (UK) knot yard (2) once (ounce) pound (livre) pound per foot pound per inch pound per square foot pound per square inch pound per cubic foot pound per cubic inch pound square foot foot of water inch of water pound force per square foot pound force per square inch (3) British thermal unit per hour square foot square inch degree Fahrenheit (4) degree Rankine (5) pound force-second per square foot pound per foot-second cubic foot cubic inch fluid ounce (UK) fluid ounce (US) gallon (UK) gallon (US)

Symbol ft/s2 Btu/Ib Btu/ft3.°F Btu/Ib°F Oe Btu/ft2.h.°F Btu Ibf/ft Ibf.in Btu/ft2.h Btu/s Ibf ft, ' in, " mile yd oz Ib Ib/ft Ib/in Ib/ft2 Ib/in2 Ib/ft3 Ib/in3 Ib.ft2 ft H2O in H2O Ibf/ft2 Ibf/in2 (psi) Btu/h sq.ft, ft2 sq.in, in2 °F °R Ibf.s/ft2 Ib/ft.s cu.ft cu.in, in3 fl oz (UK) fl oz (US) gal (UK) gal (US)

Conversion 1 ft/s2 = 0.304 8 m/s2 1 Btu/Ib = 2.326 · 103 J/kg 1 Btu/ft3.°F = 67.066 1 · 103 J/m3.°C 1 Btu/Ib.°F = 4.186 8 · 103 J(Kg.°C) 1 Oe = 79.577 47 A/m 1 Btu/ft2.h.°F = 5.678 26 W/(m2.°C) 1 Btu = 1.055 056 · 103 J 1 Ibf.ft = 1.355 818 J 1 Ibf.in = 0.112 985 J 1 Btu/ft2.h = 3.154 6 W/m2 1 Btu/s = 1.055 06 · 103 W 1 Ibf = 4.448 222 N 1 ft = 0.304 8 m 1 in = 25.4 mm 1 mile = 1.609 344 km 1 852 m 1 yd = 0.914 4 m 1 oz = 28.349 5 g (6) 1 Ib = 0.453 592 37 kg 1 Ib/ft = 1.488 16 kg/m 1 Ib/in = 17.858 kg/m 1 Ib/ft2 = 4.882 43 kg/m2 1 Ib/in2 = 703,069 6 kg/m2 1 Ib/ft3 = 16.018 46 kg/m3 1 Ib/in3 = 27.679 9 · 103 kg/m3 1 Ib.ft2 = 42.140 g.m2 1 ft H2O = 2.989 07 · 103 Pa 1 in H2O = 2,490 89 · 102 Pa 1 Ibf/ft2 = 47.880 26 Pa 1 Ibf/in2 = 6.894 76 · 103 Pa 1 Btu/h = 0.293 071 W 1 sq.ft = 9.290 3 · 10-2 m2 1 sq.in = 6.451 6 · 10-4 m2 TK = 5/9 (q °F + 459.67) TK = 5/9 q °R 1 Ibf.s/ft2 = 47.880 26 Pa.s 1 Ib/ft.s = 1.488 164 Pa.s 1 cu.ft = 1 ft3 = 28.316 dm3 1 in3 = 1.638 71 · 10-5 m3 fl oz (UK) = 28.413 0 cm3 fl oz (US) = 29.573 5 cm3 1 gaz (UK) = 4.546 09 dm3 1 gaz (US) = 3.785 41 dm3

(1) 12 in = 1 ft (2) 1 yd = 36 in = 3 ft (3) Or p.s.i.: pound force per square inch (4) T K = temperature kelvin with q°C = 5/9 (q°F - 32) (5) °R = 5/9 °K (6) Apart from mass of precious metals (silver, gold, for example) where the carat is used (1 carat = 3.110 35 10-2 kg)

Schneider Electric

Merlin Gerin MV design guide

69

Standards

The standards mentioned in this document

Where can you order IEC publications?
Central Offices of the International Electrotechnical Commission
1, rue de Varembé Geneva - Switzerland.
The documentation department (Factory A2) at Merlin Gerin can provide you with information on the standards.

