WEINTEK Logo PLC Connection Guide
Weintek Built-in CODESYS
Supported series: Weintek Built-in CODESYS HMI

HMI Setting:

ParametersRecommendedOptionsNotes
PLC typeWeintek Built-in CODESYS
PLC I/FEthernet
Online simulatorNO

How to Import Tags:

  1. Under “MainTask” set POU PLC_PRG.WEINTEK Built In CODESYS HMI
  2. Add “Symbol configuration” into Devices list.WEINTEK Built In CODESYS HMI - Devices
  3. Select PLC_RPG and its tag information is shown, build the project.
    [build] -> [Generate Code]WEINTEK Built In CODESYS HMI - Diagram 1
  4. A *.xml file is generated in the directory of the project.WEINTEK Built In CODESYS HMI - Devices 1
  5. In System Parameter Settings click [New] to add Weintek Built-in CODESYS driver into the device list and then click [Tag Manager].WEINTEK Built In CODESYS HMI - Manager
  6. In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml) generated by the PLC software.WEINTEK Built In CODESYS HMI - Manager 1
  7. When the tags are imported successfully, click [Exit] to leave.WEINTEK Built In CODESYS HMI - Manager 2

Support Device Type:

Data typeEasyBuilder data formatMemo
Boolbit
Byte16-bit BCD, Hex, Binary, Unsigned8-bit
SInt16-bit BCD, Hex, Binary, Signed8-bit
USInt16-bit BCD, Hex, Binary, Unsigned8-bit
Word16-bit BCD, Hex, Binary, Unsigned16-bit
Int16-bit BCD, Hex, Binary, Signed16-bit
UInt16-bit BCD, Hex, Binary, Unsigned16-bit
DWord32-bit BCD, Hex, Binary, Unsigned32-bit
DInt32-bit BCD, Hex, Binary, Signed32-bit
Real32-bit Float32-bit
UDInt32-bit BCD, Hex, Binary, Unsigned32-bit
LInt64-bit Signed64-bit
ULInt64-bit Unsigned64-bit
LWord64-bit Unsigned64-bit
LReal64-bit Float64-bit
StringWord array for ASCII input and displayLength=word

Note1: String length must be set identical to the length in Codesys software.
Note2: EBPro V6.03.02 or later supports 64 bits data type (cMT Series only), but please note that the address limit range is 48 bits in maximum.

Wiring Diagram:

Diagram 1
Ethernet cable:

WEINTEK Built In CODESYS HMI - DiagramWEINTEK Logo

Documents / Resources

WEINTEK Built In CODESYS HMI [pdf] User Guide
Built In CODESYS HMI, Built In, CODESYS HMI, HMI