Danfoss-logo

Danfoss AVQM Flow Controller Installation

Danfoss-AVQM-Flow-Controller-Installation-product

Flow and temperature controller with integrated control valve, WE-version (PN 25)

  • AVQM-WE – f low controller with integrated control valve
  • AVQMT-WE – f low and temperature controller with integrated control valve

Description

Danfoss-AVQM-Flow-Controller-Installation-fig- (1)

  • AVQM-WE is a self-acting flow controller with integrated control valve primarily for use in district heating systems. The controller closes when set max. flow is exceeded.
  • AVQMT-WE is a self-acting flow and temperature controller with integrated control valve primarily for use in district heating systems. The controller closes on rising temperature or when set max. flow is exceeded. All controllers have special designed (pressure relieved) control valve insert.
  • AVQM-WE controller can be combined with Danfoss electrical actuators AMV(E) (and controlled by ECL electronic controllers).
  • AVQMT-WE controller can be combined with Danfoss electrical actuators AMV(E) (and controlled by ECL electronic controllers) and with AVT or STM thermostatic actuators.

The controllers have a control valve with adjustable flow restrictor, connection neck for electrical actuator, connection neck for thermostat (AVQMT-WE only), and an actuator with one control diaphragm.

AVQM-WE and AVQMT-WE are used together with Danfoss electrical actuators:

  • AMV 150 1)
  • AMV(E) 10 1) / AMV(E) 20 / AMV(E) 30
  • AMV(E) 13 1) / AMV(E) 23 / AMV(E) 33 with spring return function
  • AMV 20 SL / AMV 23 SL / AMV 30 SL with stroke limitation

AMV 150 / AMV(E) 10 / AMV(E) 13 can be combined with DN 15 controller only.

AVQM(T)-WE combined with AMV(E) 13, AMV(E) 23 (SL) or AMV(E) 33 (SL) has been approved according to DIN 32730. The controllers combined with AVT and STM thermostats are type-tested acc. to EN 14597. Controllers combined with STM thermostats protect systems against exceeding temperatures.

Applications:

  • District heating systems acc. to DIN 4747
  • Heating systems acc. to EN 12828 (DIN 4751) and EN 12953-6 (DIN 4752)
  • Water heating systems for drinking and industrial waters acc. to DIN 4753

Main data:

  • DN 15-50
  • kVS 2.5-25 m3/h
  • PN 25
  • Setting ranges:
    • AVT thermostat:
    • 10 … 40 °C / 20 … 70 °C / 40 … 90 °C / 60 … 110 °C and 10 … 45 °C / 35 … 70 °C / 60 … 100 °C / 85 … 125 °C
    • STM monitor 20 … 75 °C / 40 … 95 °C / 30 … 110 °C
  • Flow restrictor ∆p: 0.2 bar
  • Temperature:
    • Circulation water / glycolic water up to 30%: 2 … 150 °C
  • Connections:
    • Ext. thread (weld-on, thread and flange tailpieces)
    • Flange
  • Flow and return mounting.

Ordering

Example 1 –  AVQM-WE controller:
Flow controller with integrated control valve; DN 15; kVS 2.5; PN 25; flow restrictor ∆p 0.2 bar; Tmax 150 °C; ext. thread

  • 1× AVQM-WE DN 15 controller Code No: 003H7080

Option: 1× Weld-on tailpieces Code No: 003H6908

The controller will be delivered completely assembled, inclusive impulse tube between valve and actuator. Electrical actuator AMV(E) must be ordered separately.

Example 2 –
AVT (or STM) / AVQMT-WE controller: Flow and temperature controller with integrated control valve, DN 15; kVS 2.5; PN 25; setting range 40 … 90 °C; flow restrictor ∆p 0.2 bar; Tmax 150 °C; ext. thread

  • 1× AVQMT-WE DN 15 controller Code No: 003H7084
  • 1× AVT thermostatic actuator, 40 … 90 °C Code No: 065-0598

Option:

  • – 1× Weld-on tailpieces
    Code No: 003H6908

The controller AVQMT-WE will be delivered completely assembled, inclusive impulse tube between valve and actuator. Thermostatic actuator AVT will be delivered separately. Electrical actuator AMV(E) must be ordered separately. In case of safety temp. monitoring STM should be ordered instead of AVT.

