Lindab FireProtect Round Smoke Extraction Duct Installation Guide

Brand: Lindab

Product Type: Smoke Extraction Duct

Validity

This installation guide applies to round smoke extraction ducts made of sheet steel, type Lindab FireProtect, tested according to DIN EN 12101-7:2011-08 and certified according to the performance declaration 0761-CPR-0359.

Classification: According to DIN EN 13501-4 based on EN 1366-9: E600 120 (ho) S - 1500 single.

For use within individual sections. (Must not be routed through components for which a fire resistance period is required.)

All Lindab FireProtect smoke extraction ducts are clearly marked with non-removable CE stickers as smoke extraction ducts without a fire resistance class. Components that do not comply with the performance declaration are also not marked with a sticker.

Mounting Accessories

The following components are necessary for hanging the ducts and are included:

All accessories for vertical mounting and fastening are not included in the scope of delivery and must therefore be ordered separately!

For mounting the anchors, a (site-provided) carbide hammer drill and the corresponding, separately orderable marking expansion tool are required.

Important Notes:

Mounting of Pipes and Fittings

The mounting of pipes type SRFP and fittings is carried out as described below:

Hanging of Ducts - Horizontal Mounting

Important Note:

Each pipe and fitting may only be suspended with the supplied parts. The threaded rods may only be loaded with 750 N each when fastened to fire-resistant solid components. The distance between two suspensions must not exceed 2000 mm.

Maximum suspension distance:

[Diagram showing maximum suspension distances of 2000 mm with a flexible connector indicated]

When fastening to fire-resistant clad steel components, form-fitting connecting elements must be used instead of anchors, for which the above-mentioned limitation of the calculated load must be observed. In this case, the cladding of the steel components must be extended to the suspensions over a length of at least 300 mm.

According to expert opinion MPA-BS 6000/242/20, the smoke extraction ducts can also be mounted vertically with a height offset of up to 2500 mm. See instructions for vertical wall mounting.

According to expert opinion MPA-BS 6000/242/20, the smoke extraction ducts can also be mounted vertically with a height offset of up to 2.5 m. See instructions for vertical wall mounting.

Important Note:

For smoke extraction ducts with lengths over 5 m, measured along the duct axis, flexible connectors must be installed at intervals of no more than 10 m. For vertical mounting, the interval is max. 2.5 m.

The connection of smoke extraction ducts to components for which a fire resistance period is required must be carried out with flexible connectors. See attached installation instructions for the flexible connector (WSK).

Hanging of Ducts - Horizontal Mounting (Anchor Installation)

Before installing the anchors, the concrete strength class of the anchoring base must be determined. It must be between C 20/25 and C 50/60.

Assembly check:

[Diagram showing anchor installation steps: drilling, cleaning, inserting anchor, anchoring, attaching component, applying torque]

With complete expansion, markings are visible on the expansion sleeve.

Anchoring in uncracked concrete:

Drilling nominal diameterDrill cutting diameterDrilling depthTorque during anchoring
10 mm10.45 mm40 mm8 Nm

Visible marking with complete expansion.

[Diagram showing pipe clamp assembly with threaded rod and flexible connector]

Important Note:

The suspensions may only be used for the smoke extraction system. Components that are not part of the smoke extraction duct must not be mounted!

Hanging of Ducts - Vertical Wall Mounting

Bracket Sizes

[Diagrams of different bracket types: Konsole 725/400, Konsole 550/400 gekürzt, Konsole 880/550 ohne Auflageschiene]

Bracket Assignment and Fastening

[Diagram showing bracket dimensions and attachment points]

BracketABCDEF
550/400550400-2201608
725/400725400-2201608
880/55088055023027016010
880/550 with support rail 1500 mm 41-75/75/3.01500*55023027026010

Table 1: Bracket assignment and fastening

[Diagram showing anchor loads and fastening details]

Duct diameter D [mm]Max. load per bracket [kg]Fastening with fire protection anchor BZAnchor loads (top/bottom)Fastening of L-steel to duct/bracketL-steel fastening to pipe/bracket respectively
≥200 <318550/44095.452 x M12 (top) / 1 x M12 (bottom)12 x M10/1 x M10
≥319 <565550/440108.42 x M12 (top) / 1 x M12 (bottom)22 x M10/1 x M10
≥566 <797725/400120.62 x M12 (top) / 2 x M12 (bottom)22 x M10/1 x M10
≥798 ≤1000880/550131.252 x M12 (top) / 2 x M12 (bottom)22 x M10/1 x M10

* Fastening according to Table 1 Fire protection anchor type Bolt anchor BZ

Connecting Components

Preparations:

The materials must be in a clean condition.

Cutting Pipes:

Pipes must be cut at a right angle, and the cut pipe end must be deburred.

Assembly of Individual Parts:

Pipes are connected using nipples. Fittings with nipple dimensions can be connected to the pipe or with fittings with socket dimensions.

Pipe Ø mmScrews min. Ø mmNumber
100-1253.24
140-2503.26
280-6303.28
710-9004.016
10004.024

Mounting of Pipe-in-line Grilles

Cutouts can be made in the spiral ducts SRFP and pipe-in-line grilles type RGS-0 can be installed. The grille is fastened with sheet metal screws (3.9 x 19mm), at a maximum interval of 425 mm from each other. The cutout dimension is equal to the nominal dimension of the grille.

Connection to Flexible Connectors

Pipes and fittings that are connected to round flexible connectors must be provided with a flange connection. The connection is made by a Lindab FL type flange and a loose collar. Alternatively, fittings can be manufactured with a flange, in which case the connection is made by a loose underlying flange of the Lindab FL type.