c International Electrotechnical Vocabulary
c High voltage alternating current circuit breakers
c Current transformers
c Voltage transformers
c Alternating current disconnectors and earthing disconnectors
c High voltage switches
c Metal-enclosed switchgear for alternating current at rated voltage of over 1 kV and less than or equal to 72.5 kV
c High-voltage alternating current combined fuse-switches and combined fuse-circuit breakers
c High-voltage alternating current contactors
c Specifications common to highvoltage switchgear standards
c Calculation rules in industrial installations
c Derating

IEC 60 050 IEC 60 056 IEC 60 185 IEC 60 186 IEC 60 129 IEC 60 265
IEC 60 298
IEC 60 420 IEC 60 470 IEC 60 694 IEC 60 909 ANSI C37 04

Schneider Electric

Merlin Gerin MV Design Guide

71

Standards

IEC - ANSI comparison

The following comparison is based on
different circuit breaker characteristics.

Overview of the main differences

Theme

ANSI

IEC

asymmetrical breaking

50%

30%

capacity on faults

with current

without derating

across the terminals

derating

insulation level:

imposes chopped waves

impulse wave

for outdoor equipment

115% Uw/3 s 129% Uw/2 s

short-time withstand current peak value

2.7 Isc

2.5·Isc at 50 Hz 2.6·Isc at 60 Hz 2.7·Isc for special cases

Transient Recovery voltage(1)

around twice as severe

electrical endurance

4 times K.S.Isc

3 times Isc

mechanical endurance

1 500 to 10 000

2 000

according to Ua and Isc

motor overvoltages

no text

standard test circuit

(1) the ANSI peak voltage is 10% greater than the voltage defined by the IEC. The E2/t2 slope is 50% greater than the Uc/t3 slope. However, the largest part of the graph is the initial part where the SF6 reconstitutes itself. The two standards easily allow the SF6 to reconstitute itself.

Rated voltages

According to IEC c Standardised values for Ur (kV): 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV
According to ANSI c The ANSI standard defines a class and a voltage range factor K which defines a range of rated voltages at constant power.

Standardised values for Ur (kV)

Indoor equipment

class (kV) 4.16

Umax (kV) 4.76

Umin (kV) 3.85

K 1.24

7.2

8.25

6.6

1.25

13.8

15

11.5

1.3

38

38

23

1.65

Outdoor equipment

15.5

1

25

1

38

1

Upeak (%) 100 90
50
1.2 µs
10
50 µs
Standardised wave 1.2/50 µs

t (µs)

Rated installation level

According to IEC Rated voltage (kV)
7.2 12 17.5 24 36

Rated lightning withstand voltage (kV) 60 75 95 125 170

Rated power frequency withstand voltage 50 Hz 1 mm (kV) 20 28 38 50 70

72

Merlin Gerin MV Design Guide

Schneider Electric

Standards

Upeak (%)
100 90 70

50 10
tc

t (µs)

Onde coupée suivant ANSI pour le matériel d'extérieur

IEC - ANSI comparison

According to ANSI

Rated

Rated lightning

voltage

withstand voltage

(kV)

(kV)

Indoor equipment

4.16

60

7.2

95

13.8

95

38

150

Outdoor equipment

15.5

110

25.8

125

150

38

150

200

N.B. c BIL: Basic Insulation Level The outdoor equipment is tested with chopped waves.
c The impulse withstand is equal to: 1.29 BIL for a duration of tc = 2 µs 1.15 BIL for a duration tc = 3 µs

Rated power frequency withstand voltage 50 Hz 1 mm (kV)
19 36 36 80
50 60
80

Rated normal current
According to IEC c Values of rated current: 400 - 630 - 1250 - 1600 - 2500 - 3150 A According to ANSI c Values of rated current: 1200 - 2000 - 3000 A

Short-time withstand current

According to IEC
c Values of short-circuit rated breaking capacity: 6.3 - 8 - 10 - 12.5 - 16 - 20 - 25 - 31.5 - 40 - 50 - 63 kA

According to ANSI c Values of short-circuit rated breaking capacity: v indoor equipment: 12.5 - 20 - 25 - 31.5 - 40 kA v outdoor equipment:

Class (MVA)
250 350 500 750 1000 1500 2750

Breaking capacity (kA)