Example 3 –
STM / AVT / AVQMT-WE controller: Flow and temperature controller with safety temperature monitor and integrated control valve, DN 15, kVS 2.5; PN 25; setting range 40 … 90 °C; limit range 30 … 110 °C; flow restrictor ∆p 0.2 bar; Tmax 150 °C; ext. thread

  • 1× AVQMT-WE DN 15 controller Code No 0: 03H6787
  • 1× AVT thermostatic actuator, 40 … 90 °C Code No 0: 65-0598
  • 1× STM monitor, 30 … 110 °C Code No 0: 65-0608
  • 1× K2 Combination piece Code No 0: 03H6855

Option: 1× Weld-on tailpieces Code No: 003H6908

The controller AVQMT-WE will be delivered completely assembled, inclusive impulse tube between valve and actuator. Combination piece K2, thermostats AVT and STM will be delivered separately. Electrical actuator AMV(E) must be ordered separately.

AVQM-WE Controller

PictureDN (mm)Kvs (m³/h)ConnectionCode No.
Danfoss-AVQM-Flow-Controller-Installation-fig- (2)152.5G ¾ A003H7080
154.0Cylindrical external thread acc. to ISO 228/1003H7081
206.3G1 A003H7082
208.0G 1¼ A003H7083
Danfoss-AVQM-Flow-Controller-Installation-fig- (3)25 / 32 / 4012.5003H7088
20Flanges PN 25, acc. to EN 1092-2003H7089
5025003H7090

AVQMT-WE Controller

PictureDN

(mm)

kVS

(m3/h)

ConnectionCode No.
Danfoss-AVQM-Flow-Controller-Installation-fig- 33 

15

2.5 

Cylindr. ext. thread acc. to ISO 228/1

 

G ¾ A

003H7084
4.0003H7085
206.3G 1 A003H7086
258.0G 1¼ A003H7087

AVT Thermostatic actuator

PictureFor valvesSetting range

(°C)

Temperature sensor with brass immersion pocket, length, connectionCode No.
 

Danfoss-AVQM-Flow-Controller-Installation-fig- (4)

 

 

 

 

 

DN 15-25

–10 … +40 

 

170 mm, R ½ 1)

065-0596
20 … 70065-0597
40 … 90065-0598
60 … 110065-0599
10 … 45 

 

255 mm, R ¾ 1) 2)

065-0604
35 … 70065-0605
60 … 100065-0606
85 … 125065-0607
  1. conic male thread EN 10226-1
  2. without immersion pocket

STM Safety temperature monitor (actuator)

PictureFor valvesLimit range

(°C)

Temperature sensor with brass immersion pocket, length, connectionCode No.
Danfoss-AVQM-Flow-Controller-Installation-fig- (5) 

DN 15-25

30 … 110 

210 mm, R ¾ 1)

065-0608
20 … 75065-0609
40 … 95065-0610

conic male thread EN 10226-1

Accessories for valves

PictureType designationDNConnectionCode No.
 

Danfoss-AVQM-Flow-Controller-Installation-fig- (6)

 

Weld-on tailpieces

15 

003H6908
20003H6909
25003H6910
Danfoss-AVQM-Flow-Controller-Installation-fig- (7)

 

 

External thread tailpieces

15Conical ext. thread acc. to

EN 10226-1

R ½003H6902
20R ¾003H6903
25R 1003H6904
Danfoss-AVQM-Flow-Controller-Installation-fig- (8)

 

 

Flange tailpieces

15 

Flanges PN 25, acc. to EN 1092-2

003H6915
20003H6916
25003H6917

Accessories for thermostats

 

Picture

 

Type designation

 

PN

For thermostats 

Material

 

Code No.

Danfoss-AVQM-Flow-Controller-Installation-fig- (9)

 

 

 

Immersion pocket

 

 

25

 

AVT

Brass065-4414 1)
Stainless steel, mat. No. 1.4571065-4415 1)
 

STM

Brass065-4416 1)
Stainless steel, mat. No. 1.4435065-4417 1)
Danfoss-AVQM-Flow-Controller-Installation-fig- (10) 

Combination piece K2

 

003H6855

Not for AVT thermostatic actuator code numbers: 065-0604, 065-0605, 065-0606, 065-0607

Service kits

Danfoss-AVQM-Flow-Controller-Installation-fig- 34

For AVQM-WE and AVQMT-WE controlers

Technical data

Valve

Nominal diameterDN152025324050
kVS value of dp controller 

m3/h

2.54.06.38.012.516/201)20/251)
Range of max.

flow setting

 pMCV = 0.2

bar

Qmin0.070.070.160.20.40.80.8
Qmax1.62.43.54.51010.5/121)12/141)
Avalible  p required for Qmax2)bar0.60.60.50.50.80.8/0.61)0.8/0.61)
Strokemm5710
Control valve authority1 (100%) in the range of flow setting
Control characteristicLogarithmic
Cavitation factor z≥ 0.6≥ 0.55≥ 0.5
Leakage acc. to standard IEC 534% of kVS≤ 0.02≤ 0.05
Nominal pressurePN25
Min. differential pressure 

bar

see remark 2)
Max. differential pressure2016
MediumCirculation water / glycolic water up to 30%
Medium pHMin. 7, max. 10
Medium temperatureoC2 … 150
 