[Diagram showing connection to flexible connector with flange, steel rivets, and collar]

Mounting of Flexible Connectors

Important Note:

The connection of Lindab FireProtect smoke extraction ducts to components for which a fire resistance period is required must be carried out with flexible connectors (WSK).

For ducts with a length > 5 m between classified walls, a connector must be installed. The maximum distance between connectors must not exceed 10 m. If the duct direction changes, it must be checked whether expansion possibilities or connectors need to be installed at shorter intervals than required by DIN 4102-4.

Mounting of Flexible Connector between 2 Lindab FireProtect Smoke Extraction Ducts:

[Diagram showing flexible connector installation between two ducts with dimensions and connection profiles]

Mounting of Smoke Extraction Dampers Type WXHU

In the spiral ducts SRFP, smoke extraction dampers of type WXHU can be installed as follows:

Technical Data of Actuators

BLE24BLE230
Supply voltageAC/DC 19.2 - 28.8 V, 50/60 HzAC 198-264 V, 50/60 Hz
Power consumption7.5 W5 W
For cable dimensioning9 VA12 VA
Connection1 m cable, 3x0.75 mm²1 m cable, 3x0.75 mm²
Rotary angleMax. 90°Max. 105°
Torque at nominal voltageMin. 15 NmMin. 15 Nm
Rotary directionSelection by mounting L/RSelection by mounting L/R
Position indicatorMechanical with pointerMechanical with pointer
Running time<30 s for 90°<30 s for 90°
Sound power levelMax. 62 dB (A)Max. 62 dB (A)
Protection classIII Safety extra-low voltage (Protective extra-low voltage)II (Double insulated)
Degree of protectionIP 54IP54
Ambient temperature range-30 to +50°C-40 to + 80°C
Ambient humidity95% RH95% RH

[Diagrams showing wiring connections for BLE24 and BLE230 actuators]

Maintenance Information

Commissioning:

Proper commissioning requires acceptance of the entire smoke extraction system, including volume flows and, if applicable, leakages according to DIN EN 12599.

Regular Inspections:

Regular checks/inspections must be carried out by the system operator at intervals to be determined based on the operating conditions, but at least every 12 months.

Smoke extraction dampers must be inspected at least every six months, taking into account the basic maintenance measures according to EN 13306 in conjunction with DIN 31051. If two consecutive inspections within a 6-month period reveal no functional defects, the smoke extraction damper only needs to be inspected annually.

The inspections, which must be carried out as part of the operating and maintenance requirements of the entire smoke extraction system, include the following checks and require the creation of a report with final confirmation that the duct fulfills its function as part of the smoke extraction system.

Good Thinking

Responsible thinking is Lindab's corporate philosophy that guides us in all our actions. We have made it our mission to create a healthy indoor climate – and to make building sustainable buildings easier. We achieve this through the development of innovative and easy-to-use products and solutions, as well as through our efficient delivery and logistics concept. We are also working on ways to reduce negative impacts on the environment and climate. This includes the development of methods with which we manufacture our solutions with the lowest possible energy and raw material consumption and thus reduce environmental impact. We use steel for our products. It is one of the few materials that can be recycled indefinitely without losing its properties. This means that CO2 emissions and energy consumption are significantly reduced.

We simplify construction

PDF preview unavailable. Download the PDF instead.

Montageanleitung FP rund Adobe PDF Library 15.0

Related Documents

PreviewLindab WXHU Smoke Control Damper: Technical Specifications and Features
Detailed technical specifications, classification, dimensions, and motor data for the Lindab WXHU circular smoke control damper, designed for smoke and heat evacuation systems.
PreviewLindab Ventilation Grill F50/51: Environmental Product Declaration
Environmental Product Declaration (EPD) for Lindab's F50/51 ventilation grill, detailing its life cycle assessment, environmental impact data, and sustainability aspects according to EN 15804+A2 and ISO 14025.
PreviewLindab Atrium Loggia / -H / -C Heating and Cooling Panels | Installation & Overview
Comprehensive guide to Lindab Atrium Loggia / -H / -C heating and cooling panels, covering delivery control, mounting options, water connections, and false ceiling integration. Learn about Lindab's energy-efficient HVAC solutions for improved indoor climate.
PreviewLindab OLC Overflow Unit - Installation Guide
Comprehensive installation instructions for the Lindab OLC overflow unit, including dimensions, accessories, and step-by-step mounting guidance for OLC and OLCZ models.
PreviewLindab UltraLink FTCU Controller: Technical Information and Installation Guide
Comprehensive technical information, installation, configuration, and troubleshooting guide for the Lindab UltraLink FTCU airflow controller, a highly accurate ultrasonic airflow measurement and control device for ventilation systems.
PreviewLindab Solus Ventilation Baffle Installation and Mounting Guide
Comprehensive installation instructions and mounting details for the Lindab Solus ventilation baffle, covering air and water connections, ceiling system compatibility, and accessories. Available in multiple languages.
PreviewLindab ISOL Damper DRUI/DSUI Building Product Declaration
This document is a Building Product Declaration (BPD) for Lindab's ISOL damper (DRUI/DSUI), detailing company information, product specifications, chemical content, raw materials, environmental impact, distribution, construction, use, demolition, waste management, and indoor environment aspects according to standardized formats.
PreviewLindab GD Diffuser Mounting Instructions
Official mounting instructions for the Lindab GD air diffuser, including product specifications, dimensions, parts list, maintenance guidelines, and support contact information.