I at Umax 29

KI at Umin 36

41

49

18

23

28

36

37

46

21

35

40

40

Schneider Electric

Merlin Gerin MV Design Guide

73

Standards
74

IEC - ANSI comparison

Peak value of short-time current and closing capacity
According to IEC c The peak value of short-time withstand current is equal to: v 2.5·Isc at 50 Hz v 2.6·Isc at 60 Hz v 2.7·Isc for special cases.
According to ANSI c The peak value of short-time withstand current is equal to: v 2.7 K Isc at peak value v 1.6 K Isc at rms. value. (K : voltage factor)

Rated short-circuit duration
According to IEC c The rated short-circuit duration is equal to 1 or 3 seconds.
According to ANSI c The rated short-circuit duration is equal to 3 seconds.

Rated supply voltage for closing and opening devices and auxiliary circuits

According to IEC c Supply voltage values for auxiliary circuits: v for direct current (dc): 24 - 48 - 60 - 110 or 125 - 220 or 250 volts v for alternating current (ac): 120 - 220 - 230 - 240 volts.

c Operating voltages must fall within the following ranges: v Motor and closing release units: -15% to +10% of Ur in dc et ac
v opening release units: -15% to +10% of Ur in ac; -30% to +10% of Ur in dc
v undervoltage opening release units

the release unit gives the command and forbids closing

0 %

35 %

the release unit

must not have

an action

U

70 %

100 %

(at 85%, the release unit must enable the device to close)

According to ANSI c Supply voltage values for auxiliary circuits: v for direct current (dc): 24 - 48 - 125 - 250 volts. v for alternating (ac): 120 - 240 volts

Merlin Gerin MV Design Guide

Schneider Electric

Standards
Schneider Electric

IEC - ANSI comparison

c Operating voltage must fall within the following ranges:

Voltage Motor and closing release units 48 Vsc 125 Vsc 250 Vsc 120 Vac 240 Vac

Voltage range (V)
36 to 56 90 to 140 180 to 280 104 to 127 208 to 254

Opening release units 24 Vsc 48 Vsc 125 Vsc 250 Vsc 120 Vac 240 Vac

14 to 28 28 to 56 70 to 140 140 to 220 104 to 127 208 to 254

Rated frequency
According to IEC c Rated frequency: 50 Hz. According to ANSI c Rated frequency: 60 Hz.

Short-circuit breaking capacity
at the rated operating sequence
c ANSI specifies 50% asymmetry and IEC 30%. In 95% of applications, 30% is sufficient. When 30% is too low, there are specific cases (proximity of generators) for which the asymmetry may be greater than 50%.
c For both standard systems, the designer has to check the circuit breaker breaking capacity. The difference is not important because without taking account of the asymmetry factor "S", it is equal to 10%.

ANSI: Iasym = Isym (1 + 2 A2) = 1.22 Isym (A = 50%) IEC: Iasym = Isym (1 + 2 A2) = 1.08 Isym (A = 30%)

According to IEC

c Short-circuit breaking tests must meet the following 5 test sequences:

Sequence n°

% Isym

% aperiodic component

1

10

 20

2

20

 20

3

60

 20

4

100

 20

5*

100

30

* for circuit breakers opening at least 80 ms

Merlin Gerin MV Design Guide

75

Standards

IEC - ANSI comparison

According to ANSI
c The circuit breaker must be able to break:
v the rated short circuit current at the rated maximum voltage v K times the rated short-circuit current (maxi symmetrical interrupting capability with K: voltage range factor) at the operating voltage (maximum voltage/K) v between the two currents obtained by the equation:

maxi symetrical current rated maxi voltage

=

= K

rated short-circuit current

rated voltage

We therefore have a constant breaking power (in MVA) over a given voltage range. Moreover, the asymmetrical current will be a function of the following table taking S = 1.1 for Merlin Gerin circuit breakers.

1.8 ratio S

1.7

Asymmetrical interrupting capability = S x symetrical interrupting capability.