Connections

valveExternal threadFlange
tailpiecesWeld-on, external thread and flange
Materials
 

Valve body

 

Red bronze CuSn5ZnPb (Rg5)

Ductile iron EN-GJS-400-18-LT

(GGG 40.3)

Valve seatStainless steel, mat. No. 1.4571
Valve coneDezincing free brass CuZn36Pb2As
Sealing DP, CVEPDM
 

Pressure relieve system

Control valve insert 

Piston

Valve insert

Note: DP – diff. pressure controller, MCV – control valve

  1. Flanged version
  2. For flows smaller than Danfoss-AVQM-Flow-Controller-Installation-fig- 35

Actuator

TypeAVQM-WE, AVQMT-WE
Actuator sizecm254
Nominal pressurePN25
Flow restrictor diff. pressurebar0.2
Materials
HousingUpper housing of actuatorStainless steel, mat. No.1.4301
Lower housing of actuatorDezincing free brass CuZn36Pb2As
DiaphragmEPDM
Impulse tubeCopper tube Ø 6 × 1 mm

AVT Thermostatic actuator

Setting range Xs°C−10 … 40 / 20 … 70 / 40 … 90 / 60 … 110

10 … 45 / 35 … 70 / 60 … 100 / 85 … 125

Time constant T acc. to EN 14597smax. 50 (170 mm, max. 30 (255 mm)
Gain Ksmm/°K0.2 (170 mm); 0.7 (255 mm)
Max. adm. temperature at sensor50 °C above maximum setpoint
Max. amb. temperature at thermostat°C0 … 70
Nominal pressure sensor 

PN

 

25

Nominal pressure immerison pocket
Capillary tube length5 m (170 mm), 4 m (255 mm)
Materials
Temperature sensorCooper
 

Immersion pocket 1)

Ms designBrass, nickel-plated
Stainless steel designMat. No. 1.4571 (170 mm)
Handle for temp. settingPolyamide, glass fiber-reinforced
Scale carrierPolyamide

for sensor 170

STM Safety temperature monitor (actuator)

Limit range Xs°C20 … 75 / 40 … 95 / 30 … 110
Time constant T acc. to EN 14597smax. 100
Gain Ksmm/°K0.3
Max. adm. temperature at sensor80 °C above maximum setpoint
Max. amb. temperature at thermostat°C0 … 70
Nominal pressure sensor 

PN

 

25

Nominal pressure immerison pocket
Capillary tube lengthm5
Materials
Temperature sensorCooper
 

Immersion pocket

Ms designBrass, nickel-plated
Stainless steel designmat. No. 1.4435
Handle for temp. settingPolyamide, glass fiber-reinforced
Scale carrierPolyamide

Danfoss-AVQM-Flow-Controller-Installation-fig- (15)

Application principles

Danfoss-AVQM-Flow-Controller-Installation-fig- (16)

Combinations

  • AVQM-WE / AMV(E)
    Flow controller with electrical actuatorDanfoss-AVQM-Flow-Controller-Installation-fig- (17)
  • AVT / AVQMT-WE / AMV(E)
    Flow and temperature controller with electrical actuatorDanfoss-AVQM-Flow-Controller-Installation-fig- (18)
  • STM / AVQMT-WE / AMV(E)
    Flow controller with safety temperature monitor and electrical actuatorDanfoss-AVQM-Flow-Controller-Installation-fig- (19)
  • STM / AVT / AVQMT-WE / AMV(E)
    Flow and temperature controller with safety temperature monitor and electrical actuatorDanfoss-AVQM-Flow-Controller-Installation-fig- (20)

Installation positions

  • Flow and temperature controller with integrated control valve (with AVT or STM)
  • Up to medium temperature of 100 °C the controllers can be installed in any position.Danfoss-AVQM-Flow-Controller-Installation-fig- (21)
  • For higher temperatures the controllers have to be installed in horizontal pipes only, with a pressure and temperature actuator oriented downwards.Danfoss-AVQM-Flow-Controller-Installation-fig- (22)

Electrical actuator
Note! Installation positions for electrical actuators AMV(E) have to be observed as well. Please see relevant Data sheet.

