DAUDIN-logo

DAUDIN GFDO-RM01N MELSEC-Q Modbus TCP Connection

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-product

Product Information

Product Name: 2210TW V2.0.0 and MELSEC-Q Modbus TCP Connection

The product is a remote I/O module system that allows users to connect the MELSEC-Q series communication port (Modbus TCP) externally. It includes a gateway, main controller, digital input, digital output, and power supply modules. The main controller manages and dynamically configures I/O parameters. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Remote I/O Module System Configuration List

The list includes the following:

Part No.SpecificationDescription
GFGW-RM01NModbus TCP-to-Modbus RTU/ASCII, 4 PortsGateway
GFMS-RM01SMaster Modbus RTU, 1 PortMain Controller
GFDI-RM01NDigital Input 16 ChannelDigital Input
GFDO-RM01NDigital Output 16 Channel / 0.5ADigital Output
GFPS-0202Power 24V / 48WPower Supply
GFPS-0303Power 5V / 20WPower Supply

Product Gateway Parameter Settings

This section explains how to connect the gateway to the MELSEC-Q series. For detailed information, refer to the MELSEC-Q Series Product Manual. The i-Designer program is used for setup.

i-Designer Program Setup

  1. Ensure that the module is powered and connected to the gateway module using an Ethernet cable.
  2. Launch the i-Designer software.
  3. Select M Series Module Configuration.
  4. Click on the Setting Module icon.
  5. Enter the Setting Module page for M-series.
  6. Select the mode type based on the connected module.
  7. Click on Connect.
  8. Set the Gateway Module IP Address. Note: The IP address must be in the same domain as the MELSEC-Q controller.
  9. Set Gateway Module Operational Modes. Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N).

MELSEC-Q series Connection Setup

This chapter explains how to use the GX Works2 program to connect the MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, refer to the MELSEC-Q Series Manual.

MELSEC-Q series Hardware Connections

  • The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gateway.

MELSEC-Q series IP Address and Connection Setup

  1. Launch GX Works 2 and right-click on the Intelligent Function Module menu under Project on the left side.
  2. Click on New Module to create a QJ71MB91 module.

Simple Program Demonstration using MELSEC-Q series and

  • No information provided in the user manual for this section.

Product Usage Instructions

  1. Connect the gateway to the MELSEC-Q series communication port (Modbus TCP) externally using an Ethernet cable.
  2. Use the i-Designer program to set up the gateway parameters by following the steps mentioned in section 2.1 of the user manual.
  3. Use the GX Works2 program to connect the MELSEC-Q series to the gateway module and add a remote I/O module by following the steps mentioned in section 3 of the user manual.

Remote I/O Module System Configuration List

Part No.SpecificationDescription
GFGW-RM01N 

Modbus TCP-to-Modbus RTU/ASCII, 4 Ports

Gateway
GFMS-RM01SMaster Modbus RTU, 1 PortMain Controller
GFDI-RM01NDigital Input 16 ChannelDigital Input
GFDO-RM01NDigital Output 16 Channel / 0.5ADigital Output
GFPS-0202Power 24V / 48WPower Supply
GFPS-0303Power 5V / 20WPower Supply

Product Description

  1. The gateway is used externally to connect with MELSEC-Q series’ communication port (Modbus TCP)
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  3. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Gateway Parameter Settings

This section details how to connect a gateway to MELSEC-Q series. For detailed information regardingDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15, please refer to the DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15-Series Product Manual

i-Designer Program Setup

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-1

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cableDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-2
  2. Click to launch the softwareDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-3
  3. Select “M Series Module Configuration”DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-4
  4. Click on the “Setting Module” iconDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-5
  5. Enter the “Setting Module” page for M-seriesDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-6
  6. Select the mode type based on the connected moduleDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-7
  7. Click on “Connect”DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-8
  8. Gateway Module IP Settings
    • Note: The IP address must be in the same domain as the MELSEC-Q controllerDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-9
  9. Gateway Module Operational Modes

Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)

MELSEC-Q series Connection Setup

This chapter explains how to use the GX Works2 program to use the QJ71MT91 module to connect MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, please refer to the “MELSEC-Q Series Manual

MELSEC-Q series Hardware Connections

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-10

  1. The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gateway

MELSEC-Q series IP Address and Connection Setup

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-11

  1. Launch GX Works 2 and right click on the “Intelligent Function Module” menu under “Project” on the left side. Then click on “New Module” to create a “QJ71MB91” moduleDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-12
  2. Launch GX Works 2 and select the “Intelligent Function Module” menu under “Project” on the left side. Then click on “Switch Setting” in the “QJ71MT91” menuDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-13
  3. Set “IP Address” to the same domain as the gateway domain at 192.168.1.XXX.DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-14
  4. Click on “Automatic_Communication_Parameter” to set up reading and writing methods
  • Target Station IP Address is set by default at ”192.168.1.20”
  • TheDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15 station number to be connected
  • From the drop-down menu, select “0505h:Read/Write Holding Registers”
  • Set to 1000h
  • The Target MODBUS Device Head Number is set to 4096
  • Read Points
  • Set to 3000h
  • H The Target MODBUS Device Head Number is set to 8192
  • Write Points

Notes

  • DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15first GFDI-RM01N has the register address at 1000(HEX) converted to 4096
  • DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15first GFDO-RM01N has the register address at 2000(HEX) converted to 8192
  1. Click on “Auto_Refresh” to set up the internal register for reading and writing

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-16

Simple Program

Simple Program Demonstration using MELSEC-Q series and DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15

DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-17

  • The DAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15read register address is 4096, which is D0 for the corresponding internal register of the controller.
  • And theDAUDIN-GFDO-RM01N-MELSEC-Q-Modbus-TCP-Connection-fig-15 write register address is 8192, which is D300 for the corresponding internal register of the controller.
  • Therefore, when you want to control the program, you can just use the internal register to control the writing and reading.

Documents / Resources

DAUDIN GFDO-RM01N MELSEC-Q Modbus TCP Connection [pdf] User Manual
GFDO-RM01N MELSEC-Q Modbus TCP Connection, GFDO-RM01N, MELSEC-Q Modbus TCP Connection, MELSEC-Q Modbus, Modbus

References

Leave a comment

Your email address will not be published. Required fields are marked *