1.6

Both at specified operating voltage

1.5

1.4

1.3

Symetrical interrupting capability at

1.2

specified operating voltage = 1.0

1.1

1

0 0.5 1 0 0.006 0.017

2 0.033

3 0.050

4 0.067

cycles seconds

Example:

c Isc = 40 kA c % asymmetry = 50% c Iasym = 1.1 · 40 = 44 kA

c Isym =

44

= 44 = 36 kA

1 + 2(50%)2 1,22

Sequence 6 will therefore be tested at 36 kA + 50% asymmetry, this being 44 kA of total current.

c Rated short-circuit breaking capacity (kA)

Sequence n°
1
2

current broken 10 30

% aperiodic component 50 - 100 < 20

3

60

50 - 100

4

100

< 20

5

KI to V/K

< 20

6

SI to V

50 - 100

7

KSI to V/K

50 - 100

8

electrical endurance

9/10

reclosing cycle at ASI and AKSI

11

C - 2 s - O at KI

12 13/14

rated Isc duration = KI for 3 s single phase testing at KI and KSI (0.58 V)

Short-circuit breaking testing must comply with the

14 test sequences above, with:

I

:

symmetrical breaking capacity at maximum voltage

R

:

reclosing cycle coefficient

(Reclosing factor)

K

:

voltage range factor: K = Vmax Vmin

S

:

asymmetrical factor: Iasym = 1.1 Isym
for Merlin Gerin circuit breakers

V

:

maximum rated voltage

76

Merlin Gerin MV Design Guide

Schneider Electric

Standards

IEC - ANSI comparison

Maximum rated voltage Umax (kV) 4.76 8.25 15
15.5
25.8 38

Rated voltage Ur (kV) 3.6
7.2
12
17.5
24
36
Rated short-circuit breaking current at Umax Isc (kA) 18 29 41 7 17 33 9.3 9.8 18 19 28 37 8.9 18 35 56 5.4 11 22 36

Coordination of rated values

According to IEC
Rated short-circuit breaking current
Isc (kA) 10 16 25 40 8 12.5 16 25 40 8 12.5 16 25 40 50 8 12.5 16 25 40 8 12.5 16 25 40 8 12.5 16 25 40

Rated operating current

Ir (A) 400
630

400

400

630

630

630

400

400

630

630

630

400

630

630

630

400

630

630

630

630 630 630

1250 1250 1250

1600 1600

1250 1250 1250 1250

1600 1600 1600

1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250

1600 1600 1600 1600
1600
1600 1600

1250 1250 1250 1250

1600 1600 1600

According to ANSI

Minimum

Rated

rated voltage

short-circuit breaking current at Umin

(kV)

Isc (kA)

3.5

24

3.85

36

4

49

2.3

25

4.6

30

6.6

41

6.6

21

4

37

11.5

23

6.6

43

11.5

36

11.5

48

5.8

24

12

23

12

45

12

73

12

12

12

24

23

36

24

57

Rated operating current

Ir (A) 600
600 600

1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
1200 1200
1200 1200 1200

2000 2000 2000
2000 2000 2000
2000

2500 2500 2500 2500 2500 2500 2500
2500 2500 2500 2500 2500
3000
3000 3000 3000

3150 3150 3150 3150 3150 3150 3150
4000

Schneider Electric

Merlin Gerin MV Design Guide

77

Standards
78

IEC- ANSI comparison

Derating

According to IEC c Refer to "Switchgear definition/Derating" chapter.
According to ANSI c The ANSI standard C37 04 gives for altitudes greater than 1 000 metres: v a correction factor for the applicable voltage on the rated insulation level and on the rated maximum voltage, v a correction factor for the rated operating current. The table of correction factors according to altitude (Altitude Corrections Factors: ACF).

Altitude

ACF for:

(ft)

(m)

voltage

continous current

3 300

1 000

1.00

1.00

5 000

1 500

0.95

0.99

10 000

3 000

0.8

0.96

N.B.: "sealed system" type circuit breakers, it is not necessairy to apply the voltage ACF on the maximum rated voltage

Electrical endurance
Merlin Gerin circuit breakers can withstand Isc at least 15 times. IEC and ANSI standards impose values well below this because they take account of oil breaking circuit breakers. These values are not very high and should the customer request it, we must provide those for the device being considered.

According to IEC c The electrical endurance is equal to 3 times Isc.

According to ANSI

c The electrical endurance is equal to 4 times K.S.Isc.