  • Temperature sensor
    The place of installation must be chosen in a way that the temperature of the medium is directly taken without any delay. Avoid overheating of temperature sensor. The temperature sensor must be immersed into the medium in its full length.
  • Temperature sensors 170 mm R½
    The temperature sensor may be installed in any position. Danfoss-AVQM-Flow-Controller-Installation-fig- (23)
  • Temperature sensor 255 mm R¾
    The temperature sensor must be installed as shown on the picture.Danfoss-AVQM-Flow-Controller-Installation-fig- (24)

Pressure temperature diagram

Danfoss-AVQM-Flow-Controller-Installation-fig- (25)

Design

Danfoss-AVQM-Flow-Controller-Installation-fig- (26)

  1. Control valve insert
  2. Adjustable flow restrictor
  3. Valve body
  4. Valve insert
  5. Pressure relieved valve cone
  6. Valve stem
  7. Built-in spring for flow rate control
  8. Control drain
  9. Control diaphragm
  10. Union nut
  11. Impulse tube
  12. Upper casing of diaphragm
  13. Lower casing of diaphragm
  14. Thermostat AVT, STM
  15. Thermostat stem
  16. Bellows
  17. Setting spring for temperature control
  18. Handle for temperature setting, prepared for sealing
  19. Scale carrier
  20. Capillary tube
  21. Flexible protected pipe (at 255mm only)
  22. Temperature sensor
  23. Immersion pocket
  24. Sensor stuffing box
  25. Housing of sensor stuffing box
  26. Safety spring

Function

  • Flow and temperature controller with integrated control valve (AVQM-WE, AVQMT-WE)
    Flow volume causes pressure drop across the adjustable flow restrictor. Resulting pressures are being transferred through the impulse tubes and/or control drain in the actuator stem to the actuator chambers and act on control diaphragm for flow control. The flow restrictor diff. pressure is controlled and limited by means of built-in spring for flow control. Control valve closes on rising differential pressure and opens on falling differential pressure to control max flow. Additionally the electrical actuator will operate from zero to set max. flow according to the load.
  • Safety Temperature Monitor (STM): Function
    The safety temperature monitor is proportional temperature controller which controls temperature and protects the system against exceeding temperatures. The valve cone is soft sealed and pressure relieved. In case the temperature at the temperature sensor exceeds the adjusted set point, safety temperature monitor interrupts energy supply by closing the valve. As soon as the temperature at the temperature sensor drops, the valve opens automatically. Handle for limit setting can be sealed.
  • Extended safety function
    If there is a leakage in the area of the temperature sensor, the capillary tube, or the thermostat, the valve closes by a safety spring in the safety thermostat. In this case safety temperature monitor (actuator) must be replaced.
  • Physical Function Principle
    The safety temperature monitor operates in accordance with the liquid expansionprinciple. The temperature sensor, the capillary tube and the bellows are filled with liquid. As the temperature at the temperature sensor rises, the liquid expands, the thermostat stem moves out and closes the valve.
  • Temperature Controller (AVT): Function
    By increasing of medium temperature control valve cone moves towards the seat (valve closes), by decreasing of medium temperature valve cone moves away from the seat (valve opens). Handle for temperature setting can be sealed.
  • Physical Function Principle
    Medium temperature changes cause pressure changes in temperature sensor. Resulting pressure is being transferred through the capillary tube to the bellows. Bellows moves thermostat stem and opens or closes the valve.

Settings

  • Flow setting
    Flow setting is being done by the adjustment of the flow restrictor position. The adjustment can be performed on the basis of flow adjustment diagram (see relevant instructions) and/or by the means of heat meter.
  • Temperature setting (AVT)
    Temperature setting is being done by the adjustment of the setting spring for temperature control. The adjustment can be done by means of handle for temperature setting and/or temperature indicators.
  • Limit setting (STM)
    Limit setting is being done by the adjustment of the setting spring for temperature control. The adjustment can be done by means of handle for limit setting and/or temperature indicators.

Adjustment diagram

Temperature setting
Relation between scale numbers 1-5 and closing temperature.

Note: The values given are approximate

Danfoss-AVQM-Flow-Controller-Installation-fig- (27)

Note: STM Safety temperature monitor (actuator): temperature scale is already written on the product

Dimensions

Danfoss-AVQM-Flow-Controller-Installation-fig- (28) Danfoss-AVQM-Flow-Controller-Installation-fig- (29)

Adjustment diagram

Temperature setting
Relation between scale numbers 1-5 and closing temperature.

Note: The values given are approximate

Danfoss-AVQM-Flow-Controller-Installation-fig- (30)

Note: STM Safety temperature monitor (actuator): temperature scale is already written on the product

Danfoss-AVQM-Flow-Controller-Installation-fig- (31) Danfoss-AVQM-Flow-Controller-Installation-fig- (32)

Danfoss A/S

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Documents / Resources

Danfoss AVQM Flow Controller [pdf] Installation Guide
003R9131, 7369170-2, VI.56.I2.00, AVQM Flow Controller, AVQM, Flow Controller, Controller

References