Thank you for purchasing a WiNG-CO2 wireless sensor. Before you change the measurement interval on your sensor, consult rletech.com to ensure you're working with the most recent version of documentation available. If you need further assistance, please contact RLE Technologies at support@rletech.com.
v06.21
© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and SeahawkTM, FalconTM, and RaptorTM are trademarks of Raymond & Lae Engineering, Inc. The products sold by RLE Technologies, 104 Racquette Dr., Fort Collins, CO 80524 are subject to the limited warranty, limited liability, and other terms and conditions of sale set forth at https://www.rletech.com.
Supplies Required WiNG-CO2 Sensor Small flathead screwdriver
Modify the CO2 Measurement Interval The default CO2 measurement interval of the WiNG-CO2 is 2 minutes. This interval can be changed to values from 1 to 15 minutes. Interval modifications will alter the battery life of the device; a shorter interval will reduce the battery life of the sensor. If you'd like to adjust the measurement interval of the WiNG-CO2 sensor, you can do so after you've completed the initial configuration procedure as detailed in the WiNG-CO2 Quick Start Guide. 1. After you have completed the initial configuration procedure - compensate
for altitude, set the auto-zero function, and configure the zero point in fresh air - you can adjust the measurement interval. This should be done at the same time as the initial configuration, and not separately. To configure the measurement interval:
a. Hold the push button on the top of the sensor. DO NOT release the button. The LED will turn white and then it will turn green.
b. Continue to hold the button for 5 additional seconds after the LED turns green, until the LED flashes cyan 3 times. Release the button.

2. Note the current position of the rotary switch. It is in the correct position
for the altitude setting for this sensor, and once the measurement interval
has been configured you'll need to return the rotary switch to this altitude setting.

3. Set the rotary switch to the desired number of minutes for the CO2 measurement interval.

Rotary Switch Setting CO2 Measurement Interval

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

A

10

B

11

C

12

D

13

E

14

F

15

4. Press the button to confirm the change. The LED will flash green.

5. If the rotary switch has changed from the previous position (the altitude
configuration setting) then the LED will flash red until the previous position is restored. Reset the rotary switch to the previous position. A green LED
indicates that configuration has completed successfully and that the sensor has returned to the main application mode.