1. Įvadas
This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.
The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.
2. Saugos informacija
ĮSPĖJIMAS: Elektros smūgio pavojus. Montavimą ir techninę priežiūrą turėtų atlikti tik kvalifikuoti darbuotojai.
- Always disconnect power before installing or servicing the ATS.
- Įsitikinkite, kad visa instaliacija atitinka vietinius ir nacionalinius elektros kodeksus.
- Patikrinkite teisingą ttagPrieš prijungdami įrenginį, patikrinkite jo e ir srovės vardines vertes.
- Nenaudokite prietaiso, jei jis atrodo pažeistas.
- Laikykite vaikus atokiau nuo elektros įrangos.
3. Produktas baigtasview
The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.
3.1. Pakuotės turinys
- 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)
3.2. Front Panel and Indicators

Vaizdo aprašymas: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).
The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:
- Galia: Output indication.
- >V: Per tomastage indikacija.
- <V: Nepakankamas tomastage indikacija.
- >aš: Over-current indication.
Control buttons allow for parameter settings and manual operation:
- NUSTATYTI: Menu key for accessing settings.
- Digit+/Up: Increases value or navigates up in menus.
- Digit-/Down: Decreases value or navigates down in menus.
- Rankinis įjungimas/išjungimas: Power button for manual control.
4. Sąranka ir diegimas
The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.
4.1. Laidų schema

Vaizdo aprašymas: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.
Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.
- Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
- Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
- Ensure all connections are secure and tightened to prevent loose contacts and overheating.
4.2. Pradinis įjungimas
After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.
5. Naudojimo instrukcijos
The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.
5.1. Ekrano ir indikatorių supratimas
The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Vaizdo aprašymas: Iš arti view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).
5.2. Adjusting Protection Parameters
Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.
| Parametras | Nustatymų diapazonas | Numatytasis nustatymas |
|---|---|---|
| Over Current Protection Setting Range | 1-63A/100A | 30A |
| Continuous Over Current Protection Times | 0-20 kartus | IŠJUNGTA |
| Per ttage Protection Setting Range | 230-300V | 270 V |
| Per ttage Protection Recover Setting Range | 225-295V | 265 V |
| Pagal ttage Protection Setting Range | 140-210V | 170 V |
| Pagal ttage Protection Recover Setting Range | 145-215V | 175 V |
| ttage & Current Protection Recover Delay | 1-500 | 30 s |
5.3. Automatic Phase Transfer
The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.
5.4. Automatic Recovery
Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.
6. Priežiūra
The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.
- Valymas: Įrenginį laikykite švarų, be dulkių ir šiukšlių. Valymui naudokite sausą, minkštą šluostę. Nenaudokite skystų valiklių.
- Ryšio patikrinimai: Periodically inspect all wiring connections to ensure they remain tight and free from corrosion.
- Aplinkos sąlygos: Užtikrinkite, kad darbo aplinka išliktų nurodytose temperatūros ir drėgmės ribose.
7. Problemų sprendimas
If you encounter issues with your ATS, refer to the following common problems and solutions:
| Problema | Galima priežastis | Sprendimas |
|---|---|---|
| Nėra išvesties galios | No input power; all phases unstable; device in fault state. | Check incoming power supply. Verify all phases are stable. Check fault indicators. |
| ">V" or "<V" indicator lit | Per tomastage arba pagal ttage detected on a phase. | Patikrinkite įvesties tūrįtage stability. The ATS will automatically transfer if another phase is healthy. |
| ">I" indicator lit | Over-current detected on the output. | Reduce load on the output. Check for short circuits in the connected equipment. |
| Device not transferring phases | No healthy alternative phase available; transfer delay setting too long. | Ensure at least one healthy phase is present. Check and adjust the transfer delay settings. |
| Skaitmeninis ekranas neveikia | No power to the device; internal fault. | Check power supply. If power is present and display is off, contact support. |
For issues not covered here, please contact EARU customer support.
8. Specifikacijos

Vaizdo aprašymas: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.
| Funkcija | Detalė |
|---|---|
| Prekės ženklas | EARU |
| Modelio numeris | EARU-1012 |
| Veikimo režimas | ĮJUNGTI IŠJUNGTI |
| Dabartinis reitingas | 63 Amps |
| Veiklos ttage | 440 Volts (AC 3*220V (N-L1/L2/L3)) |
| Vardinis dažnis | 50/60Hz |
| Kontakto tipas | Paprastai atidarytas |
| Jungties tipas | Standard DIN rail 63A |
| Grandinės tipas | 4 krypčių |
| Kontaktinė medžiaga | Varis |
| Over Current Protection Setting Range | 1-63A/100A (Default 30A) |
| Continuous Over Current Protection Times | 0-20 Times (Default OFF) |
| Per ttage Protection Setting Range | 230-300V (Default 270V) |
| Per ttage Protection Recover Setting Range | 225-295V (Default 265V) |
| Pagal ttage Protection Setting Range | 140-210V (Default 170V) |
| Pagal ttage Protection Recover Setting Range | 145-215V (Default 175V) |
| ttage & Current Protection Recover Delay | 1-500s (Default 30s) |
| Prekės svoris | 450 g |
| Pakuotės matmenys | 15 x 15 x 15 cm |
| Kilmės šalis | Indija |
9. Garantija ir palaikymas
9.1. Informacija apie garantiją
The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a 1 metų gamintojo garantija nuo įsigijimo datos. Ši garantija taikoma medžiagų ir gamybos defektams įprasto naudojimo sąlygomis. Ji netaikoma žalai, atsiradusiai dėl netinkamo įrengimo, netinkamo naudojimo, nelaimingų atsitikimų ar neleistinų modifikacijų.
9.2. Pagalba klientams
For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.