THE FOLLOWING MANUAL ASSUMES GOOD KNOWLEDGE OF TECHNICAL DOCUMENTATION INCLUDED WITH THE AIR HANDLING UNIT (AHU). THIS MANUAL CONSIDERS ONLY THE CONTROL AND COMMUNICATION CIRCUITS. THE INSTALLATION OF THE FREQUENCY CONVERTER AND INSTALLATION OF MAINS AND MOTOR CABLES SHOULD BE DONE ACCORDING TO THE LS G100 MANUAL.

 FOR ALL CONFIGURATIONS SET THE COMMON PARAMETER LIST

ParameterCodeValueComments
Ramp up timeACC45Recommended 45 s.
Ramp down timedEC45Recommended 45 s.
Maximum frequencydr-20100
Rated frequencydr-18*
U/f ratioAd-011Square characteristic
Overload protectionPr-402Active
Number of motor polesbA-11*2-12
Rated slipbA-12**
Rated currentbA-13*
Idle run currentbA-14**
P5 input functionIN-694Limit switch
  •  as per motor data
  •  parameters to be calculated:

rated slip = (1 – number of motor poles * rated speed / 6000) * 50 Hz idle run current = 0,3 * rated current

CONFIGURATIONS WITHOUT VTS CONTROLS

 Local control using integrated control panel

Set additional parameters:

ParameterCodeValueComments
Start / stop sourcedrv0Keypad
Frequency sourceFrq0Potentiometer

Use the RUN and STOP/RST buttons to control the drive Use buttons / potentiometer to set frequency

Remote control with three speeds

Set additional parameters:

ParameterCodeValueComments
Start / stop sourcedrv1Programmable inputs
Frequency sourceFrq4Constant speeds
Constant speed 1St1*0-100 Hz
Constant speed 1St2*0-100 Hz
Constant speed 1St3*0-100 Hz
  •  as per user preferences

Use P1/P3/P4/P5 inputs to set desired drive function (1=on,0=off)

0000 = STOP
1100 = START, 1ST SPEED
1110 = START, 2ND SPEED
1111 = START, 3RD SPEED

 EXHAUST UNIT WITH VTS CONTROL SYSTEM

Set additional parameters:

ParameterCodeValueComments
Start / stop sourcedrv1Programmable inputs
Frequency sourceFrq5Constant speeds
Constant speed 1St1*0-100 Hz
Constant speed 1St2*0-100 Hz
Constant speed 1St3*0-100 Hz
  •  as per user preferences

Use P1/P3/P4/P5 inputs to set desired drive function (1=on,0=off)

0000 = STOP
1100 = START, 1ST SPEED
1110 = START, 2ND SPEED
1111 = START, 3RD SPEED

 AHU WITH VTS CONTROLS TYPE uPC3

NOTE: To allow control of the G100 frequency drivers, set VFD type to G100 in uPC3 settings (HMI Advanced mask I03).
Set additional parameters:

ParameterCodeValueComments
Start / stop sourcedrv3Modbus RS-485
Frequency sourceFrq6Modbus RS-485
AddressCM-012Supply 1
3Exhaust 1
5Supply 2/ redundant
7Supply 3
9Supply 4
6Exhaust 2 / redundant
8Exhaust 3
10Exhaust 4
Comm. protocolCM-020Modbus RS-485
Comm. speedCM-0339600 bps
Comm. parametersCM-0408N1

NOTE: To restore G100 to default settings set dr-93 = 1 and switch off the power supply.