Isc

:

S

:

K

:

symmetrical breaking capacity at maximum voltage asymmetrical factor voltage range factor

Mechanical endurance
According to IEC c Mechanical endurance is of 2 000 switching cycles.
According to ANSI c Mechanical endurance is of between 1 500 and 10 000 switching cycles according to the voltage and the breaking capacity.

Construction
According to IEC c The IEC does not impose any particular constraints, however, the manufacturer has responsibility of determining what is required in terms of materials (thicknesses, etc) to meet performance requirements in terms of strength.
According to ANSI c ANSI imposes a thickness of 3 mm for sheet metal.

Merlin Gerin MV Design Guide

Schneider Electric

Standards
Equipment is designed to operate under the following normal conditions

IEC - ANSI comparison

Normal operating conditions

Temperature

Standards

0°C

Installation

ambient instantaneous

indoor

outdoor

IEC

minimal

- 5°C

- 25°C

maximal

+ 40°C

+ 40°C

maximum average daily value

35°C

35°C

ANSI

minimal

- 30°C

maximal

+ 40°C

N.B.: For all equipment operating under conditions other than those described above, derating must be provided (see derating chapter).

Altitude
According to IEC c The altitude must not exceed 1 000 metres, otherwise the equipment should be derated.
According to ANSI c The altitude must not exceed 3 300 feet (1 000 metres), otherwise the equipment should be derated.

Humidity
According to IEC Average relative humidity value over a period
24 hours 1 month
According to ANSI c No specific constraints.

Indoor equipment
95 % 90 %

Schneider Electric

Merlin Gerin MV Design Guide

79

References

Reference to Schneider Electric documentation
c MV partner (Pierre GIVORD)
c Protection of electrical networks (Christophe PREVE)
c Protection of electrical networks (édition HERMES fax 01 53 10 15 21) (Christophe PREVE)
c Medium voltage design (André DELACHANAL)
c Cahiers techniques v n°158 calculating short-circuit
currents v n°166 enclosures and protection
indices (Jean PASTEAU)

Schneider Electric

Merlin Gerin MV Design Guide

81

Index

Alphabetical Index

Schneider Electric

Denomination

pages

A

Acceleration Accuracy Accuracy class Accuracy limit factor Accuracy power Active power Altitude Angle Angular acceleration Angular speed Aperiodic component Apparent power Area Arrangement Asynchronous Automatic reclosing

67-69 57 62 58
57-62 68
53-79 67 67 67 48 68 67 29
14-16 48

B

Bending

28

Block

10

Breaking current

48-50-51-52-75

British thermal unit

69

British thermal unit per (pound.degree Fahrenheit) 69

British thermal unit per cubic foot.degree Fahrenheit 69

British thermal unit per hour

69

British thermal unit per pound

69

British thermal unit per second

69

British thermal unit per square foot.hour

69

Busbars

15-21-28

Busducting

27-29-37

C Cables Cable-charging Calculating a force Calculation Calorie capacity Calory power Capacitor bank Capacity Celsius Circuit breaker Closing Closing capacity Closing-opening Comparison Compartmented Concentration Condensation Conditions Conductance Conductivity Construction Coordination Cross section Cubic foot Cubic inch Cubicles Current Current transformer

15 51 27 15-17-21 69 69 51-52 68 68 45-48 52 74 47 72 10 67 38 52 68 68 78 53-77 21 69 69 10 8-67-68 54-55

D Degree Fahrenheit Degree Rankine Density Derating Dielectric strength Dielectric withstand Differential Differential transformer Disconnector Disconnector switch

69 69 67 64-65-78 38 38-39-40 59-60 60
9 9

Discordance Distances Documentation
E Earthing disconnector Electrical endurance Electrodynamic withstand Endurance Energy Energy (torque) Entropy Environment Equipment Equivalent diagram Equivalent impedance
F Factor Fault Arcs Field Fixed circuit breaker Fixed contactor Fluid ounce (UK) Fluid ounce (US) Flux Foot Foot of water Foot per second squared Force Forces Forces between conductors Frequency
G Gallon (UK) Gallon (US) Generators
H Heat capacity Humidity
I IK code Impedance method Impulse testing Inch Inch of water Inductance Induction Insulation level Intrinsic resonance frequency Ionization threshold IP code
K Knot
L Length Level of pollution Lightning impulse Linear mass Line-charging Load Low inductive currents Luminous
M... Magnetic field Magnetisation Magnitudes Making current Mass Mass per surface area Mass per volume

