Lennox LF25 Garage Heater User Manual - Download [optimized] Lennox LF25 Garage Heater User Manual - Download
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
IMPORTANT: Special procedures are required for clean-ing the aluminum coil in this unit. See page 7 in this in-struction for information.
Package 1 of 1 contains:
1 – Evaporator coil
Check the components for shipping damage; if found, im-mediately contact the last carrier.
1.5 TO 3 TON | |||||||
General Data Model No.
Nominal size – tons Factory installed expansion valve | CHX35 -18A-6F | CHX35 -24A-6F | CHX35 -24B-6F | CHX35 -30A-6F | CHX35 -30B-6F | CHX35 -36A-6F | CHX35 -36B-6F |
1.5 | 2 | 2 | 2.5 | 2.5 | 3 | 3 | |
12J18 | 12J18 | 12J18 | 12J18 | 12J18 | 12J19 | 12J19 | |
Line connections Suction o.d. – sweat in. Liquid o.d. – sweat Condensate drain (fpt) | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 |
3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | |
(2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | |
Indoor Net face area sq. ft. Coil Tube diameter – in. Number of rows Fins per inch | 3.5 | 3.5 | 4.67 | 4.33 | 4.67 | 3.5 | 4.67 |
3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | |
2 | 3 | 2 | 3 | 3 | 3 | 2 | |
19 | 13 | 19 | 16 | 13 | 13 | 18 | |
Matching Lennox Furnace – Cabinet Width Designation | A | A | B | A | B | A | B |
Coil & Furnace Cabinet Height – in. | 14-1/2 | 14-1/2 | 17-1/2 | 14-1/2 | 17-1/2 | 14-1/2 | 17-1/2 |
Shipping Data – lbs. | 44 | 46 | 50 | 56 | 54 | 48 | 49 |
3 TO 5 TON | |||||||
General Data Model No. Nominal size – Tons Factory installed expansion valve | CHX35 -36C-6F | CHX35 -42B-6F | CHX35 -42C-6F | CHX35 -48B-6F | CHX35 -48C-6F | CHX35 -51/61C-6F | CHX35 -60D-6F |
3 | 3.5 | 3.5 | 3.5/4 | 3.5/4 | 4/5 | 5 | |
12J19 | 12J20 | 12J20 | 12J20 | 12J20 | 12J20 | 12J20 | |
Line connections Suction o.d. – sweat in. Liquid o.d. – sweat Condensate drain (fpt) | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 |
3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | |
(2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | (2) 3/4 | |
Indoor Net face area sq. ft. Coil Tube diameter – in. Number of rows Fins per inch | 5.83 | 5.78 | 5.83 | 5.78 | 5.83 | 7.22 | 7.94 |
3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | |
2 | 4 | 3 | 3 | 3 | 3 | 3 | |
18 | 13 | 13 | 13 | 13 | 13 | 13 | |
Matching Lennox Furnace – Cabinet Width Designation | C | B | C | B | C | C | D |
Coil & Furnace Cabinet Height – in. | 21 | 17-1/2 | 21 | 17-1/2 | 21 | 21 | 24-1/2 |
Shipping Data – lbs. | 56 | 67 | 67 | 61 | 60 | 70 | 79 |
CAUTION
The coil is shipped from the factory pressurized with dry air. Pierce a hole in the rubber plug that seals the vapor line to relieve the pressure before removing the plugs.
NOTE – If there is no pressure released when the vapor line rubber plug is pierced, check the coil for leaks before continuing with the installation. The CHX35 coils are shipped with a 9 ± 2 psi dry air hold-ing charge. Puncture the suction line rubber plug to re-lease the charge. Remove the rubber plug. Ensure that the coil is void of pressure.
WARNING
Risk of explosion or fire.
Can cause injury or death.
Recover all refrigerant to relieve pressure before opening the system.
Install the furnace or air handler according to the installa-tion instructions provided with the unit.
NOTE – In areas of high humidity, use foam tape to in-sulate the suction line section in the cabinet as shown in figure 1.
LINE SIZES
The refrigerant line sets should be sized according to the recommendations given in the air conditioner or heat pump unit installation instructions. Use table 1 to determine cor-rect braze connection sizes. A field-provided adapter may be required to match line set connections
TABLE 1 Refrigerant Line Connections Model CHX35
Model Number | Suction | Liquid |
18-6F | ||
24-6F | ||
30-6F | ||
36-6F | 7/8 Inch | 3/8 Inch |
42-6F | ||
48-6F | ||
51/61-6F | ||
60-6F |
REPLACEMENT PARTS
If replacement parts are necessary, order kit 69J46. The kit includes:
BRAZING GUIDELINES
Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to-copper connections or 45 percent silver al-loy for copper-to-brass or copper-to-steel connections). Before making brazed connections, place a field-provided heat shield, such as a wet rag, against the unit cabinet and around the piping stubs, expansion valve and sensing bulb (or remove the sensing bulb temporarily). The heat shield must be in place to prevent heat damage during brazing. See figure 7.