Merlin Gerin MV design guide

50 38-39
81
9 53-78
27 53-78 68-69
69 68 40
9 19 16
49-61 16 68 9 9 69 69 68 69 69 69
68-69 27 27
9-29-37-47-54-67
69 69 14-15
69 38-53-79
43 17 39 69 69 68 68
6 29 38 41
69
67-69 40
39-7 29-37-67-69
51 68 52 67
69 68 67 46 67-69 67-69 67-69
83

Index

Alphabetical Index

Denomination
...M Materials Mechanical effects Mechanical endurance Mechanical withstand of busbars Metal enclosure Metal-clad Metre Mile (UK) Minimum distances Modulous of elasticity Modulous of inertia Moment of a force Moment of inertia Motors Movement Multi-stage
N Network
O Oersted Operating current Operating current Operating voltage Ounce Over-current factor Overhead lines Overview Overvoltages
P Peak Peak value Peak value of admissible current Period Periodic component Periodic phenomena Permissible short time withstand current Permissible strain Permittivity Phase error Phase shift Phase to earth Phase to phase Plane angle Pollution Potential Pound Pound force per square foot Pound force per square inch Pound force-foot Pound force-inch Pound force-second per square foot Pound per cubic foot Pound per cubic inch Pound per foot Pound per foot-second Pound per inch Pound per square foot Pound per square inch Pound square foot Pound-force Power Power level Pressure Pressure-strain Primary current Primary voltage Protection index
Q Quantity

pages
67 21 53-78 28
9 10 67 69 39 29-37 28-29-37 68 29-69 16 68 51-52
15
69 8
55 6-21
69 56 15 72
6
50 9-46-74
9 67 48 67 46-73 28 68 63 63-67 39 39-63 67 38-40 68 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 14-68 67 38-68-69 69 55 61 41-43
68

R Radiation factor Rated current Rated frequency Rated insulation level Rated short circuit Rated values Rated voltage Ratio error Reactive power Resistance Resistivity Resonance Resultant strain

68 8-21-24-46-73
75 46-72 46-74
77 6-7-21-45-47-54-72-74
63 68 68 68 29-37 28

S Safety factor Shape of parts Short circuit power Short time withstand current

57 38-39 11-21
26

Short-circuit current Solid angle Speed Square foot Square inch Standards States Strain Supports Surface area Switch Switching sequence Symbols Synchronous compensators

9-19 67 67 69 69 71 14 68
27-29 67-69
9 47-75
67 16

T Temperature Temperature rise Thermal Thermal conductivity Thermal effects Thermal flux Thermal power Thermal short circuit current Thermal withstand Thermodynamic Thermodynamic temperature Three phase calculation example Time Transformation ratio Transformers Transient

38-52-69-79 22-23 56-68 69 21 69 63 56 24 67-68 67-68 17 67 63
13-14-15 49

U

Units

67

Units of measurement

67

V Vibration Viscosity Voltage Voltage transformer Volume Volume per mass Volume per mass

29-37 68-69 6-49-62-68
61 67-69
67 68

W

Wave lengths

67

Weight

68

Withdrawable circuit breaker

9

Withdrawable contactor

9

Work

68

Y

Yard

69

84

Merlin Gerin MV design guide

Schneider Electric

Schneider Electric Industrie SA
ART 86206

Postal address F-38050 Grenoble cedex 9 Tel.: +33 (0)4 76 57 60 60 Telex: merge 320842 F http://www.schneider-electric.com
Rcs Nanterre B 954 503 439

The technical data given in this guide are given for information purposes only. For this reason, Schneider Electric Industries SA is in no way liable for any omission or error contained in its pages.
Published by: Schneider Electric Industries SA Creation, layout by: HeadLines Printed by:

This document has been printed on ecological paper.
03/2000

AMTED300014EN


Acrobat Distiller 4.0 for Macintosh