SUCTION LINE CONNECTION
Use the following procedure to connect the suction line to the indoor coil:
LIQUID LINE CONNECTION
Use the following procedure to connect the liquid line to the indoor coil:
Refer to the outdoor unit instruction for leak testing, evac-uating and charging procedures. Always leak check entire system before charging.
Ensure the duct is secured and all joints are properly sealed to the coil cabinet flanges.
WARNING
There must be an airtight seal between the bottom of the air handler and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.
IMPORTANT
DUCT SYSTEM SIZING – The duct system should be properly sized and installed according to the ASHRAE Standard Manual D. The supply and return air duct systems should be designed for the cfm and static requirements of the job. Consult the blower performance chart in the unit installation instructions to verify that the blower meets the application requirements.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.
MAIN DRAIN
Connect the main drain and route downward to drain line or sump. Do not connect drain to a closed waste system. See figure 9 for typical drain trap configuration.
OVERFLOW DRAIN
It is recommended that the overflow drain is connected to a overflow drain line for all units. If overflow drain is not connected, it must be plugged with provided cap.
BEST PRACTICES
The following practices are recommended to ensure bet-ter condensate removal:
Proper air volume must be provided over the evaporator coil. Select a blower motor speed tap that will provide 400 ± 50 CFM per 12,000 Btuh of cooling capacity (wet coil). A static pressure reading must be taken to see if the pres-sure drop falls within the proper range.
To ensure accuracy, static pressure must be read from the air entry side of the coil to the air exit side of the coil. See figure 9 for an example to obtain an accurate reading.
CAUTION
Take care when drilling test holes into the furnace flange and the duct. Drill holes away from refrigerant piping. Test holes should be drilled where specified in order to avoid unit damage.
TABLE 2. Air Volume / Static Pressure Drop Across Coil
Cabinet | Vol: CFM | Drop: in. w.g. | ||
CHX35 Model | Width in. | Dry | Wet | |
-18A-6F | 14-1/2 | 600 | .09 | .11 |
-24A-6F | 14-1/2 | 800 | .15 | .19 |
-24B-6F | 17-1/2 | 800 | .09 | .11 |
-30A-6F | 14-1/2 | 1000 | .24 | .27 |
-30B-6F | 17-1/2 | 1000 | .14 | .16 |
-36A-6F | 14-1/2 | 1200 | .30 | .39 |
-36B-6F | 17-1/2 | 1200 | .16 | .21 |
-36C-6F | 21 | 1200 | .15 | .18 |
-42B-6F | 17-1/2 | 1400 | .26 | .31 |
-42C-6F | 21 | 1400 | .18 | .21 |
-48B-6F | 17-1/2 | 1400 | .25 | .29 |
-48C-6F | 21 | 1600 | .27 | .30 |
-51/61C-6F | 21 | 1600 | .25 | .29 |
-60D-6F | 24-1/2 | 2000 | .24 | .30 |
NOTICE !
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Alu-minum coils may be damaged by exposure to solu-tions with a pH below 5 or above 9. The aluminum coil should be cleaned using potable water at a mod-erate pressure (less than 50psi). If the coil cannot be cleaned using water alone, Lennox recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning. A trained technician or service agency must perform main-tenance and service on equipment. At the beginning of each heating or cooling season, indoor coils should be inspected to determine whether the coil requires cleaning.
IMPORTANT
Ensure that the distributor lines are not rubbing together or kinked. All tubes must have enough clearance from other metal parts. Use wire ties to secure tubes to prevent movement that could cause the refrigerant tubing to fail.
LENNOX CHX35 Series Horizontal Coil [pdf] Instruction Manual CHX35 Series, Horizontal Coil, CHX35 Series Horizontal Coil, Coil |
Freestanding Stoves Product Information: This product is a freestanding stove that can be used for…
HYT H20 Watch HYT Watch Instructions HYT Watch Product Information: The HYT Watch is an…
Mylife Infusion Sets Product Information The infusion set is a medical device used for delivering…
9527278 Black Strap Smart Watch R5 Smart Sports Watch The R5 Smart Sports Watch is…
P612 Ultrasonic Fetal Doppler Product Information: Ultrasonic Fetal Doppler The P612 ultrasonic fetal doppler is…